GENERAL NOTES
DEMOLITION
EXISTING PIPING AND EQUIPMENT SHOWN IS BASED ON EXISTING PLANS AND FIELD
OBSERVATION WITHOUT DEMOLITION. AFTER DEMOLITION, ANY CLARIFICATION
REQUIRED TO DETERMINE SCOPE OF WORK MUST BE BROUGHT TO THE ATTENTION OF
THE COTR.
THE CONTRACTOR MUST VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF
WITH THE EXISTING CONDITIONS.
DRAWINGS DO NOT SHOW EVERY EXISTING PIPE, CONDUIT, DUCT, ETC. CONTRACTOR
MUST TAKE CARE TO REMOVE ONLY ITEMS REQUIRED TO BE REMOVED AND VERIFY
PIPES, DUCTS, ETC. BEFORE REMOVAL.
REMOVAL OF ITEMS MUST INCLUDE ASSOCIATED HANGERS, ANCHOR BOLTS AND OTHER
APPURTENANCES. WHERE SUCH REMOVAL RESULTS IN OPEN HOLES, VOIDS OR
EXPOSURE OF DAMAGED SURFACES, THE CONTRACTOR MUST BE RESPONSIBLE FOR
REPAIRING AND FINISHING THE SURFACE TO MATCH ADJACENT CONDITIONS. THIS WORK
MUST BE COORDINATED WITH ARCHITECTURAL FINISH SCHEDULES WHERE APPLICABLE.
BUILDING IS TO REMAIN OCCUPIED DURING CONSTRUCTION. REMOVAL OR SHUT-DOWN
OF EQUIPMENT THAT AFFECTS ANY OCCUPIED AREA'S AIR CONDITIONING OR HEATING
MUST ONLY BE DONE AS APPROVED BY THE COTR. THIS MAY REQUIRE NIGHT AND
WEEKEND WORK TO KEEP BUILDING IN OPERATION. REFER TO SPECIAL SCHEDULING
REQUIREMENTS IN THE SPECIFICATIONS.
REMOVE EXISTING PIPING NOT TO BE REUSED.
ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR DESIGNATED
TO BE TURNED OVER TO THE GOVERNMENT, MUST BECOME THE PROPERTY OF THE
CONTRACTOR, UNLESS OTHERWISE NOTED, AND MUST BE REMOVED COMPLETELY FROM
THE SITE.
GENERAL ITEMS
GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH MECHANICAL DRAWING OF
THIS SET. SEE EACH DRAWING FOR SPECIFIC NOTES APPLICABLE TO THAT DRAWING.
OVERHEAD PIPING IN SPACES WITHOUT HUNG CEILINGS MUST BE RUN AS CLOSE TO
ROOF DECK OR STRUCTURE ABOVE, AS PRACTICAL, AS CLOSE TO PARALLEL JOISTS AS
POSSIBLE AND ABOVE LIGHTING FIXTURES TO CONCEAL PIPING.
OVERHEAD PIPING IN SPACES WITH CEILINGS MUST BE CONCEALED UNLESS OTHERWISE
NOTED.
ARRANGE PIPING, PARTICULARLY ABOVE CEILING AS REQUIRED TO CLEAR STRUCTURE,
DUCTS, CONDUITS, ETC. ALLOWING SPACE FOR PIPE HANGERS, EXPANSION LOOPS AND
ACCESS TO VALVES, AND MAINTENANCE OF EQUIPMENT.
COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER TRADES.
DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF DOORS,
WINDOWS, ETC.
VALVES AND SPECIALTIES MUST BE LINE SIZE EXCEPT FOR CONTROL VALVES OR UNLESS
NOTED OTHERWISE.
NO PIPING MUST BE SMALLER THAN 1/2" UNLESS OTHERWISE NOTED.
FOR PIPE SIZES NOT INDICATED ON PLANS, SEE EQUIPMENT CONNECTION DETAILS.
PROVIDE UNION CONNECTIONS AT EACH PIECE OF EQUIPMENT.
MAINTENANCE
INSTALL PIPE RUNS AT LEAST 6" ABOVE CEILING TILES. WHERE PRACTICAL INSTALL
VALVES, AND OTHER MAINTAINABLE DEVICES LOW ENOUGH TO REACH WITH A 6' LADDER.
PROVIDE ACCESS TO ANY INSPECTION OR MAINTAINABLE DEVICE, EQUIPMENT, ETC. -
ACCESS OR ACCESS DOOR MUST BE OF ADEQUATE SIZE TO WORK ON DEVICE.
