7-Drawings.pdf
PDF 3 MB Posted
- Solicitation number
- 26/0089
- Issued by
- Harris County, Texas
About this file
This is a mechanical design and construction drawings package for the Harris Health Ben Taub Hospital Chilled Water Heat Exchanger Plate Refurbishment and System Upgrades project located at 1504 Ben Taub Loop, Houston, Texas 77030. The project involves a phased approach to upgrade the chilled water system infrastructure, including the refurbishment and replacement of plate and frame heat exchanger plates, replacement of pump impellers, updates to variable frequency drive (VFD) duty points, installation of new instrumentation and controls, and system balancing. The work is organized in three phases: Phase I involves installation of 581 new plates to replace existing 381 plates in one heat exchanger with existing plates prepared for reuse in Phase II; Phase II includes installation of refurbished 381 plates plus 200 additional new plates; Phase III involves final installation of refurbished plates with 200 additional new plates held as future spares. Key equipment modifications include updating pump duty points from original parameters (3,568-7,135 GPM) to new design parameters (4,000-8,000 GPM), installation of electromagnetic flow meters on chilled water piping, replacement of thermometers and pressure gauges with new sensors, and provision of 1-inch drain valves at heat exchanger connections. The project utilizes Bell & Gossett VSX-VSCS pumps with 100-125 horsepower motors and TRANTER GXP-205 plate and frame heat exchangers with capacities ranging from 22,497,700 to 25,030,267 BTUH.
The design includes comprehensive instrumentation and controls with direct digital control (DDC) logic, variable speed drives, temperature and pressure sensors, differential pressure transmitters, and flow meters throughout the system. The chilled water system is designed to operate continuously 24 hours per day with no automatic shutdown capability, utilizing a 2N utility pump configuration, N+1 heat exchanger configuration, and N+1 customer primary pump configuration. TECO supplies chilled water ranging from 40-43 degrees Fahrenheit with heat exchangers providing a 2-degree approach temperature to customer-side systems. The system incorporates sophisticated control sequences including automatic pump rotation based on run-hours, capacity staging algorithms based on tonnage and pump speed, and pressure control logic to maintain differential pressure setpoints. All piping connections require 2-piece stainless steel ball valves, and the system complies with 2021 International Building Code and 2021 Uniform Mechanical Code with City of Houston amendments. The estimated project budget is $2,100,000, with construction documents marked for interim review and issued for construction on October 28, 2025.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
*** choose ARCHITECT or ENGINEER *** from list in Family Types
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
F
IL
E N
A M
E
U S
E R
N A
M E
D A
T E
S T
A M
P
FOR REVIEW ONLY
P ag e P ro je ct N um be r
1111 Louisiana Street, 26th Floor Houston, TX 77002 pagethink.com
TEL 713 665 5665
CLIENT
PROJECT
ORIGINAL ISSUE
CONSULTANT TEAM PROFESSIONAL SEALS
PROJECT NUMBER
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:1
:3
P M
HARRIS HEALTH BT CHW UPGRADE
ISSUE FOR CONSTRUCTIONHARRIS HEALTH BT
422089.11
10/28/2025
1504 BEN TAUB LOOP
HOUSTON, TX 77030
.1
H
A R
R
IS
H E
A
LT
H B
T C
H W
U P
G R
A D
E
/2 8/
G -0
OCT 28 2025
Firm #15868
LC
MM
S
100100
G
~ ~MM
PHASE
PHWR
PH
PRIMARY HOT WATER RETURN
FLOW TRANSMITTER, FOOT, FEET
FOOT-POUND
ABBREVIATIONS
FT
FT LB
PREHEAT COIL
PARTS PER MILLION
PHC
PRS
PRV
PPM
PHWS
PRIMARY
PRESSURE
PRESSURE SWITCH
PRI
PRESS
PS
PSF
PLUMBINGPLBG
POUNDS PER SQUARE FOOT
PRIMARY HOT WATER SUPPLY
PRESSURE REDUCING STATION
PRESSURE REDUCING VALVE
PIPE SLEEVE
PIPE THREAD, PNEUMATIC TUBE
PSL
PSIG
PSIA
PTAC
PT
QUART
RELOCATED
QT
R
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PACKAGED TERMINAL AIR CONDITIONER
POUNDS PER SQUARE INCH GAUGE
POUNDS PER SQUARE INCH ABSOLUTE
POUNDS PER SQUARE INCHPSI
FURNACE, FURNISH
FULL VOLTAGE NON-REVERSING
FACE VELOCITY
FINNED TUBE RADIATION
FREEZING POINT
GALLON
GENERATOR, GENERAL
GAUGE (INSTRUMENT), GAGE (THICKNESS)
GLOBE VALVE
GALVANIZED IRON PIPE
GALVANIZED IRONGI
GAL
GEN
GLV
GIP
GA
FVNR
FVEL
FURN
FTR
FP
GATE VALVE
GALLONS PER HOUR
GLYCOL SUPPLY
GLYCOL RETURN, GRAINS
HOSE BIBB
HOSE CONNECTOR
HEATING COIL, HOSE CABINET
GTD
GPH
HB
HCONN
HC
GTV
GS
GR
GALLONS PER DAYGPD
GREATEST TEMPERATURE DIFFERENCE
GENERAL NOTES
RADIATOR
REFRIGERATION, REFRIGERANT
RECEIVER
RAD
RAC
REFR
RD
RCVR
RETURN
REDUCER
REVOLUTIONS
REFRIGERANT
RELATIVE HUMIDITY
ROUGHNESS
REFERENCE
RET
REV
RED
RFGT
RH
RGH
REF
ROOM AIR CONDITIONER
REHEAT COIL
REHEAT VALVE
RHC
RHG
RHV
RPM
RSL
RPS
RLL
ROOF TOP UNIT
RELIEF VALVE
SATURATION
SUPPLY AIR
SECOND
RTU
RV
SAT
SA
S
REFRIGERANT HOT GAS
REFRIGERANT LIQUID LINE
REVOLUTIONS PER MINUTE
REFRIGERANT SUCTION LINE
REVOLUTIONS PER SECOND
MERCURY
HEIGHT
HEAT PUMP, HIGH PRESSURE, HORSEPOWER
HANGER
HEAT EXCHANGER
HOUR
HIGH PRESSURE STEAM
HIGH PRESSURE DRIP TRAP
HIGH PRESSURE BOILER
HG
HGT
HPS
HPC
HPDT
HPB
HP
HGR
HEX
HR
HUMIDISTAT
HOT WATER
HOSE VALVE
HIGH TEMPERATURE HOT WATER
HUMIDITY SENSOR HIGH LIMIT
HUMIDITY SENSOR
HOT WATER RETURN
HOT WATER PUMP
HOT WATER CIRCULATING PUMP
HOT WATER COIL
HOT WATER BOILER
HSTAT
HWR
HWP
HWCP
HWC
HWB
HW
HVAC
HV
HTHW
HSH
HS
HIGH PRESSURE CONDENSATE
HEATING, VENTILATING AND AIR CONDITIONING
SPECIFIC GRAVITY, STEAM GAUGE
SHAFT HORSEPOWER
SENSIBLE HEAT GAIN
SENSIBLE HEAT
SENSIBLE HEAT RATIO
SG
SHP
SHG
SH
SHR
SEALANT
SEA LEVEL
SLEEVE
SENSOR
SUMP PUMP
SHWS
SLNT
SL
SLV
SMP
SNSR
SHWR SECONDARY HOT WATER RETURN
SECONDARY HOT WATER SUPPLY
SHUT OFF VALVE
STATIC PRESSURE
SPECIFICATION
SUPPLY
SOV
SP
SPEC
SPH
SPL
SPLY
SQUARE
STAINLESS STEEL
STEAM GENERATOR
SQ
SSP
SST
STGEN
SPS
STATIC PRESSURE HIGH LIMIT
STATIC PRESSURE LOW LIMIT
STATIC PRESSURE SENSOR
STAINLESS STEEL PIPE
SOLV SOLENOID VALVE
HYDRANT
INSTRUMENT AIR
INPUT/OUTPUT
HERTZ (FREQUENCY)
INVERT
INSTRUMENT
INSIDE DIAMETER
INDICATED HORSEPOWER
