635-21-117 Contract Drawings.pdf
PDF 23 MB Posted
- Solicitation number
- 36C25922R0108
About this file
This document contains details of a federal contract opportunity for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19 is soliciting to replace the cooling tower at its clinic in Z2DA--T2 under solicitation number 36C25922R0108. The opportunity type is a solicitation. Construction services are required to replace the existing clinic cooling tower located in VA-22-00067984. No other details are provided in this document regarding response dates, pricing terms, set asides, incumbent contractors or other salient information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25922R0108 0004.docx | DOCX document | |
| 36C25922R0108 0003.docx | DOCX document | |
| H86-HVAC Cooling Tower Details.pdf | ||
| 36C25922R0108 0002.docx | DOCX document | |
| 1-W16 Misc. Utility Details.pdf | ||
| Site Visit 10-12-22 attendance.pdf | ||
| 36C25922R0108 0001.docx | DOCX document | |
| Wage Determination OK20220049 9 2 2022.pdf | ||
| 36C25922R0108_1.docx | DOCX document | |
| 635-21-117 Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SATELLITE IMAGEAREA OF WORK SHEET INDEX
OKLAHOMA CITY, OK
VAMC PROJECT #: 635-21-117
REPLACE CLINIC COOLING TOWER
Plan North
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
REPLACE CLINIC COOLING TOWER
04/05/2022 MB MR
GI001
COVER SHEET
COOLING TOWER SITE
COOLING TOWER SITE
SHEET NO. SHEET NAME
GI001 COVER SHEET
CIVIL
SV101 IMPROVEMENT SURVEY EXISTING CONDITIONS
CD101 CIVIL DEMOLITION PLAN
CG101 CIVIL DETAILED GRADING PLAN
CS101 CIVIL SITE PLAN
CU101 CIVIL OVERALL UTILITY PLAN
CU301 SANITARY SEWER PLAN & PROFILE
CU501 CIVIL SANITARY SEWER DETAILS
STRUCTURAL
S-001 STRUCTURAL ABBREVIATIONS, LEGENDS, AND NOTES
SB111 COOLING TOWER FOUNDATION PLAN
SF111 COOLING TOWER FRAMING PLAN
SF311 STRUCTURAL FRAMING ELEVATIONS
SF511 STRUCTURAL FRAMING DETAILS
MECHANICAL
M-001 MECHANICAL ABBREVIATIONS AND GENERAL NOTES
M-002 MECHANICAL SYMBOLS
M-601 MECHANICAL SCHEDULES
MD101 MECHANICAL DEMOLITION SITE PLAN
MD102 MECHANICAL DEMOLITION PLAN - BASEMENT FLOOR
MS101 MECHANICAL SITE PLAN (AT GRADE)
MS102 MECHANICAL SITE PLAN (ABOVE TOWER STRUCTURE)
MP101 MECHANICAL PIPING PLAN - BASEMENT FLOOR
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-701 MECHANICAL CONTROLS
ELECTRICAL
E-001 ELECTRICAL SYMBOLS & ABBREVIATIONS
ED101 ELECTRICAL DEMOLITION PLAN - EXTERIOR COOLING TOWER
ES101 ELECTRICAL SITE PLAN - PROPOSED COOLING TOWER
ES102 ELECTRICAL SITE PLAN - ELECTRICAL ROUTING
E-601 ELECTRICAL ONE-LINE DIAGRAM
60083
G
G G G G G G G G G G G G G G G
G
G
G
G
G
G
G
METAL
GRATE
RAMP
GA
TE
METAL SHED
RIP RAP & METAL
GRATES AT ENTRY
1-STORY BRICK
BUILDING
1-STORY METAL
BUILDING
COOLING TOWER
EQUIPMENT
HEIGHT 27.61'
17.3'
20.3'
EXISTING STONE WALL
ASPHALT PAVEMENT
EX. 5" STEEL
BOLLARD
EX. 5" STEEL
BOLLARD
10" C.I. M.J.
RISERS
EX. 10" C.I. M.J.
RISER WITH VALVE
ELECTRICAL BOX AND CONDUITS
(CONDUITS RUN ALONG EAST SIDE OF
TOWER)
DIRT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
PUMP
EQUIP.
LADDER
VALVES
LADDER
METAL GRATES
PUMP EQUIP.
CONCRETE
SLAB
M.H. 2A
LINE "A"
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
STM
STM
STM
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
" R
CP
S
TO
RM
S
EW
ER
CONCRETE CUT-OUT
FHGV
M.H. 2J
RIM: 1221.8
INVERTS NOT
LOCATED
M.H. 3A
RIM: 1221.64
I.E.: 1209.49 N (12") I.E.: 1209.74 S (12")
I.E.: 1209.35 SW (24")
" R
CP
S
AN
IT
AR
Y
SE
W
ER
4.3 9 L
F
0.
24" RCP SANITARY SEWER
6' X 5' RCB STORM SEWER
EX. 16" C.A.
CONDENSER
WATER RETURN
(RECORD)
EX. 10" C.I. M.J.
RISER WITH VALVE
EX. 16" C.A.
CONDENSER
WATER SUPPLY
(RECORD)
W W
W W
W W
W
WATER
METER
VAULT
ESC
03/07/2022 SGL AB
SV101
CT
IMPROVEMENT SURVEY
EXISTING CONDITIONS
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Number: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
REPLACE CLINIC COOLING TOWER
KEY PLAN
GENERAL NOTES
Revision:
KEY PLAN
NO SCALE
B
D
8 G
HW
C22
5 18
Tr ue
N or th
E
A
F
CT
1. EXISTING CONDITIONS BASED UPON VETERNS HEALTH ADMINISTRATION
RECORDS AND LAND SURVEY PERFORMED BY HALFF ASSOCIATES, INC.
DATED 11/18/2021.
2. CONTROL POINTS ARE BASED ON CITY OF OKLAHOMA CITY CONTROL POINT
NUMBERS 234, 266 AND 486. CONTROL POINT 234 TO 236 USED AS BASIS OF
BEARING.
3. ALL BEARINGS ARE BASED FROM THE OKLAHOMA STATE COORDINATE
SYSTEM, NAD83 (2011), NORTH ZONE. AS DETERMINED BY GPS SURVEY
OBSERVATIONS CHECKED TO THE CITY OF OKLAHOMA CITY CONTROL. ALL
DISTANCES ARE GRID AND ADJUSTED BY FIELD MEASUREMENTS TO GROUND
DISTANCES IN US SURVEY FEET. ALL FIELD MEASUREMENTS AND ANGLES
APPLIED TO CONTROL POINTS WERE MADE WITH A TRIMBLE R10 GPS.
4. ALL ELEVATIONS OF CONTROL POINTS ARE BASED ON INITIAL ELEVATION OF
THE CITY OF OKLAHOMA CITY CONTROL POINT 234. ELEVATION BEING 1243.054
FEET, NAVD 88, GEOID 18.
G G
BOL
FSV
FH
BOLLARD
FIRE HYDRANT
STAND PIPE
WATER VALVE
ELECTRIC SWITCH CABINET
POWER POLE
LIGHT POLE
SANITARY SEWER MANHOLE
STORM SEWER MANHOLE
BUILDING
BURIED GAS LINE
FENCE, 6' HIGH CHAINLINK
PAVEMENT LINE
CONCRETE CURB
SIDEWALK
RIGHT-OF-WAY LINE
PROPERTY LINE
SECTION LINE
SYMBOLS
LINE TYPES
ECB
LEGEND
ABBREVIATIONS
C.I. CAST IRON
M.J. MECHANICAL JOINTC.A. CEMENT ASBESTOS
MH MANHOLE
EX. EXISTING
STORM SEWER MANHOLE
GV GATE VALVE
FH FIRE HYDRANT
RCB REINFORCED CONCRETE BOX CULVERT
I.E. INVERT ELEVATION
RCP REINFORCED CONCRETE PIPE
4/5/22
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
WM
AutoCAD SHX Text
PP
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text C
G G G G G G G G G G G G G G G
G
G
G
G
G
G
G
METAL
GRATE
RAMP
GA
TE
METAL SHED
RIP RAP & METAL
GRATES AT ENTRY
1-STORY BRICK
BUILDING
1-STORY METAL
BUILDING
COOLING TOWER
EQUIPMENT
HEIGHT 27.61'
17.3'
20.3'
EXISTING STONE WALL
ASPHALT PAVEMENT
EX. 5" STEEL
BOLLARD
EX. 5" STEEL
BOLLARD
10" C.I. M.J.
RISERS
EX. 10" C.I. M.J.
RISER WITH VALVE
ELECTRICAL BOX AND CONDUITS
(CONDUITS RUN ALONG EAST SIDE OF
TOWER)
DIRT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
PUMP
EQUIP.
LADDER
VALVES
LADDER
METAL GRATES
PUMP EQUIP.
CONCRETE
SLAB
M.H. 2A
LINE "A"
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
STM
STM
STM
STM
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
" R
CP
S
TO
RM
S
EW
ER
CONCRETE CUT-OUT
FHGV
M.H. 2J
RIM: 1221.8
INVERTS NOT
LOCATED
M.H. 3A
RIM: 1221.64
I.E.: 1209.49 N (12") I.E.: 1209.74 S (12")
I.E.: 1209.35 SW (24")
" R
CP
S
AN
IT
AR
Y
SE
W
ER
4.3 9 L
F
0.
24" RCP SANITARY SEWER
6' X 5' RCB STORM SEWER
EX. 16" C.A.
CONDENSER
WATER RETURN
(RECORD)
EX. 10" C.I. M.J.
RISER WITH VALVE
EX. 16" C.A.
