Seaway Visitor Center_Elevator Inspection Report.pdf

PDF 184 KB Posted

Attached to
Elevator Maintenance, Repairs, and Inspection Services Federal contract opportunity
Solicitation number
6923G525Q0599
Issued by
Department of Transportation Saint Lawrence Seaway Development Corporation

About this file

This document is an Electric Elevator Acceptance Inspection & Witness of Test Report for a passenger elevator located at the Dwight D. Eisenhower Visitors' Center in Massena, NY. The inspection was conducted by ATIS Elevator Inspections LLC on 5/1/2024 and revealed one non-compliance item: the elevator's communication system does not meet the text capability requirements of NYSBC Rule 3001.2 for emergency two-way communication.

The inspection report includes detailed test results for normal and standby power car operations, showing consistent speeds of 150 fpm (feet per minute) in all directional and load scenarios. Technical specifications include a load of 2500 lbs, a 3-inch F/L stopping distance, and a top of car clearance of 64 inches. The elevator was manufactured by Kone in 2024, follows the ASME A17.1-2016 installation code, and was inspected by NYS licensed personnel. A notable detail is that the Federal Building specifically requested that video and text capabilities not be hooked up.

View the file

Other files for this federal contract opportunity

Other files attached to Elevator Maintenance, Repairs, and Inspection Services, newest first.
File Type Posted
6923G525Q0599A00002.pdf PDF
6923G525Q0599A00001.pdf PDF
RFQ 6923G525Q0599.pdf PDF
Attachment A_PWS.pdf PDF
Attachment B_Pricing Sheet.xlsx XLSX spreadsheet
Attachment C_Service Contract Act WD 2015-4169.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Electric Elevator

Acceptance Inspection & Witness of Test Report

MRL Tract Elev Barnhart Island Rd.

Massena, NY 13662 Owner: Dwight D. Eisenhower Visitors' Center

Passenger

Kone

Type Rated Load Year Constructed Manufacturer

5/1/2024

C-6981 NAESA International

Date of Report Inspector QEI Certification # QEI Cert. Issuer

Massena, Village of Workorder Designator Authoritative Jurisdiction

Inspection & Test Items Not In Compliance Per ASME A17.1

Failure Reason Communication System does not comply with text capability requirements of NYSBC RULE 3001.2.

MAY 12th 2020 Emergency Two Way

Inspection Item

Car Emergency signal

Applicable Code Reference

Item 1.6

Test Results

Normal Car Operation Empty Car Speed Up: 150 fpm Empty Car Speed Down: 150 fpm Full Car Speed Up: 150 fpm Full Car Speed Down: 150 fpm

Standby Power Car Operation Empty Car Speed Up: 150 fpm Empty Car Speed Down: 150 fpm Full Car Speed Up: 150 fpm Full Car Speed Down: 150 fpm

Load Load Placed on Car: 2500 lbs

Safeties F/L Stopping Distance (Car): 3 inches Releasing Carrier Force: 0 lbs Pull Through Force: 112 lbs

Governor Data Plate: 210 fpm Trip Speed: 204 fpm

Buffers Runby to CW Buffer: 6 inches

Miscelaneous Top of Car Clearance: 64 inches

Notes

Installation Code ASME A 17.1-2016

NYS Licensed Mechanic # 23-6lPA5-SHEL

NYS Licensed Inspector # 132-22-06338

Federal Building requested that Video and text not be hooked up continued on next page

MRL Tract Elev Barnhart Island Rd.

Massena, NY 13662 Owner: Dwight D. Eisenhower Visitors' Center

5/1/2024

Page Date of Report Inspector Workorder Designator

Inspector's Signature This conveyance inspection was performed in compliance with the applicable provisions of ASME A17.2 Guide for Inspection of Elevators, Escalators, and Moving walks. The owner retains full responsibility to maintain this conveyance in compliance with all applicable laws, ordinances and regulations. The Authority Having Jurisdiction retains all rights and responsibilities, as defined by applicable law, regarding verification of compliance.