6-JF26-028-IFB 5747 GTI Five Story Annex CO Upgrade - Permit Set.PDF

PDF 3 MB Posted

Attached to
Construction: Fire Alarm Upgrade at GTI 5-Story and Annex
Solicitation number
JF26-028-IFB
Issued by
Salt Lake County, Utah

About this file

This is a permit set drawing package prepared by Electrical Consulting Engineers for the Granite School District's fire alarm and carbon monoxide detection system upgrade project at Granite Technical Institute (GTI), a five-story building located at 2500 South Main Street in Salt Lake City, Utah. The project involves furnishing and installing a new addressable fire alarm control panel system with integrated carbon monoxide detection capabilities throughout the GTI five-story building and adjacent annex. The scope includes installation of combination smoke/carbon monoxide detectors (part #CO1224TR), photoelectric smoke detectors, heat detectors, manual pull stations, horns with strobes, addressable strobes, flow switches, and temper switches. The system must maintain Class "A" loop wiring configuration with all new devices tied to the fire alarm control panel. The contractor must provide programming to enable new CO detectors to shut off fans during alarm conditions. The work requires existing fire alarm systems to remain operational until the new system is fully installed, tested, and commissioned. A pre-bid meeting attendance is required, and award recommendation is anticipated at the June 2, 2026 board meeting following final board approval.

The project specifications require licensed General Electrical Contractors (E200) to submit sealed bids for the complete installation. All materials must be U.L. approved and new, with a guaranteed warranty period of one year from the date of acceptance by the tenant. Contractors must conduct site inspections prior to bidding and include all charges for existing conditions in their bid packages. Shop drawings are mandatory submissions. The electrical work must comply with the current adopted National Electrical Code, utilize rigid steel set screw type fittings for interior work, and maintain minimum three-quarter inch conduit sizing. Specific conductor sizing requirements apply based on wire run lengths, and all exposed conduit must be galvanized rigid steel. Additional requirements include removal of all abandoned conduit and equipment in accessible ceilings, patching and painting of affected walls and ceilings to match existing finishes, and replacement of any damaged tiles. The contractor must provide updated typed panel schedules showing all circuit changes made during the project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E000: COVER SHEET

E001: GENERAL NOTES AND SYMBOL LISTS AND DETAILS

E002: FIRE ALARM RISER DIAGRAM

EY101: GRANITE TECHNICAL FIRST FLOOR PLAN - FIRE ALARM

EY102: GRANITE TECHNICAL SECOND FLOOR PLAN - FIRE ALARM

EY103: GRANITE TECHNICAL THIRD FLOOR PLAN - FIRE ALARM

EY104: GRANITE TECHNICAL FOURTH FLOOR PLAN - FIRE ALARM

EY105: ANNEX BASEMENT FIRST FLOOR AND SECOND FLOOR PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

JW AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

G R

A N

IT

E

T E

C H

N

IC

A L

S C

H O

O L

S

T O

R Y

B U

IL

D

IN

G

A N

D A

N N

E X

C A

R B

O N

M O

N O

X

ID

E U

P G

R A

D E

S

O U

T H

M A

IN

S

T R

E E

T

S A

L T

L A

K E

C

IT

Y

U T

A H

E000

COVER SHEET

CARBON MONOXIDE UPGRADE IN FOLLOWING SCHOOLS:

GRANITE SCHOOL DISTRICT

GRANITE TECHNICAL INSTITUTE & ANNEX

2500 SOUTH STATE ST

SOUTH SALT LAKE, UT 84115

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

E001

GENERAL NOTES,

SYMBOL LIST AND

DETAILS

FIRE ALARM SYSTEMS SYMBOL LIST

SYMBOL DESCRIPTION

ELECTRICAL PANEL LOCATION, PART #: FACU: E3-BB-BB, NAC: SBB-D4, REMOTE

ANNUNCIATOR: E3-BB-BAA

FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, PART #: ASD-PL3

FIRE ALARM HEAT DETECTOR, PART #: ATD-L3R

FIRE ALARM COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, PART #:

CO1224TR

FIRE ALARM MANUAL PULL STATION, +42" A.F.F., PART #: MS-7AF

FIRE ALARM HORN WITH STROBE, HIGH DECIBEL, +96" A.F.F., PART #: WALL: P2WL,

CEILING: PC2WL, WEATHER PROOF: P2RK

A.D.A. STROBE FOR FIRE ALARM, +96" A.F.F., PART #: WALL: SWL, CEILING: SCWL

BLUE STROBE LIGHT

FIRE SPRINKLER FLOW SWITCH, PART #: AMM-4F

FIRE SPRINKLER TEMPER SWITCH, PART #: AMM-4F

FLOOR FLOOD SENSOR

BEAM DETECTOR TRANSMITTER - LETTER INDICATES PAIRING

BEAM DETECTOR RECEIVER - LETTER INDICATES PAIRING

BEAM CONTROLLER

RELAY MODULE, PART #: PR-3

KITCHEN HOOD MONITOR

CONTROL MODULE

CONTROL MODULE WITH RELAY

B

CM

R

FFS

TS

FS

F

ABBREVIATIONS SYMBOL LIST

SYMBOL DESCRIPTION

W.P. INDICATES WEATHER PROOF EQUIPMENT

A INDICATES DEVICE IS ABOVE COUNTER TOP

AMP. AMPERAGE

A.F.F. ABOVE FINISHED FLOOR

B.CO BLUE CARBON MONOXIDE STROBE

CLG. INDICATES CEILING MOUNTED DEVICE

EM INDICATES DEVICE IS ON EMERGENCY CIRCUIT

EX INDICATES DEVICE IS EXISTING

F.A.C.P. FIRE ALARM CONTROL PANEL

F.A.R.A.P. FIRE ALARM REMOTE ANNUNCIATOR PANEL

K.V.A. KILO VOLT AMPERAGE

K.W. KILOWATT

M.C.B. MAIN CIRCUIT BREAKER

M.L.O. MAIN LUG ONLY

O.T.R. ON THE ROOF

S INDICATES DEVICE IS SURFACE MOUNTED

T.V.S.S. TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP TYPICAL

U.P.S. UNINTERRUPTIBLE POWER SUPPLY

XFMR TRANSFORMER

CALLOUT SYMBOL LIST

SYMBOL DESCRIPTION

LIGHTING FIXTURE CALLOUT NUMBER INDICATES A SUGGESTED QUANTITY- TO BE

VERIFIED

MECHANICAL EQUIPMENT CALLOUT

DETAIL REFERENCE CALLOUT

REVISION NUMBER CALLOUT

EQUIPMENT CALLOUT

REFERENCE NOTE CALLOUT

THROUGH CONCRETE WALLS

MAY 09, 2013

F RATING - 2 HR

T RATING - 0 HR

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ. FT.

L RATING AT 400 F - LESS THAN 1 CFM/SQ. FT.

SECTION A-A

WALL ASSEMBLY

A

A

SCALE: TYPICAL FIRESTOP FOR CABLES/CONDUIT

N.T.S.

ANCHOR TO WALL WITH

EPOXY ANCHORS AS

REQUIRED BY WEIGHT

SUPPORTED (TYPICAL)

TYPICAL WIRING FOR EACH SPRINKLER RISER (SEE FIRE SPRINKLER

DRAWINGS FOR QUANTITY AND LOCATIONS.)

MAIN

OS&Y VALVE

DETECTOR SWITCH FURNISHED AND

INSTALLED BY SPRINKLER

4 #14, 1/2''CONDUIT

ALARM VALVE

SEAL TIGHT

4 #14, 1/2''CONDUIT

WALL MOUNTED JUNCTION BOX

FLOW SWITCH FURNISHED AND INSTALLED BY

SPRINKLER CONTRACTOR, WIRED BY ELEC.

RISER

CONDUIT 8 #14 THW, 3/4''CONDUIT

TO FIRE ALARM MASTER TYPICAL

EACH SPRINKLER RISER.

CEILING

SCALE:

FIRE SPRINKLER CONNECTION DETAIL

N.T.S.

CONTRACTOR, WIRED BY ELEC.

GENERAL NOTES:

1. PRIOR TO SUBMITTING A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND

INCLUDE IN HIS BID PACKAGE ALL CHARGES DUE TO EXISTING CONDITIONS. SHOP

DRAWINGS ARE REQUIRED. ALL LABOR, MATERIAL AND WORKMANSHIP SHALL BE

GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT.

REPLACE OR REPAIR ALL DEFECTS DURING THE GUARANTEED PERIOD.

