659-22-103_Construct Entry Canopies_Drawings.pdf
PDF 13 MB Posted
- Attached to
- J056--Construct Entry Canopies Federal contract opportunity
- Solicitation number
- 36C24623B0037
About this file
This federal contract opportunity solicitation requests bids for the construction of entry canopies at multiple buildings within a Department of Veterans Affairs facility. The contractor will be responsible for providing all labor, tools, equipment, materials and supervision necessary to construct canopies at four building entrances, including a walkway, while adhering to the provided specifications and drawings. The base bid scope of work involves general construction and alterations to remove existing structures and build the expansions. An alternate bid is also specified which excludes restoration work at one canopy. The bid due date is not stated, but the period of performance is listed as one hundred eighty days from notice to proceed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site visit roster_4252023.pdf | ||
| 36C24623B0037 0003.docx | DOCX document | |
| RFIs 36C24623B0037 Salisbury VAMC Construct Entry Canopies_.docx | DOCX document | |
| 36C24623B0037 0002.docx | DOCX document | |
| 36C24623B0037 0001.docx | DOCX document | |
| 659-22-103_Construct Entry Canopies_Specifications.pdf | ||
| 36C24623B0037_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTS + ENGINEERS:
1601 BRENNER AVENUE
SALISBURY, NC 28144
PROJECT LOCATION:
W.G. (BILL) HEFNER VA MEDICAL CENTER
PROJECT TITLE:
A&E SERVICES CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND PARKING GARAGE
BUILDING NUMBER:
2, 21, 42, AND PARKING GARAGE
3300 Dundee Rd.
Northbrook, IL 60062 www.bancroft-ae.com
BANCROFT ARCHITECTS +
ENGINEERS
VA CONTRACT NO. VA36C24621C0050
VA PROJECT NO. 659-22-103
BANCROFT-AE PROJECT NO. 21-106
PROJECT NUMBERS:
U.S. Department of Veterans Affairs
JUNE 02, 2022
N
NOT TO SCALE
REGIONAL LOCATION MAP
CONSTRUCTION BID DOCUMENTS
CAMPUS LOCATION
N
NOT TO SCALE
CAMPUS SITE MAP
N
NOT TO SCALE
STATE MAP
ARCHITECT
PROFESSIONAL SEALS
ELECTRICAL
STRUCTURAL
Director:
DATE_____
Supervisory Projects Engineer:
DATE_____
Deputy Director:
DATE_____
VA Project Engineer:
DATE_____
VP of FMS:
DATE_____
DATE_____
PLUMBING
SALISBURY, NC
STATESVILLE BLVD
BR
EN
NE
R
AV
E
JAKE ALEXANDER BLVD W
S MAIN ST
HWY 85
INNES ST
MOORESVILLE RD
LO
NG ST
STRUCTURAL ENGINEER:
330 S. Naperville Rd, Suite 300 Wheaton, IL 60187
JOHNSON, WILBUR, ADAMS INC.
GENERAL - COVER SHEET
CZ CR G001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_ G
1.
dw g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022 crollins Dennis 06022022 crollins Dennis 06022022
GENERAL - DRAWING INDEX
XX XX G002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_ G
2.
dw g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
GENERAL - BASIS OF DESIGN PROTOCOLS
XX XX GI001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_ G
I0
.d w g 6/
/2
:3
9:
P M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
GENERAL - NOTES
XX XX GI002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_ G
I0
.d w g 6/
/2
:3
9:
P M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
GENERAL - NOTES
XX XX GI003
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_ G
I0
.d w g 6/
/2
:3
9:
P M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_ 2-
VS
1.
dw g 6/
/2
:3
9:
P M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
CIVIL - BUILDING 2 - EXISTING SITE SURVEY
CZ CR 2-VS101
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_
-V S1
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
CIVIL - BUILDING 21 - EXISTING SITE SURVEY
CZ CR 21-VS101
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_
-V S1
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
CIVIL - BUILDING 42 - EXISTING SITE SURVEY
CZ CR 42-VS101
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
_3 6C
1R
_S al is bu ry
, N C
_E nt ry C an op ie s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\6
3_
PG
-V S1
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
CIVIL - PARKING GARAGE - EXISTING SITE
SURVEY
CZ CR PG-VS101
1 GENERAL NOTES
1.1. CODES AND DESIGN CRITERIA
a BUILDING CODE: INTERNATIONAL BUILDING CODE 2018 b RISK CATEGORY II
1.2. DESIGN LOADS
a ROOF LOAD
DEAD LOAD 20 PSF
LIVE LOAD 20 PSF
b ROOF STEEL BAR JOIST
DEAD LOAD TOP CHORD 15 PSF
DEAD LOAD BOTTOM CHORD 5 PSF
LIVE LOAD TOP CHORD 30 PSF
BEND CHECK BOTTOM CHORD LOAD 300 lbs (ANY
LOCATION)
c MECHANICAL EQUIPMENT SEE PLAN d SNOW LOAD
GROUND SNOW LOAD Pg 15 PSF IMPORTANCE FACTOR Is 1.0 SNOW EXPOSURE FACTOR Ce 1.0 SNOW THERMAL FACTOR Ct 1.2 FLAT ROOF SNOW LOAD Pf 15 PSF e WIND LOADS (ASCE7-16)
MWFRS
BASIC WIND SPEED 115 mph (3 SEC GUST)
RISK CATEGORY II
WIND EXPOSURE C
OPEN STRUCTURE
COMPONENTS & CLADDING
TRIBUTARY AREA>100 SQUARE FEET
ROOF ZONE 1 +16/-17 PSF
ROOF ZONE 2 +16/-23 PSF
ROOF ZONE 3 +16/-27 PSF
TRIBUTARY AREA 10 SQUARE FEET
ROOF ZONE 1 +16/-17 PSF
ROOF ZONE 2 +16/-23 PSF
ROOF ZONE 3 +16/-27 PSF
FASCIA (TRIBUTARY AREA < 10 SQUARE FEET)
WALL ZONE 4 +16/-18 PSF
WALL ZONE 5 +16/-20 PSF
NET WIND UPLIFT (ASCE7-10)
f SEISMIC LOADS
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR 1.0
Ss .17 Sds .182 S .074 Sd1 .119
SITE CLASS D
SEISMIC DESIGN CATEGORY B
BASIC SEISMIC FORCE RESISTING SYSTEM: STEEL FRAME NOT
DETAILED FOR SEISMIC
RESPONSE MODIFICATION FACTOR R 3
SEISMIC RESPONSE COEFFICIENT Cs .06 DESIGN BASE SHEAR (LRFD) k
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
1.3 GENERAL REQUIREMENTS
a DEFINITIONS
PRIMARY STRUCTURAL SYSTEM IS THE COMPLETED
COMBINATION OF ELEMENTS WHICH SERVE TO
SUPPORT THE BUILDING'S SELF-WEIGHT, THE
APPLICABLE LIVE LOAD, AND THE ENVIRONMENTAL LOADS SUCH AS WIND,
SEISMIC.
PRE-ENGINEERED STRUCTURAL ELEMENTS ARE
STRUCTURAL ELEMENTS WHICH ARE SPECIFIED BY THE OWNER AS DESIGN
DELEGATED ITEMS TO BE THE DESIGN RESPONSIBILITY OF A SPECIALTY
STRUCTURAL ENGINEER (SSE)
SPECIAL INSPECTION IS INSPECTION PERFORMED BY A QUALIFIED PERSON,
APPROVED BY THE BUILDING OFFICIAL, FOR THE TYPES OF WORK REQUIRING
INSPECTION PER THE GOVERNING CODES AND CONTRACT DOCUMENTS.
SPECIALTY STRUCTURAL ENGINEER (SSE) IS A
LICENSED PROFESSIONAL/STRUCTURAL ENGINEER, NOT THE SER, WHO IS
RESPONSIBLE FOR SEALING PLANS AND DESIGNS FOR PRE-ENGINEERED
STRUCTURAL ELEMENTS WHICH ARE NECESSARY FOR THE
STRUCTURE TO BE COMPLETED AND THE OWNER HAS DESIGNATED AS
DESIGN DELEGATED ITEMS.
