This is a Scope of Work document prepared by R & R Environmental, Inc. for the Utah Department of Government Operations, Division of Facilities, Construction and Management (DFCM), detailing pre-demolition asbestos and hazardous materials abatement at Southern Utah University's Ponderosa Terrace Apartments located at 200 South Dewey Avenue, Cedar City, Utah. The project involves removal of multiple asbestos-containing materials (ACM) across nine residential units, including black sink undercoating (18 units at 2% chrysotile asbestos), textured ceiling materials (approximately 7,134 square feet containing up to 3% chrysotile asbestos), joint compound and wall systems (38,106 square feet containing up to 2.25% chrysotile asbestos), pipe thread sealants (approximately 1,100 square feet), one boiler assumed to contain asbestos, fire-rated doors and frames (11 units), and roofing materials and sealants (approximately 4,500 square feet). The project is divided into two bid options: Option 1 addresses items 1-8 (specific ACM removal); Option 2 addresses items 9-13 (boiler removal, textured ceiling material removal, fire-rated doors/frames removal, co-mingled waste demolition, and universal waste removal including PCB ballasts, fluorescent tubes, fire extinguishers, chemicals, microwaves, stoves, and mercury thermometers). Anticipated start and substantial completion dates are listed as TBD. The document was prepared July 17, 2026, with Mrs. Aubrey Stapel identified as the Hazmat Program Manager.
The Scope of Work establishes detailed requirements for contractor qualifications, safety protocols, and operational procedures. All contractors must possess current Utah Division of Air Quality (DAQ) certifications for workers and company-level certification, and must comply with applicable regulations including Utah Asbestos Rule (Rule R-307.801), EPA NESHAP (40 CFR Part 61, Subpart M), OSHA Asbestos Standard (29 CFR 1910.1001), and OSHA Asbestos Construction Standard (29 CFR 1926.1101). Key requirements include attendance at a pre-start meeting with the project supervisor, daily personnel air sampling for friable removal activities with next-day reporting, submission of abatement project design from an AHERA-accredited Utah Certified Project Designer at least three working days before start, hiring a Utah-licensed electrical contractor, provision of weight and measure certifications for all ACM waste with manifest documentation prior to invoice submission, use of fire-retardant poly sheeting with clear plexiglass viewing windows, continuous cleanup of removed ACM with no unattended materials, on-site chemical toilets for personnel, and use of leak-tight containers in poly-lined, enclosed, locked vehicles for waste transportation. The document includes a comprehensive Unit Price Sheet with 81 line items for unforeseen ACM materials, and Appendix B contains detailed asbestos survey and assessment results from laboratory analysis of 67 samples confirming the presence of chrysotile asbestos in identified materials and establishing their friable or non-friable conditions. The Stage II Invitation to Bid indicates a construction cost estimate of $350,000.00 and specifies that only contractors prequalified under Stage I and appearing on the DFCM Prequalified Contractors list as of the solicitation date are eligible to bid.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS AND HAZARDOUS MATERIALS
SCOPE-OF-WORK:
FOR THE
SOUTHERN UTAH UNIVERSITY
PONDEROSA TERRACE APARTMENTS
200 SOUTH DEWEY AVENUE
CEDAR CITY, UTAH 84408
July 17, 2026
Prepared for:
Mrs. Aubrey Stapel
Hazmat Program Manager Utah Department of Government Operations
Division of Facilities, Construction and Management (DFCM) Taylorsville State Office Building, 3rd Floor
4315 South 2700 West Taylorsville, Utah 84114
PH: (801) 641-0964
Prepared by:
R & R Environmental, Inc. (R & R) (ASBC-#237)
47 West 9000 South, Suite #2 Sandy, Utah 84070 jamison@rrenviro.com Phone (801) 928-1560
Division 02 - Site Work
02 000 General
02 080 Hazardous Material Abatement
02 081 Asbestos Abatement:
Scope of Work: SUU Ponderosa Terrace Apartments Building, Phase 1, 200 South Dewey Avenue, Cedar City, Utah 84720
Anticipated Start Date: TBD Substantial Completion Date: TBD
BID OPTION #1
1. Black Sink Undercoating
a. Contractor shall remove all Black Sink Undercoating from Units 1, 2, 3, 4, 5, 6, 7, 8, and 9. This material contains 2% chrysotile asbestos. There are 18 sinks to be removed. This material is not currently friable.
2. Textured Ceiling Material(s)
a. Contractor shall remove all Textured Ceiling Material(s) Units 1, 2, 3, 4, 5, 6, 7, 8, and 9. This material contains up to 3% chrysotile asbestos. There is approximately 7,134 square feet of material to be removed. This material is currently friable.
3. Joint Compound / Wall System
a. Contractor shall remove all Joint Compound / Wall System from the building’s walls and ceilings. The Joint Compound contains up to 2.25% chrysotile asbestos By Point Count. The Wall System contains Overall <1% Chrysotile asbestos By Point Count. There is approximately 38,106 square feet of material to be removed. This material is not currently friable.
4. Pipe Wrap
a. Contractor shall remove all Pipe Wrapping from the Exterior/Subgrade pipes.
This material contains 75% chrysotile asbestos. There is approximately >4 linear feet of material to be removed. This material is not currently friable.
5. Pipe Thread Sealant
a. Contractor shall remove all Pipe Thread Sealants from the building. This material contains up to 0.75% chrysotile asbestos. There is approximately 1,100 square feet of material to be removed. This material is not currently friable.
6. Boiler
a. Contractor shall remove the Boiler from the Mechanical Room. This material is assumed to contain asbestos. There is 1 boiler to be removed. This material is
b. DFCM Hot Works training and policy shall be utilized and followed for any worker/company performing hot work.
https://dfcm.utah.gov/construction-management/building-official/hot-works/
7. Fire Rated Doors/Frames
a. Contractor shall remove all Fire Rated Doors/Frames from the Building. This material is assumed to contain asbestos. There are approximately 11 doors to be removed. This material is not currently friable
8. Roofing Materials and Sealants
a. Contractor shall remove all of the Roofing Materials and Sealants. This material is assumed to contain asbestos. There is approximately 4,500 square feet to be removed. This material is currently not friable.
BID OPTION #2
9. Boiler
a. Contractor shall remove the Boiler from the Mechanical Room. This material is assumed to contain asbestos. There is 1 boiler to be removed. This material is
b. DFCM Hot Works training and policy shall be utilized and followed for any worker/company performing hot work.
10. Textured Ceiling Material(s)
a. Contractor shall remove all Textured Ceiling Material(s) Units 1, 2, 3, 4, 5, 6, 7, 8, and 9. This material contains up to 3% chrysotile asbestos. There is approximately 7,134 square feet of material to be removed. This material is currently friable.
