This is a Limited Hazardous Materials Inspection report prepared by Terracon Consultants, Inc. for the State of Utah Division of Facilities Construction and Management (DFCM) regarding the Utah State Hospital Forensics Mechanical Room located at 1300 East Center Street in Provo, Utah. The inspection was conducted on May 6, 2026, in preparation for a planned mechanical room upgrade project (Project #27136420) with a construction cost estimate of $525,000. The approximately 3,500 square-foot facility comprises four rooms: the Chiller Room, Heat Exchanger Room, Electrical Room, and Upstairs Mechanical Room with interior finishes of CMU block, metal ceiling with fireproofing, and concrete or stone flooring. The inspection included comprehensive sampling and analysis for asbestos-containing materials (ACM), lead-containing paint (LCP), and universal hazardous wastes to identify materials requiring removal or special handling prior to renovation activities.

The inspection findings indicate that no asbestos-containing materials were identified in 24 bulk samples collected from seven homogeneous areas of suspect ACM and analyzed by Eurofins EMLab P&K using polarized light microscopy per EPA Method 600/R-93/116. However, lead was detected on two surfaces tested using X-ray fluorescence (XRF) analysis, with lead concentrations at or exceeding 0.01 mg/cm². Additionally, universal waste materials and other hazardous materials requiring proper disposal in accordance with EPA regulations were visually identified, with removal cost estimates provided in the report. The report notes that inaccessible areas within walls, voids, and concealed spaces may contain additional unsampled suspect materials and recommends that all building materials assumed to contain asbestos be removed by a Utah-certified abatement contractor prior to demolition or renovation activities to comply with federal OSHA requirements and Utah Division of Air Quality regulations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Facilities | Environmental | Geotechnical | Materials I

Limited Hazardous Materials Inspection Utah State Hospital Forensics Mechanical Room Upgrade 1300 East Center Street Provo, Utah 84606

May 21, 2026 | Terracon Project No. 61267098

6952 South High Tech Dr. Ste. B Midvale, Utah 84047

P (801) 545-8500 Terracon.com

Facilities | Environmental | Geotechnical | Materials i

Cover Letter

May 21, 2026

Division of Facilities Construction and Management 4315 South 2700 West, 3rd Floor Taylorsville, Utah 84129

Attn: Ms. Aubrey Stapel P: (801) 641-0964 E: astapel@utah.gov

Re: Limited Hazardous Materials Inspection Utah State Hospital Forensics Mechanical Room Upgrade 1300 East Center Street Provo, Utah 84606 Terracon Project No. 61267098

Dear Ms. Stapel:

Terracon Consultants, Inc. (Terracon) appreciates the opportunity to provide this report to the State of Utah Division of Facilities Construction and Management (DFCM) for whom a pre-renovation Limited Hazardous Materials Inspection was conducted, including asbestos, lead-containing paint (LCP), and universal wastes, at the above-mentioned Utah State Hospital Forensics Mechanical Room in Provo, Utah.

The purpose of this report is to present the results of the pre-renovation limited hazardous materials inspection performed on May 6, 2026, at the Utah State Hospital Forensics Mechanical Room located on 1300 East Center Street in Provo, Utah. We understand that this inspection was requested in preparation for the potential future renovation of the building.

Based on laboratory analysis, no asbestos-containing materials were identified in the materials sampled during the inspection. Lead-containing paint, universal waste, and other hazardous materials were identified during the inspection. Please refer to the attached report for details.

mailto:astapel@utah.gov

Limited Hazardous Materials Inspection DFCM Utah State Hospital Forensics Mechanical Room | Provo, Utah May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials ii

Terracon appreciates the opportunity to provide this service to the State of Utah Division of Facilities Construction and Management (DFCM).

If you have any questions regarding this report, or if you need any further assistance, please contact Noah Hancock at (916) 827-8763.

Sincerely, Terracon Consultants, Inc.

Prepared by: Reviewed By:

Noah Hancock John Murphy, CIH, CSP Staff Industrial Hygienist Asbestos and Industrial Hygiene Program Utah DAQ ASB-8620 Manager

State of Utah Asbestos Company Certification No. 289

Noah Hancock

Facilities | Environmental | Geotechnical | Materials iii

Table Of Contents

1.0 Introduction

2.0 Building/Area Description

3.0 Field Activities

3.1 Asbestos

3.2 Lead

3.3 Hazardous Materials

4.0 Regulatory Overview

4.1 Asbestos

4.2 Lead Paint

4.3 Hazardous Materials

5.0 Findings

5.1 Asbestos

5.2 Lead Paint

5.3 Hazardous Materials

5.4 Inaccessible Areas

6.0 General Comments

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials iv

Appendices Appendix A Table 1: Asbestos Testing Summary

Appendix B Asbestos Sample Location Drawings

Appendix C Asbestos Laboratory Analytical Reports

Appendix D Photo Log

Appendix E Table 2: XRF Lead Coating Testing Summary

Appendix F Table 3: Universal Waste and Hazardous Materials Removal Estimates

Appendix G Certifications

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials 1

1.0 Introduction

Terracon Consultants, Inc. (Terracon) conducted a pre-demolition limited hazardous materials inspection, including asbestos, lead, and universal hazardous materials, at the Utah State Hospital Forensics Mechanical Room located at 1300 East Center Street in Provo, Utah.

