7--8- Plans- FAC125305 ADC Lobby Turnstiles.pdf
PDF 4 MB Posted
- Attached to
- SLCo FAC125305 ADC Lobby Turnstiles - CONST
- Solicitation number
- SLCo FAC125305 ADC Lobby Turnstiles - CONST
- Issued by
- Utah
About this file
This is a construction document set for the Salt Lake County ADC Lobby Turnstiles Renovation project located at 3415 S. 900 W. South Salt Lake, UT 84119. The project involves renovating the security checkpoint and lobby area, with a construction set dated August 1, 2025. The scope includes installing new turnstiles, reconfiguring the security checkpoint, updating electrical systems, and making associated architectural modifications. The project is being managed by Architectural NEXUS, Inc. for Salt Lake County, with electrical consulting by EE-LD.
The project documents indicate a comprehensive renovation focusing on the security entrance, including new millwork, flooring (luxury vinyl tile), wall treatments, and electrical infrastructure updates. The design incorporates stainless steel finishes, relocated lighting and camera systems, and integration of new card readers and power systems. The estimated construction timeline appears to be for completion in August 2025, with detailed plans for electrical relocations, power distribution, and system integration. The project will utilize existing electrical panel NLJ2A and involves careful coordination of existing systems with new installations, ensuring minimal disruption to the facility's operations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S . 9
W
C O
U N
TY
J
A
IL
P R
IV
A
TE
R
O A
DSCOPE OF WORK
Nexus Project #: Owner Project #:
VICINITY MAP
PROJECT LOCATION
Salt Lake County
ADC LOBBY
TURNSTILES
3415 S. 900 W.
South Salt Lake, UT 84119
CONSTRUCTION SET
1 AUGUST 2025
25030
RENOVATION OF SECURITY CHECKPOINT.
SLCo ADC SECURITY CHECKPOINT LEVEL 01
ACCESSIBLE FROM THE PARKING LOT ON THE WEST SIDE
OF BUILDING AT THE RADIUSED PORTION OF THE
BUILDING. AREA IS NORTH OF THE RAMP TO THE SECOND
LEVEL LOBBY.
DENOTED BY HEAVY DASHED LINE
RAMP
CONTACT: E-MAIL:
PHONE: INTERNET:
OWNER
SALT LAKE COUNTY
2001 S. State Street Suite S3200
Salt Lake City, UT 84190
385.468.0338
John Bergen jbergen@slco.org http://www.slco.org
CONTACT: E-MAIL:
PHONE: INTERNET:
ARCHITECT
Architectural NEXUS, Inc.
2505 East Parleys Way
Salt Lake City, UT 84109
801.924.5000
Stephen Springer sspringer@archnexus.com http://www.archnexus.com
CONTACT: E-MAIL:
PHONE: INTERNET:
ELECTRICAL CONSULTANT
EE-LD
1220 South 300 West
Salt Lake City, UT 84101
801.486.2222
Mansour Aghdasi mansour@ee-ld.com http://www.ee-ld.com t 2
08/15/20240808088080808088808888808080808080880880808088080808888000000000000000000000000000000000000000000000000000000000000 /15/5//5/5//5/5/5/5///5/5////////5///////5/////5///5/5/////////////5//5/5///////5/////5/////5////5//5/////////5//5//////////5/////5555555555555555555555555555555555555555555555555555 0202020202020020000020002020020200200202000200000200000202000020000002000020020000000200020200000222222222222222222222222222222222222222222222222222222222222222222222222222222222222 2422222222222222222222222222222222222222222222222222222222222222
MATCH LINE
A1 / Axxx
MATCH LINE TAG
EXISTING WALL TO REMAIN
WALL TO BE DEMOLISHED
NEW WALL
BREAK LINE
CENTER LINE SYMBOL
0' 4' 8' 16'
REVISION DESIGNATION
ELEVATION SYMBOL
T.O. WALL
100'-0"
REVISION NUMBER
ELEVATION ABOVE DATUM
ELEVATION DESCRIPTION
DRAWING SYMBOL LEGEND
000M
CASEWORK TYPE DESIGNATION
CDS NUMBER (M DENOTES
MODIFICATION - SEE SHEET
A551 FOR MODIFIED MILLWORK
ELEVATIONS AND DETAILS)
00"
00"
00"
MODIFICATION DESCRIPTION
AWS STANDARD CDS NUMBERING SYSTEM
WIDTH
HEIGHT
DEPTH
NORTH ARROW
PLAN NORTH
GRAPHIC SCALES
ROUND BREAK LINE
REVISION CLOUD
SLOPE INDICATION
1/2" / 12"
DETAIL REFERENCE
A2 A401
A1
A3
INTERIOR ELEVATIONS
DETAIL NUMBER
SHEET NUMBER
A1
A501
DETAIL REFERENCE
DETAIL NUMBER
SHEET NUMBER
A1
A201
EXTERIOR ELEVATION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1
A302
WALL SECTION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1
A301
BUILDING SECTION REFERENCE
DETAIL NUMBER
SHEET NUMBER
XX000X
00'-00"
ROOM DESIGNATION (FLOOR PLAN)
ROOM NUMBER
ROOM NAME
A1
A301
DETAIL NUMBER
SHEET NUMBER
ROOM DESIGNATION (REFLECTED
CEILING PLAN)
CEILING HEIGHT ABOVE FINISH FLOOR
ROOM NUMBER
00001
GLASS TYPE DESIGNATION
KEYED NOTE DESIGNATION
WALL TYPE DESIGNATION
EQUIPMENT DESIGNATION
WINDOW DESIGNATION
DOOR DESIGNATION
GLASS TYPE
EQUIPMENT NUMBER
KEY NOTE NUMBER
WINDOW TYPE
DOOR NUMBER
WALL TYPEXXX
MATERIAL TYPE DESIGNATION
FINISH NUMBER
SEE AI601 FINISH LEGEND
00001
12" 1/2
RISE
RUN
TRUE NORTH
CL
03:CJ1
ROOM
A1
A301
DETAIL / SHEET NUMBER
1t
CAST-IN-PLACE CONCRETE
CONCRETE MASONRY UNIT
PRECAST CONCRETE / GLASS FIBER
REINFORCED CONCRETE (GFRC)
STEEL STUDS
WOOD STUDS
BRICK VENEER
RIGID INSULATION
BATT INSULATION
CONTINUOUS MATERIAL
NON CONTINUOUS MATERIAL
(BLOCKING)
GYPSUM BOARD
PLYWOOD
GRAVEL
UNDISTURBED EARTH
HATCH LEGEND
NOTE: HATCHING ANGLES MAY VARY DUE TO ANGLE OF WALL DRAWN, WHILE HATCHING PATTERN REMAINS SIMILAR.
BACKFILL OR FILL
BALLISTIC RATED FIBERGLASS
LIST OF ABBREVIATIONS
THE PRECEDING LIST OF ABBREVIATIONS IS PRESENTED AS A GENERAL GUIDE AND DOES NOT NECESSARILY SHOW ALL ABBREVIATIONS USED. OTHER GENERALLY ACCEPTED ABBREVIATIONS MAY BE FOUND AMONG THE DRAWINGS - SOME ABBREVIATIONS SHOWN ABOVE MAY NOT BE USED WITHIN
THIS DRAWING SET.
