LiebertDeluxeSystem.pdf
PDF 8 MB Posted
- Attached to
- AHU 25 REPLACEMENT & AHU 32 INSTALL at the Atlanta Air Route Traffic Control Center (ARTCC), Hampton, GA
- Solicitation number
- 697DCK-22-R-00357
About this file
This solicitation is seeking proposals for an AHU 25 replacement and AHU 32 installation project at the Atlanta Air Route Traffic Control Center in Hampton, Georgia. The Federal Aviation Administration Enroute Construction Group, Boston Office is requesting all labor, equipment, and materials to complete the work. The North American Industry Classification System code for the work is 238220, with an estimated value between $250,000 and $500,000. Payment and performance bonds are required. A site visit is scheduled for May 19, 2022 and interested contractors must register attendees by May 17. Proposals are due electronically in PDF format by an unspecified date. The wage determination rates are included in the attachments.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 697DCK22R00357amendment4.pdf | ||
| 697DCK-22-R-00357amendment3.pdf | ||
| amendment2.pdf | ||
| 697DCK-22-R-00357 amendment00001.pdf | ||
| ztl-1705850-FINAL Signed.pdf | ||
| ZTL-1705850and1801418-FINAL-SPECIFICATIONS.pdf | ||
| ahu25bid sheet.pdf | ||
| WageRate2022.pdf | ||
| RFO697DCK-22-R-00357.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABLE OF CONTENTS
PRODUCT MODEL INFORMATION
EQUIPMENT INSPECTION
1.0 INTRODUCTION
1.1 System Descriptions
1.1.1 Chilled Water Systems
2.0 INSTALLATION
2.1 Room Preparation
2.2 Location Considerations
2.3 Unit Dimensions
2.4 Piping
2.4.1 Drain Line
2.4.2 Piping Considerations for Raised-Floor Applications
2.5 Electrical Connections
2.6 Air Distribution Considerations
2.6.1 Raised-Floor Air Flow Distribution Considerations
2.6.2 Upflow Systems Installation Considerations
2.6.3 Ducted Application Installation
2.6.4 Plenum Installation
2.6.5 Filter Box Installation (Upflow Rear Return)
3.0 CHILLED WATER MODELS
3.1 Piping Considerations
FIGURES
Figure 1 Downflow chilled water (FH models except FH599C/FH600C and FH739C/FH740C) cabinet and floor planning dimensional data
Figure 2 Downflow chilled water models FH599C/FH600C and FH739C/FH740C cabinet and floor planning dimensional data
Figure 3 Upflow chilled water (UH models) cabinet and floor planning dimensional data Figure 4 Cabinet and floor planning dimensional data (UH 599C, 600C, 739C and 740C chilled water models) Figure 5 Blower duct and deck dimensional data (UH 599C, 600C, 739C and 740C chilled water models) Figure 6 Electrical connection details Figure 7 Electrical field connections for downflow chilled water models (except FH599C/FH600C and FH739C/FH740C) Figure 8 Electrical field connections for downflow chilled water models FH599C/FH600C and
FH739C/FH740C
Figure 9 High voltage electrical field connections for upflow (UH) chilled water models except
UH599C, UH600C, UH739C and UH740C Figure 10 High voltage electrical field connections for upflow (UH) chilled water models for UH599C, UH600C, UH739C and UH740C (120" frame) Figure 11 Low voltage electrical field connections for upflow (UH) chilled water models except
UH599C, UH600C, UH739C and UH740C Figure 12 Low voltage electrical field connections for upflow (UH) UH599C, UH600C, UH739C and
UH740C (120" frame) chilled water models Figure 13 Ducting configurations Figure 14 Plenum dimensional data (FH/UH-147C�529C) Figure 15 Plenum dimensional data (FH/UH-599C�740C) Figure 16 Chilled water upflow general arrangement Figure 17 Chilled water downflow general arrangement Figure 18 Downflow chilled water (FH) piping connections Figure 19 Upflow chilled water (UH) piping connections except 599C, 600C, 739C and 740C Figure 20 Downflow chilled water (599C, 600C, 739C and 740C) piping connections Figure 21 Upflow chilled water (599C, 600C, 739C and 740C) piping connections
