SOW PHL ATCT-TRACON New FACP and loop devices in total Final rev 5.pdf

PDF 303 KB Posted

Attached to
IIJA Funded - Fire Alarm Retrofit (PHL ATCT/TRACON)
Solicitation number
697DCK25R00058
Issued by

About this file

This document is a Statement of Work (SOW) for a fire alarm system retrofit at the Philadelphia International Airport Traffic Control Tower and Terminal Radar Approach Control (PHL ATCT/TRACON) facility. The project involves replacing the existing obsolete Siemens MXL fire alarm system with a new Siemens FireFinder XLS system, including retrofitting the Fire Alarm Control Unit (FACU) and replacing devices in Signaling Line Circuit #3.

Key requirements include installing new Siemens FireFinder XLS electronics, replacing four remote annunciators, converting the fire alarm program, and replacing obsolete input devices such as detectors, pull stations, and interface devices. The contractor must provide all labor, materials, and equipment to complete the retrofit, ensuring full system integration and compliance with NFPA 72 standards. The work is to be completed within 45 calendar days after the Notice to Proceed, with specific restrictions on work hours and potential for additional circuit replacements as additive items. The project is set aside for small businesses, with an estimated construction magnitude between $50,000 and $100,000.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PHILADELPHIA INTERNATIONAL AIRPORT

AIRPORT TRAFFIC CONTROL TOWER

(PHL ATCT)/TERMINAL RADAR APPROACH

CONTROL (TRACON), PHILADELPHIA, PA

RETROFIT OF FIRE ALARM CONTROL UNIT

(FACU) AND DEVICES INTO THE EXISTING FIRE

ALARM SYSTEM

STATEMENT OF WORK

BACKGROUND: The existing fire alarm system at the PHL ATCT/TRACON is the Siemens

Industry MXL product line, which is now obsolete and no longer supported by the manufacturer.

At the present time, signaling line devices and circuit cards of the system that have failed in service need to be replaced with used devices from third party sources, and due to their rarity are either difficult to find or expensive. This can result in the fire alarm system being out of service either in part or in whole. A decision was made to convert the fire alarm system to Siemens’ current

FireFinder XLS system using their retrofit kit.

GENERAL: Removing older in-service fire alarm system hardware and replacing with new fire alarm system hardware using retrofit kits from the same manufacturer (Siemens), including new

Fire Alarm Control Unit (FACU) hardware and remote annunciator hardware as well as all alarm initiating devices in one (1) Signaling Line Circuit (SLC) at PHL ATCT/TRACON.

ADDRESS: PHL ATCT/TRACON is located at 15 Hog Island Rd, Philadelphia, PA 19153.

SCOPE OF WORK: The contractor must furnish all labor, supervision, materials, services, insurance, and equipment necessary to perform the following work:

A. Using a retrofit kit replace all electronics in the existing Siemens main fire alarm unit

(FACU) model MXL with new Siemens FireFinder XLS series electronics.

B. Using retrofit kits, replace four (4) existing fire alarm remote annunciators with new remote annunciators.

C. Convert existing fire alarm program to XLS system format and program software to result in the complete integration of new and existing devices into a fully operational fire detection and alarm system.

D. Replace obsolete Siemens fire alarm input devices in existing facility Signaling Line Circuit

#3 (see Drawing FA-1) with newest generation Siemens fire alarm input devices. Provide all input and ancillary devices and equipment as needed for a complete replacement of SLC#3 to allow its integration into the new retrofitted XLS series FACU and its continued use of the obsolete fire alarm input devices in the balance of the system. Replacement must include all detectors, pull stations, addressable interface devices with or without relays, and remote status & alarm indicators.

E. Provide and install all other equipment, devices and wiring not expressly stated that are necessary for the installation of a fully operational retrofit of the existing system with new devices on SLC#3, such as: device loop card(s), network interface card(s), cardcage(s), printer or other device module(s), batteries, enclosures, and adapters.

F. Once replaced with new devices, provide all existing obsolete Siemens fire alarm input devices removed from SLC#3 to the COR for use as spares.

G. Provide a new Siemens portable Device Programmer to the COR. The Device Programmer must be able to test, program and address the fire alarm system devices. Instruct the PHL FAA

Tech Ops ESU manager and coordinator in its use.

H. Provide a full system inspection and test of the Fire Alarm system after all work has been performed as required by National Fire Protection Association (NFPA) standard 72.

I. After the installation is complete, update all Fire Alarm as-built Computer-Aided Design

(CAD) format drawings provided by the FAA to the Contractor. The FAA will provide the set of

Drawings FA-1 through FA-5. Not every drawing will have to be updated as part of the work under this contract.

J. Fire alarm devices must be designed, engineered, furnished, installed, and tested in accordance with NFPA 72, this specification, the project drawings and any attached specification sections, as indicated:

Attachments:

Drawing Number: Title:

FA-1 (For Reference Only) Fire Alarm Floor Plan – Base Level, for PHL

TRACON/ATCT, As-Built drawing with last stamped date of 7/2/04.

FA-2 (For Reference Only) Fire Alarm Floor Plan – First-Sixth floors, for PHL

TRACON/ATCT, As-Built drawing with last stamped date of 7/2/04.

Specification Section:

Section Title

284621.11 SF ADDRESSABLE FIRE-ALARM SYSTEMS

K. All quantities and measurements in this specification of work and the project drawings are approximate. Exact quantities and measurements are the responsibility of the contractor.