A
A/C AIR CONDITIONING
AD AREA DRAIN
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALUM ALUMINUM
ANOD ANODIZED
ARCH ARCHITECT
@ AT
B
BD BOARD
BLDG BUILDING
BO BOTTOM OF
C
C CELSIUS
CCSF CLOSED-CELL SPRAY-APPLIED FOAM
CH COAT HOOK
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CG CORNER GUARD
CI CONTINUOUS INSULATION
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CT CERAMIC TILE
CTJ CONSTRUCTION JOINT
CUH CABINET UNIT HEATER
D
D DEEP
DEG DEGREE
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
DWGS DRAWINGS
E
EA EACH
EJ EXPANSION JOINT
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EOS EDGE OF SLAB
ERD EXISTING ROOF DRAIN
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
F
F FAHRENHEIT
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FDC FIRE DEPARTMENT CONNECTION
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FE FIRE EXTINGUISHER
FG FINISH GRADE
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FND FOUNDATION
FO FINISHED OPENING
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FRG FIBER REINFORCED GYPSUM
FSP FIRE STANDPIPE
FT FEET
G
GA GAUGE
GALV GALVANIZED
GFRC GLASS-FIBER-REINFORCED
CONCRETE
GFRG GLASS-FIBER-REINFORCED GYPSUM
GL GLASS
GWB GYPSUM WALL BOARD
GYP GYPSUM
H
H HIGH
HB HOSE BIBB
HDR HEADER
HM HOLLOW METAL
HPT HIGH POINT
HR HOUR
HT HEIGHT
I
ID INSIDE DIAMETER; INSIDE DIMENSION
IN INCH
INFO INFORMATION
INT INTERIOR
J
JAN JANITOR
K (NOT USED)
L
LAB LABORATORY
LAV LAVATORY
LBS POUNDS
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LPT LOW POINT
M
MACH RM MACHINE ROOM
MAX MAXIMUM
MFR MANUFACTURER
MECH MECHANICAL
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
N
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER;
OUTSIDE DIMENSION
OFD OVERFLOW DRAIN
OH DR OVERHEAD DOOR
OPH OPPOSITE HAND
OPP OPPOSITE
ORIG ORIGINAL
P
P LAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PR PAIR
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
PVC POLYVINYL CHLORIDE
Q
QT QUARRY TILE
R
R RISER OR RADIUS
RAD RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIDGERATOR
REQD REQUIRED
REV REVISION
RH RELATIVE HUMIDITY
RM ROOM
RO ROUGH OPENING
RTU ROOF TOP UNIT
RWL RAIN WATER LEADER
S
S SMOKE DETECTOR
SAM SELF ADHESIVE MEMBRANE
SCHED SCHEDULE
SECT SECTION
SIM SIMILAR
SPEC SPECIFICATION
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
T
T TREAD
TEL TELEPHONE
TEMP TEMPORARY
THK THICK
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF SLAB; TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
TO TOP OF
U
UL UNDERWRITER'S LABORATORIES
UNO UNLESS NOTED OTHERWISE
V
VCT VINYL COMPOSITE TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W
W/ WITH
W/O WITHOUT
WD WOOD
WH WALL HYDRANT
WP WORKING POINT
WRB WEATHER RESISTIVE BARRIER
X,Y,Z (NOT USED)
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
/8 /2
:1
:3
P M
A u to d e sk
D o c s:
S L
C o
A D
C T u rn st il e s_ r2
/A R
C H
_2
A D
C T u rn st il e s
R e n o v a ti o n _2
.r v t
GENERAL
INFORMATION
LS
25030
1 AUGUST 2025
CONSTRUCTION
SET
G-002
SMS
S
W
S o u th S a lt
L a k e
U T
S a lt L a k e C o u n ty
A D
C L
O B
B Y
T U
R N
S T
IL
E
S
INTERNATIONAL PLUMBING CODE
NATIONAL ELECTRICAL CODE
ZONING ORDINANCE:
INTERNATIONAL MECHANICAL CODE
INTERNATIONAL FIRE CODE
INTERNATIONAL ENERGY CONSERVATION CODE
INTERNATIONAL BUILDING CODE
ACCESSIBILITY CODE
DESIGN CRITERIA
APPLICABLE CODES OTHER CRITERIA
DEFERRED SUBMITTALS
ICC/ANSI A117.1-2021
2021 EDITION
2021 EDITION
2021 EDITION
2021 EDITION
2021 EDITION
2023 EDITION
Zoning OrdinanceSALT LAKE CITY
SHEET INDEX
x_450 CONCEPTUAL SECURITY CHECKPOINT PLAN
GENERAL:
G-001 COVER SHEET
G-002 GENERAL INFORMATION
G-101 LEVEL 01 EXITING & OCCUPANCY PLANS
ARCHITECTURAL:
A-101 REMODEL PLANS
A-102 BID ALTERNATES
A-501 MILLWORK DETAILS
ELECTRICAL:
E-001 GENERAL NOTES & DETAILS
EE-101 LEVEL 1 FLOOR PLAN - DEMOLITION SYSTEMS &
POWER
# Date Revision
C R
DH
P
P
CORRIDOR
STAIR
STAIR
CONFERENCE
VIEWING
WOMEN'S
SALLYPORT
SECURITY
CHECKPOINT
TOILET
SHOWERSSHOWERS
MENS
EXISTING CONSTRUCTION NOT IN
CONTRACT INDICATED BY HATCHED AREA
EXISTING CONSTRUCTION NOT IN
CONTRACT INDICATED BY HATCHED AREA
OFFICE
OFFICE
OFFICE
OFFICE
EXISTING CONSTRUCTION NOT IN
CONTRACT INDICATED BY HATCHED AREA
EXISTING FIRE ALARM PULL
SECURITY
BOUNDARY
546 SF
100B
CORRIDOR
353 SF
100B
SECURITY
CHECKPOINT
CONTROL ROOM
EMERGENCY
EQUIPMENT
EXIT CORRIDOR
1057 SF
7A
BRIEFING
ROOM
LOCKER ROOM
EXIT
REQ'D PROVIDED
OCCUPANT
LOAD
15.2" 36"76*0.2
REQ'D PROVIDED
OCCUPANT
LOAD
15" 36"75*0.2
REQ'D PROVIDED
OCCUPANT
LOAD
16" 36"80*0.2
EXIT
J131A
J131
EXIT ACCESS TRAVEL DISTANCE PER
TABLE 1017.2, WITH SPRINKLERS:
OCCUPANCY
MAX. TRAVEL
DISTANCE
BUSINESS AREAS (B) 300'
ASSEMBLY: NO FIXED STG (A-2) 250'
STORAGE (S-1) 400'
STORAGE (S-2) 400'
UTILITY / MISC. SERVICES (U-1) 400'
TRAVEL DISTANCE
COMMON PATH OF TRAVEL
COMMON PATH OF TRAVEL DISTANCE
PER TABLE 1006.2.1, WITH SPRINKLERS:
OCCUPANCY
MAX. TRAVEL
DISTANCE
BUSINESS AREAS (B) 100'
ASSEMBLY: NO FIXED STG (A-2/A-3) 75'
STORAGE (S-1) 100'
STORAGE (S-2) 100'
UTILITY / MISC. SERVICES (U-1) 75'
PATH OF TRAVEL
EGRESS
NUMBER OF OCCUPANTS PER
EXIT/EGRESS PATH
FIRE RATING KEY
FIRE EXTINGUISHERS
COORDINATE TYPE AND LOCATION WITH
LOCAL FIRE MARSHALL
OCCUPANCY TAG
ROOM NAME
Name
150 SF
A-3 000
ROOM AREA
OCCUPANCY TYPE
OCCUPANCY LOAD FACTOR
OCCUPANT LOAD
NO RATING -
NEW METAL STUD WALL
EXISTING CMU/CONCRETE WALL
(SECTION 1005.1)
EGRESS WIDTH
OTHER EGRESS COMPONENT WIDTH PER OCCUPANT
OTHER EGRESS COMPONENT WIDTH PROVIDED
OTHER EGRESS COMPONENT WIDTH REQUIRED
0.2"
5.8"
(SECTION 1003)
(SECTION 1004.1)
(TABLE 1004.1.1)
MEANS OF EGRESS
DESIGN OCCUPANT LOAD
FLOOR AREA IN SQUARE FEET PER OCCUPANT
ACTUAL FLOOR AREA
100 GROSS
905 SF
(SECTION 1020.1, TABLE 1020.1, SECTION 1021.2 & TABLE 1021.2)
EXITS 2 PER
1021.1.2
IBC 2021 - GENERAL CODE REQUIREMENTS
ALTERATION
CODE REFERENCE AREA '1'
[Draft 5 - 07.14.04]
AREA '2' AREA '3' BUILDING
(SECTIONS 302-312)
OCCUPANCY CLASSIFICATION
B N/A I-3
LESSNEW OCCUPANCY MORE OR LESS HAZARDOUS?
"...THE USE OR OCCUPANCY OF EXISTING BUILDINGS SHALL BE PERMITTED TO BE CHANGED AND THE BUILDING IS ALLOWED TO BE OCCUPIED FOR PURPOSES IN OTHER GROUPS WITHOUT CONFORMING TO ALL THE REQUIREMENTS OF THIS CODE FOR THOSE GROUPS, PROVIDED THE NEW OR PROPOSED USE IS LESS HAZARDOUS, BASED ON LIFE AND FIRE
RISK, THAN THE EXISTING USE."
(CHAPTER 34)
EXISTING STRUCTURES
(SECTION 3402.1)
"PORTIONS OF THE STRUCTURE NOT ALTERED AND NOT AFFECTED BY THE ALTERATION ARE NOT REQUIRED TO
COMPLY WITH THE CODE REQUIREMENTS FOR A NEW STRUCTURE."
(SECTION 3402.2)
"ADDITIONS OR ALTERATIONS TO AN EXISTING STRUCTURE SHALL NOT INCREASE THE FORCE IN ANY STRUCTURAL ELEMENT BY MORE THAN 5 PERCENT, UNLESS THE INCREASED FORCES ON THE ELEMENT ARE STILL IN COMPLIANCE WITH THE CODE FOR NEW STRUCTURES, NOR SHALL THE STRENGTH OF ANY STRUCTURAL ELEMENT
BE DECREASED TO LESS THAN THAT REQUIRED BY THIS CODE FOR NEW STRUCTURES."
N/A
N/A
N/A
EXISTING
EXISTING
EXISTING
N/A
N/A
2(SEE REGULATORY PLANS)
(SEE DWGS) N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
EXISTING
EXISTING
EXISTING
(SEE IPC SECTION 419.2 FOR URINALS)
(SEE IPC SECTION 410.1)
(SECTION 2902 & TABLE 2902.1) NO. PROVIDED
RATIO REQUIREMENT (MALE / FEMALE)
MINIMUM PLUMBING FACILITIES COLUMN
LEGEND: NO. REQUIRED
WATER CLOSETS
LAVATORIES
DRINKING FOUNTAINS
4 4
7 7
1:25 (<50) + 1:50 (>50)
1: 125/65
1:100
1:40 (<80) + 1:80 (>80)
1: 200/200
1:500
NOTE: CHANGE IN OCCUPANCY DOES NOT REQUIRE CHANGES TO
PLUMBING FACILITIES. NO CHANGE TO WATER CLOSETS.
NOTE: CHANGE IN OCCUPANCY DOES NOT REQUIRE CHANGES TO
PLUMBING FACILITIES. NO CHANGE TO LAVATORIES.
NOTE: CHANGE IN OCCUPANCY DOES NOT REQUIRE CHANGES TO
PLUMBING FACILITIES. (2) EXISTING DRINKING FOUNTAINS RELOCATED.
EXISTING FIXTURES IN SCOPE OF WORK TO REMAIN
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
/8 /2
:1
:4
P M
A u to d e sk
D o c s:
S L
C o
A D
C T u rn st il e s_ r2
/A R
C H
_2
A D
C T u rn st il e s
R e n o v a ti o n _2
.r v t
LEVEL 01
EXITING &
OCCUPANCY
PLANS
LS, AS
25030
1 AUGUST 2025
CONSTRUCTION
SET
G-101
SMS
S
W
S o u th S a lt
L a k e
U T
S a lt L a k e C o u n ty
A D
C L
O B
B Y
T U
R N
S T
IL
E
S
PATH #
COMMON
PATH OF
TRAVEL
LONGEST
PATH OF
TRAVEL
1 38' - 3" 130' - 10"
2 42' - 7" 106' - 2"
TAG DESCRIPTION
1/8" = 1'-0"G-101
A6 LEVEL 01 - OCCUPANCY & EXITING PLAN
J3
JD
JD.3
JE
JE.4
15' - 11"
CONTROL ROOM
3" 3' - 4" 3" 6' - 0 1/2" 5' - 7 1/4" ± 5 1/4"
11:MD1
11:PC1
01:QS1
09:LV1
26:CR1
26:CR1
26:PW1
09:LV1
AD
JU
ST
T
O E
XI
ST
IN
G
T
IL
ES
01:CF1
01:CF1
01:CF1
01:CF1
02:EF1
02:EF1
03:CS2
03:CS2
C L 4'
7"
7'
1" 3'
2"
9'
3/
4" 9'
1/ 4"
VI
F
1'
5"
28:CR2
09:LV2
A-501 A2
28:CR2
11:PC2
5 1/4" 4' - 5" 11' - 0 3/4" ±
09:FT1
09:FT1
09:FT1
09:FT1
09:FT1
C L
6'
8"
J3
JD
JD.3
JE
JE.4
26:LL3
26:LL3
26:LL3
09:AP1
09:AP1
11:PC3
11:PC3
26:PW1
09:AP1
10:TV1
A. ALL NEW WALL ASSEMBLIES ARE CONTINUOUS TO
BOTTOM OF DECK UNLESS NOTED OTHERWISE.
