APPLICABLE CODES, STANDARDS, & GUIDELINES:
GSA P-100 Design Guideline International Building Code 2015 (IBC) Life Safety Code 2015 (NFPA 101) Ohio Building Code 2011 (OBC) Ohio Mechanical Code 2011 Ohio Plumbing Code 2011 National Electrical Code (NFPA 70) 2017 edition National Electrical Safety Code (2017)
NFPA 24 (2016)
The Architectural Barriers Act Accessibility Standard
(ABAAS)
NASA Facility Project Requirements NPR 8820 High and low voltage Operating Instructions (OI) Local Specsintact section 26.52.00.98 NASA NPR 1620.3A, NASA Physical Security
Requirements for NASA Facilities and Property NASA NPR 1600.1A, NASA Protective Services
Program Requirements NASA STD-8719.11 Safety Standard for Fire Protection NPD 8710.5 NASA Safety Policy for Pressure Vessels and Pressurized Systems Glenn Safety Manual Glenn Occupational Health Programs Manual NASA –STD-8719.9 Standards for Lifting Devices and
Equipment
Guiding Principles for Federal Leadership in High Performance and Sustainable Buildings
ANSI/AIHA Z10-2005
GSA National Business Space Assignment Policy
(NBSAP 2013)
ANSI/BOMA Z65.1
Life-cycle costing (LCC) - NIST Handbook 135 EPA Document No. EPA-832-R-92-005 American Nursery and Landscape Association
(ANSI Z60.1)
ASTM C.635, ASTM C.636, ASTM C754, ASTM C840
NSF/ANSI 140
Green seal standard gs-11, Paints, First edition, May
20, 1993 South Coast Air Quality Management District (SCAQMD) rule 1113, Architectural Coatings, effective January 1, 2004.
SCAQMD rule 1168 with a corresponding effective date of July 1, 2005, and rule amendment date of January 7, 2005.
green seal standard for Commercial Adhesives gs-36 requirements in effect on October 19, 2000.
GSA handbook Concession Management Desk Guide PMFC-93 ASCE standards
ANSI Z359 Consensus Standard
NPR 1620.3A
ANSI/ASA S12.2-2008
Ventilation for Acceptable Indoor Air Quality (ASHRAE standard 62.1-2010)
ASHRAE 62.1-2012
ASHRAE 90.1-2004
SMACNA 1072
ISEA Z358.1 (2009)
ASME A17.1
Safety and Health Regulations for Construction
(29 CFR Part 1926) Occupational Safety and Health Standards
(29 CFR Part 1910) 10 CFR, Energy, Parts 433-435
IEEE
Interagency Security Criteria (ISC) - Physical Security Criteria for Federal Facilities, GSA PBS Site Security Design Guide , GSA PBS Design Notebook for Federal Lobby Security GSA National Business Space Assignment Policy, GSA P120 Project Estimating Requirements, GSA Order 8000.1C GSA Metric Program, GSA 3490.1A on Document Security for Sensitive But
Unclassified Building Information Executive Order 13502, Use of Project Labor
Agreements for Federal Construction Projects
APPLICABLE CODES:
International Building Code 2015 (IBC) Life Safety Code 2015 (NFPA 101) Ohio Building Code 2011 (OBC) The code review is based on the assumption that an automatic sprinkler system shall be installed throughout the entire building.
CHAPTER 3 USE AND OCCUPANCY:
IBC, 303.3 Assembly Group A-2 occupancy includes assembly uses intended for food and/or drink consumption including, but not limited to cafeterias and similar dining facilities (including associated commercial kitchens).
IBC, 304.1 Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or service-type transactions, including storage of records and accounts.
IBC, 309.1 Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof, for the display and sale of merchandise and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to public.
CHAPTER 5 GENERAL BUILDING HEIGHTS AND
AREAS:
IBC, 508.3 nonseparated uses: Building is considered non-separated mixed use composed of A-2 assembly group - banquet hall greater than 50 persons (303.1), B; Business (304.1) and M;
Mercantile (309.1).
Per IBC, tables 504.3, 504.4, and 506.2, Allowable height, stories, and areas for Type II-B construction:
Group A-2: 75ft, 3 stories, 28,500 sf Group B: 75ft, 4 stories, 69,000 sf Group M: 75ft, 3 stories, 37,500 sf
IBC, 506.3 frontage increase (A-2 is most restrictive):
increase total per story per story
Group A-2: 7,125 sf 35,625 sf Group B: 17,250 sf 86,250 sf
CHAPTER 6 TYPES OF CONSTRUCTION:
IBC, tables 601 & 602, Type II-B construction:
Building elements Fire rating (hrs) Primary structural frame 0 Bearing walls (exterior & interior) 0 Nonbearing walls (exterior) 0 > 30ft Nonbearing walls (interior) 0 Floor construction 0 Roof construction 0
CHAPTER 10 MEANS OF EGRESS CONTINUED:
NFPA 101-Table 7.3.3.1 Egress Capacity Factors 1st Floor, Total Occupants: 379 2nd Floor, Total Occupants: 633 (2nd floor governs)
NFPA 101-12.2.3.6.2(2) Assembly occupancies:
the main entrance/exit width shall accommodate one-half of the total occupant load. exits shall be permitted to be distributed around the perimeter of the building, provided that the total exit width furnishes not less than 100 percent of the width needed to accomodate the permitted occupant load.
Exit stair, width A-2 occupants 374/2 * 0.3in = 56.1in min width Main lobby exit doors, width A-2 occupants 374/2 * 0.2in = 37.4in min width
NFPA 101-7.2.1.2.2.1 Egress capacity width for doors:
36in nominal door = 34in egress capacity width 72in nominal pair = 70in egress capacity width
Egress component minimum width Stairways 44in NFPA 101-Table 7.2.2.2.1.2(B)
IBC, 1011.2
Corridors 44in NFPA 101-38.2.6.3
IBC, Table 1020.2
Corridor fire rating 0-hr IBC, Table 1020.1
NFPA 101-12.3.6(2) and 38.3.6.1(3)
Dead ends:
Assembly 20ft NFPA 101-12.2.5.1.3
IBC, 1018.4
Business 50ft NFPA 101-38.2.5.2.1
IBC, 1018.4 exception 2
Exit access travel distance:
Assembly 250ft NFPA 101-12.2.6.2(1)
IBC, Table 1017.2 Business 300ft NFPA 101-38.2.6.3
IBC, Table 1017.2
Common path of egress travel:
Assembly 20ft NFPA 101-12.2.5.1.2
30ft IBC, 1029.8 Assembly 75ft NFPA 101-12.2.5.1.2 (<50 occ.)
Business 100ft NFPA 101-38.2.5.3.1
100ft IBC, Table 1006.2.1
IBC, 1009.4 Elevators: not provided.
Elevators do not have stand-by power thus are not part of the accessible means of egress.
IBC, 1009.8 Two-way communication: provided.
Two-way communication provided at 2nd floor landing of the public elevator.
IBC, 1010.1.4.1.2 Revolving doors: provided.
Revolving door provided as other than a component of a means of egress.
Note: Elevators, monumental stair and revolving door are not part of the required means of (accessible) egress.
Primary (accessible) means of egress is through Stair S001 (north exterior) and Stair S002 (south exterior), which are separated from the building conforming to fire barrier construction, and Stair S003 (west exterior) which exits directly to the exterior.
CHAPTER 29 PLUMBING SYSTEMS:
IBC Table 2902.1, assume 50% male, 50% female.
Use Group A-2 (476 occupants) Water Closets: 1 per 75.
Lavatories: 1 per 200.
Drinking Fountains: 1 per 500
Use Group B (393 occupants) Water Closets: 1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50.
Lavatories: 1 per 40 for the first 80 and 1 per 80 for the remainder exceeding 80.
Drinking Fountains: 1 per 100
Use Group M (34 occupants) Water Closets: 1 per 500.
Lavatories: 1 per 750.
Drinking Fountains: 1 per 1000
Combined total provided / required plumbing fixtures:
(# provided / # required)
Water Closets Lavatories Drinking F.
Male 8W + 6U / 8 10 / 5 4* / 6 Fem. 14 / 9 10 / 5 -
*Drinking fountain quantity is supplemented by common-use break room faucets on each floor and the kitchen servery on the second floor.
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION:
IBC, 706.1 Fire walls: not required.
IBC 707 Fire barrier rating: 1-hour.
NFPA 101-8.2.3.3 Fire barrier supporting construction:
1-hour rating required.
IBC, 709 Smoke barriers: not required.
IBC, 712.1.7 Atriums: not provided.
IBC, 712.1.9 Two-story openings: provided.
NFPA 101-8.6.6 Communicatings spaces: provided.
Unenclosed, non separated communicating spaces Smoke baffles and closely spaced sprinklers provided as as part of the opening protectives.
IBC, 713.4 Shaft enclosure rating: 1-hour fire barrier.
IBC, 713.6 Exterior walls: Where exterior walls serve as a part of a required shaft enclosure, such walls shall comply with requirements of section 705 and the fire rated enclosure requirements shall not apply.
IBC, 3005.4 Elevator machine room: Fire-resistance rating not required at remote machine rooms per Exception 2.
Per GSA P100 document, where the application of water from fire sprinklers installed in a main electrical room constitutes a serious life or fire hazard, the main electrical room must be separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire resistance rating of not less than 2-hours.
CHAPTER 8 INTERIOR FINISHES:
Per NASA-STD 8719.11A 6.4.1:
Interior wall/ceiling finish materials: Class A
Flame spead: <25 Smoke development: <450
Interior floor finish materials: Class I Critical radiant flux: ≥0.45 W/cm2
CHAPTER 9 FIRE PROTECTION SYSTEMS:
IBC, 903: Automatic sprinkler systems - shall be provided to comply with IBC 903.3.1.1 and NFPA 13.
