724096_PERMIT_DOCUMENTS.pdf

PDF 17 MB Posted

Attached to
Auditorium Lighting Upgrades
Solicitation number
25-CR-043
Issued by
Pinellas County, Florida

About this file

The document is a set of permit documents for the Auditorium Lighting Replacement project at Gibbs High School in St. Petersburg, Florida, prepared by TLC Engineering Solutions for the School Board of Pinellas County. The project involves a comprehensive lighting upgrade for the school's auditorium, including replacing existing house lighting, work lighting, and related equipment, as well as upgrading the existing lighting control system for various fixture types. The project encompasses multiple levels of the auditorium, with specific focus on replacing fixtures in areas such as the main seating area, stairs, lobby, control booths, and technical spaces. The scope includes removing unused network lighting wiring, installing new lighting controls, and providing training on the new lighting system.

The permit documents outline detailed electrical specifications, including requirements for electrical devices, wiring, raceways, and compliance with national and local building codes, including the Florida Building Code and National Electrical Code. The project is funded through the School Board of Pinellas County, with Kevin K. Hendrick listed as the Superintendent of Schools. The total project number is AE215208, with TLC Engineering Solutions' project number 724096. The documents include comprehensive technical drawings, photometric calculations, and as-built drawing plans, indicating a thorough and professional approach to the lighting renovation. The project requires a Florida licensed Electrical "EC" or "ES" Contractor and emphasizes compliance with State Requirements for Educational Facilities (SREF).

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :5

A

M

COVER

SHEET

E000

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

VICINITY MAP

PROJECT SHEET INDEX

Sheet Number Sheet Name

E000 COVER SHEET

E001 ELECTRICAL GENERAL NOTES

E100 LIGHTING PLAN - LEVEL 1

E101 LIGHTING PLAN - LEVEL 2

E102 LIGHTING PLAN - LEVEL 3

E103 LIGHTING PLAN - LEVEL 4

E104 LIGHTING PLAN - LEVEL 5

E105 LIGHTING PLAN - LEVEL 6

E106 LIGHTING PLAN - PIT LEVEL

E200 NETWORK CONTROLS PLAN LEVEL 1

E201 NETWORK CONTROLS PLAN LEVEL 2

E202 NETWORK CONTROLS PLAN LEVEL 3

E203 NETWORK CONTROLS PLAN LEVEL 4

E400 FIXTURES SCHEDULE & CONTROLS DETAILS

E500 AS-BUILT DRAWINGS (FIPO NTS)

E501 AS-BUILT DRAWINGS (FIPO NTS)

E502 AS-BUILT DRAWINGS (FIPO NTS)

E503 AS-BUILT DRAWINGS (FIPO NTS)

E504 AS-BUILT DRAWINGS (FIPO NTS)

E505 AS-BUILT DRAWINGS (FIPO NTS)

E506 AS-BUILT DRAWINGS (FIPO NTS)

E507 AS-BUILT DRAWINGS (FIPO NTS)

E508 AS-BUILT DRAWINGS (FIPO NTS)

E509 AS-BUILT DRAWINGS (FIPO NTS)

E510 AS-BUILT DRAWINGS (FIPO NTS)

E600 PHOTOMETRIC CALCULATIONS

E601 PHOTOMETRIC CALCULATIONS

E602 PHOTOMETRIC CALCULATIONS

AUDITORIUM LOCATION

THEATER LIGHTING RENOVATION

FOR

GIBBS HIGH SCHOOL

PROJECT NO: AE215208

PREPARED FOR

SCHOOL BOARD OF PINELLAS COUNTY

Laura Hine - Chairperson

Carol J. Cook - Vice Chairperson Dawn M. Peters Eileen M. Long

Stephanie Meyer Caprice Edmond

Liisa N. Cane

SUPPERINTENDENT OF SCHOOLS

Kevin K. Hendrick January 17, 2024

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2020 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

xxxxxx724096

No. Date Description

ELECTRICAL GENERAL NOTES

ELECTRICAL DEVICES OUTLET BOXES, JUNCTION BOXES

1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS NOTED

OTHERWISE.

2. RECEPTACLES, VOICE/DATA OUTLETS AND WALL FURNITURE FEEDS SHALL BE MOUNTED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS NOTED OTHERWISE. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK

SPLASH TO CENTERLINE OF DEVICE, UNLESS NOTED OTHERWISE.

3. IT IS THE INTENT THAT ALL DEVICE OUTLET BOXES (POWER AND SYSTEMS) BE FLUSH MOUNTED IN WALLS, CEILINGS OR FLOORS, AND JUNCTION BOXES FLUSH MOUNTED IN WALLS, CEILINGS, OR FLOORS, OR CONCEALED ABOVE ACCESSIBLE CEILINGS, AND NOT SURFACE MOUNTED, UNLESS SPECIFICALLY NOTED ON THE CONTRACT DRAWINGS, OR UNLESS THE ARCHITECT/ENGINEER

GRANTS WRITTEN PERMISSION.

4. ALL COMPONENTS OF THE ELECTRICAL SYSTEM (INCLUDE RACEWAYS, ELECTRICAL EQUIPMENT, OUTLET BOXES, JUNCTION BOXES, ETC.) LOCATED IN A HAZARDOUS (CLASSIFIED) LOCATION SHALL BE APPROVED FOR USE IN SAID LOCATION, AS DEFINED

BY THE NEC, WHETHER INDICATED ON THE CONTRACT DOCUMENTS OR NOT.

5. ALL DEVICES SHALL BE MOUNTED VERTICALLY, UNLESS NOTED OTHERWISE.

6. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP.

7. WHERE DEVICES ARE SHOWN IN WALLS BACK-TO-BACK ON OPPOSITE SIDES, INSTALL SO THAT THEY ARE SEPARATED BY AT LEAST 12".

8. ALL RECEPTACLES LOCATED IN KITCHENS, BATHROOMS, MECHANICAL ROOMS, JANITOR CLOSETS, ELEVATOR SHAFTS, ELEVATOR EQUIPMENT ROOMS, FOR ELEVATOR SUMP PUMP(S) OR INSTALLED WITHIN 6' OF THE INSIDE FACE OF A SINK, SHALL BE GFCI TYPE

OR GFCI PROTECTED.

9. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES, THEY SHALL BE INSTALLED WITHOUT

AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:

A. ALL ELECTRICAL BOXES SHALL BE METALLIC.

B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.

C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.

D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED WITH JOINT COMPOUND (OR

OTHER APPROVED MATERIAL).

E.PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE WALL RATING SHALL BE

MAINTAINED.

F.THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.

G.OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE SEPARATED BY A MINIMUM

HORIZONTAL DISTANCE OF 24 INCHES.

H.OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.

I.THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH BETWEEN THE EDGES OF THE

OUTLET BOX AND THE EDGES OF THE OPENING.

ELECTRICAL EQUIPMENT

1. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED.

ALL COMPONENTS OF THE ELECTRICAL SYSTEM LOCATED OUTDOORS OR INDOORS WHERE EXPOSED TO SIGNIFICANT MOISTURE SHALL BE WEATHERPROOF, NEMA 3R, AS A MINIMUM, WHETHER INDICATED ON THE CONTRACT DRAWINGS OR NOT.

2. TERMINATION PROVISIONS FOR ALL ELECTRICAL EQUIPMENT (PANELBOARDS, SWITCHBOARD, TRANSFORMERS, DISCONNECT SWITCHES, MOTOR CONTROLLERS, AUTOMATIC TRANSFER SWITCHES, ENCLOSED CIRCUIT BREAKERS, BUSWAYS, ETC.) SHALL BE LISTED AND IDENTIFIED FOR USE WITH MINIMUM 75 DEG. F CONDUCTORS IN ACCORDANCE WITH NEC.

3. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC.

