This document is an operations and maintenance manual for the CL-ACXE-1200 HVAC unit, a portable temperature and humidity control system manufactured by Western Shelter Systems. The unit is rated for 208 or 240 volts, 30-amp, single-phase, 60 hertz operation with a cooling capacity of 3.5 tons (41,000 Btu/hr) and heating capacity of 42K Btu/hr, plus optional supplemental heating of 27/36K Btu/hr requiring a separate 50-amp circuit. The system delivers 1,400 CFM with 12-inch discharge and 14-inch return ducting and includes replaceable 16"x25"x1" filters. Unit dimensions are 56" x 35" x 41.5" (including cart), with stackable dimensions of 56" x 35" x 47.5", weighing 526 lbs. standard or 550 lbs. stackable.

The manual provides comprehensive guidance on setup, operation, and maintenance procedures. Setup requires positioning the unit on level ground near shelter HVAC attachment points, connecting 30-amp power cables to either an electrical distribution box or generator, attaching duct boots, installing a thermostat with 50-foot cable on the opposite side of the shelter, and connecting a condensate p-trap drain. Operation involves setting desired temperature and system mode on the thermostat, with the unit capable of switching between cool, heat, emergency heat, and off modes. The document emphasizes multiple critical safety warnings regarding refrigerant, high-pressure oil, electrical shock hazards, and moving parts. Maintenance tasks include weekly air filter inspections and replacement with 16x25x1 filters, annual professional service by qualified technicians covering filters, motors, condenser coils, electrical components, and condensate drains, and user-performed coil cleaning. Western Shelter Systems provides a one-year conditional warranty covering defects in materials and workmanship from date of manufacture, with customer support available at 1-800-971-7201.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C L- A CX E -1 2 0 0 H VA C

R o b u s t Te m p e r a t u r e a n d H u m i d i t y C o n t r o l

TABLE OF CONTENTS

A.Warnings� 3
B.Appliance details� 4
C.Component identification� 4
D.Operating instructions� 5
1.Setup� 5
2.Operation� 6
3.Emergency heat� 7
4.Switching operation voltage� 7
E.Maintenance / Troubleshooting� 8
1.Replacing the air filter� 8
2.Cleaning outdoor coil � 8
3.Professional service checklist� 8
4.Troubleshooting checklist� 9
5.Resetting the thermostat� 9
F.Component list� 10

CONDITIONAL WARRANTY

Western Shelter Systems warrants all products against defects in materials or workmanship for a period of one (1) year from date of manufacture. Component manufacturers’ warranties may exceed that of Western Shelter.

No warranty is made or implied regarding the intended use of the product. Warranty does not cover damage caused by abuse, misuse, neglect or improper care by the end user in the application of the Western Shelter Systems product.

Western Shelter Systems will repair or replace any component deemed to be faulty from manufacture in the most efficient and timely means available to Western Shelter Systems.

Western Shelter Systems must authorize all claims prior to any action taken by the end user.

For immediate attention regarding any defective product, please phone Customer Support at 1-800-971-7201, 7am-330pm PST.

Shipping: 815 Conger St. Eugene, OR 97402 PO Box 2729 Eugene, OR 97402 USA

Phone 1-541-344-7267 Toll Free 1-800-971-7201

Fax 1-541-284-2820 www.WesternShelter.com

FOLLOW ALL WRITTEN AND COMMON SENSE SAFETY

PROCEDURES WHEN OPERATING THIS UNIT. FAILURE TO DO SO

MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY.

A. WARNINGS

CONTAINS REFRIGERANT!

SYSTEM CONTAINS OIL AND REFRIGERANT

UNDER HIGH PRESSURE.

ANY SERVICE PROCEDURES NOT DETAILED

IN THIS MANUAL MUST BE PERFORMED BY A

QUALIFIED SERVICE TECHNICIAN.

TO PREVENT INJURY OR DEATH DUE

TO ELECTRICAL SHOCK OR CONTACT

WITH MOVING PARTS, DISCONNECT UNIT

BEFORE SERVICING.

DO NOT TOUCH TOP OF COMPRESSOR. MAY

CAUSE MINOR TO SEVERE BURNING.

Rating: 208 or 240 Volts, 30-Amp, Single-Phase, 60 Hertz

CFM: 1,400

Cooling: 3.5 tons, 41,000 Btu/hr EER/ SEER (Btu/Watt Hr) - 10.5/12.05

Heating: 42K Btu/hr Supplemental Heating: 27/36K Btu/hr (Requires separate 50 Amp circuit for operation.)

Ducting:

XE12UD Discharge - 12-inch XE12LD Return - 14-inch XE12FLTR (Replaceable 16”x25”x1” filter.)

Dimensions: (L x W x H) - 56” x 35” x 41.5” (including cart)

Stackable Dimensions: (L x W x H) - 56” x 35” x 47.5”

Weight:

Standard (Stackable) 526 lbs. (550 lbs.)