NFPA 13-8.15.4: Vertical Openings shall be protected with draft stops and sprinklers spaced no more than 6 ft. apart and 6-12 in. from the draft stop.
IBC, 905: standpipe system required by government.
IBC, 906: portable fire extinguishers shall be provided in occupancies and locations required by the international fire code:
Group A, B, M: 75ft max. travel distance Cooking Equip.: 30ft max. travel distance
IBC, 907: Manual fire alarm - required under group A-2 occupancy (over 300 occupants).
IBC, 909: Smoke control systems: not required for atrium that connects two stories.
CHAPTER 10 MEANS OF EGRESS:
NFPA 101-Table 7.3.1.2 Occupant Load Factor Assembly (less concentrated use, without fixed seating) 1 per 15 net sf = 476 occupants Kitchens 1 per 100 gross sf = 25 occupants Business (typical) 1 per 100 gross sf = 393 occupants Concentrated Business (higher density B) 1 per 50 gross sf = 53 occupants Accessory Storage (other than group M) 1 per 500 gross sf = 4 occupants Mercantile (sales area on street floor) 1 per 30 net sf = 34 occupants Mercantile (storage, receiving, shipping) 1 per 300 gross sf = 2 occupants Mechanical & Equipment Rooms 1 per 300 gross sf = 25 occupants
CAS (214) and Compass (219) are used for specific purposes with limited occupants, which meets NFPA 101 "concentrated business" classification for 1 occupant per 50 gross sf. Rooms have less than 50 occupants, allowing each room to have [1] in-swinging means of egress door per IBC 1010.1.2.1 and NFPA 101-7.2.1.4.2.
A
B
2345678913141516 10
D
1217 111
TRAVEL DISTANCE
300'-0" ALLOWABLE
164'-0: ACTUAL
TRAVEL DISTANCE
300'-0" ALLOWABLE
159'-0: ACTUAL
elev.
(1 hr) elev. (1 hr) electrical (2 hr walls and ceiling)
1.815.3
C fire egress stair (1 hr) fire egress stair (1 hr)
10' - 0" min. (UL #U040) 10' - 0" min. (UL #U040)
DEAD END
50'-0" ALLOWABLE
27'-0" ACTUAL
EXCHANGE
STORE
STORAGE
TRAINING
ROOM LOBBY
MECHANICAL
ROOM
ELECTRICAL
OPEN
OFFICECOLLAB
WORK
SPACE
COLLAB
WORK
SPACE
MEP
OPEN
OFFICE
OPEN
OFFICE
FEC-2 FEC-2
FEC-1
FE-1
FEC-2
FEC-1
FEC-1
FEC-2
.05 mechanical (2 hr walls and ceiling)
STAIR 002 req'd prov'd exterior doors @ 115 occ. 23" 40"
VESTIBULE 102J req'd prov'd exterior door @ 76 occ. 15.2" 36"
STAIR 001 req'd prov'd exterior doors @ 108 occ. 21.6" 40"
LOBBY 101 req'd prov'd exterior door @ 76 occ. 15.2" 36"
STAIR S003 req'd prov'd exterior door @ 187 occ. 37.4" 40"
LOBBY 100 req'd prov'd exterior door @ 76 occ. 15.2" 36" revolving door is not a means of egress
TCO
TRAINING
ROOM
tco (1 hr walls and ceiling) sv (1 hr walls and ceiling)
SV
A
B
2345678913141516 10
BA
BB
BC
BD
BE
BF
BG
BIBI
D
1217 111
OPEN TO
BELOW
OPEN TO
BELOW
ROOF
BELOW
TRAVEL DISTANCE
300'-0" ALLOWABLE
157'-0: ACTUAL
TRAVEL DISTANCE
250'-0" ALLOWABLE
56'-0: ACTUAL
FEC-2
TRAVEL DISTANCE
300'-0" ALLOWABLE
230'-0: ACTUAL
1.815.3
C elev.
(1 hr)elev.
(1 hr) fire egress stair (1 hr) fire egress stair (1 hr)
10' - 0" min. (UL #U040)
DEAD END
50'-0" ALLOWABLE
50'-0" ACTUAL
COMMON PATH OF TRAVEL
FROM BALCONY (<50 OCC.)
75'-0" ALLOWABLE
42'-0" ACTUAL
exterior balcony
DINING
GALLERY
OPEN
OFFICE
OPEN
OFFICE
OPEN
OFFICE
COMPASS CAS
KITCHEN
MEP
unenclosed 2-story opening protected with smoke baffles and closely spaced sprinklers below;
stair S004 is not part of the required means of egress from the 2nd floor partially enclosed 2-story opening
10' - 0" min. (UL #U040)
FE-2
FE-2
FEC-1
FEC-3
FEC-2 FEC-2
FEC-1
FEC-1
FEC-1
.05
<50 occupants at each open office area, so doors not required to swing in the direction of egress travel per IBC 1010.1.2.1 and NFPA 101-7.2.1.4.2
STAIR 002 req'd prov'd stair @ 230 occ. 69" 69" door @ 115 occ. 23" 40" door @ 115 occ. 23" 34"
STAIR 003 req'd prov'd stair @ 187 occ. 56.1" 58" door @ 187 occ. 37.4" 40"
STAIR 001 req'd prov'd stair @ 196 occ. 58.8" 69" door @ 196 occ. 39.2" 42" door @ 20 occ. 4" 34"
TRAVEL DISTANCE
300'-0" ALLOWABLE
232'-0: ACTUAL
<50 occupants Compass and CAS, so doors not required to swing in the direction of egress travel per IBC 1010.1.2.1 and NFPA 101-7.2.1.4.2 and only [1] means of egress door required
3' - 0" egress path
BUSINESS 100 gross
Business, concentrated 50 gross
ASSEMBLY
Less concentrated 15 net without fixed seating (tables & chairs)
MERCANTILE
Sales area on 30 net street floor
Mercantile, storage 300 gross
NOTES:
• NFPA 101 Life Safety Code 2015 supercedes IBC 2015 for means of egress.
• Numbers represent sq ft per person for calculating occupant load.
• Load factors per table 7.3.1.2 NFPA 101
KITCHEN 100 gross
MECH. AND EQUIP. 300 grossACCESSORY STORAGE 500 gross
Egress path
One hour fire rated construction
Two hour fire rated construction
Fire extinguisher Egress door AED
FEC-1 = Fully Recessed Cabinet, FE Type 1 FEC-2 = Semi-Recessed Cabinet, FE Type 1 FEC-3 = Surface Mount Cabinet, FE Type 1
FE-2 = Surface Mount FE Type 2 (Kitchen/Cooking Areas)
NOTES:
• Coordinate final location of fire extinguishers and cabinets with Contracting Officer and the authority having jurisdiction prior to framing walls. See specifications for more information.
• Travel distance line graphically represents path of travel. Actual calculated travel distance varies from graphically represented line.
• Required egress with:
Stairways @ 0.3in per occupant Other exits @ 0.2in per occupant
• AED material is GFE, cabinet installation and FAS monitoring interface is infrastructure in base scope
0164-COF1009-A-705
AARON
G.
HILL
814786
OETATS
R
OIHOF
E G
ISTE RED RCHIT
EC
T
A Expiration Date 12/31/2019
BUILDING 164
RESEARCH SUPPORT BUILDING
CE 0164 COF16009
ENGLISH REVIT 2016
BIDDING DOCUMENTS
BIDDING - 1
RELEASE APPROVAL:
D.ENG:
CONFIG:
APPROVED
DRAWN
RELEASE STATUS:
RELEASE APPROVAL:
PROJ. MGR:
RELEASE APPROVAL:
PROJECT ID
SYSTEM:
DR:
FACILITY:
DES:
OFFICIAL DATE:
SOFTWARE:
SCALE:
AREA:
UNITS:
SIZE BLDG/SYS
SHEET
DISCP
REVISION
OF
CAD DRAWING - DO NOT REVISE MANUALLY
NATIONAL AERONAUTICS AND SPACE ADMINISTRATION
JOHN H. GLENN RESEARCH CENTER
LEWIS FIELD & PLUM BROOK STATION, OHIO
REVISIONS
APPROVAL DATE
DESIGNED CHECKED
DESCRIPTIONCHG NUM APP/DATE
SEQTYP
P R O P E R T Y
O F
U N
IT
E D
S T A T E S
G O V E R N M E N T
F O R
O F F
IC
IA
L
U S E
O N L Y
D o n o t R e m o v e
T h is
N o ti c e P ro p e rl y d e s tr o y d o c u m e n t w h e n n o lo n g e r n e e d e d
VER
DATE:
DATE:
DATE:
DRAWING/DESIGN STATUS:
SUB-SYS:
DRAWING MANAGEMENT
NASA APPROVALS
TEMPLATE DATE: 02/28/2011
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
4 3
C
D
4 3 2
E
F
G
H
04/04/2018As indicated
G-101
LIFE SAFETY PLANS
JS, PL, TC AH
04.04.2018
AS
PRELIMINARY BUILDING CODE SUMMARY
SCALE:
N
37° 51' 21"
GRID NORTH
NASA
3/64" = 1'-0"G-101
1 LEVEL 1 LIFE SAFETY PLAN
SCALE:
N
37° 51' 21"
GRID NORTH
NASA
3/64" = 1'-0"G-101
2 LEVEL 2 LIFE SAFETY PLAN
Total Ground Floor Area: 29,540 gross square feet
OCCUPANT LOAD CALCULATION:
BUSINESS: 20,545 sf / 100 gross = 206 concentrated 831 sf / 50 gross = 17 ASSEMBLY 1,520 sf / 15 gross = 102 MERCANTILE: 1012 sf / 30 net = 34 storage 318 sf / 300 gross = 2 MECH./EQUIP: 4,790 sf / 300 gross = 16 ACC. STOR: 524 sf / 500 gross = 2
379 OCCUPANTS
Total Second Floor Area: 32,353 gross square feet
OCCUPANT LOAD CALCULATION:
BUSINESS: 18,679 sf / 100 gross = 187 concentrated 1,762 sf / 50 gross = 36 ASSEMBLY: 5,607 sf / 15 net = 374 3'-0" egress path 530 sf = n/a KITCHEN: 2,450 sf / 100 gross = 25 MECH./EQUIP: 2,685 sf / 300 gross = 9 ACC. STOR: 640 sf / 500 gross = 2
633 OCCUPANTS
OCCUPANT TYPE LEGEND &
LOAD FACTORS
GENERAL NOTES:
• Fire ratings shown are minimum requirement. Wall assemblies may have higher fire rating than shown;
maintain minimum ratings.