CONDENSER
WATER SUPPLY
(RECORD)
W W
W W
W W
W
WATER
METER
VAULT
ESC
DEMOLISH
COOLING TOWER
EQUIPMENT AND
FOUNDATION
ESC
03/07/2022 SGL AB
CD101
CT
CIVIL DEMOLITION PLAN
SCALE: 1" = 5'
0 5' 10' 15' 20'
CIVIL DEMOLITION PLAN
Tr ue
No rth
1. DEMOLISH 6' HIGH CHAINLINK FENCE & GATE.
2. DEMOLISH RIP-RAP AT GATE AND REMOVE METAL GRATES UNLESS GRATES
PREVIOUSLY REMOVED BY OTHERS.
3. ELECTRIC CONTROL CABINET & PAD TO BE REMOVED AND REPLACED. SEE
ELECTRICAL PLANS FOR NEW ELECTRIC CONTROL CABINET AND
CONCRETE PAD LOCATION.
4. PROVIDE SAWCUT ALONG PROJECT FRONTAGE TO REMOVE CURB AND
PAVEMENT. PROVIDE SAWCUT FOR UTILITY TRENCH AND REMOVE
PAVEMENT. REMOVE ALL CONCRETE AND PAVEMENT FROM SITE TO AN
APPROVED OFFSITE DISPOSAL FACILITY.
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Number: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
REPLACE CLINIC COOLING TOWER
00KEYNOTES
KEY PLAN
GENERAL NOTES
Revision:
KEY PLAN
NO SCALE
B
D
8 G
HW
C22
5 18
Tr ue
N or th
E
A
F
CT
1. EXISTING CONDITIONS BASED UPON VETERNS HEALTH ADMINISTRATION
RECORDS AND LAND SURVEY PERFORMED BY HALFF ASSOCIATES, INC.
DATED 11/18/2021.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT
ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING WITH WORK.
KEYNOTES 00
BOL
FSV
FH
BOLLARD
FIRE HYDRANT
STAND PIPE
WATER VALVE
ELECTRIC SWITCH CABINET
POWER POLE
LIGHT POLE
SANITARY SEWER MANHOLE
STORM SEWER MANHOLE
BUILDING
BURIED GAS LINE
FENCE, 6' HIGH CHAINLINK
PAVEMENT LINE
CONCRETE CURB
SIDEWALK
RIGHT-OF-WAY LINE
PROPERTY LINE
SECTION LINE
SYMBOLS
LINE TYPES
ECB
LEGEND
ABBREVIATIONS
C.I. CAST IRON
M.J. MECHANICAL JOINTC.A. CEMENT ASBESTOS
MH MANHOLE
EX. EXISTING
STORM SEWER MANHOLE
GV GATE VALVE
FH FIRE HYDRANT
RCB REINFORCED CONCRETE BOX CULVERT
I.E. INVERT ELEVATION
RCP REINFORCED CONCRETE PIPE
4/5/22
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
WM
AutoCAD SHX Text
PP
AutoCAD SHX Text S
AutoCAD SHX Text D
METAL
GRATE
RAMP
METAL SHED
1-STORY BRICK
BUILDING
1-STORY METAL
BUILDING
EXISTING STONE WALL
ASPHALT PAVEMENT
EX. 5" STEEL
BOLLARD
EX. 5" STEEL
BOLLARD
10" C.I. M.J.
RISERS
EX. 10" C.I. M.J.
RISER WITH VALVE
DIRT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
CONCRETE CUT-OUT
EX. 16" C.A.
CONDENSER
WATER RETURN
(RECORD)
EX. 10" C.I. M.J.
RISER WITH VALVE
EX. 16" C.A.
CONDENSER
WATER SUPPLY
(RECORD)
WATER
METER
VAULT
EL
EC
TR
IC
CA
BI
NE
T
PA
D
COOLING TOWER
MECHANICAL EQUIPMENT
(CONCRETE SLAB BELOW)
F.F.E. 1223.50 FT.
0+00
0+
STA: 0+00.00
N: 176275.948
E: 2118281.874
STA: 0+91.90
N: 176344.664 E: 2118316.088
PC
S
TA
: 0
+0 9.
N : 1
6.
E:
.2
PT STA: 0+48.23
N: 176300.989 E: 2118315.923
0+
END DRIVEWAY TAPER
STA: 0+60.15
N: 176312.913 E: 2118315.968
BEGIN DRIVEWAY TAPER
STA: 0+54.15
N: 176306.913 E: 2118315.945
END DRIVEWAY TAPER
STA: 0+44.05
N: 176296.831 E: 2118315.559
BEGIN DRIVEWAY TAPER
STA: 0+38.03
N: 176291.084 E: 2118313.836
514515
517 518
519520
523524
CONCRETE SLAB
F.F.E. = 1223.50
-1 .9
8%
-1.75%
-2.00%
-0 .7
4%
-2 .6
6%
-8.06%
-7.64%
-0 .7
4%
-1.17% -0 .5
7%
-1 .6
5% -0
.6 3%
MATCH EX. SIDEWALK GRADE
SAWCUT LINE 2' OFFSET FROM
FLOWLINE, MATCH EX. PAVEMENT
SAWCUT LINE , MATCH
EX. PAVEMENT
526 527
528529
ELEC. PAD
EL: 1223.30
-2.00%
COORDINATE POINT SCHEDULE
POINT #
NORTHING
176276.0865
176284.3602
176291.0835
176296.8308
176300.9894
176306.9127
176312.9126
176322.7640
176332.7639
176340.5108
176336.7760
176312.9027
176308.9219
176308.9176
176308.8475
176336.7149
176336.6748
176336.7359
176308.9618
176308.9009
176306.9372
176301.0139
176296.9373
176296.8798
176306.8797
176305.8608
176305.8608
176299.8718
176299.8608
176302.8608
EASTING
2118291.2909
2118309.5061
2118313.8360
2118315.5588
2118315.9231
2118315.9454
2118315.9681
2118316.0052
2118316.0430
2118316.0722
2118310.7617
2118310.8223
2118310.8325
2118309.4404
2118286.7910
2118286.7202
2118286.7603
2118310.7218
2118310.7924
2118286.8308
2118309.4455
2118309.4231
2118309.4077
2118286.7582
2118286.7960
2118285.7985
2118288.7912
2118288.7985
2118285.7985
2118287.2985
ELEVATION
1221.91
1221.94
1221.94
1221.95
1221.98
1222.02
1222.07
1222.14
1222.22
1222.27
1222.95
1222.75
1222.55
1222.58
1223.03
1223.19
1223.50
1223.50
1223.50
1223.50
1222.52
1222.48
1222.45
1222.90
1222.98
1222.60
1222.93
1222.89
1222.57
1223.30
DESCRIPTION
FL
FL
FL
FL
FL
FL
FL
FL
FL
FL
GRD @ SLAB
GRD @ SLAB
GRD @ SLAB
GRD @ SLAB
GRD @ SLAB
GRD @ SLAB
FFE
FFE
FFE
FFE
CONC
CONC
CONC
GB
GB
GRD
GRD
GRD
GRD
ELEC PD CTR
6" THICK CONCRETE TYPE B SLAB
W/ 6 X 6 10 X 10 WELDED WIRE MESH
6" THICK - WASHED
3/4" CRUSHED ROCK
PREPARED AND COMPACTED SUBGRADE
PER GEOTECHNICAL REPORT
4" - 6" THICK WASHED 1-1/2" CRUSHED
ROCK W/ WEED BARRIER FILTER FABRIC,
SLOPE VARIES - 2% MIN.
3/4" CHAMFER
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Number: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
REPLACE CLINIC COOLING TOWER
00KEYNOTES
KEY PLAN
GENERAL NOTES
Revision:
0 100% BID DOCUMENTS SUBMITTAL 08/13/2021
KEY PLAN
NO SCALE
B
D
8 G
HW
C22
5 18
Tr ue
N or th
E
A
F
CT
03/07/2022 SGL AB
CG101
CT
CIVIL DETAILED GRADING PLAN
SCALE: 1" = 5'
0 5' 10' 15' 20'
CIVIL DETAILED GRADING PLAN
Tr ue
No rth
1. EXISTING CONDITIONS BASED UPON VETERANS HEALTH ADMINISTRATION RECORDS AND
LAND SURVEY PERFORMED BY HALFF ASSOCIATES, INC. DATED 11/18/2021.
2. CONTROL POINTS ARE BASED ON CITY OF OKLAHOMA CITY CONTROL POINT NUMBERS 234,
266 AND 486. CONTROL POINT 234 TO 236 USED AS BASIS OF BEARING.
3. ALL BEARINGS ARE BASED FROM THE OKLAHOMA STATE COORDINATE SYSTEM, NAD83 (2011), NORTH ZONE. AS DETERMINED BY GPS SURVEY OBSERVATIONS CHECKED TO THE CITY OF
OKLAHOMA CITY CONTROL. ALL DISTANCES ARE GRID AND ADJUSTED BY FIELD
MEASUREMENTS TO GROUND DISTANCES IN US SURVEY FEET. ALL FIELD MEASUREMENTS
AND ANGLES APPLIED TO CONTROL POINTS WERE MADE WITH A TRIMBLE R10 GPS.
4. ALL ELEVATIONS OF CONTROL POINTS ARE BASED ON INITIAL ELEVATION OF THE CITY OF OKLAHOMA CITY CONTROL POINT 234. ELEVATION BEING 1243.054 FEET, NAVD 88, GEOID 18.
5. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT ANY
DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING WITH WORK.
6. SITE PREPERATION AND COMPACTION PER "GEOTECHNICAL ENGINEERING REPORT,
OKLAHOMA CITY VA HEALTH CLINIC COOLING TOWER REPLACEMENT, OKLAHOMA CITY, OK",
BY TERRACON CONSULTANTS, INC., DATED NOVEMBER 19.2021.
7. CONCRETE SHALL BE CONCRETE TYPE B. SEE SPECIFICATION 32 05 23 - CEMENT AND
CONCRETE FOR EXTERIOR IMPROVEMENTS.
