6-JF26-026-IFB 5762 Bennion JHS FA Upgrade ECE - Permit Set.pdf

PDF 3 MB Posted

Attached to
Construction: Fire Alarm Upgrade at Bennion Jr
Solicitation number
JF26-026-IFB
Issued by
Salt Lake County, Utah

About this file

File Summary

This is a permit set of architectural and engineering drawings for a Fire Alarm and Carbon Monoxide Detection System upgrade project at Bennion Junior High School, located at 6055 South 2700 West, West Jordan, Utah 84129, under Granite School District (GSD). The project involves the installation of a new fire alarm control panel, addressable fire alarm devices, combination smoke/carbon monoxide detectors, manual pull stations, horn and strobe notification appliances, duct detectors, beam detectors, a VESDA laser air sampling system in the cafeteria, and new transponders throughout the facility. The scope of work includes removal of existing fire alarm devices and associated conduit and conductors, tie-in of existing magnetic door holders and monitor modules for tamper and flow switches to the new fire alarm control panel, integration with existing EST fire alarm control panel, automatic fan shutdown capabilities during alarm conditions, and coordination with sprinkler system flow and tamper switches. The drawings detail specific device locations across two floors, mechanical rooms, and specialized areas such as the cafeteria and ductwork systems, with all new devices to be wired in Class "A" loop configuration using plenum-rated cables. The Invitation for Bids (IFB) seeks qualified, licensed General Electrical Contractors (E200) to complete the installation according to the project specifications and attached drawings, with a pre-bid meeting required and board approval anticipated at the June 2, 2026 meeting.

The project documents specify that plenum-rated cables must be used for all fire alarm device connections without splicing between devices, and all work must be coordinated with the fire alarm manufacturer representative and VESDA system provider for the air sampling installation. Device heights and mounting standards are clearly defined, including smoke/heat/flame detectors at 80 inches above finished floor, pull stations at 42 inches, and notification appliances at 96 inches. The project requires comprehensive firestopping for cables and conduits penetrating fire-rated walls, wireguard protection over devices, programming for automatic fan shutdown during CO alarm activation, and post-installation testing including transport time verification for the VESDA air sampling system. If the fire alarm system operates off-hours, a fire watch will be required. Engineering design services were provided by Electrical Consulting Engineers (ECE), with project number 5762 referenced throughout the documentation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GRANITE SCHOOL DISTRICT

6055 SOUTH 2700 WEST

WEST JORDAN, UTAH 84129

BENNION JUNIOR HIGH SCHOOL

E000

COVER SHEET

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

E000: COVER SHEET

E001: GENERAL NOTES, SYMBOLS LIST AND

DETAILS

E002: FIRE ALARM RISER DIAGRAM

E003: EXISTING CONDITIONS - PHOTOS

ED101: FIRST FLOOR DEMOLITION PLAN -

FIRE ALARM

ED102: SECOND FLOOR DEMOLITION PLAN -

FIRE ALARM

ED401: ENLARGED DEMOLITION FLOOR

PLANS - FIRE ALARM

ED402: ENLARGED DEMOLITION FLOOR

PLANS - FIRE ALARM

EY101: FIRST FLOOR PLAN - FIRE ALARM

EY102: SECOND FLOOR PLAN - FIRE ALARM

EY103: CAFETERIA - VESDA

EY401: ENLARGED FLOOR PLANS - FIRE

ALARM

EY402: ENLARGED FLOOR PLANS - FIRE

ALARM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

FIRE ALARM & CARBON MONOXIDE UPGRADE

E001

GENERAL NOTES,

SYMBOLS LIST

AND DETAILS

GENERAL NOTES:

SPECIAL NOTES:

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

TYPICAL WIRING FOR EACH SPRINKLER RISER (SEE FIRE SPRINKLER

DRAWINGS FOR QUANTITY AND LOCATIONS.)

MAIN

OS&Y VALVE

DETECTOR SWITCH FURNISHED AND

INSTALLED BY SPRINKLER

4 #14, 1/2''CONDUIT

ALARM VALVE

SEAL TIGHT

4 #14, 1/2''CONDUIT

WALL MOUNTED JUNCTION BOX

FLOW SWITCH FURNISHED AND INSTALLED BY

SPRINKLER CONTRACTOR, WIRED BY ELEC.