The inspection was conducted on May 6, 2026, by Mr. Noah Hancock. The objective of this project was to identify the presence of asbestos, lead, universal hazardous waste, and other hazardous materials present in preparation for possible renovation.

2.0 Building/Area Description

The Utah State Hospital Forensics Mechanical Room is roughly a 3,500 square foot area made up of four rooms: the Chiller Room, the Heat Exchanger Room, the Electrical Room, and the Upstairs Mechanical Room. The interior finishes consist of CMU Block, a metal ceiling coated in fireproofing, and concrete or stone flooring.

3.0 Field Activities

The hazardous materials inspection included asbestos, lead, and other hazardous materials and was conducted on May 6, 2026 by Mr. Noah Hancock, a Terracon employee and State of Utah-certified Asbestos Inspector. He is also trained to inspect for and summarize the presence of lead and universal hazardous wastes for proper disposal as required by the United States Environmental Protection Agency (EPA). Copies of Mr. Noah Hancock’s Asbestos and Lead Inspector certifications are attached as Appendix G.

3.1 Asbestos

Terracon began the asbestos sampling activities with a visual assessment and the identification and inventory of readily visible and accessible homogeneous areas of suspect ACM throughout the building. A homogeneous area consists of a material that appears similar throughout in terms of color, texture, and date of application. The assessment was conducted throughout visually accessible areas of the building. Materials identified as glass, metal, plastic, or rubber were not considered suspected asbestos containing material (ACM).

A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect material.

Based on results of the visual observation, bulk samples of suspect ACM were collected from the accessible interior spaces of the rooms. Bulk samples of suspected ACM were collected

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials 2 in accordance with Asbestos Hazard Emergency Response Act (AHERA) sampling protocols, using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers, using an indelible marker. Terracon collected 24 samples from seven homogeneous areas of suspect ACM. A sampling location drawing is provided in Appendix B. Descriptions of the suspect materials, sample locations, and laboratory results are summarized in Table 1 Appendix A. Although reasonable effort was made to survey accessible suspect materials, additional suspect but unsampled materials could be in walls, in voids, underneath the concrete slab, or in other concealed areas.

Samples of suspect ACM were delivered under standard chain-of-custody protocol to Eurofins EMLab P&K (NVLAP #500031-0) in Phoenix, Arizona, for analysis by polarized light microscopy (PLM), using EPA Method 600/R-93/116. The asbestos content, where applicable, was determined by microscopic visual estimation. Copies of the analytical reports and chain-of-custody forms are provided in Appendix C.

3.2 Lead

The lead paint inspection began by visually surveying accessible interior room components, such as walls, ceilings, floors, doors, pipes, and other metal components. Various colors of paint were found on interior surfaces. All these components can be disturbed during renovation activities.

Terracon directly measured the concentration of lead using an Olympus X-ray Fluorescence (XRF) Lead Analyzer (Serial Number 510179). The Olympus XRF nondestructively measures lead concentrations in coated surfaces, regardless of the number of paint layers present. For this survey, materials were considered lead containing if the XRF indicated lead concentrations greater than or equal to 0.01 milligram per square centimeter (mg/cm2);

however, since the Occupational Safety and Health Administration (OSHA) does not permit materials to be classified as lead-free using an XRF, Terracon cannot guarantee that lead is not present in very low concentrations when the XRF indicates no lead was detected.

3.3 Hazardous Materials

Terracon visually identified hazardous wastes requiring removal and proper disposal prior to renovation or demolition by the Salt Lake County Health Department, but no samples of these materials were collected.

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials 3

4.0 Regulatory Overview

4.1 Asbestos

The Utah Division of Air Quality (DAQ) requires an initial asbestos inspection or an asbestos re-inspection of buildings for which a previous asbestos inspection was conducted greater than three years prior. The DAQ enforces 40 CFR Part 61, Subpart M, the Asbestos National Emission Standard for Hazardous Air Pollutants (NESHAP) adopted by reference in Section 214-1, Utah Air Conservation Rules. The owner or operator must provide DAQ with written notification at least ten working days prior to the commencement of asbestos abatement activities that will disturb regulated asbestos-containing material (RACM) in amounts greater than or equal to 3 square feet or 3 linear feet.

The asbestos NESHAP regulates asbestos fiber emissions and asbestos waste disposal practices, and requires that RACM be identified, classified, and quantified prior to planned disturbances or demolition activities. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to renovation or demolition activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered RACM.

The asbestos NESHAP regulation classifies ACM as either RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM; Category I non-friable ACM that has become friable or will be or has been subjected to sanding, grinding, cutting, or abrading; and Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of demolition or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials other than Category I non-friable ACM that contain more than 1% asbestos. Category II non-friable ACM generally includes but is not limited to glazing, mortar, grouts, and cementitious material such as pipes, siding, and panels.

The OSHA asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions that employers must follow when engaging in each class of regulated work. The standard also specifies requirements for disturbing and handling materials with asbestos concentrations less than or equal to one percent.

4.2 Lead Paint

The Lead in Construction OSHA Standard 1926.62 regulates construction work involving the presence of lead in any concentration. Depending on the specific construction activities

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials 4 being performed (torch cutting, manual demolition, sanding, grinding, etc.), employers must assume their employees are exposed to lead above the occupational exposure limit and must provide personal protective equipment, including respiratory protection, until an exposure assessment proves otherwise.

4.3 Hazardous Materials

The Environmental Protection Agency (EPA) has streamlined the regulations for certain categories of commonly generated hazardous waste, called universal waste, including:

Batteries

Pesticides

Mercury-containing equipment

Lamps

Aerosol cans

The EPA also has specific hazardous waste regulations for the following wastes:

Polychlorinated biphenyls (PCBs)

Chlorofluorocarbons (CFCs)

Drums or other containers of hazardous or special waste

5.0 Findings

5.1 Asbestos

Terracon collected 24 samples from seven homogeneous areas of suspect ACM from the site.

Based on the laboratory analytical reporting, no asbestos was identified in suspect materials sampled during this inspection.

Material descriptions, locations, and sample results are summarized in Table 1: Asbestos Bulk Sampling Summary in Appendix A. Laboratory analytical reports are included in Appendix C. A drawing depicting sample locations is provided in Appendix B.

Regardless of whether a material is considered a RACM by the State of Utah Division of Air Quality, federal OSHA asbestos regulations specify worker training, work practice, and exposure assessment requirements, among others, that most demolition contractors do not meet. Therefore, Terracon recommends that all building materials containing asbestos or assumed to contain asbestos be removed by a Utah-certified asbestos abatement contractor prior to demolition that would impact the materials.

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials 5

5.2 Lead Paint

Lead was detected in two surfaces tested. Results of surface coatings tested for lead are provided in Appendix E.

5.3 Hazardous Materials

A complete list of hazardous materials with removal costs is provided in Table 3 in Appendix F: Hazardous Waste Cost Estimates. These materials should be properly disposed of or recycled in accordance with all local, state, and federal regulations as part of future renovation or demolition activities.

5.4 Inaccessible Areas

Although reasonable effort was made to inspect accessible suspect materials, additional suspect but un-sampled materials could be in walls, in voids, or in other concealed areas.

6.0 General Comments

This survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our inspection of the building. The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date.

This report has been prepared on behalf of and exclusively for use by the Division of Facilities Construction and Management.

This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied, is made.

Appendix A Table 1: Asbestos Testing Summary

Appendix A: Table 1 Asbestos Sample Results DFCM State Hospital Forensics Mechanical Room | Provo, Utah May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials

Homogeneous Area (HA) Description Sample No. Sample Location Estimated

Quantity Lab Results

M01 Yellow Vent Sealant

7124-1 Upstairs Mechanical Room South 86 SF ND7124-2 F052 Chiller Room South

7124-3 F052 Chiller Room South

M02 Gray Gasket Putty

7124-4 Upstairs Mechanical Room North 30 SF ND7124-5 Upstairs Mechanical Room North

7124-6 Upstairs Mechanical Room North

M03 Black Vibration Isolator

7124-7 Upstairs Mechanical Room West

25 SF ND

7124-8 Upstairs Mechanical Room East

M04 Red Caulking 7124-9 Upstairs Mechanical Room North

10 SF ND7124-10 F053 Heat Exchanger Room 7124-11 F053 Heat Exchanger Room

S01 Fireproofing

7124-12 Upstairs Mechanical Room Center

2,600 SF ND

7124-13 Upstairs Mechanical Room Northwest 7124-14 F052 Chiller Room Southwest 7124-15 F052 Chiller Room South 7124-16 F053 Heat Exchanger Room Center

T01 TSI Mudded Ends 7124-17 Upstairs Mechanical Room West

119 Ends ND7124-18 Upstairs Mechanical Room North 7124-19 F053 Heat Exchanger Room Center

S02 White Block Paint

7124-20 F054 Electrical Side Room West Wall

1,230 SF ND

7124-21 F054 Electrical Side Room East Wall 7124-22 F054 Electrical Room North Wall 7124-23 F054 Electrical Room South Wall 7124-24 F054 Electrical Room West Wall

Key:

ND = none detected SF = square feet

Appendix B Asbestos Sample Location Drawings

THIS DIAGRAM IS FOR GENERAL LOCATION ONLY, AND IS NOT INTENDED FOR CONSTRUCTION PURPOSES

Project Mngr:

Approved By:

Checked By:

Drawn By:

Project No.

Scale:

Date:

File No.

EXHIBITSAMPLE LOCATION DIAGRAM - HEAT EXCHANGER ROOM

ASBESTOS INSPECTION

STATE HOSPITAL FORENSICS MECHANICAL ROOM

1300 EAST CENTER STREET

PROVO, UT

NH

RLW

NH/MRF

NH

61267098

AS SHOWN

61267098-1

MAY 2026 6952 S. High Tech Drive, Ste. B Midvale, UT 84047

(801) 545-8500 (801) 545-8600

NOT TO SCALE

LEGEND

SAMPLE LOCATION

16,19

AutoCAD SHX Text N

Approved By:

Checked By:

Drawn By:

Project No.

Scale:

Date:

File No.

EXHIBITSAMPLE LOCATION DIAGRAM - CHILLER ROOM

ASBESTOS INSPECTION

STATE HOSPITAL FORENSICS MECHANICAL ROOM

1300 EAST CENTER STREET

PROVO, UT

NH

RLW

NH/MRF

NH

61267098

AS SHOWN

61267098-2

MAY 2026 6952 S. High Tech Drive, Ste. B Midvale, UT 84047

(801) 545-8500 (801) 545-8600

NOT TO SCALE

LEGEND

SAMPLE LOCATION

2,3

Approved By:

Checked By:

Drawn By:

Project No.

Scale:

Date:

File No.

EXHIBITSAMPLE LOCATION DIAGRAM - UPSTAIRS MECH ROOM

ASBESTOS INSPECTION

STATE HOSPITAL FORENSICS MECHANICAL ROOM

1300 EAST CENTER STREET

PROVO, UT

NH

RLW

NH/MRF

NH

61267098

AS SHOWN

61267098-3

MAY 2026 6952 S. High Tech Drive, Ste. B Midvale, UT 84047

(801) 545-8500 (801) 545-8600

NOT TO SCALE

LEGEND

SAMPLE LOCATION

5,6

STAIRS

Appendix C Asbestos Laboratory Analytical Reports

Approved by:

Approved Signatory Renee Luna-Trepczynski

Report for:

Noah Hancock, John Murphy Terracon Consultants, Inc. - Utah 6952 S. High Tech Dr., Suite B Midvale, UT 84047

Regarding:

Eurofins Aerotech Built Environment Testing, LLC Project: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

EML ID: 4526589

All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.

Eurofins Aerotech Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.

Dates of Analysis:

Asbestos PLM: 05-13-2026

Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA 600/R-93-116, EBET-PLM-SOP83921) NVLAP Lab Code 500031-0

EMLab ID: 4526589, Page 1 of 8Eurofins Aerotech Built Environment Testing, LLC

Eurofins Aerotech Built Environment Testing, LLC 1501 West Knudsen Drive, Phoenix, AZ 85027

(800) 651-4802 www.eurofinsus.com/BuiltClient: Terracon Consultants, Inc. - Utah C/O: Noah Hancock, John Murphy Re: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

Date of Sampling: 05-06-2026 Date of Receipt: 05-08-2026 Date of Report: 05-13-2026

ASBESTOS PLM REPORT

Total Samples Submitted: 24 Total Samples Analyzed: 24

Total Samples with Layer Asbestos Content > 1%: 0

Location: 7098-1 Lab ID-Version‡: 22780613-1

Sample Layers Asbestos Content Tan Non-Fibrous Material ND

Sample Composite Homogeneity: Good

Location: 7098-2 Lab ID-Version‡: 22780614-1

Sample Layers Asbestos Content Tan Non-Fibrous Material ND

Sample Composite Homogeneity: Good

Location: 7098-3 Lab ID-Version‡: 22780615-1

Sample Layers Asbestos Content Tan Non-Fibrous Material ND

Sample Composite Homogeneity: Good

Location: 7098-4 Lab ID-Version‡: 22780616-1

Sample Layers Asbestos Content Light Gray Sealant ND

Gray Sealant ND Sample Composite Homogeneity: Moderate

EMLab ID: 4526589, Page 2 of 8Eurofins Aerotech Built Environment Testing, LLC

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

(800) 651-4802 www.eurofinsus.com/BuiltClient: Terracon Consultants, Inc. - Utah C/O: Noah Hancock, John Murphy Re: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

Date of Sampling: 05-06-2026 Date of Receipt: 05-08-2026 Date of Report: 05-13-2026

ASBESTOS PLM REPORT

Location: 7098-5 Lab ID-Version‡: 22780617-1

Sample Layers Asbestos Content Light Gray Sealant ND

Gray Sealant ND Sample Composite Homogeneity: Moderate

Location: 7098-6 Lab ID-Version‡: 22780618-1

Sample Layers Asbestos Content Light Gray Sealant ND

Sample Composite Homogeneity: Good

Location: 7098-7 Lab ID-Version‡: 22780619-1

Sample Layers Asbestos Content Black Semi-Fibrous Material ND

Composite Non-Asbestos Content: 10% Synthetic Fibers Sample Composite Homogeneity: Good

Location: 7098-8 Lab ID-Version‡: 22780620-1

Sample Layers Asbestos Content Black Semi-Fibrous Material ND

Composite Non-Asbestos Content: 10% Synthetic Fibers Sample Composite Homogeneity: Good

Location: 7098-9 Lab ID-Version‡: 22780621-1

Sample Layers Asbestos Content Red Caulk ND Composite Non-Asbestos Content: 2% Glass Fibers Sample Composite Homogeneity: Good

EMLab ID: 4526589, Page 3 of 8Eurofins Aerotech Built Environment Testing, LLC

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is

(800) 651-4802 www.eurofinsus.com/BuiltClient: Terracon Consultants, Inc. - Utah C/O: Noah Hancock, John Murphy Re: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

Date of Sampling: 05-06-2026 Date of Receipt: 05-08-2026 Date of Report: 05-13-2026

ASBESTOS PLM REPORT

Location: 7098-10 Lab ID-Version‡: 22780622-1

Sample Layers Asbestos Content Red Caulk ND Composite Non-Asbestos Content: 2% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-11 Lab ID-Version‡: 22780623-1

Sample Layers Asbestos Content Red Caulk ND Composite Non-Asbestos Content: 2% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-12 Lab ID-Version‡: 22780624-1

Sample Layers Asbestos Content Light Gray Insulation ND

Composite Non-Asbestos Content: 50% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-13 Lab ID-Version‡: 22780625-1

Sample Layers Asbestos Content Light Gray Insulation ND

Composite Non-Asbestos Content: 50% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-14 Lab ID-Version‡: 22780626-1

Sample Layers Asbestos Content Light Gray Insulation ND

Composite Non-Asbestos Content: 50% Glass Fibers Sample Composite Homogeneity: Good

EMLab ID: 4526589, Page 4 of 8Eurofins Aerotech Built Environment Testing, LLC

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is

(800) 651-4802 www.eurofinsus.com/BuiltClient: Terracon Consultants, Inc. - Utah C/O: Noah Hancock, John Murphy Re: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

Date of Sampling: 05-06-2026 Date of Receipt: 05-08-2026 Date of Report: 05-13-2026

ASBESTOS PLM REPORT

Location: 7098-15 Lab ID-Version‡: 22780627-1

Sample Layers Asbestos Content Light Gray Insulation ND

Composite Non-Asbestos Content: 50% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-16 Lab ID-Version‡: 22780628-1

Sample Layers Asbestos Content Light Gray Insulation ND

Composite Non-Asbestos Content: 50% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-17 Lab ID-Version‡: 22780629-1

Sample Layers Asbestos Content Yellow Ceiling Tile with White Surface ND

Composite Non-Asbestos Content: 85% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-18 Lab ID-Version‡: 22780630-1

Sample Layers Asbestos Content Yellow Ceiling Tile with White Surface ND

Composite Non-Asbestos Content: 85% Glass Fibers Sample Composite Homogeneity: Good

Location: 7098-19 Lab ID-Version‡: 22780631-1

Sample Layers Asbestos Content Yellow Ceiling Tile with White Surface ND

Composite Non-Asbestos Content: 85% Glass Fibers Sample Composite Homogeneity: Good

EMLab ID: 4526589, Page 5 of 8Eurofins Aerotech Built Environment Testing, LLC

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is

(800) 651-4802 www.eurofinsus.com/BuiltClient: Terracon Consultants, Inc. - Utah C/O: Noah Hancock, John Murphy Re: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

Date of Sampling: 05-06-2026 Date of Receipt: 05-08-2026 Date of Report: 05-13-2026

ASBESTOS PLM REPORT

Location: 7098-20 Lab ID-Version‡: 22780632-1

Sample Layers Asbestos Content White Block Fill with Paint ND

Gray Block ND Sample Composite Homogeneity: Moderate

Location: 7098-21 Lab ID-Version‡: 22780633-1

Sample Layers Asbestos Content White Block Fill with Paint ND

Gray Block ND Sample Composite Homogeneity: Moderate

Location: 7098-22 Lab ID-Version‡: 22780634-1

Sample Layers Asbestos Content White Block Fill with Paint ND

Gray Block ND Sample Composite Homogeneity: Moderate

Location: 7098-23 Lab ID-Version‡: 22780635-1

Sample Layers Asbestos Content White Block Fill with Paint ND

Gray Block ND Sample Composite Homogeneity: Moderate

EMLab ID: 4526589, Page 6 of 8Eurofins Aerotech Built Environment Testing, LLC

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is

(800) 651-4802 www.eurofinsus.com/BuiltClient: Terracon Consultants, Inc. - Utah C/O: Noah Hancock, John Murphy Re: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

Date of Sampling: 05-06-2026 Date of Receipt: 05-08-2026 Date of Report: 05-13-2026

ASBESTOS PLM REPORT

Location: 7098-24 Lab ID-Version‡: 22780636-1

Sample Layers Asbestos Content White Block Fill with Paint ND

Gray Block ND Sample Composite Homogeneity: Moderate

EMLab ID: 4526589, Page 7 of 8Eurofins Aerotech Built Environment Testing, LLC

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.

Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is

(800) 651-4802 www.eurofinsus.com/BuiltClient: Terracon Consultants, Inc. - Utah C/O: Noah Hancock, John Murphy Re: 61267115-61267098; DFCM Utah State Hospital Forensics Facility Mechanical Room

Date of Sampling: 05-06-2026 Date of Receipt: 05-08-2026 Date of Report: 05-13-2026

ASBESTOS PLM REPORT

PROJECT ANALYST AND SIGNATORY REPORT

Project Analyst

The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".

Analyst: Jason Bosse

EMLab ID: 4526589, Page 8 of 8Eurofins Aerotech Built Environment Testing, LLC

5/8/2026 10:15 AM

Shannon Nast, Senior Client Relations Executive

4526589

Noah Hancock 5/6/2026 5:00 PM

X X X X

X

Terracon Consultants, Inc. - Utah (16459) 6952 S. High Tech Dr., Suite B Midvale, UT 84047

916-827-8763

Noah Hancock, John Murphy

61267115-61267098

DFCM Utah State Hospital Forensics Facility Mechanical Room

84606 05/06/2026 11:00 AM

61267115-61267098 Noah Hancock

A sb es to s P

LM

B - Bulk sample

X

X

X

X

X

X

X

X

X

X

X

7098-1 B STD N/A

7098-2 B STD N/A

7098-3 B STD N/A

7098-4 B STD N/A

7098-5 B STD N/A

7098-6 B STD N/A

7098-7 B STD N/A

7098-8 B STD N/A

7098-9 B STD N/A

7098-10 B STD N/A

7098-11 B STD N/A

u finsus /Bui

New Jersey: 3000 Lincoln Drive East, Suite A, Marlton, NJ 08053 * (866) 871-1984

Burlingame, CA: 111 Anza Blvd., Suite 122, Burlingame, CA 94010 * (833) 465-5857 Phoenix, AZ: 1501 West Knudsen Drive, Phoenix, AZ 85027 * (800) 651-4802

Doc. #1192, Rev 35, Revised 6/6/24, Page 1 of 1, QA Copyright © 2024 Eurofins EPK Built Environment Testing, LLC

4526589

Noah Hancock 5/6/2026 5:00 PM

X X X X

X

Terracon Consultants, Inc. - Utah (16459) 6952 S. High Tech Dr., Suite B Midvale, UT 84047

Room

84606 05/06/2026 11:00 AM

61267115-61267098 Noah Hancock

A sb es to s P

LM

B - Bulk sample

X

X

X

X

X

X

X

X

X

X

X

7098-12 B STD N/A

7098-13 B STD N/A

7098-14 B STD N/A

7098-15 B STD N/A

7098-16 B STD N/A

7098-17 B STD N/A

7098-18 B STD N/A

7098-19 B STD N/A

7098-20 B STD N/A

7098-21 B STD N/A

7098-22 B STD N/A

u finsus /Bui

New Jersey: 3000 Lincoln Drive East, Suite A, Marlton, NJ 08053 * (866) 871-1984

Burlingame, CA: 111 Anza Blvd., Suite 122, Burlingame, CA 94010 * (833) 465-5857 Phoenix, AZ: 1501 West Knudsen Drive, Phoenix, AZ 85027 * (800) 651-4802

4526589

Noah Hancock 5/6/2026 5:00 PM

X X X X

X

Terracon Consultants, Inc. - Utah (16459) 6952 S. High Tech Dr., Suite B Midvale, UT 84047

Room

84606 05/06/2026 11:00 AM

61267115-61267098 Noah Hancock

A sb es to s P

LM

B - Bulk sample

X

X

7098-23 B STD N/A

7098-24 B STD N/A

u finsus /Bui

New Jersey: 3000 Lincoln Drive East, Suite A, Marlton, NJ 08053 * (866) 871-1984

Burlingame, CA: 111 Anza Blvd., Suite 122, Burlingame, CA 94010 * (833) 465-5857 Phoenix, AZ: 1501 West Knudsen Drive, Phoenix, AZ 85027 * (800) 651-4802

Appendix D Photo Log

Appendix B: Photo Log

May 21, 2026 | Terracon Project No. 61257098

Facilities | Environmental | Geotechnical | Materials

Photo #1 7098-1: (HA: M01) Yellow Vent Sealant. Not asbestos containing.

Photo #2 7098-4: (HA: M02) Gray Gasket Putty. Not asbestos containing.

Photo #3 7098-7: (HA: M03) Black Vibration Isolator. Not asbestos containing.

Photo #4 7098-9: (HA: M04) Red Caulking.

Not asbestos containing.

Photo #5 7098-12: (HA: S01) Fireproofing.

Not asbestos containing.

Photo #6 7098-17: (HA: T01) TSI Mudded Ends. Not asbestos containing.

Appendix B: Photo Log

May 21, 2026 | Terracon Project No. 61257098

Facilities | Environmental | Geotechnical | Materials

Photo #7 7098-20: (HA: S02) White Block Paint. Not asbestos containing.

Photo #8 Entrance to the State Hospital Forensics Mechanical Rooms.

Appendix E Table 2: XRF Lead Coating Testing Summary

Appendix C: Table 2 Lead Coating Testing Results

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials

Measurement Location Component Substrate Color Result (mg/cm2)

1 Internal Calibration - - - PASS 2 Calibration - - Red 1.03 3 Calibration - - Red 1.09 4 Calibration - - Red 1.03 5 Calibration - - White <0.01 6 Calibration - - White <0.01 7 Calibration - - White <0.01 8 F052 Chiller Room Pipe Metal Green 0.00 9 F052 Chiller Room Pipe Metal Black 0.00

10 F052 Chiller Room Small Electrical Panel Metal Gray 0.00

11 F052 Chiller Room Cabinet Metal Gray 0.00

12 F052 Chiller Room Bacharach Gas Monitor Metal Blue 0.00

13 F052 Chiller Room Chiller Pipe Metal Tan 0.00 14 F052 Chiller Room Chiller Box Metal Tan 0.00 15 F052 Chiller Room Cabinet Metal Brown 0.00 16 F052 Chiller Room Door Metal Yellow 0.00 17 F052 Chiller Room Wall CMU Block Gray 0.00 18 F052 Chiller Room Door Metal Off White 0.00 19 F052 Chiller Room Door Frame Metal Off White 0.00 20 F052 Chiller Room Wall CMU Block Gray 0.00 21 F053 Heat Exchanger Room Wall CMU Block Gray 0.00 22 F053 Heat Exchanger Room Electrical Panel Metal Blue 0.00 23 F053 Heat Exchanger Room Door Metal Yellow 0.00 24 F053 Heat Exchanger Room Boiler Stands Metal Black 0.00 25 F053 Heat Exchanger Room Pipe Metal Copper 0.00

26 F053 Heat Exchanger Room Boiler Base Plate Metal Brown 0.00

27 F053 Heat Exchanger Room Pipe Metal Black 0.00 28 F053 Heat Exchanger Room Door Metal Off White 0.00 29 F053 Heat Exchanger Room Door Frame Metal Off White 0.00

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials

Measurement Location Component Substrate Color Result (mg/cm2)

30 F053 Heat Exchanger Room Ventilation Box Metal Gray 0.00 31 F053 Heat Exchanger Room Wall CMU Block Gray 0.00

32 F053 Heat Exchanger Room Large Electrical Panel Metal Gray 0.00

33 F053 Heat Exchanger Room Door Metal Yellow 0.00 34 F053 Heat Exchanger Room Door Frame Metal Tan 0.00

35 F053 Heat Exchanger Room Small Electrical Panel Metal Gray 0.00

36 F053 Heat Exchanger Room Thermal

Regulator Canister

Metal Red 0.00

37 F053 Heat Exchanger Room Large Thermal

Regulator Canister

Metal Red 0.00

38 F053 Heat Exchanger Room Hersey

Connector Pipe Box

Metal Gold/Black 0.73

39 F053 Heat Exchanger Room By-Pass Feeder Metal Blue 0.00 40 F053 Heat Exchanger Room Pipe Metal Copper 0.00 41 F054 Electrical Room Breaker Box Metal Gray 0.00 42 F054 Electrical Room Wall CMU Block White 0.00 43 F054 Electrical Room Pipe Metal White 0.00 44 F054 Electrical Room Breaker Box Metal White 0.00

45 F054 Electrical Room Light Switch Frame Metal Silver 0.19

46 F054 Electrical Room Lighting Control Panel Metal Off White 0.00

47 F054 Electrical Room Wall CMU Block White 0.00

48 F054 Electrical Room Siemens T-1 Box Metal Green 0.00

49 F054 Electrical Room Wall CMU Block White 0.00 50 F054 Electrical Room Wall CMU Block White 0.00

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials

Measurement Location Component Substrate Color Result (mg/cm2)

51 Upstairs Mech Room Exhaust Ventilation Metal Silver 0.00

52 Upstairs Mech Room Siemen's Breaker Box Metal Gray 0.00

53 Upstairs Mech Room Wall CMU Block Gray 0.00

54 Upstairs Mech Room Speedair Electrical Unit Metal Teal Green 0.00

55 Upstairs Mech Room Johnson Control Panel Metal Dark Gray 0.00

56 Upstairs Mech Room Wall CMU Block Gray 0.00

57 Upstairs Mech Room Confined Space Lift Metal Gray 0.00

58 Upstairs Mech Room Large Ventilation Unit Metal Silver 0.00

59 Upstairs Mech Room Main Ventilation Unit Metal Silver 0.00

60 Upstairs Mech Room Main Ventilation Unit Metal Silver 0.00

61 Upstairs Mech Room Door Metal Gray 0.00 62 Upstairs Mech Room Door Frame Metal Gray 0.00 63 Upstairs Mech Room Wall CMU Block Gray 0.00 64 Upstairs Mech Room Ventilation Unit Metal Silver 0.00 65 Upstairs Mech Room Floor Concrete Gray 0.00

Key:

A = North, B = East, C = South, D = West mg/cm2 = milligrams per square centimeter of surface area

Appendix F Table 3: Universal Waste and Hazardous Materials

Removal Estimates

Appendix F Table 3: Universal Hazardous Waste Removal Cost Estimates

May 21, 2026 | Terracon Project No. 61267098

Facilities | Environmental | Geotechnical | Materials

Material Location Quantity Approximate Removal Cost

4-Foot Light Ballasts Throughout 39 Ballasts @ $19 per Unit $741

4-Foot Fluorescent Bulbs Throughout 78 Bulbs @ $2 per Foot $156

AC Units Upstairs Mechanical Room, F052 Chiller Room, F054 Electrical Room

1 Unit @ $225 per Unit $225

Total $1,122

Notes:

1. Terracon can provide a follow-up visit to ensure these materials were removed and properly disposed of or recycled for a minimal additional cost.

2. Terracon can provide services to bid for removal of these items to locally qualified contractors at an additional cost.

Appendix G Certifications

195 North 1950 West, 4th Floor • Salt Lake City, UT Mailing Address: P.O. Box 144820 • Salt Lake City, UT 84114-4820

Telephone (801) 536-4000 • Fax (801) 536-4099 • T.D.D. (801) 536-4414 www.deq.utah.gov

Printed on 100% recycled paper

State of Utah

Department of Environmental Quality

Tim Davis Executive Director

DIVISION OF AIR QUALITY

Bryce C. Bird

Director

SPENCER J. COX

Governor

DEIDRE HENDERSON

Lieutenant Governor

DAQA-002-25

Noah Hancock 27 East Gilbride Avenue, Apartment 520 Murray, UT 84107

Dear Mr. Hancock:

Re: Utah Lead-Based Paint Program Individual Certification Card

The Utah Division of Air Quality (DAQ) has reviewed your Utah Lead-Based Paint (LBP) Program Certification Application for Individuals and we are pleased to inform you that your application has been approved. Your new LBP program individual certification card is enclosed with this letter and this card is the sole method of individual certification documentation that you will receive from the DAQ.

Please check the information on your LBP program certification card carefully. Please confirm that the photograph, name, and certification discipline(s) are correct. Also, please remember to keep your current LBP program certification card with you at all times when you are performing regulated LBP work activities.

Please contact Barbara Perkins at (801) 536-0221 or at bperkins@utah.gov if you have any questions regarding this letter or the enclosed LBP program certification card.

Sincerely, Leonard Wright, Manager Air Toxics, Lead-Based Paint, and Asbestos Section

LW:BP:aj

Leonard Wright (Sep 25, 2025 16:29:39 MDT)

September 30, 2025

Cover Letter
1.0 Introduction
2.0 Building/Area Description
3.0 Field Activities
3.1 Asbestos
3.2 Lead
3.3 Hazardous Materials
4.0 Regulatory Overview
4.1 Asbestos
4.2 Lead Paint
4.3 Hazardous Materials
5.0 Findings
5.1 Asbestos
5.2 Lead Paint
5.3 Hazardous Materials
5.4 Inaccessible Areas
6.0General Comments
Appendix ATable 1: Asbestos Testing Summary
Appendix BAsbestos Sample Location Drawings
Appendix CAsbestos Laboratory Analytical Reports
Appendix DPhoto Log
Appendix ETable 2: XRF Lead Coating Testing Summary
Appendix F Table 3: Universal Waste and Hazardous Materials Removal Estimates
Appendix GCertifications