TYPICAL CONCRETE SLAB SECTION
G
BOL
FSV
FH
BOLLARD
FIRE HYDRANT
STAND PIPE
WATER VALVE
ELECTRIC SWITCH CABINET
POWER POLE
LIGHT POLE
SANITARY SEWER MANHOLE
STORM SEWER MANHOLE
BUILDING
BURIED GAS LINE
FENCE, 6' HIGH CHAINLINK
PAVEMENT LINE
CONCRETE CURB
SIDEWALK
RIGHT-OF-WAY LINE
PROPERTY LINE
SECTION LINE
S
D
SYMBOLS
LINE TYPES
ECB
LEGEND
ABBREVIATIONS
C.I. CAST IRON M.J. MECHANICAL JOINT
C.A. CEMENT ASBESTOS
MH MANHOLE
EX. EXISTING
STORM SEWER MANHOLE
GV GATE VALVE
FH FIRE HYDRANT
PC
REINFORCED CONCRETE BOX CULVERT
POINT OF CURVE
F.F.E. FINISHED FLOOR EL.
I.E. INVERT ELEVATION
EL. ELEVATION
PT POINT OF TANGENCY
RCP REINFORCED CONCRETE PIPE
RCB
4/5/22
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
WM
AutoCAD SHX Text
PP
METAL
GRATE
RAMP
METAL SHED
1-STORY BRICK
BUILDING
1-STORY METAL
BUILDING
EXISTING STONE WALL
ASPHALT PAVEMENT
EX. 5" STEEL
BOLLARD
EX. 5" STEEL
BOLLARD
DIRT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
CONCRETE CUT-OUT
FH
WATER
METER
VAULT
5.0'
5.0' 5.1'
5.3'
8.3
8.0
.8'
3.5'
.9'
3.0
N0 0°
'59
"E
9.5 2'
Δ=088°56'28" R=25.00' L=38.81'
CB=N44°41'12"E
CD=35.03'
EL
EC
TR
IC
CA
BI
NE
T
PA
D
24.04'
.06
.06
24.04'
E
E
E
E
E
E
E
E
COOLING TOWER
MECHANICAL EQUIPMENT
(CONCRETE SLAB BELOW)
F.F.E. 1223.50 FT.
4.0' 2.0
6.0
3.0'
03/07/2022 SGL AB
CS101
CT
CIVIL SITE PLAN
SCALE: 1" = 5'
0 5' 10' 15' 20'
CIVIL SITE PLAN
Tr ue
No rth
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Number: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
REPLACE CLINIC COOLING TOWER
00KEYNOTES
KEY PLAN
GENERAL NOTES
Revision:
KEY PLAN
NO SCALE
B
D
8 G
HW
C22
5 18
Tr ue
N or th
E
A
F
CT
1. NEW 6' CHAINLINK FENCE.
2. 12' WIDE CHAINLINK FENCE WITH MANUAL SWING GATE.
3. CONCRETE DRIVEWAY APRON.
4. SAWCUT 2 FEET +/- ALONG EXISTING FLOWLINE AND MATCH EXISTING
PAVEMENT ELEVATION.
5. WASHED 1-1/2" CRUSHED ANGULAR STONE (TYPICAL).
6. EDGE OF EXISTING CONCRETE PAVEMENT.
7. NEW UNDERGROUND CONDUIT AND CONDUCTOR. REFER TO SHEET ES102.
8. UTILITY TRECH PATCH, SEE DETAILS ON SHEET CU501.
9. SANITARY SEWER CLENOUT.
10. SANITARY SEWER RISER TO MECHANICAL EQUIPMENT.
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT
AND DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING WITH WORK.
BOL
FSV
FH
BOLLARD
FIRE HYDRANT
STAND PIPE
WATER VALVE
ELECTRIC SWITCH CABINET
POWER POLE
LIGHT POLE
SANITARY SEWER MANHOLE
STORM SEWER MANHOLE
BUILDING
BURIED GAS LINE
FENCE, 6' HIGH CHAINLINK
PAVEMENT LINE
CONCRETE CURB
SIDEWALK
RIGHT-OF-WAY LINE
PROPERTY LINE
SECTION LINE
SYMBOLS
LINE TYPES
ECB
LEGEND
ABBREVIATIONS
C.I. CAST IRON
M.J. MECHANICAL JOINTC.A. CEMENT ASBESTOS
MH MANHOLE
EX. EXISTING
STORM SEWER MANHOLE
GV GATE VALVE
FH FIRE HYDRANT
RCB REINFORCED CONCRETE BOX CULVERT
I.E. INVERT ELEVATION
RCP REINFORCED CONCRETE PIPE
KEYNOTES 00
4/5/22
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
WM
AutoCAD SHX Text
PP
AutoCAD SHX Text S
AutoCAD SHX Text D
EL
EC
TR
IC
CA
BI
NE
T
PA
D
CWR
C W
R
EX. 10" C.I. M.J.
RISER WITH VALVE
EX. 10" C.I. M.J.
RISER WITH VALVE
EX. 16" C.A.
CONDENSER
WATER RETURN
(RECORD)
EX. 16" C.A.
CONDENSER
WATER SUPPLY
(RECORD)
10" C.I. M.J.
RISERS
9.5'
G G
G G G G G G G G G G G G G G G
G
G
G
G
G
G
G
METAL
GRATE
RAMP
METAL SHED
1-STORY BRICK
BUILDING
1-STORY METAL
BUILDING
EXISTING STONE WALL
ASPHALT PAVEMENT
EX. 5" STEEL
BOLLARD
EX. 5" STEEL
BOLLARD
DIRT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
CONCRETE PAVEMENT
M.H. 2A
SS SS SS SS SS SS SS
LINE "A"
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
STM
STM
STM
STM
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
" R
CP
S
TO
RM
S
EW
ER
CONCRETE CUT-OUT
FHGV
M.H. 2J
RIM: 1221.8
INVERTS NOT
LOCATED
M.H. 3A
RIM: 1221.64
I.E.: 1209.49 N (12") I.E.: 1209.74 S (12")
I.E.: 1209.35 SW (24")
" R
CP
S
AN
IT
AR
Y
SE
W
ER
4.3 9 L
F
0.
24" RCP SANITARY SEWER
6' X 5' RCB STORM SEWER
W W
W W
W W
W
WATER
METER
VAULT
12.2'
3'-0"
6'- 0"
6"3'-0"
PLAN SECTION
6 X 6 10 X 10
WELDED WIRE MESH
ELECTRIC PAD DETAIL
SCALE: 1" = 5'
0 5' 10' 15' 20'
CIVIL OVERALL UTILITY PLAN
Tr ue
No rth
1. EXISTING CONDITIONS BASED UPON VETERNS HEALTH ADMINISTRATION
RECORDS AND LAND SURVEY PERFORMED BY HALFF ASSOCIATES, INC.
DATED 11/18/2021.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT
ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING WITH WORK.
3. CONTROL POINTS ARE BASED ON CITY OF OKLAHOMA CITY CONTROL POINT
NUMBERS 234, 266 AND 486. CONTROL POINT 234 TO 236 USED AS BASIS OF
BEARING.
4. ALL BEARINGS ARE BASED FROM THE OKLAHOMA STATE COORDINATE
SYSTEM, NAD83 (2011), NORTH ZONE. AS DETERMINED BY GPS SURVEY
OBSERVATIONS CHECKED TO THE CITY OF OKLAHOMA CITY CONTROL. ALL
DISTANCES ARE GRID AND ADJUSTED BY FIELD MEASUREMENTS TO GROUND
DISTANCES IN US SURVEY FEET. ALL FIELD MEASUREMENTS AND ANGLES
APPLIED TO CONTROL POINTS WERE MADE WITH A TRIMBLE R10 GPS.
5. ALL ELEVATIONS OF CONTROL POINTS ARE BASED ON INITIAL ELEVATION OF
THE CITY OF OKLAHOMA CITY CONTROL POINT 234. ELEVATION BEING
1243.054 FEET, NAVD 88, GEOID 18.
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Number: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
REPLACE CLINIC COOLING TOWER
00KEYNOTES
KEY PLAN
GENERAL NOTES
Revision:
0 100% BID DOCUMENTS SUBMITTAL 08/13/2021
KEY PLAN
NO SCALE
B
D
8 G
HW
C22
5 18
Tr ue
N or th
E
A
F
CT
03/07/2022 SGL AB
CU101
CT
CIVIL OVERALL UTILITY PLAN
KEYNOTES 00
BOL
FSV
FH
BOLLARD
FIRE HYDRANT
STAND PIPE
WATER VALVE
ELECTRIC SWITCH CABINET
POWER POLE
LIGHT POLE
SANITARY SEWER MANHOLE
STORM SEWER MANHOLE
BUILDING
BURIED GAS LINE
FENCE, 6' HIGH CHAINLINK
PAVEMENT LINE
CONCRETE CURB
SIDEWALK
RIGHT-OF-WAY LINE
PROPERTY LINE
SECTION LINE
S
D
SYMBOLS
LINE TYPES
ECB
LEGEND
ABBREVIATIONS
C.I. CAST IRON
M.J. MECHANICAL JOINTC.A. CEMENT ASBESTOS
MH MANHOLE
EX. EXISTING
STORM SEWER MANHOLE
GV GATE VALVE
FH FIRE HYDRANT
RCB REINFORCED CONCRETE BOX CULVERT
I.E. INVERT ELEVATION
RCP REINFORCED CONCRETE PIPE
1. NEW SANITARY SEWER SERVICE LINE, SEE SHEET CU301.
2. ABOVE GRADE CHILLED WATER SUPPLY PIPING. REFER TO MECHANICAL
PLAN MS101.
3. ABOVE GRADE CHILLED WATER RETURN PIPING. REFER TO MECHANICAL
PLAN MS101.
4. NEW ELECTRIC CABINET AND CONCRETE PAD.
5. SANITARY SEWER CLEANOUT.
6. ABOVE GRADE SANITARY SEWER PIPING. REFER TO MECHANICAL PLAN
MS101.
7. 4" SANITARY SEWER RISER, REFER TO MECHANICAL SHEET MS101.