• Fireproofing required at rated egress stair locations, refer to sheet
• Glazing is not required to be blast-resistant
FIRE SAFETY &
EGRESS LEGEND
A36
A35
A11
A11
A AMENDMENT 03 05/14/2018
ABBREVIATIONS
(T) TOP REINFORCEMENT
AB ANCHOR BOLT
ADDL ADDITIONAL
AESS ARCHITECTURALLY EXPOSED STRUCUTRAL STEEL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
APPROX APPROXIMATE
ARCH ARCHITECT OR ARCHITECTURAL
BF BRACED FRAME
BLDG BUILDING
BM BEAM
BO BOTTOM OF
BOC BOTTOM OF CONCRETE
BOD BOTTOM OF DECK
BOS BOTTOM OF STEEL
BP BASE PLATE
BS BOTH SIDES
BTWN BETWEEN
BU BUILT-UP MEMBER
C TO C CENTER TO CENTER
CANT CANTILEVER
CFS COLD-FORMED STEEL
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION WELD
CL CENER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CVR COVER
DBL DOUBLE
DIA DIAMETER
DIM DIMENSIONS
DN DOWN
DWG DRAWING
DWL DOWEL
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
EOR ENGINEER OF RECORD
EQ EQUAL
EW EACH WAY
FD FLOOR DRAIN
FDN FOUNDATION
FF FAR FACE
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FTG FOOTING
GA GAGE OR GUAGE
GB GRADE BEAM
GL GRID LINES
GLB GLUED LAMINATED BEAM
HORIZ HORIZONTAL
HP HIGH POINT
ID INSIDE DIAMETER
IF INSIDE FACE
IJ ISOLATION JOINT
INT INTERMEDIATE
JT JOINT
LDT TENSION DEVELOPMENT LENGTH
LDC COMPRESSION DEVELOPMENT LENGTH
LDH HOOKED TENSION DEVELOPMENT LENGTH
LLBB LONG LEGS BACK TO BACK
LLH LONG LEGS HORIZONTAL
LLV LONG LEGS VERTICAL
LP LOW POINT
LST TENSION LAP SPLICE (CLASS B)
LSC COMPRESSION LAP SPLICE
LSL LONG SLOTTED HOLE
LVL FLOOR LEVEL
LWC LIGHTWEIGHT CONCRETE
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MISC MISCELLANEOUS
NA NOT APPLICABLE
NF NEAR FACE
NIC NOT IN CONTRACT
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
PC PILE CAP
PERP PERPENDICULAR
PG PLATE GIRDER
PJP PARTIAL JOINT PENETRATION WELD
PL PLATE
PT POST TENSIONED
RC REINFORCED CONCRETE
RD ROOF DRAIN
REINF REINFORCE, REINFORCED, REINFORCEMENT, OR REINFORCING
REQ'D REQUIRED
SC SLIP CRITICAL
SIM SIMILAR
SCH SCHEDULE
SOG SLAB ON GRADE
SPECS SPECIFICATIONS
SQ SQUARE
SSL SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STRUCT STRUCTURAL
SYM SYMMETRIC/SYMMETRICAL
T&B TOP AND BOTTOM
TBC TO BE CONFIRMED
TBD TO BE DETERMINED
TG TRANSER GIRDER
THK THICK, THICKNESS
THRU THROUGH
TOC TOP OF CONCRETE
TOF TOP OF FOUNDATION
TOS TOP OF STEEL
TOSL TOP OF STRUCTURAL SLAB
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
WP WORK POINT
WRT WITH RESPECT TO
WWR WELDED WIRE REIFNFORCEMENT
INDICATES ELEVATION AT TOP OF STRUCTURAL CONCRETE
LEGEND - SYMBOLS & NOTATIONS
XX' - XX"
INDICATES CHANGE IN SLAB SLOPE
INDICATES SLAB STEP, CHANGE IN SLAB ELEVATION
INDICATES SOIL
INDICATES GRAVEL
INDICATES BRACE BELOW
INDICATES CMU WALL, SEE PLAN FOR THICKNESSES
PLAN LEGEND
INDICATES THERMAL BREAK
INDICATES EXTRUDED POLYSTYRENE
INDICATES MOMENT CONNECTION
INDICATES AXIAL CONNECTION
INDICATES STEEL BEAM PENETRATION
INDICATES FACADE ABOVE/BELOW
INDICATES POST OR COLUMN ABOVE
INDICATES POST OR COLUMN BELOW
INDICATES COLUMN TENSION SPLICE
INDICATES THERMAL BREAK COLUMN SPLICE
INDICATES FALL PROTECTION ANCHOR ABOVE
INDICATES TYPICAL COLUMN SPLICE
INDICATES FULL DEPTH FITTED STIFFENER CONNECTION
GENERAL NOTES:
1. THE PROJECT SHALL CONFORM TO PBS-P100 2016, THE FACILITIES STANDARDS FOR THE PUBLIC
BUILDINGS SERVICE (BASED ON IBC 2015).
2. ALL STRUCTURAL WORK SHALL CONFORM TO THE PROJECT SPECIFICATIONS, ALL DRAWINGS
AND APPLICABLE REFERENCE STANDARDS. THE SCOPE OF WORK IS NOT SOLELY DEFINED BY
THESE DRAWINGS.
3. THE FOLLOWING DOCUMENTS ARE TO BE READ IN CONJUNCTION WITH THE PROJECT
SPECIFICATIONS AND THE DESIGN DRAWINGS, AS LISTED, BELOW:
A. GEOTECHNICAL REPORTS PREPARED BY DAVID V LEWIN CORP/GEOTECHNICAL
ENGINEERING DATED 22 OCTOBER 2015 AND 16 NOVEMBER 2017, INCLUDED IN SPECIFICATION
APPENDIX C.
4. TYPICAL DETAILS APPLY THROUGHOUT THE STRUCTURE, EVEN IF NOT SPECIFICALLY
REFERENCED IN PLANS OR DETAILS. DETAILS OF CONSTRUCTION NOT FULLY SHOWN OR
NOTED ON THE DRAWINGS NOR CALLED OUT IN THE SPECIFICATIONS SHALL BE OF THE SAME
SIZE AND CHARACTER AS FOR SIMILAR CONDITIONS WHICH ARE SHOWN AND NOTED.
5. ALL FORCES INDICATED IN THE STRUCTURAL DRAWINGS ARE ULTIMATE FACTORED (LRFD) LOADS AS
DEFINED BY ASCE 7, UNLESS NOTED OTHERWISE.
6. DO NOT USE SCALED DIMENSIONS; USE ONLY WRITTEN DIMENSIONS. WHERE NO DIMENSION IS
PROVIDED, CONSULT THE ARCHITECT FOR CLARIFICATIONS BEFORE PROCEEDING WITH WORK.
7. SEE ARCHITECTURAL DRAWINGS FOR SITE POSITIONING AND PROJECT DATUM REFERENCE,
FLOOR ELEVATIONS AND GRID DIMENSIONS.
8. STRUCTURAL ELEMENTS SHALL BE CENTERED ON GRIDLINES OR DIMENSION LINES, UNLESS
OTHERWISE NOTED.
9. THE CONTRACTOR IS RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE UNTIL THE
CONSTRUCTION OF THE STRUCTURE REACHES ITS FINAL CONDITION.
10. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, INSTALLATION, AND REMOVAL
OF TEMPORARY BRACING AND CONSTRUCTION SUPPORTS, FOR NEW AND EXISTING
STRUCTURES, AS NECESSARY TO COMPLETE THE PROJECT. NO PORTION OF THE PROJECT
WHILE UNDER CONSTRUCTION IS INTENDED TO BE STABLE IN THE ABSENCE OF THE
CONTRACTOR’S TEMPORARY SUPPORTS AND BRACES. CONTRACTOR SHALL RETAIN A
STRUCTURAL ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED TO
DESIGN TEMPORARY BRACING AND CONSTRUCTION SUPPORTS.
11. THE CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL STRUCTURAL WORK WITH
ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND OTHER TRADES REQUIREMENTS.
REFER TO ARCHITECTURAL DRAWINGS FOR THE DIMENSIONS NOT SHOWN ON PLAN.
DISCREPANCIES AND/OR INTERFERENCES SHALL BE REPORTED TO THE ARCHITECT
IMMEDIATELY.
12. OPENINGS SHALL NOT BE MADE IN ANY STRUCTURAL MEMBER UNLESS SPECIFICALLY SHOWN
ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE STRUCTURAL ENGINEER.
13. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ANY REQUIRED DEWATERING OF
THE SITE DURING CONSTRUCTION.
14. THE CONTRACTOR SHALL PREPARE AN ENGINEERED DESIGN AND SHALL BE RESPONSIBLE
FOR CONFIRMING ADEQUACY OF AS BUILT STRUCTURE FOR ALL SURCHARGE LOADS
RESULTING FROM COMPACTION AS WELL AS CRANES,TRUCKS, BULLDOZERS OR ANY OTHER
CONSTRUCTION EQUIPMENT.
15. CONTRACTOR'S ENGINEERED DESIGNS SHALL BE PREPARED, SIGNED AND SEALED BY A
LICENSED PROFESSIONAL ENGINEER IN THE STATE IN WHICH THE PROJECT IS LOCATED
AND SUBMITTED TO ENGINEER OF RECORD FOR REVIEW.
16. CONNECTIONS OF SYSTEMS DESIGNED BY CONTRACTOR’S ENGINEER SUCH AS, BUT NOT
LIMITED TO, CLADDING, STAIRS, ELEVATORS, ESCALATORS, AND MEP LOADS ARE ASSUMED
TO IMPOSE VERTICAL AND/OR HORIZONTAL LOADS ON THE BASE BUILDING STRUCTURAL
MEMBERS WITHOUT GENERATING TORSION IN THE SUPPORTING STRUCTURAL MEMBERS.
CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING ALL SUPPLEMENTARY
BRACING MEMBERS AS REQUIRED TO PREVENT TORSION ON THE BASE BUILDING STRUCTURE.
17. IN CASE OF CONFLICT BETWEEN DRAWINGS, DETAILS, NOTES OR SPECIFICATIONS, THE
MOST RIGID REQUIREMENTS SHALL GOVERN. CONTRACTOR SHALL MAKE NO DEVIATION
FROM THE CONTRACT DOCUMENTS WITHOUT PRIOR WRITTEN APPROVAL FROM THE
STRUCTURAL ENGINEER AND ARCHITECT.
INSPECTIONS:
SPECIAL INSPECTIONS IN ACCORDANCE WITH IBC 2015 SHALL BE PERFORMED BY
APPROVED TESTING AGENCIES. SEE RELAVANT SECTIONS OF THE SPECIFICATIONS FOR
SCOPE AND FREQUENCY OR AS MINIMUM PER REFERENCED STANDARDS.
REINFORCED CONCRETE:
1.ALL CONCRETE SHALL HAVE THE FOLLOWING ULTIMATE COMPRESSIVE STRENGTH AT
28 DAYS MADE WITH NORMAL WEIGHT (STONE) AGGREGATE (ASTM C33) UNLESS OTHERWISE
NOTED. REFER TO SPECIFICATIONS FOR MIX REQUIREMENTS.
A.STRUCTURAL SLAB AT GRADE f'c = 4,000 PSI B. GRADE BEAMS AND FOOTINGS f'c = 5,000 PSI C. RETAINING/FOUNDATION WALLS f'c = 5,000 PSI D. SLABS ON METAL DECK f'c = 3,500 PSI (LWC)
2.ALL CONCRETE NOT IN CONTACT WITH EARTH TO HAVE FINISH AS SPECIFIED BY ARCHITECT
OR AS COVERED IN PROJECT SPECIFICATIONS. UNLESS OTHERWISE NOTED, NON
ARCHITECTURAL CONCRETE COLUMNS AND WALLS SHALL HAVE ¾” CHAMFERED CORNERS.
3.ALL CAST-IN-PLACE CONCRETE WILL EXPERIENCE DIFFERING VARIATIONS OF CRACKING.
ANY ELEMENT EXPOSED TO DIRECT WEATHER AND/OR TEMPERATURE VARIATIONS DURING
CONSTRUCTION OR IN THE FINAL CONDITION IS TO BE TREATED AND REGULARLY MAINTAINED
TO PREVENT PROPAGATION OF CRACKS AND WATER PENETRATION. THE CONTRACTOR
SHALL DEVELOP A REGULAR MAINTENANCE PROGRAM AND SUBMIT IT TO THE OWNER.
4. ALL SLABS SHALL BE FLAT (FF) AND LEVEL (FL) PER THE CONCRETE SPECIFICATIONS. THE CONCRETE CONTRACTOR SHALL INCLUDE IN THEIR BID ANY EXCESS CONCRETE REQUIRED TO POUR SLABS FLAT AND LEVEL PER THESE REQUIREMENTS. THE CONCRETE PLACING PROCEDURE SHALL BE CONTROLLED TO
MINIMIZE SUPPORT MEMBER DEFLECTION.
5. ALL ADJOINING SURFACES NOT CAST MONOLITHICALLY SHALL BE ROUGHENED TO 1/4 INCH
AMPLITUDE FOR THE ENTIRE INTERSECTING SURFACE ACCORDING TO ACI
RECOMMENDATIONS AND APPLY A BONDING AGENT.
6.ALL CONCRETE SHALL BE REINFORCED. PROVIDE MINIMUM TEMPERATURE REINFORCEMENT
AS REQUIRED BY ACI-318 IN ELEMENTS WHERE NO REINFORCEMENT IS INDICATED ON THE
DRAWINGS AND REPORT TO STRUCTURAL ENGINEER IMMEDIATELY TO CONFIRM NO ADDITIONAL
REINFORCING IS REQUIRED
7.REINFORCING SHALL HAVE THE FOLLOWING MINIMUM CONCRETE COVER U.O.N.:
A. CAST AGAINST EARTH - 3"
B. EXPOSED TO EARTH OR WEATHER - 2"
C. SLABS & WALLS NOT EXPOSED - 3/4" OR BAR DIAMETER
D. BEAMS, GIRDERS, AND COLUMNS (TO TIES) - 1 1/2"
8.REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 GRADE 60,
MIN fy=60 KSI. EXCEPT USE ASTM A706 FOR ALL WELDED BARS AND DUCTILE SEISMIC
ELEMENTS AS NOTED IN THE CONTRACT DOCUMENTS.
9.WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A185 (FOR PLAIN WIRE) AND
ASTM A497 (FOR DEFORMED WIRE). Fy = 65,000PSI.
10. EPOXY COATED REINFORCEMENT SHALL BE USED IN ALL CONCRETE EXPOSED TO WEATHER,
AND WHERE NOTED IN THE CONTRACT DOCUMENTS.
11. PROVIDE DOWELS OR CONTINUOUS REINFORCING BETWEEN ALL CONCRETE ELEMENTS.
FOR FOUNDATIONS PROVIDE DOWELS OF SAME NUMBER AND SIZE AS THE VERTICAL
REINFORCEMENT OF STRUCTURE ABOVE UNLESS NOTED OTHERWISE. FOR OTHER
STRUCTURAL ELEMENTS VERTICAL DOWELS SHALL MATCH THE GREATER REINFORCING OF
EACH ELEMENT.
12. BAR SPLICES MAY BE DELETED AND CONTINUOUS REINFORCING USED AT CONTRACTORS
OPTION. BAR SPLICES SHALL BE MADE AT POINTS OF MINIMUM STRESS. IN FRAMED BEAMS
AND SLABS SPLICE TOP BARS AT MID-SPAN, BOTTOM BARS OVER SUPPORTS.
13. STEEL REINFORCEMENT SHOP DRAWINGS SHALL BE PREPARED BY THE CONTRACTOR IN
ACCORDANCE WITH ACI-315: "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT",
AND SHALL INDICATE:
A.MATERIAL AND GRADE;
B. BAR SCHEDULES WITH BAR LENGTHS AND BENT BAR DIAGRAMS;
C. ARRANGEMENT, SPACING, COVER, LAP LOCATIONS AND LENGTHS;
D. SPLICE DETAILS FOR MECHANICAL SPLICES;
E. SUPPORTS FOR CONCRETE REINFORCEMENT;
F. SPECIAL REINFORCEMENT AT OPENINGS.
14. WHERE A 90-DEG, 135 –DEG OR 180-DEG HOOK IS GRAPHICALLY INDICATED, PROVIDE
CORRESPONDING HOOKS PER ACI STANDARD U.O.N.
15. DOWELS SHALL MATCH SIZE AND SPACING OF MAIN REINFORCEMENT UNO.
16. WHERE BARS OF DIFFERENT SIZES LAP, PROVIDE LAP SPLICE LENGTH FOR LARGER BAR UNO.
17. REINFORCEMENT SHALL HAVE CONCRETE PROTECTION (CLEAR COVER) PER ACI 318
UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
18. UNLESS OTHERWISE NOTED ALL LAP SPLICES ARE TO BE TENSION LAP SPLICES PER
LAP SPLICE AND EMBEDMENT SCHEDULE.
19. CONTRACTOR SHALL FIELD VERIFY DIMENSIONS AND LOCATIONS OF ALL OPENINGS, PIPE
SLEEVES, FLOOR DEPRESSIONS, CURBS ETC., AS REQUIRED BY OTHER TRADES BEFORE
CONCRETE IS PLACED.
20. SHEAR KEY, WHERE SHOWN, SHALL BE MINIMUM 2"X2", U.O.N.
21. AT EXPOSED SLAB LOCATIONS, BOTH ON GRADE AND ON STEEL DECK, THE FOLLOWING ADDITIONAL
CRITERIA APPLY:
A.SHRINKAGE AT 28 DAYS: CONTRACTOR TO INCLUDE SHRINKAGE TEST
RESULTS IN MIX DESIGN SUBMITTAL
B. SHRINKAGE REDUCING ADMIXTURE: EUCLID CONEX, 16.5 LBS/CU YD MIN.
C. MACRO SYNTHETIC FIBERS: EUCLID TUF-STRAND SF, 4 LBS/CU YD MIN.
22. LIGHTWEIGHT CONCRETE (LWC) SHALL HAVE A CALCULATED EQUILIBRIUM UNIT WEIGHT OF 110 LB/CU FT PLUS OR MINUS 3 LB/CU FUT AS DETERMINED BY ASTM C567. LIGHTWEIGHT AGGREGATE SHALL CONFORM
TO ASTM C330.