B. PLAN WALL DIMENSIONS ARE TO GRID LINE OR FACE OF
WALL STRUCTURE, UNLESS NOTED OTHERWISE. "CLEAR"
DIMENSIONS ARE TO FACE OF WALL FINISH.
C. FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR
COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE
COMMENCEMENT OF WORK. COORDINATE
DISCREPANCIES WITH ARCHITECT.
D. DO NOT SCALE DRAWINGS.
E. COORDINATE ALL ITEMS WITH STRUCTURAL, MECHANICAL
AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.
F. SEE G SERIES SHEETS FOR WALL TYPES AND TYPICAL
ACCESSIBILITY CLEARANCE AND COMPLIANCE
REQUIREMENTS.
G. PROVIDE BACKING BEHIND ALL SURFACE MOUNTED
EQUIPMENT, FURNITURE ITEMS THAT REQUIRE
ANCHORING, WALL MOUNTED ACCESSORIES AND/OR
FIXTURES PER DETAIL .
H. REUSE OR REPLACE ANY MATERIAL TRANSITION
THRESHOLDS AT EXISTING DOORS AS NEEDED TO
COMPLETE THE WORK DURING THE TILE DEMOLITION OR
NEW TILE FLOORING INSTALLATION.
I. VERIFY DOOR NUMBERING AND LABELING WITH OWNER /
FACILITIES MANAGEMENT DURING THE WIRING AND
LABELING OF DOORS AT CLOSE OUT. CONTRACTOR IS TO
PROVIDE DOOR LABELS ON THE TOP OF THE DOOR JAMB
ON BOTH SIDES.
GENERAL NOTE - FLOOR PLAN
/C1 x_A701
A. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR
ADDITIONAL LIGHTING AND DIFFUSER INFORMATION.
B. THE CEILING HEIGHT SHOWN IN THE ROOM TAG
INDICATES THE HEIGHT OF THE DOMINANT CEILING
FINISH. SEE ADDITIONAL CEILING FINISH CALLOUTS OR
DETAILS FOR OTHER CEILING HEIGHTS OR FEATURES.
C. THE CONTRACTOR SHALL COORDINATE ALL TRADES TO
ENSURE THAT DESIGNATED CEILING HEIGHTS CAN BE
ACHEIVED. NOTIFY ARCHITECT OF ANY CONFLICTS OR
CONDITIONS THAT PREVENT THIS FROM OCCURRING
BEFORE PROCEEDING WITH THE WORK.
D. REFER TO ASSEMBLY TYPES SHEETS FOR CEILING
ASSEMBLIES.
GENERAL NOTE - RCP
JD
JD.3
JE
JE.4
02:EF1
02:EF1
AD
JU
ST
T
O E
XI
ST
IN
G
T
IL
E
FO
R M
AT
/2
02:ER1
02:EM1
02:EE1
6' - 6"
3'
6" 4'
7"
3'
6"
5'
3" 4'
7"
02:DC3
02:DC3
2'
0"
5'
6"
4' - 4" 1' - 4"
5' - 8"
02:DV1
CORRIDOR
J122
02:EM2
JD
JD.3
JE
JE.4
02:RL1
02:RL1
02:RL1
02:DC4
02:DC4
02:DC4
CORRIDOR
J122
J3
JD
JD.3
JE
JE.4
CONTROL ROOM
BRIEFING ROOM
SECURITY
CHECKPOINT
J122
EQ 1' - 6" EQ
09:FT1
09:FT1
09:FT1
09:FT1
LVT2
LVT1
LVT2
FLOOR FINISH LEGEND
CUT 18"x18" TILES
AS SHOWN
A. PROTECT WALLS, CEILINGS, FLOORS AND OTHER
EXISTING FINISH WORK THAT ARE TO REMAIN OR THAT
ARE EXPOSED DURING SELECTIVE DEMOLITION
OPERATIONS
B. PATCH AND REPAIR DAMAGE IN WALLS, CEILINGS, AND
FLOORS RESULTING FROM DEMOLITION OF EXISTING
ITEMS OR CONSTRUCTION OF NEW ITEMS AND/OR
REPLACE WITH NEW TO MATCH EXISTING. CLEAN AND
PREPARE TO RECEIVE NEW FINISH.
C. PROTECT ADJACENT AREAS FROM DUST AND DEBRIS
DURING SELECTIVE DEMOLITION OPERATIONS.
D. TRANSPORT DEMOLISHED MATERIALS OFF OWNER'S
PROPERTY AND LEGALLY DISPOSE OF DEBRIS.
E. FIELD VERIFY EXISTING CONDITIONS AND THEIR
COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE
COMMENCEMENT OF WORK. COORDINATE
DISCREPANCIES WITH ARCHITECT.
F. CLEAN ADJACENT IMPROVEMENTS OF DUST, DIRT, AND
DEBRIS CAUSE BY SELECTIVE DEMOLITION OPERATIONS.
RETURN ADJACENT AREAS TO CONDITION EXISTING
BEFORE SELECTIVE DEMOLITION OPERATIONS BEGAN.
G. SEE MECHANICAL, ELECTRICAL, AND AUDIO-VISUAL
DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE
DISCREPANCIES WITH ARCHITECT PRIOR TO PROCEEDING
WITH WORK.
GENERAL NOTE - DEMOLITION PLAN
A. THE ABSENCE OF A VIEW DOES NOT PRECLUDE THE
REQUIREMENT TO PROVIDE A FINISH AS INDICATED BY
THE FINISH SCHEDULE.
B. SEE FLOOR FINISH PLANS AND INTERIOR ELEVATION
VIEWS, WHERE DRAWN, FOR ADDITIONAL FINISH
LOCATION, TYPE, AND TRANSITION INFORMATION.
C. SEE REFLECTED CEILING PLANS FOR CEILING FEATURES
AND FINISH ELEVATIONS.
D. SATIN-NICKEL COUNTERTOP GROMMETS ARE TO BE
PROVIDED AND THEIR LOCATION COORDINATED WITH THE
OWNER/FACILITIES MANAGEMENT/ARCHITECT PRIOR TO
INSTALLATION. QUANTITIES TO MATCH NUMBER OF
DESKS/WORKSTATIONS.
ALL FINISHES:
1. WHERE A FINISH IS PARTLY HIDDEN BY AN OBJECT,
EXTEND THAT FINISH BEHIND THE OBJECT.
2. WHERE MULTIPLE FINISHES ARE SCHEDULED, REFER TO
FLOOR FINISH PLANS OR INTERIOR ELEVATIONS FOR
LOCATIONS OF TRANSITIONS.
FLOOR FINISHES:
1. EXTEND FLOOR FINISHES UNDER COUNTERS, INTO KNEE
SPACES AT CABINETS, AND UNDER ALL OTHER OBJECTS
SHOWN IN FINISH PLANS THAT MAY OBSCURE THE
EXTENT OF THE FLOOR FINISH.
BASE FINISHES:
1. ROOMS WHERE BASE SCHEDULED, PROVIDE BASE AT ALL
WALLS WHETHER OR NOT IT IS SHOWN IN ELEVATION,
INCLUDING ALCOVES AND OFFSETS.
WALLS:
1. EXTEND ALL WALL FINISHES BEHIND CABINETS, MIRRORS
AND INTO OTHER ARES THAT MAY BE HIDDEN IN
ELEVATION VIEWS.
CEILINGS:
1. PAINT AREAS ABOVE SUSPENDED CEILINGS THAT ARE
VISIBLE FROM BELOW. COLOR: BLACK.
2. VESTIBULE J111 PAINT ALL EXISTING ACCESS PANELS/
GRILL TO MATCH SCHEDULE CEILING PAINT.
GENERAL NOTES - FINISHES
1/4" = 1'-0"A-101
A4 LEVEL 01 - BASE BID FLOOR PLAN
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
/8 /2
:1
:4
P M
A u to d e sk
D o c s:
S L
C o
A D
C T u rn st il e s_ r2
/A R
C H
_2
A D
C T u rn st il e s
R e n o v a ti o n _2
.r v t
REMODEL
PLANS
LS
25030
1 AUGUST 2025
CONSTRUCTION
SET
A-101
SMS
S
W
S o u th S a lt
L a k e
U T
S a lt L a k e C o u n ty
A D
C L
O B
B Y
T U
R N
S T
IL
E
S
1/4" = 1'-0"A-101
C4 LEVEL 01 - ENLARGED REFLECTED CEILING PLAN
1/4" = 1'-0"A-101
A3 LEVEL 01 - BASE BID DEMOLITION FLOOR PLAN
1/4" = 1'-0"A-101
C3 LEVEL 01 - DEMO. REFLECTED CEILING PLAN
KEYNOTE LEGEND
01:CF1 39" CLEAR FLOOR SPACE
REQUIREMENT FOR CEILING
SENSOR. KEEP AREA CLEAR.
01:QS1 QUEUING AREA
02:DC3 DEMOLISH PORTION OF SLAB
APPROX. 3" DEEP FOR CONDUIT
TIE-IN WITH DFLOW GLASS
BARRIERS; COORDINATE W/
MANUFACTURER. SIZE PER PLAN.
