7 Plans_Bldg 131.pdf
PDF 32 MB Posted
- Attached to
- Repair Facility 131 Federal contract opportunity
- Solicitation number
- FA487721B0003
About this file
This document outlines a federal contract opportunity for facility renovation services. The Department of the Air Force Air Combat Command is soliciting proposals to reconfigure and renovate an existing facility at address 131. Renovations will include restroom and shower upgrades, communications equipment consolidation, entrance reconfiguration, exterior cleaning and painting, wet sprinkler system installation, fire alarm system replacement, new HVAC system, electrical system upgrades, life safety and ADA code compliance work, and security standard updates. Proposals are due by the date specified in solicitation number FA487721B0003. The renovation scope requires services across multiple construction disciplines.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 3-Revised C-500 sheet.pdf | ||
| RFI answers dated 04222021.xlsx | XLSX spreadsheet | |
| Amendment 3-WD-AZ20210032 dated 03052021.pdf | ||
| Solicitation Amendment FA487721B00030003 SF 30.pdf | ||
| Final Sign-In Sheet Site Visit Fac 131.xlsx | XLSX spreadsheet | |
| Amendment 2_ Attachment 2- Air Force Approval Memorandum.pdf | ||
| Amendment 2_ Attachment 1- Sheet M-001.pdf | ||
| Amendment 2- SF 30 Final.pdf | ||
| Solicitation Amendment FA487721B00030001 SF 30.pdf | ||
| Solicitation Amendment - FA487721B00030001.pdf | ||
| Solicitation - FA487721B0003.pdf | ||
| 8 Asbestos and LBP Survey Report.pdf | ||
| 6 DMAFB Design Guide.pdf | ||
| 3 AF Form 3052.pdf | ||
| 5 Specifications.pdf | ||
| 9 Contractor Environmental Guide_2019.pdf | ||
| 10 Submittal Register.xlsx | XLSX spreadsheet | |
| 1 Template of Contractor EAL.xls | XLS spreadsheet | |
| 4 Bid Schedule.pdf | ||
| 2 WD - AZ20210032 Jan 2021.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
06/10/20
06/10/20
1229367788C Text Box
SPECIAL NOTE:
Rooms 103 and 109 will remain occupied during all phases of construction. Special consideration and government coordination is required to perform construction activities in theses areas. Contractor shall ensure building systems including power, environmental conditioning, intruder detection and communication connectivity are continuous through the use of existing systems or temporary means. Notify government 30 day prior to any outages or construction activites affecting these spaces.
1229367788C Text Box
CONSTRUCTION NOTES:
1. The facility will remain occupied for the entire period of construction; so the Contractor shall make every reasonable effort to limit and minimize the effects of all construction operations on the occupied areas. At no time may access to any portion of the occupied facility be prevented.
2. Contractor shall provide a sequence of construction and phasing plan to accommodate facility and construction operations. Phasing provided is for general information and not intended to be final or a recommended solution.
3. Building systems shall remain operational for all occupied spaces. Contractor shall provide temporary building systems as necessary. Additionally, the existing Intruder Detection and Fire Alarm systems shall be protected and remain active, regardless of occupancy, until the new systems are placed-in-service.
4. Contractor shall provide and maintain temporary toilet facilities for building occupants. Provide toilets, lavatories/hand-wash stations, mirrors, toilet paper dispensers, paper towel dispenser, soap dispensers, and waste receptacles.
At a minimum, provide 2 mens and 2 womens toilets with one of each being ADA compliant, and 2 lavatories/hand-wash stations.
1229367788C Text Box Equip door with local audio alarm
GENERAL NOTES
1. EXISTING UTILITIES SHOWN ARE IN APPROXIMATE
LOCATIONS PER GIS INFORMATION PROVIDED BY DAVIS
MONTHAN AFB. SURVEY WAS NOT PERFORMED.
CONTRACTOR SHALL PROVIDE AF FORM 103 TO 355 CIVIL
ENGINEERING SQUADRON ALLOWING A MINIMUM OF 21
DAYS OF ADVANCE NOTICE FOR BASE OWNED UTILITY
LOCATIONS. ALLOW A MINIMUM OF 15 WORKING DAYS FOR
ALL UTILITY OUTAGES. UTILITY OUTAGE LASTING MORE
THAN 4 HOURS IN DURATION SHALL BE PERFORMED
DURING NON-DUTY HOURS AND WEEKENDS.
2. THE CONTRACTOR SHALL HAVE UTILITIES LOCATED BY
ARIZONA 811 (FORMERLY AZ BLUE STAKE) AT (602) 688-5900
LOCATING SERVICE PRIOR TO EXCAVATION.
3. THE CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS AND REQUIRED ELEVATIONS AT THE SUBJECT
SITE. VERIFY THE LOCATION AND SIZE OF EXISTING
UTILITIES BEFORE PROCEEDING WITH CONSTRUCTION
ACTIVITIES, INCLUDING UTILITY STRUCTURES, POINTS OF
CONNECTION, AND UTILITY CROSSINGS. NOTIFY THE
CONTRACTING OFFICER OF ANY DISCREPANCIES OR
EXCEPTIONS ENCOUNTERED PRIOR TO PROCEEDING. ANY
COSTS INCURRED AS A RESULT OF THE CONTRACTOR'S
FAILURE TO VERIFY EXISTING CONDITIONS PRIOR TO
BEGINNING CONSTRUCTION SHALL BE BORNE BY THE
CONTRACTOR.
4. THE CONTRACTOR SHALL HAVE A COMPLETE SET OF
APPROVED PLANS AND SPECIFICATIONS ON THE JOB SITE
WHENEVER CONSTRUCTION IS IN PROGRESS.
5. THE DRAWINGS INDICATE LOCATIONS, DIMENSIONS,
REFERENCES, AND TYPICAL DETAILS OF CONSTRUCTION.
THE DRAWINGS DO NOT INDICATE EVERY CONDITION.
WORK NOT FULLY DETAILED SHALL BE OF CONSTRUCTION
SIMILAR TO PARTS THAT ARE FULLY DETAILED. CONSULT
THE CONTRACTING OFFICER WITH ANY INQUIRIES THAT
MAY ARISE.
6. THE CONTRACTOR SHALL OBTAIN THE APPROPRIATE
APPROVALS AND CLEARANCES FROM THE CONTRACTING
OFFICER PRIOR TO PROCEEDING WITH CONSTRUCTION
ACTIVITIES. THE CONTRACTOR SHALL COORDINATE WITH
THE AUTHORITIES HAVING JURISDICTION TO CONFIRM
INSPECTION, TESTING, AND CERTIFICATION
REQUIREMENTS.
7. SAFETY STANDARDS AND REQUIREMENTS SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR AND COMPLIED
WITH AS SET FORTH BY OSHA.
8. THE CONTRACTOR SHALL HAVE THE APPROPRIATE
LICENSES TO PERFORM THE SPECIFIED WORK IN
CONFORMANCE WITH THE CITY OF TUCSON, STATE OF
ARIZONA AND THE US FEDERAL GOVERNMENT.
9. RECORD DRAWINGS IDENTIFYING AND ACCURATELY
LOCATING SUBSURFACE UTILITIES AND IMPROVEMENTS
AND NOTING AS-CONSTRUCTED CONDITIONS SHALL BE
PROVIDED BY THE CONTRACTOR AT THE END OF
CONSTRUCTION.
EROSION & SEDIMENT CONTROL NOTES
1. THE FOLLOWING CONSTRUCTION SEQUENCE IS
RECOMMENDED AS A GUIDELINE IN ORDER TO BEST
MINIMIZE THE POTENTIAL FOR EROSION AND
SEDIMENTATION CONTROL PROBLEMS:
a) CLEAR AND GRUB SUFFICIENTLY FOR INSTALLATION
OF TEMPORARY EROSION AND SEDIMENT CONTROL
(ESC) BEST MANAGEMENT PRACTICE MEASURES
(BMPS)
b) INSTALL TEMPORARY ESC BMPS, CONSTRUCTING
SEDIMENT TRAPPING BMPS AS ONE OF THE FIRST
STEPS PRIOR TO GRADING
c) CLEAR AND GRUB AS NEEDED FOR INSTALLATION.
d) PROTECT ALL PERMANENT STORMWATER FACILITIES
UTILIZING THE APPROPRIATE BMPS
e) INSTALL PERMANENT ESC CONTROLS, WHEN
APPLICABLE; AND,
f) REMOVE TEMPORARY ESC CONTROLS WHEN:
i. PERMANENT ESC CONTROLS, WHEN APPLICABLE, HAVE BEEN COMPLETELY INSTALLED
ii. ALL LAND-DISTURBING ACTIVITIES THAT HAVE THE
POTENTIAL TO CAUSE EROSION OR
SEDIMENTATION PROBLEMS HAVE CEASED; AND,
iii. LANDSCAPING AND ROCK MATERIALS HAVE BEEN
INSTALLED/RESTORED IN THE AREAS NOTED.
2. INSPECT ALL PAVEMENT SURFACES, AT THE END OF EACH
DAY. IF IT IS EVIDENT THAT SEDIMENT HAS BEEN TRACKED
OFF SITE, CLEANING IS REQUIRED. IF SEDIMENT REMOVAL
IS NECESSARY PRIOR TO PAVEMENT SURFACE WASHING,
IT SHALL BE REMOVED BY SHOVELING OR PICKUP
SWEEPING AND TRANSPORTED TO A CONTROLLED
SEDIMENT DISPOSAL AREA. IF FUGITIVE SOIL CONTINUES
TO BE TRACKED OFFSITE IN A PROBLEMATIC MANNER, THE
CONTRACTOR SHALL IMPLEMENT ADDITIONAL SEDIMENT
CONTROL BMPS TO MITIGATE THIS ISSUE.
3. RESTORE CONSTRUCTION ACCESS ROUTE EQUAL TO OR
BETTER THAN THE PRE-CONSTRUCTION CONDITION.
