6-JF26-028-IFB 5747 GTI Five Story Annex CO Upgrade - Permit Set.PDF
PDF 3 MB Posted
- Solicitation number
- JF26-028-IFB
- Issued by
- Salt Lake County, Utah
About this file
This is a permit set drawing package prepared by Electrical Consulting Engineers for the Granite School District's fire alarm and carbon monoxide detection system upgrade project at Granite Technical Institute (GTI), a five-story building located at 2500 South Main Street in Salt Lake City, Utah. The project involves furnishing and installing a new addressable fire alarm control panel system with integrated carbon monoxide detection capabilities throughout the GTI five-story building and adjacent annex. The scope includes installation of combination smoke/carbon monoxide detectors (part #CO1224TR), photoelectric smoke detectors, heat detectors, manual pull stations, horns with strobes, addressable strobes, flow switches, and temper switches. The system must maintain Class "A" loop wiring configuration with all new devices tied to the fire alarm control panel. The contractor must provide programming to enable new CO detectors to shut off fans during alarm conditions. The work requires existing fire alarm systems to remain operational until the new system is fully installed, tested, and commissioned. A pre-bid meeting attendance is required, and award recommendation is anticipated at the June 2, 2026 board meeting following final board approval.
The project specifications require licensed General Electrical Contractors (E200) to submit sealed bids for the complete installation. All materials must be U.L. approved and new, with a guaranteed warranty period of one year from the date of acceptance by the tenant. Contractors must conduct site inspections prior to bidding and include all charges for existing conditions in their bid packages. Shop drawings are mandatory submissions. The electrical work must comply with the current adopted National Electrical Code, utilize rigid steel set screw type fittings for interior work, and maintain minimum three-quarter inch conduit sizing. Specific conductor sizing requirements apply based on wire run lengths, and all exposed conduit must be galvanized rigid steel. Additional requirements include removal of all abandoned conduit and equipment in accessible ceilings, patching and painting of affected walls and ceilings to match existing finishes, and replacement of any damaged tiles. The contractor must provide updated typed panel schedules showing all circuit changes made during the project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E000: COVER SHEET
E001: GENERAL NOTES AND SYMBOL LISTS AND DETAILS
E002: FIRE ALARM RISER DIAGRAM
EY101: GRANITE TECHNICAL FIRST FLOOR PLAN - FIRE ALARM
EY102: GRANITE TECHNICAL SECOND FLOOR PLAN - FIRE ALARM
EY103: GRANITE TECHNICAL THIRD FLOOR PLAN - FIRE ALARM
EY104: GRANITE TECHNICAL FOURTH FLOOR PLAN - FIRE ALARM
EY105: ANNEX BASEMENT FIRST FLOOR AND SECOND FLOOR PLAN - FIRE
ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
JW AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
G R
A N
IT
E
T E
C H
N
IC
A L
S C
H O
O L
S
T O
R Y
B U
IL
D
IN
G
A N
D A
N N
E X
C A
R B
O N
M O
N O
X
ID
E U
P G
R A
D E
S
O U
T H
M A
IN
S
T R
E E
T
S A
L T
L A
K E
C
IT
Y
U T
