This document provides details on a federal solicitation for renovating the HVAC system at the Florence Regional Airport TRACON building in Florence, South Carolina. The solicitation number is 6973GH-24-R-00029 and is being issued by the Department of Transportation Federal Aviation Administration Franchise Acquisition Services to renovate various areas of the TRACON building's HVAC system located at 29501 Florence Regional Airport in Florence, South Carolina. The attached file is a technical drawing appendix to the solicitation that provides additional details on the HVAC renovation project scope and specifications. Interested contractors should review all provided documents for response requirements and project details.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

H

G

F

E

D

C

B

A

8 1234567

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY DATE

DRAWING NO

DESIGNED

REVIEWED BY

IL

/2

:2

P

M lo tt e d b y S

R V

-C

-E

O

APPROVED

8 23467 5

TRAT

I

MECHANICAL

GENERAL

ELECTRICAL

DRAWING LIST

FLO-21000450-M009

FLO-21000450-G004

FLO-21000450-G003

FLO-21000450-M010

FLO-21000450-M011

FLO-21000450-M012

FLO-21000450-M013

FLO-21000450-M014

FLO-21000450-E009

FLO-21000450-E010

FLO-21000450-E011

FLO-21000450-E012

FLO-21000450-E013

FLO-21000450-P001

T OF TRANSPO

T A T

IO

N

IC

OF

STATES

U

IT

P A

TM

SITE LOCATION: 34.19347, -79.729113

FLORENCE MUNICIPAL AIRPORT

HVAC REPLACEMENT

FLO / TRACON - FLORENCE, SOUTH CAROLINA

AVIA

LA

TRAT

SI

NI

DRAWING NO. REV. DATE DESCRIPTION

(FLO)FLORENCE HVAC REPLACEMENT TITLE SHEET AND DRAWING LIST

(FLO)FLORENCE HVAC REPLACEMENT GENERAL INFORMATION

(FLO)FLORENCE HVAC REPLACEMENT MECHANICAL LEGEND AND ABBREVIATIONS

(FLO)FLORENCE HVAC REPLACEMENT MECHANICAL EQUIPMENT SCHEDULES

(FLO)FLORENCE HVAC REPLACEMENT HVAC DEMOLITION

(FLO)FLORENCE HVAC REPLACEMENT HVAC NEW WORK

(FLO)FLORENCE HVAC REPLACEMENT TEMPORARY AIR CONDITIONING PLAN

(FLO)FLORENCE HVAC REPLACEMENT HVAC CONTROLS

(FLO)FLORENCE HVAC REPLACEMENT PLUMBING DEMOLITION AND NEW WORK

(FLO)FLORENCE HVAC REPLACEMENT ELECTRICAL LEGEND AND ABBREVIATIONS

(FLO)FLORENCE HVAC REPLACEMENT ELECTRICAL DEMOLITION

(FLO)FLORENCE HVAC REPLACEMENT ELECTRICAL NEW WORK

(FLO)FLORENCE HVAC REPLACEMENT ELECTRICAL SCHEDULES AND DIAGRAMS

(FLO)FLORENCE HVAC REPLACEMENT ELECTRICAL DETAILS

12/15/2022

IS

MGR: ENGINEERING - CENTER A

APA

FLORENCE

FLO-21000450-G003

JJ

DLS

TRACON

(FLO) FLORENCE HVAC REPLACEMENT

TITLE SHEET

AND DRAWING LIST

fl o -2

-g

.d w g

OPS INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA

THIS DRAWING PRODUCED ON ASO REGION CAD SYSTEM

PROJECT ENGINEER

21000450

SC

PLUMBING

flo-21000450-g003

2023-03-20T15:52:32-0400

SHANE C. HARVEY

2023-03-20T13:48:56-0400

DONALD LEE SPRINKLE

:0 lo tt e

BUILDING CODE

SUMMARY

MANAGER FOR ADDITIONAL INFORMATION.

DUE TO SECURITY REGULATIONS, NO FOREIGN NATIONALS WILL BE ALLOWED ON SITE WITHOUT A 30-DAY (CALENDAR) NOTIFICATION AND PRIOR APPROVAL. CONTACT THE SSC 20.

BASIS. COORDINATE ARRANGEMENTS AT THE PRE-CONSTRUCTION MEETING., TO INCLUDE EMERGENCY CONTACT AND NOTIFICATION ALERTS.

FAA ESCORT WILL ATTEND CONTRACTOR PERSONNEL TO AND FROM THE SITE ON A DAILY DESIGNATED ACCESS TO THE SITE REQUIRES PASSING THROUGH A SECURITY GATE. A 19.

CONTRACTOR MEANS.

THERE ARE NO DUMPSTERS OR DEBRIS DISPOSAL FACILITIES FOR CONTRACTOR USE. ALL PROJECT-GENERATED WASTE AND DEBRIS SHALL BE REMOVED OFF-SITE BY 18.

NORMAL BUILDING ELECTRICAL POWER MAY BE MADE AVAILABLE FOR CONTRACTOR USE ON A DAY-BY-DAY BASIS. COORDINATE NEED AT THE PRE-CONSTRUCTION MEETING.17.

WATER (POTABLE AND NON-POTABLE) IS AVAILABLE ON SITE FOR CONTRACTOR USE. USE IS LIMITED TO ORDINARY BUILDING CONSUMPTION. 16.

RESTROOM FACILITIES ARE AVAILABLE ON SITE AND USE IS PERMITTED SO LONG AS CONTRACTOR PERSONNEL EXERCISE CARE IN USING.15.

NO LEAD IS FORESEEN BEING IMPACTED BY CONSTRUCTION. 14.

NO ASBESTOS IS FORESEEN BEING IMPACTED BY CONSTRUCTION. TEST HIDDEN BUILDING ELEMENTS UNLESS INSTRUCTED OTHERWISE. SEE ENVIRONMENTAL CONCERN BELOW. 13.

LABEL ALL NEW EQUIPMENT, CONTROL DEVICES, AND ELECTRICAL POWER AS SPECIFIED.12.

HANG AND/OR SUPPORT DUCTWORK AND EQUIPMENT ONLY FROM STEEL JOISTS, AND ONLY FROM TOP CHORDS IF LOAD IS GREATER THAN 30 LBs. 11.

FIELD COORDINATE LAYOUT OF NEW EQUIPMENT FOR EASE OF ACCESS, TO AVOID OBSTRUCTIONS AND COMPLY WITH REQUIRED SERVICE-CLEARANCES. 10.

SAFEGUARD FIRE ALARM AND SECURITY SYSTEMS FROM DAMAGE OR FALSE ALARMS PRIOR TO DOING ANY WORK. RESTORE SYSTEMS TO NORMAL OPERATION BEFORE LEAVING.9.

(MERV 8 BLANKET OR ROLL FILTER MEDIA) ACROSS RETURN AIR INTAKES, IN ADDITION TO PERMANENT FILTERS OF OPERATIONAL AIR HANDLING UNITS.

CONTAMINANTS, FUMES OR ODORS PRODUCED BY CONSTRUCTION RELATED ACTIVITIES INTO OCCUPIED SPACES. FURNISH AND INSTALL DISPOSABLE 'CONSTRUCTION FILTERS'

COVER ALL OPEN DUCTS DURING CONSTRUCTION, AND PROTECT OR CLOSE IF ALLOWED, ANY OUTDOOR AIR OPENINGS THAT HAVE THE POTENTIAL TO INTRODUCE OBJECTIONABLE 8.

ELECTRICAL SYSTEM.

BOX AND INCLUDE REMOVAL OF ASSOCIATED CONDUIT BACK TO THE SAME POINT, SO LONG AS IT FACILITATES A CONTINUOUS WORKING CONDITION FOR THE REMAINING

INCLUDE ASSOCIATED ELECTRICAL POWER FEED. ELECTRICAL CIRCUITS NOT REQUIRING COMPLETE DEMOLITION BACK TO PANEL SHALL BE PROPERLY TERMINATED IN A JUNCTION

COORDINATE WITH FACILITY MAINTENANCE PERSONNEL TO LOCK-OUT / TAG-OUT EXISTING ELECTRICAL CIRCUITS PRIOR TO DEMOLITION OF RESPECTIVE HVAC EQUIPMENT, TO 7.

DOORS, GLAZING, AND EXTERIOR GROUNDS IF DAMAGED, RESTORE TO MATCH SURROUNDINGS.

REPAIR BUILDING FINISHES THAT ARE AFFECTED BY THE WORK, TO INCLUDE BUT NOT LIMITED TO: WALLS, CEILINGS, FLOORING, ROOF, FACADE, PARKING SURFACES, PARTITIONS, 6.

PROVIDE AND INSTALL PROVISIONS TO MITIGATE THE AFFECT OF THERMAL EXPANSION AND TRANSFER OF VIBRATIONS ASSOCIATED WITH MECHANICAL EQUIPMENT OR SYSTEMS. .5.

INSTALLATION. CONTACT THE SSC MANAGER FOR ALL SITE-VISIT REQUESTS.

FIELD VERIFY EXISTING CONDITIONS AND COORDINATE WORK PLACEMENT WITH COR PRIOR TO ORDERING MATERIALS AND EQUIPMENT, FABRICATION, OR MAKING PERMANENT 4.

USE AND OPERATION.

HEATING, VENTILATION AND AIR CONDITIONING SYSTEM (HVAC) SYSTEMS SHALL BE PROVIDED WITH ALL ANCILLARY COMPONENTS NECESSARY FOR COMPLETE AND FUNCTIONAL 3.

THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. DO NOT SCALE FOR EXACT LOCATIONS. 2.

MEETING.

AND CONSTRUCTION MORATORIUMS ISSUED BY FAA AIR TRAFFIC MANAGEMENT. LISTING OF HOLIDAYS AND MORATORIUMS WILL BE COVERED IN THE PRE-CONSTRUCTION

WORKING HOURS SHALL BE COORDINATED NOT LESS THAN THREE (3) WORKING DAYS IN ADVANCE AND APPROVED BY COR. NO WORK WILL BE ALLOWED OVER FEDERAL HOLIDAYS

SEE PHASING PLAN. CONTRACTOR'S WORK THAT MAY INTERFERE WITH BUILDING OPERATIONS SHALL BE PERFORMED DURING NON-BUSINESS HOURS (22:00 TO 06:00) - 1.

WARRANTIES7.5.

AS-BUILTS7.4.

O&M DOCUMENTS7.3.

SYSTEMS TRAINING7.2.

JAI7.1.

FINALIZE TURN-OVER AND CLOSE-OUT OF HVAC PROJECT7.

REMOVE TEMPORARY DUCTWORK AND RETURN RENTAL UNITS AS NO LONGER NEEDED.6.13.

RESTORE CEILING AND FINISHES. 6.12.

START-UP / COMMISSION / TURN-OVER ACU-1.6.11.

ROUGH-IN NEW DUCTWORK.6.10.

DEMO RTU-1 AND REPLACE WITH ACU-1 IN COORDINATION WITH ROOF REPLACEMENT.6.9.

TRANSITION TEMPORARY A/C TO ONLY RENTAL SPOT COOLERS. 6.8.

REPLACE / UPGRADE / INSTALL NEW EXHAUST FAN(S) FOR: TOILETS; JANITOR CLOSET; EQUIPMENT ROOM CLOSET; BREAK ROOM RANGE HOOD. 6.7.

ROUGH-IN NEW HVAC CONTROL DEVICES AND WIRING.6.6.

MODIFY DUCTWORK.6.5.

DEMO OLD VOLUME CONTROL DAMPERS AND INSTALL NEW VAVs.6.4.

FURNISH AND INSTALL TEMPORARY A/C PROVISIONS - TEMPORARY DUCTWORK SERVED BY RTU-1, RENTAL SPOT COOLERS, OR COMBINATION OF BOTH.6.3.

FIELD VERIFICATION MEASUREMENTS.6.2.

SELECTIVELY DEMOLISH CEILING TILES AND GRID. 6.1.

OFFICES AND BREAK ROOM (BOTH BUSINESS AND NON-BUSINESS HOURS)6.

RESTORE FINISHES.5.11.

REMOVE TEMPORARY AIR CONDITIONING, BUT MAINTAIN ONE (1) SPOT COOLER AS BACK-UP FOR TRACON.5.10.

START-UP / COMMISSION / TURN-OVER ACU-25.9.

ROUGH-IN DUCTWORK SERVING TRACON.5.8.

INSTALL ACU-2 OUTDOOR AND INDOOR UNITS.5.7.

CAP EXISTING CURB IN COORDINATION WITH ROOF REPLACEMENT5.6.

DEMO RTU-2 AND ASSOCIATED DUCTWORK. 5.5.

TEST AND CONFIRM TEMPORARY AIR CONDITIONING. 5.4.

AND RECORDER PLAYBACK CLOSET.

FURNISH AND INSTALL TEMPORARY A/C PROVISIONS - PERMANENT EMERGENCY DUCTWORK WITH RENTAL SPOT COOLERS IN EQUIPMENT ROOM BACK-FEEDING TRACON SUPPLY AIR 5.3.

FIELD VERIFICATION MEASUREMENTS.5.2.

SELECTIVELY DEMOLISH CEILING TILES AND GRID. 5.1.

TRACON ONLY (NON-BUSINESS HOURS)5.

START-UP / COMMISSION / TURN-OVER ACU-54.6.

DEMO AHU-5 AND REPLACE WITH ACU-54.5.

START-UP / COMMISSION / TURN-OVER ACU-44.4.

DEMO AHU-4 AND REPLACE WITH ACU-44.3.

START-UP / COMMISSION / TURN OVER ACU-3.4.2.

INSTALL ACU-34.1.

EQUIPMENT ROOM (NORMAL BUSINESS HOURS)4.

EQUIPMENT AND MATERIAL DELIVERIES3.5.

LAYDOWN AREA3.4.

FINISHES PROTECTION3.3.

REMOVE FURNISHINGS FROM WORK AREA3.2.

JOBSITE SIGNAGE3.1.

MOBILIZATION3.

PERMITS AND AUTHORIZATIONS2.

MAJOR EQUIPMENT SUBMITTAL APPROVALS1.

NOTE: PROPOSED CONSTRUCTION ACTIVITIES ARE GROUPED INTO THREE (3) AREAS OF CONCERN: 1) EQUIPMENT ROOM; 2) TRACON; 3) OFFICES, CORE, AND BREAK ROOM

CONSTRUCTION SCHEDULE AND FAA DISCRETION, TAKING INTO ACCOUNT THE PROJECT'S PRIORITIES AIR TRAFFIC OPERATIONS, BUILDING USE, WEATHER, UNFORESEEN CONDITIONS.

THE FOLLOWING IS A SUGGESTED PLAN FOR BASIS OF BID ONLY. ACTUAL ACTIVITIES, THEIR PRECEDENCE AND RELATIONSHIPS, SHALL BE PERFORMED AND ACCORDING TO CONTRACTOR'S

International Mechanical Code

IF CHEMICALS ARE USED, PLEASE PROVIDE SDS5.

LCP MATERIALS

ONLY PROPERLY TRAINED / CERTIFIED / LICENSED PERSONNEL MAY IMPACT ACM AND 4.

THE ATTACHED SOPS ASSUMED TO BE COATED WITH LEAD CONTAINING PAINTS (LCP).

ALL PAINTED SURFACES. ANY DRILLING INTO FLOOR TILE MUST BE PERFORMED USING 3.

CONCRETE BLOCK WALLS).

CONFIRM/REFUTE THE PRESENCE OF ASBESTOS INSULATION IN THE VOIDS (OF THE

IF CONCRETE WALL CORED AN ACCREDITED ASBESTOS INSPECTOR NEED TO 2.

ALL BUILDING MATERIALS ARE ASSUMED TO CONTAIN ASBESTOS (ACM). 1.

WORK REVIEW REQUEST (WRR) SECM REMARKS:

AUTHORITY HAVING JURISDICTION (AHJ).

Transportation, Federal Aviation Administration (FAA). FAA engineer of record is the

FLO TRACON is a United States Government-owned property of the Department of 3.

Government of the United States of America.

engineering work is the services of full-time, non-temporary employees of the

In compliance with South Carolina Code of Laws Title 40, Chapter 22-280: all 2.

* FAA LETTER OF AUTHORIZATION (LOA)1.

Name of Project:Florence TRACON (FLO) HVAC Renovation

Address: Florence Regional Airport; 2085 Terminal Drive; Florence, SC 29501

Facility Type: Terminal Radar Approach Control (TRACON)

Owner/Contact Person:FAA Myrtle Beach SSC Phone: (904) 845-1623

DESIGNER'S NAME LICENSE #

Architectural

Electrical

Structural

Mechanical Donald Sprinkle, PE

Jean Sanon FAA LOA*

FAA LOA* (404) 984-3954

(718) 553-4844

TELEPONE #

Applicable Codes:

Type Name Edition

Building

Life Safety

Accessiblity

Mechanical Code

Plumbing Code

Gas Code

Electrical Code

Fire Prevention

Energy Code

Boiler Control

For Automatically Fired Boilers

ASME CSD-1 Standard For Control and Safety Devices

International Energy Conservation Code

International Fire Code

NFPA 70 - National Electric Code

International Gas Code

International Plumbing Code

ANSI 117.1

Fire Protection Equipment

FAA Order 6930.1, Fire Prevention and Maintenance of

Towers 29 CFR 1960.17

Alternate Standard for Fire Safety in Airport Traffic Control

NFPA 101 - Life Safety Code

International Buidling Code 2018 w/ South Carolina Amemdments

2018 w/ South Carolina Amendments

2017 w/ South Carolina Amendments

2009 w/ South Carolina Amendments

BUSINESSOccupancy Classification, IBC and NFPA 101:

Fire

Civil

:NOTES

GENERAL NOTES:

PHASING PLAN:

ENVIRONMENTAL WARNING:

MGR: INSTALLATION - CENTER A

APA

FLO-21000450-G004

DLS

GENERAL INFORMATION

-g

OPS INFRASTRUCTURE

WARNING!

THIS IS AN OPERATIONAL

AIR TRAFFIC CONTROL FACILITY

DO NOT WORK IN ANY AREA IF YOU ARE NOT FULLY

AWARE OF THE CONSEQUENCES OF YOUR ACTIONS

THIS INCLUDES, BUT NOT LIMITED TO:

· OPENING OR CLOSING ANY CIRCUIT BREAKER.

· OPENING OR CLOSING ANY VALVE.

· CUTTING ANY WIRE OR CABLE.

· TURNING ON OR OFF ANY PIECE OF EQUIPMENT.

· PLUGGING ANYTHING INTO A POWER OUTLET.

· CUTTING, DRILLING OR CORING INTO ANY WALL, FLOOR,

ROOF, OR CEILING.

· PERFORMING ANY ACTIVITIES THAT PRODUCE FUMES,

ODORS, OR DUST.

· CAUSING LOUD NOISES OR BUILDING VIBRATIONS.

· EFFECTING A FIRE PROTECTION OR SECURITY SYSTEM

ALARM.

KNOW WHAT YOU ARE DOING BEFORE YOU DO IT!

DON'T TAKE THE CHANCE OF CAUSING AN ACCIDENT OR

INTERRUPTING AIR TRAFFIC!

Security ATM SSC

Barbara Green Calvin Little Joseph Palmer

(843) 669-2617 (843) 669-2617 (385) 499-5570

WARNING!

THIS FACILITY IS USED IN FAA AIR TRAFFIC CONTROL. LOSS OF

HUMAN LIFE MAY RESULT FROM SERVICE INTERRUPTION. ANY

PERSON WHO INTERFERES WITH AIR TRAFFIC CONTROL, OR

DAMAGES OR TRESPASSES ON THIS PROPERTY WILL BE

PROSECUTED UNDER FEDERAL LAW.

flo-21000450-g004

2023-03-20T15:53:14-0400

SHANE C. HARVEY

2023-03-20T13:49:19-0400

DONALD LEE SPRINKLE

:3

:5 lo tt e

POINT OF CONNECTION / DEMOLITION

UNION

MOTOR ACTUATED 2-WAY VALVE

HOSE BIB W/ CHAINED CAP (NF - NON-FREEZE)

GATE VALVE

NUMBER WHERE SHOWN

DETAIL NUMBER DRAWING

EXISTING EXHAUST GRILLE TO REMAIN

NECK SIZE

DESIGN CFM

DIFFUSER/GRILLE MARK

FLEX DUCT

NEW RETURN AIR GRILLE

NEW EXHAUST GRILLE

NEW DUCTWORK

NEW SUPPLY AIR DIFFUSER

EXISTING DIFFUSER TO REMAIN

EXISTING RETURN GRILLE TO REMAIN

EXISTING DUCTWORK TO REMAIN

EXISTING EQUIPMENT TO REMAIN

MANUAL VOLUME DAMPER

SPIN-IN WITH VOLUME DAMPER

TEMPERATURE SENSOR

CURRENT SENSOR

SMOKE 'DUCT' DETECTOR

DUCT REDUCER / ENLARGER

FIRE DAMPER

FIRE SMOKE DAMPER

HI-LIMIT PRESSURE SENSOR

STATIC PRESSURE SENSOR

FLOW METER

MOTOR ACTUATED 3-WAY VALVE

MOTORIZED DAMPER

TURNING VANES

AIR FILTER

STRAINER

BALL VALVE

STRAINER W/ BLOW-OFF AND CAP

MANUAL AIR RELEASE VENT

GLOBE VALVE

CHECK VALVE

DOUBLE CHECK VALVE

THERMOSTATIC EXPANSION VALVE

SOLENOID VALVE

COUPLING

PRESSURE TEMPERATURE PORT (PETE'S PLUG)

BALANCING VALVE (CIRCUIT SETTER)

COMBINED FLOW MEASURMENT AND

PRESSURE RELIEF VALVE

GAUGE (T-TEMPERATURE, P-PRESSURE)

PRESSURE REDUCING VALVE

NEW EQUIPMENT

ECCENTRIC / CONCENTRIC REDUCER

FLEXIBLE PIPE/JOINT/CONNECTION

RELATIVE HUMIDITY SENSOR

FS

XXX

EXISTING TO BE REMOVED

OR RELOCATED

END SWITCH

CS

SP

HI

RH

ES

MVD

FM

EXISTING PIPE

NEW PIPE LWT

LIQUID LINE

KILOWATT

INTERNAL STATIC PRESSURE

HEATING WATER SUPPLY & RETURN

HEATING WATER RETURN

HEATING WATER SUPPLY

HEAT PUMP

HOT GAS REHEAT

HOT GAS LINE

GALLONS PER MINUTE

FEET

FINISHED FLOOR

FILTER DRIER

FAN COIL UNIT

FIRE ALARM CONTROL PANEL

EXHAUST AIR

ENTERING WATER TEMPERATURE

EXTERNAL STATIC PRESSURE

END SWITCH

ELECTRIC

EXHAUST FAN

ELECTRICAL EFFICIENCY RATION

ELECTRIC DUCT HEATER

ELECTRICALLY COMUTATED MOTOR

ENTERING AIR

DIRECT EXPANSION

DOMESTIC WATER

DIGITAL OUTPUT

DIGITAL INPUT

COLD WATER

CONDENSER UNIT

COMPRESSION TANK

COMPUTER ROOM UNIT

COMPUTER ROOM AIR CONDITIONER

CONDENSATE LINE

CHILLED WATER SUPPLY AND RETURN

CHILLED WATER RETURN

CHILLED WATER SUPPLY

BACK DRAFT DAMPER

ASPIRATING SMOKE DETECTOR

ACCESS PANEL

ANALOG OUTPUT

ANALOG INPUT

AIR HANDLING UNIT

AIR FILTRATION UNIT

ADJUSTABLE FROM GRAPHICS

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

ACCESS DOOR / PANEL

AIR CONDITIONING AND REFRIGERANT

AIR COOLED CONDENSING UNIT

AIR CONDITIONING UNIT

AIR CONDITIONING

LWT

LL

KW

ISP

HWS&R

HWR

HWS

HP

HGR

HGL

GPM

FT

FF

FD

FCU

FACP

EXA

EWT

ESP

ES

ELEC

EF

EER

EDH

ECM

EA

DX

DW

DO

DI

CW

CU

CT

CRU

CRAC

CL

CHWS&R

CHWR

CHWS

BDD

ASD

AP

AO

AI

AHU

AFU

AFG

AFG

AFF

AD / P

ACR

ACCU

ACU

A/C

FLEXIBLE DUCT CONNECTION

E ENCAPSULATED RELAY (PAM)

DUCT SENSOR 'AUXILLARY'

ZONE AREA MODULE

WITH

WATER GAUGE

EXPANSION TANK

ELECTRICAL TRANSFORMER

VOLUME DAMPER

VARIABLE AIR VOLUME

UNIT HEATER

TYPICAL

THERMOSTATIC EXPASION VALVE

TEMPERATURE AND PRESSURE RELIEF VALVE

THERMOSTAT

TEMPORARY AIR CONDITIONING UNIT

SIGHT GLASS

SUCTION GAS LINE

SUPPLY AIR

RETURN AIR

PACKAGED TERMINAL AIR CONDITIONER

POINT OF CONTACT

POWERED INDUCTION UNIT (FAN VAV)

PRESSURE DROP

PRIMARY AIR

ORIGINAL EQUIPMENT MANUFACTURER

ON CENTER

OUTSIDE AIR

NET POSITIVE SUCTION HEAD

NOT IN CONTRACT

MAX ALLOWABLE WATER PRESSURE

METAL FLEX

MIXED AIR

ZAM

W/

WG

XT

XFMR

VD

VAV

UH

TYP

TXV

TXP

T-STAT

TACU

SG

SGL

SA

RA

PRV

PTAC

POC

PIU

PD

PA

OEM

OC

OA

NPSH

NIC

MAWP

MF

MA

TRANSFER OPENING

ACCESS DOOR / PANELAD

BLANK-OFF PLATE OR COVER

BUTTERFLY VALVE

PUMP

VENTURI FLOW METER

BACKFLOW PREVENTER

REDUCED PRESSURE ZONE

CIRCUIT SETTER BALANCING VALVE

DUCT SENSOR REMOTE ALARM INDICATOR

HVAC LEGEND AND ABBREVIATIONS

NF

FLO-21000450-M009

KP

DS

MECHANICAL LEGEND AND ABBREVIATIONS

-m

INFRASTRUCTURE

flo-21000450-m009

2023-03-20T15:54:03-0400

SHANE C. HARVEY

2023-03-20T13:49:32-0400

DONALD LEE SPRINKLE

lo tt e

DAMPER SCHEDULE

FRAME

TYPE BASIS OF DESIGNMARK

MAXIMUM

INCHES, W x H

DUCT SIZE

18 GA GALVANIZED STEELBDD-1 GREENHECK GM-30MULTI-BLADE, PARALLEL COUNTERBALANCED 12x10

TYPE

BLADE

EXTRUDED AL

BLADE

SEALS

VINYL

FIELD VERIFY INTENDED DAMPER LOCATION AND SIZE MOUNTS AND FASTENERS ACCORDINGLY.4.

INCLUDES 1/2" DURO DYNE KL SHAFT LOCK QUADRANT SET AND STANDOFF MOUNT. 3.

INCLUDES 12x12 ACCESS PANEL FOR SERVICING ACCESS: PROVIDE AND INSTALL GREENHECK CAD-10.2.

NO FLANGE - DUCT MOUNTED1.

SERVES

VAV-1-7

MAX

CFM

DESIGN

BASIS OF

PH HZ

ELECTRICAL DATA

VOLT

.258

TYPESERVESMARK

VAV-1-1

STEPS

HEAT

HEAT, KW

LEVEL

MAX NC

" WG

MAX ESP

MIN

SIZE, IN.

INLET

NOTES

TITUS DECV 008.25

OFFICE, STORE ROOM, TRAINING

VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE

.15

" WG

MIN ISP

FAN

SINGLE DUCT 760 80

SCHEDULED PERFORMANCE DATA IS FOR UNIT SELECTION - BALANCE AIR FLOWS AS INDICATED, OR AS APPROVED BY ENGINEER OF RECORD.2.

HANGER BRACKETS; AND DUCTWORK CONNECTIONS.

INCLUDES 24V DDC HVAC CONTROLS FOR FIELD INSTALLATION (COORDINATE WITH HVAC CONTROLS PROVIDER); CROSS-FLOW SENSORS; 1.

30 TITUS DECV 006.25SINGLE DUCTVAV-1-2 .15 16 400 40CONFERENCE ROOM 2

30 TITUS DECV 010.25SINGLE DUCTVAV-1-3 .15 - - 110 800 40 - -- - -FRONT OFFICES, FOYER 2

30 TITUS DECV 008.25SINGLE DUCTVAV-1-4 .15 - - 18 600 80 - -- - -SUPPLY, ADMIN, ATM 2

30 TITUS DECV 006.25SINGLE DUCTVAV-1-5 .15 16 220 40 - -OPS OFFICE, CLOSET, FOYER 2

30 TITUS DECV 006.25SINGLE DUCTVAV-1-6 .15 - - 16 440 40 - -- - -BREAK ROOM 2

30 TITUS DECV 006.25SINGLE DUCTVAV-1-7 .15 - - 16 540 80 - -- - -TRACON 2

SENSIBLE OA

INCLUDES MATCHING FACTORY ROOF CURB SIZED A MINIMUM OF 8" ABOVE FINISHED ROOF ELEVATION. 13.

INCLUDES OPTIONAL STAINLESS STEEL DRAIN PAN.12.

INCLUDES OPTIONAL DIRTY FILTER, FAN FAILURE, AIR SENSING, AND CONDENSATE DRAIN PAN OVER-FLOW SWITCHES.11.

INCLUDES OPTIONAL SUPPLY AIR SMOKE DETECTOR.10.

INCLUDES OPTIONAL POWERED CONVENIENCE OUTLET.9.

INCLUDES OPTIONAL THROUGH-THE-BASE ELECTRIC.8.

INCLUDES OPTIONAL BLACK EPOXY PRE-COATED CONDENSER COIL.7.

INCLUDES OPTIONAL 2" DISPOSABLE MERV-13 FILTERS, WITH ONE (1) EXTRA SET FOR FUTURE USE. 6.

INCLUDES OPTIONAL HINGED ACCESS PANELS5.

INCLUDES OPTIONAL HIGH-STATIC, OVER-SIZED MOTOR FOR MULTI-ZONE VARIABLE AIR VOLUME USE.4.

INCLUDES OPTIONAL ECONOMIZER, COMPARATIVE ENTHALPY WITH BAROMETRIC RELIEF.3.

INCLUDES BACnet COMMUNICATIONS INTERFACE ALLOWING COMMUNICATION DIRECTLY WITH NATIVE BACnet PROTOCOL MS/TP NETWORK BUILDING AUTOMATION SYSTEM (BAS). 2.

INCLUDES EXTENDED 5-YEAR WARRANTY, TO INCLUDE OEM PARTS AND LABOR.1.

TRANE WHC092_3RG_ _ _HFE2A0B601BH010 1 2 4

BASIS OF DESIGN

ROOF TOP AIR CONDITIONING UNIT SCHEDULE

ACU-1 OFFICES SELF-CONTAINED ROOF-TOP 1.00 3.0 1,205

TOTAL

MBHRPMHP

IN WG

SUPPLY FAN COOLING

96.2

MBH

EAT

DB, F WB, F

EAT LAT LAT

WB, FDB, F

74.7 80 67 58 56

FILTRATION

% EFF % EFFCFM

3,000

PRE POST

- 3 8

DIFFUSER, REGISTER & GRILLE SCHEDULE

BASIS OF DESIGNMARK TYPE

MAX NC

MAX ESP

"WG

FRAME

NECK

SIZE, IN. NOTES:FINISH

1TITUS TMSSUPPLY DIFFUSER 30.10LAY-IN, 24x24 VARIES WHITEA

SALVAGE IN PLACE, OR CLEAN AND RE-USE IN NEW LOCATION.3.

INCLUDE FACTORY OPTIONAL VOLUME DAMPER.2.

SEE NECK SIZE ON DRAWING1.

1TITUS PASRETURN REGISTER 30.10LAY-IN, 24x24 24x24 WHITEB

AMPS

FLA,

STOVE AND OVERHEAD CABINET.

FIELD COORDINATE AND SELECT APPROPRIATE SIZE OF UNIT (30" OR 36") TO MATCH DIMENSIONS OF EXISTING BREAK ROOM RANGE 5.

INCLUDES ON/OFF SPEED CONTROL WALL SWITCH: GREENHECK #385803. POWER LOCAL WALL RECEPTACLE.4.

INCLUDES FACTORY OPTIONAL GREENHECK WALL-MOUNT COLLAR, HOUSING AND WALL HOUSING GUARD SIZED FOR FAN ASSEMBLY.3.

PAINT TO MATCH.

INCLUDES SUPPORT FLANGES, LIGHT GAGE STEEL FRAMING, AND SHEETROCK REPAIR TO INSTALL FAN ASSEMBLY. TOUCH UP CEILING 2.

EXISTING - DO NOT DISTURB.1.

MOP,

MCA,

EXISTING GREENHECK G-70 1- -EF-2 ROOF-MOUNT DOWN CENTRIFUGAL .1 1/80 1.300 120 1 60

EXISTING GREENHECK G-80 1

BASIS OF DESIGN

EXHAUST FAN SCHEDULE

EF-1 TOILETS ROOF-MOUNT DOWN CENTRIFUGAL .1 1/20 1,550

RPMHPIN WG

SUPPLY FAN

VOLT PHASE HZ

120 1 60

TELE CLOSET 300

410-A -

46 70

208 3 60

HEATING

87.0 @ 47 F

DB, F

LAT

68 105 2"

0.2 GREENHECK SP-B150-QD 2 4- -EF-3 CEILING-MOUNT EXHAUST .5 1/6 840 120 1 60JANITOR CLOSET 149

1.0 GREENHECK SE1-12-432-A4X-QD 2 3- -EF-5 WALL-MOUNT AXIAL .25 1/4 1,750 120 1 60 4RECORDER PLAYBACK 1,282

18 GA GALVANIZED STEELBDD-2 GREENHECK VCD-33MULTI-BLADE, PARALLEL COUNTERBALANCED 12x10 EXTRUDED AL VINYLACU-2

POSITION

VERTICAL

VERTICAL

1GREENHECK XG-DGDFDOOR GRILLE 30.10RECESSED SCREW VARIES WHITE

1GREENHECK XG-V4004S-AFSUPPLY GRILLE 30.10RECESSED SCREW VARIES WHITE

AUXILLIARY

ELECTRIC, KW

18.0

3.0 HAUSLANE UC-PS18SS-36 5- -EF-4 RANGE HOOD 1.00 1/4 - 120 1 60BREAK ROOM RANGE 860

119 12

X 3EXISTINGVARIES --VARIES VARIES -

FLA,SENSIBLE OA

INCLUDES STANDARD 1" DISPOSABLE MERV-13 FILTERS, WITH ONE (1) EXTRA SET FOR FUTURE USE. 6.

INCLUDES OPTIONAL ACCESSORIES FOR A COMPLETE AND OPERATIONAL UNIT: LINE SET, MINI-SPLIT WIRE, OUTDOOR UNIT STAND, CONTROL/SERVICE TOOL.5.

INCLUDES SEACOAST PROTECTION ON OUTDOOR UNIT COMPONENTS (TRU*A0*******BA MODELS).4.

INCLUDES OPTIONAL STAINLESS STEEL DRAIN PAN.3.

INCLUDES BACnet COMMUNICATIONS INTERFACE ALLOWING COMMUNICATION DIRECTLY WITH NATIVE BACnet PROTOCOL MS/TP NETWORK BUILDING AUTOMATION SYSTEM (BAS). 2.

ECM

TRANE MITSUBISHI TPVA0A0181AA70A & TRUZA0181KA70BA 1 215 15ACU-2 MINI SPLIT, HORIZONTAL CABINET 0.50 1/6 - 18.0 15.0 78 67 59 58 208 1 601" -

BASIS OF DESIGN NOTES

MINI SPLIT AIR CONDITIONING UNIT SCHEDULE

LAT LAT

% EFF % EFFCFM CFM

PRE POST

TRACON 515 0 - - -

DB, FTYPE

410-A

- 43 5

SENSIBLE OA

INCLUDES OPTIONAL LOW AMBIENT CONTROL.4.

CONTROL PANEL.

INCLUDES OPTIONAL 2" DISPOSABLE MERV-13 FILTERS, WITH ONE (1) EXTRA SET FOR FUTURE USE. NOTE: MERV-13 FILTER USE REQUIRES SELECTION OF 'HI-SPEED' ON THE SPEED SELECTION TERMINAL STRIP INSIDE UNIT 3.

INCLUDES TECHNICOAT AA PROTECTIVE COATING ON CONDENSER COIL. 2.

INCLUDES TRANSFERABLE EXTENDED 5-YEAR WARRANTY, TO INCLUDE OEM PARTS AND LABOR.1.

WALL MOUNT AIR CONDITIONING UNIT SCHEDULE

EAT LAT LAT

CFM CFM

DB, FTYPE PRE

ECM BARD W42 AC _ B00BNXX2E 1 2ACU-3 SELF-CONTAINED, WALL-HUNG .23 1/2 - 42.0 31.1 80 67 - -EQUIP ROOM 1,340 0 - 23 35208 3 60- - - 2"

-410-A 43

FLA,SENSIBLE OA

INCLUDES MANUFACTURER'S OEM 6" FLOOR STAND WITH ADJUSTABLE FEET.11.

INCLUDES OPTIONAL 3-WAY DISCHARGE PLENUM.10.

INCLUDES OPTIONAL STAINLESS STEEL CONDENSATE DRAIN PAN.9.

INCLUDES OPTIONAL LIQUI-TECT-SENSOR.8.

INCLUDES OPTIONAL CONDENSATE PUMP.7.

INCLUDES OPTIONAL INFRARED HUMIDIFIER.6.

INCLUDES OPTIONAL E-COAT COIL PROTECTION ON EXTERIOR CONDENSER COIL.5.

INCLUDES OPTIONAL 2" DISPOSABLE MERV-11 FILTERS, WITH ONE (1) EXTRA SET FOR FUTURE USE. 4.

INCLUDES STANDARD SCROLL COMPRESSOR WITH CRANKCASE HEATER AND DISCHARGE CHECK VALVE.3.

INCLUDES BACnet COMMUNICATIONS INTERFACE ALLOWING COMMUNICATION DIRECTLY WITH NATIVE BACnet PROTOCOL MS/TP NETWORK BUILDING AUTOMATION SYSTEM (BAS). 2.

INDOOR UNIT

COMPUTER ROOM AIR CONDITIONING UNIT SCHEDULE

LAT LAT

POSTCFM CFM TYPE

OUTDOOR UNIT

HUMIDIFIER

PRE

68EC PLUG LIEBERT PX018UA1CDH22901MHBKP & MCS028E1 1 282 90ACU-4 UPFLOW, FRONT RETURN, W/ CONDENSER 0.80 5 - 62.5 57.1 75 61 53 52 208 3 60- 4EQUIP ROOM 2,800 0 3 4 15208 3 602"

EC PLUGACU-5 UPFLOW, FRONT RETURN, W/ CONDENSER 0.80 5 - 62.5EQUIP ROOM 2,800 0

4.8410A

410A

INFRARED

68 LIEBERT PX018UA1CDH22901MHBKP & MCS028E1 1 282 9057.1 75 61 53 52 208 3 60- 3 4 15208 3 602"4.8INFRARED

5 6 7 83

POST

7.7

7.7

TYPE LB WATER/HR

CONDENSER

40.9

68 81

12.0 ELECTRIC REHEAT2

AMBIENT

TEMPERATURE, F

40.9 68 81 12.0 ELECTRIC REHEAT2

9 10 11

4 5 6 7 83 9 10 11

1 2 4

1 2 4

20 GA GALVANIZED STEELCD-1 PRICE CCD-RD-LLTRUE ROUND LOW LEAKAGE 10 STEEL SILICONETRACON SUPPLY HOIZONTAL 1 3 4

2O GA GALVANIZED STEELCD-2 PRICE CCD-RD-LLMULTI-BLADE, PARALLEL COUNTERBALANCED 1O STEEL SILICONETRACON RETURN VERTICAL 1 3 4

MERV-13

STEPS OF

CAPACITY

- MERV-13

MERV-13

PLEATED MERV-11

PLEATED MERV-11

FLO-21000450-M010

MECHANICAL EQUIPMENT SCEDULES

flo-21000450-m010

2023-03-20T15:54:21-0400

SHANE C. HARVEY

2023-03-20T13:49:46-0400

DONALD LEE SPRINKLE

RETARDANT PLYWOOD

3/4" TYPE A (ASTM E84) FIRE

WITH ONE (1) COAT RED PRIMER (TYPICAL)

PLAIN STEEL SUPPORTING FRAME,4

L 3X3X

(TYPICAL)

WITH ONE (1) COAT RED PRIMER

PLAIN STEEL SUPPORTING FRAME, 4

L 3x3x

CAP WITH WELDED CORNERS

20 GA 304 STAINLESS STEEL CURB

123119

TT

A1

A2

2 3 4H lo tt e

ROOM SCHEDULE

# NAME

101 VESTIBULE

102 CORRIDOR

103 AF MANAGER

104 AF SECRETARY

105 AT MANAGER

106 AT SECRETARY

107 AF UNIT SUPERVISOR

108 ADMIN STORAGE

109 AF WORK AREA

110 CONFERENCE

111 TRAINING

112 QUATS

113 BULK STORAGE

114 ELECTRICAL

115 TELEPHONE

116 CORRIDOR

117 WOMENS TOILET

118 MENS TOILET

119 AUS

120 CORRIDOR

121 VESTIBULE

122 TRACON EQUIPMENT

123 RECORDER PLAYBACK

124 JANITOR

125 PASSAGE

126 AREA SUPERVISOR

127 TRACON

128 BREAK ROOM

129 STORAGE

10x10 x

10x8 x

RTU-2

L x x x x

10x10 10x10

AD

42x12 RTU-1

CU-2

CU-1

CRAC-1

CRAC-2

8x810x10 x

VD-1

EF-1

30x10

22x10 x

8x8

24x12

8x10

EF-2

ELECTRIC PANELS

x x x x x x

SCALE: 1/4" = 1'-0"

REFLECTED CEILING PLAN - HVAC DEMOLITION

M011

KEY NOTES:

INCLUDES SELECTIVE DEMOLITION AND DISPOSAL OF EXISTING REFRIGERANT LINE-SET, SITE GLASS AND FILTER-DRIERS.

SELECTIVELY DEMOLISH AND DISPOSE OF CRAC-2 AND ASSOCIATED CU-2 AFTER CRAC-1 IS INSTALLED, OPERATIONAL, AND TURNED OVER.

ACU-3 SHALL BE INSTALLED AND OPERATIONAL TO SERVE AS REDUNDANT AIR CONDITIONER.NOTE:

FILTER-DRIERS.

SELECTIVELY DEMOLISH AND DISPOSE OF CRAC-1 AND ASSOCIATED CU-1, TO INCLUDE EXISTING REFRIGERANT LINE-SET, SITE GLASS AND

REPLACE CRAC UNITS

INSPECTION IT CAN BE DONE WITHOUT DAMAGING THE LINER.

DUCTWORK IS INTERNALLY LINED, AND ANY CLEANING EFFORT MAY ONLY PROCEED IF IN THE OPINION OF THE AFOREMENTIONED

DUCTWORK - CLEAN EXISTING DUCTWORK REMAINING IN PLACE PER THE NADCA STANDARD: 2021 EDITION. NOTE: THE INTENDED

CLEAN DUCTWORK GO/NO GO: PURSUANT TO REQUEST BY CONTRACTING OFFICER (CO) TO EXECUTE ALTERNATE BID ITEM TO CLEAN

2/M011. COORDINATE WITH ROOF REPLACEMENT.

SELECTIVELY DEMOLISH AND DISPOSE OF RTU-2. PROVIDE AND CAP ROOF CURB WITH SUPPORTING WEATHERPROOF DECK - SEE DETAIL

SELECTIVELY DEMOLISH AND DISPOSE OF RTU-1, TO INCLUDE EXISTING ROOF CURB. COORDINATE WITH ROOF REPLACEMENT.

'TEMPORARY AIR CONDITIONING PLAN' FOR DETAILS.

PROVIDE, INSTALL, AND OPERATE STAND ALONE TEMPORARY AIR CONDITIONING UNITS (RENTALS) FOR OFFICES AND TRACON. SEE M005

PREPARE TO SET NEW AIR CONDITIONING UNITS

CONNECTED TO NEW RETURN AIR BOOT).

REGISTERS IN THE BREAK ROOM. FIELD COORDINATE THE LOCATION TO CUT 12x10 RETURN AIR DUCT WITHIN BREAK ROOM (TO BE RE-

SELECTIVELY DEMOLISH AND DISPOSE OF AIR FILTERING UNIT (AFU), TO INCLUDE THAT PORTION OF RETURN AIR DUCTWORK AND CEILING

EXAMPLE: 12x10 SUPPLY AND RETURN SERVING TRACON.

SERVING THIS AREA WITH VAV FROM ACU-1). FIELD COORDINATE POINTS OF TERMINATION OF DUCTWORK TO REMAIN IN PLACE, FOR

GRILLES INDICATED, IN CORRIDOR, RECORDER PLAYBACK, JANITOR, PASSAGE AND AREA SUPERVISOR ROOMS (TO MAKE ROOM FOR RE-

SELECTIVELY DEMOLISH AND DISPOSE OF SUPPLY AND RETURN DUCTWORK SERVING RTU-2, TO INCLUDE DIFFUSERS, REGISTERS AND

PROPERLY - REPORT FINDINGS TO COR.

VESTIBULE. DO NOT DISTURB FIRE DAMPER - OPERATE LINKAGE BEFORE AND AFTER DEMOLITION TO CONFIRM FIRE DAMPER OPERATES

SELECTIVELY DEMOLISH AND DISPOSE OF RETURN AIR TRUNK BETWEEN RTU-1 AND FIRE DAMPER IN WALL BETWEEN ADMIN STORAGE AND

MAKE ROOM TO EXTEND VAV SYSTEM

PATCH SHEET METAL OF ABANDONED DIFFUSER DROPS. BACKFILL CEILING OPENINGS WITH SPARE TILES FROM ATTIC STOCK.

SELECTIVELY DEMOLISH AND DISPOSE OF SUPPLY DIFFUSERS, RETURN REGISTERS AND GRILLES INDICATED. RESTORE DUCT LINER AND

REMOVE UNNECESSARY DIFFUSERS AND REGISTERS

WAYS AND WALL FINISHES TO MINIMIZE DISTURBANCE. NEW T-SENSORS TO BE PUT BACK IN SAME LOCATIONS.

SELECTIVELY DEMOLISH AND DISPOSE OF EXISTING WALL THERMOSTATS, 4 LOCATIONS (TYPICAL). FIELD COORDINATE SALVAGE OF WIRE-

MODE. ADJUST FAN SPEEDS, IF AVAILABLE, TO 'LOW' SETTING.

DUCTWORK AND DUCTBOARD MATERIALS TO MAINTAIN AIRFLOW TO AFFECTED AREAS. CONTROL EXISTING RTU-1 AND 2 IN SINGLE ZONE

NOTE: FIELD COORDINATE CONTINUED USE AND OPERATION OF RTU-1 AND 2. PROVIDE AND INSTALL TEMPORARY AIR DISTRIBUTION USING FLEX

TRANSITIONS. REMOVE ALL ASSOCIATED LOW VOLTAGE WIRING AND CONTROLS. 4 LOCATIONS (TYPICAL).

SELECTIVELY DEMOLISH AND DISPOSE OF AUTOMATED VOLUME DAMPERS, TO INCLUDE FLEXIBLE DUCT CONNECTOR AND INLET/OUTLET

COR AND/OR FACILITY MANAGER.

WIRING. CONTRACTOR MAY NOT LEAVE SITE WITHOUT FIRST RESTORING NORMAL HVAC CONTROLS OPERATION, UNLESS APPROVED BY

NOTIFY AND COORDINATE WITH FACILITY MANAGER BEFORE DOING ANY WORK TO HVAC CONTROLS, TO INCLUDE LOW-VOLTAGE CONTROL NOTE:

LOW-VOLTAGE CONTROLS WIRING AND DEVICES. SALVAGE IN PLACE ONE THERMOSTAT FOR RTU-1 CONTROL.

SELECTIVELY DEMOLISH AND DISPOSE OF EXISTING 'BARBER COLEMAN' HVAC CONTROL PANEL(S) IN ELECTRICAL ROOM, TO INCLUDE ALL

LOCATIONS (TYPICAL).

SELECTIVELY DEMOLISH AND DISPOSE OF MANUAL VOLUME DAMPERS. RESTORE LINER AND PATCH DUCTWORK WHERE ACCESS IS MADE. 6

REMOVE EXISTING MANUAL AND MOTORIZED VOLUME DAMPERS

PLACE. RESTORE CEILING TO PRIOR CONDITION AFTER AIR CONDITIONING WORK IS INSTALLED AND ACCEPTED.

HEPA FILTRATION VACUUM CLEANING TO MINIMIZE THE DISTURBANCE OF DUST AND DEBRIS. STORE SALVAGED CEILING TILES IN A SAFE, DRY

REPLACED OR MODIFIED. CEILING REMOVAL SHALL BE DONE IN ONE EFFORT AND THE BUILDING CLEANED IMMEDIATELY AFTERWARDS USING

SELECTIVELY REMOVE AND SALVAGE FOR RE-USE EXISTING CEILING TILE AND GRID TO REACH DUCTWORK AND EQUIPMENT BEING

OPEN CEILINGS AND INTERIM CLEAN-UP

VD-3

VD-4

HVAC PANELS

VD-2

NOT TO SCALE

DETAIL - RTU-2 CURB CAP FOR INSTALL AFTER UNIT DEMOLITION

3/16

3/16

FASTEN CAP TO CURB ON SIDES WITH 12 X 3/4 ROOFING SCREWS, 16" OC3.

DRILLING SCREWS, 16" OC. PRE-DRILL HOLES.

#3 POINT ZINC PLATED SELF 4

FASTEN PLYWOOD TO FRAME PERIMETER WITH 12 X 1 2.

24" OC. PRE-DRILL HOLES.

FASTEN FRAME TO CURB WITH 8-18 X 1 WAFER HEAD ZINC PLATED SELF DRILLING SCREWS, 1.

NOTES:

6 TYPICAL

5 TYPICAL

2 TYPICAL

TYPICAL

14 TYPICAL

L 3x3x

4 TYPICAL

1. AVAILABLE LAY DOWN AND STAGING AREAS FOR EQUIPMENT DELIVERY AND CRANE SET-UP.

2. FIELD COORDINATE TRAFFIC CONTROL AND EMPLOYEE PARKING PRIOR TO ANY EQUIPMENT DELIVERY

OR CRANE USE.

3. SUBMIT FOR TECHNICAL EVALUATION THE CRANE LIFT PLAN, TO INCLUDE NOMINAL QUALIFICATIONS

OF THE RIGGING COMPANY, CRANE PROVIDER, AND OSHA COMPLIANT CERTIFIED OPERATOR.

INCLUDE MAKE AND MODEL OF CRANE TO BE USED. PLAN SHALL BE EVALUATED PRIOR TO

MOBILIZATION.

PICTURE - AERIAL VIEW OF SITE

3 IS

FLO-21000450-M011

HVAC DEMOLITION

4' 0 4' 8' flo-21000450-m011

2023-03-20T15:54:49-0400

SHANE C. HARVEY

2023-03-20T13:51:29-0400

DONALD LEE SPRINKLE

TAPE. LAP JOINT 2" MINIMUM.

METAL DUCT WITH MASTIC AND

SECURE VAPOR BARRIER TO

EXTERNAL DUCT INSULATION

DUCT LINER

INTERNAL

WRAP

SHEETMETAL EDGE

GASKET

OVERLAP 2" MIN.

SIDE MINIMUM

SCREW FASTENERS 6" O.C. 2 PER

A LEAK-PROOF SEAL

FLASHED AND CAPPED FOR

BE SEALED, COUNTER

EXTEND TO TOP OF CURB,

ROOFING MEMBRANE SHALL

NAILER (TYPICAL)

ROOF CURB AND

DIMENSIONAL WOOD NAILER

PRESSURE TREATED

ROOF CANT (TYPICAL)

ENTIRE PERIMETER OF ROOF CURB.

SPACED NO MORE THAN 12" O.C. FOR

CONSTRUCTION AND WIND LOADING,

CONSISTENT WITH ASSOCIATED ROOF

TYPE, SIZE, AND QUANTITY OF FASTENERS

SECURE UNIT TO CURB WITH APPROPRIATE

AND NUT (TYP)

SEISMIC BRACING ROD WITH LOCK WASHER

REQUIRED)

REMOVABLE LOCK CONNECTION (4

SEISMIC CABLE ATTACHMENT WITH

SINK

ABOVE FLOOD RIM OF JANITORS

3/4" TYPE 'L' Cu DRAIN LINE TO 6"

PIPE FULL SIZE

UNION

THREAD PLUG

OPEN VENT

THREADED PLUG

PAD (TYPICAL)

DRAIN OR SPLASH

ROUTE TO OPEN

CONNECTOR

4" FLEX DUCT

ADAPTER

CURB OR CURB

ROOF CURB

WHOLE FOR EASE OF ROUTING.

MAY BE SUBSTITUTED IN PART OR

NOTE: 6" SEMI-RIGID METAL FLEX

LOCK. SLOPE TO HOOD.

6" 24 GA GALVANIZED STEEL SNAP-

WITHIN 6' OF FINISHED FLOOR.

INSULATE HOT GAS LINES

LIQUID RETURN LINES.

HOT GAS DISCHARGE AND

EACH UNIT.

WALL SLEEVE FOR

NEW

STORM DRAIN. CONSTRUCT

DRAIN TO EXISTING

1" Cu CONDENSATE

FINISH

HIGH, 12 GAUGE, 304 SS 2B

DETECTION: 50" x 50" x 2"

PAN WITH LEAK

AUXILLARY OVER-FLOW

BEAM CLAMP ATTACHMENTS AND UNI-STRUT TRAPEZE.

SUPPORTING RODS TO STRUCTURE: DOUBLE SIDED

123119112

T T lo tt e

X

ACU-3

ACU-4

ACU-5

COOLER

TEMPORARY SPOT

EF-5

ACU-1

EF-3

EF-4

FA PANEL

x x x x

AD

42x12

20x10

30x10

22x10 x

24x12 x x x x x

VAV-1-6

VAV-1-7

6" ROOF CAP

12x10

BDD-1

BDD-2

-1 -5

6 MF

-4 x

12x16

ACU-2

VAV-1-2

BOOT

ATTENUATION

12x12 SOUND

REFLECTED CEILING PLAN - HVAC NEW WORK

M012

ELEVATION - ACU-1 DUCT TRANSISTION

DETAIL - EF-4 EXHAUST DUCT

IS OPERATIONAL AND TESTED. SEE DETAIL 10/M012.

PROVIDE AND INSTALL NEW CRITICAL AIR CONDITIONING UNITS, ACUs-4 AND 5. WORK ON ONLY ONE UNIT AT A TIME. DO NOT SECOND UNTIL THE FIRST

CONDITIONING FOR EQUIPMENT ROOM, AND MUST BE OPERATIONAL BEFORE REPLACING ACUs-4 AND 5.

PROVIDE AND INSTALL NEW WALL-MOUNT AIR CONDITIONING UNIT, ACU-3. SEE EQUIPMENT SCHEDULE. THIS IS INTENDED AS BACK-UP AIR

BALANCE' COMPANY. BALANCE AIR FLOWS TO VALUES INDICATED OR PROPORTION THEREOF, AS APPROVED BY ENGINEER OF RECORD .

TEST AND BALANCE OF RESPECTIVE SYSTEM AIR FLOWS SHALL BE DONE FOR ENTIRE BUILDING AND BY A INDEPENDENT, THIRD-PARTY 'TEST AND

COMMISSION NEW EQUIPMENT AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDED START-UP AND CHECK-OUT PROCEDURES.

OPERATIONS, BUT ALSO ALLOW FOR BEST INSTALL OF NEW ROOF CURB.

SHALL BE MUTUALLY COORDINATED BETWEEN RESPONSIBLE CONTRACTORS AND FACILITY MANAGEMENT TO AFFECT THE LEAST IMPACT ON BUILDING

COORDINATE WITH ROOF PROJECT, WHICH MAY OCCUR IN CONJUNCTION WITH OR PRIOR TO HVAC REPLACEMENT. THE WORK OF BOTH EFFORTS NOTE:

CONTRACTOR AND HOLDER OF ROOF WARRANTY. SEE DETAILS 2, 5, 6, 8/M012.

RESTORATION OF ROOFING SHALL INCLUDE INSULATION, MEMBRANE, BASE AND CAP FLASHING, AND BALLAST (IF REQUIRED) BY ROOFING

PROVIDE AND INSTALL NEW ROOF-TOP AIR CONDITIONING UNIT, ACU-1. INSTALLATION SHALL INCLUDE NEW ROOF CURB BY HVAC CONTRACTOR.

OUTDOOR UNIT PLACEMENT.

COMPLETE THE INSTALL AND TEST OF NEW MINI-SPLIT, ACU-2. INSTALL OUTDOOR UNIT AFTER DEMOLITION OF RTU-2. SEE DETAIL 4/M012 FOR

DUCTWORK, NEW DUCTWORK, OR A COMBINATION OF BOTH.

UP TO THIS POINT, OFFICES AND TRACON ARE STILL BEING CONDITIONED BY EXISTING RTU-1 (MORE OR LESS IN MANUAL MODE) USING TEMPORARY NOTE:

INSTALL NEW ROOF-TOP UNIT

SENSORS, CONTROLLERS, PROGRAMMING, FRONT-END GRAPHICAL USER INTERFACE, AND OPERATOR TRAINING. SEE HVAC CONTROLS DRAWING, PROVIDE AND INSTALL NEW HVAC BUILDING AUTOMATION SYSTEM (BAS), TO INCLUDE ALL NEW HARDWARE DEVICES, PANEL, POWER SUPPLY, WIRING, ROUGH-IN HVAC CONTROLS

PROVIDE AND INSTALL SOUND ATTENUATION BOOT ON RETURN AIR DUCT OF TRACON - INSTALL IN BREAK ROOM PLENUM. SEE DETAIL 7/M012.

DUCT CONNECTIONS WHERE DIFFUSER IS ADDED OR RELOCATED.

PROVIDE AND INSTALL NEW AIR DEVICES AS INDICATED - SEE 'DIFFUSER, REGISTER AND GRILLE SCHEDULE. PROVIDE AND INSTALL NEW FLEXIBLE

SLEEVE AND HAND GUARDS. PROVIDE AND INSTALL TRANSFER GRILLE IN DOOR.

PLACEMENT. FRAME AND FINISH WALL OPENING TO MATCH SURROUNDING. INCLUDE ELECTRICAL POWER, MANUAL ON/OFF WALL SWITCH, WALL

PROVIDE AND INSTALL NEW INDIRECT COOLING FAN, EF-5, FOR RECORDER PLAYBACK ROOM. SEE EQUIPMENT SCHEDULE. FIELD COORDINATE

EF-4 TO NEW EXHAUST CAP WITH ROOF CURB - SEE DETAIL 4/M012.

PROVIDE AND INSTALL NEW BREAK ROOM RANGE HOOD EXHAUST FAN, EF-4. INSTALLATION SHALL INCLUDE 6" METAL DUCT AND FITTINGS CONNECTING

EXISTING EF-1 MAIN EXHAUST TRUNK. PROVIDE AND INSTALL TRANSFER GRILLE IN JANITOR ROOM DOOR AS INDICATED.

PROVIDE AND INSTALL NEW JANITOR'S CLOSET EXHAUST FAN, EF-3. INSTALLATION SHALL INCLUDE 6" METAL DUCT AND FITTINGS CONNECTING EF-3 TO

DETECTION AND CONSPICUOUS OVER-FLOW DRAIN. DISCHARGE CONDENSATE TO JANITOR CLOSET'S MOP SINK. SEE DETAIL 3/M012.

DUCTWORK MODIFICATIONS IN BREAK ROOM. SEE DETAIL 3/M012 FOR SEISMIC RESTRAINT. INCLUDE AUXILIARY OVER-FLOW PAN WITH LEAK

BEGIN PHASED PROVISION AND INSTALL OF MINI-SPLIT, ACU-2 - AIR HANDLER PORTION. INSTALL AIR HANDLER BEFORE OR IN CONJUNCTION WITH

TRAPEZE HANGERS WITH SADDLES - DO NOT PENETRATE VAPOR BARRIER.

SUPPORT DUCTWORK WITH METAL HANGERS. EXTERNALLY INSULATED DUCTWORK SHALL BE SUPPORTED WITH INSULATION BLOCKS AND G.

FDS1 FLEX DUCT SUPPORT, OR APPROVED EQUIVALENT) TO PREVENT CRIMPING AT ELBOWS. SEE DETAIL 9/M012.

FLEXIBLE DUCT, TO INCLUDE NEW AND EXISTING DIFFUSER DROPS, SHALL BE EQUIPPED WITH FACTORY-MADE ELBOW REINFORCEMENT (MALCO F.

ALL SQUARE OR RECTANGULAR ELBOWS SHALL INCLUDE TURNING VANES.E.

METAL SIZES AND TREATMENT OF LINER TO MAINTAIN SMOOTH AND SECURE TRANSITION ACROSS ALL JOINTS. SEE DETAIL 2/M012.

EXISTING DUCTWORK IS INTERNALLY LINED (1"). NEW DUCTWORK MAY BE EXTERNALLY INSULATED OR INTERNALLY LINED. COORDINATE SHEET D.

INTERNALLY LINED (1" LINER).

ALL DUCTWORK DIMENSIONS ARE GIVEN FOR INTERNAL CLEARANCE. ALLOW ADDITIONAL 2" TO WIDTH AND HEIGHT FOR SHEET METAL SIZING IF C.

NEW DUCTWORK SHALL HAVE ALL JOINTS SEALED.B.

DAMPERS AND REMOVABLE CAPS AT APPROXIMATELY 6' AFF.

DURING CONSTRUCTION OR FUTURE EMERGENCY). FIELD COORDINATE ROUTING AND TERMINATE BACK-FEEDS WITH 10" ROUND CONTROL

INCLUDES PERMANENT, UN-INSULATED, 10" SUPPLY AND RETURN DUCTS FOR TEMPORARY SPOT COOLER TO BACK-FEED TRACON (FOR USE A.

SELECTIVELY MODIFY EXISTING DUCTWORK AS INDICATED FOR VAV DISTRIBUTION.

COORDINATE 'HAND' SIDE FOR BEST ACCESS TO CONTROL PANEL AND MINIMAL DUCT BENDS. 7 LOCATIONS (TYPICAL).

HANGERS, DUCTWORK TRANSITIONS AND INSULATED FLEX CONNECTORS, ELECTRICAL CONTROL POWER, AND NATIVE BACnet CONTROLLERS. FIELD

PROVIDE AND INSTALL CUT-IN, PRESSURE INDEPENDENT, VAV TERMINAL UNITS WITH CROSS-FLOW AIR MEASUREMENT SENSORS. INCLUDE METAL

COORDINATE WITH DEMOLITION TO ONLY WORK IN SAME AREA AND/OR ON SAME SYSTEM AT ONE TIME.NOTE:

UPGRADE VAV DISTRIBUTION - REPLACE AUTOMATED VOLUME DAMPERS AND MODIFY DUCTWORK

1. ACTUAL DIMENSIONS OF LINED DUCT ARE LARGER BY LINER THICKNESSES. SHEET METAL DUCT

DIMENSIONS INDICATED ARE INSIDE FACE TO FACE

2. SECURE VAPOR BARRIER WITH MASTIC AND TAPE. LAP JOINT 2" MIN.

45 DEGREES UP TO STRUCTURE.

CABLE BRACING OCCURS DIAGONALLY AT 4 CORNERS OF EQUIPMENT, AND ANGLED APPROXIMATELY 1.

DETAIL - DUCTWORK TRANSISTION

DETAIL - SEISMIC RESTRAINT

42x12

CURB

COG MUST BE INSIDE ROOF

FROM ACU-2 CONDENSER

6" EXHAUST CAP. ORIENT TO BLOW AWAY

ACU-2 CONDENSER

6" METAL FLEX

WITH SLOPED TOP

12X12 ROOF CURB

FACE WITH ESCUTEION.

3/4" TYPE 'L' Cu CONPICUOUS DRAIN LINE THROUGH CEILING.

CU-4

CU-5

16x20 x

12x10

ON ENDS (TYPICAL 2)

ROUND CONTROL DAMPER AND CAP

NEW HVAC CONTROL PANEL

1 TYPICAL 7

2 TYPICAL

7 TYPICAL

12 13 TYPICAL

DETAIL - RETURN AIR SOUND ATTENUATION BOOT

CEILING

DETAIL - DIFFUSER DUCT CONNECTOR

1. FREE AREA OF RETURN BOOT IS W IDTH x HEIGHT (WxH) EXCLUDING ALLOWANCE FOR LINER.

2. LINE BOOT WITH 1" ANTI-MICROBIAL DUCT LINER - COLOR BLACK.

3. PAINT EXPOSED-TO-VIEW SURFACES FLAT BLACK

1. STRAIGHT CONNECTION LENGTH (L) SHALL BE GREATER THAN 1-1/2 DIAMETER OF

NECK (D) FOR EVEN AIR DISTRIBUTION. ALL 90 DEGREE BENDS SHALL BE HARD

DUCTED, REINFORCED OR SUPPORTED TO PREVENT CRIMPING.

OF W - MINIMUM 6"2

D =

L = 1/2 OF W - MINIMUM 12"

18x18

-3

1. PITCH HORIZONTAL HOT GAS PIPING A MINIMUM OF 1/2" PER 10 FEET SO GRAVITY

AIDS MOVING OIL IN DIRECTION OF REFRIGERANT FLOW.

2. REFRIGERANT LINES ARE NOT DETAILED. REFER TO MANUFACTURER'S

REQUIRED MATERIALS AND METHODS FOR ROUTING, TO INCLUDE SIZING,

FITTINGS AND CONNECTION POINTS.

3. PROVIDE AND INSTALL NEW RAISED FLOOR PANELS WHERE NECESSARY TO

SUPPORT PLACEMENT OF AIR CONDITIONING UNIT. MATCH SIZE AND SUPPORT

CAPACITY OF EXISTING.

ELEVATION - ACU-4 AND 5 (TYPICAL)

ACU-4, 5

3-WAY

CONDENSER

ACU-4, 5

1. PROVIDE AND INSTALL NEW CURB IN COORDINATION WITH ROOF REPLACEMENT (OR

ADAPTER IF NECESSARY) WITH REQUIREMENT TO MAINTAIN EQUIPMENT CENTER OF

GRAVITY WITHIN CURB IS ONLY APPLICABLE IF ROOFING IS NOT REPLACED.

BELOW UNIT FOR SOUND ATTENUATION

EXTEND LINED RETURN TRUNK 6'

15 TYPICAL

DETAIL - ROOF CURB

1. SELECT AND SIZE THE MANUFACTURER RECOMMENDED CURB FOR THE ASSOCIATED UNIT BEING INSTALLED. MANUFACTURER'S

RECOMMENDED INSTALLATION METHODS AND MATERIALS SUPERCEDES THIS DETAIL.

2. ATTACHMENT OF CURB TO ROOF STRUCTURE AND UNIT TO CURB SHALL COMPLY WITH WIND RESISTANCE REQUIREMENTS FOR

THAT LOCATION.

3. FINISHED CURB HEIGHT SHALL BE NOT LESS THAN 12" ABOVE SURROUNDING ROOF.

4. COORDINATE THE LAYOUT OF THE ROOF CURB WITH THE BUILDING STRUCTURE, DUCTWORK CONNECTIONS AND WORK OF OTHER

TRADES.

CD-1

CD-2

2A

PAN

COOLING COIL DRAN

H2

1TIGHT ONLY.

THREADED PLUGS SHALL BE HAND 2)

+ 1" MINIMUM

PRESSURE BETWEEN FAN AND COIL

H = ABSOLUTE INTERNAL STATIC 1)

NOTES: H

GAP

MINIMUM 1" AIR

DETAIL - CONDENSATE TRAP

H2

DRAW THROUGH COIL BLOW THROUGH COIL

FLO-21000450-M012

HVAC NEW WORK

flo-21000450-m012

2023-03-20T15:55:10-0400

SHANE C. HARVEY

2023-03-20T13:51:44-0400

DONALD LEE SPRINKLE

EXTERIOR GRADE CAULKING

CONTINUOUS BEAD OF

FASTERNERS

1-1/4" WOOD SCREW

1X3 WOOD BLOCKING W/

FLASHING

STEEL RAIN

3" GALVANIZED

- SAME AS ROUND HOLE IN PLYWOOD.

FASTENERS. INSIDE WIDTH/HEIGHT OF FRAME IS 12"

SQUARE WOOD FRAME AND 1-1/4" WOOD SCREW

INSECT SCREEN SECURED AND SEALED BY 1x3

AND SEALED TO PLYWOOD

STARTER COLLAR FASTENED

12" GALVANIZED STEEL

EXISTING DUCTS

12" UN-INSULATED FLEX DUCT

LESS THAN 1,000 FEET PER MINUTE.

EVEN AIR DISTRIBUTION AND VELOCITIES

MULTIPLE DUCTS ARE REQUIRED FOR

8" INSULATED FLEX DUCT (TYPICAL).

15' TOTAL LENGTH.

NOT EXCEED 10' VERTICAL HEIGHT AND

VINYL TUBING DISCHARGE RISER. DO

COMBINATION 3/4" PVC TO 3/8" CLEAR

CONDENSATE PUMP

123119

TT

lo tt e

REFLECTED CEILING PLAN - HVAC NEW WORK

M013

1. FIELD COORDINATE LOCATION AND CONNECTIONS FOR TEMPORARY AIR CONDITIONERS, 3 TOTAL.

2. POST PERSONNEL TO CHECK COLLECTION REGULARLY - REGARDLESS OF TIME OR DAY. MAY PROVIDE AND INSTALL CONDENATE PUMP, TO INCLUDE CONDENSATE TUBING TO NEAREST

OPEN DRAIN.

3. FOLLOW MANUFACTURER RECOMMENDED MANUFACTURER'S RECOMMENDED SET-UP INSTRUCTIONS.

4. PROVIDE AND INSTALL ADDITIONAL SHEETMETAL DUCT FITTINGS AND FLEXIBLE DUCTWORK (INSULATED) IN NUMBERS AND SIZES WITH CONNECTIONS TO EXISTING DUCTWORK SO THAT

AIR DISTRIBUTION IS BALANCED AND INTERNAL DUCT VELOCITIES DO NOT EXCEED 950 FEET PER MINUTE (MINIMUM 2 EACH 8" SUPPLY DUCTS).

5. TEMPORARY ACU(S) TO BE COMMERCIALLY AVAILABLE RENTAL EQUIPMENT, TO INCLUDE SET-UP AND SERVICE SUPPORT, FROM PROVIDER WITH READILY AVAILBLE INVENTORY OF

REPLACEMENT UNITS.

6. BASIS OF TEMPORARY AIR CONDITIONING IS NON-PEAK COOLING FOR FULLY OCCUPIED BUILDING AND NORMAL OPERATIONS: APPROXIMATELY 6 TONS.

DETAIL - TEMPORARY AIR CONDITIONING UNIT

M013

CFM PRE

24.0

COOLING COILSUPPLY FAN

MARK SERVES CABINET TYPE

"WG MBH

0.50TACU-1, 2, 3

TEMPORARY AIR CONDITIONING (TACU) SCHEDULE

601208

FLAPH NOTES

321 21

2/M013.

TURN-OVER OF NEW AIR CONDITIONING. REPLACE SALVAGED WINDOW GLASS AND RESTORE GLAZING TO PRIOR CONDITION. SEE

OPENINGS WITH WEATHER FLASHING AND INSECT SCREENS. SELECTIVELY DEMOLISH AND DISPOSE OF TEMPORARY FACADE AFTER

TEMPORARILY REPLACE WITH 1/2" B-C GRADE PLYWOOD. CUT HOLES IN PLYWOOD FOR CONDENSER AIR TERMINATIONS. PROTECT

TEMPORARILY REMOVE AND SAFELY STORE EXISTING WINDOW GLAZING: STANDARD, FIXED PANE, 18x84 GLASS WINDOWS.

AND CONDITIONS FOR INTENDED TIME OF USE.

TEST AND BALANCE TEMPORARY AIR CONDITIONING TO ASSURE SYSTEM(S) SUFFICIENTLY COOL INTENDED SPACES GIVEN THE WEATHER

TACU LOCATIONS ARE SUGGESTED ONLY - MAY FIELD COORDINATE DEPENDING UPON APPROVAL OF FACILITY MANAGER AND COR.

SUPPORT FROM EXISTING POWER, VOICE OR DATA CABLES.

TO STRUCTURE. DO NOT OBSTRUCT EGRESS OR DIMINISH BUILDING SECURITY. INDEPENDENTLY SUPPORT - DO NOT HANG OR

NEATLY ROUTE AND CONTAIN TEMPORARY DUCTWORK, WIRING, AND CONDENSATE HOSES. CONCEAL WHERE POSSIBLE, OR HOLD TIGHT

EXTENSION CORDS TO RECEIVE UTILITY CORD PROVIDED WITH UNIT(S).

COORDINATE SOURCE OF ELECTRICAL POWER WITH FACILITY MANAGEMENT AND COR. PROVIDE AND INSTALL NEMA 6-20 AND UL LISTED

MAIN POWER FEED) DEDICATED TO SAFELY AND RELIABLY PLUG IN AND ENERGIZE TEMPORARY AIR CONDITIONING UNITS. CONFIRM AND

PROVIDE AND INSTALL TEMPORARY ELECTRICAL POWER (TEMPORARY CONSTRUCTION POWER PANEL - SEE ELECTRICAL DRAWING FOR

NEED.

PROVIDE ROUTINE SERVICE, MAINTENANCE, AND 24/7 ON-CALL EMERGENCY REPAIR/REPLACEMENT OF TACUs FOR THE DURATION OF

NEW WORK. RESTORE FIRE DAMPER TO OPERABLE CONDITION WITH DUCTWORK MODIFICATIONS FOR NEW RTU-1.

CLOSE EXISTING FIRE DAMPER AND CAP INDICATED DUCTS TEMPORARILY DURING USE OF TACUs. COORDINATE WITH DEMOLITION AND

NEW.

NEW DISTRIBUTION WITHOUT DISTURBING THE PORTIONS OF THE SYSTEM TO REMAIN, OR INTERFERING WITH THE INSTALLATION OF

THAN 6 TON'S DISTRIBUTION AS INDICATED. FIELD COORDINATE THE PHASING OF DEMOLITION AND NEW WORK TO UTILIZE EXISTING AND

PROVIDE ANCILLARY COMPONENTS TO ACHIEVE A COMPLETE AND OPERABLE TEMPORARY AIR CONDITIONING SYSTEM OF NOT LESS

PLACEMENT REQUIRES PHASED COORDINATION BETWEEN DEMOLITION AND NEW WORK.

BASIS OF TEMPORARY AIR CONDITIONING IS THAT FLOOR WILL REMAIN FULLY OCCUPIED DURING CONSTRUCTION. QUANTITY AND NOTE:

BID.

FOR AND LOADING. SEE TEMPORARY AIR CONDITIONER SCHEDULE. DURATION OF REQUIREMENT: ESTIMATED 2 WEEKS FOR BASIS OF

DELIVERY, SET-UP, BREAK-DOWN, AND RETURN OF RENTAL AIR CONDITIONING UNITS, TO INCLUDE FORKLIFT AND OPERATOR IF NEEDED

CONDENSATE REMOVAL; ELECTRICAL POWER FEEDS; AND LOCAL HAND/OFF/AUTO CONTROL WITH THERMOSTAT. FIELD COORDINATE

TEMPORARY AIR CONDITIONING UNITS (TACUs); WINDOW/WALL MODIFICATIONS AND RESTORATION; TEMPORARY FLEXIBLE DUCTWORK;

PROVIDE TEMPORARY AIR CONDITIONING AS A 'TURN-KEY' SERVICE TO INCLUDE BUT NOT LIMITED TO: RENTAL OF PORTABLE, INTERIOR, HZ

12.5

DESIGN

BASIS OF

MCA

MOP

20-

WB, F

R-410A

VOLT

SCHEDULE.

TACU WITH ACCESSORIES. SEE

BREAK ROOM

OFFICES, TRACON,

USES NEMA 6-20 PLUG AND RECEPTACLE.7.

INCLUDES CONDENSATE PUMP KIT, 230V PUMP KIT INCLUDES 3/8-IN DIAMETER X 20-FT LENGTH HOSE. INCLUDES INSTALLATION HARDWARE. MAXIMUM LIFT: 17 FEET6.

INCLUDES FLEXIBLE AIR DUCT, 12-IN DIAMETER FLEXIBLE DUCTWORK (UN-INSULATED) WITH TIES, CLAMPS AND FITTINGS FOR A COMPLETE CONDENSING AIR MAKE-UP AND EXHAUST. 5.

INCLUDES SUPPLY AIR NOZZLE ADAPTER KIT, 5-IN DIAMETER. ADAPTER CONVERTS AIRFLOW FROM LOUVERS TO NOZZLES OR AIR DUCTS. UP TO FOUR NOZZLES OR AIR DUCTS.4.

INCLUDES SUPPLY AIR FLANGE KIT, 5-IN DIAMETER. WHITE METAL FLANGE WITH WIRE CLAMP AND MOUNTING SCREWS. USE WITH SUPPLY AIR DUCTS.3.

INCLUDES OUTDOOR HEAT EXCHANGER PLENUM - BLACK PLASTIC PLENUM FOR RETURN AIR TO CONDENSER. HINGED FOR FILTER CLEANING.2.

INCLUDES LOCAL HAND/OFF/AUTO CONTROL PANEL; MANUAL FAN-SPEED CONTROL; CLEANABLE AIR FILTERS. 1.

PORTABLE

AIR COOLED, INTERIOR

PRO K 24 RENTAL

MOVINCOOL CLIMATE 765

NEMA 6-20

CONDENSER AIR OUT

CONDENSER AIR IN

NEMA 5-15

SEPARATION

MAXIMIZE

ROUTE THROUGH OPEN CEILING TILE

41 2 8

6 (TYPICAL)

2 (TYPICAL)

7 (3 TYPICAL)

POST

1 32 54

FLO-21000450-M013

TEMPORARY AIR CONDITIONING PLAN

flo-21000450-m013

2023-03-20T15:55:28-0400

SHANE C. HARVEY

2023-03-20T13:51:54-0400

DONALD LEE SPRINKLE

:4 lo tt e

AID0

ACUs-4, 5 OUTDOOR

DIFF

ACUs-4, 5 INDOOR

ACTUATOR

DW VALVE

DODI

FILTER

DIRTY

RA RA

AIAI

ACU CONTROLLER

ENCAPSULATED RELAY

STARTER

36"

DETECTOR

DUCT 'SMOKE'

INDICATOR

REMOTE

AIR DISCHARGE

SUPPLY

INITIATING DEVICE.

ASSIGN A UNIQUE ADDRESS TO EACH 2.

PER NFPA 72.

3' OF THE DEVICE BEING CONTROLLED

MOUNT DUCT SENSOR RELAY WITHIN 1.

EXISTING

DISCONNECT

MANUAL

RH

TACU-1

AIAI

MIX

E EXISTING

EA

EXA

A0

(TYPICAL)VAVs-1-7

SAPA

A0

SYSTEM.

EXISTING FIRE ALARM

ALARM CIRCUIT WITH

INTERFACE SUPERVISED

AI DI

AI AI

ACU-2 OUTDOOR

ACU-2 INDOOR

COMMUNICATION LINK

DO

AI AI

kele

ACUs-4, 5

UNIT.

BENEATH/BESIDE

PAN OR ON FLOOR

AUXILIARY DRAIN

LEAK DETECTOR IN

SENSOR (7 TYPICAL)

ZONE TEMPERATURE

D0D0 D0

SATISFIED.

CALCULATION TO COOL SUPPLY AIR AND IN TURN MEET SET-POINT. ACTION SHALL REVERSE AS COOLING SUPPLY AIR TEMPERATURE IS

IF SPACE TEMPERATURE IS GREATER THAN SET-POINT, THEN REFRIGERANT CIRCUIT SHALL CYCLE COMPRESSOR ACCORDING TO A PID

PROVIDE VARIABLE CAPACITY OPERATION.

COMPRESSOR HAS VARIABLE CAPACITY OPERATION FROM 20-100%. COMPRESSOR SOLENOID VALVE UNLOADS THE COMPRESSOR TO

COOLING SET-POINT TEMPERATURE SHALL BE 76 F ADJUSTABLE AT UNIT INTERFACE CONTROL PANEL.ACU-4, 5:

SATISFIED.

CALCULATION TO COOL SUPPLY AIR AND IN TURN MEET SET-POINT. ACTION SHALL REVERSE AS COOLING SUPPLY AIR TEMPERATURE IS

IF SPACE TEMPERATURE IS GREATER THAN SET-POINT, THEN REFRIGERANT CIRCUIT SHALL CYCLE COMPRESSOR ACCORDING TO A PID

COOLING SET-POINT TEMPERATURE SHALL BE 4 F HIGHER THAN ACU-4 AND 5 SET-POINTS.ACU-3:

TEMPERATURE IS SATISFIED.

ACCORDING TO A PID CALCULATION TO COOL SUPPLY AIR AND IN TURN MEET SET-POINT. ACTION SHALL REVERSE AS COOLING SUPPLY AIR

IF SPACE TEMPERATURE IS GREATER THAN SET-POINT, SHALL START FAN AND REFRIGERANT CIRCUIT, THEN CYCLE COMPRESSOR

COOLING SET-POINT TEMPERATURE SHALL BE 4 F HIGHER THAN VAV-1-7 SET-POINT.ACU-2:

OCCURRING SIMULTANEOUSLY.

A 4 F (AFG) DEADBAND SHALL EXIST BETWEEN COOLING AND HEATING SUPPLY AIR SET-POINTS TO PREVENT RESPECTIVE ACTIONS FROM

ACCORDING TO A PID CALCULATION TO MEET SET-POINT. ACTION SHALL REVERSE AS COOLING SUPPLY AIR TEMPERATURE IS SATISFIED.

IF COOLING SUPPLY AIR TEMPERATURE IS GREATER THAN SET-POINT, THEN REFRIGERATION CIRCUIT SHALL CYCLE COMPRESSORS

POLLING OF ALL TERMINAL UNITS SERVED. 'RESET' SUPPLY AIR TEMPERATURE SHALL RANGE BETWEEN 54 TO 76 F (AFG).

CLOSES, RAISE AHU SA TEMPERATURE PROPORTIONALLY). DETERMINATION OF THE GREATEST COOLING DEMAND SHALL BE BY ROUTINE

WITH THE GREATEST COOLING DEMAND (POLL ALL VAV BOXES TO FIND ONE WITH GREATEST COOLING DEMAND - AS ITS PRIMARY DAMPER

BE 54 F (AFG). IN 'RESET' MODE: SUPPLY AIR TEMPERATURE SHALL VARY INVERSELY WITH THE PRIMARY AIR DAMPER POSITION OF THE UNIT

SHALL COOL SUPPLY AIR BY OPERATOR SELECTION OF EITHER 'FIXED' OR 'RESET' MODE. IN 'FIXED' MODE: SUPPLY AIR TEMPERATURE SHALL ACU-1:

INTEGRATED AND DERIVATIVE (PID) CALCULATION BY VAV CONTROLLER. ACTION SHALL REVERSE AS SPACE TEMPERATURE IS SATISFIED

IF SPACE TEMPERATURE IS GREATER THAN SET-POINT, THEN VAV PRIMARY VALVE SHALL MODULATE OPEN ACCORDING TO A PROPORTIONAL, COOLING SET-POINT TEMPERATURE SHALL BE 76 F ADJUSTABLE AT VAV T-SENSOR OR AFG. VAV-1-7:

COOLING

REGULATED BY THE LIEBERT ICOM CONTROL THROUGH ALL MODES OF OPERATION.

ELECTRONICALLY COMMUTATED DC MOTOR, COMMONLY REFERRED TO AS AN 'EC' FAN. FAN SPEED SHALL BE VARIABLE AND AUTOMATICALLY ACU-4, 5:

BUT OPEN 100% WHEN RESPECTIVE ACU-1 IS OFF OR CONTROL COMMAND LOST.

CONTROLS SHALL ENERGIZE AT SAME TIME AS ACU-1. VAV PRIMARY AIR VALVES SHALL MODULATE TO COMMAND POSITION WHEN ENERGIZED, VAV-1 - 7:

VARIABLE AIR VOLUME

OR HAND MODE (AFG).

POINT SHALL BE DETERMINED BY MEASUREMENT AT LOCATION OF STATIC PRESSURE SENSOR FOR DESIGN AIRFLOW IN EITHER AUTOMATIC

DETERMINED BY TEST & BALANCE TO PROVIDE DESIGN AIRFLOW, OR THAT ALLOWED BY ENGINEER OF RECORD. STATIC PRESSURE SET-

SUPPLY FAN'S VARIABLE SPEED DRIVE SHALL MODULATE MOTOR SPEED TO MAINTAIN A SUPPLY AIR STAIC PRESSURE OF NOT GREATER THAN ACU-1:

SUPPLY STATIC PRESSURE CONTROL

TRACON ISOLATION DAMPERS: SHALL OPEN BY BAROMETRIC AIR PRESSURE AND CLOSE BY BALANCED WEIGHT OR SPRING ASSIST.

STARTED AND STOPPED AUTOMATICALLY BY BAS. UNIT RUNS IF ROOM TEMPERATURE IS 4 F GREATER THAN SET-POINT (AFG). ACU-2:

SATURDAY, INCLUDING HOLIDAYS. SCHEDULE IS ADJUSTABLE FROM GRAPHICS (AFG).

STARTED AND STOPPED AUTOMATICALLY THROUGH BAS. UNIT RUNS DURING NORMAL BUSINESS HOURS, 5AM TO 9PM, MONDAY THROUGH ACU- 1:

SCHEDULED MODE:

(AFG). COMPRESSOR CYCLES DEPENDING ON COOLING NEED. HUMIDIFICATION AND DE-HUMIDIFICATION OPERATES AS NEEDED.

SCHEDULE ARE ADJUSTABLE FROM GRAPHICS SEQUENCING AND PER WEEK, 24-HOURS PER DAY, INCLUDING WEEKENDS AND HOLIDAYS.

STARTED AND STOPPED AUTOMATICALLY THROUGH BAS. ALTERNATING RUN SEQUENCING: OPERATING UNIT RUNS CONTINUOUSLY: 7-DAYS ACU-4, 5:

DEPENDING ON COOLING NEED.

UNIT'…