4. THE ELECTRICAL DEDICATED EQUIPMENT SPACE EXTENDING FROM FLOOR TO 6' ABOVE ELECTRICAL EQUIPMENT OR TO THE STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, ARCHITECTURAL APPURTENANCES AND OTHER EQUIPMENT FOREIGN TO THE

ELECTRICAL INSTALLATION IN ACCORDANCE WITH NEC.

5. PROVIDE SURGE PROTECTION DEVICE FOR ALL MAIN SERVICE EQUIPMENT, PANELBOARDS SERVING SENSITIVE ELECTRONIC EQUIPMENT (DATA RACKS) OR COMPUTERS, EMERGENCY SWITCHBOARDS AND PANELBOARDS, LIGHTING PANELS SERVING EXTERIOR LIGHTING, POWER CIRCUITS OR LOW VOLTAGE (FIRE ALARM, TELECOMMUNICATIONS) EXITING THE BUILDING. PROVIDE MINIMUM 30A/3P BREAKER IN BRANCH CIRCUIT PANELBOARDS AND 60A/3P IN DISTRIBUTION PANELBOARDS OR SWITCHBOARDS, UNLESS NOTED OTHERWISE, OR PER THE SPD MANUFACTURER'S RECOMMENDATIONS FOR SURGE PROTECTION DEVICE.

CONDUCTORS

1. ALL WIRE SHALL BE SIZED AS SHOWN ON THE DRAWINGS. IF NO WIRE SIZE IS SHOWN, THEN WIRE SHALL BE #12 AWG.

2. BRANCH CIRCUITS SHALL BE INCREASED IN SIZE AS REQUIRED TO COMPENSATE FOR VOLTAGE DROP FROM LENGTH OF CIRCUIT DUE TO FIELD ROUTING. FINAL INSTALLATION SHALL NOT EXCEED A MAXIMUM OF 3% VOLTAGE DROP FOR BRANCH CIRCUITS. REFER TO VOLTAGE DROP TABLE BELOW FOR CONDUCTOR SIZES FOR BRANCH CIRCUITS AS FOLLOWS:

A. 120V, 20A CIRCUITS SHALL BE:

i. #12 FROM 0-70 FT

ii. #10 FROM 71-115FT

iii. #8 FROM 116-180FT

B. 277V, 20A CIRCUITS SHALL BE:

i. #12 FROM 0-140FT

ii. #10 FROM 141-220FT

iii. #8 FROM 221-350FT

ANYTHING LONGER THAN THE ABOVE SHALL BE SUBMITTED TO THE ENGINEER WITH CALCULATIONS FOR APPROVAL.

3. ALL CONDUCTORS IN CABINETS MUST BE CAREFULLY FORMED AND HARNESSED SO THAT EACH CONDUCTOR DROPS OFF

DIRECTLY OPPOSITE TO TERMINAL.

4. ALL WIRE SIZES ARE BASED ON AMPACITIES FOR 60 DEG F TEMPERATURE RATING FROM 0-100A AND 75 DEG. F TEMPERATURE

RATING LISTED IN NEC FOR 100A AND ABOVE.

5. ALL CONDUCTORS SHALL BE COPPER, THHN/THWN; SOLID FOR #10 AWG AND SMALLER; STRANDED FOR #8 AWG AND LARGER.

6. CONDUCTORS USED IN WET LOCATIONS, INCLUDING BUT NOT LIMITED TO UNDERGROUND CONDUITS/DUCTBANKS AND EXTERIOR CONDUITS SHALL COMPLY WITH NEC 310.10 AND BE LISTED FOR USE IN WET LOCATIONS.

7. ALL POWER CIRCUITS HAVE BEEN DESIGNED TO MEET 2% OR LESS VOLTAGE DROP FOR FEEDERS, AND 3% OR LESS VOLTAGE

DROP FOR BRANCH CIRCUITS.

GROUNDING

1. FIRE PROTECTION PIPING SHALL NOT BE USED FOR GROUNDING.

2. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE AN EQUIPMENT GROUND CONDUCTOR. METAL RACEWAYS SHALL NOT BE

USED AS THE SOLE EQUIPMENT GROUND.

3. WHERE A PHASE CONDUCTOR IS INCREASED IN SIZE DUE TO VOLTAGE DROP, THE EQUIPMENT GROUND CONDUCTOR SHALL BE

INCREASED IN SIZE PROPORTIONATELY.

ELECTRICAL DEMOLITION NOTES:

1. DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN DASHED LINE TYPE ARE EXISTING TO BE DEMOLISHED; DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN LIGHT (SCREENED) SOLID LINE TYPE ARE EXISTING TO REMAIN, UNLESS NOTED

OTHERWISE.

2. EXISTING EQUIPMENT, LIGHT FIXTURES AND DEVICES SHOWN ARE BASED ON FIELD SURVEYS AND RECORD DRAWINGS PROVIDED BY THE OWNER, AND ARE NOT NECESSARILY INCLUSIVE OF ALL EXISTING ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND DEVICES WITHIN PROJECT AREAS. IT IS THE INTENT THAT THE DEMOLITION PLANS PROVIDE A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THE PLAN SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED

ELECTRICAL DEMOLITION WHETHER INDICATED ON THE PLANS OR NOT.

3. EXISTING CIRCUITING SHOWN IS BASED ON RECORD DRAWINGS AND THE SURVEYED PANEL DIRECTORIES, WHERE THEY WERE AVAILABLE. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE CONDITIONS SHOWN ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT, WHERE SHOWN ON THE PLAN DRAWINGS, AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION

NECESSARY TO COMPLETE THE NEW WORK. FIELD CONDITIONS SHALL GOVERN.

4. WHERE EXISTING DEVICES ARE INDICATED TO REMAIN OR BE RELOCATED, ARE WITHIN THE SCOPE OF THIS PROJECT AND EXISTING CIRCUITING INFORMATION IS UNAVAILABLE, CONTRACTOR IS TO PROVIDE CIRCUIT TRACING TO IDENTIFY PANEL AND CIRCUIT SERVING THE DEVICE TO AND PROVIDE THAT INFORMATION TO THE ARCHITECT/ENGINEER PRIOR TO ROUTING CONDUITS AND WIRING FOR NEW DEVICES AND EQUIPMENT WITHIN THE SCOPE OF THIS PROJECT.

5. WHERE EXISTING DEVICES ARE TO REMAIN, CONTRACTOR MUST EXTEND EXISTING CIRCUITING WHERE NECESSARY TO

MAINTAIN CONTINUITY OF CIRCUIT.

6. COORDINATE WITH THE OWNER FOR DISPOSITION OF ELECTRICAL ITEMS TO BE DEMOLISHED. OWNER SHALL HAVE THE OPTION TO RETAIN REUSABLE ITEMS SUCH AS COVERPLATES, RECEPTACLES, LIGHT FIXTURES, PANELBOARDS, TRANSFORMERS, ETC.

NOT BEING USED IN THE FINISHED WORK. COORDINATE WITH THE OWNER PRIOR TO START OF DEMOLITION. PROPERLY AND

LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS BEING REMOVED.

7. COORDINATE EXACT AREAS, WALLS, CEILINGS, ETC. TO BE DEMOLISHED WITH ARCHITECTURAL, STRUCTURAL, PLUMBING AND

MECHANICAL DEMOLITION PLANS.

8. WHERE EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT ARE INDICATED TO BE DEMOLISHED, REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO SOURCE PANEL OR TO NEAREST JUNCTION BOX TO MAINTAIN CIRCUIT CONTINUITY OF DEVICES AND EQUIPMENT TO REMAIN. WHERE PANELS ARE TO REMAIN, TURN BREAKER TO "OFF" POSITION AND LABEL THE CIRCUIT AS

"SPARE" ON THE PANEL DIRECTORY.

9. ALL AREAS OUTSIDE THE SCOPE OF CONSTRUCTION ARE TO REMAIN ENERGIZED. COORDINATE PHASING WITH CONSTRUCTION MANAGER AND OWNER PRIOR TO DEMOLITION OF ANY ITEM WHICH MAY RESULT IN INTERRUPTION OF POWER.

10. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR EXTENT OF AREA REQUIRING DEMOLITION AND ADDITIONAL INFORMATION ON ELECTRICAL DEMOLITION WITHIN THAT AREA. DISCONNECT ELECTRICAL SERVICE TO ALL EQUIPMENT BEING REMOVED. DEMOLITION SHALL BE PHASED AS REQUIRED BY DIVISION 1, OR DIRECTED BY THE OWNER.

11. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED OR RENOVATED AREA. CAP BOTH

ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE CUT.

12. ELECTRICAL DEVICES CONCEALED BY STORAGE SHELVING, CASEWORK, FURNITURE, ETC., AND NOT NOTED ON THE DEMOLITION DRAWINGS ARE TO BE REMOVED AS REQUIRED, UNLESS SHOWN AS EXISTING TO REMAIN.

13. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF EQUIPMENT AND ELECTRICAL DEVICES, UNLESS OTHERWISE NOTED ON ARCHITECTURAL PLANS. REPAIRS ARE TO BE DONE TO LOGICAL EDGES OF SURFACES AFFECTED AND SHALL MATCH IMMEDIATELY ADJACENT AREAS IN CONSTRUCTION, MATERIAL, FIRE RATING, FINISH AND COLOR.

14. PROVIDE BLANK COVERPLATES WHERE DEVICES ARE BEING REMOVED FROM EXISTING WALLS TO REMAIN. MATCH COLOR OF

NEW ADJACENT DEVICE COVERPLATES.

15. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND OBTAIN

CLARIFICATIONS FROM ARCHITECT/ENGINEER IF NECESSARY.

16. COORDINATE ALL POWER INTERRUPTION WITH CONSTRUCTION MANAGER, OWNER, LANDLORD, AND UTILITY COMPANY (WHERE APPLICABLE) AND DO NOT INTERRUPT POWER WITHOUT WRITTEN PERMISSION. PROVIDE A MINIMUM OF ONE WEEK'S WRITTEN NOTIFICATION PRIOR TO WHEN POWER IS DESIRED TO BE INTERRUPTED. CONTRACTOR SHALL INVESTIGATE AND IDENTIFY ALL LOADS TO BE AFFECTED BY THE REQUESTED INTERRUPTION. CONTRACTOR SHALL SUBMIT WRITTEN SEQUENCE OF STEPS FOR EACH SHUTDOWN ALONG WITH THE ESTIMATED INTERRUPTION DURATIONS. MAKE ARRANGEMENTS TO MAINTAIN POWER TO ALL EXISTING NECESSARY LIGHTING, DEVICES AND EQUIPMENT AS NEEDED AND REQUESTED BY THE

OWNER PRIOR TO COMMENCEMENT OF WORK.

17. EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES THAT MAY BE CONNECTED TO

THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.

18. INFORMATION INDICATED IN THE DEMOLITION PORTION OF THE CONTRACT DRAWINGS IS DIAGRAMMATIC IN NATURE. FIELD VERIFY ELECTRICAL CIRCUIT HOMERUNS TO ALL ELECTRICAL ITEMS SCHEDULED TO BE DEMOLISHED AND PERFORM THE WORK

AS INTENDED AND DEPICTED ON THE DRAWINGS.

19. UPDATE ALL EXISTING ELECTRICAL EQUIPMENT NAMEPLATES AND DIRECTORIES AS NECESSARY TO REFLECT FINAL AS-BUILT

CONDITIONS AT THE END OF CONSTRUCTION.

20. STORE ITEMS INDICATED TO BE RETURNED TO THE OWNER IN A DRY, CLEAN AND PROTECTED AREA. NOTIFY OWNER WHEN

ITEMS ARE READY TO BE REMOVED.

21. COORDINATE ANY ALTERATION AND CHANGES TO THE ELECTRICAL SERVICE WITH THE LOCAL UTILITY COMPANY AND THE

OWNER PRIOR TO COMMENCEMENT OF WORK.

22. PROVIDE ANY NECESSARY REPROGRAMMING OF EXISTING BUILDING FIRE ALARM SYSTEMS TO DISABLE FIRE ALARM DEVICES THAT ARE BEING DISCONNECTED AND REMOVED, AND FOR ANY NEW DEVICES THAT ARE ADDED, AS PART OF BID PRICE.

23. ALL CONDUITS SERVING OTHER SPACES THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE DISRUPTION TO THESE OTHER SPACES. ENSURE THAT ALL CONDUITS, NEW OR EXISTING

WITHIN THE PROJECT AREA ARE PROPERLY SUPPORTED IN ACCORDANCE WITH THE NEC.

24. REMOVE ALL ABANDONED WIRING AND CONDUIT THAT IS WITHIN THE PROJECT AREA PRIOR TO THE END OF CONSTRUCTION.

COORDINATION

1. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.) WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL

REQUIRED.

2. THIS PROJECT REQUIRES COORDINATION DRAWINGS BY THE CONTRACTOR. PARTICIPATE IN THE COORDINATION DRAWING PREPARATION PROCESS AND PROVIDE ALL NECESSARY INFORMATION REQUIRED TO COORDINATE ALL TRADE INFORMATION.

3. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT OF WORK. AVOID INTERFERENCES WITH THE PROGRESS OF

OTHER DIVISIONS/TRADES.

4. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR DESIGN, TECHNOLOGY, STRUCTURAL, AND VENDOR EQUIPMENT DRAWINGS FOR RELATED INFORMATION AND ADDITIONAL INSTALLATION

REQUIREMENTS TO BE PERFORMED AS PART OF THE WORK.

5. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S

DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

6. CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND/OR SITE AFFECTED BY THIS WORK PRIOR TO SUBMITTING BID PRICE, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT MAY AFFECT EXECUTION OF THE WORK. SUBMISSION OF A BID PRICE SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT AND/OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED THAT COULD HAVE

BEEN REASONABLY OBSERVED WILL NOT BE RECOGNIZED.

7. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR SUCH SHALL BE INCLUDED IN THE BID PRICE. PROVIDE ADEQUATE WORK FORCE AND EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE REQUIRED IN ORDER TO ADHERE TO THE PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG

LEAD ITEMS DO NOT IMPACT THE PROJECT'S SCHEDULE OR PHASING.

8. ANY TEMPORARY INTERRUPTION OF POWER REQUIRED FOR THE SYSTEM TIE-IN OR SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN WRITING BY THE OWNER AND SCHEDULED IN ADVANCE.

9. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC. FROM DAMAGE OR EXCESSIVE NOISE THROUGHOUT THE DURATION OF THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR ANY LOSSES OR ANY DAMAGE RESULTING FROM THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL CONDITION TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO

PROCEEDING WITH REPAIRS.

10. COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM THE ARCHITECT/ENGINEER PRIOR TO BID. CONTRACTOR SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED TO RELOCATE OUTLET

BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S WORK.

LIGHTING

1. LIGHT FIXTURES SUPPORTED BY CEILING GRID SHALL BE SUPPORTED AS FOLLOWS: LIGHT FIXTURES WEIGHING LESS THAN 10 POUNDS SHALL HAVE 12-GAUGE HANGER WIRE CONNECTED FROM THE LIGHT FIXTURE TO THE STRUCTURE ABOVE. LIGHT FIXTURES WEIGHING 10 POUNDS OR MORE SHALL HAVE (2) 12-GAUGE HANGER WIRES ATTACHED AT OPPOSITE CORNERS OF

THE LIGHT FIXTURE TO THE STRUCTURE ABOVE.

