5-20260623-Mt Bethel-Sealed Arch Set.pdf
PDF 11 MB Posted
- Attached to
- Mt. Bethel Fire Co. - Emergency Shelter 2020-63
- Solicitation number
- Not on record
- Issued by
- Northampton County, Pennsylvania
About this file
This is a sealed architectural drawing set for a state and local contract opportunity involving the Mt. Bethel Fire Company in Upper Mount Bethel Township, Northampton County, Pennsylvania. The project consists of an addition to the existing firehouse that will include approximately 1,743 square feet of new construction divided into two phases: Phase 1 encompasses 1,195 square feet and Phase 2 encompasses 548 square feet. The addition will provide handicapped accessible toilet and shower facilities, changing rooms, and table and chair storage for the adjacent multi-purpose room. An existing toilet room will be renovated to serve as a firefighter shower room with equipment extraction capabilities. The project also includes mechanical system upgrades, a new accessible entrance, and emergency shelter functionality. A pre-bid meeting was scheduled for July 9, 2026, at 9:00 A.M. at the project site located at 2341 North Delaware Drive, Mt. Bethel, PA 18343, with site viewing opportunities following the meeting. Bid submissions were due on Tuesday, July 28, 2026, at 12:00 P.M. prevailing time through the Penn Bid Program at www.pennbid.bonfirehub.com.
The sealed architectural drawing set includes comprehensive construction documents prepared by SCF Architecture (Samantha Ciotti Falcone, AIA, LEED AP) as the architect of record, with structural engineering by Base Engineering, and MEP engineering by Barry Isett & Associates. The project is designed to comply with the 2021 International Building Code, 2021 International Existing Building Code, and 2010 American Disability Act standards. The drawings specify that all work must conform to applicable municipal ordinances and codes, and the contractor is responsible for securing and paying all required permits and fees. Performance Bond and Payment Bond requirements in the amount of 100 percent of the total contract value are mandated. The addition features 2-hour fire wall separation between the existing assembly space and new construction, with 1-hour rated corridors and specific fire-rated roof sections extending 4 feet from the wall attachment. All newly installed gypsum wallboard must be GREENGUARD Gold certified or have zero grams per liter of VOCs, and insulation must comply with EPA recycled content recommendations and formaldehyde emission limits.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING MULTI-PURPOSE ROOM
EXISTING BUILDING
EXISTING ENGINE ROOM
EXISTING PARKING LOT
NORTH DELAWARE DRIVE
AREA OF WORK:
NEW CONSTRUCTION PHASE 1
AREA OF WORK:
NEW CONSTRUCTION PHASE 2
AREA OF
RENOVATION
1 HOUR FIRE-RETARDANT
PLYWOOD EXTENDS 4'-0"
PAST FIRE WALL
2 HOUR
FIREWALL
SEPARATION
LEGEND
'-9
/8
(10
'-0 " M
IN
EX.
SIREN
TOWER
PHASE 2 AREA OF
WORK: 740 SF
AREA OF WORK:
RENOVATION PHASE 1
NEW ACCESSIBLE ENTRANCE
PHASE 1PHASE 2
PHASE 1
PHASE 1 AREA OF
WORK: 1,000 SF
EXISTING PARKING LOT
EXISTING ACCESSIBLE ENTRANCE
EXISTING PLANTING BED
NORTH DELAWARE DRIVE
APPROXIMATE SEPTIC
FIELD LOCATION
1'-
6"
TO
S
EP
TI
C
FIE
LD
62'-10 7/8"
TO PROPERTY LINE
5'
-1
/1 6"
TO
P
RO
PE
RT
Y
LIN
E
PRO
PERTY LIN
E
PRO
PERTY LIN
E
PROPERTY LINE
PRO
PERTY LIN
E
SITE PLAN IS ILLUSTRATIVE ONLY
PROJECT
INFORMATION
A1.1
Pennsylvania One Call System, Inc.
811 or 1-800-242-1776 Address:
925 Irwin Run Road West Mifflin PA 15122 Hours:
24 / 7
Advance Notice:
Construction phase - 3 to 10 business days;
Design phase - 10 to 90 business days Number of days in advance of a digging project that you need to notify the one call center of your intent to dig.
Marks Valid:
as long as equipment is kept on site Defines the period of time the facility marks
(paint, flags, stakes, etc.) are valid according to state law or practice.
N GENERAL
PROJECT NOTES
SITE PLAN
LOCATION MAPONE CALL
ARCHITECTURAL
A1.1 PROJECT INFORMATION
A1.2 LIFE SAFETY PLAN
A1.3 DEMOLITION PLAN
A2.1 FLOOR PLANS
A2.2 FLOOR PLANS PHASE 2
A2.3 ROOF PLAN
A2.4 ROOF DETAILS
A2.5 PLAN DETAILS
A2.6 ACCESSIBILITY & DETAILS
A3.1 EXTERIOR ELEVATIONS
A4.1 SECTIONS
A6.1 DOORS & WINDOWS
A7.1 FINISHES
A7.2 REFLECTED CEILING PLAN
DRAWING INDEX
N
PLAN NORTHACTUAL NORTH
1. ALL WORK SHALL CONFORM TO ALL ORDINANCES AND CODES AS ADOPTED AND AMENDED BY THE MUNICIPALITY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION AND COMPLIANCE WITH ALL CODES AND ORDINANCES APPLICABLE TO THIS WORK.
2. INSTALL ALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER SPECIFICATIONS AND RECOMMENDATIONS, AND IN ACCORDANCE WITH
INDUSTRY STANDARDS AND BUILDING CODE.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING AND PAYING FOR ALL PERMITS AND FEES REQUIRED FOR THE WORK.
4. CONTRACTOR SHALL PROVIDE DUMPSTER ON SITE FOR DISPOSAL OF ALL EXCESS MATERIALS AND WASTE. CONTRACTOR SHALL BE RESPONSIBLE FOR
KEEPING THE JOB SITE CLEAN AND ORDERLY ON A DAILY BASIS AND PLACING ALL EXCESS MATERIALS AND WASTE IN THE DUMPSTER.
5. ALL INTERIOR DIMENSIONS ARE TAKEN TO FACE OF STUD UNLESS NOTED OTHERWISE. ALL EXTERIOR DIMENSIONS ARE TAKEN TO FACE STUD UNLESS
OTHERWISE NOTED.
6. THE OMISSION OF EXPRESSED REFERENCE IN THE DRAWINGS TO ANY ITEM OF LABOR OR MATERIAL NECESSARY FOR THE PROPER EXECUTION OF THE
WORK IN ACCORDANCE WITH PRESENT GOOD PRACTICE OF THE TRADE SHALL NOT RELIEVE THIS CONTRACTOR FROM PROVIDING, AT NO COST, SUCH ADDITIONAL LABOR AND MATERIALS UNDER THIS CONTRACT.
7. PROVIDE TEMPORARY CLOSURES, COVERS AND BARRIERS AS REQUIRED TO MAINTAIN SECURITY; TO PREVENT AIR, DUST AND WATER INFILTRATION; TO RETARD HEAT LOSS OR GAIN AS THE SEASON DICTATES; AND TO PROTECT PERSONS, THE WORK, THE OWNER'S PROPERTY AND THE
PROPERTY OF OTHERS.
8. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL WORK PERFORMED BY ALL TRADES, INCLUDING WORK BY CONSULTANTS, CONTRACTORS AND SUBCONTRACTORS SELECTED BY THE OWNER. REFER TO OUTLINE SPECIFICATIONS FOR WORK BEING PROVIDED UNDER SEPARATE CONTRACTS BY CONSULTANTS, CONTRACTORS AND SUBCONTRACTORS SELECTED BY THE OWNER.
9 ALL GLASS WITHIN THE DOORS SHALL BE TEMPERED; ALL GLASS W/ A VERTICAL EDGE WITHIN 24” ARC OF A DOOR SWING NEEDS TO BE TEMPERED
GLASS UNIT. SEE DOOR + WINDOW DETAILS FOR ANY ADDITIONAL REQUIREMENTS.
10. ELECTRICAL EQUIPMENT AND WIRING IN NEWLY INSTALLED PARTITIONS AND CEILINGS SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS OF NFPA 70 AND THE INTERNATIONAL ELECTRICAL CODE. INFORMATION RELATED TO ELECTRICAL WORK IS ILLUSTRATIVE ONLY TO GIVE GENERAL LOCATIONS OF SPECIFIC FIXTURES OUTLETS/DATA CONNECTIONS/PHONE JACKS, ETC. A COMPLETE DESIGN SHALL BE DEVELOPED BY GC'S
ELECTRICAL ENGINEER/DESIGNER FOR PERMITTING PURPOSES.
11. OCCUPIABLE SPACE IN ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION IN ACCORDANCE WITH THE
INTERNATIONAL MECHANICAL CODE.
12. CONTRACTOR IS RESPONSIBLE FOR SITE SAFETY. PROVIDE TEMPORARY CLOSURES, COVERS AND BARRIERS AS REQUIRED TO MAINTAIN SECURITY; TO PREVENT AIR, DUST AND WATER INFILTRATION; TO RETARD HEAT LOSS OR GAIN AS THE SEASON DICTATES; AND TO PROTECT PERSONS, THE WORK, THE OWNER'S PROPERTY AND THE PROPERTY OF OTHERS.
13. ALL NEWLY INSTALLED GWB MUST BE GREENGUARD GOLD CERTIFIED OR HAVE ZERO GRAMS PER LITER OF VOCS.
14. NEW INSULATION SPECIFICATIONS (THERMAL, ACOUSTICAL AND HVAC):
A. SHALL CONTAIN RECOVERED MATERIALS AS REQUIRED BY EPA'S CPG AND RELATED RECYCLED CONTENT RECEMMENDATIONS.
B. NO INSULATION INSTALLED WITH THIS PROJECT SHALL BE MATERIAL MANUFACTURED USING CHLOROFLUOROCARBONS (CFCS), NOR SHALL CFCS
BE USED IN THE INSTALLATION OF THE PRODUCT.
C. ALL INSULATION CONTAINING FIBROUS MATERIALS EXPOSED TO AIR FLOW SHALL BE RATED FOR THAT EXPOSURE OR SHALL BE
ENCAPSULATED.
D. INSULATING PROPERTIES FOR ALL MATERIALS SHALL MEET OR EXCEED APPLICABLE INDUSTRY STANDARDS. POLYSTYRENE PRODUCTS SHALL MEET
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) C578 91.
E. ALL INSULATION SHALL BE LOW EMITTING WITH NOT GREATER THAN .05 PPM FORMALDEHYDE EMISSIONS.
F. THE MAXIMUM FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR INSULATION SHALL MEET THE REQUIREMENTS OF THE APPLICABLE
LOCAL CODES AND ORDINANCES (CURRENT AS OF THE LEASE AWARD DATE) ADOPTED BY THE JURISDICTION IN WHICH THE BUILDING IS
LOCATED.
3515 Sunnyside Road Center Valley, PA 18034
T: 610-297-0140 E: sam@scf-arch.com These documents are instruments of the Architect's service for use solely with respect to this project.