8. NEW UNDERGROUND CONDUIT AND CONDUCTOR. REFER TO SHEET ES102.
4/5/22
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
WM
AutoCAD SHX Text
PP
EX. 16" C.A.
CONDENSER
WATER RETURN
(RECORD)
EX. 16" C.A.
CONDENSER
WATER SUPPLY
(RECORD)
SS-3
4" CLEANOUT
STA: 0+12.19
RIM: 1222.71
N: 176321.353 E: 2118311.691
SS STRC 1
12" X 4" TAPPING SLEEVE
STA: 0+00.00
RIM: 1222.20
N: 176321.382 E: 2118323.875
SS-2
4" VERT. 45° BEND
STA: 0+07.75
RIM: 1222.13
N: 176321.362 E: 2118316.125
4.43 LF OF
4" PVC @ 2.08%
.26
LF
O
F
" R
CP
0.
7.75 LF OF
4" PVC @ 100.00%
EX
. 7
5.
L F
O F
" R
C P
.7 0%
CWS
EL
EC
TR
IC
CA
BI
NE
T
PA
D
CWR
C W
R
E
E
E
E
G G
G G G G G G G G G G G G G G G
G
G
G
G
G
G
G
METAL
GRATE
RAMP
METAL SHED
1-STORY BRICK
BUILDING
1-STORY METAL
BUILDING
EXISTING STONE WALL
ASPHALT PAVEMENT
EX. 5" STEEL
BOLLARD
DIRT
CONCRETE PAVEMENT
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
ST
M
" R
CP
S
TO
RM
S
EW
ER
FHGV
W
WATER
METER
VAULT
ESC
SS 4
4" X 4" VERT. BEND
STA: 0+21.68
RIM: 1223.50
N: 176321.327 E: 2118302.201
9.49 LF OF
4" PVC @ 2.08%
SS
12.2'
SS SS
EL
EV
AT
IO
N
EL
EV
AT
IO
N
STATION
Align-SSWR-1 PROFILE
0+000+200+40
SS
S
TR
C
" X 4"
T
AP
PI
NG
S
LE
EV
E
ST
A:
0+
.00 , R
IM
: 1
2.2
IN
V
IN
: 1
9.8 3 (
" N
IN
V
IN
: 1
0.1 7 (
4" W
IN
V
OU
T:
.83
(1 2"
S
CU
T:
.4'
7.75 LF 4"
PVC @
100.00%
SS
-2
4" V
ER
T.
° B
EN
D
ST
A:
0+
.75 , R
IM
: 1
2.1
IN
V
IN
: 1
7.9 2 (
4" W
IN
V
OU
T:
.92
(4 " E
CU
T:
4.
2'
4.43 LF 4"
PVC @ 2.08%
SS
-3
4" C
LE
AN
OU
T
ST
A:
0+
.19 , R
IM
: 1
2.7
IN
V
IN
: 1
8.0 1 (
4" W
IN
V
OU
T:
.01
(4 " E
CU
T:
4.
7'
9.49 LF 4"
PVC @ 2.08%
SS
4" X
4" V
ER
T.
B
EN
D
ST
A:
0+
.68
, R
IM
: 1
3.5
IN
V
OU
T:
.21 (4
" E
CU
T:
5.
3'
TOP 6" THICK
CONCRETE SLAB
EL: 1223.50
4.3 5'
EX
. 1
6" C
A
ST
A:
0+
.22
T.
O.
P.
E
L:
.58
FI
EL
D
VE
RI
FY
LO
CA
TI
ON
BE
FO
RE
C
ON
ST
RU
CT
IO
N
MIN. 6" CLR. W/
CONCRETE CRADLE
OVER EX. 16" CA
6" THICK
ASPHALTIC
CONCRETE
PAVEMENT
FLOWABLE
FILL
GENERAL
BACKFILL
SCALE: 1" = 5'
0 5' 10' 15' 20'
SANITARY SEWER PLAN & PROFILE
Tr ue
No rth
1. EXISTING CONDITIONS BASED UPON VETERNS HEALTH ADMINISTRATION
RECORDS AND LAND SURVEY PERFORMED BY HALFF ASSOCIATES, INC.
DATED 11/18/2021.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT
ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING WITH WORK.
3. CONTROL POINTS ARE BASED ON CITY OF OKLAHOMA CITY CONTROL POINT
NUMBERS 234, 266 AND 486. CONTROL POINT 234 TO 236 USED AS BASIS OF
BEARING.
4. ALL BEARINGS ARE BASED FROM THE OKLAHOMA STATE COORDINATE
SYSTEM, NAD83 (2011), NORTH ZONE. AS DETERMINED BY GPS SURVEY
OBSERVATIONS CHECKED TO THE CITY OF OKLAHOMA CITY CONTROL. ALL
DISTANCES ARE GRID AND ADJUSTED BY FIELD MEASUREMENTS TO GROUND
DISTANCES IN US SURVEY FEET. ALL FIELD MEASUREMENTS AND ANGLES
APPLIED TO CONTROL POINTS WERE MADE WITH A TRIMBLE R10 GPS.
5. ALL ELEVATIONS OF CONTROL POINTS ARE BASED ON INITIAL ELEVATION OF
THE CITY OF OKLAHOMA CITY CONTROL POINT 234. ELEVATION BEING 1243.054
FEET, NAVD 88, GEOID 18.
6. SEE PROJECT SPECIFICATIONS 31 20 00 EARTH MOVING, 31 23 23.33 FLOWABLE
FILL, AND 33 30 00 SANITARY SEWER UTILITIES FOR EXCAVATION, PIPE
BEDDING, BACKFILL, SHORING, SHEETING SPECIFICATIONS.
7. SEE PROJECT SPECIFICATION SECTION 01 57 19 , TEMPORARY
ENVIRONMENTAL CONTROLS FOR EROSION AND SEDIMENT CONTROLS.
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Number: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
REPLACE CLINIC COOLING TOWER
00KEYNOTES
KEY PLAN
GENERAL NOTES
Revision:
0 100% BID DOCUMENTS SUBMITTAL 08/13/2021
KEY PLAN
NO SCALE
B
D
8 G
HW
C22
5 18
Tr ue
N or th
E
A
F
CT
1. ABOVE GRADE SANITARY SEWER PIPING. REFER TO MECHANICAL PLAN
MS101.
2. ABOVE GRADE CHILLED WATER SUPPLY PIPING. REFER TO MECHANICAL
PLAN MS101.
3. ABOVE GRADE CHILLED WATER RETURN PIPING. REFER TO MECHANICAL
PLAN MS101.
4. NEW ELECTRIC CABINET AND CONCRETE PAD.
5. CONTRACTOR TO PROVIDE ASPHALT SAWCUT AND PATCH FOR UTILITY
TRENCH (12' X 15' +/-).
03/07/2022 SGL AB
CU301
CT
SANITARY SEWER PLAN & PROFILE
KEYNOTES 00
BOL
FSV
FH
BOLLARD
FIRE HYDRANT
STAND PIPE
WATER VALVE
ELECTRIC SWITCH CABINET
POWER POLE
LIGHT POLE
SANITARY SEWER MANHOLE
STORM SEWER MANHOLE
BUILDING
BURIED GAS LINE
FENCE, 6' HIGH CHAINLINK
PAVEMENT LINE
CONCRETE CURB
SIDEWALK
RIGHT-OF-WAY LINE
PROPERTY LINE
SECTION LINE
S
D
SYMBOLS
LINE TYPES
ECB
LEGEND
ABBREVIATIONS
C.I. CAST IRON
M.J. MECHANICAL JOINTC.A. CEMENT ASBESTOS
MH MANHOLE
EX. EXISTING
STORM SEWER MANHOLE
GV GATE VALVE
FH FIRE HYDRANT
RCB REINFORCED CONCRETE BOX CULVERT
I.E. INVERT ELEVATION
RCP REINFORCED CONCRETE PIPE
THIS SHEET
4/5/22
AutoCAD SHX Text C
AutoCAD SHX Text
WM
AutoCAD SHX Text
PP
VEG 21.10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Number: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-117
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION
DOCUMENTS
REPLACE CLINIC COOLING TOWER
Revision:
0 100% BID DOCUMENTS SUBMITTAL 08/13/2021
03/07/2022 SGL AB
CU501
CT
CIVIL SANITARY SEWER DETAILS
SCALE: NO SCALE
SEWER LINE TRENCH & BEDDING DETAIL
SCALE: NO SCALE
SERVICE CONNECTION DETAIL
45 BEND
TRENCH
TEE FITTING FOR NEW
CONSTRUCTION,
TAPPING SADDLE
WYE OR TEE FOR
CONNECTION TO
EXISTING MAINS.
CRUSHED STONE
NOTES:
1. TRACER WIRE (NOT SHOWN) IS REQUIRED.
2. RUBBER SADDLES ARE NOT ALLOWED.
3. NO HOLES FOR NEW CONNECTIONS SHALL BE MADE BY HAMMERING, REGARDLESS OF THE
EXISTING SEWER MAIN PIPE MATERIAL.
4. ALL HOLES FOR NEW CONNECTIONS TO EXISTING PIPE SHALL BE MADE BY CORING AND
INSTALLING A PREFABRICATED SANITARY SEWER SADDLE WYE OR TEE, IN WHICH CASE, THE NEW FITTING SHALL BE AFFIXED TO THE EXISTING SEWER MAIN BY MEANS OF A WATERTIGHT RUBBER COUPLING WITH 2 STAINLESS STEEL BANDS, ALL OF WHICH SHALL BE CONCRETE ENCASED PER
THE REQUIREMENTS SHOWN ON THE DETAIL ABOVE.
SEWER MAIN 8" DIA.
OR GREATER
3/4" CLEAN ROCK OR
APPROVED ROCK
BEDDING FULL
LENGTH OF PIPE
45°
MAX
WATERTIGHT RUBBER
TRANSITION COUPLING WITH
2 STAINLESS STEEL BANDS
4" OR 6" PVC
SERVICE LINE
MIN GRADE
1/4" PER FT.
