6-Oquirrh ES Kitchen Remodel - Drawings.pdf
PDF 13 MB Posted
- Attached to
- Oquirrh Elementary Kitchen Remodel State and local contract opportunity
- Solicitation number
- 26KP12
- Issued by
- Salt Lake County, Utah
About this file
Kitchen Remodel - Oquirrh Elementary School
This is a set of architectural, mechanical, plumbing, electrical, and food service construction drawings for a kitchen remodel project at Oquirrh Elementary School in West Jordan, Utah, under Jordan School District (JSD). The project involves the remodel of approximately 1,270 square feet of kitchen and ancillary support spaces. The base bid scope includes salvaging or removing existing food service equipment and providing new equipment; cutting and patching concrete slabs for new utility lines; providing new floor sinks; removing and replacing finished flooring, ceiling systems, and wall systems; and providing new wall finishes, interior architectural millwork, and countertops. An add alternate (#01) is included for providing a new AC-1 split system with hardwired thermostat in Storage Room B19. The project documents specify that this work involves only equipment and finish replacement with no change in occupancy use or occupiable square footage. Bid documents are dated January 20, 2026, and the project is identified as Bid #26KP12 with a total estimated cost of $25,712.00.
The drawings include comprehensive architectural plans showing demolition, flooring, ceiling, and finish details; mechanical plans detailing HVAC modifications including exhaust fans (EF-1 and EF-2 with 3,000 CFM capacity each) and the new AC-1 unit; plumbing plans for water supply, waste, and vent systems including new floor sinks and floor drains; and electrical plans covering lighting, power distribution, fire alarm integration, and kitchen equipment connections. The design team includes NJRA Architects as the prime architect, with consulting engineers for structural, mechanical, electrical, plumbing, and food service coordination. The project requires coordination with existing building systems, implementation of interim life safety measures during construction, and compliance with 2021 ICC and 2023 NEC codes. Site-specific coordination is required with the existing make-up air unit, existing dishwasher equipment, and intercom/fire alarm systems that are being retained and modified as part of the remodel.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| 4-26KP12 Oquirrh Elem Kitchen Remodel.docx | DOCX document | |
| 2-Attachment A - JSD Standard Terms Conditions | — | |
| 3-JSD Vendor Response Form.pdf | ||
| 1-Attachment B - Boycott Statement - 09 | — | |
| 5-Oquirrh ES Kitchen Remodel - Project Manual.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5272 South College Drive, Suite 104
Murray, Utah 84123
Phone: 801.364.9259
Contacts: Selvam Rajavelu
Email: selraj@njraarchitects.com
Project Manager: Tyler Stanger
Email: tylsta@njraarchitects.com
ARCHITECT
NJRA Architects, Inc.
Street Address
City, State Zip
Phone:
Contacts:
Project Manager: Name
Email:
STRUCTURAL ENGINEER
N/A
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
CIVIL ENGINEER
LANDSCAPE ARCHITECT
1134 East Browning Avenue
Salt Lake City, Utah 84105
Phone: (801) 403-9073
Contacts:
Project Manager: Ric Jeddrzeiwski
Email: RicJ@JedrziewskiDesigns.com
FOOD SERVICE
CONSULTANT
Jedrziewski Designs
14 East 2700 South
Salt Lake City, Utah 84115
City, State Zip
Phone: (801) 486-4646
Contacts:
Project Manager: John Eagan
Email: john@op-eng.com
Olsen & Peterson consulting engineers, inc.
181 E 5600 S Suite 200
Murray, UT 84107
Phone:
Contacts:
Project Manager: Drayton Bailey
Email: dbailey@resolutgroup.com
RESOLUT
Street Address
City, State Zip
Phone:
Contacts:
Project Manager: Name
Email:
N/A
Street Address
City, State Zip
Phone:
Contacts:
Project Manager: Name
Email:
N/A
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5223 S. Ascension Way, Suite 350 Murray, Utah 84123
801.364.9259 www.njraarchitects.com
/2
/2
:2 :0
P
M
Oquirrh Elementary School Jordan School District
7165 South 3285 West West Jordan, UT 84084
G001
Cover Sheet
J o rd a n S c h o o l D is tr ic t
O q u ir rh
E le m e n ta ry S c h o o l
S o u th
W e st
W e st J o rd a n
U
T
25712.00
Bid Documents January 20, 2026
Bid Documents
Kitchen Remodel
K it c h e n R e m o d e l
DESIGN TEAM
Jordan School District Bid #26KP12
THE CONTRACTOR SHALL SUBMIT THE FOLLOWING TO THE BUILDING OFFICIAL FOR
REVIEW WITH AN ACCOMPANYING LETTER FROM THE ARCHITECT STATING THAT THE
CONTENTS OF THE SUBMITTAL ARE IN CONFORMANCE WITH THE DESIGN. WORK
RELATED TO THE DEFERRED SUBMITTAL IS NOT TO COMMENCE UNTIL THE BUILDING
OFFICIAL HAS APPROVED THE SUBMITTAL.
1. DETAILS AND ENGINEERING CALCULATIONS FOR ALL NONSTRUCTURAL
COMPONENTS THAT ARE PERMANENTLY ATTACHED TO STRUCTURES AND THEIR
SUPPORTS AND ATTACHMENTS. THESE SHALL BE DESIGNED AND CONSTRUCTED TO RESIST
THE EFFECTS OF EARTHQUAKE MOTIONS IN ACCORDANCE WITH ASCE 7-05. REFERENCE
IBC SECTION 1613.1. THIS INCLUDES:
- ELECTRICAL SYSTEMS
- MECHANICAL SYSTEMS
- PLUMBING SYSTEMS
- DECORATIVE ARCHITECTURAL COMPONENTS.
2. DETAILS AND ENGINEERING CALCULATIONS FOR THE FIRE SPRINKLER AND FIRE
DETECTION SYSTEMS, WHICH ARE TO BE DESIGN-BUILD BY THE CONTRACTOR TO
COMPLY WITH NFPA 13 AND SHALL INCLUDE:
- FIRE ALARM PLANS (INCLUDING CO DETECTOR LOCATIONS)
- AUTOMATIC FIRE SPRINKLER PLANS
- HOOD FIRE SUPPRESSION
- CLASS 'K' FIRE EXTINGUISHER LOCATION(S)
3. STRUCTURAL TRUSS AND JOIST DESIGNS (AS LISTED IN THE STRUCTURAL DRAWINGS).
SEE STRUCTURAL DRAWINGS FOR SPECIAL INSPECTIONS REQUIRED.
Approvers Name, Title Date
Approvers Name, Title Date
Approvers Name, Title Date
Approvers Name, Title Date
IMPLEMENTATION OF INTERIM LIFE SAFETY MEASURES (ILSM) IS REQUIRED IN OR
ADJACENT TO ALL CONSTRUCTION AREAS AND THROUGHOUT BUILDINGS WITH
EXISTING LSC DEFICIENCIES. ILSM APPLY TO ALL PERSONNEL, INCLUDING
CONSTRUCTION WORKERS, MUST BE IMPLEMENTED UPON PROJECT DEVELOPMENT,
AND CONTINUOUSLY ENFORCED THROUGH PROJECT COMPLETION. ILSM ARE
INTENDED TO PROVIDE A LEVEL OF LIFE SAFETY COMPARABLE TO THAT DESCRIBED IN
CHAPTERS 1 THROUGH 7, 31 AND THE APPLICABLE OCCUPANCY CHAPTERS OF THE LSC.
EACH ILSM ACTION MUST BE DOCUMENTED THROUGH WRITTEN POLICIES AND
PROCEDURES. EXCEPT AS STATED BELOW, FREQUENCIES FOR INSPECTION, TESTING,
TRAINING, AND ILSM CONSIST OF THE FOLLOWING ACTIONS:
Base Bid:
This project includes the remodel of approximately 1,270 SF of Kitchen and ancillary support spaces for Oquirrh Elementary School. The project base bid includes, but is not limited to, the follow scope of work as indicated in the project documents: Salvage or remove existing food service equipment and relocate salvaged or provide new food service equipment; cut and patch concrete slab on grade as required for new electrical, mechanical, or plumbing utility lines; provide new floor sinks; remove existing finished flooring and provide new finished flooring;
remove existing ceiling systems and provide new ceiling systems; selectively remove existing wall systems and provide new wall systems; provide new wall finishes, remove existing interior architectural millwork and provide new interior architectural millwork; and, any other work indicated in project documents, but not noted in this section.
Add Alternate #01 - New AC-1 System in Storage Room #B19
This base bid scope: The existing HVAC serving Storage Room #B19 remains as is.
The add alternate #01 scope includes: Provid a new AC-1 S split system and hardwired thermostat in Storage Room #B19 as indicated in the project documents.
THIS PROJECT INVOLVES ONLY EQUIPMENT & FINISH REPLACEMENT. EQUIPMENT
REPLACEMENT INCLUDES REPLACING AND RELOCATING KITCHEN FIXTURES AS WELL
AS ELECTRICAL & MECHANICAL WORK REQUIRED TO PREPARE THE SPACE FOR
EQUIPMENT REPLACEMENT. FINISH REPLACEMENT INCLUDES SUCH WORK AS FLOOR
AND CEILING FINISH REPLACEMENT, NEW WALL FINISHES, NEW MILLWORK AND
COUNTERTOPS.
THERE WILL BE NO CHANGE IN OCCUPANCY USE OR OCCUPIABLE SQUARE
FOOTAGE. THIS BUILDING WAS REVIEWED AND PERMITTED IN ITS ENTIRETY AT ITS
ORIGINAL CONSTRUCTION. GIVEN THERE WILL BE NO CHANGE IN OCCUPANCY USE
OR OCCUPIABLE SQUARE FOOTAGE, EXISTING OCCUPANCY LOADS, MEANS OF
EGRESS ELEMENTS, AND PLUMBING COUNTS ARE ASSUMED TO BE SUFFICIENT FOR THIS
WORK.
ICC CODE CYCLE: 2021
NEC CODE CYCLE: 2023
PROJECT LOCATION: OQUIRRH ELEMENTARY SCHOOL, LEVEL 1
OCCUPANCY: E
AREA OF REMODEL: 1,270 SF
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5223 S. Ascension Way, Suite 350 Murray, Utah 84123
801.364.9259 www.njraarchitects.com
/2
/2
:2 :0
P
M
G002
General Information
J o rd a n S c h o o l D is tr ic t
O q u ir rh
E le m e n ta ry S c h o o l
S o u th
W e st
W e st J o rd a n
U
T
25712.00
Bid Documents January 20, 2026
K it c h e n R e m o d e l
DRAWING INDEX
APPROVALS
DEFINITIONS
1. GENERAL: BASIC CONTRACT DEFINITIONS ARE INCLUDED IN THE CONDITIONS OF THE
CONTRACT.
2. "APPROVED": WHEN USED TO CONVEY ARCHITECT'S ACTION ON CONTRACTOR'S
SUBMITTALS, APPLICATIONS, AND REQUESTS, "APPROVED" IS LIMITED TO ARCHITECT'S
DUTIES AND RESPONSIBILITIES AS STATED IN THE CONDITIONS OF THE CONTRACT.