The Architect shall retain all common law, statutory and other reserved rights, including the copyright.
They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect.
L LC
STRUCTURAL ENGINEER OF RECORD:
101 NORTH QUEBEC STREET
ALLENTOWN, PA, 18109)
610-437-0978 bcohen@baseeng.com
M O
U N
T
BE
TH
EL
F
IR
E
CO
AD
DI
TI
O N
T O
E
XI
ST
IN
G
FI
RE
C
O M
PA
N
Y
N or th
D el aw ar e Dr iv e, M t.
Be th el , P
A
U pp er M ou nt
B et he l, N or th am pt on
C ou nt y
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
DRAWN BY:
BID DOCUMENTS
6/23/2026
REV1
REV2
OWNER:
Mt. Bethel Fire Co.
ML, SCF
BARRY ISETT & ASSOCIATES
570-688-8268 dalehandelong@hotmail.com
MEP ENGINEER OF RECORD:
5420 Crackersport Rd Allentown, PA 18104
610-437-0978 EMAIL: dhorsfield@barryisett.com
BASE ENGINEERING
2341 North Delaware Drive, Mt Bethel, PA 18343 Upper Mount Bethel Twp., Northampton County
OVERALL SITE PLAN (N.T.S.)
9.75 ACRES
STRUCTURAL
S1.1 STRUCTURAL NOTES
S1.2 STRUCTURAL PLANS
MECHANICAL
M0.0 MECHANICAL INFORMATION SHEET
M1.1 PARTIAL FLOOR PLAN - MECHANICAL
M1.2 PARTIAL ROOF PLAN - MECHANICAL
M3.0 MECHANICAL DETAILS & SCHEDULES
M4.0 MECHANICAL SPECIFICATIONS
MD1.1 PARTIAL FLOOR PLAN - MECHANICAL DEMO
ELECTRICAL
E0.0 ELECTRICAL INFORMATION SHEET
E1.1 PARTIAL FLOOR PLAN - LIGHTING
E2.1 PARTIAL POWER PLAN - POWER
E2.2 PARTIAL ROOF PLAN - POWER
E3.0 ELECTRICAL DETAILS & SCHEDULES
E4.0 ELECTRICAL SPECIFICATIONS
ED1.1 PARTIAL FLOOR PLAN DEMOLITION - POWER
PLUMBING
P0.0 PLUMBING INFORMATION SHEET
P1.1 PARTIAL FLOOR PLAN - DOMESTIC WATER
P2.1 PARTIAL FLOOR PLAN - SANITARY
P3.0 PLUMBING DETAILS & SCHEDULES
P4.0 PLUMBING SPECIFICATIONS
CORRIDOR
EXISTING SIREN
POLES
EXISTING
KITCHEN
EXISTING
BOILER
EXISTING
OFFICE
ACCESSIBLE
CHANGING
MEN
WOMEN
EXISTING SHED
NURSING/
CHANGING
2 HOUR FIRE WALL
EXISTING
MULTI-PURPOSE ROOM
EXISTING DOORS
MUST ACHIEVE A
90-MIN FIRE
RATING OR MUST
BE REPLACED,
V.I.F.
90 MINUTE
DOOR EXISTING DOORS
MUST ACHIEVE A
90-MIN FIRE
RATING OR MUST
BE REPLACED,
V.I.F.
EXISTING
MULTI-PURPOSE
ROOM
540 OCCUPANTS
EXISTING
KITCHEN
EXISTING
KITCHEN
EXISTING
STORAGE
EXISTING
STORAGE
EXISTING MAIN
ENTRANCE
EXISTING GARAGE
EXISTING OFFICE EXISTING OFFICE
EXISTING CORRIDOR
EX
IS
TI
N
G
CO
RR
ID
O R
EX
IS
TI
N
G
CO
RR
ID
O R
1 HOUR RATED
CORRIDOR
MEN WOMEN
TABLE & CHAIR
STORAGE
635 SF
4' -0
1 H
O
UR
RA
TE
D
RO
O F
M
IN
2 H
OUR FIR
E W
ALL
4' -0
1 H
O
UR
RA
TE
D
RO
O F
'-7
/8
EXTRACTOR
ROOM
RENOVATED
EXISTING TOILET
ROOM (FOR FIRE
COMPANY USE)
CHANGING
CHANG-
ING
ACCESSIBLE
CHANGING
EXISTING
STORAGE
CHANGING
1'-6"
3' -4
/8
3'-0"
3' -0
3' -0
" M
IN
. C
LE
AR
RE
Q
UI
RE
D
CORRIDOR
RENOVATED
TOILET/EXTRACTOR ROOM
SIGN ON DOORS:
"NOT AN EXIT"
EX
MODELNUMBERTRADENAMEPRODUCTMATERIAL
MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL
MODELNUMBERTRADENAMEPRODUCTMATERIAL
EXISTING TABLES
EXISTING TABLES
EXISTING TABLES
EXISTING TABLES
EXISTING TABLES EXISTING TABLES
EXISTING TABLES
EXISTING TABLES
EXISTING TABLES
EXISTING TABLES
FE
EXISTING
BUILDING
NEW
CONSTRUCTION
EX
IS
TI
N
G
BU
ILD
IN
G N
EW
CO
N
ST
RU
CT
IO
N
EX FE
EX
FEEX
MODELNUMBERTRADENAMEPRODUCTMATERIAL
EX
EX
TRAVEL DISTANCE
EXIT "A"
EXIT "B"
148'-10" 99'-5"
200'-0" ALLOWED
EXIT "A"
EXIT "B" EXIT "C"
TRAVEL DISTANCE
EXIT "A"
163'-5"
200'-0" ALLOWED
EXIT "C"
86'-0"
LIFE SAFETY
PLAN
A1.2
BUILDING CODE SUMMARY
MOUNT BETHEL FIRE COMPANY
2341 NORTH DELAWARE DRIVE, MT. BETHEL, PA 18343
ASSEMBLY W/ ACCESSORY USE STORAGE + TOILETS - A2
UPPER MT. BETHEL TOWNSHIP
2021 IBC, 2021 IEBC, 2010 AMERICAN DISABILITY ACT
VB
35'-0" (EX) 1
FIRE HOUSE
X
ASSEMBLY A-3 (COMMUNITY HALL)
LIFE SAFETY PLAN
NORTHAMPTON
PROJECT SUMMARY
ADDITION TO EXISTING FIRE COMPANY. ADDITION WILL
HOUSE NEW REST ROOMS, CHANGING ROOMS, &
TABLE/CHAIR STORAGE FOR ATTACHED MULTI-PURPOSE
ROOM.
IT IS THE INTENTION OF THE FIRE COMPANY TO USE THE
ASSEMBLY SPACE & NEW TOILET ROOMS AS AN EMERGENCY
SHELTER WHEN THE NEED ARISES.
PHASE 1 ADDITION: 1195 SF
PHASE 2 ADDITION: 548 SF
TOTAL ADDITION: 1743 SF
NOTES:
2 HOUR FIRE SEPARATION PROVIDED BETWEEN EXISTING
ASSEMBLY SPACE & NEW ADDITION (ACCESSORY SPACE TO
EXISTING ASSEMBLY SPACE).
NEW ROOF WILL BE RATED WITHIN 4'-0" OF ATTACHMENT
TO EXISTING STRUCTURE TO AVOID EXTENDING FIRE WALL
30" ABOVE ROOF.
CORRIDOR WALLS: 1 HR RATED
CORRIDOR WIDTH: 5'-0"
EXITING FROM EXISTING MULTI-PURPOSE ROOM:
OCCUPANCY –
ASSEMBLY:A-2
BANQUET HALL /MPR AREA: 8100 SF
0.2”PER OCCUPANT REQ'D FOR EGRESS
8,100 SF(MPR) / 15 SF (TABLES AND CHAIRS)=540
540 OCCUPANTS = 108" OF EGRESS WIDTH CAPACITY REQ'D
OR (3) 36” DOORS MEET THIS CAPACITY.
144" OR EGRESS WIDTH OR (6) 36" DOORS PROVIDED
20'-0"
271 271
PROJECT DATA
Mixed Occupancy:
Secondary Occupancy:
Primary Occupancy:
Building Height:
Mezzanine:
Sprinklers:
Construction Type:
BUILDING DATA
Code Requirements to be Met:
Exception:
Number of Stories:
YesNoMixed Construction:
AlterationFit OutRenovationNew Construction
PrivateCity/County Code Enforcement Jurisdiction: Township:
County: Climate Zone:
Owned By:
Name of Project:
Reconstruction
Address:
Proposed Use:
Owner or Authorized Agent: Phone #:
Existing
Addition
YesNo Existing
YesNo Unlimited High Rise: YesNo
YesNo
SCF ARCHITECTURE 610-297-0140
OCCUPANCY LOAD:
REQUIRED PLUMBING FIXTURES: MALE / FEMALE OCCUPANTS
TOILETS: MALE: ____ REQUIRED/____ PROVIDED
FEMALE:_____REQUIRED/____ PROVIDED
LAVATORIES: MALE: ____ REQUIRED/____ PROVIDED
FEMALE:_____REQUIRED/____ PROVIDED
____ ADDITIONAL UNISEX PROVIDED
SERVICE SINK: _____ REQUIRED/_____ PROVIDED
DRINKING FOUNTAIN: ______ REQUIRED/____ PROVIDED
ACCESSIBLE TOILET FIXTURES: ______ REQUIRED/ _____ PROVIDED
ACCESSIBLE LAVATORIES: ______ REQUIRED/ _____ PROVIDED
ACCESSIBLE DRINKING
FOUNTAINS: ______ REQUIRED/ _____ PROVIDED
ACCESSIBLE TOILETS/URINALS: _____
ACCESSIBLE LAVATORIES: _____
EGRESS/EXITS: _____ REQUIRED/_____ PROVIDED
MAX. DEAD END HALLWAY:
_____ SF GROSS SPACE
____ SF/PERSON = ________ OCCUPANTS
FIRE EXTINGUISHERS REQUIRED @ ___________________
8121 ASSEMBLY (TABLES & CHAIRS)
15 541
NOT REQUIRED IN
NEW SPACE
3515 Sunnyside Road Center Valley, PA 18034
T: 610-297-0140 E: sam@scf-arch.com These documents are instruments of the Architect's service for use solely with respect to this project.
The Architect shall retain all common law, statutory and other reserved rights, including the copyright.
They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect.
L LC
STRUCTURAL ENGINEER OF RECORD:
101 NORTH QUEBEC STREET
ALLENTOWN, PA, 18109)
610-437-0978 bcohen@baseeng.com
M O
U N
T
BE
TH
EL
F
IR
E
CO
AD
DI
TI
O N
T O
E
XI
ST
IN
G
FI
RE
C
O M
PA
N
Y
N or th
D el aw ar e Dr iv e, M t.
Be th el , P
A
U pp er M ou nt
B et he l, N or th am pt on
C ou nt y
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
DRAWN BY:
BID DOCUMENTS
6/23/2026
REV1
REV2
OWNER:
Mt. Bethel Fire Co.
