671A4-22-172 Med Air Final Design Drawings.pdf
PDF 30 MB Posted
- Attached to
- Z2DA--Project 671A4-22-172 Replace Med Air and Vacuum System Federal contract opportunity
- Solicitation number
- 36C25725B0001
About this file
The document appears to be the 671A4-22-172 Med Air Final Design Drawings related to the federal contract opportunity for Project # 671A4-22-172 Replace Med Air Vacuum System, Solicitation Number 36C25725B0001. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The project requires the removal and replacement of the medical air and vacuum system. The document likely contains the final design drawings for this project. No further details about required products/services, response dates, pricing, or other salient information are provided, as this appears to be a technical drawing document rather than a solicitation or other procurement document.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
PROJECT SITE MAP PROJECT LOCATION MAP
PROJECT IMAGE
/1
/2
:2
:0
A
M C
U s e rs
\n s to lt z \D o c u m e n ts
\A
-0
-V
A K e rr v ill e -M e d
A ir V a c S y s te m -T
X n s to lt z .r v t
G-001
COVER SHEET
1 3AT
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758 JANUARY 11, 2022
100% BID DOCUMENTS
671A4-22-17221-040
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758
VA PROJECT #: 671A4-22-172
TM
DRAWING LIST
GENERAL
G-001 COVER SHEET 1 3
G-100 GENERAL INFORMATION 2 3
GL100 ENLARGED BASEMENT LIFE SAFETY PLAN 3 3
PLUMBING
PG001 PLUMBING GENERAL INFORMATION 1 3
PG400 MECHANICAL ROOM MEDICAL GAS PLANS 2 3
P-601 MEDICAL GAS SCHEDULES AND EXISTING EQUIPMENT PHOTOGRAPHS 3 3
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 3
E-401 ELECTRICAL ENLARGEMENTS - DEMOLITION AND NEW WORK 2 3
E-601 ELECTRICAL SCHEDULES 3 3
KERRVILLE VA
PROJECT AREA
DocuSign Envelope ID: D2FF90DF-8975-4E1C-9A25-4C043CFA3793
1/11/2022 mnorris Snapshot
PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO
PARTICIPATE IN VOLUNTARY STANDARD BODIES.
GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND
STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
• INTERNATIONAL BUILDING CODE (IBC) 2021 (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES
BELOW)
• NFPA 101 LIFE SAFETY CODE 2021 (SEE NOTES BELOW)
• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• NFPA 70 NATIONAL ELECTRICAL CODE 2020
• INTERNATIONAL PLUMBING CODE (IPC) 2018
• ASME CODE FOR PRESSURE PIPING
• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN
STANDARD (PG-18-13)
• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 01010 OF THE
VA MASTER CONSTRUCTION SPECIFICATION.
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION
FEES.
NOTES:
1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY
HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2
:2
A
M C
U s e rs
\n s to lt z \D o c u m e n ts
\A
-0
-V
A K e rr v ill e -M e d
A ir V a c S y s te m -T
X n s to lt z .r v t
G-100
GENERAL INFORMATION
2 3AT
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758 JANUARY 11, 2022
100% BID DOCUMENTS
671A4-22-17221-040
TM
CODE STANDARDS AND EXECUTIVE ORDERS
DocuSign Envelope ID: D2FF90DF-8975-4E1C-9A25-4C043CFA3793
1/11/2022
UP
U P
UP
U P
EMS
EQUIPMENT
ROOM
010A
STORAGE
010B
IDF 010D
010D
CRAWL
SPACE
MAIN
ELEVATOR
LOBBY
ELECT.
CLOSET
MECH.
ROOM
SERVICE
ELEVATOR
LOBBY
MUSEUM
028A
SERVICE
ELEVATOR
NO. 3
PASSENGER
ELEVATOR
NO. 2
PASSENGER
ELEVATOR
NO. 1
E.C.
UP
U P
UP
U P
A
8 9 10 11 12 13 14 15
B
C
D
E
T R
A V
E L D
IS
T
A N
C E
CORRIDOR
PIPE
BASEMENT
MECHANICAL
ROOM
028A
EGRESS PATH
EGRESS PATH TAG
EGRESS PATH TAG - COMMON PATH
EGRESS IDENTIFICATION
AREA OF REFUGE
HAZARDOUS LOCATION
FIRE EXTINGUISHER BRACKET
FIRE EXTINGUISHER CABINET
FIRE BLANKET CABINET
EMERGENCY RESPONSE REFERENCE
CONTROLLED ACCESS - ALWAYS
UNLOCKED IN DIRECTION OF EGRESS
KNOX BOX
DELAYED EGRESS W/ ALARM
CA
DE
KB
XXX
XXX
FEB
FEC
FBC
CAPACITYCLR
EXTERIOR
EXIT
XX" ###
EXIT
IDENTIFICATION
EGRESS CLEAR
WIDTH
EGRESS CAPACITY
EXISTING DEADEND CORRIDOR
EXCEEDING 30' SHALL BE
PERMITTED TO CONTINUE IN USE IF
IT IS UNPRACTICAL AND
UNFEASIBLE TO ALTER FROM.
