671A4-22-172 Med Air Final Design Drawings - Revs No.1 - 01-10-2025.pdf

PDF 3 MB Posted

Attached to
Z2DA--Project 671A4-22-172 Replace Med Air and Vacuum System
Solicitation number
36C25725B0001
Issued by

About this file

This is a set of construction drawings for a project to remove and replace the medical air vacuum system at the Kerrville VA Medical Center in Kerrville, TX (Project #671A4-22-172). The drawings detail the installation of new medical air compressors and vacuum pumps in the basement mechanical room of Building 11, including demolition of existing equipment and installation of new equipment with associated electrical, plumbing and medical gas connections.

The drawings include architectural, plumbing, and electrical plans showing equipment locations, piping routes, and electrical connections. Key specifications include a new duplex oil-less scroll medical air compressor system (24 CFM at 120 PSI) with 200 gallon receiver tank and a new duplex dry claw medical vacuum pump system (65 SCFM at 19" Hg) with 200 gallon receiver. The electrical work involves connecting the new equipment to Panel PBYEA with 30A/3P circuit breakers. The project requires infection control measures including sticky mats, zipper entries, and ICRA barriers during construction. The facility is fully sprinklered and the drawings are marked as 100% bid documents dated January 11, 2022 with revisions dated January 10, 2025.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DocuSign Envelope ID: D2FF90DF-8975-4E1C-9A25-4C043CFA3793

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758

VA PROJECT #: 671A4-22-172

PROJECT SITE MAP

PROJECT IMAGE

PROJECT AREA PROJECT LOCATION MAP DRAWING LIST

GENERAL

G-001 COVER SHEET

G-100 GENERAL INFORMATION

GL100 ENLARGED BASEMENT LIFE SAFETY PLAN

PLUMBING

PG001 PLUMBING GENERAL INFORMATION

PG400 MECHANICAL ROOM MEDICAL GAS PLANS

P-601 MEDICAL GAS SCHEDULES AND EXISTING EQUIPMENT PHOTOGRAPHS

ELECTRICAL

E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS

E-401 ELECTRICAL ENLARGEMENTS - DEMOLITION AND NEW WORK

E-601 ELECTRICAL SCHEDULES

FULLY SPRINKLERED

100% BID DOCUMENTS

CONSULTANTS: PROJECT MANAGER

Headquarters:

ACG Project Number 21-040 Office of

Construction

Drawing Title

COVER SHEET

Project Title

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

VA PROJECT NUMBER

671A4-22-172

Building Number

Apogee Consulting Group, P.A. and Facilities # 11

Engineers Architects

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

Management

U.S. Department

Location

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

Approved

Date

Checked

Drawn

Drawing Number

G-001 # Revisions: Date

1/11/2022 © COPYRIGHT Apogee Consulting Group, P.A. of Veterans Affairs KERRVILLE, TX 78028-5758 JANUARY 11, 2022 TM AT Dwg

VA FORM 08-6231

KERRVILLE VA

/1

/2

:2

:0

A

M

C U s e rs

\n s to ltz \D o c u m e n ts

\A -0

-V

A K e rr v ill e -M e d A ir V a c S y s te m -T

X n s to ltz .r v t

1 3

2 3

3 3

1 3

1 3 http://www.acg-pa.com/

VA FORM 08-6231 1

/1 /2

:2

:2

U s e rs

\n s to ltz \D o c u m e n ts

\A -0

-V

A K e rr v ill e -M e d A ir V a c S y s te m -T

X n s to ltz .r v t

PROJECT MANAGER

ACG Project Number

21-040

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511

Engineers Architects www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A.

Approved Drawing Number

G-100 Dwg 2 of 3

Date Checked

JANUARY 11, 2022 TM

AT

CODE STANDARDS AND EXECUTIVE ORDERS

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO

PARTICIPATE IN VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND

STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• INTERNATIONAL BUILDING CODE (IBC) 2021 (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES

BELOW)

• NFPA 101 LIFE SAFETY CODE 2021 (SEE NOTES BELOW)

• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• NFPA 70 NATIONAL ELECTRICAL CODE 2020

• INTERNATIONAL PLUMBING CODE (IPC) 2018

• ASME CODE FOR PRESSURE PIPING

• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN

STANDARD (PG-18-13)

• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 01010 OF THE

VA MASTER CONSTRUCTION SPECIFICATION.

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION

FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY

HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

Drawing Title Project Title VA PROJECT NUMBER

CONSULTANTS: Office of GENERAL INFORMATION REMOVE/REPLACE MEDICAL 671A4-22-172

Construction AIR VACUUM SYSTEM Building Number and Facilities # 11 Management Location

KERRVILLE VA MEDICAL CENTER

U.S. Department 3600 MEMORIAL BLVD.

1/11/2022 of Veterans Affairs KERRVILLE, TX 78028-5758

# Revisions: Date http://www.cfm.va.gov/TIL/)

A. SEE SHEETS A001 FOR SYMBOLS AND

ABBREVIATIONS.

LIFE SAFETY LEGEND

SHEET NOTES:

EGRESS PATH

8 9 10 11 12 13 14 15

XXX

XXX

EXIT

IDENTIFICATION

EGRESS CLEAR

WIDTH

EGRESS PATH TAG

EGRESS PATH TAG - COMMON PATH

EGRESS IDENTIFICATION

EGRESS CAPACITY

AREA OF REFUGE

B. REFER TO MECHANICAL DRAWINGS FOR

INFORMATION

C. REFER TO ELECTRICAL DRAWINGS FOR

INFORMATION CONCERNING POWER, LIGHTING

AND COMMUNICATION SYSTEM(S)

D. CONTRACTOR TO PROVIDE ALL ADDITIONAL

FRAMING NECESSARY FOR ALL OPENINGS AND

SUPPLEMENTAL FRAMING ABOVE PARTITIONS.

E. ALL FIRE RATED ASSEMBLIES SHALL BE

INSTALLED IN STRICT ACCORDANCE WITH TESTED

ASSEMBLIES INDICATED.

F. EXTEND FIRE RATED PARTITIONS, BARRIERS, AND

OTHER SEPARATIONS TO BOTTOM OF

UP

FEB

FEC

FBC

CA

KB

DE

HAZARDOUS LOCATION

FIRE EXTINGUISHER BRACKET

FIRE EXTINGUISHER CABINET

FIRE BLANKET CABINET

EMERGENCY RESPONSE REFERENCE

CONTROLLED ACCESS - ALWAYS

UNLOCKED IN DIRECTION OF EGRESS

KNOX BOX

DELAYED EGRESS W/ ALARM

ROOF/FLOOR DECK ABOVE (OR AS DIRECTED BY

UL ASSEMBLY) AND TO EXTERIOR WALL. SEAL

JOINT BETWEEN EDGES OF PARTITION WITH FIRE

RATED SEALANT AND/OR INTUMESCENT

ASSEMBLY.

G. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES

SHALL BE FIRE-SEALED IN ACCORDANCE WITH

APPROVED MANUFACTURER'S DETAIL FOR

LOCATION, TYPE OF CONSTRUCTION,

PENETRATING ITEM AND RATING REQUIRED.

H. SMOKE RESISTANT CONSTRUCTION SHALL MEET

THE REQUIREMENTS OF ALL APPLICABLE CODES.

AREA SHALL BE SEPARATED FROM THE

REMAINDER OF THE BUILDING BE CONSTRUCTION

CAPABLE OF RESISTING THE PASSAGE OF

SMOKE. THE PARTITIONS SHALL EXTEND FROM

THE FLOOR TO THE UNDERSIDE OF THE FLOOR

OR ROOF ASSEMBLY ABOVE. DOORS SHALL BE

SELF OR AUTOMATIC CLOSING. DOORS SHALL

EGRESS LEGEND NOT HAVE AIR TRANSFER OPENINGS AND SHALL

NOT BE UNDERCUT IN EXCESS OF CLEARANCE

PERMITTED WITH ACCORDANCE TO NFPA 80.