2. COORDINATE EXACT LOCATIONS OF LIGHT FIXTURES IN LAY-IN AND GYPBOARD CEILINGS WITH ARCHITECTURAL REFLECTED CEILING PLANS, AND WALL MOUNTED EXTERIOR AND INTERIOR LIGHT FIXTURES WITH ARCHITECTURAL ELEVATIONS PRIOR TO INSTALLATION. WHERE THE QUANTITY OF LIGHTS DIFFERS BETWEEN THE ARCHITECTURAL RCP AND THE ELECTRICAL LIGHTING PLANS, PROVIDE THE HIGHEST QUANTITY OF FIXTURES IN THE BID PRICE. THE DISCREPANCY IN QUANTITY SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE HIGHEST QUANTITY SHALL BE CIRCUITED TO THE LOCAL ROOM OR AREA LIGHTING CIRCUITS AND LIGHTING CONTROL DEVICES, UNLESS OTHERWISE DIRECTED IN WRITING BY THE

ARCHITECT/ENGINEER.

3. VERIFY ACTUAL CEILING CONSTRUCTION TYPE AS DEFINED ON THE ARCHITECTURAL DRAWINGS AND FURNISH ALL LIGHT FIXTURES WITH THE CORRECT MOUNTING DEVICES WHETHER OR NOT SUCH VARIATIONS ARE INDICATED BY THE LIGHT FIXTURE CATALOG NUMBER. VERIFY THE DEPTH OF ALL RECESSED LIGHT FIXTURES WITH THE ARCHITECTURAL DRAWINGS PRIOR TO ORDERING LIGHT FIXTURES. ANY DISCREPANCIES THAT WOULD CAUSE THE RECESSED LIGHT FIXTURES NOT TO FIT

INTO CEILING SHALL BE REPORTED TO ARCHITECT/ENGINEER PRIOR TO ORDERING.

4. LIGHT FIXTURES RECESSED IN FIRE-RATED CEILINGS SHALL BE PROVIDED WITH APPROVED FIRE- RATED ENCLOSURE WITH A FIRE RATING EQUAL TO THAT OF THE CEILING. PROVIDE A MINIMUM OF 3" CLEARANCE FROM SIDES AND TOP OF RECESSED

LIGHT FIXTURES.

5. MODIFY ALL LIGHT FIXTURE CATALOG NUMBERS AS REQUIRED TO COORDINATE WITH THE LIGHTING BRANCH CIRCUIT VOLTAGES INDICATED. COORDINATE THE CATALOG NUMBERS WITH THE EXACT FIXTURE MOUNTING AND TRIM REQUIRED BY

THE CEILING IN WHICH EACH FIXTURE IS BEING INSTALLED.

6. ALL LIGHT FIXTURES SHALL BE PROVIDED COMPLETE WITH LAMPS, UNLESS OTHERWISE NOTED.

7. ALL EXIT LIGHTS, LIGHT FIXTURES INDICATED WITH UNSWITCHED CIRCUIT (NIGHTLIGHT N/L), EMERGENCY TWIN-HEAD FIXTURES WITH INTEGRAL BATTERY PACKS, AND BATTERY PACKS INTEGRAL TO LIGHT FIXTURES, SHALL BE WIRED AHEAD OF

ANY LOCAL SWITCHING OR LIGHTING CONTROLS.

8. PROVIDE UL WET LABEL OR IP67 RATED LIGHT FIXTURES FOR ALL FIXTURES LOCATED OUTSIDE OR IN PARKING GARAGES, IN

SHOWERS, OR OPEN STRUCTURES.

9. EXTERIOR LIGHTING BALLASTS/DRIVERS SHALL HAVE A MINMUM STARTING TEMPERATURE OF -40 DEGREE C, AND A NORMAL

AMBIENT OPERATING TEMPERATURE OF 40 DEGREE C.

10. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNS REQUIRED DURING THE PROJECT

CONSTRUCTION PHASE.

11. REFER TO LIGHT FIXTURE SCHEDULE FOR LIGHT FIXTURE TYPES, DESCRIPTIONS, CATALOG NUMBERS AND ADDITIONAL

INFORMATION PERTINENT TO THE LIGHT FIXTURE OR INSTALLATION THEREOF.

12. COORDINATE LIGHT FIXTURE TRIM TYPE AND FINISH COLOR WITH ARCHITECT PRIOR TO ORDERING.

13. EACH LIGHTING CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL.

14. WHERE THERE IS NO EMERGENCY GENERATOR/ LIFE SAFETY DISTRIBUTION BRANCH AVAILABLE, PROVIDE INTEGRAL BATTERY PACKS, RATED FOR A MINIMUM OF 90 MINUTES, FOR FIXTURES SHOWN WITH SOLID SHADING AND/OR WITH "E" AFTER

FIXTURE TAG, AND FOR ALL EXIT LIGHTS,OR UNLESS NOTED OTHERWISE.

15. ALL LIGHTING HAS BEEN DESIGNED IN COMPLIANCE WITH SECTION 405 OF THE FLORIDA ENERGY CONSERVATION CODE FOR LIGHTING POWER DENSITY, AUTOMATIC LIGHTING CONTROLS AND ALL ADDITIONAL REQUIREMENTS.

16. PROVIDE AS PART OF BID PRICE FOR THE SERVICES OF AN INDEPENDENT COMMISSIONING AGENT FOR THE LIGHTING SYSTEM FUNCTIONAL TESTING REQUIRED BY THE ENERGY CONSERVATION CODE, INCLUDING ALL REQUIRED REPORTS.

WHERE OCCUPANCY SENSORS, TIME SWITCHES, PROGRAMMABLE SCHEDULED LIGHTING CONTROLS, PHOTOSENSORS AND DAYLIGHTING CONTROLS ARE INSTALLED, THE SYSTEMS SHALL BE TESTED TO ENSURE THAT CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER WORKING CONDITION TO ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTRUCTIONS. CONDUCT THE FUNCTIONAL TESTS IN ACCORDANCE WITH THE ENERGY CONSERVATION CODE. PROVIDE COMISSIONING REPORT TO ENGINEER NOT LATER THAN 60 DAYS FROM THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY. DOCUMENTS CERTIFYING THAT THE INSTALLED LIGHTING CONTROLS MEET DOCUMENTED PERFORMANCE CRITERIA OF THE ENERGY CONSERVATION CODE ARE TO BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS FROM THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY.

17. CONTRACTOR TO HIRE THIRD PARTY NETWORK LIGHTING CONTROLS INTEGRATOR TO ENSURE PROPER FUNCTIONALITY OF

THE LIGHTING CONTROLS SYSTEM THAT HAS BEEN DESIGNED.

GENERAL REQUIREMENTS

1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP, METHODS AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS, BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL DIVISIONS AS A

WHOLE.

2. THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF CONSTRUCTION, METHODS, MATERIALS AND EQUIPMENT, OR EXACT LOCATIONS, ROUTING, ETC. THEY INDICATE THE RESULT TO BE ACHIEVED BY THE ASSEMBLAGE OF SEVERAL SYSTEMS FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DO NOT SCALE THE CONTRACT DOCUMENTS. COORDINATE EXACT EQUIPMENT LOCATIONS WITH THE ARCHITECTURAL, CIVIL AND STRUCTURAL CONTRACT DOCUMENTS, AS WELL AS FIELD CONDITIONS, APPROVED SHOP DRAWINGS AND WORK OF ALL OTHER DIVISIONS/TRADES.

3. THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES TO FURNISH AND INSTALL MATERIALS REQUIRED FOR

CORRECT INSTALLATION OF A COMPLETE SYSTEM, UNLESS SPECIFICALLY NOTED OTHERWISE

4. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN

APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY.

5. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE CONTRACT DOCUMENTS.

ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER, TO THE SATISFACTION OF THE

ARCHITECT/ENGINEER AND OWNER.

6. CARRY ALL INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FORTHE DURATION OF THIS

PROJECT.

7. GUARANTEE ALL MATERIALS AND WORKMANSHIP ARE FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT/ENGINEER AND OWNER, UNLESS NOTED OTHERWISE IN DIVISION 1. AT NO ADDITIONAL COSTS, PROVIDE THE CORRECTION OF ANY DEFECTS INCLUDING REPAIR OR REPLACEMENT.

8. INCLUDE ALL COSTS ASSOCIATED WITH PERMITS, LICENSES, FEES, INSPECTIONS, TESTING AND TEMPORARY POWER IN THE BID

PRICE, UNLESS NOTED OTHERWISE.