2. MINIMUM SIZE OF CONDUIT TO BE 3/4". ALUMINUM CONDUITS SHALL NOT BE USED.

3. USE RIGID STEEL SET SCREW TYPE FITTINGS ONLY FOR INTERIOR WORK. DIE CAST

FITTINGS SHALL NOT BE USED.

4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR (EACH CIRCUIT) IN A

CONDUIT. NOT MORE THAN THREE (3) CIRCUITS IN A CONDUIT. THREE (3) PHASE

CONDUCTORS, THREE (3) NEUTRAL CONDUCTORS (ONE FOR EACH PHASE) AND ONE (1)

GROUND CONDUCTOR FOR A TOTAL OF SEVEN (7) CONDUCTORS.

5. THE MINIMUM SIZE OF THE CONDUCTORS ARE TO BE #12 AWG THHN COPPER, UNLESS

INDICATED OTHERWISE ON THE DRAWINGS.

6. ALL J-BOXES SHALL HAVE MINIMUM DEPTH OF 2-3/8" UNLESS OTHERWISE SPECIFIED.

SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD

RINGS.

7. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (MC CABLE IS PERMITTED).

8. USE NO. 10 THHN CONDUCTORS FOR CONDUCTOR LENGTH OVER 100 FEET, NO. 8 THHN

OVER 200 FEET, NO. 6 THHN OVER 300 FEET AND NO. 4 THHN OVER 400 FEET LENGTH.

9. ALL CONDUITS EXPOSED TO THE WEATHER SHALL BE GALVANIZED RIGID STEEL, UNLESS

OTHERWISE NOTED.

10. PROVIDE UPDATED, TYPED WRITTEN, PANEL SCHEDULES FOR NEW AND EXISTING

PANELBOARDS SHOWING CIRCUIT CHANGES MADE DURING THIS PROJECT.

11. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE.

12. ALL MATERIALS USED IN THIS INSTALLATION SHALL BE U.L. APPROVED AND NEW.

1. EXISTING FIRE ALARM SYSTEM IS TO REMAIN IN OPERATION UNTIL THE NEW SYSTEM IS

INSTALLED, TESTED AND PUT IN OPERATION.

2. ALL CONDUIT AND BOXES IN THE BRICK WALLS CAN REMAIN. PROVIDE COVER PLATE

FOR THE BOXES TO MATCH COLOR OF THE BRICKS.

3. PATCH AND PAINT ALL WALLS WHERE DEVICES ARE REMOVED. PAINT COLOR IS TO

MATCH THE REST OF THE EXISTING WALL.

4. REPLACE ALL TILES DAMAGED DURING CONSTRUCTION AND TILES WHERE DEVICES ARE

REMOVED WITH MATCHING NEW ONES.

5. CONTRACTOR MUST REMOVE ALL ABANDONED CONDUIT, CONDUCTORS, J-BOXES, ETC.

IN ACCESSIBLE CEILINGS.

6. CLASS "A" LOOP MUST BE MAINTAINED TO ALL NEW FIRE ALARM DEVICES.

7. PLENUM CABLES ARE ALLOWED TO BE USED FOR NEW CABLES AS LONG AS THE

FOLLOWING ARE MET: THE RUN IS CONCEALED, USED IN CONJUNCTION WITH

NON-METALLIC BOXES, AND RACEWAYS ONLY. PROVIDE J-HOOKS EVERY 5 FEET TO

SUPPORT THE CABLES. DO NOT LAY THE CABLES ON TOP OF EXISTING CEILING OR

ANYWHERE THAT CAN BE DAMAGED. IF METALLIC BOXES AND CONDUIT ARE TO BE USED

UTILIZE MC CABLE FOR ALL THE WIRING.

8. THE CONTRACTOR IS ALLOWED TO USE 1/2" EMT CONDUIT ON SURFACES IN LIEU OF

WIREMOLD. PAINT CONDUIT ON EXPOSED SURFACES. COLOR TO MATCH COLOR OF

GROUT OF EXISTING BRICKS.

9. ALL EXISTING ABANDONED FIRE ALARM CONDUIT, CABLES, J-BOXES, ETC. MUST BE

REMOVED AT THE END OF THE PROJECT.

10. THE CONTRACTOR IS TO PROVIDE A UNIT COST FOR NEW 2'X2' ACCESS PANEL IN

EXISTING CEILING.