23. CONTRACTOR SHALL COORDINATE LOCATION OF ALL OPENINGS, SLAB DEPRESSIONS, PIPE SLEEVES, CURBS, INSERTS ETC. WITH ARCHITECTURAL AND MEP DRAWINGS AND SHOP DRAWINGS. NO OPENING OR SLEEVE SHALL BE INSTALLED IF NOT SHOWN ON A SHOP DRAWING APPROVED BY THE STRUCTURAL
ENGINEER.
CONCRETE JOINTS:
1.CONSTRUCTION JOINTS SHALL BE INSTALLED SUCH THAT STRENGTH AND APPEARANCE
OF CONCRETE ARE NOT IMPAIRED, AT LOCATIONS INDICATED OR AS APPROVED BY THE
ARCHITECT AND STRUCTURAL ENGINEER. SEE PROJECT SPECIFICATIONS FOR LIMITS ON
LOCATION AND SPACING.
A.LOCATE HORIZONTAL JOINTS IN WALLS AT THE UNDERSIDE OF
FLOORS, SLABS, BEAMS, AND GIRDERS AND AT THE TOP OF CAISSONS OR FLOOR
SLABS, OR AT 40-FEET MAXIMUM HEIGHT, UNLESS PERMITTED BY ENGINEER.
B. LOCATE VERTICAL JOINTS IN WALLS AT DISCONTINUITIES, BESIDES PIERS
INTEGRAL WITH WALLS, NEAR REENTRANT CORNERS, AND IN CONCEALED
LOCATIONS WHERE POSSIBLE. PREFERRED JOINT INTERVALS SHALL BE 15-25
FEET AS APPROPRIATE, WITH A MAXIMUM SPACING OF 40-FEET. AVOID LOCATING
VERTICAL JOINTS WITHIN 15-FEET OF A BUILDING CORNER.
C. LAYOUT OF CONSTRUCTION JOINTS IN SLABS ON GRADE MAY CORRESPOND WITH
CONTRACTION JOINTS.
D. LEAVE 7 DAYS, MINIMUM, BETWEEN ADJACENT POURS IN WALLS, UNLESS
APPROVED BY ENGINEER.
2.WALL CONTRACTION JOINTS SHALL BE PROVIDED TO CONTROL THE CRACKING PATTERNS
AT LOCATIONS INDICATED, OR AS APPROVED BY THE ARCHITECT.
A.LOCATE JOINTS AT COLUMN LINES WHERE APPLICABLE, WITH SPACING NOT TO
EXCEED TWICE THE WALL HEIGHT OR 20-FEET AND PREFERABLY MATCHES
LAYOUT OF SLAB JOINTING
B. FORM 1/2" DEEP CONTRACTION JOINTS BY ATTACHING 1/2"- WIDE BEVELED WOOD
STRIPS TO INSIDE OF CONCRETE FORM OF BOTH WALL FACES.
STRUCTURAL STEEL:
1. FABRICATION, CONNECTION DESIGN AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM
TO THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "MANUAL OF STEEL CONSTRUCTION,
LOAD AND RESISTANCE FACTOR DESIGN" LATEST EDITION.
2. UNLESS OTHERWISE NOTED, ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING:
A. WIDE FLANGE SECTIONS: ASTM A992 GRADE 50 (FY = 50 KSI)
B. WT SECTIONS: ASTM A992 GRADE 50 (FY = 50 KSI)
C. ANGLES AND CHANNELS: ASTM A36 (FY = 36 KSI)
D. RODS: ASTM F-1554 (FY = 55 KSI)
E. ALL IN ROOF FRAMING ANGLES AND CHANNELS: A992 GRADE 50 (FY = 50 KSI)
F. PLATES, BARS AND MEMBERS BUILT-UP FROM PLATES: ASTM A572 (FY = 50 KSI)
G. ROUND HSS: ASTM A500 GRADE B (FY= 42 KSI)
H. RECTANGULAR HSS: ASTM A500 GRADE B (FY=46 KSI)
3. STEEL USING COMPLETE JOINT PENETRATION GROOVE WELDS SHALL HAVE A MINIMUM
CHARPY V-NOTCH IMPACT TESTING VALUE AS FOLLOWS:
A. ASTM A6/A6M HOT ROLLED SHAPES WITH A FLANGE THICKNESS EXCEEDING
[2] INCHES AND BUILT-UP HEAVY SHAPES WITH PLATES EXCEEDING [2] INCHES
IN THICKNESS: 20 FT-LB @ 70 DEG. F
B. REGARDLESS OF THICKNESS, ALL TRUSSES, LATERAL SYSTEM MEMBERS
(INCLUDING COLUMNS, WIND GIRDERS, BRACES, ETC.): 20 FT-LB @ 70 DEG. F
C. STEEL EXPOSED TO TEMPERATURES IN SERVICE BELOW 50 DEG. F: 25 FT-LB
@ 40 DEG. F
D. WELD METAL: 20 FT-LB @ MINUS 20 DEG. F AND 40 FT-LB @ 70 DEG. F
E. WELD METAL EXPOSED TO TEMPERATURES IN SERVICE BELOW 50 DEG. F:
25 FT-LB @ MINUS 40 DEG. F
F. TESTING IS TO BE IN ACCORDANCE WITH ASTM A6/A6M, SUPPLEMENTARY
REQUIREMENT S30, CHARPY V-NOTCH IMPACT TEST FOR STRUCTURAL SHAPES-
ALTERNATE CORE LOCATION, AT ROLLED SHAPES AND ASTM A673 FOR PLATES,
AT ANY PERMITTED LOCATIONS.
4. TOP OF STEEL ELEVATION SHALL BE AT BOTTOM OF DECK UNLESS NOTED OTHERWISE.
5. MEMBER SPLICES SHALL ALSO HAVE FULL MEMBER CAPACITY UNLESS OTHERWISE NOTED.
6. THE CONTRACTOR SHALL SUBMIT A STEEL ERECTION PROCEDURE, PREPARED UNDER
THE SUPERVISION OF A STRUCTURAL ENGINEER LICENSED IN THE STATE OF OHIO (THE
CONTRACTOR'S ENGINEER) FOR REVIEW BY THE STRUCTURAL ENGINEER OF RECORD.
THIS PROCEDURE MUST INCLUDE THE PROPOSED SURVEY REQUIRED BY THE STEEL SPECIFICATIONS.
7. BOLTED CONNECTIONS:
A. ALL BOLTS SHALL CONFORM TO ASTM A325 OR A490, NUTS SHALL CONFORM TO
ASTM A563 AND WASHERS SHALL CONFORM TO ASTM F436
B. MINIMUM BOLT SIZE FOR THIS PROJECT ARE TO BE 3/4" DIA A325 AND 1" DIA
A490 BOLTS. MINIMUM BOLTED CONNECTIONS SHALL BE MADE WITH TWO A325N
BOLTS, 3/4" DIAMETER.
C. FOR A GIVEN BOLT DIAMETER, ONLY ONE GRADE SHALL BE USED. ONE SIZE MUST
BE SKIPPED BETWEEN DIAMTERS.
D. ANCHOR RODS SHALL CONFORM TO ASTM F-1554 GRADE 55 WITH WELDABILITY
SUPPLEMENT S1, UNO. SUBMIT GRADE CERTIFICATIONS FOR RECORD. STEEL
SUPPLIER SHALL PROVIDE RIGID STEEL TEMPLATES FOR ANCHOR ROD
INSTALLATION.
E. SLIP-CRITICAL CONNECTIONS: SLIP-CRITICAL BOLTS SHALL BE FULLY TENSIONED
WITH FAYING SURFACE PREPARATION CLASS A, UNLESS NOTED OTHERWISE. SLIP-
CRITICAL CONNECTIONS SHALL BE USED IN THE FOLLOWING LOCATIONS:
1. WHEREVER REQUIRED IN THE AISC PROVISIONS.
2. WHEREVER NOTED ON THE DRAWINGS.
3. WHENEVER OVERSIZED HOLES ARE USED.
4. AT ALL CANTILEVER AND MOMENT CONNECTIONS.
5. AT ALL TRUSS CONNECTIONS AND TRUSS SUPPORTING CONNECTIONS.
6. BRACES AT ROOF.
7. PLAN BRACES.
8. AXIALLY LOADED BEAMS AND PURLINS.
F. TENSION CONTROL ASSEMBLIES SHALL CONFORM TO ASTM F1852 FOR A325
TENSION CONTROL ASSEMBLIES AND ASTM F2280 FOR A490 TENSION CONTROL
ASSEMBLIES.
G. PRE-TENSIONED BOLTED CONNECTIONS: PRE-TENSIONED BOLTED CONNECTIONS
SHALL BE FULLY TENSIONED AND USED IN THE FOLLOWING LOCATIONS:
1. WHEREVER REQUIRED IN THE AISC PROVISIONS
2. WHEREVER NOTED ON THE DRAWINGS
3. AT ALL CONNECTIONS FOR MEMBERS DIRECTLY OR INDIRECTLY
SUPPORTING COLUMNS, POSTS, STRUTS, BRACES, MECHANICAL
EQUIPMENT AND STAIRS.