3. "DIRECTED": A COMMAND OR INSTRUCTION BY ARCHITECT. OTHER TERMS INCLUDING
"REQUESTED," "AUTHORIZED," "SELECTED," "REQUIRED," AND "PERMITTED" HAVE THE
SAME MEANING AS "DIRECTED."
4. "INDICATED": REQUIREMENTS EXPRESSED BY GRAPHIC REPRESENTATIONS OR IN
WRITTEN FORM ON DRAWINGS, IN SPECIFICATIONS, AND IN OTHER CONTRACT
DOCUMENTS. OTHER TERMS INCLUDING "SHOWN," "NOTED," "SCHEDULED," AND
"SPECIFIED" HAVE THE SAME MEANING AS "INDICATED."
5. "REGULATIONS": LAWS, ORDINANCES, STATUTES, AND LAWFUL ORDERS ISSUED BY
AUTHORITIES HAVING JURISDICTION, AND RULES, CONVENTIONS, AND AGREEMENTS
WITHIN THE CONSTRUCTION INDUSTRY THAT CONTROL PERFORMANCE OF THE WORK.
6. "FURNISH": SUPPLY AND DELIVER TO PROJECT SITE, READY FOR UNLOADING,
UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS.
7. "INSTALL": UNLOAD, TEMPORARILY STORE, UNPACK, ASSEMBLE, ERECT, PLACE,
ANCHOR, APPLY, WORK TO DIMENSION, FINISH, CURE, PROTECT, CLEAN, AND SIMILAR
OPERATIONS AT PROJECT SITE.
8. "PROVIDE": FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.
9. "PROJECT SITE": SPACE AVAILABLE FOR PERFORMING CONSTRUCTION ACTIVITIES. THE
EXTENT OF PROJECT SITE IS SHOWN ON DRAWINGS AND MAY OR MAY NOT BE
IDENTICAL WITH THE DESCRIPTION OF THE LAND ON WHICH PROJECT IS TO BE BUILT.
ABBREVIATIONS
VICINITY MAP
NORTH
SITE
SPECIAL INSPECTIONSDEFERRED SUBMITTALS
GENERAL
G001 Cover Sheet
G002 General Information
G003 General Information
G004 American National Standard Institute Requirements
G005 General Legend & Notes
ARCHITECTURAL
A111 Demolition Floor & Reflected Ceiling Plans - Level 1
A112 Floor & Dimension Plans - Level 1
A113 Reflected Ceiling & Roof Plans - Level 1
A114 Finish Floor Plan - Level 1
A251 Interior Elevations
A501A Wall Types
A502A Wall Details
A502B Wall Details
A503A Ceiling Details
A504A Door & Window Details
A505A Cabinet Legend & Details
A505B Cabinet Details
A505C Cabinet Details
A506A Details
A601A Door Schedule
A602A Window Types
A603A Finish Schedule & Details
MECHANICAL
M111 Mechanical Floor Plan Level 1
M501 Mechanical Schedules & Details
PLUMBING
PD111 Plumbing Demolition Floor Plan Level 1
P111 Plumbing Floor Plan Level 1
P501 Plumbing Schedules & Details
ELECTRICAL
E001 Electrical Title Sheet
E002 Electrical Schedules & Notes
ED111 First Floor Electrical Demolition Plan
E111 First Floor Lighting Plan
E112 First Floor Electrical Plan
E501 Panel Schedules
E601 Electrical Diagrams
E602 Electrical Diagrams
FOOD SERVICE
FS101 Level 1 Food Service Equipment Plan
FS102 Level 1 Food Service Equipment Building Requirement Plan
FS103 Level 1 Food Service Equipment Plumbing Requirement Plan
FS104 Level 1 Food Service Equipment Electrical Requirement Plan
& AND
@ AT
Ø DIAMETER
(E), EXIST. EXISTING
(N) NEW
d PENNY
# POUND OR NUMBER
A
AC ACOUSTIC
ADD ADDENDUM
A/C AIR CONDITIONING
ALT. ALTERNATE
AL ALUMINUM
A.B. ANCHOR BOLT
ARCH ARCHITECT(URAL)
ASP. ASPHALT
B
BSMT. BASEMENT
B.M. BENCHMARK
BLKG. BLOCKING
BD. BOARD
B.O. BOTTOM OF
BLDG. BUILDING
C
CAB'T CABINET
C.I.P. CAST IN PLACE
C.B. CATCH BASIN
CLG. CEILING
CL CENTER LINE
C.T. CERAMIC TILE
CH CHANNEL
C.O. CLEAN OUT
CLR. CLEAR
CL. CLOSET
COL. COLUMN
CONC. CONCRETE
CMU CONCRETE MASONRY UNIT
COND. CONDITION
CONN. CONNECTION
CONST. CONSTRUCTION
CONT CONTINUOUS
CJ CONTROL JOINT
D
D.P. DAMP PROOFING
D.B. DECK BEARING
DIAG. DIAGONAL
DIA. DIAMETER
DIM. DIMENSION
DISP. DISPENSER
INTERIM LIFE SAFETY MEASURES
1 ENSURING EXITS PROVIDE FREE AND UNOBSTRUCTED EGRESS. PERSONNEL SHALL
RECEIVE TRAINING IF ALTERNATIVE EXITS MUST BE DESIGNATED. BUILDINGS OR AREAS
UNDER CONSTRUCTION MUST MAINTAIN ESCAPE FACILITIES FOR CONSTRUCTION
WORKERS AT ALL TIMES. MEANS OF EGRESS IN CONSTRUCTION AREAS MUST BE
INSPECTED DAILY.
2 ENSURING FREE AND UNOBSTRUCTED ACCESS TO EMERGENCY DEPARTMENTS/
SERVICES AND FOR EMERGENCY FORCES.
3 ENSURE FIRE ALARM, DETECTION, AND SUPPRESSION SYSTEMS ARE NOT IMPAIRED. A
TEMPORARY, BUT EQUIVALENT, SYSTEM SHALL BE PROVIDED WHEN ANY FIRE SYSTEM IS
IMPAIRED. TEMPORARY SYSTEMS MUST BE INSPECTED AND TESTED MONTHLY.
4 ENSURING TEMPORARY CONSTRUCTION PARTITIONS ARE SMOKE TIGHT AND BUILT OF
NONCOM OR LIMITED COMBUSTIBLE MATERIALS THAT WILL NOT CONTRIBUTE TO THE
DEVELOPMENT OR SPREAD OF FIRE.
5 PROVIDING ADDITIONAL FIRE-FIGHTING EQUIPMENT AND USE TRAINING OF
PERSONNEL.
6 PROHIBITING SMOKING IN ACCORDANCE WITH MA.1.3.15 AND IN OR ADJACENT TO
ALL CONSTRUCTION AREAS.
7 DEVELOPING AND ENFORCING STORAGE, HOUSEKEEPING, AND DEBRIS REMOVAL
PRACTICES THAT REDUCE THE FLAMMABLE AND COMBUSTIBLE FIRE LOAD OF THE
BUILDING TO THE LOWEST LEVEL NECESSARY FOR DAILY OPERATIONS.
8 CONDUCTING A MINIMUM OF TWO FIRE DRILLS PER SHIFT PER QUARTER.
9 INCREASING HAZARD SURVEILLANCE OF BUILDINGS, GROUNDS, AND EQUIPMENT
WITH SPECIAL ATTENTION TO EXCAVATIONS, CONSTRUCTION AREAS CONSTRUCTION
STORAGE, AND FIELD OFFICES.
10 TRAINING PERSONNEL WHEN STRUCTURAL OR COMPARTMENT FEATURES OF FIRE
SAFETY ARE COMPROMISED.
11 CONDUCTING ORGANIZATION WIDE SAFETY EDUCATION PROGRAMS TO ENSURE
AWARENESS OF ANY LSC DEFICIENCIES, CONSTRUCTION HAZARDS, AND THESE ILSM.
PROJECT DESCRIPTION
DWL. DOWEL
DN. DOWN
D.S. DOWN SPOUT
D.W.V. DRAINAGE WASTE VENT
DWG. DRAWING
E
EA. EACH
E.W.C. ELEC. WATER COOLER
EL./ELEC. ELECTRIC
ELEV. ELEVATION
EQ. EQUAL
EQUIP. EQUIPMENT
EXH. EXHAUST
EXIST. EXISTING
E.J. EXPANSION JOINT
EXT. EXTERIOR
F
FT. FEET
FV/F.V. FIELD VERIFY
FIN. FINISH(ED)
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
FIXT. FIXTURE
FL. FLASHING
G
GALV. GALVANIZED
GA. GAUGE
G.C. GENERAL CONTRACTOR
G.S.N. GENERAL STRUCTURAL NOTES
GL. GLASS
GD. GRADE
GRL. GRILLE
GRD. GROUND
GYP. GYPSUM
H
HDW. HARDWARE
HDWD. HARDWOOD
HTR. HEATER
HT. HEIGHT
H.P. HIGH POINT
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
H.B. HOSE BIB
H.W. HOT WATER
HR. HOUR
I
IN. INCH
I.D. INSIDE DIAMETER
INSUL. INSULATION
INT. INTERIOR
INV. INVERT
J
JAN. JANITOR
JT. JOINT
JST. JOIST
L
LAM. LAMINATED
LDG. LANDING
LAV. LAVATORY
LT. LIGHT
L.W.C. LIGHT WEIGHT CONCRETE
LVR. LOUVER
M
M.B. MACHINE BOLT
MFR. MANUFACTURER
M.O. MASONRY OPENING
MAT'L MATERIAL
MAX. MAXIMUM
MECH. MECHANICAL
MTL. METAL
MIN. MINIMUM
MLDG. MOLDING
MULL. MULLION
N
N.G. NATURAL GRADE
NOM. NOMINAL
N/A NOT APPLICABLE
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
O
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.R.D. OVERFLOW ROOF DRAIN
O.F.S. OVERFLOW SCUPPER
O.F.C.I. OWNER FURNISHED, CONTRACTOR
INSTALLED
O.F.O.I. OWNER FURNISHED, OWNER INSTALLED
P
PT. PAINT
PTD. PAINTED
PR. PAIR
PNL. PANEL
d PENNY
P.L. PLASTIC LAMINATE
PL. PLATE
PLBG. PLUMBING
P.S.I. POUND PER SQUARE INCH
P.S.F. POUNDS PER SQUARE FOOT
R
RAD. RADIUS
REC. RECOMMENDATION
REG. REGISTER
REQ'D REQUIRED
R.A. RETURN AIR
REV. REVISION
R.D. ROOF DRAIN
RFG. ROOFING
RM. ROOM
RGH. ROUGH
RND. ROUND
S
SCR. SCREW
SECT. SECTION
SEL. SELECT
SHT. SHEET
SIM. SIMILAR
SLDG. SLIDING
SM. SMOOTH
SPEC. SPECIFICATION
SPL. SPLASH
SQ. SQUARE
S.S. STAINLESS STEEL
STD. STANDARD
STRUC. STRUCTURE
S.A. SUPPLY AIR
SUSP. SUSPENDED
SW.BD. SWITCHBOARD
T
TELCO TELEPHONE COMPANY
T.G. TEMPERED GLASS
T&G TONGUE & GROOVE
T&B TOP & BOTTOM
T.O. TOP OF
T.O.C. TOP OF CURB
T.O.D. TOP OF DECK
T.O.P. TOP OF PARAPET
TYP. TYPICAL
U
U.N.O. UNLESS NOTED OTHERWISE
V
V. VENT
V.T.R. VENT THROUGH ROOF
VERT. VERTICAL
V.G. VERTICAL GRAIN
VEST. VESTIBULE
V.C.T. VINYL COMPOSITION TILE
V.C.P. VITREOUS CLAY PIPE
W
W.C. WATER CLOSET
W.H. WATER HEATER
W.R. WATER RESISTANT
W.P. WATERPROOF
W.W.F. WELDED WIRE FABRIC
W.F. WIDE FLANGE
WDW. WINDOW
W/ WITH
W/O WITHOUT
WD. WOOD
CODE COMPLIANCE - EXISTING BUILDING
DRINKING FOUNTAIN
17" - 19"
8"
TO
S
P O
U T
6"
ACCESSIBLE WATER CLOSET @ RESTROOMS
FOR PRESCHOOL
GRAB
BAR
GRAB
BAR
ACCESSIBLE WATER CLOSET @ RESTROOMS
FOR KINDERGARTEN
LINE OF
WALL
GRAB
BAR
GRAB
BAR
LINE OF FLOOR
LINE OF
WALL
LINE OF
WALL
LINE OF FLOOR
NOTE:
VERIFY WITH ARCHITECT FOR FIXTURES THAT SHALL BE USED PREDOMINANTLY BY CHILDREN IN THIS BUILDING. IF FIXTURE MOUNTING
HEIGHT IS NOT INDICATED ON THE INTERIOR ELEVATIONS, VERIFY WITH ARCHITECT.