4. CONTROL FUGITIVE DUST FROM CONSTRUCTION ACTIVITY
IN ACCORDANCE WITH DAVIS-MONTHAN AIR FORCE BASE,
THE CITY OF TUCSON AND THE STATE OF ARIZONA OVER
THE PROJECT AREA. DO NOT USE WATER WHEN IT MAY
DAMAGE ADJACENT CONSTRUCTION OR CREATE
HAZARDOUS OR OBJECTIONABLE CONDITIONS, SUCH AS
ICE, FLOODING, AND POLLUTION. OIL APPLICATIONS FOR
DUST CONTROL ARE NOT ALLOWED.
5. STABILIZE EXPOSED UNWORKED SOILS (INCLUDING
STOCKPILES), WHETHER AT FINAL GRADE OR NOT, WITHIN
5 DAYS DURING THE REGIONAL WET SEASON (JULY 1
THROUGH SEPTEMBER 30) AND WITHIN 10 DAYS DURING
THE REGIONAL DRY SEASON (OCTOBER 1 THROUGH JUNE
30). SOILS MUST BE STABILIZED AT THE END OF A SHIFT
BEFORE A HOLIDAY WEEKEND IF NEEDED BASED ON THE
WEATHER FORECAST. THIS TIME LIMIT MAY ONLY BE
ADJUSTED BY THE CONTRACTING OFFICER.
6. PROTECT INLETS, DRYWELLS, CATCH BASINS AND OTHER
STORMWATER MANAGEMENT FACILITIES FROM SEDIMENT,
WHETHER OR NOT FACILITIES ARE OPERABLE.
7. INSPECT ON A REGULAR BASIS (AT A MINIMUM WEEKLY,
AND DAILY DURING/AFTER A RUNOFF PRODUCING STORM
EVENT) AND MAINTAIN ALL EROSION AND SEDIMENT
CONTROL BEST MANAGEMENT PRACTICES TO ENSURE
SUCCESSFUL PERFORMANCE OF THE MEASURES. NOTE
THAT INLET PROTECTION DEVICES SHALL BE CLEANED OR
REMOVED AND REPLACED BEFORE SIX INCHES OF
SEDIMENT CAN ACCUMULATE.
8. THE CONTRACTOR SHALL COMPLY WITH ALL
REQUIREMENTS FOR STORM WATER DISCHARGE
ASSOCIATED WITH CONSTRUCTION ACTIVITY, INCLUDING
OBTAINING THE APPROPRIATE PERMITS AND APPROVALS.
9. FILTER FENCE SHALL BE USED TO AID IN CONTAINING ANY
SEDIMENT ON THE SITE DURING CONSTRUCTION. STORM
DRAIN INLET PROTECTION SHALL BE USED ON ANY AND
ALL STORM DRAIN STRUCTURES, INCLUDING CATCH
BASINS AND DRYWELLS. THE CONTRACTOR SHALL KEEP
THE AREAS ADJACENT TO THE SITE FREE FROM DEBRIS.
10. PROVIDE A DESIGNATED, POSTED CONCRETE WASHOUT
AREA. THE CONCRETE WASHOUT SHALL NOT BE ALLOWED
TO DRAIN OFF THE SITE OR INTO ANY EXISTING OR FUTURE
STORM DRAINAGE FACILITIES. HARDENED CONCRETE
WASHOUT SHALL BE BROKEN UP AND REMOVED FROM THE
SITE.
11. LITTER, CONSTRUCTION DEBRIS, AND CONSTRUCTION
CHEMICALS THAT COULD BE EXPOSED TO STORMWATER
MUST BE PREVENTED FROM BECOMING A POLLUTANT
SOURCE IN STORM WATER DISCHARGES.
12. RETAIN THE DUFF LAYER, NATIVE TOPSOIL, AND NATURAL
VEGETATION IN AN UNDISTURBED STATE TO THE MAXIMUM
EXTENT PRACTICAL.
13. KEEP ROADS ADJACENT TO INLETS CLEAN.
14. STOCKPILE CONSTRUCTION MATERIALS (SUCH AS
TOPSOIL) ON-SITE AND KEEP THESE THESE ELEMENTS OFF
OF ROADWAY AND SIDEWALKS.
15. REMOVE TEMPORARY ESC BMPS WITHIN 30 DAYS AFTER
THE TEMPORARY BMPS ARE NO LONGER NEEDED.
PERMANENTLY STABILIZE AREAS THAT ARE DISTURBED
DURING THE REMOVAL PROCESS.
16. PROVIDE TEMPORARY EROSION AND SEDIMENTATION
CONTROL MEASURES TO PREVENT SOIL EROSION AND
DISCHARGE OF SOIL-BEARING WATER RUNOFF OR
AIRBORNE DUST TO ADJACENT PROPERTIES, ACCORDING
TO THE REQUIREMENTS OF DAVIS-MONTHAN AIR FORCE
BASE, THE CITY OF TUCSON AND THE STATE OF ARIZONA.
THE CONTRACTOR SHALL COMPLY WITH ALL
REQUIREMENTS FOR STORMWATER DISCHARGE
ASSOCIATED WITH CONSTRUCTION ACTIVITY, INCLUDING
OBTAINING THE APPROPRIATE PERMITS AND APPROVALS.
17. EROSION CONTROL MEASURES, IN ADDITION TO THOSE
INDICATED AS PART OF THESE PLANS, MAY BE REQUIRED
DUE TO UNFORESEEN CONDITIONS, IF THE MEASURES DO
NOT FUNCTION AS INTENDED, OR IF DAVIS-MONTHAN AIR
FORCE BASE, THE CITY OF TUCSON AND THE STATE OF
ARIZONA DETERMINE INDICATED MEASURES ARE
INADEQUATE.
DEMOLITION NOTES
1. MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN IN
SERVICE AND PROTECT THEM AGAINST DAMAGE DURING
DEMOLITION OPERATIONS. DO NOT INTERRUPT EXISTING
UTILITIES SERVING ADJACENT OCCUPIED OR OPERATING
FACILITIES UNLESS AUTHORIZED IN WRITING BY THE
CONTRACTING OFFICER. PROVIDE TEMPORARY SERVICES
DURING INTERRUPTIONS TO EXISTING UTILITIES, AS
ACCEPTABLE TO THE CONTRACTING OFFICER. OUTAGES
MAY BE SCHEDULED WITH A MINIMUM NOTICE OF 15
WORKING DAYS; OUTAGES LONGER THAN 4 HOURS IN
DURATION WILL REQUIRE WEEKEND AND AFTER HOURS
WORK.
2. COORDINATE DEMOLITION OPERATIONS WITH THE
CONTRACTING OFFICER, INCLUDING REQUIREMENTS AND
SCHEDULING.
3. COORDINATE EXTENT OF DEMOLITION WITH PROPOSED
IMPROVEMENTS. THE CONTRACTOR IS RESPONSIBLE FOR
REMOVING, AND RELOCATING IF NECESSARY, ANY ITEMS
NOT OTHERWISE NOTED THAT CONFLICT WITH THE
CONSTRUCTION OF THE PROPOSED IMPROVEMENTS. THE
CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER
OF ANY CONFLICTING ITEMS NOT SHOWN ON THE PLANS
THAT MUST BE REMOVED OR RELOCATED. FAILURE TO
NOTIFY THE BASE DOES NOT RELIEVE THE CONTRACTOR
OF COST RESPONSIBILITY FOR REMOVING REQUIRED
ITEMS.
4. COMPLY WITH HAULING AND DISPOSAL REGULATIONS OF
DAVIS-MONTHAN AIR FORCE BASE AND THE STATE OF
ARIZONA.
5. IF MATERIALS SUSPECTED OF CONTAINING HAZARDOUS
MATERIALS ARE ENCOUNTERED, DO NOT DISTURB;
IMMEDIATELY NOTIFY THE CONTRACTING OFFICER.
6. CONDUCT DEMOLITION ACTIVITIES AND DEBRIS REMOVAL
OPERATIONS TO ENSURE MINIMUM INTERFERENCE WITH
ADJACENT FACILITIES.
7. AREAS DISTURBED OR DAMAGED BY CONSTRUCTION
ACTIVITIES SHALL BE CONSTRUCTED OR RESTORED TO
ORIGINAL CONDITIONS OR BETTER, TO THE SATISFACTION
OF THE CONTRACTING OFFICER, AT THE CONTRACTOR'S
EXPENSE. THE CONTRACTOR IS RESPONSIBLE FOR
DOCUMENTING CONDITIONS PRIOR TO CONSTRUCTION
ACTIVITIES AND ANY DAMAGE THAT MAY OCCUR.
8. REMOVE DEMOLITION WASTE MATERIALS AND DEBRIS
FROM PROJECT SITE AND LEGALLY DISPOSE OF THEM IN
AN EPA-APPROVED LANDFILL ACCEPTABLE TO
DAVIS-MONTHAN AIR FORCE BASE AND THE STATE OF
ARIZONA.
EARTHWORK & GRADING NOTES
1. SITE PREPARATION, GRADING, EXCAVATION AND FILL
REQUIREMENTS BELOW THE PROPOSED IMPROVEMENTS,
EMBANKMENTS, AND UTILITY TRENCHING SHALL BE
COMPLETED IN CONFORMANCE WITH THE SPECIFICATIONS.
2. REFER TO ARCHITECTURAL DOCUMENTS FOR ADDITIONAL
INFORMATION REGARDING EXTERIOR DOOR LOCATIONS.
COORDINATE ARCHITECTURAL ELEVATIONS WITH SITE
GRADING.
