DUCTWORK NOTES
1. ALL SUPPLY DUCTS LARGER THAN 10" ON EITHER SIDE WITH RECTANGULAR ELBOWS SHALL
HAVE SINGLE THICKNESS TURNING VANES.
2. TRANSITION RECTANGULAR DUCTWORK ON THE BOTTOM AND THE SIDES. MAINTAIN DUCTWORK
LEVEL AND AS HIGH AS POSSIBLE UNLESS NOTED OTHERWISE.
3. LOCATIONS SHOWN FOR EQUIPMENT ARE APPROXIMATE LOCATIONS. CONTRACTOR SHALL
COORDINATE WITH THE FIELD CONDITIONS FOR THE EXACT LOCATION AND MODIFY DUCT
SYSTEM ACCORDINGLY WITHOUT ADDITIONAL COST TO THE OWNER.
4. CONTRACTOR SHALL FIELD VERIFY AVAILABLE SPACE FOR DUCTWORK BEFORE FABRICATING.
CONTRACTOR SHALL MODIFY DUCTWORK TO FIT AVAILABLE FIELD CONDITIONS.
| QCF CARSR-G001 |
| QCF CARSR-M001 |
| QCF CARSR-M002 |