INCHES WATER COLUMN
IA
ID
ICW
I/O
HZ
HYD
IHP
INV
INSTR
IN WC
INFRARED
KELVIN [DEGREES]
IRON PIPE THREADED
IRON PIPE SIZE, INCHES PER SECOND
KILOWATT
POUNDS
THOUSAND FOOT-POUNDS
LEAVING AIR TEMPERATURE
KILOWATT HOUR
THOUSAND POUNDS
IR
K
KIP
KIP FT
LB
LAT
KWh
KW
IPT
IPS
IRON PIPEIP
INDUSTRIAL CITY WATER (NON-POTABLE)
SF SAFETY FACTOR, SQUARE FEET
HOT WATER SUPPLYHWS
RETURN AIRRA
HEADHD
A
AAV
SINGLE LINE
VALVE SYMBOLS
ABS
AC
AP
ACHKV
AD
AF
ADP
AFF
AHU
ACU
AMB
ANSI
AMP
APD
APR
APPROX
ASU
ASV
ATC
ATM
ATV
AS
ALT
COMBINATION BALANCING &
BALL VALVE
BUTTERFLY VALVE
DIAPHRAGM VALVE
CHECK VALVE
PLUG VALVE
SHUT-OFF VALVE
SINGLE LINEDOUBLE LINE
PIPE AND FITTING SYMBOLS
PIPE
WELDED JOINT
SCREWED JOINT
GROOVED END JOINT
(OR GENERIC SINGLE LINE)
STUB END OR FLANGE
FLANGED JOINT
MECHANICAL (BALL) JOINT
ADAPTER W/ FLANGE RING
GROOVED END
ADAPTER FLANGE
DOUBLE LINE
AV
AVG
B/B B&S
AWG
BAL
BBD
BARO PR
BF
BFV
BLDG
BFW
BFBP
BLR
BLW
BHP
BO
BOD
BLWDN
BS
BOS
BOP
GLOBE VALVE, SEALED STEM
GLOBE VALVE
CIRCUIT SETTER
MANUAL AIR VENT
BTU
BT WLD
BSTR
BW
BV
BTUH
°C
CA
C/C C-C
BYP
CAP
CC
CB
CD
CF
CCW
CFS
CH
CHW
CHWP
CHWPP
CFM
CACU
BSP
ADAPTER
FLANGED COUPLING
UNION
BRAIDED FLEXIBLE COUPLING
TEE
TEE, BRANCH TOWARD VIEWER
TEE, BRANCH AWAY FROM VIEWER
REDUCER - ECCENTRIC
REDUCER - CONCENTRIC
VERTICAL RUN ON PLAN
READ LEFT TO RIGHT
4" CWS
H W
R C
W R
H W
S
LOWER PIPE
BOP 12'-6" AFF
2" HWS
2" HWR
4" CWR
READ TOP TO BOTTOM
2" IA
4" HPS (F) *
2" DIR
2" DIS
BOP 13'-6" AFF
2" IW
C W
S
4" HPS (F) *
UPPER PIPE
BOP 13'-6" AFF
2" DIR
2" DIS
2" IW
2" IA
D
IS
IW IA H
A
F
IA
IW
DIS
HPS (F) *
HWS
HWR
CWR
D
IR
DIR
CWS
UPPER PIPE
NOTE:
AUV
TEMPERATURE CONTROL VALVE
CELSIUS [DEGREES]
AIR LINE
AUTOMATIC AIR VENT
AUTOMATIC CHECK VALVE
ACCESS PANEL
ACCESS DOOR, AREA DRAIN
AIR FILTER
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
AMBIENT
AIR PRESSURE DROP
AIR PRESSURE RETURN
AIR SEPARATOR
AIR SUPPLY VENT
ANGLE STOP VALVE
AUTOMATIC TEMPERATURE CONTROL
ATMOSPHERE
ATMOSPHERIC VENT
AUTOMATIC VENT
AIR VENT
AVERAGE
BELL & SPIGOT
BACK TO BACK
BALANCE
BOILER BLOWDOWN
ABSOLUTE
AIR CONDITIONING UNIT
ALTERNATING CURRENT, AIR CURTAIN
ALTITUDE
AMERICAN NATIONAL STANDARDS INSTITUTE
AMERICAN WIRE GAUGE
AMPERE
APPARATUS DEW POINT
APPROXIMATE
BAROMETRIC PRESSURE
BOTH FACES
BLOWOFF
CENTER TO CENTER
BLOW DOWN LINE
CAPACITY
COMPUTER AIR CONDITIONING UNIT
COMPRESSED AIR
COOLING COIL
BYPASS
BOTH WAYS
BALL VALVE
BRITISH THERMAL UNIT PER HOUR
BRITISH THERMAL UNIT
BUTT WELD
BOOSTER
BLACK STEEL PIPE
BOTH SIDES
BOTTOM OF STEEL
BOTTOM OF PIPE
BOTTOM OF DUCT
BELOW
BOILER
BUILDING
BRAKE HORSEPOWER, BOILER HORSEPOWER
BOILER FEED WATER
BOILER FEED BOOSTER PUMP
BUTTERFLY VALVE
CUBIC CENTIMETER
CONDENSATE DRAIN
CHEMICAL FEED
CUBIC FEET PER MINUTE
CUBIC FEET PER SECOND
CHILLER
CHILLED WATER
CHILLED WATER PUMP
CHILLED WATER PRIMARY PUMP
COUNTERCLOCKWISE
CATCH BASIN
STANDARD
STRAINER
STEAM
STC
STD
STR
STP
STM
SUCTION
SUPPLY
SAFETY VALVE
THROWAWAY
SUCT
SUP
SV
T T&P
TA
SOUND TRANSMISSION CLASS
STANDARD TEMPERATURE & PRESSURE
TEMPERATURE SENSOR
TEMPERATURE AND PRESSURE [VALVE]
THERMOCOUPLE OR TRAPPED CONDENSATE
TEMPERATURE, TEMPORARY
TCP
TCV
TC
TEMP
TD
TO FLOOR BELOW
THICK(NESS)
TUNNEL
TOP OF MANHOLE
TFB
THK
TMH
TNL
TR
TFA TO FLOOR ABOVE
TEMPERATURE CONTROL PANEL
TEMPERATURE CONTROL VALVE
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
LINEAR FEET
LENGTH
LATENT HEAT GAIN
LATENT HEAT
LEAVING DRY BULB TEMPERATURE
LOW PRESSURE BOILER
LOW PRESSURE ALARM SWITCH
LOW PRESSURE
LF
LG
LMTD
LPC
LPB
LPAS
LP
LHG
LH
LDBT
LOUVER
LEAST TEMPERATURE DIFFERENCE
LOW TEMPERATURE HOT WATER
LOW PRESSURE STEAM
LOW PRESSURE DRIP TRAP SET
MAXIMUM
MANUAL AIR VENT
MAKE UP AIR UNIT
LEAVING WATER TEMPERATURE
LOW WATER CUT-OFF
LEAVING WET BULB TEMPERATURE
MAX
LTD
MAV
MAU
LWT
LWCO
LWBT
LVR
LTHW
LPS
LPDT
LEAST MEAN TEMPERATURE DIFFERENCE
LOW PRESSURE CONDENSATE
TRANSFER
TUBE STEEL
UNIT HEATER
THERMOSTAT
TRANS
TS
U
UH
TSTAT
VARIABLE
VENT, VOLTS
VAPOR PRESSURE
VELOCITY
VENT, VENTILATION
VAP PR
VAR
V
VAV
VEL
VENT
HEAT TRANSFER COEFFICIENT
VARIABLE AIR VOLUME
VISCOSITY
WATT
WET BULB
VELOCITY PRESSURE
VFD
VISC
W
WB
VP
WATER COLUMN
WATER CHILLER
WATER GAGE
WALL HUNG, WATT HOUR
WATER COOLED
WBT
WC
WCHR
WG
WH
WCLD
WET BULB TEMPERATURE
VARIABLE FREQUENCY DRIVE
VERTICALVERT
MINIMUM
MOTOR CONTROL CENTER
MINIMUM CIRCUIT AMPACITY
MEAN EFFECTIVE TEMPERATURE
MOTOR DIRECT CONNECT
THOUSAND CUBIC FEET
MILES PER HOUR
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE
MOTOR OPERATED VALVE
MCC
MCA
MOCP
MPH
MPS
MPC
MP
MOV
MIN
MET
MDC
MCF
NOT APPLICABLE
MEAN TEMPERATURE DIFFERENCE
NOISE CRITERIA, NORMALLY CLOSED
MAKE-UP WATER
MEDIUM TEMPERATURE HOT WATER
NORMALLY OPEN, NUMBER
NOISE REDUCTION
NOISE REDUCTION COEFFICIENT
NOT TO SCALE
NOT IN CONTRACT
NR
NRC
NTS
NO
NA
MTD
NIC
NC
MU
MTHW
MALE PIPE THREADMPT
MAXIMUM OVERCURRENT PROTECTION
MEDIUM PRESSURE CONDENSATE
TOP TOP OF PIPE
MIXING BOXMB
WELDED
WATER LINE
WATER METER
WATER PUMP
WL
WLD
WM
WPD
WPR
WSP
WP
YARD, YARD DRAIN
WEIGHT
YEAR
YD
WT
YR
WATER PRESSURE DROP
WORKING PRESSURE DROP
WORKING STEAM PRESSURE
Z ZONE
OUTSIDE AIR
OIL GAUGE
OIL LEVEL
OUTSIDE DIAMETER
OVERFLOW DRAIN
OUTSIDE AIR FAN
OIL SWITCH
OIL PRESSURE
OVERFLOW ROOF DRAIN
OPERATING STEAM PRESSURE
OD
OGA
OLVL
OPRS
ORD
OS
OSP
OFD
OA
OAF
PUMP
OUNCE
PERCENT
PIPE ANCHOR
PUMPED CONDENSATE
POSITIVE, PROVIDED BY OTHER SECTION
PRESSURE DROP, PRESSURE DIFFERENTIAL
PUMPED CONDENSATE DISCHARGE
PUMP DISCHARGE
PUMP SUCTION
PRECOOL COIL
P
PA
PC
PCC
PD
PCD
PDISCH
PMPSCT
POS
OZ
OVERFLOWOVFL
PRESSURE GAUGE
PUMPED RETURN
PRESSURE SWITCH
PG
PR
PRESS SW
PNEUMATIC ELECTRICPE
CHWR
CHWSP
CHWS
CKT
CIP
CKV
CI
CL
CMP
CLG
COMPR
COND
COEF
CNDS
CONDN
CONN
CPLG
CT
CU
CRP
CUH
CV
CU IN
CW
CWP
CWR
CU FT
DBT
DB
DDC
dB
DCW
DEG
DENS
DIA
DEWPT
DIFF
DDCFP
DIV
DPT
DR
DWV
DPS
EAT
ECC
ECON
EER
EFF
EDBT
ECU
DIP
CWS
CAP
ANCHOR
PIPE ALIGNMENT GUIDE
BLIND FLANGE
PG
TEST PORT
2" CHWS
2" CHWS
SYSTEM SERVICE ABBREVIATION
NOMINAL PIPE SIZE
(IN INCHES)
PIPING WITH INSULATION
(SLEEVED) PIPING
SECONDARY CONTAINMENT
EE
EE
THERMOWELL
FLOW ORIFICE PLATE EOV
ENT
EL
ESP
ET
EQIV
EWT
EWBT
EVAP
EXP
EXH
EXCH
FCU
FA
FD
F-F
FDW
FLG
FL SW
FLEX
FL
FPM
FLTR
°F
EXP JT
FRP
FSS
FSTAT
FPS
NOTES:
1.