UTILITY & DRAINAGE NOTES
1. DRAWING PLANS AND DETAILS INDICATE GENERAL
LOCATION AND ARRANGEMENT OF UNDERGROUND UTILITY
AND STORM DRAIN PIPING. LOCATION AND ARRANGEMENT
OF PIPING LAYOUT TAKE DESIGN CONSIDERATIONS INTO
ACCOUNT. INSTALL PIPING AS INDICATED, TO EXTENT
PRACTICAL. WHERE SPECIFIC INSTALLATION IS NOT
INDICATED, FOLLOW PIPING MANUFACTURER'S WRITTEN
INSTRUCTIONS AND REQUIREMENTS OF DAVIS-MONTHAN
AIR FORCE BASE AND THE CITY OF TUCSON.
2. FOR EACH TYPE OF PIPE, USE JOINING MATERIALS
RECOMMENDED BY PIPING SYSTEM MANUFACTURER,
UNLESS OTHERWISE INDICATED.
3. BURY ALL UTILITIES AT MINIMUM DEPTH TO ALLOW FOR A
MINIMUM COVER OF 36 INCHES (3 FEET) OR IN COMPLIANCE
WITH MANUFACTURER'S REQUIREMENTS, WHICHEVER IS
GREATER. THE CONTRACTOR SHALL COORDINATE WITH
THE CONTRACTING OFFICER FOR ALL REQUIREMENTS AND
TO CONFIRM THAT AN ADEQUATE DEPTH OF COVER IS
MAINTAINED OVER THE UTILITIES, INCLUDING CLEARANCES
BETWEEN THE VARIOUS UTILITIES.
4. CONTRACTOR SHALL MAINTAIN A MINIMUM TEN (10) FEET
OF HORIZONTAL SEPARATION BETWEEN WATER PIPE AND
PIPE CARRYING NON-POTABLE WATER. AT CROSSINGS,
PROVIDE A MINIMUM VERTICAL CLEARANCE OF 18 INCHES
BETWEEN WATER PIPE (ABOVE) AND PIPE CARRYING
NON-POTABLE WATER (BELOW). INSTALLATIONS FOR PIPE
CARRYING NON-POTABLE WATER MAY BE INSTALLED AT A
CLEARANCE LESS THAN THOSE STATED ABOVE IF THE
NON-POTABLE LINE IS SLEEVED. THE SLEEVE PIPE SHALL
BE ONE (1) SIZE LARGER THAN THE CONSTRUCTION PIPE.
THE SLEEVE SHALL BE AT LEAST TWENTY (20) FEET IN
LENGTH AND CENTERED ON THE CROSSING TO PROVIDE
FOR A MINIMUM HORIZONTAL SEPARATION OF TEN (10)
FEET EACH SIDE OF THE CROSSING, MEASURED
PERPENDICULAR TO THE CROSSED LINE. EACH END OF
THE SLEEVE SHALL BE SEALED WITH A FERNCO RUBBER
COUPLER.
5. CONTINUOUS WARNING TAPE SHALL BE INSTALLED AT A
DEPTH OF 12 INCHES BELOW THE BOTTOM OF THE
PAVEMENT SECTION OR A DEPTH OF 12 INCHES WHERE
THERE IS NO PAVEMENT PRESENT. INSTALL DIRECTLY
OVER UTILITY PIPE AND CONDUITS AND AT OUTSIDE OF
EDGE OF UNDERGROUND STRUCTURES. TRACER WIRE IS
ALSO REQUIRED DIRECTLY OVER THE PIPING.
6. FIELD QUALITY CONTROL SHALL COMPLY WITH THE
DAVIS-MONTHAN AFB REQUIREMENTS. INSPECT, TEST,
DISINFECT, AND CLEAN UTILITY LINES IN ACCORDANCE
WITH THE PROJECT SPECIFICATIONS.
7. UTILITIES SHALL BE STUBBED FIVE (5) FEET OUTSIDE OF
THE BUILDING. THE SITE CONTRACTOR SHALL
COORDINATE CONTINUATION OF UTILITY SERVICES FROM
THAT POINT AND UTILITY CONNECTIONS TO THE BUILDING
WITH THE BUILDING CONTRACTOR AND BUILDING PLANS. A
PLUG SHALL BE INSTALLED AT THE END OF SERVICE LINES
UNTIL SUCH TIME THAT SERVICE IS EXTENDED TO THE
BUILDING FOR CONNECTION.
8. REFER TO ELECTRICAL PLANS FOR INFORMATION
REGARDING SITE LIGHTING, POWER, AND
COMMUNICATIONS. COORDINATE REQUIREMENTS AND
SCHEDULING FOR POWER AND UTILITY INSTALLATIONS
WITH THE CONTRACTING OFFICER, INCLUDING TRENCH
EXCAVATION, BEDDING, AND BACKFILL REQUIREMENTS.
9. INSTALL PRESSURIZED UNDERGROUND PIPING WITH
RESTRAINED JOINTS AT HORIZONTAL AND VERTICAL
CHANGES IN DIRECTION. RESTRAINMENT SHALL COMPLY
WITH THE REQUIREMENTS OF DAVIS MONTHAN AFB.
CONTRACTOR TO VERIFY WATER MAIN PRESSURE PRIOR
TO BEGINNING WORK.
ABBREVIATIONS
APPROX APPROXIMATE
(E) EXISTING
FW FIRE WATER
G GAS LINE
OD OUTSIDE DIAMETER
SS SANITARY SEWER LINE
TYP TYPICAL
UGC COMMUNICATION LINE
UGE UNDERGROUND ELECTRICAL LINE
VIF VERIFY IN FIELD
W WATER LINE
SAWCUT AND REMOVE PAVEMENT
ASPHALT
CONCRETE
LIMITS OF CONSTRUCTION
WEED BARRIER
FIRE HYDRANT
VALVE
SILT FENCE
CLEAR MECHANICAL YARD OF VEGETATION
JACK AND BORE COMMUNICATIONS
EXISTING LEGEND:
PROPOSED LEGEND:
L E
A D
C
O N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E
R
E V
I S
E D
SCALE AS SHOWN
R E
P A
I
F
C
I L
I T
Y
D A
V I S
M
O N
T H
N
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C
O N
S U
L T
A N
T
S E
A L a s t
G r a y s o n
S t r e e t
S u i t e
S a n
A n t o n i o
T
X w w w c o f f m a n c o m p h
F r a z e e
R d
S u i t e
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
L
S
U B
M I T
T A
L
6/10/2020
Z G
G
N
L HA
R
SE
FO
RP
I ANO EL
T S
GE SI
N
ERE
D
E
L ATA S
I
TL
WFO
SA HI
I N
REE
NO
T E
45458
S NO
N
G
UGE
W
OHE
SS
X X
GAS LINE
WATER SERVICE LINE
FIRE WATER MAIN
SANITARY SEWER LINE
UNDERGROUND ELECTRICAL LINE
OVERHEAD ELECTRICAL LINE
ROCK LINED DRAINAGE SWALE
CONCRETE WALL
SECURITY FENCE
LIGHT POLE
POWER POLE
SANITARY SEWER MANHOLE
FIRE HYDRANT
VALVE
ELECTRICAL TRANSFORMER
TRAFFIC DIRECTIONAL ARROW
FW
LP
SSMH
FH
PP
C0.1
LEGEND AND
NOTES
FH
CONDUITS UNDER S. HERKY BLVD.
UNDERGROUND ELECTRIC LINE
WATER LINE
W
UGE
LANDSCAPED AREA
CONSTRUCTION LIMITS
http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text
AUGUST, 1991
AutoCAD SHX Text
DOWL ENGINEERS
AutoCAD SHX Text
SCOTT J. RICE
AutoCAD SHX Text
CREATED BY
S HERKY BLVD
J A
M M
W
Y
BLDG.
BLDG.
BLDG.
BLDG.
BLDG.
C A
N O
P Y
SHED
(E) LANDSCAPE
(E) PAD
MOUNTED
ANTENNA
(E) LIGHT POLE (TYP)
(E) CONCRETE PADS
WITH MECHANICAL
EQUIPMENT
(E) CONC. MAINTENANCE APRON
(E) WALL
(E) WALLS
(E) CONC. PAD
W/ MECH. EQUIP.
E
S
I D
E W
A L K
(E) SIDEWALK
(E) CONC
(E) GATE
(E) CHAIN
LINK FENCE
(TYP)
(E) ROCK LINED DITCH
(E) GATE
(E) ASPHALT
(E) PAD MOUNTED
TRANSFORMER
(E) GATE
(E) LANDSCAPE(E) LANDSCAPE
(E) AC PARKING LOT
(E) AC PARKING LOT
(E) LANDSCAPE
(E)
LANDSCAPE
(E) WALL
(E) FIRE HYDRANT (TYP)
(E)
LANDSCAPE
(E) 5' SIDEWALK,
LOCATION APPROX
(E) 5' SIDEWALK,
LOCATION APPROX
402020 10
FEETSCALE:
1 INCH = 20
AS-BUILT STATEMENT
THE EXISTING INFORMATION SHOWN ON THESE PLANS IS PER THE
AS-BUILT DRAWINGS PROVIDED BY DAVIS-MONTHAN AIR FORCE
BASE. SITE IMPROVEMENTS AND UTILITY LOCATIONS SHOWN ON
THIS DRAWING ARE APPROXIMATE ONLY. PRIOR TO BEGINNING
ANY CONSTRUCTION, THE CONTRACTOR SHALL VERIFY THE
EXISTING SITE CONDITIONS AND EXACT LOCATION OF EACH
UTILITY. THE CONTRACTOR SHALL CONTACT THE CONTRACTING
OFFICER AND ENGINEER IF DISCREPANCIES ARE NOTED.
CONTRACTOR SHALL CONTACT AZ BLUE STACK PRIOR TO
DIGGING TO LOCATE COMMERCIALLY OWNED UTILITIES.