ML, SCF
BARRY ISETT & ASSOCIATES
570-688-8268 dalehandelong@hotmail.com
MEP ENGINEER OF RECORD:
5420 Crackersport Rd Allentown, PA 18104
610-437-0978 EMAIL: dhorsfield@barryisett.com
BASE ENGINEERING
AMERICAN NATIONAL STANDARDS INSTITUTE A117.1-2009
3 3
5% 25% 5% 33%
25% 30%
LEGEND
1 HOUR FIRE RATED PARTITION
2 HOUR FIRE WALL
EXIST SIGN WITH DIRECTIONAL ARROW
EXIT SIGN WITH EMERGENCY LIGHTS
AND BATTERY PAK
EMERGENCY LIGHTS WITH BATTERY PAK
DUAL HEAD
EMERGENCY LIGHTS W/ BATTERY PACK
SINGLE HEAD
EMERGENCY LIGHTS REMOTE HEADS
DUAL HEAD
EMERGENCY LIGHTS REMOTE HEADS
SINGLE HEAD
3 EXITS RE4UIRED
3 EXITS PROVIDED
5A
EXISTING
TOILET
ROOM
EXISTING SIREN
POLES
D1
EXISTING
KITCHEN
EXISTING
BANQUET HALL
EXISTING
MULTI-PURPOSE
ROOM
EXISTING
SNACK BOOTH
EXISTING
MECHANICAL EXISTING
GARAGE
EXISTING
OFFICE
EXISTING
MEETING ROOM
EXISTING
STORAGE
EXISTING
ENGINE ROOM
EXISTING
TOILET ROOM
EXISTING SHED
EXISTING
OFFICE
EXISTING
BOILER
D9
D8
D4 D7
D5
D4
D3
D2
3'-4"51'-3" 10'-9 3/4" 9'-4"
5' -2
/4
5'
-4 1/
2"
EX
EX EX
EX
EXEX
EX
EXEX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
D6 D10
D7
EX
V.
I.F
14'-6 5/8" 3'-4" 19'-3 7/16" 6'-8 5/8"
EX
EX
D14
D15
EXISTING SIREN
POLES
D1
MODELNUMBERTRADENAMEPRODUCTMATERIAL
MODELNUMBERTRADENAMEPRODUCTMATERIAL
D13
D11 D12
MODELNUMBERTRADENAMEPRODUCTMATERIAL
EX
D14
DEMOLITION
PLAN
A1.3
SCALE:1 PHASE 1 - DEMOLITION PLAN
1/8"=1'-0"
EXISTING STUD WALL
TO BE REMOVED
A. PRIOR TO COMMENCING DEMOLITION
WORK, CONTRACTORS SHALL REVIEW WITH
THE ARCHITECT AND THE OWNER, THE
EXTENT OF ALL DEMOLITION WORK IN
ORDER TO CONFIRM THE CONTRACTORS'
UNDERSTANDING OF THE SCOPE OF WORK
B. IT SHALL BE THE CONTRACTORS SOLE
RESPONSIBILITY TO ACCOMPLISH THE
DEMOLITION IN A SAFE, ORDERLY AND
CAREFUL MANNER. ACCORDINGLY, THE
CONTRACTORS' RESPONSIBILITIES INCLUDE
BUT ARE IN NO WAY LIMITED TO,
EQUIPMENT, BARRICADES & SHORING,
LIGHTING, FIRE PROTECTION, AND THE
PROTECTION OF ADJOINING PROPERTIES,
YARDS, SIDEWALKS, STREETS, PUBLIC
SAFETY
C. USE ALL MEANS NECESSARY TO CONTROL
DUST ON OR NEAR THE WORK.
D. STRUCTURAL COMPONENTS
ENCOUNTERED DURING THE COURSE OF
DEMOLITION WORK WHICH ARE NOT
INDICATED OR IDENTIFIED ON THE PLANS
SHALL REMAIN INTACT. NOTIFY THE
ARCHITECT AND STRUCTURAL ENGINEER,
WHO SHALL DETERMINE THE DISPOSITION
AND & ISSUE SUPPLEMENTARY
INSTRUCTIONS.
E. ALL NEARBY ELEMENTS WHOSE
STRUCTURAL INTEGRITY MAY BE AFFECTED
MUST BE PROPERLY PROTECTED, BRACED
AND SHORED. IF ADJACENT ITEMS
SCHEDULED TO REMAIN ARE DAMAGED,
THE CONTRACTOR MUST SATISFACTORILY
REPAIR OR REPLACE THE DAMAGED ITEM
AT NO ADDITIONAL COST TO THE OWNER.
ITEMS WHICH ARE TO BE RETAINED AND
WHICH ARE DESTROYED OR REMOVED
SHALL BE REPLACED AT THE EXPENSE OF
THE CONTRACTOR, IF THE LOSS OCCURS
DURING THE TIME THE CONTRACTOR IS
RESPONSIBLE.
F. WHEN NEW ELEMENTS ARE SPECIFIED TO
BE INSTALLED OR CONSTRUCTED, THE
EXISTING ELEMENTS IN THE WAY OF THE
NEW INSTALLATION OR CONSTRUCTION
MUST BE REMOVED.
G. REMOVE EXISTING MECHANICAL,
ELECTRICAL, AND PLUMBING FIXTURES,
EQUIPMENT AND ACCESSORIES,
DISTRIBUTION LINES, AND SERVICES TO THE
EXTENT REQUIRED FOR INSTALLATION OF
NEW COMPONENTS AND SYSTEMS. SUCH
REMOVAL SHALL BE ACCOMPLISHED BY
THE CONTRACTOR RESPONSIBLE FOR THAT
TRADE. PATCHING SHALL BE DONE BY THE
GENERAL CONTRACTOR UNLESS NOTED
OTHERWISE. PATCHING TO MATCH
SURROUNDING MATERIALS.
H. ALL DEBRIS MUST BE REMOVED IN ITS
ENTIRETY FROM THE FROM THE PROPERTY
AND DISPOSED OF IN A SAFE AND PROPER
MANNER. THIS INCLUDES, BUT IS NOT
LIMITED TO, EXPOSED MECHANICAL
ELEMENTS, HANGERS, FITTINGS, PLUMBING
FIXTURES, APPLIANCES AND EQUIPMENT
NOT SCHEDULED FOR RE-USE. CONDUCT
LOADING IN A CAREFUL MANNER TO KEEP
THE ROUTE TO THE DISPOSAL AREA FREE
OF DEBRIS. AT COMPLETION, CLEAN THE
AREA INVOLVED AND LEAVE IT IN A NEAT
CONDITION.
I. USE ALL MEANS NECESSARY TO CONTROL
DUST ON OR NEAR THE WORK.
J. RECYCLE ALL MATERIALS APPROPRIATELY
GENERAL
DEMOLITION NOTES
EXISTING WALL TO REMAIN
WALL LEGEND
3515 Sunnyside Road Center Valley, PA 18034
T: 610-297-0140 E: sam@scf-arch.com These documents are instruments of the Architect's service for use solely with respect to this project.
The Architect shall retain all common law, statutory and other reserved rights, including the copyright.
They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect.
L LC
STRUCTURAL ENGINEER OF RECORD:
101 NORTH QUEBEC STREET
ALLENTOWN, PA, 18109)
610-437-0978 bcohen@baseeng.com
M O
U N
T
BE
TH
EL
F
IR
E
CO
AD
DI
TI
O N
T O
E
XI
ST
IN
G
FI
RE
C
O M
PA
N
Y
N or th
D el aw ar e Dr iv e, M t.
Be th el , P
A
U pp er M ou nt
B et he l, N or th am pt on
C ou nt y
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
DRAWN BY:
BID DOCUMENTS
6/23/2026
REV1
REV2
OWNER:
Mt. Bethel Fire Co.
ML, SCF
BARRY ISETT & ASSOCIATES
570-688-8268 dalehandelong@hotmail.com
MEP ENGINEER OF RECORD:
5420 Crackersport Rd Allentown, PA 18104
610-437-0978 EMAIL: dhorsfield@barryisett.com
BASE ENGINEERING
GENERAL CONTRACTOR TO
DETERMINE FIRE-RATING OF EXISTING
DOORS. REPLACE DOOR & FRAMES IF
RATING IS LESS THAN 90 MIN.
REMOVE EXISTING TOILET.
TEMPORARILY CAP DRAIN & WATER
LINES (FOR NEW FIXTURE TO BE
REPLACED AT SAME LOCATION).
REMOVE EXISTING URINALS. CAP
DRAINS & WATER LINES
REMOVE EXISTING TOILET
PARTITIONS.
REMOVE EXISTING SINK.
TEMPORARILY CAP DRAIN & WATER
LINES (FOR NEW FIXTURE TO BE
REPLACED AT SAME LOCATION).
REMOVE EXISTING TOILETS. PLUMBER
TO DETERMINE WHICH
WATER/DRAIN LINES WILL BE
SCHEDULED FOR REUSE. LINES
SCHEDULED FOR REUSE SHALL BE
TEMPORARILY CAPPED. ALL OTHER
LINES TO BE PERMANENTLY
CAPPED/SEALED.
REMOVE PORTION OF EXISTING
WALL TO ACCOMMODATE NEW
DOOR.
REMOVE EXISTING RAMP & ALL OF
ITS COMPONENTS. PIPE HANDRAIL
TO BE SALVAGED FOR REUSE AS A
NEW GUARDRAIL AND A HANDRAIL
FOR STAIR
REMOVE EXISTING HVAC UNIT.
REMOVE EXISTING VANITY + SINKS,
CAP DRAIN + WATER LINES
REMOVE EXISTING LANDING AND
ALL SUPPORTING STRUCTURE BELOW
REMOVE PHASE 1 STAIR
REMOVE STUCCO FINISH AND ALL OF
ITS COMPONENTS FROM FACE OF
EXTERIOR SHEATHING. CLEAN FACE
OF SHEATHING, REMOVING ALL
DEBRIS AND LEAVING A SMOOTH
FINISH FOR PAINTING
REMOVE EXISTING GRASS, ASPHALT
AND RETAINING WALL FOR NEW
BUILDING FOOTPRINT
EXISTING EXHAUST VENT HERE,
REDIRECT VENTING TO EXTERIOR
DEMOLITION NOTES
D1
D2
D3
D4
D6
D7
D8
D4
D5
D9
D10
SCALE:2 PHASE 2 - DEMOLITION PLAN
1/8"=1'-0"
D11
D12
D13
D14
D15
LOWHIGH
EXISTING DOORS MUST ACHIEVE A
90-MIN FIRE RATING OR MUST BE
REPLACED, V.I.F.
