STATEMENT OF WORK
FOR
Replace Coast Guard Computer Room AC
Units
Juneau, AK
***US COAST GUARD, JUNEAU, AK ***
[2]
1.0 PROJECT SUMMARY
This project will replace four Computer Room Air Condition (CRAC) units owned by the US Coast Guard and located on the 6th floor in the Hurff Ackerman Saunders
Federal Building in Juneau, AK. The Federal Building is owned and managed by the
General Services Administration (GSA). The four units service the Coast Guard
District 17 (D17) spaces primarily in Room 611 and Coast Guard Sector Juneau spaces primarily in Room 672 with two CRAC units per space.
The D17 spaces are approximately 2230 square feet in size. It consists of a conference room, telecom room, server room, and other offices and storage. These rooms are situated on a 12” high raised floor with an 8’ high drop ceiling. This space is served by two Liebert Challenger 3000 5-Ton R-22 AC units located in Mechanical Room 613
(CRAC 1 & CRAC 2). Ventilation to the space is provided by a Fan Coil Unit #6.1 that supplies the ventilation air to the return air in the mechanical room. The CRAC units for this space are downflow with a short radius duct elbow mounted to the bottom of each of the units that supply air to the floor in the conference room. The noise from these units is very loud in the conference room and upon investigation we confirmed that the sound boots that are shown in the 2007 design drawings were not installed on the supply air ducts. It appears that they were not installed due to interferences with the raised floor supports. Installation will include the installation of sound boots, and any needed modifications to the raised floor supports to accommodate this ductwork.
The Sector Juneau spaces are approximately 1860 square feet in size. It consists of a telecom room, bathroom, and other offices and storage. These rooms are situated on a
12” high raised floor with an 8’ high drop ceiling. This space is served by two Liebert
Challenger 3000 5-Ton R-22 AC units located in Mechanical Room 662 (CRAC 5 &
CRAC 6). Ventilation to the space is provided by a Fan Coil Unit #6.2 that supplies the ventilation air to the return air in the mechanical room. The CRAC units for this space are downflow with a short radius duct elbow mounted to the bottom of each of the units that supply air to the floor in the conference room. The sound boots that are shown in the 2007 design drawings were not installed on the supply air ducts. It appears that they were not installed due to interferences with the raised floor supports. Installation will include the installation of sound boots, and any needed modifications to the raised floor supports to accommodate this ductwork.
The floor layout has changed slightly from the 2007 design drawings, and the supply air floor tiles do not appear to be installed in conjunction with equipment to optimally transfer heat from the space. Any new installation should include a reevaluation of the location of supply air floor tiles to better accommodate the heat loads of the space.
A. Work must be completed in accordance with the following:
NFPA 70 National Electrical Codes- 2014 Edition
29 CFR 1910 Occupational Safety and Health Standards
29 CFR 1926 Safety and Health Regulations for Construction
[3]
ANSI A120.34 Protection of the Public on or Adjacent to Construction Sites
2.0 SCOPE OF WORK
A. The SOW is to replace four existing Liebert Challenger 3000 Air conditioning units in kind with updated environmentally compliant R-410a refrigeration type or better currently located in the Federal Building 6th floor, rooms 613 and 662. Installation will include new floor stands for each unit and new sound boots for each unit. Make any needed alterations to the current raised flooring system to accommodate ducting and sound boots that do not compromise the structural integrity of the flooring system.
B. Remove and properly dispose of the existing Liebert units, floor stands, and associated hardware and piping in accordance with all state and federal laws. Ensure and certify that removed units are evacuated in compliance with all applicable laws.
Provide all transportation and disposal provisions.
C. Contractor shall insulate all pipe & fittings per manufacture’s recommendation.
D. Contractor shall make all necessary modification to the current building liquid cooling system to ensure units are correctly operated.
E. Install new digital controls and all necessary hardware and wiring so that the CRAC units are able to be controlled from the spaces that they service. Digital controls shall include the ability to control temperature and humidity settings.
F. Units are required to reset automatically in case of power failure as soon as power is restored. Contractor must ensure that the new units integrate and communicate with the currently installed fire detection and suppression systems.
G. Contractor shall remove and then replace all interference associated with the installation of the units.
H. All work shall be performed or supervised by a licensed HVAC technician.
3.0 GENERAL REQUIREMENTS
A. The contractor shall provide all supplies, tools, equipment, transportation, supervision, and labor required to meet objective shown in 2.0 above.
B. Work Hours- The normal working hours for this project shall be from 8:00 am to
5:00 pm, Monday through Friday, excluding federal holidays. No work outside these hours shall be accomplished without the written approval of the Contracting Officer or his/her authorized representative. Contractor is required to have a Coast Guard escort during all working periods. The Coast Guard reserves the right to modify and/or delay the Contractor’s schedule due to unanticipated operational needs
[4] without prior notice.
C. Performance Period- Provide services no later than 180 days after contract signed.
D. Hazardous Conditions – If the Contractor encounters equipment that is in a condition that may endanger life or property, the Contractor shall immediately notify the COR of the condition requiring immediate action. Within 24 hours the Contractor shall provide a written report to the COR of the hazardous condition and recommended corrective action.
E. Safety Procedures - The Contractor shall comply with all appropriate safety code requirements.
F. Housekeeping-The Contractor shall leave areas where he performs work neat, clean and orderly at the end of each shift.
G. The Contractor shall coordinate all work and testing of the system with COR. The
Contractor shall notify the COR and GSA in writing of any scheduled power outages
48 hours in advance. Power outages will be scheduled after 5:00 pm unless the COR and GSA approve otherwise.
H. The Contractor shall provide a written construction schedule a minimum of 2 weeks prior to the beginning of work and a notice 2 working days prior to beginning work in the building.
I. Plan and accomplish all work so that there is a minimum of interference and inconvenience to the occupants and/or operators of the facility. Work must be sequenced so that not more than 2 CRAC units are out of service at any given time.
To minimize impacts to Coast Guard operations, no interruption to AC supply to the space is permitted. The temperature in all affected spaces is to be maintained below
75° F. If portable air conditioning units are proposed to be used, contractor will supply, install, and operate any necessary portable air conditioning units and all necessary parts and pieces to cool the space and electronic equipment. Portable air conditioning units to be 120 volt 15 amps and may exhaust into the overhead plenum.
J. Work will be performed in a secure facility where contractors will be asked to sign in and out. The Coast Guard will require prior approval of all workers needing access to the secure space. The Contractor shall provide the Coast Guard a roster of all workers needing access to the secure including their full name, date of birth, and driver’s license number at least 72 hours prior to needing access. Contractors working in the secure space will need to present a valid government-issued picture identification prior to any entry into the space. No cell phones, cameras, computers, tablets, or other electronic devices are allowed in the secured space without prior permission. If electronics are required to be used in the secure space, written notice is required at least 72 hours prior to use and permission shall be granted by the Coast
[5]
Guard in writing prior to any use. The entry door to the secure space is not allowed to remain propped open.
K. Reference Drawing A-1 in Attachment B outlines the Secure Perimeter Wall. All new and existing ductwork and piping penetrations of the security perimeter are to be protected by dielectric breaks or grounding. In addition, all openings and ductwork in excess of 90 square inches in cross section shall be provided with security bars.
L. Non-Standard Services. Non-standard services are those not listed in the SOW and it will be set forth in individual work orders. Such services shall be negotiated with the
Contractor, and services shall be performed only after the scope of the work, the qualifications of the Contractor’s organization to accomplish the services and the cost of the services have been agreed upon by the COR and Authority Having
Jurisdiction.
M. Work will be performed at a GSA-owned building and must comply with all GSA regulations. Any storage areas that are required to be on site must be coordinated with the COR and GSA in advance. No designated parking will be provided on site.
4.0 SPECIFIC REQUIREMENTS
A. INTENT. The intent of this scope of work is to replace the four existing Liebert
Challenger 3000 CRAC units serving the USCG District 17 and Sector Juneau.
Contractor shall provide all required hardware, installation, and configuration efforts. Contractor shall install remote digital controls in the spaces serviced.
B. EQUIPMENT SELECTION. Contractor shall provide four modernized and latest to date replacement CRAC units for the existing 5-Ton Liebert Challenger 3000 units.
Specifications to include: Downflow, water-cooled, 460/60/3, advance microprocessor with graphics, electric reheat, infrared humidifier, R410a refrigerant or better, smoke and leak detection, and remote digital controls. Prior to purchasing the equipment, the contractor shall complete the System Verification Review.
Government approval is required prior to ordering any equipment. Market research recommends replacing the units with Liebert PW017DC1A2H22, but this must be verified by the contractor.
C. All on site work shall be coordinated with the COR.
D. All work shall comply with the NEC.
E. All conductors shall be installed in conduit.
F. SHIPMENT OF EQUIPMENT. Equipment shall be shipped to location by unclassified commercial mean or purchased locally. The contractor is fully responsible for any damage to the equipment during shipping.
[6]
G. SITE ACCESS AND EQUIPMENT MOVEMENT. Contractor is responsible for truck & equipment required to move machinery into building basement and all equipment movement once inside the building in order to remove old units and to locate new units to the 6th floor. Contractor will comply with all required security mandates in accordance with the General Services Administration (GSA) building management and security for open building access.
H. O&M MANUALS. Two copies of O&M manuals shall be provided to the Facility
Engineer prior to departure. O&M manuals must include detailed maintenance schedule & product information. They must also include all repair and warranty information.
I. TRAINING. After installation and commissioning is complete, two training sessions shall be provided by the contractor in Juneau for all interested CG and GSA employees. One training session shall be a minimum of 1 hour, hands-on system maintenance procedures. The second training session shall be a minimum of 30 minutes hands-on system operations familiarization and procedures.
J. LABELING. All equipment and circuits installed or altered shall be correctly labeled in English. All breakers shall be correctly and permanently labeled. All installed equipment shall be properly labeled. Labeling must be completed prior to the training. Hand written labels or labels deemed by the COR to peel off too easily are not acceptable.
K. SITE RESTORATION. The contractor shall ensure that all facilities receiving this work shall be left in a condition acceptable to USCG Facility Engineer and GSA
Building Management upon completion.
L. DISPOSAL OF MATERIALS REMOVED. The contractor shall be responsible for the disposal of removed materials and equipment. All failed/redundant government owned equipment shall be disposed of by the contractor with the COR’s concurrence.
M. WARRANTY. The installing contractor shall provide a one-year warranty that includes all parts, materials, labor, travel costs, per diem, and all miscellaneous costs. The contractor may seek reimbursement from the manufacture or any other entity providing warranties for the equipment installed, but the contractor must be the responsible party for warranty repairs. The contractor shall provide, at his cost, for onsite repairs within 7 days of notification of an operational problem or failure with the warranty period.
5.0 CONTRACTING OFFICER REPRESENTATIVE (COR)
The Contracting Officer Representative (COR) will be the contractor’s contact with the
USCG. The COR will assist and direct the contractor when scheduling work, obtaining
[7] approved local supplies, and liaison with USCG personnel during the course of the project.
All questions concerning coordination of installation activities while at post shall be directed to COR (see below).
Contracting Officer (KO)
Mr. Tim Cowley
Base Kodiak
P.O. Box 195018
Kodiak, AK 99619-5018
Phone: (907) 487-5180 ext. 6619
Email: timothy.d.cowley@uscg.mil
Contracting Officer Representative (COR)
CWO Thomas Logan
Civil Engineering Unit Juneau
P.O. Box 25517
Juneau, AK 99802
Phone: (907) 463-2413
Cell: 907-942-7562
Email: thomas.m.logan@uscg.mil
6.0 TASK ORDER PROPOSAL REQUEST
A. The contractor shall submit to the KO a proposal for this project. If a site visit is needed, it may be conducted through coordination with Contracting Officer and the cost for site visit will be non-reimbursable by the government. Cost proposal shall include amounts of the following:
a. The required HVAC units, stands, parts, materials and shipping.
b. The required number of labor hours by labor classification and labor rates.
c. Total proposed price.
B. Contractor shall provide a project schedule showing (at minimum) start/completion dates for the project.
7.0 SUBMITTAL REQUIREMENTS
A. Provide submittals of all material and equipment. Including catalogue number, performance data, wiring diagrams, and rough-in dimensions.
B. Two Liebert CRAC Units.
C. Circuit Breakers as needed.
D. Unit Controls and Censors.
[8]
E. Work Schedule.
F. Roster of all workers who will need access to the secure space including their full name, date of birth, and driver’s license number.
G. Temporary cooling plan to maintain room temperature below 75°F including any equipment specifications and locations.
8.0 ATTACHMENTS
A. Pictures.
B. Previous Construction Drawings for Reference Only.
[9]
ATTACHMENT A: Pictures
CRAC 1 & 2: Return Air and Supply Pipe
District 17 Mechanical Room 613
CRAC 1 & 2: Bottom Connections
[10]
CRAC 5 & 6: Base and Piping
Sector Juneau Mechanical Room 662
CRAC 5 & 6: Return Air, Ventilation and Piping
Sector Juneau Mechanical Room 662
[11]
CRAC 2 Information Label
CRAC 2 Floor Stand