P8540243Dwgs_37-49.pdf

PDF 7 MB Posted

Attached to
Repair Waterfront at USCG Sector Long Island Sound
Solicitation number
70Z0G119BPRV07400
Issued by

About this file

Drawings

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10/12/18 FINAL SUBMISSION

N

PANELBOARD:

PANEL B (EXISTING)

VOLTAGE: 208/120V BUS RATING (A): 225A ENCLOSURE: NEMA 3R

PHASE: 3 MAIN OC DEVICE: 225A MAIN BREAKER MOUNTING: SURFACE

WIRE: 4+GND INTERRUPTING RATING (KAIC): EXISTING LOCATION: MARINA ENTRANCE

NEUTRAL: YES SERVICE ENTRANCE LABEL: NO

CKT NO. DESCRIPTION

CONNECTED LOAD (VA)

OCP OCP

CONNECTED LOAD (VA)

DESCRIPTION CKT NO.

LTS REC MTR MISC AMPS P AMPS P LTS REC MTR MISC

2 FINGER PIER 1 INNER

SHORE TIE

100 2

A 40 2

SPARE 1

4 B 3

6 FINGER PIER 1 OUTER

SHORE TIE

100 2

C 20 2

UNLEADED FUEL PUMP

8 A 1248 7

10 FINGER PIER 2 INNER

SHORE TIE

100 2

B 20 2

DIESEL FUEL PUMP

12 C 1248 11

14 FINGER PIER 2 OUTER

SHORE TIE

100 2

A 15 2

SPARE 13

16 B 15

18 FINGER PIER 3 INNER

SHORE TIE

100 2

C 60 1 1200 CENTER PIER LIGHTS 17

20 A 20 1 1200 CENTER FINGER PIER LIGHTS 19

FINGER PIER 3 OUTER

SHORE TIE

100 2

B 30 1 SPARE 21

24 C 20 1 1200 OUTBOARD FINGER PIER

LIGHTS 23

SPARE 100 2

A 20 1 1800 BUSL FINSGER PIER LIGHTS 25

28 B 20 1 360 LIGHTING CONTACTOR 27

SPARE 100 2

C 20 1 1440 UNLEADED FUEL PUMP 29

32 A 20 1

EAST DOCK FINGER PIER REC(3) 31

34 FINGER PIER 1 GFM

20 1 B 20 1

WEST DOCK FINGER PIER1

REC(4) 33

36 FINGER PIER 2 GFM 600 20 1 C 20 1 240 EMERGENCY FUEL STOP 35

38 OMNTEC

15 1 A 20 1

WEST DOCK FINGER PIER2

REC(4) 37

40 FINGER PIER 3 GFM

20 1 B 20 1

WEST DOCK FINGER

PIER3REC(3) 39

42 WEST FINGER PIER 3 GFD 600 20 1 C 20 1 120 MODHOPPER 41

QS

LTS REC MTR MISC SPARE TOTAL NOTES: PROVIDE BREAKERS AS

REQUIRED

CONNECTED LOAD (KVA) 5.4 57.6 6.4 11.4 --- 80.8 208 LINE-TO-LINE VOLTS

DEMAND FACTOR 1.25 0.90 1.00 1.00 --- --- 225 CONNECTED AMPS

DESIGN LOAD (KVA) 6.8 51.8 6.4 11.4 --- 76.4 212 DESIGN AMPS

PANELBOARD:

PANEL A (EXISTING)

VOLTAGE: 480/277 BUS RATING (A): 250A ENCLOSURE: NEMA 3R

PHASE: 3 MAIN OC DEVICE: 225A MAIN BREAKER MOUNTING: SURFACE

WIRE: 4+GND INTERRUPTING RATING (KAIC): EXISTING LOCATION: MARINA ENTRANCE

NEUTRAL: YES SERVICE ENTRANCE LABEL: NO

CKT NO. DESCRIPTION

CONNECTED LOAD (VA)

OCP OCP

CONNECTED LOAD (VA)

DESCRIPTION CKT NO.

LTS REC MTR MISC AMPS P AMPS P LTS REC MTR MISC

120V SERVICE PANEL

14400

90 3

A

60 3

CGC BOLLARD SHOCK TIE

3 14400 B 9600 4

5 14400 C 9600 6

BOLLARD SLBA COMPRESSOR

16000

100 3

A 15 2

BOLLARD PIER LIGHTING

9 16000 B 2400 10

11 16000 C 15 2

PARKING LOT LIGHTING

SPARE (OFF) 60 2

A 2400 14

15 B 30 1 4155 4 BANK (FUEL CONTACTOR) 16

17 277V PHOTOCELL/PIER LIGHTS 2770 15 1 C

15 2 SPARE (OFF)

19 SPACE - - A 20

21 SPACE - - B - SPACE 22

23 SPACE - C - SPACE 24

LOAD SUMMARY

LTS REC MTR MISC SPARE TOTAL NOTES: PROVIDE BREAKERS AS

REQUIRED

CONNECTED LOAD (KVA) 12.4 0.0 48.0 76.2 --- 136.5 480 LINE-TO-LINE VOLTS

DEMAND FACTOR 1.25 1.00 1.00 1.00 --- --- 164 CONNECTED AMPS

DESIGN LOAD (KVA) 15.5 0.0 48.0 76.2 --- 139.6 168 DESIGN AMPS

File details come from the government source that posted it.