7--8- Plans- FAC125305 ADC Lobby Turnstiles.pdf

PDF 4 MB Posted

Attached to
SLCo FAC125305 ADC Lobby Turnstiles - CONST
Solicitation number
SLCo FAC125305 ADC Lobby Turnstiles - CONST
Issued by
Utah

About this file

This is a construction document set for the Salt Lake County ADC Lobby Turnstiles Renovation project located at 3415 S. 900 W. South Salt Lake, UT 84119. The project involves renovating the security checkpoint and lobby area, with a construction set dated August 1, 2025. The scope includes installing new turnstiles, reconfiguring the security checkpoint, updating electrical systems, and making associated architectural modifications. The project is being managed by Architectural NEXUS, Inc. for Salt Lake County, with electrical consulting by EE-LD.

The project documents indicate a comprehensive renovation focusing on the security entrance, including new millwork, flooring (luxury vinyl tile), wall treatments, and electrical infrastructure updates. The design incorporates stainless steel finishes, relocated lighting and camera systems, and integration of new card readers and power systems. The estimated construction timeline appears to be for completion in August 2025, with detailed plans for electrical relocations, power distribution, and system integration. The project will utilize existing electrical panel NLJ2A and involves careful coordination of existing systems with new installations, ensuring minimal disruption to the facility's operations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S . 9

W

C O

U N

TY

J

A

IL

P R

IV

A

TE

R

O A

DSCOPE OF WORK

Nexus Project #: Owner Project #:

VICINITY MAP

PROJECT LOCATION

Salt Lake County

ADC LOBBY

TURNSTILES

3415 S. 900 W.

South Salt Lake, UT 84119

CONSTRUCTION SET

1 AUGUST 2025

25030

RENOVATION OF SECURITY CHECKPOINT.

SLCo ADC SECURITY CHECKPOINT LEVEL 01

ACCESSIBLE FROM THE PARKING LOT ON THE WEST SIDE

OF BUILDING AT THE RADIUSED PORTION OF THE

BUILDING. AREA IS NORTH OF THE RAMP TO THE SECOND

LEVEL LOBBY.

DENOTED BY HEAVY DASHED LINE

RAMP

CONTACT: E-MAIL:

PHONE: INTERNET:

OWNER

SALT LAKE COUNTY

2001 S. State Street Suite S3200

Salt Lake City, UT 84190

385.468.0338

John Bergen jbergen@slco.org http://www.slco.org

CONTACT: E-MAIL:

PHONE: INTERNET:

ARCHITECT

Architectural NEXUS, Inc.

2505 East Parleys Way

Salt Lake City, UT 84109

801.924.5000

Stephen Springer sspringer@archnexus.com http://www.archnexus.com

CONTACT: E-MAIL:

PHONE: INTERNET:

ELECTRICAL CONSULTANT

EE-LD

1220 South 300 West

Salt Lake City, UT 84101

801.486.2222

Mansour Aghdasi mansour@ee-ld.com http://www.ee-ld.com t 2

08/15/20240808088080808088808888808080808080880880808088080808888000000000000000000000000000000000000000000000000000000000000 /15/5//5/5//5/5/5/5///5/5////////5///////5/////5///5/5/////////////5//5/5///////5/////5/////5////5//5/////////5//5//////////5/////5555555555555555555555555555555555555555555555555555 0202020202020020000020002020020200200202000200000200000202000020000002000020020000000200020200000222222222222222222222222222222222222222222222222222222222222222222222222222222222222 2422222222222222222222222222222222222222222222222222222222222222

MATCH LINE

A1 / Axxx

MATCH LINE TAG

EXISTING WALL TO REMAIN

WALL TO BE DEMOLISHED

NEW WALL

BREAK LINE

CENTER LINE SYMBOL

0' 4' 8' 16'

REVISION DESIGNATION

ELEVATION SYMBOL

T.O. WALL

100'-0"

REVISION NUMBER

ELEVATION ABOVE DATUM

ELEVATION DESCRIPTION

DRAWING SYMBOL LEGEND

000M

CASEWORK TYPE DESIGNATION

CDS NUMBER (M DENOTES

MODIFICATION - SEE SHEET

A551 FOR MODIFIED MILLWORK

ELEVATIONS AND DETAILS)

00"

00"

00"

MODIFICATION DESCRIPTION

AWS STANDARD CDS NUMBERING SYSTEM

WIDTH

HEIGHT

DEPTH

NORTH ARROW

PLAN NORTH

GRAPHIC SCALES

ROUND BREAK LINE

REVISION CLOUD

SLOPE INDICATION

1/2" / 12"

DETAIL REFERENCE

A2 A401

A1

A3

INTERIOR ELEVATIONS

DETAIL NUMBER

SHEET NUMBER

A1

A501

DETAIL REFERENCE

DETAIL NUMBER

SHEET NUMBER

A1

A201

EXTERIOR ELEVATION REFERENCE

SHEET NUMBER

DETAIL NUMBER

A1

A302

WALL SECTION REFERENCE

SHEET NUMBER

DETAIL NUMBER

A1

A301

BUILDING SECTION REFERENCE

DETAIL NUMBER

SHEET NUMBER

XX000X

00'-00"

ROOM DESIGNATION (FLOOR PLAN)

ROOM NUMBER

ROOM NAME

A1

A301

DETAIL NUMBER

SHEET NUMBER

ROOM DESIGNATION (REFLECTED

CEILING PLAN)

CEILING HEIGHT ABOVE FINISH FLOOR

ROOM NUMBER

00001

GLASS TYPE DESIGNATION

KEYED NOTE DESIGNATION

WALL TYPE DESIGNATION

EQUIPMENT DESIGNATION

WINDOW DESIGNATION

DOOR DESIGNATION

GLASS TYPE

EQUIPMENT NUMBER

KEY NOTE NUMBER

WINDOW TYPE

DOOR NUMBER

WALL TYPEXXX

MATERIAL TYPE DESIGNATION

FINISH NUMBER

SEE AI601 FINISH LEGEND

00001

12" 1/2

RISE

RUN

TRUE NORTH

CL

03:CJ1

ROOM

A1

A301

DETAIL / SHEET NUMBER

1t

CAST-IN-PLACE CONCRETE

CONCRETE MASONRY UNIT

PRECAST CONCRETE / GLASS FIBER

REINFORCED CONCRETE (GFRC)

STEEL STUDS

WOOD STUDS

BRICK VENEER

RIGID INSULATION

BATT INSULATION

CONTINUOUS MATERIAL

NON CONTINUOUS MATERIAL

(BLOCKING)

GYPSUM BOARD

PLYWOOD

GRAVEL

UNDISTURBED EARTH

HATCH LEGEND

NOTE: HATCHING ANGLES MAY VARY DUE TO ANGLE OF WALL DRAWN, WHILE HATCHING PATTERN REMAINS SIMILAR.

BACKFILL OR FILL

BALLISTIC RATED FIBERGLASS

LIST OF ABBREVIATIONS

THE PRECEDING LIST OF ABBREVIATIONS IS PRESENTED AS A GENERAL GUIDE AND DOES NOT NECESSARILY SHOW ALL ABBREVIATIONS USED. OTHER GENERALLY ACCEPTED ABBREVIATIONS MAY BE FOUND AMONG THE DRAWINGS - SOME ABBREVIATIONS SHOWN ABOVE MAY NOT BE USED WITHIN

THIS DRAWING SET.

A

A/C AIR CONDITIONING

AD AREA DRAIN

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ALUM ALUMINUM

ANOD ANODIZED

ARCH ARCHITECT

@ AT

B

BD BOARD

BLDG BUILDING

BO BOTTOM OF

C

C CELSIUS

CCSF CLOSED-CELL SPRAY-APPLIED FOAM

CH COAT HOOK

CFCI CONTRACTOR FURNISHED,

CONTRACTOR INSTALLED

CG CORNER GUARD

CI CONTINUOUS INSULATION

CJ CONTROL JOINT

CL CENTERLINE

CLG CEILING

CLO CLOSET

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS

CORR CORRIDOR

CT CERAMIC TILE

CTJ CONSTRUCTION JOINT

CUH CABINET UNIT HEATER

D

D DEEP

DEG DEGREE

DEMO DEMOLITION

DF DRINKING FOUNTAIN

DIA DIAMETER

DIM DIMENSION

DN DOWN

DS DOWNSPOUT

DWGS DRAWINGS

E

EA EACH

EJ EXPANSION JOINT

EIFS EXTERIOR INSULATION AND FINISH

SYSTEM

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EOS EDGE OF SLAB

ERD EXISTING ROOF DRAIN

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXP EXPOSED

EXT EXTERIOR

F

F FAHRENHEIT

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FDC FIRE DEPARTMENT CONNECTION

FD FLOOR DRAIN

FEC FIRE EXTINGUISHER CABINET

FE FIRE EXTINGUISHER

FG FINISH GRADE

FHC FIRE HOSE CABINET

FIN FINISH

FLR FLOOR

FND FOUNDATION

FO FINISHED OPENING

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FOS FACE OF STUD

FOW FACE OF WALL

FRG FIBER REINFORCED GYPSUM

FSP FIRE STANDPIPE

FT FEET

G

GA GAUGE

GALV GALVANIZED

GFRC GLASS-FIBER-REINFORCED

CONCRETE

GFRG GLASS-FIBER-REINFORCED GYPSUM

GL GLASS

GWB GYPSUM WALL BOARD

GYP GYPSUM

H

H HIGH

HB HOSE BIBB

HDR HEADER

HM HOLLOW METAL

HPT HIGH POINT

HR HOUR

HT HEIGHT

I

ID INSIDE DIAMETER; INSIDE DIMENSION

IN INCH

INFO INFORMATION

INT INTERIOR

J

JAN JANITOR

K (NOT USED)

L

LAB LABORATORY

LAV LAVATORY

LBS POUNDS

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LPT LOW POINT

M

MACH RM MACHINE ROOM

MAX MAXIMUM

MFR MANUFACTURER

MECH MECHANICAL

MEZZ MEZZANINE

MIN MINIMUM

MO MASONRY OPENING

N

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NOM NOMINAL

NTS NOT TO SCALE

O

OC ON CENTER

OD OUTSIDE DIAMETER;