Additive Items:

Additive items entail replacing all obsolete Siemens fire alarm input devices in the remaining

Signaling Line Circuits on an individual SLC basis. Replace with newest generation Siemens fire alarm input devices. Provide all input and ancillary devices and equipment for a complete replacement of the SLC to allow its integration into the new retrofitted XLS series FACU and its continued use of the obsolete fire alarm input devices in the balance of the system. Replacement must include all detectors, pull stations, addressable interface devices with or without relays, and remote status & alarm indicators. Once replaced with new devices, provide all existing obsolete

Siemens fire alarm input devices removed from the SLC to the COR for use as spares. All requirements of the Statement of Work, the attached Specification Section and the Drawings remain applicable. Additives are as follows:

1. Additive Item #1: SLC#1 (See Drawing FA-1, for reference only)

2. Additive Item #2: SLC#2 (See Drawing FA-1, for reference only)

3. Additive Item #3: SLC#4 (See Drawing FA-1 & FA-2, for reference only)

4. Additive Item #4: SLC#5 (See Drawing FA-2, for reference only)

5. Additive Item #5: SLC#6 (See Drawing FA-1, for reference only)

MATERIALS & EQUIPMENT:

A. General. Products used must be produced by manufacturers regularly engaged in the manufacture of similar items and with a history of successful production.

Deliver all materials in their original, unopened containers with product identification clearly legible on each container. Store in clean, dry spaces in a manner to prevent damage from any cause.

Store only under conditions recommended by the manufacturers. The COR will give assistance as to available storage areas. The contractor must supply Safety Data Sheets (SDS) for all applicable materials.

An appointed representative of the Federal Aviation Administration must be permitted at any time to take samples of the materials to be tested for conformance with this specification.

B. Government Supplied Materials. There will be no government supplied materials. All materials covered in this specification must be furnished by the contractor.

C. Submittals. All equipment and materials must be submitted for approval prior to use in order to check conformance with these specifications. Submittals for the materials listed under all sections must be submitted within 14 calendar days after award of the contract and must include:

1. A complete material list showing all items proposed to be furnished and installed. The list must include manufacturer's name, and material and equipment identification such as style, type, or catalog number, to permit ready and complete identification.

2. Sufficient data to demonstrate that all such materials meet or exceed the specified requirements. A manufacturer's statement indicating complete compliance with the applicable Federal Specification or Military Specification will be acceptable proof of such compliance.

3. Specifications, installation instructions, and general recommendations from the materials' manufacturers showing applications and procedures under which it is proposed that the materials will be installed.

The FAA will review all submittals and will approve or disapprove them in writing. Approval must not be construed as a complete check, but will indicate only that the general method of construction and detailing is satisfactory. Approval will not relieve the contractor of the responsibility for any error or omission which may exist. Use of any materials not expressly approved will be at the risk of the contractor.

D. Documentation. The contractor must submit the following documentation for approval or disapproval by the FAA:

1. Material Submittal Documentation. Submit all instruction books, operations and maintenance manuals, cut sheets and parts lists for all applicable materials and equipment.

The contractor must provide Safety Data Sheets (SDS) for all applicable materials.

2. Contractor’s Health and Safety Program. The contractor must submit his or her company’s Occupational Safety and Health Administration (OSHA) compliant Health and Safety Program that covers the contractor’s employees. The program must address health and safety issues that the contractor’s employees would be subject to while performing the work under this contract such as Confined Space Entry, Respiratory

Protection, Hazardous Communication, etc.

E. Fire Alarm. The following section attached to this base specification covers Fire Alarm materials and equipment. This section is:

Section Title

284621.11 SF ADDRESSABLE FIRE-ALARM SYSTEMS

F. Electrical Materials. Any wiring and electrical materials required to perform the work in this specification must be supplied by the contractor. All electrical materials required must conform to:

1. National Electrical Code, NFPA 70, latest edition.

2. Underwriter's Laboratories, Inc. Listing Service.

3. NFPA National Fire Codes.

4. State and Local Building and Fire Codes.

5. FAA Construction Specification for Premises Wiring, FAA-C-1217, latest edition.

6. FAA Standard for Lightning and Surge Protection, Grounding, Bonding, and Shielding

Requirements for Facilities and Electronic Equipment, FAA-STD-019, latest edition.

7. Any other applicable federal, state or local codes.

Copies of the FAA documents will be provided upon request.

In case of discrepancies the matter must be promptly submitted to the Contracting Officer (CO) who will make a determination. An adjustment by the contractor without such a determination will be at their own risk and expense.

1. Electrical Conduit, Supports and Fittings. All conductors must be installed in conduit.

Size must be a minimum of 3/4”, type must be electrical metallic tubing (EMT), rigid galvanized steel, or flexible sealtight as appropriate.

2. Electrical Conductors. All conductors must be of an appropriate type and size as allowable by the manufacturer of the fire alarm devices and National Electrical Code (NEC) or FAA standards, whichever is most stringent.

INSTALLATION AND EXECUTION:

A. General. All materials must be installed according to the manufacturer's written instructions, standard industry practices and methods, all applicable laws, codes, and standards, and as outlined below.

B. Discrepancies. Discrepancies found between the drawings, the specifications or the standards must be promptly submitted to the CO who will make a determination. An adjustment by the contractor without such a determination will be at his own risk and expense.

C. Work Area Clearances. It will be the contractor's responsibility to secure, through the FAA

COR, necessary clearances of work areas, and equipment and material storage areas, including any time limitations upon the use of such areas. It will be the contractor's responsibility to confine his personnel to the designated work areas at all times. The contractor will be responsible for relocation and/or re-scheduling of his work force in the event of an operational request to clear a critical area.

