Text version

NEW!

ALARMS & INDICATION

ALARM

S & INDICATIO

N

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 24 VAC/ VDC, 120 VAC, 100 mA max

Contact Rating AIS-24D 24 VDC, 50 mA min AIS-24A 24 VAC, 90 mA min AIS-120A 120 VAC, 70 mA min Alarm Horn 80 db Dimensions 7.09"H x 4.33"W x 3.54"D

(18.0 x 11.0 x 9.0 cm) Mounting Four screws through back Enclosure Polystyrene, impact resistant, knock-outs Approvals RoHS Weight 1.1 lb (0.5 kg) Warranty 1 year

KELE ALARM INDICATION STATION

DESCRIPTION

The Model AIS Alarm Indication Station features an indication light, alarm horn and an alarm horn silence switch.

FEATURES

• Long lasting, red LED indication

• Distinct continuous audible tone

• Horn silence switch

• Compact and rugged design

• Available in 24 VDC, 24 VAC, or 120 VAC

• Bright yellow panel face

Power Supply*

Controlling Device 4 3 2 1

L

H

S

(Alarm initiated by contact closure)

Red LED Light

Alarm horn, 80 db

Alarm Horn Silence Switch

* Power must be supplied to the AIS

AIS

5 N.C.

Four-wire connection

Two-wire connection

Power supply 24 VAC/VDC or 120 VAC

Remote alarm device Alarm initiated by contact closure

A power interrupt or open alarm contact will reset the AIS to normal.

A power interrupt or open alarm contact will reset the AIS to normal.

AIS internal terminal strip

5 N.C.

Power supply 24 VAC/VDC or 120 VAC

Remote alarm device Alarm initiated by contact closure

AIS internal terminal strip

N.C.

N.C.

N.C.=no connection

N.C.=no connection

WIRING

APPLICATION

• Refrigerant leak alarm indication

• Water level alarm indication

• Pressure alarm indication

• High/Low temperature limits

• Gas leak indication

• Humidity limit alarm indication

• Vibration limit

• Voltage/Current level limit

• Any contact closure alarm application

SEQUENCE OF OPERATION

Upon an alarm contact closure, the LED indicator will light, and the horn will sound. The horn can be silenced through the alarm silence switch, while the visual indication will continue to be lighted until the alarm condition has been corrected. A power interruption or open alarm contact will reset the AIS.

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTION

AIS Alarm indication station 12VD 12 VDC powered 24D 24 VDC powered 24A 24 VAC powered 120A 120 VAC powered

Example: AIS-24A 24 VAC powered alarm indication stationAIS 24A