02:DC4 SALVAGE 2X4 ACOUSTIC CEILING
PANEL; IF DAMAGED CONTRACTOR
RESPONSIBLE TO REPLACE WITH
MATCHING CEILING TILE
02:DV1 DEMOLISH EXISTING VINYL
COMPOSITION TILE; SCRAP/CLEAN
FLOOR TO PREPARE FOR INSTALL OF
NEW TILE. CONTRACTOR TO
REPLACE ANY DAMAGED TILES.
02:EE1 EXISTING OFFICE CHAIR AND
COMPUTER TO RETURN TO OWNER
02:EF1 EXISTING VINYL COMPOSITION TILE
TO REMAIN & PROTECT IN PLACE
02:EM1 EXISTING METAL DETECTOR TO
RETURN TO OWNER
02:EM2 EXISTING HANGING MAIL STORAGE
TO REMAIN; PROTECT IN PLACE
DURING CONSTRUCTION. IF
REMOVABLE CONTRACTOR TO
REMOVE , PROTECT & STOE DURING
DEMOLITION. RE-INSTALL PRIOR TO
CONSTRUCTION COMPLETION.
PROVIDE NEW VANDAL RESISTANT
FASTENERS, CAULKING AS
NECESSARY TO PROVIDE LIKE NEW
INSTALLATION. IF DAMAGED
CONTRACTOR TO PROVIDE SIMILAR
GRADE & STYLE AT CONTRACTORS
EXPENSE.
02:ER1 EXISTING RECEPTION DESK/TABLE
TO RETURN TO OWNER
02:RL1 REMOVE EXISTING LIGHTING,
PROTECT IN PLACE UNTIL REINSTALL
03:CS2 NEW CONCRETE SLAB FILL, MATCH
EXISTING ADJACENT CONCRETE
SLAB ELEVATION; COORDINATE
ELECTRICAL CONDUIT RUNS WITH
DFLOW GLASS BARRIERS
09:AP1 2' X 4' LAY-IN ACOUSTICAL PANEL
CEILING; MATCH EXISTING IF
SALVAGED PANELS ARE DAMAGED.
09:FT1 PROVIDE FLOOR TRANSITION (BOD:
SCHLUTER VINRO-S OR VINPRO-T);
ARCHITECT TO APPROVE BEFORE
INSTALL. CONTRACTOR TO REMOVE
& REPLACE IF ANY VCT OR LVT
FLOORING IS DAMAGED DURING
CONSTRUCTION & DEMO; REPLACED
DAMAGED VCT MUST MATCH
EXISTING.
09:LV1 18"X18" LVT FLOORING; COORDINATE
PLACEMENT W/ ARCHITECT BEFORE
INSTALL; REFER TO FINISH
SCHEDULE
09:LV2 CUSTOM CUT SHAPE LVT FLOORING;
CUT & LAY AS SHOWN; COORDINATE
PLACEMENT W/ ARCHITECT BEFORE
INSTALL; REFER TO FINISH
SCHEDULE
10:TV1 CONTRACTOR PROVIDED
CONTRACTOR INSTALLED; CEILING
MOUNTED TV, ATTACH DIRECTLY TO
STRUCTURE OR PEERLESS- AV
HEAVY DUTY 2'-0" X 2'-0" SUSPENDED
CEILING TILE SECURE TO
STRUCTURAL CEILING WITH TIE
WIRES & SAFETY CABLES, TAMPER
RESISTANT/ EQUAL. COORDINATE
WITH ELECTRICAL FOR POWER &
DATA. EXACT HEIGHT TO BE
COORDINATED WITH OWNER &
SECURITY SYSTEM.
11:MD1 GARRETT PD 6500I METAL DETECTOR
BY OWNER
11:PC1 PEDESTRIAN CONTROL ACCESS
GATE (BOD: DFLOW MODEL 1200
GLASS BARRIER ULTRA WIDE)
11:PC2 PEDESTRIAN CONTROL ACCESS
GATE (BOD: DFLOW MODEL 900
GLASS BARRIER)
11:PC3 PEDESTRIAN CONTROL CEILING
SENSOR CENTERED ABOVE ACCESS
GATES PER MFR REQ'S
26:CR1 CARD SCANNER LOCATION
26:LL3 2' X 4' LAY-IN LIGHT FIXTURE; SEE
ELECTRICAL
26:PW1 4"X4" METAL POWER POLE COLUMN
RUNNING FLOOR TO CEILING;
COORDINATE WITH ELECTRICAL
28:CR2 INTEGRATED CARD READER
CONNECTED TO DOOR HARDWARE &
FIRE ALARM; CARD READERS ON
BOTH SIDES OF DOOR
1/4" = 1'-0"A-101
A6 LEVEL 01 - BASE BID FINISH FLOOR PLAN
FINISH LEGEND
CODE FINISH TYPE DESCRIPTION
FLOOR FINISHES
LVT1 LUXURY VINYL TILE MANUFACTURER: MANNINGTON COMMERCIAL
COLLECTION: UPWARD 20
STYLE: STONE
COLOR: TERRATZI MEZZO, UPW40-1231
SIZE: MATCH EXISTING
LVT2 LUXURY VINYL TILE MANUFACTURER: MANNINGTON COMMERCIAL
COLLECTION: AMTICO SIGNATURE ABSTRACT
MATERIAL EFFECT: STONE
COLOR: STUCCO FLAX, AR0AUC39
SIZE: 18"X18"; UNLESS PLANS SHOW CUT TO TRIANGLE SIZE
BASE FINISHES
MT4 UNDER BASE FINISHES MANUFACTURER: FRY REGLET
4" CHANNEL BASE W/ RETURN KEY
RB1 4" RUBBER BASE MANUFACTURER: TARKETT
STYLE: MILLWORK BASE, MONUMENT, MW-48-S4
SIZE: 4"
COLOR: 48 GREY
WALL FINISHES
P1 PAINTED CMU (IF NEEDED) MANUFACTURER: SHERWIN WILLIAMS
COLOR: SW7636 ORAGAMI WHITE
FINISH: SATIN EGGSHEL
CEILING FINISHES
ACP1 24" X 48" ACOUSTICAL
CEILING PANEL
MATCH EXISTING
MILLWORK
MT1 METAL - STAINLESS STEEL STAINLESS STEEL
FINISH MATTE
MT2 METAL - STAINLESS STEEL STAINLESS STEEL TO MATCH FINISH BELOW
MANUFACTURER MOZ
COLLECTION: CLASSIC STEEL
COLOR: LAVENDAR SILK
FINISH: MATTE
MT3 METAL TRIM MANUFACTURER: FRY REGLET
COLLECTION: DRYWALL PROFILES
STYLE: SNAP IN REVEAL
COLOR: BUFFED BRITE BLACK
SIZE: 1/2" DRM-SNAP-IN-50
SS1 SOLID SURFACE MANUFACTURER: FORMICA
STYLE: SOLID SURFACE
COLOR: 757 LUNA SAND
ROOM FINISH SCHEDULE
Room Name Floor Base
Walls
Ceiling CommentsN E S W
J122 SECURITY CHECKPOINT LVT1/LVT2 RB1 P1 (TOUCH-UP) P1 (TOUCH-UP P1 (TOUCH-UP P1 (TOUCH-UP MATCH EXIST
REFER TO FLOOR FINISH LEGEND & FINISH SCHEDULE
JC
JC.3
JC.6
JC.8
JD
JD.3
JE
JE.4
01:CL1
THIS AREA IS WITHIN
THE BASE BID
09:FT1
09:FT1
09:FT1 09:FT1
09:FT1
09:FT1
09:FT1
09:FT1
09:FT1
09:FT1
09:FT1
09:FT1
09:LV1
09:LV1
JC
JC.3
JC.6
JC.8
JD
JD.3
JE
JE.4
01:CL1
02:DV1
THIS AREA IS WITHIN
THE BASE BID
02:DV1
A. ALL NEW WALL ASSEMBLIES ARE CONTINUOUS TO
BOTTOM OF DECK UNLESS NOTED OTHERWISE.
B. PLAN WALL DIMENSIONS ARE TO GRID LINE OR FACE OF
WALL STRUCTURE, UNLESS NOTED OTHERWISE. "CLEAR"
DIMENSIONS ARE TO FACE OF WALL FINISH.
C. FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR
COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE
COMMENCEMENT OF WORK. COORDINATE
DISCREPANCIES WITH ARCHITECT.
D. DO NOT SCALE DRAWINGS.
E. COORDINATE ALL ITEMS WITH STRUCTURAL, MECHANICAL
AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.
F. SEE G SERIES SHEETS FOR WALL TYPES AND TYPICAL
ACCESSIBILITY CLEARANCE AND COMPLIANCE
REQUIREMENTS.
G. PROVIDE BACKING BEHIND ALL SURFACE MOUNTED
EQUIPMENT, FURNITURE ITEMS THAT REQUIRE
ANCHORING, WALL MOUNTED ACCESSORIES AND/OR
FIXTURES PER DETAIL .
H. REUSE OR REPLACE ANY MATERIAL TRANSITION
THRESHOLDS AT EXISTING DOORS AS NEEDED TO
COMPLETE THE WORK DURING THE TILE DEMOLITION OR
NEW TILE FLOORING INSTALLATION.
I. VERIFY DOOR NUMBERING AND LABELING WITH OWNER /
FACILITIES MANAGEMENT DURING THE WIRING AND
LABELING OF DOORS AT CLOSE OUT. CONTRACTOR IS TO
PROVIDE DOOR LABELS ON THE TOP OF THE DOOR JAMB
ON BOTH SIDES.
GENERAL NOTE - FLOOR PLAN
/C1 x_A701
A. PROTECT WALLS, CEILINGS, FLOORS AND OTHER
EXISTING FINISH WORK THAT ARE TO REMAIN OR THAT
ARE EXPOSED DURING SELECTIVE DEMOLITION
OPERATIONS
B. PATCH AND REPAIR DAMAGE IN WALLS, CEILINGS, AND
FLOORS RESULTING FROM DEMOLITION OF EXISTING
ITEMS OR CONSTRUCTION OF NEW ITEMS AND/OR
REPLACE WITH NEW TO MATCH EXISTING. CLEAN AND
PREPARE TO RECEIVE NEW FINISH.
