60716955_Issued for Bid.pdf
PDF 5 MB Posted
- Attached to
- Request For Proposal (RFP) Fire Protection Upgrades - Transit Administration and Garage Facility
- Solicitation number
- RFP-0613-0-2024/JU
- Issued by
- Winnebago County, Wisconsin
About this file
This document is the official Request for Proposal (RFP) issued by the City of Oshkosh, Wisconsin for fire protection upgrades to the Transit Administration and Garage Facility. The project involves the installation of fire sprinklers, fire alarm systems, and fire-rated doors throughout the facility. The work will be performed with a combination of federal and local funding. The RFP includes contract drawings, federal clauses and forms, insurance requirements, and standard specifications. Proposals are due by a specific date, and the selected contractor will be required to coordinate with other trades during the installation.
The RFP does not specify any pricing terms, set-asides, or incumbent information. It states the project will be funded through federal and local sources, but the exact funding amounts are not provided. The RFP indicates the selected contractor must be a qualified, licensed firm experienced in the design and installation of fire protection systems.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
City of Oshkosh
INDEX OF DRAWINGS
Winnebago County, Wisconsin
CONTACT INFORMATION
ISSUED
06/14/2024 ISSUED FOR BID
PREPARED BY: AECOM TECHNICAL SERVICES, INC.
PROJECT NUMBER: 60716955
SHEET NO. DESCRIPTION
G-100 Cover G-101 Legend and Notes FA-101 Fire Alarm Layout FACP-1 Fire Alarm Riser Diagram FP-100 Notes FP-101 Fire Protection Details FS-101 Sprinkler Layout FS-102 Underground Layout
PROJECT LOCATION
AREA
FIRE PROTECTION UPGRADES -
TRANSIT ADMINISTRATION AND GARAGE FACILITY
KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
AR
C
H D
4" x
6"
CONSULTANT
I/R DATE DESCRIPTION
ISSUE/REVISION
0 2024.06.14 ISSUED FOR BID
SHEET TITLE
COVER
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D W
G
L as t s av ed b y:
F
U N
SE
TH
N t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
G-100
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
FIRE SUPPRESSION LEGEND AND SYMBOLS
SYMBOL
F FIRE SERVICE MAIN
GATE VALVE - OS&Y
INDICATING BUTTERFLY VALVE
CHECK VALVE
PIPE CAP
PIPE ELBOW DOWN
PIPE ELBOW UP
PIPE TEE DOWN
PIPE TEE UP
PS
WF
VS
PRESSURE SWITCH
WATER FLOW SWITCH
VALVE SUPERVISORY SWITCH
DRY SPRINKLER RISER
N DRY PIPE VALVE CABINET WITH INTEGRAL NITROGEN GENERATOR
NOTE: SYMBOLS INCLUDED ARE STANDARD SYMBOLS. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT.
FIRE SUPPRESSION ZONE BOUNDARY
FIRE ALARM LEGEND AND SYMBOLS
SYMBOL
S P
AIM
AOM
CD WP
CD
F
F
WP
C
CD WP
CD WP
FACP
BPS
F
WP
C
WP
WALL-MOUNTED HORN ONLY
CEILING-MOUNTED HORN ONLY
WALL-MOUNTED STROBE
CEILING-MOUNTED STROBE
FIRE ALARM CONTROL PANEL
NOTIFICATION APPLIANCE BOOSTER POWER SUPPLY
ELECTRIC WATER ALARM BELL
NOTE: SYMBOLS INCLUDED ARE STANDARD SYMBOLS. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT.
7. ALL FLOOR AND WALL CONDUIT PENETRATIONS SHALL BE SLEEVED AND SEALED AS REQUIRED. PROVIDE FIRE STOPPING FOR ALL PENETRATIONS FOR CONDUITS OR PIPING PASSING THROUGH FLOOR SLABS, FIRE-RATED WALLS, RATED PARTITIONS, RATED CORRIDOR WALLS, AND VERTICAL SERVICE SHAFTS IN ACCORDANCE WITH NFPA 72.
8. CONDUIT SIZE AND PERCENTAGE OF FILL SHALL BE DETERMINED BY INSTALLING CONTRACTOR AND SHALL COMPLY
WITH ALL APPLICABLE STANDARDS AND SYSTEM MANUFACTURER'S REQUIREMENTS.
9. CONDUIT AND WIRING SHALL BE CONCEALED ABOVE CEILINGS IN FINISHED AREAS OR AREAS WITH DROPPED CEILINGS.
CONDUIT AND WIRING INSTALLED ABOVE CEILINGS SHALL NOT INTERFERE WITH THE REMOVAL OF THE CEILING TILES AND HVAC UNIT AIR FILTERS. IN AREAS WITHOUT CEILINGS, CONDUIT AND WIRING SHALL BE INSTALLED AS TIGHT AS
POSSIBLE TO UNDERSIDE OF FLOOR SLAB, UNLESS OBSTRUCTIONS REQUIRE OTHERWISE.
10. FIRE ALARM WIRING SHALL NOT BE INSTALLED IN THE SAME CONDUITS OR JUNCTION BOXES AS LIGHTING, POWER, OR
OTHER WIRING.
11. INSTALL ALL WIRING IN METALLIC CONDUIT. WATERTIGHT FLEX AND FLEXIBLE CONDUIT SHALL BE PERMITTED WITHIN 10
FT OF DEVICES. USE WATERTIGHT FLEX FOR DEVICES IN POTENTIALLY WET AREAS.
12. FLOW SWITCHES, PRESSURE SWITCHES, AND VALVE TAMPER SWITCHES ATTACHED TO THE SPRINKLER SYSTEM TO PROVIDE REQUIRED SUPERVISION SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM. PROVIDE A SEPARATE ADDRESS
FOR EACH FLOW SWITCH, PRESSURE SWITCH, AND TAMPER SWITCH.
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
WALL-MOUNTED HORN/STROBE
CEILING-MOUNTED HORN/STROBE
SMOKE DETECTOR
DESCRIPTION
FIRE ALARM GENERAL NOTES:
1. FIRE ALARM SYSTEM WORK SHALL COMPLY WITH NFPA 72 AND WITH THESE CONTRACT DOCUMENTS.
2. CONTRACTOR SHALL PROVIDE FINAL SYSTEM LAYOUT DRAWINGS INCLUDING BATTERY CALCULATIONS AND VOLTAGE DROP CALCULATIONS AND OBTAIN APPROVAL OF ALL AHJs. BATTERY CALCULATIONS SHALL INCLUDE 20 PERCENT
SAFETY MARGIN TO THE CALCULATED AMP-HOUR RATING.
3. IT IS THE INTENT OF THESE DOCUMENTS THAT THE CONTRACTOR IS TO PROVIDE DESIGN, MATERIALS, AND EQUIPMENT FOR A TOTALLY FUNCTIONING AND OPERATING FIRE ALARM, INCLUDING THE PROPER INTERFACING AND COORDINATING
WITH ALL OTHER BUILDING SYSTEMS.