HAND WASHING SINK
18"
TO
R
E F
LE
C
TI
V E S
U R
F A
C E
6"
Concrete
Earth
Gypsum
Board
Insulation
Rigid
Masonry
Brick
Masonry
Concrete
Block
Finish Wood
StoneSteel
Gravel
Batt
Insulation
Blocking
HATCH PATTERN BELOW INDICATES REPRESENTATION OF BUILDING MATERIALS IN
BUILDING SECTIONS, WALL SECTIONS AND DETAILS.
PAPER
TOWEL
DISPENSER
SOAP
DISPENSER
SANITARY
NAPKIN
DISPOSAL
ACCESSIBLE WATER CLOSET
LINE OF
WALLGRAB
BAR
ACCESSIBLE LAVATORY
18"
M
IN
6" MIN8" MIN
MIN
17"
M
IN
M
IN
LINE OF
WALL NOTE: EXPOSED PIPE
SHALL BE INSULATED (NO
SHARP OR ABRASIVE
SURFACES BELOW
LAVATORY)
ACCESSIBLE
URINAL
LINE OF
WALL
M A
X
15" CLEAR IF SIDEWALL IS LESS THAN 24" DEEP
18" CLEAR IF SIDEWALL IS MORE THAN 24" DEEP
F
LU
S H
H A
N D
LE
M
A X
T O
FIRE
EXTINGUISHER
CABINET
CENTERLINE OF
OPERABLE PARTS
SANITARY NAPKIN
DISPENSER
TOILET SEAT
COVER
DISPENSER
TOILET
PARTITION
URINAL
PARTITION
MIN CLR
30"
U .N
.O
7" 7"
HATCHED AREA
INDICATES AREA
WHERE
PROTRUDING
DISPENSERS BELOW
GRAB CAN BE
LOCATED
LINE OF
WALL
LINE OF
WALL
BABY
CHANGING
STATION
2"
DRINKING FOUNTAINS SIDE VIEW
17" - 19"
8"
TO
S
P O
U T
6"
STANDARD ADA
17" - 19"
8"
TO
S
P O
U T
6"
ACCESSIBLE BENCH SIDE VIEW
(WALL ATTACHED)
20" - 24"
HAND
DRYER
M
IN
M
IN
/2
24" MIN
42" MAX
NURSE CALL
AS OCCURS
LINE OF WALL
LINE OF FLOOR
3" 3"
MED GAS
OUTLETS
LINE OF
WAINSCOT
AS OCCURS
SLIDER
8"
MIRROR
WITH FRAME
MOP RACKFULL LENGTH
MIRROR
MIN.
18"
DRINKING FOUNTAINS
SPOUT
OUTLET
S U
R F A
C E
M A
X
TO
R E F
LE
C
TI
V E
M
IN
M
A X
ACCESSIBLE BENCH SIDE VIEW
(FREE STANDING)
20" - 24"
2 1/2" MAX
LINE OF
WALL
CONTROL
AREA
M
IN
TRANSFER-TYPE SHOWER ELEVATIONS
4" MAX
EQ EQ
3"
15" 15"
"4
M
A X
ACCESSIBLE ROLL-IN TYPE SHOWER ELEVATIONS
(WITH SEAT)
4" MAX
EQ EQ
3"
END WALL BACK WALL END WALLEND WALL BACK WALL END WALL
60"
M
A X
A B
O V
E G
R A
B B
A R
CONTROL
AREA
27"
16"
ACCESSIBLE ROLL-IN TYPE SHOWER ELEVATIONS
(WITHOUT SEAT)
4" MAX
EQ EQ
3"
END WALL BACK WALL END WALL
60"
M
A X
A B
O V
E G
R A
B B
A R
CONTROL
AREA
NURSE CALL
AS OCCURS
NURSE CALL
AS OCCURS
NURSE CALL
AS OCCURS
12"
12"
12"
FOLDING SHOWER SEAT
TO
R
E F
LE
C
TI
V E S
U R
F A
C E
M
A X
A
D A
3' - 5" MAX
39" MIN
3' - 6" MIN
1' - 0" MAX
MIN
2' - 0".
MIN
1' - 0".
3' - 0" MIN
LINE OF FLOOR
GRAB
BAR
LINE OF
WALL
LINE OF
WALL
1'-6".
LINE OF
WALL
LINE OF
WALL
LINE OF
WALL
LINE OF
WALL
LINE OF
WALL
A2022
A252
CLOUD INDICATES
DRAWING
REVISION AREA
ROOM NAME
ROOM NUMBER. LETTER "A" IN THE
ROOM NUMBER DENOTES "AREA A"
IN THE PROJECT. NUMBER "3"
DENOTES "FLOOR LEVEL 3", NUMBER
"24" DENOTES ROOM NUMBERING
SEQUENCE IN THE PROJECT AREA.
SHEET WHERE DRAWN
BUILDING SECTION
EXTERIOR ELEVATION
NUMBER
REVISION NUMBER
INTERIOR ELEVATION
NUMBER
SHEET WHERE DRAWN
SHEET WHERE DRAWN
DETAIL NUMBER
SHEET WHERE
DRAWN
0B
CL
TAGS ARE INDICATED ON
FINISH FLOOR PLAN. SEE
FINISH SCHEDULE, SHEET
A603A, FOR FLOOR
COVERING AND FINISHES
REQUIRED.
CENTER LINE
0A
DATUM POINT TAG
00.00
KEYED NOTES THAT ARE NOT PROJECT
SPECIFIC AS INDICATED ON GENERIC,
TYPICAL DETAILS.
MATCHLINE
3 A101
FLOOR PLAN MATCHLINE
SECTION TAGS ARE
INDICATED ON
OVERALL DIMENSION
FLOOR PLANS
SECTION TAGS ARE
INDICATED ON
DIMENSION FLOOR
PLANS
TAGS ARE INDICATED ON
OVERALL DIMENSION FLOOR
PLANS AND KEY PLAN
TAGS ARE INDICATED ON
FINISH FLOOR PLANS
WALL TAGS ARE INDICATED ON
DIMENSION FLOOR PLANS. WALL
TYPES ARE INDICATED IN SHEET A501A.
NORTH
A506
A506
A
A1
WATER DRAINAGE DIRECTION
SHOWN ON SITE AND ROOF
PLANS FROM HIGH TO LOW
POINT.
CABINET TYPES ARE
INDICATED ON
INTERIOR ELEVATIONS &
CABINET LEGEND, SHEET
A505A.
DIVISION NOTE
DIVISION #
SHEET NUMBERING SYSTEM
SHEET NUMBER SEQUENCE
A100A
SHEET TYPE
DISCIPLINE
PROJECT AREA
100' - 0"
VERTICAL ELEVATION
SPOT ELEVATION
100' - 0"
LEVEL 1
T.O.W.
HEIGHT ABOVE FINISH FLOOR
DENOTES ROOM AREA
OF 155 SQUARE FEET
A124C
F2
A101
KEYED NOTES THAT ARE PROJECT
SPECIFIC AS INDICATED ON
PLANS, SECTIONS AND
ELEVATIONS
TAGS ARE INDICATED ON
FINISH FLOOR PLAN. SEE
FINISH SCHEDULE, SHEET
A603A, FOR WALL BASE
TYPE.
TAGS ARE INDICATED ON
REFLECTED CEILING PLAN.
SEE FINISH SCHEDULE,
SHEET A603A, FOR CEILING
FINISHES REQUIRED.
B1
C3
WINDOWS TAGS ARE
INDICATED ON
DIMENSION FLOOR
PLANS
DOOR TAGS ARE
INDICATED ON
DIMENSION FLOOR PLANS
A101
A101
SHEET WHERE DRAWN
WALL SECTION
SHEET WHERE DRAWN
DETAIL NUMBER
TAGS ARE INDICATED ON
FINISH FLOOR PLAN. SEE
SIGN TYPE DETAIL
S2
GRID LINE
GRID TAG
NORTH ARROW
DETAIL TAGS
CEILING HEIGHT TAG
ROOM TAG
GRID REFERENCE LETTER - A,B,C,
ETC. (USED FOR HORIZONTAL
GRID SEQUENCE, TYPICALLY
FROM LEFT TO RIGHT)
SHEET WHERE DRAWN
DETAIL LOCATION NUMBER
THE FIRST LETTER "A" AND
THE FOLLOWING THREE
DIGITS "124" DENOTES
ROOM NUMBER
SUFFIX "C" DENOTES
SEQUENCE OF DOOR
ACCESSING THE ROOM.
GRID REFERENCE
NUMBER - 1,2,3, ETC.
(USED FOR VERTICAL GRID
SEQUENCE, TYPICALLY
FROM TOP TO BOTTOM)
ROOM COUNT DESIGNATION
A324
155 SF
OFFICE-4
O.L. 999
DENOTES OCCUPANT
LOAD IN CODE
COMPLIANCE PLANS.
TAGS ARE INDICATED ON
FINISH FLOOR PLAN &
INTERIOR ELEVATIONS. SEE
FINISH SCHEDULE, SHEET
A603A, FOR FINISHES
REQUIRED.
MS1 MM1 WP1 PL1 WC1
W14
/1 A506A
TAGS ARE INDICATED ON
FINISH FLOOR PLAN. SEE
FINISH SCHEDULE, SHEET
A603A, FOR WALL FINISHES
REQUIRED.