STRUCTURAL ENGINEER OF RECORD (SER) IS THE STRUCTURAL ENGINEER
WHO IS LEGALLY ELIGIBLE TO SEAL THE STRUCTURAL DOCUMENTS FOR A
BUILDING PROJECT. THE SER IS RESPONSIBLE FOR THE DESIGN OF THE
PRIMARY STRUCTURAL SYSTEM.
DESIGNATED REPRESENTATIVE FOR CONSTRUCTION (CONTRACTOR) IS
RESPONSIBLE FOR THE OVERALL CONSTRUCTION OF THE PROJECT
INCLUDING PROJECT SCHEDULING, JOB SITE SAFETY AND MEANS AND
METHODS OF CONSTRUCTION.
CONTRACTING OFFICER'S REPRESENTATIVE (COR)
SPECIAL INSPECTOR: A QUALIFIED PERSON EMPLOYED OR RETAINED BY AN
APPROVED AGENCY AND APPROVED BY THE BUILDING OFFICIAL AS HAVING
THE COMPETENCE NECESSARY TO INSPECT A PARTICULAR TYPE OF
CONSTRUCTION REQUIRING SPECIAL INSPECTION.
b THE STRUCTURAL DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE
SPECIFICATIONS AND THE GEOTECHNICAL REPORT.
c THE CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL AND
ARCHITECTURAL DRAWINGS AND WITH THE MECHANICAL CONTRACTOR, THE
LOCATION OF ALL MECHANICAL EQUIPMENT.
d THE CONTRACTOR SHALL NOTIFY COR IF THE WEIGHTS OF MECHANICAL UNITS
ETC. ARE DIFFERENT FROM THE WEIGHTS POSTED ON THE DESIGN
DRAWINGS. DISCREPANCIES SHALL BE RESOLVED BEFORE PROCEEDING WITH
CONSTRUCTION.
e THE CONTRACTOR SHALL NOTIFY COR IMMEDIATELY OF ANY DISCREPANCIES
TO AVOID THE POSSIBILITY OF UNNECESSARY FUTURE PROBLEMS AND
POSSIBLE FIELD ORDERS. FAILURE TO DO SO WILL PUT THE FULL
RESPONSIBILITY OF CORRECTION ON THE CONTRACTOR.
f THE CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES AND MAKE
NECESSARY INVESTIGATIONS AND FIELD MEASUREMENTS.
g DO NOT SCALE DRAWINGS.
h THE SER HAS NO SUPERVISORY RESPONSIBILITY, HAS NO CONTROL OF OR
RESPONSIBILITY FOR THE MEANS, METHODS, TECHNIQUES, PROCEDURES OR
SEQUENCE OF CONSTRUCTION, HAS NO RESPONSIBILITY FOR THE FAILURE OF
ANY CONTRACTOR TO PERFORM THE WORK IN ACCORDANCE WITH THE
DESIGN DOCUMENTS AND NO RESPONSIBILITY TO DEVISE, IMPLEMENT OR
ENFORCE ANY SAFETY PRECAUTIONS OR PROGRAMS FOR THE PROJECT
2 FOUNDATIONS
2.1 GENERAL
a THE FOUNDATION DESIGN IS BASED ON A PRESUMPTIVE ALLOWABLE
SOIL BEARING PRESSURE OF 1500 PSF.
b SUMMARY OF GEOTECHNICAL DESIGN VALUES
SHALLOW STRIP AND SPREAD FOOTINGS
ALLOWABLE SOIL BEARING PRESSURE 1,500 PSF
DEPTH OF FOOTING BELOW FINISHED GRADE 36”.
c CONTRACTOR SHALL LOCATE ALL EXISTING BELOW GRADE UTILITIES
AND INTERFERENCES PRIOR TO START OF WORK. NOTIFY THE SER OF
ANY INTERFERENCE.
d REFER TO CIVIL DRAWINGS FOR ALL SOIL IMPROVEMENT, SITE
PREPARATION, GRADING, EROSION PROTECTION AND SITE UTILITY
WORK.
e STRIP TOPSOIL OVER THE ENTIRE BUILDING AREA.
f PROTECT ALL EXPOSED SURFACES IN ACCORDANCE WITH THE
GEOTECHNICAL REPORT.
g MAINTAIN ALL EXCAVATIONS FREE OF WATER CONTINUOUSLY h CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING/BRACING OF
EXCAVATIONS.
i ALL SHALLOW FOUNDATIONS SHALL BE LOCATED SHALL BEAR AT
SUFFICIENT DEPTH TO PROVIDE ADEQUATE FROST COVERAGE PER
LOCAL REQUIREMENTS.
j A GEOTECHNICAL TESTING SERVICE SHALL CONFIRM ALL SOIL BEARING
CAPACITIES PRIOR TO PLACEMENT OF CONCRETE FOUNDATIONS.
k ALL STRUCTURAL FILL AND GENERAL FILL SHALL MEET THE
REQUIREMENTS OF THE GEOTECHNICAL REPORT INCLUDING MATERIAL
SPECIFICATION AND COMPACTION REQUIREMENTS.
2.2 SHORING AND UNDERPINNING FOUNDATIONS
a SHORING AND UNDERPINNING ARE DESIGNATED AS A DELEGATED
DESIGN ITEMS AND SHALL BE DESIGNED BY THE CONTRACTOR'S
GEOTECHNICAL ENGINEER AND LICENSED PROFESSIONAL ENGINEER.
b ALL SHORING OF EXISTING FOUNDATIONS REQUIRED BY THE
CONTRACTOR DUE TO EXCAVATIONS NEAR EXISTING STRUCTURES AND
UNDERPINNING OF EXISTING FOUNDATIONS AS INDICATED ON THE
DESIGN DRAWINGS IS A DELEGATED DESIGN ITEM AND SHALL BE
DESIGNED BY THE CONTRACTOR'S GEOTECHNICAL AND LICENSED
STRUCTURAL ENGINEERS.
c ANY UNDERPINNING PROCEDURES INDICATED ON THE DESIGN
DRAWINGS ARE CONCEPTUAL ONLY AND SHALL BE CONFIRMED BY THE
CONTRACTOR'S GEOTECHNICAL AND STRUCTURAL ENGINEERS.
d SUBMIT SHORING AND UNDERPINNING PROCEDURES AND SEALED
CALCULATIONS TO THE ARCHITECT FOR RECORD PURPOSES ONLY.
3 CONCRETE CONSTRUCTION
3.1 CAST IN PLACE CONCRETE
a GENERAL REQUIREMENTS
ALL WORK SHALL CONFORM TO ALL REQUIREMENTS OF ACI 301-14,
SPECIFICATION FOR STRUCTURAL CONCRETE, EXCEPT AS MODIFIED BY THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS.
SUBMITTALS
CONCRETE MIXES WITH HISTORICAL TEST DATA.
MATERIAL CERTIFICATES: CEMENT, AGGREGATES, ADMIXTURES, REINFORCING
STEEL
REINFORCING STEEL PLACEMENT DRAWINGS
b PRODUCTS
REINFORCING BARS: ASTM A615 GRADE 60
REINFORCING BARS WELDABLE: ASTM A706 GRADE 60
PLAIN WIRE FABRIC: ASTM A185
AGGREGATES: ASTM C33
WATER: POTABLE ASTM C94
ADMIXTURES
AIR ENTRAINING ASTM C260
CHEMICAL ADMIXTURES ASTM C 494
AIR CONTENT FOR CONCRETE EXPOSED TO WEATHER: 4 TO 7%.
SLUMP: 4"
CONCRETE STRENGTH: F'C 4,000 PSI AT 28 DAYS
MIXING PER ASTM C94
CURING COMPOUNDS: ASTM C309 OR C1315
c EXECUTION
CONCRETE COVER
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3"
CONCRETE EXPOSED TO EARTH OR WEATHER 2"
CONCRETE NOT EXPOSED TO WEATHER 1-1/2"
ALL FOOTINGS, WALL FOOTINGS, GRADE BEAMS AND PILE/CAISSON CAPS SHALL
BE FORMED UNLESS NOTED.
LAP SPLICE LENGTHS PER ACI 318 CHAPTERS 12 USING A CLASS B SPLICE. ALL
WELDED WIRE FABRIC SHALL BE LAPPED ONE GRID MINIMUM
LOCATE JOINTS AS SHOWN ON PLANS; WHERE NOT SHOWN, CONTROL OR
CONSTRUCTION JOINTS SHALL BE PLACED IN ACCORDANCE WITH ACI
RECOMMENDATIONS I.E., A MAXIMUM PANEL SIZE (IN FEET) EQUAL TO
APPROXIMATELY THREE TIMES THE THICKNESS OF THE SLAB (IN INCHES) IN BOTH
DIRECTIONS.
HOOK ENDS OF BARS INTERRUPTED BY OPENINGS.
HOOK TOP BARS AT ALL CONCRETE EDGES, AT ALL WALL AND SLAB OPENINGS,
PROVIDE 2-#5 BARS X OPENING WIDTH PLUS 4 FEET (2 FEET EACH SIDE) EACH
FACE, UNLESS SHOWN OTHERWISE.
PLACEMENT OF CONCRETE IN COLD WEATHER SHALL COMPLY WITH ACI306
PLACEMENT OF CONCRETE IN HOT WEATHER SHALL COMPLY WITH ACI305
TOLERANCES SHALL MEET ACI 117, ACI 301 AND ACI 318 AS A MINIMUM.
5.2 STEEL BAR JOISTS
a STEEL BAR JOISTS SHALL BE DESIGNED, MANUFACTURED AND
ERECTED IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE'S (SJI)
CODE OF STANDARD PRACTICE.
b JOISTS SHALL BE DESIGNED FOR THE LOADS INDICATED ABOVE. IN
ADDITION TO THE LIVE LOADS LISTED ABOVE, THE BOTTOM CHORD OF
THE JOISTS SHALL BE DESIGNED FOR A CONCENTRATED LOAD OF 300
LBS AT ANY LOCATION ALONG THE LENGTH OF THE BAR JOIST.
c PROVIDE BRIDGING IN ACCORDANCE WITH SJI REQUIREMENTS.
d MAXIMUM LIVE LOAD DEFLECTION L/360; TOTAL LOAD L/240.
e JOISTS SHALL BE REINFORCED WHERE CONCENTRATED LOADS ARE
PLACED BETWEEN PANEL POINTS IN ACCORDANCE WITH THE JOIST
MANUFACTURER'S RECOMMENDATIONS.
f JOISTS SHALL BE PRIMED PAINTED WITH MANUFACTURER'S STANDARD
PRIMER UNLESS NOTED OTHERWISE IN THE PROJECT SPECIFICATION.
5.3 METAL ROOF DECK (MRD)
a METAL ROOF DECK SHALL CONFORM TO STEEL DECK INSTITUTE
SPECIFICATIONS. METAL ROOF DECK TO BE WIDE RIB 1-1/2" -22 GAGE
STEEL DECK, UNLESS NOTED, WITH NESTING SIDE LAPS LAID 3 SPANS
MINIMUM CONTINUOUS. DECK TO BE GALVANIZED.
b UNLESS NOTED, WELD DECK TO SUPPORT MEMBERS WITH 5/8" PUDDLE
WELDS IN A 36/5 PATTERN. PLACE 5/8" DIAMETER PUDDLE WELDS 6" ON
CENTER AT ALL EDGES OF DECK ADJACENT TO WALLS AND OPENINGS.
c FASTEN SIDE LAPS AT 2'-0" MAXIMUM SPACING WITH #10 HEX WASHER
HEAD SELF-DRILLING SCREWS. WELD WASHERS SHALL BE USED FOR
ALL MATERIAL THICKNESSES LESS THAN .028.
d DO NOT SUSPEND ANYTHING FROM METAL ROOF DECK.
e COAT WELDS AND ABRADED AREAS WITH ZINC RICH GALVANIZING
PRIME PAINT.
f DECK MANUFACTURER SHALL PROVIDE REINFORCING FOR ALL
OPENINGS UP TO 18"X18". ALL OPENINGS SHALL BE REINFORCED WITH
L4X4X3/8 FRAMES SPANNING BETWEEN SUPPORT MEMBERS.
5.4 COLD-FORMED METAL FRAMING
a GENERAL:
REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
PERFORMANCE REQUIREMENTS
AISI "SPECIFICATIONS": CALCULATE STRUCTURAL CHARACTERISTICS
OF COLD-FORMED METAL FRAMING ACCORDING TO AISI'S
"SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL
STRUCTURAL MEMBERS"
STRUCTURAL PERFORMANCE: ENGINEER, FABRICATE AND ERECT
COLD-FORMED METAL FRAMING WITH THE MINIMUM PHYSICAL AND
STRUCTURAL PROPERTIES INDICATED ON THE DRAWINGS.
DESIGN LOADS: AS INDICATED ABOVE.
DESIGN FRAMING SYSTEMS TO WITHSTAND DESIGN LOADS WITHOUT
DEFLECTIONS GREATER THAN THE FOLLOWING:
INTERIOR WALLS: LATERAL DEFLECTION OF 1/240 OF THE WALL HEIGHT.
EXTERIOR WALL: LATERAL DEFLECTION OF 1/600 OF THE WALL HEIGHT.
ENGINEERING RESPONSIBILITY: CONTRACTOR TO ENGAGE A
FABRICATOR WHO ASSUMES UNDIVIDED RESPONSIBILITY FOR
ENGINEERING COLD-FORMED METAL FRAMING BY EMPLOYING A
QUALIFIED SSE TO PREPARE DESIGN CALCULATIONS, SHOP DRAWINGS,
AND OTHER STRUCTURAL DATA.
SUBMITTALS: SUBMIT SHOPS DRAWINGS AND CALCULATIONS SEALED
BY A LICENSED STRUCTURAL ENGINEER.
ALL WELDING SHALL COMPLY WITH APPLICABLE PROVISIONS OF AWS
D1.1 "STRUCTURAL WELDING CODE--STEEL" AND AWS D1.3
"STRUCTURAL WELDING CODE--SHEET STEEL."
b MATERIALS
MANUFACTURERS: SECTIONS INDICATED ON DRAWINGS ARE MINIMUMS
AND ARE DESIGNATED USING THE STEEL STUD MANUFACTURER'S
UNIVERSAL DESIGNATOR SYSTEM. MATERIALS:
GALVANIZED-STEEL SHEET: ASTM A 653, ZINC COATED ACCORDING TO
ASTM A 525 (ASTM A 525M), WITH COATING DESIGNATION: G 90 (Z 275) -
EXTERIOR AND GRADE FY= 50 KSI.
FRAMING ACCESSORIES: FABRICATE STEEL-FRAMING ACCESSORIES OF
THE SAME MATERIAL AND FINISH USED FOR FRAMING MEMBERS, WITH
A MINIMUM YIELD STRENGTH OF 50 KSI.
PROVIDE ACCESSORIES OF MANUFACTURER'S STANDARD THICKNESS
AND CONFIGURATION, UNLESS OTHERWISE INDICATED.
ANCHORS, CLIPS, AND FASTENERS ASTM A36 HOT DIP GALVANIZED PER
ASTM A123
POWDER-ACTUATED ANCHORS: FASTENER SYSTEM OF TYPE SUITABLE
FOR APPLICATION INDICATED, FABRICATED FROM
CORROSION-RESISTANT MATERIALS, WITH CAPABILITY TO SUSTAIN,
WITHOUT FAILURE, A LOAD EQUAL TO 10 TIMES THE DESIGN LOAD, AS
DETERMINED BY TESTING PER ASTM E 1190 CONDUCTED BY A
QUALIFIED INDEPENDENT TESTING AGENCY.
MECHANICAL FASTENERS: CORROSION-RESISTANT COATED,
SELF-DRILLING, SELF-THREADING STEEL DRILL SCREWS. HEAD TYPE:
LOW-PROFILE HEAD BENEATH SHEATHING, MANUFACTURER'S
STANDARD ELSEWHERE.
WELDING ELECTRODES: COMPLY WITH AWS STANDARDS.
CONNECTION COMPONENTS TO BE SIMPSON STRONG-TIE.
FABRICATION: USE MANUFACTURER'S STANDARD SECTIONS (WALL
STUDS PUNCHED, TRACKS UN-PUNCHED COMPLYING WITH ASTM A955.