9. IF HAZARDOUS MATERIALS ARE ENCOUNTERED, COMPLY WITH ALL APPLICABLE RULES, REGULATIONS AND GUIDELINES CONCERNING REMOVAL, HANDLING, DISPOSAL AND PROTECTION AGAINST ENVIRONMENTAL EXPOSURE OR POLLUTION. PROVIDE

DOCUMENTATION OF SAID COMPLIANCE.

10. PROVIDE ELECTRONIC SUBMITTALS (PRODUCT DATA & SHOP DRAWINGS) FOR EACH MAJOR COMPONENT OF THE ELECTRICAL SYSTEM FOR REVIEW BY THE ARCHITECT/ENGINEER AND OWNER. MAJOR COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO, RACEWAYS, BOXES, WIRE AND CABLE, EQUIPMENT, DEVICES, LIGHT FIXTURES, SWITCHGEAR, PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, FIRE ALARM SYSTEM, ETC. ALL SUBMITTALLS ARE TO BE REVIEWED AND APPROVED BY THE CONTRACTOR FOR CONFORMANCE WITH THE PROJECT REQUIREMENTS PRIOR TO SUBMITTING TO THE ARCHITECT/ENGINEER.

ALLOW A MINIMUM OF TEN (10) BUSINESS DAYS FOR REVIEW BY ARCHITECT/ENGINEER, UNLESS NOTED OTHERWISE IN DIVISION

11. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS, AND SAID SUBSTITUTION IS ACCEPTED BY THE ARCHITECT/ENGINEER AND OWNER, THE CONTRACTOR SHALL MAKE ALL CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A COMPLETE AND OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS. WHERE THE CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO REQUEST

COMPENSATION FROM THE CONTRACTOR FOR SAID SERVICES.

12. MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD DOCUMENTS SHALL BE ISSUED TO THE ARCHITECT/ ENGINEER FOR REVIEW AND THEN SUBMITTED TO THE OWNER WITHIN 30 DAYS AFTER THE

DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.

13. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL ACCEPTANCE. THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME, PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED

SERVICE AGENCY.

14. INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES, REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH ALL APPLICABLE STATUTES REGARDING MERCURY-CONTAINING DEVICES, AND WITH ALL LOCAL, STATE AND FEDERAL APPLICABLE GUIDELINES AT THE TIME OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF ACCEPTED DISPOSAL.

RACEWAYS

1. FLEXIBLE METAL CONDUIT AND LIQUIDTIGHT FLEXIBLE METAL CONDUIT (FMC & LFMC) SHALL NOT BE USED IN LENGTHS THAT EXCEED 6'-0" UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS THE ARCHITECT/ENGINEER GRANTS WRITTEN

PERMISSION.

2. ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS, INCLUDING LOW VOLTAGE SYSTEMS, SHALL BE INSTALLED IN A COMPLETE

RACEWAY SYSTEM (CONDUIT) UNLESS SPECIFICALLY NOTED OTHERWISE.

3. THE USE OF ELECTRICAL NON-METALLIC TUBING (ENT) AND LIQUIDTIGHT FLEXIBLE NON-METALLIC CONDUIT (LFNC) ARE PROHIBITED UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS THE ARCHITECT/ENGINEER OR OWNER GRANTS

WRITTEN PERMISSION.

4. CONNECTIONS TO TRANSFORMERS, AHU'S, AND PUMPS SHALL BE WITH LIGUIDTIGHT, FLEXIBLE METAL CONDUIT.

5. NO PVC CONDUIT MAY BE USED INSIDE OF BUILDING UNLESS ROUTED UNDERGROUND, AND UNLESS NOTED OTHERWISE.

6. ALL CONDUIT TERMINATIONS AT TERMINAL BOARDS ARE TO HAVE GROUNDING BUSHINGS AT CONDUIT ENDS.

7. ALL CONDUITS ARE TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E., EXPOSED CEILINGS, BUILDING EXTERIOR WALL RUNS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR IN WALLS AND MILLWORK. WHERE EXISTING CONDITIONS DICTATE THAT CONDUITS CANNOT BE CONCEALED, NOTIFY ARCHITECT/ENGINEER PRIOR TO INSTALLING

CONDUIT FOR RESOLUTION TO ROUTING.

8. SEAL ALL PENETRATIONS AND OPENINGS MADE DURING EXECUTION OF WORK IN FIRE-RATED AND SMOKE-RATED WALLS.

WALLS SHALL BE SEALED WITH UL-APPROVED PRODUCT WITH THE SAME OR GREATER RATING OF WALL PENETRATED.

9. PROVIDE ALL PENETRATIONS THROUGH FLOORS, WALLS, CEILINGS AND ROOFS WHERE REQUIRED. COORDINATE LOCATIONS AND SIZES WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS, FIELD CONDITIONS AND WORK OF ALL OTHER

DIVISIONS/TRADES. ALL OPENINGS ARE TO BE SEALED WATERTIGHT.

10. PANEL SCHEDULES AND FLOOR PLANS MAY INDICATE DEDICATED HOMERUNS FOR EACH BRANCH CIRCUIT. BRANCH CIRCUITS MAY BE GROUPED IN A COMMON HOMERUN WHERE THE HOMERUN DOES NOT EXCEED 3 PHASE CONDUCTORS, 3 NEUTRAL CONDUCTORS, AND 1 EQUIPMENT GROUND. THE HOMERUN RACEWAY SIZE AND CONDUCTOR SIZE SHALL BE INCREASED AS NECESSARY TO COMPLY WITH THE NEC FOR 40% MAXIMUM FILL AND DERATING REQUIREMENTS.

11. PROVIDE SEAL OFF FITTINGS, APPROVED FOR SUCH USE, WHERE RACEWAYS PENETRATE BETWEEN A DRY, CONDITIONED ENVIRONMENT AND THE EXTERIOR OR OTHER WET ENVIRONMENTS AND ADDITIONAL AREAS WHERE CONDUITS PASS FROM

WARM TO COLD LOCATIONS SUCH AS WALK-IN COOLERS OR FREEZERS, BOILER ROOMS, ETC.

12. PROVIDE POLYOLEFIN JET-LINE #232 (NYLON PULL STRING) IN EACH EMPTY CONDUIT WITH ENGRAVED METAL TAG

INDICATING CONDUIT DESIGNATION.

13. ALL HOMERUNS SHALL BE IN 3/4" RACEWAY MINIMUM. 1/2" RACEWAY IS ACCEPTABLE FOR A SINGLE CIRCUIT FROM THE

HOMERUN TO REMAINING DEVICES.

14. CONTRACTOR MAY USE EITHER SET SCREW OR COMPRESSION FITTINGS ONLY FOR EMT CONDUIT.

15. RACEWAYS SHALL NOT BE PERMITTED TO BE INSTALLED WITHIN SLABS.

WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND SPECIFICATIONS, WHERE APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED

ELECTRICAL DEMOLITION NOTES

IDENTIFICATION

1. PROVIDE TYPED PANEL DIRECTORIES FOR ALL NEW PANELBOARDS, AND EXISTING PANELBOARDS AFFECTED BY THIS PROJECT.

DIRECTORIES SHALL REFLECT PROJECT AS- BUILT CONDITIONS FOR ALL BRANCH CIRCUITS. DIRECTORIES SHALL INCLUDE WHERE EACH PANEL IS FED FROM. ADDITIONALLY, EACH BRANCH CIRCUIT LOAD DESCRIPTION SHALL INCLUDE THE ROOM NUMBER(S) FOR EACH LOAD (I.E., RECEPTACLES-RMS 501,503). ROOM NUMBERS SHALL BE BASED ON ACTUAL ROOM SIGNAGE INSTALLED IN FIELD. COORDINATE EXACT ROOM NUMBERS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO COMPLETION OF PANEL

DIRECTORIES.

2. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON EACH SWITCHBOARD, SWITCHGEAR, DISTRIBUTION PANEL, PANELBOARD, MOTOR CONTROL CENTER, SAFETY SWITCH, ENCLOSED CIRCUIT BREAKER, CABINET, STEP-DOWN TRANSFORMER, TRANSFER

SWITCH, ETC., AND ANY OTHER MAJOR COMPONENT OF THE ELECTRICAL SYSTEM.

3. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS FOR EACH DISTRIBUTION BREAKER OR BRANCH CIRCUIT BREAKER IN SWITCHGEAR, SWITCHBOARDS, MOTOR CONTROL CENTERS AND OTHER DISTRIBUTION EQUIPMENT. NAME TAG SHALL INCLUDE

LOAD DESCRIPTION AND ROOM NUMBER FOR EACH LOAD.

4. ARC FLASH DANGER/WARNING LABELS SHALL BE APPLIED TO SWITCHBOARD, PANELBOARDS, AND EQUIPMENT CONTROLLERS PER

NEC.

5. PROVIDE LABELS ON THE INSIDE OF EACH DEVICE COVERPLATE, IDENTIFYING THE PANEL(S)/ CIRCUIT NUMBER(S) DEVICE IS

CONNECTED TO.

6. PROVIDE NEATLY, HANDWRITTEN IDENTIFICATION ON THE EXTERIOR COVER OF ALL JUNCTION BOXES, PULLBOXES AND

WIREWAYS, IDENTIFYING THE PANEL(S)/ CIRCUIT NUMBER(S) CONTAINED WITHIN.

7. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BUILDING STATING THAT THE MAIN SERVICE

DISCONNECTING MEANS IS LOCATED INSIDE.

8. PROVIDE A PERMANENT LABEL ON ALL PANELBOARDS, SWITCHBOARDS, SWITCHGEAR, MOTOR CONTROL CENTERS AND DISTRIBUTION PANELS STATING "DO NOT WORK ON EQUIPMENT WHILE ENERGIZED. LOCK- OUT TAG-OUT REQUIRED".

9. PROVIDE REQUIRED IDENTIFICATION PER ANSI STANDARDS, NEC REQUIREMENTS, AND OWNER'S PUBLISHED DESIGN STANDARDS

WHERE APPLICABLE.

APPLICABLE CODES

APPLICABLE CODES:

WORK UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE AND IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING CODES AND STANDARDS INCLUDING THE REGULATIONS OF GOVERNING LOCAL, STATE, COUNTY AND OTHER

APPLICABLE CODES. REFER TO SPECIFICATIONS FOR ADDITIONAL CODE REQUIREMENTS:

BUILDING CODES:

• FLORIDA BUILDING CODE, 8TH EDITION (2023)

• FLORIDA ENERGY CONSERVATION CODE, 8TH EDITION (2023)

• FLORIDA FIRE PREVENTION CODE, 8TH EDITION (2023)

ADDITIONAL CODES, STANDARDS, AND REQUIREMENTS

1. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).

2. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).

3. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA).

4. REQUIREMENTS OF LOCAL POWER COMPANY.

5. THE AMERICANS WITH DISABILITIES ACT (ADA).

6. OWNER'S PUBLISHED DESIGN STANDARDS.

ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LAB, AS DEFINED BY OSHA. WHERE NO LABELING OR LISTING SERVICE IS AVAILABLE FOR CERTAIN TYPES OF EQUIPMENT, TEST DATA SHALL BE SUBMITTED TO VALIDATE THAT EQUIPMENT MEETS OF EXCEEDS AVAILABLE STANDARDS.

NATIONAL FIRE PROTECTION (NFPA) STANDARDS:

• NFPA 70, 2020 EDITION, NATIONAL ELECTRICAL CODE®.

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :5

A

M

ELECTRICAL

GENERAL

NOTES

E001

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

A

EMERGENCY TWIN-HEAD LIGHT WITH INTEGRAL BATTERY PACK, WALL MOUNTED

TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF TRACK HEADS)

EXTERIOR POLE-MOUNTED AREA LIGHT FIXTURE, ARMS AS INDICATED ON DRAWINGS

EXIT LIGHT, WALL MOUNTED

EXIT LIGHT, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS INDICATED;

SHADED QUADRANT INDICATES FACE(S) OF FIXTURE

CEILING WALLWASHER, ACCENT LIGHT, LANDSCAPING TREE ACCENT LIGHT, FACADE LIGHT

RECESSED, PENDANT OR SURFACE CEILING

FIXTURE RECESSED, PENDANT OR SURFACE CEILING

DIAGONAL HALF SHADING INDICATE FIXTURE CONNECTED TO CRITICAL CIRCUIT OR

PROVIDED WITH INTEGRAL EMERGENCY BATTERY PACK; "E" AFTER FIXTURE TYPE TAG

INDICATES INTEGRAL BATTERY PACK UNLESS OTHERWISE NOTED ON LIGHT FIXTURE

SCHEDULE (TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)

FULL SHADING INDICATE FIXTURE CONNECTED TO LIFE SAFETY CIRCUIT.

FIXTURE, RECESSED, PENDANT OR SURFACE CEILING

STRIP FIXTURE

FIXTURE, WALL MOUNTED

FIXTURE TYPE

LOWER CASE LETTER INDICATES CONTROLLING SWITCH

a

CIRCUIT NUMBER

LIGHTING

WALL MOUNTED

LINEAR RECESSED, PENDANT OR SURFACE CEILING

ZX-X

LIGHTING CONTROL ZONE NUMBER

EXTERIOR PEDESTRIAN SIDEWALK BOLLARD OR POST-TOP LIGHT FIXTURE

AB AB AB

AB AB AB

ABABAB AB

AB

AB

AB

AB

AB

AB

X1X1

X1

X1

EXD

ABAB AB AB

AB ABAB

AB ABAB

AB AB

EXD

AB ABAB

AB ABAB

AB ABAB

AB ABAB

K K

KK

K K

X1X1

AB

AB

AB

AB

AB

AB

AB

AB

AB

X1

X1

X1

X1

AY AY AY AY

AY AY AY AY

Y1

Y1

X1

X1

UP

DOWN

UP

DOWN

DN

CC

CC

CC

CC

CC

CC

CC

CC

CC

4HP1B-1

32 32 32 4HP1A-32

1 1

1 11

1 11

1 11

CC CC

CC

CC

CC

CC

CC

3 3

3 3

3 3 3

3 3 3

3 3 3

3 3

3 3 3

12 4HP1A-12

4HP1A-10

4LB1P-14

Y1

X1

UPS-3

14 14

H H H H H H H H H H H H

UPS-5

14 14

H H

H H

H H

H H

H H

H H

UPS-5

14 14

14 14

UPS-8

H H H H H H H H H H H H

5 5 5

14 5

H H

H H H H H H H H H HUPS-5

14 14

5 5

5 5

G

G G

G G

G G

G

UPS-4

G

G G

G G

G

14 4

14 4 14 4

14 4

G G

G G

14 4

14 4 14 4

G G

G G

G

14UPS-7

G G

G G 7

G G

G G

G G

G G

G

CC

Y1

4HP1A-13

323232

STAGE MANAGER CONTROL STATIONS

REPLACE EXISTING ORCESTRA PIT AND STAGE EDGE LIGHTING. CONTRACTOR

TO REMOVE THE EXISTING FIXTURES AND MODIFY THE EXISTING CHANNEL TO

ACCEPT THE NEW LIGHTING. PROVIDE NEW POWER SUPPLY AND TIE TO

EXISTING CONTROLS.

4HP1A-13

THEATRE LOBBY

04. 101

VEST

4. 102B

JANITOR CLOSET

4. 121A

AUDITORIUM SEATING

4. 102

STAGE

04. 103

STAIRS

04. 104

VEST

4. 102A

STAIRS

4. 130

VEST

4. 103A

VEST

4. 103B

ADD ALTERNATE #1

REPLACE ALL SCONCE FIXTURES

WITH NEW IN SAME LOCATION.