EXISTING OR
PROPOSED
SERVICE LINE
CONCRETE COLLAR 12" LONG & 4" MIN. COVER
AROUND PIPE. USE FIBER REINFORCED CONCRETE
OR REINFORCED CONCRETE. (#4 BARS)
EXISTING
GROUND
PAVEMENT REPAIR & 3/4" CRUSHED
STONE BACKFILL WHEN UNDER
STREET OR DRIVES.
TRENCH WIDTH
O.D. + 2'-0"
FINISHED TRENCH IN DIRT
SHALL BE BACKFILLED WITH
6" TOPSOIL & SODDED
ABOVE COMPACTED
ORDINARY BACKFILL.
EXISTING GRADE
CONTRACTOR SHALL
FOLLOW OSHA
REQUIREMENTS FOR
SHORING & CONFINED
SPACE ENTRY.
NOTE:
FOR SANITARY SEWER LATERAL PIPES USE 3/4" CLEAN ROCK OR APPROVED EQUIVALENT
UNDER THE FULL LENGTH OF THE INSTALLED PIPE.
4" M
IN
1'-0"
USE 6" BEDDING THICKNESS
UNDER PIPE IF IN SOLID ROCK
COMPACTED GRANULAR
BEDDING & BACKFILL
2'
MI
N.
6"
O.D.COMPACTED BACKFILL
PVC RISER (TYP)
2° ELBOW (TYP)
INVERT AS SHOWN ON
PLANS AND PROFILES
45° WYE
PVC FITTINGS WITH WATERTIGHT ELASTOMERIC SEALS
SCALE: NO SCALE
UNDERDRAIN ONE-WAY CLEAN-OUT DETAIL
THREADED PLUG
FINISHED GRADE
ADJUSTABLE PVC CLEANOUT
FOR PVC WITH BOLTED 6 1/2"
NICKEL BRONZE COVER
ELEVATION PER PLAN
ADJUST TO FINISHED GRADE
THREADED CAP
TRACER WIRE
CONCRETE COLLAR
OR PAVEMENT
SCALE: NO SCALE
TYPE 1 UTILITY TRENCH PATCH
SCALE: NO SCALE
UTILITY TRENCH PATCH NOTES
4/5/22
AutoCAD SHX Text FOR TRENCH WIDTHS EXCEEDING 4' [1219mm] REFER TO VA STANDARD DETAIL 32 12 16-02 "TYPE 2 UTILITY TRENCH PATCH". FOR TRENCH WHERE PORTLAND CEMENT CONCRETE (PCC) PAVEMENT EXISTS, REFER TO 32 12 16-03 "TYPE 3 UTILITY TRENCH PATCH".
AutoCAD SHX Text 2" [50mm] MINIMUM OR THICKNESS OF EXISTING PAVEMENT WHICHEVER IS GREATER.
AutoCAD SHX Text BITUMINOUS SURFACE TREATMENT (CHIPSEAL) REQUIRED ONLY FOR LONGITUDINAL TRENCHES WITH WIDTHS GREATER THAN 6' [1829mm].
AutoCAD SHX Text 4" [100mm] MINIMUM ABC OR THICKNESS OF EXISTING GRANULAR BASE COURSE MATERIALS (E.G. ABC & SELECT MATERIAL) WHICHEVER IS GREATER.
AutoCAD SHX Text REFER TO VA STANDARD DETAIL 32 12 16-04 "UTILITY TRENCH PAVEMENT PATCH NOTES" FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text [1219mm]
AutoCAD SHX Text [305mm]
AutoCAD SHX Text [305mm]
AutoCAD SHX Text
TRENCH BACKFILL
AutoCAD SHX Text
ABC 100% MIN. COMPACTION
AutoCAD SHX Text
ASPHALTIC CONCRETE
AutoCAD SHX Text
SAW CUT EXISTING. ASPHALT FULL DEPTH BOTH SIDES
AutoCAD SHX Text
TACK COAT (TYP.)
AutoCAD SHX Text
EXISTING PAVEMENT
AutoCAD SHX Text %%uGENERAL NOTES
1. MATERIAL AND COMPACTION REQUIREMENTS FOR PIPE BEDDING/SHADING SHALL BE IN MATERIAL AND COMPACTION REQUIREMENTS FOR PIPE BEDDING/SHADING SHALL BE IN ACCORDANCE WITH THE SPECIFICATIONS FOR THE APPLICABLE UTILITY PIPE. 2. TRENCH BACKFILL SHALL COMMENCE 1 FOOT [305mm] ABOVE THE TOP OF PIPE AND TRENCH BACKFILL SHALL COMMENCE 1 FOOT [305mm] ABOVE THE TOP OF PIPE AND SHALL BE PER SECTION 31 20 11 EARTHWORK OR SECTION 31 23 23.33 FLOWABLE FILL. 3. BACKFILL COMPACTION REQUIREMENTS SHALL BE PER SECTION 31 20 11. BACKFILL COMPACTION REQUIREMENTS SHALL BE PER SECTION 31 20 11. 4. THE 1 FOOT [305mm] TRENCH "SHOULDER" AREAS SHALL BE DELETED FOR TYPE 2 THE 1 FOOT [305mm] TRENCH "SHOULDER" AREAS SHALL BE DELETED FOR TYPE 2 TRENCHES. 5. ABC SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 12 16. ABC SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 12 16. 6. PORTLAND CEMENT CONCRETE SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF PORTLAND CEMENT CONCRETE SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 05 23. 7. ASPHALTIC TACK MATERIAL SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ASPHALTIC TACK MATERIAL SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 12 16. 8. ASPHALTIC CONCRETE SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 ASPHALTIC CONCRETE SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 12 16 FOR THE TYPE SPECIFIED. 9. BITUMINOUS SURFACE TREATMENT (CHIP SEAL) SHALL BE IN ACCORDANCE WITH THE BITUMINOUS SURFACE TREATMENT (CHIP SEAL) SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 12 16 FOR THE TYPE SPECIFIED. 10. LOAD TRANSFER DOWELS FOR JOINTS TRANSVERSE TO THE ROADWAY CENTERLINE SHALL LOAD TRANSFER DOWELS FOR JOINTS TRANSVERSE TO THE ROADWAY CENTERLINE SHALL BE SMOOTH STEEL DOWELS IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 32 05 23. DOWELS SHALL BE SIZED AND SPACED AS FOLLOWS: PCCP THICKNESS DOWEL SIZE DOWEL LENGTH DOWEL SPACING THICKNESS DOWEL SIZE DOWEL LENGTH DOWEL SPACING DOWEL SIZE DOWEL LENGTH DOWEL SPACING DOWEL LENGTH DOWEL SPACING DOWEL SPACING 6" [150mm] #5 [No. 16] 12" [305mm] 18" [455mm] #5 [No. 16] 12" [305mm] 18" [455mm] 12" [305mm] 18" [455mm] 18" [455mm] 7" [180mm] #6 [No. 19] 15" [380mm] 15" [380mm] #6 [No. 19] 15" [380mm] 15" [380mm] 15" [380mm] 15" [380mm] 15" [380mm] 8" [180mm] #8 [No. 19] 15" [380mm] 12" [305mm] #8 [No. 19] 15" [380mm] 12" [305mm] 15" [380mm] 12" [305mm] 12" [305mm] 10" [180mm] #10 [No. 19] 15" [380mm] 12" [305mm] #10 [No. 19] 15" [380mm] 12" [305mm] 15" [380mm] 12" [305mm] 12" [305mm] 11. DEFORMED TIE BARS SHALL BE USED IN TRENCH PATCHES LONGITUDINAL TO THE DEFORMED TIE BARS SHALL BE USED IN TRENCH PATCHES LONGITUDINAL TO THE ROADWAY CENTERLINE WHEN THE TRENCH LENGTH IS GREATER THAN 50 FEET [15240mm]. TIE BARS SHALL BE 24 INCHES [610mm] LONG. DEFORMED #4 [No. 13] BARS FOR PCCP LESS THAN 8 INCHES [205mm] THICK AND #5 [No. 16] BARS IF 8 INCHES [205mm] THICK OR MORE. TIE BARS SHALL BE PLACED 30 INCHES [760mm] CENTER-TO-CENTER. 12. HOLES SHALL BE DRILLED 1 FOOT [305mm] INTO THE EXISTING SLAB FOR TIE BARS AND HOLES SHALL BE DRILLED 1 FOOT [305mm] INTO THE EXISTING SLAB FOR TIE BARS AND 7 INCHES [180mm] FOR DOWELS. HOLES SHALL BE OF A DIAMETER SUFFICIENT TO ACCOMMODATE THE TIE BAR ANCHORAGE OR DOWEL CAP. TIE BARS SHALL BE ANCHORED WITH AN APPROVED HIGH VISCOSITY EPOXY. 13. IF THE CONCRETE SLAB REMAINING NEXT TO A LONGITUDINAL OR TRANSVERSE JOINT IS IF THE CONCRETE SLAB REMAINING NEXT TO A LONGITUDINAL OR TRANSVERSE JOINT IS LESS THAN 6 FEET [1829mm] AT ITS NARROWEST WIDTH, REMOVE AND REPLACE THE EXISTING CONCRETE TO THE JOINT.
NOTES:
1. TABULATED VALUES ARE BASED ON A MINIMUM YIELD STRENGTH OF 60,000 PSI. LENGTHS ARE IN INCHES.
2. TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE LENGTHS ARE CALCULATED PER ACI 318.
3. TABULATED VALUES FOR BEAMS OR COLUMNS ARE BASED ON TRANSVERSE REINFORCEMENT AND CONCRETE COVER MEETING
MINIMUM CODE REQUIREMENTS.
