PAPI Project Drawings.pdf
PDF 2 MB Posted
- Attached to
- SCREENING INFORMATION REQUEST/REQUEST FOR OFFER 1. Replace 10âx16âshelter. 2. Replace a VASI with a PAPI facility. Federal contract opportunity
- Solicitation number
- 6973GH-19-R-00187
About this file
PAPI Project Drawings (pdf)
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Contractor's Release Form DOT F 4220.4.doc | DOC document | |
| Payment Bond.pdf | ||
| Solicitation 6973GH-19-R-00187 final.pdf | ||
| MALS Project Drawings.pdf | ||
| 00187 QA's.docx | DOCX document | |
| Experience Information Form.pdf | ||
| Performance Bond.pdf | ||
| SIR WAGE DETERMINATION RI190001 as of 6-14-2019.pdf | ||
| PAPI & MALS Technical Specifications.pdf | ||
| PAPI Project Drawings.pdf | ||
| Solicitation 6973GH-19-R-00187 final.pdf | ||
| Experience Information Form.pdf | ||
| PAPI & MALS Technical Specifications.pdf | ||
| Contractor's Release Form DOT F 4220.4.doc | DOC document | |
| Performance Bond.pdf | ||
| Payment Bond.pdf | ||
| MALS Project Drawings.pdf | ||
| SIR WAGE DETERMINATION RI190001 as of 6-14-2019.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
G
F
E
D
C
B
7 6 5 4 3 2 1
H
G
~'\ OF TR4lv.' (5'.,;0
LJ...j a
C 1)
~ -0 z
F cJ
S1ATES 0~
E
INSTALLATION OF A TYPE FA-30200
LED PRECISION APPROACH PATH INDICATOR (PAPI)
TO REPLACE EXISTING VASI D
SERVING R----..... WAY 5
NORTH CENTRAL STATE AIRPORT
PAWTUCKET, RHODE ISLAND
6 5 4 3
C
04/10/2019 CONSTRUCTION, WR#17875 1204108 02/07/2019
REV APPROVED
DATE DESCRIPTION JCN RE DUNE APVD
DATE
DEPARTMENT OF TRANSPORTATION
z
FEDERAL AVIATION ADMINISTRATION g ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA g ---------------- a:: ~ .-- I- fJ rn :i;
Z 0 0 g
PAPI
RUNWAY05
FA-30200 LED PAPI
COVERSHEET
0 "'
PAWTUCKET NORTH CENTRAL STATE AIRPORT RI
REVIEWED BY SUBMITTED BY /~- : \,r A~PROV ~, §, M v.u.'"''£,'v I' ;;,;;{w. iLPt . F,'IA/Al'E,--r. ~,.,J,,c-- u
• £\C VJ fl. H1·'":v /IV/VJ ~~ ..--
PROJECT ENGINEER MGR: ENGINEERING CENTER A I
l------+----f---c--"-'-'--=---'--'-"="-'--,-------+~===-=.=:-:-:-==-=----------1 0
DESIGNED ISSUED BY DATE JCN ,
t----t-------t-DRA-WN----'-,MK ENGINEERINGSERVICEs DRAWINGNO 0411012019 1204~~e !
:: NAVAIDS SFZ-1204108-G001 ~ CHECKED
2 1
'ii 11
C
C , D
" " • • J i::; ~ m .. "~ 8 D
'I' D -m g 0 N 0, 1§ . ., H
G
F
E
D
C
B
A
DRAWING NUMBER
SFZ-1204108-G001
SFZ-1204108-G002
SFZ-1204108-G003
SFZ-1204108-G004
SFZ-1204108-C001
SFZ-1204108-C002
SFZ-1204108-C003
SFZ-1204108-0001
SFZ-1204108-S001
SFZ-1204108-S002
SFZ-1204108-E001
SFZ-1204108-E002
SFZ-1204108-E002
I
DRAWING LIST
DRAWING TITLE
COVER SHEET
INDEX SHEET
GENERAL NOTES AND GFM LIST
GENERAL AIRPORT LAYOUT
FACILITY SITE PLAN
FACILITY SITE DETAILS
MISCELLANEOUS DETAILS
PCA EQUIPMENT INSTALLATION
LHA DESIGN AND FOUNDATION
PCA RACK FOUNDATION
LED PAPI SYSTEM WIRING DIAGRAM
REMOTE CONTROL WIRING WITH A/G
LED PAPI INSTALLATION PROCEDURES (FAA REFERENCE)
7 I 6
A A-G
AGL
ALS
AOA
ARP
ASOS
AT
AWG
BCPS
BGL
BLD
BSCU
C
CFW
CKT
CND
co
COR
cw
DEB
DIA
DISC
DME
DME CO
DPU
DU
DWG
EL
EMT
EOR
FAA
FBO
FDN
FOD
FT
GA
GALV
GFCI
G-G
GFM
GND
GRSC
GS
HZ
!LS
IN
INSUL
KHZ
KV
KVA
LCU
LHA
LIR
LOC
LOM
MALS
MALSF
MALSR
MAX
MG
MHZ
MIN
MP
MS
MSL
N N/A
NAS
NDB
NEC
NOTAM
NWS
OB
OFA
OM
p
PARSONS
PAPI
PCA
PCU
PNL
PR
PRIM
R/W
RAIL
RE
REIL
REL
REQ
RF
RMM
RMMS
RMS
RRCS
RSA
RVR
RT
SAWS
SCH
SEC
SMO
SP
ss
SSC
STA
T T/W
TEL
TELCO
TH
TSA
TSSC
TYP
UPS
V
VASI
VHF
WI
ws
XFMR
XMTR
ABBREVIATIONS
- AMP
- AIR TO GROUND
- ABOVE GROUND/GRADE LEVEL
- APPROACH LIGHT SYSTEM
- AIR OPERATIONS AREA
- AIRPORT REFERENCE POINT
- AUTOMATED SURFACE OBSERVATION SYSTEM (NWS)
- AIR TRAFFIC
- AMERICAN WIRE GAUGE
- BATTERY CHARGING POWER SUPPLY (ILS/LCU)
- BELOW GROUND/GRADE LEVEL
- BUILDING
- BARE SOLID COPPER
- CONTROL
- CENTERFIELD WIND
- CIRCUIT
- CONDUIT (DUCT>
- CONTRACTING OFFICER (FAA)
- CONTRACTING OFFICER'S REPRESENTATIVE (FAA>
- COURSE WIDTH (LOCALIZER)
- DIRECT EARTH BURIAL
- DIAMETER
- DISCONNECT
- DISTANCE MEASURING EQUIPMENT
- DME CORPORATION
- DATA PROCESSING UNIT
- DISTRIBUTION UNIT
- DRAWING
- ELEVATION
- ELECTRIC METALLIC TUBING
- END OF RUNWAY
- FEDERAL AVIATION ADMINISTRATION
- FIXED BASE OPERATOR
- FOUNDATION
- FOREIGN OBJECT DEBRIS
- FEET
- GENERAL AVIATION
- GALVANIZED
- GROUND FAULT CIRCUIT INTERRUPTER
- GROUND TO GROUND
- GOVERNMENT FURNISHED MATERIAL
- GROUND
- GALVANIZED RIGID STEEL CONDUIT
- GLIDE SLOPE ( ILSJ
- HERTZ
- INSTRUMENT LANDING SYSTEM
- INCH
- INSULATED
- KILOHERTZ
- KILOVOLT
- KILOVOLT AMPERE
- LINK CONTROL UNIT CRMMS/RMS)
- LAMP HOUSING ASSEMBLY <PAPI)
- LOW IMPACT RESISTANCE
- LOCALIZER (!LS)
- LOCATOR OUTER MARKER (NOB & OM)
- MEDIUM INTENSITY APPROACH LIGHTING SYSTEM
- MALS WITH SEQUENCED FLASHERS
- MALS WITH RUNWAY ALIGNMENT INDICATOR LIGHTS CMALS-RAIL)
- MAXIMUM
- MAST-ON-GROUND CLIR)
- MEGAHERTZ
- MINIMUM
- MULTI-POINT (GROUND)
- MAST-ON-STAND CLIR)
- MEAN SEA LEVEL
- NEUTRAL
- NOT APPLICABLE
- NATIONAL AIRSPACE SYSTEM
- NON-DIRECTIONAL BEACON
- NATIONAL ELECTRIC CODE
- NOTICE TO AIRMEN
- NATIONAL WEATHER SERVICE
- OBSTRUCTION
- OBJECT FREE AREA
- OUTER MARKER ( ILSJ
- POWER
- PARSONS CORPORATION CTSSC)
- PRECISION APPROACH PATH INDICATOR
- POWER AND CONTROL ASSEMBLY
- POWER AND CONTROL UNIT
- PANEL
- PAIR
- PRIMARY
- RUNWAY
- RUNWAY ALIGNMENT INDICATOR LIGHTS
- RESIDENT ENGINEER CFAA/TSSCJ
- RUNWAY END IDENTIFIER LIGHTS
- RUNWAY EDGE LIGHTS
- REQUIRED
- RADIO FREQUENCY
- REMOTE MAINTENANCE MONITORING
- REMOTE MAINTENANCE MONITORING SYSTEM
- REMOTE MONITORING SUBSYSTEM
- REMOTE RADIO CONTROL SYSTEM
- RUNWAY SAFETY AREA
- RUNWAY VISUAL RANGE
- REMOTE TRANSMITTER
- STAND ALONE WEATHER SENSOR
- SCHEDULE
- SECONDARY
- SYSTEM MANAGEMENT OFFICE (FAA)
- SINGLE-POINT (GROUND)
- STAINLESS STEEL
- SYSTEM SUPPORT CENTER CFAAJ
- STATION
- TELEPHONE
- TAXIWAY
- TAXIWAY EDGE LIGHTS
- TELEPHONE COMPANY
- THRESHOLD
- TAXIWAY SAFETY AREA
- FAA TECHNICAL SUPPORT SERVICE CONTACT (PARSONS)
- TYPICAL
- UNINTERRUPTIBLE POWER SOURCE/SUPPLY
- VOLT
- VISUAL APPROACH SLOPE INDICATOR
- VERY HIGH FREQUENCY
- WITH
- WIND SOCK
- TRANSFORMER
- TRANSMITTER
SYMBOLS LEGEND
SUBTITLE REFERENCE
REFERENCE NUMBER/LETTER
(PLAN, DETAIL, ELEVATION OR SECTION)
-r x\ xxxxxxxxxxx 'x{~X)j/ SCALE: X=XXX
'-scALE
SHEET NUMBER(Sl WHERE CALLOUTCS) TO PLAN, DETAIL, ELEVATION OR SECTION IS/ARE LOCATED
ELEVATION CALLOUT REFERENCE
/ x'""
X I
ELEVATION REFERENCE LETTER
SHEET NUMBER WHERE
ELEVATION rs LOCATED
SECTION CALLOUT REFERENCE
/ x'\.._ xx
SECTION REFERENCE LETTER
SHEET NUMBER WHERE
SECTION IS LOCATED
DETAIL CALLOUT REFERENCE
DETAIL REFERENCE NUMBER
(x~ xx
SHEET NUMBER WHERE
DETAIL IS LOCATED
DRAWING PREFIXES
CXXX - CIVIL
EXXX - ELECTRICAL/ELECTRONIC
GXXX - GENERAL
QXXX - EQUIPMENT
SXXX - STRUCTURAL
04/10/2019 CONSTRUCTION, WR #17875 1204108 02/07/2019
REV APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE Af'VO
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAPI
RUNWAY05
FA-30200 LED PAPI
INDEX AND ABBREVIATION SHEET
PAWTUCKET NORTH CENTRAL STATE AIRPORT
REVIEWED BY SUBMITTED BY •
1--~---1 M KUSEK jvt~{« /i-cf
APPROVED BY "-_
s!fffv::t~
PROJECT ENGINEER MGR: ENGINEERING CENTER
DESIGNED !SSUEDBY DATE
04/10/2019 IJCN MK
ENGINEERING SERVICES DRAWN DRAWING NO
MK NAVAIDS
CHECKED SFZ-1204108-G002 MK
2 I 1
RI
1204108
REV
H
G
F
E
D
THIS DRAWING PRODUCED ON NEW ENGLAND REGION MICROSTATION SYSTEM
G
F
E
D
C
B
A
8 7 6
GENERAL NOTES:
1. THIS DRAWING PACKAGE INDICATES WORK REQUIRED FOR THE INSTALLATION AND ESTABLISHMENT OF A PRECISION
APPROACH PATH INDICATOR (PAPI) TO SERVE RUNWAY 5 NORTH CENTRAL STATE AIRPORT IN LINCOLN/ SMITHFIELD/ PAWTUCKETT, RHODE ISLAND. THIS DRAWING PACKAGE ALSO INDICATES REQUIRED POWER SUPPLY AND CONTROL,PROVISIONS
ASSOCIATED WITH THE INSTALLATION AND ESTABLISHMENT OF THIS FACILITY.
2. WORK ASSOCIATED WITH THE PAPI AND RELATED FACILITIES IS LOCATED ON NORTH CENTRAL STATE AIRPORT.
NO MOVEMENT BY CONTRACTOR, SUBCONTRACTORS, OR DELIVERY VEHICLES SHALL BE MADE ON THE ACTIVE AIR OPERATIONS AREA CADA) OR AIRCRAFT MOVEMENT AREA WITHOUT ESCORT BY THE FAA CONTRACTING
OFFICERS REPRESENTATIVE CCOR), THE RESIDENT ENGINEER (RE), OR DESIGNATED
CONTRACTOR ESCORT VEHICLE. THE CONTRACTOR SHALL CERTIFY IN WRITING THAT ALL DRIVING EMPLOYEES, SUBCONTRACTOR EMPLOYEES, AND DELIVERY EMPLOYEES HAVE READ AND UNDERSTAND THE FAA AIRPORT GROUND
VEHICLE OPERATIONS GUIDE (DOT/FAA/ASY-300 98/001) PER FAA ORDER 5200,7A.
3. THE CONTRACTOR SHALL ARRANGE FOR AND ABIDE BY ALL SECURITY BADGING AND ACCESS REQUIREMENTS AT NORTH cENTRAL STATE AIRPORT TO WORK ON THE AIRFIELD. SECURITY BADGING MAY BE REQUIRED, AND SHALL BE
ON DISPLAY AT ALL TIMES WHILE ON THE AIRFIELD,
4. CONTRACTOR ACCESS ROUTES, STAGING AREAS, AND EMPLOYEE PARKING AREAS SHALL BE APPROVED IN ADVANCE
BY NORTH CENTRAL STATE AIRPORT.
5. CONTRACTOR'S VEHICLES SHALL BE EQUIPPED WITH A YELLOW ROTATING BEACON AND/OR AN APPROVED ORANGE AND
WHITE FLAG.
6, CONTRACTOR'S CREW SHALL BE EQUIPPED WITH A RADIO AND SHALL MONITOR CTAF AT 123,075,
7. WORK ON THE ADA AND WITHIN 250 FEET OF RUNWAY 5 CENTERLINE AND 1000 FEET FROM THE RUNWAY THRESHOLD (DEFINED AS THE RUNWAY CONSTRUCTION SAFETY AREA) WILL REQUIRE A RUNWAY SHUTDOWN. ANY ACTIVITIES INVOLVING CRANES OR OTHER EQUIPMENT EXCEEDING 15 FEET IN HEIGHT MAY ALSO REQUIRE A RUNWAY SHUTDOWN OR OTHER PROVISIONS. COORDINATE ALL SUCH ACTIVITIES AND REQUIRED SHUTDOWNS WITH
THE COR/RE, ANO AIRPORT MANAGEMENT AT LEAST 48 HOURS IN ADVANCE.
8. WORK ASSOCIATED WITH ANY FAA FACILITY MAY REQUIRE A SHUTDOWN. COORDINATE ALL RELATED ACTIVITIES AND REQUIRED SHUTDOWNS WITH THE COR, RE, AND PROVIDENCE SSC AT LEAST 48 HOURS IN ADVANCE.
9. THE CONTRACTOR SHALL MAINTAIN A CLEAN WORK SITE. EQUIPMENT AND MATERIAL SHALL BE REMOVED FROM THE WORK SITE AT THE END OF EACH WORK SHIFT. THE CONTRACTOR SHALL KEEP THE WORK SITE FREE OF CONSTRUCTION DEBRIS ANO OTHER FOREIGN OBJECT DEBRIS (FOD) AT ALL TIMES, THE CONTRACTOR SHALL CONDUCT FOD INSPECTIONS OF ALL VEHICLES PRIOR TO DRIVING ON THE ADA. THE CONTRACTOR SHALL BE PREPARED TO REMOVE ANY DUST, DIRT, MUD, OR OTHER FOD TRACKED OR OTHERWISE LEFT ON THE ADA AT ALL TIMES.
10. THE CONTRACTOR SHALL STRICTLY COMPLY WITH ALL OSHA REGULATIONS AT ALL TIMES. THE COR AND/OR RE RESERVES THE RIGHT TO SUSPEND THE PROJECT SHOULD HE OR SHE DETERMINE THAT AN UNSAFE CONDITION EXISTS.
11. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL MATERIAL UNLESS OTHERWISE INDICATED. THE CONTRACTOR SHALL PROVIDE ALL LABOR, EQUIPMENT, AND REQUIRED TEMPORARY POWER UNLESS OTHERWISE INDICATED,
12. ALL MATERIAL FURNISHED FOR THIS PROJECT IS INDICATED AS "GOVERNMENT FURNISHED MATERIAL CGFM)".
THE GFM LIST INCLUDES SPARES FOR SOME ITEMS. ALL SPARES SHALL BE RETURNED TO THE FAA, IN WORKING ORDER, AT THE CONCLUSION OF THE CONSTRUCTION. GFM WILL BE DELIVERED TO THE AIRPORT BY THE GOVERNMENT.
13. THE CONTRACTOR SHALL LEGALLY DISPOSE OF ALL MATERIAL AND EQUIPMENT NOT RETURNED TO OR RETAINED BY
THE FAA,
14. THE CONTRACTOR SHALL FOLLOW ALL LATEST REVISIONS OF ORDERS AND SPECIFICATIONS.
SITE WORK:
1. ALL DIMENSIONS, ELEVATIONS, CONTOURS, AND HEIGHTS INDICATED ARE APPROXIMATE AND SHALL BE VERIFIED IN
THE FIELD BY THE CONTRACTOR.
2. ALL TRENCHES AND EXCAVATIONS SHALL BE BACKFILLED AND COMPACTED TO MATCH THE EXISTING GRADE BEFORE LEAVING THE SITE EVERYDAY. STEEL PLATES MAY BE USED AS AN ALTERNATIVE WITH WRITTEN PERMISSION FROM
THE COR AND AIRPORT AUTHORITY/ AIRPORT OPERATIONS.
3. EXISTING UTILITY LOCATIONS SHOWN ARE APPROXIMATE. OTHER UTILITIES MAY NOT BE SHOWN. THE CONTRACTOR SHALL FIELD LOCATED ALL SUBSURFACE UTILITIES PRIOR TO ANY EXCAVATION OR DIRECTIONAL BORING OPERATIONS.
DIRECT EARTH BURIED <DEB) RUNWAY AND TAXIWAY LIGHTING POWER CABLES AND OTHER FAA FACILITY POWER CABLES ARE HIGH VOLTAGE. FORTY-EIGHT (48) HOUR (MINIMUM) NOTICE BY THE CONTRACTOR TO THE COR, THE AIRPORT AUTHORITY, AND THE FAA SSC IS REQUIRED FOR ALL UTILITY MARKING AND/OR FACILITY SHUTDOWNS.
4. THE CONTRACTOR SHALL BE PREPARED TO IMMEDIATELY REPAIR ANY UTILITIES DAMAGED DURING EXCAVATION
OPERATIONS AND SHALL PERFORM ALL SUCH REPAIRS AT CONTRACTOR EXPENSE.
5. ALL UNDERGROUND CABLE SHALL BE IN CONDUIT EXCEPT FOR BARE COPPER GROUND WIRE, GUARD WIRE, COUNTERPOISE, AND WHERE OTHERWISE INDICATED. UNDERGROUND CONDUIT SHALL BE 24 INCHES (MINIMUM) BELOW GRADE EXCEPT WHEN INTERFACING HANDHOLE ENTRANCES OR EXISTING CONDUIT AT OTHER DEPTHS OR WHERE OTHERWISE INDICATED.
UNDERGROUND CONDUIT SHALL BE GALVANIZED RIGID STEEL CONDUIT CGRSC) EXCEPT WHERE OTHERWISE INDICATED.
GRSC FITTINGS SHALL BE THREADED TYPE. EXPOSED THREADS SHALL BE SEALED WITH APPROVED SEALANT TO PREVENT CORROSION PRIOR TO BACKFILL OPERATIONS. CONDUIT SHALL BE CLEANED OF DEBRIS, AND A NYLON PULL STRING
SHALL BE INSTALLED IN ALL CONDUITS.
6. ALL EXTERIOR CONDUITS ENTERING BUILDINGS (EXCEPT THOSE WITH GROUNDING CONDUCTORS ONLY) SHALL HAVE EXPANSION COUPLINGS. AN APPROVED GROUND JUMPER SHALL BE INSTALLED BETWEEN METALLIC CONDUIT ON EACH
SIDE OF COUPLING UNLESS COUPLING IS INTERNALLY GROUNDED.
7. FABRICATE AND INSTALL CONCRETE DUCT MARKERS IN ACCORDANCE WITH FAA-C-1391. DUCT MARKERS SHALL BE DYED ORANGE AND INSTALLED AT THE MIDPOINT OF DUCT RUNS LONGER THAN 200 FEET, AT DUCT CHANGE OF DIRECTION, EACH SIDE OF RUNWAY, TAXIWAY OR ROAD CROSSING, WHERE INDICATED ON THE DRAWINGS, AND AS DIRECTED BY THE RESIDENT ENGINEER OR COR. TOP OF DUCT MARKERS SHALL EXTEND NO MORE THAN 1 INCH ABOVE FINISH GRADE.
DUCT MARKERS ARE ONLY REQUIRED WHERE SERVICES IN CONDUIT CROSS RUNWAYS OR TAXIWAYS.
8. BACKFILL FDR CABLE OR DUCT TRENCHES OR FOR OTHER EXCAVATIONS SHALL BE PLACED IN LAYERS NOT EXCEEDING 8 INCHES, AND EACH LAYER SHALL BE THOROUGHLY COMPACTED TO WITHIN 95% OF MAXIMUM DENSITY OF OPTIMUM MOISTURE CONTENT IN ACCORDANCE WITH AASHTO T-180. WHERE FILL IS REQUIRED IN THE RUNWAY/TAXIWAY SAFETY AREA, WORK SHALL COMPLY WITH FAA AC 150/5370-10. IF REQUIRED, THE CONTRACTOR SHALL ARRANGE FOR AN
INDEPENDENT FIELD TEST TO VERIFY PROPER COMPACTION.
9. THE EXISTING GRADE SURROUNDING THE FOUNDATION OR TRENCH WORK SHALL BE STABILIZED AND PROTECTED FROM EROSION DURING AND IMMEDIATELY AFTER COMPLETION OF THE FOUNDATION OR CONDUIT INSTALLATION ANO ALL
REQUIRED EXCAVATION AND BACKFILL.
FAA
10. ALL DISTURBED AREAS SHALL BE RESTORED TO PRIOR CONDITION AT A MINIMUM. FINAL CONDITION SHALL BE APPROVED
BY THE FAA AND THE AIRPORT AUTHORITY.
11. ANY WORK WITHIN 5 FEET OF FAA OR AIRPORT FACILITY SHALL BE HAND DUG.
DEMOLITION:
1. THE CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF THE EXISTING RUNWAY 5 VASI EQUIPMENT, INCLUDING BUT LIMITED TO
CONCRETE FOUNDATIONS AND LAMP HOUSING ASSEMBLIES CLHA). DIRECT EARTH BURIED <DEB) CABLES MAY BE ABANDONED IN
PLACE UNLESS OTHERWISE NOTED.
2. THE CONTRACTOR SHALL BACKFILL AND COMPACT ALL AREAS WHERE FOUNDATIONS AND VASI EQUIPMENT HAVE BEEN REMOVED. ALL DISTURBED AREAS SHALL BE LOAMED, SEEDED AND THE FINISH GRADE SHALL MATCH THE SURROUNDING AREA.
8 7 6
5 4 3
FOUNDATION WORK:
1. ALL CONCRETE WORK SHALL COMPLY WITH ACI-304, "RECOMMENDED PRACTICE FOR MEASURING, MIXING, AND PLACING
CONCRETE", ACI-308, "STANDARD PRACTICE FOR CURING CONCRETE", AND ACI-347, "RECOMMENDED
PRACTICE FOR CONCRETE FORMWORK".
2. CONCRETE SHALL DEVELOP 3000 PSI COMPRESSIVE STRENGTH IN 28 DAYS WITH A MAXIMUM SLUMP OF 3 INCHES AND A
MAXIMUM AGGREGATE SIZE OF 3/4 INCHES.
3. ALL REINFORCEMENT STEEL SHALL COMPLY WITH ASTM A615, GRADE 60.
4. ALL ANCHOR BOLTS AND OTHER HARDWARE SHALL BE GALVANIZED, UNLESS OTHERWISE INDICATED.
5. EXPANSION ANCHORS, IF USED, SHALL BE HILT! HSL HEAVY DUTY ANCHORS OR APPROVED EQUAL AND SHALL
BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
EQUIPMENT INSTALLATION:
1. ASSEMBLE AND INSTALL PAPI AND ASSOCIATED EQUIPMENT PER MANUFACTURER'S INSTRUCTIONS.
2. USE ANTI-SEIZE COMPOUND ON ALL THREADED PARTS.
3. ALL CHANNEL SHALL BE GALVANIZED STEEL METAL STRUT, UNLESS OTHERWISE INDICATED.
4. ALL HARDWARE SHALL BE GALVANIZED STEEL, UNLESS OTHERWISE INDICATED.
ELECTRICAL WORK:
1. ALL ELECTRICAL WORK SHALL CONFORM TO FAA-C-1217 ANO FAA-C-1391 SPECIFICATIONS AND IN NO CASE
SHALL VIOLATE THE NATIONAL ELECTRIC CODE CNFPA 70, NEC).
2. THE CONTRACTOR SHALL MAKE ALL POWER SERVICE. CONTROL, AND GROUND TERMINATIONS.
3. ALL FLEXIBLE LIQUIDTIGHT CONDUIT SHALL HAVE A INTERNAL EQUIPMENT GROUNDING CONDUCTOR, 4, ALL CONTROL/DATA CABLE SHALL BE TWISTED, SHIELDED.
5. ALL CIRCUITS SHALL HAVE INDIVIDUAL NEUTRAL AND GROUNDING CONDUCTORS.
NO SHARED NEUTRALS OR GROUNDS WILL BE PERMITTED, EXCEPT AS REQUIRED BY THE NEC
6. NEUTRAL CONDUCTORS SHALL REMAIN ISOLATED FROM GROUND IN ALL LOCATIONS EXCEPT AT POWER SERVICE ENTRANCE.
7. WHERE POSSIBLE, POWER CABLES AND CONTROL/DATA CABLES SHALL RUN IN CONDUIT INDEPENDENT OF EACH OTHER.
SEPARATE POWER AND CONTROL/DATA CABLES IN COMMON HANOHOLES, ENCLOSURES, AND SHELTER SQUARE DUCT WIREWAY.
8. ALL CABLES SHALL BE PROPERLY COLOR CODED AND PERMANENTLY LABELED AT EACH END AND IN EACH HANDHOLE.
ALL CABLES IN HANDHOLES SHALL BE LOOPED AROUND SEVERAL TIMES.
9. A DYNAMOMETER GRADUATED TO ACTUALLY INDICATE THE PROPER TENSION FOR ANY CABLE PULLED THROUGH UNDERGROUND CONDUIT OR DUCT SHALL BE USED UNLESS THE CONTRACTOR ADAPTS A HARNESS OF THE PROPER SIZED ROPE THAT WILL LIMIT THE TENSION OF THE PULL. ANY COMBINATION OF CABLES PULLED IN CONDUIT OR DUCT SHALL NOT EXCEED THE
SUM OF THE INDIVIDUAL ALLOWABLE TENSION OF EACH CABLE PLUS 15%,
10. SPLICES SHALL BE AVOIDED TO THE MAXIMUM EXTENT POSSIBLE. HIGH VOLTAGE C5KV) SPLICES SHALL BE MADE ONLY WITH WRITTEN APPROVAL FROM THE COR. ALL OTHER UNDERGROUND SPLICES SHALL BE LOCATED IN HANDHOLES
ONLY AND AS APPROVED BY THE COR.
11. PVC CONDUIT SHALL BE SCH 40 UNLESS OTHERWISE NOTED.
12. NO CONDUCTORS SMALLER THEN #6 AWG SHALL BE RE-COLORED WITH TAPE TO DESIGNATE NEUTRAL (WHITE) OR (GROUND)
WIRE SHALL BE COLORED APPROPRIATELY AS MANUFACTURED PER NEC.
13. CONTRACTOR SHALL SUPPLY TWO SPARE FUSES FOR EACH FUSE INSTALLED.
ELECTRICAL GROUNDING:
2.
3.
4.
5.
6.
7.
8.
9, 1 0.
ALL ELECTRICAL ANO ELECTRONICS GROUNDING SHALL MEET OR EXCEED ALL PROVISIONS OF THE LATEST EDITION OF:
FAA-STD-019. LIGHTNING AND SURGE PROTECTION, GROUNDING, BONDING AND SHIELDING REQUIREMENTS FOR FACILITIES ANO ELECTRONIC EQUIPMENT. NATIONAL ELECTRICAL CODE (NEC): NFPA 780. STANDARD FOR THE
INSTALLATION OF LIGHTNING PROTECTION SYSTEMS.
ALL GROUND RODS SHALL BE COPPER CLAD STEEL, 3/4 INCH DIAMETER AND 10 FEET LONG. GROUND RODS
SHALL BE DRIVEN SUCH THAT THE TOP OF ROD IS NO LESS THAN 12 INCHES BELOW GRADE.
ALL UNDERGROUND GROUND CONNECTIONS SHALL BE EXOTHERMICALLY WELDED UNLESS OTHERWISE INDICATED; WELD
INTEGRITY SHALL BE VERIFIED BY A HAMMER TEST.
ALL UNDERGROUND GRSC SHALL BE GROUNDED BY A 2 AWG BARE COPPER GROUND EXOTHERMICALLY WELDED
TO THE GRSC AND THE COUNTERPOISE.
UNDERGROUND GROUNDING CONDUCTORS SHALL BE 24 INCHES (MINIMUM) BELOW GRADE EXCEPT AT GROUND RODS AND
AS OTHERWISE INDICATED,
ALL CABLE ARMOR SHALL BE GROUNDED AT PCA CABINET, USING A METHOD APPROVED BY THE COR/RE.
ALL MULTI-PAIR CONTROL/DATA CABLE SHIELDS SHALL BE GROUNDED AT ONE END.
ALL UNUSED MULTI-PAIR CONTROL/DATA CABLES SHALL BE GROUNDED AT BOTH ENDS.
WHEN INSTALLING MULTIPLE GROUND CONDUCTORS TO ONE GROUND LUG, THE CONTRACTOR SHALL
PROVIDE A BUSBAR.
A 1/0 AWG BARE COPPER STRANDED GUARD WIRE SHALL BE INSTALLED OVER ALL BURIED CABLES AND CONDUCTORS NOT ROUTED IN GALVANIZED RIGID STEEL CONDUIT. THE GUARD WIRE SHALL BE EMBEDDED IN THE SOIL, A MINIMUM OF 10 INCHES ABOVE THE CABLE TO BE PROTECTED, AND LOCATED DIRECTLY ABOVE AND PARALLEL TO THE LINES OR CABLES BEING PROTECTED. THE GUARD WIRE SHALL BE BONDED TO THE EARTH ELECTRODE SYSTEM (EES) AT EACH END AND TO GROUND RODS AT APPROXIMATELY 90-FOOT INTERVALS USING EXOTHERMIC WELDS. THE SPACING BETWEEN GROUND RODS SHALL VARY BY 10% TO 20% TO PREVENT RESONANCE. GROUND RODS SHALL BE INSTALLED APPROXIMATELY 6 FEET ON EITHER SIDE OF THE TRENCH. WHERE CABLES RUN ADJACENT TO THE EDGE OF A RUNWAY, THEY SHALL BE LOCATED
10 FEET FROM THE RUNWAY EDGE LIGHTS ON THE OUTSIDE OF THE EDGE LIGHTS,
TESTING:
1. THE CONTRACTOR SHALL TEST ALL EQUIPMENT, CABLES AND THE EARTH ELECTRODE SYSTEM IN COORDINATION
WITH ON SITE FAA PERSONNEL.
2. CONTRACTOR SHALL PERFORM INSULATION RESISTANCE TESTS ON ALL WIRES INSTALLED. CONTROL CABLE SHALL BE TESTED PER FAA ORDER 6000.204, CHAPTER 3 PARAGRAPH 10 SECTIONS A,B, and C.
POWER CABLE SHALL BE TESTED PER FAA ORDER 6950.22A, CHAPTER 3 PARAGRAPHS 3-2, 3-4, and 3-4 AS APPLICABLE. THE CORRECT TESTING VOLTAGE MUST BE SELECTED USING THE GUIDANCE PROVIDED
IN THE ORDERS TO PREVENT DAMAGE TO CABLE INSULATION,
3. CONTRACTOR SHALL TEST EACH EARTH ELECTRODE GROUNDING SYSTEM PER FAA HANDBOOK 010, CHAPTER 4 PARAGRAPH 2 SECTION 3. IF THE TEST RESULTS IN A READING HIGHER THAN 10 OHMS, THE CONTRACTOR SHALL REFER TO THE COR OR RE FOR FURTHER GUIDANCE. SUBMIT DETAILED DATA AND GRAPHS AS SHOWN IN THIS
STANDARD FOR EACH FACILITY.
4. ALL TESTS TO CABLE, EQUIPMENT AND EARTH ELECTRODE SYSTEMS MUST BE PERFORMED IN THE PRESENCE OF THE COR OR RE. TESTS CONDUCTED WITHOUT THE COR OR RE PRESENT WILL BE REJECTED.
5 + 4 3
GOVERNMENT FURNISHED MATERIAL
ITEM DESCRIPTION
1 LAMP HOUSING ASSEMBLY CLHA)
POWER AND CONTROL ASSEMBLY CPCA)
INCLINOMETER (AIMING DEVICE)
SPARE COMPONENTS
TECHNICAL INSTRUCTION BOOK.
AIR-TO-GROUND RECEIVER CONTROLLER
AND ANTENNA
FRANGIBLE COUPLINGS
REV
04/10/2019
APPROVED
DATE
CONSTRUCTION, WR#17875
DESCRIPTION
QUANTITY
4 EACH
1 EACH
1 EACH
1 SET
2 SETS
1 EACH
1 9 EACH
1204108 02/07/2019
JCN REDLINE
DATE
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
Af'VD
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAPI
RUNWAY OS
FA-30200 LED PAPI
GENERAL NOTES
PAWTUCKET NORTH CENTRAL STATE AIRPORT
REVIEWED BY
SUBMITTED BY
PROJECT ENGINEER MGR: ENGINEERING CENTER
DATE 04/10/20191 JCN
DRAWING NO
DESIGNED ISSUED BY
MK
ENGINEERING SERVICES DRAWN
SFZ-1204108-G003
MK NAVAIDS
CHECKED
MK
2 I 1
RI
1204108
REV
H
G
F
E
D
C ii u.
w
THIS DRAWING PRODUCED ON NEW ENGLAND REGION MICROSTATION SYSTEM
G
F
E
D
C
B
A
7 6
EXISTING VASI
TO BE REMOVED~
Ill
RUNWAY 5 RSA LIMIT
-0
"' N r--- ' t0 I + i r--- ' I- I V) '
1 LAMP HOUSING
,,------t--S-0-01---;ASSEMBL Y (TYP)
I I
I
I
I I
I
I I
I I
I
I I
I
I I
I I
I I
I
I I
I I
I I I
I
I I
I
I I
I I
I I
I
I I
I I
I
I
I
----------------150'-0FF-C-ENfERLINE ----- --- --------------------------------1----------------- ----1
TAXIWAY B
DIRECTIONAL BORE 3 - 2" HDPE CONDUITS
UNDER TAXIWAY B (SEE NOTES 6 & 7)
.-l
I/ I/
IJ
I I I
D
I I
I
@ PCA RACK AND FOUNDATION
I
I ' I
INST ALL NEW RACK
MOUNTED DISCONNECT
NOTES:
1. THE CONTRACTOR SHALL PROPERLY REMOVE AND DISPOSE OF VASI EQUIPMENT
AND FOUNDATIONS.
EXISTING 120/240V
TRANSFORMER
(SEE NOTE 8) -----_
EXISTING AWOS
EQUIPMENT __ _/
2. ALL DIRECT EARTH BURIED (0.E.B. l CABLE SUPPORTING THE EXISTING VASI SHALL BE
ABANDONED IN PLACE.
3. HANDHOLE LOCATIONS ARE APPROXIMATE AND SHALL BE PLACED AT A DISTANCE NO
GREATER THAN 400'.
4. POWER AND CONTROL EQUIPMENT SUPPORTING PAPI TO BE MOUNTED ON A RACK OUTSIDE OF THE RSA AND ROFA. POWER FOR FACILITY TAKEN FROM TRANSFORMER LOCATED NEAR AWOS EQUIPMENT.
5. TO MINIMIZE OUTAGES TO THE AIRPORT SERVICE, WORK NEAR THE RUNWAY MAY REQUIRE NIGHTWORK.
6. PULL 3 - 2" HOPE CONDUIT THROUGH A DIRECTIONALLY DRILLED HOLE. DIRECTIONAL DRILLING
SHALL BE 6' UNDER TAXIWAY B TO ENSURE SUB-BASE IS NOT IMPACTED.
7. 1/0 GUARDWIRE ABOVE DIRECTION BORING TO RUNWAY EDGE. TERMINATE GUARDWIRE AT A GROUND ROD EDGE
PAVEMENT
8. EXISTING TRANSFORMER
7 6
-,-1-l-.... @-co-co_3..,. //
I ' ,"' ... , I \
I \
.' EXISTING \
l CIRCLE I
\ WIND TEE /
\ I
\ I ', .,," ' ;
I / I / I / I / I / I /-... /
,-._ I
I ~'¼;
-.JI~
I 1-..J '<(i"-
1 0 10 Q::,IJ-.;
I lf)'0 I "'/0 I ;,._,'4.
I lJ,';s
't<,:~~-_-::= ____________ J 3'6 D o ~~
C001
I I
I I
I
I
FACILITY SITE PLAN
SCALE: 1"=60'
I I
I I
I I
I I
I I
I
I
I I
I I
I I
I
I I
I I
I I
I
I I
I I
I I
I I
I
I I
I I
I
I I
I I
I
I I
I I
60' 0 60' i------~-SCALE: 1" = 60'
I
I
120'
I
I I
I I
2 1
L ___ _
~ EXISTING VASI
r/' TO BE REMOVED
Ill
REV
04/10/2019 CONSTRUCTION, WR#17875 1204108 02/07/2019
APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE APVD
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAWTUCKET
PAPI
RUNWAY05
FA-30200 LED PAPI
SITE PLAN
NORTH CENTRAL STATE AIRPORT
REVIEWED BY SUBMITTED BY /I
1--~--1 M. KUSEK r\p}J.,v._, te«
PROJECT ENGINEER MGR: ENGINEERING CENTER
RI
MK ISSUED BY DATE 04/10/2019 JCN 1204108
f---+---+=-oRA=w~N---~=--i ENGINEERING SERVICES 1-D_RA_w-,N-G-No---"-'-'-'-'=-"'-'-----"'"'-r'R""Ev"-'
DESIGNED
1---+---+c-~~--~M=-iK NAVAIDS
CHECKED
MK SFZ -1204108-C001
2 1
H
G
F
E
D
C z
I I 0 m ii 5:
Cl w
!!2
THIS DRAWING PRODUCED ON NEW ENGLAND REGION MlCROSTATION SYSTEM
G
F
E
D
C
B
A
I I
0 ' ~ ~ I D 0,----------------------------~',-----,------------7~ :,: I w l/) 0 E et::
w • I :c ~ r-- L I-f- 't' !
"' r--- I ,.. 8 i
"' >- I z <( ' :::, >- I a:: V) '
~ ~~f~H¾r-/fft E -3 -3 0-,- - - - - - - --(§-i;
I I
LHA
EL 430'
300'
I I I I
~t~fFkli{w;1t:-3'-m~-------Q-=,hi ~ 1111
11 !I
,'.'.-:::,_ 11 II 8 1111
E_AE.1...LHll_ #3 __ ~---,-------1 ,II
AIMING ANGLE 2 50 ~ !/ 11111
ll HI __. 111 U1 iii UI
PAP I L HA #4 r;:::::\ _111 111
AIMING ANGLE2 30,- ------~,:~,,,:::
1111!11 1il1 llll
1111 IUI
111111!1 "'111111
1111 UII
11111111 1111!11
' 1 '\ 5 PAPI SITE PLAN
\.coo;1 SCALE: 1"=30'
'/ 1 ' 1,_5001
"" N z a::
D f-
LAMP HOUSING
ASSEMBLY ( TYP )
EFFECTIVE VISUAL THRESHOLD
CROSSING HEIGHT 42 FEET
THRESHOLD CL
425'MSL
PAPI OBSTACLE CLEARANCE CRITERIA
'C002 NOT TO SCALE ( REFERENCE ONLY)
7 6
5 +
4 3 z a::
u..
D w I "' 0 ' w I
31 z, :::, I a::, u..l o' I w' zl :;j a::, WI f-, Zj w, ul
I ' I
>- ' <( I 3 ' z I :::, ' a:: I u.. ' D I
' w I 0 I w ' I LHA LIGHT PLANE
I 1 , ABOVE R/W
' CENTERLINE ELEV I
I LHA #~o' I LHA #~o' I LHA ;iz.0 , I LHA #1 so' I !
EL 429' (+/-J---~ ----------- ~ ------------ ----------- ~r-----------------------!------------ ---------~
-----¥-Jl+-----,,-,--;+JU,--------tL.JL.l!,-------,µ~==-------i! _____ t-,' -===-=-.c::;.Ek_4_30' _
~~~ >~ i i
/ 2' ,coo~
I I
PAPI PROFILE - STA 8+49.6
NOT TO SCALE
NOTES:
1. LHA #1 SHALL BE LOCATED 50' O.C. FROM FUTURE EDGE OF PAVEMENT.
20'-0" O.C. SHALL SEPARATE ALL LHA'S.
2. USING AIMING DEVICE PROVIDED, CONSTRUCT LHAs SO THAT EACH JS
AIMED AS PROVIDED ON THIS DRAWING.
REV
04/10/2019 CONSTRUCTION, WR #17875 1204108 02/07/2019
APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE
H
G
F
E
D
C
APVD
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
4 3
PAPI
RUNWAY OS
FA-30200 LED PAPI
FACILITY SITE DETAILS
PAWTUCKET NORTH CENTRAL STATE AIRPORT
REVIEWEDBY SUBMITTEDBY N~'k" (?_7 A.::.'.2~, --~...J.-
M. KUSEK '-----· S. FINN. ~
PROJECT ENGINEER
DESIGNED
MK
DRAWN
MK
CHECKED
MK
ISSUED BY
ENGINEERING SERVICES
NAVAIDS
MGR: ENGINEERING CENTER
DATE 04/10/2019 IJCN
DRAWING NO
SFZ-1204108-C002
RI
C
A!
1204108 ~ REV i fil
THIS DRAWING PRODUCED ON NEW ENGLAND REGION MIGROSTATION SYSTEM
G
F
E
D
C
B
A
7 6
LUJAOUITH LIGHT
~ BASE CAN ( TYP l 12-1/C 10 AWG
4-1/C 10 AWG, GREEN GND
IN 2" SCH 40 PVC
2" GRSC SWEEP (TYP
LHA #4
.-.I. =D==-===- ~ W--- --------- \\
IJ ------ --,
- --LJ--- 0 \ '
4-2PR 18 AWG CONTROL
4-1/C 6 AWG, GREEN
IN 2" SCH 40 PVC
-----11--.;-' - -n----- - - - ''' \11 I ...._ I \ l!="==========!~~~=='.J ) \ \ I \ 11 ' I \ I I
----- Ji \ \ II
T LHA #3
II : : 11
11 : : jl jl
II : :
-=--=--=--=--=---s 1-"r - =-c::r- -_ ::..::\+-r= ~ i 11 ==-== <t-====:::::::----117----,, 'f :-- II
1/0 AWG TEED
OFF OF 1 /0 AWG
USING EXOTHERMIC
WELD (6 PLSl
<> i==tffl )::.:-.=tJ:it.=--=C)::: -- - - - I I I I I \ \ I - ~ ~, I 11
'11=:l=====~==~=:::::!J / "\ \ 11 '4 ,: II
'-- , / \\II: 1111
----- 11 11 i / 1111 11 I I : i II I I
11 I I : / II I I
11 I I : / 11 11
-=- =-o=- - =tW.-=:=--=:::: J 1111 ,------===1fti7-,, '):-,_ 1111
1/0 BARE COPPER
GUARD WIRE =11:.;-:, -=o::::- 1111\: '\ /\)\ II 11
/ ~\\ 1111 ~ \I I 111 l-"==t=========~,=::::::.J/ 1111 : • I
----- 111111 I / I 111111 : ' I I I 11 1111 11 : I I I I 11 I I 1111 : I I I I 11
-=--=--=--=-- -=- =-0= =1++-1# R J I I I 11 LHA #1 = = = = = ~---=====tl:ltl-t~-- "/:-,_ I I I 11 T "'~~ :L- llllfl: '\/\\Ill II
'~==="======lF====~ , ~" 11111 I 'i l I II I I II ~ , i \\ 1111111 , 11111 II lw co u
Lf1 lL
1 f- CX) z a <( I a::
f- lL
I ....I
1 \1111111: i 11111 II
11111111 : : 11111 II
11111111 : : I I I I I II
11111111 i ti! 01 H~r--- 1-2PR 18 AWG CONTROL u LJ LJ LJ : 1 ~ tJ _ H 1-1 /C 6 AWG, GREEN
3-1 /C 1 0 AWG ~ n n IN 2" SCH 40 PVC ( 4 PLS l 1-1 /C 1 0 AWG, GREEN GND n n n n : 1 ,n n IN 2" SCH 40 PVC (4 PLSl------<ttlIIJ:t: / ilflit/1-----, 11111111 V1 =~~~±,!±="" \ 11111111 4, / I I I II «:@t~t@l /
~ NON-AIRCRAFT RATED
~ HANDHOLE (4 Pll ----11 I I
I II 1 1
I I I I
I
C001
II
II
/11 / I , ,:~®-"'?-o<S/,:;;1/1==---::.:-=--::::::::::::o~-2 AWG BARE COPPER
/ II GROUND TO HANDHOLE
I II
/ II
II
LAMP HOUSING ASSEMBLY
CONDUIT CONFIGURATION PLAN
NOT TO SCALE
C002
TOPSOIL
CABLE WARNING TAPE
"UNDERGROUND CABLE"
~«:<v 1/'.o/
~' GRAVEL
' 1 /0 BARE COPPER
GUARD WIRE
SAND BEDDING
~""2~--POWER DUCT
2" SCH 40 PVC
TRENCH DETAIL
NOT TO SCALE
5 4 3
JAQUITH L868C LIGHT BASE
2" THREADED OPENING ON LID
I r--=J r---
I I I I I I I I
I
1=-- SPLICE 4-1/C 10 AWG TO
1-4/C 14 AWG MOLDED CABLE
FROM AMERACE #95-04MRJ4
RECEPTACLE
2" LB
POWER
I
I l _____ _
4-1/C 10 AWG
POWER WIRES
GROUND LUG
___-···· 2 AWG BARE
COPPER GROUND
,Ii-__- INCOMING POWER
1-1/C 6 AWG, GREEN
TO LHA
POWER
I I I I I I
' I
1-4/C 14 AWG
FROM PLUG
AMERACE #95-04MPJ4
PLUG
PLUG AND RECEPTACLE
TO FORM BREAKAWAY
CONNECTION
L--+----AMERACE #95-04MRJ4
I _J RECEPTACLE
I
B JAQUITH L868C WIRING DETAILS
C003 NOT TO SCALE
I
I
I I
___ _[___ - -Lfl I v I I
HANDHOLE COVERS SHALL
BE IDENTIFIED WITH
"POWER II. "CONTROL fl
OR "HIGH VOLTAGE"--~
28" HANDHOLE COVER
28" DI A 28"
OPENING
3/4" HOLE
1 " CHAMFER
(FOR 2 AWG BARE
COPPER GROUND) -..i
6-4 1 /2" 4" WALL
I I
KNOCKOUTS O O O
EACH s I DE ----------1-:.L:. IO ,::"
~ 00
0_~! l~''.._---==-"'7/f.~;-"---3;4• WASHED, ROUNDED, . CRUSHED STONE, WELL COMPACTED
~o
GEOTEXTILE FABRIC
CONTROL DUCT
2" SCH 40 PVC
(4 PLSl--~
D C002
E TYPICAL HANDHOLE DETAIL OUTSIDE RSA
C001 NOT TO SCALE OPEN BOTTOM
TOPSOIL
~--CABLE WARNING TAPE
"UNDERGROUND CABLE" (2 PLSl
~~~~[<;¼~-1/0 AWG BARE COPPER
GUARD WIRE (2 PLSl
Q~*~--SAND BEDDING
)4'lrr--POWER DUCT
_,_ 2" SCH 40 PVC (4 PLSl
6" 3"
TRENCH DETAIL
NOT TO SCALE
4 3
BOLT FRAME
TO HANDHOLE
(TYP, 4 CORNERS)
6-4 1 /2"
KNOCKOUTS
EACH SIDE
GRADE LINE~
Oz 1-
N -
' 0 oz ,_
4/0 AWG BARE COPPER
COUNTERPOISE
~----EXOTHERMIC WELD
--3/4"X10'-0" COPPER
GROUND ROD
E TYPICAL GROUND ROD INSTALLATION
C003 NOT TO SCALE
HANDHOLE NOTES (NON AIRCRAFT RATED}:
1. CONCRETE COMPRESSIVE STRENGTH - 5,000 PSI MINIMUM.
2. STEEL REINFORCEMENT - ASTM A615, GRADE 60, 1" MINIMUM COVER.
3. MINIMUM DESIGN LOAD -MEET OR EXCEED AASHTO HS20-44. 32,000 LB
TRUCK DESIGN LOADING
4. CAST GRAY IRON HANDHOLE FRAME AND COVER SHALL BE NEENAH HEAVY
DUTY R-1640 SERIES OR APPROVED EQUAL.
5. CAST IRON FRAME SHALL BE MECHANICALLY FASTENED TO THE HANDHOLE.
6. A PULLEYE SHALL BE PROVIDED ON EACH WALL.
7. INSTALL A CRUSHED STONE SUMP UNDER ALL HANDHOLES. TOP, SIDES
AND BOTTOM OF SUMP SHALL BE LINED WITH A WATER PERMEABLE
GEOTEXTILE FABRIC.
8. AFTER INSTALLATION OF CONDUITS THROUGH KNOCKOUTS, GROUT AROUND
CONDUIT.
9. CABLE SLACK LOOPS SHALL BE LABELED AND RACKED IN ALL HANDHOLES.
10. INSTALL ONE 3/4", 10 FOOT LONG GROUND ROD AT EACH HANDHOLE OR
SET OF ADJACENT HANDHOLES. BOND THIS GROUND ROD TO EITHER THE
GRSC OR THE 1/0 AWG BARE COPPER GUARD WIRE OVER ANY PVC CONDUIT.
11. HANDHOLE SHALL BE LOCATED OUTSIDE OF THE RUNWAY SAFETY AREA (RSA).
04/10/2019
REV APPROVED
DATE
CONSTRUCTION, WR#17875 1204108
DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
02/07/2019
REDLINE
DATE APVD
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAWTUCKET
PAPI
RUNWAY05
FA-30200 LED PAPI
MISCELLANEOUS DETAILS
NORTH CENTRAL STATE AIRPORT
REVIEWED BY SUBMITTED BY WI.,_ IJ ~
M KUSEK 1 (1.tl<i vw ~
PROJECT ENGINEER MGR: ENGINEERING CENTER
DESIGNED ISSUED BY
MK
ENGINEERING SERVICES DRAWN
DATE 04/10/2019 JCN
DRAWING NO
MK NAVAIDS
CHECKED
MK SFZ-1204108-C003
2 1
RI
1204108
REV
H
G
F
E
D
C
Ji:' u..
w
THIS DRAWING PRODUCED ON NEW ENGLAND REGION M!CROSTATION SYSTEM
~ iri g l -m ~o o N<, ~g -~
H
G
F
E
D
C
B
A if2. BARE COPPER (TYPl
II
-------- -----+t---
STAINLESS STEEL
CHANNEL FRAME
PAPI POWER &
CONTROL ASSEMBLY
I I
I
Cu CONCRETE
~FOUNDATION--+------+----~---,,
I I
4/0 BARE COPPER _-}-_.--c\\//.
RACK GROUND (TYP)- \ /
4/0 BARE COPPER
COUNTERPOISE--~-.
LLJ GROUND ROD
~ 314"x 10'
EXOTHERMIC WELD 4' -0 11
2" GRSC TRANS I~~I~ON~T~0~==~:::::::=====-----7 2" SCH 40 PVC 5' AFTER
COUNTERPOISE
Q
1 /0 BARE COPPf'fE:_FRt___---------1-1
GUARD WIRE~
Q
8'-6"
16'-6''
I
I \ I \
4' -o''
I I I
2" GRSC
' 0 I -
N
' 0 I -.,.
' 0 I -0
6" HARDPACK
OVER GEOTEXTILE
1 POWER & CONTROL ASSY - PLAN VIEW
GEOTEXTILE
A/G ANTENNA
A/G RECEIVER
PHOTOCELL
CSEE NOTE 1 l --
POWER &
CONTROL ASSEMBLY
2" EMT CONDUIT
(TYP 4 PLl
2" EMT POWER &
CONTROL CONDUITS
TO LHA'S
1 " PVC ( 2 PLS l
EXOTHERMIC WELD
4/0 BARE COPPER
EXOTHERMICALLY WELDED
AT GROUND ROD AND CLAMPED
TO PCA RACK LEG WITH
MECHANICAL CONNECTOR --
Q001 SCALE: 1/2"= 1'-0"
D
I I ll t I
! I II I I
I l II I I I I I I I I I I I I I I I I I I
LI LI
#2. BARE COPPER
GROUND (3 PLSl
II
II
II
0 •
I I I!
I I I!
I I II
I I I I I I I I
LI
A POWER & CONTROL ASSY - FRONT
Q001 SCALE: 1/2"= 1'-0"
7 6
1 /2 "x 2' COPPER AIR TERMINAL (2 TYPl C SEE NOTE 6 l
SURGE PROTECTION DEVICE
(SEE NOTE 3)
240V
DISCONNECT
SWITCH
_------BOND DOWN CONDUCTORS
ACROSS TOP CHANNEL
1" PVC (3 PLS)
TRANSITION DOWN
CONDUCTOR TO #4/0
AT 18" ABOVE FINISHED
GRADE (TYP 2 PLACES)
FINISHED
GRADE
' 0 I -N
4/0 RACK GROUND
(TYPl
GROUND ROD
3/4 11 X 10' LONG
,r-f--- 4/0 AWG
7 STRAND
BARE COPPER
COUNTERPOISE
'---- EXOTHERMIC
WELD
CONNECTION
2" STAINLESS STEEL
UNISTRUT (2 PLACES)
FUSED DISCONNECT SWITCH,
HEAVY DUTY, 100A, 240V FUSED
AT 30A, NEMA 4X TO
EXISTING TRANSFORMER-----U__jLJ
1" SCH 40 PVC (TYPJ
WI #2 BARE COPPER
TO EXISTING GROUND~-
FLOOR FLANGE
(TYP 2 PLACES)
POWER TO PAPI
PCA RACK
@CONCRETE
SONOTUBE
I I 11 I I " Ll , p
,P. A
. c·
' IS.
AIR TERMINAL (2 PLACES)
2" EMT SUPPORT (2 PLACES)
2" GRSC ( TYP l
4/0 BARE COPPER WELDED TO POST
GROUND CLAMP THOMPSON #803
APPROX. 18" ABOVE GRADE CONDUCTOR
CONTINUES TO AIR TERMINAL
lt----PVC SLEEVE TO PROTECT COPPER
INCOMING POWER
H
G
F
D POWER RACK CROSS SECTION
Q001 NOT TO SCALE
2" EMT CONDUIT
FRANGIBLE COUPLING HEX RING
COMPRESSION RING
2" GALVANIZED RIGID
STEEL PIPE COUPLING
4 •
• • 0
' 0
FRANGIBLE COUPLING
2" GALVANIZED RIGID
STEEL CONDUIT
TYPICAL FRANGIBLE COUPLING INSTALLATION
MOUNTED TO 2" CONDUIT COUPLING
NOT TO SCALE
1' 0 ---- 1' 2'
SCALE: 1/2"
5'
1'-0"
NOTES:
1, PAPI PHOTOELECTRIC CELL SHALL BE AIMED TRUE NORTH.
2. CONTRACTOR SHALL INSTALL 2" GRSC FROM FOUNDATION AND TRANSITION TO 2"
SCH 40 PVC NO CLOSER THAN 10' FROM FOUNDATION OR 5' PAST
THE COUNTERPOISE
3, SURGE PROTECTION DEVICE SHALL BE RAVOSS STRIKESDRB 120-2S-M3-3-06-A
DR APPROVED EQUAL,
4, DISCONNECT SWITCHES SHALL BE 100 AMP, 120/240, HEAVY DUTY LOCKABLE,
NEMA 4X, FUSES SHALL BE 30 AMP: LITTLEFUSE CLASS RK5, FLNR 030 OR
APPROVED EQUAL, SWITCH SIZED AT 100 AMP TO ACCOMODATE #1/0 POWER WIRE,
5, ALL METAL CHANNELS, STEELWORK, NUTS, BOLTS, ETC, ARE STAINLESS
STEEL, ALL CONDUIT AND CONNECTIONS SHALL BE 1" GALVANIZED RIGID
STEEL UNLESS OTHERWISE NOTED,
6. TOP OF AIR TERMINALS SHALL BE MINIMUM 10" HIGHER THAN TOP OF REMOTE
CONTROL ANTENNA. AIR TERMINALS SHALL BE BLUNT TIPPED.
7, SEE DRAWING SFZ-1204108-E001 FOR GROUNDING DETAILS FOR PAPI PCA AND
DISCONNECTS
8, LIGHTNING CONDUCTORS MOUNTED TO UNISTRUT AND EMT LEGS
SHALL BE FASTENED AT INTERVALS NO GREATER THAN 3' APART USING
UL LISTED BOLT CONNECTIONS. SEE STANDARD FAA-019F,
9, UNISTRUT TO BE FITTED WITH END CAPS,
04/10/2019 CONSTRUCTION, WR #17875 1204108 02/07/2019
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE
APVD
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAPI
RUNWAY05
FA-30200 LED PAPI
PCA EQUIPMENT INSTALLATION
PAWTUCKET NORTH CENTRAL STATE AIRPORT
REVIEWED BY
SUBMITTED BY
MKUSEK
PROJECT ENGINEER MGR: ENGINEERING CENTER
RI
MK ISSUED BY DATE 04/10/2019 JCN 1204108
1---+---+D~RA-W_N ___ __,=-J ENGINEERING SERVICES ,_D_RA_W_ING_N_O~~~~---~=--.~RE'-C..IV
DESIGNED
NAVA\DS MK
CHECKED
MK
SFZ-1204108-Q001
2 1
E
D
C
C rn
" ~ A!
i
11JIS DRAW!Nt;3 PRODUC!;D QN NEW ENG~NO R-E.G!QN fv!l~fl:QSTATIQfl! ~YSTEM
F
E
D
C
B
A
8 7 6
B 6 1 -0 11
L868 LIGHT BASE C003
1 1 -0 11 1'-10" 2'-4" 1 0 II
COPPER TO -- -----2 AWG BARE
GROUND LUG
IN BASE ( TYP) ~//~-- 'o======t+===================r====;i ------~ I I I
I' -----, :-.--------.--------. -------.------- .--- / 'i" : I
2 AWG BARE COPPER
BONDING JUMPER (TYP) I -;... :
I --~ ;:, --- ______ _.__ I
I //
GROUND ROD~/
2 AWG, GRN ''-
c ----------""'---v __ 7 ________ --
2" GRSC ( TYP l _/
I I I I I I
• I +-------j----- ,- - - ---t- T - - - -
: ~ L1" PVC
I I I
-::1::Cc)PWR LIGHT \
' HOUSING
ASSEMBLY
...._ ( 30 11W
X 51 "H X 14 "D l
I
- - - ""' ____ tJ CTRL
----111 I I I
I
I I
I I I I I I
I I I I I I
I I I I I •----- -•---------------- ~-------•-------J _______ _.
EXOTHERMIC WELD CTYP)
1 LIGHT HOUSING ASSEMBLY - PLAN
S001 NOT TO SCALE
LIGHT HOUSING ASSEMBLY (LHA) PROVIDE AIMING ANGLE LABEL
(AFTER FLIGHT INSPECTION)
' 0 I -'<T
• LHA #2 3• 10' • LIGHT BEAM CENTERLINE
1" LIQUID-TIGHT FMC
CONE PWR, ONE CTRL) •
4'
6" MIN COMPACTED
DEPTH CRUSHED ROCK 2" GRSC
(TYPl 1 2 AWG BARE COPPER
BONDING CONDUCTOR~ ____________ _
"---k-----\,.L ____________ _
2 AWG BARE COPPER-..--- ---
3/4" X 10'
COPPER CLAD
GROUND ROD
1 " PVC
SCH 40 PVC
2 AWG, GRN
N0.4 GRADE VERTICAL REBAR 12"
OCEW WITH NO, 3 TIES 1 O" OC
MAINTAIN 3" MIN
CLEAR FROM ALL SURFACES
2 AWG, GRN C
.,,--!----!STRUCTURAL LEG
S001
~~~-:;~-:-"":··f t> - , - - · - · ,. r ~ ...,. . p.... ,-.. • ' I , , I> , , I> ' " '• , , '. t> "• __ 711'"_,___ . -iH_,,_~_-111..,,__~-----.-. --.,· ~ 1 , 1 • · • t> · -, 1> 1., ' 1 .- , " r :: ~ .,,.,. , , , -- ·" 1 ° 0Q
' I • / ,. ' I ' ". I I JI I' ' •, I ' ' •, ' ' I_., " " ., I , '6\
.,.!' I '1'',,,,,,,f1 41 ,f>1,,,.'l>,,,.1'·,,.'l>1· . J. I .._ "'1 <1 'I> , 11 111 ," I .,. Cl ,' "' . ., , l
I / ' , , I ' It ,! ' I ' -I ' ' l • , I ' ,, , I ' ' • ' ' • ' : ~ / __ .1-_:_, __ ,_;~_~_:u~_A _ _:__~:.__:'_:_~_:._j_::,_;_~_:__,i/ .~ .
: / ~: • : • ~ h :1 I - '. J - '. , -: :A : '. J · ~ 'l /~ .._ ,1,' ' . 'JI 111',, I,,,. , 'l,. ',,. 1 ...
-'l I ', - I 4 ,,. , 1 I 'l > ' I , -' ' , ~I ":; ' I
, I" I I ,b. ' , ~ /' Ji I 6 ' I 6 ' j6 " A ' ~ .:.i: .. -n---i"-;T---- .:._-,--~-------"' ;_ /1 [b , -~ • • , • .~, • , , : ~ :
--,- -U.--"f---- i ... ...,.,,,J~~----it-;--!-{-.b-...,..:..z.n"'--,-~---...L'>T',....:.A_'_'_. __ i' '
, '1 , , , I , • , · ', 1, , 11· , •, I , ' , I•, , ' , 1 , ,, , t>- • ' , ,,, ""' • t " I • .,,. ':'!, r-rzr~ ... ! ' ''',I' ,, •!,,'1) k '·b.' k ',t:,' k ',t,. 'k '·b.t:., I"" ,,_ ' . , ! , t>' , ' I , t:,. ,, , ,..I ,,_ , ,,. I ,.,. ,. ' I,,. ,. ,,. ., .,,.
I I, I , I / ' 6 , I, I I
~..i_::__' ,-_,_:..__1-·_.:: __ ·e.._· ,_' ~ ... P/, ,',,. I .- ' ,. ' 'I" ,P-
--v'7-'--:-"?rs-:-~~~-A-.!.--:,-~:...~-:-·.P.Ji,.-~--t.>:-~{~;i>-:--.::---~--=~_.!.-,Fp,~--~ ~it. , A LIGHT HOUSING ASSEMBLY - SECTION
S001 NOT TO SCALE
3000 PSI CONCRETE
(SEE NOTE 21
1" LIQUID-TIGHT FMC
CONNECTOR, MALE
1" LIQUID-TIGHT FMC
CONNECTOR, MALE __ /
2" TO 1" REDUCING BUSHING
TOP OF FOUNDATION
• 4
1" UV RESISTANT
LIQUID-TIGHT FMC
1 /2 • _CAX
4 4 . . '
2" LB CONDULET
W/ METAL COVER
AND GASKET
z• STEEL EMT
COMPRESSION
CONNECTOR
2" EMT NIPPLE
2" FRANGIBLE COUPLING
(SEE NOTE 9)
SPLICE CAN COVER
(6 BOLTS REQUIRED)
( SEE NOTE 9 l
B POWER CONDUIT ASSMEBL Y
S001 NOT TO SCALE
JAM NUT ( GFM)
FIXED NUT (GFMl
LOWER NUT ( GFM l ----~~tttJ~1:-. 1 THREADED ROD (GFMl . ..___ ~
::E
UPPER NUT (GFMl
FLAT WASHER (GFM) -----.==..::am.__,.---1..
2" EMT
CSEE NOTE 51 --
2" FRANGIBLE
COUPLING (GFM)
(SEE NOTE 9)------
TOP OF
FOUNDATION
FLAT WASHER (GFM)
SET SCREW (GFMl
2" FLOOR FLANGE
GALV. STEEL
THREADED ROD
INSTALLED WITH
CHEMICAL ANCHORS (4 PLS)
(SEE NOTE 4)
NUT & WASHERS SECURING
FLOOR FLANGE TO THREADED
::,,._4#:!::~¥==c±!gl-_ANCHOR ROD (4 PLS)
C STRUCTURAL LEG DET~L
S001 NOT TO SCALE
4 3
2 1
NOTES:
1. CONCRETE FOUNDATIONS SHALL HAVE THEIR VERTICAL SURFACES SMOOTH
SO AS TO BE RESISTANT TO FROST HEAVES.
2. CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE CURRENT ISSUE OF
ACI-31B; BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE.
CONCRETE TO DEVELOP MIN. STRENGTH OF 3000 PSI IN 28 DAYS WITH MAX
SLUMP OF 3 INCHES AND MAX AGGREGATE SIZE 3/4 INCH. THE CONCRETE
MIX SHALL CONTAIN ADMIXTURES OF POZZOLANIC MATERIAL AND AN AIR
ENTRAINING AGENT CONFORMING TO ASTM C-494 AND ASTM C-260
RESPECTIVELY. THE CONCRETE SHALL BE CURED BY KEEPING IT WET FOR
AT LEAST 5 DAYS. THE CONCRETE SHALL BE PROTECTED FROM FREEZING FOR
AT LEAST 7 DAYS AFTER PLACING.
3. DRILL HOLES AND INSTALL EPOXY ANCHORS HILT! #HY200 OR APPROVED
EQUAL.
4. z• EMT SHALL BE CUT TO LENGTH SO THAT THE BEAM CENTERS OF ALL LIGHT
UNITS ARE WITHIN 1 INCH OF A HORIZONTAL PLANE AT THE ELEVATION
SPECIFIED IN THE DRAWING PACKAGE.
5. INSALL APPROVED FILL IN 10" LIFTS. EACH LAYER SHALL BE THROUGHLY
COMPACTED TO 95% OF MAX DENSITY AT OPTIMUM MOISTURE CONTENT
IN ACCORDANCE WITH AASHTO-T99.
6. TO PREVENT SEIZURE, ADD ANTI-SEIZE COMPOUND, NSN# 8030-00-251-3980,
JET-LUBE 550 OR EQUAL.
7. GROUNDING BUSHINGS SHALL BE USED ON ALL CONDUITS ENTEREING THE LHA.
8. TOP OF ALL CONCRETE FOUNDATIONS SHALL BE A MINIMUM OF 2" ABOVE
SURRONDING GRADE. INSTALL ALL FINISHING STONE TO THE VERY TOP
OF THE CONCRETE, AND GRADE BACK TO THE SURROUNDING GRADE .
REV
04/10/2019 CONSTRUCTION, WR #17875 1204108 02/07/2019
APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE APVD
ATO -- TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAPI
RUNWAY05
FA-30200 LED PAPI
LHA INSTALLATION
PAWTUCKET NORTH CENTRAL STATE AIRPORT
REVIEWED BY
SUBMITTED BY
;vl, I l P.
M KUSEK {t'o'\i!~
PROJECT ENGINEER
APPR52¼--t . -. _...}?
S.F11vNERTY~
MGR: ENGINEERING CENTER
RI
MK ISSUEDBY DATE 04/10/2019 JCN 1204108
1----+---+o=RA~W~N~---~cc., ENGINEERING SERVICES "'"o_RA_W-IN_G_N_o ___ ~-----~~RE---,v
DESIGNED
NAVAIDS MK
CHECKED
MK SFZ-1204108--S001
2 1
H
G
F
E
D
F
E
D
C
B
C
C a Cl 0:
1 • ~
N
" c~
0) '-~m N A
J:
0 -~ ;i;;
NN
"';'0 oz 1~ - ::;:
LO -
-N
CONCRETE
FOUNDATION
<£1 I
6 II f
1 '-0 11
I I I I I I I I I I I I I i I
<i.
vi
- ....J <Co ::r:a::
....J ,__ z Do f--u
2" GRS CONDUIT SWEEPS
(TYP 3 PLACES)---~
I I
7 ,, 7 ,, I I I I I <i.
111 I I I
I I I I
LJJ
I
<i.
11 I 11 I 11 I 11 I 11 I I
CAST COUPLING1-:::--::-2::-::-i-----\ ( 3 PLACES l S002
1 " SCH 40 PVC
COUPLING
CAST IN PLACE
(3 PLACES)
1,1 it I
I I
I
1 '-3"
1,1
<i.
I 6,, I
I 1'-0 11
2'-4 7/16 "
1'-6"
8'-6"
1 PLAN VIEW
C002 SCALE: 1" = 1'-0"
Q001
3 1 -6 11
1" SCH 40 PVC CONDUIT SWEEPS
(TYP 3 PLACES)
11 I
1 " SCH 40 11 111
PVC CONDUIT SWEEPS
11 111 (3 PLACES)
11 111
11 111
__ j_J__JJ- _ _LJ_ ____________
I I I I I~ I
CONCRETE
FOUNDATION---i
I I I I l l
C002 Q001
7-#4 0 Q3-#4
ELEV A TION VIEW
SCALE: 1" = 1'-0"
I
. t-
\7 ··,i;;,:, a I
I -N
1 " CHAMFER
GRADE
2-#40
GEOTEXTILE
FABRIC
COMPRESSION RING
WITH NUT . .____
ALUMINUM
FLOOR FLANGE
TOP OF CONCRETE
2" EMT
2" FRANGIBLE COUPLING
3/8" X 3 1/2"
STAINLESS STEEL
EXPANSION TYPE
ANCHOR BOLT
.:..~.-. _-+. _:::.$119. -~1:~-.~.,$,,~.L-..
~-·"-~·""I I_·_-: --~ ~-·I I•~-~:
BOTTOM OF FLANGE IN ':,:, '.,;·,:,.,.
CONTACT WITH CONCRETE
IS COATED WITH
ASPHALTIC COMPOUND
FOR METAL PROTECTION
FLOOR FLANGE DETAIL
NOT TO SCALE
S002
TOP OF FDN
2" COUPLING
2" GRSC
4 CAST COUPLING
Q001 NOT TO SCALE
1' 0 1'
SCALE: 1";::: 1'-0"
4 3
2'
4--#5
#3 TIES @ 1 '-0" 0, C.
REV
04/10/2019
APPROVED
DATE
1 2 II
. A
A "' ,. ..
CHAMFERED EDGES
FINISHED GRADE
6" LAYER OF
CRUSHED STONE
A •
A ..
I
GEOTEXTILE FABRIC
.A
" ,. ·_ A A
CONCRETE SONOTUBE SECTION
NOT TO SCALE
CONSTRUCTION, WR #17875 1204108
DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
02/07/2019
REDUNE
DATE APVD
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAWTUCKET
REV!EWEDBY
SUBMITTED BY
MKUSEK
PAPI
RUNWAY OS
FA-30200 LED PAPI
PC RACK FOUNDATION
NORTH CENTRAL STATE AIRPORT
MbJ/w k:~ APPRst~:c:1:::
l' S:FINNER~
RI
PROJECT ENGINEER MGR: ENGINEERING CENTER
MK ISSUEDBY DATE 04/10/2019 JCN 1204108
>----+--+-DRA_W_N ____ ~ ENGINEERING SERVICES CCDCC-RACCCWCC-INCC-GCCNO~~~~----~i-=R-=,EV
DESIGNED
NAVAIDS MK
CHECKED
MK SFZ-1204108-S002
2 1
H
G
F
E
D
_ I~I?_ ,O~·~"Xf!~? P~?9ucED _oN r-4_1;:w EN~LAt-lR ~-E~L?!;:~!2~-o_STATJQ~ sn;_'!:~M
0:
H
G
F
E
D
C
B
A
WEATHERPROOF
UL LISTED INSULATED
GROUNDING BUSHING
(TYP, ALL METALLIC
CONDUITS) SEE NOTE 13
120/240V
INCOMING POWER CABLES
2-1/C #2 AWG THWN AND
1-1/C #4 AWG THWN GROUND-
6 5
I \ I SPD l 4-1/C #10, 600V-
11 ~--~ _ II I
L 1 1 2 0 V 2 4 0 V , 6 0 A f----t-+-l f-----l-1-'-'2=--'0'--'V-------'L=-1'-----"B=-L K"----------, L 2 1 2 ov D I SCONNE CT,__-+-+-i JUNCTION f-----'---'-1 =-20"-'v'----'L"-'2~_,R..,_,E=D--------, GND SWITCH f----1-+-l BOX I NEUT WHT -H--_+---1 ----"-'--'"'----l FUSED I! 30A 1----l-l--'G-'-'N"""D'-'-----'G"-'R-'-N-------, 3-1/C 10 AWG
1-1/C 10 AWG,
GREEN GND ------,
#6 AWG BARE COPPER
BONDING JUMPER------____
l SEE NOTE 16- --~~- ,(
,----------------,==,#2 cu
E2 [_!_ BARE
GROUNDING ELECTRODE
CONDUCTOR CG/E/Cl
#2 AWG COPPER
1" SCH 40 PVC --
EXOTHERMIC WELD
I
N __, _LJ IGND
MAIN DISCONNECT SWITCH
MINIMUM REQUIREMENTS:
60A, 240V, 2P, 3W, SIN, NEMA 4X, HEAVY
I / I DUTY, 30A 200KAIC FUSING
,----+--+---' SQUARED DOR
TO GROUND ROD -~- ,:::c.__--t-----10
APPROVED EQUAL
MULTIPOINT INVEIW
:- I/
#2 A WG MA I N ~ ,.;G"-'N,,_,D:.J.+-1-+--+---.,
BONDING JUMPER~
JUNCTION BOX SIZE AS
REQ'D TO ACCOMMODATE
CONDUCTORS, NEMA 4X
q::::::t=j=::J>--- 3-1/C #10, 1#10 GND, 600V f Cl :::, Z W N (.!) z __, RNOTE 4
1----+-+>-'--t
POWER DISTRIBUTION
BLOCK CTYP) -~,.__ SPD
>----+---1-----1c---t-+---1 ( NOTE 1 4 l ~ r----.___ ---...J'--+----+--+----1--1+--t
V
TO PAPI
CONTROL CABINET
- 4-1 IC #4 AWG
( 2 ' INCOMING ELECTRIC SERVICE - WIRING DIAGRAM
\EOOt NOT TO SCALE
-------t-------·-r- r--- ,,--, .,,, 2 '
RURAL ELECTRIC
PROVIDED SURGE
PROTECTION
2 AWG
EOOJ,
SEE NOTE 8 7 /
t----RRCS AIR/GROUND
I / RECEIVER ANTENNA
-._ I [
I I --, ELECTRICAL
SERVICE
#2 AWG GRN/ORG
' L1 BLK
L2 RED
NEUTRAL WHT
GND GRN
_j Ill
"' Lu
V)~ BRN
v>o «1 RED
"'"',.., <CZ:!: YEL
N-o v>o ORG z,,, Luo, V) :c a..
SEE NOTE 12
1 -2 t-- 4 i--
4 - 3 - 2 - 1 -
TB6
UNIT 2
POWER AND CONTROL
ASSEMBLY
FA-30200
TB5
TB10
TB4
I 11 r t.)0 '-' I
~ "' TB3 ..,:_,,-.,
~on «o::- N>--0 zo Ol'l
-4 -3
1 -
4 - 3 - 2 -1 - -4 -3 -2 -1 - -4 -3
AIR/GROUND
RECEIVER
CONTROLLER
FAA-L-854
(RURAL ELECTRIC INC)
123.075 MHz
TB2 >--
#6AWG,THWN,
GRN/RED~D
FACTORY PROVIDED
JUMPER
( SEE NOTE 18 l
CONTROL 1
CONTROL 2 7
CONTROL 3 8
~ 190
RED
3-1 /C #12 AWG
REMOTE
PAPI ON
RED ( 120 VJ QJ TV3
1 SEE NOTE 5 - 3_1 /C
12 AWG
BLACK ' BLK L1 -
1 20 VAC ~ L 1-----"W'-'=H-'--'J "'TE"--------t-+---+---t------W----,HT::---t---t----,----,N----,l--J_1_ TB 1 NEUT N f--!!-'-'--'--'--=--------+-J--+----t---------t---t-----, 2
GREEN GRN -
2 -1 -
GRN C4Gl
RED (4L2J
WHT (4Nl BLK ( 4L 1 l
GRN (3Gl RED (3L2l WHT (3Nl
BLK ( 3L 1 J
GRN (2GJ
RED (2L2)
WHT (2NJ
BLK ( 2L1 )
GRN ( 1 G l RED ( 1 L2 l WHT ( 1 N l
BLK ( 1 L1 )
I SPLICE CAN NOTE 5 7
I RED/GRN fl_ E_ RED/GRN I i I
I BRN/RED BRN/RED I
WHT WHT
BLK BLK
- I ----------
-----------, I SPLICE CAN NOTE 5 I
I RED/GRN .fl .f RED/GRN I
I
', ,1 BRN/RED BRN/RED
I WHT WHT I
I BLK BLK i I _,___ j
GRN ( 4G I _1jE1
RED ( 4L2 i -1
WHT ( 4N) -2 TB1 BLK ( 4L 1 J -3 - LHA 4
RS485B ( 4 ) -2
RS485A ( 4 ) - TV2
1 -
2 AWG
BC
ITJEz
GND BUSI 1--------,
GRN (3Gl l..2-J El
RED ( 3L2) 1
WHT ( 3N J >--2
BLK ( 3L 1 J -
3 -
TB1
LHA 3
RS485B ( 3 l -~-----------~~~~2
RS485A ( 3) - TV2 ~----------~~~-~,
2 AWG
BC DJ E2
-----------, I SPLICE CAN NOTE 5 I
GND BUS1i-----, I ! RED/GRN ,E..f RED/GRN I GRN ( 2G) '-++t-t----+------+-t-r----;- ~~~'-1~ E1 i
I BRN/RED BRN/RED !