4. THE GENERAL CHARACTER AND SCOPE OF THE WORK IS ILLUSTRATED IN THE SPECIFICATIONS AND THE DRAWINGS. THE SPECIFICATIONS AND DRAWINGS ARE DIVIDED INTO SEVERAL SECTIONS FOR CONVENIENCE ONLY AND ALL OF THE CONTRACT DOCUMENTS SHALL BE CONSIDERED AS A WHOLE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
COORDINATION OF ALL TRADES, SUBCONTRACTORS, AND VENDORS ENGAGED IN THIS WORK.
5. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF FIRE ALARM SYSTEM EQUIPMENT AND FIELD DEVICES. FINAL LOCATIONS, QUANTITIES, AND APPLIANCE RATINGS SHALL BE PROVIDED BY THE INSTALLING CONTRACTOR IN
ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND CONTRACT DOCUMENTS.
6. INSTALLING CONTRACTOR SHALL COORDINATE WITH MECHANICAL, ELECTRICAL, AND OTHER TRADES TO FACILITATE INSTALLATION THAT IS COORDINATED AND CONSISTENT WITH BUILDING DESIGN, USE, AND INTENT.
ABBREVIATIONS:
AFF
AHJ
AIM
AOM
ASCE
ASTM
BPS
CD
EL
FACP
FDC
FF
FNPT
FM
FT
G.I.
GPM
HVAC
IN
ISO
NAC
NC
NFPA
NIC
NO
OS&Y
PSI
SLC
SQFT
TS
UL
WF
WP
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
AMERICAN SOCIETY OF CIVIL ENGINEERS
AMERICAN SOCIETY FOR TESTING AND MATERIALS
BOOSTER POWER SUPPLY
CANDELA RATING
ELEVATION
FIRE ALARM CONTROL PANEL
FIRE DEPARTMENT CONNECTION
FINISHED FLOOR
FEMALE NATIONAL PIPE THREAD
FACTORY MUTUAL
FEET
GALVANIZED IRON
GALLONS PER MINUTE
HEATING, VENTILATION, AND AIR CONDITIONING
INCH
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION
NOTIFICATION APPLIANCE CIRCUIT
NORMALLY CLOSED
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NORMALLY OPEN
OUTSIDE SCREW & YOKE
POUNDS PER SQUARE INCH
SIGNALING LINE CIRCUIT
SQUARE FEET
TAMPER SWITCH
UNDERWRITERS LABORATORIES
WATER FLOW SWITCH
WEATHERPROOF
NEW FIRE ALARM SYSTEM:
NFPA 72, 2019 EDITION
ADDRESSABLE
LOCATION NEAR FIRE RISERS
WATERFLOW AND PULL STATIONS WITH
SMOKE DETECTOR FOR PANEL
A-V APPLIANCES
DESCRIPTION
FIRE SUPPRESSION GENERAL NOTES: APPLICABLE CODES:
1. CONTRACTOR SHALL PROVIDE THE DESIGN AND INSTALLATION OF AN AUTOMATIC, SUPERVISED FIRE SPRINKLER
SYSTEM THROUGHOUT THE BUILDING AS SHOWN.
2. THE FIRE PROTECTION SYSTEM SHALL COMPLY WITH ALL LOCAL CODES AND THESE CONTRACT DRAWINGS.
3. ALL FIRE PROTECTION MATERIALS SHALL BE UL-LISTED AND/OR FM-APPROVED.
4. INSTALLING CONTRACTOR SHALL OBTAIN APPROVAL AS REQUIRED BY ALL AHJs.
5. IT IS THE INTENT OF THESE DOCUMENTS THAT THE CONTRACTOR PROVIDES DESIGN, MATERIALS, AND EQUIPMENT FOR A TOTALLY FUNCTIONING AND OPERATING FIRE PROTECTION SYSTEM, INCLUDING THE PROPER INTERFACING AND
COORDINATING WITH ALL OTHER BUILDING SYSTEMS.
6. THE GENERAL CHARACTER AND SCOPE OF THE WORK IS ILLUSTRATED IN THE SPECIFICATIONS AND DRAWINGS. THE SPECIFICATIONS AND DRAWINGS ARE DIVIDED INTO SEVERAL SECTIONS FOR CONVENIENCE ONLY AND ALL OF THE CONTRACT DOCUMENTS SHALL BE CONSIDERED AS A WHOLE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
COORDINATION OF ALL TRADES, SUBCONTRACTORS, AND VENDORS ENGAGED IN THIS WORK.
7. THE SPRINKLER SYSTEM CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING ALL CONFLICTS BETWEEN FIRE PROTECTION SYSTEMS AND LIGHTING FIXTURES, DIFFUSERS, GRILLES, DUCTS, EQUIPMENT FIXTURES, STRUCTURAL MEMBERS, PIPES, CONDUITS, AND OTHER OBSTRUCTIONS ENCOUNTERED. SPRINKLERS SHALL BE INSTALLED IN
OBSTRUCTED AREAS IN ACCORDANCE WITH NFPA 13.
8. PIPING LAYOUTS, WHERE SHOWN, ARE DIAGRAMMATIC AND SHOW SYSTEM INTENT. PIPING MAY REQUIRE ADDITIONAL OFFSETS, DROPS, AND RISERS. SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL PIPING LAYOUT AND
HYDRAULIC CALCULATIONS.
9. ALL SPRINKLER PIPING SHALL BE INSTALLED SO THAT ALL PORTIONS OF THE SYSTEM CAN BE DRAINED BACK THROUGH THE MAIN DRAIN VALVES. WHERE TRAPPED SECTIONS OF PIPING CANNOT BE AVOIDED, AUXILIARY DRAINS SHALL BE
PROVIDED IN ACCORDANCE WITH NFPA 13.
10. LOCATE CONTROL VALVES, TEST VALVES, AND LOW POINT DRAIN VALVES IN READILY ACCESSIBLE AREAS WITHIN 7'-0" ABOVE THE FINISHED FLOOR. WHEN VALVES ARE LOCATED IN FINISHED AREAS, LOCATE ABOVE FALSE CEILING AND PROVIDE ACCESS POINT. TEST VALVES AND EXTERIOR DRAINS SHALL DISCHARGE TO THE OUTSIDE OF THE BUILDING
ONTO A PAVED SURFACE OR CONTRACTOR-PROVIDED SPLASHBLOCK.
11. ALL NEW SPRINKLER CONTROL VALVES SHALL BE ELECTRICALLY SUPERVISED BY THE BUILDING FIRE ALARM SYSTEM
UNLESS OTHERWISE NOTED.
12. MARKING AND IDENTIFICATION OF CONTROL VALVES, DRAINS, TEST CONNECTIONS, AND OTHER EQUIPMENT SHALL BE
PROVIDED IN ACCORDANCE WITH NFPA 13.
13. PROVIDE A MINIMUM CLEARANCE OF 3'-0" IN FRONT OF AND 1'-0" BEHIND ALL FIRE SUPPRESSION VALVES AND
ASSOCIATED EQUIPMENT.
SYSTEM TYPE: DRY
HAZARD CLASSIFICATION: ORDINARY HAZARD GROUP 2
SPRINKLER DENSITY: 0.20 GPM/SQFT
DESIGN AREA: 1950 SQFT
MAXIMUM SPRINKLER COVERAGE AREA: 130 SQFT
HOSE STREAM ALLOWANCE: 250 GPM
HAZARD CLASSIFICATION: EXTRA HAZARD GROUP 1
SPRINKLER DENSITY 0.30 GPM/SQFT
DESIGN AREA: AS SHOWN ON DRAWINGS PLUS 15 FT PERIMETER PER NFPA 13
MAXIMUM SPRINKLER COVERAGE AREA 100 SQFT
HAZARD CLASSIFICATION : EXTRA HAZARD GROUP 2
SPRINKLER DENSITY 0.40 GPM/SQFT
DESIGN AREA AS SHOWN ON DRAWINGS PLUS 15 FT PERIMETER PER NFPA 13
MAXIMUM SPRINKLER COVERAGE AREA 100 SQFT
AUTHORITY HAVING JURISDICTION: WISCONSIN STATE FIRE MARSHAL AND
CITY OF OSHKOSH, WISCONSIN
INTERNATIONAL BUILDING CODE, 2015 EDITION, WITH LOCAL AMENDMENTS
INTERNATIONAL FIRE CODE, 2015 EDITION, WITH LOCAL AMENDMENTS
NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
THEIR APPURTENANCES, 2019 EDITION
NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION
NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2019 EDITION
WATER SUPPLY:
1. CONTRACTOR SHALL OBTAIN RECENT FIRE HYDRANT FLOW TEST DATA FOR USE IN HYDRAULIC
CALCULATIONS. FLOW TEST DATA UTILIZED IN CALCULATIONS SHALL BE NO MORE THAN 12 MONTHS
OLD AT THE TIME OF CALCULATION SUBMISSION IN ACCORDANCE WITH NFPA 13.
FIRE SUPPRESSION
HAZARD CLASSIFICATION:
WISCONSIN STATE FIRE CODE
14. UNDERGROUND PIPING TO BE BURIED A MINIMUM OF 6.5' BELOW GRADE
F MANUAL PULL STATION
KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AR
C
H D
4" x
6"
SHEET TITLE
NOTES
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D t s av ed b y:
F
U N
SE
t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
G-101
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
CONSULTANT
I/R DATE DESCRIPTION
ISSUE/REVISION
0 2024.06.14 ISSUED FOR BID
C D EA H K L
MEZZANINE ABOVE
MEZZANINE ABOVE
WASTE OIL STORAGE
'-0
58'-0"
'-0
'-0
309'-3 3/4"
3' -8
251'-3 3/4"
3'-10"
10'x20'
OFFICE
OPEN
ABOVE
STORAGE
1'-0"58'-0"
4' -0
'-0
6' -4
'-0
'-0
2' -2
3'
-7
3' -4
MEZZANINE
ABOVE
OFFICES
OFFICE SPACE NOT
WITHIN SCOPE
EXCEPT FOR PULL
STATION
DOOR TO BE REPLACED WITH 2-
HOUR RATED DOOR AND HARDWARE
DOOR TO BE REPLACED
WITH 2-HOUR RATED
DOOR AND HARDWARE
'-0
B F G J
2A
4A
87'-0"
'-0
'-0
130'-0"
'-0
'-0
57'-0"
'-1
'-0
80'-0"
55'-0"
'-0
'-0
FIRE RATED
STAIRWELL
8' -0
10'-0"
36'-0 19/32"
36'-0"
'-0
75'-0"
105'-0"
MOVEABLE TIRE RACKS
AREA CHANGES
'-0
'-0
/4
'-0
'-0
/4
STAIRS UP
20'-0"
10'x60' OFFICE WITH MEZZANINE ABOVE
STAIRS UP
STAIRS UP
2 HOUR FIRE RATED WALLS
NOTE:
DIMENSIONS ARE NOT EXACT; CONTRACTOR RESPONSIBLE FOR
VERIFYING ALL DIMENSIONS PRIOR TO BIDDING.
NEW RISER LOCATIONS (2) ADJUSTABLE TO
CLEAR INTERFERENCES IN FOUNDATION
AND INTERIOR. INCLUDES BACKFLOW
PREVENTER
2 HOUR FIRE RATED WALL ABOVE MEZZANINE
F
F FACP
S P
AIM AIM AIM
VS WF PS
TYP. EACH RISER
N
75 CD
75 CD WP
75 CD
75 CD
75 CD WP
75 CD
75 CD
75 C D
W P
75 C D
W P
C
D
C
D
C
D
P
75 CD
75 CD
75 CD
75 CD WP
75 CD
75 CD
75 CD
75 CD
75 CD
F
F
F
F
F
F
75 CD
75 CD
75 CD
F
BELOW MEZZANINE
ABOVE MEZZANINE
RATED FLOOR
KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AR
C
H D
4" x
6"
SHEET TITLE
FIRE ALARM LAYOUT
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D t s av ed b y:
F
U N
SE
t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
FA-101
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
FEET
0 75 150
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
CONSULTANT
I/R DATE DESCRIPTION
ISSUE/REVISION
0 2024.06.14 ISSUED FOR BID
AutoCAD SHX Text
75 75 75 75 75
WP WP WP WP WP
AIM AIM AIM AIM AIM AIMF
S
F F F
FACP
9 3
TO FACP TO FACP
TYP 5
FIRE ALARM RISER DIAGRAM
SCALE: DIAGRAMATIC
TYP
120VAC POWER
POWER SUPPLY WITH 72
HOUR BACKUP BATTERIES
AND CHARGE CONTROLLER
CLASS 'B' FA NOTIFICATION AND
DETECTION SYSTEM, TYPICAL
GENERAL NOTES:
1. PROVIDE SURGE PROTECTIVE DEVICE ( SPD) ON THE POWER SUPPLY CIRCUITS TO THE FACP.
2. ACTUATION OF ANY PULL STATIONS SHALL IMMEDIATELY CAUSE THE FACP TO ACTIVATE THE
FACILITY FIRE EVACUATION ALARM SIGNAL THROUGHOUT THE FACILITY.
KEYED NOTES:
2 2#12 AWG & 1#12 AWG GND IN 3/4"C FOR 120V POWER.
3 RISER IS DIAGRAMATIC, REFER TO FLOOR PLANS FOR EXACT QUANTITIES OF DEVICES.
4 PROVIDE CONDUIT AND SIGNAL WIRE PER MANUFACTURERS RECOMMENDATIONS, MINIMUM WIRE
SIZE FOR THIS CIRCUIT SHALL BE #14 AND SHALL BE SOLID COOPER WIRE.
5 PROVIDE CIRCUIT PROTECTION FOR ALL FIRE ALARM SYSTEMS AND CIRCUITS.
9 NAC WIRING SHALL NOT BE INSTALLED IN SAME CONDUIT WITH SLC LOOP WIRING TYPICAL.
J
INTERIOR HORN STROBES
EXTERIOR HORN/STROBES
INITIATION DEVICES
KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AR
C
H D
4" x
6"
SHEET TITLE
FIRE ALARM RISER DIAGRAM
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D t s av ed b y:
F
U N
SE
t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
FACP-1
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
CONSULTANT
I/R DATE DESCRIPTION
FIRE SUPPRESSION SPECIFICATIONS:
1. ALL EQUIPMENT, PIPING, HANGERS SUPPORT METHODS, AND SPRINKLER HEADS TO BE INSTALLED IN STRICT
ACCORDANCE WITH ALL APPLICABLE LOCAL CODES.
2. OBTAIN AND AHDERE TO ALL REQUIRED PERMITS, LICENSES, AND GOVERNMENT REQUIREMENTS.
4. THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL BE A FULLY QUALIFIED, LICENSED FIRE SUPPRESSION CONTRACTOR, EXPERIENCED IN THE DESIGN AND INSTALLATION OF AUTOMATIC FIRE SUPPRESSION SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT, AND A REGULAR SUPPLIER OF THE EQUIPMENT FOR WHICH IT IS RESPONSIBLE.
EACH CONTRACTOR SHALL SUBMIT A STATEMENT OF QUALIFICATION TO PERFORM THIS TYPE OF WORK, WHICH CITES AT LEAST TWO (2) INSTALLATIONS OF SIMILAR TYPE PERFORMED WITHIN THE PRECEDING SEVEN (7) YEARS OF THE BID.
5. WARRANT ALL PIPING, DEVICES, CONNECTIONS, HANGERS, AND ITEMS SUPPLIED TO BE FREE FROM DEFECTS AND PERFORM THE SPECIFIED FUNCTIONS WHEN USED FOR THEIR INTENDED PURPOSE. ANY ITEM FOUND TO BE DEFECTIVE WITHIN ONE (1) YEAR FROM FINAL SYSTEM ACCEPTANCE WILL BE REPAIRED, CORRECTED, OR REPLACED (PARTS AND
LABOR), AS APPROPRIATE, AT NO COST TO THE OWNER.
6. SHOP DRAWINGS SHALL COMPLY WITH ALL REQUIREMENTS OF NFPA 13. PROVIDE LAYOUT DRAWINGS, PRODUCT DATA AND HYDRAULIC CALCULATIONS AS ONE COMPLETE SUBMITTAL PACKAGE. FAILURE TO DO SO WILL RESULT IN
SUBMITTAL BEING RETURNED "CORRECT AND RESUBMIT."
7. OBTAIN APPROVAL OF THE SPRINKLER SHOP DRAWINGS FROM THE CLIENT INSURANCE CARRIER, THE FIRE MARSHAL, AND ALL LOCAL AHJs PRIOR TO ANY FABRICATION OR INSTALLATION.
8. PIPE INDICATED IN DESIGN DRAWINGS SHALL BE NEW, DESIGNED FOR A WORKING PRESSURE OF 175 PSI, CONFORM TO ASTM SPECIFICATIONS, AND HAVE THE MANUFACTURER'S NAME OR BRAND ALONG WITH THE APPLICABLE ASTM STANDARD PERMANENTLY MARKED ON EACH LENGTH OF PIPE. THE MINIMUM DIAMETER OF ANY SECTION OF
AUTOMATIC SPRINKLER PIPE SHALL BE 1 INCH EXCEPT AS OTHERWISE NOTED.
9. DRY SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPING WHEN NITROGEN GENERATION SYSTEMS ARE USED AND SCHEDULE 40 GALVANIZED PIPING OTHERWISE, WITH THREADED OR CUT GROOVED ENDS AND FITTINGS. FOR
DRY SPRINKLER PIPING SIZES 2 INCH AND SMALLER THREADED JOINTS SHALL BE USED.
10. WHERE SEISMIC BRACING IS REQUIRED BASED ON A BUILDING'S SEISMIC DESIGN CATEGORY, PIPE HANGERS AND BRACING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 13 AND ASCE 7. SHOP DRAWINGS SHALL INCLUDE SEISMIC
LOAD CALCULATIONS AS REQUIRED BY NFPA 13 AND THE AHJ.
11. ALL PIPING SHALL BE SUPPORTED BY MEANS OF FM-APPROVED AND UL-LISTED HANGERS. SPACING AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13. HANGERS SHALL BE WROUGHT IRON ADJUSTABLE SWIVEL LOOP TYPE. FOR HANGER ASSEMBLIES UNDER STEEL MEMBERS USE TOP BEAM CLAMPS, THREADED ROD AND PIPE RING. PROVIDE ADJUSTABLE HANGERS AS REQUIRED FOR PROPER SUPPORT OF ALL PIPELINES. TRAPEZE HANGERS SHALL BE USED
WHERE NECESSARY TO TRANSFER LOADS TO APPROPRIATE STRUCTURAL MEMBERS.
12. NO CUTTING, DRILLING, WELDING, OR BURNING OF ANY STRUCTURAL STEEL MEMBER SHALL BE ALLOWED. POWDER DRIVEN STUDS ARE ALLOWABLE PROVIDED IT CAN BE DEMONSTRATED THAT NO SIGNIFICANT SPALLING WILL OCCUR, AND THAT WITNESSED PULL TESTS CERTIFY LOAD CAPACITY. ALL BOLTS AND THREADED RODS SHALL BE USED WITH A DOUBLE NUT AND WASHER, OR A SINGLE NUT, WASHER, AND LOCK WASHER WHEREVER A SINGLE UNSECURED NUT
COULD WORK LOOSE AND ALLOW EITHER THREADED ROD OR SUPPORTED PIPING TO DROP.
13. STARTING LENGTH, END LENGTH, AND ALTERNATE LENGTHS OF MAIN PIPING WITH GROOVED JOINT COUPLINGS SHALL BE PROVIDED WITH TWO (2) SUPPORTS. THERE SHALL BE NOT LESS THAN ONE (1) HANGER FOR EACH SECTION OF PIPE.
THE UNSUPPORTED LENGTH BETWEEN THE END SPRINKLER AND THE LAST HANGER ON THE LINE SHALL NOT BE
GREATER THAN THE FOLLOWING:
NOMINAL PIPE DIAMETER [IN]
1¼
1½ OR LARGER
LENGTH [IN]
14. HANGER SPACING SHALL COMPLY WITH FITTING MANUFACTURER'S RECOMMENDATIONS WHERE APPLICABLE. MAXIMUM
HANGER SPACING SHALL BE AS FOLLOWS:
NOMINAL PIPE DIAMETER [IN]
1- 1¼ 1½ -8
LENGTH [FT]
15. ADDITIONAL SPRINKLERS AND SPRINKLER WRENCHES SHALL BE PROVIDED IN A CABINET INSTALLED WITHIN BUILDING PREMISES AT A LOCATION VERIFIED BY THE CLIENT AND PROPERTY MANAGER. THE ADDITIONAL HEADS SHALL CONSIST OF A MINIMUM OF SIX (6) HEADS WITH THE NUMBER OF EACH TYPE PROPORTIONAL TO THE NUMBER OF EACH TYPE
FURNISHED.
16. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY.
17. PROTECT AND SEAL ALL OPENINGS AND PIPE PENETRATIONS THROUGH FIRE-RATED WALLS AND CEILINGS WITH ADEQUATE FIRESTOPPING MATERIALS TO MAINTAIN THE FIRE RATINGS OF THE ASSEMBLIES BEING PENETRATED.
18. PROVIDE CEILING/WALL ACCESS PANELS WHERE REQUIRED TO ACCESS EQUIPMENT. PANELS SHALL BE RECESSED TYPE, FIRE-RATED IF IN FIRE-RATED WALLS OR CEILINGS. LOCATIONS OF PANELS SHALL BE COORDINATED WITH ALL OTHER
TRADES.
19. KEEP PIPE END OPENINGS CLOSED BY CAPS AND PLUGS DURING CONSTRUCTION.
20. OFFSET PIPING AS NECESSARY TO AVOID INTERFERENCE WITH OTHER WORK AND TO MAINTAIN A MINIMUM HEADROOM
OF 7'-0" IN OPEN CEILING AREAS. PROVIDE PROPER DRAIN WHERE NECESSARY.
21. THE SPRINKLER SYSTEM SHALL BE INSTALLED SO THAT NO PART WILL INTERFERE WITH DOORS, WINDOWS, HEATING, AIR CONDITIONING, PLUMBING, OR ELECTRICAL EQUIPMENT.
22. PIPING SHALL BE INSTALLED, WHETHER INDICATED OR NOT, SO AS TO RISE AND/OR DROP IN ORDER TO MAINTAIN THE DESIRED CLEAR HEIGHTS BY CLEARING CONDUITS, LIGHT FIXTURES, PIPES, DUCTWORK, STRUCTURAL MEMBERS, ETC.
23. SPRINKLER PIPING SHALL BE INSTALLED SO THAT THE SYSTEM MAY BE DRAINED. TRAPPED PIPING SHOULD BE DRAINED BY AUXILIARY DRAINS. A DRAIN CONNECTION WITH CONTROL VALVE SHALL BE PROVIDED AT THE BASE OF EACH RISER.
24. ALL PIPING AND FIRE SPRINKLER SYSTEM COMPONENTS SHALL BE TESTED ACCORDING TO THE SYSTEMS ACCEPTANCE
CRITERIA REQUIRED BY NFPA 13.
25. DRY PIPE SPRINKLER SYSTEMS SHALL BE PRESSURIZED WITH NITROGEN. THE NITROGEN GENERATOR AND ALL HYDRAULIC, PNEUMATIC AND ELECTRICAL COMPONENTS REQUIRED FOR THE CONTROL OF THE DRY PIPE SPRINKLER SYSTEM SHALL BE FACTORY-ASSEMBLED IN A SINGLE CABINET. THE CABINET SHALL BE PRE-ASSEMBLED, PRE-WIRED
AND FACTORY-TESTED UNDER ISO-9001 MANUFACTURING AND QUALITY CONTROL PROCEDURES.
2. ACCEPTANCE: REPRESENTATIVES OF THE AHJs AND THE OWNER'S REPRESENTATIVE SHALL BASE ACCEPTANCE OF THE AUTOMATIC SPRINKLER WORK UPON THE INSPECTION AND TESTS OF THE COMPLETED INSTALLATION.
3. THE INSTALLING COMPANY SHALL FURNISH A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE COUNTERSIGNED BY THE PROPERTY OWNER OR REPRESENTATIVE PRIOR TO REQUESTING FINAL APPROVAL FROM THE AHJ.
4. TESTS SHALL BE MADE BY THE CONTRACTOR IN THE PRESENCE OF THE AHJ OR THE OWNER'S REPRESENTATIVE.
5. ADDITIVES, CORROSIVE CHEMICALS SUCH AS SODIUM SILICATE, BRINE, OR OTHER CHEMICALS SHALL NOT BE USED
WHILE HYDROSTATICALLY TESTING SYSTEMS OR FOR STOPPING LEAKS.
6. ALL NEW CONTROL VALVES SHALL BE FULLY CLOSED AND OPENED UNDER SYSTEM WATER PRESSURE TO ENSURE
PROPER OPERATION.
7. PRELIMINARY TESTS: EACH SYSTEM SHALL BE HYDROSTATICALLY TESTED BY THE CONTRACTOR AT A MINIMUM OF 200 PSI FOR A PERIOD OF TWO (2) HOURS. PIPING SHALL BE FLUSHED IN ACCORDANCE WITH NFPA 13. PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO WORKING PRESSURE IN EXCESS OF 150 PSI SHALL BE TESTED AT A PRESSURE OF 50 PSI IN EXCESS OF THE NORMAL WORKING PRESSURE. PIPING ABOVE SUSPENDED CEILINGS SHALL BE INSPECTED BEFORE TESTING. THE ALARMS AND OTHER DEVICES SHALL BE TESTED BY THE CONTRACTOR. THE WATER FLOW ALARMS SHALL BE TESTED BY FLOWING WATER THROUGH THE TEST AND DRAIN ASSEMBLY. THE CONTRACTOR SHALL SUBMIT A SIGNED AND DATED CERTIFICATE WITH REQUEST FOR A FORMAL INSPECTION AND TESTS SIMILAR TO THAT SPECIFIED IN NFPA 13 WHEN ALL CONNECTIONS HAVE BEEN MADE AND TESTS HAVE BEEN COMPLETED.
8. FORMAL INSPECTION AND TESTS: TESTS SHALL BE PERFORMED ON THE AUTOMATIC SPRINKLER SYSTEM AS REQUIRED BY THE LOCAL FIRE DEPARTMENT. THE OWNER, OWNER'S REPRESENTATIVE, INSURANCE COMPANY REPRESENTATIVES AND THE LOCAL FIRE DEPARTMENT WILL WITNESS FORMAL TESTS AND APPROVE ALL SYSTEMS BEFORE THEY ARE ACCEPTED. THE REQUEST FOR FORMAL INSPECTION SHALL BE SUBMITTED AT LEAST FIFTEEN (15) DAYS PRIOR TO THE DATE THE INSPECTION IS TO TAKE PLACE. AN EXPERIENCED TECHNICIAN REGULARLY EMPLOYED BY THE SPRINKLER INSTALLER SHALL BE PRESENT DURING THE INSPECTION. AT THE INSPECTION, ANY OR ALL OF THE REQUIRED TESTS SHALL BE REPEATED AS DIRECTED. DEFECTS IN THE WORK PROVIDED BY THE CONTRACTOR SHALL BE CORRECTED AND ADDITIONAL TESTS PERFORMED UNTIL IT HAS BEEN DEMONSTRATED THAT THE SYSTEMS COMPLY WITH ALL CONTRACT REQUIREMENTS. THE CONTRACTOR SHALL FURNISH ALL APPLIANCES, EQUIPMENT, ELECTRICITY, INSTRUMENTS, CONNECTING DEVICES, AND PERSONNEL FOR THE TESTS. THE OWNER WILL FURNISH WATER FOR THE TESTS.
FIRE SUPPRESSION TESTING
AND ACCEPTANCE:
1. REPORTS OF ANY TESTING DURING INSTALLATION SHALL BE FORWARDED TO THE OWNER'S REPRESENTATIVE.
2. OBTAIN AND ADHERE TO ALL REQUIRED PERMITS, LICENSES AND GOVERNMENT REQUIREMENTS.
3. REFER TO ALL CONSTRUCTION DOCUMENTS FOR COORDINATION OF THE FIRE ALARM TRADE WITH OTHER DISCIPLINES, AND TO DETERMINE SCOPE OF WORK.
4. COORDINATE ALL FIRE ALARM WORK WITH OTHER TRADES SUCH AS ELECTRICAL, STRUCTURAL, HVAC, PLUMBING, LIGHTING, CEILING CONSTRUCTION, AND SUPPORTS. ANY CONFLICTS SHALL BE REPORTED IMMEDIATELY TO THE
OWNER PRIOR TO BEGINNING OF CONSTRUCTION.
5. THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL BE A FULLY QUALIFIED, LICENSED FIRE ALARM CONTRACTOR, EXPERIENCED IN THE DESIGN AND INSTALLATION OF FIRE ALARM SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT, AND A REGULAR SUPPLIER OF THE EQUIPMENT FOR WHICH IT IS RESPONSIBLE. EACH CONTRACTOR SHALL SUBMIT A STATEMENT OF QUALIFICATION TO PERFORM THIS TYPE OF WORK, WHICH CITES AT LEAST TWO (2) INSTALLATIONS OF
SIMILAR TYPE PERFORMED WITHIN THE PRECEDING SEVEN (7) YEARS OF THE BID.
6. WARRANT ALL FIRE ALARM EQUIPMENT, WIRING, AND COMPONENTS ITEMS SUPPLIED TO BE FREE FROM DEFECTS AND PERFORM THE SPECIFIED FUNCTIONS WHEN USED FOR THEIR INTENDED PURPOSE. ANY ITEM FOUND TO BE DEFECTIVE WITHIN ONE (1) YEAR FROM FINAL SYSTEM ACCEPTANCE WILL BE REPAIRED, CORRECTED, OR REPLACED (PARTS AND
LABOR), AS APPROPRIATE, AT NO COST TO THE OWNER.
7. SHOP DRAWINGS SHALL COMPLY WITH ALL REQUIREMENTS OF NFPA 72. PROVIDE LAYOUT DRAWINGS, PRODUCT DATA AND CALCULATIONS AS ONE COMPLETE SUBMITTAL PACKAGE. FAILURE TO DO SO WILL RESULT IN SUBMITTAL BEING
RETURNED "CORRECT AND RESUBMIT."
8. OBTAIN APPROVAL OF THE FIRE ALARM SHOP DRAWINGS FROM THE CLIENT, INSURANCE CARRIER, THE FIRE MARSHAL, AND ALL LOCAL AHJs PRIOR TO ANY FABRICATION OR INSTALLATION.
9. NEW FIRE ALARM EQUIPMENT SHALL BE UL-LISTED OR FM-APPROVED.
10. FIRE ALARM LAYOUT IN CONTRACT DOCUMENTS IS BASED ON AVAILABLE INFORMATION. SUCH LAYOUT DOES NOT RELIEVE THE CONTRACTOR FROM PROVIDING AND INSTALLING THE PROPER EQUIPMENT IN THE PROPER LOCATIONS TO
CONFORM TO THE INTENT OF THESE SPECIFICATIONS.
11. PROTECT AND SEAL ALL OPENINGS AND CONDUIT PENETRATIONS THROUGH FIRE-RATED WALLS AND CEILINGS WITH ADEQUATE FIRESTOPPING MATERIALS TO MAINTAIN THE FIRE RATINGS OF THE ASSEMBLIES BEING PENETRATED.
12. OFFSET CONDUIT AS NECESSARY TO AVOID INTERFERENCE WITH OTHER WORK AND TO MAINTAIN A MINIMUM
HEADROOM OF 7'-0" IN OPEN CEILING AREAS.
13. ALL NEW FIRE ALARM COMPONENTS SHALL BE TESTED ACCORDING TO THE SYSTEMS ACCEPTANCE CRITERIA REQUIRED
BY NFPA 72.
14. CONTRACTOR SHALL PROVIDE NEW BATTERIES AS NECESSARY TO POWER ALL NEW FIRE ALARM EQUIPMENT.
15. PROVIDE FACP PROGRAMMING AS NECESSARY TO INCORPORATE NEW NOTIFICATION APPLIANCE BOOSTER POWER SUPPLY AND NOTIFICATION APPLIANCES. NOTIFICATION APPLIANCES SHALL BE CONFIGURED TO ACTIVATE UPON ANY FIRE ALARM
CONDITION WITHIN THE BUILDING.
NOTIFICATION APPLIANCE BOOSTER POWER SUPPLY PANEL TROUBLE SHALL REGISTER AS A TROUBLE SIGNAL ON THE
FACP.
FIRE ALARM SPECIFICATIONS:
1. ALL FIRE ALARM EQUIPMENT, CONDUIT, WIRING, AND SUPPORT METHODS TO BE INSTALLED IN STRICT ACCORDANCE
WITH ALL APPLICABLE LOCAL CODES.
FIRE ALARM TESTING AND
ACCEPTANCE:
1. REPORTS OF ANY TESTING DURING INSTALLATION SHALL BE FORWARDED TO THE OWNER'S REPRESENTATIVE.
2. ACCEPTANCE: REPRESENTATIVES OF THE AHJs AND THE OWNER'S REPRESENTATIVE SHALL BASE ACCEPTANCE OF THE
FIRE ALARM WORK UPON THE INSPECTION AND TESTS OF THE COMPLETED INSTALLATION.
3. THE INSTALLING COMPANY SHALL FURNISH A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE COUNTERSIGNED BY THE PROPERTY OWNER OR REPRESENTATIVE PRIOR TO REQUESTING FINAL APPROVAL FROM THE AHJ.
4. TESTS SHALL BE MADE BY THE CONTRACTOR IN THE PRESENCE OF THE AHJ OR THE REPRESENTATIVE OF THE OWNER.
5. ALL NEW FIRE ALARM EQUIPMENT SHALL BE TESTED TO ENSURE PROPER OPERATION AT THE FIRE ALARM PANEL AND
THAT THE APPROPRIATE SIGNAL IS TRANSMITTED TO THE FIRE ALARM MONITORING STATION.
6. PRELIMINARY TESTS: COMPLY WITH THE "TEST METHODS" TABLE IN "TESTING" SECTION OF "INSPECTION, TESTING AND MAINTENANCE" CHAPTER IN NFPA 72. THE CONTRACTOR SHALL SUBMIT A SIGNED AND DATED CERTIFICATE WITH REQUEST FOR A FORMAL INSPECTION AND TESTS SIMILAR TO THAT SPECIFIED IN NFPA 72 WHEN ALL CONNECTIONS
HAVE BEEN MADE AND TESTS HAVE BEEN COMPLETED.
7. FORMAL INSPECTION AND TESTS: TESTS SHALL BE PERFORMED ON THE FIRE ALARM SYSTEM AS REQUIRED BY THE LOCAL FIRE DEPARTMENT. THE OWNER, OWNER'S REPRESENTATIVE, INSURANCE COMPANY REPRESENTATIVES AND THE LOCAL FIRE DEPARTMENT WILL WITNESS FORMAL TESTS AND APPROVE ALL SYSTEMS BEFORE THEY ARE ACCEPTED.
THE REQUEST FOR FORMAL INSPECTION SHALL BE SUBMITTED AT LEAST FIFTEEN (15) DAYS PRIOR TO THE DATE THE INSPECTION IS TO TAKE PLACE. AN EXPERIENCED TECHNICIAN REGULARLY EMPLOYED BY THE FIRE ALARM INSTALLER SHALL BE PRESENT DURING THE INSPECTION. AT THE INSPECTION, ANY OR ALL OF THE REQUIRED TESTS SHALL BE REPEATED AS DIRECTED. DEFECTS IN THE WORK PROVIDED BY THE CONTRACTOR SHALL BE CORRECTED AND ADDITIONAL TESTS PERFORMED UNTIL IT HAS BEEN DEMONSTRATED THAT THE SYSTEMS COMPLY WITH ALL CONTRACT REQUIREMENTS. THE CONTRACTOR SHALL FURNISH ALL APPLIANCES, EQUIPMENT, ELECTRICITY, INSTRUMENTS, CONNECTING DEVICES, AND PERSONNEL FOR THE TESTS.
26. DRY PIPE RISER AND PIPING SHALL BE LIMITED TO A MAXIMUM 750 GALLON CAPACITY PER RISER/DRY PIPE VALVE SYSTEM, MULTIPLE RISERS WILL BE REQUIRED.
27. UL LISTED OR FM APPROVED PIPE JOINT RESTRAINTS MAY BE USED IN LIEU OF THRUST BLOCKS FOR PIPING DIRECTION
CHANGES AND TRANSITIONS.
3. ANY CONFLICTS SHALL BE REPORTED IMMEDIATELY TO THE OWNER PRIOR TO BEGINNING OF CONSTRUCTION.
KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AR
C
H D
4" x
6"
SHEET TITLE
NOTES
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D t s av ed b y:
F
U N
SE
t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
FP-100
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
CONSULTANT
I/R DATE DESCRIPTION
NITROGEN GENERATOR AIR
PRESSURE MAINTENANCE
DEVICE CONTROL VALVE
JUNCTION
BOX
AIR
COMPRESSOR
ISOLATION
SWITCH
NITROGEN
GENERATOR
AIR
COMPRESSOR
NITROGEN GENERATOR AIR
PRESSURE MAINTENANCE
DEVICE
HOUR METER
FIRE STOP SEALANT G.I. SLEEVE
FIRE-RATED
FLOOR
DRY PIPE
ASSEMBLY
NITROGEN GENERATOR
STORAGE CYLINDER
DRAIN
OUTLET,
DISCHARGE
TO EXTERIOR
FIRE FIGHTING
PIPE
NITROGEN GENERATOR
COMPRESSOR
10 PIPE PENETRATION - RATED FLOOR/CEILING
Scale: NTS
APPROVED SEALANT G.I. SLEEVE
FLOOR
6 DRY VALVE CABINET DETAIL
Scale: NTS
BOTTOM OF CANOPY
STRUCTURAL
BEAM
FIRE STOP SEALANT PIPE SLEEVE
UPRIGHT SPRINKLER HEAD
WITH DEFLECTOR AT OR
ABOVE BOTTOM OF BEAM 1" NIPPLE 11
BRANCH LINE
FIRE SUPPRESSION
PIPING
FIRE-RATED
WALL
NOTE: SPRINKLER INSTALLATION SHALL COMPLY WITH THE OBSTRUCTION
REQUIREMENTS OF NFPA 13.
CEILING
4 PIPE PENETRATION - RATED WALL
Scale: NTS
7 SPRINKLER INSTALLATION DETAIL
Scale: NTS
STROBE ONLY
DEVICES
CEILING
NOTE:
COORDINATE LOCATION OF DEVICES/APPLIANCES WITH
OTHER TRADES TO ALIGN VERTICALLY WHERE FEASIBLE
SYNCHRONIZE MORE THAN
TWO APPLIANCES IN ANY FIELD OF VIEW
MOUNT SMOKE DETECTOR ON
WALL APPROXIMATELY 5'-0"
ABOVE TOP OF BPS CABINET
FIRE FIRE FIRE
AUDIO/VISUAL
DEVICE
AUDIO ONLY
DEVICE
PIPE PENETRATION - NONRATED FLOOR/CEILING
Scale: NTS
FIRE FIGHTING
PIPE
PIPE SLEEVE BPS PANEL
APPROVED SEALANT NOTE:
COORDINATE LOCATION OF
DEVICES/APPLIANCES WITH
OTHER TRADES TO ALIGN
VERTICALLY WHERE FEASIBLE
REFER TO THE PROPER DEVICE
INSTALLATION INSTRUCTIONS
FOR BACKBOX MOUNTING
HEIGHT
FIRE SUPPRESSION
PIPING
INTERIOR/EXTERIOR
WALL
NO HIGHER THAN 5'-0" TO
CENTER OF NAC CABINET
OR FACP DISPLAY
FINISHED FLOOR
FINISHED FLOOR
5 PIPE PENETRATION - NONRATED WALL
Scale: NTS
8 BOOSTER POWER SUPPLY MOUNTING HEIGHT
Scale: NTS
12 AUDIO/VISUAL DEVICE INSTALLATION HEIGHT
Scale: NTS
" M
AX
M
AX
IM
U
M O
F 8'
-0
TO
T
O P
O F
LE
N
S
M
IN
IM
U
M O
F 6'
-8
TO
B
O
TT
O M
O F
LE
N
S
0' -6
" M
IN
IM
U
M
7' -6
" M
IN
IM
U
M
1 STUB UP DETAIL
Scale: NTS
2 THRUST BLOCK FOR BENDS AND TEES - ELEVATION
Scale: NTS
3 TYPICAL THRUST BLOCK FOR TEES - PLAN
Scale: NTS
FACP
OR FACP
NO HIGHER
THAN 6'-0'' TO
TOP OF PANEL
TYPICAL DRY PIPE
OUTLET LOCATION,
FIELD CONDITIONS
MAY VARY
TYPICAL WATER
INLET LOCATION,
FIELD CONDITIONS
MAY VARY
KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AR
C
H D
4" x
6"
SHEET TITLE
FIRE PROTECTION DETAILS
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D t s av ed b y:
F
U N
SE
t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
FP-101
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
CONSULTANT
I/R DATE DESCRIPTION
ISSUE/REVISION
0 2024.06.14 ISSUED FOR BID
AutoCAD SHX Text
4" MIN.
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
NO FITTINGS
AutoCAD SHX Text
18" MIN.
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text 45%%D
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text 9"
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text A
A
C D EA H K L
MEZZANINE ABOVE
MEZZANINE ABOVE
'-0
58'-0"
'-0
'-0
309'-3 3/4"
3' -8
251'-3 3/4"
3'-10"
10'x20'
OFFICE
OPEN
ABOVE
STORAGE
1'-0"58'-0"
4' -0
'-0
6' -4
'-0
'-0
2' -2
3'
-7
3' -4
MEZZANINE
ABOVE
OFFICES
OFFICE SPACE NOT
WITHIN SCOPE
DOOR TO BE REPLACED WITH 2-
HOUR RATED DOOR AND HARDWARE
DOOR TO BE REPLACED
WITH 2-HOUR RATED
DOOR AND HARDWARE
'-0
B F G J
2A
4A
SPRINKLER COVERAGE:
ORDINARY HAZARD GROUP 2
SPRINKLER COVERAGE:
ORDINARY HAZARD GROUP 2
SPRINKLER COVERAGE:
ORDINARY HAZARD GROUP 2
SPRINKLER COVERAGE:
ORDINARY HAZARD GROUP 2
SPRINKLER COVERAGE:
ORDINARY HAZARD
GROUP 2
87'-0"
'-0
'-0
130'-0"
'-0
'-0
57'-0"
'-1
'-0
80'-0"
55'-0"
'-0
'-0
FIRE RATED
STAIRWELL
8' -0
10'-0"
36'-0 19/32"
36'-0"
'-0
75'-0"
105'-0"
MOVEABLE TIRE RACKS
AREA CHANGES
SPRINKLER COVERAGE:
EXTRA HAZARD EH1
'-0
'-0
/4
'-0
'-0
/4
STAIRS UP
20'-0"
10'x60' OFFICE WITH MEZZANINE ABOVE
STAIRS UP
STAIRS UP
2 HOUR FIRE RATED WALLS
NOTE:
DIMENSIONS ARE NOT EXACT; CONTRACTOR RESPONSIBLE FOR
VERIFYING ALL DIMENSIONS PRIOR TO BIDDING.
NEW RISER LOCATIONS ADJUSTABLE TO
CLEAR INTERFERENCES IN FOUNDATION
AND INTERIOR
2 HOUR FIRE RATED WALL ABOVE MEZZANINE
WASTE OIL STORAGE
SPRINKLER COVERAGE:
EXTRA HAZARD EH2
RATED FLOOR
COVERAGE REQUIRED
ABOVE AND BELOW
MEZZANINES
COVERAGE REQUIRED
ABOVE AND BELOW
MEZZANINES
COVERAGE REQUIRED ABOVE
AND BELOW MEZZANINES KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AR
C
H D
4" x
6"
SHEET TITLE
SPRINKLER LAYOUT
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D t s av ed b y:
F
U N
SE
t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
FS-101
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
FEET
0 75 150
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
CONSULTANT
I/R DATE DESCRIPTION
DEMPSEY TRAIL
JO
SS
LY
N
S T
WITZEL AVE
INDICATOR VALVE (PIV) 40' FROM
BUILDING NEW TIE-IN TO CITY WATER
MAIN FOR SYSTEM SUPPLY PER NFPA 24
KEY PLAN
REGISTRATION
PROJECT NUMBER
60716955
AR
C
H D
4" x
6"
SHEET TITLE
UNDERGROUND LAYOUT
Fi le na m e:
C
:\O N
ED
R
IV
E\
AE
C
O M
\O
SH
KO
SH
F
IR
E
PR
O
TE
C
TI
O N
G
EN
ER
AL
\9
_C
AD
_G
IS
\9
_C
AD
\2
0-
SH
EE
TS
\C
IT
YO
FO
SH
KO
SH
FI
R
EP
R O
TE
C
TI
O
N D
R
AW
IN
G
S_
X3 6L
.D t s av ed b y:
F
U N
SE
t P lo tte d:
4-
-0
Pr oj ec t M an ag em en t I ni tia ls
:D es ig ne r:
C he ck ed
Ap pr ov ed
A
B
C
D
SHEET NUMBER
FS-102
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF AECOM'S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES,
EXCEPT AS AGREED BY AECOM AND ITS CLIENT, AS REQUIRED BY LAW OR
FOR USE BY GOVERNMENTAL REVIEWING AGENCIES. AECOM ACCEPTS NO
RESPONSIBILITY, AND DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY
THAT MODIFIES THIS DRAWING WITHOUT AECOM'S EXPRESS WRITTEN
CONSENT.
DO NOT SCALE THIS DOCUMENT. ALL MEASUREMENTS MUST BE OBTAINED
FROM STATED DIMENSIONS.
NOTE:
IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO INFORM THEMSELVES
OF THE EXACT LOCATION OF, AND ASSUME ALL LIABILITY FOR DAMAGE TO
ALL UTILITIES, SERVICES AND STRUCTURES, WHETHER ABOVE GROUND OR
BELOW GRADE, BEFORE COMMENCING THE WORK. SUCH INFORMATION IS
NOT NECESSARILY SHOWN ON THE DRAWING, AND WHERE SHOWN, THE
ACCURACY CANNOT BE GUARANTEED.
WITH THE SOLE EXCEPTION OF THE BENCHMARK(S) SPECIFICALLY
DESCRIBED FOR THIS PROJECT, NO ELEVATION INDICATED OR ASSUMED
HEREON IS TO BE USED AS A REFERENCE ELEVATION FOR ANY PURPOSE.
FEET
0 15 30
LEGEND
EXISTING PRESSURIZED WATER MAINS
PROPOSED PRESSURIZED WATER MAINS
WATER HYDRANTS
WATER VALVES
WATER FITTINGS
BUILDING
AECOM Technical Services, Inc.
444 Reid Street, Suite 300 De Pere, WI 54115 www.aecom.com
CLIENT
CITY OF OSHKOSH,
WISCONSIN
PROJECT
FIRE PROTECTION
UPGRADES -
TRANSIT
ADMINISTRATION
AND GARAGE
FACILITY
CONSULTANT
I/R DATE DESCRIPTION
ISSUE/REVISION
0 2024.06.14 ISSUED FOR BID
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text D
AutoCAD SHX Text Y
AutoCAD SHX Text H
WV
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-G-100CoverPage |
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-G-101Notes |
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-FA-101FloorPlan |
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-FACP-1Fire Alarm Control Panel |
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-FP-100Notes |
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-FP-101FireProtDetails |
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-FS-101SprinklerLayout |
| Sheets and Views |
| CityofOshkoshFireProtectionDrawings_24X36L-FS-102UndergroundLayout |
File details come from the government source that posted it. Updated .