EXAMINE MANUFACTURER'S LITERATURE TO DETERMINE RECOMMENDED CLEARANCES.
THESE CLEARANCES, IN ADDITION TO MINIMUM CLEARANCES REQUIRED BY THE
NATIONAL ELECTRICAL CODE, MUST BE ESTABLISHED AND MAINTAINED. THIS APPLIES TO
NEW AND EXISTING EQUIPMENT IMPACTED BY THIS PROJECT AS WELL. THE CONTRACTOR
MUST BE RESPONSIBLE FOR COORDINATING THESE REQUIREMENTS WITH ALL OTHER
TRADES.
INTERDISCIPLINARY COORDINATION
IF THIS CONTRACTOR SHOULD ELECT TO PROPOSE ANY EQUIPMENT THAT HAS
DIFFERENT PHYSICAL OR ELECTRICAL CHARACTERISTICS, ETC. WHEN COMPARED TO THE
BASIS OF DESIGN EQUIPMENT, THIS CONTRACTOR IS RESPONSIBLE FOR COORDINATING
THESE CHANGES WITH THE OTHER TRADES PRIOR TO ORDERING OF EQUIPMENT. IF
THERE SHOULD BE ANY ADDITIONAL WORK INCURRED BY THE OTHER TRADES AS A
RESULT OF THIS CONTRACTOR'S EQUIPMENT SELECTION, ALL COSTS ASSOCIATED WITH
THE ADDITIONAL WORK MUST BE BORNE BY THIS CONTRACTOR.
UON UNLESS OTHERWISE NOTED
POINT OF DEMOLITION LIMIT
POINT OF CONNECTION NEW TO EXISTING
DEMOLITION/CONSTRUCTION NOTE DESIGNATION
LEGEND AND ABBREVIATIONS
HOSE REEL DESIGNATIONHR-1
MAXIMUMMAX
PIPE TURNING DOWN
COMPRESSED AIR PIPINGCA
MIN MINIMUM
PIPE TURNING UP
ETR EXISTING TO REMAIN
ABOVE FINISHED FLOOR
ISOLATION VALVE
AFF
(TYP) TYPICAL
IN INCH
PSIG POUND PER SQUARE INCH GAUGE
BALL VALVE
PIPE CAPPED
COTR CONTRACTING OFFICER'S
TECHNICAL REPRESENTATIVE
FT FEET
R E
P A
IR
R
O O
F A
N D
A P
P
LY
M A
S O
N R
Y S
E A
LE
R
B
9, M
C A
S C
H E
R R
Y P
O
IN
T, N
C
WALKER
i n c o r p o r a t e d
ARCHITECTURE
252-636-8992(fax)
PO BOX 541, NEW BERN, NC 28563
252-636-8778
GROUPthe
TNH MTF JAK
12815755
M E
C H
A N
I C
A L
G
E N
E R
N
O T
E S
L
E G
E N
D
A
D
S
C H
E D
U L
E
AS NOTED
M-001
COMBINATION HOSE/ELECTRIC REEL SCHEDULE
HOSE DIAMETER
TAG
(I.D. / O.D.)
HOSE / CORD LENGTH MAX PSIG AMPS REMARKS
HR-1 3/8" / 5/8" 50' 300 20 SEE NOTES
NOTES:
1. SELECTION BASED ON COXREELS C SERIES OR APPROVED EQUAL.
2. PROVIDE WITH SPRING MOTOR AND MULTI-POSITION LOCK RATCHET MECHANISM THAT SECURES HOSE
AND CORD AT DESIRED LENGTH. THE ELECTRIC CORD MUST HAVE A DUPLEX OUTLET TERMINATION.
3. PROVIDE WITH MULTI-POSITION GUIDE ARM.
06-22-20
1", ETR
A B G H I
C E F
J
D
1", ETR
3/4", ETR
3/4", ETR
1/2", ETR 1/2", ETR
3/4", ETR
1/2", ETR
CA
C A
C A
C A
C A
C A
3/4", ETR
1/2" QUICK CONNECT
CA DROP, ETR (TYP.)