TOLERANCES SHALL MEET ASTM C1007 REQUIREMENTS.
c EXECUTION
INSTALL COLD-FORMED METAL FRAMING AND ACCESSORIES PLUMB,
SQUARE, TRUE TO LINE, AND WITH CONNECTIONS SECURELY
FASTENED, ACCORDING TO MANUFACTURER'S RECOMMENDATIONS
AND THE REQUIREMENTS OF THIS SECTION. CUT FRAMING MEMBERS
BY SAWING OR SHEARING; DO NOT TORCH CUT.
FASTEN COLD-FORMED METAL FRAMING MEMBERS BY WELDING OR
SCREW FASTENING, AS STANDARD WITH FABRICATOR. WIRE TYING OF
FRAMING MEMBERS IS NOT PERMITTED.
COMPLY WITH AWS REQUIREMENTS AND PROCEDURES FOR WELDING,
APPEARANCE AND QUALITY OF WELDS, AND METHODS USED IN
CORRECTING WELDING WORK.
ERECTION TOLERANCES: PER ASTM C1007
SOILS (IBC 2018 TABLE 1705.6)
1 VERIFY BEARING CAPACITY BELOW SHALLOW FOUNDATIONS (P)
2 VERIFY EXCAVATIONS EXTEND TO PROPER DEPTH AND REACHED PROPER MATERIAL (P).
3 PERFORM CLASSIFICATION AND TESTING OF COMPACTED MATERIAL (P)
4 VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING PLACEMENT AND
COMPACTION OF COMPACTED MATERIAL (C).
5 PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT SITE HAS BEEN
PROPERLY PREPARED (P)
6 VERIFY SOIL IMPROVEMENT HAS BEEN PERFORMED PROPERLY (P)
1.9 STRUCTURAL TESTS AND INSPECTIONS (IBC 2018)
a AN INDEPENDENT APPROVED AGENCY SHALL PROVIDE SPECIAL INSPECTIONS AND TESTS
DURING CONSTRUCTION IN ACCORDANCE WITH CHAPTER 17 OF IBC 2018.
b THE APPROVED AGENCY'S SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED FOR
CONFORMANCE TO THE APPROVED DESIGN DRAWINGS AND SPECIFICATIONS.
c THE APPROVED AGENCY SHALL KEEP RECORDS OF ALL SPECIAL INSPECTIONS AND TESTS AND
SUBMIT REPORTS TO THE BUILDING OFFICIAL AND THE SER.
d ALL DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE COR FOR
CORRECTION. IF UNCORRECTED, THE APPROVED AGENCY SHALL NOTIFY THE BUILDING OFFICIAL
AND COR.
e REFER TO IBC 2018 1704.5 FOR SUBMITTALS TO THE BUILDING OFFICIAL IN ADDITION TO THE
REPORTS.
f THE APPROVED AGENCY SHALL SUBMIT A FINAL REPORT STATING WHETHER THE WORK
REQUIRING SPECIAL INSPECTION WAS IN CONFORMANCE WITH THE APPROVED CONTRACT
DOCUMENTS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THIS CODE.
g QUALITY CONTROL SHALL BE THE RESPONSIBILITY OF THE FABRICATOR/ERECTOR IN
ACCORDANCE WITH AISC360-16 CHAPTER N.
h JOB SITE VISITS BY THE SER DO NOT CONSTITUTE AN OFFICIAL SPECIAL INSPECTION.
STATEMENT OF SPECIAL INSPECTIONS:
a REFER TO THE REFERENCED DOCUMENTS (IBC 2018 CHAPTER 17, AISC 360-16 CHAPTER N, ACI530-13 CHAPTER 3, ) FOR ADDITIONAL DESCRIPTIONS OF REQUIREMENTS.
b STRUCTURAL OBSERVATIONS FOR SEISMIC NOT REQUIRED c STRUCTURAL OBSERVATIONS FOR WIND NOT REQUIRED .
d THE FOLLOWING LIST OF MATERIALS AND WORK REQUIRE SPECIAL INSPECTIONS (P) PERIODIC; (C)
CONTINUOUS
STRUCTURAL STEEL (1705.2 - AISC360-16 CHAPTER N)
1 INSPECTION TASKS PRIOR TO WELDING SHOP/FIELD (AISC360-10 TABLE N5.4-1 & AWS D1.1) a REVIEW WELDING PROCEDURE SPECIFICATIONS (WPS) & WELDING CONSUMABLES (C) b FIT UP GROOVE AND FILLET WELDS (P) c CONFIGURATION OF ACCESS HOLES (P) 2 INSPECTION TASKS DURING WELDING SHOP/FIELD (AISC360-10 TABLE N5.4-2 & AWS D1.1) a QUALIFIED WELDERS (C) b CONTROL AND HANDLING OF CONSUMABLES (C) c NO WELDING OVER TACK WELDS (C) d ENVIRONMENTAL CONDITIONS (C) e WPS FOLLOWED (C) f WELDING TECHNIQUES (C)
3 INSPECTION TASKS AFTER WELDING SHOP/FIELD (AISC360-10 TABLE N5.4-3 & AWS D1.1)
a WELDS CLEANED (C) b SIZE, LENGTH, LOCATION OF WELDS (C) c WELDS MEET VISUAL ACCEPTANCE CRITERIA (C) d CJP GROOVE WELD NDT PER AWS D1.1 (C)
4 INSPECTION TASKS PRIOR TO BOLTING (AISC360-10 TABLE N5.6-1)
a BOLT MATERIAL GRADE b PROPER FASTENERS USED PER CONTRACT DOCUMENTS (P) c PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL (P) d CONNECTION ELEMENTS INCLUDING FAYING SURFACES MEET REQUIREMENTS (P) e PROPER STORAGE OF FASTENER COMPONENTS (P)
5 INSPECTION TASKS DURING BOLTING (AISC360-10 TABLE N5..6-2)
a FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND POSITIONED AS
REQUIRED (P).
b JOINT BROUGHT TO SNUG TIGHT CONDITION (P) c FASTENER COMPONENT NOT TURNED BY WRENCH PREVENTED FROM ROTATING (P) d FASTENERS PRETENSIONED PER RCSC SPECIFICATION (P)
6 INSPECTION TASKS AFTER BOLTING (AISC360-10 TABLE N5.6-3)
a DOCUMENT ACCEPTED OR REJECTED BOLTED CONNECTIONS (C)
7 INSPECTION OF ANCHOR RODS IN CONFORMANCE WITH CONTRACT DOCUMENTS. (P)
8 INSPECTION OF STEEL FRAME/CONNECTION DETAILS IN CONFORMANCE WITH CONTRACT
DOCUMENTS. (P)
9 INSPECTION OF STEEL ELEMENTS OF COMPOSITE CONSTRUCTION PRIOR TO CONCRETE
PLACEMENT (AISC360-16 TABLE N6.1)
a PLACEMENT OF STEEL DECK (C) b PLACEMENT OF STEEL HEADED STUD (C) c DOCUMENT ACCEPTANCE OR REJECTION (C)
10 INSPECTION OF METAL DECK DIAPHRAGM CONNECTIONS TO STEEL FRAMING. (P)
11 OPEN WEB STEEL JOISTS (IBC 2018 TABLE 1705.2.3)
a END CONNECTIONS (P) b BRIDGING (P) c MEMBER SIZES IN ACCORDANCE WITH CONTRACT DOCUMENTS (P)
12 COLD FORMED STEEL FRAMING
a MATERIAL GRADES (P) b FRAMING DETAILS AND CONNECTIONS PER CONTRACT DOCUMENTS (P)
CONCRETE CONSTRUCTION (IBC 2018 TABLE 1705.3)
1 REINFORCEMENT PLACEMENT (P)
2 REINFORCING BAR WELDING (P)
3 ANCHORS CAST IN CONCRETE (P)
4 POST INSTALLED ANCHORS
a ADHESIVE (C) b MECHANICAL (P)
5 VERIFY USE OF REQUIRED MIX (P)
6 STRENGTH, SLUMP, AIR, TEMPERATURE TEST OF CONCRETE PRIOR TO PLACEMENT (C)
7 CONCRETE PLACEMENT (C)
8 VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES (P)
9 INSPECT ERECTION OF PRECAST MEMBERS INCLUDING CONNECTIONS (P)
10 INSPECT FORMWORK (P)
5 METALS
5.1 STRUCTURAL STEEL
a GENERAL
ALL STRUCTURAL STEEL WORK SHALL CONFORM TO THE AISC 360-16
"SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS",
"SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490
BOLTS" 2009, "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS
AND BRIDGES," 2016 AND AWS D1.1 2016.
