6-2-CR27023-27136420 Approved Plans.pdf
PDF 8 MB Posted
- Solicitation number
- CR27023
- Issued by
- Utah
About this file
Construction Documents Summary
These are approved construction plans and specifications for the Utah State Hospital Forensics Mechanical Room Upgrade project located in Provo, Utah, prepared by Resolut Group engineering firm and approved by the Division of Facilities Construction and Management (DFCM). The project involves replacing existing mechanical equipment in the main Forensics building mechanical room, including two domestic hot water storage tanks (500-gallon AO Smith units), four recirculating pumps (Bell & Gossett PL-30B), two steam-to-domestic hot water heat exchangers (Aerco SWDW24/4), four steam-to-hydronic heat exchangers (Bell & Gossett models), and four primary/standby heating and preheat pumps (Bell & Gossett e-1510 1.5BC). The mechanical scope includes new piping connections, valves, controls, and concrete housekeeping pads, with all existing control valves to remain and existing sequences of operation maintained. The electrical work encompasses new variable frequency drives (VFDs) for pump motors operating at 460/3/60 volts, new motor disconnects, conduit runs, wiring, and control terminations. All materials and equipment specifications comply with 2024 International Building Code, 2024 National Electrical Code, and applicable Utah state standards.
The construction cost estimate is $525,000, with Stage II bidding restricted to contractors prequalified under DFCM's Stage I Prequalification process and listed on the current DFCM Prequalified Contractors list as of the solicitation date. The general notes require contractors to verify existing field conditions, coordinate with mechanical and electrical trades during installation, ensure all equipment fits through existing doorways and openings, extend concrete pads as necessary, and maintain existing circuit integrity where applicable. Contractors must provide updated panel circuit directories, label all receptacles and disconnects, perform comprehensive system testing, and submit detailed documentation including shop drawings, manufacturer certifications, and harmonic analyses for VFD systems. All work must be completed to the satisfaction of the DFCM project reviewer and comply with manufacturer recommendations and local code requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
07/31/2026
260251
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
DFCM APPROVAL STAMP
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 8325442-2202
S TA T E O F U TAH
JACOB D.
BECK
07-31-26
JD
08/12/2026 CODE REVIEW
C001
COVER SHEET
DFCM Project No. 27136420
CONSTRUCTION DOCUMENTS
Vicinity Map
C001 COVER SHEET
MECHANICAL
M001 MECHANICAL SYMBOLS AND ABBREVIATIONS
M101 MECHANICAL OVERALL PLAN
M401 MECHANICAL ENLARGED PLAN
M501 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
ELECTRICAL
EG001 INDEX SYMBOLS & NOTES
EO100 ELECTRICAL OVERALL PLAN
EP401 ELECTRICAL ENLARGED PLANS
SHEET INDEX
UTAH STATE HOSPITAL FORENSICS
Provo, Utah 84603
MECHANICAL ROOM UPGRADE
PROJECT SITE
PROVO, UTAH
NORTH
MECHANICAL ENGINEER: RESOLUT GROUP
181 EAST 5600 SOUTH
MURRAY, UT 84107
(801) 530-3148 (JACOB BECK)
ELECTRICAL ENGINEER: RESOLUT GROUP
181 EAST 5600 SOUTH
MURRAY, UT 84107
(801) 797-5346 (LEWIS WONG)
CONSULTANTS
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)________
1) One Story: ______
c) Total Allowable Area for:
N/A (NON-SEPARATED OCCUPANCIES)
b) Sum of the Ratio Calculations for Mixed Occupancies:
a) 0.25I = 100f F P 30
WstA I 100100 fIA t taA = A + +
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
d) Drinking Fountains: ______ Service Sinks: ______
c) Bath Tubs or Showers: ______
b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: ______ Exit Width Provided: ______
Element Hours Assembly ListingListing
Element AssemblyHours
Smoke Partitions Fire Partitions
Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls Structural Frame Partitions - Permanent Fire Barriers
Floors - Ceiling Floors Roofs - Ceiling Roofs Exterior Doors and Windows Shaft Enclosures Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: ______
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
_____________________________________________________Tabular Area:I:
per Floor (square feet): _________________________________________Actual AreaH:
Number of Stories: ______ Building Height: ___________G:
Required: ______ Provided: _________ Type of Sprinkler System: __________
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code
Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: _______ ________ ________ ________ ________
CODE ANALYSIS
N
N N
I-3
X X
NO
N/AN/A
NR NR NR NR
NO
YES YES NFPA 13
1 30' - 8"
70,908
N/A
3) Deferred Submittals:
a) Seismic Bracing for Mechanical and Electrical. Work related to the deferred
N/A
N/AX
UL
submittals shall not commence until the building official has approved the submittal.
N/A
160 FT
N/A
B A-3
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/02/2026
REVIEWED FOR CODE
COMPLIANCE
PS
N
LB/HR.GPM
3-1" SLOTS
@ 48" 400
W R
12/12
45°D
FD
FSD
SD
OR
8/8
1.25D
AD
LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS
12/8 FO
ATC
CF
LATERAL STRAINER WITH BLOW-OFF VALVE, PROVIDE
HOSE END WITH CAP WHERE DISCHARGE IS NOT PIPED
TO DRAIN
F&T
AW
AV
HP(NAME)
N20
(NAME)
R
SINGLE DUCT AIR TERMINAL BOX VARIABLE OR
CONSTANT VOLUME. MIN. 1-1/2 TERMINAL INLET SIZE
STRAIGHT DUCT AT TERMINAL INLET.
HEATING OR COOLING COIL IN DUCT
ACCESS PANEL IN DUCT OR PLENUM
ATC DAMPER
SMOKE DAMPER W/ ACCESS PANEL
COMBINATION FIRE/SMOKE DAMPER W/ ACCESS PANEL
FIRE DAMPER IN DUCT, W/ ACCESS PANEL REQD.
MANUAL VOLUME DAMPER
HIGH EFFICIENCY FITTING
TAP ENTRY AREA EQUALS 150% OF BRANCH AREA
BRANCH DUCT SPLIT WITH 6" WIDTH AND MIN.
R=WIDTH OF BRANCH DUCT DOWNSTREAM. ELBOW
TURNING VANE OPTIONAL.
RECTANGULAR TO ROUND DUCT TRANSFORMATION
RECTANGULAR TO RECTANGULAR OR ROUND TO ROUND
DUCT TRANSFORMATION MAXIMUM 15° INCLUDED ANGLE
EXCEPT WHERE SHOWN OTHERWISE.
R/W=1. ROUND DUCT SIMILAR TO RECTANGULAR
INCLINED DROP
INCLINED RISE WITH RESPECT TO AIR FLOW 15°
NOMINAL INCLINE WITH RADIUS
TURNS=DEPTH OF DUCT.
ROUND DUCT WITH FREE AREA DIMENSIONS
SHOWN IN INCHES.
RECTANGULAR DUCT WITH FREE AREA
DIMENSIONS SHOWN IN INCHES.
FLAT OVAL DUCT WITH FREE AREA
DIMENSIONS SHOWN IN INCHES.
FAN
FLEXIBLE DUCT
FLEXIBLE DUCT CONNECTION
LINEAR DIFFUSER WITH PLENUM AND FLEXIBLE DUCT
CONNECTION. NO. OF SLOTS & SIZE OF SLOT ON TOP, ACTIVE
LENGTH AND CFM ON BOTTOM
CEILING AIR GRILLE WITH
FLEXIBLE DUCT
CEILING SUPPLY DIFFUSER
WITH FLEXIBLE DUCT
SIDEWALL EXHAUST OR
RETURN REGISTER
SIDEWALL SUPPLY REGISTER
CEILING EXHAUST REGISTER,
(BALANCE TO MATCH SUPPLY IF
RETURN CFM IS NOT SHOWN)
CEILING RETURN REGISTER
CEILING SUPPLY DIFFUSER
RELIEF AIR OR EXHAUST AIR LOUVER
FRESH AIR LOUVER
TURNING VANES
UNDER FLOOR DUCT
ROUND DUCT - DROP
ROUND DUCT - RISE
NEGATIVE PRESSURE DUCT - DROP
TOP FIGURES INDICATE
NECK SIZE. BOTTOM
FIGURE INDICATES CFM.
12/8
12Ø
UP
DN
12/12 12Ø
1.5D
D
12Ø 12/12
FLANGE
PRESSURE GAUGE WITH PIGTAIL
PRESSURE GAUGE WITH SHUT-OFF COCK
ANCHOR
DEMOLITION
ALIGNMENT GUIDE
FLEXIBLE EXPANSION JOINT
SOLENOID VALVE
CHEMICAL FEED
HELICOPTER FUEL RETURN
HELICOPTER FUEL SUPPLY
FUEL OIL RETURN
FUEL OIL SUPPLY
HOT GAS
EXISTING PIPING TO BE REMOVED
LIQUIFIED PETROLEUM GAS
GLYCOL PIPING SOLUTION
GLYCOL HEAT RECOVERY PIPING
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
EXISTING PIPING
NATURAL GAS
MAKE UP WATER
BOILER FEED WATER
BOILER BLOW DOWN
HIGH PRESSURE STEAM
MEDIUM PRESSURE STEAM
LOW PRESSURE STEAM
HIGH PRESSURE CONDENSATE
LOW PRESSURE CONDENSATE
HFR
HFS
FOR
FOS
HG
(NAME)
LPG
G(NAME)
GHR
HWR
HWS
E(NAME)
G
MUW
BF
BBD
HPS
MPS
LPS
HPC
LPC
DN
UNION
FLOW METER ORIFICE
FLOW SWITCH
TEMPERATURE AND PRESSURE TEST PORT
PRESSURE SWITCH
PRESSURE REDUCING, SELF CONTAINED VALVE
PRESSURE REDUCING, EXTERNAL PRESSURE VALVE
BALL VALVE (PIPE SIZES 2" AND SMALLER) BUTTERFLY
VALVE (PIPE SIZES 2-1/2" AND LARGER)
CHECK VALVE
MOTOR OPERATED BUTTERFLY VALVE
GAS COCK
RELIEF VALVE
GATE VALVE
ATC VALVE - 2 WAY
ATC VALVE - 3 WAY
GLOBE VALVE
CALIBRATED BALANCING VALVE
WITH GPM INDICATED
SHUT-OFF COCK FOR USE WITH PRESSURE GAUGE
FLOW METER
90° ELBOW
45° ELBOW
THERMOMETER - TEMP RANGE AS INDICATED
NIGHT THERMOSTAT
STEAM TRAP, F&T=FLOAT & THERMOSTATIC
B=BUCKET, T=THERMOSTATIC
ARROW INDICATES DIRECTION OF FLOW IN PIPE
LEADER INDICATES DOWNWARD SLOPE
RISER - DOWN (ELBOW)
RISER - UP (ELBOW)
BRANCH - SIDE CONNECTION
NRS GATE VALVE WITH SUPERVISION
FLOW SWITCH
HOSE VALVE
CLEAN-OUT
FLOOR CLEAN-OUT OR
CLEAN-OUT TO GRADE
VENT THRU ROOF
DOMESTIC COLD WATER (DCW)
DOMESTIC HOT WATER (DHW)
DOMESTIC HOT WATER RETURN (DHWR)
PLUMBING FIXTURES
POINT OF CONNECTION
SECTION TAG - TOP FIGURE IS SECTION NO.
BOTTOM FIGURE IS SHEET NO.
DETAIL TAG - TOP FIGURE IS DETAIL NO.
BOTTOM FIGURE IS SHEET NO.
EQUIPMENT IDENTIFICATION
KEYED NOTE IDENTIFICATION
ACID WASTE
ACID VENT
HIGH PRESSURE DOMESTIC WATER
MEDICAL OXYGEN
MEDICAL AIR
MEDICAL AIR AT PRESSURE INDICATED
MEDICAL VACUUM
NITROGEN
NITROUS OXIDE
CARBON DIOXIDE
COMPRESSED AIR
LAB AIR
LAB VACUUM
BRINE
FIXTURE FROM LEVEL ABOVE
P-1
EF
OX
MA
MA 120
MV
N
C02
CA
LA
LV
B
A M-101
A
M101
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CR
CS
CHWR
CHWS
INSTRUMENT AIR
INSTRUMENT AIR AT PRESSURE INDICATED
IA
IA 120
MEDIUM PRESSURE CONDENSATEMPC
BRANCH - BOTTOM CONNECTION
BRANCH - TOP CONNECTION
MECHANICAL
FIRE RISER
SPRINKLER HEAD
FLOOR SINK
FLOOR DRAIN
AIR VENT-MANUAL
AIR VENT-AUTO
REDUCER
HOSE BIBB
PIPE CAP
SWITCH
THERMOSTAT
SENSOR
ROOF DRAIN
DOWNSPOUT NOZZLE
INLINE PUMP
INLINE PUMP
WATER HAMMER ARRESTOR
CONCENTRIC REDUCER
ECCENTRIC REDUCER
CEILING RETURN AIR GRILLE
W/ SOUND BOOT
BDD
BACK DRAFT DAMPER
POSITIVE PRESSURE DUCT - RISE
POSITIVE PRESSURE DUCT - DROP
NEGATIVE PRESSURE DUCT - RISE
1-WAY BLOW PATTERN
2-WAY BLOW PATTERN
2-WAY BLOW PATTERN
3-WAY BLOW PATTERN
4-WAY BLOW PATTERN
DUCT SMOKE DETECTOR
UNIT HEATER
SW
OX 120
REFRIGERANT SUCTION
REFRIGERANT LIQUID
PUMPED CONDENSATE
VACUUM
RS
RL
V
ROOF DRAIN
ROOF DRAIN OVERFLOW
SEWER (BELOW GRADE)
SEWER (ABOVE GRADE)
VENT (SEWER)
SOFT DOMESTIC WATER (SW)
REVERSE OSMOSIS WATER RETURN
MEDICAL OXYGEN AT PRESSURE INDICATED
RDO
RD
ROR
FCO
COTG
GATE VALVE - NON RISING STEM
ANGLE VALVE
BALANCING COCK
VALVE IN RISE
FILL PORT
DRAIN PAN AND P-TRAP
PLUMBING PLUMBING CONT. LINETYPES LINETYPES CONT.
SYMBOLS
FIRE
FIRE SPRINKLER WATERF
RISE OR DROP
DI DEIONIZED WATER SUPPLY
DEIONIZED WATER RETURNDIR
RO REVERSE OSMOSIS WATER SUPPLY
FUEL OIL VENTFOV
REDUCED PRESSURE BACKFLOW
PREVENTOR W/ DRAIN PAN LUBRICATED PLUG COCK
THERMOSTATIC MIXING VALVE
07/31/2026
260251
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-31-26
JD
M001
MECHANICAL
SYMBOLS AND
ABBREVIATIONS
GENERAL NOTES
1. ALL BUILDING CONTROLS SHALL BE DISCONNECTED
FROM EXISTING EQUIPMENT AND RECONNECTED TO
NEW EQUIPMENT AS REQUIRED. EXISTING CONTROL
VALVES SHALL REMAIN. EXISTING SEQUENCE OF
OPERATIONS SHALL REMAIN.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/02/2026
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-31-26
JD
M101
MECHANICAL
OVERALL PLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/02/2026
1 1
1(E)3"
(E)3"
(E)3"(E)5"
(E)4"
(E)4" (E)4"
(E)2"
(E)8"
(E) LPS
(E)6" (E)6"
(E) LPC
HX
HX
HX
HX
DHX
DHX
ST
ST
P
P
P
P
(E)5"
(E)4"
(E)4" (E)4"
(E)2"
(E)8"
(E) LPS
(E)6" (E)6"
(E) LPC
(TYP.)
3"3"3"3"
4"
3"
3"
3"
3"
4"4"4" 4" 4"
2-1/2"
3/4"
2-1/2"2-1/2"2-1/2"2-1/2"
(TYP.)
DHX
DHX
ST
DCP
DCP
ST
DCP
DCP
(TYP.)
07/31/2026
260251
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-31-26
JD
KEYED NOTES#
1. DEMOLISH AND REMOVE EXISTING EQUIPMENT, PIPING, AND
ASSOCIATED ACCESSORIES. TYPICAL OF ALL. FIELD VERIFY
EXISTING CONDITIONS.
2. EXISTING CONTROL VALVES SHALL REMAIN. TYPICAL OF ALL.
FIELD VERIFY.
3. CONNECT NEW PIPING TO EXISTING. FIELD VERIFY EXISTING
CONDITIONS. TYPICAL.
M401
MECHANICAL
ENLARGED PLAN
GENERAL NOTES
1. EXTEND CONCRETE HOUSEKEEPING PAD AS NECESSARY TO
ACCOMMODATE NEW EQUIPMENT INSTALLATION.
2. ALL DEMOLISHED EQUIPMENT AND NEW EQUIPMENT SHALL FIT
THROUGH EXISTING DOORS AND OPENINGS. FIELD VERIFY
EXISTING CONDITIONS.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/02/2026
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-31-26
JD
M501
MECHANICAL
DETAILS
BUTTERFLY VALVE (TYPICAL)
RETURNSUPPLY
FLEXIBLE CONNECTION. SEE
SPECIFICATIONS (TYPICAL)
PRESSURE GAUGE WITH
SHUT-OFF COCKS AND
SNUBBER
SUCTION DIFFUSER
STEEL SUPPORT LEG WITH
ADJUSTABLE FOOT
STRAINER BLOW DOWN FULL
SIZE TO FLOOR WITH CAP
CONCRETE BASE WITH #4 BARS 12" OC
EACH WAY BEVEL EDGE ALL AROUND.
GROUT BASE PER SPECIFICATIONS.
EXTEND EXISTING 4" CONCRETE
HOUSEKEEPING PAD AS NEEDED TO
ACCOMMODATE NEW EQUIPMENT.
CHECK VALVE
THERMOMETER
UNION OR VICTUALIC
COUPLINGS (TYPICAL)
CLEARANCE TO REMOVE
MOTOR AND IMPELLER
WITHOUT DISCONNECTING
PIPING
3/8" ANCHOR BOLT WITH NUT
AND WASHER (TYPICAL)
VIBRO-ACOUSTICS CIB
SPRING INERTIA BASE
ISOLATOR PAD SEE
SPECIFICATIONS (TYPICAL)
BALANCING VALVE (NOT
REQUIRED FOR VARIABLE
SPEED PUMP)
VENTURI FLOW MEASURING STATION.
MAINTAIN 6 DIAMETERS UPSTREAM / 3
DIAMETERS DOWNSTREAM OF
STRAIGHT PIPING
PLATE (ALL LEGS)
6" x 6" x i" STEEL
3" x 3" x r"
FRONT ELEVATIONSIDE ELEVATION
SUPPORTING STRUCTURE
3" x 3" x r" ALL AROUND
8" x 8" x i" STEEL
PLATE (ALL LEGS)
s
FLOOR LINE
4"
2 x HEAT EXCHANGER
DIAMETER
s
4'- 0"
HEAT EXCHANGER
CAST STEEL SADDLE
BOLT SADDLE
TO FRAME
HEAT EXCHANGER
SADDLE
CAST STEEL
T
C
T
C
RELIEF VALVE (TYP.)
UNION (TYP.)
AGA RATED TEMP. AND
SHUT-OFF VALVE (TYP.)
(E) CONDENSATE OUT
(TYPICAL)
(TYPICAL)
CHECK VALVE
STEAM TRAP
DHW SUPPLY
FROM STEAM HEADER
DCW SUPPLY
NOTE: PROVIDE
CONCRETE BASE BELOW
WATER HEATERS
HEIGHT AS REQUIRED
FOR GRAVITY FLOW OF
CONDENSATE TO
CONDENSATE PUMP
INLET
SHUT-OFF VALVE (TYP.)
CONTROL VALVE, TYPICAL
STRAINER (TYP.)
(E)4"
3"
3" (E)3"
(E)3"
4"
4"
2-1/2"
(E)4"
(E)4"
LOCATE NEAR FLOOR FOR
EASY SERVICING
FLOW CONTROL VALVE
GLOBE VALVE (TYP)
1/2" LINE TO
SUCTION SIDE OF
PUMP
SCREEN
1/2" GLOBE VALVE
FOR DRAIN
CHECK VALVE
1/2" LINE FROM
PRESSURE SIDE OF
PUMP
STRAINER BLOWDOWN (TYPICAL)
CHECK VALVE (TYPICAL)
AUTOMATIC VALVE-ATC
SHUT-OFF VALVE (TYPICAL)
SYSTEM PIPING
FLOW SETTER
F&T TRAP
DRAIN VALVES
TO EXISTING FLOOR DRAIN
(E)CONDENSATE RETURN
12" LONGMIN, DRIP LEG
VACUUM BREAKER
RELIEF VALVE
STRAINER W/ BLOWOFF
GATE VAVLE
(E)STEAM SUPPLY
REDUCER (TYP.)
(E)AUTO CONTROL VALVE (1/3 - 2/3)
P
P
HEAT EXCHANGER
(E)HWS
(E)HWR
EXTEND EXISTING 4"
CONCRETE HOUSEKEEPING
PAD AS NEEDED TO
ACCOMMODATE NEW
EQUIPMENT.
2-1/2"
2-1/2"
2-1/2"
DHX
DHX
ST
ST
DCP
DCP
2 DCP
DCP
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/02/2026
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-31-26
JD
M601
MECHANICAL
SCHEDULES
DOMESTIC STORAGE TANK SCHEDULE
MANUFACTURER WORKING DIA/
AND CAPACITY PRESS. LENGTH
ID MODEL NUMBER SERVICE (GAL) (PSI) (IN) NOTES
ST-1 AO SMITH TJV-500A DOMESTIC HOT WATER 500 125 46 / 91 1,2,3
ST-2 AO SMITH TJV-500A DOMESTIC HOT WATER 500 125 46 / 91 1,2,3
1. VERTICAL FACTORY JACKETED AND INSULATED TANK.
2. HEAVY GAUGE STEEL WITH HIGH QUALITY PAINT. GLASSLINED WITH STANDARD TANK OPENINGS. ASME CONSTRUCTION.
3. TANKS FURNISHED WITH ANODES DESIGNED FOR PROTECTION.
RECIRCULATING PUMP SCHEDULE
FLUID ELECTRICAL
MANUFACTURER FLOW HEAD MOTOR MOTOR
AND RATE WORKING LOSS SIZE SPEED
ID MODEL NUMBER LOCATION TYPE (GPM) FLUID (FT) (HP) (RPM) VOLT/PH/HZ NOTES
DCP-1 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 2 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2
DCP-2 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 10 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2
DCP-3 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 2 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2
DCP-4 BELL & GOSSETT PL-30B MECHANICAL RECIRCULATION 10 DOMESTIC WATER 15 1/6 1750 120/1/60 1,2
1. LEAD FREE BRONZE BODY CONSTRUCTION. STAINLESS STEEL FACE PLATE.
2. PERMANENTLY LUBRICATED MOTOR TYPE.
STEAM-TO-DOMESTIC HOT WATER HEAT EXCHANGER SCHEDULE
SOURCE MEDIUM (STEAM) TRANSFER MEDIUM (HYDRONIC) PHYSICAL
ENTERING/
MANUFACTURER FLOW ENTERING FLOW LEAVING HEAD DIA./
AND LOAD RATE PRESSURE RATE TEMP. WORKING LOSS HEIGHT/
ID MODEL NUMBER LOCATION TYPE USAGE (MBH) (LB/H) (PSIG) (GPM) (°F) FLUID (FT) (IN/IN) NOTES
DHX-1 AERCO SWDW24/4 MECHANICAL RM SHELL AND TUBE DOMESTIC 2033 1911 10 37 40/140 WATER 7.4 16 / 88 1,2,3,4,5
DHX-2 AERCO SWDW24/4 MECHANICAL RM SHELL AND TUBE DOMESTIC 2033 1911 10 37 40/140 WATER 7.4 16 / 88 1,2,3,4,5
1. PROVIDE BACNET GATEWAY INTERFACE WITH BMS FOR MONITORING TEMPERATURE.
2. PROVIDE WITH AERCO STEAM TRAP PART NUMBER 99136-2.
3. UL-LISTED AS DOUBLE-WALL HEAT EXCHANGER FOR POTABLE HOT WATER USE.
4. PROVIDE WITH STAND SUPPORTS.
5. 5 FLA, 120/1 POWER CONNECTION REQUIREMENT.
STEAM-TO-HYDRONIC HEAT EXCHANGER SCHEDULE
SOURCE MEDIUM (STEAM) TRANSFER MEDIUM (HYDRONIC) PHYSICAL
ENTERING/
MANUFACTURER FLOW ENTERING PRESSURE FLOW LEAVING HEAD DIAMETER / SURFACE
AND LOAD RATE PRESSURE DROP RATE TEMP. WORKING LOSS LENGTH AREA
ID MODEL NUMBER LOCATION TYPE USAGE (BTU/H) (LB/H) (PSIG) (PSI) (GPM) (°F) FLUID (PSI) (IN/IN) (FT²) NOTES
HX-1 BELL & GOSSETT SU-85-4 MECH SHELL & TUBE HYDRONIC 1,276 1,320 5 1 87 150 / 180 WATER 4 14 / 66 41.9 - HX-2 BELL & GOSSETT SU-85-4 MECH SHELL & TUBE HYDRONIC 1,276 1,320 5 1 87 150 / 180 WATER 4 14 / 66 41.9 -
HX-4 BELL & GOSSETT SU-84-4 MECH SHELL & TUBE PREHEAT 1,087 1,148 5 1 82 85 / 115 50% PG 5 14 / 54 33.3 - HX-5 BELL & GOSSETT SU-84-4 MECH SHELL & TUBE PREHEAT 1,087 1,148 5 1 82 85 / 115 50% PG 5 14 / 54 33.3 -
PUMP SCHEDULE
FLUID PUMP ELECTRICAL
MANUFACTURER FLOW HEAD MOTOR MOTOR MOTOR
AND RATE WORKING LOSS EFFICIENCY SIZE BHP SPEED
ID MODEL NUMBER SYSTEM LOCATION TYPE (GPM) FLUID (FT) (%) CONSTRUCTION (HP) (HP) (RPM) VOLT/PH/HZ NOTES P-1 BELL & GOSSETT e-1510 1.5BC HEATING MECH ROOM BASE-MOUNTED 87 WATER 55 58% CAST IRON 3 2.1 1750 460/3/30 1,2,3,4
P-2 BELL & GOSSETT e-1510 1.5BC HEATING MECH ROOM BASE-MOUNTED 87 WATER 55 58% CAST IRON 3 2.1 1750 460/3/30 1,2,3,4
P-3 BELL & GOSSETT e-1510 1.5BC PREHEAT MECH ROOM BASE-MOUNTED 82 50% PG 55 54% CAST IRON 3 1.9 1750 460/3/30 1,2,3
P-4 BELL & GOSSETT e-1510 1.5BC PREHEAT MECH ROOM BASE-MOUNTED 82 50% PG 55 54% CAST IRON 3 1.9 1750 460/3/30 1,2,3
1. BASE-MOUNTED END SUCTION CENTRIFUGAL PUMP
2. PUMPS ARE PRIMARY / STANDBY
3. VFD BY ELECTRICAL
4. MOTOR SHALL BE VFD COMPATIBLE
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/02/2026
EG001
INDEX SYMBOLS &
NOTES
7/31/2026
260251
ST
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
SA
PM: SYDNEE ANDERSON
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
14275529
S TAT E O F U TAH
SANG TRUONG
No.
6"
CL
LC
NOTES:
1. TYP. FOR WOOD AND METAL STUD ROUGH-IN.
2. PLASTER RINGS NOT SHOWN. COORDINATE RING DEPTH TO BE FLUSH
WITH FINISHED SURFACE, UNLESS NOTED OTHERWISE.
3. LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCH. AND MECH.
DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.
4. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR PARTITIONS IN THE
SAME STUD SPACE MUST BE SEPARATED BY A MIN. OF 6" HORIZONTAL DISTANCE.
5. ELECTRICAL BOXES INSTALLED IN FIRE RESISTANT WALLS OR PARTITIONS
SHALL COMPLY WITH IBC 714.3.2.
6. INSULATED THROAT EMT CONNECTOR.
7. CADDY FASTENER, THROUGH STUD CABLE/CONDUIT SUPPORT 'FB12P'.
8. ADJUSTABLE BAR HANGER.
9. TYPICAL DEVICE JUNCTION BOX.
(TYP.)
EMT
5 4
(TYP.)
EMT
EMT
EMT
EG001
6 TYPICAL ROUGH-IN
NO SCALE
(S) (S) SIMPLEX (D) DUPLEX (Q) QUADPLEX OR DOUBLE DUPLEX(D) (Q)
STANDARD CONVENIENCE OUTLET 18"
CONVENIENCE OUTLET, GFCI 18"
STANDARD CONVENIENCE OUTLET, CUSTOM HEIGHT (6)
48"UNLESS
NOTED
CONVENIENCE OUTLET, GFCI, CUSTOM HEIGHT (6)
48"UNLESS
NOTED
CONVENIENCE OUTLET, FLOOR FLOOR
CONVENIENCE OUTLET, CEILING CEILING
J JUNCTION BOX AS NOTED (12)
J JUNCTION BOX, WALL AS NOTED (12)
J JUNCTION BOX, FLOOR FLOOR (12)
S
M MANUAL MOTOR CONTROLLER SWITCH WITHOUT
TERMINAL OVERLOAD PROTECTION
SWITCH WITH PILOT LIGHTS
P
MANUAL SWITCH WITH THERMAL OVERLOADS
TH
SINGLE POLE DOOR SWITCHS
X
NON-FUSED DISCONNECT SWITCH (13) (14)
FUSED DISCONNECT SWITCH (13) (14)
MAGNETIC STARTER (13) (14)
MAGNETIC STARTER WITH FUSED DISCONNECT (13) (14)
MAGNETIC STARTER WITH BREAKER DISCONNECT (13) (14)
POWER RELAY (13) (14)
MOTOR OUTLET
MOTOR OUTLET, ROOF MOUNTED ROOF
TRANSFORMER SEE PLANS
TRANSFORMER SEE PLANS
EMERGENCY GENERATOR SEE PLANS
MAIN DISTRIBUTION POWER PANEL
PANEL BOARD, SURFACE 6'-6" TO TOP
PANEL BOARD, RECESSED 6'-6" TO TOP
XX
X MECHANICAL/PLUMBING EQUIPMENT CALLOUT
LUMINAIRE TYPE
X
XX.X DIAGRAM/DETAIL CALLOUT
HOME RUN TO PANEL
A AMPS
AFC AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPS INTERR. CAPACITY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
C CONDUIT
CND CONDUIT
CO CONDUIT ONLY
CT CURRENT TRANSDUCER
CU COPPER MATERIAL
DED DEDICATED
DFA DROP FROM ABOVE
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EM EMER./EGRESS BATTERY
EMT ELEC. METALLIC TUBING
ENT ELEC. NON-METAL. TUBING
ER EXISTING TO BE RELOCATED
EX EXISTING TO REMAIN
FMC FLEXIBLE METAL CONDUIT
GC GENERAL CONTRACTOR
GEC GRND. ELEC. COND. AT SES
GFCI GRND. FLT. CURR. INTERR.
GFEP GRND. FLT. EQUIP. PROTECT.
GND GROUND
IMC INTER. METAL CONDUIT
IG ISOLATED GROUND
KCMIL 1000 CIRCULAR MILS (MCM)
LFMC LIQUID-TIGHT FLEX.
METAL. COND.
LFNC LIQUID-TIGHT FLEX.
NON-METAL. COND.
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
N1 NEMA 1
N3R NEMA 3R
N NEW
NL NIGHT LIGHT, BYPASS
LOCAL SWITCHING
PC PLUMBING CONTRACTOR
POC POINT OF CONNECTION
POS POINT OF SALE
R RELOCATED
RX RECEIVER
RM ROOF MOUNTED
RMC RIGID METALLIC CONDUIT
RNC RIGID NON-METALLIC COND.
SBJ SYSTEM BONDING JUMPER
SCA SHORT CIRCUIT AMPERES
TX TRANSMITTER
TC TEMP. CONTROL CONTR.
TR TAMPERPROOF
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
VA VOLT/AMPS
VIF VERIFY IN FIELD
WP WEATHERPROOF/NEMA 3R
XP EXPLOSION PROOF
XR EXISTING TO BE REMOVED
ABBREVIATIONS
(1) SEE LUMINAIRE SCHEDULE FOR FIXTURE TYPES AND DETAILS.
(2) SEE LUMINAIRE SCHEDULE FOR MOUNTING REQUIREMENTS.
(3) WIRE LIGHT FIXTURE FROM ADJACENT J-BOX
(4) CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST
(5) DIRECTIONAL ARROWS INDICATE REQUIRED CHEVRONS.
(6) COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL INTERIOR ELEVATIONS
(7) USE WITH POWER PACK.
(8) "X" IN SYMBOL IS INCHES BETWEEN RECEPTACLE ALONG WIREWAY. SEE DRAWINGS.
(9) PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
(10) MATCH THE VOLTAGE OF THE RELAY WITH THAT OF THE CONTROLLING CIRCUIT.
(11) USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE AND INSTALLATION.
(12) PROVIDE MUD RING AND/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
(13) USE HEAVY DUTY DEVICE FOR 480 VOLT.
(14) SIZE TO THE EQUIPMENT BEING CONTROLLED
(15) FIRE ALARM PANELS: FACP: FIRE ALARM CONTROL PANEL, NAC: NOTIFICATION APPLIANCE CIRCUIT PANEL, ANNUN: GRAPHIC ANNUNCIATOR PANEL, AND SES: SMOKE EVACUATION SYSTEM PANEL.
(16) LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
(17) PROVIDE 5' OF SERVICE LOOP AND TERMINATE IN 2-PORT SURFACE MOUNT BOX.
NOTESNOTES
ELECTRICAL SYMBOL SCHEDULE
SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING
GAP GENERATOR ANNUNCIATOR PANEL SEE PLANS
ATS AUTOMATIC TRANSFER SWITCH SEE PLANS
EQUIPMENT CONNECTION
GENERAL NOTES
1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS ARE TO BE CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT DOCUMENTS AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION OR CONFLICT EXIST IN EITHER THE PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING BEFORE SUBMITTING HIS BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIER SHALL SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE SYSTEMS AT THEIR OWN EXPENSE. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE, THE CONTRACTOR SHALL TEST AND CONFIRM IT'S PROPER OPERATION. ANY INCOMPLETE SYSTEM
SHALL BE MADE COMPLETE AND OPERABLE.
2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE
GREATER THAN SPECIFIED AND/OR DIMENSIONED ON THE PLANS.
3. NO ADDITIONS TO THE CONTRACTOR BID WILL BE ALLOWED FOR CHANGES MADE NECESSARY BY INTERFERENCE WITH OTHER WORK.
4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS AND LABOR FOR THE CONNECTIONS OF ALL EQUIPMENT
SHOWN ON THE PLANS - ARCHITECTURAL, MECHANICAL, ETC.
5. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH LOCAL AND STATE CODES AND THE NEC. IF AT ANY TIME DURING CONSTRUCTION, OR AFTER, SOMETHING IS FOUND TO BE INSTALLED IN VIOLATION OF THE CODES LISTED ABOVE, IT SHALL BE
CORRECTED AT THE CONTRACTORS EXPENSE.
6. ALL EQUIPMENT PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE CONDITIONS AND SPACE THAT
EQUIPMENT IS BEING INSTALLED WITHIN.
7. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED FROM. VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BREAKERS AS NECESSARY FOR A
COMPLETE AND OPERABLE SYSTEM.
8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE TELE/DATA ROOM FROM WHICH NEW TELE/DATA OUTLETS WILL BE FED FROM. VERIFY EXISTING PATCH PANEL SPACES AND PROVIDE NEW PATCH PANELS AS NECESSARY TO
LAND ALL NEW TELE/DATA CABLING.
9. THE ELECTRICAL CONTRACTOR SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR. THE ELECTRICAL CONTRACTOR SHALL GROUND THE ELECTRICAL
SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.
10. THE ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS, CABINETS, DISCONNECT, TRANSFORMERS, ETC. AND SHALL MOVE THE PANELS/EQUIPMENT AT HIS EXPENSE IF REJECTED BY AN INSPECTOR. IF CLEARANCE IS NOT POSSIBLE, THE DESIGNER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.
11. CONDUIT LAYOUTS SHOWN ON THE PLANS ARE DIAGRAMMATIC, NOT INDICATING THE ROUTING REQUIRED. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT, BUILDING STRUCTURE AND OTHER POTENTIAL OBSTRUCTIONS.
12. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE
OF 10 FEET WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.
13. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT IS SET IN PLACE USING INDUSTRY STANDARD
METHODS AND PRACTICES.
14. MINIMUM SIZE CONDUIT SHALL BE 3/4". ABOVE GROUND CONDUIT SHALL BE EMT WITH STEEL SET SCREW FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN DIRECT
CONTACT WITH THE SOIL.
15. FLEXIBLE METAL CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS OF FLEXIBLE OR SEAL-TITE CONDUIT SHALL NOT EXCEED 72” INCHES. USE LFMC IN DAMP
OR WET LOCATIONS.
16. WIRING DEVICES SHALL MATCH EXISTING COLOR AND FACEPLATE TYPE. COLOR TO MATCH ADJACENT ARCHITECTURAL FINISH.
COORDINATE WITH ARCHITECT.
17. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE APPLICATION. ANY DEVICE BOXES NOT SECURED WILL BE MADE SECURE AT THE CONTRACTORS
EXPENSE.
18. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB RATED NYLON PULL CORD.
19. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS, WALLS, ETC.), THEY SHALL BE APPROVED BY THE INSPECTING OFFICER (INSPECTOR). THE UNCOVERING AND REPLACEMENT OF ELECTRICAL WORK FOR THE INSPECTION PURPOSES WILL
BE AT THE COST OF THE ELECTRICAL CONTRACTOR.
20. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120 OR 277VAC BRANCH CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12(CU,THHN/THWN-2)+1#12(CU,THHN/THWN-2)GND IN 3/4” EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10(CU,THHN) FOR 120VAC BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 100' TO ACCOMMODATE FOR VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES AND NOTES ON DRAWINGS FOR ALL OTHER BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.
21. CONDUCTORS SHALL BE COPPER STRANDED, 600VAC RATED, TYPE THHN/THWN-2 UNLESS OTHERWISE NOTED.
22. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS, WIRES, AND OVERCURRENT PROTECTION PRIOR TO ROUGH-IN. THE ELECTRICAL CONTRACTOR SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE DIRECTED BY THE EQUIPMENT SUPPLIER.
23. THE ELECTRICAL CONTRACTOR SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER, PAINT, DIRT, GREASE, UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE
ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FROM THE PREMISES.
24. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE
OF EQUIPMENT AND ADDITIONAL COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.
25. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO PROVIDE CONDUIT AND DEVICE
MOUNTING BOXES FOR THERMOSTATS AND OTHER MECHANICAL CONTROLS.
26. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED WITH THE
ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL BE MADE TO CONCEAL WIRING METHODS.
27. PROVIDE AN UPDATED, TYPED PANEL CIRCUIT DIRECTORY FOR ALL PANELS WHERE CIRCUITS HAVE BEEN MODIFIED, ADDED, OR REMOVED BY THE SCOPE OF THIS PROJECT. CIRCUIT DESCRIPTIONS ON THE DIRECTORY SHALL BE UNIQUE AND INDICATE THE ROOM AND EQUIPMENT/DEVICE IT IS FEEDING. DATE DIRECTORY WITH PROJECT COMPLETION DATE. MODIFIED CIRCUITS TO BE IN BOLD.
28. SUBMIT A SCALED LAYOUT (1/4" = 1') OF ALL ELECTRICAL ROOMS BASED ON THE ELECTRICAL GEAR AND EQUIPMENT SUBMITTALS.
29. PROVIDE A CLEAR, TYPED LABEL ON THE FACEPLATE OF ALL RECEPTACLES AND LIGHT SWITCHES INDICATING THE CIRCUIT IT IS TIED TO.
USE LABELING CONVENTION XX-xx, WHERE "XX" IS THE NAME OF THE PANEL AND "xx" IS THE BRANCH CIRCUIT NUMBER. LABELS LENGTH
SHALL NOT EXCEED 1/4" ON EITHER SIDE OF TEXT.
30. FUSED DISCONNECTS TO BE HEAVY DUTY.
31. FURNISH AND INSTALL TAMPER-RESISTANT RECEPTACLES FOR 120V RECEPTACLES IN AREAS SPECIFIED 210.52 OF THE NEC AND AS
REQUIRED UNDER 403.12 OF THE NEC.
STRUCTURE
STRUCTURE
STRUCTURE STRUCTURE
ALL THREAD (SIZE AS
REQUIRED) 3/8" MIN.
BEAM CLAMPS OR HANGER
CLAMPS (AS REQUIRED BY
WEIGHT SUPPORTED)
RACEWAY. (3/4" - 6")
CONDUIT HANGER
BEAM CLAMPS OR HANGER
CLAMPS (AS REQUIRED BY
WEIGHT SUPPORTED)
RACEWAY. (3/4" - 6")
NOTES:
1. WIRE SHALL NOT BE USED AS A COMPONENT OF ANY
RACEWAY HANGER SYSTEM.
2. DO NOT SUPPORT ANY RACEWAY LARGER THAN 1"
FROM BOTTOM CORD OF STEEL TRUSSES.
REFER TO SECTION FOR
ATTACHMENT OF ALL
THREAD ROD TO KINDORF
CHANNEL
1 1/2"x1 1/2"-12GA. KINDORF
CHANNEL OR APPROVED
SUBSTITUTE
3/8" ALL THREAD,
MINIMUM. INCREASE ROD
SIZE IF WEIGHT
REQUIRES PER ROD
MANUFACTURERS
RECOMMENDATIONS.
SUPPORT CONDUIT WITH
KINDORF STRAP OR
APPROVED SUBSTITUTE.
BEAM CLAMPS OR
HANGER CLAMPS AS
REQUIRED BY WEIGHT
SUPPORTED
PROVIDE 25% SPACE CAPACITY
NUT
WASHER
WASHER
NUT
EXIT
44"
18"
46"
WITHIN 18"
96"
72"
84"
18"
FINISHED FLOOR
WITHIN 60"
80"
44"
NOTES:
1. THE ELECTRICAL CONTRACTOR
SHALL VERIFY THE EXACT LOCATION
OF ALL TELEVISION OUTLETS WITH
THE ARCHITECT PRIOR TO
INSTALLATION.
2. ALL DEVICES SHOWN ON THIS DETAIL
ARE FOR REFERENCES OF
MOUNTING HEIGHTS ONLY. THE
ELECTRICAL CONTRACTOR SHALL
FIELD ADJUST THE HEIGHTS OF THE
DEVICES AS REQUIRED FOR PROPER
MOUNTING OF THE DEVICES.
3. ALL DEVICES REQUIRED FOR THIS
PROJECT MAY NOT APPEAR ON THIS
DETAIL. ALL ITEMS SHOWN ON THIS
DETAIL MAY NOT BE REQUIRED FOR
THIS PROJECT.
4. FIRE ALARM HORN/STROBES ARE TO
BE MOUNTED NO HIGHER THAN 96"
AND NO LOWER THAN 80" ON
CENTER.
44"
EG001 NO SCALE
MOUNTING HEIGHTS DETAIL
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/02/2026
EG002
ELECTRICAL
SPECIFICATIONS
7/31/2026
260251
ST
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260251
SA
PM: SYDNEE ANDERSON
U
TA
H S
TA
TE
H O
SP
IT
A L
FO
R
EN
SI
C S
M
EC
H A
N
IC
A L
R O
O M
U
PG
R A
D E
PR
O
VO
, U
TA
H
L
IC
EN
SE
D P
ROFE SS I ONAL ENG
IN
E
ER
14275529
S TAT E O F U TAH
SANG TRUONG
No.
ELECTRICAL SPECIFICATIONS
PART 1 - GENERAL
A. DESCRIPTION
1. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND TRANSPORTATION AS REQUIRED TO PROPERLY INSTALL
A COMPLETE AND OPERABLE ELECTRICAL SYSTEM.
B. RULES AND REGULATIONS
1. ALL WORK AND MATERIALS SHALL BE INSTALLED AS SHOWN AND HEREIN SPECIFIED.
2. THE LATEST EDITIONS OF THE FOLLOWING SPECIFICATIONS, STANDARDS, AND AMENDMENTS, AS ADOPTED
BY THE AUTHORITY HAVING JURISDICTION, SHALL FORM A PART OF THIS SPECIFICATION THE SAME AS IF HEREIN WRITTEN OUT IN FULL (ALL MATERIALS AND INSTALLATIONS SHALL CONFORM TO THE APPLICABLE
REQUIREMENTS THEREOF):
a. NFPA (NATIONAL FIRE PROTECTION ASSOCIATION), PUBLICATION NUMBER 70, "NATIONAL, ELECTRICAL
CODE"; PUB. NO. 72E, "AUTOMATIC FIRE DETECTORS".
b. UL (UNDERWRITERS LABORATORIES, INC.).
c. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION).
d. UBC (UNIFORM BUILDING CODE) AND STANDARD BUILDING CODE.
e. IBC (INTERNATIONAL BUILDING CODE)
f. IFC (INTERNATIONAL FIRE CODE)
g. IECC (INTERNATIONAL ENERGY CONSERVATION CODE)
h. IEC (INTERNATIONAL ELECTRICAL CODE) STATE AND
i. LOCAL BUILDING AUTHORITY AND CODES
3. NO REQUIREMENT TO THESE DRAWINGS AND SPECIFICATIONS SHALL BE CONSTRUCTED TO VOID ANY OF
THE PROVISIONS OF THE ABOVE SPECIFICATIONS AND STANDARDS.
C. DEMOLITION
1. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, AND NECESSARY EQUIPMENT TO PERFORM ALL
ELECTRICAL DEMOLITION AS SHOWN ON DRAWINGS. WHERE EQUIPMENT IS TO BE REMOVED IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO DE-ENERGIZE AND DISCONNECT ALL POWER AND COMMUNICATION WIRES TO EQUIPMENT ALLOWING A SAFE REMOVAL OF EQUIPMENT. DISCONNECTED
WIRES SHALL BE REMOVED.
2. DEMOLITION WORK INDICATED IN DRAWINGS IS BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORDS OR DRAWINGS. REPORT DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING ANY EXISTING INSTALLATION. THE CONTRACTOR ACCEPTS THE EXISTING CONDITIONS OF PROJECT BY STARTING
DEMOLITION WORK.
3. FIRST RIGHT OF REFUSAL SHALL BE COORDINATED WITH OWNER PRIOR TO REMOVAL OR DISPOSAL OF ANY EQUIPMENT, DEVISES, FIXTURES, ETC. COORDINATION SHALL BE DONE PRIOR TO BIDDING ON INTENT TO REUSE EXISTING MATERIALS AND THERE SHOULD BE NO CHANGE IN COST TO THE OWNER IF ELECTRICAL
CONTRACTOR FAILS TO COORDINATE.
4. ALL CIRCUITS THAT WILL BE INSIDE SCOPE OF PROJECT SHALL BE MADE SAFE FOR CONSTRUCTION AND POWER SHALL BE MAINTAINED AND ESTABLISHED WHERE REQUIRED THROUGHOUT THE SCOPE OF THE
PROJECT.
5. ANY WIRES AND CONDUITS TO BE REUSED IN NEW CONSTRUCTION SHALL BE INSPECTED AND REPLACED AS REQUIRED FOR NEW CONSTRUCTION. ANY CIRCUITS BEING CAPPED OR CONDUCTORS BEING LEFT IN
PLACE SHALL BE PROVIDED WITH A MEANS TO LOCK CIRCUIT IN OFF POSITION.
6. ANY CONDUITS, EQUIPMENT, ETC. SCHEDULED TO BE DEMOLISHED BY DIVISION 26 SHALL BE REMOVED COMPLETELY FROM SITE. WHERE CONDUITS, EQUIPMENT, ETC. ARE INACCESSIBLE THEY SHALL BE CUT
FLUSH WITH FINISHED SURFACES AND PATCHED TO MATCH EXISTING FINISHED SURFACE.
D. PERMITS AND INSPECTIONS UNLESS OTHERWISE SPECIFIED, THE CONTRACTOR SHALL APPLY, PAY FOR AND SCHEDULE ALL APPLICABLE PERMITS, FEES AND INSPECTIONS REQUIRED BY ANY AND ALL PUBLIC
AUTHORITIES HAVING JURISDICTION AND REQUIRING INSPECTION.
1. EC SHALL INCLUDE ALL UTILITY COMPANY CHARGES IN THE BASE BID.
E. WORKMANSHIP AND MATERIALS
1. WORKMANSHIP SHALL BE OF THE BEST QUALITY AND NONE BUT COMPETENT PERSONNEL SKILLED IN THEIR
TRADE SHALL BE EMPLOYED. THE CONTRACTOR SHALL FURNISH THE SERVICES OF AN EXPERIENCED SUPERINTENDENT, WHO WILL BE IN CHARGE OF THE EXECUTION OF WORK, UNTIL COMPLETED AND
ACCEPTED.
2. UNLESS OTHERWISE HEREIN AFTER SPECIFIED, ALL MATERIALS AND EQUIPMENT UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL BE NEW, OF BEST GRADE AND AS LISTED IN PRINTED CATALOGS OF THE MANUFACTURER. EACH ARTICLE OF IT'S KIND SHALL BE THE STANDARD PRODUCT OF A SINGLE
MANUFACTURER.
3. THE OWNER'S REPRESENTATIVE SHALL HAVE THE RIGHT TO ACCEPT OR REJECT MATERIAL EQUIPMENT AND/OR WORKMANSHIP AND DETERMINE WHEN THEY HAVE COMPLIED WITH THE REQUIREMENTS HEREIN
SPECIFIED.
4. ALL MANUFACTURED MATERIALS SHALL BE CLEARLY MARKED OR STAMPED WITH THE MANUFACTURER'S
NAME AND RATING.
5. REFERENCE TO STANDARDS ARE INTENDED TO BE THE LATEST REVISION OF THE STANDARD SPECIFIED, OR
THAT ACCEPTED BY THE AUTHORITY HAVING JURISDICTION.
F. MANUFACTURER'S RECOMMENDATIONS
1. EQUIPMENT INSTALLED UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL BE INSTALLED ACCORDING
TO THE MANUFACTURER'S RECOMMENDATIONS, UNLESS OTHERWISE SHOWN ON THE DRAWINGS OR
HEREIN SPECIFIED.
G. GUARANTEE ALL MATERIALS AND EQUIPMENT PROVIDED AND INSTALLED UNDER THIS SECTION SHALL BE GUARANTEED FOR A MINIMUM OF ONE YEAR. SHOULD ANY TROUBLE OR MALFUNCTIONS DEVELOP DURING THIS PERIOD DUE TO DEFECTIVE MATERIALS OR FAULTY WORKMANSHIP, THE CONTRACTOR WILL BE HELD LIABLE AND SHALL FURNISH LABOR, MATERIALS AND EQUIPMENT NECESSARY TO CORRECT THE TROUBLE OR MALFUNCTION WITHOUT ADDITIONAL COST TO THE OWNER. ALL DEFECTIVE MATERIAL OR INFERIOR WORKMANSHIP NOTICED DURING THE TIME OF INSTALLATION SHALL BE CORRECTED IMMEDIATELY TO THE
ENTIRE SATISFACTION OF THE ARCHITECT, ENGINEER AND OWNER, AT NO ADDITIONAL COST.
I. DEFINITIONS
1. "PROVIDE" - MEANS FURNISH, INSTALL, AND CONNECT, UNLESS OTHERWISE INDICATED.
2. "FURNISH" - MEANS PURCHASE NEW AND DELIVER IN OPERATING ORDER TO PROJECT SITE.
3. "INSTALL" - MEANS TO PHYSICALLY INSTALL THE ITEMS IN-PLACE.
4. "CONNECT" - MEANS MAKE FINAL ELECTRICAL CONNECTIONS FOR A COMPLETE OPERATING PIECE OF
EQUIPMENT. THIS INCLUDES PROVIDING CONDUIT, WIRE, TERMINATIONS, ETC. AS APPLICABLE.
5. "OR EQUIVALENT" - MEANS TO PROVIDE EQUIVALENT EQUIPMENT. SUCH EQUIPMENT MUST BE APPROVED
BY THE ENGINEER PRIOR TO BIDDING.
J. SUBMITTALS
1. PROVIDE SHOP DRAWINGS AND MANUFACTURER'S LITERATURE OF MATERIALS AND EQUIPMENT AS
REQUIRED IN THE GENERAL CONDITIONS, AS DIRECTED BY THE OWNER'S REPRESENTATIVE AND AS
LISTED BELOW:
2. CATALOG CUTS
a. CIRCUIT BREAKERS (EACH SIZE AND TYPE)
b. SAFETY SWITCHES
c. MOTOR STARTERS
d. THERMAL SWITCHES
e. LIGHT FIXTURES
THE ABOVE IS A STANDARD SUBMITTAL REQUIREMENT LIST. ELECTRICAL CONTRACTOR SHALL SUBMIT ALL APPLICABLE ITEMS FOR REVIEW. MATERIAL NOT SUBMITTED AND APPROVED BY THE ARCHITECT, ENGINEER OR OWNER'S REPRESENTATIVE SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THE CONTRACTORS COST IF
DIRECTED BY THE ARCHITECT, ENGINEER OR THE OWNER'S REPRESENTATIVE.
PART 2 - MATERIALS
A. GENERAL
1. MATERIALS AND EQUIPMENT SHALL BE STANDARD CATALOGED PRODUCTS OF MANUFACTURERS
REGULARLY ENGAGED IN THE MANUFACTURE OF THE PRODUCT. UL LISTED, AND SHALL BE THE LATEST
STANDARD DESIGN THAT CONFORMS TO SPECIFIED MATERIALS AND EQUIPMENT.
B. RACEWAY
1. ELECTRICAL METALLIC TUBING (EMT) SHALL BE USED IN INTERIOR DRY LOCATIONS.
2. GALVANIZED FLEXIBLE STEEL (FMC) OR LIQUID TIGHT STEEL (LFMC) CONDUIT SHALL BE USED FOR
CONNECTIONS TO MECHANICAL EQUIPMENT, LUMINAIRES AND TRANSFORMERS AND AS INDICATED.
LIQUID TIGHT CONDUIT SHALL BE USED IN EXTERIOR OR DAMP LOCATIONS.
3. SCHEDULE 40 PVC (WITH PVC COATED OR VINYL TAPE DOUBLE WRAPPED RIGID STEEL ELBOWS AND RISES)
SHALL BE USED FOR RUNS THAT ARE IN CONTACT WITH THE EARTH.
4. 3/4" CONDUIT SHALL BE THE MINIMUM SIZE CONDUIT.
5. OUTDOOR AND WET OR DAMP LOCATIONS: PROVIDE RIGID STEEL CONDUIT.
C. FITTINGS
1. ALL FITTINGS SHALL BE STEEL/MALLEABLE IRON WITH INSULATING BUSHINGS.
D. OUTLET AND JUNCTION BOXES
1. BOXES IN INTERIOR DRY LOCATIONS SHALL BE GALVANIZED ONE-PIECE PRESSED STEEL, KNOCKOUT TYPE, NOT LESS THAN 4 INCHES SQUARE AND 2 1/8" DEEP; APPLETON, RACO, OR EQUAL.
2. BOXES SHALL BE EQUIPPED WITH PLASTER RINGS, EXTENSION RINGS, AND FIXTURE STUDS AS REQUIRED.
3. BOXES FOR FLOOR OUTLETS SHALL BE OF THE CAST-METAL THREADED-CONDUIT-ENTRANCE,
WATERPROOF TYPE WITH MEANS FOR ADJUSTING COVER PLATE TO FINISHED FLOOR LEVEL. BOXES SHALL BE SUCH AS HUBBELL B2503 OR EQUAL. THE COVER SHALL BE HUBBELL S3925, S3082 OR EQUAL TO
MATCH THE FLOOR TYPE OR AS SHOWN ON THE PLANS.
4. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.
5. BOXES FOR STRUCTURED CABLING (DATA & PHONE) IN INTERIOR DRY LOCATIONS SHALL BE GALVANIZED
ONE-PIECE PRESSED STEEL, KNOCKOUT TYPE 4 11/16" x 2 1/8"; APPLETON, RAYCO OR EQUAL.
6. ALL BOXES IN FINISHED SPACES SHALL BE PROVIDED WITH MUD RINGS AS REQUIRED FOR THE DEVICE AND
WALL MATERIAL.
7. OUTDOOR AND WET OR DAMP LOCATIONS: PROVIDE CAST METAL OR PVC OUTLET, JUNCTION, AND PULL
BOXES.
E. CONDUCTORS
1. ALL CONDUCTORS SHALL BE SOFT DRAWN, ANNEALED COPPER IN RACEWAY SIZED AS SHOWN ON THE
PLANS. ALL CONDUCTORS TO BE MINIMUM #12 AWG UNLESS NOTED OTHERWISE #8 AWG AND LARGER
SHALL BE STRANDED.
2. CONDUCTORS SHALL BE COPPER, THHN OR THWN-2 COLOR CODED IN ACCORDANCE WITH PART 3, SECTION C. 1. OF THESE SPECIFICATIONS OR AS INDICATED ON THE DRAWINGS.
F. WIRING CONNECTIONS
1. MAKE ALL ELECTRICAL CONNECTIONS.
2. MAKE CONNECTION TO DEVICES USING "PIG-TAILS". DO NOT USE A DEVICE AS A CONNECTION OR A SPLICE
UNIT.
3. DO NOT PLACE STRANDED CONDUCTORS DIRECTLY UNDER SCREWS. INSTALL CRIMP-ON, INSULATED, FORK
TERMINALS FOR CONDUCTOR TERMINATIONS, OR INSTALL SOLID CONDUCTORS.
G. NAMEPLATES
1. PROVIDE EACH PANEL BOARD, DISCONNECT SWITCH, AND BREAKER IN SWITCHBOARD WITH A MICARTA
PLASTIC NAMEPLATE MADE OF WHITE-FACED BLACKCORE PLASTIC LAMINATE. NAMEPLATE SHALL BE MINIMUM 3" WIDE BY 3/4" HIGH FOR PANEL BOARD IDENTIFICATION INCLUDE DESIGNATION, PHASE, VOLTAGE, AND CIRCUIT NUMBER. FASTEN WITH EPOXY GLUE. DOUBLE STICK TAPE IS NOT ACCEPTABLE.
J. FRACTIONAL HORSEPOWER MANUAL STARTER
1. PROVIDE FRACTIONAL HORSEPOWER MANUAL STARTER WITH THE FOLLOWING FEATURES.
a. MELTING ALLOY TYPE THERMAL OVERLOAD RELAY
b. RED NEON PILOT LIGHT
c. THERMAL ELEMENT SIZED FOR MOTOR LOAD
2. PROVIDE A NAMEPLATE ON EACH COMPONENT OF MOTOR CONTROL EQUIPMENT AS SPECIFIED IN
"NAMEPLATES".
K. SAFETY SWITCHES
1. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL SAFETY SWITCHES AS INDICATED ON THE
DRAWINGS OR AS REQUIRED. ALL SAFETY SWITCHES SHALL BE UL LISTED. THE SWITCHES SHALL BE
FUSED SAFETY SWITCHES OR NON-FUSED SAFETY SWITCHES AS SHOWN ON THE DRAWINGS OR
REQUIRED BY CODE AND SHALL BE MANUFACTURED BY SQUARE D, GENERAL ELECTRIC, SIEMENS OR
CUTLER HAMMER.
2. SWITCHES SHALL HAVE A QUICK-MAKE AND QUICK-BREAK OPERATING HANDLE AND MECHANISM WHICH SHALL BE AN INTEGRAL PART OF THE BOX. PADLOCKING PROVISIONS SHALL BE PROVIDED FOR PADLOCKING IN THE OFF POSITION WITH AT LEAST THREE PADLOCKS. SWITCHES SHALL BE HORSEPOWER RATED FOR 250 VOLTS AC OR DC OR 600 VOLTS AC AS REQUIRED. LUGS SHALL BE UL LISTED FOR COPPER
AND ALUMINUM CABLE AND SHALL HAVE A TEMPERATURE RATING OF AT LEAST 75 DEGREES C.
3. SWITCHES SHALL BE FURNISHED IN NEMA 1 HEAVY DUTY ENCLOSURES WITH KNOCKOUTS UNLESS OTHERWISE NOTED OR REQUIRED. SWITCHES LOCATED ON THE EXTERIOR OF THE BUILDING OR IN "WET"
LOCATIONS SHALL HAVE NEMA 3R ENCLOSURES (WP).
4. THE SAFETY SWITCHES SHALL BE SECURELY MOUNTED IN ACCORDANCE WITH THE NEC. THE
CONTRACTOR SHALL PROVIDE ALL MOUNTING MATERIALS AND INSTALL FUSES IN THE FUSED SAFETY
SWITCHES. THE FUSES SHALL BE DUAL ELEMENT ON MOTOR CIRCUITS.
5. PROVIDE FUSES AS SPECIFIED BELOW. FUSES SHALL BE INSTALLED SO THAT THE RATING IS CLEARLY
VISIBLE WITHOUT REMOVING FUSE. PROVIDE A SPARE FUSE FOR EACH FUSE INSTALLED.
6. PROVIDE A NAMEPLATE ON EACH DISCONNECT SWITCH AS SPECIFIED IN "NAMEPLATES".
L. FUSES
1. FUSES SHALL BE CLASS "RK-1" REJECTION TYPE. FUSES SERVING MOTOR LOADS SHALL BE DUAL
ELEMENT WITH A MINIMUM TIME DELAY OF 10 SECONDS AT 500% RATING. FUSES SHALL BE CURRENT LIMITING TIME DELAY TYPE WITH INTERRUPTING CAPACITY OF 200,000 AMP RMS SYMMETRICAL.
2. FUSES SERVING SWITCH OR CIRCUIT BREAKER DISTRIBUTION PANELS, LIGHTING PANEL BOARDS AND OTHER NON - MOTOR LOADS NEED NOT BE TIME DELAY TYPE, BUT SHALL BE CURRENT LIMITING WITH
THE INTERRUPTING CAPACITY OF 200,000AMP RMS SYMMETRICAL MINIMUM. FUSES SHALL BE
BUSSMAN, GOULD OR LITTELFUSE.
3. PROVIDE FUSES SIZED TO THE MAXIMUM SIZE RECOMMENDED BY THE MANUFACTURER OF THE
EQUIPMENT OR AS SHOWN ON THE DRAWINGS IF THE MANUFACTURER DOES NOT HAVE A
RECOMMENDED SIZE.
PART 3 - EXECUTION
A. GENERAL
1. ALL MATERIALS SHALL BE INSTALLED IN A PROFESSIONAL MANNER INDICATIVE OF THE TRADE.
2. ALL PENETRATIONS OF THE OUTSIDE WALLS OR ROOF SHALL BE SEALED WITH APPROPRIATE SEALANT OR
CAULK FOR THE PARTICULAR SURFACE INVOLVED.
3. PROVIDE CLEAR, TYPED, P-TOUCH LABEL FOR ALL RECEPTACLES COVERPLATES IDENTIFYING THE CIRCUIT
NUMBER THAT THE RECEPTACLE IS CIRCUITED TO.
4. PROVIDE UPDATED TYPED PANEL SCHEDULE INDEX FOR ALL PANELS WHERE CIRCUITS HAVE BEEN MODIFIED
OR CHANGED.
B. RACEWAYS
1. RACEWAYS SHALL RUN CONCEALED UNLESS OTHERWISE INDICATED. EXPOSED RACEWAY RUNS SHALL BE
PARALLEL WITH SUPPORTING WALLS, BEAMS, AND CEILINGS AND WITH EACH OTHER CLOSER THAN 6
INCHES TO ANY WATER PIPE OR HEATER BE INSTALLED AND SHALL NOT FLUME.
2. RACEWAY ENDS SHALL BE REAMED AFTER THREADING AND AFTER CUTTING AND BE MADE TO BUTT IN THE
CENTER OF THE COUPLING. THE USE OF RUNNING THREADS IS PROHIBITED.
3. RACEWAYS SHALL BE INSTALLED AS A COMPLETE SYSTEM, CONTINUOUS FROM OUTLET TO OUTLET, CABINET, BOX OR FITTINGS, AND SHALL BE MECHANICALLY CONNECTED SO THAT ADEQUATE ELECTRICAL CONTINUITY FROM ONE TO ANOTHER IS OBTAINED. CONDUITS SHALL BE SUPPORTED WITH ONE OR TWO HOLE STAMPED STEEL OR MALLEABLE IRON STRAPS (SUCH AS MANUFACTURED BY RACO) DESIGNED FOR SUPPORTING CONDUIT. THE SIZE OF STRAP SHALL MATCH THE SIZE OF THE CONDUIT. NAILS, PERFORATED STRAP, OR PLUMBERS TAPE SHALL NOT BE USED FOR SUPPORT OF RACEWAY.
4. PROVIDE 1/8" POLY PULL CORD IN RACEWAYS WITHOUT CONDUCTORS.
5. FOUR 90 DEGREE BENDS MAXIMUM BETWEEN TERMINATIONS OR BOXES.
C. CONDUCTORS
1. ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT AND COLOR CODED AS FOLLOWS:
PHASE 240/120 208/120 480/277
PHASE A BLACK BLACK BROWN
PHASE B RED RED ORANGE
PHASE C - BLUE YELLOW
NEUTRAL WHITE WHITE GRAY
GROUND GREEN GREEN GREEN
2. MAKE JOINTS, SPLICES, TAPS AND CONNECTIONS IN CONDUCTORS WITH SOLDERLESS CONNECTORS.
D. JUNCTION AND PULL BOXES
1. PULL BOXES SHALL BE PROVIDED WHERE INDICATED AND WHERE NECESSARY TO FACILITATE THE PULLING
OF CONDUCTORS. TELEPHONE RACEWAYS SHALL HAVE A MAXIMUM OF TWO 90 DEGREE BENDS BETWEEN
TERMINATIONS OR BOXES.
E. GROUNDING
1. INSTALL A CODE SIZED GROUNDING CONDUCTOR IN ALL RACEWAYS. DO NOT USE THE RACEWAY FOR
GROUNDING. MAKE GOOD CONTACT AT ALL PANEL BOARDS, OUTLET BOXES, AND JUNCTION OR PULL
BOXES TO THE RACEWAY SYSTEM. USE APPROVED BONDING MATERIALS.
G. BONDING
1. BOND ALL PIPING (GAS WATER, ETC) AS REQUIRED BY THE NEC. CONFIRM SYSTEMS TO BE USED WITH MC.
H. SEISMIC REQUIREMENTS
1. IF REQUIRED, RECESSED TYPE LIGHTING FIXTURES, IN ADDITION TO THE STANDARD SEISMIC CLIPS AND
SUPPORT ON T-BAR GRID SYSTEM, SHALL HAVE 2#12 STEEL SAFETY WIRES PER FIXTURE. ONE END OF EACH SAFETY WIRE SHALL BE SECURELY FASTENED TO THE BUILDING STRUCTURE. THE OTHER END (6 INCHES LONGER THAN THE T-BAR GRID SUPPORT WIRES) SHALL BE FASTENED TO DIAGONAL CORNERS OF
EACH LIGHTING FIXTURE.
I. CUTTING AND PATCHING
1. PERFORM DRILLING, CUTTING, AND PATCHING OF THE GENERAL CONSTRUCTION WORK WHETHER EXISTING
OR NEW, AS REQUIRED FOR THE INSTALLATION OF ELECTRICAL WORK. PATCH WITH THE SAME
MATERIALS, WORKMANSHIP, AND FINISH AS THE ORIGINAL WORK AND ACCURATELY MATCH ALL
SURROUNDING WORK. SUCH WORK WILL BE DONE BY A CRAFTSMAN ACCREDITED IN THE APPLICABLE
TRADE UNDER THE CONTRACTOR'S SUPERVISION AND BE ACCEPTABLE TO THE OWNER'S
REPRESENTATIVE. COORDINATE WITH OTHER TRADES AND GENERAL CONTRACTOR PRIOR TO CUTTING, DRILLING, OR CORING.
K. TESTING
1. DEMONSTRATE THAT ALL COMPONENTS OF THE WORK OF THIS DIVISION HAVE BEEN PROVIDED AND THAT
THEY OPERATE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
2. TEST WIRING AND CONNECTORS FOR CONTINUITY, SHORT CIRCUITS AND IMPROPER GROUNDS. TEST EACH
LIGHTING AND APPLIANCE PANEL WITH MAINS DISCONNECTED FROM FEEDERS, BRANCHES CONNECTED, WALL SWITCHES CLOSED AND FIXTURES PERMANENTLY CONNECTED AND COMPLETE WITH LAMPS. TEST EACH INDIVIDUAL POWER CIRCUIT WITH THE POWER EQUIPMENT CONNECTED FOR PROPER OPERATION.
3. PROVIDE DETAILED DOCUMENTATION OF EACH TEST PERFORMED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE, WITH THE NAMES AND THE SIGNATURES OF QUALIFIED INDIVIDUALS WHO CONDUCTED
AND WITNESSED EACH TEST.
PART 4 - VARIABLE FREQUENCY MOTOR CONTROLLERS
1.1 SUBMITTALS
A. PRODUCT DATA: FOR EACH TYPE AND RATING OF VFC INDICATED.
1. INCLUDE DIMENSIONS AND FINISHES FOR VFCS.
2. INCLUDE RATED CAPACITIES, OPERATING CHARACTERISTICS, ELECTRICAL CHARACTERISTIC, AND
FURNISHED SPECIAL AND ACCESSORIES.
B. SHOP DRAWINGS: FOR EACH VFC INDICATED.
1. INCLUDE MOUNTING AND ATTACHMENT DETAILS.
2. INCLUDE DETAILS OF EQUIPMENT ASSEMBLIES. INDICATE DIMENSIONS, WEIGHTS, LOADS, REQUIRED
CLEARANCES, METHOD OF FIELD ASSEMBLY, COMPONENTS, AND LOCATION AND SIZE OF EACH
FIELD CONNECTION.
3. INCLUDE DIAGRAMS FOR POWER, SIGNAL, AND CONTROL WIRING.
C. WARRANTY: MANUFACTURER AGREES TO REPAIR OR REPLACE VFCS…