DIVISION
EXPANSION JOINT
CENTER LINE ( )
CORRUGATED PIPE
CONDENSATE
COMPRESSOR
CONDENSER
CONDENSATION
CONNECTION
COUPLING
CONDENSATE RETURN PUMP
COOLING TOWER
COPPER
COEFFICIENT
COOLING
CABINET UNIT HEATER
CONDENSER WATER PUMP
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CLOCKWISE, CONDENSER WATER
CONSTANT-VOLUME [FLOW]
CUBIC FEET
CUBIC INCH
CIRCUIT
CAST IRON PIPE
CHILLED WATER RETURN
CAST IRON
CHILLED WATER SECONDARY PUMP
CHILLED WATER SUPPLY
CHECK VALVE
DRY BULB TEMPERATURE
DOMESTIC COLD WATER
DIRECT DIGITAL CONTROL
DIRECT DIGITAL CONTROL FIELD PANEL
DEGREES [CELSIUS OR FAHRENHEIT]
DUCTILE IRON PIPE
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE TRANSMITTER
DRAIN
DRAIN, WASTE & VENT
DENSITY
DEW POINT TEMPERATURE
DIFFERENCE OR
DIAMETER
DECIBEL
DRY BULB
ENTERING AIR TEMPERATURE
ECCENTRIC
ECONOMIZER
EVAPORATIVE COOLING UNIT
ENTERING DRY BULB TEMPERATURE
ENERGY EFFICIENCY RATIO
ELECTRONICALLY OPERATED VALVE
EXTERNAL STATIC PRESSURE
EXPANSION TANK, ENTERING TEMPERATURE
ENTERING WET BULB TEMPERATURE
ENTERING WATER TEMPERATURE
EXPANSION
EFFICIENCY
ENTERING
ELEVATION
EQUIVALENT
EVAPORATOR
EXCHANGER
EXHAUST
FAN COIL UNIT
FIRE DAMPER
FEEDWATER
FLOW SWITCH
FLEXIBLE CONNECTION
FLANGE
FLOW LINE ( )
FILTER
FEET PER MINUTE
FEET PER SECOND
FIBERGLASS REINFORCED PLASTIC
FLOW SENSING SWITCH
FREEZE STAT
FACE AREA, FREE AREA
FACE-to-FACE
FAHRENHEIT [DEGREES]
EXAMPLE:
HORIZONTAL RUN ON PLAN
MULTI-LINE DESIGNATION KEY
4" CWR
LOWER PIPE
BOP 12'-6" AFF
4" CWS
2" HWS
2" HWR
CFCI CONTRACTOR FURNISHED/
WITH THERMOMETER
GENERIC PUMP
ELBOW, 90 DEGREE CHANGE IN
DIRECTION TOWARD VIEWER
ELBOW, 90 DEGREE CHANGE
IN DIRECTION AWAY FROM VIEWER
INSULATED PIPE WITH HEAT
TRACING TYPE AS NOTED
(E=ELECTRIC, S=STEAM,
HW=HOT WATER)
BFBF
LATERAL
PG
UON UNLESS OTHERWISE NOTED
FL
NOMINAL PIPE SIZENPS
BELLOWS-TYPE
FLEXIBLE
COUPLING
ISOLATION VALVE
(GENERIC VALVE SYMBOL)
2-WAY VALVE,
GLOBE STYLE
PNEUMATIC ACTUATOR,
MOTOR
VALVE TYPE GRAPHICS ARE SHOWN FOR SIZES 4 INCH NOMINAL
AND LARGER, MAY OR MAY NOT BE DESCRIBED ON VALVE SIZES
SMALLER THAN 4 INCH NOMINAL.
ONLY WELDED FITTINGS ARE SHOWN FOR DOUBLE
LINE PIPING. FITTINGS WITH OTHER END
CONDITIONS ARE SIMILAR.
OFFSET (45° ELBOWS UON)
NON-SLAM (SPRING) CHECK VALVE
PRESSURE GAUGE W/GAUGE COCK
(SERVICES EXCEPT STEAM)
PRESSURE GAUGE W/GAUGE COCK
AND SYPHON LOOP
(STEAM / CONDENSATE SERVICE)
AUTOMATIC AIR VENT
PRESSURE REDUCING VALVE
INDICATING LOW SIDE
PRESSURE
PRESSURE RELIEF/SAFETY VALVE
INDICATING RELIEF PRESSURE
THREE-WAY VALVE
(BALL-TYPE BODY SHOWN)
STEAM TRAP, TYPE AS NOTED
IB = INVERTED BUCKET
F&T = FLOAT & THERMOSTATIC
TH = THERMODYNAMIC
BP = BALANCED PRESSURE
F&TF&T
BOTTOM OF STRUCTURAL STEELBSS
LEAVING TEMPERATURELT
AIR COOLED CONDENSING UNITACCU
PSID POUNDS PER SQUARE INCH DIFFERENTIAL
PSV PRESSURE SAFETY VALVE
PRV PRESSURE REGULATING VALVE
LOCKED ROTOR AMPSLRA
FULL LOAD AMPSFLA
GALLONS PER MINUTEGPM
INDIRECT WASTE, INDUSTRIAL WASTEIW
INVERT ELEVATIONIE
ABOVEABV
DIRECT CURRENTDC
VAC VOLTS ALTERNATING CURRENT
VOLTS DIRECT CURRENTVDC
MILLIAMPERESmA
Q TOTAL, TOTAL HEAT
MOTOR HORSEPOWERMHP
EXISTINGE
P/E PNEUMATIC ELECTRIC
OUTSIDE AIR INTAKEOAI
2-WAY VALVE,
GATE STYLE
2-WAY VALVE,
BUTTERFLY
STYLE
2-WAY VALVE,
BALL STYLE
ANGLE VALVE
PNEUMATIC ACTUATOR,
DIAPHRAGM
ELECTRIC ACTUATOR,
SOLENOID
ELECTRIC ACTUATOR,
MOTOR
AUTOMATIC VALVES
* - (F) INDICATES FUTURE PIPING ON RACK
AUTOMATIC ACTUATOR SYMBOLS
3-WAY VALVE,
GLOBE STYLE
3-WAY VALVE,
BUTTERFLY
STYLE
HANDWHEEL ACTUATOR,
RISING STEM, OUTSIDE
SCREW AND YOKE (OS&Y)
HANDWHEEL
ACTUATOR,
NON-RISING STEM
GEAR ACTUATOR
(HANDWHEEL OR CRANK)
LEVER ACTUATOR
SEE AUTOMATIC ACTUATOR
SYMBOLS (TYP)
STRAINER - BASKET TYPE
AIR SEPARATOR
GRAND SENSIBLE HEATGSH
GTH GRAND TOTAL HEAT
SHGC SOLAR HEAT GAIN COEFFICIENT
SC SHADING COEFFICIENT
WELD NECK FLANGEWNF
MANUAL ACTUATOR SYMBOLS
QTY QUANTITY
ELBOW, 90 DEGREE
(LONG RADIUS UON)
ELBOW, 45 DEGREE
(LONG RADIUS UON)
VACUUM BREAKER
WATER METER
SPHERICAL
FLEXIBLE
COUPLING
STRAINER - "Y"
TYPE WITH BLOW
DOWN
VENTURI FLOW METER
FLAT ON TOP
FOB
FOT
FLAT ON BOTTOM
OWNER FURNISHED /OFCI
RECT RECTANGULAR [DUCT]
ROOF DRAIN
RACK RACK
RACK
RACK
SELF-ACTUATING REGULATOR
(DIAPHRAGM-TYPE ACTUATOR UON)
PIPING DESIGNATION
DRAWING TITLE
X
XX.XX
EXAMPLE: ASSUME A SECTION IS CUT ON DWG. P2.01 WITH A TAG OF 1/P6.01.
SECTION IS DRAWN
THE SECTION No. 1 IS ON DRAWING No. P6.01.
SHEET NO. OF THE PACKAGE ON WHICH
SECTION NUMBER
DIRECTION OF CUTTING PLANE
SECTION OR DETAIL NUMBER
SCALE OF SECTION OR DETAIL
DETAIL NUMBER
SCALE: 1/4" = 1'-0"
DRAWING TITLE
GRAPHIC SYMBOLS
4. INSTALL MANUAL AIR VENTS AT THE HIGH POINTS OF THE PIPING SYSTEMS.
6. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT
STRESSING PIPE OR EQUIPMENT CONNECTED.
7. INSTALL VALVES WITH STEMS UPRIGHT OR HORIZONTAL, NOT
INVERTED.
8. INSTALL VALVES IN ACCESSIBLE LOCATIONS. INSTALL ACCESS
DOORS IN
PARTITIONS WHERE VALVES WOULD OTHERWISE BE INACCESSIBLE.
9. WHEN SOCKET-WELD OR SOLDER-END VALVES ARE INSTALLED, SPECIAL CARE
SHALL BE TAKEN TO AVOID OVERHEATING AND DAMAGING THE VALVE BODY,
TRIM OR PACKING.
10. IDENTIFY EACH PIPE WITH LABELING AS REQUIRED BY SPECIFICATIONS.
11. SLEEVE ALL PIPING THAT PENETRATES FIRE-RATED WALLS, FLOORS AND
PARTITIONS. PENETRATIONS SHALL BE SEALED WITH A U.L.-LISTED ASSEMBLY
TO PROVIDE A RATING EQUAL TO OR GREATER THAN THAT OF THE
PENETRATED WALL, FLOOR OR PARTITION.
12. SLEEVE ALL PIPING THAT PENETRATES EXTERIOR BUILDING WALLS AND GRADE
BEAMS. SEAL PENETRATIONS WATERTIGHT.
13. COORDINATE WITH OTHER TRADES BEFORE FABRICATION OR INSTALLATION OF
ANY SYSTEMS.
14. EXISTING PIPING AND EQUIPMENT SHOWN ON THESE DRAWINGS
INDICATES THE GENERAL LOCATION AND ROUTING. THE ACTUAL LOCATION
SHALL BE DETERMINED BY THE CONTRACTOR WHO SHALL COORDINATE ALL
WORK WITH ALL TRADES NECESSARY TO INSTALL NEW PIPING OR
EQUIPMENT AS SHOWN ON THE DRAWING.
15. THESE DRAWINGS DO NOT NECESSARILY SHOW ALL OFFSETS OR ELEVATION
DIFFERENCES WHICH MAY BE NECESSARY FOR THE COMPLETE INSTALLATION.
16. WHERE REMOVAL OF EXISTING DUCTWORK OR PORTIONS OF ANY AIR SYSTEM
IS NECESSARY, THE DUCT SHALL BE PATCHED AND SEALED AIRTIGHT USING
PATCH OF SAME MATERIAL AND EQUAL OR GREATER THICKNESS AS EXISTING.
PATCHES SHALL BE ATTACHED WITH SHEET METAL SCREWS OR OTHER MEANS
OF POSITIVE ATTACHMENT (WELDING, BONDING, ETC.) AS SPECIFIED FOR THE
PARTICULAR DUCT SYSTEM. NEW INSULATION MATERIAL AND ITS THERMAL
PROPERTIES SHALL BE EQUAL TO OR BETTER THAN EXISTING AND SHALL BE
PATCHED AND SEALED TO MATCH EXISTING INSULATION.
17. COORDINATE ALL REMODEL WORK WITH NEW CONSTRUCTION AND OTHER
TRADES.
