This document is a Mechanical Design Criteria section from Construction Documents for a Department of Veterans Affairs project at Wichita VA Medical Center in Wichita, Kansas (VA Project No. 589A7-23-305), dated May 17, 2024. The project involves preparing a site for Choice Dining Equipment installation.
The mechanical design criteria establish applicable standards and codes governing the project, including ASHRAE standards for ventilation, indoor air quality, mechanical refrigeration, and energy efficiency; the International Mechanical and Plumbing Codes; Americans with Disabilities Act requirements; NFPA standards for electrical, fire alarm, sprinkler systems, air-conditioning/ventilation systems, and health care facilities; VA-specific design manuals for physical security, resiliency, and fire protection; and publications from ANSI, ASME, and ASTM. Design conditions specify an elevation of 1,321 feet above mean sea level at a latitude of 37.65°N and longitude of 92.43°W. Winter heating design calls for outside air at 7.9°F with 31.4 MPH winds and inside conditions of 70°F at 35% relative humidity, while summer cooling design requires outside air at 100.5°F dry bulb and 73.8°F mean coincident wet bulb with inside conditions of 75°F at 50% relative humidity. Break rooms and office spaces must maintain 75°F in summer and 70°F in winter with 30-60% humidity, require 4 air changes per hour, and demand 2 air changes per hour of outdoor air.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF VETERANS AFFAIRS VA PROJECT NO. 589A7-23-305
WICHITA VA MEDICAL CENTER PREPARE SITE FOR CHOICE DINING EQUIPMENT
WICHITA, KS CONSTRUCTION DOCUMENTS: 05/17/2024
ALESIA ARCHITECTURE P.C. 5 ELKHORN, NE
MECHANICAL
1. APPLICABLE DESIGN CRITERIA
A. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)
Guide and Data Books.
B. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)
Standard 62; Ventilation for Acceptable Indoor Air Quality.
C. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)
Standard 15; Safety Code for Mechanical Refrigeration.
D. American Society of Heating Refrigerating, and Air-Conditioning Engineers (ASHRAE)
Standard 90.1, Energy Standard for Buildings Except Low Rise Residential Buildings.
E. Americans with Disabilities Act (ADA).
F. Energy Policy Act of 2005 (EPact 2005).
G. Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA)
HVAC Systems Duct Design Guidebooks.
H. International Mechanical Code (IMC).
I. International Plumbing Code (IPC).
J. VA Physical Security and Resiliency Design Manual, July 2022
K. VA Fire Protection Design Manual
L. NFPA 10 – Standard for Portable Fire Extinguishers, 2022 Edition
M. NFPA 13 – Standard for the Installation of Sprinkler Systems.
N. NFPA 70 – National Electrical Code, 2023 Edition
O. NFPA 72 – National Fire Alarm and Signaling Code, 2022 Edition
P. NFPA 90A – Standard for the Installation of Air-Conditioning and Ventilating Systems.
Q. NFPA 99 – Health Care Facilities Code, 2012 Edition.
R. NFPA 101 – Life Safety Code, 2021 Edition.
S. American National Standards Institute (ANSI).
T. American Society of Mechanical Engineers (ASME) Publications.
DEPARTMENT OF VETERANS AFFAIRS VA PROJECT NO. 589A7-23-305
WICHITA VA MEDICAL CENTER PREPARE SITE FOR CHOICE DINING EQUIPMENT
WICHITA, KS CONSTRUCTION DOCUMENTS: 05/17/2024
ALESIA ARCHITECTURE P.C. 6 ELKHORN, NE
U. American Society of Testing & Materials (ASTM) Publications.
V. Department of Veteran Affairs, Office of Construction & Facilities Management Design
Manuals.
W. Department of Veteran Affairs, Office of Construction & Facilities Management Design
Guides.
2. DESIGN CONDITIONS
A. Altitude and location (approximate):
• Elevation: 1321 feet AMSL
• Latitude: 37.65 deg N
• Longitude: 92.43 deg W
B. Design Temperatures:
• Winter (Heating) 99.6%:
a. Outside Air: 7.9 deg F
b. Wind: 31.4 MPH
c. Inside: 70 deg F
d. (35% RH in the Interior Spaces)
• Winter (Infiltration):
a. Outside Air: 7.9 deg F
• Summer (Cooling) 0.4%:
a. Outside Air: 100.5 deg F DB, 73.8 deg F MCWB (Per ASHRAE
Fundamentals, 2021 Edition, 0.4% occurrence)
b. Inside: 75 deg F, 50% RH
• Summer (Infiltration):
a. Outside Air: 100.5 deg F DB, 73.8 deg F MCWB
• Break Room / Office Room (Conference, Break, Office):
a. Room Temperature: 75 deg F Summer, 70 deg F Winter
b. Room Humidity: 30% to 60%
c. Pressure Relationship: None
d. ACH Rate: 4 ACH
e. OA Requirement: 2 ACH