5' -2
1/ 8"
ACCESSIBLE
CHANGING
ACCESSIBLE
SHOWER
MEN
103A 10 2A
1A
5A
WOMEN
'-9
/8
" V .I.F
(10
'-0 " M
IN
6'-4" 2'-1 1/2"
99'-10"
NURSING/
CHANGING
4A
EXISTING CMU
WALL, 2 HR RATED
EXISTING
MULTI-PURPOSE ROOM
ACCESSIBLE
SHOWER
EXISTING
STORAGE
A2.5
60'-0 5/8"
6'-0" 7'-3 5/8" 7'-9 3/4" 6'-7 1/2"
5'-5" 10'-4 5/8"7'-10 3/8" 6'-0" 6'-0" 5'-5 5/8"
4' -1
1 5 /8
CL
EA
R
HA
LL
W
AY
W
ID
TH
68'-6 1/8"
PHASE ONE
5' -6
/8
6'
-2 1/
4"
5' -1
1/ 4"
2' -0
5' -2
8' -2
1/ 4"
3' -4
/4
3' -0
5'
-2
/8
3' -4
1/ 2"
PHASE TWO PHASE ONE
'-7
4' -6
3'
-7
/8
1'- 1"
2' -4
/8
6' -6
3' -0
M
IN
CL
EA
R
5' -0
" C
LE
AR
B A4.1
CHANGING
SILL @ 6'-0" A.F.F. SILL @ 6'-0" A.F.F.
CORRIDOR
"FOLDING PARTITION"
(EXISTING)
3'-4"51'-3"
7A
106A
4" MAX.
MODELNUMBERTRADENAMEPRODUCTMATERIAL
MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL
1B
5' -3
/4
3/
8"
5' -1
SH
O
W
ER
X3
SH
O
W
ER
X3
5' -0
CO
N C.
PA
D
7'-0" CONC. PAD
A A4.1
PHASE 2 - 31'-3 7/8" - SEE SHEET A2.2
'-9
/8
NEW P.T. WOOD STAIR
11" TREADS, 7" MAX. RISERS,
NUMBER OF RISERS AS NEEDED
TO MEET EXISTING GRADE.
SALVAGE PIPE HANDRAIL FROM
EXISTING RAMP AS NEEDED TO
CONSTRUCT NEW GUARDRAIL
AND HANDRAIL FOR STAIR
5' -1
1 1 /2
'-9
/8
5' -2
1/ 2"
3'-0" 3'-11" 29'-3" 3'-11" 28'-5 1/8"
W1 W1 W1 W1
MODELNUMBERTRADENAMEPRODUCTMATERIAL
EX
B/A2.2
EXISTING SIREN
POLES
D1
U-1A
U-9A/B/C
DOWNSPOUT TO
UNDERGROUND
LEADER
GUTTER EXPANSION JOINT
TABLE & CHAIR
STORAGE
EXISTING DOORS MUST ACHIEVE A
90-MIN FIRE RATING OR MUST BE
REPLACED, V.I.F.
EXISTING SHED
'-9
/8
31'-4 1/2"
AREA OF WORK
4' -0
1-
HO
UR
FIR
E
RA
TE
D
RO
O F
A2.1
A2.1
31'-3 7/8"
PHASE TWO
8A
EXISTING
MULTI-PURPOSE ROOM
PHASE 1 - 68'-6 1/8"
2'-9 3/4"
D13
PHASE 2 ROOF
CONTINUOUS METAL FLASHINGLINE OF EXISTING WALL BELOW
SEE PHASE 1
ROOF PLAN ABOVE
FU
LL
Y
AD
HE
RE
D
EP
DM
SY
ST
EM
, C
AR
LIS
LE
S
UR
ES
EA
L O
R
EQ
UA
L
VA
:12
SL
O
PE
A2.3
A, B & C
A2.3
A
D11 D12
U-1A
U-3B
A7.1
A7.1
DURING EMERGENCY EVENT - THIS
ROOM SERVES FAMILIES WITH PETS
THAT REQUIRE SHELTER
MAX. OCCUPANCY 25 PEOPLE
- OWNER SUPPLIED
CRATES/KENNELS CAN BE
STACKED ALONG WALLS
- TEMPORARY DIVIDING
PARTITIONS CAN BE PROVIDED
FOR VISUAL SEPARATION OF
ANIMALS WHEN REQUIRED
D14
ACT CEILING @ 8'-0" AFF
CONTINUOUS P.T. BOTTOM PLATE
MECHANICALLY FASTENED TO
FOUNDATION/SLAB
FLOORING & BASE
(SEE FINISH SCHEDULE)
EXTEND STUD/GWB TO ROOF
STRUCTURE ABOVE, BRACE WHERE
REQUIRED
2X4 WD OR MTL STUD PARTITION
1 HOUR RATINGP2
RATED CORRIDOR SIDE
1 LAYER, 5/8" TYPE "X" GWB (BOTH
SIDES)
(RATED SIDE). SEE FINISH SCHEDULE
FOR FINISHES.
2X4 WD OR MTL STUD PARTITION
1 HOUR RATING & SOUND ATTENUATION BATTSP2A
FIRE CAULKING
FIRE CAULKING
CONTINUE GWB TO UNDERSIDE OF
ROOF DECK ABOVE
1 HOUR RATED TO DECK
CONTINUOUS P.T. BOTTOM PLATE,
MECHANICALLY FASTENED TO
FOUNDATION
NEUTRAL SILICONE
SEALANT TO MATCH WALL FINISH
P2A: SOUND ATTENUATION BATTS
1 LAYER, 5/8" GWB
2X4 WOOD OR METAL STUD @ 16" O.C.
SEE WALL FINISH OPTIONS BELOW
TRIM AT TOP OF WALL AS REQUIRED BY
SELECTED FINISH MATERIAL'S
MANUFACTURER INSTALLATION
REQUIREMENTS
(SEE WALL FINISH OPTIONS BELOW)
NEUTRAL SILICONE
SEALANT TO MATCH WALL FINISH
TOILET ROOM SIDE
2X4 WOOD OR METAL STUD
IMPERVIOUS FINISH ONE SIDE W/ SOUND
ATTENUATION BATTS
P3A
FLOORING & BASE
(SEE FINISH SCHEDULE)
NON-RATED
1 LAYER, 5/8" MRGWB
2X4 WOOD STUD PARTITION
W/SOUND ATTENUATION BATTS
P1A
ROOF DECK ABOVE
CONT. TOP PLATE,
MECHANICALLY FASTENED TO
UNDERSIDE OF ROOF FRAMING
CONTINUE GWB TO ROOF FRAMING
ABOVE
1 LAYER, 5/8" MRGWB
CONTINUOUS P.T. BOTTOM
PLATE, MECHANICALLY
FASTENED TO FOUNDATION
FLOORING & BASE
(SEE FINISH SCHEDULE)
SOUND ATTENUATION BATTS
2X6 WOOD OR METAL STUDS @16" O.C.
NON-RATED
1 LAYER, 5/8" GWB
TOILET ROOM SIDE
ACT CEILING SEE SHEET A7.1 FOR TYPE
ACT CEILING @ 8'-0" AFF
CONTINUOUS P.T. BOTTOM PLATE
MECHANICALLY FASTENED TO
FOUNDATION/SLAB
FLOORING & BASE
(SEE FINISH SCHEDULE)
EXTEND STUD TO ROOF
STRUCTURE ABOVE, BRACE WHERE
REQUIRED
RATED CORRIDOR SIDE
1 LAYER, 5/8" TYPE "X" GWB
FIRE CAULKING
FIRE CAULKING
CONTINUE GWB TO UNDERSIDE OF
ROOF DECK ABOVE
2X4 WD OR MTL STUD PARTITION W/ GWB ONE SIDE +
MRGWB + FIBERGLASS SHOWER INSERT ONE SIDE
1 HOUR RATING
P5A
FIBERGLASS SHOWER INSERT
1 LAYER, 5/8" TYPE "X" MRGWB
EXISTING PARTITION W/ IMPERVIOUS FINISHP4
NEUTRAL SILICONE
SEALANT TO MATCH WALL FINISH
(BOTH SIDES)
FLOORING & BASE
(SEE FINISH SCHEDULE)
EXISTING PARTITION
MRGWB W/ FRP FINISH (SEE WALL
FINISH OPTIONS BELOW) (BOTH SIDES)
SEE WALL FINISH OPTIONS BELOW
(BOTH SIDES)
TRIM AT TOP OF WALL AS REQUIRED BY
SELECTED FINISH MATERIAL'S
MANUFACTURER INSTALLATION
REQUIREMENTS
(SEE WALL FINISH OPTIONS BELOW)
(BOTH SIDES)
NEUTRAL SILICONE
SEALANT TO MATCH WALL FINISH
(BOTH SIDES)
A2.5
RENOVATED
TOILET/EXTRACTOR ROOM
9A
MODELNUMBERTRADENAMEPRODUCTMATERIAL
EXTRACTOR
EXISTING WALL NEW ROOF DECKING EXTEND TO
EXISTING WALL
FIRE CAULKING
2 LAYERS 5/8" TYPE "X"
GWB
EXISTING EXTERIOR WALL,
REMOVE EXTERIOR FINISHES
TO FACE OF STRUCTURE.
C-T STUD
FIRE CAULKING
FLOORING & BASE
(SEE FINISH SCHEDULE)
6 5/8"
2HR FIRE WALL
GA FILE #WP1711/ UL DESIGN NO. U411
P6
(2) LAYERS 1" SHAFT
WALL LINER
METAL TRACK
FASTENED TO SLAB
1-HR RATED 2X4 WD OR MTL STUD
IMPERVIOUS FINISH BOTH SIDES, W/ SOUND
ATTENUATION BATTS
P7A
CONTINUOUS P.T. BOTTOM PLATE,
MECHANICALLY FASTENED TO FOUNDATION
NEUTRAL SILICONE SEALANT TO MATCH
WALL FINISH (BOTH SIDES)
P2A: SOUND ATTENUATION BATTS
FLOORING & BASE
(SEE FINISH SCHEDULE)
2X4 WOOD OR METAL STUD @ 16" O.C.
5/8" MOISTURE RESISTANT GWB (SEE WALL
FINISH OPTIONS BELOW) (BOTH SIDES)(TYPE X
WHERE INDICATED)
SEE WALL FINISH OPTIONS BELOW (BOTH SIDES)
TRIM AT TOP OF WALL AS REQUIRED BY SELECTED FINISH
MATERIAL'S MANUFACTURER INSTALLATION REQUIREMENTS(SEE
WALL FINISH OPTIONS BELOW)
(BOTH SIDES)
NEUTRAL SILICONE SEALANT TO MATCH WALL
FINISH (BOTH SIDES)
FRP PANELS
P7A, CONTINUE MRGWB TO BOTTOM OF
ROOF DECK BOTH SIDES FOR RATED
WALL SYSTEM
ACT CEILING @ 8'-0" AFF
CONTINUOUS BOTTOM PLATE
MECHANICALLY FASTENED TO
FOUNDATION/SLAB
FLOORING & BASE
(SEE FINISH SCHEDULE)
EXTEND STUD TO ROOF
STRUCTURE ABOVE, BRACE WHERE
REQUIRED
2X4 WD OR MTL STUD PARTITION W/ GWB ONE SIDE
MRGWB+ FRP ONE SIDE
1 HOUR RATING
P8
RATED CORRIDOR SIDE
1 LAYER, 5/8" TYPE "X" GWB (BOTH
SIDES)
(RATED SIDE). SEE FINISH SCHEDULE
FOR FINISHES.