INCREASE TRAVEL DISTANCE 50FT IF
BUILDING IS SPRINKLED
TOTAL SQUARE
FOOTAGE:
MECHANICAL ROOM 028 3,409 GSF
HEALTHCARE - OUTPATIENT
- 240 SF / PERSON
EGRESS LEGEND
REQUIRED # OF
EXITS
(per NFPA 101, 19.2.4)
- 2 EXITS MIN. PER FLOOR REQ'D
- 2 EXISTING EXITS, NOT BEING
MODIFIED
OCCUPANCY:
EGRESS
REQUIRED:
EXISTING MECHANICAL SPACE. NO
SMOKE MODIFICATION OF THE
SPACE OR EGRESS BEING
PERFORMED
COMMON PATH
OF TRAVEL
(NFPA 101 -
7.13.1(2) )
IN EXISTING BUILDING, COMMON
PATH OF TRAVEL NOT TO EXCEED
150'
TRAVEL
DISTANCE
INCREASE
(per NFPA 101-19.2.6.2.1)
150'-0" MAXIMUM DISTANCE.
DEAD END
CORRIDOR
(NFPA 101-19.2.5.2)
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/1
/2
:2
:2
A
M C
U s e rs
\n s to lt z \D o c u m e n ts
\A
-0
-V
A K e rr v ill e -M e d
A ir V a c S y s te m -T
X n s to lt z .r v t
GL100
ENLARGED BASEMENT LIFE SAFETY
PLAN
3 3AT
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758 JANUARY 11, 2022
100% BID DOCUMENTS
671A4-22-17221-040
TM
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
BASEMENT
EASTWEST
NORTH MECHANICAL
ROOM
Scale: 1/8" = 1'-0"
ENLARGED BASEMENT LIFE SAFETY PLAN
PROPOSED USE:
OWNED BY:
CODE ENFORCEMENT JURISDICTION: FEDERAL
APPLICABLE CODES:
GENERAL CODE INFORMATION:
CONSTRUCTION TYPE:
PRIMARY OCCUPANCY:
SECONDARY OCCUPANCY:
PROJECT NAME:
PROJECT ADDRESS:
OWNER OR AGENT:
FEDERAL
N/A
Relevant Code Goes Here
Relevant Code Goes Here
Relevant Code Goes Here
20XX International Building Code
20XX Plumbing Code
20XX Electrical Code 20XX ADA Code
Relevant Code Goes Here
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758
KERRVILLE VA MEDICAL CENTER
CODE INFORMATION
LIFE SAFETY LEGEND
NORTH
0 4 8 16
A. SEE SHEETS A001 FOR SYMBOLS AND
ABBREVIATIONS.
B. REFER TO MECHANICAL DRAWINGS FOR
INFORMATION
C. REFER TO ELECTRICAL DRAWINGS FOR
INFORMATION CONCERNING POWER, LIGHTING
AND COMMUNICATION SYSTEM(S)
D. CONTRACTOR TO PROVIDE ALL ADDITIONAL
FRAMING NECESSARY FOR ALL OPENINGS AND
SUPPLEMENTAL FRAMING ABOVE PARTITIONS.
E. ALL FIRE RATED ASSEMBLIES SHALL BE
INSTALLED IN STRICT ACCORDANCE WITH TESTED
ASSEMBLIES INDICATED.
F. EXTEND FIRE RATED PARTITIONS, BARRIERS, AND
OTHER SEPARATIONS TO BOTTOM OF
ROOF/FLOOR DECK ABOVE (OR AS DIRECTED BY
UL ASSEMBLY) AND TO EXTERIOR WALL. SEAL
JOINT BETWEEN EDGES OF PARTITION WITH FIRE
RATED SEALANT AND/OR INTUMESCENT
ASSEMBLY.
G. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES
SHALL BE FIRE-SEALED IN ACCORDANCE WITH
APPROVED MANUFACTURER'S DETAIL FOR
LOCATION, TYPE OF CONSTRUCTION,
PENETRATING ITEM AND RATING REQUIRED.
H. SMOKE RESISTANT CONSTRUCTION SHALL MEET
THE REQUIREMENTS OF ALL APPLICABLE CODES.
AREA SHALL BE SEPARATED FROM THE
REMAINDER OF THE BUILDING BE CONSTRUCTION
CAPABLE OF RESISTING THE PASSAGE OF
SMOKE. THE PARTITIONS SHALL EXTEND FROM
THE FLOOR TO THE UNDERSIDE OF THE FLOOR
OR ROOF ASSEMBLY ABOVE. DOORS SHALL BE
SELF OR AUTOMATIC CLOSING. DOORS SHALL
NOT HAVE AIR TRANSFER OPENINGS AND SHALL
NOT BE UNDERCUT IN EXCESS OF CLEARANCE
PERMITTED WITH ACCORDANCE TO NFPA 80.
I. STORAGE OF ANY FLAMMABLE OR COMBUSTIBLE
LIQUIDS IS UNDERSTOOD TO NOT BE WITHIN THE
BUILDING. STORAGE OF ANY MATERIAL IS TO BE
IN COMPLIANCE WITH ALL APPLICABLE CODES
AND AUTHORITIES HAVING JURISDICTION.
J. FACILITY SAFETY PERSON TO VERIFY IF EXISTING
EGRESS FROM MECHANICAL SPACES MEET THE
REQUIREMENTS OF NFPA 101.