11. THE CONTRACTOR IS TO SEAL AND PAINT ALL PENETRATIONS ON FINISHED WALLS AND

CEILINGS. PAINT COLOR IS TO MATCH THE WALL OR CEILING ACCORDINGLY.

12. ASBESTOS CONTAINING MATERIALS (ACM) MAY BE PRESENT AT THE PROJECT SITE. GSD

WILL ABATE ACM OR PROVIDE CONTRACTOR WITH A PROTOCOL FOR USE WHEN

DRILLING, CUTTING, OR FASTENING TO ACM.

13. REFER TO SPECS FOR APPROVED MANUFACTURES. MANUFACTURER'S MODEL

NUMBERS AND LISTING INFORMATION FOR EQUIPMENT WILL BE PROVIDED BY THE

ELECTRICAL CONTRACTOR AND ALSO ON DEFERRED. SUBMITTALS.

SPECIAL NOTES:

SCALE:

N.T.S.

1/2" FLEX x 6' (MAX)

MAINTAIN CLASS A WIRING

LAY-IN TILE CEILING

3/4" CONDUIT FOR FIRE

ALARM LOOP

4" SQUARE x 2-1/8" J-BOX

AT CEILING DECK

3/4" CONDUIT FOR

FIRE ALARM LOOP

CONNECTIONS FOR FIRE ALARM

DEVICES IN LAY-IN CEILINGS

(3) HP-FF8

CONDUITS

& ONE 3/4"

TWO 1"

5.2" DEEP

24" WIDE

45.9" HIGH

3 PAIR #16'S TWISTED

TRANSPONDER

SBB-D4

w/FCI-DR-D4B

REMOTE

ANNUNCIATOR

E3-BB-BAA

4.5" DEEP

19.25" WIDE

10" HIGH

w/E3-ID2-A

DEDICATED CIRCUIT

120 VAC W/GROUND

1 CAT-6E TO PHONE BOARD

2 CAT-6E TO NETWORK PORTS

FACU

S3-BB-RB

4.5" DEEP

19.375" WIDE

19.375" HIGH

MINI

BATTERY

CABINET

4" DEEP

17" WIDE

8" HIGH

FLPS-7

SLC-PM

SLP-RB

DACT-E3

LCD-SLP

2 #14'S

TYPICAL 24 AUX POWER

1 PAIR #14'S TWISTED

TYPICAL ADDRESSABLE CIRCUIT

4 #14'S4 #14'S

TO FAN

SHUTDOWN

2 #14'S

TYPICAL NOTIFICATION CIRCUIT

2 #14'S

TYPICAL CO NOTIFICATION CIRCUIT

B B

WPB

E002

FIRE ALARM RISER

DIAGRAM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

JW AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

G R

A N

IT

E

T E

C H

N

IC

A L

S C

H O

O L

S

T O

R Y

B U

IL

D

IN

G

A N

D A

N N

E X

C A

R B

O N

M O

N O

X

ID

E U

P G

R A

D E

S

O U

T H

M A

IN

S

T R

E E

T

S A

L T

L A

K E

C

IT

Y

U T

A H

F.A.C.P.

F.A.C.P.EXISTING TRANSPONDER

EXISTING

REMOTE

ANNUNCIATOR

EXISTING

REMOTE

ANNUNCIATOR

REMOTE

ANNUNCIATOR

EXISTING

REMOTE

ANNUNCIATOR

EXISTING F.A.C.P.

1. FURNISH AND INSTALL A NEW CARBON MONOXIDE

DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE

THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS

"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO

NOT SPLICE CABLES BETWEEN DEVICES.

1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING

ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH

THIS WORK.

SCALE: 1/16" = 1'-0"

EY101

FIRST FLOOR

PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

JW AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

G R

A N

IT

E

T E

C H

N

IC

A L

S C

H O

O L

S

T O

R Y

B U

IL

D

IN

G

A N

D A

N N

E X

C A

R B

O N

M O

N O

X

ID

E U

P G

R A

D E

S

O U

T H

M A

IN

S

T R

E E

T

S A

L T

L A

K E

C

IT

Y

U T

A H

TRANSPONDER

1 1

1. FURNISH AND INSTALL A NEW CARBON MONOXIDE

DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE

THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS

"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO

NOT SPLICE CABLES BETWEEN DEVICES.

1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING

ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH

THIS WORK.

