561A4-21-101 Replace RF Unit Site Prep - Rm 48 Construction Drawings.pdf

PDF 40 MB Posted

Attached to
Y1DA--Project Number: 561A4-21-101 Replace RF Unit Site Prep - Rm. 48 Lyons VAMC Federal contract opportunity
Solicitation number
36C24224B0048
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This document contains construction drawings for Project Number 561A4-21-101 to Replace the RF Unit and perform Site Preparation for Room 48 at the Lyons VA Medical Center. The project is solicited by the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 2. The solicitation number is 36C24224B0048. The drawings provide details and specifications for the required construction work, including demolition, electrical, mechanical, and structural plans. No additional information about response dates, pricing, or set-asides is provided in the drawings.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--Project Number: 561A4-21-101 Replace RF Unit Site Prep - Rm. 48 Lyons VAMC, newest first.
File Type Posted
Question and Answers IFB 36C24224B0048 9-30-2024.docx DOCX document
36C24224B0048 0001.docx DOCX document
Sign in Pre-Bid Site visit S05.pdf PDF
FAR 52.225-2 BUY AMERICAN CERTIFICATE.docx DOCX document
Wages.pdf PDF
852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING-CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (DEVIATION).pdf PDF
561A4-21-101 Replace RF Unit Site Prep - Rm 48 Specifications.pdf PDF
36C24224B0048_1.docx DOCX document
Construction SOW 561A4-21-101 Replace RF Unit Site Prep - Rm 48 02.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

S

S

S

S S

S

S

S

S

S

Utility Box

Phragmites Phragmites

S

S S

S

S

D

DD

D

D

S

S S

S

S

S

S

S

S

S

S

S

HOLDING TANKMANHOLE

S

S

S

S

S

VAULT

VAULT

S

S

S

SAN

SAN

VAULT

VAULT

S

BLDG

# 70

BLDG

# 47

BUILDING # 57

BUILDING # 53

BUILDING # 54

BUILDING # 55

BLDG. 16

BLDG.

# 69

BLDG.

# 50

BLDG.

# 18

BLDG.

# 19

BUILDING # 25BUILDING # 26

BLDG

# 52

BLDG # 11

BUILDING # 135

BUILDING # 10

BUILDING # 12

FIRE HOUSE

BUILDING # 1

BUILDING

# 13

BUILDING

# 14

BUILDING

# 136

BUILDING # 15

BUILDING

# 13

BUILDING # 143

BUILDING # 5

BUILDING # 6

BUILDING # 2 BUILDING # 4

BUILDING # 7

BUILDING # 8

BUILDING # 9

S

S

S

295.5

S

S

PHRAGMITES

PHRAGMITES

TB

G G

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

POOL

M

M

M

TB

TB

TB

M

M M

FP

FP

FP

FP

FP

FP

TB

TB

TB

TB

PILE

PILE

G G

GG

G G

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

PHRAGMITES

S

S

S

S

BUILDING # 3

BUILDING # 53

BLDG. 34

BUILDING # 141

WASTEWATER PLANT

X

X X

X X

X X

X X

E

X

X

X

XX

X

X

X X

X X X X X X

X X

X X

X X

X

X X

X

X X

X

KNOLLCROFT RD.

EDF WPB

ES-001

ED-101

ES-101

HVAC: SYMBOLS, ABBREVIATIONS & NOTES MH-001

ELECTRICAL:

HVAC:

ARCHITECTURAL:

COVER SHEET WITH INDEX OF DRAWINGSGI-0011

ELECTRICAL: SYMBOLS, ABBREVIATIONS & NOTES

GI-001

COVER SHEET WITH INDEX

OF DRAWINGS

SCALE: 1"=40'

ENGINEERING LLPwww.fellp.com

BUILDING 1

HVAC: GROUND FLOOR & REFLECTIVE CEILING DEMOLITION PLANSMD-101

ELECTRICAL: GROUND FLOOR & REFLECTIVE CEILING DEMOLITION PLANS

ELECTRICAL: GROUND FLOOR & REFLECTIVE CEILING NEW CONSTRUCTION PLANS

GENERAL:

MH-101

Fi le

N am e:

C

:\U se rs \s a\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

\(1

) G I-0

.d w g

(L ay ou t:

G

1-

D at e:

T ue , J un

5,

- 1 :3

PM

N am e:

s a)

ENGINEERING LLP

www.fellp.com

181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735

22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986

FE PROJECT #: 22-171

Replace RF Unit Site Prep- Rm. 48

561A4-21-101

06-14-24

FOR CONSTRUCTION

151 KNOLLCROFT RD.

LYONS, NJ 07939

HVAC: GROUND FLOOR & REFLECTIVE CEILING NEW CONSTRUCTION PLANS

AS-001

AD-101

AS-101

ARCHITECTURAL: SYMBOLS, ABBREVIATIONS & NOTES

ARCHITECTURAL: GROUND FLOOR & REFLECTIVE CEILING DEMOLITION PLANS

ARCHITECTURAL: NEW GROUND FLOOR, RCP & EQUIPMENT CONSTRUCTION PLANS

PL-001

PLUMBING:

PLUMBING: SYMBOLS, ABBREVIATIONS & NOTES

PL-101 PLUMBING: GROUND FLOOR DEMOLITION & NEW BASEMENT/GROUND FLOOR CONSTRUCTION PLANS

PL-701 PLUMBING: DETAILS

SAFETY AND GENERAL INFORMATIONGI-0022

ICRA PLANGI-0033

GROUND FLOOR LIFE SAFETY PLANLS-1014

8 AS-401 ARCHITECTURAL: WALL SECTIONS AND INTERIOR ELEVATIONS

9 AS-501 ARCHITECTURAL: EQUIPMENT ENLARGED FLOOR PLANS

10 AS-701 ARCHITECTURAL: DETAILS

11 AS-801 ARCHITECTURAL: SCHEDULES

HVAC: DETAILSMH-701

FX-001

FIRE PROTECTION:

FIRE PROTECTION: SYMBOLS, ABBREVIATIONS & NOTES

FX-101 FIRE PROTECTION: GROUND FLOOR DEMOLITION & NEW CONSTRUCTION PLANS

ES-701

ES-801

ELECTRICAL: DETAILS

ELECTRICAL: SCHEDULES

ES-102 ELECTRICAL: GROUND FLOOR RF FEEDER PLANS

MH-102

MH-103

MH-104

MH-105

HVAC: RE-BALANCING DRAWING 1: AHU-1 (SUPPLY & RETURN) EF-2, 3 & 4

HVAC: RE-BALANCING DRAWING 2: AHU-1 (SUPPLY & RETURN) EF-2 & 3

HVAC: RE-BALANCING DRAWING 2: AHU-1 (SUPPLY & RETURN) EF-2

HVAC: RE-BALANCING, PERFORMANCE DATA: AH-1 (SUPPLY & RETURN) EF-2, 3 & 4

AutoCAD SHX Text

OIL

AutoCAD SHX Text

OIL

AutoCAD SHX Text

OIL

AutoCAD SHX Text

OIL

AutoCAD SHX Text

OIL

AutoCAD SHX Text

VENT

AutoCAD SHX Text

VENT

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text

GRAVEL DRIVE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

GRAVEL DRIVE

AutoCAD SHX Text

GRAVEL DRIVE

AutoCAD SHX Text

W/F GARAGE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

ASPHALT

AutoCAD SHX Text

ASPHALT

AutoCAD SHX Text

GRAVEL DRIVE

AutoCAD SHX Text

SPIGOT

AutoCAD SHX Text

ASPHALT

AutoCAD SHX Text

EOP

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

ELEC. BOX

AutoCAD SHX Text

EOP

AutoCAD SHX Text

GRAVEL DRIVE

AutoCAD SHX Text

UG ELEC

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

STONE DRIVE

AutoCAD SHX Text

CONC.

AutoCAD SHX Text

CONSTRUCTION STORAGE &

AutoCAD SHX Text

PARKING AREA

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

20MPH

AutoCAD SHX Text

ASPHALT DRIVE

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

GAS MARKOUT

AutoCAD SHX Text

GAS VALVE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

CHAINLINK FENCE

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

ASPHALT

AutoCAD SHX Text

GUIDERAIL

AutoCAD SHX Text

UP

AutoCAD SHX Text

BUILDING #95

AutoCAD SHX Text

SIDEWALK

AutoCAD SHX Text

DITCH

AutoCAD SHX Text

GUIDERAIL

AutoCAD SHX Text

DITCH

AutoCAD SHX Text

GUIDERAIL

AutoCAD SHX Text

RIPRAP

AutoCAD SHX Text

RIPRAP

AutoCAD SHX Text

24" SPRUCE

AutoCAD SHX Text 24"

AutoCAD SHX Text

SPRUCE

AutoCAD SHX Text 10"

AutoCAD SHX Text

SPRUCE

AutoCAD SHX Text 22"

AutoCAD SHX Text

SPRUCE

AutoCAD SHX Text 18"

AutoCAD SHX Text

MULBERRY

AutoCAD SHX Text 12"

AutoCAD SHX Text

SPRUCE

AutoCAD SHX Text 15"

AutoCAD SHX Text

SPRUCE

AutoCAD SHX Text 18"

AutoCAD SHX Text

(DEAD)

AutoCAD SHX Text 24"

AutoCAD SHX Text

SPRUCE TREES (6"-24")

AutoCAD SHX Text W O O D S

AutoCAD SHX Text

16" TRIP

AutoCAD SHX Text 15"

AutoCAD SHX Text 16"

AutoCAD SHX Text 16"

AutoCAD SHX Text

UG ELEC

AutoCAD SHX Text

EXCAVATED AREA

AutoCAD SHX Text

WATER

AutoCAD SHX Text

EAST CIRCLE DRIVE

AutoCAD SHX Text

KNOLLCROFT ROAD

AutoCAD SHX Text

BUILDING 1 LOCATION

AutoCAD SHX Text

VALLEY ROAD

AutoCAD SHX Text

KNOLLCROFT ROAD

AutoCAD SHX Text

EAST CIRCLE DRIVE

AutoCAD SHX Text

PROJECT TITLE:

AutoCAD SHX Text

MEDICAL CENTER

AutoCAD SHX Text

LYONS, N.J. 07939

AutoCAD SHX Text

DEPARTMENT OF VETERANS AFFAIRS

AutoCAD SHX Text

V.A. PROJECT NO.: 561A4-21-101

AutoCAD SHX Text

LOCATION MAP

AutoCAD SHX Text

CONSULTING ENGINEERS:

AutoCAD SHX Text

22 MULBERRY STREET MIDDLETOWN, NEW YORK 10940

AutoCAD SHX Text

REPLACE RF UNIT SITE PREP - BLDG 1 RM. 48

AutoCAD SHX Text

INDEX OF DRAWINGS

AutoCAD SHX Text

BUILDING LOCATION MAP

AutoCAD SHX Text

AERIAL VIEW

AutoCAD SHX Text

SITE LOCATION

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF STATE EDUCATION LAW.

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION DESCRIPTION

AutoCAD SHX Text

PROF. SEAL:

AutoCAD SHX Text

DESIGN APPROVED W/ COMMENTS:

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text

MARK D. FELLENZER, P.E.

AutoCAD SHX Text

NJ PROFESSIONAL ENGINEER NO. 24GE04661500 EXP. 4/26

D

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX

. S

T

EX. ST

D

D

?S

S

ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX.SAN

EX. ST

EX. ST

EX. ST

EX. ST

EX. ST

BUILDING # 1

X X X X

EX. ST

EX. ST

EX. ST

EX. ST

EX

. S

T

EX.SAN

EX. TEL

EX. TEL

8' TEMPORARY CONSTRUCTION FENCING DETAIL2 WITH DOUBLE MAN GATE DETAIL3

TEMPORARY CONSTRUCTION FENCING

SAFETY NOTES:

GENERAL NOTES:

GI-002

SAFETY AND GENERAL INFORMATION

TEMPORARY CONSTRUCTION SITE PLAN1

LEGEND:

S

E

D

Fi le

N am e:

F

:\2

2\

-1

L yo ns S ite P re p\

(2 ) G

I-0

.d w ou t:

G I-0

D at e:

T ue , J un

5,

- 1 :3 am e:

s a)

ENGINEERING LLP

www.fellp.com

181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735

22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986

FE PROJECT #: 22-171

Replace RF Unit Site Prep- Rm. 48

561A4-21-101

06-14-24

FOR CONSTRUCTION

151 KNOLLCROFT RD.

LYONS, NJ 07939

GROUND FLOOR KEY PLAN:

30EDF SL

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text

EQUIPMENT BUILDING

AutoCAD SHX Text

EXISTING TRAILER

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text

DUMPSTER

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. SEE DETAIL 1 FOR LOCATIONS OF TEMPORARY CONSTRUCTION FENCING AND SEE DETAIL 1 FOR LOCATIONS OF TEMPORARY CONSTRUCTION FENCING AND ADDITIONAL INFORMATION. 2. 2x11GA WIRE FILL 2x11GA WIRE FILL 3. TENSION BANDS W/ NUTS AND BOLTS (NOT PRESS CLIPS) TENSION BANDS W/ NUTS AND BOLTS (NOT PRESS CLIPS) 4. WIRE TIES EVERY 12" WIRE TIES EVERY 12" 5. PROVIDE SAND BAGS AS ADDITIONAL SUPPORT ATOP STABILIZERS/STANDS.PROVIDE SAND BAGS AS ADDITIONAL SUPPORT ATOP STABILIZERS/STANDS.

AutoCAD SHX Text 10'-0"

AutoCAD SHX Text

TENSION BANDS

AutoCAD SHX Text

GRADE

AutoCAD SHX Text 8'

AutoCAD SHX Text 36"

AutoCAD SHX Text 16"

AutoCAD SHX Text

STABILIZERS/ STANDS

AutoCAD SHX Text

FENCE STABILIZERS/ STANDS

AutoCAD SHX Text

FRONT VIEW

AutoCAD SHX Text

SIDE VIEW

AutoCAD SHX Text

TOP VIEW

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

PROVIDE (2) FILLED SAND BAGS FOR EACH STABILIZER/STAND FOR STABILITY.

AutoCAD SHX Text 8'-0"

AutoCAD SHX Text

GRADE

AutoCAD SHX Text 8'

AutoCAD SHX Text

MAX.

AutoCAD SHX Text 3'-0"

AutoCAD SHX Text

MIN.

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. CENTER RAIL REQUIRED ON GATE LEAVES. CENTER RAIL REQUIRED ON GATE LEAVES. 2. CONTRACTOR TO PROPOSE AND COORDINATE LOCATION WITH VA. SEE CONTRACTOR TO PROPOSE AND COORDINATE LOCATION WITH VA. SEE DETAIL #1 FOR APPROXIMATE LOCATIONS.

AutoCAD SHX Text

TENSION BANDS

AutoCAD SHX Text

STABILIZERS/ STANDS

AutoCAD SHX Text

PROVIDE (2) FILLED SAND BAGS FOR EACH STABILIZER/STAND FOR STABILITY.

AutoCAD SHX Text 3'-0"

AutoCAD SHX Text

MIN.

AutoCAD SHX Text

CENTER RAIL

AutoCAD SHX Text

1. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES, RULES & REGULATIONS FOR THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES, RULES & REGULATIONS FOR THE DEMOLITION AND CONSTRUCTION OPERATIONS. 2. THE CONTRACTOR SHALL PROVIDE ALL SIDEWALK BRIDGING AND SAFETIES REQUIRED FOR THE CONTRACTOR SHALL PROVIDE ALL SIDEWALK BRIDGING AND SAFETIES REQUIRED FOR PROPER PROTECTION OF ALL WALKWAYS AND DRIVEWAYS. SUCH BRIDGING SHALL BE HEAVY DUTY BRIDGING (300 PSF CAPACITY) WITH LIGHTS. ALL WORK TO COMPLY WITH ALL FEDERAL, STATE, & LOCAL LAWS AND REGULATIONS AS WELL AS OSHA REQUIREMENTS. BRIDGING & SCAFFOLDING SHOP DRAWING SUBMISSION SHALL INCLUDE A STRUCTURAL DESIGN, SIGNED & SEALED BY A CERTIFIED STRUCTURAL ENGINEER LICENSED IN THE STATE OF NEW JERSEY. 3. PRIOR TO START OF CONSTRUCTION, CONTRACTOR TO PROVIDE TO VA CONTRACTING OFFICER'S PRIOR TO START OF CONSTRUCTION, CONTRACTOR TO PROVIDE TO VA CONTRACTING OFFICER'S REPRESENTATIVE (COR) AND VA SAFETY REPRESENTATIVE A COMPLETE AND DETAILED CONSTRUCTION PLAN INCLUDING: CONSTRUCTION PHASING PLAN, CONSTRUCTION SCHEDULE, SAFETY PLAN WITH FALL PROTECTION SHOWING ALL SAFETY MEASURES BEING TAKEN TO PROTECT AREAS AND PEOPLE BELOW AREAS OF WORK. CONSTRUCTION PLAN TO BE APPROVED BY VA PRIOR TO START OF WORK. 4. CONSTRUCTION PLAN TO ALSO INCLUDE INSTALLATION DETAILS OF SCAFFOLDING, BRIDGING AND CONSTRUCTION PLAN TO ALSO INCLUDE INSTALLATION DETAILS OF SCAFFOLDING, BRIDGING AND MOTORIZED HOIST/TOWER ELEVATOR PLANS. INSTALLATION DETAILS TO BE CERTIFIED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OF NEW JERSEY. 5. PROVIDE FALL PROTECTION PRIOR TO ALL DEMOLITION WORK AND ONCE AGAIN PRIOR TO ANY PROVIDE FALL PROTECTION PRIOR TO ALL DEMOLITION WORK AND ONCE AGAIN PRIOR TO ANY NEW WORK. THE CONTRACTOR SHALL COMPLY WITH ALL REGULATIONS CONCERNING OSHA STANDARD 1926.500 "FALL PROTECTION". 6. CONTRACTOR TO SUPPLY AND USE ALL "PERSONAL FALL ARREST SYSTEMS" AS REQUIRED BY CONTRACTOR TO SUPPLY AND USE ALL "PERSONAL FALL ARREST SYSTEMS" AS REQUIRED BY 29 CFR 1926. 7. CONTRACTOR TO HAVE ON SITE AT ALL TIMES DURING CONSTRUCTION, A "SAFETY MONITOR" CONTRACTOR TO HAVE ON SITE AT ALL TIMES DURING CONSTRUCTION, A "SAFETY MONITOR" PERSON TO ACT AS OUTLINED IN OSHA "FALL PROTECTION SYSTEMS AND PRACTICES" STANDARD 1926.502. MONITOR TO WORK WITH VA COR AND SAFETY OFFICE AND COORDINATE ALL SAFETY ACTIVITIES. 8. CHUTES ARE NOT TO BE USED FOR THE REMOVAL OF MATERIAL FROM THE ROOFTOP. CHUTES ARE NOT TO BE USED FOR THE REMOVAL OF MATERIAL FROM THE ROOFTOP. 9. PROVIDE REFLECTIVE VINYL SIGNAGE FOR ALL FIRE DEPARTMENT CONNECTIONS FOR THE PROVIDE REFLECTIVE VINYL SIGNAGE FOR ALL FIRE DEPARTMENT CONNECTIONS FOR THE DURATION OF THE PROJECT. SIGNAGE TO NOTE "DO NOT BLOCK" "FIRE DEPARTMENT CONNECTION". 10. CONTRACTOR SHALL PROVIDE SAFETY & CONSTRUCTION SIGNS PER THE VA REQUIREMENTS CONTRACTOR SHALL PROVIDE SAFETY & CONSTRUCTION SIGNS PER THE VA REQUIREMENTS DESCRIBED IN SPECIFICATION SECTION 01 00 00. ALL SIGNAGE TO BE REVIEWED AS PART OF THE SAFETY PLAN. 11. LOCAL BARRIERS WILL BE USED WHEN MATERIAL TRANSPORTING EQUIPMENT, INCLUDING BUT LOCAL BARRIERS WILL BE USED WHEN MATERIAL TRANSPORTING EQUIPMENT, INCLUDING BUT NOT LIMITED TO SCISSOR LIFTS, MOBILE BOOM LIFTS, CRANES, SCAFFOLDIING AND HOIST TOWER ELEVATORS, ARE EMPLOYED. ALL BARRIERS SHALL BE SUBMITTED TO THE ENGINEER & VA FOR APPROVAL. 12. CONTRACTOR MUST PROTECT ALL EXISTING VEGETATION DURING EACH PHASE OF WORK BY AN CONTRACTOR MUST PROTECT ALL EXISTING VEGETATION DURING EACH PHASE OF WORK BY AN APPROVED VA METHOD. REFER TO SPECIFICATION 01 00 00 FOR FURTHER INFORMATION.

AutoCAD SHX Text

1. FINAL LOCATION FOR STAGING SHALL BE COORDINATED WITH THE VA COR PRIOR TO START OF FINAL LOCATION FOR STAGING SHALL BE COORDINATED WITH THE VA COR PRIOR TO START OF ANY WORK. 2. CONTRACTOR SHALL PROVIDE TEMPORARY FENCING AROUND STORAGE AREA PER VA GUIDELINES CONTRACTOR SHALL PROVIDE TEMPORARY FENCING AROUND STORAGE AREA PER VA GUIDELINES & STANDARDS. STAGING AREA TO BE LOCKED AND SECURED WHEN NOT ATTENDED. 3. COORDINATE WITH THE VA FOR MAXIMUM AVAILABLE AREAS FOR CONTRACTOR TRAILERS AND COORDINATE WITH THE VA FOR MAXIMUM AVAILABLE AREAS FOR CONTRACTOR TRAILERS AND MATERIAL STORAGE. CONTRACTOR TO MINIMIZE SPACE AND DURATION OF USE OF THESE SPACES AS MUCH AS POSSIBLE. 4. ANY DISTURBANCE TO TRAFFIC FLOW IN PARKING LOT AT THE VA CAMPUS, INCLUDING LIFTING ANY DISTURBANCE TO TRAFFIC FLOW IN PARKING LOT AT THE VA CAMPUS, INCLUDING LIFTING OF EQUIPMENT OR MATERIAL, MUST TAKE PLACE AFTER 5 PM AND BEFORE 6:30 AM, MONDAY THROUGH FRIDAY, OR AT ANY TIME ON WEEKENDS. MINOR MATERIAL DELIVERIES AND REMOVALS MAY TAKE PLACE DURING NORMAL BUSINESS HOURS BY USE OF THE VA APPROVED ELEVATORS. 5. CONTRACTOR TO SUPPLY AND MAINTAIN DUMPSTERS FOR CONSTRUCTION DEBRIS. CONTRACTOR TO SUPPLY AND MAINTAIN DUMPSTERS FOR CONSTRUCTION DEBRIS. 6. USE OF VA DUMPSTERS OR COMPACTOR IS NOT ALLOWED. USE OF VA DUMPSTERS OR COMPACTOR IS NOT ALLOWED. 7. PROVIDE TARP; DUMPSTERS TO BE COVERED AT ALL TIMES. PROVIDE TARP; DUMPSTERS TO BE COVERED AT ALL TIMES. 8. DUMPSTERS TO BE REMOVED/REPLACED WITHIN 24 HOURS OF REACHING MAXIMUM ALLOWABLE DUMPSTERS TO BE REMOVED/REPLACED WITHIN 24 HOURS OF REACHING MAXIMUM ALLOWABLE CAPACITY. ALL DISPOSAL FEES BY THE CONTRACTOR. 9. PROVIDE WARNING SIGNS IN AREA OF DUMPSTERS AND AS DIRECTED BY VA. PROVIDE WARNING SIGNS IN AREA OF DUMPSTERS AND AS DIRECTED BY VA. 10. PROVIDE NETTING AND BRIDGING TO PROTECT ALL AREAS INCLUDING BUT NOT LIMITED TO THE PROVIDE NETTING AND BRIDGING TO PROTECT ALL AREAS INCLUDING BUT NOT LIMITED TO THE FOLLOWING: WALKWAYS, EQUIPMENT ON LOWER ROOF AREAS, ETC. THAT ARE BELOW THE LIFT AREAS OR WORKING AREAS. ALL HVAC UNITS, INCLUDING BUT NOT LIMITED TO UNITS WITH INTAKES OR FANS BLOWING UPWARDS, SHALL BE PROTECTED FROM ANY FALLING DEBRIS WITH BRIDGING AND AREA PROTECTION SHALL NOT BLOCK OR RESTRICT THE AIR FLOW OF ANY EQUIPMENT. 11. CONTRACTOR SHALL SUBMIT MOTORIZED HOIST/TOWER ELEVATOR, SCAFFOLDING AND BRIDGING CONTRACTOR SHALL SUBMIT MOTORIZED HOIST/TOWER ELEVATOR, SCAFFOLDING AND BRIDGING PLANS TO VA FOR REVIEW & APPROVAL. 12. ALL OUTSIDE LIFTS OF EQUIPMENT OR MATERIAL TO BE PERFORMED DURING THE HOURS AFTER ALL OUTSIDE LIFTS OF EQUIPMENT OR MATERIAL TO BE PERFORMED DURING THE HOURS AFTER 5:00 PM AND BEFORE 6:30 AM, MONDAY THROUGH FRIDAY, OR DURING THE WEEKEND. 13. ALL SUSPENDED SCAFFOLDING SYSTEMS, LIFTS AND LOAD PLACED ON THE ROOF SHALL NOT ALL SUSPENDED SCAFFOLDING SYSTEMS, LIFTS AND LOAD PLACED ON THE ROOF SHALL NOT EXCEED 40 PSF. LIFTS REQUIRE ADDITIONAL WEIGHT WAIVER SHALL BE COORDINATED AND THE ACTUAL LOCATION OF PLACEMENT BE DEFINED WITH A NEW WEIGHT LIMIT/RESTRICTION. 14. PRIOR TO STARTING WORK, SUBMIT FOR VA APPROVAL DETAILED SCHEDULE INDICATING ALL PRIOR TO STARTING WORK, SUBMIT FOR VA APPROVAL DETAILED SCHEDULE INDICATING ALL WORK THAT MAY AFFECT THE OWNER'S USE OF THE FACILITY, INCLUDING UTILITY SHUT DOWNS, NOISE GENERATING ACTIVITIES, OPERATIONS IMPACTING TRAFFIC PATTERNS, AND AREAS AFFECTING PATIENT PRIVACY. 15. PROTECT ALL EXISTING COMPONENTS TO BE LEFT IN PLACE, INCLUDING PAVING, LANDSCAPING PROTECT ALL EXISTING COMPONENTS TO BE LEFT IN PLACE, INCLUDING PAVING, LANDSCAPING AND OTHER SITE COMPONENTS. MAINTAIN A WEATHER-TIGHT ENCLOSURE OVER THE OCCUPIED SPACE BENEATH THE WORK AREA AT ALL TIMES. 16. TRAFFIC ALONG ALL ACCESS ROADS MUST ALWAYS HAVE AT LEAST 1 LANE OPEN AT ALL TIMES TRAFFIC ALONG ALL ACCESS ROADS MUST ALWAYS HAVE AT LEAST 1 LANE OPEN AT ALL TIMES FOR EMERGENCY VEHICLE ACCESS. IF DOWN TO 1 LANE EVEN FOR A VERY SHORT PERIOD OF TIME, FLAG PERSONS MUST DIRECT TRAFFIC ON BOTH ENDS OF THE CLOSURE AS WELL AS THE VISITOR'S PARKING LOT ENTRANCE. 17. PEDESTRIAN AND VEHICULAR TRAFFIC TO BE MAINTAINED AT ALL TIMES AT THE MAIN ENTRANCE. PEDESTRIAN AND VEHICULAR TRAFFIC TO BE MAINTAINED AT ALL TIMES AT THE MAIN ENTRANCE. DO NOT IMPACT PICK-UP OR DROP-OFF OPERATIONS AT ANY TIMES. 18. USE OF NOISE & VIBRATION EMITTING POWER TOOLS MAY BE USED DURING THE HOURS OF USE OF NOISE & VIBRATION EMITTING POWER TOOLS MAY BE USED DURING THE HOURS OF 7:30-5:00PM, MONDAY - FRIDAY, WITHIN NOISE & VIBRATION LIMITS SPECIFIED BY THE VA. PERMISSION MUST BE REQUESTED AT LEAST 72 HOURS IN ADVANCE & APPROVAL AUTHORIZED BEFORE USE OF ANY SUCH EQUIPMENT. 19. VA COR OR SAFETY OFFICER CAN STOP THE USE OF NOISE & VIBRATION EMITTING POWER VA COR OR SAFETY OFFICER CAN STOP THE USE OF NOISE & VIBRATION EMITTING POWER TOOLS AT ANY TIME IF THE NOISE & VIBRATION IMPACTS ANY HOSPITAL FUNCTION. IF THIS OCCURS, WORK MUST BE PERFORMED OFF HOURS, BY USE OF HAND TOOLS OR AT AN ALTERNATE TIME AS APPROVED BY VA COR OR SAFETY OFFICER. 20. ALL WORK IN OCCUPIED AREAS AND BUILDING CORRIDOR SHALL NOT INTERRUPT PATIENT CARE ALL WORK IN OCCUPIED AREAS AND BUILDING CORRIDOR SHALL NOT INTERRUPT PATIENT CARE AND IS TO BE PERFORMED DURING THE HOURS AFTER 5:00 PM AND BEFORE 6:30 AM, MONDAY THROUGH FRIDAY, OR DURING THE WEEKEND. CEILING TILES MUST BE RE-INSTALLED AND AREA CLEANED EACH DAY AT FINISH OF WORK DAY PRIOR TO TURNING OVER TO VA. 21. SMOKING IS PROHIBITED ON THE VA MEDICAL CENTER PROPERTY, INCLUDING PARKING LOTS SMOKING IS PROHIBITED ON THE VA MEDICAL CENTER PROPERTY, INCLUDING PARKING LOTS AND STORAGE AREAS. 'SMOKING' INCLUDES THE USE OF ELECTRONIC CIGARETTES AND CIGARS.

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

SANITARY MANHOLE

AutoCAD SHX Text

EXISTING TRANSFORMER

AutoCAD SHX Text

BUILDING IN PROJECT SCOPE

AutoCAD SHX Text

DOOR OPENING TO REMAIN OPERATIONAL AT ALL TIMES.

AutoCAD SHX Text

PROPOSED TEMPORARY FENCING

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text

EXISTING HVAC EQUIPMENT

AutoCAD SHX Text

EXISTING BOLLARD

AutoCAD SHX Text

STORM SEWER MANHOLE

AutoCAD SHX Text

ELECTRICAL MANHOLE

AutoCAD SHX Text

PROPOSED STAGING AREA

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF STATE EDUCATION LAW.

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION DESCRIPTION

AutoCAD SHX Text

PROF. SEAL:

AutoCAD SHX Text

DESIGN APPROVED W/ COMMENTS:

AutoCAD SHX Text F

AutoCAD SHX Text

AREA OF WORK

AutoCAD SHX Text E

AutoCAD SHX Text

MARK D. FELLENZER, P.E.

AutoCAD SHX Text

NJ PROFESSIONAL ENGINEER NO. 24GE04661500 EXP. 4/26

AutoCAD SHX Text

AREA OF WORK

AutoCAD SHX Text

SP

AutoCAD SHX Text

STANDPIPE

AutoCAD SHX Text

FIRE DEPARTMENT SIAMESE CONNECTION (DO NOT BLOCK)

AutoCAD SHX Text 40'x40'±PROPOSED STAGING AREA (MUST BE LOCKED AND SECURED WHEN NOT ATTENDED.)

AutoCAD SHX Text

NO DELIVERIES OR STAGING THIS AREA

ALL DELIVERIES TO BUILDING LOADING DOCK AREA

X-RAY #1

PATIENT

TOILET

PATIENT

DRESSING

CLEAN

SUPPLY

DEXASCAN

READING

ROOM

ULTRASOUND

PATIENT

TOILET

PATIENT

TOILET

48A

CONSULT.

ROOM

PATIENT

HOLDING

ZONE 3

ANTEROOM

SOILED

45A

NURSE

TEAMING

ROOM

EQUIP.

ALCOVE

CORRIDOR

ELECTRIC

ROOM

Fi le

N am e:

F

:\2

2\

-1

L yo ns S ite P re p\

(3 ) G

I-0

IC

R

A.

dw ou t:

G I-0

D at e:

T ue , J un

5,

- 1 :3 am e:

s a)

ENGINEERING LLP

www.fellp.com

181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735

22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986

FE PROJECT #: 22-171

Replace RF Unit Site Prep- Rm. 48

561A4-21-101

06-14-24

FOR CONSTRUCTION

151 KNOLLCROFT RD.

LYONS, NJ 07939

GROUND FLOOR KEY PLAN:

GI-003

ICRA PLANS

ARCHITECTURAL: GROUND FLOOR ICRA PLAN1

EDF SL

LEGEND:

Description of Required Infection Control Precautions by Class During Construction Project Upon Completion of

1. Remove or isolate HVAC system in area where work is being done to prevent contamination of duct system.

2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with HEPA vacuum for vacuuming prior to exit) before construction begins.

3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.

4. Contain construction waste before transport in tightly covered containers.

5. Cover transport receptacles or carts. Tape covering unless solid lid.

6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.

7. Do not remove barriers from work area until completed project is inspected by the owner's Safety Section and Infection Control Department, and thoroughly cleaned by the owner's Environment Services Department.

1. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.

2. Contain construction waste before transportation in tightly covered containers.

3. Cover transport receptacles or carts. Tape covering unless solid lid.

4. Vacuum work area with HEPA filtered vacuums.

5. Wet mop area with disinfectant.

6. Remove isolation of HVAC system in areas where work is being performed.

C la ss

IV

PATIENT RISK GROUP FOR "TYPE D" CONSTRUCTION

LOW RISK GROUP

MEDIUM RISK GROUP

HIGH RISK GROUP

HIGHEST RISK GROUP Class IV

Class III / IV

Class IV Class IV

NOTES:

ICRA TEMPORARY BARRIER

KEYED NOTES:

LIFE SAFETY LEGEND:

NON-RATED INTERIOR PARTITION

ICRA PARTITION DETAILS2

GENERAL NOTES AND CONSTRUCTION DETAILS:

AutoCAD SHX Text N

AutoCAD SHX Text

SP

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text

SP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF STATE EDUCATION LAW.

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION DESCRIPTION

AutoCAD SHX Text

PROF. SEAL:

AutoCAD SHX Text

DESIGN APPROVED W/ COMMENTS:

AutoCAD SHX Text F

AutoCAD SHX Text

AREA OF WORK

AutoCAD SHX Text E

AutoCAD SHX Text

MARK D. FELLENZER, P.E.

AutoCAD SHX Text

NJ PROFESSIONAL ENGINEER NO. 24GE04661500 EXP. 4/26

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

AREA NOT IN SCOPE U.N.O.

AutoCAD SHX Text MAJOR DEMOLITION AND CONSTRUCTION PROJECTS ACTIVITIES THAT REQUIRE CONSECUTIVE WORK SHIFTS REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE CABLING SYSTEM NEW CONSTRUCTION

AutoCAD SHX Text

1. CONTRACTOR SHALL PROVIDE REQUIRED INFECTION CONTROL CONTRACTOR SHALL PROVIDE REQUIRED INFECTION CONTROL PRECAUTIONS AS SHOWN IN CHART FOR ALL WORK TO BE DONE UNDER THIS PROJECT, INCLUDING BUT NOT LIMITED TO TEMPORARY RATED PARTITIONS SEPARATION FROM OCCUPIED SPACES WITH RATED DOORS AS REQUIRED FOR ACCESS PRIOR TO STARTING ANY WORK. 2. IF AREA OF WORK IS IN QUESTION, COORDINATE WITH VA IF AREA OF WORK IS IN QUESTION, COORDINATE WITH VA REPRESENTATIVE FOR CLASSIFICATION OF AREA. 3. INSPECTION OF AREA REQUIRED BY VA COR/SAFETY/INFECTION INSPECTION OF AREA REQUIRED BY VA COR/SAFETY/INFECTION PREVENTION PRIOR TO REMOVING BARRIERS. 4. SEE DRAWING LS-101 FOR LEGEND AND LOCATIONS OF FIRE AND SEE DRAWING LS-101 FOR LEGEND AND LOCATIONS OF FIRE AND SMOKE BARRIERS ON THE GROUND FLOOR. 5. CONTRACTOR TO PROVIDE TEMPORARY DUMPSTERS, TEMPORARY SITE CONTRACTOR TO PROVIDE TEMPORARY DUMPSTERS, TEMPORARY SITE PROTECTION & SIGNAGE AS NECESSARY. 6. CONTRACTOR TO DEMO EXISTING ITEMS AS PER PLANS WITHOUT CONTRACTOR TO DEMO EXISTING ITEMS AS PER PLANS WITHOUT INTERRUPTION TO FACILITY. COVER ALL DEBRIS AND DAMPEN TO ELIMINATE DUST. 7. EXISTING SCANNING MEDICAL EQUIPMENT TO BE REMOVED BY EXISTING SCANNING MEDICAL EQUIPMENT TO BE REMOVED BY EQUIPMENT MANUFACTURER PRIOR TO START OF ANY DEMOLITION.

AutoCAD SHX Text

EXISTING FINISHED FLOOR

AutoCAD SHX Text 6 MIL. FIRE RETARDANT POLY EXTENDED TO UNDERSIDE OF STRUCTURE ABOVE TAPED AND SEALED AT ALL EDGES AND AROUND ALL PENETRATIONS

AutoCAD SHX Text

EXISTING FLOOR/ROOF STRUCTURE ABOVE

AutoCAD SHX Text EXISTING 44"Wx7'H DOOR, FRAME AND HARDWARE TO BE REMAIN FOR DURATION OF CONSTRUCTION AS TEMPORARY CONSTRUCTION ENTRANCE DOOR. PROVIDE NEGATIVE AIR PRESSURE MONITOR AT THIS PROVIDE NEGATIVE AIR PRESSURE MONITOR AT THIS 'TEMPORARY' CONSTRUCTION ENTRANCE DOOR. AFTER ROOM AFTER ROOM CONSTRUCTION AND EQUIPMENT INSTALLATION IS COMPLETE EXISTING DOOR, FRAME AND HARDWARE TO BE REMOVED AND DISPOSED. PROVIDE AND INSTALL NEW LEAD LINED DOOR & FRAME AND HARDWARE IN EXISTING LOCATION PER AS SERIES DRAWINGS. CONTRACTOR TO PROVIDE HARD BARRIER TO RIBBED CONCRETE FLOOR DECK ABOVE TO PROTECT ADJACENT AREAS FROM DUST AND DEBRIS. BARRIERS SHALL BE METAL STUD WALLS WITH (1) LAYER TYPE 'X' SHEETROCK APPROX. 3'-0" HIGH FROM TOP OF EXISTING WALL TO BOTTOM OF CONCRETE DECK. CONCRETE RIBS ARE APPROX. 8" DEEP AND APPROX. 6" WIDE. ALL JOINTS TO BE SEALED. SEE DETAIL 2/GI-003 WALL TYPE C PARTITION. PROVIDE WALK-OFF (TACKY) MAT. EXHAUST POINT TO MAINTAIN NEGATIVE PRESSURE. OPEN WINDOW OR REMOVE PANE AS NECESSARY TO EXHAUST AIR. CLOSE WINDOW OR REPLACE PANE TO EXISTING CONDITIONS UPON COMPLETION OF WORK. IDENTIFIED WINDOW SHALL BE USED FOR EXHAUST POINT. PROVIDE EXHAUST POINT/FAN AS NECESSARY TO MEET VENTILATION REQUIREMENTS. PROVIDE HEPA FILTRATION TO ALL EXHAUSTS. ALL WORK IN EXISTING CORRIDOR SHALL BE DURING OFF HOURS (NIGHTS AND WEEKENDS) AS APPROVED BY COR. PROVIDE "ICRA TEMPORARY BARRIERS" (PLASTIC SHEETING).

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXIT ROUTE FOR CONSTRUCTION DEBRIS.

AutoCAD SHX Text

AutoCAD SHX Text

1 HR FIRE RATED BARRIER (45 MINUTE DOOR)

AutoCAD SHX Text

SMOKE BARRIER - HR FIRE RATED12 HR FIRE RATED

AutoCAD SHX Text

2 HR FIRE RATED BARRIER (1-1/2 HR DOOR AND FIRE DAMPERS)

AutoCAD SHX Text

2 HR FIRE RATED BARRIER AND SMOKE PARTITION

AutoCAD SHX Text

PATCH BARRIER AT AND ABOVE CEILING LEVEL

AutoCAD SHX Text

NEW BARRIER AT CEILING LEVEL TO CONCRETE DECK. SEE DETAIL 2/GI-003

AutoCAD SHX Text

WALL BASE, EACH SIDE. SEE FINISH SCHEDULE

AutoCAD SHX Text

EXISTING STUDS

AutoCAD SHX Text ADD (1) LAYER 5/8" TYPE "X" GYPSUM WALL BD W/ " 116" LEAD LINING TO 7'-6" AFF MIN., EQUIPMENT SIDE OF EXISTING WALL. SHIELDING MUST BE FOLDED OVER AND OVERLAPPED MIN. 12" AT WALL INTERSECTIONS TO PROVIDE CONTINUOUS PROTECTION.

AutoCAD SHX Text

WALL ANGLE - SECURE TO WALL AS REQUIRED

AutoCAD SHX Text SUSPENDED CEILING GRID AND ACOUSTIC TILE. SEE REFLECTED CEILING PLAN AND FINISH SCHEDULES.

AutoCAD SHX Text

SEAL TOP AT DECK COMPLETE FOR SMOKE SEAL

AutoCAD SHX Text

LINE OF STRUCTURE ABOVE

AutoCAD SHX Text C

AutoCAD SHX Text

EXTEND ALL MATERIALS TO DECK

AutoCAD SHX Text

NOTE: USE MOISTURE RESISTANT GYP. BD ON WET SIDE(S).

AutoCAD SHX Text

LINE OF CONCRETE RIB ABOVE

AutoCAD SHX Text

NEW METAL STUDS

AutoCAD SHX Text

SCALE: N.T.S.

1. SHIELDING SHALL BE CONSTRUCTED SO THAT PROTECTION IS NOT IMPAIRED BY JOINTS, SHIELDING SHALL BE CONSTRUCTED SO THAT PROTECTION IS NOT IMPAIRED BY JOINTS, OPENINGS FOR DUCTS, PIES, ETC. PASSING THROUGH THE BARRIERS, OR BY CONDUIT, SERVICE BOXES, ETC., EMBEDDED IN THE BARRIERS. 2. ALL DOORS AND WINDOWS SHALL HAVE, AT LEAST, THE SAME LEAD EQUIVALENCE AS THE ALL DOORS AND WINDOWS SHALL HAVE, AT LEAST, THE SAME LEAD EQUIVALENCE AS THE REQUIRED BARRIERS IN WHICH THEY ARE LOCATED. 3. ALL SHIELDING SHALL EXTEND AT LEAST 7'-0" ABOVE THE FINISHED FLOOR ALL SHIELDING SHALL EXTEND AT LEAST 7'-0" ABOVE THE FINISHED FLOOR 4. ALL CONCRETE SHOULD BE ASSUMED TO BE LIGHTWEIGHT U.N.O. ALL CONCRETE SHOULD BE ASSUMED TO BE LIGHTWEIGHT U.N.O. 5. ALL NAILS, RIVETS, OR OTHER FASTENERS USED TO FIX LEAD SHEETING TO STUDS IN ALL NAILS, RIVETS, OR OTHER FASTENERS USED TO FIX LEAD SHEETING TO STUDS IN WALLS, ETC. MUST BE LEAD CAPPED. 6. DOORS SHALL BE HUNG WITH A MINIMUM SPACE BETWEEN THE BOTTOM EDGE OF THE DOORS SHALL BE HUNG WITH A MINIMUM SPACE BETWEEN THE BOTTOM EDGE OF THE DOOR AND THE FLOOR. 7. ALL SHIELDING SHALL BE INSTALLED TO COMPLY WITH RECOMMENDATIONS OF NCRP ALL SHIELDING SHALL BE INSTALLED TO COMPLY WITH RECOMMENDATIONS OF NCRP REPORT NO.147 "STRUCTURAL SHIELDING DESIGN FOR MEDICAL X-RAY IMAGING FACILITIES". 8. FIRE STOP AT ALL CONNECTIONS TO EXISTING STRUCTURES AND FINISHES. FIRE STOP AT ALL CONNECTIONS TO EXISTING STRUCTURES AND FINISHES.

RF

CONTROL

ROOM

WAITING

EX. PATIENT

PATIENT

TOILET

PATIENT

DRESSING

CLEAN

SUPPLY

DEXASCAN

CHECK-IN

READING

ROOM

ULTRASOUND

PATIENT

TOILET

PATIENT

TOILET

48A

CONSULT.

ROOM

OFFICE

36A

ADMIN.

OFFICE

TOILET

SOILED

45A

NURSE

TEAMING

ROOM

EQUIP.

ALCOVE

CORRIDOR

146 CORRIDOR

ELECTRIC

ROOM

48B

Fi le

N am e:

F

:\2

2\

-1

L yo ns S ite P re p\

(4 ) L

S-

LI

FE

S

AF

ET

Y.

ou t:

LS

-1

D at e:

T ue , J un

5,

- 1 :4 am e:

s a)

ENGINEERING LLP

www.fellp.com

181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735

22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986

FE PROJECT #: 22-171

Replace RF Unit Site Prep- Rm. 48

561A4-21-101

06-14-24

FOR CONSTRUCTION

151 KNOLLCROFT RD.

LYONS, NJ 07939

GROUND FLOOR KEY PLAN:

LS-101

GROUND FLOOR LIFE SAFETY PLAN

ARCHITECTURAL: GROUND FLOOR LIFE SAFETY PLAN1

EDF SL

GENERAL NOTE:

LIFE SAFETY LEGEND:

AutoCAD SHX Text 160'

AutoCAD SHX Text

MAX. ALLOWED 300' NFPA 101

AutoCAD SHX Text CONTRACTOR TO TEMPORARILY REMOVE EXISTING DOOR FOR EQUIPMENT INSTALLATION (ONE DAY ONLY) AND RE-INSTALL IMMEDIATELY AFTER EQUIPMENT HAS BEEN PLACED IN ROOM. COORDINATE WITH EQUIPMENT INSTALLER.

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF STATE EDUCATION LAW.

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION DESCRIPTION

AutoCAD SHX Text

PROF. SEAL:

AutoCAD SHX Text

DESIGN APPROVED W/ COMMENTS:

AutoCAD SHX Text F

AutoCAD SHX Text

AREA OF WORK

AutoCAD SHX Text E

AutoCAD SHX Text

MARK D. FELLENZER, P.E.

AutoCAD SHX Text

NJ PROFESSIONAL ENGINEER NO. 24GE04661500 EXP. 4/26

AutoCAD SHX Text

SCALE: 1/4"=1'-0"

AutoCAD SHX Text

1. TEMPORARY PARTITION DOOR TO BE FR 44" WIDE BY 7' HIGH. TEMPORARY PARTITION DOOR TO BE FR 44" WIDE BY 7' HIGH. 2. ALL WORK IN OCCUPIED AREAS AND BUILDING CORRIDOR SHALL ALL WORK IN OCCUPIED AREAS AND BUILDING CORRIDOR SHALL NOT INTERRUPT PATIENT CARE AND SHALL BE PERFORMED DURING THE HOURS AFTER 5:00 PM AND BEFORE 6:30 AM, MONDAY THROUGH FRIDAY, OR DURING THE WEEKEND WHEN AREA IS UNOCCUPIED. 3. CEILING TILES MUST BE RE-INSTALLED AND AREA CLEANED EACH CEILING TILES MUST BE RE-INSTALLED AND AREA CLEANED EACH DAY AT FINISH OF WORK DAY PRIOR TO TURNING OVER TO VA.

AutoCAD SHX Text

FEC

AutoCAD SHX Text

1 HR FIRE RATED BARRIER (45 MINUTE DOOR)

AutoCAD SHX Text

SMOKE BARRIER - HR FIRE RATED12 HR FIRE RATED

AutoCAD SHX Text

2 HR FIRE RATED BARRIER (1-1/2 HR DOOR AND FIRE DAMPERS)

AutoCAD SHX Text

EXIT

AutoCAD SHX Text

EXIT SIGN 'E' DENOTES EXISTING TO REMAIN 'N' DENOTES NEW DENOTES DIRECTION

AutoCAD SHX Text

EXISTING FIRE EXTINGUISHER CABINET

AutoCAD SHX Text

EXISTING AREA TO REMAIN (NOT IN CONTRACT)

AutoCAD SHX Text

DISTANCE TO EXIT

AutoCAD SHX Text N

AutoCAD SHX Text

2 HR FIRE RATED BARRIER AND SMOKE PARTITION

AutoCAD SHX Text

PATCH BARRIER AT AND ABOVE CEILING LEVEL

NEW BARRIER AT CEILING LEVEL TO CONCRETE DECK

FLOOR PLAN LEGEND RCP LEGEND

EDF SL

AS-001

ARCHITECTURAL: SYMBOLS,

ABBREVIATIONS & NOTES

Fi le

N am e:

F

:\2

2\

-1

L yo ns S ite P re p\

(5 ) A

S-

1.

ou t:

A-

D at e:

T ue , J un

5,

- 1 :4 am e:

s a)

ENGINEERING LLP

www.fellp.com

181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735

22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986

FE PROJECT #: 22-171

Replace RF Unit Site Prep- Rm. 48

561A4-21-101

06-14-24

FOR CONSTRUCTION

151 KNOLLCROFT RD.

LYONS, NJ 07939

ABBREVIATIONS

GENERAL SYMBOLS

GENERAL NOTES:

HT

ISOMETRIC

TYPICAL GRAB BARS AND CABINETS1

ANCHORAGE -

TYPICAL MOUNTING HEIGHTS2

NOTE:

AutoCAD SHX Text

EXISTING AREA TO REMAIN (NOT IN SCOPE)

AutoCAD SHX Text

AREA IN SCOPE

AutoCAD SHX Text

EXISTING WALL TO REMAIN

AutoCAD SHX Text

EXISTING DOOR TO REMAIN

AutoCAD SHX Text

EXISTING WALL TO BE REMOVED

AutoCAD SHX Text

EXISTING DOOR TO BE REMOVED

AutoCAD SHX Text

NEW WALL

AutoCAD SHX Text

NEW DOOR

AutoCAD SHX Text

XXX

AutoCAD SHX Text

PLUMBING FIXTURES TO REMAIN

AutoCAD SHX Text

PLUMBING FIXTURES TO BE REMOVED

AutoCAD SHX Text

NEW PLUMBING FIXTURES

AutoCAD SHX Text

EXISTING CASEWORK TO REMAIN

AutoCAD SHX Text

EXISTING CASEWORK TO BE REMOVED

AutoCAD SHX Text

NEW CASEWORK

AutoCAD SHX Text

PATCH BARRIER AT AND ABOVE CEILING LEVEL

AutoCAD SHX Text

NEW BARRIER AT CEILING LEVEL TO CONCRETE DECK

AutoCAD SHX Text

EXISTING GRID/CEILING TILE TO REMAIN

AutoCAD SHX Text

EXISTING GRID/CEILING TILE TO BE REMOVED

AutoCAD SHX Text NEW GRID/2'x2' CEILING TILE

AutoCAD SHX Text

EXISTING GYPSUM CEILING TO REMAIN

AutoCAD SHX Text

EXISTING GYPSUM CEILING TO BE REMOVED

AutoCAD SHX Text

NEW GYPSUM CEILING

AutoCAD SHX Text

EXISTING RETURN TO REMAIN

AutoCAD SHX Text

EXISTING SUPPLY TO REMAIN

AutoCAD SHX Text

EXISTING EXHAUST TO REMAIN

AutoCAD SHX Text EXISTING 2'x2' LIGHT TO REMAIN

AutoCAD SHX Text EXISTING 2'x4' LIGHT TO REMAIN

AutoCAD SHX Text

FIRE SPRINKLER HEAD TO REMAIN

AutoCAD SHX Text 2x2 ACCESS PANEL

AutoCAD SHX Text 2x4 ACCESS PANEL

AutoCAD SHX Text

CEILING MOUNTED SPEAKER

AutoCAD SHX Text

CEILING MOUNTED EXIT SIGN

AutoCAD SHX Text

SP

AutoCAD SHX Text

FIRE EXTINGUISHER CABINET

AutoCAD SHX Text

FIRE HOSE CABINET

AutoCAD SHX Text

ZONE VALVE BOX. COORDINATE WITH PLUMBING DWGS

AutoCAD SHX Text

MED GAS ALARM PANEL. COORINATE WITH PLUMBING DWGS

AutoCAD SHX Text

ELECTRICAL PANEL. COORDINATE WITH ELECTRICAL DWGS

AutoCAD SHX Text

CORNER GUARD

AutoCAD SHX Text

FEC

AutoCAD SHX Text

FHC

AutoCAD SHX Text

ZV

AutoCAD SHX Text

AP

AutoCAD SHX Text

PP

AutoCAD SHX Text

HVAC RETURN GRILLE TO BE REMOVED

AutoCAD SHX Text

HVAC SUPPLY DIFFUSER TO BE REMOVED

AutoCAD SHX Text

FIRE SPRINKLER HEAD TO BE REMOVED

AutoCAD SHX Text 2x2 LIGHT TO BE REMOVED

AutoCAD SHX Text 2x2 ACCESS PANEL TO BE REMOVED

AutoCAD SHX Text 2x4 LIGHT TO BE REMOVED

AutoCAD SHX Text 2x4 ACCESS PANEL TO BE REMOVED

AutoCAD SHX Text

CEILING MOUNTED SPEAKER TO BE REMOVED

AutoCAD SHX Text

CEILING MOUNTED EXIT SIGN TO BE REMOVED

AutoCAD SHX Text

EXHAUST AIR TERMINAL TO BE REMOVED

AutoCAD SHX Text W

AutoCAD SHX Text

CEILING MOUNTED WIFI DEVICE TO BE RELOCATED

AutoCAD SHX Text

CEILING MOUNTED NURSE CALL DEVICE TO BE RELOCATED

AutoCAD SHX Text N

AutoCAD SHX Text

NEW HVAC RETURN GRILLE

AutoCAD SHX Text

NEW HVAC SUPPLY DIFFUSER

AutoCAD SHX Text

NEW FIRE SPRINKLER HEAD

AutoCAD SHX Text NEW 2x2 LIGHTING FIXTURE

AutoCAD SHX Text NEW 2x2 ACCESS PANEL

AutoCAD SHX Text

NEW RECESSED LIGHTING FIXTURE

AutoCAD SHX Text NEW 2x4 ACCESS PANEL

AutoCAD SHX Text

NEW CEILING MOUNTED SPEAKER

AutoCAD SHX Text

NEW CEILING MOUNTED EXIT SIGN

AutoCAD SHX Text

NEW EXHAUST AIR TERMINAL

AutoCAD SHX Text W

AutoCAD SHX Text

CEILING MOUNTED WIFI DEVICE

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FULLY SPRINKLERED

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text UNAUTHORIZED ALTERATION OR ADDITION TO A PLAN BEARING A LICENSED PROFESSIONAL ENGINEER'S SEAL IS A VIOLATION OF STATE EDUCATION LAW.

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION DESCRIPTION

AutoCAD SHX Text

PROF. SEAL:

AutoCAD SHX Text

DESIGN APPROVED W/ COMMENTS:

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text

MARK D. FELLENZER, P.E.

AutoCAD SHX Text

NJ PROFESSIONAL ENGINEER NO. 24GE04661500 EXP. 4/26

AutoCAD SHX Text

VERIFY IN FIELD

AutoCAD SHX Text

VIF

AutoCAD SHX Text

ACT

AutoCAD SHX Text

ACOUSTIC CEILING TILE

AutoCAD SHX Text

GENERAL CONTRACTOR

AutoCAD SHX Text G.C.

AutoCAD SHX Text

MINIMUM

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

MIN.

AutoCAD SHX Text P.C.

AutoCAD SHX Text

NOM.

AutoCAD SHX Text

MAXIMUM

AutoCAD SHX Text

NOMINAL

AutoCAD SHX Text

PLUMBING CONTRACTOR

AutoCAD SHX Text

AC

AutoCAD SHX Text

AD

AutoCAD SHX Text

ACCU

AutoCAD SHX Text

AIR CONDITIONING UNIT

AutoCAD SHX Text

AIR COOLED CONDENSING UNIT

AutoCAD SHX Text

ACCESS DOOR

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

CG

AutoCAD SHX Text

CLG

AutoCAD SHX Text

CEILING GRILLE

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DN.

AutoCAD SHX Text

EXIST

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

FLOOR

AutoCAD SHX Text

FLR

AutoCAD SHX Text H.C.

AutoCAD SHX Text

HVAC CONTRACTOR

AutoCAD SHX Text

ABOVE FINISHED FLOOR

AutoCAD SHX Text A.F.F.

AutoCAD SHX Text

POUNDS PER SQUARE IN.

AutoCAD SHX Text

LINEAR FEET

AutoCAD SHX Text

PSI

AutoCAD SHX Text

CUBIC FEET PER MINUTE

AutoCAD SHX Text

CFM

AutoCAD SHX Text

LF

AutoCAD SHX Text

ROUGH OPENING

AutoCAD SHX Text P.T.

AutoCAD SHX Text

PRESSURE TREATED

AutoCAD SHX Text

SPF

AutoCAD SHX Text

SPRUCE PINE FIR

AutoCAD SHX Text

HDR

AutoCAD SHX Text

HEADER

AutoCAD SHX Text S.S.

AutoCAD SHX Text

SOLID STUDS

AutoCAD SHX Text

CMU

AutoCAD SHX Text

CONCRETE MASONRY UNIT

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

TYPICAL

AutoCAD SHX Text F.J.

AutoCAD SHX Text

FLOOR JOIST

AutoCAD SHX Text

CEILING JOIST

AutoCAD SHX Text R.R.

AutoCAD SHX Text

ROOF RAFTER

AutoCAD SHX Text O.C.

AutoCAD SHX Text

ON CENTER

AutoCAD SHX Text

FTG

AutoCAD SHX Text

FOOTING

AutoCAD SHX Text

GYB

AutoCAD SHX Text

GYPSUM BOARD

AutoCAD SHX Text R.O.

AutoCAD SHX Text C.J.

AutoCAD SHX Text

LVL

AutoCAD SHX Text

LAMINATED VENEER LUMBER

AutoCAD SHX Text

POUNDS PER SQUARE FT.

AutoCAD SHX Text

PSF

AutoCAD SHX Text

MECHANICAL EQUIPMENT ROOM

AutoCAD SHX Text M.E.R.

AutoCAD SHX Text N.I.C.

AutoCAD SHX Text

NOT IN CONTRACT

AutoCAD SHX Text U.O.N.

AutoCAD SHX Text

UNLESS OTHERWISE NOTED

AutoCAD SHX Text

2 HOUR FIRERATED WALL

AutoCAD SHX Text

FT

AutoCAD SHX Text

FEET OR FOOT

AutoCAD SHX Text

DRAWING

AutoCAD SHX Text

DWG

AutoCAD SHX Text

DIVISION

AutoCAD SHX Text

DIV

AutoCAD SHX Text

EQUIP.

AutoCAD SHX Text

EQUIPMENT

AutoCAD SHX Text

ELECTRICAL CONTRACTOR

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text E.C.

AutoCAD SHX Text

ELEV

AutoCAD SHX Text

ELEVATOR

AutoCAD SHX Text

EA

AutoCAD SHX Text

EACH

AutoCAD SHX Text

MTG

AutoCAD SHX Text

MOUNTING

AutoCAD SHX Text

MTD

AutoCAD SHX Text

MOUNTED

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

REQ.

AutoCAD SHX Text

REQUIRED

AutoCAD SHX Text

RM.

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

SCHED.

AutoCAD SHX Text

SCHEDULE

AutoCAD SHX Text

SECT.

AutoCAD SHX Text

SECTION

AutoCAD SHX Text

SPEC.

AutoCAD SHX Text

SPECIFICATION

AutoCAD SHX Text

SYS.

AutoCAD SHX Text

SYSTEM

AutoCAD SHX Text

TEL.

AutoCAD SHX Text

TELEPHONE

AutoCAD SHX Text

ALUMINUM

AutoCAD SHX Text

AL

AutoCAD SHX Text

CAT.

AutoCAD SHX Text

CATALOG

AutoCAD SHX Text

POINT OF CONNECTION BETWEEN NEW AND EXISTING WORK

AutoCAD SHX Text

POINT OF DISCONNECT

AutoCAD SHX Text X

AutoCAD SHX Text

XX

AutoCAD SHX Text

INDICATES SECTION LETTER

AutoCAD SHX Text

INDICATES DRAWING NUMBER WHERE LOCATED

AutoCAD SHX Text

CONC.

AutoCAD SHX Text

CONCRETE

AutoCAD SHX Text

CERAMIC TILE

AutoCAD SHX Text

CERA

AutoCAD SHX Text

DOOR TAG

AutoCAD SHX Text

WALL TAG

AutoCAD SHX Text X

AutoCAD SHX Text

RECEPTACLE

AutoCAD SHX Text 1'-6"

AutoCAD SHX Text 4'-0"

AutoCAD SHX Text 6'-0"

AutoCAD SHX Text 4'-0"

AutoCAD SHX Text 3'-6"

AutoCAD SHX Text 5'-0"

AutoCAD SHX Text 6'-0"

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

FASTEN AT BOTH ENDS WITH MIN. 4 TAPPING SCREWS.

AutoCAD SHX Text

CUT HORIZONTAL FASTENER FROM STUD

AutoCAD SHX Text

VERTICAL WALL STUDS AT 16" OR 24" O.C.

AutoCAD SHX Text

CONTRACTOR SHALL COORDINATE LOCATIONS OF HORIZONTAL FASTENERS.

AutoCAD SHX Text

TEL/ DATA

AutoCAD SHX Text

TWIST LOCK RECEPTACLE

AutoCAD SHX Text

FIRE EXTINGUISHER CABINET (FEC)

AutoCAD SHX Text

FIRE HOSE CABINET (FHC)

AutoCAD SHX Text

FEC SIGNAGE

AutoCAD SHX Text

DOOR ACTUATOR

AutoCAD SHX Text

LIGHTING SWITCHES

AutoCAD SHX Text

HUMIDISTAT

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text

ALARM PANEL

AutoCAD SHX Text

ELECTRIC PANEL (E.P.)

AutoCAD SHX Text 4'-0"

AutoCAD SHX Text 4'-0"

AutoCAD SHX Text 5'-10"

AutoCAD SHX Text

CLOTHES HOOK

AutoCAD SHX Text

CH

AutoCAD SHX Text

CH

AutoCAD SHX Text 4'-9"

AutoCAD SHX Text

NURSE CALL

AutoCAD SHX Text

NC

AutoCAD SHX Text

XXX

AutoCAD SHX Text X

AutoCAD SHX Text

WINDOW TAG

1. CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING ALL DIMENSIONS ON THESE PLANS AGAINST FIELD CONDITION PRIOR TO CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING ALL DIMENSIONS ON THESE PLANS AGAINST FIELD CONDITION PRIOR TO CONSTRUCTION AND REPORT ANY DISCREPANCIES TO THE ENGINEER. ALL DIMENSIONS AND LOCATIONS AS-INDICATED ON THE DRAWINGS SHALL BE CONSIDERED AS REASONABLY CORRECT BUT IT SHALL BE UNDERSTOOD THAT THEY ARE SUBJECT TO MODIFICATION AS MAY BE NECESSARY OR DESIRABLE AT THE TIME OF INSTALLATION TO MEET ANY UNFORESEEN OR OTHER CONDITION. 2. ALL WORK PERFORMED SHALL COMPLY WITH BUILDING AND ZONING ORDINANCE OF THE LOCAL AUTHORITY HAVING JURISDICTION, AND ALL WORK PERFORMED SHALL COMPLY WITH BUILDING AND ZONING ORDINANCE OF THE LOCAL AUTHORITY HAVING JURISDICTION, AND THE (IBC) BUILDING AND ENERGY CODES. 3. CONTRACTOR OR ANY SUBCONTRACTOR DOING ANY WORK UNDER THIS CONTRACT SHALL CARRY LIABILITY AND PROPERTY DAMAGE CONTRACTOR OR ANY SUBCONTRACTOR DOING ANY WORK UNDER THIS CONTRACT SHALL CARRY LIABILITY AND PROPERTY DAMAGE INSURANCE AGAINST ACCIDENTS OF ALL KINDS AND SHALL FURNISH OWNER WITH CERTIFICATES OF INSURANCE. 4. NEW WALL AND CEILING FINISHES SHALL HAVE A FLAME-SPREAD INDEX OF 26-75 (CLASS B) IN CORRIDORS AND EXIT ENCLOSURES, NEW WALL AND CEILING FINISHES SHALL HAVE A FLAME-SPREAD INDEX OF 26-75 (CLASS B) IN CORRIDORS AND EXIT ENCLOSURES, 76-200 (CLASS C) IN ROOMS AND ENCLOSED SPACES. 5. NEW FLOOR FINISHES SHALL NOT BE LESS THAN CLASS II, GREATER THAN OR EQUAL TO .22 WATTS/CM² (MIN. CRITICAL RADIANT NEW FLOOR FINISHES SHALL NOT BE LESS THAN CLASS II, GREATER THAN OR EQUAL TO .22 WATTS/CM² (MIN. CRITICAL RADIANT ² (MIN. CRITICAL RADIANT (MIN.