671A4-22-172 Med Air Final Design Drawings.pdf

PDF 30 MB Posted

Attached to
Z2DA--Project 671A4-22-172 Replace Med Air and Vacuum System Federal contract opportunity
Solicitation number
36C25725B0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17

About this file

The document appears to be the 671A4-22-172 Med Air Final Design Drawings related to the federal contract opportunity for Project # 671A4-22-172 Replace Med Air Vacuum System, Solicitation Number 36C25725B0001. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The project requires the removal and replacement of the medical air and vacuum system. The document likely contains the final design drawings for this project. No further details about required products/services, response dates, pricing, or other salient information are provided, as this appears to be a technical drawing document rather than a solicitation or other procurement document.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Project 671A4-22-172 Replace Med Air and Vacuum System, newest first.
File Type Posted
36C25725B0001 0006_1 Posting.docx DOCX document
36C25725B0001 0006.pdf PDF
36C25725B0001 0005_Posting Notice.docx DOCX document
36C25725B0001_Site Visit Sign In Sheet.pdf PDF
36C25725B0001 0005.pdf PDF
WD General Decision Number TX20250161 01032025.pdf PDF
Project 671A4-22-172 Bidder RFIs - FINAL RESPONSES - 1-13-2025.pdf PDF
36C25725B0001 0004.pdf PDF
671A4-22-172 Med Air Final Design Drawings - Revs No.1 - 01-10-2025.pdf PDF
FINAL SOW Project 671A4-22-172 Revs JAN 13.pdf PDF
36C25725B0001 0004_1 Posting.docx DOCX document
S06 36C25725B0001 0003.pdf PDF
36C25725B0001 0003_1.docx DOCX document
36C25725B0001 0002_1.docx DOCX document
36C25725B0001 0002.pdf PDF
PCRA MEDICAL AIR AND VACUUM SYSTEM UPGRADE PROJECT 10_30_24.pdf PDF
36C25725B0001_Solicitation_rev01.pdf PDF
36C25725B0001 0001.pdf PDF
ICRA MEDICAL AIR AND VACUUM SYSTEM UPGRADE PROJECT 10_30_24.pdf PDF
36C25725B0001 0001_1.docx DOCX document
671A4-22-172 Med Air Vac Final Design Specs.pdf PDF
S01 36C25725B0001 Solicitation.pdf PDF
36C25725B0001 Solicitation Posting.docx DOCX document
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

PROJECT SITE MAP PROJECT LOCATION MAP

PROJECT IMAGE

/1

/2

:2

:0

A

M C

U s e rs

\n s to lt z \D o c u m e n ts

\A

-0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X n s to lt z .r v t

G-001

COVER SHEET

1 3AT

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758 JANUARY 11, 2022

100% BID DOCUMENTS

671A4-22-17221-040

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758

VA PROJECT #: 671A4-22-172

TM

DRAWING LIST

GENERAL

G-001 COVER SHEET 1 3

G-100 GENERAL INFORMATION 2 3

GL100 ENLARGED BASEMENT LIFE SAFETY PLAN 3 3

PLUMBING

PG001 PLUMBING GENERAL INFORMATION 1 3

PG400 MECHANICAL ROOM MEDICAL GAS PLANS 2 3

P-601 MEDICAL GAS SCHEDULES AND EXISTING EQUIPMENT PHOTOGRAPHS 3 3

ELECTRICAL

E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 3

E-401 ELECTRICAL ENLARGEMENTS - DEMOLITION AND NEW WORK 2 3

E-601 ELECTRICAL SCHEDULES 3 3

KERRVILLE VA

PROJECT AREA

DocuSign Envelope ID: D2FF90DF-8975-4E1C-9A25-4C043CFA3793

1/11/2022 mnorris Snapshot

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO

PARTICIPATE IN VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND

STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• INTERNATIONAL BUILDING CODE (IBC) 2021 (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES

BELOW)

• NFPA 101 LIFE SAFETY CODE 2021 (SEE NOTES BELOW)

• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• NFPA 70 NATIONAL ELECTRICAL CODE 2020

• INTERNATIONAL PLUMBING CODE (IPC) 2018

• ASME CODE FOR PRESSURE PIPING

• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

STANDARD (PG-18-13)

• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 01010 OF THE

VA MASTER CONSTRUCTION SPECIFICATION.

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION

FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY

HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:2

:2

A

M C

U s e rs

\n s to lt z \D o c u m e n ts

\A

-0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X n s to lt z .r v t

G-100

GENERAL INFORMATION

2 3AT

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758 JANUARY 11, 2022

100% BID DOCUMENTS

671A4-22-17221-040

TM

CODE STANDARDS AND EXECUTIVE ORDERS

DocuSign Envelope ID: D2FF90DF-8975-4E1C-9A25-4C043CFA3793

1/11/2022

UP

U P

UP

U P

EMS

EQUIPMENT

ROOM

010A

STORAGE

010B

IDF 010D

010D

CRAWL

SPACE

MAIN

ELEVATOR

LOBBY

ELECT.

CLOSET

MECH.

ROOM

SERVICE

ELEVATOR

LOBBY

MUSEUM

028A

SERVICE

ELEVATOR

NO. 3

PASSENGER

ELEVATOR

NO. 2

PASSENGER

ELEVATOR

NO. 1

E.C.

UP

U P

UP

U P

A

8 9 10 11 12 13 14 15

B

C

D

E

T R

A V

E L D

IS

T

A N

C E

CORRIDOR

PIPE

BASEMENT

MECHANICAL

ROOM

028A

EGRESS PATH

EGRESS PATH TAG

EGRESS PATH TAG - COMMON PATH

EGRESS IDENTIFICATION

AREA OF REFUGE

HAZARDOUS LOCATION

FIRE EXTINGUISHER BRACKET

FIRE EXTINGUISHER CABINET

FIRE BLANKET CABINET

EMERGENCY RESPONSE REFERENCE

CONTROLLED ACCESS - ALWAYS

UNLOCKED IN DIRECTION OF EGRESS

KNOX BOX

DELAYED EGRESS W/ ALARM

CA

DE

KB

XXX

XXX

FEB

FEC

FBC

CAPACITYCLR

EXTERIOR

EXIT

XX" ###

EXIT

IDENTIFICATION

EGRESS CLEAR

WIDTH

EGRESS CAPACITY

EXISTING DEADEND CORRIDOR

EXCEEDING 30' SHALL BE

PERMITTED TO CONTINUE IN USE IF

IT IS UNPRACTICAL AND

UNFEASIBLE TO ALTER FROM.

INCREASE TRAVEL DISTANCE 50FT IF

BUILDING IS SPRINKLED

TOTAL SQUARE

FOOTAGE:

MECHANICAL ROOM 028 3,409 GSF

HEALTHCARE - OUTPATIENT

- 240 SF / PERSON

EGRESS LEGEND

REQUIRED # OF

EXITS

(per NFPA 101, 19.2.4)

- 2 EXITS MIN. PER FLOOR REQ'D

- 2 EXISTING EXITS, NOT BEING

MODIFIED

OCCUPANCY:

EGRESS

REQUIRED:

EXISTING MECHANICAL SPACE. NO

SMOKE MODIFICATION OF THE

SPACE OR EGRESS BEING

PERFORMED

COMMON PATH

OF TRAVEL

(NFPA 101 -

7.13.1(2) )

IN EXISTING BUILDING, COMMON

PATH OF TRAVEL NOT TO EXCEED

150'

TRAVEL

DISTANCE

INCREASE

(per NFPA 101-19.2.6.2.1)

150'-0" MAXIMUM DISTANCE.

DEAD END

CORRIDOR

(NFPA 101-19.2.5.2)

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/1

/2

:2

:2

A

M C

U s e rs

\n s to lt z \D o c u m e n ts

\A

-0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X n s to lt z .r v t

GL100

ENLARGED BASEMENT LIFE SAFETY

PLAN

3 3AT

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758 JANUARY 11, 2022

100% BID DOCUMENTS

671A4-22-17221-040

TM

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

BASEMENT

EASTWEST

NORTH MECHANICAL

ROOM

Scale: 1/8" = 1'-0"

ENLARGED BASEMENT LIFE SAFETY PLAN

PROPOSED USE:

OWNED BY:

CODE ENFORCEMENT JURISDICTION: FEDERAL

APPLICABLE CODES:

GENERAL CODE INFORMATION:

CONSTRUCTION TYPE:

PRIMARY OCCUPANCY:

SECONDARY OCCUPANCY:

PROJECT NAME:

PROJECT ADDRESS:

OWNER OR AGENT:

FEDERAL

N/A

Relevant Code Goes Here

Relevant Code Goes Here

Relevant Code Goes Here

20XX International Building Code

20XX Plumbing Code

20XX Electrical Code 20XX ADA Code

Relevant Code Goes Here

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758

KERRVILLE VA MEDICAL CENTER

CODE INFORMATION

LIFE SAFETY LEGEND

NORTH

0 4 8 16

A. SEE SHEETS A001 FOR SYMBOLS AND

ABBREVIATIONS.

B. REFER TO MECHANICAL DRAWINGS FOR

INFORMATION

C. REFER TO ELECTRICAL DRAWINGS FOR

INFORMATION CONCERNING POWER, LIGHTING

AND COMMUNICATION SYSTEM(S)

D. CONTRACTOR TO PROVIDE ALL ADDITIONAL

FRAMING NECESSARY FOR ALL OPENINGS AND

SUPPLEMENTAL FRAMING ABOVE PARTITIONS.

E. ALL FIRE RATED ASSEMBLIES SHALL BE

INSTALLED IN STRICT ACCORDANCE WITH TESTED

ASSEMBLIES INDICATED.

F. EXTEND FIRE RATED PARTITIONS, BARRIERS, AND

OTHER SEPARATIONS TO BOTTOM OF

ROOF/FLOOR DECK ABOVE (OR AS DIRECTED BY

UL ASSEMBLY) AND TO EXTERIOR WALL. SEAL

JOINT BETWEEN EDGES OF PARTITION WITH FIRE

RATED SEALANT AND/OR INTUMESCENT

ASSEMBLY.

G. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES

SHALL BE FIRE-SEALED IN ACCORDANCE WITH

APPROVED MANUFACTURER'S DETAIL FOR

LOCATION, TYPE OF CONSTRUCTION,

PENETRATING ITEM AND RATING REQUIRED.

H. SMOKE RESISTANT CONSTRUCTION SHALL MEET

THE REQUIREMENTS OF ALL APPLICABLE CODES.

AREA SHALL BE SEPARATED FROM THE

REMAINDER OF THE BUILDING BE CONSTRUCTION

CAPABLE OF RESISTING THE PASSAGE OF

SMOKE. THE PARTITIONS SHALL EXTEND FROM

THE FLOOR TO THE UNDERSIDE OF THE FLOOR

OR ROOF ASSEMBLY ABOVE. DOORS SHALL BE

SELF OR AUTOMATIC CLOSING. DOORS SHALL

NOT HAVE AIR TRANSFER OPENINGS AND SHALL

NOT BE UNDERCUT IN EXCESS OF CLEARANCE

PERMITTED WITH ACCORDANCE TO NFPA 80.

I. STORAGE OF ANY FLAMMABLE OR COMBUSTIBLE

LIQUIDS IS UNDERSTOOD TO NOT BE WITHIN THE

BUILDING. STORAGE OF ANY MATERIAL IS TO BE

IN COMPLIANCE WITH ALL APPLICABLE CODES

AND AUTHORITIES HAVING JURISDICTION.

J. FACILITY SAFETY PERSON TO VERIFY IF EXISTING

EGRESS FROM MECHANICAL SPACES MEET THE

REQUIREMENTS OF NFPA 101.

OCCUPANCY CLASSIFICATION

(NFPA 2018 101 SECTION 4.1):

HEALTHCARE OCCUPANCY BUILDING, SPRINKLERED

CONSTRUCTION TYPE I (442)

MEANS OF EGRESS:

STAIR ENCLOSURE: 2-HR (NFPA 101.7.1.3.2.1)

MIN. EXIT WIDTH: 32" CLEAR (NFPA 101.2.1.2.2)

OCCUPANT LOAD: (NFPA 101.7.3)

HEALTHCARE INPATIENT: 1:240

STORAGE: 1:300

CAPACITY FACTORS: (NFPA 101.7.3.3):

STAIRS: 0.3

OTHER: 0.2

DocuSign Envelope ID: D2FF90DF-8975-4E1C-9A25-4C043CFA3793

1/11/2022

DCWR

DHW

PIPING SYSTEM

NG NATURAL GAS

ST STORM

PD PUMP DISCHARGE

OFD OVERFLOW STORM DRAIN

GW GREASE WASTE

OW OIL WASTE

SAN SANITARY WASTE

CD CONDENSATE DRAIN

CA COMPRESSED AIR

AW ACID WASTE

N2 NITROGEN

N2O NITROUS OXIDE

MA MEDICAL AIR

O2 OXYGEN

WAGD WASTE ANESTHETIC GAS DISPOSAL

VAC VACUUM

V SANITARY VENT

OV OIL VENT

AV ACID VENT

NPCW NONPOTABLE COLD WATER

DI DE-IONIZED WATER

SCW SOFTENED COLD WATER

DCW DOMESTIC COLD WATER

RO REVERSE OSMOSIS WATER

DOMESTIC CW RECIRCULATION

DOMESTIC HOT WATER

CO2 CARBON DIOXIDE

DHW 140 DOMESTIC HOT WATER (OTHER TEMP)

PG PROPANE GAS

DHWR DOMESTIC HW RECIRCULATION

NG

ST

PD

OFD

GW

OW

SAN

CD

CA

AW

N2

N2O

MA

O2

WAGD

VAC

CO2

PG

V

OV

AV

HW 140

SCW

NPCW

DI

RO

EXISTING

NEW WORK KEYNOTE

DEMOLITION KEYNOTE

NEW BOLD TEXT INDICATES NEW ITEM

ITALICIZED TEXT INDICATES EXISTING ITEM

NEW PLUMBING EQUIPMENT MARK

DETAIL OR SECTION MARK

SHOWN ON DRAWING

DETAIL MODULE NUMBER

CONNECT TO EXISTING

LIMIT OF DEMOLITION

P-###

EXISTING PLUMBING EQUIPMENT MARKP-###

3-WAY CONTROL VALVE

ANGLE GATE VALVE

ANGLE GLOBE VALVE

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

CONTROL VALVE

GATE VALVE

GLOBE VALVE

SAFETY RELIEF VALVE

TWO POSITION CONTROL VALVE

BACKFLOW PREVENTER

ECCENTRIC REDUCER

CONCENTRIC REDUCER

FLOW ARROW

HOSE BIBB / SILLCOCK

PLUG VALVE

PRESSURE REDUCING VALVE (WATER)

PRESSURE REGULATOR (GAS)

PIPE ANCHOR

PIPE GUIDES

WALL CLEANOUT

SUSPENDED CLEANOUT

WCO

WYE STRAINER

WYE STRAINER W/DRAIN VALVE

FLOOR DRAIN - ROUND OR SQUARE

FLOOR CLEANOUT

PIPE CAP

PIPE TURNING DOWN

PIPE TURNING UP

TEE UP

TEE DOWN

DROP AND RUN

DROP AND TURN

TEE OFF TOP

TEE OFF BOTTOM

CROSS AND RISER

PLAN 90° ELBOW

PIPE TEE

PIPE UNION

FLEXIBLE PIPE CONNECTOR

WATER METER

PUMP

AUTOMATIC AIR VENT

PRESSURE SWITCH

PRESSURE GAUGE

THERMOMETER

FLOW SWITCH

TEMPERATURE SWITCH

OR

CO

PIPE SLOPE ARROW

AV

F

P

T

M

CIRCUIT SETTER

F FAHRENHEIT

FA FROM ABOVE

FB FROM BELOW

FBO FURNISHED BY OTHERS

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT (HOSE)

CONNECTION

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FU FIXTURE UNITS

G GALLON

GC GENERAL CONTRACTOR

GCO GRADE CLEANOUTS

GD GARBAGE DISPOSAL

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED WATER HEATER

H&CW HOT AND COLD WATER

HB HOSE BIBB (INTERIOR)

HD HUB DRAIN

HEX HEAT EXCHANGER

HP HORSEPOWER

HS HAND SINK

HST HOT WATER STORAGE TANK

(DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HYD HYDRANT

ICW INDUSTRIAL COLD WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

KW KILOWATT

KWHR KILOWATT-HOUR

L/S LITER PER SECOND

LA LABORATORY AIR

LAV LAVATORY

LBS/HR POUNDS PER HOUR

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH THOUSANDS OF BTU PER HOUR

MC MECHANICAL CONTRACTOR

MED MEDICAL

MER MECHANICAL EQUIPMENT ROOM

MH MANHOLE

MOU MEMORANDUM OF UNDERSTANDING

MSB MOP SINK BASIN

MV MEDICAL VACUUM

N2 NITROGEN

N2O NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

O2 OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OR OPERATING ROOM

OVFL OVERFLOW

PA PASCAL

PC PLUMBING CONTRACTOR

PD PRESSURE DROP

PDI PLUMBING AND DRAINAGE INSTITUTE

PG PRESSURE GAUGE

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH -

ABSOLUTE

PSIG POUNDS PER SQUARE INCH - GAUGE

PTRV PRESSURE TEMPERATURE RELIEF

VALVE

PW POTABLE WATER

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RO REVERSE OSMOSIS

RWL RAIN WATER LEADER

SAN SANITARY SEWER

SCFM STANDARD CUBIC FOOT/MIN

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT SQUARE FOOT

SS STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

TCV TEMPERATURE CONTROL VALVE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TDL TEMPERATURE DIFFERENTIAL

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

UPC UNIFORM PLUMBING CODE

V SANITARY VENT

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM PUMP

VS VENT STACK

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAUGE

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

WHD WALL HYDRANT

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

YCO YARD CLEANOUT

YH YARD HYDRANT

A/E ARCHITECT/ENGINEER

AC ABOVE CEILING

AD AREA DRAIN

AFF ABOVE FINISHED FLOOR

AG AIR GAP

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

AFG ABOVE FINISHED GRADE

ASD ADJUSTABLE SPEED DRIVE

ASHRAE AMERICAN SOCIETY HEATING,

REFRIGERATING, AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

ASPE AMERICAN SOCIETY PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

BAS BUILDING AUTOMATION SYSTEM

BF BELOW FLOOR

BFP BACKFLOW PREVENTER

BG BELOW GRADE

BH BOOSTER HEATER

BHP BREAK HORSEPOWER

BJ BETWEEN JOISTS

BOP BOTTOM OF PIPE

BSP BLACK STEEL PIPE

BT BATHTUB

BTUH BRITISH THERMAL UNITS PER HOUR

C CELSIUS

CF COMBINATION FIXTURE

CGA COMPRESSED GAS ASSOCIATION

CI CAST IRON

CO CLEANOUT

COND CONDENSATE

CP CONDENSATE PUMP

CS CLINICAL SINK

CV CONTROL VALVE

DA DENTAL COMPRESSED AIR

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DHWS DOMESTIC HOT WATER SUPPLY

DF DRINKING FOUNTAIN

DI DEIONIZED WATER

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DV DENTAL VACUUM

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

EC ELECTRICAL CONTRACTOR

EL ELEVATION

EMCS ENERGY MONOSERRAT AND CENTRAL

SYSTEM

EPA ENVIRONMENTAL PROTECTION

AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWS EYEWASH STATION

EX EXISTING

PLUMBING SYMBOLS PLUMBING SYMBOLS

ANNOTATION SYMBOLS

PLUMBING SYMBOLS & ABBREVIATIONS

ANNOTATION ABBREVIATIONS 1. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR REGARDING CONFLICTS BEFORE PROCEEDING WITH

WORK.

2. REMOVED ITEMS REMAIN PROPERTY OF GOVERNMENT UNTIL COR DETERMINES THAT THEY ARE NOT REQUIRED. REMOVE FROM SITE ITEMS NOT BEING RETAINED BY GOVERNMENT OR REINSTALLED AS PART OF THIS WORK.

3. DO NOT DISTURB ITEMS NOT INDICATED FOR DEMOLITION.

4. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION. RELOCATE, REMOVE AND ADJUST

MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO COORDINATE WITH NEW WORK.

5. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING ADJACENT CONDITIONS.

6. COORDINATE DEMOLITION WITH COR. SUBMIT SHUTDOWN PLAN AND SCHEDULE TO COR FOR REVIEW AND APPROVAL.

7. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION. REPAIR UTILITIES AND SERVICES DAMAGED AT

NO ADDITIONAL COST.

8. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE WORK.

9. COORDINATE WITH NEW PLUMBING WORK AND WORK OF OTHER TRADES.

10. TEST EXISTING SYSTEMS FOR OPERATION, ALARMS, AND CAPACITY THEN PROVIDE REPORT TO COR PRIOR TO START OF

DEMOLITION.

11. ISOLATE SUPPLY EQUIPMENT FROM DISTRIBUTION SYSTEMS BY SHUTTING OFF SOURCE VALVES BEFORE BEGINNING

DEMOLITION.

PLUMBING DEMOLITION GENERAL NOTES

1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.

2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.

3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.

4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE

PURPOSES INTENDED.

5. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS ARE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT

EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.

6. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT

MAINTENANCE, REPAIRS, AND REPLACEMENT.

7. SUPPORT PIPING SYSTEM AS REQUIRED BY APPLICABLE LOCAL, STATE, AND NATIONAL CODES ALONG WITH

SPECIFICATIONS, VA STANDARDS AND MANUFACTURER'S RECOMMENDATIONS.

8. FIRESTOP AND SEAL PIPING PENETRATIONS THROUGH WALLS AND FLOORS EQUAL TO THE RATING OF WALLS AND FLOORS.

9. TEST PLUMBING SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND NATIONAL CODES AND APPLICABLE VA

STANDARDS.

10. COORDINATE PLUMBING PIPING WITH WORK OF OTHER DISCIPLINES.

11. PROVIDE SHUT OFF VALVES AT BRANCH PIPING TO FIXTURES.

12. COORDINATE PLUMBING WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION. COORDINATE ROUTING OF PIPING WITH

EXISTING CONDITIONS.

13. PROVIDE ALL NECESSARY OFFSETS, TEES, ELBOWS, ETC. FOR A COMPLETE AND COORDINATED WORKING PLUMBING SYSTEM. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING

SYSTEMS.

14. CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM REQUIRED SHUTDOWN WITH THE COR 1 WEEK IN ADVANCE.

15. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH PLUMBING WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.

16. DO NOT INSTALL PIPES ABOVE TELECOM OR ELECTRICAL EQUIPMENT.

17. PROVIDE RECERTIFICATION OF NEW INSTALLED MEDICAL GAS EQUIPMENT. TEST SYSTEMS FOR OPERATION, ALARMS AND

CAPACITY AND PROVIDE FINAL COMMISSIONING REPORT.

PLUMBING GENERAL NOTES

NOM. SIZE (IN.)

PIPE (FT.)

TUBING (FT.)

5 FT

THRU 3/4

1 1 1/4

1 1/2

HANGER ROD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR

LOW TEMPERATURE

PIPE)

PROVIDE HIGH

COMPRESSIVE

STRENGTH

INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION SHIELD AT

HANGER

WELD

SADDLE

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE

SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE

SPECIFICATIONS

1/2" DIA. HANGER RODS WITH 36"

MAX. SPACING ON EACH CHANNEL

BAND

1-5/8" 12 GAUGE CHANNEL

OR 2" x 2" x 1/4" ANGLE

NOTES:

SEE SPECIFICATIONS FOR

DETAILED HANGER

REQUIREMENTS. SIDE VIEW TRAPEZE HANGER

FOR UP TO 1000 LB. UNIFORM

LOAD

1" MAX.

PROVIDE INSULATION SHIELD &

INSERT FOR ALL PIPING (8" MIN.)

2 2 1/2 3 4 5 6 8 10 12

11 12 14 16 17 19 22 23

9 10 12 13 14 16 - -

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE

MAXIMUM PIPE/TUBING SUPPORT SPACING

1. PROVIDE STICKY MAT ON ENTIRE FLOOR AREA OF SERVICE ELEVATOR LOBBY BETWEEN SERVICE ELEVATOR #3 AND THE

DOOR TO THE MECHANICAL ROOM WHERE NEW EQUIPMENT IS BEING INSTALLED.

2. PROVIDE ZIPPER ENTRY AT ACCESS POINT TO CONSTRUCTION AREA, AT DOOR TO THE MECHANICAL ROOM, IF THE WORK

REQUIRED TO INSTALL THE EQUIPMENT WILL GENERATE ANY DUST.

3. PROVIDE ICRA BARRIERS AS NECESSARY TO PERFORM THE WORK PER THE MECHANICAL DRAWINGS. THE USE OF TEMPORARY, REUSABLE TYPE BARRIERS (EX. STARC WALL SYSTEMS) IS ACCEPTABLE. ENSURE THAT ACCESS THROUGH THE BARRIERS IS PROVIDED IF THE TEMPORARY BARRIERS CUTS OFF ACCESS FROM THE MECHANICAL ROOM OR ANY

OTHER SPACE TO THE MEANS OF EGRESS.

INFECTION CONTROL NOTES

1. PROVIDE RECERTIFICATION OF BUILDING SIDE MEDICAL GAS SYSTEM. TEST SYSTEM FOR OPERATION, ALARMS AND

CAPACITY AND PROVIDE FINAL COMMISSIONING REPORT.

BID ALTERNATE NOTES

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:5

:5

A M

C U s e rs

\n s to lt z \D o c u m e n ts \M

F P

-0

-V A

K e rr v ill e -M e d A ir V a c S y s te m -T

X n s to lt z .r v t

PG001

PLUMBING GENERAL INFORMATION

1 3NAS

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758 JANUARY 11, 2022

100% BID DOCUMENTS

671A4-22-17221-040

RBK

Scale: No Scale

PIPE HANGER DETAIL

DocuSign Envelope ID: 23E13BA4-D0F9-42A1-BCB8-E4C79E81E576

1/11/2022

D A

I D

A I

U P

U P

E.C.

A

11 12 13 14

1" MA

2" MV

M A

MECHANICAL

CRAWL SPACE

UNEXCAVATED

CRAWL SPACE

PIPE BASEMENT

11-AC-1

TO OUTLET

4" MV EXHAUST

M V

E X H A U S T

FROM INTAKE

11-VP-1

TO BUILDING

DISTRIBUTION SYSTEM

FROM BUILDING

DISTRIBUTION SYSTEM

OUTLINE OF EXISTING

HOUSKEEPING PAD

A

11 12 13 14

1 2

2" MV

M A

FROM INTAKEEXHAUST TO

OUTLET

TO BUILDING

DISTRIBUTION SYSTEM

FROM BUILDING

DISTRIBUTION SYSTEM

CRAWL SPACE

UNEXCAVATED

MECHANICAL

PIPE BASEMENT

CRAWL SPACE

EX-11-AC-1

EX-11-VP-1

4" MV EXHAUST

M V

E X H A U S T

1" MA

OUTLINE OF EXISTING

HOUSKEEPING PAD

1.

1.

A

B

C

D

E

F

10 11 12 13 14

CRAWL SPACE

UNEXCAVATED

MECHANICAL

CRAWL SPACE

UNEXCAVATED

UNEXCAVATED

MECH. ROOM

SERVICE

ELEVATOR

LOBBY

ELECT.

CLOSET

MAIN

ELEVATOR

LOBBY

PASSENGER

ELEVATOR

NO. 1

PASSENGER

ELEVATOR

NO. 2

SERVICE

ELEVATOR

NO. 3

4" MV EXHAUST UP

THROUGH ROOF

SERVICE ELEVATOR FOR

ACCESS WITH EQUIPMENT

STAIRWELL EXIT TO

OUTSIDE AT FIRST

FLOOR LEVEL

Engineers Architects

# NEW WORK KEY NOTES:

# DEMOLITION KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/7

/2

:5

:0

A M

C U s e rs

\n s to lt z \D o c u m e n ts \M

F P

-0

-V A

K e rr v ill e -M e d A ir V a c S y s te m -T

X n s to lt z .r v t

PG400

MECHANICAL ROOM MEDICAL GAS

PLANS

2 3NAS

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758 JANUARY 11, 2022

100% BID DOCUMENTS

671A4-22-17221-040

RBK

N

KEY PLAN

SCALE: NO SCALE

BASEMENT

EASTWEST

NORTH MECHANICAL

ROOM

Scale: 1/4" = 1'-0"

BASEMENT MECHANICAL ROOM MEDICAL GAS PLAN

NORTH

0 2 4 8

Scale: 1/4" = 1'-0"

BASEMENT MECHANICAL ROOM MEDICAL GAS DEMOLITION PLAN

NORTH

0 2 4 8

1 NEW MEDICAL AIR COMPRESSOR SYSTEM.

CONNECT TO EXISTING SUPPLY PIPING AND AIR

INTAKE.

2 NEW MEDICAL VACUUM PUMP. CONNECT TO

EXISTING SUPPLY PIPING AND VACUUM EXHAUST.

3 RECONNECT NEW EQUIPMENT TO EXISTING

MASTER ALARM AT JUNCTION BOX.

4 PROVIDE SUPPORT FOR NEW AND EXISTING

MEDGAS PIPING ASSOCIATED WITH AIR

COMPRESSOR AND VACUUM PUMP IN MECHANICAL

ROOM. SUPPORT FOR THIS PIPING SHALL CONFORM

WITH SPECIFICATIONS.

5 PROVIDE STICKY MAT AT ENTRANCE TO

CONSTRUCTION AREA PER FACILITY ICRA

REQUIREMENTS.

1 EXISTING MEDICAL AIR COMPRESSORS, RECEIVER,

AND DESICCANT COOLER TO BE REMOVED.

DEMOLISH ASSOCIATED PIPING TO POINTS

INDICATED.

2 EXISTING MEDICAL VACUUM PUMP TO BE REMOVED.

DEMOLISH ASSOCIATED PIPING TO POINTS

INDICATED.

3 REMOVE EXISTING DEW POINT SENSOR ON MEDICAL

AIR SUPPLY MAIN AND TURN OVER TO VA.

A. COORDINATE ANY LOSS OF MEDICAL GAS

SERVICE WITH COR AT LEAST 1 WEEK IN

ADVANCE. PROVISION OF TEMPORARY MEDICAL

GAS SUPPLY EQUIPMENT DURING EQUIPMENT

CHANGEOVER IS NOT IN CONTRACT.

B. PROVIDE STICKY MAT ON ENTIRE FLOOR AREA

OF SERVICE ELEVATOR LOBBY BETWEEN

SERVICE ELEVATOR #3 AND THE DOOR TO THE

MECHANICAL ROOM WHERE NEW EQUIPMENT IS

BEING INSTALLED.

C. PROVIDE ZIPPER ENTRY AT ACCESS POINT TO

CONSTRUCTION AREA, AT DOOR TO THE

MECHANICAL ROOM, IF THE WORK REQUIRED TO

INSTALL THE EQUIPMENT WILL GENERATE ANY

DUST.

D. PROVIDE ICRA BARRIERS AS NECESSARY TO

PERFORM THE WORK PER THE MECHANICAL

DRAWINGS. THE USE OF TEMPORARY, REUSABLE

TYPE BARRIERS (EX. STARC WALL SYSTEMS) IS

ACCEPTABLE. ENSURE THAT ACCESS THROUGH

THE BARRIERS IS PROVIDED IF THE TEMPORARY

BARRIERS CUTS OFF ACCESS FROM THE

MECHANICAL ROOM OR ANY OTHER SPACE TO

THE MEANS OF EGRESS.

E. CONTRACTOR IS TO PROVIDE FLOORING

PROTECTION FROM ENTRY DOOR TO SERVICE

ELEVATOR OF THE FIRST FLOOR AND FROM THE

SERVICE ELEVATOR TO THE MECHANICAL ROOM

DOOR AT THE BASEMENT LEVEL. PLYWOOD

FLOOR COVERING IS SUGGESTED, BUT THE

CONTRACTOR CAN UTILIZE WHATEVER FLOOR

PROTECTION MATERIAL THEY FEELS WILL

ACCOMPLISH THE JOB. CONTRACTOR SHALL BE

RESPONSIBLE FOR AND DAMAGE TO THE

FLOORING, ADJACENT SURFACES, ETC. CAUSED

BY THE PERFORMANCE OF THE CONTRACTOR’S

WORK OR BY THEIR PERSONNEL.

F. FOR PHOTOGRAPHS OF EXISTING CONDITIONS

SEE PG601.

Scale: 1/8" = 1'-0"

BASEMENT MECHANICAL ROOM INFECTION CONTROL PLAN

NORTH

0 4 8 16

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:5

:0

A M

C U s e rs

\n s to lt z \D o c u m e n ts \M

F P

-0

-V A

K e rr v ill e -M e d A ir V a c S y s te m -T

X n s to lt z .r v t

P-601

MEDICAL GAS SCHEDULES AND

EXISTING EQUIPMENT PHOTOGRAPHS

3 3NAS

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758 JANUARY 11, 2022

100% BID DOCUMENTS

671A4-22-17221-040

RBK

Scale: No Scale

EXISTING AIR AND VACUUM SYSTEMS

Scale: No Scale

EXISTING DESSICANT SYSTEM

Scale: No Scale

MEDICAL AIR COMPRESSOR VIEW 1

Scale: No Scale

MEDICAL AIR COMPRESSOR VIEW 2

Scale: No Scale

MEDICAL AIR COMPRESSOR VIEW 3

Scale: No Scale

MEDICAL AIR INTAKE

Scale: No Scale

VACUUM PUMPS

Scale: No Scale

VACUUM TANK AND CONTROL PANEL

11-VP-1 BASEMENT... BUILDING 11 MEDICAL VACUUM DUPLEX DRY CLAW 200 [ 760 ] 19 [ 64 ] 65 [ 31 ] 2 7.5 5.6 [ 3 ] 460 21 2190 1, 2, 3, 4, 5, 6, 7, 8, 9

GAL [L] in Hg [kPa] SCFM STANDARD [L/s] HP [Kw]

NO. PUMPS

POWER EACH

PHASE VOLT FLA

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

SERVICE

TYPE UNIT

RECEIVER SIZE VACUUM PRESSURE

CFM DELIVERY @ VACUUM

PRESSURE (SI)

ELECTRIC POWER

WEIGHT

(LBS)

REMARKS

VACUUM PUMP SCHEDULE

11-AC-1

BASEMENT

MECHANICAL

BUILDING 11 MEDICAL AIR

DUPLEX OIL-LESS

SCROLL

24 [ 94 ] 120 [ 830 ] 200 [ 760 ] 36X84 [900X2100] 2 7.5 [ 6 ] 3 460 22 2330 1, 2, 3, 4, 5, 6, 7, 8, 9

CFM [L/s] PSIG [kPa] GAL [L] IN [mm] HP [kW]

NO. MOTORS

POWER EA.

PHASE VOLT FLA

MARK LOCATION

AREA AND/OR

BLDG SERVED

SYSTEM AND/OR

SERVICE

TYPE

NFPA AIRFLOW CAPACITY

NFPA DISCHARGE

PRESSURE

RECEIVER SIZE

RECEIVER DIMENSIONS, DIA

X LENGTH

ELECTRIC POWER [60 Hz]

WEIGHT

(LBS)

REMARKS

AIR COMPRESSOR SCHEDULE

NOTES:

1. CAPACITIES ARE AT SITE CONDITION.

2. BASIS OF DESIGN IS AMICO MODEL V-CCD-D-200P-SS-N-075-MS.

3. MODULAR UNITS THAT CAN BE DISASSEMBLED AND REASSEMBLED ON SITE.

4. PROVIDE ALL ACCESSORIES FOR FULLY FUNCTIONAL SYSTEM.

5. PROVIDE ALL ALARMS PER NFPA AND CONNECT TO EXISTING ALARM SYSTEM.

6. PROVIDE DRAIN PIPING WITH VALVE AND MAIN ISOLATION VALVE FOR THE UNIT.

7. UNIT SHALL OPERATE BETWEEN 19" Hg AND 25" Hg WITH CAPACITY AT LISTED SCFM.

8. LISTED CAPACITY IS WITH ONE PUMP IN OPERATION.

9. PROVIDE GAUGES, SENSORS, AND SAFETY DEVICES.

NOTES:

1. CAPACITIES ARE AT SITE CONDITION.

2. BASIS OF DESIGN IS AMICO MODEL A-SCD-D-200P-SS-N-075-TS

3. MODULAR UNIT THAT CAN BE DISASSEMBLED AND REASSEMBLED ON SITE.

4. PROVIDE ALL ACCESSORIES FOR FULLY FUNCTIONAL SYSTEM.

5. PROVIDE ALL ALARMS PER NFPA AND CONNECT TO EXISTING ALARM SYSTEM.

6. PROVIDE DRAIN PIPING WITH ISOLATION VALVE AND MAIN ISOLATION VALVE FOR THE UNIT.

7. PROVIDE DESSICANT AIR DRYER WITH ALL ACCESSORIES.

8. LISTED CAPACITY IS WITH ONE PUMP IN OPERATION.

9. PROVIDE GAUGES, SENSORS, AND SAFETY DEVICES.

L L

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BIPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

R RELOCATE/RELOCATED

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

2W TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCT CORRELATED COLOR TEMPERATURE

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

D DEMOLITION

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT

SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL

ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.

SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK

AREA, FOR THE STARTING POINT OF THE CALCULATIONS.

METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS

USING OHM'S LAW AND THE KNOWN RESISTIVITY CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED THE

RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH CIRCUIT CONDUCTORS.

METHOD OF VOLTAGE DROP CALCULATIONS

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE

EQUIPMENT CONNECTION

AS

NOTED

E

208V DUPLEX RECEPTACLE18"

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

120V SIMPLEX RECEPTACLE18"2' X 2' RECESSED ARCHITECTURAL TROFFER

2' X 4' RECESSED ARCHITECTURAL TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT LENS TROFFER

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

VS: VACANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

DR: DUAL RELAY

VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER

OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

4: 4 WAY

48"

CENTER

OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, LOW VOLTAGE, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

OS

OS

LS

4' LINEAR STRIP - SUSPENDED---

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:2

:2

P M

C U s e rs \j w b e e z le y \D o c u m e n ts

\E

-0

-V A

K e rr v ill e -M e d

A ir V a c S y s te m -T

X jw b e e z le y a c g

-p a .c o m

.r v t

E-001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 3JWB

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 VETERANS DRIVE, KERRVILLE, TX

28028 JANUARY 11, 2022

100% CONSTRUCTION DOCUMENTS

671-A4-22-17221-040

MJJ

ELECTRICAL ABBREVIATIONS LIST

ELECTRICAL SYMBOL NOTES

ELECTRICAL GENERAL NOTES

ELECTRICAL SYMBOL LEGENDLIGHTING SYMBOL LEGEND

A

D

A

V

E

N F

E

T

A

T

S

R

E

ENI

G

N

E

N o

E

O

MICHAEL J.

JENSEN

ELECTRICAL

A

N

O I

S S

E

F

R

P

L

Exp.

06/30/23

DocuSign Envelope ID: FCFB9153-3C99-48D2-8B65-8D3C2A627379

1/11/2022

11 12 13 14

A

MECHANICAL

EXISTING

PANEL 'PBYEA'

EX-11-AC-1 EX-11-VP-11 2

CRAWL SPACE

UNEXCAVATED

CRAWL SPACE

PIPE BASEMENT

3 4

11 12 13 14

A

MECHANICAL

11-VP-1

11-AC-11

CRAWL SPACE

UNEXCAVATED

CRAWL SPACE

PIPE BASEMENT

EXISTING

PANEL 'PBYEA'

3 4

Engineers Architects

# NEW WORK KEY NOTES:

# DEMOLITION KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/7

/2

:2

:2

P M

C U s e rs \j w b e e z le y \D o c u m e n ts

\E

-0

-V A

K e rr v ill e -M e d

A ir V a c S y s te m -T

X jw b e e z le y a c g

-p a .c o m

.r v t

E-401

ELECTRICAL ENLARGEMENTS -

DEMOLITION AND NEW WORK

2 3JWB

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 VETERANS DRIVE, KERRVILLE, TX

28028 JANUARY 11, 2022

100% CONSTRUCTION DOCUMENTS

671-A4-22-17221-040

MJJ

1 CONNECT NEW PACKAGED MEDICAL AIR

COMPRESSOR EQUIPMENT. SEE

MECHANICAL EQUIPMENT CONDUCTOR

SCHEDULE AND ASSOCIATED PANEL

SCHEDULE.

2 CONNECT NEW PACKAGED MEDICAL

VACUUM PUMP EQUIPMENT. SEE

MECHANICAL EQUIPMENT CONDUCTOR

SCHEDULE AND ASSOCIATED PANEL

SCHEDULE.

3 INSTALL A NEW 30A/3P CIRCUIT BREAKER

TO FEED THE NEW VACUUM PLANT

EQUIPMENT IN PANEL-'PBYEA',

CIRUITS-1,3,5.

4 INSTALL A NEW 30A/3P CIRCUIT BREAKER

TO FEED THE NEW AIR COMPRESSOR

EQUIPMENT IN PANEL-'PBYEA',

CIRCUITS-19,21,23.

N

KEY PLAN

SCALE: NO SCALE

BASEMENT

EASTWEST

NORTH MECHANICAL

ROOM

Scale: 1/4" = 1'-0"

BASEMENT MECHANICAL ROOM ELECTRICAL DEMOLITION PLAN

Scale: 1/4" = 1'-0"

BASEMENT MECHANICAL ROOM ELECTRICAL PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

A. COORDINATE DISCONNECTION OF EXISTING

EQUIPMENT AND CONNECTION TO NEW

EQUIPMENT WITH MECHANICAL CONTRACTOR.

B. EQUIPMENT CONNECTIONS SHALL BE MADE

ACCORDING TO MANUFACTURER'S

INSTRUCTIONS AND RECOMMENDATIONS.

C. PROVIDE EQUIPMENT CONNECTIONS TO

INCLUDE DISCONNECTING MEANS,

CONDUCTORS, CONDUIT, & OCPD ACCORDING

TO THE EQUIPMENT CONDUCTOR SCHEDULE

ON SHEET-'E-601'.

D. EXISTING CONNECTIONS TO MEDICAL-GAS

ALARM PANEL TO REMAIN FOR USE WITH NEW

EQUIPMENT. SEE EQUIPMENT CONDUCTOR

SCHEDULE NOTES.

E. DURING THE COURSE OF CONSTRUCTION,

TEMPORARY EQUIPMENT (UNITS AND/OR

CYLINDERS) FOR MAINTAINING AIR-VACUUM

OPERATION MAY BE REQUIRED. THE VA WILL

FURNISH AND INSTALL TEMPORARY SYSTEMS;

HOWEVER, COORDINATE TEMPORARY

EQUIPMENT WORK WITH VA PERSONNEL AS

NEEDED.

1 DISCONNECT AND REMOVE EXISTING

ELECTRICAL CONNECTION TO PACKAGED

MEDICAL AIR COMPRESSOR EQUIPMENT.

REMOVE EXISTING DISCONNECTING

MEANS AS WELL AS ASSOCIATED

CONDUITS AND CONDUCTORS, BACK TO

SOURCE OF ORIGIN.

2 DISCONNECT AND REMOVE EXISTING

ELECTRICAL CONNECTION TO PACKAGED

MEDICAL VACUUM EQUIPMENT. REMOVE

EXISTING DISCONNECTING MEANS AS

WELL AS ASSOCIATED CONDUITS AND

CONDUCTORS BACK TO SOURCE OF

ORIGIN.

3 REMOVE THE EXISTING 40A/3P CIRCUIT

BREAKER FEEDING THE EXISTING VACUUM

PLANT EQUIPMENT IN PANEL -'PBYEA',

CIRCUITS-1,3,5.

4 REMOVE THE EXISTING 30A/3P CIRCUIT

BREAKER FEEDING THE EXISTING AIR

COMPRESSOR EQUIPMENT IN

PANEL-'PBYEA', CIRCUITS-19,21,23.

A

D

A

V

E

N F

E

T

A

T

S

R

E

ENI

G

N

E

N o

E

O

MICHAEL J.

JENSEN

ELECTRICAL

A

N

O I

S S

E

F

R

P

L

Exp.

06/30/23

DocuSign Envelope ID: FCFB9153-3C99-48D2-8B65-8D3C2A627379

1/11/2022

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:2

:2

P M

C U s e rs \j w b e e z le y \D o c u m e n ts

\E

-0

-V A

K e rr v ill e -M e d

A ir V a c S y s te m -T

X jw b e e z le y a c g

-p a .c o m

.r v t

E-601

ELECTRICAL SCHEDULES

3 3JWB

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 VETERANS DRIVE, KERRVILLE, TX

28028 JANUARY 11, 2022

100% CONSTRUCTION DOCUMENTS

671-A4-22-17221-040

MJJ

Notes:

Total Est. Demand: 188 A

Total Conn.: 151 A

Total Est. Demand: 156.58 kVA

Total Conn. Load: 125.26 kVA

Spare 125.26 kVA 125.00% 156.58 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 159 A 159 A 140 A

Total Load: 43.23 kVA 43.23 kVA 38.80 kVA

41 2.22 0.00 42

39 2.22 0.00 40

SPS AIR COMP 20 A 3

2.22 0.00

3 40 A SPARE - 'OFF'

35 SPACE -- 1 -- 0.00 36

33 SPACE -- 1 -- 0.00 34

31 SPACE -- 1 -- 0.00

3 70 A SPARE - 'OFF'

29 2.77 -- 1 -- SPACE 30

27 2.77 4.43 28

DOMESTIC WATER BOOSTER PUMP 20 A 3

2.77 4.43

2 30 A SPD CONTROL

23 6.10 5.54 24

21 6.10 5.54 22

MEDICAL AIR 30 A 3

6.10 5.54

3 30 A BAILER

17 3.88 6.65 18

15 3.88 6.65 16

XFMR OLD DRYER 40 A 3

3.88 6.65

3 60 A A/C #5

11 0.00 0.00 12

9 0.00 0.00 10

SPD COMP - 'OFF' 20 A 3

0.00 0.00

3 20 A SPARE - 'OFF'

5 6.10 5.54 6

3 6.10 5.54 4

VACUUM SYSTEM 30 A 3

6.10 5.54

3 40 A <CONNECTED LOAD>

CKT Circuit Description Trip Poles

A B C A B C

Poles Trip Circuit Description CKT

EQUIPMENT BRANCH PANEL

Notes:

Enclosure: NEMA 1 MCB Rating: 225 A

Mounting: RECESSED Wires: 4 Mains Rating: 225 A

Supply From: SWITCHBOARD-'1YEC'...

This is the start of the file's text. The full file is on GovTribe.