ME001 _ HVAC DEMOLITION AND NEW WORK _ AVL ASR drawing.pdf
PDF 800 KB Posted
- Solicitation number
- 697DCK-24-R-00495
About this file
This document appears to be a Request for Proposal (RFP) for the replacement of two 2-ton air conditioning units at the Asheville ASR (AVL) facility in Fletcher, NC. The Federal Aviation Administration (FAA) is seeking proposals from eligible contractors to provide all labor, materials, and supervision for this HVAC replacement project. The period of performance will begin within 5 days of the Notice to Proceed. This requirement is set-aside for small businesses, including 8(a), SDVOSB, HUBZone, SDB, WOSB, and EDWOSB firms. A site visit is strongly encouraged on August 2, 2024. Proposals are due by August 23, 2024 and must be submitted electronically. The contract will be awarded as a single firm-fixed price contract. Interested contractors must have a current SAM.gov registration and cannot be suspended or debarred.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TT
TT
TT
TT
H
G
F
E
D
C
B
A
8 1234567
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN REDLINE
DATE APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY DATE
DRAWING NO
DESIGNED
REVIEWED BY
$F
IL
E$ $D
AT
E$
$T
IM
E$ $N
AM
E$
APPROVED
DATE
8 23467 5
H
G
F
E
D
C
B
A
KEY NOTES:
APPLIES TO REPLACEMENT OF TWO (2) UNITS, TO INCLUDE TURN-KEY INSTALLATION OF COMPLETE AND FULLY OPERATION AIR CONDITIONING SYSTEMS.
TEMPORARY BACK-UP AIR CONDITIONING
PROVIDE AND SET UP A RENTAL 20-TON PACKAGED AIR CONDITIONER WITH ANCILLARY DIESEL ENGINE GENERATOR, DUCTWORK, ELECTRICAL WIRING AND
CONTROLS FOR A FULLY OPERATION SYSTEM.
DEMOLITION
COORDINATE DEMOLITION AND NEW WORK TO SAME AREA AND/OR SYSTEM. ONLY WORK ON ONE UNIT AT A TIME - START TO FINISH. A REDUNDANT UNIT MUST
BE OPERATIONAL AT ALL TIMES.
FIELD INVESTIGATE EXISTING ACU CONTROLS, TO INCLUDE INTERFACE BETWEEN EXISTING UNIT AND T-STAT, WIRING CONNECTIONS, AND CONDITION PRIOR TO
DEMOLITION. NOTIFY FAA FACILITY MANAGEMENT BEFORE AFFECTING ACU CONTROL.
LOCK OUT/TAG OUT ELECTRICAL POWER. SELECTIVELY DEMOLISH EXISTING ACU SERVICE DISCONNECT, FEEDER WIRING, RIGID AND FLEX CONDUIT ABOVE GROUND. PLUG EXISTING UNDERGROUND CONDUITS AT GRADE WITH COTS MECHANICAL BLOCKING PLUGS. RE-USE EXISTING RIGID CONDUIT ABVOVE
GROUND. SALVAGE IN PLACE AND PROTECT EXISTING SERVICE POWER FEED FOR RE-USE.
SALVAGE AND PROTECT EXISTING LIGHTNING PROTECTION AND BONDING JUMPER FOR RE-USE.
RECOVER AND DISPOSE OF ACU REFRIGERANT PRIOR TO DEMOLITION OF UNIT AND REPORT RECOVERED QUANTITY TO FACILITY MANAGEMENT. SELECTIVELY DEMOLISH AND DISPOSE OF EXISTING ACU OFF SITE IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL LAWS AND REGULATIONS. INCLUDE PROVISIONS FOR
SEPARATE LIFTS TO RIG AND REMOVE BY CRANE, AND TRANSPORT OFF SITE.
SELECTIVELY DEMOLISH AND DISPOSE OF EXISTING EXTERNAL DUCTWORK BETWEEN EXTERIOR WALL AND ACU. PROTECT WALL OPENING FROM PESTS AND
INCLEMENT WEATHER AT ALL TIMES.
