6-3-CS27011-27329900-Hazmat Survey-All Locations.pdf
PDF 4 MB Posted
- Solicitation number
- CS27011
- Issued by
- Utah
About this file
This is a Hazardous Materials Survey document prepared for the State of Utah's Division of Facilities Construction and Management (DFCM) in connection with Project #27329900, which involves the replacement and repair of five pump houses to meet Utah Department of Transportation (UDOT) operational needs. The survey encompasses all project locations and serves as a supporting document for the design services request for proposal. The hazmat survey is a prerequisite assessment required to identify and document any hazardous materials present at the pump house sites prior to construction activities. This environmental assessment is critical for ensuring compliance with applicable regulations and establishing baseline conditions for the renovation and replacement work.
The hazmat survey findings will inform the design and construction phases of the project, which has an overall construction budget of $3,242,656.00. The survey results are essential for the qualified firms and individuals responding to the VBS Consultant Services design services solicitation to develop appropriate remediation plans, material handling procedures, and safety protocols. The identification of hazardous materials at all project locations will impact project scheduling, cost estimates, and the scope of work required from design consultants and construction contractors throughout the pump house replacement and repair initiative.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lead Based Paint (LBP) Report Department of Facilities Construction and Management
78oo South Midvale Shed
July 7, 2026
LBP Inspector
Scott Bainbridge
PB-2648
Air Quality Consulting LLC
PBF-756
Scope of Work
Summary of Findings
We were hired by DFCM to smaple for suspect LBP for a potential demolition. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.
There were no painted finishes that contained lead on the structure or the attached equipment.
Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.
Bold
Paint Samples
Description Sample Location Amount Substrate XRF Results
Homogeneous Area Condition
= Some lead content
LBP per HUD guidelines, >1.0 mg/cm²
Blue Pump Base 20 SF Metal 0.0 Pump Base Good
Light Gray Panel 6 SF Metal 0.0 Panels Good
Gray Pump 8 SF Metal 0.0 Pumps Good
Door Paint Door 44 SF Metal 0.0 Door Good
Door Paint Door Frame 8 SF Metal 0.0 Door Good
Cream Exterior Panel 6 SF Metal 0.0 Exterior Panels Good
8000 South Pump House
July 7, 2026
LBP Inspector
Scott Bainbridge
PB-2648
We were hired by DFCM to sample for LBP for a pending renovation and equipment replacement. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.
There in no lead in all painted finishes on the structure or equipment attached to the structure.
Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.
Bold
Paint Samples Description Sample Location Amount Substrate XRF Results Homogeneous Area Condition
= Some lead content
LBP per HUD guidelines, >1.0 mg/cm²
Gray South Wall 180 SF Concrete 0.0 Interior Walls Good
Gray East Wall 180 SF Concrete 0.0 Interior Walls Good
Gray North Wall 180 SF Concrete 0.0 Interior Walls Good
Light Gray Panel 8 SF Metal 0.0 Panels Good
Black Fan Housing 24 SF Metal 0.0 Generator Platform & Fan Good
Dark Gray North Roll-up Door 100 SF Metal 0.0 Doors Good
Gray West Wall 180 SF Concrete 0.0 Interior Walls Good
Exterior Gray North Exterior 180 SF Concrete 0.0 Exterior Walls Good
Exterior Gray East Exterior 180 SF Concrete 0.0 Exterior Walls Good
Exterior Gray South Exterior 180 SF Concrete 0.0 Exterior Walls Good
Exterior Gray West Exterior 180 SF Concrete 0.0 Exterior Walls Good
Dark Gray North Double Door Frame 12 SF Metal 0.0 Doors Good
Dark Gray North Double Doors 72 SF Metal 0.0 Doors Good
Black Generator Platform 40 SF Metal 0.0 Generator Platform & Fan Good
Cream Generator 65 SF Metal 0.0 Generator Good
3300 South Salt Lake Pump Shed
July 7, 2026
LBP Inspector
Scott Bainbridge
PB-2648
We were hired by DFCM to sample for LBP for a pending demolition of the structure and equipment attached to the structure.. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.
There was no lead found in the painted coatings on the structure and equipment attached to the structure.
Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.
Bold
Paint Samples
Description Sample Location Amount Substrate XRF Results
Homogeneous Area Condition
= Some lead content
LBP per HUD guidelines, >1.0 mg/cm²
South Exterior 160 SF Metal 0.0 Exterior Good
East Exterior 160 SF Metal 0.0 Exterior Good
North Exterior 160 SF Metal 0.0 Exterior Good
West Exterior 160 SF Metal 0.0 Exterior Good
Pump 20 SF Metal 0.0 Pump Good
Panel 8 SF Metal 0.0 Tan Panel Good
Gray Panel 8 SF Metal 0.0 Gray Panel Good
Dark Gray Door 44 SF Metal 0.0 Door Good
Dark Gray Door Frame 14 SF Metal 0.0 Door Good
Green Green Green Green Blue Tan
500 East Morgan Pump Shed
July 7, 2026
LBP Inspector
Scott Bainbridge
PB-2648
We were hired by DFCM to sample for LBP in the painted surfaces on the structure and attached equipment for a pending demolition. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.
LBP was found in the orange red paint on the Exterior Metal Hatches and the Exterior Railing.
Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.
Bold
Paint Samples
Description Sample Location Amount Substrate XRF Results Homogeneous Area Condition
Red Exterior Hatch 30 SF Metal 3.3 Good Red Railing Handrail 16 SF Metal 5.3 Handrails Good
Exterior Hatches
= Some lead content
LBP per HUD guidelines, >1.0 mg/cm²
Blue Left Pump Base 8 SF Metal 0.0 Left Pump Base Good
Green Right Pump Base 8 SF Metal 0.0 Right Pump Base Good
Dark Gray Pump 6 SF Metal 0.0 Pump Good
Dark Gray Pump 6 SF Metal 0.0 Pump Good
Dark Gray Pump 6 SF Metal 0.0 Pump Good
Dark Gray Pump 6 SF Metal 0.0 Pump Good
Gray Panel 8 SF Metal 0.0 Panels Good
Exterior Gray Exterior Panel 8 SF Metal 0.0 Exterior Panels Good
Door Gray Door 44 SF Metal 0.0 Door Good
Door Gray Door frame 14 SF Metal 0.0 Door Good
State Street Morgan Pump Shed
July 7, 2026
LBP Inspector
Scott Bainbridge
PB-2648
We were hired by DFCM to sample for LBP in the structure and attached equipment for a pending demolition. Samples were taken by Scott Bainbridge, using a SciAps X-550 XRF. Lead Based Paint (LBP) is classified as 1.0 mg/cm² by weight by HUD. The results are included in this report.
LBP was found in the orange red paint on the Exterior Hatches and Exterior Handrail attached to the structure.
Refer to HUD, OSHA and EPA regulations regarding LBP of any amount regarding handling of LBP during renovation or demolition. TCLP testing may be needed if paint with lead content is in the waste stream.
Bold
Paint Samples
Description Sample Location Amount Substrate XRF Results
Homogeneous Area Condition
Red Exterior Hatch 36 SF Metal 2.4 Exterior Hatches Dark Red Handrail 18 SF Metal 2.5 Handrails
= Some lead content
LBP per HUD guidelines, >1.0 mg/cm²
Gray Panel 6 SF Metal 0 Panels
Light Gray Pump 6 SF Metal 0 Pumps
Black Pump Base 8 SF Metal 0 Pump Bases
Light Gray Pump 6 SF Metal 0 Pumps
Black Pump Base 8 SF Metal 0 Pump Bases