MECHANICAL

ROOM

028A

PIPE

BASEMENT

TOTAL SQUARE

FOOTAGE:

OCCUPANCY:

EGRESS

REQUIRED:

TRAVEL

DISTANCE

MECHANICAL ROOM 028 3,409 GSF

HEALTHCARE - OUTPATIENT

- 240 SF / PERSON

EXISTING MECHANICAL SPACE. NO

SMOKE MODIFICATION OF THE

SPACE OR EGRESS BEING

PERFORMED

150'-0" MAXIMUM DISTANCE.

I. STORAGE OF ANY FLAMMABLE OR COMBUSTIBLE

LIQUIDS IS UNDERSTOOD TO NOT BE WITHIN THE

BUILDING. STORAGE OF ANY MATERIAL IS TO BE

IN COMPLIANCE WITH ALL APPLICABLE CODES

AND AUTHORITIES HAVING JURISDICTION.

J. FACILITY SAFETY PERSON TO VERIFY IF EXISTING

EGRESS FROM MECHANICAL SPACES MEET THE

REQUIREMENTS OF NFPA 101.

CODE INFORMATION

PROJECT NAME: REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

PROJECT ADDRESS: KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758

OWNER OR AGENT: KERRVILLE VA MEDICAL CENTER

PROPOSED USE: Relevant Code Goes Here

INCREASE

(per NFPA 101-19.2.6.2.1)

COMMON PATH

OF TRAVEL

(NFPA 101 -

7.13.1(2) )

REQUIRED # OF

A EXITS

(per NFPA 101, 19.2.4)

DEAD END

CORRIDOR

(NFPA 101-19.2.5.2)

INCREASE TRAVEL DISTANCE 50FT IF

BUILDING IS SPRINKLED

IN EXISTING BUILDING, COMMON

PATH OF TRAVEL NOT TO EXCEED

150'

- 2 EXITS MIN. PER FLOOR REQ'D

- 2 EXISTING EXITS, NOT BEING

MODIFIED

EXISTING DEADEND CORRIDOR

EXCEEDING 30' SHALL BE

PERMITTED TO CONTINUE IN USE IF

IT IS UNPRACTICAL AND

UNFEASIBLE TO ALTER FROM.

OWNED BY: FEDERAL

CODE ENFORCEMENT JURISDICTION: FEDERAL

APPLICABLE CODES:

20XX International Building Code 20XX Electrical Code 20XX ADA Code 20XX Plumbing Code Relevant Code Goes Here

GENERAL CODE INFORMATION:

CONSTRUCTION TYPE:Relevant Code Goes Here

PRIMARY OCCUPANCY: Relevant Code Goes Here

SECONDARY OCCUPANCY: N/A

OCCUPANCY CLASSIFICATION

(NFPA 2018 101 SECTION 4.1):

HEALTHCARE OCCUPANCY BUILDING, SPRINKLERED

CONSTRUCTION TYPE I (442)

B

MECH.

MEANS OF EGRESS:

STAIR ENCLOSURE: 2-HR (NFPA 101.7.1.3.2.1)

MIN. EXIT WIDTH: 32" CLEAR (NFPA 101.2.1.2.2)

OCCUPANT LOAD: (NFPA 101.7.3)

HEALTHCARE INPATIENT: 1:240

STORAGE: 1:300

CAPACITY FACTORS: (NFPA 101.7.3.3):

STAIRS: 0.3

OTHER: 0.2

SERVICE

ELEVATOR

LOBBY

ELECT.

CLOSET

SERVICE

ELEVATOR

NO. 3

KEY PLAN

SCALE: NO SCALE

D

EMS

EQUIPMENT

010A

STORAGE

010B

IDF 010D

010D

CRAWL

SPACE

E.C.

MAIN

LOBBY

PASSEN GER

NO. 2

PASSENGER

NO. 1

MUSEUM

028A

WEST

NORTH

AREA OF WORK

EAST

E

CORRIDOR BASEMENT

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

ENLARGED BASEMENT LIFE SAFETY PLAN

0 4 8 16

S S S S

SMOKE RESISTIVE HAZARDOUS AREA

Scale: 1/8" = 1'-0" FULLY SPRINKLERED

100% BID DOCUMENTS

CONSULTANTS: PROJECT MANAGER

Headquarters:

ACG Project Number 21-040 Office of

Construction

Drawing Title

ENLARGED BASEMENT LIFE SAFETY

PLAN

Project Title

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

VA PROJECT NUMBER

671A4-22-172

Apogee Consulting Group, P.A. and Facilities # 11

Engineers Architects

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511

Management

U.S. Department

Location

KERRVILLE VA MEDICAL CENTER

Date Checked Drawn

GL100

# Revisions:

1/11/2022 www.acg-pa.com 919-858-7420 of Veterans Affairs KERRVILLE, TX 78028-5758 JANUARY 11, 2022 TM AT Dwg

/1

/2

:2

:2

U s e rs

\n s to ltz \D o c u m e n ts

\A -0

-V

A K e rr v ill e -M e d A ir V a c S y s te m -T

X n s to ltz .r v t

U P

T R

A V

E L D

IS

T

A N

C E

EXTERIOR

EXIT

CLR CAPACITY

XX" ###

WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.

INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.

OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.

PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE

PURPOSES INTENDED.

EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS ARE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT

EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.

INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT

MAINTENANCE, REPAIRS, AND REPLACEMENT.

SUPPORT PIPING SYSTEM AS REQUIRED BY APPLICABLE LOCAL, STATE, AND NATIONAL CODES ALONG WITH

SPECIFICATIONS, VA STANDARDS AND MANUFACTURER'S RECOMMENDATIONS.

FIRESTOP AND SEAL PIPING PENETRATIONS THROUGH WALLS AND FLOORS EQUAL TO THE RATING OF WALLS AND FLOORS.

TEST PLUMBING SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND NATIONAL CODES AND APPLICABLE VA

STANDARDS.

COORDINATE PLUMBING PIPING WITH WORK OF OTHER DISCIPLINES.

PROVIDE SHUT OFF VALVES AT BRANCH PIPING TO FIXTURES.

COORDINATE PLUMBING WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION. COORDINATE ROUTING OF PIPING WITH

EXISTING CONDITIONS.

PROVIDE ALL NECESSARY OFFSETS, TEES, ELBOWS, ETC. FOR A COMPLETE AND COORDINATED WORKING PLUMBING

SYSTEM. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING

SYSTEMS.

CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM REQUIRED SHUTDOWN WITH THE COR 1 WEEK IN ADVANCE.

PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH PLUMBING WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.

DO NOT INSTALL PIPES ABOVE TELECOM OR ELECTRICAL EQUIPMENT.

PROVIDE RECERTIFICATION OF NEW INSTALLED MEDICAL GAS EQUIPMENT. TEST SYSTEMS FOR OPERATION, ALARMS AND

CAPACITY AND PROVIDE FINAL COMMISSIONING REPORT.

PIPE SLOPE ARROW

3-WAY CONTROL VALVE

PRESSURE REGULATOR (GAS)

HOSE BIBB / SILLCOCK

PRESSURE GAUGE

F FLOW SWITCH

PUMP

WYE STRAINER W/DRAIN VALVE

M WATER METER

FLOW ARROW

CIRCUIT SETTER

BACKFLOW PREVENTER

THERMOMETER

WYE STRAINER

OR FLOOR DRAIN - ROUND OR SQUARE

PIPE ANCHOR

PIPE GUIDES

HANGER ROD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR

LOW TEMPERATURE

PIPE)

PROVIDE HIGH

COMPRESSIVE

STRENGTH

INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD 1

INSULATION SHIELD AT

HANGER

WELD

SADDLE

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE

SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE

SPECIFICATIONS

PROVIDE INSULATION SHIELD &

INSERT FOR ALL PIPING (8" MIN.)