FIRE CAULKING
FIRE CAULKING
CONTINUE GWB TO UNDERSIDE OF
ROOF DECK ABOVE (BOTH SIDES)
FRP, INSTALLED PER MFGR'S
REQUIREMENTS. USE MFGR'S
RECOMMENDED FASTENING SYSTEM
1 LAYER, 5/8" TYPE "X" MRGWB. SEE
FINISH SCHEDULE FOR FINISHES.
LEAVE 1/4" GAP BETWEEN BOTTOM OF FRP
AND FLOOR
VINYL BASE (SEE FINISH SCHEDULE)
NEUTRAL SILICONE SEALANT TO
MATCH WALL FINISH
CONTINUOUS P.T. BOTTOM PLATE MECHANICALLY
FASTENED TO FOUNDATION/SLAB
ACT CEILING @ 8'-0" AFF
CONTINUOUS P.T. BOTTOM PLATE
MECHANICALLY FASTENED TO
FOUNDATION/SLAB
FLOORING & BASE
(SEE FINISH SCHEDULE)
EXTEND STUD/GWB TO ROOF
STRUCTURE ABOVE, BRACE WHERE
REQUIRED
2X4 WD OR MTL STUD PARTITION W/ MRGWB BOTH SIDE + FRP ONE SIDE
NON-RATEDP11
RATED CORRIDOR SIDE
1 LAYER, 5/8" TYPE "X" GWB (BOTH
SIDES)
(RATED SIDE). SEE FINISH SCHEDULE
FOR FINISHES.
FIRE CAULKING
FIRE CAULKING
CONTINUE GWB TO UNDERSIDE OF
ROOF DECK ABOVEACT CEILING @ 8'-0" AFF
CONTINUOUS P.T. BOTTOM PLATE
MECHANICALLY FASTENED TO
FOUNDATION/SLAB
FLOORING & BASE
(SEE FINISH SCHEDULE)
EXTEND STUD TO ROOF
STRUCTURE ABOVE, BRACE WHERE
REQUIRED
2X4 WD OR MTL STUD PARTITION W/ MRGWB BOTH
SIDES + FRP ONE SIDE + FIBERGLASS SHOWER INSERT
NON-RATED
P10
RATED CORRIDOR SIDE
1 LAYER, 5/8" TYPE "X" GWB (BOTH
SIDES)
(RATED SIDE+WATER RESISITANT
SIDE). SEE FINISH SCHEDULE FOR
FINISHES.
FIRE CAULKING
CONTINUE GWB TO UNDERSIDE OF
ROOF DECK ABOVE
SEE WALL FINISH OPTIONS
BELOW (BOTH SIDES)
2X4 WD OR MTL STUD
IMPERVIOUS FINISH BOTH SIDES
P9
CONTINUOUS P.T. BOTTOM PLATE,
MECHANICALLY FASTENED TO FOUNDATION
NEUTRAL SILICONE SEALANT TO MATCH WALL FINISH (BOTH SIDES)
SOUND ATTENUATION BATTS
FLOORING & BASE
(SEE FINISH SCHEDULE)
2X4 WOOD OR METAL STUD @ 16" O.C.
5/8" MOISTURE RESISTANT GWB (SEE WALL
FINISH OPTIONS BELOW) (BOTH SIDES)(TYPE X
WHERE INDICATED)
SEE WALL FINISH OPTIONS BELOW (BOTH SIDES)
TRIM AT TOP OF WALL AS REQUIRED BY SELECTED FINISH
MATERIAL'S MANUFACTURER INSTALLATION REQUIREMENTS(SEE
WALL FINISH OPTIONS BELOW)
(BOTH SIDES)
NEUTRAL SILICONE SEALANT TO MATCH WALL
FINISH (BOTH SIDES)
FRP PANELS
FLOOR PLANS
PHASE 1
A2.1
SCALE:1 FLOOR PLAN @ NEW TOILET ROOM ADDITION
1/4"=1'-0"
EXISTING WALL TO REMAIN
NEW STUD WALL
NEW MASONRY WALL
HIDDEN ABOVE
HIDDEN BELOW
W0
DOOR TAG
WINDOW TAG
PARTITION TYPE TAG
C-0 CONSTRUCTION NOTE KEY TAG
LEGEND
000A
A4.3
A4.2
A A4.1
A A4.1
+ 9'-5" PARTITION TYPE TAG
CONSTRUCTION NOTE KEY TAG
ELEVATION MARKER
SECTION DETAIL MARKER
SECTION MARKER
3515 Sunnyside Road Center Valley, PA 18034
T: 610-297-0140 E: sam@scf-arch.com These documents are instruments of the Architect's service for use solely with respect to this project.
The Architect shall retain all common law, statutory and other reserved rights, including the copyright.
They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect.
L LC
STRUCTURAL ENGINEER OF RECORD:
101 NORTH QUEBEC STREET
ALLENTOWN, PA, 18109)
610-437-0978 bcohen@baseeng.com
M O
U N
T
BE
TH
EL
F
IR
E
CO
AD
DI
TI
O N
T O
E
XI
ST
IN
G
FI
RE
C
O M
PA
N
Y
N or th
D el aw ar e Dr iv e, M t.
Be th el , P
A
U pp er M ou nt
B et he l, N or th am pt on
C ou nt y
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
DRAWN BY:
BID DOCUMENTS
6/23/2026
REV1
REV2
OWNER:
Mt. Bethel Fire Co.
ML, SCF
BARRY ISETT & ASSOCIATES
570-688-8268 dalehandelong@hotmail.com
MEP ENGINEER OF RECORD:
5420 Crackersport Rd Allentown, PA 18104
610-437-0978 EMAIL: dhorsfield@barryisett.com
BASE ENGINEERING
SCALE:
KEY PLAN
1/32"=1'-0"
SCALE:2 FLOOR PLAN @ RENOVATED EXTRACTOR ROOM 109
1/4"=1'-0"
PARTITION TYPES
EXISTING DOOR
NEW DOOR
AutoCAD SHX Text
EW2
AutoCAD SHX Text
EW1
AutoCAD SHX Text P3A
AutoCAD SHX Text P2A
AutoCAD SHX Text P2A
AutoCAD SHX Text P2A
AutoCAD SHX Text P2A
AutoCAD SHX Text P1A
AutoCAD SHX Text P1A
AutoCAD SHX Text P2A
AutoCAD SHX Text P6
AutoCAD SHX Text P6
AutoCAD SHX Text
EW1
AutoCAD SHX Text
EW2
AutoCAD SHX Text P9
AutoCAD SHX Text P9
AutoCAD SHX Text P9
AutoCAD SHX Text P9
AutoCAD SHX Text P10
AutoCAD SHX Text P10
AutoCAD SHX Text P9
AutoCAD SHX Text P7A
AutoCAD SHX Text P3A
AutoCAD SHX Text P1A
AutoCAD SHX Text P2A
AutoCAD SHX Text P2
AutoCAD SHX Text
EW1
AutoCAD SHX Text P11
AutoCAD SHX Text P7A
AutoCAD SHX Text P1A
AutoCAD SHX Text P10
AutoCAD SHX Text P10
AutoCAD SHX Text P10
AutoCAD SHX Text P5A
AutoCAD SHX Text P8
AutoCAD SHX Text P6
AutoCAD SHX Text P6
AutoCAD SHX Text
EW1
AutoCAD SHX Text
EW1
AutoCAD SHX Text P9
AutoCAD SHX Text P3A
AutoCAD SHX Text P3A
AutoCAD SHX Text P4
AutoCAD SHX Text P4
AutoCAD SHX Text P4
AutoCAD SHX Text P4
AutoCAD SHX Text P4
AutoCAD SHX Text P4
AutoCAD SHX Text P2
AutoCAD SHX Text P0
TABLE & CHAIR
STORAGE
EXISTING DOORS MUST ACHIEVE A
90-MIN FIRE RATING OR MUST BE
REPLACED, V.I.F.
'-9
/8
31'-4 1/2"
31'-3 7/8"
PHASE TWO
8A
MODELNUMBERTRADENAMEPRODUCTMATERIAL
MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL MODELNUMBERTRADENAMEPRODUCTMATERIAL
EXISTING
MULTI-PURPOSE ROOM
PHASE 1 - 68'-6 1/8"
2'-9 3/4"
MODELNUMBERTRADENAMEPRODUCTMATERIAL
DURING EMERGENCY EVENT - THIS
ROOM SERVES FAMILIES WITH PETS
THAT REQUIRE SHELTER
MAX. OCCUPANCY 25 PEOPLE
- OWNER SUPPLIED
CRATES/KENNELS CAN BE
STACKED ALONG WALLS
- TEMPORARY DIVIDING
PARTITIONS CAN BE PROVIDED
FOR VISUAL SEPARATION OF
ANIMALS WHEN REQUIRED
EX
CONTINUOUS BOTTOM PLATE,
MECHANICALLY FASTENED TO FOUNDATION
CLEAR SILICON CAULK
PHASE 1/EXISTING - R-20 FIBERGLASS BATT
OR MINERAL WOOL INSULATION
2X6 WD OR MTL STUD
INTERIOR FINISH ON PHASE 1 EXTERIOR WALL
P9
4" VINYL BASE
PHASE 1/EXISTING - 2X6 WOOD OR
METAL STUD @ 16" O.C.
CONT. TOP PLATE
PRIME AND PAINT EXISTING EXTERIOR
SHEATHING. IF SURFACE OF SHEATHING IS
DAMAGED TO THE POINT THAT IT WILL NOT
PROVIDE A SMOOTH FINISH SURFACE, APPLY
1/2" IMPACT RESISTANT GWB, PRIME AND PAINT
EXISTING WALL NEW ROOF DECKING EXTEND TO
EXISTING WALL
FIRE CAULKING
2 LAYERS 5/8" TYPE "X"
GWB
EXISTING EXTERIOR WALL,
REMOVE EXTERIOR FINISHES
TO FACE OF STRUCTURE.