R E
P A
IR
R
O O
F A
N D
A P
P
LY
M A
S O
N R
Y S
E A
LE
R
B
9, M
C A
S C
H E
R R
Y P
O
IN
T, N
C
WALKER
i n c o r p o r a t e d
ARCHITECTURE
252-636-8992(fax)
PO BOX 541, NEW BERN, NC 28563
252-636-8778
GROUPthe
TNH MTF JAK
12815756
M E
C H
A N
I C
M
O L
I T
I O
N
F
L O
R
P
A
N
AS NOTED
MD101
TNPN
MECHANICAL DEMOLITION FLOOR PLAN
SCALE: 1/8" = 1'-0"
A4
DEMOLITION NOTES
1 REMOVE COMPRESSED AIR PIPING TO POINT INDICATED AND CAP.
REMOVE DUCTWORK AND INSULATION TO LIMIT INDICATED. REMOVE
AND STORE DIFFUSER FOR REINSTALLATION UNDER NEW WORK
PHASE.
1/8" = 1'-0"
5'0'5' 10' 20'
MEASURE AIRFLOWS OF ALL EXISTING AIR DEVICES ASSOCIATED WITH
HVAC SYSTEM SERVING SHOP 106 PRIOR TO DEMOLITION WORK. THERE
ARE APPROXIMATELY 14 AIR DEVICES. SUBMIT PRETAB REPORT TO
GOVERNMENT FOR APPROVAL. FINAL AIRFLOWS SERVING SHOP 106 MUST
BE PROPORTIONALLY LOWERED TO ACCOUNT FOR ADDED DIFFUSER IN
ROOM 107. AIRFLOWS AT ALL OTHER AIR DEVICES MUST REMAIN WITHIN
TOLERANCE OF MEAURED PRETAB VALUES. SUBMIT ANTICIPATED FINAL
AIRFLOWS TO GOVERNEMNT FOR REVIEW AND APPROVAL PRIOR TO
COMMENCING FINAL TAB.
PRETAB NOTE:
1", ETR
A B
C
G H I
E F
J
D
1", ETR
3/4", ETR
3/4", ETR
1/2", ETR 1/2", ETR
3/4", ETR
1/2", ETR
CA
C A
C A
C A
C A
C A
3/4", ETR
1/2" QUICK CONNECT
CA DROP, ETR (TYP.)
A
HR-1 (TYP. OF 5)
101 102
103 105
106108
R E
P A
IR
R
O O
F A
N D
A P
P
LY
M A
S O
N R
Y S
E A
LE
R
B
9, M
C A
S C
H E
R R
Y P
O
IN
T, N
C
WALKER
i n c o r p o r a t e d
ARCHITECTURE
252-636-8992(fax)
PO BOX 541, NEW BERN, NC 28563
252-636-8778
GROUPthe
TNH MTF JAK
12815757
M E
C H
A N
I C
N
S T
R U
C T
I O
N
F
L O
A
N
A
T
A I L
AS NOTED
M-101
TNPN
MECHANICAL CONSTRUCTION FLOOR PLAN
SCALE: 1/8" = 1'-0"
A4
CONSTRUCTION NOTES
1 PROVIDE COMPRESSED AIR PIPING, HOSE REEL, HANGERS, AND
SUPPORTS COMPLETE. HOSE REEL MUST BE MOUNTED VERTICALLY
ON THE WALL TO MATCH EXISTING HOSE REELS THROUGHOUT THE
BUILDING. COORDINATE EXACT LOCATIONS AND ELEVATIONS WITH
THE COTR PRIOR TO PERFORMING ANY WORK. SEE HOSE REEL
PIPING DETAIL, THIS SHEET.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS
COMPLETE.
REINSTALL DIFFUSER SALVAGED DURING DEMOLITION PHASE.
1/8" = 1'-0"
5'0'5' 10' 20'
1/2" BALL VALVE
FLOOR
CEILING
HOSE REEL
A P
P R
O X
1/2" BALL VALVE
EXISTING COMPRESSED
AIR PIPING
CORD REEL
06-22-20
HOSE REEL PIPING DETAIL
NO SCALE M-101
B5
P A
IR
R
O O
F A
N D
A P
P
LY
M A
S O
N R
Y S
E A
LE
R
B
9, M
C A
S C
H E
R R
Y P
O
IN
T, N
C
WALKER
i n c o r p o r a t e d
ARCHITECTURE
252-636-8992(fax)
PO BOX 541, NEW BERN, NC 28563
252-636-8778
GROUPthe
ELECTRICAL PANELBOARD
ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN
TO PANELBOARD (PANEL AND CIRCUIT DESIGNATION AS
INDICATED). AS A MINIMUM CONDITION, EACH SINGLE PHASE
CIRCUIT SHALL HAVE 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL
CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR IN 1/2"
CONDUIT. PROVIDE ADDITIONAL PHASE CONDUCTORS AS
REQUIRED FOR "MULTIPLE PHASED" ELECTRICAL LOADS.