1/2" DIA. HANGER RODS WITH 36"

MAX. SPACING ON EACH CHANNEL

NOTES:

SEE SPECIFICATIONS FOR

DETAILED HANGER

1" MAX.

BAND

1-5/8" 12 GAUGE CHANNEL

OR 2" x 2" x 1/4" ANGLE

REQUIREMENTS. SIDE VIEW TRAPEZE HANGER

FOR UP TO 1000 LB. UNIFORM

LOAD

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOM. SIZE (IN.) THRU 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8 10 12

PIPE (FT.) 7 7 7 9 10 11 12 14 16 17 19 22 23

TUBING (FT.) 5 FT 6 7 8 8 9 10 12 13 14 16 - -

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE

PIPE HANGER DETAIL

Scale: No Scale

1 Revision #1

01/10/2025

PG001

Date Dwg 1 of 3

ANGLE GATE VALVE

SAFETY RELIEF VALVE

TWO POSITION CONTROL VALVE

AV

AUTOMATIC AIR VENT

P PRESSURE SWITCH

T TEMPERATURE SWITCH

PIPE UNION

FLEXIBLE PIPE CONNECTOR

PIPE TEE

PLAN 90° ELBOW

CROSS AND RISER

TEE OFF BOTTOM

TEE OFF TOP

DROP AND TURN

DROP AND RUN

TEE DOWN

TEE UP

PIPE TURNING UP

PIPE TURNING DOWN

PIPE CAP

WCO WALL CLEANOUT

CO SUSPENDED CLEANOUT

FLOOR CLEANOUT

U.S. Department of Veterans Affairs

PROVIDE STICKY MAT ON ENTIRE FLOOR AREA OF SERVICE ELEVATOR LOBBY BETWEEN SERVICE ELEVATOR #3 AND THE

DOOR TO THE MECHANICAL ROOM WHERE NEW EQUIPMENT IS BEING INSTALLED.

PROVIDE ZIPPER ENTRY AT ACCESS POINT TO CONSTRUCTION AREA, AT DOOR TO THE MECHANICAL ROOM, IF THE WORK

REQUIRED TO INSTALL THE EQUIPMENT WILL GENERATE ANY DUST.

PROVIDE ICRA BARRIERS AS NECESSARY TO PERFORM THE WORK PER THE MECHANICAL DRAWINGS. THE USE OF

TEMPORARY, REUSABLE TYPE BARRIERS (EX. STARC WALL SYSTEMS) IS ACCEPTABLE. ENSURE THAT ACCESS THROUGH

THE BARRIERS IS PROVIDED IF THE TEMPORARY BARRIERS CUTS OFF ACCESS FROM THE MECHANICAL ROOM OR ANY

OTHER SPACE TO THE MEANS OF EGRESS.

VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR REGARDING CONFLICTS BEFORE PROCEEDING WITH

WORK.

REMOVED ITEMS REMAIN PROPERTY OF GOVERNMENT UNTIL COR DETERMINES THAT THEY ARE NOT REQUIRED. REMOVE

FROM SITE ITEMS NOT BEING RETAINED BY GOVERNMENT OR REINSTALLED AS PART OF THIS WORK.

DO NOT DISTURB ITEMS NOT INDICATED FOR DEMOLITION.

VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION. RELOCATE, REMOVE AND ADJUST

MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO COORDINATE WITH NEW WORK.

AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING ADJACENT CONDITIONS.

COORDINATE DEMOLITION WITH COR. SUBMIT SHUTDOWN PLAN AND SCHEDULE TO COR FOR REVIEW AND APPROVAL.

PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION. REPAIR UTILITIES AND SERVICES DAMAGED AT

NO ADDITIONAL COST.

TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE WORK.

COORDINATE WITH NEW PLUMBING WORK AND WORK OF OTHER TRADES.

TEST EXISTING SYSTEMS FOR OPERATION, ALARMS, AND CAPACITY THEN PROVIDE REPORT TO COR PRIOR TO START OF

DEMOLITION.

ISOLATE SUPPLY EQUIPMENT FROM DISTRIBUTION SYSTEMS BY SHUTTING OFF SOURCE VALVES BEFORE BEGINNING

DEMOLITION.

PRESSURE REDUCING VALVE (WATER)

PLUG VALVE

GLOBE VALVE

GATE VALVE

CONTROL VALVE

CHECK VALVE

BUTTERFLY VALVE

BALL VALVE

ANGLE GLOBE VALVE

ECCENTRIC REDUCER

CONCENTRIC REDUCER

CONSULTANTS:

Drawn

NAS

Checked

RBK

Date

JANUARY 11, 2022

Approved Location

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758

Building Number

# 11

VA PROJECT NUMBER

671A4-22-172

Project Title

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

Drawing Title

PLUMBING GENERAL INFORMATION

/1

/2

:1

:2

U s e rs

\s m is e v ic h \D o c u m e n ts

\M F

P -0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X s m is e v ic h .r v t

