This document comprises approved construction plans for the Utah State Hospital Forensics Building Heating/Cooling End of Hall Units project (DFCM Project No. 27139420) prepared by Resolut Group, a mechanical and electrical engineering firm located in Murray, Utah. The project involves the installation of new AC split systems throughout the Forensics Building at 1300 East Center Street in Provo, Utah. The construction documents include mechanical and electrical plans with detailed specifications for eight Mitsubishi split system units (AC-1 through AC-8), each consisting of one rooftop outdoor unit and two indoor fan coil units. The mechanical plans specify refrigerant piping connections, condensate drainage systems, ductwork modifications, ceiling diffusers, and rooftop equipment mounting requirements. The electrical plans detail power distribution, scheduling, and specifications for the new systems. The construction cost estimate for this project is $200,000.00. All work must comply with 2024 International Building Code standards and applicable Utah codes. Documentation includes mechanical symbols and abbreviations, overall and enlarged plans, details, schedules, and equipment specifications for the split system components. DFCM approval was obtained on August 24, 2026, with project engineer Jacob D. Beck as the drawing responsible party.

The project requires prequalified contractors only, as this is a Stage II Invitation to Bid restricted to contractors currently on the DFCM Prequalified Contractors list. Mechanical engineer Lewis Wong and electrical engineer Lewis Wong of Resolut Group are identified as the design consultants. Key construction requirements include cutting ceiling access holes, installing security-grade ceiling diffusers with tamper-proof specifications, extending refrigerant and condensate piping from indoor units to rooftop outdoor units, and modifying existing ductwork to accommodate new equipment. All outdoor refrigerant piping must be jacketed with aluminum embossed covering, and condensate piping must use Type M copper tubing with flexible elastomeric insulation. The rooftop equipment platform must be constructed from galvanized steel channels and HSS posts with bolt connections, and no welding is permitted on the roof membrane. Before occupancy, a code inspection report, final report from the special inspection agency, and certificate of fire clearance from the State Fire Marshal must be obtained.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

07/31/2026

260252

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

B U

IL

D

IN

G

H

EA

TI

N

G /C

O O

LI

N

G E

N D

O F

H A

LL

U

N

IT

S

E

AS

T

C

EN

TE

R

S

TR

EE

T

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

C001

COVER SHEET

DFCM Project No. 27139420

CONSTRUCTION DOCUMENTS

Vicinity Map

C001 COVER SHEET

MECHANICAL

M001 MECHANICAL SYMBOLS AND ABBREVIATIONS

M101 MECHANICAL OVERALL PLAN

M401 MECHANICAL ENLARGED PLAN

M402 MECHANICAL ENLARGED PLAN

M501 MECHANICAL DETAILS AND SCHEDULES

ELECTRICAL

EG001 INDEX SYMBOLS & NOTES

EG600 ELECTRICAL SPECIFICATIONS

EG601 ELECTRICAL SCHEDULES

EP101 ELECTRICAL POWER PLAN

EP401 ELECTRICAL ENLARGED PLAN

EP402 ELECTRICAL ENLARGED PLAN

SHEET INDEX

UTAH STATE HOSPITAL

1300 EAST CENTER STREET PROVO, UTAH 84603

PROJECT SITE

PROVO, UTAH

NORTH

MECHANICAL ENGINEER: RESOLUT GROUP

181 EAST 5600 SOUTH

MURRAY, UT 84107

(801) 530-3148 (JACOB BECK)

ELECTRICAL ENGINEER: RESOLUT GROUP

181 EAST 5600 SOUTH

MURRAY, UT 84107

(801) 530-3148 (LEWIS WONG)

CONSULTANTS

FORENSICS BUILDING

HEATING/COOLING END OF HALL UNITS

North: ______ South: ______ East: ______ West: ______

Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________

d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a

3) Three Story: A (3)______

2) Two Story: A (2)________

1) One Story: ______

c) Total Allowable Area for:

N/A (NON-SEPARATED OCCUPANCIES)

b) Sum of the Ratio Calculations for Mixed Occupancies:

a) 0.25I = 100f F P 30

WstA I 100100 fIA t taA = A + +

Official for Complex Buildings. Including, but not limited to:

g) Fire Stopping, Including Tested Design Number.

f) Exterior and Interior Accessibility Route.

e) Fire Assembly Locator Sheet.

a) High Rise Requirements.

b) Atriums.

c) Performance Based Criteria.

d) Means or Egress Analysis.

