This request for proposal from the Federal Aviation Administration seeks tower strengthening and repair services in three locations in Texas. The solicitation involves standing towers in Corrizo Springs, Laredo, and Fort Davis to be completed according to the specifications in the attached statement of work. A firm fixed-price contract will be awarded, with pricing to remain valid for acceptance until September 17, 2020. Offerors must be registered in SAM and eligible under the applicable NAICS code of 237130. Questions are due by September 17, with responses provided prior to proposal submission.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Structural Analysis and Condition Assessment for LMR Sites
Laredo-Wormser Road, Texas (TX8617)
STRUCTURAL AND CONDITION ASSESSMENT
REPORT
October 12, 2016
SENSITIVE BUT UNCLASSIFIED (SBU) GSA Order #: GS-P-00-16-LY-7055 PROPERTY OF THE UNITED STATES GOVERNMENT GSA Contract #: GS-07-P-15-UC-D-7000
COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS PDN: EP-GS-P-00-16-LY-7055
DOCUMENT TO UNAUTHORIZED RECIPIENTS HGA Commission Number 2111-064-00
IS PROHIBITED
Do not remove this notice Properly destroy or return documents when no longer needed
420 North 5th Street, Suite 100 Minneapolis, Minnesota 55401
Tower Engineering Professionals
326 Tryon Road Raleigh, North Carolina 27603
TX Firm# F-11847
STRUCTURAL AND CONDITION ASSESSMENT REPORT
FOR
[LAREDO-WORMSER ROAD] TX8617
247’ SELF SUPPORTING TOWER
LAREDO, WEBB COUNTY, TEXAS
TEP # 69951_85791
Revision 0
Respectfully Submitted By:
Prepared For:
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Date: October 12, 2016
Stephen Fiskum, FAIA Tower Engineering Professionals
HGA Architects and Engineers 326 Tryon Road
420 5th Street North, Suite 100 Raleigh, NC 27603
Minneapolis, MN 55401 (919) 661-6351
(612) 758-4502 StructuresReview@tepgroup.net
Subject: Executive Summary
Tower Designation: Site Number: TX8617
Site Name: Laredo-Wormser Road
Engineering Firm Designation: TEP Project Number: 69951_85791
Site Data: Wormser Road, Laredo, Webb County, TX 78046
Lat., Long.: 27.457769, -99.420072
(N 27° 27' 27.97'', W 99° 25' 12.26”)
247 Foot ± – Self Supporting Tower
Tower Engineering Professionals (TEP) is pleased to provide this executive summary for the Phase I Scope of Work, which included a Maintenance and Condition Assessment, Capital Expenditure Table, Steel and Appurtenance
Mapping, and Structural Analysis for the above referenced site.
Maintenance and Condition Assessment
Overall Tower Condition (Excellent/Good/Average/Fair/Poor): Average*
Tower Type: 247-ft Rohn model SRSS self supporting tower
Tower Age: Approximately 14 years**
Number of Guy Wires: N/A
Tower Access Road Condition: Good, no obstacles or issues encountered
A periodic inspection for the above referenced site was performed by Bryan Gilliam, C.W.I. and Ryan Barger, E.I. of
TEP during the August 10, 2016 site visit. The inspection was in accordance with the ANSI/TIA-222-G-2005, Annex J:
Maintenance and Condition Assessment (Normative). TEP observed the following checklist items requiring some measure of possible or required corrective action: 1) Structure Condition, 2) Finish, 3) Grounding, 4) Antennas and
Lines, 5) Concrete Foundations, and 6) Non-TIA Related Items. Refer to the Maintenance and Condition Assessment
Report for specific details.
*TEP defines the tower conditions as follows:
Excellent - The tower has sufficient capacity to carry the existing loads. No modifications are required at this time. In addition, the tower has no maintenance issues of note and doesn’t require maintenance repairs at this time.
Good - The tower has sufficient capacity to carry the existing loads. No modifications are required at this time. However, the tower has some maintenance issues of note that require attention.
Average - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the
ANSI/TIA-222-G standard for the existing loading. In addition, the tower may have minor maintenance issues of note that require attention.
Fair - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the
ANSI/TIA-222-G standard for the existing loading. In addition, the tower has maintenance issues of note that require attention. Based on the itemized estimate in our Capital Expenditure Table, modifying the existing tower may be the most cost effective solution.
Poor - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the
ANSI/TIA-222-G standard for the existing loading. In addition, the tower has maintenance issues of note that require attention. Based on the itemized estimate in our Capital Expenditure Table and/or the condition of the tower, a full tower replacement may be the best solution.
**Tower Age was estimated based on tower identification tags, tower manufacturer information, tower research, type and condition of tower components, and/or historical site images
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP Project Number 69951_85791 October 12, 2016
TX8617 - Laredo-Wormser Road
326 Tryon Road, Raleigh, NC 27603 (o) 919-661-6351 (f) 919-661-6350 www.tepgroup.net
Condition Assessment of Non-Tower Assets
During the site visit, TEP conducted a visual inspection of all Non-Tower Owned Assets. TEP did not find any non-tower assets that require urgent corrective repairs. However, TEP recommends regular inspection and maintenance by licensed professionals based on manufacturer specifications. Refer to Section L of the Maintenance and Condition
Assessment Report for any applicable additional information.
Asset Type Coordinates Condition Notes
Estimated
Remaining
Life
Shelter/
Roof #1 Prefab
27.457761, -99.419967 Good GFRC Shelters tag, no major issues observed 10+ years
Shelter
Access Single Door
27.457761, -99.419967 Average
Located on south side of shelter, general wear located on door 5-10 years
HVAC Unit
(2) Through
Wall
27.457761, -99.419967 Good
Bard manufacturer tag, appears to be in good condition, no major issues observed 10+ years
Power
Supply Generator
27.457669, -99.420014 Average
Cummins, Model #: GGDB-5567283, rust on exhaust 5-10 years
Power
Supply
Power
Meter
27.457789, -99.420253 Good
Marked “Landis+Gyr”, appears to be working properly 10+ years
Power
Supply
Power
Meter
27.457694, -99.420264 Good
Marked “Landis+Gyr”, appears to be working properly 10+ years
Gas Source Fuel Tank 27.457658, -99.420061 Good
American Welding & Tank Co. 250 gal tank, no major issues visible 10+ years
Cellular
Receivers
27.457761, -99.419967 Good
Shelter #1 houses various units associated with communication equipment, no major issues of note
10+ years
Capital Expenditure Table
A cost estimate of $68,800 was provided to cover repairs and additional inspections as recommended in the
Maintenance and Condition Assessment Report and the Structural Analysis Report. The recommended repair schedule ranges from 6 months to 5 years. Also note that this estimate does not include any foundation reinforcements that may be required. TEP cannot say with certainty that modifying the existing tower would be more cost effective than a replacement without completing a Structural Modification Design Analysis. Refer to the
Capital Expenditure Table for details. For itemized repairs, refer to the Capital Expenditure Table for details. TEP estimated a ROM cost for full tower replacement would range from approximately $160,000 for a 100-ft self supporting tower to $250,000 for a 200-ft self supporting tower. These estimates do not include pricing for site specific costs related to zoning, permitting, environmental studies, etc.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Steel and Appurtenance Mapping
This tower is a 247-ft± model SRSS self supporting tower designed by Rohn in August of 2002. A Steel and
Appurtenance Mapping was performed in order to obtain the necessary tower and appurtenance loading information needed to conduct the Structural Analysis for this site. The antennas recorded during our Steel and
Appurtenance Mapping are depicted in the table below. TEP denoted the owner of the equipment under the
“Owner/Tenant” column based on information available on site. Refer to the Steel and Appurtenance Mapping
Report for additional detail.
Elevation
(ft) Qty Antenna Model
Mount
Type
Owner/
Tenant
253.0 1 Celwave Stationmaster VHF Sidearm CBP
253.0 1 Celwave Stationmaster VHF Sidearm CBP
241.0 1 Yagi VERT POL 6-3L UHF
246.5 1 Celwave BA 1010-2 VHF Sidearm CBP
234.0 1 Decibel DB-224 (Inverted)
228.0 1 Commscope HP8-71W-P3A Pipe CBP
215.0 1 10’ 2-element Dipole Sidearm CBP
211.0 1 Decibel DB-224 Sidearm Unknown
195.0 1 Commscope HP10-71W-P3A Pipe CBP
186.0 1 Empty Pipe Mount CBP
177.5 1 Celwave Master VHF Pipe CBP
166.0 1 Andrew VHP4-142-111 Pipe CBP
148.0 1 Andrew VHP2-71W-511 Pipe CBP
134.5 1 Empty Pipe Mount CBP
123.0 1 Andrew VHP4-71W-511 Pipe CBP
116.5 1 Andrew VHP4-71W-IM5 Pipe CBP
110.0 1 Andrew VHP4-71W-511 Pipe CBP
109.5 1 Andrew VHP2.5-142-111 Pipe CBP
99.0 1 Radiowaves SP4-5.2NS Pipe CBP
91.5 1 Andrew VHP7-71W-111 Pipe CBP
84.0 1 Andrew VHP2.5-142-111 Pipe CBP
72.3 1 Andrew VHP2-71W-IM5 Pipe CBP
69.5 1 Andrew VHP2-71W-IM5
67.0 1 Andrew VHP6-71W-511 Pipe CBP
63.5 1 Andrew VHP2-71W-511 Pipe
CBP
61.0 1 Andrew VHP2.5-142W-110 CBP
60.5 1 Andrew VHP4-71W-511 Pipe CBP
55.3 1 Log Periodic VHF 21 EL Sidearm CBP
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Structural Analysis
The Structural Analysis report outlines overstresses in the tower redundant diagonal bracing from 19’ to 57’ elevations and tower redundant horizontal bracing from 19’ to 57’ elevations. TEP believes that the majority of the overstresses can be attributed to the more stringent loading and analysis criteria as required by the latest ANSI/TIA-
222-G-2-2009 Standard, as compared to previous versions of the TIA Standard for which the tower was originally designed. Based on our analysis we have determined the tower stress level for each controlling component, under the following load case, to be:
LC1: Existing Equipment Insufficient Capacity Note: See Table 1 for the existing loading
Thank you for the opportunity to provide this service for you. If you have any questions or comments, please contact our office.
Component % Capacity
Leg (T12) 47.2
Diagonal (T12) 81.8
Horizontal (T12) 61.9
Secondary Horizontal (T8) 35.9
Top Girt (T1) 4.3
Redund Horz 1 Bracing (T12) 140.9
Redund Diag 1 Bracing (T12) 142.6
Redund Hip 1 Bracing (T13) 2.9
Redund Hip Diagonal 1 Bracing (T13) 1.0
Redund Sub Horz Bracing (T13) 13.6
Redund Sub Diagonal Bracing (T13) 52.0
Inner Bracing (T12) 0.5
Bolt Checks 65.8
Anchor Rods 32.5
Foundation Reaction Comparison 46.2
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
MASTER TABLE OF CONTENTS
���� MAINTENANCE AND CONDITION ASSESSMENT
���� CAPITAL EXPENDITURE TABLE
���� ANNEX A: STEEL AND APPURTENANCE MAPPING
���� ANNEX B: STRUCTURAL ANALYSIS
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
MAINTENANCE AND CONDITION ASSESSMENT
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Date: October 12, 2016
HGA Architects and Engineers 326 Tryon Road
420 5th Street North, Suite 100 Raleigh, NC 27603
Minneapolis, MN 55401 (919) 661-6351
(612) 758-4502 StructuresReview@tepgroup.net
Subject: Maintenance and Condition Assessment Report
Tower Designation: Site Number: TX8617
Site Name: Laredo-Wormser Road
Engineering Firm Designation: TEP Project Number: 69951_85791
Site Data: Wormser Road, Laredo, Webb County, TX 78046
Lat., Long.: 27.457769, -99.420072
(N 27° 27' 27.97”, W 99° 25' 12.26”)
247-ft ± – Self Supporting Tower
Dear Mr. Fiskum, Tower Engineering Professionals (TEP) completed a periodic inspection for the above referenced site. The onsite investigation was performed by Bryan Gilliam, C.W.I. and Ryan Barger, E.I. of TEP during the August 10, 2016 site visit.
The inspection was in accordance with the ANSI/TIA-222-G-2005, Annex J: Maintenance and Condition Assessment
(Normative), including all addendums (addendums TIA-222-G-1 2007 and TIA 222-G-2 2009); the checklist can be found on pages 3 thru 8 of this report.
Observations and recommendations are listed herein. The inspection included observation of the tower components and CBP owned assets. For the purpose of this inspection, the tower legs were named by letter according to the magnetic azimuth defined by a line from the center of tower to the leg. “A” leg is the leg closest to magnetic north, followed clockwise by “B” and “C.”
Thank you for the opportunity to provide this service for you. If you have any questions or comments, please contact our office.
TX Firm# F-11849
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
Self Supporting Tower Maintenance and Condition Assessment Report October 12, 2016
TEP Project Number 69951_85791 TX8617 - Laredo-Wormser Road
TABLE OF CONTENTS
1) ANSI/TIA-222-G-MAINTENANCE AND CONDITION ASSESSMENT
2) SUMMARY
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANSI/TIA-222-G MAINTENANCE AND CONDITION ASSESSMENT
A. STRUCTURE CONDITION
A.1. Damaged members (legs and bracing)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
A.2. Loose members
Okay Possible Improvement Needs Repair Not Applicable
Notes:
A.3. Missing members
Okay Possible Improvement Needs Repair Not Applicable
Notes:
A.4. Climbing facilities, platforms, catwalks – all secure
Okay Possible Improvement Needs Repair Not Applicable
Notes: Bent step peg observed at 120-ft on C-leg. Surface corrosion observed on step peg hardware at 95-ft and 190-ft on A-leg. See summary for details.
A.5. Loose and/or missing bolts and/or nut locking devices
Okay Possible Improvement Needs Repair Not Applicable
Notes: Missing nut locking device on diagonal bracing bolt at 152-ft. (1) Lock washer installed improperly at 19-ft on C-leg. See summary for details.
A.6. Visible cracks in welded connections
Notes:
B. FINISH
B.1. Paint and/or galvanizing condition
Notes:
B.2. Rust and/or corrosion condition including mounts and accessories
Okay Possible Improvement Needs Repair Not Applicable
Notes: Corroded mount members observed on the antenna mount at 56.25-ft on A-leg. See summary for details.
B.3. FAA or ICAO color marking conditions
Okay Possible Improvement Needs Repair Not Applicable
Notes:
B.4. Water collection in members (to be remedied, e.g., unplug drain holes, etc.)
Okay Possible Improvement Needs Repair Not Applicable
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
C. LIGHTING
C.1. Conduit, junction boxes, and fasteners (weather tight and secure)
Notes:
C.2. Drains and vents openings (unobstructed)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.3. Wiring Condition
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.4. Light lenses
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.5. Bulb condition
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.6.a. Controllers functioning (Flasher)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.6.b. Controllers functioning (Photo control)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
C.6.c. Controllers functioning (Alarms)
D. GROUNDING
D.1. Connections
Notes:
D.2. Corrosion
Okay Possible Improvement Needs Repair Not Applicable
Notes:
D.3. Lightning protection (secured to structure)
Okay Possible Improvement Needs Repair Not Applicable
Notes: No lightning protection installed on tower. Addition of lightning rod and homerun ground wire are up to owner’s discretion.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E. ANTENNAS AND LINES
E.1. Antenna condition
Notes: Yagi antenna located on A-leg at 56.25-ft has several bent elements and is missing an element. See summary for details.
E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)
Okay Possible Improvement Needs Repair Not Applicable
Notes: Unused mounts on C-leg at 134.5-ft and 187-ft. (4) Loose U-bolt nut locking devices on mount at 119-ft on A-leg. See summary for details.
E.3. Feed line condition (flanges, seals, dents, jacket damage, grounding, etc.)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
E.4. Hanger condition (snap-ins, bolt on, kellum grips, etc.)
Okay Possible Improvement Needs Repair Not Applicable
Notes: Corroded kellum grip attachments at 70-ft, 105-ft, and 141-ft on AB face. See summary for details.
E.5. Secured to structure
F. OTHER APPURTENANCES (WALKWAYS, PLATFORMS, SENSORS, FLOODLIGHTS, ETC.)
F.1. Condition
Notes:
F.2. Secured to structure
G. INSULATOR CONDITION
G.1. Cracking and chipping
Notes:
G.2. Cleanliness of insulators
Okay Possible Improvement Needs Repair Not Applicable
Notes:
G.3. Spark gaps set properly
Okay Possible Improvement Needs Repair Not Applicable
Notes:
G.4. Isolation transformer condition
Okay Possible Improvement Needs Repair Not Applicable
Notes:
G.5. Bolts and connection secure
Okay Possible Improvement Needs Repair Not Applicable
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
H. GUYS
H.1. Strand condition (corrosion, breaks, nicks, kinks, etc.)
Notes:
H.2.a. Guy Hardware Conditions (Turnbuckles or equivalent (secure and safety properly applied)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.b. Guy Hardware Conditions (Cable thimbles properly in place (if required))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.c. Guy Hardware Conditions (Service sleeves properly in place (if required))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.i. Guy Hardware Conditions (Cable connectors (end fittings) (Cable clamps applied properly and bolts tight))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.ii. Guy Hardware Conditions (Cable connectors (end fittings) (Wire serving properly applied))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.iii. Guy Hardware Conditions (Cable connectors (end fittings) (No signs of slippage or damaged strands))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.iv. Guy Hardware Conditions (Cable connectors (Preformed wraps – properly applied, fully wrapped, & sleeve in place))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.v. Guy Hardware Conditions (Cable connectors (end fittings) (Poured sockets secure and showing no separation))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.2.d.vi. Guy Hardware Conditions (Cable connectors (Shackles, bolts, pins, and cotter pins secure and in good condition))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.3. Guy tensions
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.4. Measure guy tensions
Okay Possible Improvement Needs Repair Not Applicable
Notes:
H.5. Record temperature, wind speed and wind direction
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
I. CONCRETE FOUNDATIONS
I.1.a. Ground condition (Settlement, movement or earth cracks)
Notes:
I.1.b. Ground condition (Erosion)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.1.c. Ground condition (Site condition (standing water, drainage, trees, etc.))
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.2.a. Anchorage condition (Nuts and/or nut locking device (tightened))
Okay Possible Improvement Needs Repair Not Applicable
Notes: (9) Missing anchor rod nut locking devices on all legs. (5) Anchor rod locking nuts were found to be recessed on the B-leg. See summary for details.
I.2.b. Anchorage condition (Grout condition)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.2.c. Anchorage condition (Anchorages and/or anchor rod condition)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.3.a. Concrete condition (Cracking, spalling, or splitting)
Okay Possible Improvement Needs Repair Not Applicable
Notes: All leg foundations are severely cracked. See summary for details.
I.3.b. Concrete condition (Chipped or broken concrete)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.3.c. Concrete condition (Honeycombing)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
I.3.d. Concrete condition (Low spots to collect moisture)
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
J. GUYED MAST ANCHORS
J.1. Settlement, movement or earth cracks
Notes:
J.2. Backfill heaped over concrete for water shedding
Okay Possible Improvement Needs Repair Not Applicable
Notes:
J.3. Anchor rod condition below earth (Maintain required structural capacity of anchor during exploration.)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
J.4. Corrosion control measures (galvanizing, coating, concrete encasement, cathodic protection systems, etc.)
Okay Possible Improvement Needs Repair Not Applicable
Notes:
J.5. Anchor heads clear of earth
K. TOWER ALIGNMENT
K.1. Tower Plumb and Twist
Notes: Tower twist and plumb was not measured as a part of this scope of work.
L. NON-TIA RELATED ITEMS
L.1. Equipment Shelter
Notes:
L.2. Security
Okay Possible Improvement Needs Repair Not Applicable
Notes: Tower compound is unsecured. See summary for details.
L.3. Other Equipment
Okay Possible Improvement Needs Repair Not Applicable
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
SUMMARY
Photograph Observations and Recommendations
A.4. Climbing facilities, platforms, catwalks (all secure)
Observation:
Bent step peg observed at 120-ft on C-leg.
Recommendation:
Replace with a new 5/8” dia. x 6” long step peg.
A.4. Climbing facilities, platforms, catwalks (all secure)
Surface corrosion observed on step peg at 95-ft and 190-ft on the A-leg.
Replace corroded step pegs.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
A.5. Loose and/or missing bolts and/or nut locking devices
Missing nut locking device on diagonal bracing bolt at 152-ft.
Install a nut locking device. If necessary, re-install a longer bolt to accommodate the use of a nut locking device. Tighten all nuts per the AISC “turn of the nut” method.
A.5. Loose and/or missing bolts and/or nut locking devices
(1) Lock washer installed on improperly at 19-ft on C-leg.
Remove and reinstall lock washer under nut. Replace with new A325N 1-1/2” dia. leg bolt. Tighten all nuts per the AISC
“turn of the nut” method.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
B.2. Rust and/or corrosion condition including mounts and accessories
Corroded mount members observed on the antenna mount at 56.25-ft on A-leg.
Clean areas of corrosion down to sound metal and coat with two brush coats of ZRC cold galvanizing compound or approved equivalent.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E.1. Antenna condition
Yagi antenna located on A-leg at 56.25-ft has several bent elements and is missing an element.
Repair or replace antenna.
E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)
Unused mounts on C-leg at 134.5-ft and 187-ft.
Removing the unused antenna mount will improve the overall structural capacity of the tower.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)
(4) Loose U-bolt nut locking devices on mount at 119-ft on A-leg.
Tighten all nut locking devices.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E.4. Hanger condition (snap-ins, bolt on, kellum grips, etc.)
Corroded kellum grip attachments at 70-ft, 105-ft, and 141-ft on AB face.
Replace kellum grip attachments.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
I.2.a. Anchorage condition (Nuts and/or nut locking device
(tightened))
(9) Missing anchor rod nut locking devices on all legs.
Install anchor rod nut locking devices. Tighten all anchor rod nuts per the AISC “turn of the nut” method.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
I.2.a. Anchorage condition (Nuts and/or nut locking device
(tightened))
(5) Anchor rod locking nuts were found to be recessed on the B-leg.
Fill the gap between the top of the bolt and the top of the locking nut with silicon to prevent water collection.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
I.3.a. Concrete condition (Cracking, spalling, or splitting)
All leg foundations are severely cracked.
Have an engineer licensed in the state of Texas design structural modifications.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
L.2. Security
Tower compound is unsecured.
Install an 8-ft, barbed wire fence around all CBP assets, including the tower and equipment shelters. Secure fence with chain and padlock.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
CAPITAL EXPENDITURE TABLE
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANSI/TIA-222-G: CAPITAL EXPENDITURE TABLE
Job Name: TX8617 - Laredo-Wormser Road
TEP Number: 69951_85791
A. STRUCTURAL CONDITION
Issue: Repair/Modification: Repair Schedule:
A.1. Damaged members (legs and bracing)
a. The following members were overstressed in the structural analysis:
0-6 months $40,000
● Tower Redundant Diagonals from 19'-57'
● Tower Redundant Horizontals from 19'-57'
Sub Total: $40,000
A.4. Climbing facilities, platforms, catwalks – all secure
a. Bent step peg observed at 120-ft on C-leg. i. Replace with a new 5/8" dia. x 6" long step peg. 0-1 year $50
b. Surface corrosion observed on step peg at 95-ft and 190-ft on the A-leg.
ii. Replace all corroded step pegs. 0-5 years $100
Sub Total: $150
A.5. Loose and/or missing bolts and/or nut locking devices
a. Missing nut locking device on diagonal bracing bolt at 152-ft i. Install a nut locking device. If necessary, re-install a longer bolt to accommodate the use of a nut locking device. Tighten all nuts per the AISC “turn of the nut” method.
0-6 months $50
b. (1) Lock washer installed on improperly at 19-ft on C-leg. ii. Remove and reinstall lock washer under nut.
Replace with new A325N 1-1/2” dia. leg bolt. Tighten all nuts per the AISC “turn of the nut” method.
0-6 months $200
Sub Total: $250
Total: $40,400
B. FINISH
Issue: Repair/Modification: Repair Schedule:
B.2. Rust and/or corrosion condition including mounts and accessories
a. Corroded mount members observed on the antenna mount at
56.25-ft on A-leg.
i. Clean areas of corrosion down to sound metal and coat with two brush coats of ZRC cold galvanizing compound or approved equivalent.
0-1 year $250
Sub Total: $250
Total: $250
C. LIGHTING
NO DEFICIENCIES WERE IDENTIFIED
D. GROUNDING
Issue: Repair/Modification: Repair Schedule:
D.3. Lightning protection (secured to structure)
a. No lightning protection observed on tower. i. Addition of lightning rod and homerun ground wire are up to owner's discretion
0-5 years $750
Sub Total: $750
Total: $750
*Items that don't require attention were omitted from this list of itemized modification costs. For a full itemized list of everything that was assessed during our site visit please reference the Maintenance and Condition Assessment.
Fee:
Fee:
Fee:
i. Order Structural Design Drawings for modifications to failing/damaged members.
ii. Complete repairs as specified in Structural Design
Drawings.
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
E. ANTENNAS AND LINES
Issue: Repair/Modification: Repair Schedule:
E.1. Antenna condition
a. Yagi antenna located on A-leg at 56.25-ft has several bent elements and is missing an element.
i. Repair or replace antenna. 0-5 years $750
Sub Total: $750
E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)
a. Unused mounts on C-leg at 134.5-ft and 187-ft. i. Removing the unused antenna mounts will improve the overall structural capacity of the tower.
0-5 years $750
b. (4) Loose U-bolt nut locking devices on mount at 119-ft on A-leg.
ii. Tighten all nut locking devices. 0-1 year $150
Sub Total: $900
E.4. Hanger condition (snap-ins, bolt on, kellum grips, etc.)
a. Corroded kellum grip attachments at 70-ft, 105-ft, and 141-ft on AB face.
i. Replace kellum grip attachments. 0-1 year $750
Sub Total: $750
Total: $2,400
F. OTHER APPURTENANCES (WALKWAYS, PLATFORMS, SENSORS, FLOODLIGHTS, ETC.)
NO DEFICIENCIES WERE IDENTIFIED
G. INSULATOR CONDITION
NO DEFICIENCIES WERE IDENTIFIED
H. GUYS
NO DEFICIENCIES WERE IDENTIFIED
I. CONCRETE FOUNDATIONS
Issue: Repair/Modification: Repair Schedule:
I.2.a. Anchorage condition (Nuts and/or nut locking device
(tightened))
a. (9) Missing anchor rod nut locking devices. i. Install anchor rod nut locking devices. Tighten all anchor rod nuts per the AISC “turn of the nut” method.
0-6 months $750
b. (5) Anchor rod lock nuts are recessed on the B-leg. ii. Fill the gap between the top of the bolt and the top of the lock nut with silicon to prevent water collection.
0-5 years $250
Sub Total: $1,000
I.3.a. Concrete condition (Cracking, spalling, or splitting)
a. All leg foundations are severely cracked. i. Have an engineer licensed in the state of Texas design structural modifications.
0-6 months $10,500
Sub Total: $10,500
Total: $11,500
J. GUYED MAST ANCHORS
NO DEFICIENCIES WERE IDENTIFIED
K. TOWER ALIGNMENT
NO DEFICIENCIES WERE IDENTIFIED
Fee:
Fee:
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
L. NON-TIA ISSUES
Issue: Repair/Modification: Repair Schedule:
L.2. Security
a. Tower compound is unsecured. i. Install an 8-ft, barbed wire fence around all CBP assets, including the tower and equipment shelters.
Secure fence with chain and padlock.
0-1 year $9,000
Sub Total: $9,000
Total: $9,000
OTHER CONSTRUCTION COSTS
Item:
a. Permits / Application Fees $1,000
b. Post Modification Inspection Report $2,000
c. Mobilization Costs $1,500
Sub Total: $4,500
Total: $4,500
GRAND TOTAL: $68,800
Fee:
Fee:
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
ANNEX A:
STEEL AND APPURTENANCE MAPPING
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Page Title Initials Page # (s) Notes Checklist & Notes
Tower Elevation Tower Section Elevation Transmission Cables
Waveguide
Antenna and Mount Sketch Photos
NSB
6-18 19-20 21-50 51-54
CHECKLIST
Latitude: Longitude:
Ground Elevation:
Site Address:
Tower ID Plate:
Existing Carriers/Site #:
Gate Combo:
Telephone Company:
Pedestal # and Location:
Power Company:
Meter # and Owner:
27.457769° (N 27° 27' 27.97")
667-FT (VIA GOOGLE EARTH)
WORMSER RD, LAREDO, TX 78046 (WEBB COUNTY)
ROHN INDUSTRIES, INC, CUSTOMER FILE NUMBER: 525 5AE, MODEL: SRSS, DRAWING NUMBER: D020419 1169264
NONE OBSERVED
NONE OBSERVED
LANDIS+GYR
131 788 193 / CBP, 191 323 410 / CBP
CBP / TX8617
UNKNOWN
N/A
-99.420072° (W 99° 25' 12.26")
Crew Leader:
Crew Member: RYAN BARGER, E.I.
Abbreviations: AGL: Above Ground Level B.C.: Bolt Circle BP: Bent Plate C-C: Center to Center C: Channel CNR: Could Not Record EW: Elliptical Waveguide FH: Foam Heliax
HCL: Hard Copper Line HSS: Hollow Structural Section L: Angle 2L: Double Angle MC: Metal Conduit M.E.: Minimum Edge MOD: Modification PL: Plate
RC: Rigid Conduit S.B.: Stitch Bolts Schl: Schifflerized Angle SM: Smooth Heliax SP: Spacing SR: Solid Rod TH: Thickness Tri: Triangular
BRYAN GILLIAM, C.W.I.
NOTES
FCC#: N/A
Special Access Issues (Key Entry, Hidden/Unmarked Access, FM/TV on tower):
Compound Detail 2 Ladder 3
NSB
NSB
NSB
NSB
NSB
NSB
NSB
NSB
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
COMPOUND DETAIL
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Access Road Compound View CBP Equipment Shelter
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
LADDER
Climbing Ladder #1-3 Sketch
Description Pegs
# Height Width Step Rail (type & size) Rung (type & size) Safety (type & size)
Ladder
6"
14"
28"
15"
A-LEG
PL11
2'x14"
SR5
8"Ø NONE0'-247'1
8"Ø8'-6"-247'
Climbing Ladder #1 Photo
Climbing Ladder #4 PhotoClimbing Ladder #4 Sketch
Pegs Pegs
6" 28" B-LEG SR5
8"Ø NONE0'-247'
6" 28" C-LEG SR5
8"Ø NONE0'-247'
4 SR5
8"Ø
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Description # Height Width Step Rail (type & size) Rung (type & size) Holes (size & spacing)
Waveguide Waveguide Waveguide Waveguide
WAVEGUIDE
10'-116'-6"± 35" 48" L11 2"x11
2"x18" L2"x11 2"x18" (15) 34"Ø, (15) 716"Ø1
Waveguide Ladder #1-4 Sketch Waveguide Ladder #2 Photo
Waveguide Ladder #3-4 Photo
10'-126'-0"± 35" 48" L11 2"x11
2"x18" L2"x11 2"x18" (15) 34"Ø, (15) 716"Ø
10'-152'-0"± 35" 48" L11 2"x11
2"x18" L2"x11 2"x18" (15) 34"Ø, (15) 716"Ø
10'-247'-0"± 35" 48" L11 2"x11
2"x18" L2"x11 2"x18" (15) 34"Ø, (15) 716"Ø
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER ELEVATION
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
BASE PLATE PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
TOWER SECTION ELEVATION
SECTION _______________1 (0' - 19')
MEMBER SIZES
25'-97 8"
23'-111 16"
MEMBER SIZES
Member
LEG
DIAG. 1
Size Bolts Gussets/Flange
SR5"Ø
2L3"x3"x14"
(8) 11 2 "Ø 16.4"Øx2"TH
8"(2) 58"Ø
DIAG. 2 L13
4"x13
4"x18" (1) 58"Ø
Stitch BoltsMin. Edge
8"
8"
DIAG. 3 L13
4"x13 4"x18" (1) 58"Ø 11
8"
DIAG. 4 2L13
4"x13 4"x18" (1) 58"Ø
HORIZ. 2L3"x3"x14" (2) 58"Ø
SUB-H1 L13
4"x13 4"x316" (1) 58"Ø
SUB-H2 L2"x2"x14" (1) 58"Ø
SUB-H3 (1) 58"ØL13
4"x13 4"x316"
8"
8"
8"
8"
8"
8"
8"
INTER. BRACE 2L21
2"x21
2"x316" (1) 58"Ø --
HIP DIAG. (1) 58"Ø2L21
2"x21 2"x316"
8"
8"
HIP HORIZ. (1) 58"ØL13
4"x13
4"x18" 3 8"
8"
8"
8"
8"
8" --
8"
8"
8"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAG. 1
Size Bolts Gussets/Flange
SR4.8"Ø
2L21
2"x21 2"x14"
(8) 11 2 "Ø 16"Øx2"TH
8"(1) 58"Ø
DIAG. 2 L2"x2"x18" (1) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________2 (19' - 38')
MEMBER SIZES
23'-111 16"
22'-01 16"
Min. Edge
8" --
HORIZ. 2L21
2"x21
2"x14" (2) 58"Ø -- SUB-HORIZ. L2"x2"x14" (1) 58"Ø --
8"
8"
8"
2L2"x2"x18" (1) 58"Ø 11 8" --
(1) 58"Ø 11 8" --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 2L2"x2"x18"
*INTERIOR BRACING LOCATED AT 28.5-FT & 38-FT
8"
8"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAG. 1
Size Bolts Gussets/Flange
SR4.8"Ø
2L21
2"x21 2"x14"
(6) 11 2 "Ø 15.5"Øx13
4"TH
8"(2) 58"Ø DIAG. 2 L2"x2"x18" (1) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________3 (38' - 57')
MEMBER SIZES
22'-01 16"
20'-11 4"
Min. Edge
HORIZ. 2L21
2"x21
2"x14" (2) 58"Ø SUB-HORIZ. L2"x2"x3
16" (1) 58"Ø
8"
8"
8"
2L2"x2"x18" (1) 58"Ø 11 8" --
8" --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 2L2"x2"x18" (1) 58"Ø
*INTERIOR BRACING LOCATED AT 47.5-FT & 57-FT
8"
8"
8"
8"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAG. 1
Size Bolts Gussets/Flange
SR4.5"Ø
2L21
2"x21 2"x14"
(6) 11 2 "Ø 15.5"Øx13
4"TH
8"(2) 58"Ø DIAG. 2 L2"x2"x18" (1) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________4 (57' - 76')
MEMBER SIZES
20'-11 4"
18'-21 4"
Min. Edge
8" --
HORIZ. 2L21
2"x21
2"x316" (2) 58"Ø SUB-HORIZ. L2"x2"x3
16" (1) 58"Ø
8"
8"
8"
2L13 4"x13
4"x18" (1) 58"Ø 11 8" --
8" --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 (1) 58"Ø
*INTERIOR BRACING LOCATED AT 66.5-FT & 76-FT
2L13 4"x13
4"x18"
8" --
8" --
8" --
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAG. 1
Size Bolts Gussets/Flange
SR4.25"Ø
2L21
2"x21 2"x316"
(6) 11 2 "Ø 15.5"Øx13
4"TH
8"(2) 58"Ø
DIAG. 2 L13
4"x13 4"x316" (1) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________5 (76' - 95')
MEMBER SIZES
18'-21 4"
16'-31 4"
Min. Edge
8" --
HORIZ. 2L2"x2"x14" (2) 58"Ø
SUB-HORIZ. L13
4"x13 4"x316" (1) 58"Ø
8"
8"
8"
2L13 4"x13
4"x18" (1) 58"Ø -- --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 2L13
4"x13
4"x18" (1) 58"Ø
*INTERIOR BRACING LOCATED AT 85.5-FT & 95-FT
8" --
8" --
8" --
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR4"Ø
2L2"x2"x14"
(6) 11 2 "Ø 15"Øx13
4"TH
8"(1) 58"Ø
(1) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________6 (95' - 114')
MEMBER SIZES
16'-31 4"
14'-43 16"
Min. Edge
8" (1) 58"Ø HORIZ. 2L2"x2"x18" 11
8" (1) 58"Ø 3 8"
2L13 4"x13
4"x18" (1) 58"Ø -- --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 (1) 58"Ø
*INTERIOR BRACING LOCATED AT 99'-9" & 109'-3".
2L13 4"x13
4"x18"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR4"Ø
2L2"x2"x3
16"
(8) 1"Ø 11.6"Øx214"TH
8"(1) 58"Ø
(1) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________7 (114' - 133')
MEMBER SIZES
14'-43 16"
12'-57 16"
Min. Edge
8" (1) 58"Ø HORIZ. 2L2"x2"x18" 11
8" (1) 58"Ø 3 8"
L2"x2"x18" (1) 58"Ø -- --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 L2"x2"x18" (1) 58"Ø
*INTERIOR BRACING LOCATED AT 118'-9" & 128'-3".
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR3.8"Ø
2L2"x2"x3
16"
(8) 1"Ø 11.6"Øx214"TH
8"(1) 58"Ø
(1) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________8 (133' - 152')
MEMBER SIZES
12'-57 16"
10'-67 16"
Min. Edge
8" (1) 58"Ø HORIZ. 2L2"x2"x18" (1) 58"Ø 3
8" L2"x2"x18" (1) 58"Ø -- --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 L2"x2"x18" (1) 58"Ø
*INTERIOR BRACING LOCATED AT 137-9" & 147'-3".
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR3.5"Ø
2L21
2"x21 2"x316"
(6) 1"Ø 11.3"Øx2"TH
8"(1) 34"Ø
(1) 34"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________9 (152' - 171')
MEMBER SIZES
10'-67 16"
8'-77 16"
Min. Edge
8" (1) 34"Ø
HORIZ. L21
2"x21 2"x316" 11
8" (1) 34"Ø 3 8"
L13 4"x13
4"x18" (1) 58"Ø -- --
8"
8"
INTER. BRACE 1
INTER. BRACE 2 (1) 58"Ø
*INTERIOR BRACING LOCATED AT 156'-9" & 166'-3".
L13 4"x13
4"x18"
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR3"Ø
L2"x2"x14"
(6) 1"Ø 10.8"Øx2"TH
8"(2) 58"Ø
(1) 58 "Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________10 (171' - 190')
MEMBER SIZES
8'-77 16"
6'-83 16"
Min. Edge
8" (1) 58"Ø GIRT L3"x3"x3
16" -- -- 3
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR2.8"Ø
L21
2"x21 2"x14"
(6) 78"Ø 9.85"Øx13
4"TH
8"(2) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________11 (190' - 209')
MEMBER SIZES
6'-83 16"
6'-715 16"
Min. Edge
8" (1) 58"Ø
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR2.3"Ø
L2"x2"x14"
(4) 78"Ø 9.1"Øx112"TH 4"(2) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________12 (209' - 228')
MEMBER SIZES
6'-715 16"
6'-71 2"
Min. Edge
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TOWER SECTION ELEVATION
PHOTO PHOTO
Face Width at Top ___________ Face Width at Bottom_________
MEMBER SIZES
Member
LEG
DIAGIONAL
Size Bolts Gussets/Flange
SR2.3"Ø
L2"x2"x14"
(4) 58"Ø 7.1"Øx1"TH 4"(2) 58"Ø
Stitch Bolts
TOWER SECTION ELEVATION
SECTION _______________13 (228' - 247')
MEMBER SIZES
6'-71 2"
6'-71 2"
Min. Edge
GIRT L2"x2"x18" 1 4"(1) 58"Ø 11
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
240 120
TOWER MAPPING
Site Name
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
TRANSMISSION CABLES
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Coax # Type/Style Start Height End Height Antenna Carrier Notes
CBP2 109'-6"
CBP
91'-6" 9 CBP
EW 77 9'-0" 116'-6" 13 CBP
EW 132 9'-0"
3 EW 77 9'-0"
7 EW 77 9'-0"
8 EW 77 9'-0"
9 EW 77 9'-0"
11 EW 77 9'-0"
FH 78
EW 132 9'-0"
EW 132 9'-0"
EW 132 9'-0"
9'-0"
84'-0" 8 61'-0" 3 55'-3" 1 63'-6" 69'-6" 6 72'-3" 7
166'-0" 16 123'-0" 14
CBP
CBP
CBP
CBP
CBP
CBP
CBP
CBP
CBP DISCONNECTED AT SHELTER
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
TRANSMISSION CABLES (CONTINUED)
Coax # Type/Style Start Height End Height Antenna Carrier Notes
CBP13 67'-0"
CBP
60'-6" 2 CBP14
EW77 9'-0" 110'-0" 12 CBP
EW77
EW77
EW77
EW77
EW77
FH 58
FH 78
FH 78
FH 78
FH 78
FH 78
FH 78
FH 78
FH 78
SM 58"Ø
SM 58"Ø
9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0"
148'-0" 15 99'-0" 10
209'-3" 20 244'-0" 22 244'-0" 25 244'-0" 26 244'-0" 24, 17 244'-0" 24 201'-0" 19 195'-0" 18 228'-0" 21 241'-0" 23
129'-6" SIDELIGHTS
247'-0" BEACON
CBP
CBP
CBP
CBP
CBP
CBP
CBP
CBP
UNKNOWN
CBP
CBP
CBP
CBP
CBP
CBP
DISCONNECTED @ SHELTER
DISCONNECTED @ SHELTER
DISCONNECTED @ SHELTER
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Side Elevation Plan View
Photo
Mount Elevation LegAntenna # 1 55'-3" A
Mount Type Azimuth
SIDEARM 330°
Antenna Manufacturer Antenna Model #
LOG PERIODIC VHF 21 EL
TMA (#) / Model # (Coax Quantity) Size
N/A (1) FH 7/8
Antenna Elevation 55'-3"
Carrier______________CBP
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Side Elevation Plan View
Photo
Mount Elevation LegAntenna # 2 60'-6" C
Mount Type Azimuth
PIPE 220°
Antenna Manufacturer Antenna Model #
ANDREW
TMA (#) / Model # (Coax Quantity) Size
N/A (1) EW 77
Antenna Elevation 60'-6"
Carrier______________CBP
VHP4-71W-511
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Side Elevation Plan View
Photo
Mount Elevation LegAntenna # 3 62'-3" A
Mount Type Azimuth
PIPE 15°
Antenna Manufacturer Antenna Model #
ANDREW
TMA (#) / Model # (Coax Quantity) Size
N/A (1) EW 132
Antenna Elevation 61'-0"
Carrier______________CBP
VHP2.5-142W-110
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Side Elevation Plan View
Photo
Mount Elevation LegAntenna # 4 62'-3" A
Mount Type Azimuth
PIPE 285°
Antenna Manufacturer Antenna Model #
ANDREW
TMA (#) / Model # (Coax Quantity) Size
N/A (1) EW 77
Antenna Elevation 63'-6"
Carrier______________CBP
VHP2-71W-511
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Side Elevation Plan View
Photo
Mount Elevation LegAntenna # 5 67'-0" C
Mount Type Azimuth
PIPE 220°
Antenna Manufacturer Antenna Model #
ANDREW
TMA (#) / Model # (Coax Quantity) Size
N/A (1) EW 77
Antenna Elevation 67'-0"
Carrier______________CBP
VHP6-71W-511
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Side Elevation Plan View
Photo
Mount Elevation LegAntenna # 6 70'-6" A
Mount Type Azimuth
PIPE 290°
Antenna Manufacturer Antenna Model #
ANDREW
TMA (#) / Model # (Coax Quantity) Size
N/A (1) EW 77
Antenna Elevation 69'-6"
Carrier______________CBP
VHP2-71W-IM5
PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED
TEP #
Client # Date Page of
LAREDO-WORMSER ROAD
69951_85791
TX8617
OCTOBER 12, 2016
ANTENNA AND MOUNT SKETCH
326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net
Side Elevation Plan View
Photo
Mount Elevation LegAntenna # 7 70'-6" A
Mount Type Azimuth
PIPE 290°
Antenna Manufacturer Antenna Model #
ANDREW
TMA (#) / Model # (Coax Quantity) Size
N/A (1) EW 77
Antenna Elevation 72'-3"
Carrier______________CBP
VHP2-71W-IM5
PROPERTY OF THE UNITED STATES…