PLUMBING SYMBOLS & ABBREVIATIONS

ANNOTATION ABBREVIATIONS

A/E ARCHITECT/ENGINEER F FAHRENHEIT O2 OXYGEN

AC ABOVE CEILING FA FROM ABOVE OC ON CENTER

AD AREA DRAIN FB FROM BELOW OD OUTSIDE DIAMETER

AFF ABOVE FINISHED FLOOR FBO FURNISHED BY OTHERS OFD OVERFLOW DRAIN

AG AIR GAP FCO FLOOR CLEANOUT OR OPERATING ROOM

AP ACCESS PANEL FCW FILTERED COLD WATER OVFL OVERFLOW

AS AUTOMATIC SPRINKLER FD FLOOR DRAIN

AFG ABOVE FINISHED GRADE FDC FIRE DEPARTMENT (HOSE) PA PASCAL

ASD ADJUSTABLE SPEED DRIVE CONNECTION PC PLUMBING CONTRACTOR

ASHRAE AMERICAN SOCIETY HEATING, FM FLOW METER PD PRESSURE DROP

REFRIGERATING, AIR CONDITIONING FOP FUEL OIL PUMP PDI PLUMBING AND DRAINAGE INSTITUTE

ENGINEERS FOR FUEL OIL RETURN PG PRESSURE GAUGE

ASME AMERICAN SOCIETY OF MECHANICAL FOS FUEL OIL SUPPLY PP PLUMBING PUMP

ENGINEERS FOV FUEL OIL VENT PPM PARTS PER MILLION

ASPE AMERICAN SOCIETY PLUMBING FS FLOOR SINK PRS PRESSURE REDUCING STATION

ENGINEERS FU FIXTURE UNITS PRV PRESSURE REDUCING VALVE

ASR AUTOMATIC SPRINKLER RISER PSI POUNDS PER SQUARE INCH

AV ACID VENT G GALLON PSIA POUNDS PER SQUARE INCH -

AW ACID WASTE GC GENERAL CONTRACTOR ABSOLUTE

GCO GRADE CLEANOUTS PSIG POUNDS PER SQUARE INCH - GAUGE

BAS BUILDING AUTOMATION SYSTEM GD GARBAGE DISPOSAL PTRV PRESSURE TEMPERATURE RELIEF

BF BELOW FLOOR GPD GALLONS PER DAY VALVE

BFP BACKFLOW PREVENTER GPH GALLONS PER HOUR PW POTABLE WATER

BG BELOW GRADE GPM GALLONS PER MINUTE

BH BOOSTER HEATER GPR GAS PRESSURE REGULATOR RD ROOF DRAIN

BHP BREAK HORSEPOWER GRS GAS REGULATOR STATION RDL ROOF DRAIN LEADER

BJ BETWEEN JOISTS GT GREASE TRAP RL ROOF LEADER

BOP BOTTOM OF PIPE GVTR GAS VENT THROUGH ROOF RO REVERSE OSMOSIS

BSP BLACK STEEL PIPE GWH GAS FIRED WATER HEATER RWL RAIN WATER LEADER

BT BATHTUB

BTUH BRITISH THERMAL UNITS PER HOUR H&CW HOT AND COLD WATER SAN SANITARY SEWER

HB HOSE BIBB (INTERIOR) SCFM STANDARD CUBIC FOOT/MIN

C CELSIUS HD HUB DRAIN SCW SOFTENED COLD WATER

CF COMBINATION FIXTURE HEX HEAT EXCHANGER SDMH STORM DRAIN MANHOLE

CGA COMPRESSED GAS ASSOCIATION HP HORSEPOWER SP SUMP PUMP

CI CAST IRON HS HAND SINK SPR SPRINKLER LINE

CO CLEANOUT HST HOT WATER STORAGE TANK SQFT SQUARE FOOT

COND CONDENSATE (DOMESTIC) SS STAINLESS STEEL

CP CONDENSATE PUMP HWB HOT WATER BOILER ST STORAGE TANK

CS CLINICAL SINK HWCP HOT WATER CIRCULATING PUMP SW STORM WATER

CV CONTROL VALVE HWP HOT WATER PUMP

HYD HYDRANT TCV TEMPERATURE CONTROL VALVE

DA DENTAL COMPRESSED AIR TD TRENCH DRAIN

DCW DOMESTIC COLD WATER ICW INDUSTRIAL COLD WATER TDH TOTAL DYNAMIC HEAD

DHW DOMESTIC HOT WATER INV INVERT TDL TEMPERATURE DIFFERENTIAL

DHWR DOMESTIC HOT WATER RETURN IPC INTERNATIONAL PLUMBING CODE TEMP TEMPERATURE

DHWS DOMESTIC HOT WATER SUPPLY IRW IRRIGATION WATER TMV THERMOSTATIC MIXING VALVE

DF DRINKING FOUNTAIN IW INDIRECT WASTE TP TRAP PRIMER

DI DEIONIZED WATER IWH INSTANTANEOUS WATER HEATER TSTAT THERMOSTAT

DN DOWN IWR INDUSTRIAL WATER RETURN TWR TEMPERED WATER RETURN

DOE DEPARTMENT OF ENERGY IWS INDUSTRIAL WATER SUPPLY TWS TEMPERED WATER SUPPLY

DS DOWNSPOUT TYP TYPICAL

DV DENTAL VACUUM KW KILOWATT

DW DISHWASHER KWHR KILOWATT-HOUR UPC UNIFORM PLUMBING CODE

DWG DRAWING

DWH DOMESTIC WATER HEATER L/S LITER PER SECOND V SANITARY VENT

DWR DRINKING WATER RETURN LA LABORATORY AIR VAC VACUUM

DWS DRINKING WATER SUPPLY LAV LAVATORY VB VACUUM BREAKER

DWV DRAIN WASTE VENT LBS/HR POUNDS PER HOUR VCO VACUUM CLEANER OUTLET

LCW LABORATORY COLD WATER VP VACUUM PUMP

EC ELECTRICAL CONTRACTOR LHW LABORATORY HOT WATER VS VENT STACK

EL ELEVATION LNG LIQUID NATURAL GAS VTR VENT THROUGH ROOF

EMCS ENERGY MONOSERRAT AND CENTRAL LOX LIQUID OXYGEN

SYSTEM LV LABORATORY VACUUM W WASTE

EPA ENVIRONMENTAL PROTECTION LW LOW WATER WC WATER CLOSET

AGENCY WCO WALL CLEANOUT

EPACT ENERGY POLICY ACT M METER WG WATER GAUGE

ESC ESCUTCHEON MA MEDICAL AIR WH WATER HEATER

ESH EMERGENCY SHOWER MAV MANUAL AIR VENT WHA WATER HAMMER ARRESTOR

ET EXPANSION TANK MBH THOUSANDS OF BTU PER HOUR WHD WALL HYDRANT

EWC ELECTRIC WATER COOLER MC MECHANICAL CONTRACTOR WL WATER LINE

EWH ELECTRIC WATER HEATER MED MEDICAL WM WATER METER

EWS EYEWASH STATION MER MECHANICAL EQUIPMENT ROOM WPD WATER PRESSURE DROP

EX EXISTING MH MANHOLE WS WASTE STACK

MOU MEMORANDUM OF UNDERSTANDING

MSB MOP SINK BASIN YCO YARD CLEANOUT

MV MEDICAL VACUUM YH YARD HYDRANT

N2 NITROGEN

N2O NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

PLUMBING SYMBOLS

PIPING SYSTEM

AW AW ACID WASTE

CA CA COMPRESSED AIR

CD CD CONDENSATE DRAIN

CO2 CO2 CARBON DIOXIDE

NG NG NATURAL GAS

GW GW GREASE WASTE

MA MA MEDICAL AIR

N2 N2 NITROGEN

N2O N2O NITROUS OXIDE

OFD OFD OVERFLOW STORM DRAIN

OW OW OIL WASTE

O2 O2 OXYGEN

PD PD PUMP DISCHARGE

PG PG PROPANE GAS

ST ST STORM

VAC VAC VACUUM

WAGD WAGD WASTE ANESTHETIC GAS DISPOSAL

SAN SAN SANITARY WASTE

AV

OV

V

AV ACID VENT

OV OIL VENT

V SANITARY VENT

DCW DOMESTIC COLD WATER

DI DI DE-IONIZED WATER

NPCW NPCW NONPOTABLE COLD WATER

RO RO REVERSE OSMOSIS WATER

SCW SCW SOFTENED COLD WATER

HW 140

DHW DOMESTIC HOT WATER

DHW 140 DOMESTIC HOT WATER (OTHER TEMP)

DCWR DOMESTIC CW RECIRCULATION

DHWR DOMESTIC HW RECIRCULATION

ANNOTATION SYMBOLS

# NEW WORK KEYNOTE

# DEMOLITION KEYNOTE

NEW BOLD TEXT INDICATES NEW ITEM

EXISTING ITALICIZED TEXT INDICATES EXISTING ITEM

DETAIL MODULE NUMBER

DETAIL OR SECTION MARK

SHOWN ON DRAWING

CONNECT TO EXISTING

LIMIT OF DEMOLITION

P-### NEW PLUMBING EQUIPMENT MARK

P-### EXISTING PLUMBING EQUIPMENT MARK

PROJECT MANAGER

ACG Project Number

21-040

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511

10 11 12 13 14

CRAWL SPACE

UNEXCAVATED

11 12

TO BUILDING

DISTRIBUTION SYSTEM

13 FROM BUILDING

1.

1" MA

2" MV

EX-11-VP-1

A. COORDINATE ANY LOSS OF MEDICAL GAS

SERVICE WITH COR AT LEAST 1 WEEK IN

ADVANCE. PROVISION OF TEMPORARY MEDICAL

GAS SUPPLY EQUIPMENT DURING EQUIPMENT

CHANGEOVER IS NOT IN CONTRACT.

B. PROVIDE STICKY MAT ON ENTIRE FLOOR AREA

OF SERVICE ELEVATOR LOBBY BETWEEN

SERVICE ELEVATOR #3 AND THE DOOR TO THE

MECHANICAL ROOM WHERE NEW EQUIPMENT IS

BEING INSTALLED.

C. PROVIDE ZIPPER ENTRY AT ACCESS POINT TO

CONSTRUCTION AREA, AT DOOR TO THE

MECHANICAL ROOM, IF THE WORK REQUIRED TO

STAIRWELL EXIT TO

OUTSIDE AT FIRST

FLOOR LEVEL

EX-11-AC-1

OUTLINE OF EXISTING

HOUSKEEPING PAD

4" MV EXHAUST

INSTALL THE EQUIPMENT WILL GENERATE ANY

DUST.

