GENERAL REPAIR REPORT - SV.pdf
PDF 7 MB Posted
- Solicitation number
- 6973GH-20-R-000191
About this file
This solicitation is for tower strengthening and repair work at three locations in Texas. The Federal Aviation Administration seeks firm fixed-price proposals to repair towers in Corrizo Springs, Laredo, and Fort Davis in accordance with the specifications. The NAICS code is 237130 and the size standard is $39.5 million. Offerors must register in SAM and submit all requested information for eligibility. Questions are due by September 17 and the response deadline was not provided.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE UNITED STATES
GOVERNMENT
COPYING, DISSEMINATION, OR
DISTRIBUTION OF THIS DOCUMENT TO
UNAUTHORIZED RECIPIENTS IS
PROHIBITED
Do not remove this notice
Properly destroy or return documents when no longer needed
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Texas Firm No. F-11847
STRUCTURAL AND CONDITION ASSESSMENT REPORT
FOR
[SIERRA VIEJA] TX8584
80’ GUYED TOWER
VALENTINE, JEFF DAVIS COUNTY, TEXAS
TEP # 63591_37920
Revision 1
January 8, 2016
Revision # Date Issued Description
0 November 19, 2015 Original issued document
1 January 8, 2016 Revised per client request
Respectfully Submitted By:
Prepared For:
US Army Corps Of Engineers ®
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Date: January 8, 2016
Lesley R. Schwalje, P.E. Tower Engineering Professionals
HNTB - Halff JV 326 Tryon Road
5910 W. Plano Pkwy, Suite 200 Raleigh, NC 27603
Plano, TX 75093 (919) 661-6351
(214) 557-1745 mgardner@tepgroup.net
Subject: Executive Summary - Revision 1
Tower Designation: Site Name: Sierra Vieja
TRIRIGA BU Number: TX8584
Engineering Firm Designation: TEP Project Number: 63591_37920
Site Data: 12.5± Miles West of Valentine, Jeff Davis County, TX 79854
Lat., Long.: 30.579800, -104.706600 (N 30° 34' 47.28'', W 104° 42' 23.76'')
80 Foot – Guyed Tower
Tower Engineering Professionals (TEP) is pleased to provide this executive summary for the Phase I Scope of Work, which included a Maintenance and Condition Assessment, Capital Expenditure Table, Steel and Appurtenance
Mapping, and Structural Analysis for the above referenced site.
Maintenance and Condition Assessment
Overall Tower Condition (Excellent/Good/Average/Fair/Poor): Average*
Tower Type: 80-ft guyed tower
Tower Age: Approximately 20-30 years**
Number of Guy Wires: 2 Levels (39.7’, 79.7’)
Tower Access Road Condition: Good, no obstacles or issues encountered
A periodic inspection for the above referenced site was performed by Kyle Underhill, E.I. and Jeremiah Fox of TEP during the October 1st, 2015 site visit. The inspection was in accordance with the ANSI/TIA-222-G-2005, Annex J:
Maintenance and Condition Assessment (Normative). TEP observed the following checklist items requiring some measure of possible or required corrective action: 1) Structure Condition, 2) Finish, 3) Grounding, 4) Antennas and
Lines, 5) Guys, 6) Concrete Foundations, and 7)Tower Alignment. Refer to the Maintenance and Condition
Assessment Report for specific details.
*TEP defines the tower conditions as follows:
Excellent - The tower has sufficient capacity to carry the existing loads. No modifications are required at this time. In addition, the tower has no maintenance issues of note and doesn’t require maintenance repairs at this time.
Good - The tower has sufficient capacity to carry the existing loads. No modifications are required at this time. However, the tower has some maintenance issues of note that require attention.
Average - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the
ANSI/TIA-222-G standard for the existing loading. In addition, the tower may have minor maintenance issues of note that require attention.
Fair - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the ANSI/TIA-
222-G standard for the existing loading. In addition, the tower has maintenance issues of note that require attention. Based on the itemized estimate in our Capital
Expenditure Table, modifying the existing tower may be the most cost effective solution.
Poor - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the ANSI/TIA-
222-G standard for the existing loading. In addition, the tower has maintenance issues of note that require attention. Based on the itemized estimate in our Capital
Expenditure Table and/or the condition of the tower, a full tower replacement may be the best solution.
**Tower Age was estimated based on tower identification tags, tower manufacturer information, tower research, type and condition of tower components, and/or historical site images
Texas Firm No. F-11847
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP Project Number 63591_37920, Revision 1 January 8, 2016
Sierra Vieja (TX8584)
Tower Engineering Professionals 326 Tryon Road, Raleigh, NC 27603 (o) 919-661-6351 (f) 919-661-6350 www.tepgroup.net
Condition Assessment of Non-Tower Assets
During the site visit, TEP conducted a visual inspection of all Non-Tower Owned Assets. TEP did not find any non-tower assets that require urgent corrective repairs. However, TEP recommends regular inspection and maintenance by licensed professionals based on manufacturer specifications. Refer to Section L of the Maintenance and Condition
Assessment Report for any applicable additional information.