4. FOR ALL BOLTS WITH TENSION LOADS (END PLATE CONNECTIONS,
HANGERS, BRACES OR BEAMS)
H. SNUG-TIGHT BOLTED CONNECTIONS: SNUG-TIGHT BOLTED CONNECTIONS MAY BE
USED WHERE PERMITTED BY AISC PROVISIONS, AND AT LOCATIONS NOT NOTED
ABOVE WITH PRIOR APPROVAL FROM STRUCTURAL ENGINEER.
8. WELDED STUDS (HEADED OR THREADED) SHALL BE ASTM A108, MINIMUM DIAMETER SHALL BE
3/4" UNLESS NOTED OTHERWISE.
9. WELDED CONNECTIONS:
A. WELDING ELECTRODES SHALL BE CLASS E70XX.
B. MINIMUM FILLET WELD SIZE SHALL BE 3/16”.
C. WELDING SHALL BE PERFORMED BY QUALIFIED WELDERS, REFER TO
SPECIFICATIONS.
D. ALL WELDING SHALL CONFORM TO THE REQUIREMENTS OF THE STRUCTURAL
WELDING CODE, ANSI/AWS D1.1, LATEST EDITION. ALL WELD SIZES SHALL BE THE
LARGER OF THE SIZE REQUIRED BY CONNECTION FORCES, THE MINIMUM SIZE PER
ANSI/AWS D1.1, OR 3/16" MINIMUM FILLET WELD UNO. ANY WELD SIZES SHOWN ON
THE DESIGN DRAWINGS ARE CONSIDERED EFFECTIVE WELD SIZES AND SHALL BE
INCREASED IN ACCORDANCE WITH AWS AS REQUIRED BY GAPS OR SKEWS
BETWEEN COMPONENTS.
E. WELDING EXPOSED TO LOW (OUTDOOR) TEMPERATURES IN SERVICE SHALL
CONFORM TO AWS D1.5.
F. USE RUNOFF TABS AT ALL BEVEL AND FULL PENETRATION WELDS. REMOVE
RUNOFF TABS AND GRIND SMOOTH AFTER WELD IS COMPLETED.
G. REMOVE WELD BACK UP BARS AND GRIND SMOOTH AFTER WELD IS COMPLETED,
UNO.
STEEL FLOOR DECK:
1. STEEL FLOOR DECK AND ACCESORIES SHALL BE GALVANIZED DECK CONFORMING
TO ASTM A653 WITH MINIMUM YIELD STRESS, FY=50 KSI. ALL FLOOR DECK SHALL
BE COMPOSITE STEEL DECK.
2. PROVIDE MINIMUM STEEL REINFORCEMENT FOR CONCRETE SLABS ON STEEL DECK,
UNO ON DRAWINGS.
3. DECK DESIGN IS BY THE DECK SUPPLIER. DECK SHALL BE BE UNSHORED DURING
CONCRETING AND TWO SPAN MINIMUM. WHERE POSSIBLE ARRANGE DECK PANELS
SUCH THAT THREE SPAN CONTINUOUS SUPPORT CONDITIONS EXIST.
4. PROVIDE 2.5" MINIMUM END BEARING AND 1" MINIMUM SIDE BEARING
5. DECK SHALL BE FASTENED TO STRUCTURAL STEEL AT ENDS OF UNITS AND AT ALL
INTERMEDIATE SUPPORTS BY:
- 3/4" DIAMETER PUDDLE WELDS AT 12" O/C. MAX., A 3/4" DIA. SHEAR STUD WELDED
THROUGH THE DECK MAY SUBSTITUTE FOR A PUDDLE WELD.
- SIDE LAPS OF ADJACENT UNITS WITH SIDE SEAM WELDING 1 1/2" X 1/2" WELDS AT A
MAXIMUM SPACING OF 24" O.C AND AT WELD AT EACH SUPPORT
6. MINIMUM STUD REQUIREMENTS FOR STEEL FRAMING WITH DECK AND FILL ABOVE:
- 3/4" DIA. HEADED STUDS AT 12” O.C. MAXIMUM, REFER TO DRAWINGS AND DETAILS
FOR CLOSER SPACING REQUIREMENTS.
- ALL STUDS SHALL BE PLACED AT A UNIFORM SPACING OVER THE LENGTH OF THE
BEAM.
- HEADED SHEAR STUDS SHALL EXTEND A MINIMUM OF 1 ½ INCHES ABOVE THE TOP
OF STEEL DECK WITH A MINIMUM CLEAR COVER OF ½ INCH FROM THE TOP OF
SLAB.
- CENTER OF STUD SHALL NOT BE LESS THAN 1-1/4" FROM EDGE OF BEAM FLANGE.
- PROVIDE A SINGLE LINE OF STUDS AS SPACE ALLOWS. NO MORE THAN TWO STUDS
MAY BE PLACED ACROSS WIDTH OF A FLANGE.
7. CONTRACTOR TO PROVIDE ALL NECESSARY DECK ACCESSORIES SUCH AS, POUR
STOPS, CELL CLOSURE PIECES, STRAPS, ETC., TO CONTAIN CONCRETE.
8. DECKING CONTRACTOR SHALL COORDINATE DECK OPENING SIZES AND LOCATIONS FROM
ARCHITECTURAL AND MEP CONTRACT DOCUMENTS, PROVIDE HEADER MEMBERS OR
REINFORCEMENT AS REQUIRED AND SUBMIT PROPSED OPENINGS THROUGH DECK FOR
REVIEW BY ARCHITECT AND STRUCTURAL ENGINEER.
9. BEAMS SUPPORTING STEEL DECK HAVE BEEN DESIGNED FOR A MAXIMUM OF 1" ADDITIONAL
CONCRETE OVER-POUR BEYOND DESIGN THICKNESS. CONTRACTOR SHALL LIMIT OVER-POUR
AS MUCH AS POSSIBLE, WITH A MAXIMUM ADDITIONAL CONCRETE THICKNESS OF 1". ADDITIONAL
CONCRETE OVER-POUR MATERIALS SHALL BE AT CONTRACTOR'S EXPENSE.
STEEL ROOF DECK:
1. STEEL ROOF DECK SHALL CONFORM TO ASTM-A446, MINIMUM YIELD STRENGTH OF
40 KSI, AND HOT-DIP GALVANIZED PER ASTM A525 G60.
2. DESIGN AND DETAIL ROOF DECK AND ITS ANCHORAGE TO SUPPORTING MEMBERS TO
SUPPORT DESIGN LOADS, INDICATED DIAPHRAGM SHEAR, AND INDICATED ROOF UPLIFT.
3. STEEL ROOF DECK UNITS SHALL BE FASTENED TO THE STEEL FRAME TO SUPPORT THE
FOLLOWING UNFACTORED LOADS AND MEET THE MINIMUM REUIREMENTS:
A. GRAVITY LOAD 10 PSF MINIMUM EXCLUDING DECK SELF WEIGHT,
SEE LOAD DIAGRAMS ON S0 SERIES. CONSIDER ADDITIONAL 10 PSF
FOR FUTURE CHECKER PLATE ON ROOF.
B. DIAPHRAGM SHEAR FORCE (LRFD): WIND: 1080 LB/FT, SEISMIC: 850 LB/FT
C. NET UPLIFT FORCE 30 PSF MINIMUM
4. ROOF DECK AND ITS ANCHORAGE TO SUPPORTING MEMBERS SHALL MEET THE FOLLOWING
MINIMUM FASTENING REQUIREMENTS AT ENDS OF UNITS AND AT ALL INTERMEDIATE
SUPPORTS:
- 5/8" DIA. PUDDLE WELDS SPACED AT 12" O.C. MAX.
- SIDE LAPS OF ADJACENT UNITS: SHALL BE FASTENED BY SIDE SEAM WELDING OR
SIDELAP SCREWS SPACED PER MANUFACTURERS ENGINEERED CALCULATIONS
WITH A MAXIMUM SPACING OF 24 INCHES ON CENTER. ARC SEAM WELDS SHALL BE
A MINIMUM OF1-1/2 INCH BY 1/2 INCH.
5. LOADS MAY NOT BE HUNG DIRECTLY FROM STEEL ROOF DECK WITHOUT THE PRIOR APPROVAL
OF THE DECK SUPPLIER AND STRUCTURAL ENGINEER.
6. DECKING CONTRACTOR SHALL COORDINATE DECK OPENING SIZES AND LOCATIONS FROM
ARCHITECTURAL AND MEP CONTRACT DOCUMENTS, PROVIDE HEADER MEMBERS OR
REINFORCEMENT AS REQUIRED AND SUBMIT PROPSED OPENINGS THROUGH DECK FOR
REVIEW BY ARCHITECT AND STRUCTURAL ENGINEER.
7. DECK DESIGN IS BY THE DECK SUPPLIER. DECK DESIGN SHALL HAVE A TWO SPAN MINIMUM.
WHERE POSSIBLE ARRANGE DECK PANELS SUCH THAT THREE SPAN CONTINUOUS SUPPORT
CONDITIONS EXIST.
FOUNDATIONS:
1. FOUNDATION DESIGN CRITERIA ARE BASED ON THE GEOTECHNICAL ENGINEER RECOMMENDATIONS
PREPARED BY DAVID V LEWIN CORP/GEOTECHNICAL ENGINEERING DATED 22 OCTOBER 2015.