TABLES
Table 1 Model number designation Table 2 Unit weights Table 3 Downflow chilled water (except FH599C/FH600C and FH739C/FH740C) floor cutout dimensions Table 4 Downflow chilled water models FH599C/FH600C and FH739C/FH740C floor cutout dimensions Table 5 Upflow chilled water (UH models) cabinet and floor planning dimensional data Table 6 Blower duct and deck dimensional data (UH 599C, 600C, 739C and 740C chilled water models . 9 Table 7 Recommended free area ft2 (m2) for grilles or perforated panels at output velocities of 550 and 600 fpm (2.8 and 3.1 m/s) Table 8 Plenum dimensional data in. (mm) for FH/UH-147C�529C Table 9 Plenum dimensional data in. (mm) for FH/UH-599C�740C Table 10 Downflow chilled water cooled (FH) piping connection sizes, inches Table 11 Upflow chilled water cooled (UH) piping connection sizes, inches Table 12 Downflow chilled water cooled (FH, 120" frame) piping connection sizes, inches
PRODUCT MODEL INFORMATION
EQUIPMENT INSPECTION
Upon arrival of the unit, inspect all items for either visible or concealed damage. Damage should be immedi-ately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representa-tive.
Table 1 Model number designation
DH FH 376 C � A A E I
FH = Downflow
CW
Nominal Capacity in Thousand
BTU/H
C = Chilled Water
- = Std. CW A = 460/3/60 A = Advanced Micro-processor
0 = No Reheat
0 = No Humidifier
B = 575/3/60
UH = Upflow
CW
V
VSD
(Variabl e Speed Drive)
C = 208/3/60 G = Advanced Graphics Micro-processor
E = Electric Reheat
I = Infrared Humidifier
D = 230/3/60
F = 380/3/50 H
Hot Water Reheat
G
Steam Grid HumidifierG = 415/3/50
H = 230/3/50 T = Steam Reheat
S = Steam Generatin g Humidifier
J = 200/3/50
M
380/415/ 3/50
WARNING
Installation and service of this equipment should be done only by qualified personnel who have been specially trained in the installation of air conditioning equipment. Improper installation could result in property damage, injury or loss of life.
WARNING
Hazardous voltage! Always disconnect power before servicing.
CAUTION
Evaporator unit requires drain connections and may also require water supply. Do not locate directly above any equipment that could sustain water damage.
Table 2 Unit weights
Model Weight lbs (kg)
Chilled Water Models FH/UH, 60 (50) Hz
147C 770 (350)
200C 805 (365)
248C 855 (388)
302C 1090 (495)
376C 1155 (524)
422C 1320 (599)
529C 1420 (644)
600C (599C) 1785 (810)
740C (739C) 1925 (873)
FH = Downflow C = Chilled - = Std. CW A = 460/3/60 A = Advanced- = Std. CW A = 460/3/60 A = Advanced
H
S = Steam
422C
1.0 INTRODUCTION
1.1 System Descriptions
Deluxe System/3 12 to 60 ton Chilled Water environmental control system is available in several con-figurations. Each configuration can operate with either Advanced Microprocessor Controls (AM), or Advanced Microprocessor Controls with Graphics (AG). A brief description of each, including opera-tional differences, can be found below. Check model numbers to see what is supplied with your unit.
1.1.1 Chilled Water Systems
Cooling
These systems utilize a central chiller and control cooling by modulating a control valve in the chilled water line.
Heating
Three stages of electric reheat standard; steam/hot water optional
Humidification
Infrared standard; steam grid and steam generating optional
Dehumidification
Chilled water valve opens proportionally in response to room needs
2.0 INSTALLATION
2.1 Room Preparation
The room should be well-insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling can be a polyethylene film type. Use a rubber-base or plastic-base paint on concrete walls and floors. Doors should not be undercut or have grilles in them.