SCALE: 1/16" = 1'-0"

EY102

SECOND

FLOOR PLAN -

FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

JW AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

G R

A N

IT

E

T E

C H

N

IC

A L

S C

H O

O L

S

T O

R Y

B U

IL

D

IN

G

A N

D A

N N

E X

C A

R B

O N

M O

N O

X

ID

E U

P G

R A

D E

S

O U

T H

M A

IN

S

T R

E E

T

S A

L T

L A

K E

C

IT

Y

U T

A H

1. FURNISH AND INSTALL A NEW CARBON MONOXIDE

DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE

THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS

"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO

NOT SPLICE CABLES BETWEEN DEVICES.

1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING

ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH

THIS WORK.

SCALE: 1/16" = 1'-0"

EY103

THIRD FLOOR

PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

JW AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

G R

A N

IT

E

T E

C H

N

IC

A L

S C

H O

O L

S

T O

R Y

B U

IL

D

IN

G

A N

D A

N N

E X

C A

R B

O N

M O

N O

X

ID

E U

P G

R A

D E

S

O U

T H

M A

IN

S

T R

E E

T

S A

L T

L A

K E

C

IT

Y

U T

A H

1. FURNISH AND INSTALL A NEW CARBON MONOXIDE

DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE

THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS

"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO

NOT SPLICE CABLES BETWEEN DEVICES.

1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING

ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH

THIS WORK.

SCALE: 1/16" = 1'-0"

EY104

FOURTH

FLOOR PLAN -

FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

JW AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

G R

A N

IT

E

T E

C H

N

IC

A L

S C

H O

O L

S

T O

R Y

B U

IL

D

IN

G

A N

D A

N N

E X

C A

R B

O N

M O

N O

X

ID

E U

P G

R A

D E

S

O U

T H

M A

IN

S

T R

E E

T

S A

L T

L A

K E

C

IT

Y

U T

A H

OFFICE OR

GOWNING

MOCK CLEAN LAB

UNISEX

SERVER

ROOM

OFFICE

DIRTY LAB

GENERAL LAB

VESTIBULE

STAIR

VETERINARY

STORAGE

VETERINARY

OFFICE

VETERINARY

LAB

VETERINARY

WASH

HEARING

CENTER

WOMEN'S

MEN'S

CUSTODIAL

STAIR

HALL

HALL

F.A.C.P.

TRANSPONDER

1. FURNISH AND INSTALL A NEW DEVICE IN THE APPROXIMATE

LOCATION SHOWN. TIE THE NEW DEVICE TO FIRE ALARM

CONTROL PANEL IN CLASS "A" LOOP. IN AND OUT CABLES

MUST RUN IN PLENUM. DO NOT SPLICE CABLES BETWEEN

DEVICES.

2. FURNISH AND INSTALL A NEW CONTROL MODULE IN THE

APPROXIMATE LOCATION SHOWN. TIE TO F.A.C.P. B IN CLASS

"A" LOOP.

3. FURNISH AND INSTALL A BLUE STROBE LIGHT FOR NEW "CO"

DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE TO

FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP FOR A

COMPLETE INSTALLATION.

4. FURNISH AND INSTALL AN ADDRESSABLE FIRE ALARM

CONTROL PANEL AND TRANSPONDER IN THE APPROXIMATE

LOCATION SHOWN, COORDINATE WITH GSD REPRESENTATIVE

FOR EXACT LOCATION. TIE THE NEW F.A.C.P. AND

TRANSPONDER TO A 20 AMP, 1-POLE RED CIRCUIT BREAKER

IN THE NEAREST PANEL. PROVIDE CONDUIT AND

CONDUCTORS FOR A COMPLETE INSTALLATION.

1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING ALARM.

PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH THIS WORK.

EY105

BASEMENT,

FIRST FLOOR

AND SECOND

FLOOR PLANS

- FIRE ALARM

SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0" CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

JW AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747

G R

A N

IT

E

T E

C H

N

IC

A L

S C

H O

O L

S

T O

R Y

B U

IL

D

IN

G

A N

D A

N N

E X

C A

R B

O N

M O

N O

X

ID

E U

P G

R A

D E

S

O U

T H

M A

IN

S

T R

E E

T

S A

L T

L A

K E

C

IT

Y

U T

A H

File details come from the government source that posted it. Updated .