11. Fire Rated Doors/Frames
a. Contractor shall remove all Fire Rated Doors/Frames from the Building. This material is assumed to contain asbestos. There are approximately 11 doors to be removed. This material is not currently friable
12. Co-mingled Waste Demolition. Contractor to demolish or sub-contract the demolition and disposal of the building with the below Category I and Category II non-friable materials to be left in place. Note that this is an OSHA Class II work practice. All comingled waste is to be handled, packaged, and disposed of in accordance with OSHA 29 CFR 1926.1101 requirements.
a. Black Sink Undercoating. This material contains 2% chrysotile asbestos.
There are 18 sinks. This material is not currently friable.
b. Joint Compound / Wall System. The Joint Compound contains up to 2.25% chrysotile asbestos By Point Count. The Wall System contains Overall <1% Chrysotile asbestos By Point Count. There is approximately 38,106 square feet of material. This material is not currently friable.
c. Pipe Wrap. This material contains 75% chrysotile asbestos. There is approximately >4 linear feet of material. This material is not currently friable.
d. Pipe Thread Sealant. This material contains up to 0.75% chrysotile asbestos.
There is approximately 1,100 square feet of material. This material is not friable.
e. Roofing Materials and Sealants. This material is assumed to contain asbestos.
There is approximately 50 square feet of material. This material is currently not
13. Universal Waste
a. Contractor shall remove and properly dispose of all PCB-containing fluorescent light ballasts from the building. 6 ballasts are suspected.
b. Contractor shall remove and properly dispose of all fluorescent light tubes in the building. 125 bulbs have been identified.
c. Contractor shall remove and properly dispose of 4 fire extinguishers and the coolants therein.
d. Contractor shall remove and properly dispose of all paints and chemicals left in the building. There are approximately 6 gallons of inventory.
e. Contractor shall remove and properly dispose of all microwaves and stoves in the building. 10 units have been identified.
f. Contractor shall remove and properly dispose of all mercury thermometers in the building. 4 units have been identified.
14. General
a. All applicable rules will apply including Utah Division of Air Quality (DAQ) Utah
Asbestos Rule (Rule R-307.801), EPA NESHAP (40 CFR Part 61, Subpart M), OSHA Asbestos Standard (29 CFR 1910.1001), and OSHA Asbestos Construction Standard (29 CFR 1926.1101)
b. Contractor shall have current and up-to-date Utah DAQ certifications for all workers conducting abatement. Contractor shall have current and up-to-date Utah DAQ Company Certification. Contractor shall submit a copy of Company Certification and all Individual Certifications as part of their Statement of Qualifications (SOQ).
c. Contractor shall attend a pre-start meeting on the first day of the project and shall ensure that the project supervisor is in attendance. The exact time for this meeting will be confirmed with the Contractor by the Consultant no later than one week prior.
d. Contractor shall conduct personnel air sampling each day of friable removal activity, and shall submit (in writing) all personal air sampling results from the workers on the project to the Consultant no later than the end of the shift the following workday.
e. Contractor shall ensure his work does not cause undue interference with the facility operation outside his abatement area, or unsightly accumulations of debris, materials, personal belongings, etc., and that all areas of the work are secure from the unauthorized entry of patrons and employees of the Owner.
f. Contractor shall provide Consultant with his abatement project design, prepared by an AHERA-accredited Utah Certified Project Designer, no later than 3 working days prior to the start of the project. Any modifications to the design shall be approved by an AHERA-accredited and Utah Certified Project Designer. The design shall be emailed or otherwise delivered to the offices of R&R Environmental, Inc., to the attention of Steve Smith, 47 West 9000 South, Suite 2, Sandy, Utah, 84070, steve@rrenviro.com.
g. Contractor shall hire a Utah-licensed electrical contractor to ensure his electrical design and plans are compatible with the facility operation and with the National Electrical Code. Contractor shall use only electrical equipment rated for work in "damp environments" in the containment area. Any equipment not labeled "rated for work in damp environments" may not be permitted.
h. Contractor shall ensure all equipment brought onto the site is free of suspect asbestos-containing material (ACM). Consultant may disallow use of any equipment with obvious suspect ACM.
i. All ladders and their components shall be maintained in good repair and fully operational, withut makeshift repairs.
j. Reserved.
k. Contractor shall take appropriate steps to safeguard existing items that are scheduled to remain in the facility. These items may include carpeting, flooring, baseboards, wood panels, ceiling trim, equipment such as burglar and fire alarms, sprinklers and sensors, speakers, clocks, mechanical grilles, furnaces, light fixtures, conduits, etc.
l. Contractor shall provide a certificate of weight and measure (or other certification acceptable to the Consultant) for all ACM waste taken from the site. The certification shall list gross, tare and net weights for all ACM waste. Contractor shall also provide, on Contractor's letterhead, a listing of each manifest used for the project, by number and waste tonnage (in pounds) specific to that manifest.
Listing shall show if ACM was disposed of as regulated waste, non-hazardous or any other state-approved category of waste. This information shall be provided prior to, or at the time of invoice submission. No final payment to Contractor will be made without this certification and documentation.
m. All poly sheeting used by Contractor on the project shall be of the fire-retardant type. Each containment area shall be built with a clear plexiglass window no smaller than two feet square, which allows viewing of the entire work from outside the regulated area.
n. Smoking / vaping is not allowed in the building. Contractor's employees who smoke shall go off-site or to a corner of the property and shall police and clean up any cigarette butts or associated debris, transporting this waste immediately to their privately-owned vehicle or a company vehicle. Owner's trash receptacles shall not be used for this waste. Any violation of this provision is grounds for expulsion of the offending party from the work site for its duration.
o. The most stringent regulations in effect for the work site shall apply. Contractor shall determine the extent of city, county, AQMD, state, federal and all other applicable regulations and perform the work in compliance with these regulations.
p. Reserved.
q. Contractor shall provide the Industrial Hygiene Consultant with SDSs for all materials used on their work site. SDSs shall be provided prior to the use of the product.
r. Contractor shall provide an English-speaking interpreter on-site any time
Contractor personnel are non-English-speaking.
s. Contractor’s electrical extension cords shall be suspended off the floor or covered with trip-resistant covering. GFCIs shall be used on all electrical equipment.
t. Removed ACM shall be cleaned up and bagged on a continual basis. No removed ACM shall be left unattended at any time until placed in the locked waste dumpster. All waste shall be disposed of at an in-state waste facility unless agreed to in writing by the Consultant prior to transport. Contractor shall use a waste container that can be made secure from unauthorized disposal, so no extraneous waste is included with the ACM waste generated by Contractor. All ACM waste shall be transported in leak-tight containers, in poly-lined, enclosed, locked vehicles, separate from non-ACM material.
u. Contractor shall maintain a job telephone at Contractor's expense. Telephone shall be operational prior to disturbance of any ACM. Contractor shall be fully responsible for all charges to this telephone.
v. Contractor shall provide chemical toilets on the job site for Contractor's personnel, the Consultant and any authorized visitors. Contractor shall ensure these toilets are maintained appropriately and in a hygienic manner and are established and maintained throughout the duration of the project while contractor is on site.
w. All dimensions, quantities and areas provided in this scope of work are approximations to assist Contractor in determining the amount of ACM designated for removal. Contractor is entirely responsible for accurately determining the amount of ACM included in the scope of work prior to submitting bid forms and proposal.