RISER

CONDUIT 8 #14 THW, 3/4''CONDUIT

TO FIRE ALARM MASTER TYPICAL

EACH SPRINKLER RISER.

CEILING

SCALE:

FIRE SPRINKLER CONNECTION DETAIL

N.T.S.

CONTRACTOR, WIRED BY ELEC.

ANCHOR TO WALL WITH

EPOXY ANCHORS AS

REQUIRED BY WEIGHT

SUPPORTED (TYPICAL)

SCALE: STANDARD HEIGHTS FOR

N.T.S.

M

A X

M

IN

IM

U

M

ELECTRICAL

OUTLETS

PULL

FIRE

CEILING

DECK

STROBE LIGHT

OR HORN &

STROBE

SMOKE, HEAT,

& FLAME

DETECTORS

LIGHT SWITCHES

FIRE ALARM PULL STATION

M

A X

PUSH BUTTONS

BEAM

STRUCTURAL

JOIST OR

DROPPED

CEILING

STANDARD HEIGHTS

FOR AREAS WITH

CEILING DECK OR

DROPPED CEILINGS

SURFACE MOUNT CONDUITS ON CEILING.

DO NOT PENDANT MOUNT CONDUITS

EXCEPT AT ROOF DECK MAINTAIN 1-1/2"

SEPARATION BETWEEN DECK &

HANDICAPPED ACCESS

CONDUITS.

THROUGH CONCRETE WALLS

MAY 09, 2013

F RATING - 2 HR

T RATING - 0 HR

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ. FT.

L RATING AT 400 F - LESS THAN 1 CFM/SQ. FT.

SECTION A-A

WALL ASSEMBLY

A

A

SCALE: TYPICAL FIRESTOP FOR CABLES/CONDUIT

N.T.S.

FIRE ALARM SYSTEMS SYMBOL LIST

SYMBOL DESCRIPTION

ELECTRICAL PANEL LOCATION, PART #: FACU: E3-BB-BB, NAC: SBB-D4, REMOTE

ANNUNCIATOR: E3-BB-BAA

FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, PART #: ASD-PL3

FIRE ALARM HEAT DETECTOR, PART #: ATD-L3R

FIRE ALARM COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, PART #:

CO1224TR

FIRE ALARM MANUAL PULL STATION, +42" A.F.F., PART #: MS-7AF

FIRE ALARM HORN WITH STROBE, HIGH DECIBEL, +96" A.F.F., PART #: WALL: P2WL,

CEILING: PC2WL, WEATHER PROOF: P2RK

A.D.A. STROBE FOR FIRE ALARM, +96" A.F.F., PART #: WALL: SWL, CEILING: SCWL

BLUE STROBE LIGHT

FIRE SPRINKLER FLOW SWITCH, PART #: AMM-4F

FIRE SPRINKLER TEMPER SWITCH, PART #: AMM-4F

BEAM DETECTOR TRANSMITTER - LETTER INDICATES PAIRING

BEAM DETECTOR RECEIVER - LETTER INDICATES PAIRING

BEAM CONTROLLER

RELAY MODULE, PART #: PR-3

KITCHEN HOOD MONITOR

CONTROL MODULE

CONTROL MODULE WITH RELAY

B

CM

R

CALLOUT SYMBOL LIST

SYMBOL DESCRIPTION

LIGHTING FIXTURE CALLOUT NUMBER INDICATES A SUGGESTED QUANTITY- TO BE

VERIFIED

MECHANICAL EQUIPMENT CALLOUT

DETAIL REFERENCE CALLOUT

REVISION NUMBER CALLOUT

EQUIPMENT CALLOUT

REFERENCE NOTE CALLOUT

ABBREVIATIONS SYMBOL LIST

SYMBOL DESCRIPTION

W.P. INDICATES WEATHER PROOF EQUIPMENT

A INDICATES DEVICE IS ABOVE COUNTER TOP

AMP. AMPERAGE

A.F.F. ABOVE FINISHED FLOOR

B.CO BLUE CARBON MONOXIDE STROBE

CLG. INDICATES CEILING MOUNTED DEVICE

EM INDICATES DEVICE IS ON EMERGENCY CIRCUIT

EX INDICATES DEVICE IS EXISTING

F.A.C.P. FIRE ALARM CONTROL PANEL

F.A.R.A.P. FIRE ALARM REMOTE ANNUNCIATOR PANEL

K.V.A. KILO VOLT AMPERAGE

K.W. KILOWATT

M.C.B. MAIN CIRCUIT BREAKER

M.L.O. MAIN LUG ONLY

O.T.R. ON THE ROOF

S INDICATES DEVICE IS SURFACE MOUNTED

T.V.S.S. TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP TYPICAL

U.P.S. UNINTERRUPTIBLE POWER SUPPLY

XFMR TRANSFORMER

SCALE:

N.T.S.

1/2" FLEX x 6' (MAX)

MAINTAIN CLASS A WIRING

LAY-IN TILE CEILING

3/4" CONDUIT FOR FIRE

ALARM LOOP

4" SQUARE x 2-1/8" J-BOX

AT CEILING DECK

3/4" CONDUIT FOR

FIRE ALARM LOOP

CONNECTIONS FOR FIRE ALARM

DEVICES IN LAY-IN CEILINGS

EXISTING EST PANEL

CONDUITS

& ONE 3/4"

TWO 1"

TRANSPONDER

DEDICATED CIRCUIT

120 VAC W/GROUND

1 CAT-6E TO PHONE BOARD

2 CAT-6E TO NETWORK PORTS

FACU

MINI

BATTERY

CABINET

2 #14'S

TYPICAL 24 AUX POWER

1 PAIR #14'S TWISTED

TYPICAL ADDRESSABLE CIRCUIT

4 #14'S4 #14'S

TO FAN

SHUTDOWN

2 #14'S

TYPICAL NOTIFICATION CIRCUIT

2 #14'S

TYPICAL CO NOTIFICATION CIRCUIT

B WP

E002

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

TYPICAL FIRE

ALARM RISER

DIAGRAM

SPECIAL NOTES:

E003

EXISTING

CONDITIONS -

PHOTOS

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

E0033

E003

DUCT DETECTOR IN FAN

ROOM OFF OF SCIENCE 202

(1 OF 2)

E003

DUCT DETECTOR IN FAN ROOM

ABOVE BOY'S RESTROOM

(1 OF 3)

E003

DUCT DETECTOR IN FAN ROOM

ABOVE THEATER (1 OF 8)

E003

E003 6

E003

DUCT DETECTORS IN MECH.

ROOM ON 2ND FLOOR (2 OF 4)

DUCT DETECTOR IN FAN

ROOM ABOVE STE 121 (1 OF 4)

DUCT DETECTOR IN

MECHANICAL ROOM ABOVE

BOILER ROOM (1 OF 2)

FIRE ALARM CONTROL PANEL

IN OFFICE

FIRST FLOOR

COMP LAB

COMP LAB

UT. STUDY

READ

ISS

CONF

ROOM

S T

O R

A G

E

PRINCIPAL CONF

ROOM

OFFICE

FAC ROOM

COUN

COUN

COUN

SEC

ASST

PRIN

OFFICE

GIRLS

LOCKER

RM

GYMNASIUM

BOYS

LOCKER

RM

OFFICE

PE

STORAGE

RM

GIRLS PE

STORAGE

RM

SEWING

HEALTH

FOOD

STORAGE

STORAGE

SHOP

STE

DRAMA

CAFETERIA

CHORUS

GEOGRAPHY

HISTORY

RESOURCE

STORAGE

RESOURCE

RESOURCE

9 ENG 109

8 ENG 110

9TH ENG

8TH ENG

MATH

AUDITORIUM

STAGE

BAND/ORCHESTRA

ART

ART

WEIGHT TRAINING

RESOURCE

STE COM

LAB 127

STORAGE

F.A.C.P.