D. Safety and Liability. The contractor must be responsible for his/her employees and his/her subcontractor's employees, for strict observance of all rules and regulations of the Occupational

Safety and Health Administration (OSHA), applicable FAA authorities, and other governing authorities during the performance of this contract. The contractor will be required to make certain that his employees observe all local FAA rules and regulations governing the movement and parking of equipment and vehicles on FAA property.

1. Contractor’s Health and Safety Program. The contractor must have an OSHA compliant

Health and Safety Program for his or her employees. The program must address health and safety issues that the contractor’s employees would be subject to while performing the work under this contract such as Confined Space Entry, Hazardous Communication, etc. A copy of this program must be submitted to the FAA for review.

E. Protection.

1. General. The contractor must be responsible for the performance and enforcement of all forms of protection of persons, property, and work. Adjacent areas of the work area will be occupied during the procession of the work. When needed, the contractor must provide barriers in order to direct the traffic flow of personnel. Building personnel and equipment present as work is being performed must be completely protected from any dust, dirt, or debris caused by the work. It will be the contractor's responsibility to locate and protect all utility lines from damage, underground and otherwise. The FAA will assist in locating utility lines through the use of drawings only. If underground utility lines are present in any work area it is the contractor’s responsibility to coordinate professional mark-out services to locate such lines. All damage caused by the contractor to existing utilities must be repaired by the contractor at his own expense. If existing surfaces, materials or equipment are damaged or defaced during the process of dismantling, demolition or installation, they must be repaired or replaced with like or other approved materials and returned to equal or better than existing conditions and/or appearance, at no additional cost to the Government. At the end of each work day it will be the contractor's responsibility to clean all work areas and store all materials.

2. Protection of Existing Air Traffic Control Facility. The work required is to be performed within an existing Air Traffic Control operation. This facility will remain in operation twenty-four hours a day, seven days a week. The contractor must perform all his work in such a manner so as not to endanger the operation of the facility. Extremely sensitive electronic equipment will be in use by personnel in various rooms as the work under this contract is being performed. The contractor must ensure that these personnel are protected from excessive noise, odors, fumes, dust or debris produced from this work.

Extra-clean work practices must be employed by the contractor. The complete protection of equipment and personnel is essential while the work is being performed.

If feasible, the contractor might be required to perform some aspects of the work in another room to minimize disruptions to personnel and room environments. The FAA

COR will be able to provide further direction in this matter.

3. Special Precautions. The contractor must protect against any movement or settlement of existing or new construction, and install barriers and/or control elements to protect against air, smoke, water, noise and vibration.

F. Qualification of Contractor and Installers. The installing contractor must be licensed, regularly engaged in the performance of installing fire alarm systems and have five (5) or more years of experience as such. Additionally, the contractor must be an official Siemens USA Fire

Alarm Systems Partner. The contractor must submit proof of licensing, partnership, qualifications, references, and other similar jobs, with his bid. The contractor and installers must be thoroughly trained and experienced in the necessary skills for proper execution of the work and thoroughly familiar with the specified requirements.

G. Removal of Existing Materials. Existing equipment and materials that are required to be removed in order to install new equipment and materials noted in this contract must be removed in their entirety, inclusive of all accessories and ancillary components no longer required.

H. Fire Alarm. The following section attached to this base specification covers Fire Alarm installation and execution. This section is:

Section Title

284621.11 SF ADDRESSABLE FIRE-ALARM SYSTEMS

I. Electrical Installation. All electrical work must conform to:

1. National Electrical Code, NFPA 70, latest edition.

2. NFPA 70E, Standard for Electrical Safety in the Workplace, latest edition.

3. Underwriter's Laboratories, Inc. Listing Service.

4. NFPA National Fire Codes.

5. State and Local Building and Fire Codes.

6. FAA Construction Specification for Premises Wiring, FAA-C-1217, latest edition.

7. FAA Standard for Lightning and Surge Protection, Grounding, Bonding, and Shielding

Requirements for Facilities and Electronic Equipment, FAA-STD-019, latest edition.

8. Any other applicable federal, state or local codes.

Copies of the FAA documents will be provided upon request.

In case of discrepancies the matter must be promptly submitted to the CO who will make a determination. An adjustment by the contractor without such a determination will be at his own risk and expense.

Conduit and conductors must be installed in concealed locations above the suspended ceiling and in the walls and must be connected to circuits as shown on the drawings. Adequately support all conduit runs.

J. Documentation. The contractor must supply two (2) copies of all instruction books, operations and maintenance manuals, and parts lists for all applicable materials and equipment.

K. Final Cleanup. All soil and face smears on materials must be corrected and cleaned. Any area disturbed or items damaged by the work must be restored or repaired. After all work is complete, all debris, dirt, waste, old material, and the contractor's equipment and tools, must be removed from all work areas. Debris and old material must be removed from the job site, off

Government owned property. The facility dumpsters are not permitted to be used for the disposal of any waste materials as a result of the work under this contract.

PERIOD OF PERFORMANCE: All work in this specification must be completed within 45 calendar days after the Notice to Proceed (NTP) is issued by the Contracting Officer (CO).

WORK HOURS: A work schedule must be agreed upon between the contractor and the COR before the commencement of this work at the facility.

All work not requiring activation of the fire alarm audio and visual notification devices will normally be performed between the hours of 8:00 AM and 4:30 PM, Monday through Friday unless otherwise agreed upon.

All work requiring activation of the fire alarm audio and visual notification devices must be performed between the hours of 11:00 PM and 5:00 AM, Monday through Friday.