2. ALL FOUNDATIONS SHALL REST ON SUBGRADE CONDITIONS SUITABLE FOR THE IDENTIFIED
ALLOWABLE BEARING CAPACITY (4,500PSF). ADEQUACY OF BEARING STRATUM SHALL BE VERIFIED
IN THE FIELD BY THE GEOTECHNICAL ENGINEER OR SPECIAL INSPECTOR PRIOR TO INSTALLING
FOUNDATIONS. ADJUST BOTTOM OF FOUNDATION ELEVATIONS AS REQUIRED TO ACHIEVE
THE REQUIRED BEARING CAPACITY. DRILLED PIERS, CAISSONS, SHOULD BEAR AT LEAST ONE CAISSON DIAMETER INTO THE HARD TILL BEARING STRATA. TEMPORARY CASING WILL BE REQUIRED IN ORDER TO
MAINTAIN AN OPEN EXCAVATION AND TO CONTROL GROUNDWATER.
3. SOIL PREPARATION OF THE SITE SHALL FOLLOW THE RECOMMENDATIONS DESCRIBED IN
THE GEOTECHNICAL REPORT. THIS INCLUDES REMOVAL OF EXISTING STRUCTURES &
UTILITIES, REMOVAL OF EXISTING FILL WHERE DEEMED NECESSARY, PREPARATION OF
THE SUBGRADE & COMPACTION, EXCAVATIONS FOR NEW FOUNDATIONS & SLABS, AND
BACKFILLING TO RETAINING WALLS.
4. WHERE SOIL CONDITIONS ARE FOUND DURING CONSTRUCTION THAT DO NOT MEET CRITERIA
DESCRIBED IN THE REPORT, SPECIAL INSPECTOR/CONTRACTOR SHALL NOTIFY ENGINEER
IMMEDIATELY.
5. LOCATION OF ALL UNDERGROUND UTILITIES SHALL BE VERIFIED PRIOR TO CONSTRUCTION
OF FOUNDATION TO AVOID ANY INTERFERENCE. CONTRACTOR SHALL EXPOSE EXISTING
UTILITY LINES IN THE IMMEDIATE AREA TO DETERMINE THEIR EXACT INVERT ELEVATION,
SIZE AND LOCATION RELATIVE TO THE FOUNDATION. NOTIFY THE ENGINEER IMMEDIATELY
OF ANY INTERFERENCE WITH FOOTINGS OR THE FOUNDATION WALL.
6. DO NOT PLACE BACKFILL AGAINST BASEMENT / PROPPED RETAINING WALLS UNTIL ALL FLOOR
SLABS AND OTHER STRUCTURES BRACING THESE WALLS ARE IN PLACE AND ALL WALLS AND
BRACING STRUCTURES HAVE ACHIEVED DESIGN STRENGTH.
7. DO NOT UNDERMINE CONSTRUCTED FOUNDATIONS WITHIN THE AREA OF INFLUENCE WITHOUT
SHORING OR UNDERPINNING. THE INFLUENCE LINE SHALL EXTEND FROM THE BOTTOM OF
FOUNDATIONS, ELEVATOR PIT SLABS, AND SUMP PITS ETC AT THE SLOPE STATED IN THE
GEOTECHNICAL REPORT.
8. WATER SHALL NOT BE ALLOWED TO STAND IN TRENCHES OR FORMS BEFORE OR AFTER
CONCRETE IS PLACED, AND SHALL BE PUMPED OUT. IF BOTTOMS OF TRENCHES BECOME
SOFTENED DUE TO RAIN OR OTHER WATER BEFORE FOUNDATIONS ARE CAST, THE
CONTRACTOR SHALL, AT THEIR OWN EXPENSE, EXCAVATE THE SOFTENED MATERIAL AND
REPLACE WITH CONCRETE.
9. ALL EXTERIOR FOOTINGS AND GRADE BEAMS SHALL BE PLACED A MINIMUM OF 3'-6" BELOW FINAL GRADE.
BUILDING 164
RESEARCH SUPPORT BUILDING
CE 0164 COF16009
ENGLISH REVIT 2016
BIDDING DOCUMENTS
BIDDING - 1
RELEASE APPROVAL:
D.ENG:
CONFIG:
APPROVED
DRAWN
RELEASE STATUS:
RELEASE APPROVAL:
PROJ. MGR:
RELEASE APPROVAL:
PROJECT ID
SYSTEM:
DR:
FACILITY:
DES:
OFFICIAL DATE:
SOFTWARE:
SCALE:
AREA:
UNITS:
SIZE BLDG/SYS
SHEET
DISCP
REVISION
OF
CAD DRAWING - DO NOT REVISE MANUALLY
NATIONAL AERONAUTICS AND SPACE ADMINISTRATION
JOHN H. GLENN RESEARCH CENTER
LEWIS FIELD & PLUM BROOK STATION, OHIO
REVISIONS
APPROVAL DATE
DESIGNED CHECKED
DESCRIPTIONCHG NUM APP/DATE
SEQTYP
P R O P E R T Y
O F
U N
IT
E D
S T A T E S
G O V E R N M E N T
F O R
O F F
IC
IA
L
U S E
O N L Y
D o n o t R e m o v e
T h is
N o ti c e P ro p e rl y d e s tr o y d o c u m e n t w h e n n o lo n g e r n e e d e d
VER
DATE:
DATE:
DATE:
DRAWING/DESIGN STATUS:
SUB-SYS:
DRAWING MANAGEMENT
NASA APPROVALS
TEMPLATE DATE: 02/28/2011
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
4 3
C
D
4 3 2
E
F
G
H
04/04/2018As indicated
S-001
GENERAL NOTES 1
Author CheckerDesigner
DESIGN LOADS AND CRITERIA
1.LIVE LOADS
A. CORRIDORS 100 PSF
B. OFFICE 100 PSF
C. LOBBIES 100 PSF
D. PUBLIC ASSEMBLY 100 PSF
E. STAIRS 100 PSF
F. BALCONIES 100 PSF
G. KITCHEN 150 PSF
H. STORAGE 125 PSF
I. MEP 150 PSF
2.SNOW LOADS
A. GROUND SNOW LOAD, PG = 20 PSF
B. FLAT ROOF SNOW LOAD, PF = 20 PSF
C. SNOW EXPOSURE FACTOR, CE = 1.0
D. SNOW IMPORTANCE FACTOR, I = 1.0
E. THERMAL FACTOR, CT = 1.0
F. DRIFT LOADS: CALCULATED PER ASCE-7 10
3.WIND LOADS
ASCE-7 2010
A. BASIC WIND SPEED, V = 115 MPH
B. RISK CATEGORY II
C. EXPOSURE C
D. EXTERNAL PRESSURE COEFF = 0.8 WINDWARD
E. INTERNAL PRESSURE COEFF VARIES
F. MEAN ROOF HEIGHT VARIES
4.SEISMIC LOAD
ASCE-7 2010
A. SEISMIC IMPORTANCE FACTOR, Ie = 1.0
SEISMIC USE GROUP I
B. SS = 0.155g S1 = 0.056g
C. SITE CLASS E (BASED ON GEOTECH REPORT DATED 10/22/2015)
D. SDS = 0.258g
SD1 = 0.131g
E. SEISMIC DESIGN CATEGORY B
F. STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE (OCBF)
G. V = 385 KIPS
H. Cs = 0.086 I. R = 3
J. EQUIVALENT LATERAL FORCE PROCEDURE
SERVICEABILITY:
1.DEFLECTION AND DRIFT
A. VERTICAL DEFLECTION
FOR EXTERIOR SPANDREL BEAMS SUPPORTING FACADE/CLADDING:
LIVE LOAD VERTICAL DEFLECTION AT MID SPAN LIMITED TO THE LESSER OF L/500 OR 3/4"
TOTAL LOAD VERTICAL DEFLECTION AT MID SPAN LIMITED TO L/360
FOR ROOF MEMBERS IN NON-ACCESSIBLE LOCATIONS NOT SUPPORTING MEP OR PV EQUIPMENT:
LIVE LOAD VERTICAL DEFLECTION AT MID SPAN LIMITED TO L/240
TOTAL VERTICAL DEFLECTION AT MID SPAN LIMITED TO L/180
FOR ALL OTHER MEMBERS:
LIVE LOAD DEFLECTION LIMITED TO L/360
TOTAL LOAD VERTICAL DEFLECTION AT MID SPAN LIMITED TO L/240
L=LENGTH OF MEMBER SPANNING COLUMN CENTERLINE TO COLUMN CENTERLINE (FT)
B. HORIZONTAL DEFLECTION
HORIZONTAL DRIFT DUE TO WIND LOAD LIMITED TO H/400
FOR SEISMIC INTERSTORY DRIFT REQUIREMENT, REFER TO SEISMIC LOADING CRITERIA
H=TOTAL BUILDING HEIGHT (FT)
RADIANT FLOOR IN SLAB:
1. PLACE PIPES MINIMUM 1" ABOVE STEEL DECK FLUTES AND 1" MINIMUM BELOW TOP OF SLAB
2. AVOID LONGITUDINAL PIPES RUNNING WITHIN 8" EACH SIDE OF STEEL BEAMS
3. CROSS BEAMS WITH TRANSVERSE PIPES AT OUTER THIRDS OF SPAN
4. ONLY SINGLE LAYER OF PIPING PERMITTED EXCEPT THAT PIPING MAY CROSS TRANSVERSELY AT
SELECT LOCATIONS APPROVED BY STRUCTURAL ENGINEER
5. NO RADIANT PIPING IS PERMITTED IN CONCRETE ON STEEL DECK SLABS UNLESS THE
LAYOUT IS APPROVED BY THE EOR AND THE CRITERIA NOTED IS FOLLOWED.
6. RADIANT PIPING IS NOT PERMITTED IN THE CLEAR COVER ZONE BETWEEN THE REINFORCING AND THE
FACE OF THE ELEMENT.