18. THE CONTRACTOR SHALL ADJUST AND BALANCE ALL MECHANICAL SYSTEMS
TO DESIGN SETTINGS AS SHOWN AND SHALL REBALANCE TO RESTORE
SETTINGS OF SYSTEMS TEMPORARILY ALTERED FOR THE PURPOSES OF
COMPLETING THE WORK OF THIS PROJECT.
19. NOTIFY AND COORDINATE WITH OWNER PRIOR TO SHUTDOWN OF ANY
EQUIPMENT. SHUTDOWN TIME TO BE MINIMUM.
20. ANY ITEMS DAMAGED DURING DEMOLITION SHALL BE REPLACED WITH NEW
MATERIALS TO MATCH EXISTING.
21. CONTRACTOR SHALL PROVIDE TEMPORARY DUCTWORK, ELECTRICAL
SERVICE,
PIPING OR OTHER BUILDING SERVICES AS REQUIRED TO KEEP OTHER AREAS
IN
OPERATION DURING REMODELING.
22. DUCT ROUTING CHANGES MADE BY THE CONTRACTOR FOR THE PURPOSE OF
ACCOMMODATING FIELD CONDITIONS SHALL INCLUDE FIRE DAMPERS AND
COMBINATION FIRE/SMOKE DAMPERS IN RATED PARTITIONS AS SHOWN IN
ORIGINAL ROUTING ARRANGEMENTS.
23. FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS SHALL BE UL-
APPROVED, SHALL BEAR THE UL LABEL AND SHALL COMPLY WITH NFPA
BULLETIN NO. 90A. FULLY-OPEN DAMPERS SHALL NOT HAVE ANY
PROJECTIONS INTO THE AIRSTREAM.
24. ABANDONED DUCT SHALL BE REMOVED WHERE INDICATED ON THE
DRAWINGS. DUCT REMAINING IN PLACE SHALL BE CAPPED AND SEALED AIR-
TIGHT AT POINT(S) OF DEMOLITION.
25. THE OWNER SHALL HAVE THE OPTION TO DESIGNATE ANY MATERIALS
REMOVED OR DEMOLISHED DURING THIS WORK AS "RECYCLABLE" AND SHALL
HAVE FINAL DISPOSITION OVER THE DISPOSAL OF THESE MATERIALS. ALL
MATERIALS REMOVED/DEMOLISHED BY THE CONTRACTOR FOR THIS JOB AND
NOT RETAINED BY THE OWNER FOR RECYCLING OR OTHER PURPOSES SHALL
BE DISPOSED OFF-SITE BY THE CONTRACTOR.
26. ANY AND ALL WATER CONNECTIONS MADE FOR THE PURPOSE OF CLEANING
TOOLS OR THE WORK AREA OR FOR ANY OTHER CONSTRUCTION-RELATED
PURPOSES SHALL BE MADE ONLY TO DOMESTIC WATER HOSE BIBBS OR TO
CONTRACTOR-SUPPLIED WATER SOURCES. FOR THESE PURPOSES,
CONNECTIONS SHALL NOT BE MADE TO FIRE WATER, CHILLED WATER,
CONDENSER WATER, HEATING HOT WATER, DOMESTIC HOT WATER OR ANY
OTHER TREATED-WATER SOURCE UNLESS REQUIRED AS PART OF WORK ON
THESE SYSTEMS.
27. EXCEPT WHERE REQUIRED AT EQUIPMENT NOZZLES, FLANGES SHALL BE
RAISED FACE WELD-NECK.
28. INSTALL DIELECTRIC FITTINGS AT ALL FERROUS-PIPE CONNECTIONS TO
NON-FERROUS METALLIC PIPE OR EQUIPMENT.
29. BULLHEAD TEES SHALL NOT BE USED TO JOIN CONVERGING (RETURN)
FLOWS, REGARDLESS OF ARRANGEMENT SHOWN ON PLANS.
30. PROVIDE ESCUTCHEON PLATES WHERE PIPES EXPOSED TO VIEW PENETRATE
FINISHED WALLS.
31. PROVIDE DRAIN VALVES AT LOW POINTS OF PIPING SECTIONS AND EQUIPMENT
CONNECTIONS, VENTS AT HIGH POINTS. PROVIDE HOSE BIB
CONNECTIONS AT DRAIN VALVES WHICH DO NOT DISCHARGE DIRECTLY OVER
OR ARE NOT PIPED DIRECTLY TO AN APPROPRIATE DRAIN.
32. PIPING, DUCTWORK OR EQUIPMENT CONNECTIONS OPENED BY DEMOLITION OR
RENOVATION SHALL BE TEMPORARILY SEALED TO KEEP OUT FOREIGN MATTER
UNTIL SUCH TIME AS RECONNECTIONS ARE MADE.
33. ALL PIPING RUN-OUTS TO VV AND CV TERMINAL UNIT HOT WATER COILS
SHALL BE 3/4" NPS UNLESS NOTED OTHERWISE.
34. CONTRACTOR SHALL AVOID DAMAGE TO SYSTEMS WHICH ARE THE WORK OF
OTHER TRADES. ANY SYSTEM COMPONENTS WHICH ARE DAMAGED AND ARE
NOT IN THE CONTRACTOR'S SCOPE OF WORK SHALL BE REPAIRED, BY THE
CONTRACTOR, TO THE AS-INSTALLED CONDITION.
INTERNATIONAL BUILDING CODE - 2021 EDITION WITH COH AMENDMENTS
UNIFORM MECHANICAL CODE - 2021 EDITION WITH COH AMENDMENTS
SHEET NO. ON WHICH DETAIL
IS DRAWN
APPLICABLE CODES & STANDARDS
FLM FLOW METER
COEFFICIENT - VALVE FLOWCv
CONTRACTOR INSTALLED VV VARIABLE-VOLUME [FLOW]
C [THERMAL] CONDUCTANCE
THERMAL CONDUCTIVITYk
STAIRWELL PRESSURIZATION FANSPF
SD SMOKE DAMPER
SUPPLY AIR FANSAF
CDC CONDENSATE DRAIN COOLER
HUMIDIFIERH
HIGH EFFICIENCY PARTICULATE ARRESTANCEHEPA
HEPA FILTER CABINETHFC
DRAWING INDEX
1. THIS IS A STANDARD LEGEND SHEET. SOME INFORMATION ON THIS SHEET
MAY NOT NECESSARILY APPLY TO THIS PROJECT.
2. ISOLATION VALVES SHALL BE PROVIDED IN ALL BRANCH PIPING AND
AT
EQUIPMENT CONNECTIONS.
3. PIPING CONNECTIONS TO ALL EQUIPMENT SHALL BE FABRICATED WITH THE
ISOLATION VALVES, FLANGES AND/OR UNIONS POSITIONED TO ALLOW REMOVAL
AND SERVICE OF THE COMPONENT PARTS.
5. ROUTE PIPING IN AN ORDERLY MANNER AND MAINTAIN PROPER GRADES.
INSTALL TO CONSERVE HEADROOM AND TO CREATE MINIMUM INTERFERENCE
WITH USE OF SPACE. ROUTE EXPOSED PIPING PARALLEL TO BUILDING LINES.
GROUP PIPING AT COMMON BOP ELEVATIONS WHENEVER PRACTICAL. PIPES
LOCATED IN CONCEALED SPACES SHALL BE ROUTED CLOSE TO THE BUILDING
STRUCTURE UON.
M-501
XXX-1
MISCELLANEOUS SYMBOLS
(D)
(R)
(E)
(N)
EQUIPMENT DESIGNATIONS
PIPE SECTION
PIPE BREAK
FLOW ARROW
STANDARD BREAK / RECTANGULAR
DUCT BREAK
SAW CUT SLAB AREA FOR
INSTALLATION OF NEWITEMS
KEYED NOTE
POINT OF DISCONNECTION
POINT OF CONNECTION (NEW TO EXISTING)
NEW ITEMS (PIPING/DUCTWORK/EQUIPMENT)
EXISTING ITEMS TO REMAIN
EXISTING ITEMS TO BE DEMOLISHED
OR RELOCATED
LIMIT OF EXISTING ITEMS TO BE REMOVED
NEWITEM
(NOTATION SHOWN AS NECESSARY FOR
CLARIFICATION)
EXISTINGITEM
(NOTATION SHOWN AS NECESSARY FOR
CLARIFICATION)
EXISTING ITEM TO BE RELOCATED
(NOTATION SHOWN AS NECESSARY FOR
CLARIFICATION)
EXISTING ITEM TO BE DEMOLISHED
(NOTATION SHOWN AS NECESSARY FOR
CLARIFICATION)
ROOM-MOUNTED THERMOSTAT
OR TEMPERATURE SENSOR
ROOM-MOUNTED HUMIDISTAT OR HUMIDITY
SENSOR
ROOM-MOUNTED SMOKE DETECTOR
DUCT-MOUNTED THERMOSTAT OR
TEMPERATURE SENSOR
DUCT-MOUNTED HUMIDISTAT OR
HUMIDITY SENSOR
DUCT-MOUNTED SMOKE DETECTOR
T
H
S
T
H
S
CONTRACTOR INSTALLED
DESIGN CONDITIONS
TECO DESIGN PARAMETERS
CHILLED WATER
SUPPLY RETURN
40°F - 43°F AT 45 PSIG >54°F
BTGH DESIGN PARAMETERS
CHILLED WATER
SUPPLY RETURN
42°F - 45°F 56°F
GATE VALVE
PUMPED CONDENSATE RETURNPCR
N/A
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
H
U S
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:2
:4
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
M-001
28 OCT 2025
ISSUE FOR CONSTRUCTION
JK
422089.11
LD
MECHANICAL - LEGENDS,
ABBREVIATIONS, AND GENERAL
NOTES
HHBTCHW
M-001 MECHANICAL - LEGENDS, ABBREVIATIONS, AND GENERAL NOTES
M-101A-1 MECHANICAL - PHYSICAL PLANT - LEVEL 1 - AREA A - PHASE I
M-101A-2 MECHANICAL - PHYSICAL PLANT - LEVEL 1 - AREA A - PHASE II
M-101A-3 MECHANICAL - PHYSICAL PLANT - LEVEL 1 - AREA A - PHASE III
M-301 MECHANICAL SECTIONS
M-501 MECHANICAL - DETAILS
M-601 MECHANICAL - SCHEDULES
MI-001 MECHANICAL - INSTRUMENTATION AND CONTROLS - LEGEND
MI-602 MECHANICAL - INSTRUMENTATION AND CONTROLS - DIAGRAMS
MI-603 INSTRUMENTATION AND CONTROLS - DIAGRAMS
DCB
A
HX-PP-1
(E)HX-PP-2
(E)HX-PP-3
3 3 3
(E)TECO-CHWP-1
(E)BTGH-CHWP-1 (E)BTGH-CHWP-2 (E)BTGH-CHWP-3
BTGH-FM-1
TECO-FM-14
M-301
20" TECO CHWS
20" BTGH CHWS
20" BTGH CHWR
B T
G H
C H
W S
B T
G H
C H
W R
20" BTGH CHWR
20" BTGH CHWS
20" BTGH CHWR
20" TECO CHWS
20" TECO CHWS
20" TECO CHWR
(E)TECO-CHWP-2
NUMBER DESCRIPTION
KEYED NOTES
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
A B
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
KEYPLAN
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:1
:1
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
M-101A-1
28 OCT 2025
ISSUE FOR CONSTRUCTION
JK
422089.11
LD
MECHANICAL - PHYSICAL PLANT -
LEVEL 1 - AREA A - PHASE I
HHBTCHW
SCALE: 1/4" = 1'-0"1 MECHANICAL - PHYSICAL PLANT - LEVEL 1 - AREA A - PHASE I
1 NEW (581) PLATE SET TO BE INSTALLED AS REPLACEMENT
FOR EXISTING PLATES. EXISTING (381) PLATES TO BE
CLEANED, REFURBISHED, AND PREPARED FOR
INSTALLATION IN NEXT PHASE.