ADD ALTERNATE #1

REPLACE ALL SCONCE FIXTURES

WITH NEW IN SAME LOCATION.

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

RE-CIRCUIT FIXTURE POWER TO BE AHEAD OF EXISTING LINE VOLTAGE CONTROLS VIA

NEAREST HOME RUN JUNCTION BOX. CONTRACTOR TO TRACE CIRCUIT TO DETERMINE

NEAREST CONNECTION POINT. EXTEND NEW WIRING AND CONDUIT AS NEEDED TO

ACCOMMODATE SCOPE. WIRE AND CONDUIT TO BE #12 AND 3/4" C. REFER TO PROVIDED

AS-BUILTS FOR ADDITIONAL INFORMATION.

EXISTING CONTROLS SHOULD BE LOCAL, CONTRACTOR TO VERIFY. RE-CIRCUIT

FIXTURES TO BE AHEAD OF EXISTING CONTROLS VIA NEAREST HOME RUN JUNCTION

BOX. EXTEND NEW WIRING AND CONDUIT AS NEEDED TO ACCOMMODATE SCOPE. WIRE

AND CONDUIT TO BE #12 AND 3/4" C. REFER TO PROVIDED AS-BUILTS FOR ADDITIONAL

INFORMATION.

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :0

A

M

LIGHTING

PLAN -

LEVEL 1

E100

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

1/8" = 1'-0"

LEVEL 1 FLOOR PLAN

GENERAL NOTES:

1. ALL SCREENED ITEMS ARE EXISTING TO REMAIN AND SHOWN FOR INFORMATIONAL PURPOSES ONLY.

2. ALL LIGHTING FIXTURES SHOWN ARE REPLACING EXISTING FIXTURES. DISCONNECT AND RECONNECT

FIXTURES TO EXISTING CIRCUITS AND CONTROLS, U.O.N.

3. OWNER HAS FIRST RIGHT OF REFUSAL FOR DEMOLISHED LIGHTING FIXTURES.

4. COORDINATE WITH OWNER FOR SCHEDULED ACCESS AND WORK TIMES.

J J

Y1 Y1

UP

DOWN

Y1

Y1

UP

DOWN

Y1

UP

Y1

Y1

AB AB AB AB

ABABABAB

AB AB AB AB

AB AB

AB AB

AB AB

AX AX

Z Z Z

A

A

A

BO

4LP2B-32,34

23 23 4LP3A-23

8a8a

4HP2A-8b

4HP2A-1

4HP1A-12

TIE

4HP1A-10

TIE

UTILIZE EXISTING BATTENS TO MOUNT NEW WORK

LIGHTS INDICATED. PROVIDE NECESSARY

MOUNTING HARDWARE FOR SUPPORT (TYP OF 2).

F2

F2

F2

F2 F2

F2

F2

F2

Y1

BOOTH ACCESS

4. 214

CONTROL BOOTH A

4. 216

MECH. ACCESS

4. 215

STAIRS

4. 231

BOX BOOM ROOM

4. 231A

BOX BOOM ROOM

4. 230A

STAIRS

4. 230

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

PROVIDE CONNECTION TO 3 PIN EDISON CONNECTOR

FOR POWERING ALL FIXTURES ON BATTON. MOUNT

CONNECTION/DEVICE TO BATTON UTILIZING PIPE

CLAMP STYLE INSTALLATION. (TYP OF 2)

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :0

A

M

LIGHTING

PLAN -

LEVEL 2

E101

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

N.T.S.

LEVEL 2 FLOOR PLAN

GENERAL NOTES:

1. ALL SCREENED ITEMS ARE EXISTING TO REMAIN AND SHOWN FOR INFORMATIONAL PURPOSES ONLY.

2. ALL LIGHTING FIXTURES SHOWN ARE REPLACING EXISTING FIXTURES. DISCONNECT AND RECONNECT

FIXTURES TO EXISTING CIRCUITS AND CONTROLS, U.O.N.

3. OWNER HAS FIRST RIGHT OF REFUSAL FOR DEMOLISHED LIGHTING FIXTURES.

T

UP

AX

BO

BD BD BD

BD

BD

BD

BD

BDBDBD

BD BD BD

BD

BD

BD

BD

BD

BD

BD

BD

BDBDBD

BD BD BD

BD

BD

BD

BD

BDBDBD

BD BD BD

EE EE EE

EE

EE

EE

EE EE

EE

EEEEEE

EE EE EE

EE EE

EE

EE

EE

EEEEEE

EE

EE

EE

EE

EE

EE

Y1 Y1

UP

DOWN

AX

Y1

Y1

UP

DOWN

AX

F1

F1

AX AX

F1 F1

F1

F1

F1

F1

F1

Z Z Z

4HP3A

4LP3A 4LP3B

T43A

DNP RELAY

4LP3C

4LP3A-2121 21

4HP3A-7 7

4LP3A-2

4LP3A-6

4HP3A-7

4HP3A-9

4HP3A-11

4HP3A-7,9,11 VIA COTACTORS: 'a','b','c' a b c a c b a a b c a c b a c c

4HP3A-13,15,17 VIA COTACTORS: 'a','b','c' a b

15b a c a a c 17

15c a 13 a b c a b

19a

21b

19a

21b b

EE

4HP3A-19,21,23 VIA COTACTORS: 'a','b','c'

M M M

M M

M M

M M M

N d

1 1 1 cc c c c c c c cc

4HP3A-1,3,5

4HP1A-10 TIE

4HP1A-12 TIE

DR1 DR2 DR3 DR4

UPS-4

UPS-4

UPS-4

UPS-2

UPS-2

UPS-2

CONTACTOR "A"

CONTACTOR "B"

CONTACTOR "C"

DR1

DR2

DR3

EXISTING FIXTURES TO REMAINNEW FIXTURES TO BE PROVIDED

AND SUSPENDED BELOW

EXISTING CHILLED WATER

PIPING.

a

FOLLOW SPOT BOOTH

4. 314

Room

4. 315

STAIRS

4. 331

ELECTRICAL DIMMER ROOM

4. 300A

MECH. ACCESS

4. 300

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

CONTACTORS ARE LOCATED

WITHIN THE WIRE WAY LOCATED

WITHIN THE ELECTRICAL ROOM

CONTACTOR "UPS"

IQ12 - 1

IQ12 - 1

IQ12 - 1

IQ12 - 1

IQ12 - 1

IQ12 - 1

IQ12 - 3

IQ12 - 3

IQ12 - 3

IQ12 - 3

IQ12 - 3

IQ12 - 3 IQ12 - 5

IQ12 - 5

IQ12 - 5

IQ12 - 5

IQ12 - 5

IQ12 - 5

IQ12 - 7

IQ12 - 7

IQ12 - 7

IQ12 - 7

IQ12 - 7

IQ12 - 11

IQ12 - 11

IQ12 - 11

IQ12 - 11

IQ12 - 9

IQ12 - 9

IQ12 - 9

HOUSE LIGHTING FIXTURE "EE" CIRCUITING SHALL BE REDONE TO REFLECT THE

UPDATED IQ12 PANEL CIRCUITING INDICATED. THE EXISTING CIRCUITS SHALL BE RE-

WIRED WITHIN THE EXISTING WIRE WAY LOCATED WITHIN THE EXISTING ELECTRICAL

ROOM. THE UPS CIRCUITS FOR THESE FIXTURES SHALL REMAIN AS IS.

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :0

A

M

LIGHTING

PLAN -

LEVEL 3

E102

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

1/8" = 1'-0"1

LEVEL 3 FLOOR PLAN

GENERAL NOTES:

1. ALL SCREENED ITEMS ARE EXISTING TO REMAIN AND SHOWN FOR INFORMATIONAL PURPOSES ONLY.

2. ALL LIGHTING FIXTURES SHOWN ARE REPLACING EXISTING FIXTURES. DISCONNECT AND RECONNECT

FIXTURES TO EXISTING CIRCUITS AND CONTROLS, U.O.N.

