This document provides specifications for power cables required by the Western Area Power Administration for their Liberty Substation project. The Western Area Power Administration is soliciting quotes for various sizes and lengths of 600V power cables to adhere to the specifications detailed in the attachments. This is a 100% small business set-aside Request for Quotation with a firm-fixed price purchase order award contemplated. Quotes including shipping costs should be submitted to Timothy Kramer by email by the date specified, with any questions directed to Steve Turner, Contracting Officer. The requirement has an NAICS code of 335929 for Other Communication and Energy Wire Manufacturing with a size standard of 1,000 employees. Respondents must be registered in the System for Award Management to be eligible for award.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet2
| Voltage | Conductor | Cable | ||
| Item | Type | Number & size | Length | |
| 1 | ACSR | 795 Kcmil | 15' | |
| 2 | 600V | 1/C-500Kcmil | 5040' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 3 | 600V | 1/C-350Kcmil | 4370' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 4 | 600V | 1/C-300Kcmil | 1360' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 5 | 600V | 1/C-250Kcmil | 80' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 6 | 600V | 1/C-4/0 AWG | 120' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 7 | 600V | 1/C-3/0 AWG | 2080' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 8 | 600V | 1/C-2/0 AWG | 1560' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 9 | 600V | 1/C-1/0 AWG | 240' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 10 | 600V | 1/C-1 AWG | 240' | 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 11 | 600V | 3/C-4 AWG | 80' | Power Cable with Ground, multi conductor, 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 12 | 600V | 3/C-6 AWG | 1894' | Power Cable with Ground, multi conductor, 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 13 | 600V | 3/C-8 AWG | 404' | Power Cable with Ground, multi conductor, 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |
| 14 | 600V | 2/C-12 AWG | 40' | Power Cable with Ground, multi conductor, 600V, shielded type, NEC 90°C XHHW-2, Cross-linked polyethylene type per ANSI/NEMA WC 7-2009 / ICEA S-95-658 , Section 3 |