I WHT WHT
I BLK BLK
I ~L, I
RED ( 2L2) 3
WHT C2N l -
BLK ( 2L 1 ) J__ TB1
1--
RS485B ( 2 l i--r----------------, 2 RS485A (2) >-- TV2 r----~-----------"'--------J 1
2 AWG
BC DJE2
LHA 2
-----------, I SPLJ CE CAN NOTE 5 I
GND Bus1 ,___
I RED/GRN ,fl,.!: RED/GRN I GRN ( 1 G) '-----+++HH+1---t-++------+-
~~~-----1_1j E 1
1, II
BRN/RED BRN/RED RED ( 1 L2) f--
GND G 2PR 18 AWG_ I WHT WHT I
WHT ( 1 N l f--
NOTES:
1 .
2.
3.
4.
5.
6.
7.
8.
9.
ALL WIRING SHALL MEET LATEST EDITION OF NFPA 70, THE NATIONAL
ELECTRIC CODE CNECl, AND FAA STD-019: LIGHTNING AND SURGE PROTECTION, GROUNDING, BONDING AND SHIELDING REQUIREMENTS FOR FACILITIES
AND ELECTRONIC EQUIPMENT,
ONE SET OF SPARE FUSES SHALL BE FURNISHED FOR EACH FUSIBLE DEVICE.
EACH CIRCUIT SHALL MAINTAIN AN INDIVIDUAL NEUTRAL
AND GROUND CONDUCTOR.
UNDERGROUND CONDUCTORS SHALL BE INSTALLED IN SCHEDULE
PVC CONDUIT OR GALVANIZED RIGID STEEL CONDUIT (GRCS).
CONDUIT WITH GROUNDING CONDUCTORS ONLY ARE SCHEDULE 40
CONDUCTORS SHALL BE 600 VOLT RATED, TYPE THWN UNLESS
OTHERWISE SPECIFIED.
ALL CONDUCTORS #6 AWG AND SMALLER SHALL BE COLORED AS
INDICATED. COLORS IN SPLICE CAN TO BE CODED GRN & RED
GROUND TERMINATIONS SHOWN ARE DIAGRAMMATIC ONLY;
MULTIPLE GROUNDING CONDUCTORS SHALL NOT BE TERMINATED
SINGLE CONDUCTOR GROUND LUGS. USE APPROVED GROUNDING
CBURNDY FRAMATOME #YCHC OR EQUAL) AS REQUIRED.
PVC.
AS SHOWN.
IN
CONNECTORS
ALL UNUSED CONDUCTORS SHALL BE GROUNDED AT BOTH ENDS. ALL CABLE
OVERALL SHIELDS SHALL BE GROUNDED AT BOTH ENDS. ALL INDIVIDUAL SHIELDS
SHALL BE GROUNDED AT ONE END ONLY.
ANTENNA SURGE PROTECTORS SHALL BE POLYPHASOR IS-50NX-CO-ME OR APPROVED
EQUAL.
GROUND BUS BARS SHALL BE ADDED TO THE PCA AND LHASAS NEEDED TO
ACCOMMODATE ADDITIONAL GROUND CONNECTIONS. CONNECT BUS BARS TO
EQUIPMENT GROUND LUG WITH A 6 AWG, GREEN WIRE.
--~ .___.--___ ....,_n..__ _____ ~
SEE NOTE 16 ___--
TO GND LUG #6 AWG GRN/ORG
NOTES
(CONTINUED):
10, CONTRACTOR SHALL DUCT SEAL ALL CONDUITS ENTERING THE POWER
DISCONNECTS AND ALL EQUIPMENT DEVICE ENCLOSURES.
11, CONTROL CABLE BETWEEEN PCA AND LHA SHALL BE 18 AWG, SHIELDED, TWISTED PAIR,
WITH WATERBLOCK TAPE SUCH AS BELDEN 5340F1 OR EQUAL SUITABLE FOR WET
LOCATIONS. CABLE MAY BE ONE CABLE OF TWO PAIRS, OR TWO SEPARATE ONE PAIR
CABLES TO EACH LHA. THE SECOND PAIR IN EACH RUN JS A SPARE.
1 2.
1 3.
1 4.
1 5.
THE PAPI PHOTOCELL SHALL BE MOUNTED AND AIMED TO MAGNETIC NORTH.
THE MOUNTING LOCATION SHALL PROVIDE AN UNOBSTRUCTED VIEW, ADDITIONAL
CABLE MAY BE NEEDED TO EXTEND PHOTOCELL WIRING BACK TO THE PCA.
INSTALL A GROUNDING BUSHING AT BOTH ENDS OF ALL METALLIC
CONDUITS IN ALL ENCLOSURES.
SURGE PROTECTOR DEVICE CSPD) SHALL BE RAYVOSS STRIKESORB
120-2S-M3-3-06-A-H OR APPROVED EQUAL. SPD SHALL BE INSTALLED AS CLOSE AS
POSSIBLE (WITHIN 12"l TO THE SERVICE SWITCH. SHARP BENDS OR KINKS IN WIRING
SHALL BE AVOIDED. APPLY DUCT SEALANT TO ALL CONDUIT OPENINGS TO SPD TO
PREVENT FLASHOVER INTO JUNCTION BOX.
CABLE AND CONDUIT SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE FAA AND
LOCAL CABLE INSTALLATION STANDARDS. ALL CABLES SHALL BE TESTED IN THE
PRESENCE OF THE RESIDENT ENGINEER CREl IN ACCORDANCE WITH FAA-C-1391B.
16. INSTALL A #2 AWG GREEN WIRE FROM THE GROUND ROD TO A
GROUND LUG IN THE ENCLOSURE.
17. GROUND TERMINALS SHOWN AT MULTIPLE LOCATIONS FOR DRAWING CLARITY.
18. FACTORY PROVIDED JUMPERS TO BE FIELD INSTALLED BY FAA. CONTROL
SWITCH SHALL BE SET TO •PARALLEL".
6 5
( 1 ' \E001'
-8 -7 -
~ - 5 - -- TV1 - ,....!
,...:._ 2, ,--- GND BUS 2
0 -- 1 f---,-- 0
F A-3O2OO ELECTRICAL SYSTEM WIRING
WITH AIR TO GROUND CONTROL
NOT TO SCALE
4 3
CONTROL CABLE
(4 PLSJ
RS485B (4)
RS485A (4)
RS485B ( 3 ) 7
RS485A ( 3 )
RS4858 ( 2 ) 7
RS485A ( 2 )
RS485B ( 1 ) :,
RS485A ( 1 )
4-1/C 6 AWG,
DIAGRAM
I BLK BLK i I ~'-' I ~---------
2 TB1
BLK ( 1 L 1 I f--f--
LHA 1
RS485B ( 1 ) f--
RS485A ( 1 ) 1-- TV2
f--
2 AWG
BC
DJE2
GND BUSI -
GREEN GND
03/05/2019 CONSTRUCTION, WR •17342 1204108 05/21/2018
REV APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL A VIA TI ON ADMINISTRATION
REDLINE
DATE APVD
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
PAPI
RUNWAY 05 (SFZ) FA-30200 LED PAPI
ELECTRONIC WIRING DIAGRAM
WITH A-G RRCS CONTROL
PAWTUCKET /J NORTH CENTRAL STATE AIRPbRT'
PROJECT ENGINEER MGR: ENGINEERING CENTER
DESIGNED
RI
ISSUEDBY DATE 03/05/2019IJCN
1---+----+=oRA~w=N~---~MK ENGINEERING SERVICES ,_o_RA_w-,N-G~No~~~~----~,=-;
1204108
REV
NAVAIDS MK
CHECKED MK SFZ-1204108-EOOl
H
G
F
E
D
C z 0 N ::) .. a:: "' .... "' (/)
0 z 0
0 0
0 ;"
0 w
!!l e
A /p, ..
' N -m
" 0 w
G
F
E
D
C
B
A
PAPI
PCA
TV3
A/G RECEIVER
ANTENNA
~i/ SURGE PROTECTOR rPi CITEL P8AX09-N/FF --------'-t~ =
OR APPROVED EQUAL
AIR/GROUND
RECEIVER
CONTROLLER
L-854
RURAL ELECTRIC INC
PAPI REMOTE RED
CONTROL ( 1 2 D V ) 1 1----------<-+------1
1/C 12 AWG-
PAPI
PCA
TB1
1~~ JUMPERS
(SEE NOTE 8)
- BLK ~}~ ~
120V 1
N 2 -GND 0
3-1/C 12 AWG-
WHT N N
GRN
G GND
1' A ', AIR TO GROUND REMOTE CONTROL
' E002 NOT TO SCALE
ANTENNA
PAPI
PCA
TB1
N
"' z -
3-1 IC 12 AWG--ct=t=t::J, 3' a _J
AIR-GROUND
RECEIVER
CONTROL
INDUSTRIES
RC-1T5A
5 •
-1/C 12 AWG
PAPI
PCA
TV3
~---B-------l 1 PAPI REMOTE
CONTROL (120V)
ANTENNA
,r B ' CONTROL INDUSTRIES A/G RECEIVER WIRING
~00~ NOT TO SCALE
PAPI
PCA
TB1
N
"' z -
3-1/C 12 AWG--d:=t:=!)
0 3'
N 0 z ....... (!) _J
I
AIR-GROUND
RECEIVER
ADB
RCE-1X1X
- 1/C 12 AWG
~---B-------l 1 PAPI REMOTE
CONTROL ( 120V J
SW1
OFF 4 DEBUG MODE
I--
OFF 3 CANADA MODE
I--
ON 2 RELAY CHANNEL A CUMULATIVE MODE
I--
ON 1 RELAY CHANNEL B CUMULATIVE MODE
,r C' ADS A/G RECEIVER WIRING
~002 NOT TO SCALE
4 3
2 1
NOTES:
1, GROUND TERMINATIONS SHOWN ARE DIAGRAMMATIC ONLY;
MULTIPLE GROUNDING CONDUCTORS SHALL NOT BE TERMINATED IN
SINGLE CONDUCTOR GROUND LUGS. INSTALL ADDITIONAL GROUND LUGS
OR BARS IN PCA AND LHASAS REQUIRED. CONNECT NEW LUGS/BARS TO
EXISTING GROUND LUG WITH 6 AWG GREEN WIRE.
2, ALL UNUSED CONDUCTORS…