Asset Type Coordinates Condition Notes
Estimated
Remaining
Life
CBP Shelter/
Roof Concrete
30.579836, -104.706600 Good
Structure appears to be in good condition, no major issues visible 10+ years
Shelter
Access
(2) Single
Doors
30.579836, -104.706600 Good
(2) doors located on east side of shelter, door and door frame are in good condition 10+ years
Power
Supply Generator
30.579836, -104.706600 Good
Kohler manufacturer tag, inside shelter, appears to be in good condition, no major issues visible
10+ years
Power
Supply Battery
30.579836, -104.706600 Good
On the floor of the shelter, there is a battery wired to cellular equipment 5-10 years
Cellular
Receivers
30.579836, -104.706600 Good
CBP Shelter houses various units associated with communication equipment 10+ years
Exhaust Fan Through
Wall
30.579836, -104.706600 Good
(2) fans appears to be in good working condition 5-10 years
Heating Unit Wall
Mounted
30.579836, -104.706600 Good
HVAC unit mounted to exterior of shelter, appear to be in good condition 5-10 years
Fuel Tank Metal 30.579850, -104.706644 Good
Trinity Industries manufacturer tag, tank appears to be in good working condition 10+ years
Capital Expenditure Table
A cost estimate of $50,350 was provided to cover repairs as recommended in the Maintenance and Condition
Assessment Report and the Structural Analysis Report. The recommended repair schedule ranges from 6 months to 5 years. Note that this estimate does not include any foundation reinforcements that may be required. TEP cannot say with certainty that a replacement would be more cost effective than modifying the existing tower without completing a Structural Modification Design Analysis. For itemized repairs, refer to the Capital Expenditure Table for details. TEP estimated a ROM cost for full tower replacement would range from approximately $150,000 for a 100-ft guyed tower to $225,000 for a 300-ft guyed tower. These estimates do not include pricing for site specific costs related to zoning, permitting, environmental studies, etc.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Steel and Appurtenance Mapping
The original design criteria were unavailable for review. A Steel and Appurtenance Mapping was performed in order to obtain the necessary tower and appurtenance loading information needed to conduct the Structural Analysis for this site. The antennas recorded during our Steel and Appurtenance Mapping are depicted in the table below. TEP denoted the owner of the equipment under the “Owner/Tenant” column based on information available on site.
Refer to the Steel and Appurtenance Mapping Report for additional detail.
Elevation
(ft) Qty Antenna Model
Mount
Type
Owner/
Tenant
78.7 1 3ӯ x 3-ft 2-Pole Antenna Side Arm CBP
78.6 2 22-ft x 4-Element Dipole Side Arm CBP
77.6 1 Scala CL-400A Side Arm CBP
77.1 1 Scala CL-400A Side Arm CBP
72.1 1 6-Element Yagi Direct CBP
69.3 1 6-Element Yagi Direct CBP
64.5 1 Radiation Systems P-17A96F Dish Mount CBP
52.8 1 22-ft x 4-Element Dipole Side Arm CBP
35.0 1 6-Element Yagi Direct CBP
25.5 1 Radiation Systems P-17A72GP Dish Mount CBP
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Structural Analysis
LC1: Existing Equipment Insufficient Capacity Note: See Table 1 for the existing loading
Thank you for the opportunity to provide this service for you. If you have any questions or comments, please contact our office.
Component % Capacity
Leg (T2) 47.5%
Diagonal (T2) 147.5%
Horizontal (T1) 31.6%
Top Girt (T3) 16.3%
Bottom Girt (T3) 28.6%
Guy A (T1) 66.7%
Guy B (T1) 68.5%
Guy C (T1) 71.4%
Top Guy Pull-Off (T4) 39.7%
Torque Arm Top (T1) 31.8%
Torque Arm Bottom (T1) 43.3%
Bolt Checks 41.5%
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
The Structural Analysis report outlines overstresses in the diagonals at the 40’ to 80’ elevations. TEP believes that the majority of the overstresses can be attributed to the more stringent loading and analysis criteria as required by the latest ANSI/TIA-222-G-2-2009 Standard, as compared to previous versions of the TIA Standard for which the tower was originally designed. Based on our analysis we have determined the tower stress level for each controlling component, under the following load case, to be:
MASTER TABLE OF CONTENTS
���� MAINTENANCE AND CONDITION ASSESSMENT
���� CAPITAL EXPENDITURE TABLE
���� ANNEX A: STEEL AND APPURTENANCE MAPPING
���� ANNEX B: STRUCTURAL ANALYSIS
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
MAINTENANCE AND CONDITION ASSESSMENT
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
HNTB-Halff JV 326 Tryon Road
5910 W. Plano Pkwy., Suite 200 Raleigh, NC 27603
Plano, TX 75093 (919) 661-6351
(214) 557-1745 mgardner@tepgroup.net
Subject: Maintenance and Condition Assessment Report - Revision 1
Tower Designation: Site Name: Sierra Vieja
TRIRIGA BU Number: TX8584
Engineering Firm Designation: TEP Project Number: 63591_37920
Site Data: 12.5± Miles West of Valentine, Jeff Davis County, TX 79854
Lat., Long.: 30.579800, -104.706600 (N 30° 34' 47.28'', W 104° 42' 23.76'')
80 Foot – Guyed Tower
Dear Ms. Schwalje, Tower Engineering Professionals (TEP) completed a periodic inspection for the above referenced site. The onsite investigation was performed by Kyle Underhill, E.I. and Jeremiah Fox of TEP during the October 1st, 2015 site visit. The inspection was in accordance with the ANSI/TIA-222-G-2005, Annex J: Maintenance and Condition Assessment
(Normative), including all addendums (addendums TIA-222-G-1 2007 and TIA 222-G-2 2009); the checklist can be found on pages 3 thru 8 of this report.