E003

ED401

MEN

WOMEN

BOILER

ROOM

LIBRARY

WOMEN

MEN

WP

E003

1. REMOVE EXISTING FIRE ALARM DEVICES, ASSOCIATED

CONDUIT AND CONDUCTORS. PROVIDE A BLANK

COVER PLATE FOR J-BOXES IN THE BRICK WALLS.

COVER PLATE TO MATCH COLOR OF THE BRICK.

2. TIE EXISTING MAGNETIC DOOR HOLDER TO NEW FIRE

ALARM CONTROL PANEL FOR AUTOMATIC RELEASE

DURING FIRE ALARM. PROVIDE CONDUIT AND

CONDUCTORS FOR A COMPLETE INSTALLATION.

3. REMOVE EXISTING FIRE ALARM ANNUNCIATOR PANEL

ASSOCIATED CONDUCTORS AND CONDUIT. PROVIDE A

BLANK COVER PLATE FOR THE BOX AND PAINT TO

MATCH COLOR OF WALL.

4. REMOVE EXISTING MONITOR MODULES FOR THE

TEMPER AND FLOW SWITCHES AND REPLACE WITH

NEW ADDRESSABLE MONITOR MODULE.

5. EXISTING EST FIRE ALARM CONTROL PANEL IS TO

REMAIN WITH ASSOCIATED POWER SUPPLY, CONDUIT,

CONDUCTORS, BOXES, ETC.

SCALE: 1/16" = 1'-0"

ED101

FIRST FLOOR

DEMOLITION

PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com

OPEN TO BELOW

OPEN TO BELOW

SCIENCE

SCIENCE

SCIENCE

SKILL 4 SUC

MATH

MATH

MATH/HISTORY

MATH

MATH 7

CHINESE

7 READ

WOMEN

MEN

COM LAB

SCIENCE

SCIENCE

TP

COMPUTER LAB -

LIBRARY LOFT

BUSINESS

WOMEN

MEN

COM LAB

COM LAB

GEOGRAPHY

MECH.

MECHANICAL

ZONE 6

ED401

ED401

ED401

ED402

E003

E003

E003

E003

ED401

E003

1. REMOVE EXISTING FIRE ALARM DEVICES, ASSOCIATED

CONDUIT AND CONDUCTORS. PROVIDE A BLANK

COVER PLATE FOR J-BOXES IN THE BRICK WALLS.

COVER PLATE TO MATCH COLOR OF THE BRICK.

SCALE: 1/16" = 1'-0"

ED102

SECOND

FLOOR

DEMOLITION

PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007

1. REMOVE EXISTING DUCT DETECTOR AND SAMPLING

TUBE IN RETURN AND SUPPLY DUCTS. REMOVE

ASSOCIATED CONDUIT, J-BOXES, ETC. NEW DUCT

DETECTOR WILL ONLY BE INSTALLED IN RETURN DUCT.

2. REMOVE EXISTING MONITOR MODULES FOR THE

TAMPER AND FLOW SWITCHES AND REPLACE WITH

NEW MONITOR MODULE. FIELD VERIFY EXACT

NUMBERS.

ZONE 5

ZONE 5

ZONE 5

SCALE: 1/2" = 1'-0"

ED401

ENLARGED

DEMOLITION

FLOOR PLANS

- FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

SCALE: 1/2" = 1'-0"

SCALE: 1/2" = 1'-0"

SCALE: 1/2" = 1'-0"

SCALE: 1/2" = 1'-0"

ED401

ED401

ED401

ED401

ED401

ASSOCIATED CONDUIT, J-BOXES, ETC. NEW DUCT

DETECTOR WILL ONLY BE INSTALLED IN RETURN DUCT.

ED402

ENLARGED

DEMOLITION

FLOOR PLANS

- FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

SCALE: 1/2" = 1'-0"

ED402

B.CO

FIRST FLOOR

COMP LAB

COMP LAB

UT. STUDY

READ

ISS

CONF

ROOM

S T

O R

A G

E

PRINCIPAL

CONF

ROOM

OFFICE

FAC ROOM

COUN

COUN

COUN

SEC

ASST

PRIN

OFFICEGIRLS

LOCKER

RM

GYMNASIUM

BOYS

LOCKER

RM

OFFICE

PE

STORAGE

RM

GIRLS PE

STORAGE

RM

SEWING

HEALTH

FOOD

STORAGE

STORAGE

SHOP

STE

DRAMA

CAFETERIA

CHORUS

GEOGRAPHY

HISTORY

RESOURCE

STORAGE

RESOURCE

RESOURCE

9 ENG 109

8 ENG 110

9TH ENG

8TH ENG

MATH

AUDITORIUM

STAGE

BAND/ORCHESTRA

ART

ART

WEIGHT TRAINING

RESOURCE

STE COM

LAB 127

STORAGE

ZONE 1

ZONE 1

ZONE 2

ZONE 3

ZONE 2

ZONE 2

ZONE 4

F.A.C.P.

MEN

WOMEN

BOILER

ROOM

LIBRARY

WOMEN

MEN

EY401

WP

WP

WP

WP

WP

WP

B

H

NEW

TRANSPONDER

B

1. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE

APPROXIMATE LOCATION SHOWN. TIE THE NEW DEVICES TO

FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP. IN AND

OUT CABLES MUST BE PLENUM. DO NOT SPLICE CABLES

BETWEEN DEVICES. COORDINATE THIS WORK WITH FIRE

ALARM MANUFACTURER REPRESENTATIVE.

2. TIE EXISTING MAGNETIC DOOR HOLDERS TO NEW FIRE

ALARM CONTROL PANEL. PROVIDE CONTROL MODULE,

CONDUCTORS, ETC. FOR A COMPLETE INSTALLATION.

3. PROVIDE NEW MONITOR MODULE FOR EXISTING TAMPER

AND FLOW SWITCHES. TIE TO FIRE ALARM CONTROL PANEL

IN CLASS "A" LOOP.

4. FURNISH AND INSTALL NEW FIRE ALARM TRANSPONDER IN

THE APPROXIMATE LOCATION SHOWN. TIE THE

TRANSPONDER TO A NEW RED 20A., 1-POLE CIRCUIT

BREAKER IN EMERGENCY ELECTRICAL PANEL. PROVIDE

CONDUIT, CONDUCTORS, ETC. FOR A COMPLETE

INSTALLATION. REFER TO FA RISER DIAGRAM FOR MORE

INFORMATION.

5. EXISTING EST FIRE ALARM CONTROL PANEL. TIE THE FIRE

ALARM CONTROL PANEL TO THE TRANSPONDER. PROVIDE

CONDUIT, CONDUCTORS, CIRCUIT BREAKER, ETC. FOR A

COMPLETE INSTALLATION. REFER TO FIRE ALARM RISER

DIAGRAM FOR MORE INFORMATION.

6. TIE FIRE ALARM CONTROL PANEL / TRANSPONDER TO A NEW

20 AMP., 1 POLE RED CIRCUIT BREAKER IN EXISTING

EMERGENCY PANEL IN THE BOILER ROOM. PROVIDE

CONDUIT AND CONDUCTORS FOR A COMPLETE

INSTALLATION.

7. FURNISH AND INSTALL A BLUE STROBE LIGHT FOR CO

NOTIFICATION ON THE CEILING IN THE APPROXIMATE

LOCATION SHOWN. TIE TO FIRE ALARM CONTROL PANEL IN

CLASS "A" LOOP FOR A COMPLETE INSTALLATION.

8. PROVIDE WIREGUARD PROTECTION OVER DEVICES.

9. PROVIDE THREE CONTROL MODULES FOR ELEVATOR

RECALL. COORDINATE WITH ELEVATOR MANUFACTURER FOR

TERMINATION POINTS. TIE TO F.A.C.P. FOR A COMPLETE

INSTALLATION.

10. FURNISH AND INSTALL A BLUE STROBE LIGHT FOR NEW "CO"

DETECTORS IN THE APPROXIMATE LOCATION SHOWN. BLUE

LIGHT TO COME ON WHEN ONE OF THE CO DETECTORS IS ON

ALARM. TIE TO THE NEW FIRE ALARM CONTROL PANEL IN

CLASS "A" LOOP FOR A COMPLETE INSTALLATION.

11. FURNISH AND INSTALL NEW CONTROL MODULE IN THE

APPROXIMATE LOCATION SHOWN FOR THE CO BLUE LIGHT

STROBE. TIE TO FIRE ALARM CONTROL PANEL IN A CLASS "A"

LOOP.

FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN

THE APPROXIMATE LOCATION SHOWN. TIE THE NEW

DEVICES TO FIRE ALARM CONTROL PANEL IN CLASS

"A" LOOP. IN AND OUT CABLES MUST BE PLENUM. DO

NOT SPLICE CABLES BETWEEN DEVICES.

COORDINATE THIS WORK WITH FIRE ALARM

MANUFACTURER REPRESENTATIVE.

TIE AIR FANS TO NEW F.A.C.P. FOR AUTOMATIC SHUT

DOWN. PROVIDE ALL REQUIRED PROGRAMMING FOR

PROPER FAN SHUT DOWN DURING ALARM.

CO DETECTORS ARE TO SHUT DOWN PROPER AIR

FANS DURING ALARM. PROVIDE ALL REQUIRED

PROGRAMING FOR PROPER FAN SHUT DOWN DURING

ALARM.

IF THE FIRE ALARM SYSTEM IS TO BE OFF AFTER

HOURS A FIRE WATCH WILL BE REQUIRED.

1.

2.

3.

4.

SCALE: 1/16" = 1'-0"

EY101

FIRST FLOOR

PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007

SCIENCE

SCIENCE

SCIENCE

205SKILL 4 SUC

MATH

MATH

MATH/HISTORY

MATH

MATH 7

CHINESE

7 READ

WOMEN

MEN

COM LAB

SCIENCE

SCIENCE

202TP

COMPUTER LAB -

LIBRARY LOFT

BUSINESS

WOMEN

MEN

COM LAB

COM LAB

GEOGRAPHY

MECH.

MECHANICAL

OPEN TO BELOW

OPEN TO BELOW

OPEN TO BELOW

EY401

EY401

EY401

EY402

EY401

H

1. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE

APPROXIMATE LOCATION SHOWN. TIE THE NEW DEVICES TO

FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP. IN AND

OUT CABLES MUST BE PLENUM. DO NOT SPLICE CABLES

BETWEEN DEVICES. COORDINATE THIS WORD WITH FIRE

ALARM MANUFACTURE REPRESENTATIVE.

SCALE: 1/16" = 1'-0"

EY102

SECOND

FLOOR PLAN -

FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007

CAFETERIA

SCIENCE

COMPUTER LAB -

LIBRARY LOFT

COM LAB

SCIENCE

TP

AUDITORIUM

1. FURNISH AND INSTALL NEW V.E.S.D.A. LASER PLUS 4 PORT AIR

SAMPLING DEVICE IN THE APPROXIMATE LOCATION SHOWN.

TIE THE ALARM OUTPUTS (PRE-ALERT, ALERT, ALARM AND

TROUBLE) TO THE FIRE ALARM PANEL. TIE THE VESDA UNIT TO

A NEW RED 20A, 120V. CIRCUIT BREAKER IN THE NEAREST

PANEL WITH AVAILABLE SPACE. PROVIDE CONDUIT,

CONDUCTORS, CIRCUIT BREAKER, BATTERIES, ETC. FOR A

COMPLETE INSTALLATION.

2. FURNISH AND INSTALL NEW VESDA LASER PLUS AIR

SAMPLING TUBES IN THE APPROXIMATE LOCATIONS SHOWN.

REFER TO THE VESDA SAMPLING PORT DETAIL FOR MORE

INFORMATION. AIR SAMPLING ZONES SHALL COVER LESS

THAN 33 PORTS PER DETECTION UNIT. AIR SAMPLING SYSTEM

MUST BE ENGINEERED, INSTALLED AND CERTIFIED BY VESDA

SYSTEM PROVIDER. PROVIDE TEST PORT AT 4FT A.F.F. AT THE

END OF EACH PIPE RUN TO TEST TRANSPORT TIME . TEST

PORT SHALL BE A VENTED END-CAP. PROVIDE SIGN

INDICATING "TEST PORT". TRANSPORT TIME SHALL BE LESS

THAN 60 SECONDS FOR EQUIPMENT SPACE.

SCALE: 1/8" = 1'-0"

1. DETECTOR LOCATIONS ARE SHOWN TO INDICATE

APPROXIMATE DEVICES COVERAGE LIMITS. FIELD VERIFY

EXACT LOCATIONS TO INSURE THAT DETECTORS ARE

ACCESSIBLE FROM THE FLOOR AND THAT THEY ARE NOT

INSTALLED WITH 4'-0" OF AN AIR DISCHARGE LOUVER.

EY103

CAFETERIA -

VESDA

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007

1. TIE EXISTING FAN UNIT TO FIRE ALARM CONTROL PANEL FOR

AUTOMATIC SHUTDOWN. PROVIDE CONDUIT, CONDUCTORS,

RELAYS, ETC. FOR A COMPLETE INSTALLATION.

2. FURNISH AND INSTALL A DUCT DETECTOR IN RETURN AIR

DUCT WITH SAMPLING TUBE FOR EXISTING FAN UNIT. TIE

THE DUCT DETECTOR IN CLASS "A" LOOP TO FIRE ALARM

CONTROL PANEL. PROVIDE CONDUIT AND CONDUCTORS

FOR A COMPLETE INSTALLATION.

3. PROVIDE NEW MONITOR MODULE FOR EXISTING TAMPER

AND FLOW SWITCHES. TIE TO FIRE ALARM CONTROL PANEL

IN CLASS "A" LOOP.

4. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE

APPROXIMATE LOCATION SHOWN. TIE THE NEW DEVICES TO

FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP. IN AND

OUT CABLES MUST BE PLENUM. DO NOT SPLICE CABLES

BETWEEN DEVICES. COORDINATE THIS WORD WITH FIRE

ALARM MANUFACTURE REPRESENTATIVE.

5. TIE VESDA CONTROL PANEL TO A NEW 20 AMP, 1 POLE RED

CIRCUIT BREAKER IN NEAREST ELECTRICAL PANEL. PROVIDE

CONDUIT AND CONDUCTORS FOR A COMPLETE

INSTALLATION. TIE VESA CONTROL PANEL TO EXISTING FIRE

ALARM CONTROL PANEL.

6. FURNISH AND INSTALL NEW TRANSPONDERS IN THE

APPROXIMATE LOCATION SHOWN. FIELD VERIFY EXACT

LOCATION WITH GSD. TIE THE TRANSPONDER TO FIRE ALARM

CONTROL PANEL FOR A COMPLETE INSTALLATION.

7. TIE THE TRANSPONDER TO A 20 AMP, 1 POLE RED CIRCUIT

BREAKER IN NEAREST PANEL. PROVIDE CONDUIT AND

CONDUCTORS FOR A COMPLETE INSTALLATION.

NEW

TRANSPONDER

NEW

TRANSPONDER

VESDA

CONTROL

PANEL

NEW

TRANSPONDER

SCALE: 1/2" = 1'-0"

EY401

ENLARGED

FLOOR PLANS

- FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762

SCALE: 1/2" = 1'-0"

SCALE: 1/2" = 1'-0"

SCALE: 1/2" = 1'-0"

ASSOCIATED CONDUIT, J-BOXES, ETC. NEW DUCT

DETECTOR WILL ONLY BE INSTALLED IN RETURN DUCT

2. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN

THE APPROXIMATE LOCATION SHOWN. TIE THE NEW

DEVICES TO FIRE ALARM CONTROL PANEL IN CLASS "A"

LOOP. IN AND OUT CABLES MUST BE PLENUM. DO NOT

SPLICE CABLES BETWEEN DEVICES. COORDINATE THIS

WORD WITH FIRE ALARM MANUFACTURE

REPRESENTATIVE.

EY402

ENLARGED

FLOOR PLANS

- FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

LD AM

B E

N N

IO

N

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

U P

G R

A D

E

S

O U

T H

W E

S T

W E

S T

J O

R D

A N

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com