4. LAP SPLICE LENGTHS (MINIMUM OF 12 INCHES) ARE MULTIPLES OF TENSION DEVELOPMENT LENGTHS; CLASS B = 1.3 ℓd. WHEN
DETERMINING THE LAP SPLICE LENGTH, ℓd IS CALCULATED WITHOUT THE 12-INCH MINIMUM OF ACI.
BAR SIZE
CONCRETE REINFORCING LAP SPLICE SCHEDULE (IN)
f' = 3000 PSIc f' = 4000 PSIc f' = 5000 PSIc f' = 6000 PSIc
#3
#4
#5
#6
#7
#8
#9
#10
#11
28 22
37 29
47 36
56 43
81 63
93 72
105 81
118 91
131 101
24 19
32 25
40 31
48 37
70 54
80 62
91 70
102 79
113 87
22 17
29 22
36 28
43 33
63 49
72 55
81 63
91 70
101 78
20 15
26 20
33 25
40 31
58 44
66 51
74 57
83 64
93 71
TOP
BARS
OTHER
BARS
TOP
BARS
OTHER
BARS
TOP
BARS
OTHER
BARS
TOP
BARS
OTHER
BARS
CONCRETE COVER SCHEDULE
NOTES:
1. MINIMUM CONCRETE COVER PROTECTION FOR REINFORCEMENT BARS SHALL BE AS
FOLLOWS: (RE: ACI 318 LATEST EDITION FOR CONDITIONS NOT NOTED). DIMENSIONS FOR
BAR PLACEMENT GIVEN IN SECTIONS AND DETAILS SHALL SUPERSEDE MINIMUM COVER
REQUIREMENTS GIVEN HERE.
2. PROVIDE STANDARD BAR CHAIRS AND SPACERS AS REQUIRED TO MAINTAIN CONCRETE
PROTECTION SPECIFIED
CONCRETE EXPOSURE MEMBER REINFORCEMENT COVER (IN)
CAST AGAINST AND PERMANENTLY
IN CONTACT WITH GROUND
EXPOSED TO WEATHER OR IN
CONTACT WITH THE GROUND
NOT EXPOSED TO WEATHER OR IN
CONTACT WITH GROUND
ALL
ALL
SLABS, JOISTS, AND WALLS
BEAMS, COLUMNS, PEDESTALS,
AND TENSION TIES
ALL 3
#5 BAR & SMALLER
#14 & #18 BARS
#6 THRU #18 BARS
#11 BAR & SMALLER
PRIMARY
REINFORCEMENT,
STIRRUPS, TIES,
SPIRALS & HOOPS
1 1/2
1 1/2
3/4
1 1/2
#6
#7
#8
#10
#11
#9
HOOK DEVELOPMENT LENGTH
ℓdh (INCHES)
STANDARD HOOKS IN
TENSION PER ACI 318
BAR SIZE
#5
#4
#3 f'c=4000 PSI
NOTES:
1. CONCRETE IS NORMAL WEIGHT CONCRETE. FOR
LIGHTWEIGHT CONC MULTIPLY VALUES BY 1.33.
2. BAR YIELD STRENGTH, Fy = 60 KSI.
3. SIDE COVER REQUIREMENTS OF ACI 318 ARE
ASSUMED TO BE MET.
4. TIE OR STIRRUP REQUIREMENTS OF ACI 318 ARE
ASSUMED TO BE MET.
5. REDUCTION FOR EXCESS REINFORCEMENT IS NOT
TAKEN.
6. HOOK DEVELOPMENT LENGTH IS VALID FOR 180°
HOOKS ALSO.
7. ℓext PER ACI 318 TABLE 25.3.1
STANDARD CONCRETE HOOK SCHEDULE
f'c=3000 PSI
LENGTH, ℓdh
HOOK DEVELOPMENT
P E
R A
C I 3 ℓe xt ℓext
32 4 5 6 7 8 9
E
T ru e N o rt h
KEY PLAN
NO SCALE
B
D
G
HW
C
5 18
E
A
F
CT
00KEYNOTES
KEY PLAN
GENERAL NOTES
VEG 21.10
VA FORM 08 - 6231
A
F ile
P a th
B
C
D
E
F
A
B
C
D
E
F
1 10
321 4 5 6 7 8 9 10
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.CO
M
100% CONSTRUCTION
DOCUMENTS
635-21-117 Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Phase
Project Director
Issued: Date:
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP:
REPLACE CLINIC COOLING TOWERSTRUCTURAL ABBREVIATIONS,
LEGENDS, AND NOTES
921 NE 13TH ST OKLAHOMA CITY, OK 73104
04/05/22 UJE NJ
S-001
SYM.
# NUMBER
()" INCH OR INCHES
()' FOOT OR FEET
()° DEGREE
= EQUAL
CL CENTERLINE
CL() CHANNEL
HSS() HOLLOW STRUCTURAL SECTION
K() OPEN WEB STEEL JOIST
L() ANGLE
LL() DOUBLE ANGLE
MC() MISCELLANEOUS CHANNEL
S() AMERICAN STANDARD PIPE
W() WIDE FLANGE
WT() STRUCTURAL TEE
A
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ABV ABOVE
ACI AMERICAN CONCRETE
INSTITUTE
ADDL ADDITIONAL
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
APPROX APPROXIMATE
ARCH ARCHITECT OR
ARCHITECTURAL(S)
ASTM AMERICAN SOCIETY FOR
TESTING AND MATERIALS
AT/FP ANTI-TERRORISM/FORCE
PROTECTION
B
B/ BOTTOM OF
BF BOTH FACES
BLDG BUILDING
BLK BLOCK
BM BEAM
BP BASE PLATE OR BEARING PLATE
BRG BEARING
BS BOTH SIDES
BT BENT PLATE
BTR BETTER
BTWN BETWEEN
C
C-C CENTER TO CENTER
CF CUBIC FOOT OR CUBIC FEET
CFS COLD FORMED STEEL
CHAM CHAMFER
CIP CAST IN PLACE
CJ CONTROL
JOINT/CONSTRUCTION JOINT
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPOSITE
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
COORD COORDINATION
CRSI CONCRETE REINFORCING
STEEL INSTITUTE
D d DISTANCE
DB DECK BEARING
db BAR DIAMETER
DBE DECK BEARING ELEVATION
DBL DOUBLE
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DT DOUBLE TEE
DTL DETAIL
DWG(S) DRAWING(S)
DWL DOWEL
E
(E) EXISTING
EA EACH
EF EACH FACE
EL ELEVATION
ELEC ELECTRICAL
EMBED EMBEDMENT
ENGR ENGINEER
EOR ENGINEER OF RECORD
STRUCTURAL ABBREVIATIONS
1. THE CONSTRUCTION DOCUMENTS CONSIST OF THE DRAWINGS, PROJECT SPECIFICATIONS, ADDENDA ISSUED PRIOR TO
EXECUTION OF THE CONTRACT, OTHER DOCUMENTS LISTED IN THE AGREEMENT AND MODIFICATIONS ISSUED VIA SUPPLEMENT
INSTRUCTION.
2. THE CONSTRUCTION DOCUMENTS ARE COMPLIMENTARY, AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IF CONFLICTING REQUIREMENTS ARE FOUND BETWEEN THE DRAWINGS, SPECIFICATIONS AND/OR THESE GENERAL STRUCTURAL NOTES, THE MORE STRINGENT PROVISION SHALL CONTROL UNLESS DIRECTED OTHERWISE IN WRITING
BY THE STRUCTURAL ENGINEER.
3. THE STRUCTURAL GENERAL NOTES SUPPLEMENT THE PROJECT SPECIFICATIONS. REFER TO THE PROJECT SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
4. METHODS, PROCEDURES AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING AND IMPLEMENTING THE NECESSARY PRECAUTIONS TO MAINTAIN AND
ENSURE THE INTEGRITY OF THE STRUCTURE AT ALL STAGES OF CONSTRUCTION.
5. TEMPORARY BRACING, SHEETING, SHORING, ETC, REQUIRED TO ENSURE THE STRUCTURAL INTEGRITY/STABILITY OF EXISTING BUILDINGS, SIDEWALKS, UTILITIES, ETC, DURING CONSTRUCTION IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE
DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER EMPLOYED BY THE CONTRACTOR.
6. IMPLEMENTATION OF JOB SITE SAFETY IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
7. M/E/P/F COORDINATION:
A. THE FOLLOWING ARE NOT SPECIFICALLY, NOR GENERALLY INDICATED ON THE STRUCTURAL DRAWINGS:
a. ANCHORS, HANGERS, AND SUPPORTS FOR EQUIPMENT, PIPING, AND UTILITIES
b. SLEEVES OR BLOCK-OUTS FOR PASSAGE OF DUCTWORK, PIPING, DRAINS, CONDUIT, ETC.
B. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING SUCH REQUIREMENTS PRIOR TO THE FABRICATION OR ERECTION
OF STRUCTURE.
C. PENETRATIONS OF STRUCTURAL MEMBERS ARE SUBJECT TO APPROVAL BY THE ENGINEER.
8. DIMENSIONS AND INSTALLATION DETAILS OF PURCHASED EQUIPMENT MUST BE VERIFIED AND COORDINATED WITH THE SUPPORTING STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING SUCH REQUIREMENTS FROM SUBCONTRACTORS AND EQUIPMENT SUPPLIERS ALONG WITH COORDINATING THE LOCATIONS AND DETAILS FOR THESE ITEMS PRIOR TO FABRICATION OR ERECTION OF THE SUPPORTING STRUCTURE. ADDITIONAL FRAMING MAY BE REQUIRED FOR THE PROPER SUPPORT OF SUCH UNITS AND/OR EQUIPMENT. LATERAL SUPPORT FOR THE EQUIPMENT SHALL BE PROVIDED BY THE EQUIPMENT INSTALLER. ANY CONFLICTS BETWEEN THESE ITEMS AND THE BUILDING STRUCTURE IS TO BE BROUGHT TO THE
ATTENTION OF THE ENGINEER FOR RESOLUTION.