2 REPLACE PUMP IMPELLER WITH NEW 13.125" SIZE. REFER
TO PUMP SCHEDULE FOR NEW DUTY POINT.
3 UPDATE PUMP VFD DUTY POINT PER SCHEDULE AND
BALANCE PUMP TO 4000GPM.
4 PROVIDE FLOW METER FOR CHILLED WATER PIPING.
CONTRACTOR TO FIELD VERIFY LOCATION. INSTALLATION
TO BE ACCORDING TO MANUFACTURER
RECOMMENDATIONS.
5 PROVIDE AND REPLACE ALL EXISTING THERMOMETERS
AND PRESSURE GAUGES. PROVIDE TEMPERATURE
SENSORS, PRESSURE SENSORS, FLOW METERS, AND
PRESSURE GAUGE. CONTRACTOR TO REMOVE AND
REPLACE INSULATION AS NEEDED TO PERFORM WORK.
REFER TO 1/M-501.
6 PROVIDE 1" DRAIN VALVE AT HEAT EXCHANGER
CONNECTIONS.
HX-PP-1
HX-PP-2
(E)HX-PP-3
TECO-FM-1
BTGH-FM-1 BTGH-FM-2
TECO-FM-22
3 (E)TECO-CHWP-2
20" TECO CHWS
20" BTGH CHWS
20" BTGH CHWR
B T
G H
C H
W S
B T
G H
C H
W R
20" BTGH CHWR
20" BTGH CHWS
20" BTGH CHWR
20" TECO CHWS
20" TECO CHWS
20" TECO CHWR
(E)BTGH-CHWP-1 (E)BTGH-CHWP-2 (E)BTGH-CHWP-3
(E)TECO-CHWP-1
NUMBER DESCRIPTION
KEYED NOTES
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
A B
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
KEYPLAN
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:1
:2
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
M-101A-2
28 OCT 2025
ISSUE FOR CONSTRUCTION
JK
422089.11
LD
MECHANICAL - PHYSICAL PLANT -
LEVEL 1 - AREA A - PHASE II
HHBTCHW
SCALE: 1/4" = 1'-0"1 MECHANICAL - PHYSICAL PLANT - LEVEL 1 - AREA A - PHASE II
1 REFURBISHED (381) PLATE SET TO BE INSTALLED WITH
(200) ADDITIONAL NEW PLATES. EXISTING (381) PLATES TO
BE CLEANED, REFURBISHED, AND PREPARED FOR
INSTALLATION IN NEXT PHASE.
2 PROVIDE FLOW METER FOR CHILLED WATER PIPING.
CONTRACTOR TO FIELD VERIFY LOCATION. INSTALLATION
TO BE ACCORDING TO MANUFACTURER
RECOMMENDATIONS.
3 REPLACE PUMP IMPELLER WITH NEW 13.125" SIZE. REFER
TO PUMP SCHEDULE FOR NEW DUTY POINT.
4 PROVIDE AND REPLACE ALL EXISTING THERMOMETERS
AND PRESSURE GAUGES. PROVIDE TEMPERATURE
SENSORS, PRESSURE SENSORS, FLOW METERS, AND
PRESSURE GAUGE. CONTRACTOR TO REMOVE AND
REPLACE INSULATION AS NEEDED TO PERFORM WORK.
REFER TO 1/M-501.
5 PROVIDE 1" DRAIN VALVE AT HEAT EXCHANGER
CONNECTIONS.
HX-PP-1
HX-PP-2
HX-PP-31
TECO-FM-1
BTGH-FM-1 BTGH-FM-2
TECO-FM-2
BTGH-FM-3
TECO-FM-3
20" TECO CHWS
20" BTGH CHWS
20" BTGH CHWR
B T
G H
C H
W S
B T
G H
C H
W R
20" BTGH CHWR
20" BTGH CHWS
20" BTGH CHWR
20" TECO CHWS
20" TECO CHWS
20" TECO CHWR
(E)TECO-CHWP-2
(E)TECO-CHWP-1
(E)BTGH-CHWP-1 (E)BTGH-CHWP-2 (E)BTGH-CHWP-3
NUMBER DESCRIPTION
KEYED NOTES
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
A B
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
KEYPLAN
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:1
:2
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
M-101A-3
28 OCT 2025
ISSUE FOR CONSTRUCTION
JK
422089.11
LD
MECHANICAL - PHYSICAL PLANT -
LEVEL 1 - AREA A - PHASE III
HHBTCHW
SCALE: 1/4" = 1'-0"1 MECHANICAL - PHYSICAL PLANT - LEVEL 1 - AREA A - PHASE III
1 REFURBISHED (381) PLATE SET TO BE INSTALLED WITH
(200) ADDITIONAL NEW PLATES. EXISTING (381) PLATES TO
BE CLEANED, REFURBISHED, AND RETURNED IN
PACKAGING FOR USE AS FUTURE SPARES.
2 PROVIDE FLOW METER FOR CHILLED WATER PIPING.
CONTRACTOR TO FIELD VERIFY LOCATION. INSTALLATION
TO BE ACCORDING TO MANUFACTURER
RECOMMENDATIONS.
3 PROVIDE AND REPLACE ALL EXISTING THERMOMETERS
AND PRESSURE GAUGES. PROVIDE TEMPERATURE
SENSORS, PRESSURE SENSORS, FLOW METERS, AND
PRESSURE GAUGE. CONTRACTOR TO REMOVE AND
REPLACE INSULATION AS NEEDED TO PERFORM WORK.
REFER TO 1/M-501.
4 PROVIDE 1" DRAIN VALVE AT HEAT EXCHANGER
CONNECTIONS.
Physical Plant - Level 1 -178' - 7"
Central Plant - Level 1 -176' - 5"
Physical Plant - Mezzanine A -168' - 1"
Physical Plant - B.O.R -157' - 9 1/2"
4 3 2
EXISTING ISOLATION VALVE
(TYPICAL)
EXISTING CHECK VALVE
(TYPICAL)
BTGH 12" CHWR
NEW DRAIN VALVE
(TYPICAL)
EXISTING CONTROL VALVE
EXISTING 1/3 CONTROL VALVE
EXISTING 2/3 CONTROL VALVE
B T
G H
2"
C H
W R
BTGH 12 CHWS
TECO 12" CHWS
T E
C O
2'
C
H W
R
TECO 20" CHWS
(E)BTGH-CHWP-1
(E)TECO-CHWP-1
EXISTING ISOLATION VALVE
(TYPICAL)
BTGH 20" CHWS
BTGH-FM-1TECO-FM-1
(TYPICAL) (TYPICAL)
NEW DRAIN VALVE
(TYPICAL)
HX-PP-1
NUMBER DESCRIPTION
KEYED NOTES
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:1
:2
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
M-301
28 OCT 2025
ISSUE FOR CONSTRUCTION
JK
422089.11
LD
MECHANICAL SECTIONS
HHBTCHW
SCALE: 3/8" = 1'-0"1 TYP. CHILLED WATER SECTION
FLOOR DRAIN
NEW TEMP.
SENSOR
PCWS
PCWR
CHSFROM PUMP
FROM PUMP
THERMOMETER (TYP)
PRESSURE GAUGE (TYP)
PLUG VALVE (TYP)
EXISTING 2/3 CONTROL VALVE
BALANCE
METER
PLUG VALVE (TYP)
BALANCE
METER
TS
DUPLEX STRAINER
NEW TEMP.
SENSORTS
NEW PRESS.
SENSORPS
NEW PRESS.
SENSORPS
NEW TEMP.
SENSORTS
NEW TEMP.
SENSORTS
NEW PRESS.
SENSORPS
NEW PRESS.
SENSORPS
NEW PRESS.