D. PROVIDE ICRA BARRIERS AS NECESSARY TO

PERFORM THE WORK PER THE MECHANICAL

DRAWINGS. THE USE OF TEMPORARY, REUSABLE

TYPE BARRIERS (EX. STARC WALL SYSTEMS) IS

ACCEPTABLE. ENSURE THAT ACCESS THROUGH

THE BARRIERS IS PROVIDED IF THE TEMPORARY

BARRIERS CUTS OFF ACCESS FROM THE

MECHANICAL ROOM OR ANY OTHER SPACE TO

THE MEANS OF EGRESS.

E. CONTRACTOR IS TO PROVIDE FLOORING

PROTECTION FROM ENTRY DOOR TO SERVICE

ELEVATOR OF THE FIRST FLOOR AND FROM THE

SERVICE ELEVATOR TO THE MECHANICAL ROOM

DOOR AT THE BASEMENT LEVEL. PLYWOOD

FLOOR COVERING IS SUGGESTED, BUT THE

CONTRACTOR CAN UTILIZE WHATEVER FLOOR

PROTECTION MATERIAL THEY FEELS WILL

ACCOMPLISH THE JOB. CONTRACTOR SHALL BE

RESPONSIBLE FOR AND DAMAGE TO THE

FLOORING, ADJACENT SURFACES, ETC. CAUSED

BY THE PERFORMANCE OF THE CONTRACTOR’S

WORK OR BY THEIR PERSONNEL.

F. FOR PHOTOGRAPHS OF EXISTING CONDITIONS

SEE PG601.

MECH. ROOM

4" MV EXHAUST UP

THROUGH ROOF

EXHAUST TO

OUTLET

PIPE BASEMENT

FROM INTAKE

# NEW WORK KEY NOTES:

1 NEW MEDICAL AIR COMPRESSOR SYSTEM.

CONNECT TO EXISTING SUPPLY PIPING AND AIR

INTAKE.

2 NEW MEDICAL VACUUM PUMP. CONNECT TO

EXISTING SUPPLY PIPING AND VACUUM EXHAUST.

3 RECONNECT NEW EQUIPMENT TO EXISTING

MASTER ALARM AT JUNCTION BOX.

4 PROVIDE SUPPORT FOR NEW AND EXISTING

ELECT.

CLOSET

NO. 3

ELEVATOR

LOBBY

SERVICE ELEVATOR FOR

ACCESS WITH EQUIPMENT

BASEMENT MECHANICAL ROOM MEDICAL GAS DEMOLITION PLAN

Scale: 1/4" = 1'-0"

0 2 4 8 MEDGAS PIPING ASSOCIATED WITH AIR

COMPRESSOR AND VACUUM PUMP IN MECHANICAL

ROOM. SUPPORT FOR THIS PIPING SHALL CONFORM

WITH SPECIFICATIONS.

5 PROVIDE STICKY MAT AT ENTRANCE TO

CONSTRUCTION AREA PER FACILITY ICRA

REQUIREMENTS.

6 PROVIDE NEW MEDICAL AIR INTAKE PIPING.

1 PROVIDE SUPPORTS FOR MEDICAL PIPING INSIDE

MECHANICAL ROOM AND OUTSIDE. SUPPORTS FOR

E.C.

MAIN

LOBBY

NO. 2

NO. 1

11 12 TO BUILDING

13 FROM BUILDING

1" MA

2" MV

THIS PIPING SHALL CONFORM WITH

SPECIFICATIONS.

7 TURN DOWN AND SCREEN OUTSIDE INTAKE PIPING.

E UNEXCAVATED

11-AC-1

OUTLINE OF EXISTING

HOUSKEEPING PAD

11-VP-1

# DEMOLITION KEY NOTES:

F

BASEMENT MECHANICAL ROOM INFECTION CONTROL PLAN

Scale: 1/8" = 1'-0"

2 1/2" MA

4" MV EXHAUST

1 EXISTING MEDICAL AIR COMPRESSORS, RECEIVER,

AND DESICCANT COOLER TO BE REMOVED.

DEMOLISH ASSOCIATED PIPING TO POINTS

INDICATED.

2 EXISTING MEDICAL VACUUM PUMP TO BE REMOVED.

DEMOLISH ASSOCIATED PIPING TO POINTS

INDICATED.

3 REMOVE EXISTING DEW POINT SENSOR ON MEDICAL

AIR SUPPLY MAIN AND TURN OVER TO VA.

4 DEMOLISH MEDICAL AIR INTAKE PIPING COMPLETE

INCLUDING PIPING INSTALLED OUTSIDE.

TO OUTLET

FROM 3RD

FLOOR ROOF

WEST

NORTH MECHANICAL

EAST

BASEMENT MECHANICAL ROOM MEDICAL GAS PLAN

Scale: 1/4" = 1'-0"

0 2 4 8

S S S S SMOKE RESISTIVE HAZARDOUS AREA

Drawing Title

Project Title

100% BID DOCUMENTS

VA PROJECT NUMBER

Office of Construction

MECHANICAL ROOM MEDICAL GAS

PLANS

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

671A4-22-172 and Facilities # 11

1 Revision #1

01/10/2025

Management

U.S. Department

Location

KERRVILLE VA MEDICAL CENTER

Date Checked Drawn

PG400

Date of Veterans Affairs KERRVILLE, TX 78028-5758 JANUARY 11, 2022 RBK NAS Dwg

CONSULTANTS:

/1

/2

:1

:2

U s e rs

\s m is e v ic h \D o c u m e n ts

\M F

P -0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X s m is e v ic h .r v t

U

M

V

E

X H

A U

S

M

V

E

X H

A U

S

I D

A I

PROJECT MANAGER

ACG Project Number

21-040

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511

DocuSign Envelope ID: 23E13BA4-D0F9-42A1-BCB8-E4C79E81E576

VACUUM PUMP SCHEDULE

MARK

LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

TYPE UNIT

RECEIVER SIZE VACUUM PRESSURE

CFM DELIVERY @ VACUUM

PRESSURE (SI)

ELECTRIC POWER

WEIGHT

(LBS)

REMARKS

NO. PUMPS

POWER EACH

PHASE VOLT FLA

GAL [L] in Hg [kPa] SCFM STANDARD [L/s] HP [Kw]

11-VP-1 BASEMENT... BUILDING 11 MEDICAL VACUUM DUPLEX DRY CLAW 200 [ 760 ] 19 [ 64 ] 65 [ 31 ] 2 7.5 5.6 [ 3 ] 460 21 2190 1, 2, 3, 4, 5, 6, 7, 8, 9

NOTES:

1. CAPACITIES ARE AT SITE CONDITION.

2. BASIS OF DESIGN IS AMICO MODEL V-CCD-D-200P-SS-N-075-MS.

3. MODULAR UNITS THAT CAN BE DISASSEMBLED AND REASSEMBLED ON SITE.

4. PROVIDE ALL ACCESSORIES FOR FULLY FUNCTIONAL SYSTEM.

5. PROVIDE ALL ALARMS PER NFPA AND CONNECT TO EXISTING ALARM SYSTEM.

6. PROVIDE DRAIN PIPING WITH VALVE AND MAIN ISOLATION VALVE FOR THE UNIT.

7. UNIT SHALL OPERATE BETWEEN 19" Hg AND 25" Hg WITH CAPACITY AT LISTED SCFM.

8. LISTED CAPACITY IS WITH ONE PUMP IN OPERATION.

9. PROVIDE GAUGES, SENSORS, AND SAFETY DEVICES.

AIR COMPRESSOR SCHEDULE

MARK

LOCATION

AREA AND/OR

BLDG SERVED

SYSTEM AND/OR

TYPE

NFPA AIRFLOW CAPACITY

NFPA DISCHARGE

PRESSURE

RECEIVER SIZE

RECEIVER DIMENSIONS, DIA

X LENGTH

ELECTRIC POWER [60 Hz]

WEIGHT

(LBS)

REMARKS

NO. MOTORS

POWER EA.

PHASE

VOLT

FLA

CFM [L/s] PSIG [kPa] GAL [L] IN [mm] HP [kW]

11-AC-1

BASEMENT

MECHANICAL

BUILDING 11 MEDICAL AIR

DUPLEX OIL-LESS

SCROLL

24 [ 94 ] 120 [ 830 ] 200 [ 760 ] 36X84 [900X2100] 2 7.5 [ 6 ] 3 460 22 2330 1, 2, 3, 4, 5, 6, 7, 8, 9

NOTES:

1. CAPACITIES ARE AT SITE CONDITION.

2. BASIS OF DESIGN IS AMICO MODEL A-SCD-D-200P-SS-N-075-TS

3. MODULAR UNIT THAT CAN BE DISASSEMBLED AND REASSEMBLED ON SITE.

4. PROVIDE ALL ACCESSORIES FOR FULLY FUNCTIONAL SYSTEM.

5. PROVIDE ALL ALARMS PER NFPA AND CONNECT TO EXISTING ALARM SYSTEM.

6. PROVIDE DRAIN PIPING WITH ISOLATION VALVE AND MAIN ISOLATION VALVE FOR THE UNIT.

7. PROVIDE DESSICANT AIR DRYER WITH ALL ACCESSORIES.

8. LISTED CAPACITY IS WITH ONE PUMP IN OPERATION.

9. PROVIDE GAUGES, SENSORS, AND SAFETY DEVICES.

MEDICAL AIR COMPRESSOR VIEW 1

Scale: No Scale

EXISTING AIR AND VACUUM SYSTEMS

Scale: No Scale

VACUUM PUMPS

Scale: No Scale

MEDICAL AIR COMPRESSOR VIEW 3

Scale: No Scale

MEDICAL AIR COMPRESSOR VIEW 2

Scale: No Scale

EXISTING DESSICANT SYSTEM

Scale: No Scale

VACUUM TANK AND CONTROL PANEL

Scale: No Scale

MEDICAL AIR INTAKE

Scale: No Scale

P-601 # Revisions: Date

JANUARY 11, 2022 Dwg of Veterans Affairs

Drawn

NAS

Checked

RBK

Location

KERRVILLE VA MEDICAL CENTER

3600 MEMORIAL BLVD.

KERRVILLE, TX 78028-5758

Building Number

# 11

919-858-7420 www.acg-pa.com Engineers Architects © COPYRIGHT Apogee Consulting Group, P.A.

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511

VA PROJECT NUMBER

671A4-22-172

Project Title

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

Drawing Title

MEDICAL GAS SCHEDULES AND

EXISTING EQUIPMENT PHOTOGRAPHS

Office of Construction and Facilities Management

ACG Project Number

21-040 PROJECT MANAGER

1/11/2022

CONSULTANTS:

/7

/2

:5

:0

U s e rs

\n s to ltz \D o c u m e n ts

\M F

P -0

-V

A K e rr v ill e -M e d

A ir V a c

S y s te m -T

X n s to ltz .r v t

DocuSign Envelope ID: FCFB9153-3C99-48D2-8B65-8D3C2A627379

ELECTRICAL ABBREVIATIONS LIST

1P

1 POLE (2P, 3P, 4P, ETC.)

CONST

CONSTRUCTION

GAL

GALLON

MTR

MOTOR, MOTORIZED

SPKR

SPEAKER

1PH 1 PHASE CONT CONTINUATION OR CONTINUOUS GALV GALVANIZED MTS MANUAL TRANSFER SWITCH SP SPARE 2/C TWO-CONDUCTOR (3/C, 4/C, ETC.) CONTR CONTRACTOR GC GENERAL CONTRACTOR SR SURFACE RACEWAY 2W TWO-WIRE (3W, 4W, ETC.) COORD COORDINATE GEN GENERATOR NA NOT APPLICABLE SS STAINLESS STEEL 3PH 3 PHASE COR CONTRACTING OFFICER'S GFI GROUND FAULT CIRCUIT INTERRUPTER NC NORMALLY CLOSED SSW SELECTOR SWITCH

A AMPERE REPRESENTATIVE GND GROUND NEC NATIONAL ELECTRICAL CODE STD STANDARD

AAP ALARM ANNUNCIATOR PANEL CPT CONTROL POWER TRANSFORMER GRS GALVANIZED RIGID STEEL (CONDUIT) NEMA NATIONAL ELECTRICAL SURF SURFACE MOUNTED AC ABOVE COUNTER CRI COLOR RENDERING INDEX GYP BD GYPSUM BOARD MANUFACTURER'S ASSOCIATION SW SWITCH

AIR CONDITIONER CT CURRENT TRANSFORMER NFDS NON-FUSED SAFETY DISCONNECT SWBD SWITCHBOARD ALTERNATING CURRENT CTV CABLE TELEVISION HID HIGH-INTENSITY DISCHARGE SWITCH SYM SYMMETRICAL

ACC ACCESSIBLE CTR CENTER HOA HAND-OFF-AUTOMATIC NIC NOT IN CONTRACT SYS SYSTEM

ACLG ABOVE CEILING CU COPPER HP HORSEPOWER NL NIGHT LIGHT

ADO AUTOMATIC DOOR OPENER CU FT CUBIC FEET NO NORMALLY OPEN TC TIMECLOCK

A/E ARCHITECT/ENGINEER HT HEIGHT NTS NOT TO SCALE TEL TELEPHONE

AF AMP FRAME D DEMOLITION HTR HEATER TEL/DATA TELEPHONE/DATA

AFC AVAILABLE FAULT CURRENT (KILOAMPS) dB DECIBEL HV HIGH VOLTAGE OC ON CENTER TERM TERMINAL AFF ABOVE FINISHED FLOOR DB DIRECT BURIAL HVAC HEATING, VENTILATING AND AIR OD OUTSIDE DIAMETER TP TWISTED PAIR AFG ABOVE FINISHED GRADE DC DIRECT CURRENT CONDITIONING OH OVERHEAD TPS TWISTED PAIR SHIELDED AFI ARC FAULT CIRCUIT INTERRUPTER DEG C DEGREES CELSIUS OL OVERLOAD TR TAMPER RESISTANT AHJ AUTHORITY HAVING JURISDICTION DEG F DEGREES FAHRENHEIT IES ILLUMINATION ENGINEERING SOCIETY T-STAT THERMOSTAT AHU AIR HANDLING UNIT DEMO DEMOLISH/DEMOLITION IG ISOLATED GROUND PA PUBLIC ADDRESS TTB TELEPHONE TERMINAL BOARD AIC AMPERE INTERRUPTING CAPACITY DEPT DEPARTMENT IMC INTERMEDIATE METAL CONDUIT PB PULL BOX OR PUSHBUTTON TTC TELEPHONE TERMINAL CABINET AL ALUMINUM DIA DIAMETER IR INFRARED PBPU PREFABRICATED BEDSIDE PATIENT TV TELEVISION

ALT ALTERNATE DISC DISCONNECT I/W INTERLOCK WITH UNIT TYP TYPICAL

AMP AMPERE DIST DISTRIBUTION IWH INSTANTANEOUS WATER HEATER PCB POLYCHLORINATED BIPHENYL

APPROX APPROXIMATELY DN DOWN PC PHOTOELECTRIC CELL UC UNDER COUNTER

ARCH ARCHITECT, ARCHITECTURAL DS SAFETY DISCONNECT SWITCH J-BOX JUNCTION BOX PED PEDESTAL UE UNDERGROUND ELECTRICAL

AT AMP TRIP DT DOUBLE THROW PEND PENDANT UG UNDERGROUND

ATS AUTOMATIC TRANSFER SWITCH DWG DRAWING KV KILOVOLT PF POWER FACTOR UH UNIT HEATER

AUTO AUTOMATIC KVA KILOVOLT-AMPERE PH PHASE UL UNDERWRITER'S LABORATORY

AUX AUXILIARY EC ELECTRICAL CONTRACTOR KVAR KILOVOLT-AMPERE REACTIVE PIV POST INDICATING VALVE UT UNDERGROUND TELEPHONE AV AUDIO VISUAL EG EQUIPMENT GROUND KW KILOWATT PNL PANEL UTP UNSHIELDED TWISTED PAIR AWG AMERICAN WIRE GAUGE ELEC ELECTRIC, ELECTRICAL KWH KILOWATT HOUR POE POWER-OVER-ETHERNET UTIL UTILITY

ELEV ELEVATOR PR PAIR UV UNIT VENTILATOR OR

BAS BUILDING AUTOMATION SYSTEM EM EMERGENCY LED LIGHT-EMITTING DIODE PRI PRIMARY ULTRAVIOLET BATT BATTERY EMI ELECTROMAGNETIC INTERFERENCE LF LINEAR FEET/FOOT PROJ PROJECTION

BC BARE COPPER EMS ENERGY MANAGEMENT SYSTEM LM LUMEN PRV POWER ROOF VENTILATOR V VOLT BD BOARD EMT ELECTRICAL METALLIC TUBING LRA LOCKED ROTOR AMPS PT POTENTIAL TRANSFORMER VA VOLT-AMPERES BFF BELOW FINISHED FLOOR EPO EMERGENCY POWER OFF LT LIGHT PVC POLYVINYL CHLORIDE (CONDUIT) VERT VERTICAL BLDG BUILDING EQUIP EQUIPMENT LTG LIGHTING PWR POWER VFD VARIABLE FREQUENCY DRIVE

BMS BUILDING MANAGEMENT SYSTEM ESMT EASEMENT LTNG LIGHTNING VOL VOLUME

BYP BYPASS ETR EXISTING TO REMAIN LV LOW VOLTAGE QTY QUANTITY

EWC ELECTRIC WATER COOLER W WATT

C CONDUIT EWH ELECTRIC WALL HEATER MATV MASTER ANTENNA TELEVISION SYSTEM R RELOCATE/RELOCATED W/ WITH CAB CABINET ELECTRIC WATER HEATER MAX MAXIMUM RCP REFLECTED CEILING PLAN WH WATER HEATER

CALC CALCULATED EX EXISTING MC MECHANICAL CONTRACTOR RCPT RECEPTACLE W/O WITHOUT

CAP CAPACITY EXP EXPLOSION PROOF METAL-CLAD (CONDUIT) REQD REQUIRED WP WEATHERPROOF

CAT CATALOG, CATEGORY MCA MINIMUM CIRCUIT AMPACITY RGS RIGID GALVANIZED STEEL

CATV COMMUNITY ANTENNA TELEVISION FA FIRE ALARM MCB MAIN CIRCUIT BREAKER RM ROOM XFMR TRANSFORMER CB CIRCUIT BREAKER FAAP FIRE ALARM ANNUNCIATOR PANEL MCC MOTOR CONTROL CENTER RMS ROOT MEAN SQUARE XFR TRANSFER CCR CONTROL CONTACTOR FACP FIRE ALARM CONTROL PANEL MDP MAIN DISTRIBUTION PANEL RTU ROOF TOP UNIT

CCT CORRELATED COLOR TEMPERATURE FC FOOTCANDLE MECH MECHANICAL

CCTV CLOSED CIRCUIT TELEVISION FCU FAN COIL UNIT MFR MANUFACTURER SC SURFACE CONDUIT ANGLE cd CANDELA FIXT FIXTURE MFS MAIN FUSED DISCONNECT SWITCH SEC SECONDARY @ AT

CD CONSTRUCTION DOCUMENTS FLR FLOOR MH MANHOLE SF SQUARE FEET/FOOT

DELTA

CF CONTRACTOR-FURNISHED MIC MICROPHONE SHT SHEET ' FEET

CKT CIRCUIT FU FUSE MIN MINIMUM SI INTERNATIONAL SYSTEM OF UNITS " INCHES

CLG CEILING FUDS FUSED SAFETY DISCONNECT MISC MISCELLANEOUS SIM SIMILAR # NUMBER

CO CONTRACTING OFFICER SWITCH MLO MAIN LUGS ONLY S/N SOLID NEUTRAL Φ PHASE

COAX COAXIAL CABLE FVR FULL VOLTAGE REVERSING MOA MULTIOUTLET ASSEMBLY SPEC SPECIFICATION CL CENTER LINE COMM COMMUNICATION FVNR FULL VOLTAGE NON-REVERSING MSBD MAIN SWITCHBOARD PL PLATE

CONN CONNECTION MT MOUNT

100% CONSTRUCTION DOCUMENTS

E-001

Date Dwg

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

'LPN'-1,3,5

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

E1

T1

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

d

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

c

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

E2

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING

FIXTURES INDICATED BY 'd'.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

EXAMPLE: TRANSFORMER TYPE 'T1'.

'LPN'

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

A1 b of Veterans Affairs

06/30/23

USING OHM'S LAW AND THE KNOWN RESISTIVITY CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM PER

FOOT) FOR COPPER CONDUCTORS, CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED THE

RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH CIRCUIT CONDUCTORS.

ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE

PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE

CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH

WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL

ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY

STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL

AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING

EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE

DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE

STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.

SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED

THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO

THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK

AREA, FOR THE STARTING POINT OF THE CALCULATIONS.

JWB

Checked

MJJ

Date

JANUARY 11, 2022

Approved Location

KERRVILLE VA MEDICAL CENTER

3600 VETERANS DRIVE, KERRVILLE, TX

28028

Building Number

# 11

VA PROJECT NUMBER

671-A4-22-172

Project Title

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

Drawing Title

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

/7

/2

:2

:2

U s e rs

\jw b e e z le y \D o c u m e n ts

\E -0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X jw b e e z le y a c g -p a .c o m

.r v t

LIGHTING SYMBOL LEGEND

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 2' RECESSED ARCHITECTURAL TROFFER

--- 2' X 4' RECESSED ARCHITECTURAL TROFFER

--- 2' X 4' RECESSED FLAT LENS TROFFER

7'-0"

CENTER

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

4' LINEAR - WALL MOUNTED

--- 4' LINEAR STRIP - SUSPENDED

--- 6" DIAMETER RECESSED DOWNLIGHT

7'-5"

BOTTOM

EXIT SIGN - WALL MOUNTED

--- EXIT SIGN - CEILING MOUNTED

7'-6"

CENTER

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

6'-0"

CENTER

WALL SCONCE

48"

CENTER

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

VS: VACANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

DR: DUAL RELAY

VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER

OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

4: 4 WAY

OS ---

OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY - CEILING MOUNTED

OS --- OCCUPANCY SENSOR, LOW VOLTAGE, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

RC --- LOW VOLTAGE LIGHTING CONTROL DEVICE

RCD ---

LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

LS ---

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

ELECTRICAL SYMBOL LEGEND

SYMBOL HEIGHT DESCRIPTION

18" 120V SIMPLEX RECEPTACLE

18" 120V DUPLEX RECEPTACLE

18"

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

18" 120V QUADRUPLEX RECEPTACLE

18" 120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

18" 208V DUPLEX RECEPTACLE

18" SPECIAL RECEPTACLE

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

J AS

NOTED

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

J

CLNG

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

J

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

E

AS

NOTED

EQUIPMENT CONNECTION

72" TOP DISCONNECT SWITCH NON-FUSED

72" TOP DISCONNECT SWITCH FUSED

48" SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SWITCH MODIFIERS:

M: MOTOR-RATED

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

PROJECT MANAGER

ACG Project Number

21-040

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 mailto:System-TX_jwbeezley@acg-pa.com.rvt

11 12 13 14

A. COORDINATE DISCONNECTION OF EXISTING

EQUIPMENT AND CONNECTION TO NEW

EQUIPMENT WITH MECHANICAL CONTRACTOR.

B. EQUIPMENT CONNECTIONS SHALL BE MADE

ACCORDING TO MANUFACTURER'S

INSTRUCTIONS AND RECOMMENDATIONS.

C. PROVIDE EQUIPMENT CONNECTIONS TO

INCLUDE DISCONNECTING MEANS,

CONDUCTORS, CONDUIT, & OCPD ACCORDING

TO THE EQUIPMENT CONDUCTOR SCHEDULE

ON SHEET-'E-601'.

D. EXISTING CONNECTIONS TO MEDICAL-GAS

ALARM PANEL TO REMAIN FOR USE WITH NEW

EQUIPMENT. SEE EQUIPMENT CONDUCTOR

SCHEDULE NOTES.

EX-11-AC-1 1

EX-11-VP-1 2

E. DURING THE COURSE OF CONSTRUCTION,

TEMPORARY EQUIPMENT (UNITS AND/OR

CYLINDERS) FOR MAINTAINING AIR-VACUUM

OPERATION MAY BE REQUIRED. THE VA WILL

FURNISH AND INSTALL TEMPORARY SYSTEMS;

HOWEVER, COORDINATE TEMPORARY

EQUIPMENT WORK WITH VA PERSONNEL AS

NEEDED.

# NEW WORK KEY NOTES:

EXISTING 3 4

PANEL 'PBYEA'

1 CONNECT NEW PACKAGED MEDICAL AIR

COMPRESSOR EQUIPMENT. SEE

MECHANICAL EQUIPMENT CONDUCTOR

SCHEDULE AND ASSOCIATED PANEL

SCHEDULE.

2 CONNECT NEW PACKAGED MEDICAL

VACUUM PUMP EQUIPMENT. SEE

MECHANICAL EQUIPMENT CONDUCTOR

SCHEDULE AND ASSOCIATED PANEL

SCHEDULE.

3 INSTALL A NEW 30A/3P CIRCUIT BREAKER

TO FEED THE NEW VACUUM PLANT

EQUIPMENT IN PANEL-'PBYEA',

CIRUITS-1,3,5.

4 INSTALL A NEW 30A/3P CIRCUIT BREAKER

TO FEED THE NEW AIR COMPRESSOR

EQUIPMENT IN PANEL-'PBYEA',

CIRCUITS-19,21,23.

BASEMENT MECHANICAL ROOM ELECTRICAL DEMOLITION PLAN

# DEMOLITION KEY NOTES:

11 12 13 14

1 DISCONNECT AND REMOVE EXISTING

ELECTRICAL CONNECTION TO PACKAGED

MEDICAL AIR COMPRESSOR EQUIPMENT.

REMOVE EXISTING DISCONNECTING

MEANS AS WELL AS ASSOCIATED

CONDUITS AND CONDUCTORS, BACK TO

SOURCE OF ORIGIN.

2 DISCONNECT AND REMOVE EXISTING

ELECTRICAL CONNECTION TO PACKAGED

MEDICAL VACUUM EQUIPMENT. REMOVE

EXISTING DISCONNECTING MEANS AS

WELL AS ASSOCIATED CONDUITS AND

1 11-AC-1

11-VP-1 2

CONDUCTORS BACK TO SOURCE OF

ORIGIN.

3 REMOVE THE EXISTING 40A/3P CIRCUIT

BREAKER FEEDING THE EXISTING VACUUM

PLANT EQUIPMENT IN PANEL -'PBYEA',

CIRCUITS-1,3,5.

4 REMOVE THE EXISTING 30A/3P CIRCUIT

BREAKER FEEDING THE EXISTING AIR

COMPRESSOR EQUIPMENT IN

PANEL-'PBYEA', CIRCUITS-19,21,23.

EXISTING 3 4

PANEL 'PBYEA'

NORTH MECHANICAL

WEST EAST

BASEMENT MECHANICAL ROOM ELECTRICAL PLAN

S S S S

SMOKE RESISTIVE HAZARDOUS AREA

ELECTRICAL ENLARGEMENTS -

DEMOLITION AND NEW WORK

100% CONSTRUCTION DOCUMENTS

Location

KERRVILLE VA MEDICAL CENTER

3600 VETERANS DRIVE, KERRVILLE, TX

E-401

28028 JANUARY 11, 2022 Dwg

VA PROJECT NUMBER

671-A4-22-172

U.S. Department of Veterans Affairs

Drawn

JWB

Checked

MJJ

Building Number

# 11

919-858-7420 www.acg-pa.com Engineers Architects © COPYRIGHT Apogee Consulting Group, P.A.

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511

Project Title

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

Office of Construction and Facilities Management

ACG Project Number

21-040 PROJECT MANAGER

/7

/2

:2

:2

U s e rs

\jw b e e z le y \D o c u m e n ts

\E -0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X jw b e e z le y a c g -p a .c o m

.r v

MICHAEL J.

JENSEN

Exp. 06/30/23

ELECTRICAL

Branch Panel: PBYEA Location: MECHANICAL ROOM-028 Volts: 277/480 A.I.C. Rating: 14,000 AMPS SYMMETRICAL

Supply From: SWITCHBOARD-'1YEC'... Phases: 3 Mains Type: MLO

Mounting: RECESSED Wires: 4 Mains Rating: 225 A

Enclosure: NEMA 1 MCB Rating: 225 A

Notes:

EQUIPMENT BRANCH PANEL

CKT

Circuit Description

Trip

Poles

Poles

Trip

Circuit Description

CKT

VACUUM SYSTEM

30 A

6.10 5.54

40 A

<CONNECTED LOAD>

3 6.10 5.54 4

5 6.10 5.54 6

SPD COMP - 'OFF'

20 A

0.00 0.00

SPARE - 'OFF'

9 0.00 0.00 10

11 0.00 0.00 12

XFMR OLD DRYER

3.88 6.65

60 A

A/C #5

15 3.88 6.65 16

17 3.88 6.65 18

MEDICAL AIR

6.10 5.54

BAILER

21 6.10 5.54 22

23 6.10 5.54 24

DOMESTIC WATER BOOSTER PUMP

2.77 4.43

2 30 A SPD CONTROL

27 2.77 4.43 28

29 2.77 -- 1 -- SPACE 30

31 SPACE -- 1 -- 0.00

70 A

33 SPACE -- 1 -- 0.00 34

35 SPACE -- 1 -- 0.00 36

SPS AIR COMP

2.22 0.00

39 2.22 0.00 40

41 2.22 0.00 42

Total Load: 43.23 kVA 43.23 kVA 38.80 kVA

Total Amps: 159 A 159 A 140 A

Legend:

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Spare 125.26 kVA 125.00% 156.58 kVA

Total Conn. Load: 125.26 kVA Total Est. Demand: 156.58 kVA Total Conn.: 151 A

Total Est. Demand: 188 A

Notes:

ELECTRICAL SCHEDULES

FULLY SPRINKLERED

100% CONSTRUCTION DOCUMENTS

VA PROJECT NUMBER

671-A4-22-172

Building Number

# 11

Location

KERRVILLE VA MEDICAL CENTER

3600 VETERANS DRIVE, KERRVILLE, TX

E-601 # Revisions: Date

28028 JANUARY 11, 2022 Dwg of Veterans Affairs

Drawn

JWB

Checked

MJJ

919-858-7420 www.acg-pa.com Engineers Architects

© COPYRIGHT Apogee Consulting Group, P.A.

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511

Project Title

REMOVE/REPLACE MEDICAL

AIR VACUUM SYSTEM

Office of Construction and Facilities Management

ACG Project Number

21-040 PROJECT MANAGER

/7

/2

:2

:2

U s e rs

\jw b e e z le y \D o c u m e n ts

\E -0

-V

A K e rr v ill e -M e d

A ir V a c S y s te m -T

X jw b e e z le y a c g -p a .c o m

.r v

MICHAEL J.

JENSEN

Exp. 06/30/23

ELECTRICAL

File details come from the government source that posted it. Updated .