591.23112.LWM_MDOTEngadineGarageGenerator_Addendum 1_Issued_20231115.pdf
PDF 1 MB Posted
- Solicitation number
- RFQ - 171 - 240000000059
- Issued by
- Mackinac County, Michigan
About this file
This document is an Addendum to a state and local contract opportunity issued by the Michigan Department of Technology, Management and Budget (DTMB) for the MDOT Engadine Garage Generator Replacement project. The Addendum updates the contract documents, including revised conduit runs, slope restoration, and removal and reinstallation of a sign. It also provides clarified notes and demolition extents for gas dispenser circuits, revised conduit runs from the diesel tank dispensers, and the requirement to provide a handhole detail. A pre-bid meeting attendance sheet is attached. Bids are due on Wednesday, December 6, 2023 at 2:00 p.m. EST.
The contract requires the replacement of the generator at the MDOT Engadine Garage, located in Mackinac County, Michigan. The project involves the installation of a 40 kW natural gas standby generator, an automatic transfer switch, and related electrical work. Contractors will be required to provide daily construction reports with a minimum of 5 photographs. No changes have been made to the bid date.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM NO. 1
DATE: November 15, 2023
PROJECT: MDOT Engadine Garage Generator Replacement
OWNER: MI DTMB
DTMB FILE NO.: 591/23112.LWM
BID DATE: Wednesday, December 6, 2023 @ 2:00 p.m. EST. **THIS ADDENDUM DOES
NOT CHANGE THE BID DATE**
The following shall be incorporated into the Contract Documents dated 2023 OCTOBER 27.
GENERAL
The pre-bid meeting attendance sheet is attached.
Contractor daily reports are to include a minimum of 5 photos daily that show relevant work of that day.
PROJECT MANUAL
DRAWINGS
C-110 SITE PLAN – Revised conduit runs to diesel tank dispensers through concrete pad. Added slope restoration for conduit going to handhole behind the diesel tank dispensers. Added remove, salvage and reinstall of sign in front of the diesel tanks.
EDP101 FIRST FLOOR ELECTRICAL DEMOLITION PLAN – Clarified notes and removal extents of conduit for gas dispensers.
EP101 FIRST FLOOR POWER PLAN - Revise conduit runs from diesel tank dispensers to be individually run to main building with seal offs. Provide handhole within existing homerun route to sign shop in order to re-feed exterior gas-dispenser lights to main building SP panel. Clarify notes on gas dispenser and gas dispenser lighting conduit runs above/below grade on homerun back to SP panel.
E-501 ELECTRICAL DETAILS – Provide handhole detail to specify requirements of handhole.
End of Addendum No. 1
DTMB-0441 (R 19.02)
MEETING ATTENDANCE RECORD
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
State Facilities Administration Design and Construction Division
PROJECT DESCRIPTION/LOCATION
DATE
TIME
FILE NUMBER
CONTRACT NUMBER
MEETING PLACE
PLEASE PRINT YOUR NAME
FIRM YOU REPRESENT
EMAIL ADDRESS
TELEPHONE NUMBER
Know what's below.
before you dig.Call
R feetGRAPHIC SCALE: FULL feetHALF
3020105
P :\7
1_
\7
0_
M D
O
TE
ng ad in eG ar ag eG en er at or \D ra w in gs
\S ite
\X re fs _B as e\
C
O N
.d w g
N ov
4,
- 4
:4 6p m D
R A
W
IN
G P
A
TH
OHM-ADVISORS.COM
ARCHITECTS ENGINEERS PLANNERS
CO
PY
RI
G
HT
O
HM
A
DV
IS
O
RS
. A
LL
D
RA
W
IN
G
S
AN
D W
RI
TT
EN
M
AT
ER
IA
LS
A
PP
EA
RI
NG
H
ER
EI
N
CO
NS
TI
TU
TE
T
HE
O
RI
G
IN
AL
A
ND
U
NP
UB
LI
SH
ED
W
O
RK
O F
O
HM
A
DV
IS
O
RS
A
ND
T
HE
S
AM
E
M
AY
N O
T
BE
D
UP
LI
CA
TE
D, D
IS
TR
IB
UT
ED
, O R
DI
SC
LO
SE
D W
IT
HO
UT
P
RI
O
R W
RI
TT
EN
C
O
NS
EN
T
O F
O
HM
A
DV
IS
O
RS
R
CL
IE
NT
P
RO
J N
O
RE
VI
SI
ON
DA
TE
DE
SC
RI
PT
IO
N
DI
SC
IP
LIN
E
LE
AD
PM
PR
OJ
EC
T
NU
MB
ER
IS
SU
ED
F
OR
D
TM
B /M
D O
T
E N
G A
D
IN
E G
A R
A G
E G
E N
E R
A
TO
R R
E P
LA
C
E M
E N
T
M
-1
E ng ad ine
, M I 4
SI
TE
P
LA
N
C-110
-2 3-
LM
M
MH
1/2
.A
BG
/10
/27
CO
NS
TR
UC
TI
ON
D
OC
UM
EN
TS
A
DD
EN
DU
M
/11
/14
TRENCH DETAIL FOR UTILITIES UNDER ROAD3
TRENCH DETAIL FOR PLASTIC OR METAL UTILITIES2
HMA PATCH CROSSECTION5
HMA APPLICATION TABLE6
SITE PLAN1
CONCRETE SIDEWALK CROSSECTION4
CONCRETE JOINT TIE7 SIGN TO BE REMOVED, SALVAGED, AND REPLACED8
AutoCAD SHX Text
FLAMMABLE MATERIAL
AutoCAD SHX Text
HAZARDOUS OR
AutoCAD SHX Text
TRENCH WIDTH
AutoCAD SHX Text 8"
AutoCAD SHX Text I.D.
AutoCAD SHX Text
6" MDOT 22A OR 21AA AGGREGATE
AutoCAD SHX Text
(COMPACTED TO 98%%%)
AutoCAD SHX Text
GRANULAR MATERIAL
AutoCAD SHX Text
MDOT CLASS II OR CLASS IIIA
AutoCAD SHX Text
ELECTRICAL CONDUIT
AutoCAD SHX Text
4" MINIMUM BEDDING
AutoCAD SHX Text
5EL
AutoCAD SHX Text
4EL
AutoCAD SHX Text
EXISTING HMA
AutoCAD SHX Text
EXISTING HMA
AutoCAD SHX Text
EXISTING HMA
AutoCAD SHX Text
EXISTING HMA
AutoCAD SHX Text
(COMPACTED TO 95%%%)
AutoCAD SHX Text
4EL
AutoCAD SHX Text
WARNING TAPE
AutoCAD SHX Text 4"
AutoCAD SHX Text
GRANULAR MATERIAL
AutoCAD SHX Text
MDOT CLASS II
AutoCAD SHX Text
(COMPACTED TO 95%%%)
AutoCAD SHX Text
TRENCH WIDTH
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text I.D.
AutoCAD SHX Text
SUITABLE MATERIAL
AutoCAD SHX Text
EXCAVATED FROM
AutoCAD SHX Text
TRENCH
AutoCAD SHX Text
(OTHER THAN WET
AutoCAD SHX Text
UNSTABLE CLAY)
AutoCAD SHX Text
GRANULAR MATERIAL
AutoCAD SHX Text
MDOT CLASS II OR CLASS IIIA
AutoCAD SHX Text
PLASTIC OR METAL UTILITIES
AutoCAD SHX Text
EXISTING GROUND
AutoCAD SHX Text
4" MINIMUM BEDDING
AutoCAD SHX Text
(COMPACTED TO 95%)
AutoCAD SHX Text
WARNING TAPE
AutoCAD SHX Text
1 1/2" MDOT 5EL TOP COURSE
AutoCAD SHX Text
6" MDOT 22A OR 21AA AGGREGATE (COMPACTED TO 98%)
AutoCAD SHX Text
8" TO 12" GRANULAR MATERIAL MDOT CLASS II (COMPACTED TO 95%)
AutoCAD SHX Text
2" MDOT 4EL LEVELING COURSE
AutoCAD SHX Text
2" MDOT 4EL BASE COURSE
AutoCAD SHX Text
PERMANENT HMA APPLICATION CHART
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
PAY ITEM
AutoCAD SHX Text
RATE (LB/SYD)
AutoCAD SHX Text
DEPTH (IN)
AutoCAD SHX Text
PERFORMANCE GRADE
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
HMA, 5EL
AutoCAD SHX Text
165 LB
AutoCAD SHX Text 1.5
AutoCAD SHX Text 58-34
AutoCAD SHX Text
TOP COURSE, AWI = 260 MINIMUM
AutoCAD SHX Text
HMA, 4EL
AutoCAD SHX Text
220 LB
AutoCAD SHX Text
AutoCAD SHX Text 58-34
AutoCAD SHX Text
BASE AND LEVELING COURSE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
0.05 - 0.15 GAL/SYD
AutoCAD SHX Text
AutoCAD SHX Text TYPE SS-1h
AutoCAD SHX Text
BOND COAT - TO BE APPLIED BETWEEN EACH LIFT OF NEW PERMANENT HMA
AutoCAD SHX Text
5EL
AutoCAD SHX Text
4EL
AutoCAD SHX Text
AutoCAD SHX Text
SUITABLE SUBGRADE MATERIAL COMPACTED TO 95%
AutoCAD SHX Text 6" CONC WITH 6"X6" REINFORCING MESH W1.4xW1.4 WWF
AutoCAD SHX Text
6" MDOT 22A OR 21AA (COMPACTED TO 95%)
http://www.ohm-advisors.com AutoCAD SHX Text
UNDERGROUND ELECTRIC, MINIMUM BURY DEPTH 24" UNDER ROAD WAY, SEE SHEET EP-101
AutoCAD SHX Text
2" GAS
AutoCAD SHX Text
GENERATOR PAD +/- 4" ON EACH SIDE TO MATCH GENERATOR INSTALLED. SEE SHEET E-501
AutoCAD SHX Text
SLOPE RESTORATION (TYP)
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NTS
AutoCAD SHX Text 1" = 10'
AutoCAD SHX Text
UNDERGROUND ELECTRIC, SEE SHEET EP-101
AutoCAD SHX Text
UNDERGROUND ELECTRIC
AutoCAD SHX Text
REMOVE AND REPLACE CONC PAD, 6"
AutoCAD SHX Text
REMOVE AND REPLACE CURB, TYPE E
AutoCAD SHX Text
NTS
AutoCAD SHX Text
PROTECT STORAGE BUILDING
AutoCAD SHX Text
FUEL PUMPS
AutoCAD SHX Text
REMOVE AND REPLACE HMA
AutoCAD SHX Text
MINIMUM SEPARATION BETWEEN UTILITES
AutoCAD SHX Text
MINIMUM BURY DEPTH 18"
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
(4) BARRICADE TYPE III
AutoCAD SHX Text
(4) BARRICADE TYPE III
AutoCAD SHX Text
HAND DIG BETWEEN SHED AND CONCRETE PAD TO INSTALL CONDUIT
AutoCAD SHX Text
HH WITH SEAL-OFF, SEE SHEET EP-101
AutoCAD SHX Text
CONDUIT WITH SEAL-OFFS, SEE SHEET EP-101
AutoCAD SHX Text
REMOVE, SALVAGE AND REINSTALL SIGN
AutoCAD SHX Text
REMOVE AND REPLACE CONCRETE PAD WITH JOINT TIES TO INSTALL CONDUIT AS NECESSARY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text DRILL HOLE INTO EXISTING CONCRETE PAVEMENT AND GROUT-IN-PLACE #5 X 1' LONG EPOXY COATED DEFORMED BARS. INSTALL 6" FROM END OF CONCRETE REPAIR EVERY 1'3" ALTERNATING EXISTING CONCRETE SIDES.
AutoCAD SHX Text
12 PAVEMENT THICKNESS
AutoCAD SHX Text
EXISTING CONCRETE
AutoCAD SHX Text
CONCRETE REPAIR
AutoCAD SHX Text
NTS
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
AutoCAD SHX Text
SIGN TO BE REMOVED, SALVAGED AND REINSTALLED.
T
S
M
M
PO LP-1
MECH ROOM PANEL
MAIN SERVICE PANEL
15 KW GENERATOR
60A MANUAL TRANSFER SWITCH. SEE DETAIL 2 ON ED501.
PANEL SP
GAS METER
CT CABINET AND METER
GENERATOR EXHAUST
GENERATOR GAS TANK
EQUIPMENT ROOM
MECHANICS OFFICE
GENERATOR ROOM
WOMENS LOCKER
MENS LOCKER
TMW OFFICE
CLERK/FILE OFFICE
SUPERVISORS OFFICE
EXISTING FOYER
EXISTING UTILITY ROOM
LUNCH/MEETING/TRAINING ROOM
EXIST J.C.
EXIST UNISEX TOILET
1. DRAWINGS SHOW MAJOR DEMOLITION ONLY; THE CONTRACTOR SHALL PROVIDE ALL DEMOLITION
FOR THE COMPLETION OF THE WORK WHETHER EXPLICITLY SHOWN OR NOT.
2. THE OWNER RESERVES THE RIGHT TO KEEP ANY REMOVED EQUIPMENT OR MATERIALS. ALL
DEMOLITION DEBRIS TO BE REMOVED FROM THE SITE AND DISPOSED OF IN AN APPROVED LANDFILL.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY TEMPORARY EXTERIOR OPENINGS MADE FROM
DEMOLITION WORK TO ENSURE THEY ARE WEATHER TIGHT AT THE END OF EACH DAY.
4. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL PATCHING WHERE CONDUITS AND
JUNCTION BOXES ARE REMOVED UNLESS OTHERWISE NOTED.
5. ANY JUNCTION BOXES REMAINING IN PLACE THAT HAVE HAD DEVICES REMOVED ARE TO RECEIVE
BLANK COVER PLATES MATCHING PROJECT REQUIREMENTS.
6. CONDUITS AND CONDUCTORS ABANDONED AS PART OF THE WORK SHALL BE DEMOLISHED WHERE NOT BURIED IN WALLS OR UNDERGROUND. CAP OR PLUG ANY ABANDONED CONDUITS THAT REMAIN.
7. WHERE DEVICES ARE REMOVED FROM THE MIDDLE OF A CIRCUIT, THE CONTRACTOR SHALL BE RESPONSIBLE TO RE-ROUTE THE CIRCUIT TO MAINTAIN CIRCUIT INTEGRITY TO REMAINING DEVICES.
8. CONTRACTOR TO NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND IN EXISTING CONDITIONS.
9. CONTRACTOR TO COORDINATE WITH THE OWNER OR ENGINEER A MINIMUM OF 24 HOURS IN
ADVANCE OF SHUTTING OFF OR DISCONNECTING ANY UTILITIES. CONTRACTOR TO ENSURE ALL
EXISTING SYSTEMS TO REMAIN ARE MAINTAINED THROUGHOUT THE DURATION OF THE PROJECT
UNLESS OTHERWISE DIRECTED BY THE ENGINEER/OWNER.
10. CONTRACTOR TO TAKE ALL PRECAUTIONS NECESSARY TO PROTECT ITEMS NOT INTENDED TO BE
DEMOLISHED AND TO RESTORE TO EXISTING CONDITIONS ANY ITEMS DAMAGED THAT WERE NOT
INTENDED TO BE DEMOLISHED.
GENERAL NOTES - ELECTRICAL DEMOLITION
GAS DISPENSER
GAS DISPENSER
RELOCATE CIRCUITS 1, 5, AND 7 WITHIN
SIGN SHOP PANEL TO NEW SP PANEL
LOCATED WITHIN MAINTENANCE
GARAGE IN MAIN BUILDING
SIGN SHOP PANEL
MAIN BUILDING
SIGN SHOP
SALT STORAGE
COLD
STORAGE
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D
B U
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
R E
V
IS
IO
N
P R
O
JE
C T
N U
M B
E R
P M
D
IS
C
IP
LI
N
E L
E A
D
D E
S C
R
IP
T
IO
N D
A T
E
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
/1
4/
:0 5:
P
M A ut od es k
D oc s:
//7
6-
-0
M D
O T
E ng ad in e G ar ag e/
_F P
M E
_M D
O T
_E ng ad in eG ar
_2
3_ C
E N
.rv t
EDP101
F
IR
S T
F
LO
O R
E
LE
C T
R
IC
A L
D E
M O
LI
T
IO
N
P
LA
N
M -1
E ng ad in e, M I 4
M D
O T
E N
G A
D
IN
E G
A R
A G
E G
E N
E R
A T
O R
R E
P
LA
C E
M E
N T
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 3-
LM
M
/1 0/
1/
2.
LW
M F
C
O N
D T
M B
F ile
N o.
M D
O T
P ro je ct
N o.
S W
1/8" = 1'-0"2
MAIN BUILDING DEMOLITION PLAN
SHEET KEYNOTES - ELEC. DEMOLITION
1 DISCONNECT AND REMOVE PANEL. BRANCH CIRCUIT CONDUIT AND CONDUCTORS TO REMAIN. REMOVE
FEEDER CONDUIT AND CONDUCTOR BACK TO SOURCE.
2 REMOVE MANUAL TRANSFER SWITCH. REMOVE CONDUIT AND CONDUCTORS BACK TO SOURCE.
3 REMOVE RECEPTACLE. REMOVE CONDUCTORS AND SALVAGE CONDUIT FOR RE-USE. SALVAGE IT
EQUIPMENT GROUND FOR RE-USE.
4 DISCONNECT CIRCUITS 1, 5, 7. REMOVE CONDUCTORS. REMOVE CONDUIT ABOVE GRADE AND WITHIN BUILDING. ABANDON CONDUIT BELOW GRADE. REMOVE SLEEVE AND SEAL EXTERIOR WALL PENETRATION
WITH MORTAR.
5 SALVAGE EMERGENCY FUEL SHUT OFF AND EXISTING EMERGENCY FUEL SHUTOFF SIGN. REMOVE
CONDUCTORS. REMOVE CONDUIT ABOVE GRADE AND ABANDON CONDUIT BELOW GRADE. REMOVE
SLEEVE AND SEAL EXTERIOR WALL PENETRATION WITH MORTAR.
6 REMOVE GENERATOR AND DISPOSE OF LEGALLY FOLLOWING REGULATORY REQUIREMENTS. REMOVE CONDUIT AND CONDUCTORS BACK TO MANUAL TRANSFER SWITCH. REMOVE GENERATOR STAND. SEAL
ANY WALL/FLOOR PENETATIONS.
7 REMOVE 60A BREAKER FOR SHOP SP GENERATOR FROM MAIN SERVICE PANEL.
8 REMOVE CIRCUITS 3, 4, 5, 6, 7, 33, 35, 37 FROM LP-1. CIRCUITS TO BE RE-LOCATED TO NEW SP PANEL.
9 REMOVE GENERATOR EXHAUST AND GAS TANK. REMOVE ANY STRUCTURALLY SUPPORTING DEVICES.
REMOVE EXHAUST PIPE WITHIN EXTERIOR WALL AND SEAL EXTERIOR WALL PENETRATION WITH MORTAR.
10 REMOVE EXISTING SEAL OFF AND ANY CONDUIT AND CONDUCTORS THAT REMAIN ABOVE GRADE FROM
PREVIOUS GAS DISPENSER ELECTRICAL FEED.
11 REMOVE CONDUIT FROM GAS DISPENSER BELOW GRADE TO EXTENTS OF CONCRETE REMOVAL.
ABANDON CONDUIT PAST REMOVAL EXTENTS.
1/8" = 1'-0"1
SIGN SHOP BUILDING DEMOLITION PLAN
KEYPLAN
A
D D
E N
D U
M
/1
1/
M
T
S
M
PO
MAIN SERVICE PANEL
LP-1
MECH ROOM PANEL
SP
GAS DISPENSER
GAS DISPENSER
125A, NEMA 12, NON-SERVICE RATED ATS.
SEE DETAIL 1 ON E-501 FOR ELEVATION.
40KW NATURAL GAS GENERATOR.
GENERATOR PAD. SEE DETAIL 4
ON E-501.
CONDUIT TO TERMINATE ABOVE
GROUND WITH CONDUIT SEAL OFFS.
CAN TRANSITION TO 1" EMT BEYOND
SEAL OFFS INTO BUILDING VIA J-BOX
RE-FEED GAS DISPENSER FROM NEW SP PANEL IN
MAINTENANCE GARAGE. 8' WIDE OPEN CUT PAVEMENT FOR
CONDUIT AND CONDUCTORS. REFER TO C-110 FOR
DEMOLITION EXTENTS AND RESTORATION DETAILS.
RE-FEED EXISTING CIRCUITS WITHIN NEW SP PANEL
REINSTALL SALVAGED EMERGENCY FUEL
SHUTOFF PUSH BUTTON AND SIGN
BUILDING MOUNTED
GENERATOR E-STOP
2" CONDUIT W/ 4-#1AWG + #6EG TO PANEL SP
1" CONDUIT W/ 8-#14AWG + RJ45 STP TO REMOTE ANNUNCIATOR
1" CONDUIT W/ 6-#12AWG + #12EG FOR
GAS DISPENSER PUMPS AND LIGHTING RECIRCUITED TO SP PANEL.
1-3/4" CONDUIT W/ 4-#12AWG + #12EG FOR BATTERY CHARGER/BATTERY
HEATER & BLOCK HEATER.
GAS METER
CT CABINET AND METER
2" CONDUIT W/ 4-#1AWG + #6EG.
1" CONDUIT W/ 8-#14AWG FOR CONTROLS.
1-3/4" CONDUIT W/ 4-#12AWG + #12EG FOR
BATTERY CHARGER & BLOCK HEATER.
8' - 0"
REMOTE ANNUNCIATOR
SEE CIVIL SHEET C-110 FOR CONCRETE REMOVAL
NEEDED FOR GAS PIPE & CONDUIT INSTALLATION
CONDUIT TO TERMINATE ABOVE
GROUND WITH CONDUIT SEAL OFFS.
3 - 1" CONDUIT W/ 2 - #12AWG + #12EG.
CONDUIT TO BE PVC COATED RMC
BETWEEN SEAL OFFS.
EQUIPMENT ROOM
MECHANICS OFFICE
GENERATOR ROOM
WOMENS LOCKER
MENS LOCKER
TMW OFFICE
CLERK/FILE OFFICE
SUPERVISORS OFFICE
EXISTING FOYER
EXISTING UTILITY ROOM
LUNCH/MEETING/TRAINING ROOM
EXIST J.C.
EXIST UNISEX TOILET
DISCONNECT EXISTING CIRCUIT TO SIGN SHOP
AND PLACE HANDHOLE WITHIN HOMERUN IN
ORDER TO RE-FEED LIGHTS TO MAIN BUILDING.
PROVIDE SEAL-OFF WITHIN HANDHOLE.
HH
RUN CONDUIT WITHIN GREEN SPACE NEXT TO
STORAGE BUILDING AND DIESEL TANK CONCRETE
EXISTING LIGHTING
MAIN BUILDING
SIGN SHOP
SALT STORAGE
COLD
STORAGE
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
R E
V
IS
IO
N
P R
O
JE
C T
N U
M B
E R
P M
D
IS
C
IP
LI
N
E L
E A
D
D E
S C
R
IP
T
IO
N D
A T
E
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
/1
4/
:0 5:
P
M A ut od es k
D oc s:
//7
6-
-0
M D
O T
E ng ad in e G ar ag e/
_F P
M E
_M D
O T
_E ng ad in eG ar
_2
3_ C
E N
.rv t
EP101
F
IR
S T
F
LO
O R
P O
W E
R P
LA
N
M -1
E ng ad in e, M I 4
M D
O T
E N
G A
D
IN
E G
A R
A G
E G
E N
E R
A T
O R
R E
P
LA
C E
M E
N T
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 3-
LM
M
/1 0/
1/
2.
LW
M F
C
O N
D T
M B
F ile
N o.
M D
O T
P ro je ct
N o.
S W1/8" = 1'-0"1
MAIN BUILDING POWER PLAN
KEYPLAN
1 1 A
D D
E N
D U
M
/1
1/
PANEL
MECH
RM
MAIN
BREAKER800A
SIGN SHOP200A WELDER
SHOP 1Ø
(PANEL LP-1)
PANEL SP
COLD
STORAGE
100A
PANEL
MECH RM
SHOP 3Ø
(PANEL PO)
125A
SALT
STORAGE
OFFICE
HVAC
60A SPACE
100A
100A
100A
100A
100A
120/240 VOLT
3 PHASE 4 WIRE DELTA
EATON: PRL-4B
J#: HGR81505
IT FRONT END
RE-INSTALL SALVAGED
RECEPTACLE & CONDUIT.
REPLACE BREAKER W/ 125A 3Ø BREAKER
125A NON-SERVICE RATED ATS W/ SOLID NEUTRAL
RE-FEED IT EQUIPMENT GROUND FOR IT FRONT END.
COLD-STORAGE PANEL
MAIN SERVICE PANEL 800A
800A SERVICE RATED SWITCHBOARD,
800A MCB, 240V/120V DELTA
60A SPARE
PANEL PO (LABELED
AS SHOP 3Ø AT DP)
100A 100A 100A
M
GEN.
NATURAL GAS STANDBY
GENERATOR
40KW, 240V/120 DELTA
240/120V, 3Ø, 125A.
NEMA 12, 25KA, NON-
SERVICE RATED ATS
WITH SOLID NEUTRAL
POLE MOUNT TRANSFORMERS
240V/120 DELTA SECONDARY
CT CABINET & METER
100A 100A 200A 100A 125A
OFFICE HVAC
SALT-STORAGE PANEL
SIGN
SHOP
LP-1 (LABELED
AS 1Ø AT DP)
MECH RM
PANEL
WELDER
PANEL SP
120/240V, 3Ø, 125A
42 CKT
BUILDING
DISCONNECT
LOCATED IN SEPARATE
BUILDINGS
LOCATED IN SEPARATE
BUILDING
OVERHEAD UTILITY CONDUCTORS OVERHEAD UTILITY CONDUCTORS
125A
2" CONDUIT W/ 4-#1AWG + #6EG
NATURAL GASCUMMINS
FUELMANUFACTURER MODEL # VOLTAGE
GENERATOR SCHEDULE
C40N6
RATING (kW)
PHASE
240V/120D 3Φ
COMMENTS
PROVIDE SOUND ATTENUATION
ENCLOSURE
#6 AWG CU GND
GRADE
5/8" X 8' GROUND ROD
BOND GROUND TO
FOUNDATION REBAR
#2 AWG BOND TO REBAR AND FABRIC1" CHAMFER EDGE AROUND
ENTIRE PERIMETER
#4 REBAR AROUND ENTIRE
THICKENED PERIMETER 6" CONC SLAB ON GRADE W/ 6"X6"
W2.9XW2.9 WELDED WIRE FABRIC IN
SHEETS SUPPORTED OFF GRADE W/
CONCRETE SUPPORTS
PROVIDE 12" OF CLEAN COMPACTED
SAND UNDER ENTIRE SLAB.
CONC SLAB ON GRADE W/ 6"X6" WELDED WIRE
FABRIC SUPPORTED OFF GRADE W/ SUPPORTS
10"
1'-4"
6"
18'
GENERATOR DIMENSION + 4"
G E
N E
R A
T O
R D
IM
E
N S
IO
N
4"
94"
.5
SP PANEL
1" CONDUIT FOR POWER
TO BATTERY CHARGER,
BATTERY WARMER AND
ENGINE BLOCK WARMER.
1" CONDUIT FOR
GENERATOR START AND
ATS STATUS
ATS
2" CONDUIT FOR
POWER CONDUCTORS
GENERATOR
CONTROL PANEL
CONCRETE PAD
FINISHED GRADE
WEATHER PROOF ENCLOSURE
MAIN SERVICE
ENTRANCE PANEL
REMOTE
ANNUNCIATOR
PANEL
1" CONDUIT FOR
COMMUNICATION AND POWER
E-STOP
3/4" CONDUIT
WITH 2-#14AWG
BUILDING MOUNTED E-STOP
2" CONDUIT FOR POWER
CONDUCTORS
BOX SHALL BE CONCRETE OR COMPOSITE. METAL COVER IS ACCEPTABLE.
COVERS SHALL BE SECURED WITH 3/8" BOLTS, NUTS AND WASHERS. WHICH SHALL BE
BRASS, STAINLESS STEEL OR OTHER CORROSION RESISTANT MATERIAL. STAINLESS STEEL
SHALL HAVE A CHROMIUM CONTENT OF NOT LESS THAN 18% AND A NICKEL CONTENT OF
NOT LESS THAN 8%, NUTS SHALL BE RECESSED BELOW TOP SURFACE OF COVER.
COVER LETTERING SHALL BE 1/2" MINIMUM LETTERS CAST IN STANDARD MARKINGS:
(ELECTRICAL).
CONDUIT ENTERING THE BOX SHALL HAVE 90 DEGREE LONG RADIUS BEND (INSIDE THE
BOX). THE CONDUITS OPENING, IINSIDE THE BOX, SHALL BE AT LEAST 4" BELOW THE LID,
OPENING SHALL HAVE SMOOTH EDGE. IF THE CONDUIT IS P.V.C. A SLIP COUPLING MUST BE
USED. IF THE CONDUIT IS RIGID PIPE, A PROTECTIVE BUSHING SHALL BE USED.
CONDUCTORS SHALL HAVE A MINIMUM OF 24" SLACK FROM CONDUIT BELL END.
BACKFILL WITH EXCAVATED MATERIAL AND THOROUGHLY COMPACT.
WHERE PULLBOXES ARE INSTALLED IN CONCRETE AREAS, 1/2" PREMOLDED EXPANSION
JOINT SHALL BE INSTALLED AROUND THE BOX.
BOXES IN NON-VEHICLE TRAFFIC AREAS TO BE TIER 8 AND IN VEHICLE TRAFFIC AREAS TO
BE TIER 22 UNLESS OTHERWISE NOTED.
NOTE:
1.)
2.)
3.)
4.)
5.)
6.)
7.)
5/8" x4" LIFTING SLOTS
16" x 8" CONCRETE BRICK
COVER TO BE FLUSH WITH FINISH GRADE
ALL CONDUIT END BELLS SHALL BE
INSTALLED BEFORE PULLING WIRE
1" PVC CONDUIT FOR DRAINAGE
6A BACKFILL WITH MINIMUM
OF 5" DEPTH
23 3/4"
21 1/4"
15 9/16"
/2
/8
15 3/8"
ELECTRICAL
M
IN
8.)
PROVIDE CONDUIT SEAL-OFF ON
HOMERUN TO MAIN BUILDING
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
R E
V
IS
IO
N
P R
O
JE
C T
N U
M B
E R
P M
D
IS
C
IP
LI
N
E L
E A
D
D E
S C
R
IP
T
IO
N D
A T
E
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
/1
4/
:0 5:
P
M A ut od es k
D oc s:
//7
6-
-0
M D
O T
E ng ad in e G ar ag e/
_F P
M E
_M D
O T
_E ng ad in eG ar
_2
3_ C
E N
.rv t
E-501
E
LE
C T
R
IC
A L
D E
T A
IL
S
M -1
E ng ad in e, M I 4
M D
O T
E N
G A
D
IN
E G
A R
A G
E G
E N
E R
A T
O R
R E
P
LA
C E
M E
N T
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 3-
LM
M
/1 0/
1/
2.
LW
M F
C
O N
D T
M B
F ile
N o.
M D
O T
P ro je ct
N o.
S W
N.T.S1
MAIN SERVICE PANEL ELEVATION
N.T.S2
ONE-LINE DIAGRAM
N.T.S3
GENERATOR SCHEDULE
N.T.S4
GENERATOR PAD DETAIL
N.T.S6
GENERATOR WIRING DIAGRAM
N.T.S5
HANDHOLE DETAIL
1 1 A
D D
E N
D U
M
/1
1/
| ADDENDUM NO. 1 |
| GENERAL |
| PROJECT MANUAL |
| DRAWINGS |
| PROJECT DESCRIPTIONLOCATION: MDOT Engadine Garage Generator Replacement |
| DATE: 11-07-2023 |
| TIME: 10:00 a.m. |
| FILE NUMBER: 591/23112.LWM |
| CONTRACT NUMBER: |
| MEETING PLACE: 7045 M-117, Engadine, Michigan 49827 |
| PLEASE PRINT YOUR NAMERow1: Louis Meyette |
| FIRM YOU REPRESENTRow1: OHM Advisors |
| EMAIL ADDRESSRow1: louis.meyette@ohm-advisors.com |
| TELEPHONE NUMBERRow1: 906-696-7120 |
| PLEASE PRINT YOUR NAMERow2: Curt Carlson |
| FIRM YOU REPRESENTRow2: MDOT Facilities |
| EMAIL ADDRESSRow2: carlsonc7@michigan.gov |
| TELEPHONE NUMBERRow2: 517-420-1870 |
| PLEASE PRINT YOUR NAMERow3: James Daly |
| FIRM YOU REPRESENTRow3: Rolls Mechanical |
| EMAIL ADDRESSRow3: jimmyd@ljrolls.com |
| TELEPHONE NUMBERRow3: 810-206-8312 |
| PLEASE PRINT YOUR NAMERow4: Garrett Peterman |
| FIRM YOU REPRESENTRow4: J Ranck Electric |
| EMAIL ADDRESSRow4: gpeterman@jranck.com |
| TELEPHONE NUMBERRow4: 989-205-2154 |
| PLEASE PRINT YOUR NAMERow5: Dan Hall |
| FIRM YOU REPRESENTRow5: DTMB |
| EMAIL ADDRESSRow5: halld22@michigan.gov |
| TELEPHONE NUMBERRow5: 517-256-4938 |
| PLEASE PRINT YOUR NAMERow6: Jason Richter |
| FIRM YOU REPRESENTRow6: STE Group LLC. |
| EMAIL ADDRESSRow6: frankrichter@sbcglobal.net |
| TELEPHONE NUMBERRow6: 586-709-5048 |
| PLEASE PRINT YOUR NAMERow7: Kris Miller |
| FIRM YOU REPRESENTRow7: Great Lakes Environmental |
| EMAIL ADDRESSRow7: theresa@glenvllc.com |
| TELEPHONE NUMBERRow7: 906-322-8255 |
| PLEASE PRINT YOUR NAMERow8: Steve Olsen |
| FIRM YOU REPRESENTRow8: Olsen & Olsen BLD Contracting |
| EMAIL ADDRESSRow8: olsenbld75@gmail.com |
| TELEPHONE NUMBERRow8: 906-341-3550 |
| PLEASE PRINT YOUR NAMERow9: Nick LaChapelle |
| FIRM YOU REPRESENTRow9: MDOT Garage Supervisor |
| EMAIL ADDRESSRow9: lachapellen@michigan.gov |
| TELEPHONE NUMBERRow9: 906-630-5600 |
| PLEASE PRINT YOUR NAMERow10: |
| FIRM YOU REPRESENTRow10: |
| EMAIL ADDRESSRow10: |
| TELEPHONE NUMBERRow10: |
| PLEASE PRINT YOUR NAMERow11: |
| FIRM YOU REPRESENTRow11: |
| EMAIL ADDRESSRow11: |
| TELEPHONE NUMBERRow11: |
| PLEASE PRINT YOUR NAMERow12: |
| FIRM YOU REPRESENTRow12: |
| EMAIL ADDRESSRow12: |
| TELEPHONE NUMBERRow12: |
| PLEASE PRINT YOUR NAMERow13: |
| FIRM YOU REPRESENTRow13: |
| EMAIL ADDRESSRow13: |
| TELEPHONE NUMBERRow13: |
| PLEASE PRINT YOUR NAMERow14: |
| FIRM YOU REPRESENTRow14: |
| EMAIL ADDRESSRow14: |
| TELEPHONE NUMBERRow14: |
| PLEASE PRINT YOUR NAMERow15: |
| FIRM YOU REPRESENTRow15: |
| EMAIL ADDRESSRow15: |
| TELEPHONE NUMBERRow15: |
| PLEASE PRINT YOUR NAMERow16: |
| FIRM YOU REPRESENTRow16: |
| EMAIL ADDRESSRow16: |
| TELEPHONE NUMBERRow16: |
| PLEASE PRINT YOUR NAMERow17: |
| FIRM YOU REPRESENTRow17: |
| EMAIL ADDRESSRow17: |
| TELEPHONE NUMBERRow17: |
| PLEASE PRINT YOUR NAMERow18: |
| FIRM YOU REPRESENTRow18: |
| EMAIL ADDRESSRow18: |
| TELEPHONE NUMBERRow18: |
| PLEASE PRINT YOUR NAMERow19: |
| FIRM YOU REPRESENTRow19: |
| EMAIL ADDRESSRow19: |
| TELEPHONE NUMBERRow19: |
File details come from the government source that posted it. Updated .