2) Additional Code Information shall be provided at the discretion of the Building

Code Accessibility Chapters, the more restrictive requirement shall govern.

through - ADA Guidelines and specific reference to the International Building

1) In case of conflict with the U.S. Department of Justice Federal Registers Parts

FOOTNOTES:

d) Drinking Fountains: ______ Service Sinks: ______

c) Bath Tubs or Showers: ______

b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______

a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____

M. Minimum Number of Required Plumbing Facilities:

Exit Width Required: ______ Exit Width Provided: ______

Element Hours Assembly ListingListing

Element AssemblyHours

Smoke Partitions Fire Partitions

Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls Structural Frame Partitions - Permanent Fire Barriers

Floors - Ceiling Floors Roofs - Ceiling Roofs Exterior Doors and Windows Shaft Enclosures Fire Walls

BAHTBABABA

Design Wind Speed: ______ mphB. Seismic Design Category: ______

L. Design Occupant Load: ______

K. Fire Resistance Rating Requirements for Building Elements (hours).

Area Modifications:J:

_____________________________________________________Tabular Area:I:

per Floor (square feet): _________________________________________Actual AreaH:

Number of Stories: ______ Building Height: ___________G:

Required: ______ Provided: _________ Type of Sprinkler System: __________

Sprinklers:F:

Mixed Occupancies: ______ Nonseparated Uses: ______E.

separation distance (in hours):

Requirements for the Exterior Walls based on the fireFire Resistance RatingD.

C. Type of Construction (circle one):

Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______

Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code

Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code

YearYear

APPLICABLE CODES

A. Occupancy and Group: _______ ________ ________ ________ ________

CODE ANALYSIS

N

N N

I-3

X X

NO

N/AN/A

NR NR NR NR

NO

YES YES NFPA 13

1 30' - 8"

70,908

N/A

3) Deferred Submittals:

a) Seismic Bracing for Mechanical and Electrical. Work related to the deferred

N/A

N/AX

UL

submittals shall not commence until the building official has approved the submittal.

N/A

160 FT

N/A

B A-3

1. THE FOLLOWING DOCUMENTS ARE REQUIRED

BEFORE A CERTIFICATE OF OCCUPANCY IS

ISSUED:

· A CODE INSPECTION REPORT RECOMMENDING

THAT A CERTIFICATE OF OCCUPANCY BE ISSUED.

· FINAL REPORT FROM THE SPECIAL INSPECTION

AGENCY.

· CERTIFICATE OF FIRE CLEARANCE FROM THE

STATE FIRE MARSHALL.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/24/2026

REVIEWED FOR CODE

COMPLIANCE

PS

N

LB/HR.GPM

3-1" SLOTS

@ 48" 400

W R

12/12

45°D

FD

FSD

SD

OR

8/8

1.25D

AD

LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS

12/8 FO

ATC

CF

LATERAL STRAINER WITH BLOW-OFF VALVE, PROVIDE

HOSE END WITH CAP WHERE DISCHARGE IS NOT PIPED

TO DRAIN

F&T

AW

AV

HP(NAME)

N20

(NAME)

R

SINGLE DUCT AIR TERMINAL BOX VARIABLE OR

CONSTANT VOLUME. MIN. 1-1/2 TERMINAL INLET SIZE

STRAIGHT DUCT AT TERMINAL INLET.

HEATING OR COOLING COIL IN DUCT

ACCESS PANEL IN DUCT OR PLENUM

ATC DAMPER

SMOKE DAMPER W/ ACCESS PANEL

COMBINATION FIRE/SMOKE DAMPER W/ ACCESS PANEL

FIRE DAMPER IN DUCT, W/ ACCESS PANEL REQD.

MANUAL VOLUME DAMPER

HIGH EFFICIENCY FITTING

TAP ENTRY AREA EQUALS 150% OF BRANCH AREA

BRANCH DUCT SPLIT WITH 6" WIDTH AND MIN.

R=WIDTH OF BRANCH DUCT DOWNSTREAM. ELBOW

TURNING VANE OPTIONAL.

RECTANGULAR TO ROUND DUCT TRANSFORMATION

RECTANGULAR TO RECTANGULAR OR ROUND TO ROUND

DUCT TRANSFORMATION MAXIMUM 15° INCLUDED ANGLE

EXCEPT WHERE SHOWN OTHERWISE.

R/W=1. ROUND DUCT SIMILAR TO RECTANGULAR

INCLINED DROP

INCLINED RISE WITH RESPECT TO AIR FLOW 15°

NOMINAL INCLINE WITH RADIUS

TURNS=DEPTH OF DUCT.

ROUND DUCT WITH FREE AREA DIMENSIONS

SHOWN IN INCHES.

RECTANGULAR DUCT WITH FREE AREA

DIMENSIONS SHOWN IN INCHES.

FLAT OVAL DUCT WITH FREE AREA

DIMENSIONS SHOWN IN INCHES.

FAN

FLEXIBLE DUCT

FLEXIBLE DUCT CONNECTION

LINEAR DIFFUSER WITH PLENUM AND FLEXIBLE DUCT

CONNECTION. NO. OF SLOTS & SIZE OF SLOT ON TOP, ACTIVE

LENGTH AND CFM ON BOTTOM

CEILING AIR GRILLE WITH

FLEXIBLE DUCT

CEILING SUPPLY DIFFUSER

WITH FLEXIBLE DUCT

SIDEWALL EXHAUST OR

RETURN REGISTER

SIDEWALL SUPPLY REGISTER

CEILING EXHAUST REGISTER,

(BALANCE TO MATCH SUPPLY IF

RETURN CFM IS NOT SHOWN)

CEILING RETURN REGISTER

CEILING SUPPLY DIFFUSER

RELIEF AIR OR EXHAUST AIR LOUVER

FRESH AIR LOUVER

TURNING VANES

UNDER FLOOR DUCT

ROUND DUCT - DROP

ROUND DUCT - RISE

NEGATIVE PRESSURE DUCT - DROP

TOP FIGURES INDICATE

NECK SIZE. BOTTOM

FIGURE INDICATES CFM.

12/8

12Ø

UP

DN

12/12 12Ø

1.5D

D

12Ø 12/12

FLANGE

PRESSURE GAUGE WITH PIGTAIL

PRESSURE GAUGE WITH SHUT-OFF COCK

ANCHOR

DEMOLITION

ALIGNMENT GUIDE

FLEXIBLE EXPANSION JOINT

SOLENOID VALVE

CHEMICAL FEED

HELICOPTER FUEL RETURN

HELICOPTER FUEL SUPPLY

FUEL OIL RETURN

FUEL OIL SUPPLY

HOT GAS

EXISTING PIPING TO BE REMOVED

LIQUIFIED PETROLEUM GAS

GLYCOL PIPING SOLUTION

GLYCOL HEAT RECOVERY PIPING

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

EXISTING PIPING

NATURAL GAS

MAKE UP WATER

BOILER FEED WATER

BOILER BLOW DOWN

HIGH PRESSURE STEAM

MEDIUM PRESSURE STEAM

LOW PRESSURE STEAM

HIGH PRESSURE CONDENSATE

LOW PRESSURE CONDENSATE

HFR

HFS

FOR

FOS

HG

(NAME)

LPG

G(NAME)

GHR

HWR

HWS

E(NAME)

G

MUW

BF

BBD

HPS

MPS

LPS

HPC

LPC

DN

UNION

FLOW METER ORIFICE

FLOW SWITCH

TEMPERATURE AND PRESSURE TEST PORT

PRESSURE SWITCH

PRESSURE REDUCING, SELF CONTAINED VALVE

PRESSURE REDUCING, EXTERNAL PRESSURE VALVE

BALL VALVE (PIPE SIZES 2" AND SMALLER) BUTTERFLY

VALVE (PIPE SIZES 2-1/2" AND LARGER)

CHECK VALVE

MOTOR OPERATED BUTTERFLY VALVE

GAS COCK

RELIEF VALVE

GATE VALVE

ATC VALVE - 2 WAY

ATC VALVE - 3 WAY

GLOBE VALVE

CALIBRATED BALANCING VALVE

WITH GPM INDICATED

SHUT-OFF COCK FOR USE WITH PRESSURE GAUGE

FLOW METER

90° ELBOW

45° ELBOW

THERMOMETER - TEMP RANGE AS INDICATED

NIGHT THERMOSTAT

STEAM TRAP, F&T=FLOAT & THERMOSTATIC

B=BUCKET, T=THERMOSTATIC

ARROW INDICATES DIRECTION OF FLOW IN PIPE

LEADER INDICATES DOWNWARD SLOPE

RISER - DOWN (ELBOW)

RISER - UP (ELBOW)

BRANCH - SIDE CONNECTION

NRS GATE VALVE WITH SUPERVISION

FLOW SWITCH

HOSE VALVE

CLEAN-OUT

FLOOR CLEAN-OUT OR

CLEAN-OUT TO GRADE

VENT THRU ROOF

DOMESTIC COLD WATER (DCW)

DOMESTIC HOT WATER (DHW)

DOMESTIC HOT WATER RETURN (DHWR)

PLUMBING FIXTURES

POINT OF CONNECTION

SECTION TAG - TOP FIGURE IS SECTION NO.

BOTTOM FIGURE IS SHEET NO.

DETAIL TAG - TOP FIGURE IS DETAIL NO.

BOTTOM FIGURE IS SHEET NO.

EQUIPMENT IDENTIFICATION

KEYED NOTE IDENTIFICATION

ACID WASTE

ACID VENT

HIGH PRESSURE DOMESTIC WATER

MEDICAL OXYGEN

MEDICAL AIR

MEDICAL AIR AT PRESSURE INDICATED

MEDICAL VACUUM

NITROGEN

NITROUS OXIDE

CARBON DIOXIDE

COMPRESSED AIR

LAB AIR

LAB VACUUM

BRINE

FIXTURE FROM LEVEL ABOVE

P-1

EF

OX

MA

MA 120

MV

N

C02

CA

LA

LV

B

A M-101

A

M101

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CR

CS

CHWR

CHWS

INSTRUMENT AIR

INSTRUMENT AIR AT PRESSURE INDICATED

IA

IA 120

MEDIUM PRESSURE CONDENSATEMPC

BRANCH - BOTTOM CONNECTION

BRANCH - TOP CONNECTION

MECHANICAL

FIRE RISER

SPRINKLER HEAD

FLOOR SINK

FLOOR DRAIN

AIR VENT-MANUAL

AIR VENT-AUTO

REDUCER

HOSE BIBB

PIPE CAP

SWITCH

THERMOSTAT

SENSOR

ROOF DRAIN

DOWNSPOUT NOZZLE

INLINE PUMP

INLINE PUMP

WATER HAMMER ARRESTOR

CONCENTRIC REDUCER

ECCENTRIC REDUCER

CEILING RETURN AIR GRILLE

W/ SOUND BOOT

BDD

BACK DRAFT DAMPER

POSITIVE PRESSURE DUCT - RISE

POSITIVE PRESSURE DUCT - DROP

NEGATIVE PRESSURE DUCT - RISE

1-WAY BLOW PATTERN

2-WAY BLOW PATTERN

2-WAY BLOW PATTERN

3-WAY BLOW PATTERN

4-WAY BLOW PATTERN

DUCT SMOKE DETECTOR

UNIT HEATER

SW

OX 120

REFRIGERANT SUCTION

REFRIGERANT LIQUID

PUMPED CONDENSATE

VACUUM

RS

RL

V

ROOF DRAIN

ROOF DRAIN OVERFLOW

SEWER (BELOW GRADE)

SEWER (ABOVE GRADE)

VENT (SEWER)

SOFT DOMESTIC WATER (SW)

REVERSE OSMOSIS WATER RETURN

MEDICAL OXYGEN AT PRESSURE INDICATED

RDO

RD

ROR

FCO

COTG

GATE VALVE - NON RISING STEM

ANGLE VALVE

BALANCING COCK

VALVE IN RISE

FILL PORT

DRAIN PAN AND P-TRAP

PLUMBING PLUMBING CONT. LINETYPES LINETYPES CONT.

SYMBOLS

FIRE

FIRE SPRINKLER WATERF

RISE OR DROP

DI DEIONIZED WATER SUPPLY

DEIONIZED WATER RETURNDIR

RO REVERSE OSMOSIS WATER SUPPLY

FUEL OIL VENTFOV

REDUCED PRESSURE BACKFLOW

PREVENTOR W/ DRAIN PAN LUBRICATED PLUG COCK

THERMOSTATIC MIXING VALVE

07/31/2026

260252

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

B U

IL

D

IN

G

H

EA

TI

N

G /C

O O

LI

N

G E

N D

O F

H A

LL

U

N

IT

S

E

AS

T

C

EN

TE

R

S

TR

EE

T

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M001

MECHANICAL

SYMBOLS AND

ABBREVIATIONS

GENERAL NOTES

1. ALL CEILING DIFFUSERS SHOWN AS SUCH ARE CD-1.

CFM AS NOTED, UNLESS OTHERWISE NOTED, REFER TO

DETAIL 3/M501.

2. ALL CEILING DIFFUSERS SHOWN AS SUCH ARE RG-1

UNLESS OTHERWISE NOTED. PROVIDE SOUND BOOT

PER DETAIL 4/M501.

3. THE EXISTING FORENSICS ROOF IS UNDER WARRANTY

BY CARLISLE ROOFING SYSTEMS. ALL REPAIR WORK

SHALL BE PERFORMED BY PERKES ROOFING.

4. ALL OUTDOOR REFRIGERANT PIPING SHALL BE

INSTALLED WITH AN ALUMINUM, STUCCO EMBOSSED,

0.016" THICK, PIPE JACKET.

5. CONDENSATE PIPING SHALL BE TYPE M,

DRAWN-TEMPER COPPER TUBING, WROUGHT-COPPER

FITTINGS, AND SOLDERED JOINTS.

6. CONDENSATE PIPING INSULATION SHALL BE 1/2" THICK

FLEXIBLE ELASTOMERIC OR 1/2" THICK MINERAL-FIBER,

PREFORMED PIPE INSULATION, TYPE I.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/24/2026

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

B U

IL

D

IN

G

H

EA

TI

N

G /C

O O

LI

N

G E

N D

O F

H A

LL

U

N

IT

S

E

AS

T

C

EN

TE

R

S

TR

EE

T

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M101

MECHANICAL

OVERALL PLAN

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/24/2026

12/12

10"

/10

12/12

10"

/10

AC

4A

AC

4B

12/12

10"

/10

AC

3B

12/12

10"

/10

AC

3A

3/4"

3/4"

AC

AC

10/103

12/12

14/10

10/16

12/10

12/12

10"

/10

12/12

10"

/10

AC

2A

AC

2B

12/12

10"

/10

AC

1B

12/12

10"

/10

AC

1A

3/4"

3/4"

AC

AC

(TYP.) (TYP.)

10/10

14/10

12/10

12/12

10/16

07/31/2026

260252

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

B U

IL

D

IN

G

H

EA

TI

N

G /C

O O

LI

N

G E

N D

O F

H A

LL

U

N

IT

S

E

AS

T

C

EN

TE

R

S

TR

EE

T

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

GENERAL NOTES

1. ALL NEW WORK SHOWN IS LOCATED ABOVE A HARD LID

CEILING. CONTRACTOR SHALL CUT HOLES IN CEILING

THROUGHOUT TO ACCOMMODATE ALL NECESSARY

WORK. PATCH, REPAIR, AND PAINT UPON COMPLETION

OF WORK. MATCH EXISTING. FIELD VERIFY EXISTING

CONDITIONS.

2. PROVIDE AND INSTALL ONE CEILING ACCESS PANEL FOR

EACH INSTALLED FAN COIL UNIT. REFER TO

SPECIFICATIONS FOR ACCESS PANEL TYPE.

KEYED NOTES#

1. EXTEND AND CONNECT REFRIGERANT PIPING FROM INDOOR

UNIT TO OUTDOOR UNIT. PROVIDE, INSTALL, AND SIZE

REFRIGERANT PIPING PER MANUFACTURERS

RECOMMENDATIONS.

2. EXTEND 3/4" CONDENSATE DRAIN LINE AND TERMINATE

THROUGH EXTERIOR WALL.

3. CONTRACTOR TO RAISE / LOWER EXISTING DUCTWORK AS

NEEDED TO ACCOMMODATE INSTALLATION OF NEW

DUCTWORK, FAN COIL UNIT, AND PIPING. FIELD VERIFY

EXISTING CONDITIONS. TYPICAL OF ALL.

M401

MECHANICAL

ENLARGED PLAN

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/24/2026

12/12

10"

/10

12/12

10"

/10

AC

7A

AC

7B

12/12

10"

/10

AC

8B

12/12

10"

/10

AC

8A

3/4"

3/4"

AC

AC

3 10/16

6/6

10/10

6/6

10/8

10/10

10/10

12/12

10"

/10

12/12

10"

/10

AC

5A

AC

5B

12/12

10"

/10

AC

6B

12/12

10"

/10

AC

6A

3/4"

3/4"

AC

AC

(TYP.) (TYP.)