OCCUPANCY CLASSIFICATION
(NFPA 2018 101 SECTION 4.1):
HEALTHCARE OCCUPANCY BUILDING, SPRINKLERED
CONSTRUCTION TYPE I (442)
MEANS OF EGRESS:
STAIR ENCLOSURE: 2-HR (NFPA 101.7.1.3.2.1)
MIN. EXIT WIDTH: 32" CLEAR (NFPA 101.2.1.2.2)
OCCUPANT LOAD: (NFPA 101.7.3)
HEALTHCARE INPATIENT: 1:240
STORAGE: 1:300
CAPACITY FACTORS: (NFPA 101.7.3.3):
STAIRS: 0.3
OTHER: 0.2
DocuSign Envelope ID: D2FF90DF-8975-4E1C-9A25-4C043CFA3793
1/11/2022
DCWR
DHW
PIPING SYSTEM
NG NATURAL GAS
ST STORM
PD PUMP DISCHARGE
OFD OVERFLOW STORM DRAIN
GW GREASE WASTE
OW OIL WASTE
SAN SANITARY WASTE
CD CONDENSATE DRAIN
CA COMPRESSED AIR
AW ACID WASTE
N2 NITROGEN
N2O NITROUS OXIDE
MA MEDICAL AIR
O2 OXYGEN
WAGD WASTE ANESTHETIC GAS DISPOSAL
VAC VACUUM
V SANITARY VENT
OV OIL VENT
AV ACID VENT
NPCW NONPOTABLE COLD WATER
DI DE-IONIZED WATER
SCW SOFTENED COLD WATER
DCW DOMESTIC COLD WATER
RO REVERSE OSMOSIS WATER
DOMESTIC CW RECIRCULATION
DOMESTIC HOT WATER
CO2 CARBON DIOXIDE
DHW 140 DOMESTIC HOT WATER (OTHER TEMP)
PG PROPANE GAS
DHWR DOMESTIC HW RECIRCULATION
NG
ST
PD
OFD
GW
OW
SAN
CD
CA
AW
N2
N2O
MA
O2
WAGD
VAC
CO2
PG
V
OV
AV
HW 140
SCW
NPCW
DI
RO
EXISTING
NEW WORK KEYNOTE
DEMOLITION KEYNOTE
NEW BOLD TEXT INDICATES NEW ITEM
ITALICIZED TEXT INDICATES EXISTING ITEM
NEW PLUMBING EQUIPMENT MARK
DETAIL OR SECTION MARK
SHOWN ON DRAWING
DETAIL MODULE NUMBER
CONNECT TO EXISTING
LIMIT OF DEMOLITION
P-###
EXISTING PLUMBING EQUIPMENT MARKP-###
3-WAY CONTROL VALVE
ANGLE GATE VALVE
ANGLE GLOBE VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
CONTROL VALVE
GATE VALVE
GLOBE VALVE
SAFETY RELIEF VALVE
TWO POSITION CONTROL VALVE
BACKFLOW PREVENTER
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLOW ARROW
HOSE BIBB / SILLCOCK
PLUG VALVE
PRESSURE REDUCING VALVE (WATER)
PRESSURE REGULATOR (GAS)
PIPE ANCHOR
PIPE GUIDES
WALL CLEANOUT
SUSPENDED CLEANOUT
WCO
WYE STRAINER
WYE STRAINER W/DRAIN VALVE
FLOOR DRAIN - ROUND OR SQUARE
FLOOR CLEANOUT
PIPE CAP
PIPE TURNING DOWN
PIPE TURNING UP
TEE UP
TEE DOWN
DROP AND RUN
DROP AND TURN
TEE OFF TOP
TEE OFF BOTTOM
CROSS AND RISER
PLAN 90° ELBOW
PIPE TEE
PIPE UNION
FLEXIBLE PIPE CONNECTOR
WATER METER
PUMP
AUTOMATIC AIR VENT
PRESSURE SWITCH
PRESSURE GAUGE
THERMOMETER
FLOW SWITCH
TEMPERATURE SWITCH
OR
CO
PIPE SLOPE ARROW
AV
F
P
T
M
CIRCUIT SETTER
F FAHRENHEIT
FA FROM ABOVE
FB FROM BELOW
FBO FURNISHED BY OTHERS
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE)
CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FU FIXTURE UNITS
G GALLON
GC GENERAL CONTRACTOR
GCO GRADE CLEANOUTS
GD GARBAGE DISPOSAL
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H&CW HOT AND COLD WATER
HB HOSE BIBB (INTERIOR)
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK
(DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
ICW INDUSTRIAL COLD WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
KW KILOWATT
KWHR KILOWATT-HOUR
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH THOUSANDS OF BTU PER HOUR
MC MECHANICAL CONTRACTOR
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SINK BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N2O NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW
PA PASCAL
PC PLUMBING CONTRACTOR
PD PRESSURE DROP
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAUGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH -
ABSOLUTE
PSIG POUNDS PER SQUARE INCH - GAUGE
PTRV PRESSURE TEMPERATURE RELIEF
VALVE
PW POTABLE WATER
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RO REVERSE OSMOSIS
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SCFM STANDARD CUBIC FOOT/MIN
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT SQUARE FOOT
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TDL TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
UPC UNIFORM PLUMBING CODE
V SANITARY VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VTR VENT THROUGH ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAUGE
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
WHD WALL HYDRANT
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
YCO YARD CLEANOUT
YH YARD HYDRANT
A/E ARCHITECT/ENGINEER
AC ABOVE CEILING
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
AFG ABOVE FINISHED GRADE
ASD ADJUSTABLE SPEED DRIVE
ASHRAE AMERICAN SOCIETY HEATING,
REFRIGERATING, AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY PLUMBING
ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BAS BUILDING AUTOMATION SYSTEM
BF BELOW FLOOR
BFP BACKFLOW PREVENTER
BG BELOW GRADE
BH BOOSTER HEATER
BHP BREAK HORSEPOWER
BJ BETWEEN JOISTS
BOP BOTTOM OF PIPE
BSP BLACK STEEL PIPE
BT BATHTUB
BTUH BRITISH THERMAL UNITS PER HOUR
C CELSIUS
CF COMBINATION FIXTURE
CGA COMPRESSED GAS ASSOCIATION
CI CAST IRON
CO CLEANOUT
COND CONDENSATE
CP CONDENSATE PUMP
CS CLINICAL SINK
CV CONTROL VALVE
DA DENTAL COMPRESSED AIR
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DF DRINKING FOUNTAIN
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DV DENTAL VACUUM
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EC ELECTRICAL CONTRACTOR
EL ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL
SYSTEM
EPA ENVIRONMENTAL PROTECTION
AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWS EYEWASH STATION
EX EXISTING
PLUMBING SYMBOLS PLUMBING SYMBOLS
ANNOTATION SYMBOLS
PLUMBING SYMBOLS & ABBREVIATIONS
ANNOTATION ABBREVIATIONS 1. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR REGARDING CONFLICTS BEFORE PROCEEDING WITH
WORK.
2. REMOVED ITEMS REMAIN PROPERTY OF GOVERNMENT UNTIL COR DETERMINES THAT THEY ARE NOT REQUIRED. REMOVE FROM SITE ITEMS NOT BEING RETAINED BY GOVERNMENT OR REINSTALLED AS PART OF THIS WORK.
3. DO NOT DISTURB ITEMS NOT INDICATED FOR DEMOLITION.
4. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION. RELOCATE, REMOVE AND ADJUST
MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO COORDINATE WITH NEW WORK.
5. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING ADJACENT CONDITIONS.
6. COORDINATE DEMOLITION WITH COR. SUBMIT SHUTDOWN PLAN AND SCHEDULE TO COR FOR REVIEW AND APPROVAL.
7. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION. REPAIR UTILITIES AND SERVICES DAMAGED AT
NO ADDITIONAL COST.
8. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE WORK.
9. COORDINATE WITH NEW PLUMBING WORK AND WORK OF OTHER TRADES.
10. TEST EXISTING SYSTEMS FOR OPERATION, ALARMS, AND CAPACITY THEN PROVIDE REPORT TO COR PRIOR TO START OF
DEMOLITION.
11. ISOLATE SUPPLY EQUIPMENT FROM DISTRIBUTION SYSTEMS BY SHUTTING OFF SOURCE VALVES BEFORE BEGINNING
DEMOLITION.
PLUMBING DEMOLITION GENERAL NOTES
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE
PURPOSES INTENDED.
5. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS ARE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT
EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
6. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT
MAINTENANCE, REPAIRS, AND REPLACEMENT.
7. SUPPORT PIPING SYSTEM AS REQUIRED BY APPLICABLE LOCAL, STATE, AND NATIONAL CODES ALONG WITH
SPECIFICATIONS, VA STANDARDS AND MANUFACTURER'S RECOMMENDATIONS.
8. FIRESTOP AND SEAL PIPING PENETRATIONS THROUGH WALLS AND FLOORS EQUAL TO THE RATING OF WALLS AND FLOORS.
9. TEST PLUMBING SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND NATIONAL CODES AND APPLICABLE VA
STANDARDS.
10. COORDINATE PLUMBING PIPING WITH WORK OF OTHER DISCIPLINES.
11. PROVIDE SHUT OFF VALVES AT BRANCH PIPING TO FIXTURES.
12. COORDINATE PLUMBING WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION. COORDINATE ROUTING OF PIPING WITH
EXISTING CONDITIONS.
13. PROVIDE ALL NECESSARY OFFSETS, TEES, ELBOWS, ETC. FOR A COMPLETE AND COORDINATED WORKING PLUMBING SYSTEM. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING
SYSTEMS.
14. CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM REQUIRED SHUTDOWN WITH THE COR 1 WEEK IN ADVANCE.
15. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH PLUMBING WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
16. DO NOT INSTALL PIPES ABOVE TELECOM OR ELECTRICAL EQUIPMENT.
17. PROVIDE RECERTIFICATION OF NEW INSTALLED MEDICAL GAS EQUIPMENT. TEST SYSTEMS FOR OPERATION, ALARMS AND
CAPACITY AND PROVIDE FINAL COMMISSIONING REPORT.
PLUMBING GENERAL NOTES
NOM. SIZE (IN.)
PIPE (FT.)
TUBING (FT.)
5 FT
THRU 3/4
1 1 1/4
1 1/2
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR
LOW TEMPERATURE
PIPE)
PROVIDE HIGH
COMPRESSIVE
STRENGTH
INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD AT
HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH CHANNEL
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
NOTES:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS. SIDE VIEW TRAPEZE HANGER
FOR UP TO 1000 LB. UNIFORM
LOAD
1" MAX.
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8" MIN.)
2 2 1/2 3 4 5 6 8 10 12
11 12 14 16 17 19 22 23
9 10 12 13 14 16 - -
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
MAXIMUM PIPE/TUBING SUPPORT SPACING
1. PROVIDE STICKY MAT ON ENTIRE FLOOR AREA OF SERVICE ELEVATOR LOBBY BETWEEN SERVICE ELEVATOR #3 AND THE
DOOR TO THE MECHANICAL ROOM WHERE NEW EQUIPMENT IS BEING INSTALLED.
2. PROVIDE ZIPPER ENTRY AT ACCESS POINT TO CONSTRUCTION AREA, AT DOOR TO THE MECHANICAL ROOM, IF THE WORK
REQUIRED TO INSTALL THE EQUIPMENT WILL GENERATE ANY DUST.
3. PROVIDE ICRA BARRIERS AS NECESSARY TO PERFORM THE WORK PER THE MECHANICAL DRAWINGS. THE USE OF TEMPORARY, REUSABLE TYPE BARRIERS (EX. STARC WALL SYSTEMS) IS ACCEPTABLE. ENSURE THAT ACCESS THROUGH THE BARRIERS IS PROVIDED IF THE TEMPORARY BARRIERS CUTS OFF ACCESS FROM THE MECHANICAL ROOM OR ANY
OTHER SPACE TO THE MEANS OF EGRESS.
INFECTION CONTROL NOTES
1. PROVIDE RECERTIFICATION OF BUILDING SIDE MEDICAL GAS SYSTEM. TEST SYSTEM FOR OPERATION, ALARMS AND
CAPACITY AND PROVIDE FINAL COMMISSIONING REPORT.
BID ALTERNATE NOTES
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:5
:5
A M
C U s e rs
\n s to lt z \D o c u m e n ts \M
F P
-0
-V A
K e rr v ill e -M e d A ir V a c S y s te m -T
X n s to lt z .r v t
PG001
PLUMBING GENERAL INFORMATION
1 3NAS
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758 JANUARY 11, 2022
100% BID DOCUMENTS
671A4-22-17221-040
RBK
Scale: No Scale
PIPE HANGER DETAIL
DocuSign Envelope ID: 23E13BA4-D0F9-42A1-BCB8-E4C79E81E576
1/11/2022
D A
I D
A I
U P
U P
E.C.
A
11 12 13 14
1" MA
2" MV
M A
MECHANICAL
CRAWL SPACE
UNEXCAVATED
CRAWL SPACE
PIPE BASEMENT
11-AC-1
TO OUTLET
4" MV EXHAUST
M V
E X H A U S T
FROM INTAKE
11-VP-1
TO BUILDING
DISTRIBUTION SYSTEM
FROM BUILDING
DISTRIBUTION SYSTEM
OUTLINE OF EXISTING
HOUSKEEPING PAD
A
11 12 13 14
1 2
2" MV
M A
FROM INTAKEEXHAUST TO
OUTLET
TO BUILDING
DISTRIBUTION SYSTEM
FROM BUILDING
DISTRIBUTION SYSTEM
CRAWL SPACE
UNEXCAVATED
MECHANICAL
PIPE BASEMENT
CRAWL SPACE
EX-11-AC-1
EX-11-VP-1
4" MV EXHAUST
M V
E X H A U S T
1" MA
OUTLINE OF EXISTING
HOUSKEEPING PAD
1.
1.
A
B
C
D
E
F
10 11 12 13 14
CRAWL SPACE
UNEXCAVATED
MECHANICAL
CRAWL SPACE
UNEXCAVATED
UNEXCAVATED
MECH. ROOM
SERVICE
ELEVATOR
LOBBY
ELECT.
CLOSET
MAIN
ELEVATOR
LOBBY
PASSENGER
ELEVATOR
NO. 1
PASSENGER
ELEVATOR
NO. 2
SERVICE
ELEVATOR
NO. 3
4" MV EXHAUST UP
THROUGH ROOF
SERVICE ELEVATOR FOR
ACCESS WITH EQUIPMENT
STAIRWELL EXIT TO
OUTSIDE AT FIRST
FLOOR LEVEL
Engineers Architects
# NEW WORK KEY NOTES:
# DEMOLITION KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/7
/2
:5
:0
A M
C U s e rs
\n s to lt z \D o c u m e n ts \M
F P
-0
-V A
K e rr v ill e -M e d A ir V a c S y s te m -T
X n s to lt z .r v t
PG400
MECHANICAL ROOM MEDICAL GAS
PLANS
2 3NAS
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758 JANUARY 11, 2022
100% BID DOCUMENTS
671A4-22-17221-040
RBK
N
KEY PLAN
SCALE: NO SCALE
BASEMENT
EASTWEST
NORTH MECHANICAL
ROOM
Scale: 1/4" = 1'-0"
BASEMENT MECHANICAL ROOM MEDICAL GAS PLAN
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
BASEMENT MECHANICAL ROOM MEDICAL GAS DEMOLITION PLAN
NORTH
0 2 4 8
1 NEW MEDICAL AIR COMPRESSOR SYSTEM.
CONNECT TO EXISTING SUPPLY PIPING AND AIR
INTAKE.
2 NEW MEDICAL VACUUM PUMP. CONNECT TO
EXISTING SUPPLY PIPING AND VACUUM EXHAUST.
3 RECONNECT NEW EQUIPMENT TO EXISTING
MASTER ALARM AT JUNCTION BOX.
4 PROVIDE SUPPORT FOR NEW AND EXISTING
MEDGAS PIPING ASSOCIATED WITH AIR
COMPRESSOR AND VACUUM PUMP IN MECHANICAL
ROOM. SUPPORT FOR THIS PIPING SHALL CONFORM
WITH SPECIFICATIONS.
5 PROVIDE STICKY MAT AT ENTRANCE TO
CONSTRUCTION AREA PER FACILITY ICRA
REQUIREMENTS.
1 EXISTING MEDICAL AIR COMPRESSORS, RECEIVER,
AND DESICCANT COOLER TO BE REMOVED.
DEMOLISH ASSOCIATED PIPING TO POINTS
INDICATED.
2 EXISTING MEDICAL VACUUM PUMP TO BE REMOVED.
DEMOLISH ASSOCIATED PIPING TO POINTS
INDICATED.
