Construction Documents Summary

These are approved construction plans and specifications for the Utah State Hospital Forensics Mechanical Room Upgrade project located in Provo, Utah, prepared by Resolut Group engineering firm and approved by the Division of Facilities Construction and Management (DFCM). The project involves replacing existing mechanical equipment in the main Forensics building mechanical room, including two domestic hot water storage tanks (500-gallon AO Smith units), four recirculating pumps (Bell & Gossett PL-30B), two steam-to-domestic hot water heat exchangers (Aerco SWDW24/4), four steam-to-hydronic heat exchangers (Bell & Gossett models), and four primary/standby heating and preheat pumps (Bell & Gossett e-1510 1.5BC). The mechanical scope includes new piping connections, valves, controls, and concrete housekeeping pads, with all existing control valves to remain and existing sequences of operation maintained. The electrical work encompasses new variable frequency drives (VFDs) for pump motors operating at 460/3/60 volts, new motor disconnects, conduit runs, wiring, and control terminations. All materials and equipment specifications comply with 2024 International Building Code, 2024 National Electrical Code, and applicable Utah state standards.

The construction cost estimate is $525,000, with Stage II bidding restricted to contractors prequalified under DFCM's Stage I Prequalification process and listed on the current DFCM Prequalified Contractors list as of the solicitation date. The general notes require contractors to verify existing field conditions, coordinate with mechanical and electrical trades during installation, ensure all equipment fits through existing doorways and openings, extend concrete pads as necessary, and maintain existing circuit integrity where applicable. Contractors must provide updated panel circuit directories, label all receptacles and disconnects, perform comprehensive system testing, and submit detailed documentation including shop drawings, manufacturer certifications, and harmonic analyses for VFD systems. All work must be completed to the satisfaction of the DFCM project reviewer and comply with manufacturer recommendations and local code requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

07/31/2026

260251

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

L

IC

EN

SE

D P

ROFESS I ONAL ENG

IN

E

ER

No. 8325442-2202

S TA T E O F U TAH

JACOB D.

BECK

07-31-26

JD

08/12/2026 CODE REVIEW

C001

COVER SHEET

DFCM Project No. 27136420

CONSTRUCTION DOCUMENTS

Vicinity Map

C001 COVER SHEET

MECHANICAL

M001 MECHANICAL SYMBOLS AND ABBREVIATIONS

M101 MECHANICAL OVERALL PLAN

M401 MECHANICAL ENLARGED PLAN

M501 MECHANICAL DETAILS

M601 MECHANICAL SCHEDULES

ELECTRICAL

EG001 INDEX SYMBOLS & NOTES

EO100 ELECTRICAL OVERALL PLAN

EP401 ELECTRICAL ENLARGED PLANS

SHEET INDEX

UTAH STATE HOSPITAL FORENSICS

Provo, Utah 84603

MECHANICAL ROOM UPGRADE

PROJECT SITE

PROVO, UTAH

NORTH

MECHANICAL ENGINEER: RESOLUT GROUP

181 EAST 5600 SOUTH

MURRAY, UT 84107

(801) 530-3148 (JACOB BECK)

ELECTRICAL ENGINEER: RESOLUT GROUP

181 EAST 5600 SOUTH

MURRAY, UT 84107

(801) 797-5346 (LEWIS WONG)

CONSULTANTS

North: ______ South: ______ East: ______ West: ______

Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________

d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a

3) Three Story: A (3)______

2) Two Story: A (2)________

1) One Story: ______

c) Total Allowable Area for:

N/A (NON-SEPARATED OCCUPANCIES)

b) Sum of the Ratio Calculations for Mixed Occupancies:

a) 0.25I = 100f F P 30

WstA I 100100 fIA t taA = A + +

Official for Complex Buildings. Including, but not limited to:

g) Fire Stopping, Including Tested Design Number.

f) Exterior and Interior Accessibility Route.

e) Fire Assembly Locator Sheet.

a) High Rise Requirements.

b) Atriums.

c) Performance Based Criteria.

d) Means or Egress Analysis.

2) Additional Code Information shall be provided at the discretion of the Building

Code Accessibility Chapters, the more restrictive requirement shall govern.

through - ADA Guidelines and specific reference to the International Building

1) In case of conflict with the U.S. Department of Justice Federal Registers Parts

FOOTNOTES:

d) Drinking Fountains: ______ Service Sinks: ______

c) Bath Tubs or Showers: ______

b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______

a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____

M. Minimum Number of Required Plumbing Facilities:

Exit Width Required: ______ Exit Width Provided: ______

Element Hours Assembly ListingListing

Element AssemblyHours

Smoke Partitions Fire Partitions

Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls Structural Frame Partitions - Permanent Fire Barriers

Floors - Ceiling Floors Roofs - Ceiling Roofs Exterior Doors and Windows Shaft Enclosures Fire Walls

BAHTBABABA

Design Wind Speed: ______ mphB. Seismic Design Category: ______

L. Design Occupant Load: ______

K. Fire Resistance Rating Requirements for Building Elements (hours).

Area Modifications:J:

_____________________________________________________Tabular Area:I:

per Floor (square feet): _________________________________________Actual AreaH:

Number of Stories: ______ Building Height: ___________G:

Required: ______ Provided: _________ Type of Sprinkler System: __________

Sprinklers:F:

Mixed Occupancies: ______ Nonseparated Uses: ______E.

separation distance (in hours):

Requirements for the Exterior Walls based on the fireFire Resistance RatingD.

C. Type of Construction (circle one):

Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______

Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code

Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code

YearYear

APPLICABLE CODES

A. Occupancy and Group: _______ ________ ________ ________ ________

CODE ANALYSIS

N

N N

I-3

X X

NO

N/AN/A

NR NR NR NR

NO

YES YES NFPA 13

1 30' - 8"

70,908

N/A

3) Deferred Submittals:

a) Seismic Bracing for Mechanical and Electrical. Work related to the deferred

N/A

N/AX

UL

submittals shall not commence until the building official has approved the submittal.

N/A

160 FT

N/A

B A-3

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/02/2026

REVIEWED FOR CODE

COMPLIANCE

PS

N

LB/HR.GPM

3-1" SLOTS

@ 48" 400

W R

12/12

45°D

FD

FSD

SD

OR

8/8

1.25D

AD

LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS

12/8 FO

ATC

CF

LATERAL STRAINER WITH BLOW-OFF VALVE, PROVIDE

HOSE END WITH CAP WHERE DISCHARGE IS NOT PIPED

TO DRAIN

F&T

AW

AV

HP(NAME)

N20

(NAME)

R

SINGLE DUCT AIR TERMINAL BOX VARIABLE OR

CONSTANT VOLUME. MIN. 1-1/2 TERMINAL INLET SIZE

STRAIGHT DUCT AT TERMINAL INLET.

HEATING OR COOLING COIL IN DUCT

ACCESS PANEL IN DUCT OR PLENUM

ATC DAMPER

SMOKE DAMPER W/ ACCESS PANEL

COMBINATION FIRE/SMOKE DAMPER W/ ACCESS PANEL

FIRE DAMPER IN DUCT, W/ ACCESS PANEL REQD.

MANUAL VOLUME DAMPER

HIGH EFFICIENCY FITTING

TAP ENTRY AREA EQUALS 150% OF BRANCH AREA

BRANCH DUCT SPLIT WITH 6" WIDTH AND MIN.

R=WIDTH OF BRANCH DUCT DOWNSTREAM. ELBOW

TURNING VANE OPTIONAL.

RECTANGULAR TO ROUND DUCT TRANSFORMATION

RECTANGULAR TO RECTANGULAR OR ROUND TO ROUND

DUCT TRANSFORMATION MAXIMUM 15° INCLUDED ANGLE

EXCEPT WHERE SHOWN OTHERWISE.

R/W=1. ROUND DUCT SIMILAR TO RECTANGULAR

INCLINED DROP

INCLINED RISE WITH RESPECT TO AIR FLOW 15°

NOMINAL INCLINE WITH RADIUS

TURNS=DEPTH OF DUCT.

ROUND DUCT WITH FREE AREA DIMENSIONS

SHOWN IN INCHES.

RECTANGULAR DUCT WITH FREE AREA

DIMENSIONS SHOWN IN INCHES.

FLAT OVAL DUCT WITH FREE AREA

DIMENSIONS SHOWN IN INCHES.

FAN

FLEXIBLE DUCT

FLEXIBLE DUCT CONNECTION

LINEAR DIFFUSER WITH PLENUM AND FLEXIBLE DUCT

CONNECTION. NO. OF SLOTS & SIZE OF SLOT ON TOP, ACTIVE

LENGTH AND CFM ON BOTTOM

CEILING AIR GRILLE WITH

FLEXIBLE DUCT

CEILING SUPPLY DIFFUSER

WITH FLEXIBLE DUCT

SIDEWALL EXHAUST OR

RETURN REGISTER

SIDEWALL SUPPLY REGISTER

CEILING EXHAUST REGISTER,

(BALANCE TO MATCH SUPPLY IF

RETURN CFM IS NOT SHOWN)

CEILING RETURN REGISTER

CEILING SUPPLY DIFFUSER

RELIEF AIR OR EXHAUST AIR LOUVER

FRESH AIR LOUVER

TURNING VANES

UNDER FLOOR DUCT

ROUND DUCT - DROP

ROUND DUCT - RISE

NEGATIVE PRESSURE DUCT - DROP

TOP FIGURES INDICATE

NECK SIZE. BOTTOM

FIGURE INDICATES CFM.