Outside, or fresh, air should be kept to an absolute minimum. Outside air adds to the heating, cooling, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept below 5% of the total air circulated in the room.
2.2 Location Considerations
For a downflow unit, the unit can sit on an accessible, elevated flooring system. It may be necessary to furnish additional pedestal support below the unit to ensure maximum structural support. A separate floor stand for the unit may be used as support, independent of the elevated floor and installed prior to the flooring system.
For downflow and upflow units, provide approximately 34" (864 mm) service clearance on the left, right and in front of the unit whenever possible. The minimum space required for service is 18" (45.7
cm) on the left end, 18" (45.7 cm) on the right end, and 24" (61 cm) in front of the unit. This space is necessary to permit routine maintenance, such as replacing filters, adjusting the fan speed and clean-ing the humidifier. On downflow chilled water units and upflow 599C, 600C, 735C and 740C models, left- and right-end minimum clearances are 0" (0 cm), with the exception of rear return.
Avoid locating units in an alcove or at the extreme end of a room that has a high aspect ratio (long narrow room). Also avoid locating units too close together. This tends to reduce the effectiveness of the air distribution as compared to units located 30-40 feet (9-12m) apart.
NOTE
If high efficiency 6" filters are used, 25" (63.5 cm) clearance on the right end is required for removal and replacement of filters.
2.3 Unit Dimensions
Figure 1 Downflow chilled water (FH models except FH599C/FH600C and FH739C/FH740C) cabinet and floor planning dimensional data
Table 3 Downflow chilled water (except FH599C/FH600C and FH739C/FH740C) floor cutout dimensions
Chilled Water Model
Dimensional Data inches (mm)
A B C D E F G H J K
FH147C 50 (1270) 46 (1168) 35 (889) 32 (813) 48 (1219) 33 (838) 10-1/2 (267) 35-1/2 (902) 35-5/8 (905) 31 (787)
FH200C 50 (1270) 46 (1168) 35 (889) 32 (813) 48 (1219) 33 (838) 10-1/2 (267) 35-1/2 (902) 35-5/8 (905) 31 (787)
FH248C 50 (1270) 46 (1168) 35 (889) 32 (813) 48 (1219) 33 (838) 10-1/2 (267) 35-1/2 (902) 35-5/8 (905) 31 (787)
FH302C 74 (1880) 70 (1778) 35 (889) 32 (813) 72 (1829) 33 (838) 10-1/2 (267) 59-1/2 (1511) 35-5/8 (905) 31 (787)
FH376C 74 (1880) 70 (1778) 35 (889) 32 (813) 72 (1829) 33 (838) 10-1/2 (267) 59-1/2 (1511) 35-5/8 (905) 31 (787)
FH422C 99 (2515) 95 (2413) 35 (889) 32 (813) 97 (2464) 33 (838) 16-1/4 (413) 78-3/4 (2000) 35-5/8 (905) 31 (787)
FH529C 99 (2515) 95 (2413) 35 (889) 32 (813) 97 (2464) 33 (838) 16-1/4 (413) 78-3/4 (2000) 35-5/8 (905) 31 (787)
FH422C 99 (2515) 95 (2413) 35 (889) 32 (813) 97 (2464) 33 (838) 16-1/4 (413) 78-3/4 (2000) 35-5/8 (905) 31 (787)
Figure 2 Downflow chilled water models FH599C/FH600C and FH739C/FH740C cabinet and floor planning dimensional data
Table 4 Downflow chilled water models FH599C/FH600C and FH739C/FH740C floor cutout dimensions
Chilled Water Model
Dimensional Data inches (mm)
A B C D E F G H I
FH599C, 600C 122
(3099)
(2997)
(889)
(787)
(3048)
(838)
35-5/8 (905)
(762)
(864)
FH739C, 740C
(3099)
(2997)
(889)
(787)
(3048)
(838) 35-5/8 (905)
(762)
(864)
Figure 3 Upflow chilled water (UH models) cabinet and floor planning dimensional data
Table 5 Upflow chilled water (UH models) cabinet and floor planning dimensional data
Chilled Water Model
# of Blowers
Dimensional Data inches (mm)
A B C D E F G H J K L M
UH147C 1 50
(1270)
(1219)
(1168)
(1118)
(76)
(127)
(457)
15 7/8 (403)
18 5/8 (473)
2 3/16 (55)
17 3/8 (454)
UH200C 1 50
(1270)
(1219)
(1168)
(1118)
(76)
(127)
(457)
15 7/8 (403)
18 5/8 (473)
2 3/16 (55)
17 3/8 (454)
UH248C 1 50
(1270)
(1219)
(1168)
(1118)
(76)
(127)
(457)
15 7/8 (403)
18 5/8 (473)
2 3/16 (55)
17 3/8 (454)
UH302C 2 74
(1880)
(1829)
(1778)
(1727)
(76)
(102)
(508)
15 7/8 (403)
14 5/8 (371)
2 3/16 (55)
20 3/8 (517)
11-1/4 (286)
UH376C 2 74
(1880)
(1829)
(1778)
(1727)
(76)
(102)
(508)
15 7/8 (403)
14 5/8 (371)
2 3/16 (55)
20 3/8 (517)
11-1/4 (286)
UH422C 2 99
(2515)
(2464)
(2413)
(1727)
6 1/2 (165)
(127)
(457)
15 7/8 (403)
18 5/8 (473)
3 1/4 (82)
20 5/8 (524)
12-5/8 (321)
UH529C 2 99
(2515)
(2464)
(2413)
(1727)
6 1/2 (165)
(127)
(457)
15 7/8 (403)
18 5/8 (473)
3 1/4 (82)
20 5/8 (524)
12-5/8 (321)
* Bottom return not available on UH600 and 740C
Figure 4 Cabinet and floor planning dimensional data (UH 599C, 600C, 739C and 740C chilled water models)
Figure 5 Blower duct and deck dimensional data (UH 599C, 600C, 739C and 740C chilled water models)
Table 6 Blower duct and deck dimensional data (UH 599C, 600C, 739C and 740C chilled water models
Model Blower Supply Motor Hp
Dimensional Data inches (mm)
A B C D E F
UH599C
UH739C
UH600C
UH740C
15x15 Top Front 10-15 27-1/2
(699) 3-1/2 (89)
18-11/16 (475)
16-3/16 (411)
(254)
4-1/2 (114)
Top Rear 10-15 27-1/2 (699)
12-5/16 (313)
18-11/16 (475)
16-3/16 (411)
(254)
4-1/2 (114)
15x11 Top Front
10-15 30 (762)
3-1/2 (89)
14-3/4 (375)
16-3/16 (411)
(254)
4-1/2 (114)20
Top Rear 10-20 30 (762)
12-5/16 (313)
14-3/4 (375)
16-3/16 (411)
(254)
4-1/2 (114)
2.4 Piping
All fluid and refrigeration connections to the unit, with the exceptions of the condensate drain and live steam, are sweat copper. Factory-installed piping brackets must not be removed. Field-installed piping must be installed in accordance with local codes and must be properly assembled, supported, isolated and insulated. Avoid piping runs through noise-sensitive areas, such as office walls and con-ference rooms.
Refer to specific text and detailed diagrams in this manual for other unit-specific piping require-ments.
2.4.1 Drain Line
A 3/4" NPT (1-1/4" NPT on 599C, 600C, 739C and 740C) is provided for the evaporator coil condensate drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will not be exposed to freezing temperatures. The drain should be at least the full size of the drain connec-tion and pitched a minimum of 1/8" per ft. (11 mm per meter).
2.4.2 Piping Considerations for Raised-Floor Applications
All piping below the elevated floor must be located so that it offers the least resistance to air flow.