C. PROTECT ADJACENT AREAS FROM DUST AND DEBRIS
DURING SELECTIVE DEMOLITION OPERATIONS.
D. TRANSPORT DEMOLISHED MATERIALS OFF OWNER'S
PROPERTY AND LEGALLY DISPOSE OF DEBRIS.
E. FIELD VERIFY EXISTING CONDITIONS AND THEIR
COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE
COMMENCEMENT OF WORK. COORDINATE
DISCREPANCIES WITH ARCHITECT.
F. CLEAN ADJACENT IMPROVEMENTS OF DUST, DIRT, AND
DEBRIS CAUSE BY SELECTIVE DEMOLITION OPERATIONS.
RETURN ADJACENT AREAS TO CONDITION EXISTING
BEFORE SELECTIVE DEMOLITION OPERATIONS BEGAN.
G. SEE MECHANICAL, ELECTRICAL, AND AUDIO-VISUAL
DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE
DISCREPANCIES WITH ARCHITECT PRIOR TO PROCEEDING
WITH WORK.
GENERAL NOTE - DEMOLITION PLAN
A. THE CONSTRUCTION DOCUMENTS, AS PROVIDED AND
DESIGNED HERE-IN, HAVE BEEN DOCUMENTED AND
DETAILED "IN FULL," DEMOSTRATING THE SCOPE OF
WORK IF ALL OF THE BID ALTERNATES WERE TO BE
ACCEPTED AND EXECUTED. THE FOLLOWING BID
ALTERNATE PROVIDES DETAILS AND DESCRIPTIONS TO
BETTER GAIN AN UNDERSTANDING OF THE SCOPE OF
WORK.
GENERAL NOTE - BID ALTS
JC
JC.3
JC.6
JC.8
JD
JD.3
JE
JE.4
01:CL1
THIS AREA IS WITHIN
THE BASE BID
LVT1
LVT1
A. THE ABSENCE OF A VIEW DOES NOT PRECLUDE THE
REQUIREMENT TO PROVIDE A FINISH AS INDICATED BY
THE FINISH SCHEDULE.
B. SEE FLOOR FINISH PLANS AND INTERIOR ELEVATION
VIEWS, WHERE DRAWN, FOR ADDITIONAL FINISH
LOCATION, TYPE, AND TRANSITION INFORMATION.
C. SEE REFLECTED CEILING PLANS FOR CEILING FEATURES
AND FINISH ELEVATIONS.
D. SATIN-NICKEL COUNTERTOP GROMMETS ARE TO BE
PROVIDED AND THEIR LOCATION COORDINATED WITH THE
OWNER/FACILITIES MANAGEMENT/ARCHITECT PRIOR TO
INSTALLATION. QUANTITIES TO MATCH NUMBER OF
DESKS/WORKSTATIONS.
ALL FINISHES:
1. WHERE A FINISH IS PARTLY HIDDEN BY AN OBJECT,
EXTEND THAT FINISH BEHIND THE OBJECT.
2. WHERE MULTIPLE FINISHES ARE SCHEDULED, REFER TO
FLOOR FINISH PLANS OR INTERIOR ELEVATIONS FOR
LOCATIONS OF TRANSITIONS.
FLOOR FINISHES:
1. EXTEND FLOOR FINISHES UNDER COUNTERS, INTO KNEE
SPACES AT CABINETS, AND UNDER ALL OTHER OBJECTS
SHOWN IN FINISH PLANS THAT MAY OBSCURE THE
EXTENT OF THE FLOOR FINISH.
BASE FINISHES:
1. ROOMS WHERE BASE SCHEDULED, PROVIDE BASE AT ALL
WALLS WHETHER OR NOT IT IS SHOWN IN ELEVATION,
INCLUDING ALCOVES AND OFFSETS.
WALLS:
1. EXTEND ALL WALL FINISHES BEHIND CABINETS, MIRRORS
AND INTO OTHER ARES THAT MAY BE HIDDEN IN
ELEVATION VIEWS.
CEILINGS:
1. PAINT AREAS ABOVE SUSPENDED CEILINGS THAT ARE
VISIBLE FROM BELOW. COLOR: BLACK.
2. VESTIBULE J111 PAINT ALL EXISTING ACCESS PANELS/
GRILL TO MATCH SCHEDULE CEILING PAINT.
GENERAL NOTES - FINISHES
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
/8 /2
:1
:4
P M
A u to d e sk
D o c s:
S L
C o
A D
C T u rn st il e s_ r2
/A R
C H
_2
A D
C T u rn st il e s
R e n o v a ti o n _2
.r v t
BID
ALTERNATES
LS
25030
1 AUGUST 2025
CONSTRUCTION
SET
A-102
SMS
S
W
S o u th S a lt
L a k e
U T
S a lt L a k e C o u n ty
A D
C L
O B
B Y
T U
R N
S T
IL
E
S
3/16" = 1'-0"A-102
A4 LEVEL 01 - BID ALT FLOOR PLAN - ADD SCOPE
3/16" = 1'-0"A-102
A2 LEVEL 01 - BID ALT DEMOLITION PLAN - ADD SCOPE
KEYNOTE LEGEND
01:CL1 CLEARED CONSTRUCTION LIMIT.
OUTSIDE OF THIS AREA WILL REQUIRE
APPROVAL FROM OWNER.
02:DV1 DEMOLISH EXISTING VINYL
COMPOSITION TILE; SCRAP/CLEAN
FLOOR TO PREPARE FOR INSTALL OF
NEW TILE. CONTRACTOR TO REPLACE
ANY DAMAGED TILES.
09:FT1 PROVIDE FLOOR TRANSITION (BOD:
SCHLUTER VINRO-S OR VINPRO-T);
ARCHITECT TO APPROVE BEFORE
INSTALL. CONTRACTOR TO REMOVE &
REPLACE IF ANY VCT OR LVT
FLOORING IS DAMAGED DURING
CONSTRUCTION & DEMO; REPLACED
DAMAGED VCT MUST MATCH EXISTING.
09:LV1 18"X18" LVT FLOORING; COORDINATE
PLACEMENT W/ ARCHITECT BEFORE
INSTALL; REFER TO FINISH SCHEDULE
LVT1 LUXURY VINYL TILE
3/16" = 1'-0"A-102
A6 LEVEL 01 - BID ALT FINISH FLOOR PLAN - ADD SCOPE
FLOATING COUNTERTOP
WALL BRACKET @ 32" o.c.
PROVIDE (1) 2" GROMMET IN
COUNTERTOP, SEE PLAN FOR LOCATION
SCHEDULED SOLID SURFACE
COUNTERTOP W/ 3/4" SUBSTRATE
4" BASE REGLET
ELECTRICAL OUTLET, COORDINATE
W/ ELECTRICAL DRAWINGS
2X4 WOOD STUD FRAMING
STAINLESS STEEL LAMINATE
OVER 3/4" PLYWOOD SUBSTRATE
3/4" MILLWORK PANEL W/
STAINLESS STEEL LAMINATE
A-501 C6
1/
2"
8" 2'
/6
4"
8 1/8" 1' - 11 1/8"
3'
/6 4"
3/4" PLYWOOD BASE LAYER
STAINLESS STEEL LAMINATE
OVER 3/4" PLYWOOD SUBSTRATE
4" MILLWORK CHANNEL BASE
3/4" MILLWORK PANEL W/
STAINLESS STEEL LAMINATE
A-501 C6
2X4 WOOD STUD FRAMING
3/4" PLYWOOD BASE LAYER
8" 2'
3'
6"
1' - 7 1/2"
3/4"3/4"
B2
A-501
MT2
SS1
MT1
C5
A-501
MT2
MT1
B2
A-501
EQ 3' - 0" EQ
MT2MT2
MT1
B5
A-501
MT2
B3
A-501
3'
6"MT2MT2 MT2
EQ 3' - 0" EQ
MT1
SS1
B6
A-501
C5
A-501
MT1
MT2
B3
A-501
MT2 MT2 MT2MT2
MT1
EQ 3' - 0" EQ
MT1
A-501
A4
A-501
A3
B2
A-501
B3
A-501
______A-501
A5
1/
4" 5'
4"
1/
4" 3'
3/ 4"
1/
4" 1/
4"
2 1/4" 5' - 8"
2 1/4"
A-501
A6
1/
4"
1/ 2"
1/
4"
MT1 TRANSACTION TOP
METAL LAMINATE PLYWOOD PANELS (LIGHT GRAY POCHE)
2x4 FRAMING (DARK GRAY POCHE)
8" 1'
/1
6"
11 1/2" 8"
2 1/4" 4' - 4 1/4"
3/4"5'
1/
2" 3'
6"
6' - 0 1/2"
3/4"
3/4" MILLWORK PANEL W/
STAINLESS STEEL LAMINATE
MILLWORK INSIDE CORNER TRIM
W/ RETURN KEYS, BLACK
(BOD: FRY REGLET MWCISC75)
PLYWOOD BASE LAYER
3/4" MILLWORK PANEL W/
STAINLESS STEEL LAMINATE
MILLWORK 3/4" CORNER ACCENT, BLACK
(BOD: FRY REGLET MWCK75)
3/4" PLYWOOD BASE LAYER3/4" MILLWORK PANEL W/
STAINLESS STEEL LAMINATE
MILLWORK 1/4" POST TRIM, BLACK
(BOD: FRY REGLET MWP2575)
3/4" PLYWOOD BASE LAYER
3/4" MILLWORK PANEL W/
STAINLESS STEEL LAMINATE
4" MILLWORK CHANNEL BASE W/
RETURN KEY, BLACK
(BOD: FRY REGLET MWCB75400)
PLYWOOD BASE LAYER
4"
A-501
D3 3D SECURITY CHECKPOINT AREA
KEYNOTE LEGEND
MT1 BRUSHED STAINLESS STEEL LAMINATE
MILLWORK PANEL; SEE FINISH
SCHEDULE FOR MORE INFO
MT2 COLORED STAINLESS STEEL LAMINATE
MILLWORK PANEL; SEE FINISH
SCHEDULE FOR MORE INFO
SS1 SOLID SURFACE; SEE FINISH SCHEDULE
FOR MORE INFO
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
/8 /2
:1
:5
P M
A u to d e sk
D o c s:
S L
C o
A D
C T u rn st il e s_ r2
/A R
C H
_2
A D
C T u rn st il e s
R e n o v a ti o n _2
.r v t
MILLWORK
DETAILS
LS
25030
1 AUGUST 2025
CONSTRUCTION
SET
A-501
SMS
S
W
S o u th S a lt
L a k e
U T
S a lt L a k e C o u n ty
A D
C L
O B
B Y
T U
R N
S T
IL
E
S
1 1/2" = 1'-0"A-501
B2 SECURITY COUNTER MILLWORK DETAIL @ WORKTOP
1 1/2" = 1'-0"A-501
B3 SECURITY COUNTER MILLWORK DETAIL
1/2" = 1'-0"A-501
A6 SECURITY CHECKPOINT - ELEV. - N
1/2" = 1'-0"A-501
A4 SECURITY CHECKPOINT - ELEV. - S
1/2" = 1'-0"A-501
A3 SECURITY CHECKPOINT - ELEV. - W
1/2" = 1'-0"A-501
A5 SECURITY CHECKPOINT - ELEV. - E
OWNER PROVIDED OWNER
INSTALLED TV; MOUNT PROVIDED &
INSTALLED BY CONTRACTOR
1/2" = 1'-0"A-501
A2 LEVEL 01 - ENLARGED FRONT DESK
3" = 1'-0"A-501
C5 INSIDE CORNER MILLWORK REGLET
3" = 1'-0"A-501
B5 OUTSIDE CORNER MILLWORK REGLET
3" = 1'-0"A-501
B6 MILLWORK DIVIDER REGLET
3" = 1'-0"A-501
C6 MILLWORK CHANNEL BASE REGLET
DETAIL
NOT TO
SCALE
SCALE:
D1
TYPICAL ROUGH−IN DETAIL
NOTES:
IN ACCORDANCE W/ IBC 711.3.2, OUTLETS ON OPPOSITE SIDES OF
FIRE RATED WALLS OR PARTITIONS IN THE SAME STUD SPACE
MUST BE SEPARATED BY MIN. OF 24" HORIZONTAL DISTANCE.
