THERMOSTATIC
ACTUATION
CONTROLLING FLOW IN RESPONSE TO TEMPERATURE
M VETREX ALVE
TECHNICAL DATA REFERENCE
Thermowell (Sold Separately)
"AirSensing" Adapter (Included, Specify)
Model 190 Air Sensing
Models 338, 339 Plain Bulb w/o Fitting
Models 203, 230, 261, 318, 346 Standard Plain Bulb
IPS Adapter (Included)
For direct contact with pipes, tanks.
TYPICAL APPLICATION
SENSING BULB STYLES
Range Designator
Crack Open Temperature Adjustment Range
Change to Full Open Across the Range*
L low 5 to 105 F (-15 to 40 C) 35 to 12 F (19 to 7 C)
X cross ambient 60 to 140 F (15 to 60 C) 25 to 12 F (14 to 7C)
S standard 90 to 140 F (30 to 60 C) 20 to 12 F (11 to 7 C)
H high 100 to 170 F (40 to 80 C) 25 to 12 F (14 to 7C)
V very high 160 to 230 F (70 to 110 C) 40 to 21 F (22 to 12 C)
* The temperature change necessary to bring the valve from crack to full open decreases exponentially from the low end of the Crack Open Temperature to the high end of the Crack Open Temperature in each range. Example: a valve with a S (standard) range actuator set to open at 95°F will require an approximate rise in temperature of 20°F to go full open. The same valve set to open at 135°F will require an approximate rise in temperature of 12°F to go full open.
Bulb
Valve
BypassCooling Fluid
Supply
Return Hot Process Fluid
Cooled Process Fluid
Condenser or Heat Exchanger
Series
FEATURES
Thermostatic actuated valves are typically used to modulate the water flow in response to a temperature signal and are used in a wide variety of industrial and commercial process control applications where water is used as a heat transfer medium. For example, this type of valve is used to maintain precise control of the temperature of hydraulic fluid in plastic injection molding equipment.
Actuation by temperature
For all Metrex Valve sizes, 2-Way and 3-Way
For Direct Acting and Pilot Operated valves
For fresh water and marine
Fully adjustable control within desired range
Self-operating
Available in a wide variety of sensing bulb styles
Optional open on temperature decrease (on most direct acting models)
T REMPERATURE ANGES
METREX VALVE CORP. ENGINEERED CONTROL SOLUTIONS FOR REFRIGERATION NUCLEAR
505 S. Vermont Ave., Glendora, CA 91741, USA (800) 266-4027 Fax: (626) 335-1514 www.metrexvalve.com
MARINEHVAC
THERMOSTATIC
ACTUATION
CONTROLLING FLOW IN RESPONSE TO TEMPERATURE
M VETREX ALVE
TECHNICAL DATA REFERENCE
METREX VALVE CORP. ENGINEERED CONTROL SOLUTIONS FOR REFRIGERATION NUCLEAR
505 S. Vermont Ave., Glendora, CA 91741, USA (800) 266-4027 Fax: (626) 335-1514 www.metrexvalve.com
MARINEHVAC
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
5-105° or 60-140°F 4.50 50M-203-37L OR 37X
90-140°F 2.25 50M-203-37S
100-170° or 160-230° 2.25 50M-203-50H OR 50V
5-105°F or 60-140°F 6.00 50M-203-50L OR 50X
90-140° F 2.25 50M-203-50S
100-170° or 160-230° 2.25 50M-203-50H OR 50V
5-105° or 60-140°F 15.00 50M-203-1L OR 1X
90-140° F 4.50 50M-203-1S
100-170° or 160-230° 4.50 50M-203-1H OR 1V
5-105°F or 60-140°F 41.00 50M-203-2L OR 2X
90-140° F 11.00 50M-203-2S
100-170° or 160-230° 11.00 50M-203-2H OR 2V
MODEL 203 • 3/4" NPT INSERTION TYPE • "A"=3/4"
FOR 500,800,900 SERIES VALVES
3/8"
1/2", 3/4"
1", 1-1/4", & 1/2"
2" & 2-1/2"
L
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
5-105° or 60-140°F 8.00 50M-230-37L OR 37X
90-140° F 2.00 50M-230-37S
100-170° or 160-230° 2.00 50M-230-37H OR 37V
5-105° or 60-140°F 11.00 50M-230-50L OR 50X
90-140° F 4.00 50M-230-50S
100-170° or 160-230° 4.00 50M-230-50H OR 50V
5-105° or 60-140°F 30.00 50M-230-1L OR 1X
90-140° F 8.00 50M-230-1S
100-170° or 160-230° 8.00 50M-230-1H OR 1V
90-140° F 21.00 50M-230-2S
100-170° or 160-230° 21.00 50M-203-2H OR 2V
MODEL 230 • 1/2" NPT INSERTION TYPE • "A"=9/16"
FOR 500,800,900 SERIES VALVES
3/8"
1/2", 3/4"
1", 1 1/4", 1 1/2"
2" & 2-1/2"
L
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
1". 1 1/4", 1 1/2" 5-105°F or 60-140°F 10.00 50M-346-1L OR 1X
2", 2 1/2" 5-105°F or 60-140°F 26.00 50M-346-2L OR 2X
MODEL 346 • INSERTION PLAIN TUBE TYPE • "A"=1"
FOR 500,800,900 SERIES VALVES
L
L
A
1. Select the desired Bulb style for the appropriate valve series.
2. Select the Applicable Valve size.
3. Select the Temperature Range to reference the part number.
TO DETERMINE ACTUATOR PART NUMBER
Example: For a 1” 2-Way application to control at 110°F, you could select our 800 Series valve and specify a 50M-203-1S thermostatic actuator (see Model 203 below).
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
5-105° or 60-140°F 6.00 50M-190-37L OR 37X
90-140° F 2.00 50M-190-37S
100-170°F or 160-230°F 2.00 50M-190-37H OR 37V
5-105°F or 60-140°F 9.00 50M-190-50L OR 50X
90-140° F 3.00 50M-190-50S
100-170°F or 160-230°F 3.00 50M-190-50H OR 50V
5-105°F or 60-140°F 24.00 50M-190-1L OR 1X
90-140° F 7.00 50M-190-1S
100-170°F or 160-230°F 7.00 50M-190-1H OR 1V
90-140°F 20.00 50M-190-2S
100-170° or 160-230° 20.00 50M-190-2H OR 2V
L
1", 1-1/4", & 1-1/2"
2" & 2-1/2"
3/8"
1/2", 3/4"
MODEL 190 • FINNED TUBE AIR SENSING TYPE • "A"=3/4"
FOR 500, 800, 900 SERIES VAVES
O IDERING NFORMATION
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
5-105°F or 60-140°F 6.00 50M-261L OR 261X
90-140°F 2.25 50M-261S
100-170°F or 160-230°F 2.25 50M-261H OR 261V
L
MODEL 261 • 3/4" NPT INSERTION TYPE • "A"=3/4"
FOR PILOT, WCCW AND WCME SERIES VALVES
ALL
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
5-105°F or 60-140°F 11.00 50M-318L OR 318X
90-140°F 4.00 50M-318S
100-170°F or 160-230°F 4.00 50M-318H OR 318V
ALL
L
MODEL 318 • 1/2" NPT INSERTION TYPE • "A"=9/16"
FOR PILOT, WCCW AND WCME SERIES VALVES
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
5-105°F or 60-140°F 6.00 50M-339L OR 339X
90-140°F 2.25 50M-339S
100-170°F or 160-230°F 2.25 50M-339H OR 339V
L
MODEL 339 • PLAIN TUBE STRAP-ON TYPE • "A"=3/4"
FOR PILOT, WCCW AND WCME SERIES VALVES
ALL
APPLICABLE TEMPERATURE PART
VALVE SIZES RANGE NUMBER
5-105° or 60-140°F 4.50 50M-338-37L OR 37X
90-140° F 2.25 50M-338-37S
100-170°F or 160-230°F 2.25 50M-338-37H OR 37V
5-105°F or 60-140°F 6.00 50M-338-50L OR 50X
90-140° F 2.25 50M-338-50S
100-170°F or 160-230°F 2.25 50M-338-50H OR 50V
5-105°F or 60-140°F 15.00 50M-338-1L OR 1X
90-140° F 4.50 50M-338-1S
100-170°F or 160-230°F 4.50 50M-338-1H OR 1V
5-105°F or 60-140°F 41.00 50M-338-2L OR 2X
90-140°F 11.00 50M-338-2S
100-170° or 160-230°F 11.00 50M-338-2H OR 2V
3/8"
1/2", 3/4"
L
MODEL 338 • PLAIN TUBE STRAP-ON TYPE • "A"=3/4"
FOR 500,800,900 SERIES VALVES
1", 1-1/4", & 1-1/2"
2", 2 1/2"