W3
B.O.C. BOTTOM OF CEILING
B.O.H. BOTTOM OF HEADER
T.O.W. TOP OF WALL
T.O.C. TOP OF CURB
D.B.E. DECK BEARING ELEVATION
F.F.E. FINISH FLOOR ELEVATION
B.O.V. BOTTOM OF VENEER
T.O.S. TOP OF SIDEWALK
T.O.C. TOP OF CURB
9' - 0" B.O.C.
DENOTES BUILDING
REFERENCE ELEVATION
DENOTES FLOOR LEVEL
BUILDING SECTIONS
WALL SECTIONS
DETAIL TAGS
EXTERIOR ELEVATION TAGS
INTERIOR ELEVATION TAGS
WALL TAG
KEYED NOTES - GENERIC
KEYED NOTES - PROJECT SPECIFIC
REVISION TAG
FLOW ARROW
DOOR TAG
WINDOW TAG
FLOOR FINISH TAG
WALL BASE TAG
WALL FINISH TAG
CEILING FINISH TAG
OTHER FINISH TAG
CABINET TAG
SIGN TAG
DENOTES BUILDING
REFERENCE ELEVATION
AC1
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5223 S. Ascension Way, Suite 350 Murray, Utah 84123
801.364.9259 www.njraarchitects.com
/2
/2
:2 :0
P
M
G003
General Information
J o rd a n S c h o o l D is tr ic t
O q u ir rh
E le m e n ta ry S c h o o l
S o u th
W e st
W e st J o rd a n
U
T
25712.00
Bid Documents January 20, 2026
K it c h e n R e m o d e l
LEGEND - MATERIALS GENERAL INFORMATION SYMBOLS & TAGS
SCALE: 3/8" = 1'-0"
Typical Mounting Heights of Fixtures Used by Children
SCALE: 3/8" = 1'-0"
Typical Mounting Heights
36" MIN CLEAR
4" MAX 26" MIN
M
IN
C
LR
18"
M
IN
AMBULATORY TOILET
COMPARTMENT
36" MIN
60" MIN CLEAR
M
IN
C
LR
16" - 18"
ACCESSIBLE TOILET
COMPARTMENT
ACCESSIBLE
LAVATORY PLAN
U.N.O.
18" TYP.
FINISHED
FACE OF
WALL
MIN
32"
4 1/2" MAX
M
IN
11" MIN
ACCESSIBLE
URINAL PLAN
C
LR
30" CLR
36" MIN CLR
M
IN
C
LR
MIN
12" 3
48"
22"-23"
M A
X
/2
MAX
2 1/2"
15"-16"
18"
ACCESSIBLE SHOWER PLAN
60"
ACCESSIBLE ROLL-IN TYPE
SHOWER PLAN
(WITH SEAT)
6" MAX
17 1/2" MAX
60" MIN CLR
M
IN
C
LR
30" 3"
" 1
M
IN
M A
X
6" MIN.
DRINKING
FOUNTAINS
PLAN VIEW
ACCESSIBLE BENCH PLAN VIEW
30" CLEAR 42" MIN.
C
LE
A
R
BENCH
M A
X
60"
ACCESSIBLE ROLL-IN TYPE
SHOWER PLAN
(WITHOUT SEAT ADAAG)
6" MAX 6" MAX
60" MIN CLR
M A
X
M
IN
C
LR
M A
X 6
M A
X
LINE OF
WAINSCOT
AS OCCURS
CL
2 1/2" MAX
M A
X
/2
15"-16"
GRAB BAR SHALL NOT
EXTEND ABOVE SEAT.
FOLDING SHOWER
SEAT. SEE DETAIL
FOLDING
SHOWER SEAT
SEE DETAIL
MANEUVERING CLEARANCE AT SWINGING DOORS
(B) FRONT APPROACH, PUSH SIDE (C) HINGE APPROACH, PULL SIDE (D) HINGE APPROACH, PULL SIDE
FIG. 404.2.4.1
(E) HINGE APPROACH, PUSH SIDE (G) LATCH APPROACH, PUSH SIDE(F) LATCH APPROACH, PULL SIDE
FIG. 404.2.4.2
MANEUVERING CLEARANCE AT SLIDING AND FOLDING DOORS
(A) FRONT APPROACH (B) POCKET OR HINGE APPROACH (C) STOP OR LATCH APPROACH
FIG. 404.2.6
TWO DOORS IN A SERIES
(A) (B)
(A) CIRCULAR (B) T-SHAPED
(A) FORWARD (B) PARALLEL
FIG. 304.3
SIZE OF WHEELCHAIR TURNING SPACE
FIG. 405.5
POSITION OF CLEAR FLOOR OR GROUND SPACE
(A) FORWARD APPROACH (B) PARALLEL APPROACH
FIG. 305.7
MANEUVERING CLEARANCE IN AN ALCOVE
FIG. 604.5.2
REAR WALL GRAB BAR FOR
WATER CLOSET
FIG. 604.7
DISPENSER LOCATION
SIDE
FIG. 604.8.1.1
WHEELCHAIR ACCESSIBLE TOILET COMPARTMENTS
(B) FLOOR-MOUNTED WATER CLOSET(A) WALL-HUNG WATER CLOSET
FIG. 604.8.3
TOILET COMPARTMENT DOORS
FIG. 606.3
HEIGHT OF LAVATORIES AND SINKS
FIG. 602.5
DRINKING FOUNTAIN SPOUT LOCATION
(A) PARALLEL APPROACH (B) FORWARD APPROACH
FIG. 503.3
PASSENGER LOADING ZONE ACCESS AISLE
BACK WALL
SEAT
WALL
CONTROL
WALL
FIG. 608.3.2
GRAB BARS IN ROLL-IN-TYPE SHOWERS
(C) GRAB BARS IN ROLL-IN-TYPE
SHOWERS
FIG. 608.5
CONTROLS IN TRANSFER-TYPE
SHOWERS
CONTROL
WALL
(A) (B)
BACK
WALL
FIG. 608.6
LOCATION OF SHOWER SPRAY UNIT
FIG. 609.3
SPACING OF GRAB
BARS
FIG. 610.3.1
RECTANGULAR SHOWER
COMPARTMENT SEAT
FIG. 610.3.2
L-SHAPED SHOWER
COMPARTMENT SEAT
FIG. 702.3.3.1
LOCATION OF WALL-MOUNTED APPLIANCES
(A) WALL ALARM (B) WALL ALARM WITH
SMOKE DETECTOR
FLOOR OR GROUND FLOOR OR GROUND
CEILING CEILING
FIG. 702.3.3.2
LOCATION OF CEILING-MOUNTED APPLIANCES
FIG. 702.3.5.1
APPLIANCE SPACING IN CORRIDORS
FIG. 702.3.6.2
APPLIANCE LOCATION IN
SLEEPING ROOMS
(A) ONE BED
(B) TWO BEDS
FIG. 703.2.4.4
CHARACTER HEIGHT
LIBRARY
FIG. 703.2.8
MOUNTING LOCATION AT DOORS
(A) PARALLEL APPROACH
(B) FORWARD APPROACH
FIG. 704.2.1
CLEAR FLOOR OR GROUND
SPACE FOR TELEPHONES
FIG. 705.3.1.1
TRUNCATED DOME SIZE
(A) VERTICAL RISER (B) CURVED NOSING
(C) BEVELED NOSING (D) ANGLED RISER
RADIUS 1/2" MAX. TYP.
30 max.
beveled
FIG. 504.5
STAIR NOSINGS
FIG. 504.2
TREADS AND RISERS FOR
ACCESSIBLE STAIRWAYS
(A) STAIRS (B) RAMPS
FIG. 505.7
HANDRAIL CROSS SECTION
FIG. 505.4
HANDRAIL HEIGHT
FIG. 505.5
HANDRAIL CLEARANCE
(A) CIRCULAR
4"-6 1/4" PERIMETER
FIG. 505.10.1
TOP AND BOTTOM HANDRAIL EXTENSIONS AT RAMPS
FIG. 505.10.2
TOP HANDRAIL EXTENSIONS AT STAIRS
X = TREAD DEPTH
FIG. 505.10.2
BOTTOM HANDRAIL EXTENSIONS AT STAIRS
FIG. 306.3
KNEE CLEARANCE
FIG. 306.2
TOE CLEARANCE
FIG. 403.5.1
CLEAR WIDTH AT TURN
LANDING
AT LEAST AS WIDE AS RAMP RUN
LANDING
(A)
FIG. 405.7
RAMP LANDINGS
LANDING
RAMP RUN RAMP RUN
RAMP
RUN
(B)
(A) HINGED DOOR
(B) SLIDING DOOR
(C) FOLDING DOOR
FIG. 404.2.3
CLEAR WIDTH OF DOORWAYS
FIG. 307.4
REDUCED VERTICAL CLEARANCE
FIG. 407.2.2
ELEVATOR CALL BUTTONS
FIG. 407.2.3.2.1
HEIGHT OF ELEVATOR VISIBLE SIGNALS
FIG. 406.12
ISLANDS
(A) CUT THROUGH AT ISLAND
(B) CURB RAMP AT ISLAND
(A) EXTENDED SURFACE
FIG. 405.9
RAMP EDGE PROTECTION
(B) CURB OR BARRIER
FIG. 406.3
COUNTER SLOPE OF SURFACES ADJACENT TO CURB RAMPS
ADJOINING SURFACE
MAXIMUM SLOPE
CURB RAMP
MAXIMUM SLOPE
(A) (B)
FIG. 406.4
SIDES OF CURB RAMPS
RETURNED CURB
(C)
PLANTING
AREA
PLANTING
AREA
(A) (B)
FIG. 406.11
DIAGONAL CURB RAMPS
(A) FRONT APPROACH, PULL SIDE
FIG. 604.2/604.3.1
WATER CLOSET LOCATION/
SIZE CLEARANCE
FIG. 604.4/604.5.1
HEIGHT OF WATER CLOSET/
SIDE WALL GRAB BAR FOR WATER
CLOSET
FIG. 502.2/502.3
VEHICLE PARKING SPACE/
PARKING SPACE ACCESS AISLE
(B) NON-CIRCULAR (C) NON-CIRCULAR
BUILDING BLOCKS
FIG. 303.2
VERTICAL CHANGES IN LEVEL
FIG. 303.3
BEVELED CHANGES IN LEVEL
FIG. 302.3
OPENINGS IN FLOOR
OR GROUND SURFACES
PROTRUDING OBJECTS
FIG. 307.3
POST-MOUNTED PROTRUDING OBJECTS
FIG. 307.2
LIMITS OF PROTRUDING OBJECTS
FIG. 308.2.1
UNOBSTRUCTED FORWARD REACH
FIG. 308.2.2
OBSTRUCTED HIGH FORWARD REACH
FIG. 308.3.1
UNOBSTRUCTED SIDE REACH
FIG. 308.3.2
OBSTRUCTED HIGH SIDE REACH
FIG. 607.4.1
GRAB BARS FOR BATHTUBS
WITH PERMANENT SEATS
(WITH FIG. 607.2 CLEARANCES)
FIG. 607.4.2
GRAB BARS FOR BATHTUBS
WITHOUT PERMANENT SEATS
(WITH FIG. 607.2 CLEARANCES)
FIG. 608.2.2
STANDARD ROLL-IN-TYPE
SHOWER COMPARTMENT
FIG. 403.5
CLEAR WIDTH OF AN ACCESSIBLE ROUTE
ACCESS AISLE SERVING
VAN PARKING SPACES
ACCESS AISLE SERVING
CAR PARKING SPACES
LONG DIMENSION
PERPENDICULAR
TO DIRECTION OF TRAVEL
(A) STANDARD ROLL-IN-TYPE
SHOWER
(B) ROLL-IN-TYPE
SHOWER WITH SEAT
FIG. 607.5
LOCATION OF BATHTUB
CONTROLS
FIG. 608.2.1/608.3.1
TRANSFER-TYPE SHOWER
COMPARTMENT WITH GRAB BARS
FLARED SIDES 1:10 MAX. SLOPE FLARED SIDES 1:12 MAX. SLOPE
*36" MIN. WHEN
WALL SPACE
PERMITS
curved
END WALL
DOORS AND DOORWAYS
CLEAR FLOOR SPACE
PLUMBING ELEMENTS AND FACILITIES
TRANSFER
GENERAL SITE AND BUILDING ELEMENTS
X
ACCESSIBLE ROUTES
COMMUNICATION ELEMENTS AND FEATURES
AREA TO BE MARKED
PLANTING
AREA
PLANTING
AREA
AREA TO BE
MARKED
A R
E A
T O
B E M
A R
K E D
CL
CL
CL
CL
CL
CL
M
IN
M A
X
CONTROL
WALL
H E A
D E
N D
W A
LL
F O
O T
E N
D W
A
LL
BACK
WALL
F O
O T
E N
D W
A
LL
H E A
D E
N D
W A
LL
BACK WALL
M
IN
M
IN
MAX.