12/8

12Ø

UP

DN

12/12 12Ø

1.5D

D

12Ø 12/12

FLANGE

PRESSURE GAUGE WITH PIGTAIL

PRESSURE GAUGE WITH SHUT-OFF COCK

ANCHOR

DEMOLITION

ALIGNMENT GUIDE

FLEXIBLE EXPANSION JOINT

SOLENOID VALVE

CHEMICAL FEED

HELICOPTER FUEL RETURN

HELICOPTER FUEL SUPPLY

FUEL OIL RETURN

FUEL OIL SUPPLY

HOT GAS

EXISTING PIPING TO BE REMOVED

LIQUIFIED PETROLEUM GAS

GLYCOL PIPING SOLUTION

GLYCOL HEAT RECOVERY PIPING

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

EXISTING PIPING

NATURAL GAS

MAKE UP WATER

BOILER FEED WATER

BOILER BLOW DOWN

HIGH PRESSURE STEAM

MEDIUM PRESSURE STEAM

LOW PRESSURE STEAM

HIGH PRESSURE CONDENSATE

LOW PRESSURE CONDENSATE

HFR

HFS

FOR

FOS

HG

(NAME)

LPG

G(NAME)

GHR

HWR

HWS

E(NAME)

G

MUW

BF

BBD

HPS

MPS

LPS

HPC

LPC

DN

UNION

FLOW METER ORIFICE

FLOW SWITCH

TEMPERATURE AND PRESSURE TEST PORT

PRESSURE SWITCH

PRESSURE REDUCING, SELF CONTAINED VALVE

PRESSURE REDUCING, EXTERNAL PRESSURE VALVE

BALL VALVE (PIPE SIZES 2" AND SMALLER) BUTTERFLY

VALVE (PIPE SIZES 2-1/2" AND LARGER)

CHECK VALVE

MOTOR OPERATED BUTTERFLY VALVE

GAS COCK

RELIEF VALVE

GATE VALVE

ATC VALVE - 2 WAY

ATC VALVE - 3 WAY

GLOBE VALVE

CALIBRATED BALANCING VALVE

WITH GPM INDICATED

SHUT-OFF COCK FOR USE WITH PRESSURE GAUGE

FLOW METER

90° ELBOW

45° ELBOW

THERMOMETER - TEMP RANGE AS INDICATED

NIGHT THERMOSTAT

STEAM TRAP, F&T=FLOAT & THERMOSTATIC

B=BUCKET, T=THERMOSTATIC

ARROW INDICATES DIRECTION OF FLOW IN PIPE

LEADER INDICATES DOWNWARD SLOPE

RISER - DOWN (ELBOW)

RISER - UP (ELBOW)

BRANCH - SIDE CONNECTION

NRS GATE VALVE WITH SUPERVISION

FLOW SWITCH

HOSE VALVE

CLEAN-OUT

FLOOR CLEAN-OUT OR

CLEAN-OUT TO GRADE

VENT THRU ROOF

DOMESTIC COLD WATER (DCW)

DOMESTIC HOT WATER (DHW)

DOMESTIC HOT WATER RETURN (DHWR)

PLUMBING FIXTURES

POINT OF CONNECTION

SECTION TAG - TOP FIGURE IS SECTION NO.

BOTTOM FIGURE IS SHEET NO.

DETAIL TAG - TOP FIGURE IS DETAIL NO.

BOTTOM FIGURE IS SHEET NO.

EQUIPMENT IDENTIFICATION

KEYED NOTE IDENTIFICATION

ACID WASTE

ACID VENT

HIGH PRESSURE DOMESTIC WATER

MEDICAL OXYGEN

MEDICAL AIR

MEDICAL AIR AT PRESSURE INDICATED

MEDICAL VACUUM

NITROGEN

NITROUS OXIDE

CARBON DIOXIDE

COMPRESSED AIR

LAB AIR

LAB VACUUM

BRINE

FIXTURE FROM LEVEL ABOVE

P-1

EF

OX

MA

MA 120

MV

N

C02

CA

LA

LV

B

A M-101

A

M101

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CR

CS

CHWR

CHWS

INSTRUMENT AIR

INSTRUMENT AIR AT PRESSURE INDICATED

IA

IA 120

MEDIUM PRESSURE CONDENSATEMPC

BRANCH - BOTTOM CONNECTION

BRANCH - TOP CONNECTION

MECHANICAL

FIRE RISER

SPRINKLER HEAD

FLOOR SINK

FLOOR DRAIN

AIR VENT-MANUAL

AIR VENT-AUTO

REDUCER

HOSE BIBB

PIPE CAP

SWITCH

THERMOSTAT

SENSOR

ROOF DRAIN

DOWNSPOUT NOZZLE

INLINE PUMP

INLINE PUMP

WATER HAMMER ARRESTOR

CONCENTRIC REDUCER

ECCENTRIC REDUCER

CEILING RETURN AIR GRILLE

W/ SOUND BOOT

BDD

BACK DRAFT DAMPER

POSITIVE PRESSURE DUCT - RISE

POSITIVE PRESSURE DUCT - DROP

NEGATIVE PRESSURE DUCT - RISE

1-WAY BLOW PATTERN

2-WAY BLOW PATTERN

2-WAY BLOW PATTERN

3-WAY BLOW PATTERN

4-WAY BLOW PATTERN

DUCT SMOKE DETECTOR

UNIT HEATER

SW

OX 120

REFRIGERANT SUCTION

REFRIGERANT LIQUID

PUMPED CONDENSATE

VACUUM

RS

RL

V

ROOF DRAIN

ROOF DRAIN OVERFLOW

SEWER (BELOW GRADE)

SEWER (ABOVE GRADE)

VENT (SEWER)

SOFT DOMESTIC WATER (SW)

REVERSE OSMOSIS WATER RETURN

MEDICAL OXYGEN AT PRESSURE INDICATED

RDO

RD

ROR

FCO

COTG

GATE VALVE - NON RISING STEM

ANGLE VALVE

BALANCING COCK

VALVE IN RISE

FILL PORT

DRAIN PAN AND P-TRAP

PLUMBING PLUMBING CONT. LINETYPES LINETYPES CONT.

SYMBOLS

FIRE

FIRE SPRINKLER WATERF

RISE OR DROP

DI DEIONIZED WATER SUPPLY

DEIONIZED WATER RETURNDIR

RO REVERSE OSMOSIS WATER SUPPLY

FUEL OIL VENTFOV

REDUCED PRESSURE BACKFLOW

PREVENTOR W/ DRAIN PAN LUBRICATED PLUG COCK

THERMOSTATIC MIXING VALVE

07/31/2026

260251

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M001

MECHANICAL

SYMBOLS AND

ABBREVIATIONS

GENERAL NOTES

1. ALL BUILDING CONTROLS SHALL BE DISCONNECTED

FROM EXISTING EQUIPMENT AND RECONNECTED TO

NEW EQUIPMENT AS REQUIRED. EXISTING CONTROL

VALVES SHALL REMAIN. EXISTING SEQUENCE OF

OPERATIONS SHALL REMAIN.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/02/2026

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M101

MECHANICAL

OVERALL PLAN

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/02/2026

1 1

1(E)3"

(E)3"

(E)3"(E)5"

(E)4"

(E)4" (E)4"

(E)2"

(E)8"

(E) LPS

(E)6" (E)6"

(E) LPC

HX

HX

HX

HX

DHX

DHX

ST

ST

P

P

P

P

(E)5"

(E)4"

(E)4" (E)4"

(E)2"

(E)8"

(E) LPS

(E)6" (E)6"

(E) LPC

(TYP.)

3"3"3"3"

4"

3"

3"

3"

3"

4"4"4" 4" 4"

2-1/2"

3/4"

2-1/2"2-1/2"2-1/2"2-1/2"

(TYP.)

DHX

DHX

ST

DCP

DCP

ST

DCP

DCP

(TYP.)

07/31/2026

260251

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

KEYED NOTES#

1. DEMOLISH AND REMOVE EXISTING EQUIPMENT, PIPING, AND

ASSOCIATED ACCESSORIES. TYPICAL OF ALL. FIELD VERIFY

EXISTING CONDITIONS.

2. EXISTING CONTROL VALVES SHALL REMAIN. TYPICAL OF ALL.

FIELD VERIFY.

3. CONNECT NEW PIPING TO EXISTING. FIELD VERIFY EXISTING

CONDITIONS. TYPICAL.

M401

MECHANICAL

ENLARGED PLAN

GENERAL NOTES

1. EXTEND CONCRETE HOUSEKEEPING PAD AS NECESSARY TO

ACCOMMODATE NEW EQUIPMENT INSTALLATION.

2. ALL DEMOLISHED EQUIPMENT AND NEW EQUIPMENT SHALL FIT

THROUGH EXISTING DOORS AND OPENINGS. FIELD VERIFY

EXISTING CONDITIONS.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/02/2026

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M501

MECHANICAL

DETAILS

BUTTERFLY VALVE (TYPICAL)

RETURNSUPPLY

FLEXIBLE CONNECTION. SEE

SPECIFICATIONS (TYPICAL)

PRESSURE GAUGE WITH

SHUT-OFF COCKS AND

SNUBBER

SUCTION DIFFUSER

STEEL SUPPORT LEG WITH

ADJUSTABLE FOOT

STRAINER BLOW DOWN FULL

SIZE TO FLOOR WITH CAP

CONCRETE BASE WITH #4 BARS 12" OC

EACH WAY BEVEL EDGE ALL AROUND.

GROUT BASE PER SPECIFICATIONS.

EXTEND EXISTING 4" CONCRETE

HOUSEKEEPING PAD AS NEEDED TO

ACCOMMODATE NEW EQUIPMENT.

CHECK VALVE

THERMOMETER

UNION OR VICTUALIC

COUPLINGS (TYPICAL)

CLEARANCE TO REMOVE

MOTOR AND IMPELLER

WITHOUT DISCONNECTING

PIPING

3/8" ANCHOR BOLT WITH NUT

AND WASHER (TYPICAL)

VIBRO-ACOUSTICS CIB

SPRING INERTIA BASE

ISOLATOR PAD SEE

SPECIFICATIONS (TYPICAL)

BALANCING VALVE (NOT

REQUIRED FOR VARIABLE

SPEED PUMP)

VENTURI FLOW MEASURING STATION.

MAINTAIN 6 DIAMETERS UPSTREAM / 3

DIAMETERS DOWNSTREAM OF

STRAIGHT PIPING

PLATE (ALL LEGS)

6" x 6" x i" STEEL

3" x 3" x r"

FRONT ELEVATIONSIDE ELEVATION

SUPPORTING STRUCTURE

3" x 3" x r" ALL AROUND

8" x 8" x i" STEEL

PLATE (ALL LEGS)

s

FLOOR LINE

4"

2 x HEAT EXCHANGER

DIAMETER

s

4'- 0"

HEAT EXCHANGER

CAST STEEL SADDLE

BOLT SADDLE

TO FRAME

HEAT EXCHANGER

SADDLE

CAST STEEL

T

C

T

C

RELIEF VALVE (TYP.)

UNION (TYP.)

AGA RATED TEMP. AND

SHUT-OFF VALVE (TYP.)

(E) CONDENSATE OUT

(TYPICAL)

(TYPICAL)

CHECK VALVE

STEAM TRAP

DHW SUPPLY

FROM STEAM HEADER

DCW SUPPLY

NOTE: PROVIDE

CONCRETE BASE BELOW

WATER HEATERS

HEIGHT AS REQUIRED

FOR GRAVITY FLOW OF

CONDENSATE TO

CONDENSATE PUMP

INLET

SHUT-OFF VALVE (TYP.)

CONTROL VALVE, TYPICAL

STRAINER (TYP.)

(E)4"

3"

3" (E)3"

(E)3"

4"

4"

2-1/2"

(E)4"

(E)4"

LOCATE NEAR FLOOR FOR

EASY SERVICING

FLOW CONTROL VALVE

GLOBE VALVE (TYP)

1/2" LINE TO

SUCTION SIDE OF

PUMP

SCREEN

1/2" GLOBE VALVE

FOR DRAIN

CHECK VALVE

1/2" LINE FROM

PRESSURE SIDE OF

PUMP

STRAINER BLOWDOWN (TYPICAL)

CHECK VALVE (TYPICAL)

AUTOMATIC VALVE-ATC

SHUT-OFF VALVE (TYPICAL)

SYSTEM PIPING

FLOW SETTER

F&T TRAP

DRAIN VALVES

TO EXISTING FLOOR DRAIN

(E)CONDENSATE RETURN

12" LONGMIN, DRIP LEG

VACUUM BREAKER

RELIEF VALVE

STRAINER W/ BLOWOFF

GATE VAVLE

(E)STEAM SUPPLY

REDUCER (TYP.)

(E)AUTO CONTROL VALVE (1/3 - 2/3)

P

P

HEAT EXCHANGER

(E)HWS

(E)HWR

EXTEND EXISTING 4"

CONCRETE HOUSEKEEPING

PAD AS NEEDED TO

ACCOMMODATE NEW

EQUIPMENT.

2-1/2"

2-1/2"

2-1/2"

DHX

DHX

ST

ST

DCP

DCP

2 DCP

DCP

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/02/2026

JB

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

DFCM APPROVAL STAMP

No. 8325442-2202

JACOB D.

BECK

07-31-26

JD

M601

MECHANICAL

SCHEDULES

DOMESTIC STORAGE TANK SCHEDULE

MANUFACTURER WORKING DIA/

AND CAPACITY PRESS. LENGTH

ID MODEL NUMBER SERVICE (GAL) (PSI) (IN) NOTES

ST-1 AO SMITH TJV-500A DOMESTIC HOT WATER 500 125 46 / 91 1,2,3

ST-2 AO SMITH TJV-500A DOMESTIC HOT WATER 500 125 46 / 91 1,2,3

1. VERTICAL FACTORY JACKETED AND INSULATED TANK.

2. HEAVY GAUGE STEEL WITH HIGH QUALITY PAINT. GLASSLINED WITH STANDARD TANK OPENINGS. ASME CONSTRUCTION.

3. TANKS FURNISHED WITH ANODES DESIGNED FOR PROTECTION.

RECIRCULATING PUMP SCHEDULE

FLUID ELECTRICAL

MANUFACTURER FLOW HEAD MOTOR MOTOR

AND RATE WORKING LOSS SIZE SPEED

ID MODEL NUMBER LOCATION TYPE (GPM) FLUID (FT) (HP) (RPM) VOLT/PH/HZ NOTES

DCP-1 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 2 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2

DCP-2 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 10 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2

DCP-3 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 2 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2

DCP-4 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 10 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2

1. LEAD FREE BRONZE BODY CONSTRUCTION. STAINLESS STEEL FACE PLATE.

2. PERMANENTLY LUBRICATED MOTOR TYPE.

STEAM-TO-DOMESTIC HOT WATER HEAT EXCHANGER SCHEDULE

SOURCE MEDIUM (STEAM) TRANSFER MEDIUM (HYDRONIC) PHYSICAL

ENTERING/

MANUFACTURER FLOW ENTERING FLOW LEAVING HEAD DIA./

AND LOAD RATE PRESSURE RATE TEMP. WORKING LOSS HEIGHT/

ID MODEL NUMBER LOCATION TYPE USAGE (MBH) (LB/H) (PSIG) (GPM) (°F) FLUID (FT) (IN/IN) NOTES

DHX-1 AERCO SWDW24/4 MECHANICAL RM SHELL AND TUBE DOMESTIC 2033 1911 10 37 40/140 WATER 7.4 16 / 88 1,2,3,4,5

DHX-2 AERCO SWDW24/4 MECHANICAL RM SHELL AND TUBE DOMESTIC 2033 1911 10 37 40/140 WATER 7.4 16 / 88 1,2,3,4,5

1. PROVIDE BACNET GATEWAY INTERFACE WITH BMS FOR MONITORING TEMPERATURE.

2. PROVIDE WITH AERCO STEAM TRAP PART NUMBER 99136-2.

3. UL-LISTED AS DOUBLE-WALL HEAT EXCHANGER FOR POTABLE HOT WATER USE.

4. PROVIDE WITH STAND SUPPORTS.

5. 5 FLA, 120/1 POWER CONNECTION REQUIREMENT.

STEAM-TO-HYDRONIC HEAT EXCHANGER SCHEDULE

SOURCE MEDIUM (STEAM) TRANSFER MEDIUM (HYDRONIC) PHYSICAL

ENTERING/

MANUFACTURER FLOW ENTERING PRESSURE FLOW LEAVING HEAD DIAMETER / SURFACE

AND LOAD RATE PRESSURE DROP RATE TEMP. WORKING LOSS LENGTH AREA

ID MODEL NUMBER LOCATION TYPE USAGE (BTU/H) (LB/H) (PSIG) (PSI) (GPM) (°F) FLUID (PSI) (IN/IN) (FT²) NOTES

HX-1 BELL & GOSSETT SU-85-4 MECH SHELL & TUBE HYDRONIC 1,276 1,320 5 1 87 150 / 180 WATER 4 14 / 66 41.9 - HX-2 BELL & GOSSETT SU-85-4 MECH SHELL & TUBE HYDRONIC 1,276 1,320 5 1 87 150 / 180 WATER 4 14 / 66 41.9 -

HX-4 BELL & GOSSETT SU-84-4 MECH SHELL & TUBE PREHEAT 1,087 1,148 5 1 82 85 / 115 50% PG 5 14 / 54 33.3 - HX-5 BELL & GOSSETT SU-84-4 MECH SHELL & TUBE PREHEAT 1,087 1,148 5 1 82 85 / 115 50% PG 5 14 / 54 33.3 -

PUMP SCHEDULE

FLUID PUMP ELECTRICAL

MANUFACTURER FLOW HEAD MOTOR MOTOR MOTOR

AND RATE WORKING LOSS EFFICIENCY SIZE BHP SPEED

ID MODEL NUMBER SYSTEM LOCATION TYPE (GPM) FLUID (FT) (%) CONSTRUCTION (HP) (HP) (RPM) VOLT/PH/HZ NOTES P-1 BELL & GOSSETT e-1510 1.5BC HEATING MECH ROOM BASE-MOUNTED 87 WATER 55 58% CAST IRON 3 2.1 1750 460/3/30 1,2,3,4

P-2 BELL & GOSSETT e-1510 1.5BC HEATING MECH ROOM BASE-MOUNTED 87 WATER 55 58% CAST IRON 3 2.1 1750 460/3/30 1,2,3,4

P-3 BELL & GOSSETT e-1510 1.5BC PREHEAT MECH ROOM BASE-MOUNTED 82 50% PG 55 54% CAST IRON 3 1.9 1750 460/3/30 1,2,3

P-4 BELL & GOSSETT e-1510 1.5BC PREHEAT MECH ROOM BASE-MOUNTED 82 50% PG 55 54% CAST IRON 3 1.9 1750 460/3/30 1,2,3

1. BASE-MOUNTED END SUCTION CENTRIFUGAL PUMP

2. PUMPS ARE PRIMARY / STANDBY

3. VFD BY ELECTRICAL

4. MOTOR SHALL BE VFD COMPATIBLE

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/02/2026

EG001

INDEX SYMBOLS &

NOTES

7/31/2026

260251

ST

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

SA

PM: SYDNEE ANDERSON

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

L

IC

EN

SE

D P

ROFESS I ONAL ENG

IN

E

ER

14275529

S TAT E O F U TAH

SANG TRUONG

No.

6"

CL

LC

NOTES:

1. TYP. FOR WOOD AND METAL STUD ROUGH-IN.

2. PLASTER RINGS NOT SHOWN. COORDINATE RING DEPTH TO BE FLUSH

WITH FINISHED SURFACE, UNLESS NOTED OTHERWISE.

3. LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCH. AND MECH.

DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.

4. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR PARTITIONS IN THE

SAME STUD SPACE MUST BE SEPARATED BY A MIN. OF 6" HORIZONTAL DISTANCE.

5. ELECTRICAL BOXES INSTALLED IN FIRE RESISTANT WALLS OR PARTITIONS

SHALL COMPLY WITH IBC 714.3.2.

6. INSULATED THROAT EMT CONNECTOR.

7. CADDY FASTENER, THROUGH STUD CABLE/CONDUIT SUPPORT 'FB12P'.

8. ADJUSTABLE BAR HANGER.

9. TYPICAL DEVICE JUNCTION BOX.

(TYP.)

EMT

5 4

(TYP.)

EMT

EMT

EMT

EG001

6 TYPICAL ROUGH-IN

NO SCALE

(S) (S) SIMPLEX (D) DUPLEX (Q) QUADPLEX OR DOUBLE DUPLEX(D) (Q)

STANDARD CONVENIENCE OUTLET 18"

CONVENIENCE OUTLET, GFCI 18"

STANDARD CONVENIENCE OUTLET, CUSTOM HEIGHT (6)

48"UNLESS

NOTED

CONVENIENCE OUTLET, GFCI, CUSTOM HEIGHT (6)

48"UNLESS

NOTED

CONVENIENCE OUTLET, FLOOR FLOOR

CONVENIENCE OUTLET, CEILING CEILING

J JUNCTION BOX AS NOTED (12)

J JUNCTION BOX, WALL AS NOTED (12)

J JUNCTION BOX, FLOOR FLOOR (12)

S

M MANUAL MOTOR CONTROLLER SWITCH WITHOUT

TERMINAL OVERLOAD PROTECTION

SWITCH WITH PILOT LIGHTS

P

MANUAL SWITCH WITH THERMAL OVERLOADS

TH

SINGLE POLE DOOR SWITCHS

X

NON-FUSED DISCONNECT SWITCH (13) (14)

FUSED DISCONNECT SWITCH (13) (14)

MAGNETIC STARTER (13) (14)

MAGNETIC STARTER WITH FUSED DISCONNECT (13) (14)

MAGNETIC STARTER WITH BREAKER DISCONNECT (13) (14)

POWER RELAY (13) (14)

MOTOR OUTLET

MOTOR OUTLET, ROOF MOUNTED ROOF

TRANSFORMER SEE PLANS

TRANSFORMER SEE PLANS

EMERGENCY GENERATOR SEE PLANS

MAIN DISTRIBUTION POWER PANEL

PANEL BOARD, SURFACE 6'-6" TO TOP

PANEL BOARD, RECESSED 6'-6" TO TOP

XX

X MECHANICAL/PLUMBING EQUIPMENT CALLOUT

LUMINAIRE TYPE

X

XX.X DIAGRAM/DETAIL CALLOUT

HOME RUN TO PANEL

A AMPS

AFC AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPS INTERR. CAPACITY

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

C CONDUIT

CND CONDUIT

CO CONDUIT ONLY

CT CURRENT TRANSDUCER

CU COPPER MATERIAL

DED DEDICATED

DFA DROP FROM ABOVE

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EM EMER./EGRESS BATTERY

EMT ELEC. METALLIC TUBING

ENT ELEC. NON-METAL. TUBING

ER EXISTING TO BE RELOCATED

EX EXISTING TO REMAIN

FMC FLEXIBLE METAL CONDUIT

GC GENERAL CONTRACTOR

GEC GRND. ELEC. COND. AT SES

GFCI GRND. FLT. CURR. INTERR.

GFEP GRND. FLT. EQUIP. PROTECT.

GND GROUND

IMC INTER. METAL CONDUIT

IG ISOLATED GROUND

KCMIL 1000 CIRCULAR MILS (MCM)

LFMC LIQUID-TIGHT FLEX.

METAL. COND.

LFNC LIQUID-TIGHT FLEX.

NON-METAL. COND.

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPS

N1 NEMA 1

N3R NEMA 3R

N NEW

NL NIGHT LIGHT, BYPASS

LOCAL SWITCHING

PC PLUMBING CONTRACTOR

POC POINT OF CONNECTION

POS POINT OF SALE

R RELOCATED

RX RECEIVER

RM ROOF MOUNTED

RMC RIGID METALLIC CONDUIT

RNC RIGID NON-METALLIC COND.

SBJ SYSTEM BONDING JUMPER

SCA SHORT CIRCUIT AMPERES

TX TRANSMITTER

TC TEMP. CONTROL CONTR.

TR TAMPERPROOF

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

VA VOLT/AMPS

VIF VERIFY IN FIELD

WP WEATHERPROOF/NEMA 3R

XP EXPLOSION PROOF

XR EXISTING TO BE REMOVED

ABBREVIATIONS

(1) SEE LUMINAIRE SCHEDULE FOR FIXTURE TYPES AND DETAILS.

(2) SEE LUMINAIRE SCHEDULE FOR MOUNTING REQUIREMENTS.

(3) WIRE LIGHT FIXTURE FROM ADJACENT J-BOX

(4) CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST

(5) DIRECTIONAL ARROWS INDICATE REQUIRED CHEVRONS.

(6) COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL INTERIOR ELEVATIONS

(7) USE WITH POWER PACK.

(8) "X" IN SYMBOL IS INCHES BETWEEN RECEPTACLE ALONG WIREWAY. SEE DRAWINGS.

(9) PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.

(10) MATCH THE VOLTAGE OF THE RELAY WITH THAT OF THE CONTROLLING CIRCUIT.

(11) USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE AND INSTALLATION.

(12) PROVIDE MUD RING AND/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.

(13) USE HEAVY DUTY DEVICE FOR 480 VOLT.

(14) SIZE TO THE EQUIPMENT BEING CONTROLLED

(15) FIRE ALARM PANELS: FACP: FIRE ALARM CONTROL PANEL, NAC: NOTIFICATION APPLIANCE CIRCUIT PANEL, ANNUN: GRAPHIC ANNUNCIATOR PANEL, AND SES: SMOKE EVACUATION SYSTEM PANEL.

(16) LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.

(17) PROVIDE 5' OF SERVICE LOOP AND TERMINATE IN 2-PORT SURFACE MOUNT BOX.

NOTESNOTES

ELECTRICAL SYMBOL SCHEDULE

SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING

GAP GENERATOR ANNUNCIATOR PANEL SEE PLANS

ATS AUTOMATIC TRANSFER SWITCH SEE PLANS

EQUIPMENT CONNECTION

GENERAL NOTES

1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS ARE TO BE CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT DOCUMENTS AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION OR CONFLICT EXIST IN EITHER THE PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING BEFORE SUBMITTING HIS BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIER SHALL SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE SYSTEMS AT THEIR OWN EXPENSE. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE, THE CONTRACTOR SHALL TEST AND CONFIRM IT'S PROPER OPERATION. ANY INCOMPLETE SYSTEM

SHALL BE MADE COMPLETE AND OPERABLE.

2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE

GREATER THAN SPECIFIED AND/OR DIMENSIONED ON THE PLANS.

3. NO ADDITIONS TO THE CONTRACTOR BID WILL BE ALLOWED FOR CHANGES MADE NECESSARY BY INTERFERENCE WITH OTHER WORK.

4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS AND LABOR FOR THE CONNECTIONS OF ALL EQUIPMENT

SHOWN ON THE PLANS - ARCHITECTURAL, MECHANICAL, ETC.

5. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH LOCAL AND STATE CODES AND THE NEC. IF AT ANY TIME DURING CONSTRUCTION, OR AFTER, SOMETHING IS FOUND TO BE INSTALLED IN VIOLATION OF THE CODES LISTED ABOVE, IT SHALL BE

CORRECTED AT THE CONTRACTORS EXPENSE.

6. ALL EQUIPMENT PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE CONDITIONS AND SPACE THAT

EQUIPMENT IS BEING INSTALLED WITHIN.

7. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED FROM. VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BREAKERS AS NECESSARY FOR A

COMPLETE AND OPERABLE SYSTEM.

8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE TELE/DATA ROOM FROM WHICH NEW TELE/DATA OUTLETS WILL BE FED FROM. VERIFY EXISTING PATCH PANEL SPACES AND PROVIDE NEW PATCH PANELS AS NECESSARY TO

LAND ALL NEW TELE/DATA CABLING.

9. THE ELECTRICAL CONTRACTOR SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR. THE ELECTRICAL CONTRACTOR SHALL GROUND THE ELECTRICAL

SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.

10. THE ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS, CABINETS, DISCONNECT, TRANSFORMERS, ETC. AND SHALL MOVE THE PANELS/EQUIPMENT AT HIS EXPENSE IF REJECTED BY AN INSPECTOR. IF CLEARANCE IS NOT POSSIBLE, THE DESIGNER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.

11. CONDUIT LAYOUTS SHOWN ON THE PLANS ARE DIAGRAMMATIC, NOT INDICATING THE ROUTING REQUIRED. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT, BUILDING STRUCTURE AND OTHER POTENTIAL OBSTRUCTIONS.

12. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE

OF 10 FEET WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.

13. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT IS SET IN PLACE USING INDUSTRY STANDARD

METHODS AND PRACTICES.

14. MINIMUM SIZE CONDUIT SHALL BE 3/4". ABOVE GROUND CONDUIT SHALL BE EMT WITH STEEL SET SCREW FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN DIRECT

CONTACT WITH THE SOIL.

15. FLEXIBLE METAL CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS OF FLEXIBLE OR SEAL-TITE CONDUIT SHALL NOT EXCEED 72” INCHES. USE LFMC IN DAMP

OR WET LOCATIONS.

16. WIRING DEVICES SHALL MATCH EXISTING COLOR AND FACEPLATE TYPE. COLOR TO MATCH ADJACENT ARCHITECTURAL FINISH.

COORDINATE WITH ARCHITECT.

17. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE APPLICATION. ANY DEVICE BOXES NOT SECURED WILL BE MADE SECURE AT THE CONTRACTORS

EXPENSE.

18. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB RATED NYLON PULL CORD.

19. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS, WALLS, ETC.), THEY SHALL BE APPROVED BY THE INSPECTING OFFICER (INSPECTOR). THE UNCOVERING AND REPLACEMENT OF ELECTRICAL WORK FOR THE INSPECTION PURPOSES WILL

BE AT THE COST OF THE ELECTRICAL CONTRACTOR.

20. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120 OR 277VAC BRANCH CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12(CU,THHN/THWN-2)+1#12(CU,THHN/THWN-2)GND IN 3/4” EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10(CU,THHN) FOR 120VAC BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 100' TO ACCOMMODATE FOR VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES AND NOTES ON DRAWINGS FOR ALL OTHER BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.

21. CONDUCTORS SHALL BE COPPER STRANDED, 600VAC RATED, TYPE THHN/THWN-2 UNLESS OTHERWISE NOTED.

22. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS, WIRES, AND OVERCURRENT PROTECTION PRIOR TO ROUGH-IN. THE ELECTRICAL CONTRACTOR SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE DIRECTED BY THE EQUIPMENT SUPPLIER.

23. THE ELECTRICAL CONTRACTOR SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER, PAINT, DIRT, GREASE, UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE

ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FROM THE PREMISES.

24. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE

OF EQUIPMENT AND ADDITIONAL COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.

25. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO PROVIDE CONDUIT AND DEVICE

MOUNTING BOXES FOR THERMOSTATS AND OTHER MECHANICAL CONTROLS.

26. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED WITH THE

ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL BE MADE TO CONCEAL WIRING METHODS.

27. PROVIDE AN UPDATED, TYPED PANEL CIRCUIT DIRECTORY FOR ALL PANELS WHERE CIRCUITS HAVE BEEN MODIFIED, ADDED, OR REMOVED BY THE SCOPE OF THIS PROJECT. CIRCUIT DESCRIPTIONS ON THE DIRECTORY SHALL BE UNIQUE AND INDICATE THE ROOM AND EQUIPMENT/DEVICE IT IS FEEDING. DATE DIRECTORY WITH PROJECT COMPLETION DATE. MODIFIED CIRCUITS TO BE IN BOLD.

28. SUBMIT A SCALED LAYOUT (1/4" = 1') OF ALL ELECTRICAL ROOMS BASED ON THE ELECTRICAL GEAR AND EQUIPMENT SUBMITTALS.

29. PROVIDE A CLEAR, TYPED LABEL ON THE FACEPLATE OF ALL RECEPTACLES AND LIGHT SWITCHES INDICATING THE CIRCUIT IT IS TIED TO.

USE LABELING CONVENTION XX-xx, WHERE "XX" IS THE NAME OF THE PANEL AND "xx" IS THE BRANCH CIRCUIT NUMBER. LABELS LENGTH

SHALL NOT EXCEED 1/4" ON EITHER SIDE OF TEXT.

30. FUSED DISCONNECTS TO BE HEAVY DUTY.

31. FURNISH AND INSTALL TAMPER-RESISTANT RECEPTACLES FOR 120V RECEPTACLES IN AREAS SPECIFIED 210.52 OF THE NEC AND AS

REQUIRED UNDER 403.12 OF THE NEC.

STRUCTURE

STRUCTURE

STRUCTURE STRUCTURE

ALL THREAD (SIZE AS

REQUIRED) 3/8" MIN.

BEAM CLAMPS OR HANGER

CLAMPS (AS REQUIRED BY

WEIGHT SUPPORTED)

RACEWAY. (3/4" - 6")

CONDUIT HANGER

BEAM CLAMPS OR HANGER

CLAMPS (AS REQUIRED BY

WEIGHT SUPPORTED)

RACEWAY. (3/4" - 6")

NOTES:

1. WIRE SHALL NOT BE USED AS A COMPONENT OF ANY

RACEWAY HANGER SYSTEM.

2. DO NOT SUPPORT ANY RACEWAY LARGER THAN 1"

FROM BOTTOM CORD OF STEEL TRUSSES.

REFER TO SECTION FOR

ATTACHMENT OF ALL

THREAD ROD TO KINDORF

CHANNEL

1 1/2"x1 1/2"-12GA. KINDORF

CHANNEL OR APPROVED

SUBSTITUTE

3/8" ALL THREAD,

MINIMUM. INCREASE ROD

SIZE IF WEIGHT

REQUIRES PER ROD

MANUFACTURERS

RECOMMENDATIONS.

SUPPORT CONDUIT WITH

KINDORF STRAP OR

APPROVED SUBSTITUTE.

BEAM CLAMPS OR

HANGER CLAMPS AS

REQUIRED BY WEIGHT

SUPPORTED

PROVIDE 25% SPACE CAPACITY

NUT

WASHER

WASHER

NUT

EXIT

44"

18"

46"

WITHIN 18"

96"

72"

84"

18"

FINISHED FLOOR

WITHIN 60"

80"

44"

NOTES:

1. THE ELECTRICAL CONTRACTOR

SHALL VERIFY THE EXACT LOCATION

OF ALL TELEVISION OUTLETS WITH

THE ARCHITECT PRIOR TO

INSTALLATION.

2. ALL DEVICES SHOWN ON THIS DETAIL

ARE FOR REFERENCES OF

MOUNTING HEIGHTS ONLY. THE

ELECTRICAL CONTRACTOR SHALL

FIELD ADJUST THE HEIGHTS OF THE

DEVICES AS REQUIRED FOR PROPER

MOUNTING OF THE DEVICES.

3. ALL DEVICES REQUIRED FOR THIS

PROJECT MAY NOT APPEAR ON THIS

DETAIL. ALL ITEMS SHOWN ON THIS

DETAIL MAY NOT BE REQUIRED FOR

THIS PROJECT.

4. FIRE ALARM HORN/STROBES ARE TO

BE MOUNTED NO HIGHER THAN 96"

AND NO LOWER THAN 80" ON

CENTER.

44"

EG001 NO SCALE

MOUNTING HEIGHTS DETAIL

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/02/2026

EG002

ELECTRICAL

SPECIFICATIONS

7/31/2026

260251

ST

REVISIONS

SHEET CONTENTS

RESOLUT PROJECT #:

CHECKED BY:

DRAWN BY:

CURRENT/ISSUE DATE:A

B

C

D

E

1 2 3 4 5 6

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com

Project #: 260251

SA

PM: SYDNEE ANDERSON

U

TA

H S

TA

TE

H O

SP

IT

A L

FO

R

EN

SI

C S

M

EC

H A

N

IC

A L

R O

O M

U

PG

R A

D E

PR

O

VO

, U

TA

H

L

IC

EN

SE

D P

ROFE SS I ONAL ENG

IN

E

ER

14275529

S TAT E O F U TAH

SANG TRUONG

No.

ELECTRICAL SPECIFICATIONS

PART 1 - GENERAL

A. DESCRIPTION

1. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND TRANSPORTATION AS REQUIRED TO PROPERLY INSTALL

A COMPLETE AND OPERABLE ELECTRICAL SYSTEM.

B. RULES AND REGULATIONS

1. ALL WORK AND MATERIALS SHALL BE INSTALLED AS SHOWN AND HEREIN SPECIFIED.

2. THE LATEST EDITIONS OF THE FOLLOWING SPECIFICATIONS, STANDARDS, AND AMENDMENTS, AS ADOPTED

BY THE AUTHORITY HAVING JURISDICTION, SHALL FORM A PART OF THIS SPECIFICATION THE SAME AS IF HEREIN WRITTEN OUT IN FULL (ALL MATERIALS AND INSTALLATIONS SHALL CONFORM TO THE APPLICABLE

REQUIREMENTS THEREOF):

a. NFPA (NATIONAL FIRE PROTECTION ASSOCIATION), PUBLICATION NUMBER 70, "NATIONAL, ELECTRICAL

CODE"; PUB. NO. 72E, "AUTOMATIC FIRE DETECTORS".

b. UL (UNDERWRITERS LABORATORIES, INC.).

c. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION).

d. UBC (UNIFORM BUILDING CODE) AND STANDARD BUILDING CODE.

e. IBC (INTERNATIONAL BUILDING CODE)

f. IFC (INTERNATIONAL FIRE CODE)

g. IECC (INTERNATIONAL ENERGY CONSERVATION CODE)

h. IEC (INTERNATIONAL ELECTRICAL CODE) STATE AND

i. LOCAL BUILDING AUTHORITY AND CODES

3. NO REQUIREMENT TO THESE DRAWINGS AND SPECIFICATIONS SHALL BE CONSTRUCTED TO VOID ANY OF

THE PROVISIONS OF THE ABOVE SPECIFICATIONS AND STANDARDS.

C. DEMOLITION

1. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, AND NECESSARY EQUIPMENT TO PERFORM ALL

ELECTRICAL DEMOLITION AS SHOWN ON DRAWINGS. WHERE EQUIPMENT IS TO BE REMOVED IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO DE-ENERGIZE AND DISCONNECT ALL POWER AND COMMUNICATION WIRES TO EQUIPMENT ALLOWING A SAFE REMOVAL OF EQUIPMENT. DISCONNECTED

WIRES SHALL BE REMOVED.

2. DEMOLITION WORK INDICATED IN DRAWINGS IS BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORDS OR DRAWINGS. REPORT DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING ANY EXISTING INSTALLATION. THE CONTRACTOR ACCEPTS THE EXISTING CONDITIONS OF PROJECT BY STARTING

DEMOLITION WORK.

3. FIRST RIGHT OF REFUSAL SHALL BE COORDINATED WITH OWNER PRIOR TO REMOVAL OR DISPOSAL OF ANY EQUIPMENT, DEVISES, FIXTURES, ETC. COORDINATION SHALL BE DONE PRIOR TO BIDDING ON INTENT TO REUSE EXISTING MATERIALS AND THERE SHOULD BE NO CHANGE IN COST TO THE OWNER IF ELECTRICAL

CONTRACTOR FAILS TO COORDINATE.

4. ALL CIRCUITS THAT WILL BE INSIDE SCOPE OF PROJECT SHALL BE MADE SAFE FOR CONSTRUCTION AND POWER SHALL BE MAINTAINED AND ESTABLISHED WHERE REQUIRED THROUGHOUT THE SCOPE OF THE

PROJECT.

5. ANY WIRES AND CONDUITS TO BE REUSED IN NEW CONSTRUCTION SHALL BE INSPECTED AND REPLACED AS REQUIRED FOR NEW CONSTRUCTION. ANY CIRCUITS BEING CAPPED OR CONDUCTORS BEING LEFT IN

PLACE SHALL BE PROVIDED WITH A MEANS TO LOCK CIRCUIT IN OFF POSITION.

6. ANY CONDUITS, EQUIPMENT, ETC. SCHEDULED TO BE DEMOLISHED BY DIVISION 26 SHALL BE REMOVED COMPLETELY FROM SITE. WHERE CONDUITS, EQUIPMENT, ETC. ARE INACCESSIBLE THEY SHALL BE CUT

FLUSH WITH FINISHED SURFACES AND PATCHED TO MATCH EXISTING FINISHED SURFACE.

D. PERMITS AND INSPECTIONS UNLESS OTHERWISE SPECIFIED, THE CONTRACTOR SHALL APPLY, PAY FOR AND SCHEDULE ALL APPLICABLE PERMITS, FEES AND INSPECTIONS REQUIRED BY ANY AND ALL PUBLIC

AUTHORITIES HAVING JURISDICTION AND REQUIRING INSPECTION.

1. EC SHALL INCLUDE ALL UTILITY COMPANY CHARGES IN THE BASE BID.

E. WORKMANSHIP AND MATERIALS

1. WORKMANSHIP SHALL BE OF THE BEST QUALITY AND NONE BUT COMPETENT PERSONNEL SKILLED IN THEIR

TRADE SHALL BE EMPLOYED. THE CONTRACTOR SHALL FURNISH THE SERVICES OF AN EXPERIENCED SUPERINTENDENT, WHO WILL BE IN CHARGE OF THE EXECUTION OF WORK, UNTIL COMPLETED AND

ACCEPTED.

2. UNLESS OTHERWISE HEREIN AFTER SPECIFIED, ALL MATERIALS AND EQUIPMENT UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL BE NEW, OF BEST GRADE AND AS LISTED IN PRINTED CATALOGS OF THE MANUFACTURER. EACH ARTICLE OF IT'S KIND SHALL BE THE STANDARD PRODUCT OF A SINGLE

MANUFACTURER.

3. THE OWNER'S REPRESENTATIVE SHALL HAVE THE RIGHT TO ACCEPT OR REJECT MATERIAL EQUIPMENT AND/OR WORKMANSHIP AND DETERMINE WHEN THEY HAVE COMPLIED WITH THE REQUIREMENTS HEREIN

SPECIFIED.

4. ALL MANUFACTURED MATERIALS SHALL BE CLEARLY MARKED OR STAMPED WITH THE MANUFACTURER'S

NAME AND RATING.

5. REFERENCE TO STANDARDS ARE INTENDED TO BE THE LATEST REVISION OF THE STANDARD SPECIFIED, OR

THAT ACCEPTED BY THE AUTHORITY HAVING JURISDICTION.

F. MANUFACTURER'S RECOMMENDATIONS

1. EQUIPMENT INSTALLED UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL BE INSTALLED ACCORDING

TO THE MANUFACTURER'S RECOMMENDATIONS, UNLESS OTHERWISE SHOWN ON THE DRAWINGS OR

HEREIN SPECIFIED.

G. GUARANTEE ALL MATERIALS AND EQUIPMENT PROVIDED AND INSTALLED UNDER THIS SECTION SHALL BE GUARANTEED FOR A MINIMUM OF ONE YEAR. SHOULD ANY TROUBLE OR MALFUNCTIONS DEVELOP DURING THIS PERIOD DUE TO DEFECTIVE MATERIALS OR FAULTY WORKMANSHIP, THE CONTRACTOR WILL BE HELD LIABLE AND SHALL FURNISH LABOR, MATERIALS AND EQUIPMENT NECESSARY TO CORRECT THE TROUBLE OR MALFUNCTION WITHOUT ADDITIONAL COST TO THE OWNER. ALL DEFECTIVE MATERIAL OR INFERIOR WORKMANSHIP NOTICED DURING THE TIME OF INSTALLATION SHALL BE CORRECTED IMMEDIATELY TO THE

ENTIRE SATISFACTION OF THE ARCHITECT, ENGINEER AND OWNER, AT NO ADDITIONAL COST.

I. DEFINITIONS

1. "PROVIDE" - MEANS FURNISH, INSTALL, AND CONNECT, UNLESS OTHERWISE INDICATED.

2. "FURNISH" - MEANS PURCHASE NEW AND DELIVER IN OPERATING ORDER TO PROJECT SITE.

3. "INSTALL" - MEANS TO PHYSICALLY INSTALL THE ITEMS IN-PLACE.

4. "CONNECT" - MEANS MAKE FINAL ELECTRICAL CONNECTIONS FOR A COMPLETE OPERATING PIECE OF

EQUIPMENT. THIS INCLUDES PROVIDING CONDUIT, WIRE, TERMINATIONS, ETC. AS APPLICABLE.

5. "OR EQUIVALENT" - MEANS TO PROVIDE EQUIVALENT EQUIPMENT. SUCH EQUIPMENT MUST BE APPROVED

BY THE ENGINEER PRIOR TO BIDDING.

J. SUBMITTALS

1. PROVIDE SHOP DRAWINGS AND MANUFACTURER'S LITERATURE OF MATERIALS AND EQUIPMENT AS

REQUIRED IN THE GENERAL CONDITIONS, AS DIRECTED BY THE OWNER'S REPRESENTATIVE AND AS

LISTED BELOW:

2. CATALOG CUTS

a. CIRCUIT BREAKERS (EACH SIZE AND TYPE)

b. SAFETY SWITCHES

c. MOTOR STARTERS

d. THERMAL SWITCHES

e. LIGHT FIXTURES

THE ABOVE IS A STANDARD SUBMITTAL REQUIREMENT LIST. ELECTRICAL CONTRACTOR SHALL SUBMIT ALL APPLICABLE ITEMS FOR REVIEW. MATERIAL NOT SUBMITTED AND APPROVED BY THE ARCHITECT, ENGINEER OR OWNER'S REPRESENTATIVE SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THE CONTRACTORS COST IF

DIRECTED BY THE ARCHITECT, ENGINEER OR THE OWNER'S REPRESENTATIVE.

PART 2 - MATERIALS

A. GENERAL

1. MATERIALS AND EQUIPMENT SHALL BE STANDARD CATALOGED PRODUCTS OF MANUFACTURERS

REGULARLY ENGAGED IN THE MANUFACTURE OF THE PRODUCT. UL LISTED, AND SHALL BE THE LATEST

STANDARD DESIGN THAT CONFORMS TO SPECIFIED MATERIALS AND EQUIPMENT.

B. RACEWAY

1. ELECTRICAL METALLIC TUBING (EMT) SHALL BE USED IN INTERIOR DRY LOCATIONS.

2. GALVANIZED FLEXIBLE STEEL (FMC) OR LIQUID TIGHT STEEL (LFMC) CONDUIT SHALL BE USED FOR

CONNECTIONS TO MECHANICAL EQUIPMENT, LUMINAIRES AND TRANSFORMERS AND AS INDICATED.

LIQUID TIGHT CONDUIT SHALL BE USED IN EXTERIOR OR DAMP LOCATIONS.

3. SCHEDULE 40 PVC (WITH PVC COATED OR VINYL TAPE DOUBLE WRAPPED RIGID STEEL ELBOWS AND RISES)

SHALL BE USED FOR RUNS THAT ARE IN CONTACT WITH THE EARTH.

4. 3/4" CONDUIT SHALL BE THE MINIMUM SIZE CONDUIT.

5. OUTDOOR AND WET OR DAMP LOCATIONS: PROVIDE RIGID STEEL CONDUIT.

C. FITTINGS

1. ALL FITTINGS SHALL BE STEEL/MALLEABLE IRON WITH INSULATING BUSHINGS.

D. OUTLET AND JUNCTION BOXES

1. BOXES IN INTERIOR DRY LOCATIONS SHALL BE GALVANIZED ONE-PIECE PRESSED STEEL, KNOCKOUT TYPE, NOT LESS THAN 4 INCHES SQUARE AND 2 1/8" DEEP; APPLETON, RACO, OR EQUAL.

2. BOXES SHALL BE EQUIPPED WITH PLASTER RINGS, EXTENSION RINGS, AND FIXTURE STUDS AS REQUIRED.

3. BOXES FOR FLOOR OUTLETS SHALL BE OF THE CAST-METAL THREADED-CONDUIT-ENTRANCE,

WATERPROOF TYPE WITH MEANS FOR ADJUSTING COVER PLATE TO FINISHED FLOOR LEVEL. BOXES SHALL BE SUCH AS HUBBELL B2503 OR EQUAL. THE COVER SHALL BE HUBBELL S3925, S3082 OR EQUAL TO

MATCH THE FLOOR TYPE OR AS SHOWN ON THE PLANS.

4. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.

5. BOXES FOR STRUCTURED CABLING (DATA & PHONE) IN INTERIOR DRY LOCATIONS SHALL BE GALVANIZED

ONE-PIECE PRESSED STEEL, KNOCKOUT TYPE 4 11/16" x 2 1/8"; APPLETON, RAYCO OR EQUAL.

6. ALL BOXES IN FINISHED SPACES SHALL BE PROVIDED WITH MUD RINGS AS REQUIRED FOR THE DEVICE AND

WALL MATERIAL.

7. OUTDOOR AND WET OR DAMP LOCATIONS: PROVIDE CAST METAL OR PVC OUTLET, JUNCTION, AND PULL

BOXES.

E. CONDUCTORS

1. ALL CONDUCTORS SHALL BE SOFT DRAWN, ANNEALED COPPER IN RACEWAY SIZED AS SHOWN ON THE

PLANS. ALL CONDUCTORS TO BE MINIMUM #12 AWG UNLESS NOTED OTHERWISE #8 AWG AND LARGER

SHALL BE STRANDED.

2. CONDUCTORS SHALL BE COPPER, THHN OR THWN-2 COLOR CODED IN ACCORDANCE WITH PART 3, SECTION C. 1. OF THESE SPECIFICATIONS OR AS INDICATED ON THE DRAWINGS.

F. WIRING CONNECTIONS

1. MAKE ALL ELECTRICAL CONNECTIONS.

2. MAKE CONNECTION TO DEVICES USING "PIG-TAILS". DO NOT USE A DEVICE AS A CONNECTION OR A SPLICE

UNIT.

3. DO NOT PLACE STRANDED CONDUCTORS DIRECTLY UNDER SCREWS. INSTALL CRIMP-ON, INSULATED, FORK

TERMINALS FOR CONDUCTOR TERMINATIONS, OR INSTALL SOLID CONDUCTORS.

G. NAMEPLATES

1. PROVIDE EACH PANEL BOARD, DISCONNECT SWITCH, AND BREAKER IN SWITCHBOARD WITH A MICARTA

PLASTIC NAMEPLATE MADE OF WHITE-FACED BLACKCORE PLASTIC LAMINATE. NAMEPLATE SHALL BE MINIMUM 3" WIDE BY 3/4" HIGH FOR PANEL BOARD IDENTIFICATION INCLUDE DESIGNATION, PHASE, VOLTAGE, AND CIRCUIT NUMBER. FASTEN WITH EPOXY GLUE. DOUBLE STICK TAPE IS NOT ACCEPTABLE.

J. FRACTIONAL HORSEPOWER MANUAL STARTER

1. PROVIDE FRACTIONAL HORSEPOWER MANUAL STARTER WITH THE FOLLOWING FEATURES.

a. MELTING ALLOY TYPE THERMAL OVERLOAD RELAY

b. RED NEON PILOT LIGHT

c. THERMAL ELEMENT SIZED FOR MOTOR LOAD

2. PROVIDE A NAMEPLATE ON EACH COMPONENT OF MOTOR CONTROL EQUIPMENT AS SPECIFIED IN

"NAMEPLATES".

K. SAFETY SWITCHES

1. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL SAFETY SWITCHES AS INDICATED ON THE

DRAWINGS OR AS REQUIRED. ALL SAFETY SWITCHES SHALL BE UL LISTED. THE SWITCHES SHALL BE

FUSED SAFETY SWITCHES OR NON-FUSED SAFETY SWITCHES AS SHOWN ON THE DRAWINGS OR

REQUIRED BY CODE AND SHALL BE MANUFACTURED BY SQUARE D, GENERAL ELECTRIC, SIEMENS OR

CUTLER HAMMER.

2. SWITCHES SHALL HAVE A QUICK-MAKE AND QUICK-BREAK OPERATING HANDLE AND MECHANISM WHICH SHALL BE AN INTEGRAL PART OF THE BOX. PADLOCKING PROVISIONS SHALL BE PROVIDED FOR PADLOCKING IN THE OFF POSITION WITH AT LEAST THREE PADLOCKS. SWITCHES SHALL BE HORSEPOWER RATED FOR 250 VOLTS AC OR DC OR 600 VOLTS AC AS REQUIRED. LUGS SHALL BE UL LISTED FOR COPPER

AND ALUMINUM CABLE AND SHALL HAVE A TEMPERATURE RATING OF AT LEAST 75 DEGREES C.

3. SWITCHES SHALL BE FURNISHED IN NEMA 1 HEAVY DUTY ENCLOSURES WITH KNOCKOUTS UNLESS OTHERWISE NOTED OR REQUIRED. SWITCHES LOCATED ON THE EXTERIOR OF THE BUILDING OR IN "WET"

LOCATIONS SHALL HAVE NEMA 3R ENCLOSURES (WP).

4. THE SAFETY SWITCHES SHALL BE SECURELY MOUNTED IN ACCORDANCE WITH THE NEC. THE

CONTRACTOR SHALL PROVIDE ALL MOUNTING MATERIALS AND INSTALL FUSES IN THE FUSED SAFETY

SWITCHES. THE FUSES SHALL BE DUAL ELEMENT ON MOTOR CIRCUITS.

5. PROVIDE FUSES AS SPECIFIED BELOW. FUSES SHALL BE INSTALLED SO THAT THE RATING IS CLEARLY

VISIBLE WITHOUT REMOVING FUSE. PROVIDE A SPARE FUSE FOR EACH FUSE INSTALLED.

6. PROVIDE A NAMEPLATE ON EACH DISCONNECT SWITCH AS SPECIFIED IN "NAMEPLATES".

L. FUSES

1. FUSES SHALL BE CLASS "RK-1" REJECTION TYPE. FUSES SERVING MOTOR LOADS SHALL BE DUAL

ELEMENT WITH A MINIMUM TIME DELAY OF 10 SECONDS AT 500% RATING. FUSES SHALL BE CURRENT LIMITING TIME DELAY TYPE WITH INTERRUPTING CAPACITY OF 200,000 AMP RMS SYMMETRICAL.

2. FUSES SERVING SWITCH OR CIRCUIT BREAKER DISTRIBUTION PANELS, LIGHTING PANEL BOARDS AND OTHER NON - MOTOR LOADS NEED NOT BE TIME DELAY TYPE, BUT SHALL BE CURRENT LIMITING WITH

THE INTERRUPTING CAPACITY OF 200,000AMP RMS SYMMETRICAL MINIMUM. FUSES SHALL BE

BUSSMAN, GOULD OR LITTELFUSE.

3. PROVIDE FUSES SIZED TO THE MAXIMUM SIZE RECOMMENDED BY THE MANUFACTURER OF THE

EQUIPMENT OR AS SHOWN ON THE DRAWINGS IF THE MANUFACTURER DOES NOT HAVE A

RECOMMENDED SIZE.

PART 3 - EXECUTION

A. GENERAL

1. ALL MATERIALS SHALL BE INSTALLED IN A PROFESSIONAL MANNER INDICATIVE OF THE TRADE.

2. ALL PENETRATIONS OF THE OUTSIDE WALLS OR ROOF SHALL BE SEALED WITH APPROPRIATE SEALANT OR

CAULK FOR THE PARTICULAR SURFACE INVOLVED.

3. PROVIDE CLEAR, TYPED, P-TOUCH LABEL FOR ALL RECEPTACLES COVERPLATES IDENTIFYING THE CIRCUIT

NUMBER THAT THE RECEPTACLE IS CIRCUITED TO.

4. PROVIDE UPDATED TYPED PANEL SCHEDULE INDEX FOR ALL PANELS WHERE CIRCUITS HAVE BEEN MODIFIED

OR CHANGED.

B. RACEWAYS

1. RACEWAYS SHALL RUN CONCEALED UNLESS OTHERWISE INDICATED. EXPOSED RACEWAY RUNS SHALL BE

PARALLEL WITH SUPPORTING WALLS, BEAMS, AND CEILINGS AND WITH EACH OTHER CLOSER THAN 6

INCHES TO ANY WATER PIPE OR HEATER BE INSTALLED AND SHALL NOT FLUME.

2. RACEWAY ENDS SHALL BE REAMED AFTER THREADING AND AFTER CUTTING AND BE MADE TO BUTT IN THE

CENTER OF THE COUPLING. THE USE OF RUNNING THREADS IS PROHIBITED.

3. RACEWAYS SHALL BE INSTALLED AS A COMPLETE SYSTEM, CONTINUOUS FROM OUTLET TO OUTLET, CABINET, BOX OR FITTINGS, AND SHALL BE MECHANICALLY CONNECTED SO THAT ADEQUATE ELECTRICAL CONTINUITY FROM ONE TO ANOTHER IS OBTAINED. CONDUITS SHALL BE SUPPORTED WITH ONE OR TWO HOLE STAMPED STEEL OR MALLEABLE IRON STRAPS (SUCH AS MANUFACTURED BY RACO) DESIGNED FOR SUPPORTING CONDUIT. THE SIZE OF STRAP SHALL MATCH THE SIZE OF THE CONDUIT. NAILS, PERFORATED STRAP, OR PLUMBERS TAPE SHALL NOT BE USED FOR SUPPORT OF RACEWAY.

4. PROVIDE 1/8" POLY PULL CORD IN RACEWAYS WITHOUT CONDUCTORS.

5. FOUR 90 DEGREE BENDS MAXIMUM BETWEEN TERMINATIONS OR BOXES.

C. CONDUCTORS

1. ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT AND COLOR CODED AS FOLLOWS:

PHASE 240/120 208/120 480/277

PHASE A BLACK BLACK BROWN

PHASE B RED RED ORANGE

PHASE C - BLUE YELLOW

NEUTRAL WHITE WHITE GRAY

GROUND GREEN GREEN GREEN

2. MAKE JOINTS, SPLICES, TAPS AND CONNECTIONS IN CONDUCTORS WITH SOLDERLESS CONNECTORS.

D. JUNCTION AND PULL BOXES

1. PULL BOXES SHALL BE PROVIDED WHERE INDICATED AND WHERE NECESSARY TO FACILITATE THE PULLING

OF CONDUCTORS. TELEPHONE RACEWAYS SHALL HAVE A MAXIMUM OF TWO 90 DEGREE BENDS BETWEEN

TERMINATIONS OR BOXES.

E. GROUNDING

1. INSTALL A CODE SIZED GROUNDING CONDUCTOR IN ALL RACEWAYS. DO NOT USE THE RACEWAY FOR

GROUNDING. MAKE GOOD CONTACT AT ALL PANEL BOARDS, OUTLET BOXES, AND JUNCTION OR PULL

BOXES TO THE RACEWAY SYSTEM. USE APPROVED BONDING MATERIALS.

G. BONDING

1. BOND ALL PIPING (GAS WATER, ETC) AS REQUIRED BY THE NEC. CONFIRM SYSTEMS TO BE USED WITH MC.

H. SEISMIC REQUIREMENTS

1. IF REQUIRED, RECESSED TYPE LIGHTING FIXTURES, IN ADDITION TO THE STANDARD SEISMIC CLIPS AND

SUPPORT ON T-BAR GRID SYSTEM, SHALL HAVE 2#12 STEEL SAFETY WIRES PER FIXTURE. ONE END OF EACH SAFETY WIRE SHALL BE SECURELY FASTENED TO THE BUILDING STRUCTURE. THE OTHER END (6 INCHES LONGER THAN THE T-BAR GRID SUPPORT WIRES) SHALL BE FASTENED TO DIAGONAL CORNERS OF

EACH LIGHTING FIXTURE.

I. CUTTING AND PATCHING

1. PERFORM DRILLING, CUTTING, AND PATCHING OF THE GENERAL CONSTRUCTION WORK WHETHER EXISTING

OR NEW, AS REQUIRED FOR THE INSTALLATION OF ELECTRICAL WORK. PATCH WITH THE SAME

MATERIALS, WORKMANSHIP, AND FINISH AS THE ORIGINAL WORK AND ACCURATELY MATCH ALL

SURROUNDING WORK. SUCH WORK WILL BE DONE BY A CRAFTSMAN ACCREDITED IN THE APPLICABLE

TRADE UNDER THE CONTRACTOR'S SUPERVISION AND BE ACCEPTABLE TO THE OWNER'S

REPRESENTATIVE. COORDINATE WITH OTHER TRADES AND GENERAL CONTRACTOR PRIOR TO CUTTING, DRILLING, OR CORING.

K. TESTING

1. DEMONSTRATE THAT ALL COMPONENTS OF THE WORK OF THIS DIVISION HAVE BEEN PROVIDED AND THAT

THEY OPERATE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

2. TEST WIRING AND CONNECTORS FOR CONTINUITY, SHORT CIRCUITS AND IMPROPER GROUNDS. TEST EACH

LIGHTING AND APPLIANCE PANEL WITH MAINS DISCONNECTED FROM FEEDERS, BRANCHES CONNECTED, WALL SWITCHES CLOSED AND FIXTURES PERMANENTLY CONNECTED AND COMPLETE WITH LAMPS. TEST EACH INDIVIDUAL POWER CIRCUIT WITH THE POWER EQUIPMENT CONNECTED FOR PROPER OPERATION.

3. PROVIDE DETAILED DOCUMENTATION OF EACH TEST PERFORMED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE, WITH THE NAMES AND THE SIGNATURES OF QUALIFIED INDIVIDUALS WHO CONDUCTED

AND WITNESSED EACH TEST.

PART 4 - VARIABLE FREQUENCY MOTOR CONTROLLERS

1.1 SUBMITTALS

A. PRODUCT DATA: FOR EACH TYPE AND RATING OF VFC INDICATED.

1. INCLUDE DIMENSIONS AND FINISHES FOR VFCS.

2. INCLUDE RATED CAPACITIES, OPERATING CHARACTERISTICS, ELECTRICAL CHARACTERISTIC, AND

FURNISHED SPECIAL AND ACCESSORIES.

B. SHOP DRAWINGS: FOR EACH VFC INDICATED.

1. INCLUDE MOUNTING AND ATTACHMENT DETAILS.

2. INCLUDE DETAILS OF EQUIPMENT ASSEMBLIES. INDICATE DIMENSIONS, WEIGHTS, LOADS, REQUIRED

CLEARANCES, METHOD OF FIELD ASSEMBLY, COMPONENTS, AND LOCATION AND SIZE OF EACH

FIELD CONNECTION.

3. INCLUDE DIAGRAMS FOR POWER, SIGNAL, AND CONTROL WIRING.

C. WARRANTY: MANUFACTURER AGREES TO REPAIR OR REPLACE VFCS…