OUTSIDE DIMENSION

OFD OVERFLOW DRAIN

OH DR OVERHEAD DOOR

OPH OPPOSITE HAND

OPP OPPOSITE

ORIG ORIGINAL

P

P LAM PLASTIC LAMINATE

PLAS PLASTER

PLUMB PLUMBING

PR PAIR

PSI POUNDS PER SQUARE INCH

PSF POUNDS PER SQUARE FOOT

PVC POLYVINYL CHLORIDE

Q

QT QUARRY TILE

R

R RISER OR RADIUS

RAD RADIUS

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REF REFRIDGERATOR

REQD REQUIRED

REV REVISION

RH RELATIVE HUMIDITY

RM ROOM

RO ROUGH OPENING

RTU ROOF TOP UNIT

RWL RAIN WATER LEADER

S

S SMOKE DETECTOR

SAM SELF ADHESIVE MEMBRANE

SCHED SCHEDULE

SECT SECTION

SIM SIMILAR

SPEC SPECIFICATION

SS STAINLESS STEEL

STD STANDARD

STRUCT STRUCTURAL

T

T TREAD

TEL TELEPHONE

TEMP TEMPORARY

THK THICK

TOC TOP OF CONCRETE

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOS TOP OF SLAB; TOP OF STEEL

TOW TOP OF WALL

TYP TYPICAL

TO TOP OF

U

UL UNDERWRITER'S LABORATORIES

UNO UNLESS NOTED OTHERWISE

V

VCT VINYL COMPOSITE TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

W

W/ WITH

W/O WITHOUT

WD WOOD

WH WALL HYDRANT

WP WORKING POINT

WRB WEATHER RESISTIVE BARRIER

X,Y,Z (NOT USED)

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

/8 /2

:1

:3

P M

A u to d e sk

D o c s:

S L

C o

A D

C T u rn st il e s_ r2

/A R

C H

_2

A D

C T u rn st il e s

R e n o v a ti o n _2

.r v t

GENERAL

INFORMATION

LS

25030

1 AUGUST 2025

CONSTRUCTION

SET

G-002

SMS

S

W

S o u th S a lt

L a k e

U T

S a lt L a k e C o u n ty

A D

C L

O B

B Y

T U

R N

S T

IL

E

S

INTERNATIONAL PLUMBING CODE

NATIONAL ELECTRICAL CODE

ZONING ORDINANCE:

INTERNATIONAL MECHANICAL CODE

INTERNATIONAL FIRE CODE

INTERNATIONAL ENERGY CONSERVATION CODE

INTERNATIONAL BUILDING CODE

ACCESSIBILITY CODE

DESIGN CRITERIA

APPLICABLE CODES OTHER CRITERIA

DEFERRED SUBMITTALS

ICC/ANSI A117.1-2021

2021 EDITION

2021 EDITION

2021 EDITION

2021 EDITION

2021 EDITION

2023 EDITION

Zoning OrdinanceSALT LAKE CITY

SHEET INDEX

x_450 CONCEPTUAL SECURITY CHECKPOINT PLAN

GENERAL:

G-001 COVER SHEET

G-002 GENERAL INFORMATION

G-101 LEVEL 01 EXITING & OCCUPANCY PLANS

ARCHITECTURAL:

A-101 REMODEL PLANS

A-102 BID ALTERNATES

A-501 MILLWORK DETAILS

ELECTRICAL:

E-001 GENERAL NOTES & DETAILS

EE-101 LEVEL 1 FLOOR PLAN - DEMOLITION SYSTEMS &

POWER

# Date Revision

C R

DH

P

P

CORRIDOR

STAIR

STAIR

CONFERENCE

VIEWING

WOMEN'S

SALLYPORT

SECURITY

CHECKPOINT

TOILET

SHOWERSSHOWERS

MENS

EXISTING CONSTRUCTION NOT IN

CONTRACT INDICATED BY HATCHED AREA

EXISTING CONSTRUCTION NOT IN

CONTRACT INDICATED BY HATCHED AREA

OFFICE

OFFICE

OFFICE

OFFICE

EXISTING CONSTRUCTION NOT IN

CONTRACT INDICATED BY HATCHED AREA

EXISTING FIRE ALARM PULL

SECURITY

BOUNDARY

546 SF

100B

CORRIDOR

353 SF

100B

SECURITY

CHECKPOINT

CONTROL ROOM

EMERGENCY

EQUIPMENT

EXIT CORRIDOR

1057 SF

7A

BRIEFING

ROOM

LOCKER ROOM

EXIT

REQ'D PROVIDED

OCCUPANT

LOAD

15.2" 36"76*0.2

REQ'D PROVIDED

OCCUPANT

LOAD

15" 36"75*0.2

REQ'D PROVIDED

OCCUPANT

LOAD

16" 36"80*0.2

EXIT

J131A

J131

EXIT ACCESS TRAVEL DISTANCE PER

TABLE 1017.2, WITH SPRINKLERS:

OCCUPANCY

MAX. TRAVEL

DISTANCE

BUSINESS AREAS (B) 300'

ASSEMBLY: NO FIXED STG (A-2) 250'

STORAGE (S-1) 400'

STORAGE (S-2) 400'

UTILITY / MISC. SERVICES (U-1) 400'

TRAVEL DISTANCE

COMMON PATH OF TRAVEL

COMMON PATH OF TRAVEL DISTANCE

PER TABLE 1006.2.1, WITH SPRINKLERS:

OCCUPANCY

MAX. TRAVEL

DISTANCE

BUSINESS AREAS (B) 100'

ASSEMBLY: NO FIXED STG (A-2/A-3) 75'

STORAGE (S-1) 100'

STORAGE (S-2) 100'

UTILITY / MISC. SERVICES (U-1) 75'

PATH OF TRAVEL

EGRESS

NUMBER OF OCCUPANTS PER

EXIT/EGRESS PATH

FIRE RATING KEY

FIRE EXTINGUISHERS

COORDINATE TYPE AND LOCATION WITH

LOCAL FIRE MARSHALL

OCCUPANCY TAG

ROOM NAME

Name

150 SF

A-3 000

ROOM AREA

OCCUPANCY TYPE

OCCUPANCY LOAD FACTOR

OCCUPANT LOAD

NO RATING -

NEW METAL STUD WALL

EXISTING CMU/CONCRETE WALL

(SECTION 1005.1)

EGRESS WIDTH

OTHER EGRESS COMPONENT WIDTH PER OCCUPANT

OTHER EGRESS COMPONENT WIDTH PROVIDED

OTHER EGRESS COMPONENT WIDTH REQUIRED

0.2"

5.8"

(SECTION 1003)

(SECTION 1004.1)

(TABLE 1004.1.1)

MEANS OF EGRESS

DESIGN OCCUPANT LOAD

FLOOR AREA IN SQUARE FEET PER OCCUPANT

ACTUAL FLOOR AREA

100 GROSS

905 SF

(SECTION 1020.1, TABLE 1020.1, SECTION 1021.2 & TABLE 1021.2)

EXITS 2 PER

1021.1.2

IBC 2021 - GENERAL CODE REQUIREMENTS

ALTERATION

CODE REFERENCE AREA '1'

[Draft 5 - 07.14.04]

AREA '2' AREA '3' BUILDING

(SECTIONS 302-312)

OCCUPANCY CLASSIFICATION

B N/A I-3

LESSNEW OCCUPANCY MORE OR LESS HAZARDOUS?

"...THE USE OR OCCUPANCY OF EXISTING BUILDINGS SHALL BE PERMITTED TO BE CHANGED AND THE BUILDING IS ALLOWED TO BE OCCUPIED FOR PURPOSES IN OTHER GROUPS WITHOUT CONFORMING TO ALL THE REQUIREMENTS OF THIS CODE FOR THOSE GROUPS, PROVIDED THE NEW OR PROPOSED USE IS LESS HAZARDOUS, BASED ON LIFE AND FIRE

RISK, THAN THE EXISTING USE."

(CHAPTER 34)

EXISTING STRUCTURES

(SECTION 3402.1)

"PORTIONS OF THE STRUCTURE NOT ALTERED AND NOT AFFECTED BY THE ALTERATION ARE NOT REQUIRED TO

COMPLY WITH THE CODE REQUIREMENTS FOR A NEW STRUCTURE."

(SECTION 3402.2)

"ADDITIONS OR ALTERATIONS TO AN EXISTING STRUCTURE SHALL NOT INCREASE THE FORCE IN ANY STRUCTURAL ELEMENT BY MORE THAN 5 PERCENT, UNLESS THE INCREASED FORCES ON THE ELEMENT ARE STILL IN COMPLIANCE WITH THE CODE FOR NEW STRUCTURES, NOR SHALL THE STRENGTH OF ANY STRUCTURAL ELEMENT

BE DECREASED TO LESS THAN THAT REQUIRED BY THIS CODE FOR NEW STRUCTURES."

N/A

N/A

N/A

EXISTING

EXISTING

EXISTING

N/A

N/A

2(SEE REGULATORY PLANS)

(SEE DWGS) N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

EXISTING

EXISTING

EXISTING

(SEE IPC SECTION 419.2 FOR URINALS)

(SEE IPC SECTION 410.1)

(SECTION 2902 & TABLE 2902.1) NO. PROVIDED

RATIO REQUIREMENT (MALE / FEMALE)

MINIMUM PLUMBING FACILITIES COLUMN

LEGEND: NO. REQUIRED

WATER CLOSETS

LAVATORIES

DRINKING FOUNTAINS

4 4

7 7

1:25 (<50) + 1:50 (>50)

1: 125/65

1:100

1:40 (<80) + 1:80 (>80)

1: 200/200

1:500

NOTE: CHANGE IN OCCUPANCY DOES NOT REQUIRE CHANGES TO

PLUMBING FACILITIES. NO CHANGE TO WATER CLOSETS.

NOTE: CHANGE IN OCCUPANCY DOES NOT REQUIRE CHANGES TO

PLUMBING FACILITIES. NO CHANGE TO LAVATORIES.

NOTE: CHANGE IN OCCUPANCY DOES NOT REQUIRE CHANGES TO

PLUMBING FACILITIES. (2) EXISTING DRINKING FOUNTAINS RELOCATED.

EXISTING FIXTURES IN SCOPE OF WORK TO REMAIN

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

/8 /2

:1

:4

P M

A u to d e sk

D o c s:

S L

C o

A D

C T u rn st il e s_ r2

/A R

C H

_2

A D

C T u rn st il e s

R e n o v a ti o n _2

.r v t

LEVEL 01

EXITING &

OCCUPANCY

PLANS

LS, AS

25030

1 AUGUST 2025

CONSTRUCTION

SET

G-101

SMS

S

W

S o u th S a lt

L a k e

U T

S a lt L a k e C o u n ty

A D

C L

O B

B Y

T U

R N

S T

IL

E

S

PATH #

COMMON

PATH OF

TRAVEL

LONGEST

PATH OF

TRAVEL

1 38' - 3" 130' - 10"

2 42' - 7" 106' - 2"

TAG DESCRIPTION

1/8" = 1'-0"G-101

A6 LEVEL 01 - OCCUPANCY & EXITING PLAN

J3

JD

JD.3

JE

JE.4

15' - 11"

CONTROL ROOM

3" 3' - 4" 3" 6' - 0 1/2" 5' - 7 1/4" ± 5 1/4"

11:MD1

11:PC1

01:QS1

09:LV1

26:CR1

26:CR1

26:PW1

09:LV1

AD

JU

ST

T

O E

XI

ST

IN

G

T

IL

ES

01:CF1

01:CF1

01:CF1

01:CF1

02:EF1

02:EF1

03:CS2

03:CS2

C L 4'

7"

7'

1" 3'

2"

9'

3/

4" 9'

1/ 4"

VI

F

1'

5"

28:CR2

09:LV2

A-501 A2

28:CR2

11:PC2

5 1/4" 4' - 5" 11' - 0 3/4" ±

09:FT1

09:FT1

09:FT1

09:FT1

09:FT1

C L

6'

8"

J3

JD

JD.3

JE

JE.4

26:LL3

26:LL3

26:LL3

09:AP1

09:AP1

11:PC3

11:PC3

26:PW1

09:AP1

10:TV1

A. ALL NEW WALL ASSEMBLIES ARE CONTINUOUS TO

BOTTOM OF DECK UNLESS NOTED OTHERWISE.

B. PLAN WALL DIMENSIONS ARE TO GRID LINE OR FACE OF

WALL STRUCTURE, UNLESS NOTED OTHERWISE. "CLEAR"

DIMENSIONS ARE TO FACE OF WALL FINISH.

C. FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR

COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE

COMMENCEMENT OF WORK. COORDINATE

DISCREPANCIES WITH ARCHITECT.

D. DO NOT SCALE DRAWINGS.

E. COORDINATE ALL ITEMS WITH STRUCTURAL, MECHANICAL

AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

F. SEE G SERIES SHEETS FOR WALL TYPES AND TYPICAL

ACCESSIBILITY CLEARANCE AND COMPLIANCE

REQUIREMENTS.

G. PROVIDE BACKING BEHIND ALL SURFACE MOUNTED

EQUIPMENT, FURNITURE ITEMS THAT REQUIRE

ANCHORING, WALL MOUNTED ACCESSORIES AND/OR

FIXTURES PER DETAIL .

H. REUSE OR REPLACE ANY MATERIAL TRANSITION

THRESHOLDS AT EXISTING DOORS AS NEEDED TO

COMPLETE THE WORK DURING THE TILE DEMOLITION OR

NEW TILE FLOORING INSTALLATION.

I. VERIFY DOOR NUMBERING AND LABELING WITH OWNER /

FACILITIES MANAGEMENT DURING THE WIRING AND

LABELING OF DOORS AT CLOSE OUT. CONTRACTOR IS TO

PROVIDE DOOR LABELS ON THE TOP OF THE DOOR JAMB

ON BOTH SIDES.

GENERAL NOTE - FLOOR PLAN

/C1 x_A701

A. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR

ADDITIONAL LIGHTING AND DIFFUSER INFORMATION.

B. THE CEILING HEIGHT SHOWN IN THE ROOM TAG

INDICATES THE HEIGHT OF THE DOMINANT CEILING

FINISH. SEE ADDITIONAL CEILING FINISH CALLOUTS OR

DETAILS FOR OTHER CEILING HEIGHTS OR FEATURES.

C. THE CONTRACTOR SHALL COORDINATE ALL TRADES TO

ENSURE THAT DESIGNATED CEILING HEIGHTS CAN BE

ACHEIVED. NOTIFY ARCHITECT OF ANY CONFLICTS OR

CONDITIONS THAT PREVENT THIS FROM OCCURRING

BEFORE PROCEEDING WITH THE WORK.

D. REFER TO ASSEMBLY TYPES SHEETS FOR CEILING

ASSEMBLIES.

GENERAL NOTE - RCP

JD

JD.3

JE

JE.4

02:EF1

02:EF1

AD

JU

ST

T

O E

XI

ST

IN

G

T

IL

E

FO

R M

AT

/2

02:ER1

02:EM1

02:EE1

6' - 6"

3'

6" 4'

7"

3'

6"

5'

3" 4'

7"

02:DC3

02:DC3

2'

0"

5'

6"

4' - 4" 1' - 4"

5' - 8"

02:DV1

CORRIDOR

J122

02:EM2

JD

JD.3

JE

JE.4

02:RL1

02:RL1

02:RL1

02:DC4

02:DC4

02:DC4

CORRIDOR

J122

J3

JD

JD.3

JE

JE.4

CONTROL ROOM

BRIEFING ROOM

SECURITY

CHECKPOINT

J122

EQ 1' - 6" EQ

09:FT1

09:FT1

09:FT1

09:FT1

LVT2

LVT1

LVT2

FLOOR FINISH LEGEND

CUT 18"x18" TILES

AS SHOWN

A. PROTECT WALLS, CEILINGS, FLOORS AND OTHER

EXISTING FINISH WORK THAT ARE TO REMAIN OR THAT

ARE EXPOSED DURING SELECTIVE DEMOLITION

OPERATIONS

B. PATCH AND REPAIR DAMAGE IN WALLS, CEILINGS, AND

FLOORS RESULTING FROM DEMOLITION OF EXISTING

ITEMS OR CONSTRUCTION OF NEW ITEMS AND/OR

REPLACE WITH NEW TO MATCH EXISTING. CLEAN AND

PREPARE TO RECEIVE NEW FINISH.

C. PROTECT ADJACENT AREAS FROM DUST AND DEBRIS

DURING SELECTIVE DEMOLITION OPERATIONS.

D. TRANSPORT DEMOLISHED MATERIALS OFF OWNER'S

PROPERTY AND LEGALLY DISPOSE OF DEBRIS.

E. FIELD VERIFY EXISTING CONDITIONS AND THEIR

COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE

COMMENCEMENT OF WORK. COORDINATE

DISCREPANCIES WITH ARCHITECT.

F. CLEAN ADJACENT IMPROVEMENTS OF DUST, DIRT, AND

DEBRIS CAUSE BY SELECTIVE DEMOLITION OPERATIONS.

RETURN ADJACENT AREAS TO CONDITION EXISTING

BEFORE SELECTIVE DEMOLITION OPERATIONS BEGAN.

G. SEE MECHANICAL, ELECTRICAL, AND AUDIO-VISUAL

DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE

DISCREPANCIES WITH ARCHITECT PRIOR TO PROCEEDING

WITH WORK.

GENERAL NOTE - DEMOLITION PLAN

A. THE ABSENCE OF A VIEW DOES NOT PRECLUDE THE

REQUIREMENT TO PROVIDE A FINISH AS INDICATED BY

THE FINISH SCHEDULE.

B. SEE FLOOR FINISH PLANS AND INTERIOR ELEVATION

VIEWS, WHERE DRAWN, FOR ADDITIONAL FINISH

LOCATION, TYPE, AND TRANSITION INFORMATION.

C. SEE REFLECTED CEILING PLANS FOR CEILING FEATURES

AND FINISH ELEVATIONS.

D. SATIN-NICKEL COUNTERTOP GROMMETS ARE TO BE

PROVIDED AND THEIR LOCATION COORDINATED WITH THE

OWNER/FACILITIES MANAGEMENT/ARCHITECT PRIOR TO

INSTALLATION. QUANTITIES TO MATCH NUMBER OF

DESKS/WORKSTATIONS.

ALL FINISHES:

1. WHERE A FINISH IS PARTLY HIDDEN BY AN OBJECT,

EXTEND THAT FINISH BEHIND THE OBJECT.

2. WHERE MULTIPLE FINISHES ARE SCHEDULED, REFER TO

FLOOR FINISH PLANS OR INTERIOR ELEVATIONS FOR

LOCATIONS OF TRANSITIONS.

FLOOR FINISHES:

1. EXTEND FLOOR FINISHES UNDER COUNTERS, INTO KNEE

SPACES AT CABINETS, AND UNDER ALL OTHER OBJECTS

SHOWN IN FINISH PLANS THAT MAY OBSCURE THE

EXTENT OF THE FLOOR FINISH.

BASE FINISHES:

1. ROOMS WHERE BASE SCHEDULED, PROVIDE BASE AT ALL

WALLS WHETHER OR NOT IT IS SHOWN IN ELEVATION,

INCLUDING ALCOVES AND OFFSETS.

WALLS:

1. EXTEND ALL WALL FINISHES BEHIND CABINETS, MIRRORS

AND INTO OTHER ARES THAT MAY BE HIDDEN IN

ELEVATION VIEWS.

CEILINGS:

1. PAINT AREAS ABOVE SUSPENDED CEILINGS THAT ARE

VISIBLE FROM BELOW. COLOR: BLACK.

2. VESTIBULE J111 PAINT ALL EXISTING ACCESS PANELS/

GRILL TO MATCH SCHEDULE CEILING PAINT.

GENERAL NOTES - FINISHES

1/4" = 1'-0"A-101

A4 LEVEL 01 - BASE BID FLOOR PLAN

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

/8 /2

:1

:4

P M

A u to d e sk

D o c s:

S L

C o

A D

C T u rn st il e s_ r2

/A R

C H

_2

A D

C T u rn st il e s

R e n o v a ti o n _2

.r v t

REMODEL

PLANS

LS

25030

1 AUGUST 2025

CONSTRUCTION

SET

A-101

SMS

S

W

S o u th S a lt

L a k e

U T

S a lt L a k e C o u n ty

A D

C L

O B

B Y

T U

R N

S T

IL

E

S

1/4" = 1'-0"A-101

C4 LEVEL 01 - ENLARGED REFLECTED CEILING PLAN

1/4" = 1'-0"A-101

A3 LEVEL 01 - BASE BID DEMOLITION FLOOR PLAN

1/4" = 1'-0"A-101

C3 LEVEL 01 - DEMO. REFLECTED CEILING PLAN

KEYNOTE LEGEND

01:CF1 39" CLEAR FLOOR SPACE

REQUIREMENT FOR CEILING

SENSOR. KEEP AREA CLEAR.

01:QS1 QUEUING AREA

02:DC3 DEMOLISH PORTION OF SLAB

APPROX. 3" DEEP FOR CONDUIT

TIE-IN WITH DFLOW GLASS

BARRIERS; COORDINATE W/

MANUFACTURER. SIZE PER PLAN.

02:DC4 SALVAGE 2X4 ACOUSTIC CEILING

PANEL; IF DAMAGED CONTRACTOR

RESPONSIBLE TO REPLACE WITH

MATCHING CEILING TILE

02:DV1 DEMOLISH EXISTING VINYL

COMPOSITION TILE; SCRAP/CLEAN

FLOOR TO PREPARE FOR INSTALL OF

NEW TILE. CONTRACTOR TO

REPLACE ANY DAMAGED TILES.

02:EE1 EXISTING OFFICE CHAIR AND

COMPUTER TO RETURN TO OWNER

02:EF1 EXISTING VINYL COMPOSITION TILE

TO REMAIN & PROTECT IN PLACE

02:EM1 EXISTING METAL DETECTOR TO

RETURN TO OWNER

02:EM2 EXISTING HANGING MAIL STORAGE

TO REMAIN; PROTECT IN PLACE

DURING CONSTRUCTION. IF

REMOVABLE CONTRACTOR TO

REMOVE , PROTECT & STOE DURING

DEMOLITION. RE-INSTALL PRIOR TO

CONSTRUCTION COMPLETION.

PROVIDE NEW VANDAL RESISTANT

FASTENERS, CAULKING AS

NECESSARY TO PROVIDE LIKE NEW

INSTALLATION. IF DAMAGED

CONTRACTOR TO PROVIDE SIMILAR

GRADE & STYLE AT CONTRACTORS

EXPENSE.

02:ER1 EXISTING RECEPTION DESK/TABLE

TO RETURN TO OWNER

02:RL1 REMOVE EXISTING LIGHTING,

PROTECT IN PLACE UNTIL REINSTALL

03:CS2 NEW CONCRETE SLAB FILL, MATCH

EXISTING ADJACENT CONCRETE

SLAB ELEVATION; COORDINATE

ELECTRICAL CONDUIT RUNS WITH

DFLOW GLASS BARRIERS

09:AP1 2' X 4' LAY-IN ACOUSTICAL PANEL

CEILING; MATCH EXISTING IF

SALVAGED PANELS ARE DAMAGED.

09:FT1 PROVIDE FLOOR TRANSITION (BOD:

SCHLUTER VINRO-S OR VINPRO-T);

ARCHITECT TO APPROVE BEFORE

INSTALL. CONTRACTOR TO REMOVE

& REPLACE IF ANY VCT OR LVT

FLOORING IS DAMAGED DURING

CONSTRUCTION & DEMO; REPLACED

DAMAGED VCT MUST MATCH

EXISTING.

09:LV1 18"X18" LVT FLOORING; COORDINATE

PLACEMENT W/ ARCHITECT BEFORE

INSTALL; REFER TO FINISH

SCHEDULE

09:LV2 CUSTOM CUT SHAPE LVT FLOORING;

CUT & LAY AS SHOWN; COORDINATE

PLACEMENT W/ ARCHITECT BEFORE

INSTALL; REFER TO FINISH

SCHEDULE

10:TV1 CONTRACTOR PROVIDED

CONTRACTOR INSTALLED; CEILING

MOUNTED TV, ATTACH DIRECTLY TO

STRUCTURE OR PEERLESS- AV

HEAVY DUTY 2'-0" X 2'-0" SUSPENDED

CEILING TILE SECURE TO

STRUCTURAL CEILING WITH TIE

WIRES & SAFETY CABLES, TAMPER

RESISTANT/ EQUAL. COORDINATE

WITH ELECTRICAL FOR POWER &

DATA. EXACT HEIGHT TO BE

COORDINATED WITH OWNER &

SECURITY SYSTEM.

11:MD1 GARRETT PD 6500I METAL DETECTOR

BY OWNER

11:PC1 PEDESTRIAN CONTROL ACCESS

GATE (BOD: DFLOW MODEL 1200

GLASS BARRIER ULTRA WIDE)

11:PC2 PEDESTRIAN CONTROL ACCESS

GATE (BOD: DFLOW MODEL 900

GLASS BARRIER)

11:PC3 PEDESTRIAN CONTROL CEILING

SENSOR CENTERED ABOVE ACCESS

GATES PER MFR REQ'S

26:CR1 CARD SCANNER LOCATION

26:LL3 2' X 4' LAY-IN LIGHT FIXTURE; SEE

ELECTRICAL

26:PW1 4"X4" METAL POWER POLE COLUMN

RUNNING FLOOR TO CEILING;

COORDINATE WITH ELECTRICAL

28:CR2 INTEGRATED CARD READER

CONNECTED TO DOOR HARDWARE &

FIRE ALARM; CARD READERS ON

BOTH SIDES OF DOOR

1/4" = 1'-0"A-101

A6 LEVEL 01 - BASE BID FINISH FLOOR PLAN

FINISH LEGEND

CODE FINISH TYPE DESCRIPTION

FLOOR FINISHES

LVT1 LUXURY VINYL TILE MANUFACTURER: MANNINGTON COMMERCIAL

COLLECTION: UPWARD 20

STYLE: STONE

COLOR: TERRATZI MEZZO, UPW40-1231

SIZE: MATCH EXISTING

LVT2 LUXURY VINYL TILE MANUFACTURER: MANNINGTON COMMERCIAL

COLLECTION: AMTICO SIGNATURE ABSTRACT

MATERIAL EFFECT: STONE

COLOR: STUCCO FLAX, AR0AUC39

SIZE: 18"X18"; UNLESS PLANS SHOW CUT TO TRIANGLE SIZE

BASE FINISHES

MT4 UNDER BASE FINISHES MANUFACTURER: FRY REGLET

4" CHANNEL BASE W/ RETURN KEY

RB1 4" RUBBER BASE MANUFACTURER: TARKETT

STYLE: MILLWORK BASE, MONUMENT, MW-48-S4

SIZE: 4"

COLOR: 48 GREY

WALL FINISHES

P1 PAINTED CMU (IF NEEDED) MANUFACTURER: SHERWIN WILLIAMS

COLOR: SW7636 ORAGAMI WHITE

FINISH: SATIN EGGSHEL

CEILING FINISHES

ACP1 24" X 48" ACOUSTICAL

CEILING PANEL

MATCH EXISTING

MILLWORK

MT1 METAL - STAINLESS STEEL STAINLESS STEEL

FINISH MATTE

MT2 METAL - STAINLESS STEEL STAINLESS STEEL TO MATCH FINISH BELOW

MANUFACTURER MOZ

COLLECTION: CLASSIC STEEL

COLOR: LAVENDAR SILK

FINISH: MATTE

MT3 METAL TRIM MANUFACTURER: FRY REGLET

COLLECTION: DRYWALL PROFILES

STYLE: SNAP IN REVEAL

COLOR: BUFFED BRITE BLACK

SIZE: 1/2" DRM-SNAP-IN-50

SS1 SOLID SURFACE MANUFACTURER: FORMICA

STYLE: SOLID SURFACE

COLOR: 757 LUNA SAND

ROOM FINISH SCHEDULE

Room Name Floor Base

Walls

Ceiling CommentsN E S W

J122 SECURITY CHECKPOINT LVT1/LVT2 RB1 P1 (TOUCH-UP) P1 (TOUCH-UP P1 (TOUCH-UP P1 (TOUCH-UP MATCH EXIST

REFER TO FLOOR FINISH LEGEND & FINISH SCHEDULE

JC

JC.3

JC.6

JC.8

JD

JD.3

JE

JE.4

01:CL1

THIS AREA IS WITHIN

THE BASE BID

09:FT1

09:FT1

09:FT1 09:FT1

09:FT1

09:FT1

09:FT1

09:FT1

09:FT1

09:FT1

09:FT1

09:FT1

09:LV1

09:LV1

JC

JC.3

JC.6

JC.8

JD

JD.3

JE

JE.4

01:CL1

02:DV1

THIS AREA IS WITHIN

THE BASE BID

02:DV1

A. ALL NEW WALL ASSEMBLIES ARE CONTINUOUS TO

BOTTOM OF DECK UNLESS NOTED OTHERWISE.

B. PLAN WALL DIMENSIONS ARE TO GRID LINE OR FACE OF

WALL STRUCTURE, UNLESS NOTED OTHERWISE. "CLEAR"

DIMENSIONS ARE TO FACE OF WALL FINISH.

C. FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR

COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE

COMMENCEMENT OF WORK. COORDINATE

DISCREPANCIES WITH ARCHITECT.

D. DO NOT SCALE DRAWINGS.

E. COORDINATE ALL ITEMS WITH STRUCTURAL, MECHANICAL

AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

F. SEE G SERIES SHEETS FOR WALL TYPES AND TYPICAL

ACCESSIBILITY CLEARANCE AND COMPLIANCE

REQUIREMENTS.

G. PROVIDE BACKING BEHIND ALL SURFACE MOUNTED

EQUIPMENT, FURNITURE ITEMS THAT REQUIRE

ANCHORING, WALL MOUNTED ACCESSORIES AND/OR

FIXTURES PER DETAIL .

H. REUSE OR REPLACE ANY MATERIAL TRANSITION

THRESHOLDS AT EXISTING DOORS AS NEEDED TO

COMPLETE THE WORK DURING THE TILE DEMOLITION OR

NEW TILE FLOORING INSTALLATION.

I. VERIFY DOOR NUMBERING AND LABELING WITH OWNER /

FACILITIES MANAGEMENT DURING THE WIRING AND

LABELING OF DOORS AT CLOSE OUT. CONTRACTOR IS TO

PROVIDE DOOR LABELS ON THE TOP OF THE DOOR JAMB

ON BOTH SIDES.

GENERAL NOTE - FLOOR PLAN

/C1 x_A701

A. PROTECT WALLS, CEILINGS, FLOORS AND OTHER

EXISTING FINISH WORK THAT ARE TO REMAIN OR THAT

ARE EXPOSED DURING SELECTIVE DEMOLITION

OPERATIONS

B. PATCH AND REPAIR DAMAGE IN WALLS, CEILINGS, AND

FLOORS RESULTING FROM DEMOLITION OF EXISTING

ITEMS OR CONSTRUCTION OF NEW ITEMS AND/OR

REPLACE WITH NEW TO MATCH EXISTING. CLEAN AND

PREPARE TO RECEIVE NEW FINISH.

C. PROTECT ADJACENT AREAS FROM DUST AND DEBRIS

DURING SELECTIVE DEMOLITION OPERATIONS.

D. TRANSPORT DEMOLISHED MATERIALS OFF OWNER'S

PROPERTY AND LEGALLY DISPOSE OF DEBRIS.

E. FIELD VERIFY EXISTING CONDITIONS AND THEIR

COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO THE

COMMENCEMENT OF WORK. COORDINATE

DISCREPANCIES WITH ARCHITECT.

F. CLEAN ADJACENT IMPROVEMENTS OF DUST, DIRT, AND

DEBRIS CAUSE BY SELECTIVE DEMOLITION OPERATIONS.

RETURN ADJACENT AREAS TO CONDITION EXISTING

BEFORE SELECTIVE DEMOLITION OPERATIONS BEGAN.

G. SEE MECHANICAL, ELECTRICAL, AND AUDIO-VISUAL

DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE

DISCREPANCIES WITH ARCHITECT PRIOR TO PROCEEDING

WITH WORK.

GENERAL NOTE - DEMOLITION PLAN

A. THE CONSTRUCTION DOCUMENTS, AS PROVIDED AND

DESIGNED HERE-IN, HAVE BEEN DOCUMENTED AND

DETAILED "IN FULL," DEMOSTRATING THE SCOPE OF

WORK IF ALL OF THE BID ALTERNATES WERE TO BE

ACCEPTED AND EXECUTED. THE FOLLOWING BID

ALTERNATE PROVIDES DETAILS AND DESCRIPTIONS TO

BETTER GAIN AN UNDERSTANDING OF THE SCOPE OF

WORK.

GENERAL NOTE - BID ALTS

JC

JC.3

JC.6

JC.8

JD

JD.3

JE

JE.4

01:CL1

THIS AREA IS WITHIN

THE BASE BID

LVT1

LVT1

A. THE ABSENCE OF A VIEW DOES NOT PRECLUDE THE

REQUIREMENT TO PROVIDE A FINISH AS INDICATED BY

THE FINISH SCHEDULE.

B. SEE FLOOR FINISH PLANS AND INTERIOR ELEVATION

VIEWS, WHERE DRAWN, FOR ADDITIONAL FINISH

LOCATION, TYPE, AND TRANSITION INFORMATION.

C. SEE REFLECTED CEILING PLANS FOR CEILING FEATURES

AND FINISH ELEVATIONS.

D. SATIN-NICKEL COUNTERTOP GROMMETS ARE TO BE

PROVIDED AND THEIR LOCATION COORDINATED WITH THE

OWNER/FACILITIES MANAGEMENT/ARCHITECT PRIOR TO

INSTALLATION. QUANTITIES TO MATCH NUMBER OF

DESKS/WORKSTATIONS.

ALL FINISHES:

1. WHERE A FINISH IS PARTLY HIDDEN BY AN OBJECT,

EXTEND THAT FINISH BEHIND THE OBJECT.

2. WHERE MULTIPLE FINISHES ARE SCHEDULED, REFER TO

FLOOR FINISH PLANS OR INTERIOR ELEVATIONS FOR

LOCATIONS OF TRANSITIONS.

FLOOR FINISHES:

1. EXTEND FLOOR FINISHES UNDER COUNTERS, INTO KNEE

SPACES AT CABINETS, AND UNDER ALL OTHER OBJECTS

SHOWN IN FINISH PLANS THAT MAY OBSCURE THE

EXTENT OF THE FLOOR FINISH.

BASE FINISHES:

1. ROOMS WHERE BASE SCHEDULED, PROVIDE BASE AT ALL

WALLS WHETHER OR NOT IT IS SHOWN IN ELEVATION,

INCLUDING ALCOVES AND OFFSETS.

WALLS:

1. EXTEND ALL WALL FINISHES BEHIND CABINETS, MIRRORS

AND INTO OTHER ARES THAT MAY BE HIDDEN IN

ELEVATION VIEWS.

CEILINGS:

1. PAINT AREAS ABOVE SUSPENDED CEILINGS THAT ARE

VISIBLE FROM BELOW. COLOR: BLACK.

2. VESTIBULE J111 PAINT ALL EXISTING ACCESS PANELS/

GRILL TO MATCH SCHEDULE CEILING PAINT.

GENERAL NOTES - FINISHES

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

/8 /2

:1

:4

P M

A u to d e sk

D o c s:

S L

C o

A D

C T u rn st il e s_ r2

/A R

C H

_2

A D

C T u rn st il e s

R e n o v a ti o n _2

.r v t

BID

ALTERNATES

LS

25030

1 AUGUST 2025

CONSTRUCTION

SET

A-102

SMS

S

W

S o u th S a lt

L a k e

U T

S a lt L a k e C o u n ty

A D

C L

O B

B Y

T U

R N

S T

IL

E

S

3/16" = 1'-0"A-102

A4 LEVEL 01 - BID ALT FLOOR PLAN - ADD SCOPE

3/16" = 1'-0"A-102

A2 LEVEL 01 - BID ALT DEMOLITION PLAN - ADD SCOPE

KEYNOTE LEGEND

01:CL1 CLEARED CONSTRUCTION LIMIT.

OUTSIDE OF THIS AREA WILL REQUIRE

APPROVAL FROM OWNER.

02:DV1 DEMOLISH EXISTING VINYL

COMPOSITION TILE; SCRAP/CLEAN

FLOOR TO PREPARE FOR INSTALL OF

NEW TILE. CONTRACTOR TO REPLACE

ANY DAMAGED TILES.

09:FT1 PROVIDE FLOOR TRANSITION (BOD:

SCHLUTER VINRO-S OR VINPRO-T);

ARCHITECT TO APPROVE BEFORE

INSTALL. CONTRACTOR TO REMOVE &

REPLACE IF ANY VCT OR LVT

FLOORING IS DAMAGED DURING

CONSTRUCTION & DEMO; REPLACED

DAMAGED VCT MUST MATCH EXISTING.

09:LV1 18"X18" LVT FLOORING; COORDINATE

PLACEMENT W/ ARCHITECT BEFORE

INSTALL; REFER TO FINISH SCHEDULE

LVT1 LUXURY VINYL TILE

3/16" = 1'-0"A-102

A6 LEVEL 01 - BID ALT FINISH FLOOR PLAN - ADD SCOPE

FLOATING COUNTERTOP

WALL BRACKET @ 32" o.c.

PROVIDE (1) 2" GROMMET IN

COUNTERTOP, SEE PLAN FOR LOCATION

SCHEDULED SOLID SURFACE

COUNTERTOP W/ 3/4" SUBSTRATE

4" BASE REGLET

ELECTRICAL OUTLET, COORDINATE

W/ ELECTRICAL DRAWINGS

2X4 WOOD STUD FRAMING

STAINLESS STEEL LAMINATE

OVER 3/4" PLYWOOD SUBSTRATE

3/4" MILLWORK PANEL W/

STAINLESS STEEL LAMINATE

A-501 C6

1/

2"

8" 2'

/6

4"

8 1/8" 1' - 11 1/8"

3'

/6 4"

3/4" PLYWOOD BASE LAYER

STAINLESS STEEL LAMINATE

OVER 3/4" PLYWOOD SUBSTRATE

4" MILLWORK CHANNEL BASE

3/4" MILLWORK PANEL W/

STAINLESS STEEL LAMINATE

A-501 C6

2X4 WOOD STUD FRAMING

3/4" PLYWOOD BASE LAYER

8" 2'

3'

6"

1' - 7 1/2"

3/4"3/4"

B2

A-501

MT2

SS1

MT1

C5

A-501

MT2

MT1

B2

A-501

EQ 3' - 0" EQ

MT2MT2

MT1

B5

A-501

MT2

B3

A-501

3'

6"MT2MT2 MT2

EQ 3' - 0" EQ

MT1

SS1

B6

A-501

C5

A-501

MT1

MT2

B3

A-501

MT2 MT2 MT2MT2

MT1

EQ 3' - 0" EQ

MT1

A-501

A4

A-501

A3

B2

A-501

B3

A-501

______A-501

A5

1/

4" 5'

4"

1/

4" 3'

3/ 4"

1/

4" 1/

4"

2 1/4" 5' - 8"

2 1/4"

A-501

A6

1/

4"

1/ 2"

1/

4"

MT1 TRANSACTION TOP

METAL LAMINATE PLYWOOD PANELS (LIGHT GRAY POCHE)

2x4 FRAMING (DARK GRAY POCHE)

8" 1'

/1

6"

11 1/2" 8"

2 1/4" 4' - 4 1/4"

3/4"5'

1/

2" 3'

6"

6' - 0 1/2"

3/4"

3/4" MILLWORK PANEL W/

STAINLESS STEEL LAMINATE

MILLWORK INSIDE CORNER TRIM

W/ RETURN KEYS, BLACK

(BOD: FRY REGLET MWCISC75)

PLYWOOD BASE LAYER

3/4" MILLWORK PANEL W/

STAINLESS STEEL LAMINATE

MILLWORK 3/4" CORNER ACCENT, BLACK

(BOD: FRY REGLET MWCK75)

3/4" PLYWOOD BASE LAYER3/4" MILLWORK PANEL W/

STAINLESS STEEL LAMINATE

MILLWORK 1/4" POST TRIM, BLACK

(BOD: FRY REGLET MWP2575)

3/4" PLYWOOD BASE LAYER

3/4" MILLWORK PANEL W/

STAINLESS STEEL LAMINATE

4" MILLWORK CHANNEL BASE W/

RETURN KEY, BLACK

(BOD: FRY REGLET MWCB75400)

PLYWOOD BASE LAYER

4"

A-501

D3 3D SECURITY CHECKPOINT AREA

KEYNOTE LEGEND

MT1 BRUSHED STAINLESS STEEL LAMINATE

MILLWORK PANEL; SEE FINISH

SCHEDULE FOR MORE INFO

MT2 COLORED STAINLESS STEEL LAMINATE

MILLWORK PANEL; SEE FINISH

SCHEDULE FOR MORE INFO

SS1 SOLID SURFACE; SEE FINISH SCHEDULE

FOR MORE INFO

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

/8 /2

:1

:5

P M

A u to d e sk

D o c s:

S L

C o

A D

C T u rn st il e s_ r2

/A R

C H

_2

A D

C T u rn st il e s

R e n o v a ti o n _2

.r v t

MILLWORK

DETAILS

LS

25030

1 AUGUST 2025

CONSTRUCTION

SET

A-501

SMS

S

W

S o u th S a lt

L a k e

U T

S a lt L a k e C o u n ty

A D

C L

O B

B Y

T U

R N

S T

IL

E

S

1 1/2" = 1'-0"A-501

B2 SECURITY COUNTER MILLWORK DETAIL @ WORKTOP

1 1/2" = 1'-0"A-501

B3 SECURITY COUNTER MILLWORK DETAIL

1/2" = 1'-0"A-501

A6 SECURITY CHECKPOINT - ELEV. - N

1/2" = 1'-0"A-501

A4 SECURITY CHECKPOINT - ELEV. - S

1/2" = 1'-0"A-501

A3 SECURITY CHECKPOINT - ELEV. - W

1/2" = 1'-0"A-501

A5 SECURITY CHECKPOINT - ELEV. - E

OWNER PROVIDED OWNER

INSTALLED TV; MOUNT PROVIDED &

INSTALLED BY CONTRACTOR

1/2" = 1'-0"A-501

A2 LEVEL 01 - ENLARGED FRONT DESK

3" = 1'-0"A-501

C5 INSIDE CORNER MILLWORK REGLET

3" = 1'-0"A-501

B5 OUTSIDE CORNER MILLWORK REGLET

3" = 1'-0"A-501

B6 MILLWORK DIVIDER REGLET

3" = 1'-0"A-501

C6 MILLWORK CHANNEL BASE REGLET

DETAIL

NOT TO

SCALE

SCALE:

D1

TYPICAL ROUGH−IN DETAIL

NOTES:

IN ACCORDANCE W/ IBC 711.3.2, OUTLETS ON OPPOSITE SIDES OF

FIRE RATED WALLS OR PARTITIONS IN THE SAME STUD SPACE

MUST BE SEPARATED BY MIN. OF 24" HORIZONTAL DISTANCE.

1. TYP. FOR WOOD & METAL STUD ROUGH-IN.

2. PLASTER RINGS NOT SHOWN.

3. LOCATE ALL OUTLET BOXES IN

ACCORDANCE W/ ARCH. & MECH. DWGS.,

AND W/ ALL APPLICABLE SHOP DWGS.

TYPICAL DUPLEX

OUTLET BOX

TYPICAL SWITCH

OUTLET BOX

BAR

STRAPS

BAR

STRAPS

TYPICAL WALL

OUTLETS

PROVIDE CONDUIT SUPPORTS IN

ACCORDANCE W/ NEC SPACING

REQUIREMENTS FOR THE TYPE OF

RACEWAY REQUIRED

AS REQUIRED FOR TYPE OF

CONSTRUCTION

STEEL CITY NO.

7501 BOX SUPPORT

DETAIL

NOT TO

SCALE

SCALE:

A

B

NOTES:

1. THE CONTRACTOR MUST COORDI NATE EXACT LOCATI ON OF THE DI SCONNECT WI TH THE MECHANI CAL

CONTRACTOR TO ELI MINATE ANY OBSTACLE (PI PE,CONCRETE PAD ETC. ) I N FRONT OF THE DISCONNECT.

IF THERE ARE ANY OBSTACLES, PROVI DE UNI STRUT AND INSTALL THE DI SCONNECT NEXT TO

MECHANI CAL EQUI PMENT I N ORDER TO PROVI DE THE REQUI RED CLEARANCE.

2. PROVI DE MINI MUM CLEARANCE AS FOLLOWS:

SYSTEM VOLTAGE

A B

42"

36" 30"

30"

DISCONNECT

SWITCH

FLEXIBLE LIQUID

TIGHT METALLIC

CONDUIT

MECHANICAL

EQUIPMENT

TYPICAL

CLEARED

SPACE

TYPICAL DISCONNECT CLEARANCE REQUIREMENTS

D2

DETAIL

NOT TO

SCALE

SCALE:

NOTE:

TYPI CAL DETAILS SHOWI NG GENERAL FI RE

STOPPI NG PROCEDURE . ACTUAL PROCEDURE

DEPENDS UPON ANNULAR SP ACE BETWEEN

PI PE AND/ OR I NSULATI ON AND OPENING.

FOLLOW MANUFACTURER' S I NSTRUCTI ONS.

DAMMING MATERIAL

(BACKER ROD, FIBERGLASS

OR MINERAL WOOL)

3M FIRE BARRIER

CP 25WB CAULK

FIRE RATED CONCRETE

FLOOR SLAB

CONDUIT OR

INSULATED CABLES

TYPICAL FIRESTOP FOR CABLES/CONDUIT

THROUGH CONCRETE FLOORINGD3

DETAIL

NOT TO

SCALE

SCALE:

NOTE:

TYPI CAL DETAILS SHOWI NG GENERAL FI RE

STOPPI NG PROCEDURE . ACTUAL PROCEDURE

DEPENDS UPON ANNULAR SP ACE BETWEEN

PI PE AND/ OR I NSULATI ON AND OPENING.

FOLLOW MANUFACTURER' S I NSTRUCTI ONS.

CP 25WB CAULK ON

BOTH SIDES OF WALL

INSULATED CABLES OR CONDUIT

FIRE RATED CONCRETE/CONCRETE

BLOCK WALL

DAMMING MATERIAL

(BACKER ROD, FIBER−GLASS

OR MINERAL WOOL)

NON−METALLIC SLEEVE MAY

EXTEND A MAX 2" (51 mm)

BEYOND THE WALL SURFACE

TYPICAL FIRESTOP FOR CABLES/CONDUIT

THROUGH CONCRETE WALLSD4

DETAIL

NOT TO

SCALE

SCALE:

D5

NOTE:

TYPICAL DETAIL SHOWING GENERAL FIRE

STOPPING PROCEDURE. ACTUAL PROCEDURE

DEPENDS UPON ANNULAR SPACE BETWEEN

PIPE AND/OR INSULATION AND OPENING.

FOLLOW MANUFACTURER'S INSTRUCTIONS.

1/4" MINIMUM DIAMETER

BEAD OF 3M FIRE BARRIER CP

25 CAULK OR MP MOLDABLE

PUTTY

METALLIC

CONDUIT

1/4" MINIMUM DIAMETER

BEAD OF 3M FIRE BARRIER

CP 25 CAULK OR MP

MOLDABLE PUTTY

1 OR 2 HOUR FIRE RATED

GYPSUM WALL BOARD

WOOD OR STEEL STUD

FIRESTOP FOR METAL CONDUIT

THROUGH GYPSUM WALL BOARD

DETAIL

NOT TO

SCALE

SCALE:

PULL

FIRE

ELECTRICAL

OUTLETS

FIRE ALARM PULL STATION

LIGHT SWITCHES

M

IN

M A

X

STROBE LIGHT OR

HORN & STROBE

STANDARD HEIGHTS FOR HANDICAPPED ACCESS

D6

M

IN

IM

U

M

M A

X

NL

E

X

S

EWC

J

T

S

ELECTRICAL SYMBOLS LIST

SYMBOL DESCRIPTION

LIGHTING SYMBOLS

LIGHT FIXTURE TO STAY ON AT NIGHT (NIGHT LIGHT). PROVIDE UNSWITCHED LIGHTING CIRCUIT.

LIGHT FIXTURE ON EMERGENCY POWER PROVIDE BATTERY AS REQUIRED

REFERENCE NOTES CALL OUT

SINGLE POLE TOGGLE SWITCH - 20 AMP

POWER SYMBOLS

DUPLEX CONVENIENCE OUTLET - 20 AMP

DUPLEX CONVENIENCE OUTLET - 20 AMP, GFCI PROTECTED.

DUPLEX CONVENIENCE OUTLET - 20 AMP ELECTRIC WATER COOLER

FOUR - PLEX CONVENIENCE OUTLET - 20 AMP

JUNCTION BOX - SIZE AND FUNCTION AS REQUIRED

EACH ARROW INDICATES A HOME RUN. RUN GROUND CONDUCTOR REGARDLESS OF CONDUIT TYPE.

NUMBER OF CONDUCTORS AS REQUIRED

FUSED DISCONNECT SWITCH - SIZE AS REQUIRED-STANDARD HEIGHT TO BE 66" AFF TO THE TOP

FLUSH TELEPHONE, DATA OUTLET

FLUSH TELEPHONE OUTLET

FLUSH DATA OUTLET

MOTOR LOCATION

MECHANICAL EQUIPMENT CALL OUT

MANUAL DISCONNECT WITH THERMAL OVERLOAD PROTECTION

ELECTRICAL PANEL LOCATION

GENERAL NOTE SYMBOLS

WP INDICATES WEATHER PROOF EQUIPMENT

A INDICATES DEVICE IS ABOVE COUNTER TOP-42" AFF REFER TO ARCHITECTURAL ELEVATION

CLG INDICATES DEVICES MOUNTED ON THE CEILING, COORDINATE LOCATION WITH THE ARCHITECT.

XX−1

DETAIL

NOT TO

SCALE

SCALE:

D38

TYPICAL CONDUIT RACK SUPPORT DETAIL

CONDUIT CLAMP - 3/4" TO 1"

UNISTRUT 2 PIECE CHANNEL

PIPE STRAPS - 1 1/4" TO 6"

BEAM CLAMP, HANGER CLAMP,

OR APPROVED SUPPORT, AS

REQUIRED BY WEIGHT

SUPPORTED

UNISTRUT CHANNEL -

SIZE AS REQUIRED BY

WEIGHT SUPPORTED

RACEWAY 3/4" TO 6" (TYP.)

ALL THREAD ROD

SIZE AS REQUIRED

(MIN. 3/8")

1. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE (NEC) AND

ALL THE LOCAL CODES.

2. PROVIDE TAMPER-RESISTANCE RECEPTACLES IN THE AREAS WHERE KIDS ARE PRESENT, AND

AREAS REQUIRED BY NEC 406.12(3). INCLUDING DWELLING UNITS, GUEST ROOMS,

PRESCHOOL/ELEMENTARY/ CHILDCARE FACILITIES, WAITING ROOMS, ETC.

3. NOT MORE THAN THREE (3) CIRCUITS SHALL BE INSTALLED IN A 3/4" CONDUIT.

4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. DO NOT SHARE THE NEUTRAL

CONDUCTOR IN HOMERUNS. (NEC 210.4).

5. THE MINIMUM SIZE OF THE CONDUCTORS SHALL BE A NO. 12 AWG, THHN COPPER. UNLESS

INDICATED OTHERWISE ON THE DRAWINGS.

6. LIGHT FIXTURES, RACEWAYS AND OTHER ELECTRICAL DEVICES SHALL BE SUPPORTED FROM

THE STRUCTURE NOT FROM METAL OR WOOD CEILING DECK. UTILIZE UNISTRUTS IN BETWEEN

STRUCTURE AS NEEDED.

7. ALL J-BOXES SHALL BE RECESSED INTO THE FINISHED WALL/CEILING UNLESS THE FINISHED

WALL/CEILING IS CONCRETE AND IS NOT BEING FURRED OUT. ALL CONDUITS SHALL BE RUN

THROUGH THE STUDS BEHIND THE FINISHED WALL/CEILING. COORDINATE WITH

ENGINEER/ARCHITECT PRIOR TO ROUGH-IN FOR ANY EXPOSED CONDUITS/J-BOX THAT

CANNOT BE RUN INSIDE THE WALL/CEILING AND NEED TO BE SURFACE MOUNTED ON THE

FINISHED WALL/CEILING. SURFACE MOUNTED CONDUITS IN EXPOSED CEILING SHALL BE

INSTALLED CLOSE TO CEILING (AND NOT PENDANT MOUNTED BELOW THE

BEAMS/STRUCTURE).

8. PROVIDE GFCI PROTECTED OUTLETS FOR EVERY LOCATION SHOWN ON THE DRAWINGS. DO

NOT USE MULTIPLE LOCATION PROTECTION.

9. WHERE CIRCUIT CONDUCTORS ARE TO BE INCREASED IN SIZE TO MEET THE VOLTAGE DROP

REQUIREMENT, THE EQUIPMENT GROUNDING CONDUCTORS MUST BE INCREASED

ACCORDINGLY (NEC 250.122)

10. ALL J-BOXES SHALL HAVE A MINIMUM DEPTH OF 2-1/8" UNLESS OTHERWISE SPECIFIED.

SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD RINGS.

11. ALL THE HOMERUNS MUST BE ACCESSIBLE. DO NOT CARRY A HOMERUN FROM ONE DEVICE

TO ANOTHER WHICH IS TIED TO A SEPARATE HOMERUN INSIDE THE WALL. MARK ON ALL THE

J-BOXES THE CIRCUIT NAMES AND NUMBERS.

12. ALL J-BOXES IN FIRE RATED WALLS SHALL MEET THE FIRE RATING REQUIREMENT OF THE

WALL AND SHALL NOT BE INSTALLED LESS THAN 24" BACK-TO-BACK.

13. ALL DISCONNECTS SHALL BE OF A HEAVY-DUTY TYPE.

14. ALL DISCONNECTS, J-BOXES, AND CONDUITS EXPOSED TO THE OUTSIDE WEATHER AND

MECHANICAL ROOMS SHALL BE OF A NON-CORROSIVE, WEATHERPROOF TYPE.

15. ALL NEW EXPOSED CONDUITS MUST RUN AGAINST THE WALL OR CEILING. DO NOT PENDANT

MOUNT ANY CONDUIT FROM THE CEILING. EXPOSED CONDUITS ARE ONLY ALLOWED IN

EXPOSED CEILING AREA.

16. ALL MATERIALS USED IN INSTALLATION SHALL BE U.L. APPROVED AND NEW.

17. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (ROMEX NOT PERMITTED).

18. ALL EXTERIOR RECEPTACLES SHALL BE OF WEATHER-RESISTANT TYPE AS PER NEC 406.8.

19. NO CONDUITS SHALL RUN IN DUCT WORK.

20. CABLES OR RACEWAYS INSTALLED IN EXPOSED OR CONCEALED LOCATIONS UNDER METAL-

CORRUGATED SHEET ROOF DECKING SHALL BE INSTALLED AND SUPPORTED SO THAT THE

NEAREST OUTSIDE SURFACE OF THE CABLE OR RACEWAY IS NOT LESS THAN 38 MM (1 1/2 IN.)

FROM THE NEAREST SURFACE OF THE ROOF DECKING.

21. PROVIDE LATERAL AND LONGITUDINAL BRACING FOR ALL CONDUIT RACKS, CABLE TRAYS,

ETC., EXCEEDING 20 FEET IN LENGTH.

22. MINIMUM SIZE CONDUIT SHALL BE 3/4" FOR INTERIOR APPLICATION, AND 1" FOR CONDUIT

BURIED BELOW GRADE IN EXTERIOR APPLICATION.

23. LABELING IS REQUIRED FOR ALL PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL

CENTERS, MOTOR STARTERS, TRANSFORMERS, MAJOR JUNCTION BOXES, DISCONNECT

SWITCHES, BREAKERS, PUSH BUTTONS, ETC., INTERLOCKS AND RELAY PANELS.

24. USE RIGID STEEL, SET SCREW TYPE FITTINGS ONLY. DIE CAST FITTING SHALL NOT BE USED.

25. USE EPOXY ANCHORS TO SUPPORT THE ELECTRICAL EQUIPMENT. EXPANSION ANCHOR

BOLTS ARE NOT ACCEPTABLE.

26. AT THE END OF THE JOB, PROVIDE BLANK, MATCHING COVER PLATES FOR ALL J-BOXES

WHERE DEVICES HAVE NOT YET BEEN INSTALLED.

27. SEAL AROUND ALL CONDUIT PENETRATIONS THROUGH WALLS AND CEILINGS WITH A FIRE

RATED MATERIAL. 3M IS AN APPROVED MANUFACTURER.

28. PRIOR TO SUBMITTAL FOR A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND

INCLUDE IN THEIR BID PACKAGE ALL CHARGES RELATED TO EXISTING CONDITIONS AND

DEMOLITION WORK. PROVIDE SHOP DRAWINGS AS REQUIRED BY CONSTRUCTION

DOCUMENTS. ALL LABOR, MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A

PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT. REPLACE OR REPAIR

ALL DEFECTS DURING THE GUARANTEED PERIOD.

29. THE ELECTRICAL CONTRACTOR SHALL TERMINATE THE ELECTRICAL CONNECTIONS TO ALL

THE EQUIPMENT BY PROVIDING THE NECESSARY MALE/ FEMALE CONNECTOR, RECEPTACLE,

PLUG, ETC.

30. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE,

CONNECTION REQUIREMENT, ETC.) OF EQUIPMENT FURNISHED UNDER OTHER DIVISIONS

WITH APPROVED SHOP DRAWINGS.

31. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ENGINEER, IN WRITING, OF ANY

DISCREPANCIES FOUND BETWEEN THE INTENDED FUNCTION OF EQUIPMENT AND EQUIPMENT

SPECIFIED IN THE CONTRACT DOCUMENTS WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR

TO ISSUANCE OF THE FINAL ADDENDUM. FAILURE TO REPORT ANY DISCREPANCY (CATALOG

NUMBERS, DISCONTINUED ITEMS, ETC.) DOES NOT RELIEVE THE CONTRACTOR FROM

PROVIDING EQUIPMENT WHICH SHALL CONFORM TO AND FULFILL THE INTENT OF THE

CONTRACT DOCUMENTS. NOR SHALL IT BE USED AS A CONDITION TO OBTAIN ADDITIONAL

FUNDS FROM THE OWNER AFTER THE CONTRACT IS AWARDED. THE CONTRACTOR SHALL

REQUEST ALL CLARIFICATIONS OF CONTRACT DOCUMENT REQUIREMENTS, IN WRITING, TO

THE ARCHITECT/ ENGINEER WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE

OF THE FINAL ADDENDUM.

32. CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS

SPECIFICALLY NOTED OTHERWISE.

33. THE OWNER MUST SCHEDULE INTERRUPTIONS OF SERVICE WHEN CONTRACTOR WISHES TO

MAKE UTILITY CONNECTIONS. NOTIFY, IN WRITING, THE OWNER'S REPRESENTATIVE 72 HOURS

PRIOR TO TIME WHEN INTERRUPTION IS DESIRED. INTERRUPTION MUST BE AT THE COUNTY'S

CONVENIENCE. OVERTIME, IF REQUIRED FOR THIS WORK, IS TO BE AT CONTRACTOR’S

EXPENSE.

34. ALL CONDUCTORS SHALL BE IN CONDUIT (3/4" MINIMUM). MC CABLES ARE ONLY ALLOWED

FOR CONNECTION TO THE LIGHT FIXTURES. (MAXIMUM OF 6').

35. ALL METALLIC CONDUITS, JOINTS, FITTINGS, ETC. IN CONTACT WITH THE GROUND SHALL BE SPIRAL WRAPPED WITH 3M SCOTCHRAP-51, 20 MIL TAPE (OR APPROVED EQUAL). 1/2" OVERLAP

IS REQUIRED.

36. PROVIDE TYPED PANEL INDEX FOR EXISTING ELECTRICAL PANELS AFFECTED BY THE SCOPE

OF THIS WORK. EXISTING/UNAFFECTED CIRCUITS IN THE PANEL SHALL BE ITALICIZED AND

CHANGED/ADDED CIRCUITS SHALL BE TYPED BOLD.

GENERAL NOTES:

334543-2202

MANSOUR

AGHDASI

NO.

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

#1016

/3

/2

:0

:2

A

M

A u to d e s k D o c s

/2

S

L C o A

D C

T u rn s ti le s r2

/1

S L

C O

A D

C T u rn s ti le

.r v t

GENERAL

NOTES &

DETAILS

Author

25030

08.01.25

CD SET

E-001

S

W

S

O U

T H

S A

L T

L A

K E

U

T

S a lt

L a k e

C o u n ty

A D

C L

O B

B Y

T U

R N

S T

IL

E

S

# Date Revision

2. CIRCUIT NUMBERS ARE SCHEMATIC AND SHOW THE DESIGN INTENTION AND LOAD BALANCE REQUIREMENTS. CONTRACTORS SHALL VERIFY ALL EXISTING AVAILABLE CIRCUITS AND THOSE WHICH BECOME AVAILABLE AS A RESULT OF DEMOLITION. CONTRACTOR SHALL INDICATE ACTUAL CIRCUITS USED ON AS-BUILT DRAWINGS. THE CONTRACTOR IS TO INFORM GC/ENGINEER IF SUFFICIENT BREAKER SPACES DID NOT FREE UP, PRIOR TO ROUGH-IN.