C-T STUD
FIRE CAULKING
FLOORING & BASE
(SEE FINISH SCHEDULE)
6 5/8"
2HR FIRE WALL
GA FILE #WP1711/ UL DESIGN NO. U411
P6
(2) LAYERS 1" SHAFT
WALL LINER
METAL TRACK
FASTENED TO SLAB
5/8" GWB (SEE FINISH
SCHEDULE)
R-20 MIN, FIBERGLASS BATT OR MINERAL
WOOL INSULATION W/ VAPOR BARRIER
ON INTERIOR SIDE
2X6 STUDS @ 16" O.C
5/8" DENSGLASS SHEATHING
(2) LAYERS #15 BUILDING PAPER
EIFS ELASTOMERIC
FINISH + BASE COATS
2X6 EXTERIOR WALL - GWB INTERIOR FINISH
5/8" MRGWB (SEE WALL FINISH
SCHEDULE)
R-20 MIN, FIBERGLASS BATT OR MINERAL
WOOL INSULATION W/ VAPOR BARRIER
ON INTERIOR SIDE
2X6 STUDS @ 16" O.C
5/8" DENSGLASS SHEATHING
(2) LAYERS #15 BUILDING PAPER
EIFS ELASTOMERIC
FINISH + BASE COATS
SEE IMPERVIOUS WALL FINISH
OPTION, SHEET A7.1
2X6 EXTERIOR WALL WITH IMPERVIOUS WALL FINISH ON INTERIOR SIDE
SEE IMPERVIOUS WALL FINISH OPTIONS, THIS PAGE
EW2
EW1
METAL LATH
2" RIGID INSULATION
2" RIGID INSULATION
METAL LATH
FLOOR PLANS
PHASE 2
A2.2
SCALE:1 FLOOR PLAN - PHASE 2
1/4"=1'-0"
EXISTING WALL TO REMAIN
NEW STUD WALL
NEW MASONRY WALL
HIDDEN ABOVE
HIDDEN BELOW
W0
DOOR TAG
WINDOW TAG
PARTITION TYPE TAG
C-0 CONSTRUCTION NOTE KEY TAG
LEGEND
000A
A4.3
A4.2
A A4.1
A A4.1
+ 9'-5" PARTITION TYPE TAG
CONSTRUCTION NOTE KEY TAG
ELEVATION MARKER
SECTION DETAIL MARKER
SECTION MARKER
3515 Sunnyside Road Center Valley, PA 18034
T: 610-297-0140 E: sam@scf-arch.com These documents are instruments of the Architect's service for use solely with respect to this project.
The Architect shall retain all common law, statutory and other reserved rights, including the copyright.
They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect.
L LC
STRUCTURAL ENGINEER OF RECORD:
101 NORTH QUEBEC STREET
ALLENTOWN, PA, 18109)
610-437-0978 bcohen@baseeng.com
M O
U N
T
BE
TH
EL
F
IR
E
CO
AD
DI
TI
O N
T O
E
XI
ST
IN
G
FI
RE
C
O M
PA
N
Y
N or th
D el aw ar e Dr iv e, M t.
Be th el , P
A
U pp er M ou nt
B et he l, N or th am pt on
C ou nt y
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
DRAWN BY:
BID DOCUMENTS
6/23/2026
REV1
REV2
OWNER:
Mt. Bethel Fire Co.
ML, SCF
BARRY ISETT & ASSOCIATES
570-688-8268 dalehandelong@hotmail.com
MEP ENGINEER OF RECORD:
5420 Crackersport Rd Allentown, PA 18104
610-437-0978 EMAIL: dhorsfield@barryisett.com
BASE ENGINEERING
EXISTING DOOR
NEW DOOR
EXTERIOR WALL TYPES
AutoCAD SHX Text P6
AutoCAD SHX Text
EW1
AutoCAD SHX Text
EW1
AutoCAD SHX Text P9
P0
U-8A
U-1A
GUTTER EXPANSION JOINT AS
REQUIRED
CONTINUOUS METAL FLASHING
LINE OF EXISTING WALL BELOW
4'-0"
1-HOUR
FIRE RATED
ROOF
4' -0
1-
HO
UR
FIR
E
RA
TE
D
RO
O F
M
IN
APPROX LOCATION OF NEW ELECTRICAL/MECHANICAL
ROOFTOP UNITS (RTU)
SEE MEP/STRUCTURAL PLANS + DETAILS
FU
LL
Y
AD
HE
RE
D
EP
DM
SY
ST
EM
, C
AR
LIS
LE
S
UR
ES
EA
L O
R
EQ
UA
L
VA
:12
SL
O
PE
DOWNSPOUT TO
UNDERGROUND
LEADER
DOWNSPOUT TO
UNDERGROUND
LEADER
RTUERV-1
3,500 LBS
CU-1
975 LBS
CU-2
1135 LBS
U-12A U-5C
U-2A
A/A2.2
U-9A/B/C
U-12A U-5C
U-12A U-5C
EXISTING
HVAC
B/A2.2
U-1A
4' -0
1-
HO
UR
FIR
E
RA
TE
D
RO
O F
U-1A
U-3B
SEE SHEET A2.5 FOR ROOF LEGEND
B/A2.2
U-1A
U-9A/B/C
DOWNSPOUT TO
UNDERGROUND
LEADER
GUTTER EXPANSION JOINT
4' -0
1-
HO
UR
FIR
E
RA
TE
D
RO
O F
EXISTING
HVAC
PHASE 2 ROOF
CONTINUOUS METAL FLASHINGLINE OF EXISTING WALL BELOW
SEE PHASE 1
ROOF PLAN ABOVE
FU
LL
Y
AD
HE
RE
D
EP
DM
SY
ST
EM
, C
AR
LIS
LE
S
UR
ES
EA
L O
R
EQ
UA
L
VA
:12
SL
O
PE
A2.3
A, B & C
A2.3
A
U-1A
U-3B
SEE CARLISLE ROOF DETAIL U2-A ON SHEET
A2.4 FOR EPDM ROOF SPLICE DETAIL
FULLY ADHERED EPDM SYSTEM.
CARLISLE SURESEAL OR EQUAL.
MATCH PHASE 1 EPDM.
11-7/8" TJII JOISTS @ 16" O.C.
DOUBLE TOP PLATE
BUILT UP BLOCKING AS REQUIRED
3/4" PLYWOOD
R-30 POLYISOCYANURATE
RIGID INSULATION
METAL WRAPPED WOOD FASCIA, COLOR
AND METAL TO MATCH EXISTING ROOF,
METAL GAUGE SHALL BE
22 (PREFERRED)
OR 24 GA
SEALANT
FULLY ADHERED EPDM SYSTEM.
CARLISLE SURESEAL OR EQUAL
CONT. METAL DRIP
EDGE
SEE EXTERIOR WALL
TYPES FOR WALL
CONSTRUCTION
A. PHASE 1 B. PHASE 2 - DEMOLITION C. PHASE 2 - NEW CONSTRUCTION
EXISTING WALL AND
ROOF STRUCTURE TO
REMAIN IN PLACE
REMOVE WOOD BLOCKING
REMOVE EXISTING METAL
WRAPPED WOOD FASCIA,
CONT. METAL DRIP
EDGE
REMOVE STUCCO FINISH FROM
EXTERIOR SIDE OF WALL. CLEAR ALL
DEBRIS/ADHESIVES FROM EXTERIOR
SHEATHING.
GALVANIZED WATER
DAM
REMOVE GALVANIZED
WATER DAM
REMOVE EPDM AND CUT BACK RIGID INSULATION TO
CREATE CLEAN EDGE TO BUTT NEW INSULATION UP TO
1X WOOD RIM JOIST
(WILL SUPPORT EDGE OR FUTURE
PLYWOOD)
PRIME AND PAINT EXISTING EXTERIOR
SHEATHING. IF SURFACE OF SHEATHING IS
DAMAGED TO THE POINT THAT IT WILL NOT
PROVIDE A SMOOTH FINISH SURFACE, APPLY
1/2" IMPACT RESISTANT GWB, PRIME AND PAINT
R-30 POLYISOCYANURATE
RIGID INSULATION
3/4" PLYWOOD
SEE STRUCTURAL FOR ROOF
FRAMING
PHASE 2 ROOF ASSEMBLYPHASE 1 ROOF ASSEMBLY
ROOF PLAN
A2.3
SCALE:1 ROOF PLAN - PHASE 1
1/4"=1'-0"
1 HOUR RATED ROOF LOCATIONS
LINE OF WALL BELOW
GUTTERS: PREFINISHED ALUMINUM,
K-STYLE, GAUGE PER SMACNA
REQUIREMENTS FOR TOTAL GIRTH
D.S.= DOWNSPOUT, PREFINISHED
ALUMINUM CORRUGATED
RECTANGULAR,
MTL GAUGE PER SMACNA
(SEE ELEVATIONS FOR D.S.
LOCATIONS)
COLOR: WHITE
PROVIDE CONTINUOUS ALUMINUM
FLASHING @ VERTICAL
CONNECTION OF NEW
ROOF/GARAGE WALL/WALL
EDPM ROOFING MEMBRANE
SYSTEM, CLASS B MIN.
DIRECTIONAL ARROW INDICATING
DIRECTION OF WATER DRAINAGE
ON SITE
ROOF TYPE, SEE A2.4 FOR DETAILS
ROOF PLAN LEGEND
DR
AI
N
DO
W
NS
PO
UT
S
AW
AY
FR
OM
B
UI
LD
IN
G
3515 Sunnyside Road Center Valley, PA 18034
T: 610-297-0140 E: sam@scf-arch.com These documents are instruments of the Architect's service for use solely with respect to this project.
The Architect shall retain all common law, statutory and other reserved rights, including the copyright.
They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect.
L LC
STRUCTURAL ENGINEER OF RECORD:
101 NORTH QUEBEC STREET
ALLENTOWN, PA, 18109)
610-437-0978 bcohen@baseeng.com
M O
U N
T
BE
TH
EL
F
IR
E
CO
AD
DI
TI
O N
T O
E
XI
ST
IN
G
FI
RE
C
O M
PA
N
Y
N or th
D el aw ar e Dr iv e, M t.
Be th el , P
A
U pp er M ou nt
B et he l, N or th am pt on
C ou nt y
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
DRAWN BY:
BID DOCUMENTS
6/23/2026
REV1
REV2
OWNER:
Mt. Bethel Fire Co.
ML, SCF
BARRY ISETT & ASSOCIATES
570-688-8268 dalehandelong@hotmail.com
MEP ENGINEER OF RECORD:
5420 Crackersport Rd Allentown, PA 18104
610-437-0978 EMAIL: dhorsfield@barryisett.com
BASE ENGINEERING
SCALE:2 ROOF PLAN - PHASE 2
1/4"=1'-0"
SCALE:3 ROOF PLAN - PHASE 2
1/4"=1'-0"
U-XX
ROOF
DETAILS
A2.4
3515 Sunnyside Road Center Valley, PA 18034
T: 610-297-0140 E: sam@scf-arch.com These documents are instruments of the Architect's service for use solely with respect to this project.
The Architect shall retain all common law, statutory and other reserved rights, including the copyright.
They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect.
L LC
STRUCTURAL ENGINEER OF RECORD:
101 NORTH QUEBEC STREET
ALLENTOWN, PA, 18109)
610-437-0978 bcohen@baseeng.com
M O
U N
T
BE
TH
EL
F
IR
E
CO
AD
DI
TI
O N
T O
E
XI
ST
IN
G
FI
RE
C
O M
PA
N
Y
N or th
D el aw ar e Dr iv e, M t.
Be th el , P
A
U pp er M ou nt
B et he l, N or th am pt on
C ou nt y
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
DRAWN BY:
BID DOCUMENTS
6/23/2026
REV1
REV2
OWNER:
Mt. Bethel Fire Co.