Observations and recommendations are listed herein. The inspection included observation of tower components and
CBP owned assets. For the purpose of this inspection, the tower legs were named by letter according to the magnetic azimuth defined by a line from the center of tower to the leg. “A” leg is the leg closest to magnetic north, followed clockwise by “B” and “C.” Guy wires were numbered from the ground up. Guy wires 1 thru 2 are at the 39.7-ft and
79.7-ft elevations respectively.
Thank you for the opportunity to provide this service for you. If you have any questions or comments, please contact our office.
Texas Firm #: F-11847
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Guyed Tower Maintenance and Condition Assessment Report January 8, 2016
TEP Project Number 63591_37920, Revision 1 TX8584 - Sierra Vieja
TABLE OF CONTENTS
1) ANSI/TIA-222-G-MAINTENANCE AND CONDITION ASSESSMENT
2) SUMMARY
3) APPENDIX A
Guy Tensions
4) APPENDIX B
Tower Plumb and Twist Measurements
5) APPENDIX C
Typical Guy Anchor Configuration
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANSI/TIA-222-G MAINTENANCE AND CONDITION ASSESSMENT
A. STRUCTURE CONDITION
A.1. Damaged members (legs and bracing)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
A.2. Loose members
Okay Possible Improvement Needs Repair Not Applicable
Notes:
A.3. Missing members
Okay Possible Improvement Needs Repair Not Applicable
Notes:
A.4. Climbing facilities, platforms, catwalks – all secure
Okay Possible Improvement Needs Repair Not Applicable
Notes: Corrosion was noted on safety cable restraint bolts. See summary for details.
A.5. Loose and/or missing bolts and/or nut locking devices
Okay Possible Improvement Needs Repair Not Applicable
Notes:
A.6. Visible cracks in welded connections
Notes:
B. FINISH
B.1. Paint and/or galvanizing condition
Notes: Deteriorated galvanizing coating observed. See summary for details.
B.2. Rust and/or corrosion condition including mounts and accessories
Okay Possible Improvement Needs Repair Not Applicable
Notes: Surface corrosion was observed throughout the entire tower. See summary for details.
B.3. FAA or ICAO color marking conditions
Okay Possible Improvement Needs Repair Not Applicable
Notes:
B.4. Water collection in members (to be remedied, e.g., unplug drain holes, etc.)
Okay Possible Improvement Needs Repair Not Applicable
Notes: All tower members are solid round or angle.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
C. LIGHTING
C.1. Conduit, junction boxes, and fasteners (weather tight and secure)
Notes: No lighting equipment installed on tower.
C.2. Drains and vents openings (unobstructed)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.3. Wiring Condition
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.4. Light lenses
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.5. Bulb condition
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.6.a. Controllers functioning (Flasher)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.6.b. Controllers functioning (Photo control)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.6.c. Controllers functioning (Alarms)
Notes: Could not verify.
D. GROUNDING
D.1. Connections
Notes:
D.2. Corrosion
Okay Possible Improvement Needs Repair Not Applicable
Notes:
D.3. Lightning protection (secured to structure)
Okay Possible Improvement Needs Repair Not Applicable
Notes: No lightning rod attached to top of tower. Structure is grounded so addition of homerun grounding wire is up to tower owner’s discretion.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E. ANTENNAS AND LINES
E.1. Antenna condition
Notes: Damaged/disconnected antenna located at top of tower. See summary for details.
E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)
Okay Possible Improvement Needs Repair Not Applicable
Notes: Loose bolt, bent threaded rod, and surface corrosion located on antenna mount and connections. See summary for details.
E.3. Feed line condition (flanges, seals, dents, jacket damage, grounding, etc.)
Okay Possible Improvement Needs Repair Not Applicable
Notes: Feed line weatherproofing deteriorated and disconnected from antenna. See summary for details.
E.4. Hanger condition (snap-ins, bolt on, kellum grips, etc.)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
E.5. Secured to structure
F. OTHER APPURTENANCES (WALKWAYS, PLATFORMS, SENSORS, FLOODLIGHTS, ETC.)
F.1. Condition
Notes:
F.2. Secured to structure
G. INSULATOR CONDITION
G.1. Cracking and chipping
Notes:
G.2. Cleanliness of insulators
Okay Possible Improvement Needs Repair Not Applicable
Notes:
G.3. Spark gaps set properly
Okay Possible Improvement Needs Repair Not Applicable
Notes:
G.4. Isolation transformer condition
Okay Possible Improvement Needs Repair Not Applicable
Notes:
G.5. Bolts and connection secure
Okay Possible Improvement Needs Repair Not Applicable
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
H. GUYS
H.1. Strand condition (corrosion, breaks, nicks, kinks, etc.)
Notes:
H.2.a. Guy Hardware Conditions (Turnbuckles or equivalent (secure and safety properly applied)
Okay Possible Improvement Needs Repair Not Applicable
Notes: Improper installation of safety wires observed. See summary for details.
H.2.b. Guy Hardware Conditions (Cable thimbles properly in place (if required))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.c. Guy Hardware Conditions (Service sleeves properly in place (if required))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.i. Guy Hardware Conditions (Cable connectors (end fittings) (Cable clamps applied properly and bolts tight)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.ii. Guy Hardware Conditions (Cable connectors (end fittings) (Wire serving properly applied))
Okay Possible Improvement Needs Repair Not Applicable
Notes: Refer to item H.2.a.
