504-19-102 Drawings Upgrade Fire Systems and Doors.pdf

PDF 16 MB Posted

Attached to
Y1DA--504-19-102 - UPGRADE FIRE SYSTEMS AND DOORS (VA-22-00019557)
Solicitation number
36C25722B0015
Issued by

About this file

This document outlines a federal contract opportunity to upgrade fire systems and doors at a Department of Veterans Affairs medical center. The solicitation seeks a contractor to remove and replace designated smoke and fire doors, frames and hardware in five buildings as well as upgrading fire pumps, replacing a dry system clapper valve, optional additional fire and smoke doors, and replacing all exit signs with new LED signage. The work will be performed at the Thomas E. Creek VA Medical Center located in Amarillo, Texas. The solicitation number is 36C25722B0015 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The document provides details on the products and services required as well as the location of the work.

View the file

Other files

File Type Posted
Pre-Bid Sign In Sheet.pdf PDF
36C25722B0015 0001.docx DOCX document
Attachment OSHA - EMR Requirement.pdf PDF
36C25722B0015_1.docx DOCX document
Attachment SELF-PERFORMED CALCULATIONS.pdf PDF
504-19-102 SPECS Upgrade Fire Systems and Doors.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NUMBER:

ISSUE DATE:

EA #:

CLIENT #:

PROJECT DIRECTORY:

EA02.1001

UPGRADE FIRE SYSTEMS, SMOKE AND FIRE DOORS

6010 WEST AMARILLO BLVD. / AMARILLO, TEXAS 79106

U P

G R

A D

E F

IR

E

S Y

S T

E M

S

S M

O K

E A

N D

F

IR

E D

O O

R S

E A

.1

207 WEST MAIN STREET

MESQUITE, TX 75149

T. 214.607.0247

WWW.ENAPAYLLC.COM

504-19-102

1331 RIVER BEND DRIVE

DALLAS, TEXAS 75247

MR. FRED C. CRABTREE, JR., P.E.

T. 214.696.6291

6010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

MR. ANDREW J. WIECK

T. 806.673.8618

1255 CORPORATE DRIVE - SUITE 200

IRVING, TEXAS 75038

MR. MICHAEL BURCH

T. 469.242.4707

207 WEST MAIN STREET

MESQUITE, TX 75149

MR. ROGER L. STEPHENS, AIA

T. 214.505.0659

CAMPOS ENGINEERING

VA AMARILLOENAPAY, LLC

HILL INTERNATIONAL

1255 CORPORATE DRIVE - SUITE 100

IRVING, TEXAS 75038

MR. DANIEL LeCLAIR, P.E.

T. 972.887.5553

MOYE CONSULTING

A-000

- BUILDINGS 1, 4, 28, 29 AND 33

IFC DOCUMENTS

11-04-20

IF

C

D O

C U

M

EN

TS

11-04-20

DWG 1 OF 56

COMMENTS:

CALLOUT HEAD

DOOR TAG

? INTERIOR ELEVATION

ROOM TAG WITH

AREA

BUILDING SECTION

SPOT ELEVATION - TARGET

? WALL TAG

? WINDOW TAG

TEMP. CONSTRUCTION PARTITION

REVISION SYMBOL

REVISION NUMBER

CABINET / CEILING SECTION

EQUIPMENT TAG EQ.000

ROOM SIGNAGE TAG

X

A1/A001

KEYNOTE LEGEND

KEY VALUE KEYNOTE TEXT

00 00 00.A1 DESCRIPTIONSPECIFICATION SECTION KEYNOTE INFORMATION

ABBREVIATIONS AND ANNOTATIONS LEGEND

ROOM NAME

ROOM SF

01 PHOTO CALLOUT

N.I.C. NOT IN CONTRACT

EXISTING WALL TO REMAIN

NEW CONSTRUCTION PARTITION

EXISTING WALL - DEMOLISHED

PROJECT SCOPE

PROJECT DATA AND BUILDING

CODE INFORMATION

PROJECT DATA

PROJECT NAME:

PROJECT ADDRESS:

OWNER:

APPLICABLE CODES

BUILDING CODE:

ACCESSIBILITY CODE: 2010 STANDARDS FOR ACCESSIBLE

DESIGN (SAD)

201 INTERNATIONAL BUILDING CODE

EAB PROJECT NUMBER: N/A

UPGRADE FIRE SYSTEMS & DOORS

MECHANICAL CODE:

ELECTRICAL CODE:

PLUMBING CODE:

NFPA:

201 INTERNATIONAL MECHANICAL

CODE

201 NATIONAL ELECTRICAL CODE

(NFPA 70)

LIFE SAFETY INFORMATION

OCCUPANCY:

COMMENTS

TYPE OF

CONSTRUCTION: EXISTING NA

SPRINKLER SYSTEM: EXISTING NA

COMMENTSFIRE PROTECTION REQUIREMENTS

INT. BEARING WALLS: EXISTING

EXT.BEARING WALLS: EXISTING

EXISTING

EXISTING

INT. NONBEARING WALLS:

EXT. NONBEARING WALLS:

EXISTING

EXISTING

EXISTING

ROOF:

CEILING:

FLOOR:

STRUCTURAL BEAMS:

STRUCTURAL COLUMNS:

EXISTING

EXISTING

RATED SEPARATIONS: EXISTING

MEANS OF EGRESS

TOTAL OCCUPANT LOAD:

MAX. ALLOWED MAX. PROVIDED

X / 100

DIST. BETWEEN EXITS: 112'-0" EXISTING

X/2 IF SPRINKLED

EGRESS WIDTH / OCCUPANT MIN. ALLOWED PROVIDED

0.2" STAIRS:

0.15" DOORS:

EXISTING

EXISTING EXISTING

EXISTING

EXISTINGEXISTING

NA

COMMENTS

COMMENTS

COMMENTS

COMMENTS

COMMENTS

TRAVEL DISTANCE TO EXIT: 200'-0" EXISTING

6010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

DEPARTMENT OF VETERANS AFFAIRS

CUTTING AND PATCHING

GENERAL NOTES

THE CONTRACTOR SHALL REPLACE OR REPAIR ANY EXISTING-

TO-REMAIN MATERIALS AND FINISHES (CEILING GRID, CEILING

TILE, GYPSUM BOARD, DOORS, WINDOWS, FRAMES, WALL

PROTECTION, PAINT, ETC) WHICH ARE DAMAGED DURING

DEMOLITION OR CONSTRUCTION OR ANY OTHER WORK

PERFORMED UNDER THIS CONTRACT. THE CONTRACTOR

SHALL PATCH, REPAIR, AND ALIGN ALL EXISTING

CONSTRUCTION SO AS TO LEAVE NO EVIDENCE OF PATCHING

OR REPAIR AND PREPARE EXISTING SURFACE TO RECEIVE

NEW SCHEDULED FINISHES.

1.

2.

3.

4.

5.

6.

WHERE EXISTING EXTERIOR WALL OR INTERIOR PARTITIONS

ARE DAMAGED IN AREAS OF SELECTIVE DEMOLITION BY THE

REMOVAL OF EXISTING CONSTRUCTION OR ANY OTHER

DEMOLITION ACTION, THE CONTRACTOR SHALL REPAIR

EXISTING WALL SURFACES TO MATCH EXISTING OR PRODUCE

A SMOOTH SURFACE TO RECEIVE NEW FINISHES.

WHERE LEVEL CHANGES, HOLES, DEPRESSIONS, OR FORMED

TRENCHES ARE UNCOVERED IN EXISTING CONCRETE SLAB BY

THE REMOVAL OF EXISTING WALLS / EXISTING FLOORING OR

ANY OTHER DEMOLITION ACTION, THE CONTRACTOR SHALL

PATCH AND REPAIR EXISTING CONCRETE SURFACES WITH A

LATEX OR GYPROCETE LEVELING COMPOUND UNLESS

SPECIFIED OTHERWISE TO PRODUCE A SMOOTH LEVEL

SURFACE TO RECEIVE NEW FINISHES.

WHERE PIPES, CONDUITS, DUCTWORK, ETC. ARE TO BE

REMOVED FROM EXISTING RATED WALL / PARTITION TO

REMAIN, THE CONTRACTOR SHALL INFILL THE OPENING

PENETRATION WITH MATERIALS THAT MATCH THE EXISTING

CONSTRUCTION OR AN APPROVED MATERIAL TO MAINTAIN THE

EXISTING FIRE-RATED ASSEMBLY.

WHERE PIPES, CONDUITS, DUCTWORK, ETC. ARE TO BE

REMOVED FROM ANY FLOOR OR ROOF ASSEMBLY TO REMAIN

THE CONTRACTOR SHALL INFILL THE OPENING WITH

MATERIALS TO MAINTAIN DESIGNATED FIRE OR SMOKE RATING

AS INDICATED BELOW:

A: WHERE OPENINGS ARE ACCESSIBLE TO FOOT

TRAFFIC, OR EXPOSED TO VIEW, OR ARE GREATER

THAN 2" THE OPENING MUST BE FILLED WITH A

CONCRETE SYSTEM SIMILAR TO EXISTING.

B: AREAS NOT EXPOSED TO VIEW CONCEALED BY

CONSTRUCTION OR WHERE THE OPENING IS LESS

THAN 6" THE OPENING MUST BE FILLED WITH A UL

DESIGN SYSTEM AS SPECIFIED IN DIVISION 7 THROUGH

PENETRATION RESISTIVE MATERIAL"

IF ANY EXISTING FIREPROOFING AND/OR RATED ASSEMBLIES

TO REMAIN ARE DAMAGED DURING DEMOLITION, THEY SHALL

BE REPLACED OR REPAIRED TO CONFORM TO THE ORIGINAL

FIRE PROTECTION REQUIREMENTS. THE INTEGRITY OF

EXISTING RATED FLOOR, WALL, BARRIER, AND ROOF

ASSEMBLIES TO REMAIN SHALL BE MAINTAINED THROUGHOUT

ALL PHASES OF CONSTRUCTION, AS APPLICABLE, CONTACT

THE ARCHITECT TO VERIFY TESTED ASSEMBLIES TO BE USED

FOR REPAIRS.

3" =1

1/ 2"

'-0

1"

'-0

3/ 4"

'-0

1/ 2"

'-0

1/ 4"

'-0

1/ 8"

'-0

1/

'-0

If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.

A

1 2 3 4 5 6 7 8

B

C

D

E

F

A

B

C

D

E

F

OFFICE OF

FACILITIES

MANAGEMENT

PROJECT NUMBER:

BUILDING NUMBER:

VA DRAWING NUMBER:

PROJECT TITLE:

LOCATION:

DATE: CHECKED: DRAWN:

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR

PROJECT DIRECTORY:DESCRIPTION:

03/

8"

'-0

EA:CLIENT:

PR

O

JE

C

T N

U M

BE

R

1 2 3 4 5 6 7 8

A-001

INDEX AND GENERAL

INFORMATION 1 / 4 / 28 / 29 / 33

EA02.1001

U

PG

R

AD

E

SY

ST

EM

A N

D D

O O

R S

504-19-102

EA

.1

ARCHITECTURE

F5

INTERIOR PARTITION RATING LEGEND

F2

ABBREVIATIONS AND ANNOTATIONS LEGEND

F7

PROJECT SCOPE

E7

PROJECT DATA AND CODE INFO

D2

GENERAL PROJECT NOTES

D4

CONTRACTOR RESPONSIBILITIES

E6

DEMOLITION GENERAL NOTES

F4

CUTTING AND PATCHING GENERAL NOTES

F6

ADD ALTERNATES

REVISION SCHEDULE

No. DESCRIPTION DATE

FIRE PROTECTION

FA-001 GENERAL NOTES AND LEGEND

FA-B1-1 FIRE ALARM BUILDING 1 - FIRST FLOOR PLAN

FA-B1-2 FIRE ALARM BUILDING 1 - SECOND FLOOR PLAN

FA-B1-3 FIRE ALARM BUILDING 1 - THIRD FLOOR PLAN

FA-B1-4 FIRE ALARM BUILDING 1 - FOURTH FLOOR PLAN

FA-B4-1 FIRE ALARM BUILDING 4 - FIRST & SECOND FLOORS

FA-B28-1 FIRE ALARM BUILDING 28 - FIRST FLOOR PLAN

FA-B28-2 FIRE ALARM BUILDING 28 - SECOND FLOOR PLAN

FA-B28-3 FIRE ALARM BUILDING 28 - THIRD FLOOR PLAN

FA-B28-4 FIRE ALARM BUILDING 28 - FOURTH FLOOR PLAN

FA-B29-1 FIRE ALARM BUILDING 29 - BASEMENT FLOOR PLAN

FA-B29-2 FIRE ALARM BUILDING 29 - FIRST FLOOR PLAN

FA-B29-3 FIRE ALARM BUILDING 29 - SECOND FLOOR PLAN

FA-B33-1 FIRE ALARM BUILDING 33 - FIRST FLOOR PLAN

FA-DET-1 FIRE ALARM DETAILS

FP-001 FIRE PROTECTION GENERAL NOTES AND LEGEND

FP-401 FIRE PROTECTION BUILDING 1 - FIRE PUMP ROOM

FP-402 FIRE PROTECTION BUILDING 28 - FIRE PUMP ROOM

FP-501 FIRE PROTECTION DETAILS

FP-B1-1 FIRE PROTECTION BUILDING 1 - FIRST FLOOR PLAN

FP-B28- FIRE PROTECTION BUILDING 28 -

UPGRADE FIRE

SYSTEMS, SMOKE AND

FIRE DOORS

6010 WEST AMARILLO BLVD. / AMARILLO, TEXAS

79106

D E

S

IG

N D

E V

E

LO

P M

E N

T R

E V

IE

W

A-000 COVER SHEET

A-001 INDEX AND GENERAL INFORMATION

A B1-1 BUILDING 1 - FIRST FLOOR PLAN

A B1-2 BUILDING 1 - SECOND FLOOR PLAN

A B1-3 BUILDING 1 - THIRD FLOOR PLAN

A B1-4 BUILDING 1 - FOURTH FLOOR PLAN

A B1-5 BUILDING 1 - FIFTH FLOOR PLAN

A B4-1 & 2 BUILDING 4 - FIRST & SECOND FLOOR PLANS

A B28-1 BUILDING 28 - FIRST FLOOR PLAN

A B28-2 BUILDING 28 - SECOND FLOOR PLAN

A B28-3 BUILDING 28 - THIRD FLOOR PLAN

A B28-4 BUILDING 28 - FOURTH FLOOR PLAN

A B29-B BUILDING 29 - BASEMENT

A B29-1 BUILDING 29 - FIRST FLOOR PLAN

A B29-2 BUILDING 29 - SECOND FLOOR PLAN

A B33-1 BUILDING 33 - FIRST FLOOR PLAN

A-841 DOOR TYPES / FRAME TYPES / DETAILS

E B1-2 ELECTRICAL POWER PLAN BUILDING 1 - SECOND FLOOR

PLAN

E B1-3 ELECTRICAL POWER PLAN BUILDING 1 - THIRD FLOOR

PLAN

E B1-4 ELECTRICAL POWER PLAN BUILDING 1 - FOURTH FLOOR

PLAN

E B1-5 ELECTRICAL POWER PLAN BUILDING 1 - FIFTH FLOOR

PLAN

E B4-1 & 2 ELECTRICAL POWER PLAN BUILDING 4 - FIRST &

SECOND FLOOR PLANS

E B28-1 ELECTRICAL POWER PLAN BUILDING 28 - FIRST FLOOR

PLAN

E B28-2 ELECTRICAL POWER PLAN BUILDING 28 - SECOND

FLOOR

E B28-3 ELECTRICAL POWER PLAN BUILDING 28 - THIRD FLOOR

PLAN

E B28-4 ELECTRICAL POWER PLAN BUILDING 28 - FOURTH

FLOOR PLAN

E B29-1 ELECTRICAL POWER PLAN BUILDING 29 - FIRST FLOOR

PLAN

E B29-2 ELECTRICAL POWER PLAN BUILDING 29 - SECOND

FLOOR PLAN

E B29-B ELECTRICAL POWER PLAN BUILDING 29 - BASEMENT

E B33-1 ELECTRICAL POWER PLAN BUILDING 33 - FIRST FLOOR

PLAN

0 BSMNT. FLOOR PLAN

GRAPHIC REPRESENTATION: THE CONSTRUCTION DRAWINGS

ARE A GRAPHIC REPRESENTATION OF THE SCOPE, LOCATION,

AND ARRANGEMENT OF MATERIALS AND EQUIPMENT SHOWING

THE EXECUTION OF THE WORK. THE INTENT OF THE

SPECIFICATIONS IS TO OUTLINE AND/OR FURTHER INDICATE THE

TYPES AND QUALITIES OF THE MATERIALS AND WORKMANSHIP.

SHOULD THE SPECIFICATIONS AND CONSTRUCTIONS DRAWINGS

DISAGREE IN THEMSELVES OR WITH EACH OTHER, WRITTEN

CLARIFICATIONS IN THE FORM OF A REQUEST FOR INFORMATION

(RFI) SHALL BE ISSUED TO THE ARCHITECT BY THE GENERAL

CONTRACTOR. IN ABSENSE OF THE RFI, THE GENERAL

CONTRACTOR'S PROPOSAL SHALL BE BASED UPON THE MOST

EXPENSIVE COMBINATION OF QUALITY AND QUANTITY OF WORK

INDICATED.

CONFLICTS: IN CASES OF CONFLICTS, INCONSISTENCIES OR

DISCREPANCIES WITHIN THE CONSTRUCTION DRAWINGS AND

SPECIFICATIONS, THE GENERAL CONTRACTOR SHALL PROVIDE

THE BETTER QUALITY AND GREATER QUANTITY OF WORK AS

DETERMINED AND DIRECTED BY THE COR.

1.

2.

GENERAL PROJECT NOTES

3.

4.

5.

6.

8.

7.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

28.

27.

26.

24.

23.

22.

21.

20.

19.

ERRORS / OMISSIONS IN THE SCHEDULES: SUCH AS THE

ROOM FINISH SCHEDULE, DOOR SCHEDULE AND EQUIPMENT

SCHEDULE SHALL NOT RELIEVE THE GENERAL CONTRACTOR

FROM THE PERFORMANCE OF THE WORK AS SHOWN IN THE

CONSTRUCTION DRAWINGS OR SPECIFICATIONS.

ASBESTOS: THE GENERAL CONTRACTOR IS RESPONSIBLE FOR

ASBESTOS ABATEMENT IF IT IS DETERMINED THAT REMOVING

DOOR FRAMES WILL DISTRUB FLOORING CONTAINING ASBESTOS.

EQUIPMENT VERIFICATION: THE GENERAL CONTRACTOR

SHALL BE RESPONSIBLE FOR THE VERIFICATION OF THE SIZE

AND LOCATION OF ALL OPENINGS FOR THE MECHANICAL /

ELECTRICAL / PLUMBING WORK AND EQUIPMENT AND SHALL

COORDINATE WITH ALL SUB-CONTRACTORS INVOLVED.

SIGNAGE: NOT INCLUDED IN THE PROJECT SCOPE FOR THE

GENERAL CONTRACTOR.

REQUIRED UTILITIES: THE GENERAL CONTRACTOR IS TO

PROVIDE THE NECESSARY UTILITIES AS SHOWN ON THE FIRE

PROTECTION AND MEP DRAWINGS.

SERVICE TO UTILITIES: THE GENERAL CONTRACTOR SHALL

MAINTAIN SERVICE TO EQUIPMENT UTILITIES AND PROTECT

AGAINST DAMAGE TO SUCH DURING CONSTRUCTION AND SHALL

NOT INTERRUPT EXISTING UTILITIES SERVING OCCUPIED /

OPERATING FACILITIES EXCEPT WHEN AUTHORIZED IN WRITING

BY THE COR. ALL SHUTDOWNS WILL REQUIRE THAT THE COR BE

NOTIFIED TWO (2) WEEKS PRIOR TO THE SHUTDOWN AND WILL

HAVE TO BE APPROVED BY THE FACILITY.

BYPASS CONNECTIONS: WHERE UTILITY SERVICES ARE

REQUIRED TO BE REMOVED, RELOCATED OR MODIFIED,

PROVIDE BYPASS CONNECTIONS TO MAINTAIN CONTINUITY OF

SERVICE BEFORE PROCEEDING WITH THE WORK.

COORDINATE WITH THE OWNER PROJECT MANAGER.

NOT ALLOWED: NO GASOLINE POWERED TOOLS OR POWER

ACTUATED FASTENING DEVICES SHALL BE ALLOWED INSIDE THE

FACILITY.

EGRESS: THE GENERAL CONTRACTOR SHALL MAINTAIN

EXISTING EXITS SERVING THE PROJECT AREA THROUGHOUT

CONSTRUCTION.

STANDARD REFERENCED DESIGN SHEETS: THE FOLLOWING

SHEETS CONTAIN STANDARD ARCHITECTURAL DESIGN

INFORMATION: A-870.

DOOR OPENINGS: DOORWAYS BETWEEN BUILDING - ALL LEVELS

- SHALL BE DEMARCATED / LABELED WITH THE BUILDING NUMBER

BEING ENTERED FROM BOTH DIRECTIONS.

ABBREVIATIONS: REFERENCED FROM THE U.S. NATIONAL

CAD STANDARD VERSION 6.0.

BLOCKING: THE GENERAL CONTRACTOR IS RESPONSIBLE FOR

PROVIDING FIRE TREATED WOOD BLOCKING IN THE WALLS FOR

ALL WALL MOUNTED FIXTURES AND EQUIPMENT.

CONSTRUCTION: CONSTRUCTION SHALL COMPLY WITH THE

APPLICABLE CURRENTLY RECOGNIZED INTERNATIONAL

BUILDING CODES.

DESIGN STANDARDS: EACH BUILDING OR PORTION

THEREOF SHALL BE DESIGNED AND CONSTRUCTED TO

SUSTAIN ALL LIVE AND DEAD LOADS, INCLUDING SEISMIC

AND OTHER ENVIRONMENTAL FORCES IN ACCORDANCE

WITH ACCEPTED ENGINEERING PRACTICES AND

STANDARDS AS PRESCRIBED BY THE LOCAL JURISDICTION

OR BY THE MOST CURRENT MODEL BUILDING CODES.

DIMENSIONS: ARE TYPICALLY SHOWN FROM A COLUMN

CENTER LINE TO THE FINISH FACE OF A WALL OR FROM THE

FINISH FACE OF A WALL TO THE FINISH FACE OF WALL.

DO NOT SCALE THE DRAWINGS: USE FIGURED DIMENSIONS ONLY.

ENLARGED PLANS: WHERE ENLARGED OR PARTIAL PLANS ARE

REFERENCED, DIMENSIONS AND SPECIAL DETAILING OR FINISH

REQUIREMENTS ARE NOTED ON THE ENLARGED PLANS AND

ARE USUALLY OMITTED FROM THE SMALLER SCALE PLANS.

EXISTING CONDITIONS: ONLY THE AREAS DESCRIBED IN

F7/A-001 PROJECT SCOPE HAVE BEEN FIELD-VERIFIED. THIS

MEANS THAT THE EXISTING PARTITION WALLS HAVE BEEN

PARTIALLY LOCATED, MOST OF THE VISIBLE MECHANICAL,

ELECTRICAL AND PLUMBING ITEMS HAVE BEEN LOCATED, AND

MOST OF THE VISIBLE ARCHITECTURAL ELEMENTS LOCATED.

AREAS THAT ARE CONCEALED OR NOT ACCESSIBLE HAVE NOT

BEEN FIELD VERIFIED.

FIELD VERIFY: THE GENERAL CONTRACTOR IS TO FIELD VERIFY

ALL DIMENSIONS AND CONDITIONS BEFORE PROCEEDING WITH

THE SCHEDULED WORK AS WELL AS COORDINATING THE

EXISTING CONDITIONS WITH THE SCHEDULED WORK. WHEN THE

GENERAL CONTRACTOR IDENTIFIES A POTENTIAL LOCATION

PROBLEM WITH HVAC, PLUMBING, ELECTRICAL, OR SPRINKLER

SYSTEMS HE IS TO NOTIFY THE COR BEFORE PROCEEDING WITH

THE SCHEDULED WORK.

FIRE ALARM: ALL HEALTHCARE OCCUPANCIES SHALL BE

PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH

NFPA 72 AND NFPA 101.

INTERIOR FINISHES: INTERIOR FINISH MATERIALS SHALL

COMPLY WITH THE FLAME SPREAD AND SMOKE

PRODUCTION LIMITATIONS AS INDICATED IN NFPA 101.

LIFE SAFETY SYSTEMS: ALL SYSTEMS ARE TO REMAIN FULLY

OPERATIONAL OVER THE COURSE OF THE CONSTRUCTION

PROJECT. ALL FIRE SPRINKLERS IN LOCATIONS WITH THE

CEILING BEING REMOVED ARE TO BE TURNED UP DURING

CONSTRUCTION. ALL FIRE SPRINKLERS ARE TO BE RETURNED

TO NORMAL FUNCTION AND ORIENTATION ONCE CONSTRUCTION

IS COMPLETE.

EXISTING FIRE ALARM DEVICES: INCLUDING BUT NOT LIMITED

TO, SMOKE AND HEAT DETECTORS, MANUAL PULL STATIONS,

SPEAKERS, AND STROBES ARE TO BE SECURED OR REMOVED

PRIOR TO DEMOLITION OF A WALL OR CEILING CONTAINING A

FIRE ALARM DEVICE. IF THE DEVICES ARE LEFT IN PLACE

DURING DEMOLITION, THEY SHALL BE SECURED TO PROTECT

AGAINST PHYSICAL DAMAGE AND/OR CONTAMINATION. IN

ADDITION, DEVICES LEFT IN PLACE SHALL NEVER BE

SUPPORTED BY THEIR CONDUCTORS AT ANY TIME. IF THE

DEVICES ARE TO BE REMOVED, THEY SHALL BE REMOVED BY A

STATE LICENSED FIRE ALARM TECHNICIAN.

DESIGN AND INSTALLATION OF FIRE PROTECTION AND LIFE

SAFETY EQUIPMENT: ALL WORK SHALL BE PERFORMED BY A

LICENSED FIRE PROTECTION ENGINEER OR A TEXAS STATE

FIRE MARSHALL'S OFFICE LICENSED CONTRACTOR AS

FOLLOWS:

FIRE ALARM DESIGN - "FIRE ALARM PLANNING

SUPERINTENDENT" (APS) LICENSE / FIRE ALARM INSTALLATION

AND SERVICE - "FIRE ALARM TECHNICIAN" (FAL) LICENSE / FIRE

SPRINKLER SYSTEM DESIGN - "RESPONSIBLE MANAGING

EMPLOYEE (RME) LICENSE.

FIRE PROTECTION AND LIFE SAFETY EQUIPMENT: INCLUDING

FIRE ALARM DEVICES, FIRE SPRINKLERS, FIRE EXTINGUISHERS,

EMERGENCY LIGHTING, AND EXIT SIGNS SHALL BE INSTALLED

IN ACCORDANCE WITH THE REQUIREMENTS OF THE

FOLLOWING: NFPA 10 STANDARD FOR PORTABLE FIRE

EXTINGUISHERS / NFPA 13 STANDARD FOR THE INSTALLATION

OF SPRINKLER SYSTEMS / NFPA 72 NATIONAL FIRE ALARM

CODE / NFPA 101 LIFE SAFETY CODE.

G. C. RESPONSIBILITIES TO

EXISTING CONDITIONS

1.

2.

3.

4.

5.

6.

8.

7.

9.

10.

THE CONTRACTOR SHALL PERFORM A SITE VISIT. IN DOING

SO THE CONTRACTOR HAS AGREED THAT THEY HAVE

INVESTIGATED THE EXISTING CONDITIONS TO BE

RENOVATED AND COMPARE THEM TO THE WORK TO BE

PERFORMED ACCORDING TO THE CONTRACT DOCUMENTS.

INFORMATION CONTAINED ON THESE DRAWINGS WITH

REGARD TO EXISTING CONDITIONS OF CONSTRUCTION IS

PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR IN

EXECUTING THE NEW WORK. REASONABLE ATTEMPTS HAVE

BEEN MADE TO PROVIDE COMPLETE AND ACCURATE

REPRESENTATION OF SUCH EXISTING CONDITIONS. THIS

INTERPRETATION HAS BEEN DERIVED FROM DRAWINGS

SUPPLIED BY THE COR AND HAS BEEN FURTHER

SUPPLEMENTED WITH FIELD-MEASUREMENTS AND

OBSERVATIONS BU THE A/E TEAM. THE INFORMATION

CONTAINED IN THESE DRAWINGS, WITH REGARD TO THE

EXISTING CONDITIONS OF CONSTRUCTION IN NO WAY

RELEASES THE CONTRACTOR FROM THE RESPONSIBILITY

OF VERIFYING COMPLETELY ALL FIELD CONDITIONS

RELATING TO THE EXECUTION OF THE WORK, AS

DESCRIBED IN THE CONTRACT DOCUMENTS.

NO GUARANTEE IS MADE AS TO THE GENERAL CONDITIONS

OF THE EXISTING BUILDING, THE CONTRACTOR SHALL FIELD

VERIFY AND DOCUMENT ALL EXISTING DIMENSIONS,

ELEVATIONS, BENCHMARKS, MATERIALS, UTILITIES AND

CONSTRUCTION TYPE THAT MAY AFFECT OR BE EFFECTED

BY NEW WORK AND SHALL COORDINATE SUCH FIELD

VERIFICATION WITH THE CONTRACT DOCUMENTS AND THE

EXECUTION OF THE WORK. THE CONTRACTOR SHALL NOTE

ANY DISCREPANCIES AND/OR CONFLICTS INVOLVING

EXISTING CONDITIONS AND BRING THEM TO THE ATTENTION

OF THE COR AND ARCHITECT IMMEDIATELY.

THE CONTRACTOR SHALL FIELD-VERIFY THE EXISTING

CONDITIONS AS THEY RELATE TO SPECIFIC PORTIONS OF

THE WORK. VERIFICATION SHALL BE UNDERTAKEN IN

ADVANCE TO ALLOW FOR THE TIMELY IDENTIFICATION OF

EXISTING CONDITIONS THAT MAY AFFECT THE SCHEDULED

INSTALLATION OF NEW WORK AS DESIGNED AND DETAILED,

AND TO AVOID UNIQUE AND UNREASONABLE DELAYS TO THE

PROJECT SHOULD SUCH CONDITIONS BE DISCOVERED.

TIMELY IDENTIFICATION OF SUCH CONDITIONS SHALL

PROVIDE FOR A MINIMUM PERIOD OF FIVE (5) CALENDAR

DAYS ASPER THE STATEMENT OF WORK.

THE CONTRACTOR SHALL FIELD VERIFY THE LOCATION AND

EXTENT OF THE LIFE SAFETY SYSTEM (INCLUDING BUT NOT

LIMITED TO SPRINKLER SYSTEMS, SMOKE DETECTION

SYSTEMS, EMERGENCY LIGHTING SYSTEMS) AS THEY MAY BE

AFFECTED BY THE NEW WORK. THE CONTRACTOR IS

RESPONSIBLE FOR ACCOMMODATING THESE SYSTEMS WHEN

AFFECTED BY NEW WORK SO THAT ALL APPLICABLE CODES

REQUIREMENTS ARE SATISFIED.

THE AREAS ADJACENT TO THE PROJECT ARE CURRENTLY

OCCUPIED, AND MUST REMAIN COMPLETELY OPERATIONAL

DURING THEIR BUSINESS HOURS THE CONTRACTOR SHALL

COORDINATE WITH THE COR ANY CONSTRUCTION ACTIVITIES

WHICH MAY IMPEDE THEIR NORMAL OPERATIONS, INCLUDING

ANY ACTIVITY WHICH CREATES EXCESSIVE NOISE, VIBRATION,

DUST AND NOTIFY ANY OCCUPANTS OF THE BUILDING OF ANY

CONSTRUCTION ACTIVITIES WHICH MAY AFFECT THEIR

ABILITY TO OPERATE NORMALLY.

THE CONTRACTOR SHALL TAKE ALL NECESSARY

PRECAUTIONS TO PREVENT DAMAGE TO AREAS ADJACENT

TO NEW CONSTRUCTION OR OCCUPIED AREAS WHERE

VARIOUS SYSTEMS CONNECTIONS OR EXTENSIONS ARE

REQUIRED AND SHALL BE RESPONSIBLE FOR DAMAGE

CAUSED BY CONSTRUCTION ACTIVITIES.

THE CONTRACTOR SHALL IDENTIFY POINTS OF ACCESS TO

THE BUILDING AND VERIFY MINIMUM CLEARANCES AVAILABLE

FOR USE IN TRANSPORTING NECESSARY CONSTRUCTION

MACHINERY, EQUIPMENT, MATERIALS, AND COMPONENTS

INTO THE BUILDING. USE OF SUCH POINTS OF ACCESS

SHALL BE APPROVED BY THE COR.

THE CONTRACTOR SHALL IDENTIFY EXISTING COMPONENTS

AND ASSEMBLIES WITHIN THE BUILDING THAT ARE

CONSTRUCTED AS FIRE-RATED ASSEMBLIES; SHALL NOTE

ANY DISCREPANCIES AND/OR CONFLICTS INVOLVING

EXISTING CONDITIONS AND BRING THEM TO THE ATTENTION

OF THE COR AND ARCHITECT IMMEDIATELY.

THE CONTRACT LIMIT OF WORK SHOWN ON DRAWINGS IS

PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR.

ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY THE

COR. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING

PROPER INTERFACE BETWEEN EXISTING AND NEW WORK.

DEMOLITION GENERAL NOTES

1.

2.

3.

4.

5.

6.

8.

7.

9.

10.

11.

12.

13.

14.

15.

16.

17.

THE "LIMITS OF CONSTRUCTION" LINES SHOWN ON THE

ARCHITECT'S DEMOLITION PLANS APPLY ONLY TO THE LIMITS

OF THE ARCHITECTURAL DEMOLITION. SEE THE OTHER

DISCIPLINES' DRAWINGS FOR THE LIMITS OF DEMOLITION FOR

THEIR DISCIPLINE.

THE DEMOLITION DRAWINGS HAVE BEEN DEVELOPED FROM

EXISTING DRAWINGS WHICH WERE PROVIDED TO THE

ARCHITECT/ENGINEER BY COR AND THEY MAY NOT REFLECT

ACTUAL FIELD CONDITIONS. PRIOR TO PROCEEDING WITH ANY

WORK, THE CONTRACTOR SHALL VERIFY THE ACCURACY OF

THESE DRAWINGS IN COMPARISON TO EXISTING FIELD

CONDITIONS AND THEN IMMEDIATELY NOTIFY THE COR AND

ARCHITECT OF ANY INCONSISTENCIES BETWEEN THESE

DRAWINGS AND ACTUAL CONDITIONS.

DEMOLITION IS INTENDED TO PREPARE THE BUILDING TO

RECEIVE THE NEW WORK. THE INFORMATION PROVIDED IN NO

WAY INTENDS TO MEAN THAT DEMOLITION IS LIMITED ONLY TO

THOSE ITEMS SPECIFICALLY IDENTIFIED. THE CONTRACTOR

SHALL REMOVE ALL EXISTING ITEMS OF CONSTRUCTION AND

EQUIPMENT WITHIN THE PROJECT AREA INDICATED ON THE

DEMOLITION PLAN, INCLUDING, BUT NOT LIMITED TO FLOOR

MATERIAL, BASE, WALLS, CEILINGS, DOORS, DOOR FRAMES,

WINDOWS, WINDOW FRAMES, CASEWORK, ATTACHMENTS,

ELECTRICAL, MECHANICAL, PLUMBING FIXTURES AND SYSTEM,

AS REQUIRED TO ALLOW FOR THE EXECUTION OF NEW WORK.

AFTER DEMOLITION WORK IS COMPLETE, REPAIR ALL HOLES

IN EXISTING-TO-REMAIN FLOORS, WALLS, FIRE BARRIERS,

AND ROOFS TO COMPLY WITH ORIGINAL FIRE/SMOKE/SOUND

ASSEMBLIES, FIRE PROTECTION REQUIREMENTS, AND

STRUCTURAL INTEGRITY.

VA SHALL REMOVE ALL NON-BUILT-IN EXISTING MEDICAL

EQUIPMENT STORAGE UNITS AND FURNITURE. THE

CONTRACTOR SHALL REMOVE SUPPORTS, TRACKS, BUILT-IN

ITEMS (STORAGE CABINETS, CASEWORK, ETC.), ALONG WITH

THE NORMAL DEMOLITION WORK. THE CONTRACTOR SHALL

REMOVE / PROTECT AND TURN OVER TO THE VA FOR STORAGE

ANY ANCILLARY PIECES SUCH AS (BUT NOT LIMITED TO)

MOUNTING BRACKETS, HARDWARE, MISC. SUPPORT ITEMS,

ETC. REQUIRED FOR THE REINSTALLATION OF EQUIPMENT.

THE CONTRACTOR SHALL REMOVE ALL ITEMS TO BE

DEMOLISHED IN THEIR ENTIRETY INCLUDING ALL

ASSOCIATED PIPING, WIRING, HANGERS, SUPPORTS,

PROJECTIONS, BOLTS, NAILS, ETC. FROM EXISTING

SURFACES, AND PATCH ALL HOLES TO MATCH ADJACENT

SURFACES OR PROVIDE NEW SCHEDULED FINISHES.

THE CONTRACTOR SHALL NOTIFY THE COR AND ARCHITECT

IMMEDIATELY IF ANY DEMOLITION OR NEW CONSTRUCTION

WORK CANNOT BE PERFORMED DUE TO EXISTING FIELD

CONDITIONS.

N.I.C.

WHERE NEW FLOORING IS INDICATED, THE CONTRACTOR

SHALL REMOVE ALL EXISTING FLOOR FINISHES AND ADHESIVE

DOWN TO THE CONCRETE SLAB, AND LEAVE FLOOR SMOOTH

FOR NEW FINISH. THE CONTRACTOR SHALL OBSERVE

MANUFACTURERS REQUIREMENTS FOR SUB-FLOOR

PREPARATION.

THE CONTRACTOR SHALL REMOVE EXISTING FINISHES,

INCLUDING CERAMIC TILE, VINYL WALL COVERING, WALL

PROTECTION, WALL BASE ETC. AT ALL EXISTING WALLS TO

RECEIVE NEW FINISHES, UNLESS NOTED OTHERWISE, AND

LEAVE WALL SURFACE SMOOTH TO RECEIVE NEW FINISHES.

THE CONTRACTOR SHALL REMOVE ALL EXISTING CEILINGS

TO ALLOW FOR PROPER INSTALLATION OF MECHANICAL,

PLUMBING AND ELECTRICAL WORK, AND PATCH AND

REPAIR EXISTING CEILINGS TO MATCH EXISTING.

WHERE NEW CEILINGS ARE INDICATED, THE CONTRACTOR

SHALL REMOVE ALL EXISTING CEILINGS TO ALLOW FOR

PROPER INSTALLATION OF NEW CEILINGS.

THE CONTRACTOR SHALL REFER TO CIVIL, MECHANICAL,

PLUMBING, FIRE PROTECTION, COMMUNICATIONS, SECURITY

SYSTEMS, AND ELECTRICAL DOCUMENTS FOR REQUIRED

DEMOLITION WORK AS WELL AS EXISTING PIPING, CONDUITS,

DUCTWORK, UTILITIES, ETC. TO REMAIN WITHIN AREAS OF

DEMOLITION

THE CONTRACTOR SHALL COORDINATE DEMOLITION WORK

WITH PHASING PLANS TO DETERMINE THE SCOPE OF WORK

TO BE PERFORMED IN EACH PHASE AND TO CAREFULLY

INTEGRATE WITH EXISTING CONSTRUCTION TO REMAIN FOR

EACH PHASE AND UPON COMPLETION OF FINAL PHASE

WITH MINIMAL DISRUPTION OF BUILDING OPERATIONS.

THE CONTRACTOR SHALL REFER TO MECHANICAL,

PLUMBING FIRE PROTECTION, ELECTRICAL,

COMMUNICATIONS, AND SECURITY DRAWINGS FOR EXTENT

AND LOCATION OF THE CHANNELING OF EXISTING FLOORS.

IF EXISTING PIPING OR CONDUIT OTHER THAN THE DESIRED

CONNECTION IS ENCOUNTERED WHILE CHANNELING, THE

CONTRACTOR SHALL NOTIFY THE COR AND ARCHITECT

IMMEDIATELY PRIOR TO CONTINUING WITH ANY WORK.

N.I.C.

THE CONTRACTOR SHALL BRACE ALL EXISTING STRUCTURES

AND STRUCTURAL ELEMENTS AS NECESSARY DURING

DEMOLITION. THE CONTRACTOR SHALL ENGAGE A

STRUCTURAL ENGINEER TO DETERMINE REQUIREMENTS.

N/A

N/A

HEALTH CARE

AND

BUSINESS

REF. TO VA'S LIFE SAFETY PLANS

REF. TO VA'S LIFE SAFETY PLANS

REF. TO VA'S LIFE SAFETY PLANS

REF. TO VA'S LIFE SAFETY PLANS

REF. TO VA'S LIFE SAFETY PLANS

IF

C

D O

C U

M

EN

TS

11-04-20

11-04-20 MDM RLS

BASE BID / ADD

ALTERNATES

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

INTERIOR PARTITION RATING

01 - EXISTING MASONRY CONSTRUCTION WITH 5/8" FIRE

RATED GYP. BOARD AND / OR TILE AND PLASTER.

02 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

03 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

COMMENTS:

COMMENTS:

COMMENTS TO THE PARTITION LEGEND

N/A

13 - STANDARD FOR THE

INSTALLATION OF SPRINKLER

SYSTEMS, 2016 ED.

20 - STANDARD FOR THE

INSTALLATION OF STATIONARY

PUMPS FOR FIRE PROTECTION, 2016

ED.

72 - NATIONAL FIRE ALARM AND

SIGNALING CODE, 2016 ED.

207 WEST MAIN STREET

MESQUITE, TX 75149

T. 214.607.0247

WWW.ENAPAYLLC.COM

6010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

MR. ANDREW J. WIECK

T. 806.673.8618

1331 RIVER BEND DRIVE

DALLAS, TEXAS 75247

MR. FRED C. CRABTREE, JR., P.E.

T. 214.696.6291

1255 CORPORATE DRIVE - SUITE 100

IRVING, TEXAS 75038

MR. DANIEL LeCLAIR, P.E.

T. 972.887.5553

1255 CORPORATE DRIVE - SUITE 200

IRVING, TEXAS 75038

MR. MICHAEL BURCH

T. 469.242.4707

207 WEST MAIN STREET

MESQUITE, TX 75149

MR. ROGER L. STEPHENS, AIA

T. 214.505.0659

CAMPOS ENGINEERING

MOYE CONSULTINGENAPAY, LLC

HILL INTERNATIONAL

VA AMARILLO

29. FOR DOOR TYPES / FRAME TYPES AND DETAILS REFER TO

SHEET A-841.

AUTOMATIC DOOR EQ. 156.10

SWING DOOR OPERATORS A156.10

BHMA:

ASTM: E119/UL; 263 TEST STANDARDS

N/A

SIGNALING CODE, 2016 ED.

101- LIFE SAFETY CODE, 2012 ED.

80 - STANDARD FOR FIRE DOORS

AND OTHER OPENING PROTECTIVES

THIS PROJECT WILL REMOVE AND REPLACE THE

DESIGNATED SMOKE / FIRE DOORS, FRAMES AND

HARDWARE IN BUILDINGS 1,4,28,29, AND 33. THE REPLACED

DOOR SYSTEMS SHALL BE CODE COMPLIANT. THE PROJECT

WILL ALSO INCLUDE UPGRADING FIRE PUMPS TO CURRENT

STANDARDS AND REPLACING THE DRY SYSTEM CLAPPER

VALVE. REPLACES ADDITIONAL FIRE & SMOKE DOORS. IN

ADDITION, ALL EXIT SIGNAGE WILL BE REMOVED AND

REPLACED WITH LED EXIT SIGNAGE.

ALL EXISTING FLOOR, BASE, WALL AND CEILING FINISHES

THAT ARE DAMAGED DURING THE DOOR REPLACEMENT

SHALL BE REPLACED AND MATCH THE DAMAGED FINISHES.

THE PROJECT WILL BE PHASED AS FOLLOWS:

BUILDING 1 - BY FLOOR, COMPARTMENT THEN BY DOOR #

BUILDING 4 - BY FLOOR, COMPARTMENT THEN BY DOOR #

BUILDING 28 - BY FLOOR, COMPARTMENT THEN BY DOOR #

BUILDING 29 - BY FLOOR, COMPARTMENT THEN BY DOOR #

BUILDING 33 - BY FLOOR, COMPARTMENT THEN BY DOOR #

DOORS MARKED AS "PRIORITY" WILL BE COMPLETED

IN THE ORDER PER BUILDING AS SHOWN.

A-600 OPENING SCHEDULE AND FIELD INSPECTION

A-870 ACCESSIBILITY STANDARDS

ELECTRICAL

E 0.01 ELECTRICAL LEGENDS AND GENERAL NOTES

E B1-1 BUILDING 1 - FIRST FLOOR DOOR LOCATION PLAN

1 VA CLARIFICATIONS FROM IFC REVIEW 2/11/2021

Base Bid and Add Alternates will be prioritized as follows:

ITEM A: FIRE DOORS - BASE BID / REPLACE METAL DOORS / FRAME /

HARDWARE AND PRIME / PAINT TO MATCH ADJACENT DOORS / FRAMES.

ITEM B: SMOKE DOORS - BASE BID / REPLACE METAL DOORS / FRAMES /

HARDWARE AND PRIME / PAINT TO MATCH ADJACENT DOORS / FRAMES.

ITEM C: FIRE PUMPS - ADD ALTERNATE #01

ITEM D: DRY SYSTEM CLAPPER VALVE - ADD ALTERNATE # 02

ITEM E: OPTIONAL FIRE & SMOKE DOORS - ADD ALTERNATE # 03

ITEM F: EXIT SIGNAGE - ADD ALTERNATE # 04

ITEM G: OPTIONAL FIRE & SMOKE DOORS - ADD ALTERNATE # 05

NOTE: THE GENERAL CONTRACTOR'S BID SHALL BE SUBMITTED IN SUCH A

WAY THAT ALLOWS THE VA TO SEE EACH OF THE SIX LINE ITEMS

A-F AS INDIVIDUAL CONSTRUCTION COST ESTIMATES WITHIN THE

OVERALL CONSTRUCTION COST ESTIMATE.

C

P

PROJECT AREA PROJECT AREA

PROJECT AREA

PROJECT AREA 1-SD1

1-FD2

3" =1

1/ 2"

'-0

1"

'-0

3/ 4"

'-0

1/ 2"

'-0

1/ 4"

'-0

1/ 8"

'-0

1/

'-0

If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.

A

1 2 3 4 5 6 7 8

B

C

D

E

F

A

B

C

D

E

F

OFFICE OF

FACILITIES

MANAGEMENT

PROJECT NUMBER:

BUILDING NUMBER:

VA DRAWING NUMBER:

PROJECT TITLE:

LOCATION:

DATE: CHECKED: DRAWN:

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR

PROJECT DIRECTORY:DESCRIPTION:

03/

8"

'-0

EA:CLIENT:

PR

O

JE

C

T N

U M

BE

R

1 2 3 4 5 6 7 8

A_B1-1

BUILDING 1 - FIRST FLOOR

DOOR LOCATION PLAN

UPGRADE FIRE

SYSTEMS, SMOKE AND

FIRE DOORS

6010 WEST AMARILLO BLVD. / AMARILLO, TEXAS

79106

1 / 4 / 28 / 29 / 336010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

MR. ANDREW J. WIECK

T. 806.673.8618

1331 RIVER BEND DRIVE

DALLAS, TEXAS 75247

MR. FRED C. CRABTREE, JR., P.E.

T. 214.696.6291

1255 CORPORATE DRIVE - SUITE 100

IRVING, TEXAS 75038

MR. DANIEL LeCLAIR, P.E.

T. 972.887.5553

1255 CORPORATE DRIVE - SUITE 200

IRVING, TEXAS 75038

MR. MICHAEL BURCH

T. 469.242.4707

207 WEST MAIN STREET

MESQUITE, TX 75149

MR. ROGER L. STEPHENS, AIA

T. 214.505.0659

EA02.1001

U

PG

R

AD

E

FI

R E

SY

ST

EM

S, S M

O

KE

A N

D F

IR

E

D O

O R

S

504-19-102

EA

.1

CAMPOS ENGINEERING

MOYE CONSULTINGENAPAY, LLC

HILL INTERNATIONAL

VA AMARILLO

N

PLAN

1/8" = 1'-0"

BUILDING 1 - LEVEL 1 - DOOR LOCATION PLANF1

REVISION SCHEDULE

No. DESCRIPTION DATE

STAIRWELL

REHAB STORAGE

SOILED LINEN

STAIRWELL

BUILDING 1

ASBESTOS SURVEY REPORT

Amarillo VA Medical Center Hospital Administration

Building No. 1

6010 West Amarillo Boulevard, Amarillo, Texas

Prepared for:

Thomas E. Creek VA Medical Center

6010 West Amarillo Boulevard

Amarillo, Texas 79106

VA Project Number: 36C25718C0214

December 24, 2018

ASBESTOS REPORT

THERAPIST

TREATMENT

PHYSICAL

THERAPY

NOTE 01

NOTE 01NOTE 01

TUB

PHY MED

CONFERENCE

COORDINATOR

STORAGE

STRG / WORKROOM

BUILDING 28

STORAGE

1110A

SECRETARY

WAITING AREA

IDF

CHIEF

117 1108

EXAM

1108A

EXAM

CARDIO

OFFICE

1106A

DRESS

1106B

OFFICE

1106C

OFFICE

SOILED

STORAGE

1.1.2

1118A

CLOSET

1.1.1

STORAGE

MEN'S

RESTROOM

OFFICE

1117A

ELECT.

FIRE PUMP

WOMEN'S

RESTROOM

STORAGE

STORAGE / FILES

RECEPTION

STORAGE

STORAGE

PROST.

OFFICE

ELECTRIC

PAINTERS

LOCKERS

STORAGE

MEN'S

LOCKER

MECHANICAL

ROOM

1123A

CLOSET

1134A

LOCKER

1132A

LOCKER

UPS

COMP.

1-FD1

1-FD3

BUILDING 28

ELECTRICAL RM

ELECTRICAL RM

ARMORY

1131B

STORAGE

1131A

REPORT RM

CHIEF'S

OFFICE

DENTIST

OFFICE

FILES/SEC/RECEP

1155A

PHYSICIAN

WORKRM

1155B

TRANSCRIPTION

1155C

POLICE

FILE RM

POLICE

REST

STAIRWELL

WOMEN'S

RESTROOM

ELECTRIC

REST

1131B

PHONES

DENTAL LAB

ALL

PURPOSE

1158A

VC

PUMP

22 1156

WAITING RM

X-RAY

X-RAY

OFFICE

OPERATORY

OPERATORY

OPERATORY

91 1148

CLEAN

OPERATORY

SOILED

UTILITY

OFFICE

OPERATORY

OPERATORY

SUCTION

MECH RM

1.1.1 1.1.2

1-FD4

PRIORITY

FD-111

PROJECT AREA

4-FD11

PROJECT AREA

1-SD2

FIRE DOOR # LOCATION

1-FD1 STAIR #

1-FD2 STAIR #

1-FD3 STAIR #

1-FD4 ROOM 1160 SOILED LINEN (PRIORITY)

FD-111 CONNECTING CORR. BLDG. 28

4-FD11 CONNECTING CORR. BLDG 1

SMOKE DOOR # LOCATION

1-SD1 MAIN CORR.BLDG. 1

1-SD2 DOOR RO ROOM 1123

NOTE 01 - REFER TO THE ATTACHED ASBESTOS REPORT FOR:

BLACK MASTIC UNDER TIGER STRIPE AND

GENERAL NOTES TO THE PROJECT:

A -

B - ALL FIRE AND SMOKE DOORS, FRAMES AND HARDWARE ARE

TO BE REMOVED AND REPLACED WITH NEW. MATCH THE

EXISTING HOLLOW METAL DOOR FRAME, HARDWARE AND

ELECTRONIC DEVICES.

MATCH MEANS: ADA COMPLIANT AND RATED VISION PANELS,

PROTECTION PLATES, CLOSERS, ELECTRONIC DEVICES,

AND HARDWARE / FINISH. THE ENTIRE ASSEMBLY SHALL

MEET THE REQUIREMENTS FOR THE RATED WALL IN WHICH

IT IS LOCATED.

C - THE NEW HOLLOW METAL FRAMES ARE TO TO BE ANCHORED

TO THE ADJACENT WALL ASSEMBLY, PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOOR FRAMES. THE

HOLLOW METAL DOORS ARE TO BE PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOORS.

D - WHERE FLOORING HAS TO BE REPLACED MATCH THE

ADJACENT FLOORING. COORDINATE WITH THE VA FOR

FINISHES.

E - WHERE HOLLOW METAL FRAMES HAVE BEEN REMOVED, THE

ADJACENT WALL ASSEMBLY IS TO BE REPAIRED, TEXTURED,

PRIMED AND PAINTED. THE COLOR AND FINISH IS TO MATCH

THE ADJACENT WALLS.

F - IF THE LAY-IN CEILING ABOVE THE FIRE OR SMOKE DOOR HAS

TO BE REMOVED SALVAGE THE CEILING TILES AND METAL

GRID FOR RE-INSTALLATION.

G -

207 WEST MAIN STREET

MESQUITE, TX 75149

T. 214.607.0247

WWW.ENAPAYLLC.COM

D E

S

IG

N D

E V

E

LO

P M

E N

T R

E V

IE

W

KEY PLAN / FULLY SPRINKLERED

& 4

ACCENT FLOOR TILE

IF DISTRUBED, ASBESTOS SHALL BE ABATED IN THE AREAS

REFERENCED IN THE ATTACHED ASBESTOS REPORT.

IF

C

D O

C U

M

EN

TS

11-04-20

11-04-20 MDM RLS

ELEV.

S-1

ELEV.

P-1

ELEV.

P-2

ALL NEW FIRE AND SMOKE DOOR FRAMES SHALL BE

IDENTIFIED BY THEIR NUMBERS ON THE HEAD OF EACH

HOLLOW METAL DOOR FRAME, BOTH SIDES (INGRESS &

EGRESS). THE GENERAL CONTRACTOR IS TO SALVAGE THE

EXISTING DOOR NUMBERS FOR REUSE ON THE NEW FRAMES.

IF THE DOOR NUMBERS CANNOT BE SALVAGED NEW VINYL

NUMBERS AND LETTERS SHALL BE BLACK AND NO SMALLER

THAN 1" IN HEIGHT.

PHASING - SPECIFIC NOTES TO THIS BUILDING LEVEL:

A1 - BY COMPARTMENT THEN BY DOORS, FIRE DOORS FIRST BY

REFERENCING THE DOOR NUMBER, SMOKE DOORS SECOND

BY REFERENCING THE DOOR NUMBER. DOORS MARKED

"PRIORITY" WILL TAKE PRECEDENCE.

COMMENTS:

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

01 - EXISTING MASONRY CONSTRUCTION WITH 5/8" FIRE

RATED GYP. BOARD AND / OR TILE AND PLASTER.

02 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

03 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

COMMENTS:

COMMENTS:

COMMENTS TO THE PARTITION LEGEND

EXISTING FIRE BARRIER LEGEND

MATCH EXISTING BARRIER RATING.

DWG 3 OF 56

BASE BID

BASE BID

BASE BID

ALT. BID 3

ALT. BID 3ALT. BID 3

ALT. BID 3

ALT. BID 3

BID PRIORITY

ALT. BID 3

ALT. BID 3

BASE BID

BASE BID

ALT. BID 3

ALT. BID 3

BID PRIORITY

ALT. BID 3

BASE BID

IC

1-FD6

1-SD3

1-FD5

1-FD4

PROJECT AREA

PROJECT AREA

PROJECT AREA

PROJECT AREA

3" =1

1/ 2"

'-0

1"

'-0

3/ 4"

'-0

1/ 2"

'-0

1/ 4"

'-0

1/ 8"

'-0

1/

'-0

If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.

A

1 2 3 4 5 6 7 8

B

C

D

E

F

A

B

C

D

E

F

OFFICE OF

FACILITIES

MANAGEMENT

PROJECT NUMBER:

BUILDING NUMBER:

VA DRAWING NUMBER:

PROJECT TITLE:

LOCATION:

DATE: CHECKED: DRAWN:

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR

PROJECT DIRECTORY:DESCRIPTION:

03/

8"

'-0

EA:CLIENT:

PR

O

JE

C

T N

U M

BE

R

1 2 3 4 5 6 7 8

A_B1-2

BUILDING 1 - SECOND

FLOOR DOOR LOCATION

PLAN

UPGRADE FIRE

SYSTEMS, SMOKE AND

FIRE DOORS

6010 WEST AMARILLO BLVD. / AMARILLO, TEXAS

79106

1 / 4 / 28 / 29 / 336010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

MR. ANDREW J. WIECK

T. 806.673.8618

1331 RIVER BEND DRIVE

DALLAS, TEXAS 75247

MR. FRED C. CRABTREE, JR., P.E.

T. 214.696.6291

1255 CORPORATE DRIVE - SUITE 100

IRVING, TEXAS 75038

MR. DANIEL LeCLAIR, P.E.

T. 972.887.5553

1255 CORPORATE DRIVE - SUITE 200

IRVING, TEXAS 75038

MR. MICHAEL BURCH

T. 469.242.4707

207 WEST MAIN STREET

MESQUITE, TX 75149

MR. ROGER L. STEPHENS, AIA

T. 214.505.0659

EA02.1001

U

PG

R

AD

E

FI

R E

SY

ST

EM

S, S M

O

KE

A N

D F

IR

E

D O

O R

S

504-19-102

EA

.1

CAMPOS ENGINEERING

MOYE CONSULTINGENAPAY, LLC

HILL INTERNATIONAL

VA AMARILLO

N

PLAN

1/8" = 1'-0"

BUILDING 1 - LEVEL 2 - DOOR LOCATION PLANF1

REVISION SCHEDULE

No. DESCRIPTION DATE

OFFICE

STAIRWELL

WOMEN'S

REST

POLICE

1252146A

ELECT

STAIRWELL

STAIRWELL

2111A

OFFICE

KEY PLAN / FULLY SPRINKLERED

BUILDING 1

ASBESTOS SURVEY REPORT

Amarillo VA Medical Center Hospital Administration

Building No. 1

6010 West Amarillo Boulevard, Amarillo, Texas

Prepared for:

Thomas E. Creek VA Medical Center

6010 West Amarillo Boulevard

Amarillo, Texas 79106

VA Project Number: 36C25718C0214

December 24, 2018

BUILDING 28

4-FD10

PROJECT AREA

REFER TO

BUILDING 4

2111C

AUDIO / VISUAL

211B

STORAGE

LIBRARY

2112E

DR. OFFICE

2112D

PRIVACY

OFFICER

2112C

WHC

2112B

GHAPT

2112A

GPM

DR. OFFICE

DR. OFFICE

DR. OFFICE

DR. OFFICE

RN OFFICE

2102A

RN OFFICE

BUILDING 28

28-FD13

PROJECT AREA

REFER TO

BUILDING 28

ASBESTOS REPORT

1.2.21.2.1

NOTE 01 NOTE 01 NOTE 01

207 WEST MAIN STREET

MESQUITE, TX 75149

T. 214.607.0247

WWW.ENAPAYLLC.COM

D E

S

IG

N D

E V

E

LO

P M

E N

T R

E V

IE

W

FIRE DOOR # LOCATION

1-FD4 STAIR # 3

1-FD5 STAIR # 2

1-FD6 STAIR # 1

SMOKE DOOR # LOCATION

1-SD3 MAIN CORR.BLDG. 1

NOTE 01 - REFER TO THE ATTACHED ASBESTOS REPORT FOR:

BLACK MASTIC UNDER TIGER STRIPE AND

ASCCESNT FLOOR TILE

POLICE CHIEF

SUPERVISOR

EEO OFFICE

2153A

CLOSET

B R

E S

T R

O O

M 51 2151

STORAGE

STORAGE

ELEV.

S-1

ELEV.

P-1

ELEV.

P-2

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

RESTROOM

2113A

MEN

RESTROOM

2113B

ELEC.

HALL OF HONOR

MEDICAL

ADMIN.

SWING

OFFICE

GPM

STORAGE

2116A

FILES

DR. OFFICE

DR. OFFICE

DR. OFFICE

DR. OFFIC E

DR. OFFICE

DR. OFFICE

PRIMARY

NURSE MGR.

2123B

RESTRM.

2123A

CLOSET

EXECCUTIVE

ASST. AD

LEAN

2126A

COPIER

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

COPIER

STOR.

CONFERENCE

2147A

OFFICE

OFFICE

EXEC. CONF.

RM.

IDF

AO to COS

2132A

PLANNER

2132E

ASSOC. DIR.

2132B

WAITING

EXEC.

SECRETARY (3)

2132C1

RESTRM.

2132C

DIRECTOR'S

OFFICE

2132D

CHIEF OF

STAFF

ACCENT FLOOR TILE

IF

C

D O

C U

M

EN

TS

11-04-20

11-04-20 MDM RLS

COMMENTS:

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

01 - EXISTING MASONRY CONSTRUCTION WITH 5/8" FIRE

RATED GYP. BOARD AND / OR TILE AND PLASTER.

02 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

03 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

COMMENTS:

COMMENTS:

COMMENTS TO THE PARTITION LEGEND

EXISTING FIRE BARRIER LEGEND

GENERAL NOTES TO THE PROJECT:

A -

B - ALL FIRE AND SMOKE DOORS, FRAMES AND HARDWARE ARE

TO BE REMOVED AND REPLACED WITH NEW. MATCH THE

EXISTING HOLLOW METAL DOOR FRAME, HARDWARE AND

ELECTRONIC DEVICES.

MATCH MEANS: ADA COMPLIANT AND RATED VISION PANELS,

PROTECTION PLATES, CLOSERS, ELECTRONIC DEVICES,

AND HARDWARE / FINISH. THE ENTIRE ASSEMBLY SHALL

MEET THE REQUIREMENTS FOR THE RATED WALL IN WHICH

IT IS LOCATED.

C - THE NEW HOLLOW METAL FRAMES ARE TO TO BE ANCHORED

TO THE ADJACENT WALL ASSEMBLY, PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOOR FRAMES. THE

HOLLOW METAL DOORS ARE TO BE PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOORS.

D - WHERE FLOORING HAS TO BE REPLACED MATCH THE

ADJACENT FLOORING. COORDINATE WITH THE VA FOR

FINISHES.

E - WHERE HOLLOW METAL FRAMES HAVE BEEN REMOVED, THE

ADJACENT WALL ASSEMBLY IS TO BE REPAIRED, TEXTURED,

PRIMED AND PAINTED. THE COLOR AND FINISH IS TO MATCH

THE ADJACENT WALLS.

F - IF THE LAY-IN CEILING ABOVE THE FIRE OR SMOKE DOOR HAS

TO BE REMOVED SALVAGE THE CEILING TILES AND METAL

IF DISTRUBED, ASBESTOS SHALL BE ABATED IN THE AREAS

REFERENCED IN THE ATTACHED ASBESTOS REPORT.

ALL NEW FIRE AND SMOKE DOOR FRAMES SHALL BE

IDENTIFIED BY THEIR NUMBERS ON THE HEAD OF EACH

HOLLOW METAL DOOR FRAME, BOTH SIDES (INGRESS &

EGRESS). THE GENERAL CONTRACTOR IS TO SALVAGE THE

EXISTING DOOR NUMBERS FOR REUSE ON THE NEW FRAMES.

IF THE DOOR NUMBERS CANNOT BE SALVAGED NEW VINYL

NUMBERS AND LETTERS SHALL BE BLACK AND NO SMALLER

THAN 1" IN HEIGHT.

MATCH EXISTING BARRIER RATING.

PHASING - SPECIFIC NOTES TO THIS BUILDING LEVEL:

A1 - BY COMPARTMENT THEN BY DOORS, FIRE DOORS FIRST BY

REFERENCING THE DOOR NUMBER, SMOKE DOORS SECOND

BY REFERENCING THE DOOR NUMBER. DOORS MARKED

"PRIORITY" WILL TAKE PRECEDENCE.

DWG 4 OF 56

BASE BID

ALT. BID 3

ALT. BID 3

ALT. BID 3

ALT. BID 3

BID PRIORITY

ALT. BID 3

ALT. BID 3

ALT. BID 3

BID PRIORITY

PROJECT AREA

1-SD8

PROJECT AREA

1-SD5

PROJECT AREA

1-FD7

PROJECT AREA

3" =1

1/ 2"

'-0

1"

'-0

3/ 4"

'-0

1/ 2"

'-0

1/ 4"

'-0

1/ 8"

'-0

1/

'-0

If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.

A

1 2 3 4 5 6 7 8

B

C

D

E

F

A

B

C

D

E

F

OFFICE OF

FACILITIES

MANAGEMENT

PROJECT NUMBER:

BUILDING NUMBER:

VA DRAWING NUMBER:

PROJECT TITLE:

LOCATION:

DATE: CHECKED: DRAWN:

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR

PROJECT DIRECTORY:DESCRIPTION:

03/

8"

'-0

EA:CLIENT:

PR

O

JE

C

T N

U M

BE

R

1 2 3 4 5 6 7 8

A_B1-3

BUILDING 1 - THIRD FLOOR

DOOR LOCATION PLAN

UPGRADE FIRE

SYSTEMS, SMOKE AND

FIRE DOORS

6010 WEST AMARILLO BLVD. / AMARILLO, TEXAS

79106

1 / 4 / 28 / 29 / 336010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

MR. ANDREW J. WIECK

T. 806.673.8618

1331 RIVER BEND DRIVE

DALLAS, TEXAS 75247

MR. FRED C. CRABTREE, JR., P.E.

T. 214.696.6291

1255 CORPORATE DRIVE - SUITE 100

IRVING, TEXAS 75038

MR. DANIEL LeCLAIR, P.E.

T. 972.887.5553

1255 CORPORATE DRIVE - SUITE 200

IRVING, TEXAS 75038

MR. MICHAEL BURCH

T. 469.242.4707

207 WEST MAIN STREET

MESQUITE, TX 75149

MR. ROGER L. STEPHENS, AIA

T. 214.505.0659

EA02.1001

U

PG

R

AD

E

FI

R E

SY

ST

EM

S, S M

O

KE

A N

D F

IR

E

D O

O R

S

504-19-102

EA

.1

CAMPOS ENGINEERING

MOYE CONSULTINGENAPAY, LLC

HILL INTERNATIONAL

VA AMARILLO

N

PLAN

1/8" = 1'-0"

BUILDING 1 - LEVEL 3 - DOOR LOCATION PLANF1

REVISION SCHEDULE

No. DESCRIPTION DATE

STAIRWELL

PATIENT ROOM 3

3760D

OXYGEN

STORAGE

STAIRWELL

DR. OFFICE

STAIRWELL

KEY PLAN / FULLY SPRINKLERED

BUILDING 1

ASBESTOS SURVEY REPORT

Amarillo VA Medical Center Hospital Administration

Building No. 1

6010 West Amarillo Boulevard, Amarillo, Texas

Prepared for:

Thomas E. Creek VA Medical Center

6010 West Amarillo Boulevard

Amarillo, Texas 79106

VA Project Number: 36C25718C0214

December 24, 2018

BUILDING 28

ASBESTOS REPORT

1.3.1 1.3.2

1.3.21.3.1

1-FD10

1-FD8

1-FD19

1-FD18

3707 CLEAN

UTILITY

SOILED UTILITY

C O

R R

ID

O

R 3A

-C

1-SD6

ANTERM

NOTE 01NOTE 01NOTE 01

BUILDING 28

OFFICE

1-FD17

207 WEST MAIN STREET

MESQUITE, TX 75149

T. 214.607.0247

WWW.ENAPAYLLC.COM

D E

S

IG

N D

E V

E

LO

P M

E N

T R

E V

IE

W

NOTE 01 - REFER TO THE ATTACHED ASBESTOS REPORT FOR:

BLACK MASTIC UNDER TIGER STRIPE AND

FIRE DOOR # LOCATION

1-FD7 STAIR # 3

1-FD8 STAIR # 2

1-FD10 STAIR # 1

SMOKE DOOR # LOCATION

1-SD8 DOOR TO RM. 3722

DR. WORK RM.

3A-C6A

STOR.

DR. SLEEP RM.

CORR.

3A-C6

OFFICE

3718A

RESTROOM

DR. OFFICE

DR. SLEEP RM.

OFFICE

NURSE MGR.

BREAKROOM

CORR.

3A-C7

3710A

LOCKERS

MEN'S

RESTROOM

WOMEN'S

RESTROOM

ELECT.

CONFERENCE

HAC

PHARMACIST

CONFERENCE

3726A

RESTROOM

PATIENT RM.

PATIENT RM.

3724A

RESTRM.

3724B

STOR.

PATIENT RM.

266 3722

STOR.

3723A

RESTRM.

3727B

RESTRM.

ELECT.

PATIENT RM.

P.O.S.

3729B

CLEAN UTL.

3729A

PRINTERS

STOR.

ANTERM.

3733A

PATIENT RM.

3733B

RESTRM.

3735A

RESTRM.

PATIENT RM.

SOILED

UTIL.

3745A

RESTRM.

ELECT.

MED

HAC

PATIENT RM.

3747A

RESTRM.

PATIENT RM.

PATIENT RM.

3749A

RESTRM.

PATIENT RM.

3751A

REST RM.

P.O.S.

NOURISHMENT

FAMILY RM.

214 3740

COUNSELING

OI & T

3736A

RESTRM.

PATIENT RM.

PATIENT RM.

3734A

RESTRM.

ELEV.

S-1

ELEV.

P-1

ELEV.

P-2

3760A

RESTRM.

3760C

VISITOR

KITCHEN

3760B

FAMILY RM.

3742A

RESTRM.

P.O.S.

PATIENT RM.

3744A

RESTRM.

PATIENT RM.

3746A

RESTRM.

ACCENT FLOOR TILE

IF

C

D O

C U

M

EN

TS

11-04-20

11-04-20 MDM RLS

NOTE 01

COMMENTS:

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

01 - EXISTING MASONRY CONSTRUCTION WITH 5/8" FIRE

RATED GYP. BOARD AND / OR TILE AND PLASTER.

02 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

03 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

COMMENTS:

COMMENTS:

COMMENTS TO THE PARTITION LEGEND

EXISTING FIRE BARRIER LEGEND

GENERAL NOTES TO THE PROJECT:

A -

B - ALL FIRE AND SMOKE DOORS, FRAMES AND HARDWARE ARE

TO BE REMOVED AND REPLACED WITH NEW. MATCH THE

EXISTING HOLLOW METAL DOOR FRAME, HARDWARE AND

ELECTRONIC DEVICES.

MATCH MEANS: ADA COMPLIANT AND RATED VISION PANELS,

PROTECTION PLATES, CLOSERS, ELECTRONIC DEVICES,

AND HARDWARE / FINISH. THE ENTIRE ASSEMBLY SHALL

MEET THE REQUIREMENTS FOR THE RATED WALL IN WHICH

IT IS LOCATED.

C - THE NEW HOLLOW METAL FRAMES ARE TO TO BE ANCHORED

TO THE ADJACENT WALL ASSEMBLY, PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOOR FRAMES. THE

HOLLOW METAL DOORS ARE TO BE PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOORS.

D - WHERE FLOORING HAS TO BE REPLACED MATCH THE

ADJACENT FLOORING. COORDINATE WITH THE VA FOR

FINISHES.

E - WHERE HOLLOW METAL FRAMES HAVE BEEN REMOVED, THE

ADJACENT WALL ASSEMBLY IS TO BE REPAIRED, TEXTURED,

PRIMED AND PAINTED. THE COLOR AND FINISH IS TO MATCH

THE ADJACENT WALLS.

F - IF THE LAY-IN CEILING ABOVE THE FIRE OR SMOKE DOOR HAS

TO BE REMOVED SALVAGE THE CEILING TILES AND METAL

ALL NEW FIRE AND SMOKE DOOR FRAMES SHALL BE

IDENTIFIED BY THEIR NUMBERS ON THE HEAD OF EACH

HOLLOW METAL DOOR FRAME, BOTH SIDES (INGRESS &

EGRESS). THE GENERAL CONTRACTOR IS TO SALVAGE THE

EXISTING DOOR NUMBERS FOR REUSE ON THE NEW FRAMES.

IF THE DOOR NUMBERS CANNOT BE SALVAGED NEW VINYL

NUMBERS AND LETTERS SHALL BE BLACK AND NO SMALLER

THAN 1" IN HEIGHT.

MATCH EXISTING BARRIER RATING.

PHASING - SPECIFIC NOTES TO THIS BUILDING LEVEL:

A1 - BY COMPARTMENT THEN BY DOORS, FIRE DOORS FIRST BY

REFERENCING THE DOOR NUMBER, SMOKE DOORS SECOND

BY REFERENCING THE DOOR NUMBER. DOORS MARKED

"PRIORITY" WILL TAKE PRECEDENCE.

DWG 5 OF 56

ALT. BID 3

ALT. BID 3

ALT. BID 3

ALT. BID 3

BID PRIORITY

ALT. BID 3

ALT. BID 3

ALT. BID 3

R

1-FD12PROJECT AREA

1-SD7 PROJECT AREA

1-FD11 PROJECT AREA

1-FD13

PROJECT AREA

3" =1

1/ 2"

'-0

1"

'-0

3/ 4"

'-0

1/ 2"

'-0

1/ 4"

'-0

1/ 8"

'-0

1/

'-0

If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.

A

1 2 3 4 5 6 7 8

B

C

D

E

F

A

B

C

D

E

F

OFFICE OF

FACILITIES

MANAGEMENT

PROJECT NUMBER:

BUILDING NUMBER:

VA DRAWING NUMBER:

PROJECT TITLE:

LOCATION:

DATE: CHECKED: DRAWN:

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR

PROJECT DIRECTORY:DESCRIPTION:

03/

8"

'-0

EA:CLIENT:

PR

O

JE

C

T N

U M

BE

R

1 2 3 4 5 6 7 8

A_B1-4

BUILDING 1 - FOURTH

FLOOR DOOR LOCATION

PLAN

UPGRADE FIRE

SYSTEMS, SMOKE AND

FIRE DOORS

6010 WEST AMARILLO BLVD. / AMARILLO, TEXAS

79106

1 / 4 / 28 / 29 / 336010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

MR. ANDREW J. WIECK

T. 806.673.8618

1331 RIVER BEND DRIVE

DALLAS, TEXAS 75247

MR. FRED C. CRABTREE, JR., P.E.

T. 214.696.6291

1255 CORPORATE DRIVE - SUITE 100

IRVING, TEXAS 75038

MR. DANIEL LeCLAIR, P.E.

T. 972.887.5553

1255 CORPORATE DRIVE - SUITE 200

IRVING, TEXAS 75038

MR. MICHAEL BURCH

T. 469.242.4707

207 WEST MAIN STREET

MESQUITE, TX 75149

MR. ROGER L. STEPHENS, AIA

T. 214.505.0659

EA02.1001

U

PG

R

AD

E

FI

R E

SY

ST

EM

S, S M

O

KE

A N

D F

IR

E

D O

O R

S

504-19-102

EA

.1

CAMPOS ENGINEERING

MOYE CONSULTINGENAPAY, LLC

HILL INTERNATIONAL

VA AMARILLO

N

PLAN

1/8" = 1'-0"

BUILDING 1 - LEVEL 4 - DOOR LOCATION PLANF1

REVISION SCHEDULE

No. DESCRIPTION DATE

STAIRWELL

LIBRARY

STAIRWELL

OFFICE

PICIS

4160A

RESTROOM

STAIRWELL

4113A

SHOWER

MEN'S

RESTROOM

KEY PLAN / FULLY SPRINKLERED

BUILDING 1

ASBESTOS SURVEY REPORT

Amarillo VA Medical Center Hospital Administration

Building No. 1

6010 West Amarillo Boulevard, Amarillo, Texas

Prepared for:

Thomas E. Creek VA Medical Center

6010 West Amarillo Boulevard

Amarillo, Texas 79106

VA Project Number: 36C25718C0214

December 24, 2018

BUILDING 28

ASBESTOS REPORT

1.4.1 1.4.2

BUILDING 28

NOTE 01

NOTE 01NOTE 01

28-FD26 PROJECT AREA

REFER TO BUILDING

1.4.21.4.1

207 WEST MAIN STREET

MESQUITE, TX 75149

T. 214.607.0247

WWW.ENAPAYLLC.COM

NOTE 01 - REFER TO THE ATTACHED ASBESTOS REPORT FOR:

BLACK MASTIC UNDER TIGER STRIPE AND

ASCCESNT FLOOR TILE

FIRE DOOR # LOCATION

1-FD11 STAIR # 2

1-FD12 STAIR # 1

1-FD13 STAIR # 3

SMOKE DOOR # LOCATION

1-SD7 MAIN CORR. BLDG. 1

SOCIAL WORKERS

OFFICE

OFFICE (2)

OFFICE

4115A

STOR.

67 4114A

OFFICE

4112A

WOMENMS

RESTRM.

RESTROOM

HAC

KITCHEN

REST

BED STOR.

RECEPTION

KITCHEN

CALL CENTER / OVERFLOW

4101A

OFFICE

HEALTH ADMIN. CALL CENTER

ELECT.

4120B

ENTRY

OFFICE

4121A

REST

22 4121

OFFICE OPT

1704123B

REST

4123A

STOR.

OFFICE

VACANT

4119A

STOR.

TELEHEALTH

OFFICE

CHAPLAIN

STOR.

TELEHEALTH

CHAPLIN

CHUTE

ELEV.

S-1

ELEV.

P-1

ELEV.

P-2

IDF

RECEPTION

WAITING

EXAM 2

4146C

ELECT.

4146A

STOR.

LASER RM

4134A

VISUAL

FIELDS

EXAM

4123C

RESTRM

EXAM 3

EXAM 4

ELECT.

4626A1

VISUAL FIELDS

4126A

EXAM

DR.OFFICE

4126B

EXAM

4124A

OFFICE OPT

4124B

OFFICE

OPTICAL

TELEHEALTH

TELEHEALTH

TELEHEALTH

TELEHEALTH

TRIAGE

OFFICE

4149A

OFFICE

RESTRM.

PIV BADGE

CLEAN

UTLY.

BREAK RM.

OFFICE (2)

OFFICE (2)

4141A

BREAK RM.

OFFICE

OFFICE (2)

OFFICE

OFFICE

OFFICE

CHIEF

OFFICE

OFFICE (2)

OFFICE

OFFICE

REST RM

4146B

REST RM

ACCENT FLOOR TILE

IF

C

D O

C U

M

EN

TS

11-04-20

11-04-20 MDM RLS

COMMENTS:

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

01 - EXISTING MASONRY CONSTRUCTION WITH 5/8" FIRE

RATED GYP. BOARD AND / OR TILE AND PLASTER.

02 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

03 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

COMMENTS:

COMMENTS:

COMMENTS TO THE PARTITION LEGEND

EXISTING FIRE BARRIER LEGEND

GENERAL NOTES TO THE PROJECT:

A -

B - ALL FIRE AND SMOKE DOORS, FRAMES AND HARDWARE ARE

TO BE REMOVED AND REPLACED WITH NEW. MATCH THE

EXISTING HOLLOW METAL DOOR FRAME, HARDWARE AND

ELECTRONIC DEVICES.

MATCH MEANS: ADA COMPLIANT AND RATED VISION PANELS,

PROTECTION PLATES, CLOSERS, ELECTRONIC DEVICES,

AND HARDWARE / FINISH. THE ENTIRE ASSEMBLY SHALL

MEET THE REQUIREMENTS FOR THE RATED WALL IN WHICH

IT IS LOCATED.

C - THE NEW HOLLOW METAL FRAMES ARE TO TO BE ANCHORED

TO THE ADJACENT WALL ASSEMBLY, PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOOR FRAMES. THE

HOLLOW METAL DOORS ARE TO BE PRIMED AND PAINTED TO

MATCH THE ADJACENT HOLLOW METAL DOORS.

D - WHERE FLOORING HAS TO BE REPLACED MATCH THE

ADJACENT FLOORING. COORDINATE WITH THE VA FOR

FINISHES.

E - WHERE HOLLOW METAL FRAMES HAVE BEEN REMOVED, THE

ADJACENT WALL ASSEMBLY IS TO BE REPAIRED, TEXTURED,

PRIMED AND PAINTED. THE COLOR AND FINISH IS TO MATCH

THE ADJACENT WALLS.

F - IF THE LAY-IN CEILING ABOVE THE FIRE OR SMOKE DOOR HAS

TO BE REMOVED SALVAGE THE CEILING TILES AND METAL

ALL NEW FIRE AND SMOKE DOOR FRAMES SHALL BE

IDENTIFIED BY THEIR NUMBERS ON THE HEAD OF EACH

HOLLOW METAL DOOR FRAME, BOTH SIDES (INGRESS &

EGRESS). THE GENERAL CONTRACTOR IS TO SALVAGE THE

EXISTING DOOR NUMBERS FOR REUSE ON THE NEW FRAMES.

IF THE DOOR NUMBERS CANNOT BE SALVAGED NEW VINYL

NUMBERS AND LETTERS SHALL BE BLACK AND NO SMALLER

THAN 1" IN HEIGHT.

MATCH EXISTING BARRIER RATING.

PHASING - SPECIFIC NOTES TO THIS BUILDING LEVEL:

A1 - BY COMPARTMENT THEN BY DOORS, FIRE DOORS FIRST BY

REFERENCING THE DOOR NUMBER, SMOKE DOORS SECOND

BY REFERENCING THE DOOR NUMBER. DOORS MARKED

"PRIORITY" WILL TAKE PRECEDENCE.

DWG 6 OF 56

BASE BID

ALT. BID 3

ALT. BID 3

ALT. BID 3

ALT. BID 3

BID PRIORITY

ALT. BID 3

ALT. BID 3

ALT. BID 3

N

F T

N

1-FD16

1-FD14

PROJECT AREA

PROJECT AREA

3" =1

1/ 2"

'-0

1"

'-0

3/ 4"

'-0

1/ 2"

'-0

1/ 4"

'-0

1/ 8"

'-0

1/

'-0

If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.

A

1 2 3 4 5 6 7 8

B

C

D

E

F

A

B

C

D

E

F

OFFICE OF

FACILITIES

MANAGEMENT

PROJECT NUMBER:

BUILDING NUMBER:

VA DRAWING NUMBER:

PROJECT TITLE:

LOCATION:

DATE: CHECKED: DRAWN:

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR

PROJECT DIRECTORY:DESCRIPTION:

03/

8"

'-0

EA:CLIENT:

PR

O

JE

C

T N

U M

BE

R

1 2 3 4 5 6 7 8

A_B1-5

BUILDING 1 - FIFTH FLOOR

DOOR LOCATION PLAN

UPGRADE FIRE

SYSTEMS, SMOKE AND

FIRE DOORS

6010 WEST AMARILLO BLVD. / AMARILLO, TEXAS

79106

1 / 4 / 28 / 29 / 336010 W. AMARILLO BLVD.

AMARILLO, TEXAS 79106

MR. ANDREW J. WIECK

T. 806.673.8618

1331 RIVER BEND DRIVE

DALLAS, TEXAS 75247

MR. FRED C. CRABTREE, JR., P.E.

T. 214.696.6291

1255 CORPORATE DRIVE - SUITE 100

IRVING, TEXAS 75038

MR. DANIEL LeCLAIR, P.E.

T. 972.887.5553

1255 CORPORATE DRIVE - SUITE 200

IRVING, TEXAS 75038

MR. MICHAEL BURCH

T. 469.242.4707

207 WEST MAIN STREET

MESQUITE, TX 75149

MR. ROGER L. STEPHENS, AIA

T. 214.505.0659

EA02.1001

U

PG

R

AD

E

FI

R E

SY

ST

EM

S, S M

O

KE

A N

D F

IR

E

D O

O R

S

504-19-102

EA

.1

CAMPOS ENGINEERING

MOYE CONSULTINGENAPAY, LLC

HILL INTERNATIONAL

VA AMARILLO

N

PLAN

REVISION SCHEDULE

No. DESCRIPTION DATE

1/8" = 1'-0"

BUILDING 1 - LEVEL 5 - DOOR LOCATION PLANF1

PROJECT AREA

STAIRWELL

STAIRWELL

IDF

STAIRWELL

NOTE

NOTE 01

NOTE 01

KEY PLAN / FULLY SPRINKLERED

BUILDING 1

ASBESTOS SURVEY REPORT

Amarillo VA Medical Center Hospital Administration

Building No. 1

6010 West Amarillo Boulevard, Amarillo, Texas

Prepared for:

Thomas E. Creek VA Medical Center

6010 West Amarillo Boulevard

Amarillo, Texas 79106

VA Project Number: 36C25718C0214

December 24, 2018

ASBESTOS REPORT

1.5.1

1-FD15

1.5.1

ELEVATOR

PENTHOUSE

STAIR 2

NOTE 01

D20

ELEVATORS

PENTHOUSE

HVAC

STORAGE

RESTROOM

HAC

LOBBY

WORK RM

5100A

OFFICE

ATTIC

STORAGE

STORAGE

HVAC

HVAC

HVAC

MECHANICAL

HVAC

HVAC

PROJECT AREA

207 WEST MAIN STREET

MESQUITE, TX 75149

T. 214.607.0247

WWW.ENAPAYLLC.COM

D E

S

IG

N D

E V

E

LO

P M

E N

T R

E V

IE

W

NOTE 01 - REFER TO THE ATTACHED ASBESTOS REPORT FOR:

BLACK MASTIC UNDER TIGER STRIPE AND

FIRE DOOR # LOCATION

1-FD14 STAIR # 2

1-FD15 STAIR # 2 (PENTHOUSE)

1-FD16 STAIR # 1

STAIR # 3

SMOKE DOOR # LOCATION

NA

ELEV.

S-1

ELEV.

P-1

ELEV.

P-2

1-FD13

1-FD13

ACCENT FLOOR TILE

STAIR 2

IF

C

D O

C U

M

EN

TS

11-04-20

11-04-20 MDM RLS

COMMENTS:

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

01 - EXISTING MASONRY CONSTRUCTION WITH 5/8" FIRE

RATED GYP. BOARD AND / OR TILE AND PLASTER.

02 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH 5/8" TYPE "X" GYP. BOARD EACH SIDE.

03 - EXISTING 3 5/8" AND / OR 5 1/2" 16 GUAGE METAL STUDS

WITH…

This is the start of the file's text. The full file is on GovTribe.