Careful planning of the piping layout under the raised floor is required to prevent the air flow from being blocked. When installing piping on the subfloor, it is recommended that the pipes be mounted in a horizontal plane rather than stacked one above the other. Whenever possible, the pipes should be run parallel to the air flow.
NOTE
This line may contain boiling water. Use copper or other suitable material for the drain line.
The unit is shipped from the factory with an internally-mounted trap. No external trap is required. The drain line must comply with all applicable codes.
The unit is shipped from the factory with a condensate pump installed. The condensate pump discharge (drain) line must comply with all applicable codes.
The unit is shipped from the factory with the condensate pump option, unmounted in the unit, which must be installed in the field. The unit has an internally mounted trap. The drain line from the unit to the condensate pump does not require a trap. The discharge (drain) line from the pump must comply with all applicable codes.
2.5 Electrical Connections
Three-phase electrical service is required for all models in either 208, 230, 460 or 575 V, 60 Hz; or 200, 230 or 400 V, 50 Hz. Electrical service shall conform to national and local electrical codes.
Install a manual electrical disconnect switch within 5 feet (1.6 m) of the unit in accordance with codes. A factory-supplied disconnect switch may be factory-mounted within the unit and accessible from the exterior.
Figure 6 Electrical connection details
Remote Heat Rejection Connections
Diagram is for direct drive air-cooled condensers (for air-cooled units) and direct drive drycoolers (for glycol/GLYCOOL units).
Control Board
Wire Legend
2-wire connection for heat rejection interlock (Note 5)
2-wire connection for common alarm
4-pin plug connections for optional remote temperature and humidity sensor
Factory-supplied line voltage wiring
Field-supplied line voltage wiring
Factory-supplied 24V, NEC Class 2 wiring
Field-supplied 24V NEC Class 2 wiring
Field-supplied earth grounding wire
2-wire connection optional SiteScan
2-wire connection for each Special Alarm (Note 4)
2-wire connection for remote unit shutdown (Note 3)
Earth ground to ground lug bolt or optional ground bar
3-phase line voltage supply to line voltage connection block or optional main disconnect switch (Note 2)
To line voltage components on Liebert room unit electric panel
To line voltage components in Liebert room unit
OR
37 38 24 50 51 55 56 77 78
L1
L2
L3
P16
22 ga. 4-wire cable
75 76 70 71 6-inch pigtails at junction box
Terminals 75 & 76 are connected to common alarm relay (K3) NO contact (max 1A at 24V)
Wires 70 & 71 are connected to compressor side switches and Econ-O-Coil relay (R5).
R5 is provided on FE/UE units only.
NOTES
1. Refer to specification sheet for Full Load Amps and Wire Sizing Amps.
2. Field-supplied room unit main disconnect switch in accordance with local codes ordered as optional equipment and factory-installed in Liebert room unit.
3. For remote unit shutdown, replace jumper between 37 & 38 at terminal strip with Normally Closed switch having a minimum 75VA rating.
4. Special alarm connection made by adding Normally Open contacts between Terminals 24 & 50, 24 & 51, 24 & 55 and 24 & 56. Only one alarm (between 24 & 50) is available on standard microprocessor.
5. Heat rejection interlock is not supplied on chilled water models.
6. Field-supplied disconnect switch mounted within sight of condenser/drycooler and in accordance with local codes or ordered as optional equipment and factory-installed in Liebert condenser/drycooler. CDF-065, CDF-083, CDF-086, CDF-097 and CDF-104L are single-phase fan speed condensers. All other condensers and all drycooler and pump packages require a 3-phase line voltage supply.
7. Glycol pump package supplied with drycoolers only. Pump 2 is supplied only when dual pump package is ordered.
8. Lee-Temp tanks and assembly supplied on air-cooled condensers with Lee-Temp control systems only.
ROOM UNIT CONNECTIONS
3-wire line voltage connection plus ground for glycol pump. An additional 3-wire line voltage needed for dual pump packages (Note 7).
2-wire connection for heat rejection interlock
Earth Ground
3- or single-phase line voltage supply to optional main disconnect switch (Note 6)
2-wire connection plus ground for Lee-Temp heater pads (Note 8)
1 fan 2 fan
See Note 8
3 fan
In te rc o n n e ct e d
Figure 7 Electrical field connections for downflow chilled water models (except FH599C/FH600C and
FH739C/FH740C)
Figure 8 Electrical field connections for downflow chilled water models FH599C/FH600C and FH739C/
FH740C
Figure 9 High voltage electrical field connections for upflow (UH) chilled water models except UH599C, UH600C, UH739C and UH740C
Refer to specification sheet for full load amp and wire size amp ratings.
Figure 10 High voltage electrical field connections for upflow (UH) chilled water models for UH599C, UH600C, UH739C and UH740C (120" frame)
Refer to specification sheet for full load amp and wire size amp ratings.
Figure 11 Low voltage electrical field connections for upflow (UH) chilled water models except UH599C, UH600C, UH739C and UH740C
Refer to specification sheet for full load amp and wire size amp ratings.
Figure 12 Low voltage electrical field connections for upflow (UH) UH599C, UH600C, UH739C and UH740C (120" frame) chilled water models
2.6 Air Distribution Considerations
2.6.1 Raised-Floor Air Flow Distribution Considerations
To ensure proper air distribution, any unusual restrictions within the air circuit must be avoided. For under-floor air distribution, observe the following guidelines:
Select the air supply grilles and perforated panels for the raised floor to ensure minimum loss of pres-sure in the circuit. Air volume dampers on grilles, which extend several inches below the surface of the raised floor, are usually detrimental to airflow. Consideration of the height of the damper on the grille in conjunction with the floor height will determine whether this type of grille may be used.
The grilles used in raised floors vary in size, the largest being approximately 18" x 6" (457 x 152 mm).
A larger grille size would be detrimental to the structural capacity of the raised floor panel. An 18" x 6" (457 x 152 mm) heavy-duty pencil proof type grille typically has 56 square inches (0.036 m2) of free area. Perforated panels are available from various manufacturers of raised floors. These panels are usually 2' x 2' (610 x 610 mm) square and have a nominal free area of approximately 108 to 144 square inches (0.07 to 0.09 m2). Use caution in selecting perforated panels as some manufacturers have only 36 to 40 square inches (0.023 to 0.026 m2) of free area, requiring four times as many panels.
Avoid floor elevations below 7-1/2" (190.5 mm), loosely installed flooring systems, and below-floor obstruc-tions such as: electrical wiring chases, unusually long computer system cables, or piping clusters.
All piping below the elevated floor must be located so that it offers the least resistance to air flow.
Careful planning of the piping layout under the raised floor is required to prevent the air flow from being blocked. When installing piping on the subfloor, it is recommended that the pipes be mounted in a horizontal plane rather than stacked one above the other. Whenever possible, the pipes should be run parallel to the air flow.
Always check specifications of the floor supplier before specifying the total number of perforated pan-els and grilles required to handle the air flow. The proper specifications for grilles and perforated pan-els should indicate the total free area required for air delivery rather than the number of panels and grilles. (See Table 7 below for recommended free area required for each model.) This table indicates the recommended free area based on having the supply air grilles and perforated panels sized to han-dle approximately 75% of the total cubic feet per minute (CFM) of the units at a velocity of 550 to 600 ft./min. (2.8 - 3.1 m/s). The remaining 25 percent of the air flow in the raised floor passes through cable cutouts, cracks between the panels and other leakage areas.
Table 7 Recommended free area ft2 (m2) for grilles or perforated panels at output velocities of 550 and 600 fpm (2.8 and 3.1 m/s)
Model FH 60 (50) Hz
550 fpm (2.8 m/s)
600 fpm (3.1 m/s)
Chilled Water Units
147C 7.2 (0.65) 6.6 (0.60)
200C 8.2 (0.74) 7.6 (0.70)
248C 8.0 (0.73) 7.4 (0.67)
302C 12.7 (1.15) 11.6 (1.05)
376C 12.4 (1.13) 11.4 (1.03)
422C 17.0 (1.54) 15.6 (1.42)
529C 16.9 (1.53) 15.5 (1.41)
600C (599C) 23.3 (2.16) 21.4 (1.95)
740C (739C) 22.5 (2.09) 20.6 (1.89)
422C 17.0 (1.54) 15.6 (1.42)
2.6.2 Upflow Systems Installation Considerations
Upflow models can be configured in several different ways with front return, rear return, or bottom return and top front supply or top rear supply. For in-room applications with no ductwork, and optional plenum with grill, proper clearance must be maintained on the return air side of the unit.
For a front return, this means several feet in front of the unit. For a bottom return, at least 6-8 inches of unrestricted under-floor height is needed.
2.6.3 Ducted Application Installation
Duct flanges are supplied on the blower outlets. Follow the SMACNA-Duct Construction Standard for single-, dual-, or triple-blower systems. Do not run ductwork off the perimeter flange on the top of the unit. This flange is for positioning and attaching the optional air discharge plenum with grill. Attach-ing a duct to this flange may reduce airflow to inadequate levels.
Figure 13 Ducting configurations
2.6.4 Plenum Installation
When installing the plenum to the top of system, secure the plenum to the unit flange using sheet metal screws.
2.6.5 Filter Box Installation (Upflow Rear Return)
When installing the filter box to the back of the unit, secure the box to the unit using self tapping sheet metal screws. Seal around all edges with a silicone sealant to prevent air leakage.
NOTE
Air distribution plenums are available as Top Return/Downflow, Top Discharge/Upflow, and Front Discharge (with or without grilles)/Upflow. These plenums are shipped separate and unassembled. Refer to assembly manual included with plenums.
Straight section of duct off unit to be 1.5 to 2.5 times the longest blower dimension
Typical ducting shown; may run to either side
* Follow standard practices on all duct work
Figure 14 Plenum dimensional data (FH/UH-147C�529C)
Table 8 Plenum dimensional data in. (mm) for FH/UH-147C�529C
Model A B C D E F Grille Free Area
Sq Ft (sq m)
FH/UH-147C, 200C, 248C 50 (1270) 34 (864) 46 (1168) 32 (813) 44 (1118) 3 (76) 4.29 (.40)
FH/UH-302C, 376C 74 (1880) 34 (864) 70 (1778) 32 (813) 60 (1524) 7 (178) 5.85 (.54)
FH/UH-422C, 529C 99 (2515) 34 (864) 95 (2413) 32 (813) 70 (1778) 14-1/2 (368) 6.83 (.63)
Plenum Height In. (mm)
H J
20 (508) 1 (25)
22-3/4 (578) 2-3/8 (60)
34-3/4 (883) 2-3/8 (60)
FH/UH-422C, 529CFH/UH-422C, 529CFH/UH-422C, 529C
Figure 15 Plenum dimensional data (FH/UH-599C�740C)
Table 9 Plenum dimensional data in. (mm) for FH/UH-599C�740C
Model A B C D E F G H J
Grille Free Area
Sq Ft (sq m)
FH/UH-599C, 600C
FH/UH-739C, 740C
(3099)
(864)
(2997)
(813)
(1118)
3-1/2 (89)
(102)
(178)
(406)
10.14 (.94)
Plenum Height in (mm)
K L
508)
(25)
22-3/4 (578)
2-3/8 (60)
34-3/4 (883)
2-3/8 (60)
3.0 CHILLED WATER MODELS
3.1 Piping Considerations
Manual shut-off valves should be installed at the supply and return lines to each unit. This provides for routine service and emergency isolation of the unit.
The lowest water temperature to be supplied by the chiller will determine whether insulation is needed to prevent condensation on the supply and return lines. To prevent water damage to flooring and subflooring, install a water detection system, such as a Liqui-tect or floor drains with wet traps.
Figure 16 Chilled water upflow general arrangement
Chilled Water SupplyChilled
Water Return
Shutoff Valve *
Flow Switch (optional)
Valve Actuator
Bleed Valve
Chilled Water Coil
Air Flow
Chilled Water Coil
Valve ActuatorChilled
Water Supply
Chilled Water Return
Shutoff Valves *
Hose Bibs *
Hose Bibs *
3-W ay Chille d
Water V alve
Ball Valve (optional)
Air Flow
3-WAY VALVE
2-WAY VALVE
Bleed Valve
FACTORY PIPING
FIELD PIPING
2-Way Chilled Water Valve
Ball Valve (optional)
* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance
A
AB
B
SL-18200-06-01
Figure 17 Chilled water downflow general arrangement
Chilled Water Supply
Chilled Water Return
Shutoff Valve *
Flow Switch (optional)
Valve Actuator
Bleed Valve
Chilled Water Coil
Air Flow
Chilled Water Coil
Valve Actuator
Chilled Water Supply
Chilled Water Return
Shutoff Valves *
Hose Bibs *
Hose Bibs *
Ball Valve (optional)
Air Flow
3-WAY VALVE
2-WAY VALVE
Bleed Valve
FACTORY PIPING
FIELD PIPING
2-Way Chilled Water Valve
Ball Valve (optional)
* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance
A
AB
B 3-Way Chilled Water Valve
SL-18200-06-02
Figure 18 Downflow chilled water (FH) piping connections
Table 10Downflow chilled water cooled (FH) piping connection sizes, inches
Chilled Water
Models A
(OD Cu) B
(OD Cu) C
(NPT Male) D
(OD Cu) E
(NPT Male) F
(OD Cu)
FH147C 1-1/8 1-1/8 1/2 5/8 1/2 5/8
FH200C 1-3/8 1-3/8 1/2 5/8 1/2 5/8
FH248C 1-5/8 1-5/8 1/2 5/8 1/2 5/8
FH302C 1-5/8 1-5/8 1/2 7/8 1/2 7/8
FH376C 2-1/8 2-1/8 3/4 7/8 3/4 7/8
FH422C 2-1/8 2-1/8 3/4 7/8 3/4 7/8
FH529C 2-1/8 2-1/8 3/4 7/8 3/4 7/8
FH422C 2-1/8 2-1/8 3/4
Figure 19 Upflow chilled water (UH) piping connections except 599C, 600C, 739C and 740C
Table 11 Upflow chilled water cooled (UH) piping connection sizes, inches
Chilled Water Models 50 & 60 Hz
A (OD Cu)
B (OD Cu)
C (NPT Male)
D (OD Cu)
E (NPT Male)
F (OD Cu)
UH147C 1-1/8 1-1/8 1/2 5/8 1/2 5/8
UH200C 1-3/8 1-3/8 1/2 5/8 1/2 5/8
UH248C 1-5/8 1-5/8 1/2 5/8 1/2 5/8
UH302C 2-5/8 2-5/8 3/4 7/8 1/2 7/8
UH376C 2-1/8 2-1/8 3/4 7/8 3/4 7/8
UH422C 2-1/8 2-1/8 3/4 7/8 3/4 7/8
UH529C 2-1/8 2-1/8 3/4 7/8 3/4 7/8
Figure 20 Downflow chilled water (599C, 600C, 739C and 740C) piping connections
Table 12 Downflow chilled water cooled (FH, 120" frame) piping connection sizes, inches
120" Frame Chilled Water A
(OD CU)
B
(OD CU)
C
(NPT Male) D
(OD CU)
E
(NPT Male) F
(OD CU)
FH599C, 600C 2-1/8 2-1/8 3/4 7/8 3/4 7/8
FH739C, 740C 2-5/8 2-5/8 3/4 7/8 3/4 7/8
Figure 21 Upflow chilled water (599C, 600C, 739C and 740C) piping connections