ML, SCF
BARRY ISETT & ASSOCIATES
570-688-8268 dalehandelong@hotmail.com
MEP ENGINEER OF RECORD:
5420 Crackersport Rd Allentown, PA 18104
610-437-0978 EMAIL: dhorsfield@barryisett.com
BASE ENGINEERING
K:\_ 00 Australia (DONT ERASE THIS)\CARLISLE\LOGOS\Carlisle SynTec Systems Logo_Dec 2011-For Print.jpg
K:\_ 00 Australia (DONT ERASE THIS)\CARLISLE\LOGOS\Carlisle SynTec Systems Logo_Dec 2011-For Print.jpg K:\_ 00 Australia (DONT ERASE THIS)\CARLISLE\LOGOS\Carlisle SynTec Systems Logo_Dec 2011-For Print.jpg
K:\_ 00 Australia (DONT ERASE THIS)\CARLISLE\LOGOS\Carlisle SynTec Systems Logo_Dec 2011-For Print.jpg
K:\_ 00 Australia (DONT ERASE THIS)\CARLISLE\LOGOS\Carlisle SynTec Systems Logo_Dec 2011-For Print.jpg
K:\_ 00 Australia (DONT ERASE THIS)\CARLISLE\LOGOS\Carlisle SynTec Systems Logo_Dec 2011-For Print.jpg
K:\_ 00 Australia (DONT ERASE THIS)\CARLISLE\LOGOS\Carlisle SynTec Systems Logo_Dec 2011-For Print.jpg
AutoCAD SHX Text AT CORNERS, 6" (15cm) WIDE PRESSURE-SENSITIVE RUSS MUST BE INSTALLED 12" (30cm) MAXIMUM FROM THE BASE OF THE WATER DAM AND EXTEND 36" (90cm) MINIMUM IN EACH DIRECTION.
AutoCAD SHX Text 12" (30cm) O.C.
AutoCAD SHX Text 36" (90cm) O.C.
AutoCAD SHX Text
CORNER REINFORCEMENT
AutoCAD SHX Text NOTE: 1. MAXIMUM MEMBRANE THICKNESS GOING OVER MAXIMUM MEMBRANE THICKNESS GOING OVER THE WATER DAM IS 60-MIL. FOR THICKER MEMBRANES, RUN FIELD SHEET UNDER THE WATER DAM AND STRIP-IN WITH MAXIMUM 60-MIL MEMBRANE. 2. USE MF-1A FOR MECHANICALLY FASTENED USE MF-1A FOR MECHANICALLY FASTENED MF-1A FOR MECHANICALLY FASTENED FOR MECHANICALLY FASTENED SYSTEMS AND B-1A FOR BALLASTED SYSTEMS.B-1A FOR BALLASTED SYSTEMS. FOR BALLASTED SYSTEMS.
AutoCAD SHX Text U-1A
AutoCAD SHX Text CARLISLE SecurEDGE 200
AutoCAD SHX Text 1-1/2" (38mm) RING-SHANK NAIL @ 6" (15cm) O.C.
AutoCAD SHX Text SecurEdge 200 METAL FASCIA OR METAL FASCIA BY OTHERS
AutoCAD SHX Text
PRESSURE-SENSITIVE T-JOINT COVER AND EPDM PRIMER
AutoCAD SHX Text
AutoCAD SHX Text
GALVANIZED WATER DAM
AutoCAD SHX Text
WOOD NAILER BY OTHERS
AutoCAD SHX Text
LAP SEALANT
AutoCAD SHX Text
MEMBRANE SEAM AT EDGE
AutoCAD SHX Text
MAXIMUM WARRANTY: 20 YEARS
AutoCAD SHX Text
THERMOSET MEMBRANE
AutoCAD SHX Text
EPDM
AutoCAD SHX Text
DETAIL NO.
AutoCAD SHX Text
THERMOSET UNIVERSAL
AutoCAD SHX Text 2022 Carlisle SynTec a division of Carlisle Construction Materials Incorporated
AutoCAD SHX Text C
AutoCAD SHX Text NOTES: 1. OVERLAP THE ENDS OF THE FIELD APPLIED SecurTAPE A OVERLAP THE ENDS OF THE FIELD APPLIED SecurTAPE A MINIMUM OF 1" (2.5cm). APPLY LAP SEALANT AT TAPE OVERLAPS 2" (5cm) IN EACH DIRECTION AS SHOWN. 2. APPLY LAP SEALANT ALONG THE EXPOSED EDGE OF THE APPLY LAP SEALANT ALONG THE EXPOSED EDGE OF THE MEMBRANE SPLICE COVERING THE EXPOSED SPLICE TAPE 1/2" (1.5cm) IN EACH DIRECTION FROM THE SPLICE INTERSECTION AND OVERLAY WITH A 6" (15cm) T-JOINT COVER. 3. WHEN USING 90-MIL MEMBRANE, INSTALL A 12" (30cm) WHEN USING 90-MIL MEMBRANE, INSTALL A 12" (30cm) T-JOINT COVER CENTERED OVER THE FIRST T-JOINT COVER PER DETAIL U-2B.1. U-2B.1. . 4. LAP SEALANT IS REQUIRED ON CUT EDGES OF REINFORCED LAP SEALANT IS REQUIRED ON CUT EDGES OF REINFORCED EPDM MEMBRANE. 5. REFER TO DETAIL MF-2A FOR MECHANICALLY FASTENED REFER TO DETAIL MF-2A FOR MECHANICALLY FASTENED MF-2A FOR MECHANICALLY FASTENED FOR MECHANICALLY FASTENED SPLICES.
AutoCAD SHX Text
EPDM MEMBRANE SPLICE
AutoCAD SHX Text U-2A
AutoCAD SHX Text 3" (15cm) FACTORY-APPLIED TAPE AND EPDM PRIMER
AutoCAD SHX Text MIN. 3" (7.5cm) WIDE SecurTAPE AND EPDM PRIMER
AutoCAD SHX Text F.A.T.
AutoCAD SHX Text
EPDM PRIMER
AutoCAD SHX Text
EPDM PRIMER
AutoCAD SHX Text FIELD APPLIED SecurTAPE
AutoCAD SHX Text
TAPE OVERLAP
AutoCAD SHX Text
LAP SEALANT
AutoCAD SHX Text
LAP SEALANT BELOW THE T-JOINT COVER
AutoCAD SHX Text 1/8" (0.5cm) TO 1/2" (1.5cm) MAX.
AutoCAD SHX Text
AutoCAD SHX Text
EPDM PRIMER
AutoCAD SHX Text
AutoCAD SHX Text
THERMOSET MEMBRANE
AutoCAD SHX Text
EPDM
AutoCAD SHX Text
DETAIL NO.
AutoCAD SHX Text
THERMOSET UNIVERSAL
AutoCAD SHX Text 2022 Carlisle SynTec a division of Carlisle Construction Materials Incorporated
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PRESSURE-SENSITIVE T-JOINT DETAIL U-2B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MAXIMUM WARRANTY: 20 YEARS
AutoCAD SHX Text
DECK-TO-WALL EXPANSION JOINT
AutoCAD SHX Text
CARLISLE EXPANSION JOINT SUPPORT OR SPONGE TUBING BY OTHERS
AutoCAD SHX Text
SURE-SEAL BONDING ADHESIVE
AutoCAD SHX Text
AutoCAD SHX Text
EXPANSION JOINT FILLER BY OTHERS
AutoCAD SHX Text U-3B
AutoCAD SHX Text
AutoCAD SHX Text CARLISLE FASTENER & SEAM PLATE, MAX. 12" (30cm) O.C.
AutoCAD SHX Text 6" (15cm) WIDE PRESSURE-SENSITIVE RUSS AND EPDM PRIMER
AutoCAD SHX Text
ANY U-9 U-9 TERMINATION (ABOVE ANTICIPATED WATER LEVEL)
AutoCAD SHX Text NOTES: 1. ALL OUTSIDE AND INSIDE CORNERS REQUIRE TWO ALL OUTSIDE AND INSIDE CORNERS REQUIRE TWO COMPLETE CORNER APPLICATIONS OF PRESSURE-SENSITIVE ELASTOFORM FLASHING AS PER DETAILS U-15D.1 OR U-15G.1. DETAILS U-15D.1 OR U-15G.1. . 2. ROOF MEMBRANE SHALL BE LOOSE-LAID OVER ROOF MEMBRANE SHALL BE LOOSE-LAID OVER THE EXPANSION JOINT SUPPORT OR SPONGE TUBING. 3. WIDTH OF JOINT SHALL BE A MINIMUM OF 3/4" WIDTH OF JOINT SHALL BE A MINIMUM OF 3/4" (2cm) AND MAXIMUM 2" (5cm) WHEN CARLISLE EXPANSION JOINT SUPPORT IS USED. 4. USE DETAIL U-2C FOR EPDM MEMBRANE USE DETAIL U-2C FOR EPDM MEMBRANE DETAIL U-2C FOR EPDM MEMBRANE FOR EPDM MEMBRANE SPLICES AT ANGLE CHANGES. 5. HP FASTENERS AND POLYMER SEAM PLATES ARE HP FASTENERS AND POLYMER SEAM PLATES ARE REQUIRED ON MECHANICALLY FASTENED SYSTEMS OVER STEEL DECKS. 6. MAXIMUM 6" (15cm) FASTENER SPACING FOR MAXIMUM 6" (15cm) FASTENER SPACING FOR WARRANTY WIND SPEEDS GREATER THAN 90 MPH OR WARRANTIES EXCEEDING 20 YEARS.
AutoCAD SHX Text 1/8" (0.5cm) TO 1" (2.5cm) MAX.
AutoCAD SHX Text
AutoCAD SHX Text
THERMOSET MEMBRANE
AutoCAD SHX Text
EPDM
AutoCAD SHX Text
DETAIL NO.
AutoCAD SHX Text
THERMOSET UNIVERSAL
AutoCAD SHX Text 2022 Carlisle SynTec a division of Carlisle Construction Materials Incorporated
AutoCAD SHX Text C
AutoCAD SHX Text
MAXIMUM WARRANTY: 30 YEARS
AutoCAD SHX Text
AutoCAD SHX Text
EPDM PRIMER
AutoCAD SHX Text
CURB FLASHING - WITH 20" PRESSURE-SENSITIVE CURED FLASHING
AutoCAD SHX Text
SHEET METAL FLASHING BY OTHERS
AutoCAD SHX Text U-5C
AutoCAD SHX Text NOTES: 1. WHEN MECHANICAL FASTENERS ARE USED TO WHEN MECHANICAL FASTENERS ARE USED TO PENETRATE THE METAL COUNTER-FLASHING, USE EPDM WASHERS, APPLY WATER CUT-OFF MASTIC UNDER THE COUNTER-FLASHING OR CAULK THE FASTENER HEADS. 2. 3" (7.5cm) FOR UP TO 20 YEARS AND 6" 3" (7.5cm) FOR UP TO 20 YEARS AND 6" (15cm) FOR 25/30 YEARS. 3. HP FASTENERS AND POLYMER SEAM PLATES ARE HP FASTENERS AND POLYMER SEAM PLATES ARE REQUIRED FOR MECHANICALLY-FASTENED ROOFING SYSTEMS OVER STEEL DECKS. 4. IF THE VERTICAL SPLICE ON THE CURB FLASHING IF THE VERTICAL SPLICE ON THE CURB FLASHING IS NOT LOCATED AT THE CORNER, USE DETAIL U-2C FOR EPDM MEMBRANE SPLICES AT ANGLE FOR EPDM MEMBRANE SPLICES AT ANGLE CHANGES.
AutoCAD SHX Text MAXIMUM 12"(30cm) O.C. SPACING
AutoCAD SHX Text 20" (50cm) WIDE PRESSURE- SENSITIVE CURED FLASHING
AutoCAD SHX Text 3" (7.5cm) MIN.
AutoCAD SHX Text
AutoCAD SHX Text CARLISLE FASTENER & SEAM PLATES, MAX. 12" (30cm) O.C.
AutoCAD SHX Text
FLASH OUTSIDE CORNERS PER APPLICABLE U-15 DETAILS. DETAILS.
AutoCAD SHX Text
LAP SEALANT
AutoCAD SHX Text
FASTENERS INTO DECK
AutoCAD SHX Text
AutoCAD SHX Text
FASTENERS INTO CURB
AutoCAD SHX Text
THERMOSET MEMBRANE
AutoCAD SHX Text
EPDM
AutoCAD SHX Text
DETAIL NO.
AutoCAD SHX Text
THERMOSET UNIVERSAL
AutoCAD SHX Text 2022 Carlisle SynTec a division of Carlisle Construction Materials Incorporated
AutoCAD SHX Text C
AutoCAD SHX Text
MAXIMUM WARRANTY: 30 YEARS
AutoCAD SHX Text
EPDM PRIMER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
XXXXXX
AutoCAD SHX Text 9C
AutoCAD SHX Text
CARLISLE UNIVERSAL SINGLE-PLY SEALANT OR SEALANT BY OTHERS
AutoCAD SHX Text
METAL COUNTER-FLASHING BY OTHERS.
AutoCAD SHX Text FASTEN MEMBRANE @ 12" (30cm) O.C. MAX.
AutoCAD SHX Text
CARLISLE UNIVERSAL SINGLE-PLY SEALANT OR SEALANT BY OTHERS
AutoCAD SHX Text
METAL COUNTER-FLASHING BY OTHERS.
AutoCAD SHX Text
CARLISLE TERMINATION BAR
AutoCAD SHX Text 9D
AutoCAD SHX Text
XXXXXX
AutoCAD SHX Text CARLISLE HP TERM BAR NAIL-IN 6" (15cm) O.C. FASTENING RECOMMENDED.
AutoCAD SHX Text
CARLISLE TERMINATION BAR
AutoCAD SHX Text NOTES: 1. APPLY ON HARD SMOOTH SURFACE ONLY; NOT APPLY ON HARD SMOOTH SURFACE ONLY; NOT FOR USE ON EXPOSED WOOD. 2. DO NOT WRAP TERMINATION BAR AROUND DO NOT WRAP TERMINATION BAR AROUND CORNERS. 3. DETAIL 9E MUST BE USED AT VERTICAL JOINTS DETAIL 9E MUST BE USED AT VERTICAL JOINTS 9E MUST BE USED AT VERTICAL JOINTS MUST BE USED AT VERTICAL JOINTS IN PANEL WALLS.
AutoCAD SHX Text 9A
AutoCAD SHX Text
MEMBRANE TERMINATIONS PAGE 1 OF 2
AutoCAD SHX Text
CARLISLE UNIVERSAL SINGLE-PLY SEALANT OR SEALANT BY OTHERS
AutoCAD SHX Text
CARLISLE HP TERM BAR NAIL-IN
AutoCAD SHX Text U-9
AutoCAD SHX Text
XXX
AutoCAD SHX Text
WATER CUT-OFF MASTIC- MUST BE HELD UNDER CONSTANT COMPRESSION.
AutoCAD SHX Text
APPLICABLE BONDING ADHESIVE
AutoCAD SHX Text NOTE: 1. WHEN MECHANICAL FASTENERS ARE USED WHEN MECHANICAL FASTENERS ARE USED TO PENETRATE THE METAL COUNTER-FLASHING, USE EPDM WASHERS, APPLY WATER CUT-OFF MASTIC UNDER THE COUNTER-FLASHING OR CAULK THE FASTENER HEADS.
AutoCAD SHX Text NOTES: 1. APPLY ON HARD SMOOTH SURFACE ONLY; NOT APPLY ON HARD SMOOTH SURFACE ONLY; NOT FOR USE ON EXPOSED WOOD. 2. DO NOT WRAP TERMINATION BAR AROUND DO NOT WRAP TERMINATION BAR AROUND CORNERS. 3. DETAIL 9E MUST BE USED AT VERTICAL JOINTS DETAIL 9E MUST BE USED AT VERTICAL JOINTS 9E MUST BE USED AT VERTICAL JOINTS MUST BE USED AT VERTICAL JOINTS IN PANEL WALLS.
AutoCAD SHX Text MIN. 1/4" (1cm)
AutoCAD SHX Text MAX. 1/2" (1.5cm)
AutoCAD SHX Text
MECHANICAL TERMINATION WITH COUNTER FLASHING
AutoCAD SHX Text
COUNTER FLASHING TERMINATION
AutoCAD SHX Text
MECHANICAL TERMINATION
AutoCAD SHX Text MIN. 1/4" (1cm)
AutoCAD SHX Text MAX. 1/2" (1.5cm)
AutoCAD SHX Text
THERMOSET MEMBRANE
AutoCAD SHX Text
EPDM
AutoCAD SHX Text
DETAIL NO.
AutoCAD SHX Text
THERMOSET UNIVERSAL
AutoCAD SHX Text 2022 Carlisle SynTec a division of Carlisle Construction Materials Incorporated
AutoCAD SHX Text C
AutoCAD SHX Text
MAXIMUM WARRANTY: 30 YEARS
AutoCAD SHX Text
MAXIMUM WARRANTY: 10-30 YEARS
AutoCAD SHX Text
MAXIMUM WARRANTY: 10 YEARS
AutoCAD SHX Text
MAXIMUM WARRANTY: 20 YEARS
AutoCAD SHX Text
SURE-SEAL TERMINATION BAR
AutoCAD SHX Text 9E
AutoCAD SHX Text
SEALANT
AutoCAD SHX Text
BY OTHERS
AutoCAD SHX Text
MEMBRANE TERMINATIONS PAGE 2 OF 2
AutoCAD SHX Text U-9
AutoCAD SHX Text 1" (2.5cm)
AutoCAD SHX Text
APPLICABLE BONDING ADHESIVE
AutoCAD SHX Text
MECHANICAL TERMINATION AT VERTICAL JOINTS
AutoCAD SHX Text
XXX
AutoCAD SHX Text
WATER CUT-OFF MASTIC- MUST BE HELD UNDER CONSTANT COMPRESSION.
AutoCAD SHX Text NOTES: 1. THIS DETAIL MUST BE USED FOR ANY PROJECT THIS DETAIL MUST BE USED FOR ANY PROJECT REGARDLESS OF WARRANTY. . 2. CONTINUOUS COUNTER FLASHING REQUIRED FOR CONTINUOUS COUNTER FLASHING REQUIRED FOR WARRANTY PROJECTS EXCEEDING 20-YEARS. 3. VERTICAL JOINTS IN THE PRE-CAST PANEL AS VERTICAL JOINTS IN THE PRE-CAST PANEL AS WELL AS ALL GAPS AT THE JUNCTION OF THE TILT-UP PANEL AND ROOF DECK MUST BE FULLY SEALED TO PREVENT AIR INFILTRATION. 4. APPLY ON HARD SMOOTH SURFACE ONLY. APPLY ON HARD SMOOTH SURFACE ONLY.
AutoCAD SHX Text
SEALANT BY OTHERS
AutoCAD SHX Text
METAL COUNTER FLASHING BY OTHERS
AutoCAD SHX Text 0.5" (1.5cm)
AutoCAD SHX Text
WALL PANEL JOINTS
AutoCAD SHX Text
ROOF MEMBRANE AT TERMINATION LEVEL
AutoCAD SHX Text
THERMOSET MEMBRANE
AutoCAD SHX Text
EPDM
AutoCAD SHX Text
DETAIL NO.
AutoCAD SHX Text
THERMOSET UNIVERSAL
AutoCAD SHX Text 2022 Carlisle SynTec a division of Carlisle Construction Materials Incorporated
AutoCAD SHX Text C
AutoCAD SHX Text
MAXIMUM WARRANTY: 30 YEARS
AutoCAD SHX Text
MAXIMUM WARRANTY: 30 YEARS
AutoCAD SHX Text U-12A
AutoCAD SHX Text
ANY U-9 U-9 TERMINATION (ABOVE ANTICIPATED WATER LEVEL)
AutoCAD SHX Text
PARAPET / CURB WITH CONTINUOUS MEMBRANE
AutoCAD SHX Text NOTES: 1. FASTENERS AND PLATES ARE REQUIRED AT 6" FASTENERS AND PLATES ARE REQUIRED AT 6" (15cm) O.C. FOR ADHERED SYSTEMS WITH WARRANTY WIND SPEED COVERAGE GREATER THAN 90 MPH AND FOR ALL PROJECTS WITH WARRANTIES GREATER THAN 20 YEARS. HP FASTENERS AND POLYMER SEAM PLATES ARE REQUIRED OVER STEEL DECKS ON MECHANICALLY FASTENED SYSTEMS. 2. PROJECTS WITH 25 AND 30-YEAR WARRANTIES PROJECTS WITH 25 AND 30-YEAR WARRANTIES OR WHEN USING 90-MIL MEMBRANE. REFER TO . REFER TO DETAIL U-2C. U-2C. . 3. FOR CORNERS AND RUSS APPLICATION REFER TO FOR CORNERS AND RUSS APPLICATION REFER TO DETAILS U-15A OR U-15B..
AutoCAD SHX Text CARLISLE FASTENER & SEAM PLATE, MAX. 12" (30cm) O.C.
AutoCAD SHX Text 6" (15cm) WIDE PRESSURE-SENSITIVE RUSS
AutoCAD SHX Text
LAP SEALANT
AutoCAD SHX Text
SURE-SEAL BONDING ADHESIVE OR CAV-GRIP III
AutoCAD SHX Text PRESSURE- SENSITIVE T-JOINT COVER OR 6" (15cm) P.S. ELASTOFORM
AutoCAD SHX Text
AutoCAD SHX Text
THERMOSET MEMBRANE
AutoCAD SHX Text
EPDM
AutoCAD SHX Text
DETAIL NO.
AutoCAD SHX Text
THERMOSET UNIVERSAL
AutoCAD SHX Text 2022 Carlisle SynTec a division of Carlisle Construction Materials Incorporated
AutoCAD SHX Text C
AutoCAD SHX Text
MAXIMUM WARRANTY: 30 YEARS
AutoCAD SHX Text OPTIONAL: SEAM PLATE/FASTENER MAY BE INSTALLED INTO THE STRUCTURAL DECK UP TO 6" (15cm) FROM ANGLE CHANGE.
AutoCAD SHX Text
AutoCAD SHX Text
EPDM PRIMER
AutoCAD SHX Text A
AutoCAD SHX Text cm
AutoCAD SHX Text
DIMENSION
AutoCAD SHX Text 1/8"-1"
AutoCAD SHX Text 0.5-2.5
Aut…