THE PROVISIONS OF THE ALLOWABLE STRENGTH DESIGN METHOD
(ASD) WAS USED AS A BASIS FOR DESIGN. ALL FORCES/REACTIONS
INDICATED ON THE DESIGN DOCUMENTS ARE THEREFORE
NON-FACTORED ASD FORCES/REACTIONS.
THE CONTRACTOR'S STRUCTURAL STEEL DETAILER SHALL PREPARE
STEEL ERECTION AND SHOP DRAWINGS IN ACCORDANCE WITH THE
GUIDELINES AND GOOD PRACTICES NOTED IN THE AISC “DETAILING FOR
STEEL CONSTRUCTION.” THIRD EDITION
STEEL CONNECTIONS ARE DESIGNATED AS A DESIGN DELEGATED
COMPONENT TO BE DESIGNED BY THE CONTRACTOR'S SSE.
SUBMITTALS
CHECKED STEEL SHOP DRAWINGS: PREPARED IN ACCORDANCE WITH
AISC DETAILING FOR STEEL CONSTRUCTION 3RD ED.
CONNECTION CALCULATIONS PREPARED, SIGNED AND SEALED BY
CONTRACTOR'S SSE.
MATERIAL CERTIFICATES (UPON REQUEST)
WELDING CERTIFICATES (UPON REQUEST)
b MATERIALS ALL STRUCTURAL STEEL SHAPES SHALL BE ASTM A992 (Fy=50 ksi)
ALL STRUCTURAL STEEL PLATES AND ANGLES SHALL BE ASTM A36
(Fy=36 KSI).
ALL STRUCTURAL TUBES SHALL BE ASTM A500 GRADE B (Fy=46 KSI).
ALL STRUCTURAL PIPES SHALL BE ASTM A53 GRADE B (Fy=35 KSI).
ALL ANCHOR RODS ASTM F1554-36
ALL WELDING SHALL CONFORM TO AMERICAN WELDING SOCIETY
"STRUCTURAL WELDING CODE", AWS D1.1.
ALL WELD ELECTRODES SHALL BE E70XX AND ALL WELDING SHALL BE
PERFORMED BY CERTIFIED WELDERS. ALL WELDING SHALL BE TO
CLEAN BARE STEEL.
PROVIDE FULL SIZE 1/4" SETTING PLATES ON 4,000 PSI NON-SHRINK
GROUT FOR ALL COLUMNS AND (4)-3/4" DIAMETER ASTM F-1554-36
ANCHOR BOLTS, UNLESS NOTED.
ERECT ALL MEMBERS WITH NATURAL CAMBER UP, EXCEPT FOR
CERTAIN CANTILEVERED MEMBERS.
PROVIDE SUB-FRAMING FOR EQUIPMENT SUPPORTED ON OR
SUSPENDED FROM THE STRUCTURE.
ALL STEEL SHALL BE GALVANIZED
CONNECTIONS SHOWN ON THE DESIGN DRAWINGS ARE CONCEPTUAL
ONLY.
CONNECTIONS ARE A DELEGATED DESIGN ITEM TO BE DESIGNED BY
CONTRACTOR'S SSE.
CONNECTIONS SHALL BE IN ACCORDANCE WITH AISC 360-16 USING
ALLOWABLE STRENGTH (ASD) DESIGN BASIS. POSTED CONNECTION
FORCES ARE ASD.
DESIGN SHEAR CONNECTIONS FOR THE LARGER OF POSTED FORCES
ON THE DESIGN DRAWINGS AND 50% (75% FOR COMPOSITE BEAMS) OF
THE MAXIMUM TOTAL LOAD FOR THE SPECIFIED BEAM AND SPAN IN
AISC “STEEL CONSTRUCTION MANUAL” TABLE 3-6.
DESIGN MOMENT CONNECTIONS FOR FULL MOMENT CAPACITY OF THE
MEMBER OR THE POSTED MOMENT ALONG WITH THE SHEAR LOADS
NOTED ABOVE.
AXIALLY LOADED MEMBERS SHALL BE DESIGNED USING THE POSTED
LOADS AND THE AISC UNIFORM FORCE METHOD.
ALL SHEAR CONNECTIONS SHALL BE AS A MINIMUM FULL DEPTH OF
MEMBER.
ALL BOLTS SHALL BE ASTM A325 FULLY TENSIONED BEARING BOLTS
WITH SHORT SLOTTED HOLES UNLESS NOTED. A325 SLIP CRITICAL
BOLTS SHALL BE USED FOR ALL MOMENT CONNECTIONS AND AXIALLY
LOADED MEMBERS.
ALL WELD SIZES SHOWN ARE SIZED FOR LOAD ONLY. WELDS SHALL BE
INCREASED IN SIZE AS REQUIRED TO MEET AISC MINIMUMS.
ALL GROOVE WELDS SHOWN ARE FULL PENETRATION WELDS UNLESS
NOTED OTHERWISE.
WELDS NOTED AS PARTIAL PENETRATION GROOVE WELDS SHOW
"EFFECTIVE" SIZE OF WELD.
WELD JOINTS SHALL BE DETAILED BASED ON PROCESS USED AND
POSITION OF WELD TO MEET THE "EFFECTIVE" SIZE SHOWN ON THE
DRAWINGS.
c EXECUTION
VERIFY THAT FIELD CONDITIONS ARE ACCEPTABLE AND ARE READY TO
RECEIVE WORK.
STEEL ERECTION TOLERANCES SHALL BE IN ACCORDANCE WITH THE
CODE OF STANDARD PRACTICE.
STRUCTURAL ABBREVIATIONS LEGEND:
A.B.S. - ANCHOR BOLTS
ARCH - ARCHITECTURAL DRAWINGS
B/ - BOTTOM OF
BOTT. - BOTTOM
CGF - COMPACTED GRANULAR FILL
CL - CENTERLINE
CMU - CONCRETE MASONRY UNITS
CONT. - CONTINUOUS
CONC - CONCRETE
E - EXISTING MATERIAL
FT - FOOT
HD - HOLD DOWN
HKD - HOOKED
k - KIP
LBS - POUNDS
MEP - MECHANICAL, ELECTRICAL, PLUMBING DRAWINGS
N - NEW MATERIAL
O.C. - ON CENTER
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PCF - POUNDS PER CUBIC FOOT
RD - ROOF DRAIN
STL - STEEL
SOG - SLAB ON GRADE
T/ - TOP OF
U.N. - UNLESS NOTED
VB - VAPOR BARRIER
VIF - VERIFY IN FIELD
W/ - WITH
# - POUNDS OR NUMBER
SSE - SPECIALTY STRUCTURAL ENGINEER
SER - STRUCTURAL ENGINEER OF RECORD
CONTRACTOR - DESIGNATED REPRESENTATIVE FOR CONSTRUCTION
COR - CONTRACTING OFFICER'S REPRESENTATIVE
1.4 SLEEVES, ANCHORAGES, OPENINGS, ETC.
a IN GENERAL, STRUCTURAL DRAWINGS DO NOT SHOW EQUIPMENT PADS, DRAINS, HOLES, ANCHORAGES, INSERTS AND SLEEVES FOR ITEMS
PASSING THROUGH OR ATTACHED TO CONCRETE OR FRAMING. REFER TO
ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
PROJECT SPECIFICATIONS. ADJUST EQUIPMENT PADS AND SUB FRAMING
TO FIT EQUIPMENT FURNISHED.
b PROVIDE SUB FRAMING FOR EQUIPMENT SUPPORTED ON OR SUSPENDED
FROM THE STRUCTURE.
1.5 STRUCTURAL STABILITY AND CONSTRUCTION
a INDIVIDUAL STRUCTURAL COMPONENTS ARE DESIGNED TO SUPPORT
LOADS IN THEIR FINAL ERECTED POSITION AS PART OF THE TOTAL
COMPLETED STRUCTURE.
b CONTRACTOR TO PROVIDE TEMPORARY GUYING AND BRACING AS
REQUIRED UNTIL ALL CONSTRUCTION AFFECTING LATERAL STABILITY IS
COMPLETED.
c CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR STABILITY OF
STRUCTURE, ITS PARTS BY USE OF GUYING, BRACING, SHORING,
BARRICADES, SAFETY RAILINGS AND DEVICES DURING THE ENTIRE PERIOD
OF CONSTRUCTION.
d CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL JOB SITE SAFETY
AND MEANS AND METHOD OF CONSTRUCTION.
1.6 SHOP DRAWINGS AND TEST REPORTS
a CONTRACTOR SHALL CHECK ALL SHOP DRAWINGS BEFORE SUBMITTAL TO
SER FOR REVIEW.
b CONTRACTIR SHALL PREPARE A SHOP DRAWING SUBMITTAL SCHEDULE
WITH A MINIMUM OF TWO WEEKS INCLUDED FOR THE SER'S REVIEW OF
EACH SUBMITTAL LISTED BELOW.
c REVIEW BY SER WILL BE FOR CONFORMANCE TO GENERAL LAYOUT AND
DESIGN INTENT ONLY.
d CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ACCURACY OF
DIMENSIONS, FABRICATION, FIT UP OF PARTS AND BILLS OF MATERIALS.
e CONTRACTOR SHALL COORDINATE WORK OF VARIOUS TRADES AND MAKE
NECESSARY FIELD MEASUREMENTS.
f THE CONTRACT SPECIFICATIONS PROVIDE A COMPLETE LISTING OF
SUBMITTALS. THE FOLLOWING IS A SUMMARY OF THE REQUIRED
SUBMITTALS:
CONCRETE
CONCRETE MIX DESIGNS WITH ASSOCIATED
HISTORICAL TEST DATA
REINFORCING STEEL PLACEMENT DRAWINGS PER
ACI 315
STRUCTURAL STEEL
STRUCTURAL STEEL SHOP DRAWINGS
CONNECTION DESIGN SIGNED AND SEALED BY
LICENSED SSE.
COLD FORMED METAL FRAMING
COLD FORMED SHOP DRAWINGS
DESIGN CALCULATIONS SIGNED AND SEALED BY
LICENSED SSE.
STEEL BAR JOISTS
SHOP PLACEMENT DRAWINGS
DESIGN CALCULATIONS SIGNED AND SEALED BY
LICENSED SSE.
METAL DECK (ROOF)
SHOP DRAWINGS
1.7 DEFERRED SUBMITTALS - OWNER SPECIFIED DESIGN DELEGATED
COMPONENTS TO BE PROVIDED BY CONTRACTOR'S ENGINEER
a CERTAIN COMPONENTS OF THE COMPLETED
CONSTRUCTION ARE DESIGN DELEGATED TO THE
MANUFACTURER OF THE COMPONENT. THE
MANUFACTURER'S SSE SHALL BE RESPONSIBLE FOR THE DESIGN OF THE
COMPONENT. THE FOLLOWING ARE DESIGNATED TO BE DESIGN
DELEGATED COMPONENTS ON THIS PROJECT:
b STRUCTURAL STEEL CONNECTIONS c COLD FORMED STEEL FRAMING d TEMPORARY SHORING AND BRACING e TEMPORARY EARTH RETENTION SYSTEMS f OTHER WORK AS LISTED ON DRAWINGS, SPECIFICATIONS AND CUSTOMARY INDUSTRY
STANDARDS. WHERE DELEGATION OF DESIGN IS
SPECIFIED,
g THE MANUFACTURER SHALL BE RESPONSIBLE FOR RETAINING THE
SERVICES OF A LICENSED SPECIALTY STRUCTURAL ENGINEER (SSE) IN
THE STATE HAVING JURISDICTION. THE SSE SHALL DESIGN AND DETAIL
COMPONENTS TO MEET GOVERNING BUILDING CODES, STANDARDS AND
THE SPECIFIED PERFORMANCE CRITERIA. SIGNED AND SEALED
CALCULATIONS SHALL BE SUBMITTED FOR RECORD. THE DESIGN
DELEGATED SSE SHALL BE SOLELY RESPONSIBLE FOR THE DESIGN OF
THE COMPONENT.
h SSE SUBMITTALS WILL BE REVIEWED BY THE SER FOR LOADING CRITERIA
AND GENERAL CONFORMANCE TO THE PRIMARY STRUCTURAL SYSTEM.
1.8 DEMOLITION
a THE ARCHITECTURAL DEMOLITION DRAWINGS INDICATE THE GENERAL
AREAS OF DEMOLITION. THE CONTRACTOR SHALL VERIFY IN THE FIELD
ALL ITEMS TO BE REMOVED TO MEET THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS.
b THE CONTRACTOR SHALL CAREFULLY REMOVE ONLY THE EXISTING ITEMS
IDENTIFIED ON THE ARCHITECTURAL AND STRUCTURAL DRAWINGS.
c IN NO CASE SHALL THE REMOVAL OF ANY PORTION OF THE EXISTING
STRUCTURE BE PERFORMED IN SUCH A WAY AS TO AFFECT THE
STRUCTURAL INTEGRITY OF THE REMAINING PORTION OF THE BUILDING.
d THE CONTRACTOR SHALL NOTIFY COR IMMEDIATELY OF ANY STRUCTURAL
ITEMS WHICH NEED TO BE DEMOLISHED BUT ARE NOT CLEARLY
IDENTIFIED ON THE STRUCTURAL OR ARCHITECTURAL DRAWINGS.
e THE CONTRACTOR SHALL MINIMIZE THE EXTENT OF THE DEMOLITION TO
THE EXISTING STRUCTURE TO ONLY THAT REQUIRED TO INSTALL THE NEW
BUILDING MODIFICATIONS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
C :\U se rs
\p cw ur \W or k\
VA
B an cr of t P ro je ct s\
VA
S al is bu ry
N C
\J W
A\ S0
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
JOHNSONWILBUR ADAMS, INC.
Wheaton, Illinois 60187 330 S. Naperville Road Suite 300
STRUCTURAL ENGINEERING
06/02/2022
STRUCTURAL -
GENERAL NOTES
MW PW
S010
NTS
STRUCTURAL GENERAL NOTES
S010
A
B
C1 / P1 F5.0
(-)3'-0"
'-1
0" 31'-10"
'-9
3/ 8"
(V.
I.F
C1 / P1 F5.0
(-)3'-0"
C1 / P1 F5.0
(-)3'-0"
C1 / P1 F5.0
(-)3'-0"
T/ EXIST. FDN.
EL. 0'-0" (V.I.F.)
T/ EXIST. FTG.
EL.(-)3'-0" (V.I.F.)
EXIST. CONC. STOOP (V.I.F.)
S200
TYP.
EQUAL (V.I.F.) EQUAL (V.I.F.)
CL. EXISTING BUILDING
T/ EXIST. FLOOR
EL. 0'-0" (V.I.F.)
T/ PIER
EL. 0'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
C :\U se rs
\p cw ur \W or k\
VA
B an cr of t P ro je ct s\
VA
S al is bu ry
N C
\J W
A\ 2-
SB
1.
dw g 6/
/2
:3
9:
P M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
JOHNSONWILBUR ADAMS, INC.
Wheaton, Illinois 60187 330 S. Naperville Road Suite 300
STRUCTURAL ENGINEERING
06/02/2022
GENERAL SHEET NOTES
CONTRACTOR NOTE:
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID TO ENSURE ALL
CONFLICTS FOR INSTALLATION OF NEW WORK HAS BEEN IDENTIFIED AND ANY
WORK REQUIRED TO MODIFY EXISTING IS INCLUDED IN BID PRICE.
(E) - INDICATES EXISTING CONSTRUCTION; VERIFY IN FIELD
(N) - INDICATES PROPOSED NEW CONSTRUCTION
STRUCTURAL SCHEDULES
COLUMN SCHEDULE:
C1 - GALV. HSS10x10x1/2 W/ GALV. BASE PL. 3/4"x16"x16" & (4)-3/4"Ø F1554-36 ANCHOR RODS
CONCRETE PIER SCHEDULE:
P1 - 26"x26" CONC. PIER W/ 8-#6 VERT. REINFORCING & (2)-#4 TIES @ 12" O.C.
T/ PIER 6" ABOVE FINISH GRADE
FOOTING SCHEDULE:
F5.0 - 5'-0"x5'-0"x1'-3" W/ 6-#7 EACH WAY, BOTT.
STRUCTURAL - BUILDING 2
ENTRY CANOPY FOUNDATION PLAN
MW PW
2-SB101
0 2' 4' 8' 16'1/8"=1'-0"1 BUILDING 2 - ENTRY CANOPY FOUNDATION PLAN
NORTH
C? / P?
F?
(-)X'-X"
- INDICATES COLUMN MARK / PIER MARK; SEE SCHEDULE BELOW
- INDICATES FOOTING MARK; SEE SCHEDULE BELOW
- INDICATES TOP OF FOOTING ELEVATION BELOW FINISH GRADE,
SEE CIVIL SHEETS FOR GRADING PLAN.
B
8 E
QU
AL
SP
AC
ES
'-1 0"
31'-10"
SE
E A
RC
H.
SH
TS
ME
TA
L R
OO
F D
EC
K
W24x55
W24x55
W2 4x5
W2 4x5
W16x26
W16x26
W16x26
W16x26
W16x26
W16x26
W16x26
COORD. W/
ARCH. SHTS.
COORD. W/
ARCH. SHTS.
EQUAL (V.I.F.) EQUAL (V.I.F.)
CO
OR
D.
W/
AR
CH
. S
HT
S.
CO
OR
D.
W/
AR
CH
. S
HT
S.
C12x20.7
C12x20.7
C1 2x2
0.7
C1
W8x18
W8x18
W8x18, TYP.
W12x19 W12x19
W12x19 W12x19
C1 2x2
0.7
W8x18, TYP.
S300
S300
S300
TYP.
S300
S300
CL. EXIST. BUILDING (V.I.F.)
3 EQUAL SPACES
V=35k M=100k-ft
V=35k M=100k-ft
V=35k M=100k-ft
V=35k M=100k-ft
V=35k M=100k-ft
V=35k M=100k-ft
V=35k M=100k-ft
V=35k M=100k-ft
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
C :\U se rs
\p cw ur \W or k\
VA
B an cr of t P ro je ct s\
VA
S al is bu ry
N C
\J W
A\ 2-
SF
1.
dw g 6/
/2
:3
9:
P M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
JOHNSONWILBUR ADAMS, INC.
Wheaton, Illinois 60187 330 S. Naperville Road Suite 300
STRUCTURAL ENGINEERING
06/02/2022
SHEET KEY NOTES -
GENERAL SHEET NOTES
1 PROVIDE 1 1/2" - 22 GAUGE GALVANIZED METAL ROOF DECK, TYPE B (WIDE RIB). DECK
SHALL BE CONTINUOUS OVER THREE SUPPORTS MINIMUM PER SDI DIAPHRAGM MANUAL.
WELD IN 36/5 PATTERN & PROVIDE MNIMUM 2 STITCH CONNECTORS BETWEEN SUPPORTS.
WELD WITH 5/8"Ø PUDDLE WELDS @ 6" O.C. AROUND PERIMETER.
CONTRACTOR NOTE:
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID TO ENSURE ALL
CONFLICTS FOR INSTALLATION OF NEW WORK HAS BEEN IDENTIFIED AND ANY
WORK REQUIRED TO MODIFY EXISTING IS INCLUDED IN BID PRICE.
(E) - INDICATES EXISTING CONSTRUCTION; VERIFY IN FIELD
(N) - INDICATES PROPOSED NEW CONSTRUCTION
STRUCTURAL - BUILDING 2
ENTRY CANOPY ROOF FRAMING PLAN
MW PW
2-SF101
T/ STEEL, COORDINATE WITH ARCHITECTURAL SHTS.
INDICATES A MOMENT CONNECTION. CONNECTION SHALL
BE DESIGNED BY STEEL FABRICATOR FOR SERVICE
MOMENT INDICATED ON PLAN
0 2' 4' 8' 16'1/8"=1'-0"1 BUILDING 2 - ENTRY CANOPY ROOF FRAMING PLAN
NORTH
M = BENDING MOMENT REACTION k-ft (ASD) V = VERTICAL SHEAR REACTION k (ASD)
ALL STEEL AND CONNECTIONS SHALL BE HOT-DIPPED GALVANIZED
C1 / P1 F4.0
(-)3'-0"
B
C
17'-4"
'-0
'-0
SE
E A
RC
H.
(V.
I.F
1'-5" (V.I.F.) 1'-5" (V.I.F.)
14'-10 3/4" (V.I.F.) 20'-2" (V.I.F.) 14'-10 3/4" (V.I.F.)
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
EQUAL (V.I.F.) EQUAL (V.I.F.)
CL. EXISTING BUILDING (V.I.F.)
S200
1 TYP.
EXIST. CONC. PIER
(-)3'-0" (V.I.F.)
SH
TS
A D
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
15'-0" 15'-0"
T/ EXIST. FLOOR
EL. 0'-0", SEE CIVIL
T/ PIER, TYP.
EL. 0'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
C :\U se rs
\p cw ur \W or k\
VA
B an cr of t P ro je ct s\
VA
S al is bu ry
N C
\J W
A\
-S B1
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
JOHNSONWILBUR ADAMS, INC.
Wheaton, Illinois 60187 330 S. Naperville Road Suite 300
STRUCTURAL ENGINEERING
06/02/2022
GENERAL SHEET NOTES
CONTRACTOR NOTE:
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID TO ENSURE ALL
CONFLICTS FOR INSTALLATION OF NEW WORK HAS BEEN IDENTIFIED AND ANY
WORK REQUIRED TO MODIFY EXISTING IS INCLUDED IN BID PRICE.
(E) - INDICATES EXISTING CONSTRUCTION; VERIFY IN FIELD
(N) - INDICATES PROPOSED NEW CONSTRUCTION
STRUCTURAL SCHEDULES
COLUMN SCHEDULE:
C1 - GALV. HSS10x10x1/2 + GALV. BASE PL. 3/4"x16"x16" & (4)-3/4"Ø F1554-36 ANCHOR RODS
CONCRETE PIER SCHEDULE:
P1 - 26"x26" CONCRETE PIER W/ 8-#6 VERT. REINFORCING & (2)-#4 TIES @ 12" O.C.
T/ PIER 6" ABOVE FINISH GRADE
FOOTING SCHEDULE:
F4.0 - 4'-0"x4'-0"x1'-0" W/ 5-#5 EACH WAY, BOTT.
STRUCTURAL - BUILDING 21
ENTRY CANOPY FOUNDATION PLAN
MW PW
21-SB101
0 2' 4' 8' 16'1/8"=1'-0"1 BUILDING 21 - ENTRY CANOPY FOUNDATION PLAN
NORTH
C? / P?
F?
(-)X'-X"
- INDICATES COLUMN MARK / PIER MARK; SEE SCHEDULE BELOW
- INDICATES FOOTING MARK; SEE SCHEDULE BELOW
METAL ROOF DECK
B
C
3 EQUAL SPACES = 17'-4"
'-0
'-0
4'- 1 1
/2" 4'-
5 1 /4"
(V .I.F
1'-5" (V.I.F.) 1'-5" (V.I.F.)
14'-10 3/4" (V.I.F.) 20'-2" (V.I.F.) 14'-10 3/4" (V.I.F.)
W16x36
W1 6x3
W1 6x3
W16x36
W16x36
W1 6x3
W1 6x3
S300
CO
OR
D.
W/
AR
CH
. S
HT
S.
CO
OR
D.
W/
AR
CH
. S
HT
S.
S300
S300
W1 6x2
W1 6x2
W1 6x2
W1 6x2
W1 6x2
W1 6x2
C1 2x2
0.7
C1 2x2
0.7
C1 2x2
0.7
C1 2x2
0.7
C12x20.7
S300
S300
S300
S300
COORD. W/
ARCH. SHTS.
COORD. W/
ARCH. SHTS.
3'- 5 1
/2" 4'-
3 E
QU
AL
SP
AC
ES
2 E Q.
SP
AC
ES 1'-10" 1'-10"
C12x20.7 C12x20.7
SIM.
TYP.,
W8x18, TYP.
W1 6x3
A
W1 6x3
W16x36
W16x36
W16x36
W1 6x2
W1 6x2
W1 6x2
W1 6x2
D
W1 6x3
W1
6x3
W16x36
W16x36
W1 6x2
W1 6x2
W1 6x2
W1 6x2
W8x18, TYP.
W8x18, TYP.
3 EQUAL SPACES = 15'-0" 3 EQUAL SPACES = 15'-0"
W16x36
V= k M= k-f t
V= k M= k-f t
V= k M= k-f t
V= k M= k-f t
V= k M= k-f t
V= k M= k-f t
V= k M= k-f t
V= k M= k-f t
V=20k M=30k-ft
V=20k M=30k-ft
C12x20.7
V=20k M=30k-ft
V=20k M=30k-ft
V=20k M=25k-ft
TYP. MOMENT CONNECTION LOADS, U.N.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
C :\U se rs
\p cw ur \W or k\
VA
B an cr of t P ro je ct s\
VA
S al is bu ry
N C
\J W
A\
-S F1
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
JOHNSONWILBUR ADAMS, INC.
Wheaton, Illinois 60187 330 S. Naperville Road Suite 300
STRUCTURAL ENGINEERING
06/02/2022
GENERAL SHEET NOTES
CONTRACTOR NOTE:
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID TO ENSURE ALL
CONFLICTS FOR INSTALLATION OF NEW WORK HAS BEEN IDENTIFIED AND ANY
WORK REQUIRED TO MODIFY EXISTING IS INCLUDED IN BID PRICE.
STRUCTURAL - BUILDING 21
ENTRY CANOPY ROOF FRAMING PLAN
MW PW
21-SF101
0 2' 4' 8' 16'1/8"=1'-0"1 BUILDING 21 - ENTRY CANOPY ROOF FRAMING PLAN
NORTH
SHEET KEY NOTES -
1 PROVIDE 1 1/2" - 22 GAUGE GALVANIZED METAL ROOF DECK, TYPE B (WIDE RIB). DECK
SHALL BE CONTINUOUS OVER THREE SUPPORTS MINIMUM PER SDI DIAPHRAGM MANUAL.
WELD IN 36/5 PATTERN & PROVIDE MNIMUM 2 STITCH CONNECTORS BETWEEN SUPPORTS.
WELD WITH 5/8"Ø PUDDLE WELDS @ 6" O.C. AROUND PERIMETER.
(E) - INDICATES EXISTING CONSTRUCTION; VERIFY IN FIELD
(N) - INDICATES PROPOSED NEW CONSTRUCTION
T/ STEEL, COORDINATE WITH ARCHITECTURAL SHTS.
INDICATES A MOMENT CONNECTION. CONNECTION SHALL
BE DESIGNED BY STEEL FABRICATOR FOR SERVICE
MOMENT INDICATED ON PLAN
M = BENDING MOMENT REACTION k-ft (ASD)
B
A
13'-2"
28'- 8"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
C1 / P1 F4.0
(-)3'-0"
S200
TYP.
6'-9 1/2"
6'-4 1/2"
(V.I.F.)
(V.I.F.)
CL. EXIST. COORIDOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
C :\U se rs
\p cw ur \W or k\
VA
B an cr of t P ro je ct s\
VA
S al is bu ry
N C
\J W
A\
-S B1
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
JOHNSONWILBUR ADAMS, INC.
Wheaton, Illinois 60187 330 S. Naperville Road Suite 300
STRUCTURAL ENGINEERING
06/02/2022
GENERAL SHEET NOTES
CONTRACTOR NOTE:
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID TO ENSURE ALL
CONFLICTS FOR INSTALLATION OF NEW WORK HAS BEEN IDENTIFIED AND ANY
WORK REQUIRED TO MODIFY EXISTING IS INCLUDED IN BID PRICE.
(E) - INDICATES EXISTING CONSTRUCTION; VERIFY IN FIELD
(N) - INDICATES PROPOSED NEW CONSTRUCTION
STRUCTURAL SCHEDULES
COLUMN SCHEDULE:
C1 - GALV. HSS10x10x3/8 + GALV. BASE PL. 3/4"x16"x16" W/ (4)-3/4"Ø F1554-36 ANCHOR RODS
CONCRETE PIER SCHEDULE:
P1 - 24"x24" W/ 8-#6 VERT. REINFORCING & (2)-#4 TIES @ 12" O.C.
T/ PIER 6" ABOVE FINISH GRADE
FOOTING SCHEDULE:
F4.0 - 4'-0"x4'-0"x1'-0" W/ 5-#6 EACH WAY, BOTT.
STRUCTURAL - BUILDING 42
ENTRY CANOPY FOUNDATION PLAN
MW PW
42-SB101
0 2' 4' 8' 16'1/8"=1'-0"1 BUILDING 42 - ENTRY CANOPY FOUNDATION PLAN
NORTH
C? / P?
F?
(-)X'-X"
- INDICATES COLUMN MARK / PIER MARK; SEE SCHEDULE BELOW
- INDICATES FOOTING MARK; SEE SCHEDULE BELOW
META
L R
OOF D
ECK
B
A
13'-2"
5 EQUAL SPACES = 28'
-8"
W14x
W14x26 W14x
W14x26 W14x26
W14x26 W14x26
W14x26
C12x20.7
C12x 20.7
C12x 20.7
C12x20.7 s300 s300
S300
TYP.
TYP.
TYP.
COORD. W/
ARCH. SHTS.
COORD. W/
ARCH. SHTS.
COORD. W/
ARCH. SHTS.
COORD. W/
ARCH. SHTS.
W8x18, TYP.
W8x18, TYP.
W8x18
W8x18
W8x18
W8x18
EXISTING STEEL
ROOF CANOPY (V.I.F.)
TYP. MOMENT LOADS:
V=20k M=25k-ft
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
C :\U se rs
\p cw ur \W or k\
VA
B an cr of t P ro je ct s\
VA
S al is bu ry
N C
\J W
A\
-S F1
.d w g
6/
/2
:3 9:
P
M
CONSTRUCTION BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
CONSTRUCT ENTRY CANOPIES
BUILDING 2, 21, 42, AND
PARKING GARAGE
SALISBURY, NC
659-22-103
2, 21, 42, PG
Project Director
Revisions: Date:
www. bancroft-ae.com
BAE PROJECT NO. 21-106
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. VA36C24621C005015% SCHEMATIC DESIGN SUBMISSION 09/02/2021
65% DESIGN DEVELOPMENT SUBMISSION 12/01/2021
100% CONSTRUCTION DOCUMENTS SUBMISSION 03/24/2022
CONSTRUCTION BID DOCUMENTS 06/02/2022
06/02/2022
JOHNSONWILBUR ADAMS, INC.
Wheaton, Illinois 60187 330 S. Naperville Road Suite 300
STRUCTURAL ENGINEERING
06/02/2022
STRUCTURAL - BUILDING 42
ENTRY CANOPY ROOF FRAMING PLAN
MW PW
42-SF101
0 2' 4' 8' 16'1/8"=1'-0"1 BUILDING 42 - ENTRY CANOPY ROOF FRAMING PLAN
NORTH
GENERAL SHEET NOTES
CONTRACTOR NOTE:
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID TO ENSURE ALL
CONFLICTS FOR INSTALLATION OF NEW WORK HAS BEEN IDENTIFIED AND ANY
WORK REQUIRED TO MODIFY EXISTING IS INCLUDED IN BID PRICE.
SHEET KEY NOTES -
1 PROVIDE 1 1/2" - 22 GAUGE GALVANIZED METAL ROOF DECK, TYPE B (WIDE RIB). DECK
SHALL BE CONTINUOUS OVER THREE SUPPORTS MINIMUM PER SDI DIAPHRAGM MANUAL.
WELD IN 36/5 PATTERN & PROVIDE MNIMUM 2 STITCH CONNECTORS BETWEEN SUPPORTS.
WELD WITH 5/8"Ø PUDDLE WELDS @ 6" O.C. AROUND PERIMETER.
(E) - INDICATES EXISTING CONSTRUCTION; VERIFY IN FIELD
(N) - INDICATES PROPOSED NEW CONSTRUCTION
T/ STEEL,…
This is the start of the file's text. The full file is on GovTribe.