6-3-CS27011-27329900-Hazmat Survey-All Locations.pdf

PDF 4 MB Posted

Attached to
DFCM Construction - VBS Consultant Services - Design Services - Department of Transportation - Multiple Pump House Replacements and Repairs - Project #27329900
Solicitation number
CS27011
Issued by
Utah

About this file

This is a Hazardous Materials Survey document prepared for the State of Utah's Division of Facilities Construction and Management (DFCM) in connection with Project #27329900, which involves the replacement and repair of five pump houses to meet Utah Department of Transportation (UDOT) operational needs. The survey encompasses all project locations and serves as a supporting document for the design services request for proposal. The hazmat survey is a prerequisite assessment required to identify and document any hazardous materials present at the pump house sites prior to construction activities. This environmental assessment is critical for ensuring compliance with applicable regulations and establishing baseline conditions for the renovation and replacement work.

The hazmat survey findings will inform the design and construction phases of the project, which has an overall construction budget of $3,242,656.00. The survey results are essential for the qualified firms and individuals responding to the VBS Consultant Services design services solicitation to develop appropriate remediation plans, material handling procedures, and safety protocols. The identification of hazardous materials at all project locations will impact project scheduling, cost estimates, and the scope of work required from design consultants and construction contractors throughout the pump house replacement and repair initiative.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Lead Based Paint (LBP) Report Department of Facilities Construction and Management

78oo South Midvale Shed

July 7, 2026

LBP Inspector

Scott Bainbridge

PB-2648

Air Quality Consulting LLC

PBF-756

Scope of Work

Summary of Findings

We were hired by DFCM to smaple for suspect LBP for a potential demolition. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.

There were no painted finishes that contained lead on the structure or the attached equipment.

Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.

Bold

Paint Samples

Description Sample Location Amount Substrate XRF Results

Homogeneous Area Condition

= Some lead content

LBP per HUD guidelines, >1.0 mg/cm²

Blue Pump Base 20 SF Metal 0.0 Pump Base Good

Light Gray Panel 6 SF Metal 0.0 Panels Good

Gray Pump 8 SF Metal 0.0 Pumps Good

Door Paint Door 44 SF Metal 0.0 Door Good

Door Paint Door Frame 8 SF Metal 0.0 Door Good

Cream Exterior Panel 6 SF Metal 0.0 Exterior Panels Good

8000 South Pump House

July 7, 2026

LBP Inspector

Scott Bainbridge

PB-2648

We were hired by DFCM to sample for LBP for a pending renovation and equipment replacement. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.

There in no lead in all painted finishes on the structure or equipment attached to the structure.

Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.

Bold

Paint Samples Description Sample Location Amount Substrate XRF Results Homogeneous Area Condition

= Some lead content

LBP per HUD guidelines, >1.0 mg/cm²

Gray South Wall 180 SF Concrete 0.0 Interior Walls Good

Gray East Wall 180 SF Concrete 0.0 Interior Walls Good

Gray North Wall 180 SF Concrete 0.0 Interior Walls Good

Light Gray Panel 8 SF Metal 0.0 Panels Good

Black Fan Housing 24 SF Metal 0.0 Generator Platform & Fan Good

Dark Gray North Roll-up Door 100 SF Metal 0.0 Doors Good

Gray West Wall 180 SF Concrete 0.0 Interior Walls Good

Exterior Gray North Exterior 180 SF Concrete 0.0 Exterior Walls Good

Exterior Gray East Exterior 180 SF Concrete 0.0 Exterior Walls Good

Exterior Gray South Exterior 180 SF Concrete 0.0 Exterior Walls Good

Exterior Gray West Exterior 180 SF Concrete 0.0 Exterior Walls Good

Dark Gray North Double Door Frame 12 SF Metal 0.0 Doors Good

Dark Gray North Double Doors 72 SF Metal 0.0 Doors Good

Black Generator Platform 40 SF Metal 0.0 Generator Platform & Fan Good

Cream Generator 65 SF Metal 0.0 Generator Good

3300 South Salt Lake Pump Shed

July 7, 2026

LBP Inspector

Scott Bainbridge

PB-2648

We were hired by DFCM to sample for LBP for a pending demolition of the structure and equipment attached to the structure.. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.

There was no lead found in the painted coatings on the structure and equipment attached to the structure.

Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.

Bold

Paint Samples

Description Sample Location Amount Substrate XRF Results

Homogeneous Area Condition

= Some lead content

LBP per HUD guidelines, >1.0 mg/cm²

South Exterior 160 SF Metal 0.0 Exterior Good

East Exterior 160 SF Metal 0.0 Exterior Good

North Exterior 160 SF Metal 0.0 Exterior Good

West Exterior 160 SF Metal 0.0 Exterior Good

Pump 20 SF Metal 0.0 Pump Good

Panel 8 SF Metal 0.0 Tan Panel Good

Gray Panel 8 SF Metal 0.0 Gray Panel Good

Dark Gray Door 44 SF Metal 0.0 Door Good

Dark Gray Door Frame 14 SF Metal 0.0 Door Good

Green Green Green Green Blue Tan

500 East Morgan Pump Shed

July 7, 2026

LBP Inspector

Scott Bainbridge

PB-2648

We were hired by DFCM to sample for LBP in the painted surfaces on the structure and attached equipment for a pending demolition. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.

LBP was found in the orange red paint on the Exterior Metal Hatches and the Exterior Railing.

Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.

Bold

Paint Samples

Description Sample Location Amount Substrate XRF Results Homogeneous Area Condition

Red Exterior Hatch 30 SF Metal 3.3 Good Red Railing Handrail 16 SF Metal 5.3 Handrails Good

Exterior Hatches

= Some lead content

LBP per HUD guidelines, >1.0 mg/cm²

Blue Left Pump Base 8 SF Metal 0.0 Left Pump Base Good

Green Right Pump Base 8 SF Metal 0.0 Right Pump Base Good

Dark Gray Pump 6 SF Metal 0.0 Pump Good

Dark Gray Pump 6 SF Metal 0.0 Pump Good

Dark Gray Pump 6 SF Metal 0.0 Pump Good

Dark Gray Pump 6 SF Metal 0.0 Pump Good

Gray Panel 8 SF Metal 0.0 Panels Good

Exterior Gray Exterior Panel 8 SF Metal 0.0 Exterior Panels Good

Door Gray Door 44 SF Metal 0.0 Door Good

Door Gray Door frame 14 SF Metal 0.0 Door Good

State Street Morgan Pump Shed

July 7, 2026

LBP Inspector

Scott Bainbridge

PB-2648

We were hired by DFCM to sample for LBP in the structure and attached equipment for a pending demolition. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.

LBP was found in the orange red paint on the Exterior Hatches and Exterior Handrail attached to the structure.

Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.

Bold

Paint Samples

Description Sample Location Amount Substrate XRF Results

Homogeneous Area Condition

Red Exterior Hatch 36 SF Metal 2.4 Exterior Hatches Dark Red Handrail 18 SF Metal 2.5 Handrails

= Some lead content

LBP per HUD guidelines, >1.0 mg/cm²

Gray Panel 6 SF Metal 0 Panels

Light Gray Pump 6 SF Metal 0 Pumps

Black Pump Base 8 SF Metal 0 Pump Bases

Light Gray Pump 6 SF Metal 0 Pumps

Black Pump Base 8 SF Metal 0 Pump Bases