9. THE STRUCTURAL DRAWINGS GOVERN THE WORK FOR STRUCTURAL FEATURES, UNLESS OTHERWISE NOTED. DIMENSIONS SHOWN ON PLANS AND DETAILS ARE TO GOVERN THE STRUCTURAL WORK. THE CONTRACTOR IS TO REFER TO THE ARCHITECTURAL DRAWINGS FOR DIMENSIONS AND DETAILS NOT PROVIDED. DIMENSIONAL CONFLICTS IN THE DOCUMENTS
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
10. WORK NOT INDICATED ON A PART OF THE DRAWINGS, BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT
CORRESPONDING LOCATIONS, IS TO BE REPEATED.
11. ANY EXISTING CONSTRUCTION INFORMATION SHOWN IS BASED UPON EXISTING BUILDING DOCUMENTS AND/OR FROM FIELD OBSERVATION. THE INFORMATION CONTAINED HEREIN MAY REQUIRE ADJUSTMENTS AND/OR MODIFICATIONS TO CONFORM TO EXISTING CONDITIONS. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING BUILDING INFORMATION SHOWN (DIMENSIONS, ELEVATIONS, ETC) AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO FABRICATION OF ANY STRUCTURAL
COMPONENT.
12. DETAILS DESIGNATED AS “TYPICAL DETAILS,” APPLY GENERALLY TO THE DRAWINGS IN AREAS WHERE CONDITIONS ARE SIMILAR
TO THOSE DESCRIBED IN THE DETAILS.
13. SHOP DRAWINGS:
A. SHOP DRAWINGS FOR ALL MATERIALS ARE TO BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO THE START OF
FABRICATION OR COMMENCEMENT OF WORK< PER THE PROJECT SPECIFICATIONS>.
B. SHOP DRAWINGS MUST BE CHECKED AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMISSION. THE CONTRACTOR’S STAMP OF APPROVAL WILL CONSTITUTE CERTIFICATION THAT HE HAS VERIFIED ALL FIELD MEASUREMENTS, CONSTRUCTION CRITERIA, MATERIALS, AND SIMILAR DATA; AND HAS CHECKED EACH DRAWING FOR COMPLETENESS, COORDINATION, AND COMPLIANCE WITH THE CONTRACT DOCUMENTS.
C. SHOP DRAWINGS SHALL BE ORIGINAL DRAWINGS, PREPARED BY CONTRACTOR, SUBCONTRACTOR, SUPPLIER OR DISTRIBUTOR. REPRODUCTION OF STRUCTURAL CONSTRUCTION DOCUMENTS AS ERECTION PLANS OR DETAILS WILL NOT
BE PERMITTED AND WILL BE REJECTED WITHOUT REVIEW.
D. CHANGES TO SHOP DRAWINGS THAT ARE RE-SUBMITTED MUST BE CLOUDED OR SOMEHOW INDICATE THAT A CHANGE HAS
BEEN MADE TO PREVIOUSLY ISSUED AND REVIEWED DRAWING.
E. THE CONTRACTOR IS TO PROVIDE THE ENGINEER WITH WRITTEN NOTICE OF DEVIATIONS OF ANY TYPE FROM THE REQUIREMENTS OF THE CONSTRUCTION DOCUMENTS. THE NOTICE MUST BE RECEIVED PRIOR TO SHOP DRAWING SUBMITTAL. THE CONTRACTOR REMAINS LIABLE FOR ANY DEVIATION UNLESS REVIEWED BY THE ENGINEER AND
ACKNOWLEDGED IN WRITING, PRIOR TO THE RECEIPT OF THE SHOP DRAWINGS.
14. THE GENERAL CONTRACTOR SHALL REPORT PROGRESS OF WORK TO ENGINEER OF RECORD.
15. THE CONSTRUCTION DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS SPECIFICALLY NOTED
OTHERWISE.
16. INSPECTION, TESTING, CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF THE GOVERNING BUILDING CODES AND REFERENCED STANDARDS. ASTM, ASCE, <IBC RFP>, <UFC> AND OTHER STANDARDS SHALL BE PER THE EDITIONS INDICATED IN THE <IBC RFP>, OR AS AMENDED TO LATEST DATE IF NOT SO INDICATED.
17. OBSERVATION VISITS TO THE SITE BY REPRESENTATIVES OF THE ENGINEER OF RECORD SHALL NOT BE CONSTRUED AS INSPECTION OR APPROVAL OF CONSTRUCTION. CONTRACTOR SHALL PROVIDE SPECIAL INSPECTIONS AS INDICATED IN THE STATEMENT OF SPECIAL INSPECTIONS PROVIDED FOR THIS PROJECT [<IN THE SPECIFICATIONS><UNDER SEPARATE COVER>].
18. COORDINATE ANY CONSTRUCTION SITUATION NOT COVERED BY THESE PLANS, GENERAL NOTES, OR SPECIFICATIONS WITH
THE ENGINEER OF RECORD.
19. NON-BEARING INTERIOR WALLS SHALL BE ADEQUATELY BRACED TO THE STRUCTURE ABOVE WITH ALLOWANCE FOR
DEFLECTION OF THE STRUCTURE ABOVE AND/OR BELOW.
20. STAIRS SHALL BE PER THE ARCHITECTURAL DRAWINGS.
21. ELEVATOR MACHINERY SUPPORT BEAMS, GUIDE RAILS, SUPPORTS, ETC., SHALL BE SUPPLIED BY THE ELEVATOR MANUFACTURER. ALL LOADS IMPOSED BY THE ELEVATOR ONTO THE STRUCTURE SHALL BE DETERMINED BY THE ELEVATOR MANUFACTURER AND SHALL BE CLEARLY SHOWN ON SHOP DRAWINGS SUBMITTED FOR REVIEW. ADDITIONAL FRAMING MAY BE REQUIRED FOR THE PROPER SUPPORT OF THESE LOADS. COORDINATE WITH THE ENGINEER OF RECORD.
GENERAL STRUCTURAL NOTES
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE(D)
ETC ET CETERA
EW EACH WAY
EXC EXCAVATE OR EXCAVATION
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F
FD FLOOR DRAIN
FDN FOUNDATION
FF FAR FACE
FIN FINISHED
FL FLOOR
FS FAR SIDE
FT FOOT OR FEET
FTG FOOTING
FULL
PEN
FULL PENETRATION WELD
fy STEEL YIELD STRENGTH
G
GA GAGE OR GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
GR GRADE
GSN GENERAL STRUCTURAL NOTES
H
Hef EFFECTIVE EMBEDMENT
HORIZ HORIZONTAL
HP HIGH POINT
HSA HEADED STUD ANCHOR
HT HEIGHT
I
I.E. IN OTHER WORDS
IBC INTERNATIONAL BUILDING
CODE
ID INSIDE DIAMETER
IN INCH(ES)
INCL INCLUDE(D)(ING), INCLUSIVE
INFO INFORMATION
INT INTERIOR
ISO JT ISOLATION JOINT
J
JB JOIST BEARING
JST JOIST
JT JOINT
K
K KIP(S)
KB KNEE BRACE
KCF KIPS PER CUBIC FOOT
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
L
L LENGTH
LB POUND
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLO LONG LEG OUTSTANDING
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LP LOW POINT
LSL LAMINATED STRAND LUMBER
LVL LAMINATED VENEER LUMBER
ℓd DEVELOPMENT LENGTH ℓdh HOOK DEVELOPMENT LENGTH ℓext STRAIGHT EXTENSION
M
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL(S)
MEP MECHANICAL, ELECTRICAL, AND
PLUMBING
MFR MANUFACTURER
MID MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP MASONRY PIER
N
N NORTH
NF NEAR FACE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OHNG OVERHANG
OPNG OPENING
OPP
HAND
OPPOSITE HAND
P
PCF POUNDS PER CUBIC FOOT
PCI POUNDS PER CUBIC INCH
PEN PENETRATION
PERM PERMANENT
PL PLATE
PLF POUNDS PER LINEAR FOOT
PROJ PROJECTION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PVMT PAVEMENT
Q
QTY QUANTITY
R
RAD RADIUS OR RADII
RE: REFER TO
REF REFERENCE
REINF REINFORCEMENT/REINFORCING
REQD REQUIRED
REV REVISION OR REVISE
RTU ROOF TOP UNIT
S
SC SLIP CRITICAL
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SECT SECTION
SHT SHEET
SIM SIMILAR
SJ SLAB CONTROL JOINT
SL SLOPE(D) OR SLOPING
SLO SHORT LEG OUTSTANDING
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SP SPACE(S)
SPA SPACES OR SPACING
SPEC SPECIFICATIONS
SS STAINLESS STEEL
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL
SW SHEAR WALL
T
T THICKNESS
T&B TOP AND BOTTOM
T&S TEMPERATURE AND SHRINKAGE
T/ TOP OF
TEMP TEMPORARY
THD THREAD(ED)
THK THICKNESS
THRU THROUGH
TMS THE MASONRY SOCIETY
TRANS TRANSVERSE
TSF TONS PER SQUARE FOOT
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
V
VERT VERTICAL
VIF VERIFY IN FIELD
W
W WIDTH
W/ WITH
W/O WITHOUT
WL WIND LOAD
WP WORKING POINT
WT WEIGHT
WWR WELDED WIRE
REINFORCEMENT
1. GOVERNING BUILDING CODES
A. IBC 2018 INTERNATIONAL BUILDING CODE WITH OKLAHOMA CITY AMENDMENTS
B. ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
2. WIND DESIGN CRITERIA
A. ULTIMATE WIND SPEED (Vult) 121 MPH B. NOMINAL DESIGN WIND SPEED (Vasd) 95 MPH
C. EXPOSURE CATEGORY B
3. SEISMIC DESIGN CATEGORY
A. RISK CATEGORY IV
B. SEISMIC IMPORTANCE FACTOR (le) 1.25
C. SITE CLASS C
D. SEISMIC DESIGN CATEGORY C
E. SHORT PERIOD SPECTRAL ACCELERATION (Ss) 0.309
F. ONE SECOND SPECTRAL ACCELERATION (S1) 0.081
G. SHORT PERIOD RESPONSE ACCELERATION (Sds) 0.268 H. ONE SECOND RESPONSE ACCELERATION (Sd1) 0.081 I. SEISMIC RESPONSE COEFFICIENT (Cs) 0.1236
J. SEISMIC RESISTING SYSTEM ORDINARY CONCENTRICALLY BRACED FRAMES
K. RESPONSE MODIFICATION FACTOR (R) 3.25
L. OVERSTRENGTH FACTOR (Ω0) 2.0
M. DEFLECTION AMPLIFICATION FACTOR (Cd) 3.25
N. ANALYSIS METHOD EQUIVALENT LATERAL FORCE PROCEDURE
4. DEAD LOAD BASIS OF DESIGN:
A. BALTIMORE AIRCOIL COMPANY COOLING TOWER
MODEL XES3E-1424-07N-2/SDY 78,410 LBS OPERATING WEIGHT
5. LIVE LOADS
A. MECHANICAL 150 PSF
6. SNOW LOADS
A. GROUND SNOW LOAD (Pg) 10 PSF B. FLAT ROOF SNOW LOAD (Pf) 12 PSF C. SNOW IMPORTANCE FACTOR (Is) 1.20 D. SNOW EXPOSURE FACTOR (Ce) 1.0 E. SNOW THERMAL FACTOR (Ct) 1.2