H.2.d.iii. Guy Hardware Conditions (Cable connectors (end fittings) (No signs of slippage or damaged strands))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.iv. Guy Hardware Conditions (Cable connectors (Preformed wraps – properly applied, fully wrapped, & sleeve in place))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.v. Guy Hardware Conditions (Cable connectors (end fittings) (Poured sockets secure and showing no separation))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.vi. Guy Hardware Conditions (Cable connectors (Shackles, bolts, pins, and cotter pins secure and in good condition))
Okay Possible Improvement Needs Repair Not Applicable
Notes: Guy wire connection shackles have no nut locking devices.
H.3. Guy tensions
Okay Possible Improvement Needs Repair Not Applicable
Notes: Guy tensions not within the ANSI/TIA-222-G-2005 recommended limits. See summary for details.
H.4. Measure guy tensions
Okay Possible Improvement Needs Repair Not Applicable
Notes: Tensions measured using a Dillon tension meter.
H.5. Record temperature, wind speed and wind direction
Notes: Temperature was 87 degrees Fahrenheit at the time of measurement.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
I. CONCRETE FOUNDATIONS
I.1.a. Ground condition (Settlement, movement or earth cracks)
Notes:
I.1.b. Ground condition (Erosion)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.1.c. Ground condition (Site condition (standing water, drainage, trees, etc.))
Okay Possible Improvement Needs Repair Not Applicable
Notes: Excess vegetation observed at compound, equipment shelter, and anchor locations. See summary for details.
I.2.a. Anchorage condition (Nuts and/or nut locking device (tightened))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.2.b. Anchorage condition (Grout condition)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.2.c. Anchorage condition (Anchorages and/or anchor rod condition)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.3.a. Concrete condition (Cracking, spalling, or splitting)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.3.b. Concrete condition (Chipped or broken concrete)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.3.c. Concrete condition (Honeycombing)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.3.d. Concrete condition (Low spots to collect moisture)
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
J. GUYED MAST ANCHORS
J.1. Settlement, movement or earth cracks
Notes:
J.2. Backfill heaped over concrete for water shedding
Okay Possible Improvement Needs Repair Not Applicable
Notes:
J.3. Anchor rod condition below earth (Maintain required structural capacity of anchor during exploration.)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
J.4. Corrosion control measures (galvanizing, coating, concrete encasement, cathodic protection systems, etc.)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
J.5. Anchor heads clear of earth
K. TOWER ALIGNMENT
K.1. Tower Plumb and Twist
Notes: Tower twist and plumb not within ANSI/TIA-222-G-2005 recommended limits. See Appendix B for details.
L. NON-TIA RELATED ITEMS
L.1. Equipment Shelter
Notes:
L.2. Security
Okay Possible Improvement Needs Repair Not Applicable
Notes: Perimeter fencing was observed missing around compound and guy anchor locations. See summary for details.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
SUMMARY
Photograph Observations and Recommendations
A.4. Climbing Facilities, platforms, catwalks - all secure
Observation:
Surface corrosion was noted on safety cable restraint throughout the tower height.
Recommendation:
Replace any safety wire restraints that have experienced corrosion.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
B.1. Paint and/or galvanizing condition
Deteriorated galvanizing condition was observed throughout the entire tower height.
Thoroughly clean areas of corrosion and coat with at least two coats of ZRC cold galvanizing compound or approved equivalent. During or before cleaning, if any hardware exhibits section loss, pitting, or holes, they should be replaced.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
B.2. Rust and/or corrosion condition including mounts and accessories
Surface corrosion was observed throughout the tower height including mounts located at:
• 41.5-ft (A-Leg)
• 61.5-ft (A-Leg)
• 78.6-ft (C-Leg)
Thoroughly clean areas of corrosion and coat with at least two coats of ZRC cold galvanizing compound or approved equivalent. During or before cleaning, if any hardware exhibits section loss, pitting, or holes, they should be replaced.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E.1. Antenna Condition
Damaged antenna observed at the following locations on the tower:
• 72.1-ft : 5-ft Yagi Antenna (A-Leg)
• 78.6-ft: Dipole Antenna (C-Leg)
Notify the carrier about the condition and possible repair of the damaged antenna.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)
Loose bolt located on antenna mount at the following location:
• 25-ft : 8-ft Grid Dish (C-Leg)
Bent threaded rod on antenna mount at the following location:
• 61.5-ft : Dipole Antenna (C-Leg)
Ensure that a proper nut locking device is installed and tighten nut per the AISC “turn of the nut method”.
Remove threaded rods and replace with new threaded rods equivalent in size, length, and strength. Ensure that a proper nut locking device is installed and tighten nut per the AISC “turn of the nut method”.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E.3. Feed line condition (flanges, seals, dents, jacket damage, grounding, etc.)
Feed line weatherproofing deteriorated and disconnected from antenna at the following location on the tower:
• 25-ft : 8-ft Grid Dish (C-Leg)
Re-seal the feed-line jumper connections and jumper to antenna connections to ensure the lines are weather tight. If feed line has been cut, ensure there are no future plans for the cut feed line then remove it from the tower.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
H.2.a Guy Hardware Conditions (Safety Properly Applied)
Improper installation of guy wire safety cable observed at the following locations
• Anchor A, all guy levels
• Anchor B, all guy levels
• Anchor C, all guy levels
Reinstall turnbuckle safety cables so they are looping through the thimbles with 2 Crosby clamps. See Appendix C for proper installation of turnbuckle safety loops.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
H.2.d.vi. Guy Hardware Conditions (Cable connectors
(Shackles, bolts, pins, and cotter pins secure and in good condition))
Guy wire connection shackles have no nut locking devices.