3. OWNER HAS FIRST RIGHT OF REFUSAL FOR DEMOLISHED LIGHTING FIXTURES.

J J

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

Y1

Y1

UP

DOWN

Y1 Y1

UP

DOWN

X1

Y

X

X

AX

AX

X

DMX Receptacle DMX Receptacle

4HP3A-44

12 - TIE

4HP1A-10 - TIE 10 - TIE

4LP3A-17

4LP3A-19

4HP1A-12 TIE

STAIR

4. 431

STAIRS

4. 430

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

ADD ALTERNATE #2

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

X1

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :0

A

M

LIGHTING

PLAN -

LEVEL 4

E103

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

N.T.S.

LEVEL 4 FLOOR PLAN -

CATWALKS

GENERAL NOTES:

1. ALL SCREENED ITEMS ARE EXISTING TO REMAIN AND SHOWN FOR INFORMATIONAL PURPOSES ONLY.

2. ALL LIGHTING FIXTURES SHOWN ARE REPLACING EXISTING FIXTURES. DISCONNECT AND RECONNECT

FIXTURES TO EXISTING CIRCUITS AND CONTROLS, U.O.N.

3. OWNER HAS FIRST RIGHT OF REFUSAL FOR DEMOLISHED LIGHTING FIXTURES.

AX

AX

4HP3A-4

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :1

A

M

LIGHTING

PLAN -

LEVEL 5

E104

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

1/8" = 1'-0"

LEVEL 5 FLOOR PLAN -

CATWALKS

GENERAL NOTES:

1. ALL SCREENED ITEMS ARE EXISTING TO REMAIN AND SHOWN FOR INFORMATIONAL PURPOSES ONLY.

2. ALL LIGHTING FIXTURES SHOWN ARE REPLACING EXISTING FIXTURES. DISCONNECT AND RECONNECT

FIXTURES TO EXISTING CIRCUITS AND CONTROLS, U.O.N.

3. OWNER HAS FIRST RIGHT OF REFUSAL FOR DEMOLISHED LIGHTING FIXTURES.

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

AX

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

4HP3A-44

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :1

A

M

LIGHTING

PLAN -

LEVEL 6

E105

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

1/8" = 1'-0"

LEVEL 6 FLOOR PLAN -

PLATFORM

GENERAL NOTES:

1. ALL SCREENED ITEMS ARE EXISTING TO REMAIN AND SHOWN FOR INFORMATIONAL PURPOSES ONLY.

2. ALL LIGHTING FIXTURES SHOWN ARE REPLACING EXISTING FIXTURES. DISCONNECT AND RECONNECT

FIXTURES TO EXISTING CIRCUITS AND CONTROLS, U.O.N.

3. OWNER HAS FIRST RIGHT OF REFUSAL FOR DEMOLISHED LIGHTING FIXTURES.

DOWN

UP

DOWNY1

Y1

Y1

Y1 Y1 Y1 Y1

EX

Y2

Y2

Y2

Y2

Y2

Y2

Y2

Y1Y1

ADD ALTERNATE #3

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

ADD ALTERNATE #3

REPLACE EXISTING STAIRWELL LIGHTING WITH NEW IN PLACE ( "Y1" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

ADD ALTERNATE #4

REPLACE EXISTING PIT LIGHTING WITH NEW IN PLACE ( "Y2" FIXTURES).

EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

ADD ALTERNATE #4

REPLACE EXISTING CONTROL ROOM LIGHTING WITH NEW IN PLACE ( "Y1"

FIXTURES). EXISTING CIRCUITNG, WIRING, ETC TO BE REUSED.

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida License #65501

4890 W Kennedy Blvd, Suite 250 Tampa, FL 33609 P 813.637.0110 www.tlc-engineers.com

© Copyright 2022 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

724096

PERMIT DOCUMENTS

ISSUE DATE: 03/06/2025

C

U s e rs

\m a tt h e w

.d ra k e \D o c u m e n ts

\7 M

E P

R m a tt h e w

.d ra k e tl c -e n g .c o m

.r v t

/6

/2

:2 :1

A

M

LIGHTING

PLAN - PIT

LEVEL

E106

Gibbs HS Auditorium

Lighting Replacement

850 34th St S, St.

Petersburg, FL 33711

1/8" = 1'-0"1

PIT LEVEL FLOOR PLAN

GENERAL NOTES:

1. ALL SCREENED ITEMS ARE EXISTING TO REMAIN AND SHOWN FOR INFORMATIONAL PURPOSES ONLY.

2. ALL LIGHTING FIXTURES SHOWN ARE REPLACING EXISTING FIXTURES. DISCONNECT AND RECONNECT

FIXTURES TO EXISTING CIRCUITS AND CONTROLS, U.O.N.

3. OWNER HAS FIRST RIGHT OF REFUSAL FOR DEMOLISHED LIGHTING FIXTURES.

OSOS

OSOS

UP

DOWN

UP

DOWN

DN

MODIFY EXISTING STAGE

MANAGER CONTROLS STATION AS

INDICATED IN CONTROLS DETAILS

IF ADD ALTERNATE #2 IS ACCEPTED, USE EXISTING CONDUIT

INFRASTRUCTURE TO PULL NEW CONTROL WIRING TO NEW

WALL SCONCES. OTHERWISE, PULL NEW 600V RATED 0-10V

CONTROL WIRES TO THIS JUNCTION BOX AND PROVIDE

ON/OFF CONTROL PACK TO ALLOW FOR CONTROL FROM

NETWORK CONTROLS VIA NEW 0-10V CONTROLLER. PROVIDE

BLANK OUT COVER PLATE FOR JUNCTION BOX.

EPS

EPS

PORTABLE PARADIGM TOUCH SCREEN

NORTH ALCOVE 0-10V ZONE 7

REPLACE OLD STRAND CONTROL

UNIT WITH NEW MULTI SCEEN DIGITAL

TOUCH SCREEN (TYP)

NORTH ALCOVE 0-10V ZONE 7

REPLACE OLD STRAND CONTROL

UNIT WITH NEW MULTI SCEEN DIGITAL

TOUCH SCREEN

NORTH ALCOVE 0-10V ZONE 8NORTH ALCOVE 0-10V ZONE 8

WALL SCONCE 0-10V ZONE 9. IF ALTERNATE #2 IS

EXECUTED, INLCUDE EXTENDING 600V RATED 0-10V

CONTROL WIRING FROM NEW CONTROLLER TO NEW

SCONCE FIXTURES VIA EXISTING RACEWAYS.

OTHERWISE, PROVIDE 600V RATED 0-10V CONTROL

WIRES TO NEW ON/OFF ONLY CONTROL PACK.

WALL SCONCE 0-10V ZONE 10. IF ALTERNATE #2 IS

EXECUTED, INLCUDE EXTENDING 600V RATED 0-10V

CONTROL WIRING FROM NEW CONTROLLER TO NEW

SCONCE FIXTURES VIA EXISTING RACEWAYS.

OTHERWISE, PROVIDE 600V RATED 0-10V CONTROL

WIRES TO NEW ON/OFF ONLY CONTROL PACK.

IF ADD ALTERNATE #2 IS ACCEPTED, USE EXISTING CONDUIT

INFRASTRUCTURE TO PULL NEW CONTROL WIRING TO NEW

WALL SCONCES. OTHERWISE, PULL NEW 600V RATED 0-10V

CONTROL WIRES TO THIS JUNCTION BOX AND PROVIDE

ON/OFF CONTROL PACK TO ALLOW FOR CONTROL FROM

NETWORK CONTROLS VIA NEW 0-10V CONTROLLER. PROVIDE

BLANK OUT COVER PLATE FOR JUNCTION BOX.

A

EF F L

O

SE

SI

R

AN

O

L

I

NE

D IN

O P

R STATE OF R

E

E

No. 65501

LICENSE

G

L

DLA

N O

R

SLIE O'BR

IE

N

Ronald Leslie O'Brien, P.E.

Florida…