3 REMOVE EXISTING DEW POINT SENSOR ON MEDICAL
AIR SUPPLY MAIN AND TURN OVER TO VA.
A. COORDINATE ANY LOSS OF MEDICAL GAS
SERVICE WITH COR AT LEAST 1 WEEK IN
ADVANCE. PROVISION OF TEMPORARY MEDICAL
GAS SUPPLY EQUIPMENT DURING EQUIPMENT
CHANGEOVER IS NOT IN CONTRACT.
B. PROVIDE STICKY MAT ON ENTIRE FLOOR AREA
OF SERVICE ELEVATOR LOBBY BETWEEN
SERVICE ELEVATOR #3 AND THE DOOR TO THE
MECHANICAL ROOM WHERE NEW EQUIPMENT IS
BEING INSTALLED.
C. PROVIDE ZIPPER ENTRY AT ACCESS POINT TO
CONSTRUCTION AREA, AT DOOR TO THE
MECHANICAL ROOM, IF THE WORK REQUIRED TO
INSTALL THE EQUIPMENT WILL GENERATE ANY
DUST.
D. PROVIDE ICRA BARRIERS AS NECESSARY TO
PERFORM THE WORK PER THE MECHANICAL
DRAWINGS. THE USE OF TEMPORARY, REUSABLE
TYPE BARRIERS (EX. STARC WALL SYSTEMS) IS
ACCEPTABLE. ENSURE THAT ACCESS THROUGH
THE BARRIERS IS PROVIDED IF THE TEMPORARY
BARRIERS CUTS OFF ACCESS FROM THE
MECHANICAL ROOM OR ANY OTHER SPACE TO
THE MEANS OF EGRESS.
E. CONTRACTOR IS TO PROVIDE FLOORING
PROTECTION FROM ENTRY DOOR TO SERVICE
ELEVATOR OF THE FIRST FLOOR AND FROM THE
SERVICE ELEVATOR TO THE MECHANICAL ROOM
DOOR AT THE BASEMENT LEVEL. PLYWOOD
FLOOR COVERING IS SUGGESTED, BUT THE
CONTRACTOR CAN UTILIZE WHATEVER FLOOR
PROTECTION MATERIAL THEY FEELS WILL
ACCOMPLISH THE JOB. CONTRACTOR SHALL BE
RESPONSIBLE FOR AND DAMAGE TO THE
FLOORING, ADJACENT SURFACES, ETC. CAUSED
BY THE PERFORMANCE OF THE CONTRACTOR’S
WORK OR BY THEIR PERSONNEL.
F. FOR PHOTOGRAPHS OF EXISTING CONDITIONS
SEE PG601.
Scale: 1/8" = 1'-0"
BASEMENT MECHANICAL ROOM INFECTION CONTROL PLAN
NORTH
0 4 8 16
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:5
:0
A M
C U s e rs
\n s to lt z \D o c u m e n ts \M
F P
-0
-V A
K e rr v ill e -M e d A ir V a c S y s te m -T
X n s to lt z .r v t
P-601
MEDICAL GAS SCHEDULES AND
EXISTING EQUIPMENT PHOTOGRAPHS
3 3NAS
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 MEMORIAL BLVD.
KERRVILLE, TX 78028-5758 JANUARY 11, 2022
100% BID DOCUMENTS
671A4-22-17221-040
RBK
Scale: No Scale
EXISTING AIR AND VACUUM SYSTEMS
Scale: No Scale
EXISTING DESSICANT SYSTEM
Scale: No Scale
MEDICAL AIR COMPRESSOR VIEW 1
Scale: No Scale
MEDICAL AIR COMPRESSOR VIEW 2
Scale: No Scale
MEDICAL AIR COMPRESSOR VIEW 3
Scale: No Scale
MEDICAL AIR INTAKE
Scale: No Scale
VACUUM PUMPS
Scale: No Scale
VACUUM TANK AND CONTROL PANEL
11-VP-1 BASEMENT... BUILDING 11 MEDICAL VACUUM DUPLEX DRY CLAW 200 [ 760 ] 19 [ 64 ] 65 [ 31 ] 2 7.5 5.6 [ 3 ] 460 21 2190 1, 2, 3, 4, 5, 6, 7, 8, 9
GAL [L] in Hg [kPa] SCFM STANDARD [L/s] HP [Kw]
NO. PUMPS
POWER EACH
PHASE VOLT FLA
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR
SERVICE
TYPE UNIT
RECEIVER SIZE VACUUM PRESSURE
CFM DELIVERY @ VACUUM
PRESSURE (SI)
ELECTRIC POWER
WEIGHT
(LBS)
REMARKS
VACUUM PUMP SCHEDULE
11-AC-1
BASEMENT
MECHANICAL
BUILDING 11 MEDICAL AIR
DUPLEX OIL-LESS
SCROLL
24 [ 94 ] 120 [ 830 ] 200 [ 760 ] 36X84 [900X2100] 2 7.5 [ 6 ] 3 460 22 2330 1, 2, 3, 4, 5, 6, 7, 8, 9
CFM [L/s] PSIG [kPa] GAL [L] IN [mm] HP [kW]
NO. MOTORS
POWER EA.
PHASE VOLT FLA
MARK LOCATION
AREA AND/OR
BLDG SERVED
SYSTEM AND/OR
SERVICE
TYPE
NFPA AIRFLOW CAPACITY
NFPA DISCHARGE
PRESSURE
RECEIVER SIZE
RECEIVER DIMENSIONS, DIA
X LENGTH
ELECTRIC POWER [60 Hz]
WEIGHT
(LBS)
REMARKS
AIR COMPRESSOR SCHEDULE
NOTES:
1. CAPACITIES ARE AT SITE CONDITION.
2. BASIS OF DESIGN IS AMICO MODEL V-CCD-D-200P-SS-N-075-MS.
3. MODULAR UNITS THAT CAN BE DISASSEMBLED AND REASSEMBLED ON SITE.
4. PROVIDE ALL ACCESSORIES FOR FULLY FUNCTIONAL SYSTEM.
5. PROVIDE ALL ALARMS PER NFPA AND CONNECT TO EXISTING ALARM SYSTEM.
6. PROVIDE DRAIN PIPING WITH VALVE AND MAIN ISOLATION VALVE FOR THE UNIT.
7. UNIT SHALL OPERATE BETWEEN 19" Hg AND 25" Hg WITH CAPACITY AT LISTED SCFM.
8. LISTED CAPACITY IS WITH ONE PUMP IN OPERATION.
9. PROVIDE GAUGES, SENSORS, AND SAFETY DEVICES.
NOTES:
1. CAPACITIES ARE AT SITE CONDITION.
2. BASIS OF DESIGN IS AMICO MODEL A-SCD-D-200P-SS-N-075-TS
3. MODULAR UNIT THAT CAN BE DISASSEMBLED AND REASSEMBLED ON SITE.
4. PROVIDE ALL ACCESSORIES FOR FULLY FUNCTIONAL SYSTEM.
5. PROVIDE ALL ALARMS PER NFPA AND CONNECT TO EXISTING ALARM SYSTEM.
6. PROVIDE DRAIN PIPING WITH ISOLATION VALVE AND MAIN ISOLATION VALVE FOR THE UNIT.
7. PROVIDE DESSICANT AIR DRYER WITH ALL ACCESSORIES.
8. LISTED CAPACITY IS WITH ONE PUMP IN OPERATION.
9. PROVIDE GAUGES, SENSORS, AND SAFETY DEVICES.
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK
AREA, FOR THE STARTING POINT OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED THE
RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP CALCULATIONS
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18"2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:2
:2
P M
C U s e rs \j w b e e z le y \D o c u m e n ts
\E
-0
-V A
K e rr v ill e -M e d
A ir V a c S y s te m -T
X jw b e e z le y a c g
-p a .c o m
.r v t
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 3JWB
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 VETERANS DRIVE, KERRVILLE, TX
28028 JANUARY 11, 2022
100% CONSTRUCTION DOCUMENTS
671-A4-22-17221-040
MJJ
ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES
ELECTRICAL GENERAL NOTES
ELECTRICAL SYMBOL LEGENDLIGHTING SYMBOL LEGEND
A
D
A
V
E
N F
E
T
A
T
S
R
E
ENI
G
N
E
N o
E
O
MICHAEL J.
JENSEN
ELECTRICAL
A
N
O I
S S
E
F
R
P
L
Exp.
06/30/23
DocuSign Envelope ID: FCFB9153-3C99-48D2-8B65-8D3C2A627379
1/11/2022
11 12 13 14
A
MECHANICAL
EXISTING
PANEL 'PBYEA'
EX-11-AC-1 EX-11-VP-11 2
CRAWL SPACE
UNEXCAVATED
CRAWL SPACE
PIPE BASEMENT
3 4
11 12 13 14
A
MECHANICAL
11-VP-1
11-AC-11
CRAWL SPACE
UNEXCAVATED
CRAWL SPACE
PIPE BASEMENT
EXISTING
PANEL 'PBYEA'
3 4
Engineers Architects
# NEW WORK KEY NOTES:
# DEMOLITION KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/7
/2
:2
:2
P M
C U s e rs \j w b e e z le y \D o c u m e n ts
\E
-0
-V A
K e rr v ill e -M e d
A ir V a c S y s te m -T
X jw b e e z le y a c g
-p a .c o m
.r v t
E-401
ELECTRICAL ENLARGEMENTS -
DEMOLITION AND NEW WORK
2 3JWB
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 VETERANS DRIVE, KERRVILLE, TX
28028 JANUARY 11, 2022
100% CONSTRUCTION DOCUMENTS
671-A4-22-17221-040
MJJ
1 CONNECT NEW PACKAGED MEDICAL AIR
COMPRESSOR EQUIPMENT. SEE
MECHANICAL EQUIPMENT CONDUCTOR
SCHEDULE AND ASSOCIATED PANEL
SCHEDULE.
2 CONNECT NEW PACKAGED MEDICAL
VACUUM PUMP EQUIPMENT. SEE
MECHANICAL EQUIPMENT CONDUCTOR
SCHEDULE AND ASSOCIATED PANEL
SCHEDULE.
3 INSTALL A NEW 30A/3P CIRCUIT BREAKER
TO FEED THE NEW VACUUM PLANT
EQUIPMENT IN PANEL-'PBYEA',
CIRUITS-1,3,5.
4 INSTALL A NEW 30A/3P CIRCUIT BREAKER
TO FEED THE NEW AIR COMPRESSOR
EQUIPMENT IN PANEL-'PBYEA',
CIRCUITS-19,21,23.
N
KEY PLAN
SCALE: NO SCALE
BASEMENT
EASTWEST
NORTH MECHANICAL
ROOM
Scale: 1/4" = 1'-0"
BASEMENT MECHANICAL ROOM ELECTRICAL DEMOLITION PLAN
Scale: 1/4" = 1'-0"
BASEMENT MECHANICAL ROOM ELECTRICAL PLAN
NORTH
0 4 8 16
NORTH
0 4 8 16
A. COORDINATE DISCONNECTION OF EXISTING
EQUIPMENT AND CONNECTION TO NEW
EQUIPMENT WITH MECHANICAL CONTRACTOR.
B. EQUIPMENT CONNECTIONS SHALL BE MADE
ACCORDING TO MANUFACTURER'S
INSTRUCTIONS AND RECOMMENDATIONS.
C. PROVIDE EQUIPMENT CONNECTIONS TO
INCLUDE DISCONNECTING MEANS,
CONDUCTORS, CONDUIT, & OCPD ACCORDING
TO THE EQUIPMENT CONDUCTOR SCHEDULE
ON SHEET-'E-601'.
D. EXISTING CONNECTIONS TO MEDICAL-GAS
ALARM PANEL TO REMAIN FOR USE WITH NEW
EQUIPMENT. SEE EQUIPMENT CONDUCTOR
SCHEDULE NOTES.
E. DURING THE COURSE OF CONSTRUCTION,
TEMPORARY EQUIPMENT (UNITS AND/OR
CYLINDERS) FOR MAINTAINING AIR-VACUUM
OPERATION MAY BE REQUIRED. THE VA WILL
FURNISH AND INSTALL TEMPORARY SYSTEMS;
HOWEVER, COORDINATE TEMPORARY
EQUIPMENT WORK WITH VA PERSONNEL AS
NEEDED.
1 DISCONNECT AND REMOVE EXISTING
ELECTRICAL CONNECTION TO PACKAGED
MEDICAL AIR COMPRESSOR EQUIPMENT.
REMOVE EXISTING DISCONNECTING
MEANS AS WELL AS ASSOCIATED
CONDUITS AND CONDUCTORS, BACK TO
SOURCE OF ORIGIN.
2 DISCONNECT AND REMOVE EXISTING
ELECTRICAL CONNECTION TO PACKAGED
MEDICAL VACUUM EQUIPMENT. REMOVE
EXISTING DISCONNECTING MEANS AS
WELL AS ASSOCIATED CONDUITS AND
CONDUCTORS BACK TO SOURCE OF
ORIGIN.
3 REMOVE THE EXISTING 40A/3P CIRCUIT
BREAKER FEEDING THE EXISTING VACUUM
PLANT EQUIPMENT IN PANEL -'PBYEA',
CIRCUITS-1,3,5.
4 REMOVE THE EXISTING 30A/3P CIRCUIT
BREAKER FEEDING THE EXISTING AIR
COMPRESSOR EQUIPMENT IN
PANEL-'PBYEA', CIRCUITS-19,21,23.
A
D
A
V
E
N F
E
T
A
T
S
R
E
ENI
G
N
E
N o
E
O
MICHAEL J.
JENSEN
ELECTRICAL
A
N
O I
S S
E
F
R
P
L
Exp.
06/30/23
DocuSign Envelope ID: FCFB9153-3C99-48D2-8B65-8D3C2A627379
1/11/2022
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:2
:2
P M
C U s e rs \j w b e e z le y \D o c u m e n ts
\E
-0
-V A
K e rr v ill e -M e d
A ir V a c S y s te m -T
X jw b e e z le y a c g
-p a .c o m
.r v t
E-601
ELECTRICAL SCHEDULES
3 3JWB
REMOVE/REPLACE MEDICAL
AIR VACUUM SYSTEM
KERRVILLE VA MEDICAL CENTER
3600 VETERANS DRIVE, KERRVILLE, TX
28028 JANUARY 11, 2022
100% CONSTRUCTION DOCUMENTS
671-A4-22-17221-040
MJJ
Notes:
Total Est. Demand: 188 A
Total Conn.: 151 A
Total Est. Demand: 156.58 kVA
Total Conn. Load: 125.26 kVA
Spare 125.26 kVA 125.00% 156.58 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 159 A 159 A 140 A
Total Load: 43.23 kVA 43.23 kVA 38.80 kVA
41 2.22 0.00 42
39 2.22 0.00 40
SPS AIR COMP 20 A 3
2.22 0.00
3 40 A SPARE - 'OFF'
35 SPACE -- 1 -- 0.00 36
33 SPACE -- 1 -- 0.00 34
31 SPACE -- 1 -- 0.00
3 70 A SPARE - 'OFF'
29 2.77 -- 1 -- SPACE 30
27 2.77 4.43 28
DOMESTIC WATER BOOSTER PUMP 20 A 3
2.77 4.43
2 30 A SPD CONTROL
23 6.10 5.54 24
21 6.10 5.54 22
MEDICAL AIR 30 A 3
6.10 5.54
3 30 A BAILER
17 3.88 6.65 18
15 3.88 6.65 16
XFMR OLD DRYER 40 A 3
3.88 6.65
3 60 A A/C #5
11 0.00 0.00 12
9 0.00 0.00 10
SPD COMP - 'OFF' 20 A 3
0.00 0.00
3 20 A SPARE - 'OFF'
5 6.10 5.54 6
3 6.10 5.54 4
VACUUM SYSTEM 30 A 3
6.10 5.54
3 40 A <CONNECTED LOAD>
CKT Circuit Description Trip Poles
A B C A B C
Poles Trip Circuit Description CKT
EQUIPMENT BRANCH PANEL
Notes:
Enclosure: NEMA 1 MCB Rating: 225 A
Mounting: RECESSED Wires: 4 Mains Rating: 225 A
Supply From: SWITCHBOARD-'1YEC'...