APPENDIX A
UNIT PRICE SHET
SOUTHERN UTAH UNIVERSITY
PONDEROSA TERRACE APARTMENT BUILDING
July 17, 2026 Company Name:
Unit Pricing: Bidding abatement contractors are to submit their base bid along with the following unit costs for any unforeseen asbestos-containing building materials using the Unit Pricing Cost Sheet which is posted separately.
Item No.
Description
Unit
Unit Price
1 Additional Mobilizations Each $ 2 Hourly Supervisor Rate Hr $ 3 Hourly Worker Rate Hr $ 4 Auto Door Closer Units Each $ 5 Batteries Each $ 6 Fire Extinguisher Each $ 7 Gas Cylinder Each $ 8 Fluorescent light ballast Each $ 9 Fluorescent light tubes 2’ to 8’ long Each $ 10 PCB Ballast Each $ 11 Radioactive Emergency Exit Signs Each $ 12 Transformer Oil gal $ 13 Chemicals gal $ 14 Fertilizer gal $ 15 Fuel gal $ 16 Glycol gal $ 17 Oil gal $ 18 Paints gal $ 19 Thermometers Each $ 20 Pipe fittings 0” to 12” total diameter Each $ 21 Refrigerant unit CFC evacuation Each $ 22 Refrigerant unit CFC evacuation (<50 lbs) Each $ 23 Refrigerant unit CFC evacuation (>300 lbs) Each $ 24 Refrigerant unit CFC evacuation (>50 to 300 lbs) Each $ 25 E-waste (Large) Each $ 26 E-waste (Med) Each $ 27 E-waste (Small) Each $ 28 TV/Monitor/Laptop Each $ 29 Fire Doors/Frames (Insulation) Each $ 30 Fire Rated Blanket Each $ 31 Fire Rated Safe Each $ 32 Fire Rated Curtains SF $ 33 Boiler Each $ 34 All-in Loaded Rate: Dump Trailer Wrapping Per Truck/
Trailer $
35 Roof Vapor Paper SF $ 36 Roof mastic/coating SF $ 37 Roof Plaster Coating SF $ 38 Roof sealant/caulk SF $ 39 Roofing Membrane SF $ 40 Roofing Shingle SF $ 41 Roofing Tar SF $ 42 Vermiculite in CMU Wall SF $
Item No.
Description
Unit
Unit Price
43 Ceiling Texture Material SF $ 44 Wall Texture Material SF $ 45 Wallboard and joint compound (Wall System) SF $ 46 Ceiling Demo SF $ 47 Tar Pipe Wrap SF $ 48 TSI-Tank Wrapping SF $ 49 TSI-Mudded Fittings SF $ 50 Pipe Thread Sealant SF $ 51 Sink Undercoating Each $ 52 CMU Wall Demo SF $ 53 Ducting Demo SF $ 54 Asbestos Cement Board (Transite) SF $ 55 HVAC Duct Gasket SF $ 56 HVAC Duct Sealant SF $ 57 HVAC Paper Tape SF $ 58 AHU Gasket SF $ 59 Concrete Surfacing SF $ 60 Vinyl floor tile and mastic on concrete SF $ 61 Vinyl floor tile and mastic on concrete under carpet SF $ 62 Vinyl floor tile on concrete SF $ 63 Vinyl floor tile on concrete under carpet SF $ 64 Mastic on concrete SF $ 65 Mastic on concrete under carpet SF $ 66 Window Caulk SF $ 67 Window Glaze/Putty SF $ 68 Door Caulk SF $ 69 Caulk SF $ 70 TSI-End Sealant SF $ 71 TSI-Lagging LF $ 72 Wall Adhesive SF $ 73 Electrical Penetration Tar SF $ 74 Waterproofing Mastic SF $ 75 Pipe Chase Debris SF $ 76 Cove Base & Mastic on Drywall SF $ 77 Cove Base removal on drywall SF $ 78 Cove Base Mastic on Drywall SF $ 79 Cove Base & Mastic on CMU SF $ 80 Cove Base Mastic SF $ 81 Cove Base Mastic on Wood / Cabinet SF $
APPENDIX B
SITE PLANS
A S
B E
S T
O S
F
LO
O R
P
LA
N
S O
U T
H E
R N
U
TA
H U
N
IV
E R
S
IT
Y P
O N
D E
R O
S A
T E
R R
A C
E C
E D
A R
C
IT
Y, U
TA
H
D E
C E
M B
E R
P O
N D
E R
O S
A T
E R
R A
C E
S A
M P
LE
N
U M
B E
R A
N D
L O
C A
T
IO
N
T
E X
T U
R E
D W
A
LL
C
E
IL
IN
G
M A
T E
R
IA
L
A P
A R
T M
E N
T N
U M
B E
R
T
E X
T U
R E
D C
E
IL
IN
G
M A
T E
R
IA
L
U N
IT
S
IN
K U
N D
E R
C O
A T
IN
G
B A
S E
M E
N T
F
LO
O R
C E
IL
IN
G S
U N
IT
U
N
IT
U N
IT
B E
S T
O S
F
LO
O R
P
LA
N
S O
U T
H E
R N
U
TA
H U
N
IV
E R
S
IT
Y P
O N
D E
R O
S A
T E
R R
A C
E C
E D
A R
C
IT
Y, U
TA
H
D E
C E
M B
E R
P O
N D
E R
O S
A T
E R
R A
C E
S A
M P
LE
N
U M
B E
R A
N D
L O
C A
T
IO
N
A
P A
R T
M E
N T
N U
M B
E R
T
E X
T U
R E
D C
E
IL
IN
G
M A
T E
R
IA
L
U N
IT
M A
IN
F
LO
O
R C
E
IL
IN
G
S
U N
IT
U
N
IT
U N
IT
S
IN
K
U N
D E
R C
O A
T
IN
G
30 31
21 22
B E
S T
O S
F
LO
O R
P
LA
N
S A
M P
LE
N
U M
B E
R A
N D
L O
C A
T
IO
N
S O
U T
H E
R N
U
TA
H U
N
IV
E R
S
IT
Y P
O N
D E
R O
S A
T E
R R
A C
E C
E D
A R
C
IT
Y, U
TA
H
D E
C E
M B
E R
P O
N D
E R
O S
A T
E R
R A
C E
T
E X
T U
R E
D W
A
LL
C
E
IL
IN
G
M A
T E
R
IA
L
A P
A R
T M
E N
T N
U M
B E
R
T
E X
T U
R E
D C
E
IL
IN
G
M A
T E
R
IA
L
U N
IT
U
N
IT
U N
IT
U N
IT
S
IN
K U
N D
E R
C O
A T
IN
G
U P
P E
R F
LO
O
R C
E
IL
IN
G
S
APPENDIX C
ASBESTOS SURVEY AND ASSESSMENT REPORTS
ASBESTOS, LEAD, AND HAZARDOUS MATERIALS
INSPECTION, SURVEY AND ASSESSMENT
FOR THE
SOUTHERN UTAH UNIVERSITY
PONDEROSA TERRACE
CEDAR CITY, UTAH 84720
AN ASBESTOS SURVEY AND ASSESSMENT
FOR THE
SOUTHERN UTAH UNIVERSITY
PONDEROSA TERRACE
Mrs. Aubrey Stapel Project Manager
State of Utah Department of Administrative Services
Division of Facilities Construction and Management (DFCM) State Office Building Room 4110
Salt Lake City, Utah 84114
PH: (801) 641-0964
R & R Environmental, Inc. (R & R)
47 West 9000 South, Suite #2 Sandy, Utah 84070 jamison@rrenviro.com Phone (801) 928-1560
TABLE OF CONTENTS
ASBESTOS
1.0 INTRODUCTION
2.0 EXECUTIVE SUMMARY
3.0 SAMPLING METHODS
4.0 SURVEY RESULTS
5.0 CONCLUSIONS
6.0 LIMITATIONS AND EXCLUSION OF WARRANTY.……………………………………………………6
List of Appendices
Appendix A Sample Log
Appendix B Laboratory Report
Appendix C Photo Log
Appendix D Floor Plans
Appendix E State of Utah Certifications
Asbestos Survey Report Page 1 SUU, Ponderosa Terrace Cedar City, Utah 84720
1.0 INTRODUCTION