Work during other hours might be required at any time during the performance of this contract if needed to minimize disruption of equipment and/or personnel or if it is determined to be beneficial to the mission of the facility.

SECTION 284621.11 - ADDRESSABLE FIRE-ALARM SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Existing fire-alarm system to be modified.

2. Addressable fire-alarm system.

3. Fire-alarm control unit (FACU).

4. Manual fire-alarm boxes.

5. System smoke detectors.

6. Duct smoke detectors.

7. Heat detectors.

8. Fire-alarm remote annunciators.

9. Fire-alarm addressable interface devices.

1.2 DEFINITIONS

A. DACT: Digital alarm communicator transmitter.

B. FACU: Fire-alarm control unit.

C. Voltage Class: For specified circuits and equipment, voltage classes are defined as follows:

1. Control Voltage: Listed and labeled for use in remote-control, signaling, and power-limited circuits supplied by a Class 2 or Class 3 power supply having rated output not greater than

150 V and 5 A, allowing use of alternate wiring methods complying with NFPA 70, Article 725.

2. Low Voltage: Listed and labeled for use in circuits supplied by a Class 1 or other power supply having rated output not greater than 1000 V, requiring use of wiring methods complying with NFPA 70, Article 300, Part I.

1.3 SEQUENCING AND SCHEDULING

A. Existing Fire-Alarm Equipment: Maintain existing equipment fully operational until new equipment has been tested and accepted. When new equipment is installed, label it "NOT IN

SERVICE" until it is accepted. Remove labels from new equipment when put into service, and label existing fire-alarm equipment "NOT IN SERVICE" until removed from building.

B. Equipment Removal: After acceptance of new fire-alarm system, remove existing disconnected fire-alarm equipment and wiring.

1.4 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For fire-alarm systems and components to include in emergency, operation, and maintenance manuals.

1. Include the following and deliver copies to the FAA.

a. Comply with "Records" section of "Inspection, Testing and Maintenance" chapter in

NFPA 72.

b. Provide "Fire-Alarm and Emergency Communications System Record of Completion

Documents" in accordance with "Completion Documents" Article in

"Documentation" section of "Fundamentals" chapter in NFPA 72.

c. Complete wiring diagrams showing connections between devices and equipment.

Each conductor must be numbered at every junction point with indication of origination and termination points.

d. Riser diagram.

e. Device addresses.

f. Record copy of site-specific software.

g. Provide "Inspection and Testing Form" in accordance with "Inspection, Testing and

Maintenance" chapter in NFPA 72, and include the following:

1) Equipment tested.

2) Frequency of testing of installed components.

3) Frequency of inspection of installed components.

4) Requirements and recommendations related to results of maintenance.

5) Manufacturer's user training manuals.

h. Manufacturer's required maintenance related to system warranty requirements.

i. Abbreviated operating instructions for mounting at FACU and each annunciator unit.

B. Software and Firmware Operational Documentation:

1. Software operating and upgrade manuals.

2. Program Software Backup: On USB media.

3. Device address list.

4. Printout of software application and graphic screens.

1.5 QUALITY ASSURANCE

A. Installer Qualifications:

1. Personnel must be trained and certified by manufacturer for installation of units required for this Project.

2. Installation must be by personnel certified by NICET as fire-alarm Level II technician.

3. Obtain certification by NRTL in accordance with NFPA 72.

4. Licensed or certified by authorities having jurisdiction.

PART 2 - PRODUCTS

2.1 EXISTING FIRE-ALARM SYSTEM TO BE MODIFIED

A. New Siemens FireFinder XLS retrofit kit and new devices for existing SLC#3.

B. Description: Retrofit of existing Siemens Model MXL FACU and replacement of all existing devices in SLC#3.

C. Accessories: See below, project base specification and project drawings.

D. Source Limitations for Fire-Alarm System and Components: Components must be compatible with, and operate as extension of, existing system. Provide system manufacturer's certification that components provided have been tested as, and will operate as, a system.

2.2 ADDRESSABLE FIRE-ALARM SYSTEM

A. Description:

1. Noncoded, UL-certified addressable system, with multiplexed signal transmission and horn-and-strobe notification for evacuation.

B. Performance Criteria:

1. Regulatory Requirements:

a. Fire-Alarm Components, Devices, and Accessories: Listed and labeled by a NRTL in accordance with NFPA 70 for use with selected fire-alarm system and marked for intended location and application.

2. General Characteristics:

a. Sensitivity control of certain smoke detectors.

b. Fire-alarm signal initiation must be by one or more of the following devices and systems, either existing (if installed and remaining) or new (to be installed via this project). New FACU must have the capability to accept signal initiation from all devices and systems noted:

1) Manual stations.

2) Heat detectors.

3) Flame detectors.

4) Smoke detectors.

5) Duct smoke detectors.

6) Carbon monoxide detectors.

7) Combustible gas detectors.

8) Automatic sprinkler system water flow.

9) Preaction system.

10) Fire-extinguishing system operation.

11) Fire standpipe system.

12) Dry system pressure flow switch.

13) Fire pump running.

c. Fire-alarm signal must initiate the following actions via the new FACU if they are currently initiated via the existing FACU being replaced. New FACU must have the capability to perform all actions noted:

1) Continuously operate alarm notification appliances.

2) Identify alarm and specific initiating device at FACU, connected network control panels, off-premises network control panels, and remote annunciators.

3) Transmit alarm signal to remote alarm receiving station.

4) Unlock electric door locks in designated egress paths.

5) Release fire and smoke doors held open by magnetic door holders.

6) Activate voice/alarm communication system.

7) Switch HVAC equipment controls to fire-alarm mode.

8) Activate smoke-control system (smoke management) at firefighters' smoke-control system panel.

9) Activate stairwell and elevator-shaft pressurization systems.

10) Close smoke dampers in air ducts of designated air-conditioning duct systems.

11) Activate preaction system.

12) Recall elevators to primary or alternate recall floors.

13) Activate elevator power shunt trip.

14) Activate emergency lighting control.

15) Activate emergency shutoffs for gas and fuel supplies, except for shutoffs serving legally required life-safety systems such as emergency generators and fire pumps.

16) Record events in system memory.

17) Record events by system printer.

18) Indicate device in alarm on graphic annunciator.

d. Supervisory signal initiation must be by one or more of the following devices and actions either existing (if installed and remaining) or new (to be installed via this project). New FACU must have the capability to accept supervisory signal initiation from all devices and actions noted:

1) Valve supervisory switch.

2) High- or low-air-pressure switch of dry-pipe or preaction sprinkler system.

3) Elevator shunt-trip supervision.

4) Independent fire-detection and -suppression systems.

5) Fire pump is running.

6) Fire pump has lost power.

7) Power to fire pump has phase reversal.

8) Zones or individual devices have been disabled.

9) FACU has lost communication with network.

e. System trouble signal initiation must be by one or more of the following devices and actions either existing (if installed and remaining) or new (to be installed via this project). New FACU must have the capability to accept system trouble signal initiation from all devices and actions noted:

1) Open circuits, shorts, and grounds in designated circuits.

2) Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating devices.

3) Loss of communication with addressable sensor, input module, relay, control module, remote annunciator, printer interface, or Ethernet module.

4) Loss of primary power at FACU.

5) Ground or single break in internal circuits of FACU.

6) Abnormal ac voltage at FACU.

7) Break in standby battery circuitry.

8) Failure of battery charging.

9) Abnormal position of switch at FACU or annunciator.

10) Voice signal amplifier failure.

11) Hose cabinet door open.

f. System Supervisory Signal Actions. The actions noted must be performed by the new FACU if they are currently performed by the existing FACU being replaced. In addition, the new FACU must have the capability to perform all other actions noted.

1) Initiate notification appliances.

2) Identify specific device initiating event at FACU, connected network control panels, off-premises network control panels, and remote annunciators.

3) Record event on system printer.

4) After time delay transmit trouble or supervisory signal to remote alarm receiving station.

5) Transmit system status to building management system.

6) Display system status on graphic annunciator.

g. Network Communications: The network communications noted must be performed by the new FACU if they are currently performed by the existing

FACU being replaced. In addition, the new FACU must have the capability to perform all other network communications noted.

1) Provide network communications for fire-alarm system in accordance with fire-alarm manufacturer's written instructions.

2) Provide network communications pathway per manufacturer's written instructions and requirements in NFPA 72 and NFPA 70.

3) Provide integration gateway for connection to building automation system.

h. System Printer:

1) New FACU must be able to use the existing system printer that is listed and labeled as integral part of fire-alarm system.

2.3 FIRE-ALARM CONTROL UNIT (FACU)

A. New Siemens FireFinder Model XLS retrofit of existing Siemens Model MXL

B. Description: Field-programmable, microprocessor-based, modular, power-limited design with electronic modules.

C. Performance Criteria:

1. Regulatory Requirements: Comply with NFPA 72 and UL 864.

2. General Characteristics:

a. System software and programs must be held in nonvolatile flash, electrically erasable, programmable, read-only memory, retaining information through failure of primary and secondary power supplies.

b. Include real-time clock for time annotation of events on event recorder and printer.

c. Provide communication between FACU and remote circuit interface panels, annunciators, and displays.

d. FACU must be listed for connection to central-station signaling system service.

e. Provide nonvolatile memory for system database, logic, and operating system and event history. System must require no manual input to initialize in the event of complete power down condition. FACU must provide minimum 500-event history log.

f. Addressable Initiation Device Circuits: FACU must indicate which communication zones have been silenced and must provide selective silencing of alarm notification appliance by building communication zone.

1) Addressable Control Circuits for Operation of Notification Appliances and

Mechanical Equipment: FACU must be listed for releasing service.

g. Fire-Alarm Annunciator: Arranged for interface between human operator at FACU and addressable system components including annunciation and supervision.

Display alarm, supervisory, and component status messages and programming and control menu.

h. Initiating-Device, Notification-Appliance, and Signaling-Line Circuits:

1) Pathway Class Designations: NFPA 72, Class A

2) Pathway Survivability: Level 0.

i. Serial Interfaces:

1) One dedicated RS 485 port for remote station operation using point ID DACT.

2) One RS 485 port for remote annunciators, Ethernet module, or multi-interface module (printer port).

http://www.specagent.com/LookUp/?ulid=13912&mf=&src=wd

j. Stairwell Pressurization: Provide output signal using addressable relay to start stairwell pressurization system. Signal must remain on until alarm conditions are cleared and fire-alarm system is reset. Signal must not stop in response to alarm acknowledge or signal silence commands.

1) Pressurization starts when alarm is received at FACU.

2) Alarm signals from smoke detectors at pressurization air supplies have higher priority than other alarm signals that start system.

k. Notification-Appliance Circuit:

1) Audible appliances must sound in three-pulse temporal pattern, as defined in

NFPA 72.

2) Where notification appliances provide signals to sleeping areas, alarm signal must be 520 Hz square wave with intensity 15 dB above average ambient sound level or 5 dB above maximum sound level, or at least 75 dB(A-weighted), whichever is greater, measured at pillow.

3) Visual alarm appliances must flash in synchronization where multiple appliances are in same field of view, as defined in NFPA 72.

l. Elevator Recall: Initiate by one of the following alarm-initiating devices:

1) Elevator lobby detectors except lobby detector on designated floor.

2) Smoke detectors in elevator machine room.

3) Smoke detectors in elevator hoistway.

m. Elevator controller must be programmed to move cars to alternate recall floor if lobby detectors located on designated recall floors are activated.

n. Water-flow alarm connected to sprinkler in elevator shaft and elevator machine room must shut down elevators associated with location without time delay.

1) Water-flow switch associated with sprinkler in elevator pit may have delay to allow elevators to move to designated floor.

o. Door Controls: Door hold-open devices that are controlled by smoke detectors at doors in smoke-barrier walls must be connected to fire-alarm system.

p. Remote Smoke-Detector Sensitivity Adjustment: Controls must select specific addressable smoke detectors for adjustment, display their current status and sensitivity settings, and change those settings. Allow controls to be used to program repetitive, time-scheduled, and automated changes in sensitivity of specific detector groups. Record sensitivity adjustments and sensitivity-adjustment schedule changes in system memory, and print out final adjusted values on system printer.

q. Transmission to Remote Alarm Receiving Station: Automatically transmit alarm, supervisory, and trouble signals to remote alarm station.

r. Voice/Alarm Signaling Service: Central emergency communication system with redundant microphones, preamplifiers, amplifiers, and tone generators provided as special module that is part of FACU.

s. Indicate number of alarm channels for automatic, simultaneous transmission of different announcements to different zones or for manual transmission of announcements by use of central-control microphone. Amplifiers must comply with

UL 1711.

1) Allow application of, and evacuation signal to, indicated number of zones and simultaneously allow voice paging to other zones selectively or in combination.

2) Programmable tone and message sequence selection.

3) Standard digitally recorded messages for "Evacuation" and "All Clear."

4) Generate tones to be sequenced with audio messages of type recommended by

NFPA 72 and that are compatible with tone patterns of notification-appliance circuits of FACU.

t. Status Annunciator: Indicate status of various voice/alarm speaker zones and status of firefighters' two-way telephone communication zones (if equipped).

u. Preamplifiers, amplifiers, and tone generators must automatically transfer to backup units, on primary equipment failure.

v. Printout of Events: On receipt of signal, print alarm, supervisory, and trouble events.

Identify zone, device, and function. Include type of signal (alarm, supervisory, or trouble) and date and time of occurrence. Differentiate alarm signals from other printed indications. Also, print system reset event, including same information for device, location, date, and time. Commands initiate printing of list of existing alarm, supervisory, and trouble conditions in system and historical log of events.

w. Primary Power: 24 V(dc) obtained from 120 V(ac) service and power-supply module.

Initiating devices, notification appliances, signaling lines, trouble signals, supervisory and DACT must be powered by 24 V(dc) source.

x. Alarm current draw of entire fire-alarm system must not exceed 80 percent of power-supply module rating.

y. Secondary Power: 24 V(dc) supply system with batteries, automatic battery charger, and automatic transfer switch.

z. Batteries: Sealed lead calcium.

D. Accessories:

1. Instructions: Computer printout or typewritten instruction card mounted behind plastic or glass cover in stainless steel or aluminum frame. Include interpretation and describe appropriate response for displays and signals. Briefly describe functional operation of system under normal, alarm, and trouble conditions.

2. Preaction System Functionality:

a. Initiate Presignal Alarm: This function must cause audible and visual alarm and indication to be provided at FACU. Activation of initiation device connected as part of preaction system must be annunciated at FACU only, without activation of general evacuation alarm.

2.4 MANUAL FIRE-ALARM BOXES

A. New Siemens Model XMS-D Addressable Dual-Action Manual Pull Station with Isolation

B. General Requirements for Manual Fire-Alarm Boxes: Comply with UL 38. Boxes must be finished in red with molded, raised-letter operating instructions in contrasting color; must show visible indication of operation; and must be mounted on recessed outlet box. If indicated as surface mounted, provide manufacturer's surface back box.

1. Double-action mechanism requiring two actions to initiate alarm, pull-lever type; with integral addressable module arranged to communicate manual-station status (normal, alarm, or trouble) to FACU.

2. Station Reset: Key- or wrench-operated switch.

2.5 SYSTEM SMOKE DETECTORS

A. Photoelectric Smoke Detectors: New Siemens Model OP921.

1. Performance Criteria:

a. Regulatory Requirements:

1) NFPA 72.

2) UL 268.

b. General Characteristics:

1) Detectors must be two-wire type.

2) Integral Addressable Module: Arranged to communicate detector status

(normal, alarm, or trouble) to FACU.

3) Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation.

4) Integral Visual-Indicating Light: LED type, indicating detector has operated and power-on status.

5) Detector address must be accessible from FACU and must be able to identify detector's location within system and its sensitivity setting.

6) Operator at FACU, having designated access level, must be able to manually access the following for each detector:

a) Primary status.

b) Device type.

c) Present average value.

d) Present sensitivity selected.

e) Sensor range (normal, dirty, etc.).

7) Detector must have functional humidity range within 0 to 95 percent relative humidity.

8) Color: White

9) Remote Control: Unless otherwise indicated, detectors must be digital-addressable type, individually monitored at FACU for calibration, sensitivity, and alarm condition and individually adjustable for sensitivity by FACU.

10) Multiple levels of detection sensitivity for each sensor.

2.6 DUCT SMOKE DETECTORS

A. Description: Photoelectric-type, duct-mounted smoke detector. New Siemens Model OP921 in new Siemens Model FDBZ492 air-duct-detector housing.

B. Performance Criteria:

1. Regulatory Requirements:

a. NFPA 72.

b. UL 268A.

2. General Characteristics:

a. Detectors must be two-wire type.

b. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to FACU.

c. Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation.

d. Integral Visual-Indicating Light: LED type, indicating detector has operated and power-on status.

e. Detector address must be accessible from FACU and must be able to identify detector's location within system and its sensitivity setting.

f. Operator at FACU, having designated access level, must be able to manually access the following for each detector:

1) Primary status.

2) Device type.

3) Present average value.

4) Present sensitivity selected.

5) Sensor range (normal, dirty, etc.).

g. Weatherproof Duct Housing Enclosure: NEMA 250, Type 4X; NRTL listed for use with supplied detector for smoke detection in HVAC system ducts.

h. Each sensor must have multiple levels of detection sensitivity.

i. Sampling Tubes: Design and dimensions as recommended by manufacturer for specific duct size, air velocity, and installation conditions where applied.

2.7 HEAT DETECTORS

A. Combination-Type Heat Detectors: New Siemens Model HI921.

1. Performance Criteria:

a. Regulatory Requirements:

1) NFPA 72.

2) UL 521.

b. General Characteristics:

1) Temperature sensors must test for and communicate sensitivity range of device.

c. Actuated by fixed temperature of 135 deg F or one of six (6) other field-selectable, pre-programmed temperature settings; or rate of rise that exceeds 15 deg F per minute unless otherwise indicated.

d. Mounting: Twist-lock base interchangeable with smoke-detector bases.

e. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to FACU.

f. Detector must have functional humidity range of 0 to 95 percent relative humidity.

g. Color: White.

2.8 FIRE-ALARM REMOTE ANNUNCIATORS

A. New Siemens Model SSD-C using Model XLS-RCC13F-ADPT adapter kit.

B. Performance Criteria:

1. Regulatory Requirements:

a. NFPA 72.

2. General Characteristics:

a. Annunciator functions must match those of FACU for alarm, supervisory, and trouble indications. Manual switching functions must match those of FACU, including acknowledging, silencing, resetting, and testing, with the exception of disable/enable functions which will not be retained on the remote annunciators (due to limitations of the retrofit process).

1) Mounting: Surface cabinet, NEMA 250, Type 1.

b. Display Type and Functional Performance: Alphanumeric display and LED indicating lights must match those of FACU. Provide controls to acknowledge, silence, reset, and test functions for alarm, supervisory, and trouble signals.

2.9 FIRE-ALARM ADDRESSABLE INTERFACE DEVICES

A. New Siemens Model XTRI-R.

B. Performance Criteria:

1. Regulatory Requirements:

a. NFPA 72.

2. General Characteristics:

a. Include address-setting means on module.

b. Store internal identifying code for control panel use to identify module type.

c. Listed for controlling HVAC fan motor controllers.

d. Monitor Module: Microelectronic module providing system address for alarm-initiating devices for wired applications with normally open contacts.

http://www.specagent.com/LookUp/?ulid=13934&mf=&src=wd

e. Integral Relay: Capable of providing direct signal to initiate HVAC AHU Shutdown, and to initiate Fan Start-up for Tower Stairwell Pressurization. Both functions are performed by addressable interface devices on the existing SLC#3.

1) Allow control panel to switch relay contacts on command.

2) Designed to monitor a normally open (N.O) or (N.C) normally closed dry contact.

f. Control Module: Have the capability to:

1) Operate notification devices.

2) Operate solenoids for use in sprinkler service.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas and conditions for compliance with requirements for ventilation, temperature, humidity, and other conditions affecting performance of the Work.

1. Verify that manufacturer's written instructions for environmental conditions have been permanently established in spaces where equipment and wiring are installed, before installation begins.

B. Examine roughing-in for electrical connections to verify actual locations of connections before installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Preinstallation Testing: Perform verification of functionality of installed components of existing system prior to starting work. Document equipment or components not functioning as designed.

B. Interruption of Existing Fire-Alarm Service: Do not interrupt fire-alarm service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary guard service in accordance with requirements indicated:

1. Notify FAA Management and the COR no fewer than seven (7) days in advance of proposed interruption of fire-alarm service.

2. Do not proceed with interruption of fire-alarm service without FAA written permission.

C. Protection of In-Place Conditions: Protect devices during construction unless devices are placed in service to protect facility during construction.

3.3 INSTALLATION OF EQUIPMENT

A. Comply with NECA 305, NFPA 72, NFPA 101, and requirements of authorities having jurisdiction for installation and testing of fire-alarm equipment. Install electrical wiring to comply with requirements in NFPA 70 including, but not limited to, Article 760, "Fire Alarm Systems."

1. Devices placed in service before other trades have completed cleanup must be replaced.

2. Devices installed, but not yet placed, in service must be protected from construction dust, debris, dirt, moisture, and damage in accordance with manufacturer's written storage instructions.

B. Connecting to Existing Equipment: Verify that existing fire-alarm system is operational before making changes or connections.

1. All new equipment used to retrofit the existing system must be installed in locations dictated by the existing equipment and/or be in compliance with requirements of this section if location of the new equipment is not fixed by the existing equipment.