1. PROVIDE NEW CIRCUIT BREAKERS AS NECESSARY. NEW BREAKERS SHALL MATCH AIC RATING OF EXISTING BREAKERS.

NOTES:

Total Est. Demand: 6 A

Total Conn.: 6 A

Total Est. Demand: 2020 VA

Receptacle 1300 VA 100.00% 1300 VA Total Conn. Load: 2020 VA

Power 720 VA 100.00% 720 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 3 A 14 A 0 A AIC: Total Load: 360 VA 1660 VA 0 VA

20 A 1 EXISTING -- E 41 0 / 0 42 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 39 0 / 0 40 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 37 0 / 0 38 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 35 0 / 0 36 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 33 0 / 0 34 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 31 0 / 0 32 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 29 0 / 0 30 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 27 0 / 0 28 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 25 0 / 0 26 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 23 0 / 0 24 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 21 0 / 0 22 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 19 0 / 0 20 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 17 0 / 0 18 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 15 0 / 0 16 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 13 0 / 0 14 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 11 0 / 0 12 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 9 0 / 0 10 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 7 0 / 0 8 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 5 0 / 0 6 E -- EXISTING 1 20 A

20 A 1 EXISTING -- E 3 0 / 1660 4 N Po... OUTLETS & POLE - CORR J122 1 20 A 20 A 1 EXISTING -- E 1 0 / 360 2 N Po... J-BOX - TURNSTILE AND DIGCON 1 20 A

BREAKE

R

A P

DESCRIPTION TYPE

E/ N

CIR.

A B C

CIR.

E/ N

TYPE DESCRIPTION

BREAKE

R P A

AMPS: 250 A MAIN: Volts: 120/208 Wye PHASE: 3 # OF WIRES: 4 MOUNTING: Surface LOCATION:

EXISTING PANEL NLJ2A

C R

C R

J

C R

S

S

JJ

J

C R

J

J

CR

C R

J1

JC.6

JC.8

JD

JD.3

JE

JE.4

J2 J3

BRIEFING ROOM

EXIT CORRIDOR

J123

SALLYPORT

J120

STAIR

J118

STAIR

P3

P1

P4

P2

NLJ2A-2,4

TYP

P6

P3

SECURITY CHECKPOINT

J351

CLG

CLG

P5

P2

P8

P10

A

CLG

CLG

P12

J1

JC.6

JC.8

JD

JD.3

JE

JE.4

J2 J3

P7

P7

P11

NLJ2B NHJ1

NHJ1A

NHJ1.2

NLJ2

NLJ2A

EXISTING

COMM.

ROOM

APPROXIMATE PATH

OF 3/4" CONDUIT

NORTH

1/8" = 1’−0"

LEVEL 1 FLOOR PLAN − FIRE ALARM/ SYSTEMS & POWER

REFERENCE NOTES

P1 FURNISH AND INSTALL A 4"X4" FLOOR TO CEILING METAL POWER POLE WITH POWER/COMMUNICATION DIVIDER IN THE

APPROXIMATE LOCATION SHOWN. PROPERLY SECURE THE POWER POLE ON THE FLOOR AND CEILING. UTILIZE THE POWER POLE TO PROVIDE POWER/DATA CABLE TO THE DESK AND EQUIPMENT SHOWN. LEGRAND/WIREMOLD IS THE APPROVED

MANUFACTURER.

P2 PROVIDE ONE 120 VOLT DEDICATED POWER TO THE TURNSTILE AND DIGCON. COORDINATE EXACT LOCATION WITH THE SUPPLIER PRIOR TO ROUGH-IN. RUN A CAT6 CABLE FROM EACH TURNSTILE AND ANOTHER ONE FROM DIGICON TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS.

COORDINATE THIS WORK WITH ADC. IN ADDITION, RUN CAT6 CABLE IN 3/4" CONDUIT FROM THE CEILING SENSOR TO THE CORRESPONDING TURNSTILE FOR SIGNAL. COORDINATE WITH THE SUPPLIER AND SAWCUT THE FLOOR TO RUN POWER AND COMMUNICATION CABLES AS NEEDED. RUN THE POWER AND THE CAT6 CABLE FOR THE CEILING MOUNTED SENSORS IN THE

POWER POLE.

P3 CARD READERS ARE INTEGRATED AS PART OF THE ACCESS GATE. THE CONTRACTOR IS TO COORDINATE WITH THE EQUIPMENT SUPPLIER AND RUN NEW CAT6 CABLE IN 1" CONDUIT FROM THE CARD READER TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK WITH ADC.

P4 RELOCATE EXISTING CARD READERS TO THE NEW LOCATIONS SHOWN. FURNISH AND INSTALL NEW J-BOX. RUN A CAT6 CABLE IN 1" CONDUIT FROM THE J-BOX TO THE COMMUNICATION ROOM. ALSO RUN PROPER CONDUCTORS (TO MATCH EXISTING CARD READERS) IN 3/4" CONDUIT TO THE COMMUNICATION ROOM FOR THE ELECTRIFIED DOOR HARDWARE AND DOOR CONTACT.

TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK WITH ADC. THE CONTRACTOR IS ALLOWED TO REUSE EXISTING DATA CABLE FOR THE CARD READER IF POSSIBLE.

P5 FURNISH AND INSTALL A NEW J-BOX FOR THE CCTV CAMERA. RUN A CAT6 CABLE FROM THE J-BOX TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK

WITH ADC. COORDINATE WITH ADC FOR EXACT LOCATION.

P6 FURNISH AND INSTALL A 4"X4" X2-1/8" J-BOX WHERE VOICE/DATA OUTLETS ARE SHOWN. RUN A CAT6 CABLE IN 1" CONDUIT FROM THE J-BOX TO THE COMMUNICATION ROOM. TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR THE CABLE/JACKS. COORDINATE THIS WORK WITH ADC. COORDINATE WITH THE OWNER/ARCHITECT FOR THE EXACT LOCATION

PRIOR TO ROUGH-IN.

P7 RELOCATE THE EXISTING LIGHT FIXTURES AND THE ASSOCIATED CIRCUIT TO THE NEW LOCATION SHOWN TO ALLOW THE

INSTALLATION OF TURNSTILE DEVICES.

P8 FURNISH AND INSTALL A NEW J-BOX IN THE APPROXIMATE LOCATION SHOWN FOR CARD READER. RUN A CAT6 CABLE IN 1" CONDUIT FROM THE J-BOX TO THE COMMUNICATION ROOM. ALSO RUN PROPER CONDUCTORS (TO MATCH EXISTING CARD READERS) IN 3/4" CONDUIT TO THE COMMUNICATION ROOM FOR THE ELECTRIFIED DOOR HARDWARE AND DOOR CONTACT.

TERMINATE BOTH ENDS. BELDEN IS THE APPROVED MANUFACTURER FOR CABLE/JACKS. COORDINATE WITH THE GC/DOOR

HARDWARE FOR CONDUCTOR PATH. COORDINATE THIS WORK WITH ADC.

P10 RELOCATE THE EXISTING CAMERA AND ASSOCIATED CONDUIT/CABLE TO THE APPROXIMATE LOCATION SHOWN. ENSURE THE CAMERA IS OPERATIONAL AFTER THE RELOCATION. COORDINATE WITH ADC FOR EXACT LOCATION.

P11 ROTATE THE EXISTING EXIT SIGN 90 DEGREES. REPLACE THE FRONT FACE WITH A DIRECTING FACE WITH AN ARROW. POINT THE

ARROW TOWARD THE EXIT DOOR.

P12 PROVIDE POWER TO THE DOOR ALARM. COORDINATE WITH THE DOOR HARDWARE SUPPLIER FOR EXACT TERMINATION POINT

PRIOR TO ROUGH-IN.

SHEET NOTES - DEMOLITION

1 ALL MATERIALS THAT ARE TO BE REMOVED FROM THE PREMISES SHALL BE RETURNED TO THE OWNER. MATERIALS WHICH THE

OWNER DECIDES NOT TO KEEP SHALL BE SALVAGED AND REMOVED FROM THE SITE BY THE CONTRACTOR.

2 ALL CONCEALED CONDUITS THAT CANNOT BE REMOVED SHALL BE CUT FLUSH WITH THE FINISHED SURFACES AND CAPPED OFF AFTER THE WIRING HAS BEEN DISCONNECTED AT THE PANEL AND REMOVED FROM THE CONDUIT.

3 IN AREAS WHERE CIRCUIT CONTINUITY IS INTERRUPTED BUT MUST BE MAINTAINED BECAUSE OF THE NATURE OF THE FACILITY, MAKE ALL THE NECESSARY MODIFICATIONS TO THE CIRCUITS IN ORDER TO MAINTAIN THE CIRCUITS INTEGRITY.

334543-2202

MANSOUR

AGHDASI

NO.

DATE:

DRAWN BY:

CHECKED BY:

NEXUS PROJ. #:

123456

E

D

C

B

A

Architectural NEXUS, Inc.

2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com

Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.

© ARCH NEXUS All Rights Reserved

#1016

/3

/2

:0

:2

A

M

A u to d e s k D o c s

/2

S

L C o A

D C

T u rn s ti le s r2

/1

S L

C O

A D

C T u rn s ti le

.r v t

LEVEL 1 FLOOR

PLAN -

DEMOLITION,

SYSTEMS &

POWER

Author

25030

08.01.25

CD SET

EE-101

MA

S

W

S

O U

T H

S A

L T

L A

K E

U

T

S a lt

L a k e

C o u n ty

A D

C L

O B

B Y

T U

R N

S T

IL

E

S

# Date Revision

NORTH

1/8" = 1’−0"

LEVEL 1 FLOOR PLAN − DEMOLITION

0' 2' 4' 8'

0' 2' 4' 8'

NORTH

1" = 20’−0"

OVERALL PLAN

GENERAL
G-001 - COVER SHEET

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .