Q and A for duct cleaning work.docx

DOCX document 20 KB Posted

Attached to
HVAC air duct cleaning services at Coast Guard Station Lake Worth Inlet
Solicitation number
70Z02824Q0000010
Issued by

About this file

This document contains a solicitation for HVAC air duct cleaning services at the Coast Guard Station Lake Worth Inlet. The solicitation requests quotes for cleaning, disinfecting, and treating for mold the main and shop building HVAC ducts. Quotes are due by February 16, 2024. The contract will be awarded as a small business set-aside using lowest price technically acceptable procedures. The period of performance is expected to commence within 10 business days of award and be complete by March 2024. The solicitation provides a scope of work, site visit details, wage determinations, and instructions to offerors. Vendors must be registered in SAM and have applicable NAICS codes to be considered for award.

View the file

Other files

File Type Posted
Q and A for duct cleaning work.docx DOCX document
SF_30.pdf PDF
Air Duct Diagram.pdf PDF
15-4573.txt TXT text file
Clauses and Provisions (Supply and Service).docx DOCX document
SOW - Duct Cleaning.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Scope of Work for HVAC air duct services CG STA Lake Worth Inlet *Questions*

· What is the square footage of the buildings?

Please see building diagram

· Is the the interior duct work is internally lined, the proper way to clean this without doing any damage or causing fibers to get loose is to Contact brush and vacuum (hand cleaning). Using push pull method (High Pressure Air & Negative) can damage the interior liner especially if the liner is starting to break down. Sealing the duct work will prevent any loose fibers from entering the air stream and out into the occupied space. This is all stated in the NADCA standards (NADCA.com), standards stated in bid docs to follow

Metal ducting, please see diagram

· Please verify we are not cleaning any bathroom exhaust?

Yes you will be cleaning bathroom exhaust

· Is there any drawing for all of the associated HVAC systems on the project?

Yes, please see attached

· Please verify new filters for units will be supplied by facility or contractor?

Contractor supplied

· Is a bond required for this project?

· Can the contract/task be completed at night and on weekends, will the contractor have full access to the building so the contractor can schedule their work and man power properly? Will there be any schedule conflict with the Federal employees?

During the day only between 0800-1500.

· Can the contractor work on multiple units and areas at the same time?

Yes, We can accommodate two areas at a time.

· What if the contractor finds ductwork that we are cleaning has an active air leaks at the joint of the duct or at a duct fitting, does the contractor need to seal the leak as we are working? What would the protocol be for this project? Would the owner provide a change order to the contractor to complete this work? Notify site POC, Minor repairs can be handled at the unit, we will work together on a case by case basis.

· Will the government provide a storage area for the contractor’s equipment during the performance period of the project? Garage area can hold contractor equipment

· Will the government Tech POC approve our work for each unit before we move on to other areas?

Yes, contractor will need to show a Tech POC proof of completion to include camera or digital pictures of ducting after cleaned

· Is the inspection/acceptance of project completion provided for each unit or just at the end of the project?

Each unit as completed, show Tech POC proof of completion to include camera or digital pictures of ducting after cleaned. Tech POC will be available and monitoring work.

· Does the contractor need to document and provide a form that all of our equipment has been cleaned before being allowed on site? Yes, please ensure equipment is clean and satisfactory for conducting the project

· Besides Drivers License is there any other ID required?

Only drivers license is required

· What is the size of the access panels in the ductwork for inspection and cleaning purposes?

Standard exhaust and intake vents, 10 x 10, 12x6, etc.

· Are pictures, diagrams, schematics available for the Air Duct Work for the referenced building? If so, would it be possible to provide that information?

Yes, diagram is included in the e-mail.