A H
E000
COVER SHEET
CARBON MONOXIDE UPGRADE IN FOLLOWING SCHOOLS:
GRANITE SCHOOL DISTRICT
GRANITE TECHNICAL INSTITUTE & ANNEX
2500 SOUTH STATE ST
SOUTH SALT LAKE, UT 84115
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
E001
GENERAL NOTES,
SYMBOL LIST AND
DETAILS
FIRE ALARM SYSTEMS SYMBOL LIST
SYMBOL DESCRIPTION
ELECTRICAL PANEL LOCATION, PART #: FACU: E3-BB-BB, NAC: SBB-D4, REMOTE
ANNUNCIATOR: E3-BB-BAA
FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, PART #: ASD-PL3
FIRE ALARM HEAT DETECTOR, PART #: ATD-L3R
FIRE ALARM COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, PART #:
CO1224TR
FIRE ALARM MANUAL PULL STATION, +42" A.F.F., PART #: MS-7AF
FIRE ALARM HORN WITH STROBE, HIGH DECIBEL, +96" A.F.F., PART #: WALL: P2WL,
CEILING: PC2WL, WEATHER PROOF: P2RK
A.D.A. STROBE FOR FIRE ALARM, +96" A.F.F., PART #: WALL: SWL, CEILING: SCWL
BLUE STROBE LIGHT
FIRE SPRINKLER FLOW SWITCH, PART #: AMM-4F
FIRE SPRINKLER TEMPER SWITCH, PART #: AMM-4F
FLOOR FLOOD SENSOR
BEAM DETECTOR TRANSMITTER - LETTER INDICATES PAIRING
BEAM DETECTOR RECEIVER - LETTER INDICATES PAIRING
BEAM CONTROLLER
RELAY MODULE, PART #: PR-3
KITCHEN HOOD MONITOR
CONTROL MODULE
CONTROL MODULE WITH RELAY
B
CM
R
FFS
TS
FS
F
ABBREVIATIONS SYMBOL LIST
SYMBOL DESCRIPTION
W.P. INDICATES WEATHER PROOF EQUIPMENT
A INDICATES DEVICE IS ABOVE COUNTER TOP
AMP. AMPERAGE
A.F.F. ABOVE FINISHED FLOOR
B.CO BLUE CARBON MONOXIDE STROBE
CLG. INDICATES CEILING MOUNTED DEVICE
EM INDICATES DEVICE IS ON EMERGENCY CIRCUIT
EX INDICATES DEVICE IS EXISTING
F.A.C.P. FIRE ALARM CONTROL PANEL
F.A.R.A.P. FIRE ALARM REMOTE ANNUNCIATOR PANEL
K.V.A. KILO VOLT AMPERAGE
K.W. KILOWATT
M.C.B. MAIN CIRCUIT BREAKER
M.L.O. MAIN LUG ONLY
O.T.R. ON THE ROOF
S INDICATES DEVICE IS SURFACE MOUNTED
T.V.S.S. TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
U.P.S. UNINTERRUPTIBLE POWER SUPPLY
XFMR TRANSFORMER
CALLOUT SYMBOL LIST
SYMBOL DESCRIPTION
LIGHTING FIXTURE CALLOUT NUMBER INDICATES A SUGGESTED QUANTITY- TO BE
VERIFIED
MECHANICAL EQUIPMENT CALLOUT
DETAIL REFERENCE CALLOUT
REVISION NUMBER CALLOUT
EQUIPMENT CALLOUT
REFERENCE NOTE CALLOUT
THROUGH CONCRETE WALLS
MAY 09, 2013
F RATING - 2 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ. FT.
L RATING AT 400 F - LESS THAN 1 CFM/SQ. FT.
SECTION A-A
WALL ASSEMBLY
A
A
SCALE: TYPICAL FIRESTOP FOR CABLES/CONDUIT
N.T.S.
ANCHOR TO WALL WITH
EPOXY ANCHORS AS
REQUIRED BY WEIGHT
SUPPORTED (TYPICAL)
TYPICAL WIRING FOR EACH SPRINKLER RISER (SEE FIRE SPRINKLER
DRAWINGS FOR QUANTITY AND LOCATIONS.)
MAIN
OS&Y VALVE
DETECTOR SWITCH FURNISHED AND
INSTALLED BY SPRINKLER
4 #14, 1/2''CONDUIT
ALARM VALVE
SEAL TIGHT
4 #14, 1/2''CONDUIT
WALL MOUNTED JUNCTION BOX
FLOW SWITCH FURNISHED AND INSTALLED BY
SPRINKLER CONTRACTOR, WIRED BY ELEC.
RISER
CONDUIT 8 #14 THW, 3/4''CONDUIT
TO FIRE ALARM MASTER TYPICAL
EACH SPRINKLER RISER.
CEILING
SCALE:
FIRE SPRINKLER CONNECTION DETAIL
N.T.S.
CONTRACTOR, WIRED BY ELEC.
GENERAL NOTES:
1. PRIOR TO SUBMITTING A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND
INCLUDE IN HIS BID PACKAGE ALL CHARGES DUE TO EXISTING CONDITIONS. SHOP
DRAWINGS ARE REQUIRED. ALL LABOR, MATERIAL AND WORKMANSHIP SHALL BE
GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT.
REPLACE OR REPAIR ALL DEFECTS DURING THE GUARANTEED PERIOD.