7. RADIANT PIPING SHALL IN NO WAY INTERFERE WITH REINFORCING STEEL. PULL BOXES AND SIMILAR
PENETRATIONS SHALL BE REINFORCED PER TYPICAL OPENINGS DETAILS.
8. CONTRACTOR TO SUBMIT COORDINATED PLANS INDICATING EXACT LAYOUT AND ROUTING OF ALL
PIPING IN CONCRETE SLABS FOLLOWING THE RULES ABOVE FOR STRUCTURAL ENGINEER
REVIEW. PLANS TO INCLUDE ALL DEVICES/PENETRATIONS. RADIANT PIPING OR OTHER CONDUIT NOT
SHOWN ON REVIEWED PLANS IS NOT PERMITTED. CONTRACTOR MUST SUBMIT PLANS
REGARDLESS OF WHETHER CONDUIT OR PIPING IS SHOWN IN SLAB ELSEWHERE ON CONTRACT
DOCUMENTS.
9. FINAL LOCATION OF RADIANT PIPING SHALL BE REVIEWED BY THE INDEPENDENT INSPECTION AGENCY PRIOR TO PLACING OF THE CONCRETE SLAB TO CONRIM COMPLIANCE WITH THE APPROVED LAYOUT
DEFERRED SUBMITTALS:
1. THE FOLLOWING ITEMS ARE TO BE DESIGNED AND SUBMITTED SUBSEQUENT TO THE TIME OF PERMIT
APPLICATION AS DEFERRED SUBMITTALS PER SECTION 107.3.4.1 OF IBC:
STRUCTURAL STEEL CONNECTIONS
STEEL COMPOSITE DECK ATTACHMENTS AND CONNECTIONS
STEEL ROOF DECK ATTACHMENTS AND CONNECTIONS
PRECAST CONCRETE "THIN WALL" AND ATTACHMENTS
CONCRETE CAISSON FOUNDATIONS
2. THE CONTRACTOR SHALL PROVIDE COORDINATED DESIGNS OF DEFERRED SUBMITTAL ITEMS AS PART OF THE BASE BUILDING STRUCTURE. THESE DESIGNS SHALL BE PERFORMED BY A PROFESSIONAL ENGINEER
LICENSED IN THE STATE OF OHIO.
STRUCTURAL STEEL (CONT'D):
10. DESIGN OF STEEL CONNECTIONS:
A. STEEL CONNECTIONS ARE NOT FULLY DETAILED IN THE STRUCTURAL
DRAWINGS. THE CONTRACTOR'S DESIGN ENGINEER LICENSED IN THE STATE OF
OHIOMUST DESIGN ALL CONNECTIONS.
B. THE CONTRACTOR’S DESIGN ENGINEER SHALL SUPERVISE THE PREPARATION
OF CALCULATIONS AND SHOP DRAWINGS FOR THESE CONNECTIONS, AND TO
CHECK THE SHOP DRAWINGS FOR COMPLIANCE WITH CONTRACT DOCUMENTS,
GOVERNING CODES, AND PREVAILING STANDARDS OF PRACTICE. THE SHOP
DRAWINGS AND CALCULATIONS NOT STAMPED AND SIGNED AS REQUIRED FOR
CONTRACTOR ENGINEERED DESIGNS WILL BE RETURNED UNREVIEWED FOR
RESUBMISSION.
C. STEEL CONNECTIONS SHALL BE DESIGNED, DETAILED AND CONSTRUCTED PER
THE REQUIREMENTS OF AISC “MANUAL OF STEEL CONSTRUCTION” INCLUDING
AISC SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490
BOLTS AND "AISC SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS”.
D. DESIGN OF STEEL CONNECTIONS FOR SHEAR SHALL INCLUDE THE EFFECTS OF
ECCENTRICITY.
E. CONTRACTOR SHALL PROVIDE STIFFENERS AND REINFORCING PLATES WHERE
NEEDED TO RESIST THE LOCAL EFFECTS OF DESIGN LOADS.
F. DESIGN, DETAIL, FURNISH AND INSTALL STIFFENERS, CONTINUITY PLATES,
DOUBLER PLATES, OR OTHER NECESSARY ADDITIONAL LOCAL STRENGTHENING
MEASURES AS REQUIRED. MEMBER SIZES INDICATED ON THE DRAWINGS ARE
BASED ON MEMBER CAPACITY AT MIDSPAN OF BEAM.
G. MOMENT CONNECTIONS ARE REQUIRED TO DEVELOP THE FULL MOMENT AND
SHEAR CAPACITY OF THE MEMBER UNLESS OTHERWISE NOTED.
H. ALTERNATE CONNECTIONS TO THOSE CONNECTIONS CONCEPTS SHOWN ON
DRAWINGS WILL ONLY BE CONSIDERED ACCEPTABLE IF CONTRACTOR
FORMALLY SUBMITS ALTERNATES FOR THE STRUCTURAL ENGINEER'S REVIEW.
I. THE NOTE OF "FULL DEPTH STIFFENER" ON THE STRUCTURAL DRAWINGS
IMPLIES A STIFFENER THAT EXTENDS TO AND IS CONNECTED TO BOTH TOP &
BOTTOM FLANGES OF A W SECTION.
J. FOR CONNECTION DESIGN AND DETAILING, SET CONNECTION WORK POINT AT
INTERSECTION OF MEMBER CENTERLINES, UNO.
K. DESIGN ALL CONNECTIONS FOR FORCES INDICATED ON THE DRAWINGS.
CONNECTION DESIGN FORCES INDICATED ON THE DRAWINGS ARE FACTORED (LRFD)
UNO.
L. FOR TRUSS DETAILING USE A MINIMUM BOLT SPACING OF 3 TIMES THE BOLT
DIAMETER AND A MINIMUM EDGE DISTANCE OF 2 INCHES. ALSO REFER TO
TYPICAL DETAILS.
M. MINIMUM ASTM A325 OR A490 BOLT DIAMETER IS 3/4".
11. SHOP DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL.
NO FABRICATION OF STEEL SHALL COMMENCE WITHOUT APPROVED SHOP DRAWINGS.
12. WHERE REQUIRED AT STEEL CONNECTIONS, ALL GROUT SHALL BE NON-SHRINK WITH A
MINIMUM COMPRESSIVE STRENGTH OF 8000 PSI.
13. STEEL FINISHES SHALL BE AS FOLLOWS, UNO IN ARCHITECTURAL DRAWINGS:
A. INTERIOR TO RECEIVE ENCASEMENT OR SPRAY-ON FIREPROOFING: REFER TO
SPECIFICATIONS
B. INTERIOR TO RECEIVE FINISH PAINT: REFER TO SPECIFICATIONS
C. EXTERIOR: HOT-DIPPED GALVANIZED COATING CONFORMING TO ASTM A123 OR
HIGH-PERFORMANCE COATING AT CONDITIONS AS IDENTIFIED IN SPECIFICATIONS.
14. FIELD CUTTING OR DRILLING STRUCTURAL STEEL IS STRICTLY PROHIBITED WITHOUT PRIOR
REVIEW AND APPROVAL BY DESIGN ENGINEER. ALL HOLES AND CUTS SHALL BE
PERFORMED IN THE SHOP AS IDENTIFIED ON STRUCTURAL DRAWINGS OR SHOP DRAWINGS.
15. ALL STEELS EXPOSED TO WEATHER ARE TO BE PAINTED WITH RUST INHIBITIVE PAINT,
MINIMUM TWO PRIME COAT AND ONE FINISH COAT.
16. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS FOR ARCHITECTURALLY EXPOSED STRUCTURAL STEEL (AESS).
17. REFER TO ARCHITECTURAL DOCUMENTS FOR FULL FIRE PROTECTION SPECIFICATIONS
AND DETAILS.
18. THE STRUCTURE IS NOT SELF SUPPORTING DURING ERECTION FOR GRAVITY AND
LATERAL LOADS. THE CONTRACTOR IS RESPONSIBLE FOR STABILITY DURING
CONSTRUCTION.
19. PRIOR TO THE START OF ERECTION THE CONTRACTOR SHALL SUBMIT CALCULATIONS
AND ERECTION DRAWINGS SIGNED AND SEALED BY AN ENGINEER LICENSED IN THE
STATE OF OHIO FOR THE PROPOSED ERECTION PROCEDURE, SHORING, BRACING
AND SUPPORT FOR CONSTRUCTION EQUIPMENT TO BE REVIEWED BY THE STRUCTURAL
ENGINEER.
20. ALL HSS MEMBERS ARE TO CAPPED WITH 1/4" PLATE AT ENDS.
21. ALL NATURAL BEAM CAMBER TO BE FABRICATED SO THAT CAMBER IS UPWARDS
SHEET LIST
Sheet Name Sheet Number
GENERAL NOTES 1 S-001
LOAD MAPS S-010
LEVEL 01 FOUNDATION PLAN PART A S-101
LEVEL 01 FOUNDATION PLAN PART B S-102
LEVEL 02 FRAMING PLAN PART A S-103
LEVEL 02 FRAMING PLAN PART B S-104
ROOF FRAMING PLAN PART A S-105
ROOF FRAMING PLAN PART B S-106
BRACE ELEVATIONS 1 S-201
BRACE ELEVATIONS 2 S-202
TRUSS ELEVATIONS S-203
TYPICAL CONCRETE DETAILS S-501
FOUNDATION DETAILS 1 S-510
FOUNDATION DETAILS 2 S-511
FOUNDATION DETAILS 3 S-512
SLAB ON GRADE DETAILS S-515
COLUMN DETAILS S-520
STEEL DETAILS 1 S-530
STEEL DETAILS 2 S-531
STEEL DETAILS 3 S-532
STEEL DETAILS 4 S-533
TRUSS DETAILS S-540
TYP…