2. All new input devices for SLC#3 must be installed in the same locations as the devices to be replaced. Comply with this this section for relocation requirements if there are individual devices where this cannot be accomplished.

3. Connect new equipment to existing control panel in existing part of building.

4. Connect new equipment to existing monitoring equipment at supervising station.

5. Expand, modify, and supplement existing control and monitoring equipment as necessary to extend existing control and monitoring functions to new points. New components must be capable of merging with existing configuration without degrading performance of either system.

C. Install wall-mounted equipment, with tops of cabinets not more than 78 inches above finished floor.

D. Manual Fire-Alarm Boxes:

1. Install manual fire-alarm box in normal path of egress within 60 inches of exit doorway.

2. Mount manual fire-alarm box on background of contrasting color.

3. Operable part of manual fire-alarm box must be between 42 and 48 inches above floor level.

Devices must be mounted at same height unless otherwise indicated.

E. Smoke- and Heat-Detector Spacing:

1. Comply with "Smoke-Sensing Fire Detectors" section in "Initiating Devices" chapter in

NFPA 72, for smoke-detector spacing.

2. Comply with "Heat-Sensing Fire Detectors" section in "Initiating Devices" chapter in

NFPA 72, for heat-detector spacing.

3. Smooth ceiling spacing must not exceed 30 ft.

4. Spacing of detectors for irregular areas, for irregular ceiling construction, and for high ceiling areas must be determined in accordance with Annex A or Annex B in NFPA 72.

5. HVAC: Locate detectors not closer than 60 inches from air-supply diffuser or return-air opening.

6. Lighting Fixtures: Locate detectors not closer than 12 inches from lighting fixture and not directly above pendant mounted or indirect lighting.

F. Install cover on each smoke detector that is not placed in service during construction. Cover must remain in place except during system testing. Remove cover prior to system turnover.

G. Duct Smoke Detectors: Comply with NFPA 72 and NFPA 90A. Install sampling tubes so they extend full width of duct. Tubes more than 36 inches long must be supported at both ends.

H. Elevator Shafts: Coordinate temperature rating and location with sprinkler rating and location. Do not install smoke detectors in sprinklered elevator shafts.

I. Remote Status and Alarm Indicators: Install in visible location near each smoke detector, sprinkler water-flow switch, and valve-tamper switch that is not readily visible from normal viewing position.

J. Audible Alarm-Indicating Devices: Install not less than 6 inches below ceiling. Install bells and horns on flush-mounted back boxes with device-operating mechanism concealed behind grille.

Install devices at same height unless otherwise indicated.

K. Visible Alarm-Indicating Devices: Install adjacent to each alarm bell or alarm horn and at least 6 inches below ceiling. Install devices at same height unless otherwise indicated.

L. Device Location-Indicating Lights: Locate in public space near device they monitor.

M. Antenna for Radio Alarm Transmitter: Mount to building structure where indicated. Use mounting arrangement and substrate connection that resists wind load of 100 mph with gust factor of 1.3 without damage.

3.4 ELECTRICAL CONNECTIONS

A. Connect wiring in accordance with FAA Construction Specification for Premises Wiring, FAA-C-

1217, latest edition.

B. Ground equipment in accordance with FAA Standard for Lightning and Surge Protection, Grounding, Bonding, and Shielding Requirements for Facilities and Electronic Equipment, FAA-

STD-019, latest edition.

C. Install electrical devices furnished by manufacturer, but not factory mounted, in accordance with

NFPA 70 and NECA 1.

D. Identify each new electrical connection completed under this contract, indicating electrical equipment designation and circuit number feeding connection. Use self-adhesive labels.

3.5 CONTROL CONNECTIONS

A. Re-use existing control and electrical power wiring to field-mounted control devices.

B. Connect control wiring in accordance with applicable NFPA Regulations, manufacturer’s instructions, and general industry standards.

C. Ensure existing nameplate for each control connection is correct, indicating field control panel designation and I/O control designation feeding connection. If needed, correct errors using self-adhesive labels.

3.6 PATHWAYS

A. Pathways must be installed in EMT.

B. Exposed EMT must be painted red enamel.

3.7 IDENTIFICATION

A. Identify system components, wiring, cabling, and terminals modified under this retrofit project.

Use self-adhesive labels.

B. Install framed instructions in location visible from FACU.

3.8 GROUNDING

A. Ground FACU and associated circuits in accordance with FAA Standard for Lightning and Surge

Protection, Grounding, Bonding, and Shielding Requirements for Facilities and Electronic

Equipment, FAA-STD-019, latest edition.

B. Ground shielded cables at control panel location only. Insulate shield at device location.

3.9 FIELD QUALITY CONTROL

A. Field tests must be witnessed by the COR.

B. Administrant for Tests and Inspections:

1. Administer and perform tests and inspections with assistance of factory-authorized service representative.

C. Tests and Inspections:

1. Visual Inspection: Conduct visual inspection prior to testing.

a. Inspection must be based on completed record Drawings and system documentation that is required by "Completion Documents, Preparation" table in "Documentation" section of "Fundamentals" chapter in NFPA 72.

b. Comply with "Visual Inspection Frequencies" table in "Inspection" section of

"Inspection, Testing and Maintenance" chapter in NFPA 72; retain

"Initial/Reacceptance" column and list only installed components.

2. System Testing: Comply with "Test Methods" table in "Testing" section of "Inspection, Testing and Maintenance" chapter in NFPA 72.

3. Test audible appliances for public operating mode in accordance…