3 10/1014/12

14/14

10/10

07/31/2026

260252

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

B U

IL

D

IN

G

H

EA

TI

N

G /C

O O

LI

N

G E

N D

O F

H A

LL

U

N

IT

S

E

AS

T

C

EN

TE

R

S

TR

EE

T

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M402

MECHANICAL

ENLARGED PLAN

GENERAL NOTES

1. ALL NEW WORK SHOWN IS LOCATED ABOVE A HARD LID

CEILING. CONTRACTOR SHALL CUT HOLES IN CEILING

THROUGHOUT TO ACCOMMODATE ALL NECESSARY

WORK. PATCH, REPAIR, AND PAINT UPON COMPLETION

OF WORK. MATCH EXISTING. FIELD VERIFY EXISTING

CONDITIONS.

2. PROVIDE AND INSTALL ONE CEILING ACCESS PANEL FOR

EACH INSTALLED FAN COIL UNIT. REFER TO

SPECIFICATIONS FOR ACCESS PANEL TYPE.

KEYED NOTES#

1. EXTEND AND CONNECT REFRIGERANT PIPING FROM INDOOR

UNIT TO OUTDOOR UNIT. PROVIDE, INSTALL, AND SIZE

REFRIGERANT PIPING PER MANUFACTURERS

RECOMMENDATIONS.

2. EXTEND 3/4" CONDENSATE DRAIN LINE AND TERMINATE

THROUGH EXTERIOR WALL.

3. CONTRACTOR TO RAISE / LOWER EXISTING DUCTWORK AS

NEEDED TO ACCOMMODATE INSTALLATION OF NEW

DUCTWORK, FAN COIL UNIT, AND PIPING. FIELD VERIFY

EXISTING CONDITIONS. TYPICAL OF ALL.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/24/2026

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

B U

IL

D

IN

G

H

EA

TI

N

G /C

O O

LI

N

G E

N D

O F

H A

LL

U

N

IT

S

E

AS

T

C

EN

TE

R

S

TR

EE

T

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M501

MECHANICAL

DETAILS AND

SCHEDULES

ROOFTOP EQUIPMENT - IF

EQUIPMENT MOUNTING POINTS ALIGN WITH

THE CHANNEL FRAME, ATTACHMENT OF

EQUIPMENT CAN BE MADE DIRECTLY TO

THE FRAME - IF EQUIPMENT MOUNTING

POINTS DO NOT ALIGN WITH THE CHANNEL

FRAME, MOUNT TO A UNI-STRUT SYSTEM

THAT WOULD SPAN BETWEEN AND ATTACH

TO BOTH THE CHANNEL FRAME AS WELL AS

THE EQUIPMENT MOUNTS

FIELD CUT BOTTOM OF SUPPORT POSTS

AS REQ'D. TO ACHIEVE A LEVEL PLATFORM

ROTATE DIRECTION OF BASE

PLATES AS REQ'D TO ALIGN WITH

SLOPE OF DECK (TYP.)

EQUIPMENT PLATFORM 3D

1/8

GALVANIZED C4x5.4

CHANNEL

NOTE:

NO WELDING WILL BE ALLOWED ON

THE ROOF - WELDING SHALL BE DONE

IN THE PARKING LOT OR IN A SHOP

24" TALL GALVANIZED HSS 3x.203 -

MEASURE AND FIELD CUT BOTTOM OF

POSTS AS REQ'D. TO ACHIEVE LEVEL

TOP OF PLATFORM

1/2" Ø THROUGH BOLT WITH LOCK

WASHER - DRILL THROUGH ANGLES

AND HSS POST AS REQ'D.

3x3x1/4x 4" LONG GALVANIZED STEEL

ANGLE WELDED TO BASE PLATE -

EACH SIDE OF HSS POST

ROOFING MEMBRANE

12x12x1/2" GALVANIZED STEEL

PLATE - FASTEN INTO DECK 1/4

1/4

CJP (TYP @ MITERED CHANNEL

JOINTS TOP & SIDES)

1/4

NOTE:

6 SUCH SUPPORT LEGS ARE TO BE

PROVIDED FOR EACH PIECE OF

EQUIPMENT - INSTALL IN A 24" x 48"

RECTANGULAR CONFIGURATION - MITER

CHANNEL CORNERS AND WELD (TYP.)