Install mousing wire to prevent shackle pins from loosening.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
I.1.c. Ground condition (site condition)
Excess vegetation observed at compound, equipment shelter, and anchor locations.
Compound perimeter and anchor locations should be cleared of vegetative growth and maintained to prevent future growth.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
L.1. Security
Perimeter fencing observed missing.
Tower owner determines if fencing should be installed around the compound and guy anchor locations.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
APPENDIX A: GUY TENSIONS
Table A-1 (Assumed Initial Tension is 10% of Breaking Strength)
Guy
Path
Guy #
Guy Size
(diameter in inches)
Measured
-10% of Initial
Tension at 60°°°°F
(lbs)
+10% of Initial
Tension at 60°°°°F
(lbs)
Measured tension converted to
60°°°°F (lbs)
Results
A
1 at 39.7’ 9/16 3150 3850 4242 HIGH
2a at 79.7’ 7/16 1872 2288 1972 OK
2b at 79.7’ 7/16 1872 2288 1952 OK
B
1 at 39.7’ 9/16 3150 3850 4562 HIGH
2a at 79.7’ 7/16 1872 2288 1612 LOW 2b at 79.7’ 7/16 1872 2288 2352 HIGH
C
1 at 39.7’ 9/16 3150 3850 3919 HIGH
2a at 79.7’ 7/16 1872 2288 2090 OK
2b at 79.7’ 7/16 1872 2288 1970 OK
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
APPENDIX B: TOWER PLUMB AND TWIST MEASUREMENTS
Table B-1: Tower Twist Measurements
Reference
(above conc.)
Twist with
Respect
To Base (°°°°)
Allowable Twist with Respect
To Base (°°°°)
Relative Twist
Between Reference
Elevations (°°°°)
Allowable Twist
Between Reference
Elevations (°°°°)
T o w e r T w is t M e a su re m e n ts
80-ft 4.22 ± 4.00
0.00 ± 1.00
60-ft 4.22 ± 3.00
0.00 ± 1.00
40-ft 4.22 ± 2.00
0.00 ± 1.00
20-ft 4.22 ± 1.00
4.22 ± 1.00
0-ft 0.00 ± 0.00
Table B-2: Lateral Deflection Measurements
Reference
(above conc.)
Resultant
Deflection (in)
Allowable
Resultant
Deflection (in) per TIA
Resultant Deflection
Between Reference
Elevations (in)
Allowable Deflection
Between Reference
Elevations (in) per TIA
T o w e r D e fl e ct io n
M e a su re m e n ts
80-ft 0.00 ± 2.40
0.00 ± 0.60
60-ft 0.00 ± 1.80
0.00 ± 0.60
40-ft 0.00 ± 1.20
0.00 ± 0.60
20-ft 0.00 ± 0.60
0.00 ± 0.60
0-ft 0.00 ± 0.00
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
APPENDIX C: TYPICAL GUY ANCHOR CONFIGURATION
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
CAPITAL EXPENDITURE TABLE
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANSI/TIA-222-G: CAPITAL EXPENDITURE TABLE
Job Name: Sierra Vieja
TEP Number: 63591_37920, Revision 1
A. STRUCTURAL CONDITION
Issue: Repair/Modification: Repair Schedule:
A.1. Damaged members (legs and bracing)
a. The following members were failing under existing loading conditions in the structural analysis:
- Diagonals from 40-ft to 80-ft
i. Complete repairs as specified in Structural
Design Drawings
0-1 year $20,500
Sub Total: $20,500
A.4. Climbing facilities, platforms, catwalks – all secure
a. Corrosion was noted on safety cable restraint throughout the tower height.
i. Replace safety cable restraint. 0-1 year $750
Sub Total: $750
Total: $21,250
B. FINISH
Issue: Repair/Modification: Repair Schedule:
B.1. Paint and/or galvanizing condition
a. Deteriorated galvanizing condition throughout entire tower height.
i. Regalvanize the tower. 0-5 years $9,000
Sub Total: $9,000
B.2. Rust and/or corrosion condition including mounts and accessories
a. Surface corrosion throughout entire tower height. Refer to item B.1. 0-6 months $0
Sub Total: $0
Total: $9,000
C. LIGHTING
NO DEFICIENCIES WERE IDENTIFIED
D. GROUNDING
Issue: Repair/Modification: Repair Schedule:
D.3. Lightning protection (secured to structure)
a. No lightning rod attached to top of tower. Structure is grounded so addition of homerun grounding wire is up to tower owner’s discretion.
i. Install lightning rod system. 0-5 years $1,500
Sub Total: $1,500
Total: $1,500
*Items that don't require attention were omitted from this list of itemized modification costs. For a full itemized list of everything that was assessed during our site visit please reference the Maintenance and Condition Assessment.
Fee:
Modification Fee:
Fee:
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E. ANTENNAS AND LINES
Issue: Repair/Modification:
E.1. Antenna condition
Damaged antenna observed at the following locations on the tower:
• 72.1-ft : 5-ft Yagi Antenna (A-Leg)
• 78.6-ft: Dipole Antenna (C-Leg)
i. Repair/replace antennas $0
Sub Total: $0
E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)
Loose bolt located on antenna mount at the following location:
• 25-ft : 8-ft Grid Dish (C-Leg)
Bent threaded rod on antenna mount at the following location:
• 61.5-ft : Dipole Antenna (C-Leg)
i. Tighten the nut per the AISC "turn of the nut method". ii. Replace threaded rods
$750
Sub Total: $750
E.3. Feed line condition (flanges, seals, dents, jacket damage, grounding, etc.)