R & R Environmental, Inc. (R & R) was contacted to conduct an asbestos survey for the Southern Utah University, Ponderosa Terrace located at 200 South Dewey Avenue in Cedar City, Utah 84720. The Ponderosa Terrace is set to be demolished. The survey consisted of a visual assessment of the structure for suspect asbestos containing materials (ACM) and bulk sampling of the materials. The fieldwork component of this survey was conducted by Mr. Jamison Moss and Mr.
Steve Smith, both of whom are Utah Certified Asbestos Building Inspectors.
This report presents the conditions and observations noted on the visit dates.
The following general information is included in this survey report:
• Executive Summary (Section 2.0)
• Sampling Methods (Section 3.0)
• Analytical Results (Section 4.0)
• Conclusions (5.0)
• Limitations & Exclusion of Warranty (6.0)
Asbestos Survey Report Page 2
2.0 EXECUTIVE SUMMARY
The asbestos-containing material (ACM) identified at the Southern Utah University, Ponderosa Terrace located at 200 South Dewey Avenue in Cedar City, Utah 84720 is as follows:
Material Location Quantity % Asbestos Friable Condition Photo
Sink Undercoating Units 1, 2, 3, 4, 5, 6, 7, 8, and 9 18 ea 2% Chrysotile No Good 2
Textured Ceiling Materials
Units 1, 2, 3, 4, 5, 6, 7, 8, and 9 7,134 ft² Up to
3% Chrysotile Yes Good 3-5
Joint Compound / Wall System2
Walls & Ceilings 38,106 ft²
2.25% Chrysotile Joint Compound (By Point Count)
Overall <1% Chrysotile
(By Point Count)
Yes Good 3-5
Pipe Thread Sealant Throughout ~1,100 ft²
Up to 0.75% Chrysotile
(By Point Count) No Good 6
Pipe Wrap1 Exterior >165 ft² 75% Chrysotile No Good 7 Boiler Mechanical 1 unit Assumed No Good 8
Roofing Materials Roof ~4,500 ft² Assumed Yes Good 9 Fire Rated
Doors/Frames Throughout 11 ea Assumed No Good 10
Notes:
1- This material appears to exist underground.
2- The joint compound contains 2.25% Chrysotile asbestos (by point count) and is considered by the OSHA as an ACM. The Wall System material as defined by the EPA contains Chrysotile Asbestos in the joint compound with an overall asbestos content of less than 1% (by point count). According to the Federal Register page 542, Wednesday, January 5, 1994, 40 CFR Part 61, "Asbestos NESHAP Clarification Regarding Analysis of Multi-Layered Systems", when joint compound is applied to wallboard, it becomes an integral part of it, forming a wall system. Composite analysis of the wall system is to be conducted. In this case, the wall system contains less than 1% asbestos and is therefore not subject to the NESHAP. The joint compound however is regulated by the OSHA. Removal of this material is a Class II Operation under OSHA, which requires 40-hour trained supervisors, trained workers and specific work practices (wet methods, prompt clean-up of debris, HEPA vacuums, etc.)
Asbestos Survey Report Page 3
SOUTHERN UTAH UNIVERSITY, PONDEROSA TERRACE
200 SOUTH DEWEY AVENUE, CEDAR CITY, UTAH 84720
DATE OF SURVEY: JULY 2026
NESHAP - REGULATED
ASBESTOS-CONTAINING MATERIALS (R-ACM)
1. Friable asbestos material (>1% asbestos and can be crumbled, pulverized, or reduced to powder by hand pressure) X Thermal system insulation (TSI)* X Textured ceiling material (TCM)* Spray-on insulation or fireproofing* Blown-in insulation* Ceiling tiles/panels* X_ Plaster, gypsum board, gypsum board joint compound* Cloth materials* (Boiler Flue Gasket) Paper materials* (HVAC Paper Tape and Insulating Board) Electrical wiring insulation* Sink undercoating (loose)* X Other (Wall System / Joint Compound)*
2. Category I ACM which has become friable
Packings Gaskets Resilient floor coverings (floor tile and sheet vinyl) Asphalt roofing products (Dust Debris, Roofing Underlayment Debris, Flashing Material)
3. Category I ACM that will be or has been subjected to sanding, grinding, cutting, or abrading
Packings Gaskets Resilient floor coverings (floor tile and sheet vinyl) Asphalt roofing products
4. Category II ACM that has a high probability of becoming or has become friable during demolition or renovation operations Asbestos cement materials (TransiteT)* Asphalt, tar and rubber-base ACM products other than roofing products* Non-asphalt and non-paper roofing products* Paint* Fire brick and/or mortar* X Stainless steel sink undercoating (solid)* Encapsulated TCM* Encapsulated TSI* Mastic for floor tile, ceiling tile, cove molding, etc.* X Other (Joint Compound)
Asbestos Survey Report Page 4
SOUTHERN UTAH UNIVERSITY, PONDEROSA TERRACE
200 SOUTH DEWEY AVENUE, CEDAR CITY, UTAH 84720
DATE OF SURVEY: JULY 2026
NESHAP NON-REGULATED
ASBESTOS-CONTAINING MATERIAL (N-R-ACM)
1. > 1% asbestos
2. Category I Non-friable (cannot be crumbled, pulverized, or reduced to powder by hand pressure)
ACM with >1% asbestos by new PLM procedure Packings Gaskets (Window Glazing & Caulking) Resilient floor coverings (floor tile) X Asphalt roofing products
3. Category II Non-friable ACM with >1% asbestos by new PLM procedure (Category includes items meeting Category I definition but not specifically listed in that category) Asbestos cement materials (TransiteT)* (Fume hoods, counter tops, and window panels) Asphalt, tar and rubber-base ACM products other than roofing products* Non-asphalt and non-paper roofing products* Paint* (Silver Paint Sealant) Fire brick and/or mortar* __ Sink undercoating (solid)* Mastic for floor tile, ceiling tile, cove molding, etc.* X Other* (Fire Rated Door/Frame)
Notes:
1. (*) Denotes R&R’s interpretation of materials included in this category.
2. New PLM procedure is outlined in Appendix A, Subpart F, 40 CFR, Part 783, Section 1, Polarized Light Microscopy.
3. The Environmental Protection Agency (EPA) National Emission Standard for Hazardous Air
Pollutants (NESHAP) asbestos revision as outlined in 40 CFR, Part 61, became effective November 20, 1990. The asbestos classification system outlined in the revision and included in this section is dynamic in nature. Asbestos materials classified as “NON-REGULATED” at the time of the survey may become “REGULATED” due to ongoing or planned maintenance, renovation, or demolition actions, which can transform a material containing greater than 1% asbestos from a “non-friable” and NON-REGULATED to a friable and REGULATED condition.
Classification of ACM in this section and in the executive summary of this report is, therefore, based on the observations of the surveyor at the time of the survey and may or may not be appropriate at later dates.
4. Maintenance, renovation, demolition, weathering, normal wear, water, or other damage can alter the “NON-REGULATED” status of materials, and necessitate precautions required for handling them as “REGULATED” asbestos-materials.
Asbestos Survey Report Page 5
Cedar City, Utah 84720
3.0 SAMPLING METHODS
Survey procedures were based on those outlined in Title 40 Code of Federal Regulation (CFR) Part 763, USEPA Asbestos Hazard Emergency Response Act, and the Asbestos Model Accreditation Plan (effective April 4, 1994). The procedures included visual observation, physical inspection, bulk sample collection, and condition assessment of suspect ACM. The number of samples collected was based on the amount and accessibility of each homogeneous material, with consideration given for the type, age, and condition.
Sixty-seven (67) samples were collected from the suspect materials to assess the presence of asbestos (or lack thereof) in building materials/systems. Each sample collected was placed into a sealable plastic bag or tub, marked with a unique sample identification code, and packaged for subsequent shipment to the laboratory for analysis. Individual sample identification consisted of a numeric code denoting the sampling media/location.
After packaging and labeling, samples were submitted under proper chain-of-custody to Reservoirs Environmental, Inc., Denver, Colorado. The National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896 accredits Reservoirs for asbestos analysis.
Samples were analyzed via Polarized Light Microscopy (PLM) utilizing EPA Method 600/M4- 82-020. Please note that USEPA and OSHA regulations define an ACM as a material containing more than one (1) percent asbestos, by volume, as determined by PLM analysis. In the case of multi-layer systems (e.g., floor tile/mastic layers), the laboratory analyzed and reported each layer separately.
4.0 SURVEY RESULTS
Sixty-seven (67) representative samples collected were submitted for analytical determination.
A summary of analytical results for samples collected and analyzed for this survey are in Appendix B (Laboratory Results) and are discussed below by building material/system type.
Photographs of the buildings where samples were taken are included as Appendix C. Floor Plans of the building where samples were taken are included in Appendix D
Asbestos Survey Report Page 6
5.0 CONCLUSIONS
Asbestos-containing materials were identified in the building. See Executive Summary for details.
The identified materials must be removed prior to disturbance by a licensed abatement contractor.
6.0 LIMITATIONS AND EXCLUSION OF WARRANTY
This asbestos survey and assessment was performed using procedures and a level of diligence typically exercised by professional consultants performing similar services. However, asbestos-containing material (ACM) can be present in a structure, but not identified using ordinary investigative procedures.
No asbestos survey can completely, eliminate uncertainty regarding the presence of ACM.
R&R Environmental, Inc.’s level of diligence and investigative procedures are intended to reduce, but not eliminate, potential uncertainty regarding the presence of ACM. The procedures used for this survey attempt to establish a balance between the competing goals of limiting investigative costs, time, and building damage, and reducing the uncertainty about unknown conditions. Therefore, the determinations in this report should not be construed as a guarantee that all ACM present in the subject property has been included in this report.
This report presents R&R Environmental, Inc.’s professional determinations, which are dependent upon information obtained during performance of consulting services. R&R Environmental, Inc. assumes no responsibility for omissions or errors resulting from inaccurate information provided by sources outside of R&R Environmental, Inc.
No warranty or guarantee, expressed or implied, is made regarding the findings, conclusions, or recommendations contained in this report. The limitations presented above supersede the requirements or provisions of all other contracts or scopes of work, implied, or otherwise, except stated or acknowledged herein.
Asbestos Survey Report Page 7
OF THE
SOUTHERN UTAH UNIVERSITY
PONDEROSA TERRACE
During the months 2013, August 2025, and July 2026 R & R Environmental, Inc. (R & R) of Sandy, Utah, conducted an asbestos survey and assessment of the Southern Utah University, Ponderosa Terrace located at 200 South Dewey Avenue in Cedar City, Utah 84720. Bulk samples of suspect asbestos-containing materials were collected and analyzed. The condition of all friable and non-friable asbestos-containing materials was, assessed. The following accredited inspector conducted the survey and assessment.
Inspected by:
Jamison Moss Date State of Utah, Division of Air Quality Inspector Certification Number: ASB-6674 State of Utah Company Certification: ASBC-237
Steve B. Smith Date State of Utah, Division of Air Quality Inspector Certification Number: ASB-3274 State of Utah Company Certification ASBC-237
This report was reviewed by:
July 17, 2026 David C. Roskelley, MSPH, CIH, CSP Date State of Utah, Division of Air Quality Inspector Certification Number: ASB-1370 AHERA Inspector #5 PSI 65451 I Certified Safety Professional #15774 Certified Industrial Hygienist #8529 State of Utah Company Certification: ASBC-237
Appendix A
Sample Log
SAMPLE LOG
Sample # Material/
Homogenous Area
Sample
Location
Quantity
Lab Result (%/Type)
Assessment
SUU-PT-12-17-01 Sheet Vinyl Tile #1 & Mastic Unit 5 1,004 ft² None Detected Undamaged
SUU-PT-12-17-02 Sheet Vinyl Tile #1 & Mastic Unit 6 1,255 ft² None Detected Undamaged
SUU-PT-12-17-03 Vinyl Cove Base (Tan) & Mastic Unit 6 515 ft2 None Detected Undamaged
SUU-PT-12-17-04 Sink Undercoating Unit 5 18 ft2 2% Chrysotile Undamaged SUU-PT-12-17-05 Exterior Caulking Exterior 108 lf None Detected Undamaged SUU-PT-12-17-06 Wall System Unit 4 38,106 ft² 1.5% Chrysotile Undamaged SUU-12-PT-17-07 Wall System Unit 2 38,106 ft² 1.5% Chrysotile Undamaged SUU-12-PT-17-08 Wall System Unit 3 38,106 ft² 1.5% Chrysotile Undamaged SUU-12-PT-17-09 Wall System Unit 5 38,106 ft² 1.5% Chrysotile Undamaged SUU-PT-12-17-10 Wall System Unit 6 38,106 ft² 1.5% Chrysotile Undamaged SUU-PT-12-17-11 Wall System Unit 7 38,106 ft² 1.5% Chrysotile Undamaged SUU-PT-12-17-12 Wall System Unit 9 38,106 ft² 1.5% Chrysotile Undamaged SUU-PT-12-17-13 Textured Ceiling Material Unit 1 6,426 ft2 3% Chrysotile Undamaged SUU-PT-12-17-14 Textured Ceiling Material Unit 2 6,426 ft2 3% Chrysotile Undamaged SUU-PT-12-17-15 Textured Ceiling Material Unit 3 6,426 ft2 3% Chrysotile Undamaged SUU-PT-12-17-16 Textured Ceiling Material Unit 5 6,426 ft2 3% Chrysotile Undamaged SUU-PT-12-17-17 Textured Ceiling Material Unit 6 6,426 ft2 3% Chrysotile Undamaged SUU-PT-12-17-18 Textured Ceiling Material Unit 7 6,426 ft2 3% Chrysotile Undamaged SUU-PT-12-17-19 Textured Ceiling Material Unit 9 6,426 ft2 3% Chrysotile Undamaged SUU-PT-12-17-20 Textured Ceiling Material Laundry Room 120 ft² None Detected Undamaged SUU-PT-12-17-21 Textured Ceiling Material Laundry Room 120 ft² None Detected Undamaged
SUU-PT-12-17-22 Textured Ceiling Material Laundry Room 120 ft² None Detected Undamaged SUU-PT-12-17-23 Textured Ceiling Material Unit 2 3,453 ft² None Detected Undamaged SUU-PT-12-17-24 Textured Ceiling Material Unit 2 3,453 ft² None Detected Undamaged SUU-PT-12-17-25 Textured Ceiling Material Unit 2 357 ft² 1% Chrysotile Undamaged SUU-PT-12-17-26 Textured Ceiling Material Unit 3 357 ft² None Detected Undamaged SUU-PT-12-17-27 Textured Ceiling Material Unit 3 357 ft² None Detected Undamaged SUU-PT-12-17-28 Textured Ceiling Material Unit 3 117 ft² 1.2% Chrysotile Undamaged SUU-PT-12-17-29 Textured Ceiling Material Unit 4 117 ft² None Detected Undamaged SUU-PT-12-17-30 Textured Ceiling Material Unit 4 117 ft² None Detected Undamaged SUU-PT-12-17-31 Textured Ceiling Material Unit 4 117 ft² None Detected Undamaged SUU-PT-12-17-32 Textured Ceiling Material Unit 5 117 ft² None Detected Undamaged SUU-PT-12-17-33 Textured Ceiling Material Unit 5 117 ft² None Detected Undamaged SUU-PT-12-17-34 Textured Ceiling Material Unit 5 117 ft² None Detected Undamaged SUU-PT-12-17-35 Textured Ceiling Material Unit 8 117 ft² 1.2% Chrysotile Undamaged SUU-PT-12-17-36 Textured Ceiling Material Unit 8 117 ft² None Detected Undamaged SUU-PT-12-17-37 Textured Ceiling Material Unit 8 117 ft² None Detected Undamaged SUU-PT-12-17-38 Textured Ceiling Material Unit 9 117 ft² None Detected Undamaged SUU-PT-12-17-39 Textured Ceiling Material Unit 9 117 ft² 1.2% Chrysotile Undamaged SUU-PT-12-17-40 Textured Ceiling Material Unit 9 117 ft² 1.2% Chrysotile Undamaged SUU-PT-12-17-41 Textured Wall Material Unit 1 3,453 ft² None Detected Undamaged SUU-PT-12-17-42 Textured Wall Material Unit 2 3,453 ft² None Detected Undamaged SUU-PT-12-17-43 Textured Wall Material Unit 3 3,453 ft² None Detected Undamaged SUU-PT-12-17-44 Textured Wall Material Unit 8 3,453 ft² None Detected Undamaged SUU-PT-12-17-45 Textured Wall Material Unit 9 3,453 ft² None Detected Undamaged
B-46 Vinyl Cove Base (Tan) & Mastic Unit 7 515 ft² None Detected Undamaged
B-47 Caulk (Exterior) Exterior 108 ft² None Detected Undamaged
B-48 Sheet Vinyl Tile #1 & Mastic Unit 8 1,255 ft² None Detected Undamaged
B-49 Sheet Vinyl Tile #2 & Mastic Unit 7 250 ft² None Detected Undamaged
B-50 Sheet Vinyl Tile #2 & Mastic Unit 7 250 ft² None Detected Undamaged
B-51 Pipe Thread Sealant Unit 9 ~1,100 ft² 0.25% Chrysotile (By Point Count) Undamaged
B-52 Pipe Thread Sealant Unit 2 ~1,100 ft² 0.5% Chrysotile (By Point Count) Undamaged
B-53 Pipe Thread Sealant Mechanical ~1,100 ft² None Detected Undamaged
B-54 Pipe Thread Sealant Mechanical ~1,100 ft² 0.75% Chrysotile (By Point Count) Undamaged
B-55 Window Caulk (Gray) Unit 4 1,116 ft² None Detected Undamaged B-56 Window Caulk (Gray) Unit 9 1,116 ft² None Detected Undamaged B-57 Pipe Wrap Exterior >4 ft² 75 % Chrysotile Undamaged B-58 Pipe Wrap Exterior >4 ft² 75 % Chrysotile Undamaged
R-01 Joint Compound / Wall System Unit 01 38,106 ft2
2.0% Chrysotile (Joint Compound)
0.55% Chrysotile (Composite) Undamaged
R-02 Joint Compound / Wall System Unit 01 38,106 ft2
2.0% Chrysotile (Joint Compound)
0.58% Chrysotile (Composite) Undamaged
R-03 Joint Compound / Wall System Unit 01 38,106 ft2
2.25% Chrysotile (Joint Compound)
0.67% Chrysotile (Composite) Undamaged
R-04 Joint Compound / Wall System Unit 01 38,106 ft2
2.25% Chrysotile (Joint Compound)
0.67% Chrysotile (Composite) Undamaged
R-05 Joint Compound / Wall System Unit 01 38,106 ft2
2.0% Chrysotile (Joint Compound)
0.82% Chrysotile (Composite) Undamaged
R-06 Joint Compound / Wall System Unit 01 38,106 ft2
2.5% Chrysotile (Joint Compound)
0.63% Chrysotile (Composite) Undamaged
R-07 Joint Compound / Wall System Unit 01 38,106 ft2
2.0% Chrysotile (Joint Compound)
0.29% Chrysotile (Composite) Undamaged
R-08 Joint Compound / Wall System Unit 01 38,106 ft2
2.5% Chrysotile (Joint Compound)
0.95% Chrysotile (Composite) Undamaged
R-09 Joint Compound / Wall System Unit 01 38,106 ft2
1.75% Chrysotile (Joint Compound)
0.72% Chrysotile (Composite) Undamaged
Appendix B
Laboratory Report
August 11, 2025
Sincerely, Jeanne Spencer President
Subcontractor Number:
Laboratory Report: RES 680634-2
Project #/P.O. #: SUU
Project Description: Ponderosa Apts
Trevor Thacker R & R Environmental 47 West 9000 South #2 Sandy UT 84070
Dear Trevor, Eurofins Reservoirs is an analytical laboratory accredited for the analysis of Industrial Hygiene and Environmental matrices by the National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896-0 for Transmission Electron Microscopy (TEM) and Polarized Light Microscopy (PLM) analysis and the American Industrial Hygiene Association (AIHA LAP), Lab ID 101533 for Phase Contrast Microscopy (PCM) analysis. This laboratory is currently proficient in both Proficiency Testing and PAT programs respectively.
Eurofins Reservoirs has analyzed the following samples for asbestos content as per your request. The analysis has been completed in general accordance with the appropriate methodology as stated in the attached analysis table. The results have been submitted to your office.
RES 680634-2 is the job number assigned to this study. This report is considered highly confidential and the sole property of the customer. Eurofins Reservoirs will not discuss any part of this study with personnel other than those of the client. The results described in this report only apply to the samples analyzed, as received and with the information provided by the customer. This report must not be used to claim endorsement of products or analytical results by NVLAP or any agency of the U.S. Government. This report shall not be reproduced except in full, without written approval from Eurofins Reservoirs. Samples will be disposed of after sixty days unless longer storage is requested. If you have any questions about this report, please feel free to call 303-964-1986.
by Camryn Baumgartner
08/11/202508/11/202508/11/202508/11/2025
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective September 06, 2023 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
4955 Yarrow St, Suite 100, Arvada, CO 80002
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non- AAAA SubSubSubSub AsbestosAsbestosAsbestosAsbestos FibrousFibrousFibrousFibrous YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%)
680634 -680634 -680634 -680634 - B-46B-46B-46B-46 A Yellow adhesive 6 NDNDNDND 0 100.0
B Gray cove base w/ off-white paint 94 NDNDNDND 0 100.0
680634 -680634 -680634 -680634 - B-47B-47B-47B-47 A White caulk 100 NDNDNDND 0 100.0
680634 -680634 -680634 -680634 - B-48B-48B-48B-48 A Yellow adhesive 4 NDNDNDND 0 100.0
B Gray/multi-colored sheet vinyl w/ off-white fibrous backing material
96 NDNDNDND 20 80.0
680634 -680634 -680634 -680634 - B-49B-49B-49B-49 A Yellow adhesive TR NDNDNDND 0 100.0
B Gray leveling compound 2 NDNDNDND 6 94.0
C Gray/multi-colored sheet vinyl w/ a trace of tan adhesive 28 NDNDNDND 5 95.0
D Light-gray sheet vinyl w/ off-white fibrous backing material 70 NDNDNDND 25 75.0
680634 -680634 -680634 -680634 - B-50B-50B-50B-50 A Tan adhesive 3 NDNDNDND 0 100.0
B Yellow adhesive 7 NDNDNDND 0 100.0
C Gray/multi-colored sheet vinyl 40 NDNDNDND 4 96.0
D Light-gray sheet vinyl w/ off-white fibrous backing material 50 NDNDNDND 25 75.0
680634 -680634 -680634 -680634 - B-51B-51B-51B-51 A Gray resinous material 100 ChrysotileChrysotileChrysotileChrysotile TRTRTRTR 0 100.0
Point Count Point Count Point Count Point Count 0.250.250.250.25
TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective September 06, 2023 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
RES Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
RES 680634-2
R & R Environmental
SUU
Ponderosa Apts August 08, 2025 EPA 600/R-93/116 - Point Count, Bulk (400) Priority August 08, 2025
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%)
680634 -680634 -680634 -680634 - B-52B-52B-52B-52 A Tan resinous material 100 ChrysotileChrysotileChrysotileChrysotile TRTRTRTR 0 100.0
Point Count Point Count Point Count Point Count 0.500.500.500.50
680634 -680634 -680634 -680634 - B-53B-53B-53B-53 A Tan/light-gray resinous material 100 NDNDNDND 0 100.0
680634 -680634 -680634 -680634 - B-54B-54B-54B-54 A Tan/multi-colored paint 40 NDNDNDND 0 100.0
B Gray resinous material 60 ChrysotileChrysotileChrysotileChrysotile TRTRTRTR 0 100.0
Point Count Point Count Point Count Point Count 0.750.750.750.75
680634 -680634 -680634 -680634 - B-55B-55B-55B-55 A Gray caulk 100 NDNDNDND 0 100.0
680634 -680634 -680634 -680634 - B-56B-56B-56B-56 A Gray caulk 100 NDNDNDND 0 100.0
680634 -680634 -680634 -680634 - B-57B-57B-57B-57 A Black multi-layered tar 17 NDNDNDND 0 100.0
B White fibrous material 83 ChrysotileChrysotileChrysotileChrysotile 75757575 0 25.0
680634 -680634 -680634 -680634 - B-58B-58B-58B-58 A Black multi-layered tar 5 NDNDNDND 0 100.0
B White fibrous material 95 ChrysotileChrysotileChrysotileChrysotile 75757575 0 25.0
TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Daniel Erhard Analyst
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective September 06, 2023 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
RES Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
RES 680634-2
R & R Environmental
SUU
Ponderosa Apts August 08, 2025 EPA 600/R-93/116 - Point Count, Bulk (400) Priority August 08, 2025
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
SUBMITTED BY INVOICE TO
Client Sample ID Number
RES Job #: 680634
CONTACT INFORMATION SERIES
ASBESTOS LABORATORY REQUESTED ANALYSIS VALID MATRIX CODES LAB NOTES
CHEMISTRY LABORATORY
MICROBIOLOGY LABORATORY
**Turnaround times establish a laboratory priority, subject to laboratory volume and are not guaranteed. Additional fees apply for afterhours, weekends and holidays.**
Laboratory Analysis Instructions
(Sample ID's must be unique)
Company: R & R Environmental Company: R & R Environmental
Address: 47 West 9000 South #2 Address: 47 West 9000 South #2
Sandy, UT 84070 Sandy, UT 84070
Project Number and/or P.O. #: SUU Project Zip Code:
Project Description/Location: Ponderosa Apts
Contact: Trevor Thacker -1 PLM Priority Phone: (435) 229-9174
Fax:
Cell: (435) 229-9174
Final Data Deliverable Email Address:
tthacke2008@yahoo.com (+ 22 ADDNL. CONTACTS)
PLM / PCM / TEM DTL RUSH PRIORITY STANDARD Air = A Bulk = B
Dust = D Food = F
Paint = P Soil = S
Dust RUSH PRIORITY STANDARD
*PRIOR NOTICE REQUIRED FOR SAME DAY TAT
Surface = SU Swab = SW
Tape = T Wipe = W
Metals RUSH PRIORITY STANDARD Drinking Water = DW
Waste Water = WW
Organics* SAME DAY RUSH PRIORITY STANDARD **ASTM E1792 approved wipe media only**
Viable Analysis** PRIORITY STANDARD
**TAT DEPENDENT ON SPEED OF MICROBIAL GROWTH
Medical Device Analysis RUSH STANDARD
Mold Analysis RUSH PRIORITY STANDARD
Special Instructions:
ASBESTOS CHEMISTRY MICROBIOLOGY ICO
1 B-46 X B
2 B-47 X B
3 B-48 X B
4 B-49 X B
5 B-50 X B
6 B-51 X B
7 B-52 X B
8 B-53 X B
9 B-54 X B
10 B-55 X B
11 B-56 X B
12 B-57 X B
13 B-58 X B
P L
M
P L
M S h o rt R ep o rt (E
PA
/6
/R
-9 3/
6)
T E
M
P C
M
D U
S T
M E
TA
L
S
O R
G A
N
IC
S
V
IA
B L
E S
M E
D
IC
A L
M O
L D
S am pl e
V ol um e
(L
A re a
S am pl e
Te m pe ra tu re
C
Le ng th (o r A liq uo ts
) x W id th
(o r A re a/
A liq uo t)
M at rix C od e of
C on ta in er s
D at e C ol le ct ed m m
/d d/ yy
T im e C ol le ct ed hh :m m
Eurofins Reservoirs Environmental, Inc establishes a unique Lab Sample ID, for each sample, by preceding each unique Client Sample ID with the laboratory RES Job Number.
Eurofins Reservoirs Environmental, Inc will analyze incoming samples based on information received and will not be responsible for errors or omissions in calculations resulting from the inaccuracy of original data. By signing, client/company representative agrees that submission of the following samples for requested analysis as indicated on this Chain of Custody shall consitute an analytical services agreement with payment terms of NET 30 days. Failure to comply with payment terms may result in a 1.5% monthly interest surcharge.
Relinquished By:
Trevor Thacker Date/Time: 08/07/2025 11:34:08 Sample Condition: Acceptable
Received By:
Emily Creasey Date/Time: 08/08/2025 10:58:48 Carrier: Fed-Ex
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective September 06, 2023 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
June 29, 2026
Sincerely, Jeanne Spencer President
Subcontractor Number:
Laboratory Report: RES 762353-2
Project #/P.O. #: Ponderosa Terrace
Project Description: Bulk Samples
Trevor Thacker R & R Environmental 47 West 9000 South #2 Sandy, UT 84070
Dear Trevor, Eurofins Reservoirs is an analytical laboratory accredited for the analysis of Industrial Hygiene and Environmental matrices by the National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896-0 for Transmission Electron Microscopy (TEM) and Polarized Light Microscopy (PLM) analysis and the American Industrial Hygiene Association (AIHA LAP), Lab ID 101533 for Phase Contrast Microscopy (PCM) analysis. This laboratory is currently proficient in both Proficiency Testing and PAT programs respectively.
Eurofins Reservoirs has analyzed the following samples for asbestos content as per your request. The analysis has been completed in general accordance with the appropriate methodology as stated in the attached analysis table. The results have been submitted to your office.
RES 762353-2 is the job number assigned to this study. This report is considered highly confidential and the sole property of the customer. Eurofins Reservoirs will not discuss any part of this study with personnel other than those of the client. The results described in this report only apply to the samples analyzed, as received and with the information provided by the customer (i.e. sample volumes and areas). This report must not be used to claim endorsement of products or analytical results by NVLAP or any agency of the U.S. Government. This report shall not be reproduced except in full, without written approval from Eurofins Reservoirs. Samples will be disposed of after sixty days unless longer storage is requested. If you have any questions about this report, please feel free to call 303-964-1986.
by Camryn Baumgartner
06/29/202606/29/202606/29/202606/29/2026
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%)
762353 -762353 -762353 -762353 - R1R1R1R1 A Off-white compound 12 ChrysotileChrysotileChrysotileChrysotile 3333 0 97.0
Point Count Point Count Point Count Point Count 2.002.002.002.00
B Off-white joint compound 13 ChrysotileChrysotileChrysotileChrysotile 3333 0 97.0
Point Count Point Count Point Count Point Count 1.751.751.751.75
C White paint 15 NDNDNDND 0 100.0
D White tape 30 NDNDNDND 95 5.0
E Off-white/tan drywall 30 NDNDNDND 15 85.0
Composite Composite Composite Composite 0.550.550.550.55
762353 -762353 -762353 -762353 - R2R2R2R2 A Off-white compound 12 ChrysotileChrysotileChrysotileChrysotile 3333 0 97.0
Point Count Point Count Point Count Point Count 2.002.002.002.00
B Off-white joint compound 13 ChrysotileChrysotileChrysotileChrysotile 3333 0 97.0
Point Count Point Count Point Count Point Count 1.501.501.501.50
C White tape 20 NDNDNDND 95 5.0
D White paint 25 NDNDNDND 0 100.0
E Off-white/tan drywall 30 NDNDNDND 15 85.0
Composite Composite Composite Composite 0.580.580.580.58
TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Only compound, tape and wallboard layers are used in the calculation of a composite result.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
762353-2 R & R Environmental Ponderosa Terrace Bulk Samples June 26, 2026 EPA 600/R-93/116 - Point Count, Bulk (400) Priority June 29, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos…