QandA Sheet 6973GH-24-R-00022.pdf
PDF 224 KB Posted
- Attached to
- BIL-FUNDED** SOLICITATION FOR ROOF REPLACE OF THE TRACON BUILDING AT FLO AIRPORT IN FLORENCE, SC.
- Solicitation number
- 6973GH-24-R-00022
About this file
This document contains a Q&A sheet and details of a federal contract opportunity for roof replacement at a TRACON building in Florence, South Carolina. The Q&A sheet addresses a question about substituting Soprema Sentinel P150 polyvinyl chloride roofing, stating it would be considered acceptable pending the contractor's evaluation and submission for approval of factors such as membrane thickness, warranty period, fastening method, compatibility with electronics, and compliance with wind load standards and jet fume resistance. The related federal contract opportunity is solicited by the Department of Transportation Federal Aviation Administration Franchise Acquisition Services for a BIL-funded roof replacement project at the Florence Airport TRACON building. Contractors are to respond with roofing systems meeting the manufacturer evaluation and approval requirements specified in the Q&A sheet.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 6973GH-24-R-00022.pdf | ||
| Wage_Determination_Florence_County_SC.pdf | ||
| SOW - FLO Roof Replacement.pdf | ||
| Drawings_For Construction _FLO Roof.pdf | ||
| SF24 Bid Bond Form.pdf | ||
| SF25A Payment Bond Form.doc | DOC document | |
| Contractors Release Form DOT F 4220.4.doc | DOC document | |
| Specifications _ For Construction _ FLO Roof.pdf | ||
| SF25 Performance Bond Form.pdf | ||
| Offeror Organizational Experience Form.pdf | ||
| Uniform Bipartisan Infrastructure Law Report.xlsx | XLSX spreadsheet |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Q&A Sheet
6973GH-24-R-00022: FLO TRACON ROOF
Q1. I would like to submit a substitution request for Soprema Sentinel P150 as an option for the polyvinyl-chloride (PVC) roofing specified in section 075419.
A. SOPREMA shall be considered an acceptable manufacturer of PVC roofing product in accordance with Part 2 – Products paragraph 2.6 A.1. of the project specifications.
However, which PVC membrane product by SOPREMA (as with the other listed manufactures) is approved for use, shall be evaluated and proposed by the installing contractor taking into consideration their respective roofing manufacturer’s recommendations, and submitted to the FAA for review and approval prior to use. As a minimum, consideration shall be given the following:
1) minimum 60 mils PVC
2) minimum 20 year roof warranty
3) mechanically fastened or fully adhered depending upon installing contractor’s evaluation of existing conditions
4) induction welding process is not allowed (suspected electronics interference)
5) results of substrate pull test and compliance with prevailing building code requirements regarding wind loading
6) resistance to jet fumes