ACU
PROVIDE AND INSTALL NEW ACU PER SCHEDULE, AND IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS, PREVAILING BUILDING CODE, AND INDUSTRY
STANDARDS. SET ON PRESSURE TREATED TIMBER SUPPORTS PER DETAIL 4/ME001.
PROVIDE AND INSTALL NEW TYPE 'L' Cu CONDENSATE DRAIN, TRAP, AND CLEAN-OUTS PER DETAIL 7/ME001. ROUTE TO DRAIN AWAY FROM BUILDING.
PROVIDE AND INSTALL NEW ACU MANUFACTURER OEM COMPATIBLE T-STAT. CONNECT TO UNIT USING NEW 18-8 LOW VOLTAGE WIRING. RE-USE EXISTING RIGID 'CONTROLS' CONDUIT BUT PROVIDE AND INSTALL NEW UL LISTED, LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMC) WHIP FROM END OF EXISTING RIGID CONDUIT TO ACU. MANUALLY ADJUST REDUNDANT ACU SET-POINT TO BE 4 F HIGHER THAN PRIMARY (USER CAN CHANGE ON MONTHLY BASIS TO EVEN UNIT RUN TIMES).
COMMISSION NEW ACU IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDED START-UP AND CHECK-OUT PROCEDURES.
TEST AND BALANCE OF RESPECTIVE SYSTEM AIR FLOWS SHALL BE LIMITED TO MAIN SUPPLY AND RETURN TRUNKS ONLY: BALANCE AIR FLOWS TO VALUES
INDICATED OR PROPORTION THEREOF, AS APPROVED BY ENGINEER OF RECORD .
ELECTRICAL
PROVIDE AND INSTALL NEW LIGHTNING PROTECTION AND BONDING COMPONENTS TO EXTEND AND RE-ATTACH EXISTING GROUND LEADER TO NEW ACU.
PROVIDE AND INSTALL NEW SS NEMA 4X 'HEAVY DUTY,' 200A FUSED SERVICE DISCONNECT IN PLACE OF EXISTING. INCLUDE NEW 150A, CURRENT-LIMITING
FUSES, WITH TWO (2) ADDITIONAL SETS OF SPARES. SEE DIAGRAM 8/ME001.
PROVIDE AND INSTALL NEW AND ADDITIONAL SURGE PROTECTION DEVICE (SPD) FOR ACU SERVICE. WIRING CONNECTIONS SHALL BE MADE ON LOAD SIDE OF SERVICE DISCONNECT SWITCH. PROVIDE AND INSTALL NEW AND ADDITIONAL SS NEMA 4X 'HEAVY DUTY,' 60A FUSED DISCONNECT BETWEEN ACU SERVICE AND SPD. INCLUDE NEW 60A, CURRENT LIMITING FUSES, WITH TWO (2) ADDITIONAL SETS OF SPARES. SEE DIAGRAM 8/ME001.
PROVIDE AND INSTALL ALL NEW WIRING FROM ACU SERVICE DISCONNECT TO UNIT - CONDUCTORS SHALL NOT BE SPLICED. PROVIDE AND INSTALL NEW UL LISTED, LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMC) WHIP FROM END OF EXISTING RIGID CONDUIT TO ACU. SEE DIAGRAM 8/ME001.
DUCTWORK
PROVIDE AND INSTALL NEW EXTERIOR DUCTWORK PER SMACNA STANDARD. EXTERNALLY INSULATE, TO INCLUDE FOIL VAPOR BARRIER AND ALUMINUM JACKET.
PROTECT WALL OPENINGS AND NEW DUCTWORK DURING CONSTRUCTION FROM PESTS AND INCLEMENT WEATHER AT ALL TIMES. SEE DETAIL 5/ME001.
SCALE: 1/4" = 1'-0"
FLOOR PLAN - DEMOLITION
ME001
SCALE: 1/4" = 1'-0"
PART PLAN - NEW WORK
ME001
S 26-13/16 x 25-9/16
SENSIBLE OA
1. INCLUDES CONTRACTOR WARRANTED EXTENDED 5-YEAR WARRANTY, TO INCLUDE LABOR, ANCILLARY REPAIR MATERIALS, REFRIGERANT, AND OEM PARTS.
2. INCLUDES HINGED ACCESS PANELS AND POWERED CONVENIENCE OUTLET.
3. INCLUDES STAINLESS STEEL DRAIN PAN.
4. INCLUDES LOW AMBIENT CONTROLLER AND WINTER START.
TYPE
410-A TRANE THJ240A3S00**00E000B00000*10A 1 2 4
BASIS OF DESIGN NOTES
AIR CONDITIONING UNIT SCHEDULE
ACU-1 ASR BUILDING OUTDOOR PACKAGED HORIZONTAL 1.50 2 x 3.0 1,531
TOTAL
MBHRPMHP
MIN
IN WG
ESP
TYPESERVESMARK
SUPPLY FAN COOLING
228.0
MBH
EAT
DB, F WB, F
EAT LAT LAT
WB, FDB, F
165.4 80 67 60 58
FILTRATION
% EFF % EFFCFM
8,000
CFM
0 2"
PRE POST
- 3
ELECTRICAL
AMPS
FLA,
AMPS
MOP,
AMPS
MCA,
118 150
VOLT PHASE HZ
208 3 60
HEATING
EAT
DB, F
LAT
DB, F
TYPE
MERV-10
AUXILLIARY
ELECTRIC, KW
410-A TRANE THJ240A3S00**00E000B00000*10A 1 2 4ACU-2 ASR BUILDING OUTDOOR PACKAGED HORIZONTAL 1.50 2 x 3.0 1,531 228.0 165.4 80 67 60 588,000 0 2" - 3- 118 150208 3 60- - MERV-10-
STEPS OF
CAPACITY
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
EXISTING TO BE REMOVED
OR RELOCATED
AIR CONDITIONING UNIT
ACCESS DOOR / PANEL
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BAROMETRIC BACKDRAFT DAMPER
CONDUIT
COMMERCIAL OFF THE SHELF
ELECTRIC DUCT HEATER
EXHAUST AIR
FIRE ALARM CONTROL PANEL
FINISHED FLOOR
GROUND
NOT IN CONTRACT
OUTSIDE AIR
LIQUID-TIGHT FLEX METAL CONDUIT
MINI-SPLIT
PRESSURE DROP
RETURN AIR
SUPPLY AIR
SURGE PROTECTION DEVICE
UNIT HEATER
VOLUME DAMPER
EXISTING
ACU
AD / AP
AFF
AFG
BBD
C
COTS
EDH
EXH
FACP
FF
GND
NIC
OA
LFMC
MS
PD
RA
SA
SPD
UH
VD
X
FLEXIBLE DUCT CONNECTION
LEGEND AND ABBREVIATIONS
NECK SIZE
DESIGN CFM
DIFFUSER/GRILLE MARK
NEW DUCTWORK
EXISTING DUCTWORK TO REMAIN
A 500
OPEN VENT
COOLING COIL
DRAN PAN
2 H
NOTES:
1) H = ABSOLUTE INTERNAL STATIC
PRESSURE BETWEEN FAN AND
COIL + 1" MINIMUM
2) THREADED PLUGS SHALL BE
HAND TIGHT ONLY.
PIPE FULL SIZE
THREAD PLUG
(TYPICAL)
H
MINIMUM 1"
AIR GAP
ROUTE TO
OPEN DRAIN
OR SPLASH
PAD (TYPICAL)
UNION
NOT TO SCALE
DETAIL - CONDENSATE TRAP
ME001
H
2 H
THREADED PLUG
(TYPICAL)
DRAW THROUGH COIL
BLOW THROUGH COIL
IS
SU
ED
F
OR
ED
M
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
DO NOT SIGN
06/01/2024
SHANE HARVEY, PE
PLATFORM MANAGER, AJW-2E15B
APA
FLETCHER
AVL-E-18068688-ME001
DLS
DLS
ASHEVILLE ASR
ACU REPLACEMENT
DEMOLITION AND NEW WORK
fil e.
dw g
SN
OPS INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
Is su e R ea so n
INDUSTRIAL PARK
THIS DRAWING PRODUCED ON THE XXXXXXXXXX REGION AUTOCAD SYSTEM
DONALD SPRINKLE, PE
PROJECT ENGINEER, AJW-2E15B
18068688
NC
SIMPSON STRONG-TIE TP 4-1/8x7 - 20-GAUGE GALVANIZED TIE PLATE; AND EVERBILT 1/4x1
SS PAN-HEAD SCREWS (TYPICAL)
SIMPSON STRONG-TIE 2x3x3 - 12-GAUGE GALVANIZED STEEL ANGLE; AND EVERBILT 3/8x1-1/2
HOT DIPPED HEX HEX-HEAD LAG SCREWS (TYPICAL)
HILTI 3/8 - 16 TPI HDV CARBON SEEL
DROP-IN ANCHOR; AND EVERBILT 3/8x1 - 16
TPI ZINC PLATED HEX BOLT (TYPICAL)
GASKET
INTERNAL
DUCT LINER
SHEETMETAL
EDGE WRAP
EXTERNAL DUCT
INSULATION
SECURE VAPOR BARRIER TO
METAL DUCT WITH MASTIC AND
TAPE. LAP JOINT 2" MINIMUM.
NOTES:
1. ACTUAL DIMENSIONS OF LINED DUCT ARE LARGER BY LINER THICKNESSES.
SHEET METAL DUCT DIMENSIONS INDICATED ARE INSIDE FACE TO FACE
2. SECURE VAPOR BARRIER WITH MASTIC AND TAPE. LAP JOINT 2" MIN.
INTERIOR
DUCT
SCREW FASTENERS 6" O.C. 2
PER SIDE MINIMUM
NOT TO SCALE
DETAIL - DUCTWORK TRANSISTION
ME001
NOT TO SCALE
PARTIAL ONE-LINE DIAGRAM - ELECTRICAL INSTALLATION
ME001
M
E0
2 EACH, YELLAWOOD 6x6 PRESSURE
TREATED TIMBERS CUT TO LENGTH
TO FIT UNIT SUPPORT FRAME
R x
46-1/2
NOT TO SCALE
ELEVATION - SUPPORT FRAME
ME001
NOT TO SCALE
ELEVATION - SUPPORT FRAME
ME001
NOT TO SCALE
PICTURE - EXISTING CONDITION
ME001
EXISTING PANEL 'EPA'
208/120V, 3P, 4W, ESSENTIAL
EXISTING 3-3/0 AWG, #4
GND; 2-1/2" RGS CONDUIT
NEW 200A, SS NEMA 4X 'HEAVY
DUTY' FUSED 240VAC RATED,
3-PHASE 3-POLE, DOUBLE LUG KIT;
SCHNEIDER ELECTRIC MODEL
VH364SSGL, OR APPROVED
EQUIVALENT.
FUSES: FERRAZ MODEL TR, 150A,
208V, 200KA INTERRUPTING
CAPACITY, OR APPROVED
EQUIVALENT. 9 EACH.
(TYPICAL 2)
NEW 3-3/0 AWG, #4 GND;
NEW 2-1/2" RGS CONDUIT
ACU-1
DS
ACU-1
NEW 3-3/0 AWG, #4
GND; 2-1/2" LFMC
EXISTING
BREAKER 2/4/6
150A / 3P
SPD-1
DS
SPD-1
NEW 100A, SS NEMA 4X 'HEAVY DUTY' FUSED DISCONNECT SWITCH,
240VAC RATED, 3-PHASE 3-POLE, DOUBLE LUG KIT, SCHNEIDER
ELECTRIC MODEL VH364SSGL, OR APPROVED EQUIVALENT.
FUSES: FERRAZ MODEL TR, 60A, 208V, 200KA INTERRUPTING
CAPACITY, OR APPROVED EQUIVALENT; 9 EACH.
(TYPICAL 2)
NEW SPD, TYPE-2, SS NEMA 4X; RAYVOSS MODEL
#120-3Y-M3-3-06-A-SS, OR APPROVED EQUIVALENT
(TYPICAL 2)
NEW 3-#8 AWG,
#10 GND; 1" LFMC
NEW 3-#8 AWG,
#10 GND; 1" RGS
ACU-2
DS
ACU-2
SPD-2
DS
SPD-2
NOTES:
1. TYPICAL CIRCUITRY FOR ACU-2
2. WALL-MOUNTED DISCONNECTS AND SPD. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
3. BOND AND GROUND RACEWAY PER FIGURE 7 OF FAA STD-019F-CHG 3
4. NEW WIRING SHALL BE THHW.
NEW 3" HEAVY DUTY FLEX
DUCT CONNECTION
20 GUAGE ALUMINUM SHROUD
OVER TOP AND SIDES OF
DUCTWORK. FRAME AND
SUPPORT WITH GALVANIZED
STEEL ANGLE SIZED AND
FASTENED TO SHAPE. LAP JOINTS
MINIMUM 2", AND IN DIRECTION TO
SHED WATER.
24 GAUGE MINIMUM GALVANIZED STEEL
SHEETMETAL DUCTWORK CONSTRUCTED
PER SMACNA STANDARD.
EXTERNALLY INSULATE DUCTWORK WITH
1.5" POLYISO RIGID INSULATION CLASS 'A'
FOIL FACED. PIN TO DUCT FACE. SEAL
JOINTS ON TOP AND SIDES OF DUCT WITH
ALUMINUM TAPE. CAULK JOINTS AT ACU
AND WALL WITH POLYURETHANE MASTIC.
DO NOT SEAL JOINTS ON BOTTOM OF
DUCT - MUST SHED WATER.
FRAME WALL OPENING
WITH 3x3 GALVANIZED STEEL ANGLE FLASHINGFASTEN SHROUD WITH 2" WIDE x
20 GUAGE ALUMINUM HOLD
DOWN STRAPS ACROSS BOTTOM
OF DUCTWORK, ATTACHED WITH
3/4" #10 SS SHEET METAL
SCREWS. 3 MINIMUM.
32 5
4 6
SET EMERGENCY A/C IN REAR. FABRICATE TEMPORARY
PLYWOOD AND DIMENSIONAL LUMBER DOOR OPENING TO
ROUTE TEMPORARY DUCTWORK THROUGH BACK DOOR.
X 2,667 36x16 (TYPICAL 3) 11 12
14 15
EXISTING
BREAKER 7/9/11
150A 3P
NEW 3-#8 AWG,
#10 GND; 1" RGS
AP
AP
BDD
BBD
UH
(TYPICAL)
(TYPICAL)
INTERIOR
DUCT
NEW 3-#8 AWG,
#10 GND; 1" LFMC
END VIEW SIDE VIEW
UH
UH
UH
ACU-1
8 (TYPICAL)
ACU-2
(TYPICAL)
IN COMPLIANCE WITH
STATE OF NORTH
CAROLINA GENERAL
STATUTES, CHAPTER 87 -
CONTRACTORS, including changes through SL 2023-151: any person who performs work which is subject to the provisions of this chapter on land titled to and operated by the Federal Government shall be required to be licensed pursuant to their respective trade at the time of beginning work.
ALL ENGINEERING WORK
IS THE SERVICES OF
FULL-TIME,
NON-TEMPORARY
EMPLOYEES OF THE
GOVERNMENT OF THE
UNITED STATES OF
AMERICA.
AutoCAD SHX Text %%uENGINE GENERATOR%%U
AutoCAD SHX Text %%uROOM%%U
AutoCAD SHX Text %%uEQUIPMENT ROOM%%U
AutoCAD SHX Text M
AutoCAD SHX Text M
| Sheets and Views |
| Layout1 |
File details come from the government source that posted it. Updated .