7. CONSTRUCTION LOADS
A. NOT TO EXCEED THE DESIGN LIVE LOADS.
8. FOUNDATION DESIGN CRITERIA
A. ALLOWABLE SKIN FRICTION FOR PIERS 2 KSF
B. ALLOWABLE END BEARING PRESSURE FOR PIERS 20 KSF
C. FROST BEARING DEPTH 18 INCHES
DESIGN CRITERIA
1. REINFORCED CONCRETE WORK IS TO BE IN ACCORDANCE WITH THE AMERICAN CONCRETE INSTITUTE (ACI) EDITIONS OF:
A. ACI 301 (LATEST EDITION), "SPECIFICATIONS FOR STRUCTURAL CONCRETE".
B. ACI 318 (2014), "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE", EXCEPT AS MODIFIED BY THE IBC.
C. ACI 347 (LATEST EDITION), "GUIDE TO FORMWORK FOR CONCRETE".
2. MIXING, TRANSPORTING, PLACING AND TESTING OF CONCRETE IS TO BE DONE IN ACCORDANCE WITH ACI 301.
3. PRIOR TO CONCRETE PLACEMENT, THE CONTRACTOR MUST SUBMIT CONCRETE MIX DESIGNS FOR EACH TYPE OF CONCRETE TO BE USED, PREPARED IN ACCORDANCE WITH THE SPECIFICATIONS TO THE ENGINEER FOR REVIEW.
4. CAST-IN-PLACE CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH (f'c) AS INDICATED ON THE CONCRETE
MATERIALS SCHEDULE ON DRAWING <S-004>.
5. THE SLUMP AT POINT OF PLACEMENT IS NOT TO EXCEED 4”+/-1” AND THE WATER/CEMENT RATIO IS NOT TO EXCEED 0.45. IF ADDITIONAL SLUMP (UP TO 8”) IS DESIRED FOR PUMPING, A SUPER-PLASTICIZER ADMIXTURE MAY BE ADDED.
6. CONCRETE EXPOSED TO WEATHER AND FREEZE/THAW SHALL HAVE AN AIR CONTENT FROM 5% TO 7% IN ACCORDANCE WITH
ACI RECOMMENDATIONS. AIR ENTRAINING ADMIXTURE SHALL CONFORM TO ASTM C260.
7. CONCRETE TO BE NORMAL WEIGHT CONCRETE (150 PCF) WITH CEMENT CONFORMING TO ASTM C150 TYPE I.
8. HOOKED BARS TO HAVE STANDARD ACI HOOKS UNLESS NOTED OTHERWISE.
9. CONCRETE SHALL BE PROPERLY VIBRATED DURING PLACEMENT.
10. PRIOR TO PLACING CONCRETE, CHECK WITH ALL TRADES TO ENSURE THE FOLLOWING ITEMS ARE INSTALLED, COORDINATED, AND PROVIDED FOR AS REQUIRED BY EQUIPMENT MANUFACTURERS, AND AS SHOWN ON THE ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS: SLEEVES, INSERTS, MECHANICAL OPENINGS, CONDUITS, PIPES, RECESSES, DEPRESSIONS, CURBS, AND OTHER EMBEDDED ITEMS TO BE PROVIDED.
A. ANCHOR BOLTS,RODS, AND DOWELS SHALL BE PLACED PRIOR TO CASTING CONCRETE.
11. ALL CONTACT SURFACES, NEW OR EXISTING, AT CONSTRUCTION JOINTS SHALL BE INTENTIONALLY ROUGHENED TO 1/4"
AMPLITUDE PRIOR TO CASTING ADJACENT POUR.
12. GROUT SOLID AROUND ALL JOIST AND BEAM BEARING POCKETS, TYPICAL UNLESS NOTED OTHERWISE.
13. LEVELING GROUT TO BE NON-SHRINK, FACTORY PREMIXED GROUT IN ACCORDANCE WITH ASTM C1107, HAVING A MINIMUM
COMPRESSIVE STRENGTH OF NOT LESS THAN 5000 PSI.
14. ANCHOR RODS TO BE ASTM F1554 Fy=36 KSI MINIMUM, <GALVANIZED,> UNLESS NOTED OTHERWISE. <DIAMETER AND LOCATIONS SHALL BE AS INDICATED ON THE PRE-ENGINEERED METAL BUILDING DRAWINGS (BY OTHERS). ANCHOR ROD
EMBEDMENT SHALL BE AS INDICATED ON THESE STRUCTURAL DRAWINGS.>
A. ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR PER
MANUFACTURER’S RECOMMENDATIONS.
REINFORCED CONCRETE NOTES
REINFORCING STEEL - CONCRETE NOTES
1. REINFORCING STEEL SHALL BE DEFORMED BARS AND SHALL CONFORM TO ASTM A615 GRADE 60, WITH A DESIGN YIELD
STRENGTH OF 60,000 PSI, EXCEPT AS NOTED BELOW.
A. DOWELS TO BE BENT IN THE FIELD DURING CONSTRUCTION SHALL BE ASTM A706 GRADE 60, "LOW-ALLOY STEEL".
B. REINFORCING TO BE WELDED SHALL BE ASTM A706 GRADE 60, "LOW-ALLOY STEEL".
2. MECHANICAL SPLICE COUPLERS SHALL BE CAPABLE OF DEVELOPING 125% OF THE SPECIFIED STRENGTH OF THE BAR.
3. REINFORCING STEEL SHALL BE FREE OF LOOSE FLAKY RUST, SCALE, GREASE, OIL, DIRT, AND OTHER MATERIALS WHICH MIGHT
AFFECT OR IMPAIR BOND.
4. BENDS SHALL BE MADE COLD. DO NOT USE HEAT. BENDS SHALL BE DONE IN THE FABRICATOR'S SHOP UNLESS SPECIFICALLY
NOTED FOR THE FIELD. DO NOT UN-BEND OR RE-BEND A PREVIOUSLY BENT BAR.
5. NO REINFORCING SHALL BE WELDED UNLESS SPECIFICALLY NOTED AS SUCH. USE E90XX ELECTRODES AND ASTM A706
REINFORCING. COMPLY WITH AWS D1.4 REQUIREMENTS.
6. CODES AND STANDARDS:
A. CONCRETE REINFORCING STEEL INSTITUTE (CRSI) "MANUAL OF STANDARD PRACTICE".
B. AMERICAN CONCRETE INSTITUTE, ACI 315 (OR SP-66) "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT".
7. REINFORCING SHALL BE DETAILED, FABRICATED, BOLSTERED, AND SUPPORTED PER ACI 315.
8. SPLICES IN CONTINUOUS REINFORCING IN CONCRETE SHALL BE PER THE CONCRETE REINFORCING LAP SPLICE SCHEDULE.
9. REINFORCING STEEL SHALL HAVE COVER PER THE CONCRETE COVER SCHEDULE.
10. REINFORCING STEEL SHALL BE SECURELY ANCHORED AND TIED IN PLACE PRIOR TO PLACING CONCRETE. IF REQUIRED, ADDITIONAL BARS, STIRRUPS, OR CHAIRS SHALL BE PROVIDED BY THE CONTRACTOR FOR SUPPORT OF ALL BARS WHERE
NECESSARY DURING CONSTRUCTION.
CONCRETE MATERIALS SCHEDULE
STRUCTURAL
ELEMENT
MIN f'c 28 DAYS
(PSI)
MAX
WATER/CEMENT
RATIO AGGREGATE AIR CONTENT REMARKS
WALLS 4000 0.45 #57 2%
FOOTINGS 3000 0.45 #57 EXT 5-7%
INT 2%
INTERIOR SLABS 4000 0.45 #57 2%
EXTERIOR SLABS 4000 0.45 #57 5-7%
<LIGHTWEIGHT>
COMP FLOOR DECK
4000 0.45 #57 2% DESIGN DENSITY=110 PCF
04/05/2022
A
B
C
SF3111
SF311
SF311
SF311
7" 14'-11 1/2" 7"
1'-0"
TYP
3'-0"
T Y
P
3' -0
1'
-0
1'-0"
1' -0
5"
5"
5"
7"
'-9
/2
'-9
/2
7"
HSS4X
4X
1/4
BP2 HSS4X
4X
1/4
BP2
HSS4X
4X
1/4
BP1 HSS4X
4X
1/4
BP1
HSS4X
4X
1/4
BP2 HSS4X
4X
1/4
BP2
CONC SLAB,
SEE…