24"
MIN.
48"
MAX.
24"
48" MIN.
M
IN
M
IN
X
32" MIN.
32" MIN.
32" MIN.
60" MIN. 60" MIN.
60" MIN.
M
IN
12" MIN. 12" MIN.
X
X
36" MIN.
M
IN
48" M
IN
. 48 " M
IN
X
M
IN
42"30"
18"
36" MIN.
48" MIN.
M
IN
60" MIN.
M
IN
M
IN
60" MIN.
36" MIN.
M
A X
15" MAX.
27" MAX. 15"-16"
2 1/2" MAX.
M A
X
/2
M A
X
2 1/2" MAX.
15"-16" 1
22"-23"
/2
M A
X
M
IN
1 1/2".
LENGTH OF TUB 3
M
IN
15"-16"
M
IN
12" MAX. 24" MAX.
M
IN
LENGTH OF TUB 12" MIN.
M
IN
15" MAX.
M
IN
12" MAX.
M
A X
6" MAX. 6" MAX.
M A
X
M A
X
6" MAX.
M A
X
6" MAX. 6" MAX.
M A
X
M
IN
4" MAX.
60" MIN.60" MIN.
M
IN
7"-9"
/2
M
IN
M
A X
M
IN
24" MIN.
36" MIN.
12" MAX. 42" MIN.
54" MIN.
16"-18"
60" MIN.
M
IN
5" MAX. 15" MAX.
3 1/2" MAX.
15' MAX. 50'-100' 50'-100' 15' MAX.
' M
A X
' M A
X
C E
IL
IN
G
H E
IG
H T
16' MAX.
16' MAX.
/8
18" MIN.
M
A X
M
A X
.3
2.35".
/2
M
A X
/4
/2
M A
X
/4
4" MAX.
12" MAX. 12" MAX.
M
A X
36"
36"
M
IN
22"
12" MIN.
22"
24"
12" MIN.
12" MIN.
2 1/4" MAX.1 1/4"-2"
1 13/32" MAX.
96" MIN.
FU
LL
L E N
G
TH
O F
P A
R K
IN
G
S P
A C
E
96" MIN. 60" MIN.
M
IN
20' MIN. 3
" 1 1/2" MIN.
M
A X
24" MAX.
M
A X
10" MAX.
M
A X
20" - 25"
M
A X
M
A X
20" MAX.
M
IN
M
A X
X
M
A X
17" MIN.
M
IN
M
IN
11" MIN.
M
IN
8" MIN.
60" MIN.
M
IN
X
36" MIN.
M
IN
X
48" MIN.
M
IN
30" MIN.
M
IN
12" MIN. 36" MIN. 12" MIN.
M
IN
M
IN
60" MIN.60" MIN.
18" MIN. 12" MIN.
M
IN
36" MIN.
M
IN
42" MIN.
M
IN
M
IN
54" MIN.
M
IN
24" MIN.
24" MIN.
M
IN
48" MIN. 48" MIN.
M
IN
54" MIN.
M
IN
M
IN
24" MIN.
1" MAX.
X
X
M
IN
M A
X
11" MIN.
X
X
X > 12"
X > 12"
REACH RANGES
M
IN
M
IN
M
IN
39"-41"
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5223 S. Ascension Way, Suite 350 Murray, Utah 84123
801.364.9259 www.njraarchitects.com
/2
/2
:2 :1
P
M
G004
American National Standard Institute
Requirements
J o rd a n S c h o o l D is tr ic t
O q u ir rh
E le m e n ta ry S c h o o l
S o u th
W e st
W e st J o rd a n
U
T
25712.00
Bid Documents January 20, 2026
K it c h e n R e m o d e l
SCALE: 3/16" = 1'-0"
American National Standard Institute (ICC A117.1 - 2009) Requirements
0 00
/- ---ROOF DRAIN. SEE DETAIL
TAPERED INSULATION CRICKET WITH 1/8" PER
FOOT SLOPE, MINIMUM, ALONG VALLEY
AND 1/4" PER FOOT SLOPE, MINIMUM,
ACROSS CRICKET.
SLOPE DOWN DIRECTION FOR WATER
FLOW TOWARD ROOF DRAINS.
ROOF HATCH SEE DETAIL
AS ROOF STRUCTURE IS LEVEL (FLAT WITH NO
SLOPE) IN THIS AREA, USE TAPERED INSULATION
(1/4" PER FOOT SLOPE) FOR DRAINAGE.
PROVIDE CRICKETS AS REQUIRED ON THE TOP
OF TAPERED INSULATION.
BUILDING COMPONENTS (ROOF DRAINS, HATCH, ETC.) ARE DRAWN AT 1/4" = 1' - 0".
ON PLANS DRAWN AT 1/8" = 1' - 0" SCALE, COMPONENTS SHALL APPEAR HALF THIS
SIZE.
2' X 2' LAY-IN ACOUSTICAL PANEL CEILING.
SEE DETAILS
CEILING HEIGHT ABOVE FINISHED FLOOR
NEW RETURN AIR GRILLE - SEE MECHANICAL
DRAWINGS
9'-0"
BUILDING COMPONENTS (CEILING, LIGHT FIXTURES, ETC) INDICATED BELOW IN
THIS LEGEND ARE DRAWN AT 1/4" = 1'-0" SCALE. COMPONENTS SHALL APPEAR
HALF THE SIZE (SMALLER) ON PLANS DRAWN AT 1/8" = 1'-0" SCALE.
2' X 4' LAY-IN ACOUSTICAL PANEL CEILING.
SEE DETAILS
SUSPENDED GYPSUM BOARD CEILING OR
SOFFIT SEE DETAILS
NEW SUPPLY AIR GRILLE - SEE MECHANICAL
DRAWINGS
NEW EXHAUST FAN - SEE MECHANICAL
DRAWINGS
NEW 2' X 4' LIGHT FIXTURE - SEE ELECTRICAL
DRAWINGS
,/1 A503A /4 A503A /7 A503A
/10 A503A
,/1 A503A /4 A503A /7 A503A
/10 A503A
/2 A503A /3 A503A
/5 A503A /8 A503A
NEW DOOR IN NEW WALL. SEE DOOR
SCHEDULE.
NEW WINDOW. SEE WINDOW TYPES.
TAGS ARE PLACED ON THE FRONT
SIDE OF WINDOW.
NEW CMU WALL. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
NEW CAST-IN-PLACE CONCRETE
WALL. SEE WALL TAGS ON DIMENSION
PLANS FOR MORE INFORMATION.
NEW BRICK MASONRY WALL. SEE
STRUCTURAL DRAWINGS FOR MORE
INFORMATION.
NEW METAL STUD WALL. SEE WALL
TAGS ON DIMENSION PLANS AND
WALL TYPES SHEET A501A FOR MORE
INFORMATION.
NEW PLUMBING FIXTURES
BUILDING COMPONENTS (DOORS, WALLS, ETC) INDICATED BELOW IN THIS LEGEND
ARE DRAWN AT 1/4" = 1'-0" SCALE. COMPONENTS SHALL APPEAR HALF THE SIZE
(SMALLER) ON PLANS DRAWN AT 1/8" = 1'-0" SCALE.
A1
A
A101A
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING WINDOW TO REMAIN
EXISTING WINDOW TO BE
DEMOLISHED
EXISTING WALL TO REMAIN
EXISTING WALL TO BE DEMOLISHED.
EXISTING PLUMBING
FIXTURES TO REMAIN
EXISTING PLUMBING
FIXTURES TO BE DEMOLISHED
BUILDING COMPONENTS (DOORS, WALLS, ETC) INDICATED BELOW IN THIS LEGEND
ARE DRAWN AT 1/4" = 1'-0" SCALE. COMPONENTS SHALL APPEAR HALF THE SIZE
(SMALLER) ON PLANS DRAWN AT 1/8" = 1'-0" SCALE.
BOLLARD
FENCE LINE (CHAIN LINK)
FENCE LINE (ORNAMENTAL)
PROPERTY LINE
LIGHT POLE
FIRE HYDRANT
POWER POLE
CATCH BASIN
CONCRETE SIDEWALK OR
PAVING WITH CONTROL
JOINTS
SITE COMPONENTS (FENCES, HYDRANTS, SIDEWALKS, ETC) INDICATED BELOW IN THIS
LEGEND ARE DRAWN AT 1/16" = 1'-0" SCALE. COMPONENTS SHALL APPEAR HALF THE
SIZE (SMALLER) ON PLANS DRAWN AT 1/32" = 1'-0" SCALE.
/4 A505B /5 A505B
/11 A503A
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5223 S. Ascension Way, Suite 350 Murray, Utah 84123
801.364.9259 www.njraarchitects.com
/2
/2
:2 :1
P
M
G005
General Legend &
Notes
J o rd a n S c h o o l D is tr ic t
O q u ir rh
E le m e n ta ry S c h o o l
S o u th
W e st
W e st J o rd a n
U
T
25712.00
Bid Documents January 20, 2026
K it c h e n R e m o d e l
GENERAL NOTES - FLOOR & DIM. PLANS
A. REFER TO THE CODE COMPLIANCE PLANS FOR INDICATION OF FIRE RATED WALLS.
B. AT LOCATIONS WITHOUT CEILINGS (ROOM IS OPEN TO STRUCTURE ABOVE), EXTEND
ALL WALLS, SOFFITS, AND HEADERS (INCLUDING ALL STUD FRAMING, GYPSUM
BOARD, INSULATION & CMU, WHERE APPLICABLE) TO THE METAL ROOF DECK
ABOVE.
C. WHEN FLOOR HEIGHT VARIES IN A ROOM, THE CEILING HEIGHT SHOWN IS THE HEIGHT
ABOVE THE FLOOR AT THE ENTRY, UNO.
D. SEE INTERIOR ELEVATIONS FOR TOILET AND BATHROOM ACCESSORIES (GRAB BARS,
MIRRORS, DISPENSERS, ETC.).
E. AT ALL VERTICAL EDGES OF INTERIOR CMU WALLS THAT ARE VISIBLE, USE BULLNOSE
CMU BLOCKS FROM FINISHED FLOOR ELEVATION TO A HEIGHT OF 7'-4".
F. FOR CLARITY SAKE, DIMENSIONS ARE NOT SHOWN AT THE FOLLOWING LOCATIONS:
a. WHERE THE FACE OF WALL COINCIDES WITH THE MAIN GRID LINE OR 4'-0" X 4'-0"
SUBGRID.
b. WHERE THE CENTER OF WALL COINCIDES WITH THE MAIN GRID LINE OR 4'-0" X 4'-0"
SUBGRID.
G. VERIFY WITH ARCHITECT FOR DIMENSIONS NOT SHOWN.
H. SEE STRUCTURAL DRAWINGS FOR CMU WALLS, MASONRY COLUMNS, AND MASONRY
BEAMS. SEE BUILDING EXTERIOR ELEVATIONS FOR VENEER TYPES. SEE FINISH SCHEDULE
FOR CMU THAT IS HONED, SCORED, SEALED, PAINTED, ETC.
I. SEE CIVIL, FOOD SERVICE, PLUMBING, AND MECHANICAL DRAWINGS FOR FLOOR
SINKS, FLOOR DRAINS, AND OPENINGS IN FLOOR SLABS AND ROOFS FOR
DUCTWORK, ETC.
J. SEE DOOR AND WINDOW SCHEDULE FOR THE REQUIRED DOOR AND WINDOW
OPENING SIZES
K. SEE FINISH SCHEDULE AND STRUCTURAL DRAWINGS AND PROVIDE RECESS IN
CONCRETE FLOOR SLAB AS REQUIRED TO ACCOMMODATE FLOOR FINISHES.
CONCRETE FLOOR SLAB THAT IS ON GRADE, SHALL BE RECESSED AS REQUIRED, FOR
A THICK SET MORTAR FOR CERAMIC TILE FINISH. SLOPE SHALL BE AT 1/8" PER FOOT
TOWARDS THE FLOOR DRAIN. CONCRETE FLOOR SLAB, THAT IS NOT ON GRADE,
NEED NOT BE RECESSED. IN SUCH LOCATION, USE THIN SET MORTAR FOR CERAMIC
TILE FINISH WITH A GENTLE SLOPE TOWARDS DRAIN.
L. ALL PENETRATIONS (PIPES, CONDUITS, JOISTS, ETC.) THROUGH FIRE RATED BARRIER
WALLS SHALL BE SEALED COMPLETELY WITH FIRE RATED SEALANTS. FILL GAP BETWEEN
FLUTES OF THE METAL DECK AND METAL TRACK TOP RUNNER WITH FIRE RATED
SEALANTS. SEAL TIGHTLY AROUND PIPES, CONDUITS, DUCTS, ETC. THAT PENETRATES
THE FIRE BARRIER WALL WITH FIRE RATED SEALANTS. APPLY SEALANT AS PER
MANUFACTURERS RECOMMENDATIONS WITH ANY ADDITIONAL MATERIAL AS
REQUIRED INSTALLED AROUND PENETRATIONS TO MAINTAIN THE INTEGRITY OF THE
FIRE WALL. SEE MECHANICAL DRAWINGS FOR FIRE AND SMOKE DAMPERS.
M. WALL CABINETS HAVE A DEPTH OF 1'-3" UNLESS NOTED OTHERWISE.
N. ALL MASONRY MORTAR JOINTS LOCATED INSIDE THE BUILDING SHALL BE TOOLED
JOINTS, UNLESS NOTED OTHERWISE. MASONRY JOINTS ON THE BUILDING EXTERIOR
SIDE SHALL BE RAKED JOINTS AS INDICATED IN BUILDING EXTERIOR ELEVATIONS.
O. SEE OVERALL FLOOR PLAN SHEETS FOR ANGLES, PIVOT POINT AND DIMENSIONS
BETWEEN GRID LINES.
P. SEE CODE COMPLIANCE FLOOR PLANS FOR LOCATION OF FIRE BARRIER, NON
RATED WALLS, ETC.
Q. SEE ENLARGED FLOOR PLANS FOR ADDITIONAL DIMENSIONS.
R. IN SOME PROJECTS, DUE TO THE LARGE BUILDING FOOTPRINT SIZE, FLOOR PLANS ARE
SPLIT AS AREAS A, B, C, ETC. AND EACH AREA IS INDICATED ON SEPARATE SHEETS.
MATCH LINES INDICATE THE BOUNDARIES OF EACH AREA. WHEN CONTRACTORS ARE
PREPARING BID FOR THE PROJECT, COST SHALL INCLUDE ONLY THE BUILDING
ELEMENTS AND ASSOCIATED CONSTRUCTION WORK CALLED OUT WITH KEYED NOTES
IN THE AREA INDICATED ON THE SHEET. KEYED NOTES INDICATED OUTSIDE THE MATCH
LINE IN ADJACENT FLOOR AREAS SHALL NOT BE COUNTED FOR THAT AREA. THIS
AVOIDS DUPLICATION OF BUILDING ELEMENTS AND CONSTRUCTION WORK.
GENERAL NOTES - REFLECTED CEILING PLAN
A. SEE MECHANICAL DRAWINGS FOR DIFFUSER LOCATIONS IN CEILING. CONTRACTOR
SHALL COORDINATE WITH LIGHT FIXTURES (AS INDICATED IN ELECTRICAL DRAWINGS)
AND MOVE DIFFUSERS AROUND THE LIGHT FIXTURE IF THERE IS ANY CONFLICT
BETWEEN THE TWO.
B. SOME OF THE ITEMS ON CEILING INDICATED IN MECHANICAL AND ELECTRICAL
DRAWINGS, MAY OR MAY NOT BE INDICATED ON ARCHITECTURAL CEILING PLANS.
SEE MECHANICAL AND ELECTRICAL DRAWINGS AND COORDINATE WITH ARCHITECT
FOR ANY REQUIRED CLARIFICATIONS.
C. CONTRACTOR SHALL NOT HANG CEILING TILES AND LIGHTS FROM DUCTS. FOR
AREAS ABOVE THE CEILING WHERE OVERSIZE DUCTS OCCUR SEE DETAIL .
D. PAINT ALL VISIBLE EXPOSED ITEMS LIKE METAL DECK, STEEL ANGLES, STEEL BEAMS,
STEEL TRUSSES, MISCELLANEOUS EXPOSED STEEL STRUCTURAL COMPONENTS,
HOLLOW METAL DOORS, DOOR FRAMES & WINDOW FRAMES. PAINT EXPOSED
SURFACES (WITH COLORS AND ACCENT COLORS AS SELECTED BY ARCHITECT)
EXCEPT WHERE NATURAL FINISH OR MATERIAL IS SPECIFICALLY NOTED AS A SURFACE
NOT TO BE PAINTED. DO NOT PAINT CONCEALED SURFACES, FINISHED METAL
SURFACES, OPERATING PARTS AND PRE FINISHED ITEMS.
GENERAL NOTES - ROOF PLAN
A. PROVIDE CRICKET ON THE HIGH SIDE OF ROOF AT ALL CURB LOCATIONS FOR
MECHANICAL EQUIPMENT, SKYLIGHT, ROOF HATCH, ETC. WHETHER INDICATED ON
THE ROOF PLAN OR NOT.
B. PROVIDE WEATHERHEAD (GOOSNECK 2" CONDUIT) WHERE CONDUCTORS
PENETRATE ROOF FOR DISCONNECT SWITCHES, POWER OUTLETS, ETC. SECURE
GOOSENECK TO STRUCTURE BELOW.
C. PROVIDE WALKWAY PADS BETWEEN MECHANICAL EQUIPMENT, TO AND FROM ROOF
HATCHES AND OTHER ROOF ACCESS POINTS, AND AROUND MECHANICAL
EQUIPMENT REQUIRING PERIODIC MAINTENANCE.
A. CONTRACTOR SHALL VERIFY ALL EXISTING SITE AND BUILDING CONDITIONS INCLUDING
UNDERGROUND UTILITIES AND SERVICE LINES, IRRIGATION LINES AND SUB SURFACE
STRUCTURES AND ALL OTHER EXISTING CONSTRUCTION BOTH ABOVE AND BELOW
GRADE.
B. PRIOR TO REMOVAL OF EXISTING BUILDING MATERIALS (INCLUDING WALLS, DOORS,
WINDOWS, CEILING, ETC.) INDICATED IN THE DEMOLITION PLANS, CONTRACTOR SHALL
THOROUGHLY COORDINATE ARCHITECTURAL FLOOR PLANS, CEILING PLANS, FINISH
SCHEDULES AND ALL CONSULTANT DRAWINGS TO DETERMINE EXACT EXTENT OF
REMOVAL.
C. COORDINATE WITH OWNER'S REPRESENTATIVE REGARDING ITEMS SHOWN TO BE
REMOVED THAT WILL BECOME PROPERTY OF THE OWNER. CAREFULLY REMOVE SUCH
ITEMS SO AS NOT TO DAMAGE THEM.
D. IN EXISTING WALLS THAT ARE NOTED TO REMAIN, ANY NAILS, SCREWS, OR OPENINGS
THAT REMAIN AS A RESULT OF EXISTING EQUIPMENT REMOVAL OR WALL REMOVAL
SHALL BE PATCHED WITH SMOOTH, EVEN, INVISIBLE TRANSITION. IN PLACES WHERE THE
EXISTING WALL IS CUT FOR INSTALLATION OF POWER OUTLETS, SWITCH, THERMOSTAT,
ETC. PATCH OPENING IN WALL WITH GYPSUM BOARD. PROVIDE SMOOTH, EVEN,
INVISIBLE TRANSITION BETWEEN NEW AND EXISTING WALL FINISH.
E. THE OWNERS STAFF WILL CONTINUE TO OCCUPY AREAS DIRECTLY ADJACENT TO THE
CONSTRUCTION AREA. THE CONTRACTOR AND SUB-CONTRACTORS SHALL TAKE ALL
NECESSARY MEASURES TO MINIMIZE DISRUPTION ACTIVITIES CONDUCTED BY THE
OWNERS STAFF. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF
NOISY ACTIVITIES, SHUT-DOWNS, AND ANY OTHER ACTIVITIES WHICH MAY DISRUPT
NORMAL OPERATIONS PRIOR TO PERFORMING THE WORK.
F. ONCE FLOORING DEMOLITION HAS OCCURRED, CLEAN AND PREPARE FLOOR TO
RECEIVE NEW FLOOR COVERINGS. THIS SHALL BE COORDINATED WITH THE FINISH
SCHEDULE AND MANUFACTURER OF NEW PRODUCTS FOR FLOOR PREPARATION
REQUIREMENTS.
G
ITEMS SHOWN ON THESE FLOOR PLANS FOR REMOVAL ARE BUILT-IN ITEMS. EQUIPMENT,
FURNITURE, & OTHER ITEMS EXISTING IN THE SPACE THAT ARE NOT BUILT-IN SHALL BE
REMOVED OR CLEARED TEMPORARILY BY THE OWNER.
GENERAL NOTES - DEMOLITION FLOOR PLAN
LEGEND - ROOF PLANLEGEND - FLOOR & DIMENSION PLANS LEGEND - REFLECTED CEILING PLANLEGEND - SITE PLAN LEGEND - DEMOLITION FLOOR PLAN
A. STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS (IF PRESENT) ARE
SUPPLEMENTAL TO THE ARCHITECTURAL DRAWINGS. IT SHALL BE THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR TO CHECK WITH THE ARCHITECTURAL DRAWINGS
BEFORE THE INSTALLATION OF MECHANICAL OR ELECTRICAL CONSTRUCTION. ANY
DISCREPANCIES BETWEEN THE ARCHITECTURAL AND CONSULTING ENGINEERS'
DRAWINGS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION FOR CLARIFICATION.
ANY CONSTRUCTION INSTALLED IN CONFLICT WITH THE ARCHITECTURAL DRAWINGS
SHALL BE CORRECTED BY THE GENERAL CONTRACTOR AT HIS/HER OWN EXPENSE
AND AT NO EXPENSE TO THE OWNER OR ARCHITECT.
B. ALL WORK SHALL COMPLY WITH THE CURRENT ADA ACCESSIBILITY GUIDELINES
(AMERICANS WITH DISABILITIES ACT).
C. REFER TO THE CODE COMPLIANCE PLAN FOR APPLICABLE CODES GOVERNING THIS
WORK. CODE REQUIREMENTS AND REGULATIONS SHALL BE CONSIDERED AS
MINIMUM. WHERE THE CONTRACT DOCUMENTS EXCEED (WITHOUT VIOLATING)
CODE AND REGULATION REQUIREMENTS, CONTRACT DOCUMENTS SHALL TAKE
PRECEDENCE. IF CONFLICT EXIST, THE MORE STRINGENT SHALL APPLY. COMPLY WITH
REQUIREMENTS OF THE ADOPTED EDITIONS OF THE INTERNATIONAL CODE COUNCIL
CODES, THE CODES AND STANDARDS REFERENCED WITHIN THE ICC CODES AND THE
AMERICANS WITH DISABILITIES ACT.
D. THE CONTRACTOR SHALL PROVIDE ADEQUATE BARRICADES AND PROTECTIVE
DEVICES SEPARATING CONSTRUCTION AREAS. TEMPORARY PASSAGES SHALL BE
PROVIDED AS REQUIRED. PRIOR TO DELIVERY OF MATERIALS TO CONSTRUCTION
ZONE AND REMOVAL OF WASTE FROM SITE, THE CONTRACTOR SHALL CHECK WITH
THE OWNER FOR AN ACCEPTABLE ROUTE AND TIME.
E. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER LOCATION AND SIZE OF
OPENINGS FOR ALL TRADES AND SHALL COORDINATE ALL CONSTRUCTION AS
INDICATED BY THE CONTRACT DOCUMENTS, INCLUDING SHOP DRAWINGS
REVIEWED BY THE ARCHITECT.
F. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND NOTIFY THE
ARCHITECT OF ANY DISCREPANCIES PRIOR TO COMMENCEMENT OF WORK.
G. FOR ALL REMODEL WORK AS OCCURS, THE CONTRACTOR SHALL COORDINATE WITH
THE OWNER ALL MEASURES TO ACCOMPLISH THE WORK WITH THE MINIMUM OF
INTERRUPTION TO NORMAL BUILDING PROCEDURES. SYSTEM SHUTDOWNS OF HVAC,
PLUMBING, ELECTRICAL, AND NOISY CONSTRUCTION INCLUDING ROTO HAMMER,
SAW CUTTING, CONCRETE ANCHORS, ETC. SHALL BE COORDINATED WITH THE
OWNER AT LEAST 72 HOURS PRIOR TO COMMENCEMENT.
H. ALL DIMENSIONS ARE SHOWN TO FACE OF GYPSUM BOARD OF NEW
CONSTRUCTION OR STRUCTURAL WALL, UNLESS NOTED OTHERWISE.
I. ALL DRAWINGS, THOUGH NOTED TO SCALE ARE FOR ILLUSTRATION ONLY. THE
CONTRACTOR SHALL NOT SCALE DRAWINGS.
J. WHEN A DETAIL IS IDENTIFIED AS TYPICAL, THE CONTRACTOR IS TO APPLY THIS DETAIL
IN ESTIMATING AND CONSTRUCTION TO EVERY LIKE CONDITION WHETHER OR NOT
THE REFERENCE IS REPEATED IN EVERY INSTANCE.
K. DRAWINGS HAVE BEEN DETAILED IN COMPLIANCE WITH U.L. LISTING REQUIREMENTS
AND ICBO REPORTS FOR THE MATERIALS SPECIFIED. IF AN ALTERNATE OR SUBSTITUTED
MATERIAL IS ACCEPTED AS AN EQUAL BY THE GENERAL CONTRACTOR, HE/SHE WILL
ASSUME THE RESPONSIBILITY FOR WHATEVER CONSTRUCTION MODIFICATION
AND/OR ADDITIONAL COSTS ARE REQUIRED.
L. ALL TRASH SHALL BE REMOVED DAILY. BUILDING MATERIALS MAY NOT BE STORED IN
THE CORRIDORS AT ANY TIME. BLOCKAGE OF ANY REQUIRED EXIT IS PROHIBITED.
M. ALL PENETRATIONS INTO SOUND OR FIRE RATED PARTITIONS, FLOORS OR CEILING
ASSEMBLIES SHALL BE SEALED WITH APPROVED PERMANENT RESILIENT SEALANT. REFER
TO IBC CURRENT VERSION FOR REQUIREMENTS FOR OPENINGS IN FIRE RATED WALLS.
FOR OPENINGS LESS THAN 16 SQUARE INCHES, THE SPACE BETWEEN THE WALL AND
ALLOWED PENETRATIONS MUST BE SEALED TO PREVENT THE MOVEMENT OF HOT
FLAME OR GASES. ELECTRICAL DEVICES, RECESSED CABINETS, ETC. SHALL BE SEALED,
LINED, INSULATED OR OTHERWISE TREATED TO MAINTAIN THE INTEGRITY OF THE
ASSEMBLY. SEE PENETRATION DETAILS.
N. ABBREVIATIONS THROUGHOUT THE PLAN ARE THOSE IN COMMON USE. THE
ARCHITECT SHALL DEFINE THE INTENT OF ANY IN QUESTION.
O. THE CONTRACTOR SHALL VERIFY SIZES AND LOCATIONS OF WATER AND DRAIN
INSTALLATIONS AND OTHER REQUIRED SERVICES WITH EQUIPMENT MANUFACTURERS.
P. MAINTAIN ALL EXISTING SPRAY-APPLIED FIRE PROOFING ON STEEL STRUCTURAL
MEMBERS. WHERE EXISTING FIRE PROOFING IS REMOVED FOR INSTALLATION OF NEW
BEAMS, UNISTRUTS, ETC. THE CONTRACTOR SHALL PATCH AGAIN WITH EQUIVALENT
FIRE PROOFING MATERIAL TO MATCH ADJACENT EXISTING MATERIAL.
Q. ALL WOOD CANTS, NAILERS, CURBS, ETC. THROUGHOUT JOB SHALL BE FIRE
RETARDANT PRESSURE-TREATED, AS PER I.B.C. CURRENT VERSION. SEE RELEVANT
DETAILS.
R. CONTRACTOR SHALL REFER TO THE PROJECT MANUAL FOR A COMPLETE LIST OF
GENERAL CONDITIONS, SPECIAL CONDITIONS AND OTHER NOTES.
GENERAL NOTES
GENERAL NOTES - INTERIOR ELEVATIONSGENERAL NOTES - WALL SECTIONS
GENERAL NOTES - DOOR SCHEDULE
A. SEE PROJECT MANUAL FOR DOOR HARDWARE SCHEDULE.
B. SUB-CONTRACTOR UNDER SECTION 'ALUMINUM ENTRANCES AND STOREFRONT',
SHALL PROVIDE ALL THE DOOR HARDWARE FOR ALL ALUMINUM DOORS. SEE DOOR
SCHEDULE FOR ALUMINUM DOORS AND THE REQUIRED HARDWARE.
C. SUB-CONTRACTOR UNDER SECTION 'DOOR HARDWARE', SHALL PROVIDE ALL THE
DOOR HARDWARE FOR ALL THE WOOD AND HOLLOW METAL DOORS. SEE DOOR
SCHEDULE FOR WOOD AND HOLLOW METAL DOORS AND THE REQUIRED
HARDWARE.
D. ALL EXTERIOR DOORS SHALL BE INSULATED.
E. FIELD VERIFY WINDOW AND DOOR FRAME OPENING SIZES BEFORE FRAME
INSTALLATION. OVERALL DIMENSIONS INDICATED FOR EACH FRAME TYPE ARE
ROUGH OPENING SIZES IN WALLS. CONTRACTOR SHALL ADJUST INNER DIMENSIONS
AS REQUIRED TO MAKE DOORS AND WINDOWS WORK.
F. ELECTRICAL DEVICES SUCH AS MAG. LOCKS, CARD READERS AND ALARM SYSTEMS
BEING PART OF THE DOOR FUNCTION ARE INCLUDED AS PART OF THE ELECTRICAL
PLANS AND THE HARDWARE GROUPS. GENERAL CONTRACTOR IS RESPONSIBLE TO
COORDINATE LOCATIONS OF CARD READERS ETC. SHOWN ON ARCHITECTURAL
AND ELECTRICAL DRAWINGS WITH ALL TRADES INVOLVED.
G. COORDINATE DOORS & GATES OUTSIDE BUILDING WITH SITE PLAN.
A. PROVIDE LOCKS FOR CABINETS AS INDICATED ON THE CABINET LEGEND ON SHEET
A505A AND IF INDICATED ON INTERIOR ELEVATIONS.
B. IN ROOMS WHERE CABINETS ARE REQUIRED TO BE LOCKED, PROVIDE LOCKS
OPERABLE WITH SINGLE KEY.
C. FOR TYPICAL MOUNTING HEIGHTS, SEE SHEET G003. FOLLOW THE HEIGHT UNLESS
NOTED OTHERWISE IN INTERIOR ELEVATIONS. VERIFY WITH ARCHITECT FOR ITEMS NOT
INDICATED.
D. CONTRACTOR SHALL VERIFY WITH OWNER FOR OWNER FURNISHED CONTRACTOR
INSTALLED ITEMS AND PROVIDE BACKING IN WALL AS REQUIRED FOR INSTALLATION.
E. INTERIOR ELEVATIONS OF CERTAIN ROOMS ARE NOT DRAWN AND ARE NOTED AS
SIMILAR ELEVATIONS OF ROOMS THAT ARE INDICATED IN THE DRAWINGS.
F. CONTRACTOR SHALL PROVIDE FILLER PANELS (PLASTIC LAMINATE WRAPPED OVER
5/8" PARTICLE BOARD) WHEREVER GAP OCCURS BETWEEN CABINETS AND WALL.
G. SEE FINISH FLOOR PLANS AND FINISH SCHEDULE A603A FOR WALL, CABINET AND
COUNTERTOP FINISHES.
H. SEE SHEET A505A FOR CABINET LEGEND (TYPES B1, W1, T1, ETC.). UNLESS NOTED
OTHERWISE, ALL THE CABINETS AND COUNTERTOPS IN EACH ROOM SHALL BE OF THE
SAME FINISH (PL1, PL2, SS1, ETC.) AS INDICATED ON THE INTERIOR ELEVATION OF
EACH ROOM. WHERE MULTIPLE FINISHES ARE REQUIRED FOR CABINETS, WALLS, ETC.
IN THE ROOM, EACH FINISH IS INDICATED SEPARATELY. CONTACT ARCHITECT FOR
REQUIRED CLARIFICATIONS.
I. COUNTERTOPS ARE TYPICALLY SUPPORTED BY WALLS AND BASE CABINETS. IN PLACES
WHERE COUNTERTOP SPAN EXCEEDS 4’ - 0”, STEEL SUPPORTS SHALL BE PROVIDED AS
INDICATED IN DETAILS AND .
J. AS INDICATED ON INTERIOR ELEVATIONS, WALL CABINETS AT CERTAIN LOCATIONS
MAY REQUIRE A VERTICAL OR A SLOPED FASCIA PANEL.
K. AN ENLARGED FLOOR PLAN HAS BEEN INCLUDED ALONG WITH INTERIOR
ELEVATIONS FOR ROOMS THAT ARE COMPLEX IN DESIGN. SUCH COMPLEX ROOMS
ARE INDICATED ON THE A400 SERIES SHEETS (STARTING WITH SHEET A401). ENLARGED
FLOOR PLANS ARE NOT SHOWN FOR ROOMS THAT ARE SIMPLE IN DESIGN. INTERIOR
ELEVATIONS OF SUCH SIMPLE ROOMS ARE INDICATED ON THE A250 SERIES SHEETS
(STARTING WITH SHEET A251).
L. FOR ALL CABINETS PROVIDE BACKING IN WALL AS PER DETAIL 3/A505B.
A. ALL EXTERIOR WALL FINISHES ARE TO BE 6" ABOVE FINISH GRADE, TYPICAL.
B. SEE WINDOW SCHEDULE FOR WINDOW OPENINGS AND SILL HEIGHT (UNLESS NOTED
ON THE EXTERIOR ELEVATIONS). SEE DOOR SCHEDULE FOR DOOR OPENING SIZES.
C. ALL FINISHES TO BE INSTALLED PER MANUFACTURER RECOMMENDATIONS AND PER
SPECIFICATION SECTION IN THE PROJECT MANUAL.
D. SEE FINISH FLOOR PLANS FOR AREAS WHERE HONED CMU BLOCKS ARE INDICATED.
AT THESE AREAS, THE CONTRACTOR HAS THE OPTION OF USING REGULAR BLOCK IN
CONCEALED AREAS AND CEILING SPACES THAT ARE NOT VISIBLE.
E. SPACING BETWEEN STRUCTURAL MEMBERS SHALL FOLLOW INDICATIONS GIVEN ON
STRUCTURAL PLANS (TYPICAL).
F. FIRE PROTECTION ON ASSEMBLIES, ELEMENTS AND MEMBERS SHALL COMPLY WITH
ALL THE CODE REQUIREMENTS, TYPICAL - REFER TO CODE COMPLIANCE PLANS.
G. WOOD MATERIAL UNDER TYPE IIB CONSTRUCTION SHALL BE FIRE-RETARDANT,
PRESSURE-TREATED, TYPICAL, U.N.O.
H. ALL INTERIOR WALLS SHALL BE BUILT FOLLOWING WALL TYPE DETAILS, TYPICAL.
I. IN ROOMS/AREAS WHERE HONED, SCORED OR COLORED C.M.U. BLOCKS ARE
INDICATED FOR WALLS IN THE FINISH SCHEDULE, CONTRACTOR HAS THE OPTION OF
USING REGULAR (LESS EXPENSIVE NATURAL GRAY COLOR) BLOCKS IN CONCEALED
AREAS AND CEILING SPACES THAT ARE NOT VISIBLE. THIS DOES NOT APPLY TO AREAS
THAT CAN CHANGE OVER THE LIFE OF THE BUILDING SUCH AS WALL LOCATED
BEHIND CABINETS, ARTWORK, WHITE BOARD, TACK BOARD, ETC. WHEN OTHER
BLOCKS ARE SUBSTITUTED, THE STRUCTURAL INTEGRITY OF THE BLOCK SHALL REMAIN
THE SAME AS BLOCK INDICATED IN STRUCTURAL DRAWINGS AND SPECIFICATION
SECTION IN THE PROJECT MANUAL.
J. AT INTERIOR MASONRY WALL OUTSIDE CORNERS, PROVIDE BULL NOSE BLOCK.
K. CORE DRILLING WALLS AND SLABS: CONTRACTOR SHALL USE GROUND PENETRATING
RADAR OR OTHER APPROVED METHOD TO SCAN CONCRETE OVER METAL DECK,
CONCRETE SUSPENDED SLABS, MASONRY WALLS, AND CONCRETE WALLS TO
LOCATE REBAR PRIOR TO CORE DRILLING ANY HOLES. HOLES SHALL BE LOCATED TO
AVOID REBAR DETECTED. ALL OPENINGS AND GROUPS OF OPENINGS SHALL BE
REINFORCED AS SHOWN ON THE STRUCTURAL DRAWINGS. OPENINGS NOT SHOWN
ON THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER
PRIOR TO DRILLING.
FREEZER
EWC
02.02
02.0202.02 02.02
02.01
02.01
02.01
02.01
02.06 02.06
02.1802.18
02.1802.18
02.11
02.06
02.01
02.01
02.07
02.0702.07
02.06
02.10
02.18
02.0802.08
02.3502.35 02.01
02.21
02.22
02.0102.01
02.14
02.56
02.5702.57
02.57
02.57
02.57
02.03
02.03
02.03
02.03
02.53
02.47
02.47
02.48
02.57
02.61
TYP.
02.61
02.61
TYP.
TYP.
02.02
02.51
02.51
02.51
02.51
02.1602.16
02.1602.16
02.16
02.15
02.15
02.15
02.58
02.59
9' - 6"
EXISTING CEILING
02.55
02.55
02.60
02.60
02.62
ON ROOF
02.63
02.63
02.64
02.65
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5223 S. Ascension Way, Suite 350 Murray, Utah 84123
801.364.9259 www.njraarchitects.com
/2
/2
:2 :1
P
M
A111
Demolition Floor &
Reflected Ceiling Plans -
Level 1
J o rd a n S c h o o l D is tr ic t
O q u ir rh
E le m e n ta ry S c h o o l
S o u th
W e st
W e st J o rd a n
U
T
25712.00
Bid Documents January 20, 2026
K it c h e n R e m o d e l
KEYED NOTES
GENERAL NOTES
A. SEE SHEET G003 AND G005 FOR SYMBOLS, GENERAL NOTES AND LEGEND.
B. SEE SHEET A505A FOR CABINET LEGEND.
C. SEE SHEET A601A FOR DOOR SCHEDULE.
D. SEE SHEET A602A FOR WINDOW SCHEDULE.
E. SEE SHEET A603A FOR FINISH SCHEDULE AND GENERAL NOTES.
02.01 WALL. EXISTING WALL TO REMAIN. PROTECT WALL FROM DAMAGE DURING
CONSTRUCTION.
02.02 WALL. EXISTING WALL INDICATED WITH DASHED LINE TO BE REMOVED.
02.03 WALL FINISH (WALL COVERING, WALL PROTECTION SHEETS, WAINSCOT,
CORNER GUARDS, ACOUSTICAL PANELS, ETC.). EXISTING TO REMAIN.
PROTECT WALL FINISH FROM DAMAGE DURING CONSTRUCTION.
02.06 DOOR AND DOOR FRAME. EXISTING INDICATED WITH DASHED LINE TO BE
REMOVED. DOOR FRAME TO BE REMOVED UNLESS NOTED OTHERWISE.
02.07 DOOR FRAME. EXISTING TO REMAIN. PROTECT DOOR FRAME FROM DAMAGE
DURING CONSTRUCTION.
02.08 DOOR FRAME. EXISTING INDICATED WITH DASHED LINE TO BE REMOVED.
02.10 WINDOW. EXISTING WINDOW INDICATED WITH DASHED LINE TO BE REMOVED.
02.11 PLUMBING FIXTURE. EXISTING TO REMAIN. PROTECT FIXTURE FROM DAMAGE
DURING CONSTRUCTION.
02.14 CABINET AND COUNTERTOP. EXISTING CABINET AND COUNTERTOP INDICATED
WITH DASHED LINE TO BE REMOVED.
02.15 CEILING. EXISTING TO REMAIN. PROTECT CEILING FROM DAMAGE DURING
CONSTRUCTION.
02.16 CEILING. EXISTING CEILING INDICATED (AS LAY-IN TILES WITH GRID SYSTEM OR
GYPSUM BOARD) IN THIS AREA TO BE REMOVED.
02.18 FLOOR COVERING. EXISTING FLOOR COVERING INDICATED IN THIS AREA TO
BE REMOVED. COORDINATE EXTENT OF REMOVAL WITH FINISH FLOOR PLANS
FOR NEW FLOOR COVERING LOCATIONS AND TRANSITION LINE BETWEEN
EXISTING AND NEW FLOOR COVERINGS.
02.21 TRENCH SUBFLOOR. EXISTING SUBFLOOR INDICATED IN THIS AREA TO BE
TRENCHED AND REPLACED WITH NEW SUBFLOOR TO MATCH EXISTING.
COORDINATE EXTENT OF TRENCHING WITH ELECTRICAL, MECHANICAL, AND
FOOD SERVICE DRAWINGS.
02.22 WALL TILE. EXISTING WALL TILE AND SUBSTRATE INDICATED IN THIS AREA TO BE
REMOVED. RETAIN AND PROTECT EXISTING METAL FRAMING. PREPARE
FRAMING TO RECEIVE NEW TILE SUBSTRATE AND WALL TILE.
02.35 DOORS TO BE REMOVED AND SWAPPED TO ALLOW THE ROTATION OF 180
DEGREES. PROTECT DOOR FROM DAMAGE DURING CONSTRUCTION.
02.47 ELECTRICAL AND FIRE PROTECTION FIXTURES. EXISTING FIXTURES TO BE
RELOCATED. SEE ELECTRICAL DRAWINGS AND COORDINATE.
02.48 WARE WASHING STATION. EXISTING TO REMAIN. PROTECT FROM DAMAGE.
02.51 SAWCUT EXISTING FLOOR AS REQUIRED FOR FLOOR SINK. PROTECT EXISTING
WALLS & EQUIPMENT FROM DAMAGE. FIELD VERIFY. SEE PLUMBING AND
FOOD SERVICE DRAWINGS AND COORDINATE.
02.53 PLUMBING. EXISTING WATER LINES, VALVES, & WASTE LINE TO REMAIN.