PROVIDE NEUTRAL CONDUCTOR TO ALL WALL SWITCH OUTLET
BOXES WHETHER REQUIRED OR NOT. PROVIDE ADDITIONAL
"SWITCH LEG" CONDUCTORS TO PROVIDE THE LIGHT FIXTURE
CONTROL INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS
MAY BE GROUPED TOGETHER IN A COMMON CONDUIT IN
ACCORDANCE WITH THE NEC AND AT THE CONTRACTOR'S
DISCRETION. GROUNDING CONDUCTORS MAY BE SHARED AS
ALLOWED BY THE NEC. NEUTRAL CONDUCTORS SHALL NOT BE
SHARED. MULTI-POLE BREAKERS SHALL BE PROVIDED IN
ACCORDANCE WITH THE NEC WHERE MULTI-WIRE BRANCH
CIRCUITS ARE REQUIRED. CONDUIT LARGER THAN 1/2" AND
CONDUCTORS LARGER THAN #12 SHALL BE AS INDICATED.
POWER
GENERAL
NEW WORK NOTE SYMBOL
GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL WORK SHOWN ON ELECTRICAL DRAWINGS IS NEW WORK
TO BE PROVIDED UNDER THIS CONTRACT.
COORDINATION: COORDINATE AND COOPERATE WITH ALL
TRADES ON THE PROJECT. THE CONTRACTOR SHALL REVIEW
ALL CONTRACT DOCUMENTS INCLUDING CIVIL, STRUCTURAL,
ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
CONTRACTOR SHALL COORDINATE AND ADJUST
ACCORDINGLY AS DIRECTED BY THE CONTRACTING
OFFICER.
AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF
ELECTRICAL DRAWINGS TO BE KEPT ON SITE AND MARK,
DAILY, THE DRAWINGS IN RED AS THE PROJECT
PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF
ALL DEVIATIONS BETWEEN THE WORK SHOWN ON THE
DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED.
THESE MARKED DRAWINGS SHALL REFLECT ANY AND ALL
CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH
EXISTS IN THE COMPLETED WORK. DELIVER THE MARKED
DRAWINGS TO THE ENGINEER AT PROJECT CLOSE-OUT.
INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS.
DELIVER ALL REQUIRED INSPECTION CERTIFICATES TO THE
CONTRACTING OFFICER.
GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH
THE NEC FOR THE ENTIRE ELECTRICAL SYSTEM INCLUDING
EQUIPMENT FRAMES CONDUITS, SWITCHES, CONTROLLERS,
WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHER
EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL
POWER CONDUITS.
J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH
PERMANENT MARKER IDENTIFYING CIRCUIT NUMBER AND
PANELBOARD OF CIRCUITS WITHIN.
WIRING DEVICES: LABEL ALL WIRING DEVICES WITH
PANELBOARD AND CIRCUIT DESIGNATION PERMANENTLY
ATTACHED WITH BLACK TYPED DESIGNATION ON CLEAR
TAPE.
CONNECTION DETAILS: SECURE APPROVED SHOP
DRAWINGS SHOWING WIRING DIAGRAMS, ROUGH-IN AND
HOOK UP DETAILS FROM OTHER INVOLVED CONTRACTORS
FOR EQUIPMENT WHICH MUST BE CONNECTED
ELECTRICALLY.
COORDINATION DETAILS: MECHANICAL EQUIPMENT WILL BE
FURNISHED AND INSTALLED BY THE MECHANICAL
CONTRACTOR. THE LOCATIONS SHOWN ON THE ELECTRICAL
DRAWINGS ARE APPROXIMATE. COORDINATE WITH THE
MECHANICAL CONTRACTOR TO DETERMINE THE EXACT
LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINE
THE EXACT ROUGH-IN AND CONNECTION REQUIREMENTS.
WORKING CLEARANCE: COORDINATE FINAL LOCATIONS OF
ELECTRICAL EQUIPMENT WITH MECHANICAL DUCTWORK,
PIPING ETC. AND ASSURE WORKING CLEARANCE REQUIRED
BY NEC WILL BE MET. SUFFICIENT ACCESS AND WORKING
SPACE SHALL BE PROVIDED AND MAINTAINED AROUND
ELECTRICAL EQUIPMENT AS REQUIRED BY THE NATIONAL
ELECTRICAL CODE. CONTRACTOR SHALL COORDINATE FINAL
LOCATION OF EQUIPMENT PROVIDED AND INSTALLED BY
OTHER TRADES.