Optional and Replacement Equipment:

WAC-12 12” Window Duct Panel

B. APPLIANCE DETAILS

Air supply

Air disharge duct

Thermostat cover

C. COMPONENT IDENTIFICATION

Condensate drain connection point

50’ 30-Amp input

Air supply duct Hex driver for filter panel Condensate p-trap

Thermostat

Accessory/ thermostat bag

Voltage adjustment

Emergency heat strip 50-Amp input

Air discharge

Air filter

Duct bag

Locking wheels

1. Setup

ØRemove the cover and orient the unit so the circulation vents face one of the HVAC attachment points on your shelter. Locate the unit on solid, level ground, using shoring or a plywood base if necessary.

ØNote: The main power cables and thermostat are routed around the back of the unit. The 30-Amp cable can attach to either an electrical distribution box or directly to a generator with a 30-Amp, 208/240V output.

D. OPERATING INSTRUCTIONS

ØNote: In the green vinyl pouch on the rear of the unit, you will find the thermostat with 50 foot cable, operations manuals, and a hex driver for unit maintenance.

ØThe HVAC unit attaches to any of the duct boot openings around any WSS shelter. To eliminate trip hazard, it is recommended that the HVAC unit be positioned away from the most used doorways if possible.

ØTo access the panels, remove the square vinyl covers from both ports, and the square insulation panels, if installed. They can be stored in the duct-boot bag on the HVAC unit so they will not be misplaced.

ØIf you are using an air plenum, install it now.

See documentation accompanying the air plenum for installation information.

ØIn the side pouch are the two duct boots for attaching the HVAC unit to your shelter. The tapered boot attaches to the top of the unit, and the re-enforced boot with filter screen attaches to the bottom. Also in the pouch is the p-trap for condensation discharge.

ØAttach the duct boots to the shelter. The angled boot goes on top, and the re-enforced boot underneath.

ØTo attach the unit, align it with the duct boot openings, about two feet from the shelter wall.

ØAttach the duct boots to the HVAC unit with the black nylon straps. Place the lower duct boot over the lower port, then snug the strap tight. Be sure the seal is tight all around. Repeat on the top port. Move the unit back a few inches to put some tension on the boots so air will flow easily. Lock the wheels.

Be sure you have read and understood all safety warnings before attempting to operate this unit.

ØAttach the p-trap by filling it with water, capping one end with your hand, and firmly push the non-threaded end into the drain.

A standard garden hose can be attached to drain water away from the shelter base.

ØUnwrap and install the thermostat. Make a small opening in the bottom of the upper duct opening and pass the thermostat through, along with 50’ of cable.

ØInside the shelter, string the cable over roof trusses until it is located on the opposite side of the shelter from the ducting. This results in a more accurate reading of the shelter temperature.

ØSecure the thermostat about six feet off the ground.

2. Operation

ØCAUTION: Be sure the green vinyl bags are away from air intakes when the unit is operational

ØIf you are drawing power directly from a generator, attach the power cable from the HVAC system to your generator. Generator operation is not covered in this manual, and should be performed by a trained individual. You can also attach the system to an electrical distribution box. The main power connects to a 30-Amp outlet, and the emergency heating to a 50-Amp outlet.

ØOnce the system is connected and the power is running to the unit, set the desired temperature and system mode on the thermostat. The unit is designed not to change modes more than once every three minutes, so it may take up to three minutes for the HVAC unit to begin operating.

ØThe thermostat has very simple controls.

The “SYSTEM” button switches between cool, heat, emergency heat and off. The fan can be switched to either Auto or On position and programmed with a 90 second Off-delay. To adjust the Off-delay see page 7.

The up and down buttons set the desired temperature. The system is designed to go into emergency heating mode, if available, when the ambient temperature is at least six degrees cooler than the temperature set on the thermostat.

UP

DOWN

FAN SYSTEM

3. Emergency heat

ØThe emergency heat connection, if included on you unit, can be located under the small panel above the “emergency heat power” notice. This connection will boost the heating power of the unit by 11,000 BTUs/hr, and requires a 50-Amp, 240 volt connection. The connection draws 42 Amps continuously when operating, so plan your power distribution accordingly. When operating in conditions under 40 degrees, the emergency heat is recommended to keep the unit running well.

4. Switching operation voltage

ØThe HVAC unit is capable of running off either 208 or 240 volts, depending on your electrical setup. Do not change modes without a solid understanding of your electrical distribution setup. Do not run the HVAC unit until it is properly setup up for your system.

ØTo change between 208 volt and 240 volt operation, detach the panel with shock hazard warnings located next to where the power cables come out of the unit.

ØLocate the red wire with white clip running to a transformer with two leads. The leads are printed “208” and “240.” When using a single-phase generator, connect to the 240 volt connection. When using three-phase generator, connect to the 208 volt connection. The unit comes preset to the 208 volt connection, unless otherwise noted on label.

COMPLETELY

DISCONNECT ALL

ELECTRICAL SYSTEMS

BEFORE SWITCHING

VOLTAGE.

Fan Off-Delay options:

90 seconds SW5

ON

SW6

OFF

set by factory

180 seconds SW5

ON

SW6

OFF

option 2

0 seconds SW5

OFF

SW6

OFF

option 3

Switch is located on the lower left power panel and is colored blue.

ON

OFF

1 2 3 4 5 6 7 8

WARNING: Follow the hazardous voltage instructions on front panel!

3. Professional service checklist

ØTo keep your unit operating as designed, a qualified serviceman should check over the entire system at least once each year as well as any other time that you feel that service is needed. Your serviceman should examine and inspect:

•Filters (for cleaning or replacement)

•Motors and drive system components

•Condenser coils (for cleaning)

•Safety controls (for mechanical cleaning)

•Electrical components and wiring (for possible replacement and connection tightness)

•Condensate drain (for cleaning)

•Unit duct connections to see that they are physically sound and sealed to the unit casing

•Unit mounting support to see that it is sound

•Unit to see that there is no obvious unit deterioration.

E. MAINTENANCE / TROUBLESHOOTING

ØYou can do some of the periodic maintenance functions for your XE1200 unit yourself. These functions include replacing the disposable or cleaning the permanent air filters, cleaning the unit’s cabinet, cleaning the condenser coil, and conducting a general inspection of the unit on a regular basis.

1. Replacing the air filter

ØIt is very important to keep the duct system air filters clean. Be sure to inspect them at least once each week when the system is in constant operation.

ØReplace used filters with new filters of the same type and size. Do not try to clean disposable filters.

ØLocated on the front side of the unit are the discharge and return ports. The air return port uses a filter similar to most home systems (16x25x1), and can easily be replaced.

ØTo replace the air filter, unscrew the four hex screws securing the front port cover.

Inside the cover is the air filter. Pull up on the filter, then out on the bottom to remove.

Place a new filter in top end first and push up to fit into place.

2. Cleaning outdoor coil

ØWith the front cover off, you can see the heating and cooling elements. They should be free from dust and debris.

ØUnfiltered air circulated through the unit’s outdoor coil can cause the coil’s surface to become clogged with dust, dirt, etc. To clean the coil, stroke the coil surface with a soft-bristled brush vertically, that is, in the direction of the fins.

4. Troubleshooting check list

•Is the unit properly and securely located and level with the proper clearance?

•Is the duct work correctly run with the proper unit arrangement?

•Is the condensate line properly run? Does it drain freely?

•Is the filter of the correct size and number? Are the supply and return ports unobstructed?

•Is the power supply correct for the unit’s requirements?

•Are all wiring connections, including those in the unit itself, tight?

•Is the thermostat well located and accurately adjusted?

•Do the outdoor fan and the indoor fan turn free without rubbing? Are both fans tight on their shafts?

•Are all cover and access panels in place to prevent air loss and to protect against safety hazards?

•Have all tools and debris around, on top of, and under the unit been removed?

5. Resetting the thermostat

ØIt may become necessary to reset the unit thermostat. If the thermostat has lost power or is not operating properly, follow these steps to reset it.

ØReplace the AA batteries in the thermostat.

ØPress and hold the UP and FAN buttons until the unit display changes to settings mode.

ØPress the UP and DOWN buttons to change settings.

ØPress NEXT to advance to the next function.

ØPress DONE to save and exit.

ØFactory recommended settings are as follows:

Setup Function Recommended Setting 1 - System Type 5 - 2 heat/1 cool heat pump 2 - Changeover valve 0 - O/B terminal energized in cooling 6 - Second Stage Heat 9 - For electric furnaces 9 - Compressor Cycle 3 - Recommended 12 - System setting 0 - Manual changeover 14 - Temperature Display 0 - Fahrenheit (1 Celsius) 15 - Compressor protection 3 - Minutes 26 - Auxiliary Heat control 0 - Comfort 27 - Heat temperature range 90 28 - Cool temperature range 50

4/5

F. COMPONENT LIST

PART # DESCRIPTION

1 XE-12UFST Frame, Upper for Stackable unit. Includes 2 handles and neces-sary hardware for upgrading standard frame.

2 XE12-PNL Panel, Replacement XE-1200 Duct, with Filter

3 XE-12 TSTAT Thermostat, Honeywell 2 Stage for XE-1200 HVAC (thermostat only)

4 XE12-

CST5.2R

Caster, Rigid 5”x 2” Rubber on Steal

5 XE12-

CST5.2S

Caster, Swivel 5”x 2” Rubber on Steal

6 XE 12 FLTR Filter, 16x25x1 Pleated for XE1200 CASE OF 12 FILTERS

7 XE1200 CVR Cover, Vinyl for XE-1200 HVAC unit

8 XE 12-DRN Condensation Drain for XE1200