ADDITIONALLY, CONTRACTOR SHALL SUBMIT AF FORM 103 TO 355
CIVIL ENGINEERING SQUADRON TO MARK ALL BASE OWNED
UTILITIES. ALLOW MINIMUM OF 21 DAYS TO PROCESS AF FORM 103
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C
O N
S U
L T
A N
T
S E
A L s t
G r a y s o n
S t r e e t
S u i t e
S n t o n i o
T
X w w w c o f f m a n c o m
F r a z e e
R d
S u i t e
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
B
M I T
T A
L
6/10/2020
Z G
G
N
L HA
R
SE
FO
RP
I ANO EL
T S
GE SI
N
ERE
D
E
L ATA S
I
TL
WFO
SA HI
I N
REE
NO
T E
45458
S NO
N
GENERAL NOTES
KEY NOTES
1. DEMOLISH EXISTING CURB TO MATCH LIMITS
OF DEMOLISHED PAVEMENT.
2. CONTRACTOR TO ALIGN PROPOSED
EXCAVATION FOR UTILITIES ROUTING WITH
EXISTING CONCRETE SIDEWALK PANEL.
ONLY DEMOLISH WHOLE PORTIONS OF
EXISTING PANEL.
3. REMOVE AND SALVAGE LANDSCAPING AND
ROCK MATERIALS FOR RESTORATION.
4. JACK AND BORE COMMUNICATION CONDUITS
UNDER S. HERKY BLVD.
5. CONTRACTOR SHALL BACKFILL AND
STABILIZE/RESTORE TRENCH SURFACE
WITHIN 72 HOURS OF COMPLETING THE
UTILITY WORK AND/OR INSPECTION.
6. CLEAR MECHANICAL YARD OF VEGETATION.
7. EXISTING PAD MOUNT TRANSFORMER TO BE
DEMOLISHED. PROTECT EXISTING PAD AND
CONDUCTORS TO REMAIN FOR REUSE. SEE
ELECTRICAL PLAN FOR MORE INFORMATION.
8. DEMOLISH PAD MOUNT TRANSFORMER,PAD,
AND SECONDARY CONDUCTORS TO EXISTING
SERVICE ENTRANCE. SEE ELECTRICAL PLANS
FOR MORE INFORMATION.
9. PROTECT EXISTING UNDERGROUND POWER.
SEE ELECTRICAL PLANS FOR MORE
INFORMATION.
10. SAWCUT AND REMOVE EXISTING ASPHALT
PAVEMENT.
11. CONTRACTOR STAGING AREA. TEMPORARY
POWER IS NOT AVAILABLE.
12. LIMITS OF CONSTRUCTION
13. INSTALL SILT FENCE PER DETAIL 6, SHEET
C-500
14. REMOVE AND SALVAGE LANDSCAPING
MATERIALS FOR RESTORATION
1. SURVEY AND UTILITY LOCATES WERE NOT
PERMITTED DURING PROJECT DESIGN.
CONTRACTOR SHALL PERFORM UTILITY
LOCATES IN ACCORDANCE WITH THE BASE
PROCEDURES AND EXCAVATE WITH CAUTION. IF
THE CONTRACTOR DISCOVERS ADDITIONAL
UTILITIES WITHIN THE EXCAVATION AREA, THEY
WILL NOTIFY THE CONTRACTING OFFICER
IMMEDIATELY. CONTRACTOR SHALL NOT
INTERRUPT UTILITIES SERVICES WITHOUT
EXPRESSED PERMISSION FROM THE
CONTRACTING OFFICER.
2. COORDINATE ROAD CLOSURES (INCLUDING
PARKING AREAS) WITH DMAFB CIVIL
ENGINEERING. ALLOW A MINIMUM OF 15
WORKING DAYS FOR ROAD CLOSURES.
3. CONTRACTOR MUST VERIFY ELEVATIONS OF
EXISTING UTILITIES AT ALL UTILITY CROSSINGS.
IF CONFLICT EXISTS CONTRACTOR SHALL
RELOCATE UTILITIES AS NECESSARY AND
NOTIFY DMAFB CIVIL ENGINEERING.
EXISTING CONDITIONS & DEMOLITION PLAN
C1.0
EXISTING
CONDITIONS &
DEMOLITION
PLAN
AutoCAD SHX Text
LP
AutoCAD SHX Text
PP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
FH
AutoCAD SHX Text
FH
AutoCAD SHX Text
SSMH
AutoCAD SHX Text
SSMH
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
FH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FH
AutoCAD SHX Text
COMM
AutoCAD SHX Text http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text
AUGUST, 1991
AutoCAD SHX Text
DOWL ENGINEERS
AutoCAD SHX Text
SCOTT J. RICE
AutoCAD SHX Text
CREATED BY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C1.0
1"=20'
S HERKY BLVD
J A
M M
W
Y
BLDG.
BLDG.
BLDG.
BLDG.
BLDG.
C A
N O
P Y
SHED
(E) LANDSCAPE
(E) PAD
MOUNTED
ANTENNA
(E) LIGHT POLE (TYP)
(E) CONCRETE PADS
WITH MECHANICAL
EQUIPMENT
(E) CONC. MAINTENANCE APRON
(E) WALL
(E) WALLS
(E) CONC. PAD
W/ MECH. EQUIP.
E
S
I D
E W
A L K
(E) SIDEWALK
(E) CONC
(E) GATE
(E) CHAIN
LINK FENCE
(TYP)
(E) ROCK LINED DITCH
(E) GATE
(E) ASPHALT
(E) PAD MOUNTED
TRANSFORMER
(E) GATE
(E) LANDSCAPE(E) LANDSCAPE
(E) AC PARKING LOT
(E) AC PARKING LOT
(E) LANDSCAPE
(E)
LANDSCAPE
(E) WALL
(E) FIRE HYDRANT (TYP)
(E)
LANDSCAPE
(E) 5' SIDEWALK,
LOCATION APPROX
(E) 5' SIDEWALK,
LOCATION APPROX
UGC
UG
C
UG
C
UG
C
UG
C
UG
C
UG
C
UG
C
UG
C
UGC
UGC UGC
UGC
W W
W
WALL MOUNTED FDC
~78 LF 8" C900 PVC LATERAL,
3.0' MINIMUM COVER
33' ATFP
BUFFER LINE
(3) 4" CONDUITS FOR
TELECOMMUNICATIONS
PER DETAIL 8, SHEET C-501
33.0'
33.0'
33.0'
R
R
R
R
R
R
R
R=33.0'
(1) 8"x8"x8" TEE PER DETAIL
3, SHEET C-500
(1) GATE VALVE (MJxFL)
PER DETAIL 4, SHEET C-500
CONCRETE BLOCKING
~8LF 6" C900 PVC 3.0'
MINIMUM COVER
(1) 8"x8"x6" TEE PER DETAIL
3, SHEET C-500
(1) GATE VALVE (MJxFL)
PER DETAIL 4, SHEET C-500
CONCRETE BLOCKING PER
DETAIL 2, SHEET C-500
R
33.0'
R
CORE EXISTING STRUCTURE
C2.0
SITE
DEVELOPMENT
PLAN
GENERAL NOTES
KEY NOTES
1. REPLACE DEMOLISHED CONCRETE CURB AND GUTTER IN
KIND PER DETAIL 1, SHEET C-501.
2. REPLACE DEMOLISHED INTEGRATED CONCRETE
SIDEWALK PANEL IN KIND PER DETAIL 3, SHEET C-501
3. RESTORE ROCK AND LANDSCAPE AREAS TO EXISTING
CONDITIONS.
4. JACK AND BORE COMMUNICATION CONDUITS UNDER
SOUTH HERKY BLVD.
5. TRENCH BACKFILL FOR UTILITIES PER DETAIL 5, SHEET
C-500
6. SOURCE WATER LINE SIZE AS NOTED IN RECORD
DRAWINGS. CONTRACTOR TO FIELD VERIFY VALVE SIZE
TO BE 12" x 12" x 8".
7. REPLACE DEMOLISHED CONCRETE SIDEWALK PANEL IN
KIND PER DETAIL 4, SHEET C-501.
8. REPLACE PAVEMENT MARKINGS IN KIND WITH 4-INCH
WIDE WHITE PAINT. ALL STRIPING SHALL BE IN
ACCORDANCE WITH SECTION 4.1.7 OF ATTACHMENT C:
DMAFB DESIGN COMPATIBILITY GUIDELINES (2017).
9. INSTALL WEED BARRIER AND 2-INCH DEPTH MINIMUM OF
PEA GRAVEL.
10. LIMITS OF CONSTRUCTION
11. CONTRACTOR TO FIELD VERIFY EXISTING UTILITY
LOCATION AND DEPTH. MAINTAIN 18" VERTICAL
CLEARANCE AT CROSSING.
12. FIRE HYDRANT CLOW MEDALLION - MODEL F2545 PER
DETAIL 1, SHEET C-500. THE HYDRANT SHALL BE
INSTALLED AT A MAXIMUM OF 100LF FROM THE FDC,
TAKING FUTURE PARKED CARS INTO CONSIDERATION.
CONTRACTOR SHALL FLOW TEST FIRE HYDRANTS AND
PAINT BONNET PER NFPA 25. HYDRANT BARREL SHALL BE
PAINTED PER IAW DAVIS MONTHAN STANDARDS.
13. UTILITY PATCH PER DETAIL 5, SHEET C-501
14. CONTRACTOR TO RELOCATE GAS LINE AS NEEDED FOR
INSTALLATION THRUST BLOCKING
1. SURVEY AND UTILITY LOCATES WERE NOT PERMITTED
DURING PROJECT DESIGN. CONTRACTOR SHALL
PERFORM UTILITY LOCATES AND SANITARY SEWER
MAIN INVERTS IN ACCORDANCE WITH THE BASE
PROCEDURES AND EXCAVATE WITH CAUTION. IF THE
CONTRACTOR DISCOVERS ADDITIONAL UTILITIES
WITHIN THE EXCAVATION AREA, THEY WILL NOTIFY THE
CONTRACTING OFFICER IMMEDIATELY. CONTRACTOR
SHALL NOT INTERRUPT UTILITIES SERVICES WITHOUT
EXPRESSED PERMISSION FROM THE CONTRACTING
OFFICER.
2. CONTRACTOR SHALL PROVIDE NEW FIRE WATER LINE
AND COMMUNICATION SERVICES TO FACILITY 131. THE
CONTRACTOR SHALL ALSO PROVIDE A NEW FIRE
HYDRANT.
3. COORDINATE ROAD CLOSURES (INCLUDING PARKING
AREAS) WITH DMAFB CIVIL ENGINEERING. ALLOW A
MINIMUM OF 15 WORKING DAYS FOR ROAD CLOSURES.
4. CONTRACTOR MUST VERIFY ELEVATIONS OF EXITING
UTILITIES AT ALL UTILITY CROSSINGS. IF CONFLICT
EXISTS CONTRACTOR SHALL RELOCATE UTILITIES AS
NECESSARY AND NOTIFY DMAFB CIVIL ENGINEERING.
5. TRENCH UTILITIES PER DETAIL 5, SHEETC-500
402020 10
FEETSCALE:
1 INCH = 20
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C
O N
S U
L T
A N
T
S E
A L
E a s t
G r a y s o r e e t
S u i
S a n
A n t o n i o
T
X w w w c o f f m a n c o m
F r a z e e
R d
S u i t e
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
B
M I T
T A
L
6/10/2020
Z G
G
N
L HA
R
SE
FO
RP
I ANO EL
T S
GE SI
N
ERE
D
E
L ATA S
I
TL
WFO
SA HI
I N
REE
NO
T E
45458
S NO
N
SITE DEVELOPMENT PLAN
AutoCAD SHX Text
LP
AutoCAD SHX Text
PP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
FH
AutoCAD SHX Text
FH
AutoCAD SHX Text
SSMH
AutoCAD SHX Text
SSMH
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
FH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FH
AutoCAD SHX Text
COMM
AutoCAD SHX Text http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text
AUGUST, 1991
AutoCAD SHX Text
DOWL ENGINEERS
AutoCAD SHX Text
SCOTT J. RICE
AutoCAD SHX Text
CREATED BY
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C2.0
1"=20'
TYPICAL TRENCH BACKFILL DETAIL
1. CONTRACTOR TO PROVIDE
BLOCKING ADEQUATE TO
WITHSTAND FULL TEST
PRESSURE.
2. DIVIDE THRUST BY SAFE
BEARING LOAD TO DETERMINE
REQUIRED AREA (IN SQUARE
FEET) OF CONCRETE TO
DISTRIBUTE LOAD.
3. AREAS TO BE ADJUSTED FOR
OTHER PRESSURE
CONDITIONS.
4. PROVIDE TWO 1" MINIMUM
DIAMETER RODS ON VALVES
UP THROUGH 10" DIAMETER.
VALVES LARGER THAN 10"
REQUIRE SPECIAL TIE ROD
DESIGN.
5. USE 3000 PSI CONCRETE FOR
THRUST BLOCKING.
NOTES:
4" 6" 8"
10" 12" 14" 16" 24"
TEST
PRESSURE
PSISIZE DEAD
ENDS
A
THRUST AT FITTINGS IN POUNDS
14468 21758 30780 41355 53483 117608225
90°
BEND
45°
BEND
22.5°
BEND
11.25°
BEND
30°
BEND
B C D E F
11869 20460 30770 43529 58485 75636
166322
11073 16652 23558 31652 40934 90013
12010 16136 20868 45888
10484 2305560878
UNBALANCED CROSS PLUGGED CROSS PLUGGED CROSS
(USE COLUMN A) (USE COLUMN B) (USE COLUMN A)
BENDVALVEPLUGGED TEE
DEAD ENDOFFSETTEE
(USE COLUMN A)(USE COLUMN B)
12" MIN.
3" 2768225 3914 2118 1080 543 11263 15933 21407 27685
COL A COL A
COL A
COL A
FIRE HYDRANT,
THREE WAY, SIZE
5-1/4, 6" INLET
" M
IN
2"
CAST IRON
COVER WITH
"FIRE" EMBOSSED
2 PIECE CAST IRON VALVE
BOX. PROVIDE OPERATING
NUT EXTENSION WHEN
FINISH GRADE EXCEEDS 30"
ABOVE GATE VALVE NUT
6" GATE VALVE
(FLG x MJ)
8" FIRE MAIN
1/2" DIA. RODS
UNDISTURBED SOIL 2 - 3/4" DIA SHACKLE
RODS COATED
WITH BITUMASTIC
6" ADAPTOR
THRUST BLOCK
CONCRETE BLOCK
4"x16"x16"
WASHED AND SCREENED GRAVEL
3/4" NO FINES. FIELD TO EXTEND
APPROX. 2 FEET AROUND & ABOVE
HYDRANT BASE AND DOWN TO
UNDISTURBED SOIL AS SHOWN.
FINISH GRADE
HYDRANT STANDARD
DO NOT OBSTRUCT
HYDRANT DRAIN
UNDISTURBED SOIL
COL "A"
6" SQ. STL
PL, 1" THK
SIDE OF TRENCH
2" SCH 40. STL. PIPE FOR 8" DIA. MAIN AND LESS
3" SCH 40 STL. PIPE FOR 10" AND 12" DIA. MAIN
4" SCH 40 STL PIPE FOR 18" DIA. MAIN
PIPE
PLUGTHRUST BLOCK
1/2" RODS THRU 10"Ø
1" GREATER THAN 10"Ø
COL C-F
COL C-F
COL B
STEEL PLATE
TYPICAL THRUST BLOCKING DETAILSTYPICAL FIRE HYDRANT DETAIL
GATE VALVE DETAIL
CAST IRON FRAME
AND COVER; COVER
TO READ "WATER"
FINISHED GRADE 4" WIDE UNDERGROUND
UTILITY MARKING TAPE
1'- 6"
MI
N
1'- 0"
TY
P
UTILITY
GRAVEL
BEDDING
GR
AV
EL
B
ED
DI
NG
6" MI
N
1/2 O
D
AG
GR
EG
AT
E
BA
SE
C
OU
RS
E P-
NEW PAVEMENT
SECTION PER
DETAILS, SHEET C-501
6"
MIN
PIPE OD 6"
MIN
40" DIA x 8" DEEP
CONCRETE COLLAR
COMPACTED SUBGRADE
ADJUSTABLE CAST IRON
VALVE BOX, MIN 6" DIA
SERVICE STOP (BALL VALVE)
8" BUILDING LINE SERVICE
PROVIDE INSULATED 12 GA
COPPER TRACER WIRE
COMPACTED WASHED STONE
ARCH PATTERN BASE
WITH FOOT PIECE
FINISH GRADE
BUILDING SERVICE LINE
TEE
WATER/FIRE MAIN
DOUBLE STRAP
SERVICE SADDLE
20" MAX
4.5 ' M
IN
C
OV
ER
1"
6"
WATER SERVICE CONNECTION DETAIL
SILT FENCE
INSTALL
TRACER
WIRE
PVC BRASS BRASS PVC
PLASTIC METER BOX
COMPACTED
WASHED STONE
MAINLINE
GATE VALVE
USE DAVIS-MONTHAN BASE
STANDARD CONNECTION
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C
O N
S U
L T
A N
T
S E
A L s t
G r a y s o n
S t r e e t
S u i
S a n
A n t o n i o
T
X w w w c o f f m a n c o m r a z e e
R d
S u i
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
B
M I T
T A
L
6/10/2020
Z G
G
N
L HA
R
SE
FO
RP
I ANO EL
T
S
GE SI
N
ERE
D
EL ATA S
I
TL
WFO
SA HI
IN
REE
NO
T E
45458
S NO
N
C-500
DETAILS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-500
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TEMPORARY DEAD END PLUG
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-500
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-500
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-500
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-500
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-500
AutoCAD SHX Text
NTS
http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text
AUGUST, 1991
AutoCAD SHX Text
DOWL ENGINEERS
AutoCAD SHX Text
SCOTT J. RICE
JOINT SEALANT
GRADE3/8" TO 1/2" R
CAST-IN-PLACE CONCRETE
5/8" DIA. BACKER ROD
1/2
1 1 /4"
1/2"
1/2" PREMOLDED EXPANSION
JOINT FILLER
EXPANSION JOINT SEALANT DETAIL
1" R
5 1/2"1"
6 1/2"
1/2" R
18"
PAVEMENT
MATCH ADJACENT
PAVEMENT SLOPE
CONCRETE TRAFFIC
CURB AND GUTTER DETAIL
4"
EXISTING UNDISTURBED SUBGRADE
OR NEW STRUCTURAL FILL, COMPACT
UPPER 12" TO AT LEAST 95% OF MAX
DRY DENSITY (ASTM D1557)
PORTLAND CEMENT
CONCRETE (PCC)
3,000 PSI @ 28 DAYS
EXISTING PAVEMENT6"
EXISTING
BUILDING
INTEGRATED CONCRETE SIDEWALK
6"
12"
* MATCH EXISTING
MATCH
(E) RADIUS
SEE DETAIL
MATCH (E),
1.5% MAX SLOPE
UTILITY PATCH DETAIL
4"
EXISTING UNDISTURBED SUBGRADE
OR NEW STRUCTURAL FILL, COMPACT
UPPER 12" TO AT LEAST 95% OF MAX
DRY DENSITY (ASTM D1557)
PORTLAND CEMENT CONCRETE
(PCC) 3,000 PSI @ 28 DAYS, PER
AZDOT STD DWG C-05.20
SEE DETAIL
CONCRETE SIDEWALK DETAIL
EXISTING
SIDEWALK
EXISTING
GRAVEL
MATCH
EXISTING
ASPHALT PAVEMENT
(HMA CLASS 3/4"
PG64-22)
TACK COAT
TACK COAT
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C
O N
S U
L T
A N
T
S E
A L s t
G r a y s o n
S t r e e t
S u i
S a n
A n t o n i o
T
X w w w c o f f m a n c o m r a z e e
R d
S u i
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
B
M I T
T A
L
6/10/2020
Z G
G
N
L HA
R
SE
FO
RP
I ANO EL
T
S
GE SI
N
ERE
D
EL ATA S
I
TL
WFO
SA HI
IN
REE
NO
T E
45458
S NO
N
C-501
DETAILS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-501
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-501
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-501
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-501
AutoCAD SHX Text
NTS
AutoCAD SHX Text
AutoCAD SHX Text C-501
AutoCAD SHX Text
AutoCAD SHX Text C-501
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text C-501
AutoCAD SHX Text
NTS
http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text
AUGUST, 1991
AutoCAD SHX Text
DOWL ENGINEERS
AutoCAD SHX Text
SCOTT J. RICE
CENTER
FUEL TANKS
MAIN
HQ
HOUSING
12 AF
GATE
41101, 41102
COMMISSARY
OFFICE
FAMILY
VISITOR
COURSE
ANTENNA FARM
TRAINING
FAMCAMP OVERFLOW
MOTORCYCLE
GYM
HAEFFNER
SUNGLOW RD
T
H
S
T
T
H
S
T
T
H
S
T
Y
U
M
T
Z
A
P
P
E
R
D
R
Y
U
M
T
S
O
U
T
H
H
E
R
K
Y
B
V
D
1600800800 400
FEETSCALE:
1 INCH = 300
HAUL ROUTE
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C
O N
S U
L T
A N
T
S E
A L s t
G r a y s o n
S t r e e t
S u i
S a n
A n t o n i o
T
X w w w c o f f m a n c o m
F r a z e e
R d
S u i t e
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
B
M I T
T A
L
6/10/2020
Z G
G
N
L HA
R
SE
FO
RP
I ANO EL
T S
GE SI
N
ERE
D
E
L ATA S
I
TL
WFO
SA HI
I N
REE
NO
T E
45458
S NO
N
T1.0
HAUL ROUTE
MATCH LINE - SEE THIS SHEET
MATCH LINE - SEE THIS SHEET
HAUL ROUTE
AutoCAD SHX Text
HELIPAD
AutoCAD SHX Text
TAXIWAY D
AutoCAD SHX Text
NORTH RAMP
AutoCAD SHX Text
WEST RAMP
AutoCAD SHX Text
TAXIWAY C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONTRACTING OFFICE
AutoCAD SHX Text
MAIN GATE/ VISITOR CENTER ALL OTHER HOURS & WEEKENDS
AutoCAD SHX Text
SWAN GATE M-F 6:00AM TO 6:00PM
AutoCAD SHX Text
PROJECT SITE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text T1.0
AutoCAD SHX Text 1"=500' http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text
AUGUST, 1991
AutoCAD SHX Text
DOWL ENGINEERS
AutoCAD SHX Text
SCOTT J. RICE
AutoCAD SHX Text
CREATED BY
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text T1.0
1"=500'
APPLICABLE CRITERIA
· DAVIS MONTHAN AIR FORCE BASE, DESIGN COMPATABILITY GUIDE, 2017 EDITION
· 355 CS BASE DESIGN GUIDE, 2018 EDITION
· UFC 1-200-01, GENERAL BUILDING REQUIREMENTS, 2016 EDITION
· UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES, 2016 EDITION
· UFC 4-021-01, DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, 2010 EDITION
· UFC 4-010-05 DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, 2013 EDITION
· INTERNATIONAL BUILDING CODE (IBC), 2015 EDITION
· NFPA 1, FIRE CODE, 2015 EDITION
· NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION
· NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2016
EDITION
· NFPA 70, NATIONAL ELECTRICAL CODE, 2017 EDITION
· NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2016 EDITION
· NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2018 EDITION
· NFPA 101, LIFE SAFETY CODE, 2018 EDITION
· AIR FORCE MANUAL 14-304, 2016 EDITION
· DODM 5105.21 VOLUME 2, 2012 EDITION
· ARCHITECTURAL BARRIERS ACT STANDARDS, 2008 EDITION
· ICD/ICS 705 TECH SPEC VER 1.4, SEPTEMBER 2017
AUTOMATIC FIRE SUPPRESSION AND FIRE ALARM MASS NOTIFICATION SYSTEMS
THE FACILITY WILL BE PROVIDED WITH NEW FIRE ALARM / MASS NOTIFICATION AND FIRE SPRINKLER SYSTEMS.
OCCUPANCY CLASSIFICATION
· GROUPS B, S-1, S-2 OCCUPANCIES
ALLOWABLE AREA/HEIGHT/NUMBER OF STORIES, AND CONSTRUCTION TYPE
CONSTRUCTION TYPE: TYPE VB CONSTRUCTION
SPRINKLER PROTECTION: YES
OCCUPANCY TYPE: NON-SEPARATED MIXED-USE
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS
EXTERIOR SEPARATION REQUIREMENTS
THE SIZE AND HEIGHT OF THE EXISTING BUILDING ARE NOT CHANGING.
ALLOWABLE AVERAGE ROOF HEIGHT (IBC TABLE 504.3)
60 FEET
ACTUAL MAXIMUM HEIGHT TO ROOF PEAK 15 FEET
ALLOWABLE NUMBER OF STORIES (IBC TABLE 504.4)
3 STORIES
ACTUAL NUMBER OF STORIES 1 STORY
ALLOWABLE AREA (IBC TABLE 506.2) 36,000 SQ FT (GROUP S-1)
FIRE RATED CONSTRUCTION
CLASSIFICATION OF HAZARD OF CONTENTS (NFPA 101)
· LIGHT AND ORDINARY HAZARD CONTENTS (6.2.2.3)
OCCUPANT LOAD (NFPA 101 AND UFC 3-600-01)
· REFER TO THE LIFE SAFETY EGRESS PLAN.
ARRANGEMENT AND REQUIRED NUMBER OF MEANS OF EGRESS (NFPA 101)
· REFER TO THE LIFE SAFETY EGRESS PLAN.
CAPACITY OF MEANS OF EGRESS (NFPA 101)
· CAPACITY FACTOR
DOORWAYS, PASSAGEWAYS, RAMPS: 0.20 IN./PERSON (TABLE 7.3.3.1)
THE WIDTH OF ANY MEANS OF EGRESS, EXCEPT DOORS, SHALL NOT BE LESS THAN 36 IN. (7.3.4.1)
MEANS OF EGRESS COMPONENTS (NFPA 101)
· DOORS
WHERE PROVIDED, DOOR OPENINGS IN MEANS OF EGRESS SHALL NOT BE LESS THAN 36 IN CLEAR WIDTH AND AS
DETERMINED BY THE OCCUPANT LOAD FACTOR. (7.2.1.2.3.2)
· LOCKS, LATCHES, AND ALARM DEVICES
DOOR LEAVES SHALL BE ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
OCCUPIED. (7.2.1.5.1)
LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
OPERATION FROM THE EGRESS SIDE. (7.2.1.5.2)
A LATCH OR OTHER FASTENING DEVICE ON A DOOR LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN
OBVIOUS METHOD OF OPERATION AND THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS (INCLUDING
COMPLETE DARKNESS). (7.2.1.5.9)
THE RELEASING MECHANISM SHALL OPEN THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING OPERATION.
(7.2.1.5.9.2)
ILLUMINATION OF MEANS OF EGRESS (NFPA 101)
· ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED THROUGHOUT THE ENTIRE BUILDING, INCLUDING THE
UNOCCUPIED AREA. EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, AND CORRIDORS LEADING TO AN
EXIT. EXIT DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, CORRIDORS, AND WALKWAYS LEADING TO A
PUBLIC WAY. (7.8.1.1)
· THE FLOORS AND OTHER WALKING SURFACES WITHIN AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND
EXIT DISCHARGE SHALL BE ILLUMINATED AS FOLLOWS: (7.8.1.3)
1 FT-CANDLE FOR FLOORS
10 FT-CANDLE FOR STAIRS
0.2 FT-CANDLE DUE TO FAILURE OF ANY SINGLE LIGHTING UNIT
EMERGENCY ILLUMINATION OF MEANS OF EGRESS (NFPA 101)
· EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS AND
ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS
SHALL BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE
BURNING OUT OF A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES EMERGENCY ILLUMINATION.
(NFPA 70, 2014 EDITION SECTION 700.16)
· EMERGENCY ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED. EXIT ACCESS SHALL INCLUDE ONLY
DESIGNATED STAIRS, AISLES, AND CORRIDORS LEADING TO AN EXIT. EXIT DISCHARGE SHALL INCLUDE ONLY
DESIGNATED STAIRS, AISLES, CORRIDORS, AND WALKWAYS LEADING TO A PUBLIC WAY. (7.9.1.2)
· EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1-½ HOURS IN THE EVENT OF FAILURE OF NORMAL
LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS
THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL. ILLUMINATION LEVELS SHALL BE
PERMITTED TO DECLINE TO NOT LESS THAN AN AVERAGE OF 0.6-FT-CANDLE AND, AT ANY POINT, NOT LESS THAN 0.06
FT-CANDLE AT THE END OF 1.5 HOURS. A MAXIMUM-TO-MINIMUM ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL
NOT BE EXCEEDED. (7.9.2.1)
EXIT SIGNS (NFPA 101)
· EXIT SIGNS SHALL BE PROVIDED IN AREAS ACCESSIBLE TO THE PUBLIC AND WHERE AN EXIT IS NOT IMMEDIATELY
APPARENT. (7.10 AND 42.2.10)
· ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
REACH THE EXIT IS NOT READILY APPARENT TO THE OCCUPANTS. (7.10.1.5.1)
INTERIOR FINISH CLASSIFICATIONS (NFPA 101)
MEANS OF EGRESS (NFPA 101)
BUILDING CODE SUMMARY LIFE SAFETY CODE SUMMARY
ACTUAL AREA
14,600 SQ. FT.
BUILDING ELEMENT FIRE-RESISTANCE RATING
PRIMARY STRUCTURAL FRAME 0
BEARING WALLS 0
NON-BEARING WALLS AND PARTITIONS
- EXTERIOR
- INTERIOR
DEPENDANT ON FIRE SEPARATION
DISTANCE
FLOOR CONSTRUCTION 0
ROOF CONSTRUCTION 0
REQUIRED SEPARATION FIRE-RESISTANCE RATING
PROTECTION FROM HAZARDS
- SEPARATION OF GENERAL STORAGE
ROOMS FROM ADJACENT SPACES (NFPA
101 8.7 AND A38.3.2.1)
OCCUPANCY SEPARATION N/A
CODE COMPLIANCE
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C O
N S
U L T
A N
T
S E
A L s t
G r a y s o n
S t r e e t
S u i t e
S t o n i o
T
X w w w c o f f m a n c o m
F r a z e e
R d
S u i t e
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
A L
S
U B
M I T
T A
L
LS001
http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com
RISER
ROOM
CORRIDOR
CORRIDOR
MECHANICAL
BREAK
OFFICE
SHOWER
JAN
CONFERENCE
ROOM
BOILER
MEN
WOMEN
OFFICE
INTELLIGENCE
ADP-2
ADP-1
CLASSROOM
COMM
CLASSROOM
OFFICE
CLASSROOM
BRIEFING
AREA
SIMULATOR
OFFICE
MAINTENANCE
AREA
MAINTENANCE
AREA
OPEN
OFFICE
VESTIBULE
ENTRAPMENT
M.S.F. YARD
BUSINESS
130 FEET
(300 FEET MAX)
90 FEET
(100 FEET MAX)
BUSINESS
STORAGE
91 FEET
(400 FEET MAX)
29 FEET
(100 FEET MAX)
STORAGE
LEGEND
GENERAL NOTES
1. THE BUILDING IS SPRINKLERED AND IS UTILIZING THE
NON SEPARATED USE APPROACH.
# FEET
TRAVEL DISTANCE - TO EXIT
# FEET
COMMON PATH OF TRAVEL
(# FEET MAX)
# FEET
TRAVEL DISTANCE - TO EXIT
(# FEET MAX)
# FEET
COMMON PATH OF TRAVEL
(# FEET MAX)
COMPONENT
REQUIRED WIDTH
PROVIDED WIDTH
OCCUPANT LOAD
WIDTH FACTOR
COMPONENT
REQUIRED WIDTH
PROVIDED WIDTH
OCCUPANT LOAD
CAPACITY
WIDTH FACTOR
DOOR
0.2
32" CLEAR
43" CLEAR
DOOR
0.2
32" CLEAR
43" CLEAR
DOOR
0.2
32" CLEAR
32" CLEAR
DOOR
0.2
32" CLEAR
68" CLEAR
DOOR
0.2
32" CLEAR
60" CLEAR
EXIT SIGN
OCCUPANT LOADS
FIRST FLOOR LIFE SAFETY
PLAN
LS101
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C O
N S
U L
T A
N T
S
E A
L s t
G r a y s o n
S t r e e t
S u i
S a n
A n t o n i o
T
X w w w c o f f m a n c o m
F r a z e e
R d
S u i t e
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
8'0' 4' 16'
SCALE:1/8"=1'
F I N
B
M I T
T A
L
NORTH
DOOR
0.2
32" CLEAR
32" CLEAR
LIFE SAFETY FLOOR PLAN
OCCUPANT LOAD CALCULATIONS
SPACE OCCUPANCY USE
AREA
(SQ. FT.)
OCCUPANT LOAD FACTOR
(SQ. FT. / OCC.)
OCCUPANT LOAD
OPEN OFFICE - 129 BUSINESS
1,750 150 12
CONFERENCE ROOM - 126 ASSEMBLY
483 15 33
MECHANICAL - 119 STORAGE
398 500 1
BREAK 125 ASSEMBLY
122 15 9
BOILER - 118 STORAGE
80 500 1
JANITOR - 132 STORAGE
64 500 1
MEN - 115 BUSINESS
150 150 1
WOMEN - 114 BUSINESS
150 150 1
OFFICE - 112 BUSINESS
350 150 3
OFFICE - 110 BUSINESS
350 150 3
MAINTENANCE AREA - 123 STORAGE
211 500 1
MAINTENANCE AREA - 122 STORAGE
454 500 1
SIMULATOR OFFICE - 121 BUSINESS
219 150 2
BREIFING AREA - 120 BUSINESS
227 150 2
CLASSROOM - 117 EDUCATIONAL
454 20 23
OFFICE - 113 BUSINESS
378 150 3
CLASSROOM - 111 EDUCATIONAL
378 20 19
COMM - 109 STORAGE
311 500 1
MECHANICAL - 130 STORAGE
280 500 1
OFFICE - 107 BUSINESS
248 150 2
SHOWER - 106 BUSINESS
40 150 1
INTELLIGENCE - 108 BUSINESS
516 150 4
CLASSROOM - 102 EDUCATIONAL
655 20 33
ADP-1 - 103 BUSINESS
337 500 1
ADP-2 - 105 BUSINESS
350 500 1
CORRIDOR - 104 AND 124 BUSINESS
1,917 150 13
ENTRAPMENT 101 BUSINESS
67 150 1
VESTIBULE - 100 BUSINESS
254 150 2
RISER ROOM - 133 STORAGE 85
500 1
TOTAL
11,278
FIRE EXTINGUISHER (MINIMUM 2A:40B:C)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text
LS100
AutoCAD SHX Text 1/8"=1'-0"
SEQUENCE OF OPERATIONS
FIRE ALARM GENERAL NOTES
FIRE ALARM SEQUENCE OF
OPERATIONS MATRIX
FIRE ALARM
SYSTEMS NOTES
AND DETAILS
FA001
L E
N
S U
L T
A N
T
P R
O J E
C T
F
B N
V
I S
S U
E V
I S
E D
SCALE AS SHOWN
R E
P A
C
I L
I T
Y
D A
V I S
M
O N
T H
B
A
Z c
2020 MOCA Systems, Inc.
S E
A L
C
O N
S U
L T
A N
T
S E
A L s t
G r a y s o n
S t r e e t
S u i
S a n
A n t o n i o
T
X w w w c o f f m a n c o m
F r a z e e
R d
S u i t e
S a n
D i e g o
C
A
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
UNCLASSIFIED/ FOR OFFICIAL USE ONLY
F I N
B
M I T
T A
L
FAMNS
MONACO MAPP-X
AMP NAC 1
BOOSTER
BATTERIES BATTERIES
NAC
S
SLC
LOC/RDU
BATTERIES BATTERIES
TO DEDICATED
120 VAC
CIRCUIT
LOCKED OUT
AND TAGGED
TO DEDICATED
120 VAC
CIRCUIT
LOCKED OUT
AND TAGGED
TO DEDICATED
120 VAC
CIRCUIT
LOCKED OUT
AND TAGGED
TO DEDICATED
120 VAC
CIRCUIT
LOCKED OUT
AND TAGGED
S
R
TEXT
S
WF
SSCOF
TS
FIRE ALARM/ MNS RISER DIAGRAM
FIRE
FIRE
5'-0"
MAX
MANUAL
FIRE ALARM
PULL STATION
AUDIO /
VISUAL DEVICE
AUDIO DEVICE
FIRE ALARM/ MNS APPLIANCE MOUNTING HEIGHTS
AutoCAD SHX Text A. THE ACTIVATION OF MANUAL PULL STATIONS THE ACTIVATION OF MANUAL PULL STATIONS AND AREA SMOKE DETECTORS SHALL CAUSE FIRE ALARM OPERATION AS FOLLOWS: A.1. AUDIBLE APPLIANCES (SPEAKERS) TO SOUND A AUDIBLE APPLIANCES (SPEAKERS) TO SOUND A PRE-RECORDED MESSAGE THROUGHOUT THE FACILITY. A.2. VISUAL APPLIANCES (STROBE LIGHTS) TO VISUAL APPLIANCES (STROBE LIGHTS) TO ACTIVATE THROUGHOUT THE FACILITY. A.3. THE VISUAL INDICATION OF THE ALARM INITIATING THE VISUAL INDICATION OF THE ALARM INITIATING AREA OF INCIDENCE BY DEVICE TYPE AND LOCATION AT THE FIRE ALARM CONTROL PANEL. A.4. ACTIVATION OF AN AUDIBLE SIGNAL AT THE FIRE ACTIVATION OF AN AUDIBLE SIGNAL AT THE FIRE ALARM CONTROL PANEL. B. THE ACTIVATION OF FIRE SPRINKLER SYSTEM THE ACTIVATION OF FIRE SPRINKLER SYSTEM WATER FLOW SWITCHES SHALL CAUSE FIRE ALARM OPERATION AS FOLLOWS: B.A. FIRE ALARM OPERATION AS STATED ABOVE IN FIRE ALARM OPERATION AS STATED ABOVE IN PARAGRAPH A. B.B. WATER FLOW SWITCHES SHALL BE ZONED ON A WATER FLOW SWITCHES SHALL BE ZONED ON A PER SWITCH BASIS AND BY LOCATION. C. ACTIVATION OF A SPRINKLER SYSTEM ACTIVATION OF A SPRINKLER SYSTEM TAMPER SWITCH SHALL CAUSE A SYSTEM SUPERVISORY INDICATED BY A "TAMPER SUPERVISORY ALERT" AT THE FACP AND ANNUNCIATOR. D. DISPLAY INITIATING DEVICE CIRCUIT TROUBLE DISPLAY INITIATING DEVICE CIRCUIT TROUBLE CONDITIONS, SINGLE OPENS AND SINGLE GROUNDS, FOR EACH FIRE ALARM AND SUPERVISORY INITIATING CIRCUITS, AND PROVIDE A COMMON SYSTEM TROUBLE AT THE LOCAL FIRE ALARM CONTROL PANEL. E. DISPLAY NOTIFICATION APPLIANCE CIRCUIT DISPLAY NOTIFICATION APPLIANCE CIRCUIT TROUBLE CONDITIONS, SINGLE OPENS, SHORTS, AND SINGLE GROUNDS, FOR EACH CIRCUIT, AND A COMMON SYSTEM TROUBLE AT THE FIRE ALARM CONTROL PANEL. F. THE EFFECTIVE INTENSITY OF ALL THE EFFECTIVE INTENSITY OF ALL NOTIFICATION STROBES SHALL BE A MINIMUM FOR 15 CANDELA PRODUCING AN EQUIVALENT ILLUMINANCE OF 0.03 LUMENS / SW. FT. AT 50 FEET ON A HORIZONTAL AXIS. G. SYSTEM OPERATION SHALL BE LOW VOLTAGE SYSTEM OPERATION SHALL BE LOW VOLTAGE (24 VOLTS DC) INCLUDING ALL SUPERVISOR AND CONTROL FUNCTIONS. H. UPON LOSS OF 120 VAC OPERATING POWER, UPON LOSS OF 120 VAC OPERATING POWER, THE ENTIRE SYSTEM SHALL OPERATE ON STANDBY BATTERY POWER FOR 48 HOURS IN SUPERVISORY MODE AND THEN BE CAPABLE OF ALARM OPERATION FOR 15 MINUTES. I. THE TRANSFER TO STANDBY POWER SHALL THE TRANSFER TO STANDBY POWER SHALL NOT CAUSE A GENERAL ALARM TO BE GENERATED BUT SHALL BE INDICATED AT THE FIRE ALARM CONTROL PANEL AS A PRIMARY POWER LOSS TROUBLE. J. AUDIBLE AND VISUAL EVACUATION SIGNALS AUDIBLE AND VISUAL EVACUATION SIGNALS SHALL MEET THE REQUIREMENTS AND RECOMMENDATIONS OF NFPA-72 AND THE AMERICANS WITH DISABILITIES ACT (ADA). K. SYSTEM SHALL BE MONITORED BY THE SYSTEM SHALL BE MONITORED BY THE DAVIS MONTHAHN AFB MONACO D21 RADIO ALARM SIGNAL RECEIVING STATION.
AutoCAD SHX Text
1. THE FACILITY WILL REMAIN OCCUPIED FOR THE ENTIRE PERIOD OF THE FACILITY WILL REMAIN OCCUPIED FOR THE ENTIRE PERIOD OF CONSTRUCTION. CONSTRUCTION WORK SHALL BE PHASED TO LIMIT THE EFFECTS OF ALL CONSTRUCTION OPERATIONS ON THE OCCUPANTS. CONSTRUCTION WORK SHALL BE COORDINATED IN PHASES THAT WILL ENSURE THAT SCIF CERTIFICATION IS MAINTAINED AT ALL TIMES DURING CONSTRUCTION. 2. ALL WIRE AND CONDUIT MUST BE INSTALLED IN ACCORDANCE WITH PLANS ALL WIRE AND CONDUIT MUST BE INSTALLED IN ACCORDANCE WITH PLANS AND SPECIFICATIONS AND MUST MEET ALL APPLICABLE CODES. CONDUITS CONTAINING POWER LIMITED CIRCUITS SHALL BE PAINTED RED. BOXES AND COVERS CONTAINING POWER LIMITED CIRCUITS SHALL BE PAINTED RED. 3. ALL WIRE AND CABLE MUST BE RATED FOR FIRE ALARM USE PER THE ALL WIRE AND CABLE MUST BE RATED FOR FIRE ALARM USE PER THE LATEST REVISIONS OF THE NATIONAL ELECTRICAL CODE SECTION 760. THIS IS A POWER LIMITED FIRE ALARM SYSTEM. ALL CABLE MUST BE MARKED FPL, FPLR, OR FPLP. 4. THE FIRE ALARM CONTROL PANEL SHALL BE MOUNTED APPROXIMATELY THE FIRE ALARM CONTROL PANEL SHALL BE MOUNTED APPROXIMATELY 70" A.F. (TOP OF PANEL). 5. TO RETAIN WARRANTY, THE FIRE ALARM EQUIPMENT MUST BE POWERED TO RETAIN WARRANTY, THE FIRE ALARM EQUIPMENT MUST BE POWERED UP UNDER THE DIRECTION OF A QUALIFIED MANUFACTURER'S TECHNICIAN. 6. THE LIFE SAFETY SYSTEM IS A COMPLETELY SUPERVISED SYSTEM. THE LIFE SAFETY SYSTEM IS A COMPLETELY SUPERVISED SYSTEM. 7. INSTALLING CONTRACTOR SHALL COORDINATE ALL FIELD CHANGES WITH INSTALLING CONTRACTOR SHALL COORDINATE ALL FIELD CHANGES WITH THE FIRE ALARM CONTRACTOR INCLUDING CHANGES IN DEVICES, WIRE, CONDUIT RUNS AND OPERATION IN THE SYSTEM. FIRE ALARM CONTRACTOR SHALL NOT BE HELD RESPONSIBLE FOR UNDOCUMENTED CHANGES, OR THE RESULTS CAUSED BY THOSE CHANGES. 8. LIFE SAFETY AUDIBLE SHALL BE AUDIBLE THROUGHOUT THE SPACE AND LIFE SAFETY AUDIBLE SHALL BE AUDIBLE THROUGHOUT THE SPACE AND SHALL HAVE A SOUND PRESSURE LEVEL NOT LESS THAN 15db ABOVE AMBIENT NOISE LEVEL MEASURED AT 4'-0" ABOVE FINISHED FLOOR. 9. SLC CIRCUITS SHALL BE CLASS A IN CONFIGURATION AND SIGNALING, IDC SLC CIRCUITS SHALL BE CLASS A IN CONFIGURATION AND SIGNALING, IDC CIRCUITS SHALL BE CLASS B IN CONFIGURATION SLC CIRCUITS SHALL BE TWISTED PAIR NON-SHIELDED FP CABLE PER MANUFACTURERS REQUIREMENTS. 10. LOCATE ALL PULL STATIONS AND HORN/STROBE UNITS AT SPECIFIED LOCATE ALL PULL STATIONS AND HORN/STROBE UNITS AT SPECIFIED HEIGHTS PER NFPA 72. 11. SMOKE DETECTOR LOCATIONS ARE FOR REFERENCE ONLY AND SHALL BE SMOKE DETECTOR LOCATIONS ARE FOR REFERENCE ONLY AND SHALL BE INSTALLED PER NFPA 72. 12. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ROUGH-IN ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ROUGH-IN INSTALLATIONS WITH THE FIRE ALARM CONTRACTOR. 13. PER NFPA SPACING RECOMMENDATIONS, AREAS PROTECTED BY SMOKE PER NFPA SPACING RECOMMENDATIONS, AREAS PROTECTED BY SMOKE DETECTORS SHALL NOT HAVE ANY POINT ON THE CEILING GREATER THAN 0.7 TIMES THE LISTED SPACING OF THE DETECTOR (21 FT.) 14. ALL FIRE ALARM DEVICE SHALL BE RIGIDLY AND SECURELY FASTENED TO ALL FIRE ALARM DEVICE SHALL BE RIGIDLY AND SECURELY FASTENED TO WALLS OR CEILINGS. 15. NO SMOKE DETECTORS SHALL BE LOCATED CLOSER THAN 36" TO ANY AIR NO SMOKE DETECTORS SHALL BE LOCATED CLOSER THAN 36" TO ANY AIR REGISTER OR DIFFUSER. 16. NO DETECTOR SHALL BE LOCATED CLOSER THAN 18" TO ANY PART OF NO DETECTOR SHALL BE LOCATED CLOSER THAN 18" TO ANY PART OF ANY LIGHT FIXTURE. 17. INITIATING AND SIGNALING CIRCUITS ARE SEPARATE YET MAY BE RUN IN INITIATING AND SIGNALING CIRCUITS ARE SEPARATE YET MAY BE RUN IN SAME CONDUIT. 18. ALL CONDUCTORS SHALL BE LABELED BY CIRCUIT, IDENTIFIED BY WIRE ALL CONDUCTORS SHALL BE LABELED BY CIRCUIT, IDENTIFIED BY WIRE SIZE, AND ALL COLOR CODES SHALL MATCH. 19. FOR ALL SLC CLASS "A" SYSTEMS; ALL CIRCUIT FEED AND RETURNS FOR ALL SLC CLASS "A" SYSTEMS; ALL CIRCUIT FEED AND RETURNS SHALL BE SEPARATED BY A MINIMUM OF 6'-0". 20. ALL PANELS AND JUNCTION BOXES WILL BE LABELED "POWER LIMITED ALL PANELS AND JUNCTION BOXES WILL BE LABELED "POWER LIMITED FIRE ALARM SYSTEM" PER NEC 760. 21. WRITTEN OPERATING INSTRUCTIONS WILL BE LEFT AT THE FACP PER NFPA WRITTEN OPERATING INSTRUCTIONS WILL BE LEFT AT THE FACP PER NFPA 72 AND CLOSE OUT DOCUMENTATION WILL CONTAIN OR NOT BE LIMITED TO: 21.1. AN OWNER'S MANUAL AND MANUFACTURER'S PUBLISHED INSTRUCTIONS AN OWNER'S MANUAL AND MANUFACTURER'S PUBLISHED INSTRUCTIONS COVERING ALL SYSTEM EQUIPMENT 21.2.