SENSORPS
NEW FLOW
METERFM
NEW FLOW
METERFM
EXISTING 1/3 CONTROL VALVE
NEW PRESSURE GAUGE
CHR
2000# 1/2" THREADOLET
GAUGE COCK
PRESSURE GAUGE
WATER SERVICE
SWAGE NIPPLE TBE
NOTES:
1. PROVIDE 2-PIECE STAINLESS BALL VALVE FOR CHILLED WATER.
2. PROVIDE GAUGE COCK APPROPRIATE FOR FLUID PRESSURE AND TEMPERATURE.
3. ALL TECO PIPING SHALL COMPLY WITH TECO SPECIFICATIONS.
TEMPERATURE SENSOR CONNECTION OR
DIRECT-READING THERMOMETER
FOR INSULATED PIPE, PROVIDE THERMOWELL WITH
LAGGING EXTENSION TO CLEAR FACE OF INSULATION
THREAD-O-LET FITTING
INSERTION LENGTH EQUAL TO 1/2 OF
PIPE ID WITH MIN LENGTH EQUAL TO
1/3 OF PIPE ID (NOT LESS THAN 2") &
MAX LENGTH EQUAL TO 2/3 OF PIPE ID
THERMOWELL. RE: SPECIFICATIONS
PIPE
NOTES:
1. DETAIL REPRESENTATIVE OF WELDED PIPE INSTALLATION.
2. FOR THREADED PIPE INSTALLATION, USE THREADED TEE IN LIEU OF WELDED FITTING.
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:1
:2
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
M-501
28 OCT 2025
ISSUE FOR CONSTRUCTION
JK
422089.11
LD
MECHANICAL - DETAILS
HHBTCHW
SCALE: NONE1
HEAT EXCHANGER PIPING
DETAIL
SCALE: NONE3 PRESSURE GAUGE DETAIL
SCALE: N.T.S.2
THERMOWELL PIPE MOUNTING
DETAIL
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:1
:2
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
M-601
28 OCT 2025
ISSUE FOR CONSTRUCTION
JK
422089.11
LD
MECHANICAL - SCHEDULES
HHBTCHW
PUMP SCHEDULE (NEW DUTY POINT)
MARK SERVICE FLOWRATE (GPM) HEAD (FT.H2O) TYPE
MOTOR
MANUFACTURER MODEL NOTESMHP V PH HZ RPM CONTROLLER
(E)BTGH-CHWP-1 CHILLED WATER 4000 77 DOUBLE SUCTION SPLIT CASE 100 480 3 60 1200 VFD Bell & Gossett VSX-VSCS -
(E)BTGH-CHWP-2 CHILLED WATER 4000 77 DOUBLE SUCTION SPLIT CASE 100 480 3 60 1200 VFD Bell & Gossett VSX-VSCS -
(E)BTGH-CHWP-3 CHILLED WATER 4000 77 DOUBLE SUCTION SPLIT CASE 100 480 3 60 1200 VFD Bell & Gossett VSX-VSCS -
(E)TECO-CHWP-1 CHILLED WATER 8000 52 DOUBLE SUCTION SPLIT CASE 125 480 3 60 1200 VFD Bell & Gossett VSX-VSCS -
(E)TECO-CHWP-2 CHILLED WATER 8000 52 DOUBLE SUCTION SPLIT CASE 125 480 3 60 1200 VFD Bell & Gossett VSX-VSCS -
PLATE AND FRAME HEAT EXCHANGER SCHEDULE
MARK SYSTEM TYPE PLATE #
MAX CAPACITY
(BTUH)
MIN CAPACITY
(BTUH)
COLD SIDE (TECO) PROCESS SIDE (BTGH)
MANUFACTURER MODEL NOTESFLUID
FLOWRATE
(GPM)
MAX PERFORMANCE MIN PERFORMANCE WPD (FT.
H2O) FLUID
FLOWRATE
(GPM)
MAX PERFORMANCE MIN PERFORMANCE
WPD (FT. H20)EWT (°F) LWT(°F) EWT (°F) LWT(°F) EWT (°F) LWT (°F) EWT (°F) LWT(°F) HX-PP-1 CHILLED WATER PLATE & FRAME 581 25030267 22497700 CHILLED WATER 4000 40.0 52.5 42.0 53.2 15.0 CHILLED WATER 4000 55.6 43.1 56.0 44.8 15.0 TRANTER GXP-205 1,2
HX-PP-2 CHILLED WATER PLATE & FRAME 581 25030267 22497700 CHILLED WATER 4000 40.0 52.5 42.0 53.2 15.0 CHILLED WATER 4000 55.6 43.1 56.0 44.8 15.0 TRANTER GXP-205 1,2
HX-PP-3 CHILLED WATER PLATE & FRAME 581 25030267 22497700 CHILLED WATER 4000 40.0 52.5 42.0 53.2 15.0 CHILLED WATER 4000 55.6 43.1 56.0 44.8 15.0 TRANTER GXP-205 1,2
NOTES:
1. EACH HEAT EXCHANGER IS SIZED FOR 50% OF TOTAL DEMAND FLOW RATE.
2. MINIMUM AND MAXIMUM CAPACITIES ARE DEPENDENT ON TECO CHILLED WATER SUPPLY TEMPERATURE.
BTGH-FM-3 CHILLED WATER 12" 4000 ELECTROMAGNETIC ONICON FT-3100
BTGH-FM-2 CHILLED WATER 12" 4000 ELECTROMAGNETIC ONICON FT-3100
BTGH-FM-1 CHILLED WATER 12" 4000 ELECTROMAGNETIC ONICON FT-3100
TECO-FM-3 CHILLED WATER 12" 4000 ELECTROMAGNETIC ONICON FT-3100
TECO-FM-2 CHILLED WATER 12" 4000 ELECTROMAGNETIC ONICON FT-3100
TECO-FM-1 CHILLED WATER 12" 4000 ELECTROMAGNETIC ONICON FT-3100
MARK SERVICE SIZE FLOWRATE (GPM) TYPE MANUFACTURER MODEL NOTES
FLOW METER SCHEDULE
PUMP SCHEDULE (ORIGINAL DUTY POINT FOR INFORMATION ONLY)
MARK SERVICE FLOWRATE (GPM) HEAD (FT.H2O) TYPE
MOTOR
MANUFACTURER MODEL NOTESMHP V PH HZ RPM CONTROLLER
(E)BTGH-CHWP-1 CHILLED WATER 3568 85 DOUBLE SUCTION SPLIT CASE 100 480 3 60 1180 VFD Bell & Gossett VSX-VSCS -
(E)BTGH-CHWP-2 CHILLED WATER 3568 85 DOUBLE SUCTION SPLIT CASE 100 480 3 60 1180 VFD Bell & Gossett VSX-VSCS -
(E)BTGH-CHWP-3 CHILLED WATER 3568 85 DOUBLE SUCTION SPLIT CASE 100 480 3 60 1180 VFD Bell & Gossett VSX-VSCS -
(E)TECO-CHWP-1 CHILLED WATER 7135 45 DOUBLE SUCTION SPLIT CASE 125 480 3 60 1180 VFD Bell & Gossett VSX-VSCS -
(E)TECO-CHWP-2 CHILLED WATER 7135 45 DOUBLE SUCTION SPLIT CASE 125 480 3 60 1180 VFD Bell & Gossett VSX-VSCS -
EXISTING PLATE AND FRAME HEAT EXCHANGER SCHEDULE (FOR INFORMATION ONLY)
MARK SYSTEM TYPE PLATE # CAPACITY (BTUH)
COLD SIDE (TECO) PROCESS SIDE (BTGH)
MANUFACTURER MODEL NOTESFLUID
FLOWRATE
(GPM) EWT (°F) LWT(°F)
WPD (FT.
H2O) FLUID
FLOWRATE
(GPM) EWT (°F) LWT (°F) WPD (FT. H20)
(E)HX-PP-1 CHILLED WATER PLATE & FRAME 381 24263574 CHILLED WATER 3568 40 54 32.0 CHILLED WATER 3568 56 42 32.0 TRANTER GXP-205 -
(E)HX-PP-2 CHILLED WATER PLATE & FRAME 381 24263574 CHILLED WATER 3568 40 54 32.0 CHILLED WATER 3568 56 42 32.0 TRANTER GXP-205 -
(E)HX-PP-3 CHILLED WATER PLATE & FRAME 381 24263574 CHILLED WATER 3568 40 54 32.0 CHILLED WATER 3568 56 42 32.0 TRANTER GXP-205 -
DDC
VSD
CONTROL LEGEND
LOCAL OPERATOR PANEL
FLOWMETER - TOTALIZER
LOCAL PANEL
FQ
LP
LOP
VIDEO CAMERARY
TW THERMOWELL
DX COIL
OR
HEAT PIPE
FLAT
FILTER
HIGH
EFFICIENCY
FILTER
ANGLED
FILTER
EXAMPLE:
PRESSURE
DIFFERENTIAL
TRANSMITTER #2
SEQUENTIAL
INSTRUMENT
NUMBER
(OPTIONAL)
FUNCTIONMEASURED VARIABLE
INSTRUMENT TAG FORMAT
PDT
VARIABLE
SPEED
DRIVE
UV LAMP
MOTORIZED
DAMPER
MOTORIZED
VALVE
MISC. INSTRUMENTS AND CONTROLS LEGEND
PRESSURE SAFETY VALVE
PRESSURE RELIEF VALVE
CARBON DIOXIDE SENSOR
FLOW RESTRICTION ORIFICE
PSV
CS
PRV
FO VIDEO MONITORRI
HYDRONI
C
HEATING
COIL
HYDRONIC
COOLING
COIL
FAN
PUMP
C
C
PDT
DIRECT DIGITAL
CONTROL (DDC)
PANEL
SCHEMATIC SYMBOLS
PRESSURE
DIFFERENTIAL
TRANSMITTER
M
M
S W
IT
C
H L
O W
S
E N
S O
R -L
O W
L
IM
IT
T R
A N
S M
IT
T
E R
S W
IT
C
H H
IG
H
S
E N
S O
R -H
IG
H
L
IM
IT
C O
N T
R O
L L E
R
A L A
R M
L O
W
A L A
R M
H I/ L O
A L A
R M
H
IG
H
ZTZSH ZSLZICZAL ZEZ ZAHPOSITION
PDE
M E
A S
U R
E D
O R
C O
N T
R O
L L
IN
G V
A R
IA
B
L E
MULTI-VAR.
TEMPERATURE
SPEED/FREQ.
PRESS. DIFF.