MATERIAL COORDINATION: VERIFY CEILING AND WALL
CONSTRUCTION AND MATERIAL PRIOR TO ORDERING
DEVICES TO INSURE PROPER FIXTURE OR DEVICE IS
FURNISHED TO MATCH CONSTRUCTION.
MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE
FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE
WIRING DEVICE UNLESS OTHERWISE NOTED. MOUNTING
HEIGHTS OF LIGHTING FIXTURES ARE TO THE BOTTOM OF
THE FIXTURE UNLESS OTHERWISE NOTED.
DEVICE LOCATIONS: COORDINATE LOCATIONS OF
SWITCHES, RECEPTACLES, AND TELE/DATA OUTLETS WITH
OTHER WALL MOUNTED DEVICES SUCH AS THERMOSTATS
AND CONTROL STATIONS.
FIRE STOPPING: FOR ANY WALL OR FLOOR PENETRATIONS
THROUGH FIRE-RATED STRUCTURES PROVIDE
FIRE-STOPPING TO SEAL ALL THE PENETRATIONS AFTER THE
CONDUIT HAS BEEN INSTALLED. FIRE STOPPING FOR
PENETRATIONS SHALL BE UL APPROVED PER THE
PENETRATION MADE IN ORDER TO MAINTAIN FIRE-RATED
INTEGRITY OF THE STRUCTURE.
CLEAN UP: ON PROJECT CLOSE-OUT CLEAN ALL
ELECTRICAL DEVICES, LIGHTING FIXTURES, LENSES, AND
REMOVE ALL PAINT SPATTERS FROM DEVICES, FIXTURES
AND PLATES. REPAIR ALL INOPERATIVE LIGHTING FIXTURES.
THE FOLLOWING SUBSCRIPT SHALL APPLY TO RECEPTACLES WHERE USED:
CONTRACTOR SHALL PROVIDE AN APPROPRIATE LISTED THROUGH-PENETRATION FIRE STOPPING
ASSEMBLY AT EACH PENETRATION OF FIRE RATED CONSTRUCTION (I.E. WALLS AND SLABS, ETC.).
SLEEVES SHALL ONLY BE PERMITTED WHERE INDICATED IN THE CONTRACTOR SELECTED
THROUGH-PENETRATION FIRE STOPPING ASSEMBLY. REFER TO ARCHITECTURAL DRAWINGS FOR
LOCATION OF ALL RATED ASSEMBLIES AND ASSOCIATED UL DESIGNATIONS. DEVICES INSTALLED RECESSED WITHIN FIRE RATED CONSTRUCTION (I.E. LIGHT SWITCHES, RECEPTACLES, ETC.) ARE
ONLY PERMITTED WHEN AN APPROVED LISTED FIRE STOPPING SYSTEM EXISTS FOR THE
APPLICATION. IF AN APPROVED LISTED FIRE STOPPING SYSTEM IS UNAVAILABLE, THE CONTRACTOR
SHALL BRING THE CONDITION TO THE ATTENTION OF THE A/E FOR RESOLUTION PRIOR TO
PROCEEDING WITH WORK.
GENERAL ELECTRICAL NOTES ELECTRICAL LEGEND
AND
DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, 18" AFF, UON
· CR: CORD REEL - SEE DETAIL SHEET E501
ABBREVIATIONS
A AMPERE
AFF ABOVE FINISHED FLOOR
AIC AMPERE INTERRUPTING
CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
C CONDUIT
CKT CIRCUIT
CB CIRCUIT BREAKER
DE DOMINION ENERGY
EC EMPTY CONDUIT
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
FHP FRACTIONAL AC HORSEPOWER
FLA FULL LOAD AMPS
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSE POWER/HEAT PUMP
KAIC THOUSAND AMPERE
INTERRUPTING CAPACITY
KVA KILO-VOLT-AMPERES
KW KILO-WATTS
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NTS NOT TO SCALE
P POLE
Ø PHASE
PRI PRIMARY
RECEPT RECEPTACLE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
W WATTS/WIRE
FIRE STOPPING NOTE:
WALL MOUNTED DUAL TECHNOLOGY VACANCY SENSOR WITH
DIMMING CAPABILITIES, 120/277V, MOUNT 46"AFF. COORDINATE
VOLTAGE AND RATINGS OF SWITCH WITH TYPE AND QUANTITY
OF DRIVERS TO BE CONTROLLED.
VD
LIGHTING FIXTURE
LIGHTING
TELECOMMUNICATIONS
TELE/DATA OUTLET, 4"X4"X2 1/8"D BOX WITH SINGLE GANG
PLASTER RINGS AND SINGLE GANG COVERPLATES TO MATCH
ELECTRICAL OUTLET COVERPLATE MATERIAL AND COLOR, 18"
AFF, UON, WITH (1) 1"C WITH (4) CAT6 UTP CABLING STUB CONDUIT
ABOVE CEILING AND TERMINATE WITH BUSHINGS.
ELECTRICAL DEMOLITION NOTES
GENERAL: DRAWINGS ARE BASED ON EXISTING PLANS
AND FIELD INVESTIGATION PRIOR TO DEMOLITION.
CIRCUITING TO REMAIN: EXISTING CIRCUITING TO
REMAIN SHALL BE REROUTED OR RECONNECTED, AS
REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER
TO MAINTAIN CONTINUITY OF THE CIRCUIT.
REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY
SERVING LIGHTING FIXTURES AND/OR RECEPTACLES
FOR A GIVEN AREA SHALL BE REUSED WHERE
INDICATED TO SERVE THE NEW LAYOUT. PROVIDE
CIRCUIT MODIFICATIONS INDICATED OR AS OTHERWISE
REQUIRED TO MAINTAIN THE CONTINUITY OF EXISTING
CIRCUITS THAT REMAIN.
EXISTING CONDUIT: ALL EXISTING CONDUITS AND
WIRING THAT WILL NOT BE REUSED SHALL BE
REMOVED WHERE THEY WILL BE EXPOSED UPON
COMPLETION OF NEW WORK. EXISTING CONDUIT TO
REMAIN CONCEALED IN WALLS SHALL BE ABANDONED.
EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB
SHALL BE CUT OFF ONE INCH BELOW ROUGH FLOOR
AND GROUTED FLUSH. ALL EXISTING WIRING IN
CONDUITS TO BE ABANDONED SHALL BE
DISCONNECTED FROM POWER SOURCE AND REMOVED.
REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF
DEMOLITION ITEMS. REPAIR, AT NO ADDITIONAL COST
TO THE OWNER, ANY DAMAGE CAUSED TO EXISTING
CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.
ASSOCIATED APPURTENANCES: REMOVE ALL
ELECTRICAL APPURTENANCES (DISCONNECTS,
STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH
ITEMS TO BE REMOVED INCLUDING EQUIPMENT TO BE
REMOVED BY OTHERS.
KNOCKOUT PLUGS AND COVERS: ALL CONDUIT
REMOVED SHALL BE REMOVED IN ITS ENTIRETY,
INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING
HARDWARE, ETC. PROVIDE CONDUIT PLUGS AND
BLANKS FOR ALL OPENINGS CREATED BY THE
REMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES
FOR ALL OPENED OUTLET BOXES CREATED BY THE
REMOVAL OF EQUIPMENT AND/OR DEVICES
DEMOLISHED MATERIALS: ALL MATERIALS REMOVED
UNDER DEMOLITION, NOT TO BE RELOCATED OR
DESIGNATED TO BE TURNED OVER TO THE OWNER,
SHALL BECOME THE PROPERTY OF THE CONTRACTOR
AND SHALL BE REMOVED COMPLETELY FROM THE SITE.
SCHEDULE OUTAGES: ALL WORK AND ALL POWER
OUTAGES IN THE EXISTING BUILDING SHALL BE
SCHEDULED AT TIMES CONVENIENT TO THE OWNER.
NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING
OFF ANY CIRCUITS.
KPM KPM JEB
12815758
G E
N E
R A
L
N
O T
E S
L
E G
E N
D
A
B B
R E
V I A
T I O
N S
AS NOTED
E-001
A B
G H I
E F
J
D
CR
CR
CR
CR
CR
LPA-32
LPA-34
LPA-36
LPA-38
LPA-19
ETR PANEL "L"
ETR PANEL "LPA"
ETR PANEL "MDP"
V D
LPA-21
101 102
103 105
106108
R E
P A
IR
R
O O
F A
N D
A P
P
LY
M A
S O
N R
Y S
E A
LE
R
B
9, M
C A
S C
H E
R R
Y P
O
IN
T, N
C
WALKER
i n c o r p o r a t e d
ARCHITECTURE
252-636-8992(fax)
PO BOX 541, NEW BERN, NC 28563
252-636-8778
GROUPthe
KPM KPM JEB
12815759
N E
W
W
O R
K
F
L O
A
N
AS NOTED
E-101
TN
PN
NEW WORK FLOOR PLAN
SCALE: 1/8" = 1'-0"
A4 1/8" = 1'-0"
5'0'5' 10' 20'
EXISTING LIGHT FIXTURED RETAINED DURING DEMOLITION. REWORK
EXISTING LIGHTING CIRCUIT TO CONTROL LIGHT FIXTURES AS INDICATED.
PROVIDE ALL REQUIRED RACEWAY, OUTLET BOXES, CABLING ETC. FOR A
COMPLETE AND USABLE SYSTEM. ALL CONDUITS SHALL BE HONE RUN TO
COMM RACK/BACKBOARD LOCATION INDICATED. TERMINATE AND TEST ALL
CABLING PER TIA AND BASE STANDARDS. COORDINATE EXACT
REQUIREMENTS AND LOCATIONS WITH OWNER PRIOR TO INSTALLATION.
REFER TO ARCHITECTURAL SHEETS D-101 AND A-101 FOR WORK TO BE
PROVIDED FOR RECEPTACLES AND SWITCHES.
NOTES THIS SHEET
06-22-20
REFER TO ARCHITECTURAL SHEETS D-104 AND A-104 FOR LIGHTNING PROTECTION WORK.
LIGHTNING PROTECTION NOTE:
REFER TO ARCHITECTURAL SHEETS D-102 AND A-102 FOR LIGHT FIXTURE REPAIRS.
LIGHTING NOTE:
P A
IR
R
O O
F A
N D
A P
P
LY
M A
S O
N R
Y S
E A
LE
R
B
9, M
C A
S C
H E
R R
Y P
O
IN
T, N
C
WALKER
i n c o r p o r a t e d
ARCHITECTURE
252-636-8992(fax)
PO BOX 541, NEW BERN, NC 28563
252-636-8778
GROUPthe
RECEPTACLE
RECEPTACLE
PULL-DOWN REEL
COXREEL C-L350-5012-B, OR EQUAL
MOUNT ON WALL 72" AFF
PENDANT OUTLET BOX WITH A 20A,
120V, DUPLEX RECEPTACLE.
MOUNTING:
PENDANT
MOUNTED
OUTLET BOX
RECEPTACLES:
CABLE:
DESCRIPTION:
REEL:
50', #12/3 TYPE SJ.
CABLE GRIP
CABLE
WALL
JUNCTION BOX
MOUNTED TO WALL
FOR HARDWIRE
CONNECTION
CABLE
CR
PROVIDE
RETRACTABLE CORD
STOPPER
PROVIDE RETRACTABLE
CORD STOPPER AT CEILING
PANELBOARD LPA SCHEDULE
225 MCB, 208/120 VOLT, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNT, GROUND BUS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)
LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
RM 1 REC. * 20/1P 1 2 20/1P * RM 1 LIGHTS
RM 1 REC. * 20/1P 3 4 20/1P * RM 1 LIGHTS
RM 1 REC. * 20/1P 5 6 20/1P * RM 1 LIGHTS
RM 1 REC. * 20/1P 7 8 20/1P * RM 1 LIGHTS
RM 1 REC. & OUTSIDE * 20/1P 9 10 20/1P * RM 2 LIGHTS
RM 2 REC. * 20/1P 11 12 20/1P * RM 2 LIGHTS
RM 2 REC. * 20/1P 13 14 20/1P * RM 2 LIGHTS
PARTS WASHER * 20/1P 15 16 20/1P * RM 2 LIGHTS
PARTS WASHER * 20/1P 17 18 20/1P * RM 4 LIGHTS
CORD REEL 3.0 20/1P 19 20 20/1P * RM 5 LIGHTS
RECEPTACLES 4.5 20/1P 21 22 20/1P * RM 6 LIGHTS
RECEPTACLES * 20/1P 23 24 20/1P *
RM 8,10,11,12,13 LTS
RM 5 REC. * 20/1P 25 26 20/1P * OUTSIDE LIGHTS
RM 5 REC. * 20/1P 27 28 20/1P * PAINT STORAGE RM
RM 6 REC. * 20/1P 29 30 20/1P * BOILER & VAULT LTS
RM 6 REC. * 20/1P 31 32 20/1P 3.0 CORD REEL
DRUG TEST REC. * 20/1P 33 34 20/1P 3.0 CORD REEL
DRUG TEST REC. * 20/1P 35 36 20/1P 3.0 CORD REEL
SONIC CLEANER * 20/3P 37 38 20/1P 3.0 CORD REEL
* 40 20/1P * EXISTING LOAD
* 42 20/1P * RTAC REC.
