Q&A_10-1-18.pdf
PDF 77 KB Posted
- Attached to
- WA RIDGE MAIN (1), MAIN AVENUE ACCESS IMPROVEMENT Federal contract opportunity
- Solicitation number
- 69056718B000010
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| BidSum.pdf | ||
| Q&A_10-25-18.pdf | ||
| Amendment_A005.pdf | ||
| Amendment_A004.pdf | ||
| Q&A_10-17-18.pdf | ||
| Amendment_A003.pdf | ||
| WA_RIDGE_MAIN_FINAL_10-12-18.xml | XML file | |
| Utility_relocation_agreement_NW_Natural.pdf | ||
| WA_RIDGE_MAIN_FINAL_10-12-18.tin | — | |
| Q&A_10-12-18.pdf | ||
| Amendment_A002.pdf | ||
| Amendment_A001.pdf | ||
| Q&A_10-4-18.pdf | ||
| WA_RIDGE_MAIN(1)_Plans_3-5-18.pdf.pdf | ||
| Geo_Rpt_12-16_WA_RIDGE_MAIN_(1)_Final_Geotech_Report.pdf | ||
| WA_RIDGE_MAIN_FINAL.tin | — | |
| WA_RIDGE_MAIN(1)_Hydraulic_Report.pdf | ||
| IFB.pdf | ||
| Mitigation_Site.tin | — | |
| WA_RIDGE_MAIN_(1)_Cross_Sections.pdf | ||
| WA-a2015008_EW.pdf | ||
| SWPPP_WA_RIDGE_MAIN(1)_Main_Avenue_Access_Improvements.pdf | ||
| PROJECT_DESCRIPTION.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WA RIDGE MAIN (1)
MAIN AVENUE ACCESS IMPROVEMENT
# General Technical Question Answer Date 1 X Are you requiring DR18 or DR14 C900 PVC pipe for the sewer FM?
Per CRWWD requirements, Polyvinyl chloride (PVC) pipe AWWA C900 or AWWA
C905, SDR 18
10/1/18
2 X Are you requiring restrained pipe joints on any of the C900 PVC sewer FM?
Per CRWWD requirements, Thrust forces in pressurized pipelines shall be restrained or anchored to prevent excessive movement and joint separation under all projected conditions. Thrust restraint shall be mechanically restrained joints.
10/1/18
3 X The plans call for (4) 4” ductile iron MJ 45 bends, are you requiring all the fittings on the sewer force main to be ductile iron or just those (4)?
Please clarify. The (4) each 4‐inch MJ 45 Bends shown on sheet H.1 are part of the Sanitary Sewer. Sanitary Sewer pipe and fitting are PVC according to Subsection 708.05.
10/1/18
4 X Clean‐out detail on sheet H‐8 calls for a (threaded plug 12” with 2” square nut)‐ are you requiring the clean‐out to be 12” diameter on a 4” sewer main?
This will be addressed in a forthcoming Amendment.
10/1/18
5 X Are you requiring restrained pipe joints on any of the 8” CL52 water main? Note 3 on sheet I.2 references a detail which shows minimum pipe joint restrained lengths near fittings, but it isn’t included in the plans or spec.
Yes, the contract does require joint restraint per City of Ridgefield Standards.
10/1/18
6 X Item numbers 62501‐0000 Line A1040 and 62501‐0000 Line A1060 refer to wetland and upland turf establishment. What are the seed type requirements for both of these line items?
Material requirements for Section 625 Turf Establishment are specified in Subsection 625.02.
10/1/2018