1. TYP. FOR WOOD & METAL STUD ROUGH-IN.
2. PLASTER RINGS NOT SHOWN.
3. LOCATE ALL OUTLET BOXES IN
ACCORDANCE W/ ARCH. & MECH. DWGS.,
AND W/ ALL APPLICABLE SHOP DWGS.
TYPICAL DUPLEX
OUTLET BOX
TYPICAL SWITCH
OUTLET BOX
BAR
STRAPS
BAR
STRAPS
TYPICAL WALL
OUTLETS
PROVIDE CONDUIT SUPPORTS IN
ACCORDANCE W/ NEC SPACING
REQUIREMENTS FOR THE TYPE OF
RACEWAY REQUIRED
AS REQUIRED FOR TYPE OF
CONSTRUCTION
STEEL CITY NO.
7501 BOX SUPPORT
DETAIL
NOT TO
SCALE
SCALE:
A
B
NOTES:
1. THE CONTRACTOR MUST COORDI NATE EXACT LOCATI ON OF THE DI SCONNECT WI TH THE MECHANI CAL
CONTRACTOR TO ELI MINATE ANY OBSTACLE (PI PE,CONCRETE PAD ETC. ) I N FRONT OF THE DISCONNECT.
IF THERE ARE ANY OBSTACLES, PROVI DE UNI STRUT AND INSTALL THE DI SCONNECT NEXT TO
MECHANI CAL EQUI PMENT I N ORDER TO PROVI DE THE REQUI RED CLEARANCE.
2. PROVI DE MINI MUM CLEARANCE AS FOLLOWS:
SYSTEM VOLTAGE
A B
42"
36" 30"
30"
DISCONNECT
SWITCH
FLEXIBLE LIQUID
TIGHT METALLIC
CONDUIT
MECHANICAL
EQUIPMENT
TYPICAL
CLEARED
SPACE
TYPICAL DISCONNECT CLEARANCE REQUIREMENTS
D2
DETAIL
NOT TO
SCALE
SCALE:
NOTE:
TYPI CAL DETAILS SHOWI NG GENERAL FI RE
STOPPI NG PROCEDURE . ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SP ACE BETWEEN
PI PE AND/ OR I NSULATI ON AND OPENING.
FOLLOW MANUFACTURER' S I NSTRUCTI ONS.
DAMMING MATERIAL
(BACKER ROD, FIBERGLASS
OR MINERAL WOOL)
3M FIRE BARRIER
CP 25WB CAULK
FIRE RATED CONCRETE
FLOOR SLAB
CONDUIT OR
INSULATED CABLES
TYPICAL FIRESTOP FOR CABLES/CONDUIT
THROUGH CONCRETE FLOORINGD3
DETAIL
NOT TO
SCALE
SCALE:
NOTE:
TYPI CAL DETAILS SHOWI NG GENERAL FI RE
STOPPI NG PROCEDURE . ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SP ACE BETWEEN
PI PE AND/ OR I NSULATI ON AND OPENING.
FOLLOW MANUFACTURER' S I NSTRUCTI ONS.
CP 25WB CAULK ON
BOTH SIDES OF WALL
INSULATED CABLES OR CONDUIT
FIRE RATED CONCRETE/CONCRETE
BLOCK WALL
DAMMING MATERIAL
(BACKER ROD, FIBER−GLASS
OR MINERAL WOOL)
NON−METALLIC SLEEVE MAY
EXTEND A MAX 2" (51 mm)
BEYOND THE WALL SURFACE
TYPICAL FIRESTOP FOR CABLES/CONDUIT
THROUGH CONCRETE WALLSD4
DETAIL
NOT TO
SCALE
SCALE:
D5
NOTE:
TYPICAL DETAIL SHOWING GENERAL FIRE
STOPPING PROCEDURE. ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SPACE BETWEEN
PIPE AND/OR INSULATION AND OPENING.
FOLLOW MANUFACTURER'S INSTRUCTIONS.
1/4" MINIMUM DIAMETER
BEAD OF 3M FIRE BARRIER CP
25 CAULK OR MP MOLDABLE
PUTTY
METALLIC
CONDUIT
1/4" MINIMUM DIAMETER
BEAD OF 3M FIRE BARRIER
CP 25 CAULK OR MP
MOLDABLE PUTTY
1 OR 2 HOUR FIRE RATED
GYPSUM WALL BOARD
WOOD OR STEEL STUD
FIRESTOP FOR METAL CONDUIT
THROUGH GYPSUM WALL BOARD
DETAIL
NOT TO
SCALE
SCALE:
PULL
FIRE
ELECTRICAL
OUTLETS
FIRE ALARM PULL STATION
LIGHT SWITCHES
M
IN
M A
X
STROBE LIGHT OR
HORN & STROBE
STANDARD HEIGHTS FOR HANDICAPPED ACCESS
D6
M
IN
IM
U
M
M A
X
NL
E
X
S
EWC
J
T
S
ELECTRICAL SYMBOLS LIST
SYMBOL DESCRIPTION
LIGHTING SYMBOLS
LIGHT FIXTURE TO STAY ON AT NIGHT (NIGHT LIGHT). PROVIDE UNSWITCHED LIGHTING CIRCUIT.
LIGHT FIXTURE ON EMERGENCY POWER PROVIDE BATTERY AS REQUIRED
REFERENCE NOTES CALL OUT
SINGLE POLE TOGGLE SWITCH - 20 AMP
POWER SYMBOLS
DUPLEX CONVENIENCE OUTLET - 20 AMP
DUPLEX CONVENIENCE OUTLET - 20 AMP, GFCI PROTECTED.
DUPLEX CONVENIENCE OUTLET - 20 AMP ELECTRIC WATER COOLER
FOUR - PLEX CONVENIENCE OUTLET - 20 AMP
JUNCTION BOX - SIZE AND FUNCTION AS REQUIRED
EACH ARROW INDICATES A HOME RUN. RUN GROUND CONDUCTOR REGARDLESS OF CONDUIT TYPE.
NUMBER OF CONDUCTORS AS REQUIRED
FUSED DISCONNECT SWITCH - SIZE AS REQUIRED-STANDARD HEIGHT TO BE 66" AFF TO THE TOP
FLUSH TELEPHONE, DATA OUTLET
FLUSH TELEPHONE OUTLET
FLUSH DATA OUTLET
MOTOR LOCATION
MECHANICAL EQUIPMENT CALL OUT
MANUAL DISCONNECT WITH THERMAL OVERLOAD PROTECTION
ELECTRICAL PANEL LOCATION
GENERAL NOTE SYMBOLS
WP INDICATES WEATHER PROOF EQUIPMENT
A INDICATES DEVICE IS ABOVE COUNTER TOP-42" AFF REFER TO ARCHITECTURAL ELEVATION
CLG INDICATES DEVICES MOUNTED ON THE CEILING, COORDINATE LOCATION WITH THE ARCHITECT.
XX−1
DETAIL
NOT TO
SCALE
SCALE:
D38
TYPICAL CONDUIT RACK SUPPORT DETAIL
CONDUIT CLAMP - 3/4" TO 1"
UNISTRUT 2 PIECE CHANNEL
PIPE STRAPS - 1 1/4" TO 6"
BEAM CLAMP, HANGER CLAMP,
OR APPROVED SUPPORT, AS
REQUIRED BY WEIGHT
SUPPORTED
UNISTRUT CHANNEL -
SIZE AS REQUIRED BY
WEIGHT SUPPORTED
RACEWAY 3/4" TO 6" (TYP.)
ALL THREAD ROD
SIZE AS REQUIRED
(MIN. 3/8")
1. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE (NEC) AND
ALL THE LOCAL CODES.
2. PROVIDE TAMPER-RESISTANCE RECEPTACLES IN THE AREAS WHERE KIDS ARE PRESENT, AND
AREAS REQUIRED BY NEC 406.12(3). INCLUDING DWELLING UNITS, GUEST ROOMS,
PRESCHOOL/ELEMENTARY/ CHILDCARE FACILITIES, WAITING ROOMS, ETC.
3. NOT MORE THAN THREE (3) CIRCUITS SHALL BE INSTALLED IN A 3/4" CONDUIT.
4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. DO NOT SHARE THE NEUTRAL
CONDUCTOR IN HOMERUNS. (NEC 210.4).
5. THE MINIMUM SIZE OF THE CONDUCTORS SHALL BE A NO. 12 AWG, THHN COPPER. UNLESS
INDICATED OTHERWISE ON THE DRAWINGS.
6. LIGHT FIXTURES, RACEWAYS AND OTHER ELECTRICAL DEVICES SHALL BE SUPPORTED FROM
THE STRUCTURE NOT FROM METAL OR WOOD CEILING DECK. UTILIZE UNISTRUTS IN BETWEEN
STRUCTURE AS NEEDED.
7. ALL J-BOXES SHALL BE RECESSED INTO THE FINISHED WALL/CEILING UNLESS THE FINISHED
WALL/CEILING IS CONCRETE AND IS NOT BEING FURRED OUT. ALL CONDUITS SHALL BE RUN
THROUGH THE STUDS BEHIND THE FINISHED WALL/CEILING. COORDINATE WITH
ENGINEER/ARCHITECT PRIOR TO ROUGH-IN FOR ANY EXPOSED CONDUITS/J-BOX THAT
CANNOT BE RUN INSIDE THE WALL/CEILING AND NEED TO BE SURFACE MOUNTED ON THE
FINISHED WALL/CEILING. SURFACE MOUNTED CONDUITS IN EXPOSED CEILING SHALL BE
INSTALLED CLOSE TO CEILING (AND NOT PENDANT MOUNTED BELOW THE
BEAMS/STRUCTURE).
8. PROVIDE GFCI PROTECTED OUTLETS FOR EVERY LOCATION SHOWN ON THE DRAWINGS. DO
NOT USE MULTIPLE LOCATION PROTECTION.
9. WHERE CIRCUIT CONDUCTORS ARE TO BE INCREASED IN SIZE TO MEET THE VOLTAGE DROP
REQUIREMENT, THE EQUIPMENT GROUNDING CONDUCTORS MUST BE INCREASED
ACCORDINGLY (NEC 250.122)
10. ALL J-BOXES SHALL HAVE A MINIMUM DEPTH OF 2-1/8" UNLESS OTHERWISE SPECIFIED.
SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD RINGS.
11. ALL THE HOMERUNS MUST BE ACCESSIBLE. DO NOT CARRY A HOMERUN FROM ONE DEVICE
TO ANOTHER WHICH IS TIED TO A SEPARATE HOMERUN INSIDE THE WALL. MARK ON ALL THE
J-BOXES THE CIRCUIT NAMES AND NUMBERS.
12. ALL J-BOXES IN FIRE RATED WALLS SHALL MEET THE FIRE RATING REQUIREMENT OF THE
WALL AND SHALL NOT BE INSTALLED LESS THAN 24" BACK-TO-BACK.
13. ALL DISCONNECTS SHALL BE OF A HEAVY-DUTY TYPE.
14. ALL DISCONNECTS, J-BOXES, AND CONDUITS EXPOSED TO THE OUTSIDE WEATHER AND
MECHANICAL ROOMS SHALL BE OF A NON-CORROSIVE, WEATHERPROOF TYPE.
15. ALL NEW EXPOSED CONDUITS MUST RUN AGAINST THE WALL OR CEILING. DO NOT PENDANT
MOUNT ANY CONDUIT FROM THE CEILING. EXPOSED CONDUITS ARE ONLY ALLOWED IN
EXPOSED CEILING AREA.
16. ALL MATERIALS USED IN INSTALLATION SHALL BE U.L. APPROVED AND NEW.
17. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (ROMEX NOT PERMITTED).
18. ALL EXTERIOR RECEPTACLES SHALL BE OF WEATHER-RESISTANT TYPE AS PER NEC 406.8.
19. NO CONDUITS SHALL RUN IN DUCT WORK.
20. CABLES OR RACEWAYS INSTALLED IN EXPOSED OR CONCEALED LOCATIONS UNDER METAL-
CORRUGATED SHEET ROOF DECKING SHALL BE INSTALLED AND SUPPORTED SO THAT THE
NEAREST OUTSIDE SURFACE OF THE CABLE OR RACEWAY IS NOT LESS THAN 38 MM (1 1/2 IN.)
FROM THE NEAREST SURFACE OF THE ROOF DECKING.
21. PROVIDE LATERAL AND LONGITUDINAL BRACING FOR ALL CONDUIT RACKS, CABLE TRAYS,
ETC., EXCEEDING 20 FEET IN LENGTH.
22. MINIMUM SIZE CONDUIT SHALL BE 3/4" FOR INTERIOR APPLICATION, AND 1" FOR CONDUIT
BURIED BELOW GRADE IN EXTERIOR APPLICATION.
23. LABELING IS REQUIRED FOR ALL PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL
CENTERS, MOTOR STARTERS, TRANSFORMERS, MAJOR JUNCTION BOXES, DISCONNECT
SWITCHES, BREAKERS, PUSH BUTTONS, ETC., INTERLOCKS AND RELAY PANELS.
24. USE RIGID STEEL, SET SCREW TYPE FITTINGS ONLY. DIE CAST FITTING SHALL NOT BE USED.
25. USE EPOXY ANCHORS TO SUPPORT THE ELECTRICAL EQUIPMENT. EXPANSION ANCHOR
BOLTS ARE NOT ACCEPTABLE.
26. AT THE END OF THE JOB, PROVIDE BLANK, MATCHING COVER PLATES FOR ALL J-BOXES
WHERE DEVICES HAVE NOT YET BEEN INSTALLED.
27. SEAL AROUND ALL CONDUIT PENETRATIONS THROUGH WALLS AND CEILINGS WITH A FIRE
RATED MATERIAL. 3M IS AN APPROVED MANUFACTURER.
28. PRIOR TO SUBMITTAL FOR A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND
INCLUDE IN THEIR BID PACKAGE ALL CHARGES RELATED TO EXISTING CONDITIONS AND
DEMOLITION WORK. PROVIDE SHOP DRAWINGS AS REQUIRED BY CONSTRUCTION
DOCUMENTS. ALL LABOR, MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A
PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT. REPLACE OR REPAIR
ALL DEFECTS DURING THE GUARANTEED PERIOD.
29. THE ELECTRICAL CONTRACTOR SHALL TERMINATE THE ELECTRICAL CONNECTIONS TO ALL
THE EQUIPMENT BY PROVIDING THE NECESSARY MALE/ FEMALE CONNECTOR, RECEPTACLE,
PLUG, ETC.
30. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE,
CONNECTION REQUIREMENT, ETC.) OF EQUIPMENT FURNISHED UNDER OTHER DIVISIONS
WITH APPROVED SHOP DRAWINGS.
31. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ENGINEER, IN WRITING, OF ANY
DISCREPANCIES FOUND BETWEEN THE INTENDED FUNCTION OF EQUIPMENT AND EQUIPMENT
SPECIFIED IN THE CONTRACT DOCUMENTS WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR
TO ISSUANCE OF THE FINAL ADDENDUM. FAILURE TO REPORT ANY DISCREPANCY (CATALOG
NUMBERS, DISCONTINUED ITEMS, ETC.) DOES NOT RELIEVE THE CONTRACTOR FROM
PROVIDING EQUIPMENT WHICH SHALL CONFORM TO AND FULFILL THE INTENT OF THE
CONTRACT DOCUMENTS. NOR SHALL IT BE USED AS A CONDITION TO OBTAIN ADDITIONAL
FUNDS FROM THE OWNER AFTER THE CONTRACT IS AWARDED. THE CONTRACTOR SHALL
REQUEST ALL CLARIFICATIONS OF CONTRACT DOCUMENT REQUIREMENTS, IN WRITING, TO
THE ARCHITECT/ ENGINEER WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE
OF THE FINAL ADDENDUM.
32. CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS
SPECIFICALLY NOTED OTHERWISE.
33. THE OWNER MUST SCHEDULE INTERRUPTIONS OF SERVICE WHEN CONTRACTOR WISHES TO
MAKE UTILITY CONNECTIONS. NOTIFY, IN WRITING, THE OWNER'S REPRESENTATIVE 72 HOURS
PRIOR TO TIME WHEN INTERRUPTION IS DESIRED. INTERRUPTION MUST BE AT THE COUNTY'S
CONVENIENCE. OVERTIME, IF REQUIRED FOR THIS WORK, IS TO BE AT CONTRACTOR’S
EXPENSE.
34. ALL CONDUCTORS SHALL BE IN CONDUIT (3/4" MINIMUM). MC CABLES ARE ONLY ALLOWED
FOR CONNECTION TO THE LIGHT FIXTURES. (MAXIMUM OF 6').
35. ALL METALLIC CONDUITS, JOINTS, FITTINGS, ETC. IN CONTACT WITH THE GROUND SHALL BE SPIRAL WRAPPED WITH 3M SCOTCHRAP-51, 20 MIL TAPE (OR APPROVED EQUAL). 1/2" OVERLAP
IS REQUIRED.
36. PROVIDE TYPED PANEL INDEX FOR EXISTING ELECTRICAL PANELS AFFECTED BY THE SCOPE
OF THIS WORK. EXISTING/UNAFFECTED CIRCUITS IN THE PANEL SHALL BE ITALICIZED AND
CHANGED/ADDED CIRCUITS SHALL BE TYPED BOLD.
GENERAL NOTES:
334543-2202
MANSOUR
AGHDASI
NO.
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
#1016
/3
/2
:0
:2
A
M
A u to d e s k D o c s
/2
S
L C o A
D C
T u rn s ti le s r2
/1
S L
C O
A D
C T u rn s ti le
.r v t
GENERAL
NOTES &
DETAILS
Author
25030
08.01.25
CD SET
E-001
S
W
S
O U
T H
S A
L T
L A
K E
U
T
S a lt
L a k e
C o u n ty
A D
C L
O B
B Y
T U
R N
S T
IL
E
S
# Date Revision
2. CIRCUIT NUMBERS ARE SCHEMATIC AND SHOW THE DESIGN INTENTION AND LOAD BALANCE REQUIREMENTS. CONTRACTORS SHALL VERIFY ALL EXISTING AVAILABLE CIRCUITS AND THOSE WHICH BECOME AVAILABLE AS A RESULT OF DEMOLITION. CONTRACTOR SHALL INDICATE ACTUAL CIRCUITS USED ON AS-BUILT DRAWINGS. THE CONTRACTOR IS TO INFORM GC/ENGINEER IF SUFFICIENT BREAKER SPACES DID NOT FREE UP, PRIOR TO ROUGH-IN.
1. PROVIDE NEW CIRCUIT BREAKERS AS NECESSARY. NEW BREAKERS SHALL MATCH AIC RATING OF EXISTING BREAKERS.
NOTES:
Total Est. Demand: 6 A
Total Conn.: 6 A
Total Est. Demand: 2020 VA
Receptacle 1300 VA 100.00% 1300 VA Total Conn. Load: 2020 VA
Power 720 VA 100.00% 720 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 3 A 14 A 0 A AIC: Total Load: 360 VA 1660 VA 0 VA
20 A 1 EXISTING -- E 41 0 / 0 42 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 39 0 / 0 40 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 37 0 / 0 38 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 35 0 / 0 36 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 33 0 / 0 34 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 31 0 / 0 32 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 29 0 / 0 30 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 27 0 / 0 28 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 25 0 / 0 26 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 23 0 / 0 24 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 21 0 / 0 22 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 19 0 / 0 20 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 17 0 / 0 18 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 15 0 / 0 16 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 13 0 / 0 14 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 11 0 / 0 12 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 9 0 / 0 10 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 7 0 / 0 8 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 5 0 / 0 6 E -- EXISTING 1 20 A
20 A 1 EXISTING -- E 3 0 / 1660 4 N Po... OUTLETS & POLE - CORR J122 1 20 A 20 A 1 EXISTING -- E 1 0 / 360 2 N Po... J-BOX - TURNSTILE AND DIGCON 1 20 A
BREAKE
R
A P
DESCRIPTION TYPE
E/ N
CIR.
A B C
CIR.
E/ N
TYPE DESCRIPTION
BREAKE
R P A
AMPS: 250 A MAIN: Volts: 120/208 Wye PHASE: 3 # OF WIRES: 4 MOUNTING: Surface LOCATION:
EXISTING PANEL NLJ2A
C R
C R
J
C R
S
S
JJ
J
C R
J
J
CR
C R
J1
JC.6
JC.8
JD
JD.3
JE
JE.4
J2 J3
BRIEFING ROOM
EXIT CORRIDOR
J123
SALLYPORT
J120
STAIR
J118
STAIR
P3
P1
P4
P2
NLJ2A-2,4
TYP
P6
P3
SECURITY CHECKPOINT
J351
CLG
CLG
P5
P2
P8
P10
A
CLG
CLG
P12
J1
JC.6
JC.8
JD
JD.3
JE
JE.4
J2 J3
P7
P7
P11
NLJ2B NHJ1
NHJ1A
NHJ1.2
NLJ2
NLJ2A
EXISTING
COMM.
ROOM
APPROXIMATE PATH
OF 3/4" CONDUIT
NORTH
1/8" = 1’−0"
LEVEL 1 FLOOR PLAN − FIRE ALARM/ SYSTEMS & POWER
REFERENCE NOTES
P1 FURNISH AND INSTALL A 4"X4" FLOOR TO CEILING METAL POWER POLE WITH POWER/COMMUNICATION DIVIDER IN THE
APPROXIMATE LOCATION SHOWN. PROPERLY SECURE THE POWER POLE ON THE FLOOR AND CEILING. UTILIZE THE POWER POLE TO PROVIDE POWER/DATA CABLE TO THE DESK AND EQUIPMENT SHOWN. LEGRAND/WIREMOLD IS THE APPROVED
MANUFACTURER.
P2 PROVIDE ONE 120 VOLT DEDICATED POWER TO THE TURNSTILE AND DIGCON. COORDINATE EXACT LOCATION WITH THE SUPPLIER PRIOR TO ROUGH-IN. RUN A CAT6 CABLE FROM EACH TURNSTILE AND ANOTHER ONE FROM DIGICON TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS.
COORDINATE THIS WORK WITH ADC. IN ADDITION, RUN CAT6 CABLE IN 3/4" CONDUIT FROM THE CEILING SENSOR TO THE CORRESPONDING TURNSTILE FOR SIGNAL. COORDINATE WITH THE SUPPLIER AND SAWCUT THE FLOOR TO RUN POWER AND COMMUNICATION CABLES AS NEEDED. RUN THE POWER AND THE CAT6 CABLE FOR THE CEILING MOUNTED SENSORS IN THE
POWER POLE.
P3 CARD READERS ARE INTEGRATED AS PART OF THE ACCESS GATE. THE CONTRACTOR IS TO COORDINATE WITH THE EQUIPMENT SUPPLIER AND RUN NEW CAT6 CABLE IN 1" CONDUIT FROM THE CARD READER TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK WITH ADC.
P4 RELOCATE EXISTING CARD READERS TO THE NEW LOCATIONS SHOWN. FURNISH AND INSTALL NEW J-BOX. RUN A CAT6 CABLE IN 1" CONDUIT FROM THE J-BOX TO THE COMMUNICATION ROOM. ALSO RUN PROPER CONDUCTORS (TO MATCH EXISTING CARD READERS) IN 3/4" CONDUIT TO THE COMMUNICATION ROOM FOR THE ELECTRIFIED DOOR HARDWARE AND DOOR CONTACT.
TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK WITH ADC. THE CONTRACTOR IS ALLOWED TO REUSE EXISTING DATA CABLE FOR THE CARD READER IF POSSIBLE.
P5 FURNISH AND INSTALL A NEW J-BOX FOR THE CCTV CAMERA. RUN A CAT6 CABLE FROM THE J-BOX TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK
WITH ADC. COORDINATE WITH ADC FOR EXACT LOCATION.
P6 FURNISH AND INSTALL A 4"X4" X2-1/8" J-BOX WHERE VOICE/DATA OUTLETS ARE SHOWN. RUN A CAT6 CABLE IN 1" CONDUIT FROM THE J-BOX TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK WITH ADC. COORDINATE WITH THE OWNER/ARCHITECT FOR THE EXACT LOCATION
PRIOR TO ROUGH-IN.
P7 RELOCATE THE EXISTING LIGHT FIXTURES AND THE ASSOCIATED CIRCUIT TO THE NEW LOCATION SHOWN TO ALLOW THE
INSTALLATION OF TURNSTILE DEVICES.
P8 FURNISH AND INSTALL A NEW J-BOX IN THE APPROXIMATE LOCATION SHOWN FOR CARD READER. RUN A CAT6 CABLE IN 1" CONDUIT FROM THE J-BOX TO THE COMMUNICATION ROOM. ALSO RUN PROPER CONDUCTORS (TO MATCH EXISTING CARD READERS) IN 3/4" CONDUIT TO THE COMMUNICATION ROOM FOR THE ELECTRIFIED DOOR HARDWARE AND DOOR CONTACT.
TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR CABLE/JACKS. COORDINATE WITH THE GC/DOOR
HARDWARE FOR CONDUCTOR PATH. COORDINATE THIS WORK WITH ADC.
P10 RELOCATE THE EXISTING CAMERA AND ASSOCIATED CONDUIT/CABLE TO THE APPROXIMATE LOCATION SHOWN. ENSURE THE CAMERA IS OPERATIONAL AFTER THE RELOCATION. COORDINATE WITH ADC FOR EXACT LOCATION.
P11 ROTATE THE EXISTING EXIT SIGN 90 DEGREES. REPLACE THE FRONT FACE WITH A DIRECTING FACE WITH AN ARROW. POINT THE
ARROW TOWARD THE EXIT DOOR.
P12 PROVIDE POWER TO THE DOOR ALARM. COORDINATE WITH THE DOOR HARDWARE SUPPLIER FOR EXACT TERMINATION POINT
PRIOR TO ROUGH-IN.
SHEET NOTES - DEMOLITION
1 ALL MATERIALS THAT ARE TO BE REMOVED FROM THE PREMISES SHALL BE RETURNED TO THE OWNER. MATERIALS WHICH THE
OWNER DECIDES NOT TO KEEP SHALL BE SALVAGED AND REMOVED FROM THE SITE BY THE CONTRACTOR.
2 ALL CONCEALED CONDUITS THAT CANNOT BE REMOVED SHALL BE CUT FLUSH WITH THE FINISHED SURFACES AND CAPPED OFF AFTER THE WIRING HAS BEEN DISCONNECTED AT THE PANEL AND REMOVED FROM THE CONDUIT.
3 IN AREAS WHERE CIRCUIT CONTINUITY IS INTERRUPTED BUT MUST BE MAINTAINED BECAUSE OF THE NATURE OF THE FACILITY, MAKE ALL THE NECESSARY MODIFICATIONS TO THE CIRCUITS IN ORDER TO MAINTAIN THE CIRCUITS INTEGRITY.
334543-2202
MANSOUR
AGHDASI
NO.
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
#1016
/3
/2
:0
:2
A
M
A u to d e s k D o c s
/2
S
L C o A
D C
T u rn s ti le s r2
/1
S L
C O
A D
C T u rn s ti le
.r v t
LEVEL 1 FLOOR
PLAN -
DEMOLITION,
SYSTEMS &
POWER
Author
25030
08.01.25
CD SET
EE-101
MA
S
W
S
O U
T H
S A
L T
L A
K E
U
T
S a lt
L a k e
C o u n ty
A D
C L
O B
B Y
T U
R N
S T
IL
E
S
# Date Revision
NORTH
1/8" = 1’−0"
LEVEL 1 FLOOR PLAN − DEMOLITION
0' 2' 4' 8'
0' 2' 4' 8'
NORTH
1" = 20’−0"
OVERALL PLAN
| GENERAL |
| G-001 - COVER SHEET |
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .