05 - Specifications - Control Cable Shielded - XLPE Insulation - Copper Tape Shield - 600 V.pdf
PDF 119 KB Posted
- Solicitation number
- 89503122QWA000214
About this file
This solicitation is seeking quotes for power cables to be utilized at the Liberty Substation. The Western Area Power Administration, Desert Southwest Region, Phoenix, AZ office requires cables of various lengths and sizes adhering to the specifications in the attachments. This is a 100% small business set-aside Request for Quotation solicited as a commercial item acquisition under FAR Subparts 12 and 13, with a firm-fixed price purchase order contemplated. Quotes including shipping costs should be sent to Timothy Kramer by email at kramer@wapa.gov by the date provided. Questions may be submitted to Steve Turner at sturner@wapa.gov. The NAICS code is 335929 for other communication and energy wire manufacturing with a size standard of 1,000 employees. Quotes will be accepted from all responsible sources. Registration in the System for Award Management is required for eligibility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
6-2450…2500…2550-SH.41
TYPE TC-ER
CONTROL CABLE, SHIELDED
XLPE Insulation Copper Tape Shield PVC Jacket 600 Volts, 90°C Wet/Dry
APPLICATIONS:
As multi-conductor shielded control, tray or power cables rated 600 volts, 90°C in dry and wet locations, specifically approved for installation in cable trays per NEC Article 340. Approved for use in Class 1 remote-control and signaling circuits per Article 725-11(b) of the NEC. Type TC-ER cables (for Exposed Run applications) are permitted for use in Class I Division 2 industrial hazardous locations per NEC. Cables may be installed outdoors, in open air, in ducts or conduits, in tray or trough, and may be direct buried. All cables when used in accordance with the NEC, meet the requirements of OSHA.
CONSTRUCTION:
Stranded copper conductors, 30-mil XLPE (Cross-Linked Polyethylene) insulated, Method 1 - Table E1 or E2 color-coded, or Method 4 phase-identified; multiple conductors cabled together, fillers as required for a circular cross-section, helically applied (spiral) flat bare copper tape shield, sunlight resistant black PVC (Polyvinyl Chloride) jacket, surface printed.
STANDARDS:
1. ASTM B-3, B-8.
2. UL 44, Type XHHW-2.
3. UL 1277 Type TC-ER.
4. IEEE-383, IEEE-1202/CSA FT-4 Flame Tests.
5. Sunlight Resistant, Direct Burial.
6. ICEA S-95-658/NEMA WC70, ICEA S-73-532/NEMA WC57.
No. of BASIC O.A. O.D. WEIGHT BASIC O.A. O.D. WEIGHT BASIC O.A. O.D. WEIGHT conds. cat no. mils in. lbs/mft cat no. mils in. lbs/mft cat no. mils in. lbs/mft
14 AWG - STRANDED 12 AWG - STRANDED 10 AWG - STRANDED
2 6-2452-SH 45 .37 95 6-2502-SH 45 .41 125 6-2552-SH 45 .46 175
3 6-2453-SH 45 .39 115 6-2503-SH 45 .43 150 6-2553-SH 45 .48 230
4 6-2454-SH 45 .43 140 6-2504-SH 45 .48 195 6-2554-SH 60 .56 335
5 6-2455-SH 45 .47 185 6-2505-SH 45 .51 245 6-2555-SH 60 .62 365
6 6-2456-SH 45 .51 210 6-2506-SH 60 .60 275 6-2556-SH 60 .68 395
7 6-2457-SH 45 .51 225 6-2507-SH 60 .60 300 6-2557-SH 60 .68 430
8 6-2458-SH 60 .58 275 6-2508-SH 60 .64 345 6-2558-SH 60 .73 485
9 6-2459-SH 60 .64 290 6-2509-SH 60 .69 395 6-2559-SH 60 .79 555
11 6-2461-SH 60 .66 360 6-2511-SH 60 .74 565 6-2561-SH 80 .90 710
12 6-2462-SH 60 .70 385 6-2512-SH 60 .77 600 6-2562-SH 80 .91 760
15 6-2465-SH 60 .76 490 6-2515-SH 80 .89 660 6-2565-SH 80 1.05 925
19 6-2469-SH 60 .80 580 6-2519-SH 80 .93 765 6-2569-SH 80 1.10 1090
20 6-2470-SH 80 .88 620 6-2520-SH 80 1.04 830 6-2570-SH 80 1.18 1170
25 6-2475-SH 80 .97 745 6-2525-SH 80 1.15 1035 6-2575-SH 80 1.30 1445
27 6-2477-SH 80 1.00 790 6-2527-SH 80 1.17 1100 6-2577-SH 80 1.33 1545
30 6-2480-SH 80 1.04 865 6-2530-SH 80 1.19 1195 6-2580-SH 80 1.35 1665
32 6-2482-SH 80 1.12 920 6-2532-SH 80 1.25 1290 6-2582-SH 80 1.44 1805
37 6-2487-SH 80 1.17 1040 6-2537-SH 80 1.30 1435 6-2587-SH 80 1.48 2035
Dimensional data not binding. We reserve the right to alter specifications without notice.
SHIPPING TOLERANCE +/- 10%
Stranded Copper
Copper Tape Shield
XLPE Insulation
PVC Jacket
Robert Stamp