PRESSURE
VIBRATION
ON/OFF
WEIGHT
HUMIDITY
UAHL
WAHL
U UAH
V
X
W
VAH
WAH
UAL
VEVAL
WAL WE
TAHL
SAHL
PAHL
M
PD
T
S
P
TAH
PDAH
SAH
PAH
ME
PDAL
TAL
SAL
TE
SE
PAL PE
MANUAL
POWER
LEVEL
TIME
CURRENT
ANALYSIS
FLOW
VOLTAGE
H
LAHL
JAHL
KAHL
IAHL
L
K
J
LAH
JAH
KAH
I IAH
JAL
LAL
KAL
LE
JE
KE
IAL IE
AAHL
FAHL
EAHL
AHL
A
F
E
AAH
FAH
EAH
AH
AEAAL
FAL
EAL
FE
EE
AL E
UIR
WIR
UI
VI
WI WIC
UR
WIT WR
TIR
SIR
PIR
PDIR
TI
PDI
SI
PI
TIC
PDIC
SIC
PIC
PDIT
TIT
SIT
TR
PDR
SR
PIT PR
WSHL
VSH
WSHWC
VT
WT
VSL
WSL
TSHL
SSHL
PSHL
PDSH
PSH
TSH
SSH
TC
PDC
SC
PC
TT
PDT
ST
PT
PDSL
TSL
SSL
PSL
HIC
LIR
JIR
KIR
IIR
LI
JI
KI
LIC
JIC
KIC
II IIC
LIT
KIT
JIT
LR
JR
KR
IIT IR
AIR
FIR
EIR
AI
FI
EI
AIC
FIC
EIC
I IC
ARAIT
FIT
EIT
FR
ER
IR IT R
LSHL
KSHL
JSHL
ISHL
JSH
LSH
KSH
ISH
LC
JC
KC
IC
LSL
JSL
LT
JT
KTKSL
ISL IT
ASHL
FSHL
ESHL
SHL
ASH
FSH
ESH
AC
FC
EC
SHC
AT
FT
ET
ASL
FSL
ESL
SL T
INSTRUMENT
LEGEND
E L E
M E
N T
INSTRUMENT FUNCTION
IN
D
E P
E N
D E
N T
R E
C O
R D
E R
IN
D
IC
A
T O
R
IN
D
E P
E N
D E
N T
C O
N T
R O
L L E
R
IN
D
E P
E N
D E
N T
T R
A N
S M
IT
T
E R
R E
C O
R D
E R
S W
IT
C
H -C
L O
S E
D
C O
N V
/C O
M P
D E
V
IC
E
S W
IT
C
H O
R S
E N
S O
R
V A
L V
E S
E L F
-A C
T U
A T
IN
G
S W
IT
C
H -O
P E
N
V A
L V
E
ZSCZL ZS ZSO
UY
VY
XY
WY
XS XV
WV
PY
TY
SY
TV
PV
TCV
PCV
HYHS HV
LY
KY
JY
IYIS
LV
KV
LCV
AY
FY
EY
YS
AV
FV
VCV SC SOL
L
IG
H T
ELECTRICAL
DISCONNEC
T
TS
MT
VS
PS
RESISTANC
E
HEATING
ELEMENT
FS
SD SMOKE DETECTOR
PERFORATED
PLATE
MANUAL
(VOLUME)
DAMPER
VD
S W
IT
C
H H
IG
H
/L O
W
S E
N S
O R
-H
IG
H /L
O W
R A
N G
E
PDS
OS OCCUPANCY SENSOR
NS FIRE ALARM STATUS
NOTES:
1. UNLISTED COMBINATIONS OF INSTRUMENT LEGEND
LETTER GROUPS MAY BE USED WHEN REQUIRED.
2. THE TAG NUMBER BY WHICH INSTRUMENTS OR LOOPS
ARE IDENTIFIED IN A PANEL OR CONTROL SYSTEM IS
THE TAG NUMBER OF THE MAIN FIELD INSTRUMENT.
3. NEW OR SPECIAL DEVICES WHICH CANNOT BE
IDENTIFIED FROM THE LEGEND (SEE NOTE 1) SHALL BE
ASSIGNED THE FIRST LETTER "N". THE INSTRUMENT
LEGEND FOR SPECIFIC PROJECTS SHOULD BE
MODIFIED TO INDICATE DEFINITIONS FOR THESE
ADDITIONAL SYMBOLS.
C
H
X
D
MS
ECM ELECTRONICALL
Y COMMUTATED
MOTOR
MSH
NOTES:
N1. THE POINT NAME ON THIS LINE REFERS TO A PIECE OF EQUIPMENT OR SYSTEM INSTEAD OF A POINT. THE FIELD DEVICE LISTED ON THIS LINE REFERS TO THE POINTS LIST OF THE SAME NAME. REFER TO THE POINTS LIST CORRESPONDING TO THE NAME LISTED UNDER FIELD DEVICE FOR ALL DETAILED REQUIREMENTS FOR THE LISTED EQUIPMENT/SYSTEM. ALL POINTS IDENTIFIED ON THE REFERENCED EQUIPMENT'S POINTS LIST FOR GRAPHICAL DISPLAY ON THE SYSTEM GRAPHIC, WILL
BE SHOWN ON THIS SYSTEM GRAPHIC.
N2. SIGNAL TO BE PHYSICALLY WIRED TO BOTH BMS CONTROLLER FOR MONITORING AND VFD SAFETY CIRCUIT FOR HARD-WIRED SHUTDOWN N3. MUST BE SET TO A SUB-AMBIENT PRESSURE WITHIN THE SMACNA CONSTRUCTION STANDARDS OF THE ASSOCIATED DUCTWORK OR AHU CASING N4. DEPENDING ON MANUFACTURER, THIS POINT MAY BE A MULTI-STATE VALUE. BMS CONTRACTOR TO ADVISE ENGINEER IN WRITING OF ALL AVAILABLE MULTI- STATE VALUES SO ALL DESIRED INFORMATION IS OBTAINED. NOTE THAT THE DESCRIPTION OF THE ANALOG VALUE MUST BE DISPLAYED, NOT THE ACTUAL ANALOG
VALUE READ.
N5. DEPENDING ON MANUFACTURER, THIS POINT MAY BE A MULTI-STATE VALUE. ONLY VALUES NOTED IN POINT DESCRIPTION ARE REQUIRED. NOTE THAT THE DESCRIPTION OF THE ANALOG VALUE MUST BE DISPLAYED, NOT THE ACTUAL ANALOG VALUE READ.
N6. FIELD DEVICE TO BE PROVIDED AND INSTALLED BY OTHERS. POINT TO BE MONITORED BY SYSTEM AS NOTED.
N7. REFERENCED POINT IS PER DEVICE. THE SYSTEM WILL COMMUNICATE WITH THE REFERENCED POINT IN EACH INSTANCE OF THE ASSOCIATED EQUIPMENT IN
THE SYSTEM.
N8. POINT MUST BE DIRECTLY WIRED TO THE CONTROLLER. IT IS NOT PERMISSIBLE FOR SIGNAL INPUT TO BE COMMUNICATED TO CONTROLLER OVER
COMMUNICATIONS NETWORK.
N9. REFER TO EQUIPMENT MANUFACTURER'S DATA FOR NOMINAL VALUES.
N10. SIGNAL TO BE PHYSICALLY WIRED TO THE I/O TERMINAL STRIP ON THE EQUIPMENT ON BOARD CONTROLLER.
N11. THE REFERENCED INFORMATION IS PER BATTERY CELL. COORDINATE WITH BATTERY SYSTEM INFORMATION FOR QUANTITY OF CELLS N12. THE REFERENCED INFORMATION IS PER BATTERY STRING. COORDINATE WITH BATTERY SYSTEM INFORMATION FOR QUANTITY OF STRINGS N13. DEPENDING ON MANUFACTURER, THIS MAY BE AN AGGREGATION OF MULTIPLE POINTS INTO A SINGLE LOGIC POINT. NOTE THAT WHILE MULTIPLE INTEGRATION POINTS MAY BE REQUIRED AS INPUTS, ONLY ONE OUTPUT OR RESULTANT VALUE IS DESIRED. POINTS TO BE AGGREGATED SHALL NOT INCLUDE OTHER SIMILAR
POINTS EXPLICITLY REQUIRED ELSEWHERE IN THE POINTS LIST.
N14. DEPENDING ON MANUFACTURER, THIS MAY BE AN AGGREGATION OF MULTIPLE POINTS INTO A SINGLE LOGIC POINT. NOTE THAT WHILE MULTIPLE INTEGRATION POINTS MAY BE REQUIRED AS INPUTS, ONLY ONE OUTPUT OR RESULTANT VALUE IS DESIRED. POINTS TO BE AGGREGATED SHALL NOT INCLUDE OTHER SIMILAR
POINTS EXPLICITLY REQUIRED ELSEWHERE IN THE POINTS LIST.
N15. SYSTEM UTILIZES REDUNDANT PLCs. EACH PLC AGGREGATES DATA FROM EACH FIELD DEVICE. BMS TO OBTAIN DATA FROM EACH PLC, BUT ONLY DISPLAY AND LOG DATA FROM ACTIVE PLC. FIELD DEVICE IN THIS CASE REFERS TO THE DEVICE FROM WHICH THE PLC OBTAINS THE INFORMATION. BMS CONNECTION IS TO THE
PLC.
N16. VALUE TO BE NORMALLY "OFF". "OFF" CONDITION MEANS "LEAD PLC IN CONTROL". "ON" CONDITION MEANS "REDUNDANT PLC IN CONTROL".
N17. VALUE SHALL BE TRUE WHEN THE CORRESPONDING ANALOG "COUNT" VALUE IN INCREMENTED. VALUE SHALL BE MADE FALSE ONLY BY OPERATOR
ACKNOWLEDGEMENT OF EVENT
N18. THIS VALUE MAY NOT BE AVAILABLE VIA INTERFACE. IN THIS CASE, VALUE REPORTED SHALL BE THE CALCULATED AVERAGE OF THE ASSOCIATED MEASURED
VALUES.
N19. THIS VALUE MAY NOT BE AVAILABLE VIA INTERFACE. IN THIS CASE, VALUE REPORTED SHALL BE THE SUM TOTAL OF THE ASSOCIATED MEASURED VALUES.
N20. COORDINATE WITH DEVICE MANUFACTURER. WITH SOME ALLOWABLE DEVICES, DATA IS CONTAINED IN A FILE THAT MUST BE REQUESTED FROM THE REFERENCED METER AND DOWNLOADED BY THE SYSTEM FOR LOGGING. GRAPHICAL DISPLAY OF DATA TO BE THROUGH METER'S NATIVE GRAPHICS VIA IP.
N21. SIGNAL TO BE PROVIDED TO THE PLC VIA FACTORY-INSTALLED ACCESSORY, WIRED TO THE PLC. BMS SHALL OBTAIN THE VALUE VIA INTEGRATION TO THE PLC.
N22. SYSTEM TO WRITE VALUES TO BOTH PLCS TO ENSURE EVENT TIME STAMPING IS CONSISTENT THROUGHOUT THE FACILITY N23. VALUE IS TO BE CALCULATED BY ADDING THE VALUES FROM THE REFERENCED FIELD DEVICES N24. FIELD DEVICE IS WIRED PHYSICALLY TO THE UNIT CONTROLLER, AND IS MONITORED BY THE BMS VIA INTEGRATION.
