This document is an internal Navy memorandum dated July 10, 2024, from Juan C. Padró (Design Team Supervisor, Facility and Infrastructure Design Section) to Joseph H. Lupton at FRC East in Cherry Point, North Carolina, forwarding a work recommendation for Building 4035 (Plating Shop) mechanical room overflow containment tank repairs.

The work involves replacing deteriorated sealing elements on three (3) pipe penetrations used on pipes penetrating the cyanide secondary containment system. The seals were originally installed circa 2012 and have significantly deteriorated, though the existing wall sleeves and concrete surfaces remain in good condition. The contractor is required to reuse the existing wall sleeves and piping while installing new modular pipe sealing systems similar to Link-Seal Model OS-316, featuring nitrile green rubber seal elements, reinforced nylon polymer pressure plates, and 316 stainless steel hardware, installed per manufacturer specifications. After removing existing sealing elements, all sleeve and pipe surfaces must be cleaned to a smooth finish as recommended by the manufacturer. The work area involves hazardous conditions (cyanide waste), requiring the selected contractor to obtain a Confined Space Entry permit per FRC East Instruction FRCEASTINST 5100.14C and use appropriate Personal Protective Equipment in accordance with FRC East Instruction FRCEASTINST 5100.2. FRC East's HAZMAT team will handle sump emptying prior to contractor work. The document includes detailed technical drawings and an aerial facility map showing Building 4035's location within the Naval Air Station Cherry Point complex.

View the file

Other files

File Type Posted
7516334 MACC.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Juan C. Padró Facility and Plant Planning Division Design Team Supervisor Infrastructure Investment Branch Facility and Infrastructure Design Section FRC East, PO Box 8021 JC21200/31300 Cherry Point, NC 28533-0021 10 JUL 2024 Desk: (252) 464-7661

Recipients: Joseph H. Lupton, 252-464-7819 Re. Support requested for B4035 Plating Shop Mechanical Room Overflow Containment Tanks as recorded below:

From: Spitz, Michael D CTR (USA) <michael.d.spitz.ctr@us.navy.mil> Sent: Thursday, June 20, 2024 12:31 PM To: Lupton, Joseph H Jr CIV USN (USA) <joseph.h.lupton.civ@us.navy.mil>; Padro Octaviani, Juan C CIV USN COMNAVAIRSYSCOM PAX (USA) <juan.c.padrooctaviani.civ@us.navy.mil>; Velazquez, Rogelio CIV USN (USA) <rogelio.velazquez4.civ@us.navy.mil> Subject: FW: B4035 Plating Shop Mechanical Room Overflow Containment Tanks

Joe, Juan is going to help with identifying the appropriate seals for the piping penetration. He has the plans from a similar effort that was developed back in 2012. It’s not clear whether this effort was carried out. He would like to arrange a field visit with the black light to look and see if they did any of the construction from the plans he has.

Michael Spitz, PE Civil/industrial Engineer FRCE Facilities & Infrastructure Design Section Ph: 252.464.9969

Joseph, During the site visit we noticed that the sealing elements of the pipe penetration systems used on the pipes penetrating the cyanide secondary containment has deteriorated significantly. Seals installation circa 2012. The pipe sleeves and concrete surface appear to be in good conditions.

We recommend replacing the sealing element for each of the three (3) penetrations. Wall sleeves and piping may be re-used. Refer to enclosed sketch for additional details.

As discussed with FRC East Environmental Department, sumps are to be emptied by FRC East HAZMAT team. The hazardous conditions of the work area warrant the selected contractor to comply with specific occupational safety and health requirements. Contractor must obtain a Confine Space Entry permit in accordance with FRC East Instruction “FRCEASTINST 5100.14C_Confine Space Entry Program”. Also, Contractor must use Personal Protective Equipment (PPE) suitable for hazardous environment in accordance with FRC East Instruction “FRCEASTINST 5100.2 Occupational Safety and Health Manual”.

If you have any questions or require additional input or investigation on my part, please contact the Facilities and Infrastructure Design Team at your convenience.

mailto:michael.d.spitz.ctr@us.navy.mil mailto:joseph.h.lupton.civ@us.navy.mil mailto:juan.c.padrooctaviani.civ@us.navy.mil mailto:rogelio.velazquez4.civ@us.navy.mil

ACID WASTE

T-401

CHROMATE

WASTE

T-402

CYANIDE

WASTE

T-403

4" DUCTILE IRON

4" DUCTILE IRON

4" DUCTILE IRON

SUMP'S CONCRETE WALL (TYPICAL)

(ETR) PIPE - 4" DUCTILE IRON

NEW MODULAR PIPE SEALING SYSTEM. NITRILE

GREEN RUBBER SEAL ELEMENT, REINFORCED

NYLON POLYMER PRESSURE PLATES, 316

STAINLESS STEEL HARDWARE. SIMILAR TO

MODEL OS-316 AS MANUFACTURED BY LINK-SEAL.

INSTALL PER MANUFACTURER INSTRUCTION.

SUMP CONCRETE WALL

EXISTING NON METALLIC, HIGH

DENSITY POLYETHYLENE WALL SLEEVE

A DETAIL - MECHANICAL SEAL

NOT TO SCALE

*CONDITION TYPICAL FOR 3

MECHANICAL SEAL TO BE

REPLACED. WALL

SLEEVE TO REMAIN

A N/A

AFTER REMOVING EXISTING SEALING

ELEMENT, CLEAN SLEEVE AND PIPE

SURFACES TO A SMOOTH FINISH, AS

RECOMMENDED BY MANUFACTURER.

5/21/26, 7:17 AM secureprovider (1806×830) https://mas8.manage.usmcmax.usmc.mil/maximo/servlet/secureprovider?file=3aWahWOLs9cqk2Q5gd2mrLhyhS22M4tMpC3x5jaxr73lXpUxBJudNdaz4C1tKDU0obVw5j3nQAf4t3aQvVV4ldAGZsWFfHa… 1/1

5/21/26, 7:09 AM secureprovider (1796×826) https://mas8.manage.usmcmax.usmc.mil/maximo/servlet/secureprovider?file=3aWahWOLs9cqk2Q5gd2mrLhyhS22M4tMpC3x5jaxr73lXpUxBJudNdaz4C1tKDU0obVw5j3nQAf4t3aQvVV4ldAGZsWFfHa… 1/1

B4035PlatingShopCyanideTankPipePenetrations
From: Spitz, Michael D CTR (USA) <michael.d.spitz.ctr@us.navy.mil> Sent: Thursday, June 20, 2024 12:31 PM To: Lupton, Joseph H Jr CIV USN (USA) <joseph.h.lupton.civ@us.navy.mil>; Padro Octaviani, Juan C CIV USN COMNAVAIRSYSCOM PAX (USA) <juan.c.padro...
B4035 Plating Shop Mechanical Room Overflow Containment Tanks-21323M-1.pdf
Sheets and Views
21323M-1
smallMap
locationMap

File details come from the government source that posted it. Updated .