2. MINIMUM SIZE OF CONDUIT TO BE 3/4". ALUMINUM CONDUITS SHALL NOT BE USED.
3. USE RIGID STEEL SET SCREW TYPE FITTINGS ONLY FOR INTERIOR WORK. DIE CAST
FITTINGS SHALL NOT BE USED.
4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR (EACH CIRCUIT) IN A
CONDUIT. NOT MORE THAN THREE (3) CIRCUITS IN A CONDUIT. THREE (3) PHASE
CONDUCTORS, THREE (3) NEUTRAL CONDUCTORS (ONE FOR EACH PHASE) AND ONE (1)
GROUND CONDUCTOR FOR A TOTAL OF SEVEN (7) CONDUCTORS.
5. THE MINIMUM SIZE OF THE CONDUCTORS ARE TO BE #12 AWG THHN COPPER, UNLESS
INDICATED OTHERWISE ON THE DRAWINGS.
6. ALL J-BOXES SHALL HAVE MINIMUM DEPTH OF 2-3/8" UNLESS OTHERWISE SPECIFIED.
SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD
RINGS.
7. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (MC CABLE IS PERMITTED).
8. USE NO. 10 THHN CONDUCTORS FOR CONDUCTOR LENGTH OVER 100 FEET, NO. 8 THHN
OVER 200 FEET, NO. 6 THHN OVER 300 FEET AND NO. 4 THHN OVER 400 FEET LENGTH.
9. ALL CONDUITS EXPOSED TO THE WEATHER SHALL BE GALVANIZED RIGID STEEL, UNLESS
OTHERWISE NOTED.
10. PROVIDE UPDATED, TYPED WRITTEN, PANEL SCHEDULES FOR NEW AND EXISTING
PANELBOARDS SHOWING CIRCUIT CHANGES MADE DURING THIS PROJECT.
11. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE.
12. ALL MATERIALS USED IN THIS INSTALLATION SHALL BE U.L. APPROVED AND NEW.
1. EXISTING FIRE ALARM SYSTEM IS TO REMAIN IN OPERATION UNTIL THE NEW SYSTEM IS
INSTALLED, TESTED AND PUT IN OPERATION.
2. ALL CONDUIT AND BOXES IN THE BRICK WALLS CAN REMAIN. PROVIDE COVER PLATE
FOR THE BOXES TO MATCH COLOR OF THE BRICKS.
3. PATCH AND PAINT ALL WALLS WHERE DEVICES ARE REMOVED. PAINT COLOR IS TO
MATCH THE REST OF THE EXISTING WALL.
4. REPLACE ALL TILES DAMAGED DURING CONSTRUCTION AND TILES WHERE DEVICES ARE
REMOVED WITH MATCHING NEW ONES.
5. CONTRACTOR MUST REMOVE ALL ABANDONED CONDUIT, CONDUCTORS, J-BOXES, ETC.
IN ACCESSIBLE CEILINGS.
6. CLASS "A" LOOP MUST BE MAINTAINED TO ALL NEW FIRE ALARM DEVICES.
7. PLENUM CABLES ARE ALLOWED TO BE USED FOR NEW CABLES AS LONG AS THE
FOLLOWING ARE MET: THE RUN IS CONCEALED, USED IN CONJUNCTION WITH
NON-METALLIC BOXES, AND RACEWAYS ONLY. PROVIDE J-HOOKS EVERY 5 FEET TO
SUPPORT THE CABLES. DO NOT LAY THE CABLES ON TOP OF EXISTING CEILING OR
ANYWHERE THAT CAN BE DAMAGED. IF METALLIC BOXES AND CONDUIT ARE TO BE USED
UTILIZE MC CABLE FOR ALL THE WIRING.
8. THE CONTRACTOR IS ALLOWED TO USE 1/2" EMT CONDUIT ON SURFACES IN LIEU OF
WIREMOLD. PAINT CONDUIT ON EXPOSED SURFACES. COLOR TO MATCH COLOR OF
GROUT OF EXISTING BRICKS.
9. ALL EXISTING ABANDONED FIRE ALARM CONDUIT, CABLES, J-BOXES, ETC. MUST BE
REMOVED AT THE END OF THE PROJECT.
10. THE CONTRACTOR IS TO PROVIDE A UNIT COST FOR NEW 2'X2' ACCESS PANEL IN
EXISTING CEILING.
11. THE CONTRACTOR IS TO SEAL AND PAINT ALL PENETRATIONS ON FINISHED WALLS AND
CEILINGS. PAINT COLOR IS TO MATCH THE WALL OR CEILING ACCORDINGLY.
12. ASBESTOS CONTAINING MATERIALS (ACM) MAY BE PRESENT AT THE PROJECT SITE. GSD
WILL ABATE ACM OR PROVIDE CONTRACTOR WITH A PROTOCOL FOR USE WHEN
DRILLING, CUTTING, OR FASTENING TO ACM.
13. REFER TO SPECS FOR APPROVED MANUFACTURES. MANUFACTURER'S MODEL
NUMBERS AND LISTING INFORMATION FOR EQUIPMENT WILL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR AND ALSO ON DEFERRED. SUBMITTALS.
SPECIAL NOTES:
SCALE:
N.T.S.
1/2" FLEX x 6' (MAX)
MAINTAIN CLASS A WIRING
LAY-IN TILE CEILING
3/4" CONDUIT FOR FIRE
ALARM LOOP
4" SQUARE x 2-1/8" J-BOX
AT CEILING DECK
3/4" CONDUIT FOR
FIRE ALARM LOOP
CONNECTIONS FOR FIRE ALARM
DEVICES IN LAY-IN CEILINGS
(3) HP-FF8
CONDUITS
& ONE 3/4"
TWO 1"
5.2" DEEP
24" WIDE
45.9" HIGH
3 PAIR #16'S TWISTED
TRANSPONDER
SBB-D4
w/FCI-DR-D4B
REMOTE
ANNUNCIATOR
E3-BB-BAA
4.5" DEEP
19.25" WIDE
10" HIGH
w/E3-ID2-A
DEDICATED CIRCUIT
120 VAC W/GROUND
1 CAT-6E TO PHONE BOARD
2 CAT-6E TO NETWORK PORTS
FACU
S3-BB-RB
4.5" DEEP
19.375" WIDE
19.375" HIGH
MINI
BATTERY
CABINET
4" DEEP
17" WIDE
8" HIGH
FLPS-7
SLC-PM
SLP-RB
DACT-E3
LCD-SLP
2 #14'S
TYPICAL 24 AUX POWER
1 PAIR #14'S TWISTED
TYPICAL ADDRESSABLE CIRCUIT
4 #14'S4 #14'S
TO FAN
SHUTDOWN
2 #14'S
TYPICAL NOTIFICATION CIRCUIT
2 #14'S
TYPICAL CO NOTIFICATION CIRCUIT
B B
WPB
E002
FIRE ALARM RISER
DIAGRAM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
JW AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
G R
A N
IT
E
T E
C H
N
IC
A L
S C
H O
O L
S
T O
R Y
B U
IL
D
IN
G
A N
D A
N N
E X
C A
R B
O N
M O
N O
X
ID
E U
P G
R A
D E
S
O U
T H
M A
IN
S
T R
E E
T
S A
L T
L A
K E
C
IT
Y
U T
A H
F.A.C.P.
F.A.C.P.EXISTING TRANSPONDER
EXISTING
REMOTE
ANNUNCIATOR
EXISTING
REMOTE
ANNUNCIATOR
REMOTE
ANNUNCIATOR
EXISTING
REMOTE
ANNUNCIATOR
EXISTING F.A.C.P.
1. FURNISH AND INSTALL A NEW CARBON MONOXIDE
DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE
THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS
"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO
NOT SPLICE CABLES BETWEEN DEVICES.
1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING
ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH
THIS WORK.
SCALE: 1/16" = 1'-0"
EY101
FIRST FLOOR
PLAN - FIRE
ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
JW AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
G R
A N
IT
E
T E
C H
N
IC
A L
S C
H O
O L
S
T O
R Y
B U
IL
D
IN
G
A N
D A
N N
E X
C A
R B
O N
M O
N O
X
ID
E U
P G
R A
D E
S
O U
T H
M A
IN
S
T R
E E
T
S A
L T
L A
K E
C
IT
Y
U T
A H
TRANSPONDER
1 1
1. FURNISH AND INSTALL A NEW CARBON MONOXIDE
DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE
THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS
"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO
NOT SPLICE CABLES BETWEEN DEVICES.
1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING
ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH
THIS WORK.
SCALE: 1/16" = 1'-0"
EY102
SECOND
FLOOR PLAN -
FIRE ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
JW AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
G R
A N
IT
E
T E
C H
N
IC
A L
S C
H O
O L
S
T O
R Y
B U
IL
D
IN
G
A N
D A
N N
E X
C A
R B
O N
M O
N O
X
ID
E U
P G
R A
D E
S
O U
T H
M A
IN
S
T R
E E
T
S A
L T
L A
K E
C
IT
Y
U T
A H
1. FURNISH AND INSTALL A NEW CARBON MONOXIDE
DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE
THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS
"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO
NOT SPLICE CABLES BETWEEN DEVICES.
1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING
ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH
THIS WORK.
SCALE: 1/16" = 1'-0"
EY103
THIRD FLOOR
PLAN - FIRE
ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
JW AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
G R
A N
IT
E
T E
C H
N
IC
A L
S C
H O
O L
S
T O
R Y
B U
IL
D
IN
G
A N
D A
N N
E X
C A
R B
O N
M O
N O
X
ID
E U
P G
R A
D E
S
O U
T H
M A
IN
S
T R
E E
T
S A
L T
L A
K E
C
IT
Y
U T
A H
1. FURNISH AND INSTALL A NEW CARBON MONOXIDE
DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE
THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS
"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO
NOT SPLICE CABLES BETWEEN DEVICES.
1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING
ALARM. PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH
THIS WORK.
SCALE: 1/16" = 1'-0"
EY104
FOURTH
FLOOR PLAN -
FIRE ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
JW AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
G R
A N
IT
E
T E
C H
N
IC
A L
S C
H O
O L
S
T O
R Y
B U
IL
D
IN
G
A N
D A
N N
E X
C A
R B
O N
M O
N O
X
ID
E U
P G
R A
D E
S
O U
T H
M A
IN
S
T R
E E
T
S A
L T
L A
K E
C
IT
Y
U T
A H
OFFICE OR
GOWNING
MOCK CLEAN LAB
UNISEX
SERVER
ROOM
OFFICE
DIRTY LAB
GENERAL LAB
VESTIBULE
STAIR
VETERINARY
STORAGE
VETERINARY
OFFICE
VETERINARY
LAB
VETERINARY
WASH
HEARING
CENTER
WOMEN'S
MEN'S
CUSTODIAL
STAIR
HALL
HALL
F.A.C.P.
TRANSPONDER
1. FURNISH AND INSTALL A NEW DEVICE IN THE APPROXIMATE
LOCATION SHOWN. TIE THE NEW DEVICE TO FIRE ALARM
CONTROL PANEL IN CLASS "A" LOOP. IN AND OUT CABLES
MUST RUN IN PLENUM. DO NOT SPLICE CABLES BETWEEN
DEVICES.
2. FURNISH AND INSTALL A NEW CONTROL MODULE IN THE
APPROXIMATE LOCATION SHOWN. TIE TO F.A.C.P. B IN CLASS
"A" LOOP.
3. FURNISH AND INSTALL A BLUE STROBE LIGHT FOR NEW "CO"
DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE TO
FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP FOR A
COMPLETE INSTALLATION.
4. FURNISH AND INSTALL AN ADDRESSABLE FIRE ALARM
CONTROL PANEL AND TRANSPONDER IN THE APPROXIMATE
LOCATION SHOWN, COORDINATE WITH GSD REPRESENTATIVE
FOR EXACT LOCATION. TIE THE NEW F.A.C.P. AND
TRANSPONDER TO A 20 AMP, 1-POLE RED CIRCUIT BREAKER
IN THE NEAREST PANEL. PROVIDE CONDUIT AND
CONDUCTORS FOR A COMPLETE INSTALLATION.
1. NEW CO DETECTORS ARE TO SHUT OFF FANS DURING ALARM.
PROVIDE REQUIRED PROGRAMMING TO ACCOMPLISH THIS WORK.
EY105
BASEMENT,
FIRST FLOOR
AND SECOND
FLOOR PLANS
- FIRE ALARM
SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0" CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
JW AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5747
G R
A N
IT
E
T E
C H
N
IC
A L
S C
H O
O L
S
T O
R Y
B U
IL
D
IN
G
A N
D A
N N
E X
C A
R B
O N
M O
N O
X
ID
E U
P G
R A
D E
S
O U
T H
M A
IN
S
T R
E E
T
S A
L T
L A
K E
C
IT
Y
U T
A H
File details come from the government source that posted it. Updated .