N25. MONITORED VALUE IS AN INDEX. BMS WILL DISPLAY TEXT CORRESPONDING TO APPROPRIATE INDEX VALUE ON THE GRAPHICS.
N26. THIS POINT IS AN UNPUBLISHED OPTION AVAILABLE FROM THE MANUFACTURER. COORDINATE WITH MANUFACTURER'S REPRESENTATIVE FOR REGISTER MAP
INFORMATION.
N27. FIELD DEVICE IS SHOWN ELSEWHERE IN THE PLANS WITH THE ASSOCIATED SPACE. NOTE THAT THE REFERENCED POINT IS OBTAINED THROUGH THE NETWORK
TO THIS CONTROL LOOP, AND THAT AN ADDITIONAL FIELD DEVICE IS NOT REQUIRED.
N28. PROVIDE AND INSTALL A RED PUSHBUTTON UNDER A CLEAR PLASTIC COVER. WIRE CONTACTS ON PUSHBUTTON TO SYSTEM PANEL, EMERGENCY STROBE, AND
HORN.
N29. VALUE IS THE CALCULATED DIFFERENCE IN TOTALIZED MAKEUP AND TOTALIZED BLOWDOWN N30. EQUIPMENT MAY HAVE MULTIPLE DEVICES OF THIS TYPE (IE COMPRESSOR, FAN, CIRCUIT, ETC). PROVIDE THE ASSOCIATED POINT FOR EACH DISCRETE DEVICE.
N31. VALUE IS CALCULATED BY SELECTING THE MOST DEMANDING ASSOCIATED ZONE AS THE CRITICAL ZONE
N32. DEVICE IS PROVIDED BY EQUIPMENT MANUFACTURER AND INSTALLED BY CONTRACTOR
N33. RE: MI-10X PLANS FOR DEVICE COUNTS AND LOCATIONS.
N34. BIANARY INPUT IS RECIEVED FROM PROGRAMABLE CONTACT ON SWITCHGEAR BUS METER.
ALARMS:
A1. IF ON OR TRUE
A2. IF OFF, FALSE OR 0.
A3. FALSE FOR 30 SECONDS WITH START COMMAND TRUE
A4. FALSE FOR 5 MINUTES WHEN START COMMAND TRUE
A5. TURNS FALSE OR TO 0 WITH START COMMAND STILL TRUE
A6. STATUS FEEDBACK POINT DOES NOT MATCH COMMANDED POSITION +/- 2% WITHIN 90 SECONDS OF COMMAND
A7. VALUE IS 100% FOR 5 MINUTES
A8. IF GREATER THAN OR EQUAL TO 100%
A9. VALUE IS OVER 100% OF SETPOINT FOR 5 MINUTES
A10. IF GREATER THAN 61 Hz OR LESS THAN 59 Hz
A11. IF SETPOINT CANNOT BE MAINTAINED FOR 5 MINUTES
A12. VALUE IS GREATER THAN + 2F (COOLING MODE) OR -2F (HEATING MODE) OF ACTIVE SETPOINT FOR 5 MINUTES
A13. VALUE IS GREATER THAN +/- 10% OF NOMINAL VALUE OR SETPOINT FOR 5 MINUTES
A14. VALUE IS GREATER THAN 5F ABOVE SETPOINT FOR 5 MINUTES
A15. VALUE IS LOWER THAN 50F FOR 5 MINUTES
A16. TEMPERATURE IS ABOVE 80F OR BELOW 64F FOR 5 MINUTES - ALARM "OUTSIDE RECOMMENDED RANGE" A17. TEMPERATURE IS ABOVE 90F OR BELOW 59F FOR 5 MINUTES - ALARM "OUTSIDE ALLOWABLE RANGE" A18. VALUE IS LOWER THAN 42F DEWPOINT, GREATER THAN 60% RH, OR GREATER THAN 59F DEWPOINT - ALARM "OUTSIDE RECOMMENDED RANGE" A19. VALUE IS LOWER THAN 20% RH, GREATER THAN 80% RH, OR GREATER THAN 62.5F DEWPOINT - ALARM "OUTSIDE ALLOWABLE RANGE"
A20. TEMPERATURE IS ABOVE 104F FOR 5 MINUTES
A21. IF VALUE IS GREATER THAN INITIAL VALUE + 1.0 IWC
A22. IF BOTH THE OPEN AND CLOSED POINTS ARE ACTIVE AT THE SAME TIME
A23. IF SWITCH POSITION IS NOT VERIFIED WITHIN ALLOWABLE STROKE TIME AFTER COMMAND. ALLOWABLE STROKE TIME IS DETERMINED IN THE FIELD BY MEASURING ACTUAL TIME TO STROKE OPEN AND SEPARATELY ACTUAL TIME TO STROKE CLOSED, AND ADDING 15 SECONDS TO THE MEASURED
TIME TO STROKE.
A24. STATUS FEEDBACK POINT DOES NOT MATCH COMMAND WITHIN 3 SECONDS OF ISSUING COMMAND A25. IF POINT AND ASSOCIATED POINT(S) ARE BOTH "CLOSED", OFF OR FALSE SIMULTANEOUSLY
A26. IF VALUE IS AT OR ABOVE 100% FOR ANY DURATION
A27. IF VALUE IS BELOW MINIMUM REQUIRED TO DELIVER SYSTEM DESIGN CAPACITY. MINIMUM VALUE TO BE DETERMINED DURING TEST AND BALANCE.
A28. THERE ARE MULTIPLE ALARMS FOR THIS POINT. REFER TO VALUES LISTED IN THE "NOMINAL VALUE/ SETPOINT" COLUMN. (LL,L;H,HH) - LOW-LOW, LOW, HIGH AND HIGH-HIGH
A29. VALUE IS LOWER THAN SETPOINT FOR 5 MINUTES CONTINUOUSLY
A30. VALUES LISTED IN "NOM. VALUE/ SETPOINT" ARE (MIN AIRFLOW, MAX AIRFLOW), (LOW ALARM, SETPOINT, HIGH ALARM) OR (LOW ALARM, HEATING
SETPOINT, COOLING SETPOINT, HIGH ALARM)
A31. COORDINATE WITH EQUIPMENT MANUFACTURER FOR RECOMMENDED SETPOINT
GRAPHICS:
G1. VALUE TO BE NORMALLY HIDDEN, AND DISPLAYED IN RED FONT WHEN TRUE / IN ALARM.
G2. NOTED VALUES ARE MUTUALLY EXCLUSIVE AND THEREFORE WILL BE SHOWN ONLY WHEN TRUE. NOTED VALUES SHOULD OCCUPY THE SAME
PHYSICAL SPACE ON THE GRAPHIC
G3. IF BOTH OPEN AND CLOSED END SWITCHES ARE OFF SIMULTANEOUSLY, DISPLAY "MOVING"
G4. REFER TO RISERS AND SCHEDULES FOR EQUIPMENT CAPACITY
G5. REFER TO M-60X FOR SETPOINT
G6. 125% OF MANUFACTURER'S MINIMUM
TRENDING:
T1. CHANGE OF VALUE
T2. DURING COMMISSIONING PHASE SET TRENDING FOR 5 SECOND INTERVAL. POST-COMMISSIONING, SET TRENDING TO 15 MINUTE INTERVAL
T3. 60 MINUTE INTERVAL
T4. TWO CONCURRENT TRENDS TO EXIST. THE PRIMARY TREND WILL SAMPLE AT A 15 MINUTE INTERVAL. THE SECOND TREND WILL BE AT A 5 SECOND INTERVAL, AND SHALL PASS THROUGH A FIRST-IN-FIRST-OUT BUFFER. IT WILL NOT NORMALLY BE STORED TO THE HISTORIAN SERVER. UPON AN ALARM CONDITION, THE SECOND TREND WILL BE SAVED TO THE HISTORIAN AS A "SNAP SHOT" WHEN THE TIMESTAMP OF THE OLDEST DATA IN THE BUFFER IS 1
MINUTE PRIOR TO THE TIMESTAMP OF THE ALARM TRIGGER.
PDS
H HUMIDITY SENSOR
JACE TRIDIUM JACE
FACP
FIRE ALARM
CONTROL PANEL
CM
CONTROL
MODULE
AS
Page Southerland Page, Inc.
ARCHITECTURE / ENGINEERING / INTERIORS / PLANNING / CONSULTING
Albany / Albuquerque / Atlanta / Austin / Boston / Charleston / Dallas / Denver /
Dubai / Houston / Los Angeles / Mexico City / New York City / Orlando / Phoenix /
Raleigh / Richmond / San Antonio / San Francisco / Tampa / Washington DC
JOHN JOSEPH KLUBER
122644
THIS DOCUMENT IS RELEASED FOR THE
PURPOSE OF INTERIM REVIEW UNDER THE
AUTHORITY OF
IT IS NOT TO BE USED FOR REGULATORY
APPROVAL, BIDDING, PERMIT, OR
CONSTRUCTION PURPOSES.
INTERIM REVIEW
DESCRIPTIONREVISION DATE
F
IL
E P
A T
E R
N A
M E
D A
T E
S T
A M
P
1111 Louisiana Street 26th Floor Houston, TX 77002 pagethink.com
TEL 713 871 8484
FAX 713 871 8440
REVISION HISTORY
PROFESSIONAL SEALS
CLIENT
PROJECT
CHECKED BYDRAWN BY
PROJECT NUMBER ABBREVIATION
ORIGINAL ISSUE
SHEET NAME
SHEET NUMBER
A u to d e s k D o c s /4
.1
-H a rr is H e a lt h B
T C
H W
U p g ra d e /4
.1
M
R
C
E N
T R
A L
.r v t
/2 /2
:2
:4
P M
HARRIS HEALTH BT
HARRIS HEALTH BT CHW
UPGRADE
1504 BEN TAUB LOOP
HOUSTON, TX 77030
MI-001
28 OCT 2025
ISSUE FOR CONSTRUCTION
JGN
422089.11
Author
MECHANICAL - INSTRUMENTATION AND
CONTROLS - LEGEND
HHBTCHW
TECO CHILLED
WATER SUPPLY
VFD
VFD
TECO CHILLED
WATER RETURN
VFD
TCHWP-2
TCHWP-1
HX-PP-3
HX-PP-2
HX-PP-1
AIR SEPARATOR
PCHWP-PP-1
PCHWP-PP-2
PCHWP-PP-3
VF…