Feed line weatherproofing deteriorated and disconnected from antenna at the following location on the tower:
• 25-ft : 8-ft Grid Dish (C-Leg)
i. Repair or remove feed line. $750
Sub Total: $750
Total: $1,500
F. OTHER APPURTENANCES (WALKWAYS, PLATFORMS, SENSORS, FLOODLIGHTS, ETC.)
NO DEFICIENCIES WERE IDENTIFIED
G. INSULATOR CONDITION
NO DEFICIENCIES WERE IDENTIFIED
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
H. GUYS
Issue: Repair/Modification: Repair Schedule:
H.2.a. Guy Hardware Conditions (Turnbuckles or equivalent
(secure and safety properly applied)
a. Turnbuckle safety cables are attached with only (1)
Crosby clamp and installed incorrectly.
i. Install/replace guy wire hardware as required.
0-6 months $650
Sub Total: $650
H.2.d.ii. Guy Hardware Conditions (Cable connectors (end fittings) (Wire serving properly applied))
a. Wire servings not currently installed on guy wires. Refer to item H.2.a. 0-1 year $650
Sub Total: $650
H.2.d.vi. Guy Hardware Conditions (Cable connectors
(Shackles, bolts, pins, and cotter pins secure and in good condition))
a. Surface corrosion and pitting on cotter pin of inside anchor C, guy level 2.
b. No nut locking devices installed on turnbuckle bolts.
i. Replace guy wire hardware as required.
Ii. Install nut locking devices.
0-6 months $650
Sub Total: $650
H.3. Guy tensions
a. Guy wire tensions were not within acceptable limits per
ANSI/TIA-222-G-2005.
i. Re-tension guy wires. 0-1 year $3,000
Sub Total: $3,000
Total: $4,950
I. CONCRETE FOUNDATIONS
Issue: Repair/Modification: Repair Schedule:
I.1.c. Ground condition (Site condition (standing water, drainage, trees, etc.))
Excess vegetation observed at compound, equipment shelter, and anchor locations.
i. Clear compound and anchor locations of excess vegitation.
$650
Sub Total: $650
Fee:
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
J. GUYED MAST ANCHORS
NO DEFICIENCIES WERE IDENTIFIED
K. TOWER ALIGNMENT
Issue: Repair/Modification: Repair Schedule:
K.1. Tower Plumb and Twist
a. Tower twist and plumb were not within acceptable limits per ANSI/TIA-222-G-2005.
i. Re-tension guy wires to bring tower within acceptable limits.
0-1 year $0
Sub Total: $0
Total: $0
L. NON-TIA RELATED ITEMS
Issue: Repair/Modification: Repair Schedule:
L.2. Security
a. Perimeter fencing was observed missing around compound and guy anchor locations. See summary for details.
i. Tower owner determines if fencing should be installed around the compound and guy anchor locations.
0-1 year $8,500
Sub Total: $8,500
Total: $8,500
OTHER CONSTRUCTION COSTS
Item:
a. Permits / Application Fees $1,000
b. Post Modification Inspection Report $2,000
c. Mobilization Costs
Sub Total: $3,000
Total: $3,000
GRAND TOTAL: $50,350
Fee:
Fee:
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANNEX A:
STEEL AND APPURTENANCE MAPPING
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
Page Title Initials Page # (s) Notes Checklist & Notes
Ladder
Tower Elevation
Latitude: Longitude:
Ground Elevation:
Site Address:
Special Access Issues (Key Entry, Hidden/Unmarked Access, FM/TV on tower):
FCC#:
Tower ID Plate:
Existing Carriers/Site #:
Gate Combo:
Telephone Company:
Pedestal # and Location:
Power Company:
Meter # and Owner:
30.579800 (N 30° 34' 47.28")
5785' ± (GOOGLE EARTH)
12.5± MILES WEST OF VALENTINE, TX 79854 (JEFF DAVIS COUNTY)
N/A
CNR
CNR
CNR
RIO GRANDE ELEC COOP INC
49 951 934
N/A
-104.706600 (W 104° 42' 23.76")
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna and Mount Sketch
Guy Anchor Details
EAE
Signature of Crew Leader
Print Name:
Signature of Crew Member
Print Name:KYLE R. UNDERHILL
Transmission Cables
Abbreviations: AGL: Above Ground Level BP: Bent Plate B-B: Bolt to Bolt C-C: Center to Center C: Channel CNR: Could Not Record EW: Elliptical Waveguide FH: Foam Heliax
L: Angle 2L: Double Angle MC: Metal Conduit ME: Minimum Edge MOD: Modification PL: Plate RC: Rigid Conduit RHSS: Round Hollow Struct. Section
S.B.: Stitch Bolts Schl: Schifflerized Angle SM: Smooth Heliax SP: Spacing SR: Solid Rod Th: Thickness Tri: Triangular
EAE
EAE
EAE
EAE
EAE
EAE
Torque Arm Detail
Compound Detail EAE
Typical Tower Section Detail 6-8EAE
12-19
Waveguide Ladder 4EAE
JEREMIAH FOX
NONE
20-21Photos EAE
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
CBP
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
COMPOUND DETAIL
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Plan View
Access Road Equipment Shelter Compound View
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
LADDER
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Climbing Ladder #1 Sketch
Description Ladder
# Height Width Step Rail (type & size) Rung (type & size) Safety (type & size)
Climbing Ladder #1 Photo
18" 39" A & C LEGS 5
8"Ø SR 3
8"Ø10'-0" - 80-0"1
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
WAVEGUIDE
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Waveguide #1 Sketch
Description Waveguide
# Height Width Step Rail (type & size) Rung (type & size) Holes
Waveguide #1 Photo
38" 39" A & C LEGS L 2" x 2" x 18" (12) 34"10'-0" - 80'-0"1
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
21TOWER ELEVATION 5
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
TOWER SECTION ELEVATION
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
MEMBER SIZES
Member Size Bolts Stitch Bolts Gusset/Flange
LEG 1.75"Ø SR (3) 34"Ø N/A
▲ 61
2"x61 2"x34"
H1 5
8"Ø SR WELD N/A -
D1 5
8"Ø SR WELD N/A -
H2 L 11 2x11
2x316 WELD N/A - D2 7
8"Ø SR WELD N/A -
LADDER 5
8"Ø SR WELD N/A -
Face Width: 36"
Section 1 (0'-20') Photo
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
TOWER SECTION ELEVATION
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
MEMBER SIZES
Member Size Bolts Stitch Bolts Gusset/Flange
LEG 1.75"Ø SR (3) 34"Ø N/A
▲ 61
2"x61 2"x34"
H1 L11 2"x11
2"x316" WELD N/A - D1 7
8"Ø SR WELD N/A -
Face Width: 36"
Sections 2-3 (20'-60') Photo
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
TOWER SECTION ELEVATION
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
MEMBER SIZES
Member Size Bolts Stitch Bolts Gusset/Flange
LEG 1.75"Ø SR (3) 34"Ø N/A
▲ 61
2"x61 2"x34"
H1 L11 2"x11
2"x316" WELD N/A - D1 7
8"Ø SR WELD N/A -
D2 5
8"Ø SR WELD N/A -
Face Width: 36"
Sections 4 (60'-80') Photo
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANCHOR HEAD
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Photo
Guy #1-3 Connection at Tower
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
Guy #
2A
Pin Hole Min Edge Turnbuckle (Type & Size) (A-Anchor)
Turnbuckle Gap (B-Anchor) (C-Anchor)
Guy Wire (Diameter)
Guy Wire (# of Strands)
7/16"
Preform (Color)
GREEN
8"
Shackle (Type & Size)
Lug Hole (Diameter)
1 58"
Lug Hole (Min. Edge)
Guy Lug (Type & Size)
Guy Lug (Connection)
Guy Banding
1 78" (3) 34"Ø BOLTS
Elevation (At Tower)
79'-8" 39'-8"
Guy #
2A
1 WELD1 12"
9/16"
N/A 1" SEE DRAWING
YELLOW
Ring:
Anchor Rod:
Anchor Loop:
Radius (A - Anchor):
Radius (B - Anchor):
Radius (C - Anchor):
Anchor Head Thickness:
SINGLE
PL 11
2"x1" 16"Ø
Elevation:
Elevation:
Elevation:
Anchor Holes:
1 - GUY 1
2 - GUY 2A
3 - GUY 2B
66.5' 66.5' 66.0'
+0 +0 +0
1"Ø 5 12"3
4" J-E 1 12"
PL 10"x 12"
5"7 8" J-E
2B 77/16" GREEN 6 12"3
4" J-E
2B
1 12" 4 12"
4" 6"
7 12"
5 14"
N/A
8" 1 58" 1 78"
1 12" 1 12"
PL 10"x 12" (3) 34"Ø BOLTS N/A N/A79'-8"
4"
1"Ø 1"Ø
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
A
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
TORQUE ARM DETAIL
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
PHOTOS PLAN VIEW
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
1-2 3-5
6-9
45°
165°285°
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
TRANSMISSION CABLES
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Color Code: B = Blue, Br=Brown, G = Green, O = Orange, R = Red, W = White, Y = Yellow Coax# Type/ Size Height Antenna Color Code Carrier Notes
1 FH 78 10' - 56'-8" 3 - CBP -
2 FH 78 10' - 77'-1" 6, 7 - CBP -
3 FH 78 10' - 77'-7" 8 - CBP -
4 3
8"Ø SM 10' - 78'-8" 9 - CBP -
5 3
8"Ø SM 10' - 35'-0" 2 - CBP -
6 FH 78 10' - 64'-6" 4 - CBP -
7 FH 78 10' - 25'-6" 1 - CBP -
8 FH 78 10' - 69'-3" 5 - CBP -
9 FH 78 10' - 79'-7" 11 - CBP -
ANT 10 HAS NO COAX
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
RADIATION SYSTEMS P-17A72GP - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier
CBP
Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
Mount Elevation LegAntenna # 1 25'-6" A
Mount Type Azimuth
PIPE 340°
Antenna Elevation 25'-6"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
NONE 5-FT 6-ELEMENT YAGI - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier
CBP
Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
Mount Elevation LegAntenna # 2 - A
Mount Type Azimuth
DIRECT N/A
Antenna Elevation 35'-0"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
UNKNOWN 22-FT 4-ELEMENT DIPOLE - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
- -- -CBP
Mount Elevation LegAntenna # 3 52'-9" C
Mount Type Azimuth
STANDOFF N/A
Antenna Elevation 52'-9"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
RADIATION SYSTEMS P-17A96GF - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier
CBP
Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
Mount Elevation LegAntenna # 4 64'-6" A
Mount Type Azimuth
PIPE 110°
Antenna Elevation 64'-6"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
UNKNOWN 5-FT 6-ELEMENT YAGI - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
- -- -CBP
Mount Elevation LegAntenna # 5, 6 - C, A
Mount Type Azimuth
DIRECT N/A
Antenna Elevation 69'-3", 72'-1"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
SCALA CL-400A - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier
CBP
Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
Mount Elevation LegAntenna # 7, 8 77'-1", 77'-7" A, C
Mount Type Azimuth
PIPE N/A
Antenna Elevation 77'-1", 77'-7"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
UNKNOWN 3' TALL 3"Ø 2-POLE ANT - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier
CBP
Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
Mount Elevation LegAntenna # 9 78'-8" C
Mount Type Azimuth
STANDOFF N/A
Antenna Elevation 78'-8"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Site Name
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Antenna Manufacturer Antenna Model #
UNKNOWN 22' 4-ELEMENT DIPOLE - -
Side Elevation Plan View
TMA # TMA Model #
Photo of Antenna
Carrier
CBP
Horiz. Coax Run @ Antenna Coax Jumper LengthD-Tilt (Mech.) Frequency
Mount Elevation LegAntenna # 10, 11 - A, B
Mount Type Azimuth
DIRECT N/A
Antenna Elevation 89'-7", 89'-7"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
PHOTOS
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
TOWER ELEVATION
COMPOUND
POWER METER
COMPOUND
COMPOUND
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
SIERRA VIEJA
63591_37920, REV. 1
TX8584
JANUARY 8, 2016
PHOTOS
326 Tryon Rd, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
ANT. 8,9 TAG
ANT 5 TAG
TYPICAL TORQUE ARM CONNECTION
TYPICAL GUY ANCHOR
ICE BRIDGE
TYPICAL FLANGE
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANNEX B:
STRUCTURAL ANALYSIS
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
HNTB - Halff JV 326 Tryon Road 5910 W. Plano Pkwy, Suite 200 Raleigh, NC 27603 Plano, TX 75093 (919) 661-6351
(214) 557-1745 mgardner@tepgroup.net
Subject: Structural Analysis Report - Revision 1
HNTB - Halff JV Designation: Site Name: Sierra Vieja TRIRIGA BU Number: TX8584
Engineering Firm Designation: TEP Project Number: 63591_37920
Site Data: 12.5± Miles West of Valentine, Jeff Davis County, TX 79854 Lat., Long.: 30.579800, -104.706600(N30°34'47.28'',W104°42'23.76'') 80 Foot - Guyed Tower Dear Ms. Schwalje, Tower Engineering Professionals is pleased to submit this “Structural Analysis Report” to determine the structural integrity of the above mentioned tower.
The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have determined the tower stress level for the structure, under the following load case, to be:
LC1: Existing Equipment Insufficient Capacity Note: See Table 1 for the existing loading
The analysis has been performed in accordance with the ANSI/TIA-222-G-2-2009 Structural Standard for Antenna Supporting Structures and Antennas – Addendum 2 and the 2006 International Building Code based upon a wind speed of 90 mph 3-second gust and exposure category C.
All modifications and equipment proposed in this report shall be installed in accordance with the appurtenances listed in Table 1 and the attached drawings for the determined available structural capacity to be effective.
We at Tower Engineering Professionals appreciate the opportunity of providing our continuing professional services to you and HNTB - Halff JV. If you have any questions or need further assistance on this or any other projects please give us a call.
Structural analysis prepared by: Stephen E. Bunting, E.I.
Structure Capacity
Controlling Component
147.5% Tower Diagonal T2: (60 – 73.33 ft)
Texas Firm #F-11847
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
80-ft Guyed Tower Structural Analysis TX8584 - Sierra Vieja TEP Project Number 63591_37920, Revision 1 Page 2 tnxTower Report - version 6.1.4.1
TABLE OF CONTENTS
1) INTRODUCTION
2) ANALYSIS CRITERIA
Table 1 - Existing Antenna and Cable Information Table 2 - Design Antenna and Cable Information
3) ANALYSIS PROCEDURE
Table 3 - Documents Provided 3.1) Analysis Method 3.2) Assumptions
4) ANALYSIS RESULTS
Table 4 - Section Capacity (Summary)
Table 5 - Dish Twist/Sway Results for 60 mph Service Wind Speed 4.1) Recommendations
5) APPENDIX A
tnxTower Output
6) APPENDIX B
Coax Configuration
7) APPENDIX C
Conceptual Modification Plan
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP Project Number 63591_37920, Revision 1 Page 3
1) INTRODUCTION
This tower is an 80-ft guyed tower located in Jeff Davis County, Texas. The original design criteria were unavailable for review. TEP visited the site in October of 2015 to gather existing tower steel and appurtenance information. All other information provided to TEP was assumed to be accurate and complete.
2) ANALYSIS CRITERIA
The analysis has been performed in accordance with the ANSI/TIA-222-G-2-2009 Structural Standard for Antenna Supporting Structures and Antennas – Addendum 2 using a 3-second gust wind speed of 90 mph with no ice and 60 mph under service…