CONT. BEAD OF

APPROVED SEALANT

STAINLESS STEEL

CLAMPING RING

FIELD FABRICATED

METAL HOOD

PRE-MOLDED PVC

PIPE FLASHING

2" MIN. WELDED

SPLICE

8" M

IN

NOTE:

PATCH AND REPAIR

ROOF AS NEEDED,

MATCH EXISTING

BOTH ENDS

PROVIDE AND INSTALL

WALKING MATS ON ALL

4 SIDES OF ELEVATED

PLATFORM

2" AS REQ'D. 2"

LINE SET OR OTHER SIM.

PENETRATIONS THROUGH

ROOF

PLAN VIEW

FASTEN FLANGES OF ENCLOSURE

TO DECK WITH (12) #14 STS (OR

APPROPRIATE FASTENERS FOR

DECK TYPE)

SEAL OR FOAM IN AND

AROUND OPENINGS TO

FURTHER PROTECT THE

OPENING FROM THE

ELEMENTS AND INSECTS ETC.

FASTEN PARTIAL COATED

METAL PIPE EXTENSION TO

ENCLOSURE - SEE PHOTO

ABOVE (SIM.) - COVER ALL

FASTENERS / JOINTS WITH

WELDED MEMBRANE

NOTCH CAP WHERE PIPES

PENETRATE (IF REQ'D.)

NOTE (TYPICAL):

LOCATE NEW LINE SET

ENCLOSURES A MININUM OF 18"

AWAY FROM THE UNIT BEING

SERVED

LINE SET OR OTHER SIM.

PENETRATIONS THROUGH ROOF

AT BASE OF ENCLOSURE,

PROVIDE INSULATION THAT IS

FASTEN FLANGES OF ENCLOSURE TO DECK WITH

(12) #14 STS (OR APPROPRIATE FASTENERS FOR

DECK TYPE)

ROOFING MEMBRANE

NOTE THAT LINE SET

MUST ENTER THE

ENCLOSURE DRAPING

UPWARDS AS SHOWN

2"

COATED METAL

ENCLOSURE WITH ALL

SEAMS / JOINTS /

FASTENERS ETC. FULLY

COVERED /

WATERPROOFED WITH

HEAD WELDED

MEMBRANE

HEAT WELD FLASHING

TO COATED METAL

ENCLOSURE

NOTE THAT THIS EDGE OF THE CAP

IS TO EXTEND 4" BEYOND THE FACE

OF THE ENCLOSURE TO SHIELD

LINE SET PENETRATION FROM

WEATHER - PROVIDE HEMMED DRIP

EDGE AS SHOWN

4" AS REQ'D.

REMOVABLE COATED METAL

CAP - FASTEN TO

ENCLOSURE W/ (2 PER SIDE

ON 3 SIDES) HIGH-DOMED,

CAPPED, GASKETED

FASTENERS - ALL SEAMS /

JOINTS THAT ARE NOT

REQUIRED FOR REMOVAL OF

CAP ARE TO BE FULLY

WATERPROOFED WITH HEAT

WELDED MEMBRANE

RIGID INSULATION -

ROOF DECK

NOTE THAT PITCH POCKETS

ARE NOT AN ACCEPTABLE

METHOD OF WATER-PROOFING

BASE OF PIPES

2"

AS

R

EQ

'D

2"

1'

8" M

IN

EQUIVALENT TO THE R-VALUE

OF THE ROOF SYSTEM

ENCLOSURE SHOWN IN PHOTO FOR REFERENCE ONLY -

NOTE THAT ALL METAL MUST BE COATED METAL, (NOT

GALVANIZED METAL)

LINE WITH 1" OF

ACOUSTICAL INSULATION

SHEET ROCK CEILING

SURFACE MOUNT

SEE PLAN FOR DUCT SIZE

O.B.D.

LAY-IN TEE BAR CEILING

SEE PLAN FOR NECK SIZE

AND LOCATION

3/4 W

W

2W

(MIN. 12")

ANY NOISE SOURCE

ABOVE CEILING DIRECT AWAY FROM

OPEN INTO RETURN AIR PLENUM

SUPPORT FROM STRUCTURE

FOR SIZE AND LOCATION

RETURN AIR GRILLE SEE PLANS

CEILING

(BOOT WIDTH SAME AS GRILLE WIDTH)

ACOUSTICAL INSULATION

SHEET METAL BOOT LINE WITH 1"

AIR FLOW

L

NOTE:

DAMPERS SHOULD NOT BE

INSTALLED CLOSER THAN TWO

DUCT WIDTHS TO ELBOWS OR

INTERSECTIONS.

REMOTE CEILING

OPERATOR WHERE

DAMPER IS

INACCESIBLE

NOTE

L=1/4 W (4" MIN.)

VOLUME DAMPER

PROVIDE CONCEALED

CEILING DAMPER

REGULATORW

45°

GRILLES, REGISTERS AND DIFFUSERS

MAX

ID MANUFACTURER MODEL NC DESCRIPTION NOTES

MAXIMUM SECURITY STEEL PERFORATED FACE CEILING DIFFUSERS. ALL

WELDED CONSTRUCTION. WHITE POWER COAT FINISH. REMOVABLE FACE & CORE.

CD-1 EH PRICE MSRRP 20 REAR OPPERATED OPPOSED BLADE DAMPER. 1

SURFACE MOUNTED. 3/16" MAXIMUM HOLE DIAMETER.

PROVIDE TORX SECURITY TAMPER-PROOF PIN SCREWS FOR ALL SECURITY GRILLES.

MAXIMUM SECURITY STEEL PERFORATED FACE CEILING DIFFUSERS. ALL

WELDED CONSTRUCTION. WHITE POWER COAT FINISH. REMOVABLE FACE & CORE.

RG-1 EH PRICE MSRRP 20 REAR OPPERATED OPPOSED BLADE DAMPER. 1

SURFACE MOUNTED. 3/16" MAXIMUM HOLE DIAMETER.

1. PROVIDE TORX SECURITY TAMPER-PROOF PIN SCREWS FOR ALL SECURITY GRILLES.

SPLIT SYSTEM

MANUFACTURER COOLING HEATING INDOOR UNIT OUTDOOR UNIT REFRIGERANT LINES

AND CAPACITY CAPACITY CFM DIMENSIONS AMPS AMPS DIMENSIONS WEIGHT AMPS AMPS

ID MODEL NUMBER LOCATION (BTU/H) (BTU/H) RANGE W" x D" x H" (MCA) (MOCP) VOLTS/PH/HZ. W" x D" x H" (LBS.) (MCA) (MOCP) VOLTS/PH/HZ. LIQUID GAS NOTES

AC-1 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-1A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-1B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-2 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-2A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-2B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-3 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-3A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-3B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-4 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-4A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-4B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-5 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-5A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-5B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-6 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-6A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-6B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-7 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-7A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-7B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-8 MITSUBISHI MXZ-2D20NL ROOF 20,000 13,700 - - - - - 34 X 28 X 13 150 21.7 38 208-230/1/60 1/4 3/8 1,2,3,4,5,6AC-8A MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

AC-8B MITSUBISHI PEAD-AA09NL INDOOR 9,000 9,000 265 - 350 36 X 29 X 10 2.1 15 208-230/1/60 - - - - - 1/4 3/8

1. CAPACITIES RATED AT THE FOLLOWING OUTDOOR CONDITIONS: COOLING - 95 DEG. F. D.B., 75 DEG. F. W.B. HEATING - 5 DEG F DB

2. CAPACITIES RATED AT THE FOLLOWING INDOOR CONDITIONS: COOLING - 80 DEG. F. D.B., 67 DEG. F. W.B., HEATING - 70 DEG F DB

3. R454B REFRIGERANT.

4. PROVIDE ACCESSORY CONDENSATE PUMP FOR INDOOR UNIT.

5. UNIT TO COME WITH BACNET CARD.

6. TWO INDOOR UNITS SHALL BE TIED TO ONE OUTDOOR UNIT. UNIT TO COME WITH NECESSARY CONTROLLER FOR TWINING REQUIREMENTS.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/24/2026

Sheets and Views
C001 COVER SHEET
M001 MECHANICAL SYMBOLS AND ABBREVIATIONS
M101 MECHANICAL OVERALL PLAN
M401 MECHANICAL ENLARGED PLAN
M402 MECHANICAL ENLARGED PLAN
M501 MECHANICAL DETAILS AND SCHEDULES

File details come from the government source that posted it. Updated .