NOTES:
EXISTING PANELBOARD IS CHALLENGER "POWERMASTER" SERIES
* INDICATES EXISTING LOAD TO REMAIN
BOLD INDICATES NEW LOAD AND CIRCUIT BREAKER AS INDICATED
POWER CORD REEL
COMPRESSED AIR
CORD REEL (SEE
MECHANICAL
DRAWINGS FOR
SPECIFICATIONS)
1-1/4"C TO CABLE TRAY
(4) 4 PAIR 24 AWG
COPPER CAT 6 UTP
(4) DUAL 8P8C JACKS
XXX A XXX
SECONDARY NMC1
(GREEN)
RTD & E (GREEN)
PRIMARY NMC1
(BLUE)
VOICE (GRAY)
XXX A XXX
FIRST FLOOR
COMM ROOM
ACCESSIBLE CEILING
1"C WITH (4)
CAT6 UTP
(TYP)
KPM KPM JEB
12815760
D E
T A
I L
S
A
N
E L
B O
A R
D
S
C H
E D
U L
E S
AS NOTED
E-501
06-22-20
TELECOMMUNICATIONS RISER DIAGRAM
NO SCALE
B2
COMBINATION TELEPHONE / DATA JACK
NO SCALE
A2 PULL-DOWN POWER CABLE REEL TYPE DETAIL
NO SCALE
A4
P A
IR
R
O O
F A
N D
A P
P
LY
M A
S O
N R
Y S
E A
LE
R
B
9, M
C A
S C
H E
R R
Y P
O
IN
T, N
C
WALKER
i n c o r p o r a t e d
ARCHITECTURE
252-636-8992(fax)
PO BOX 541, NEW BERN, NC 28563
252-636-8778
GROUPthe
75KW
PDU
ELEVATOR
DISC. SW.
100A/3/1, W/ FUSES
PANEL
'400'
400HZ
FREQ.
CONV.
PANEL
'DC'
24V DC
RECT.
EXISTING 500KVA,
12.47KV-208Y/120V
SUBSTATION TYPE
TRANSFORMER
EXISTING 4-WAY
OIL SWITCH
(15KV)
ELECTRICAL VAULT 1ST FLOOR
2ND FLOOR
EXISTING
PANEL
MDP-1
208/120V
3Ø, 4W
EXISTING
PANEL
MDP
208/120V
3Ø, 4W
EXISTING
PANEL
LPA
208/120V
3Ø, 4W
EXISTING
PANEL
L
208/120V
3Ø, 4W
EXISTING
PANEL
B
208/120V
3Ø, 4W
EXISTING
PANEL
A
208/120V
3Ø, 4W
EXISTING
PANEL
HVAC
208/120V
3Ø, 4W
EXISTING
PANEL
C
208/120V
3Ø, 4W
Ø N
GND
L N G
BLDG LOAD
EGC
3-PHASE,
4 WIRE SERVICE
SERVICE EQUIPMENT
BREAKER
UTILITY SUPPLY
TRANSFORMER
SOLIDLY
GROUNDED
SYSTEM
GROUND RISER DIAGRAM
NO SCALE
C4 TO GROUND RING CONDUCTOR
TO EXISTING FOUNDATION GROUNDING ELECTRODE
EGC
EXISTING POWER RISER DIAGRAM
NO SCALE
A2
KPM KPM JEB
12767087
R I S
I A
G R
A M
S
AS NOTED
E-502
| 12815729 |
| 12815730 |
| 12815731 |
| 12815732 |
| 12815733 |
| 12815734 |
| 12815735 |
| 12815736 |
| 12815737 |
| 12815738 |
| 12815739 |
| 12815740 |
| 12815741 |
| 12815742 |
| 12815743 |
| 12815744 |
| 12815745 |
| 12815746 |
| 12815747 |
| 12815748 |
| 12815749 |
| 12815750 |
| 12815751 |
| 12815752 |
| 12815753 |
| 12815754 |
| 12815755 |
| 12815756 |
| 12815757 |
| 12815758 |
| 12815759 |
| 12815760 |
| 12767087 |
File details come from the government source that posted it. Updated .