2-1066222.000 UMBT FIRE E 20260515.pdf
PDF 2 MB Posted
- Attached to
- Mt. Bethel Fire Co. - Emergency Shelter 2020-63
- Solicitation number
- Not on record
- Issued by
- Northampton County, Pennsylvania
About this file
This file comprises electrical construction drawings and specifications for the Mt. Bethel Fire Company's emergency shelter addition project (Project 2020-63) located at 2341 North Delaware Drive, Mt. Bethel, Pennsylvania 18343, Upper Mount Bethel Township, Northampton County. The project involves the installation of a complete electrical, lighting, and power system for approximately 2,000 square feet of new addition space, including new toilet and shower facilities, accessible entrance, and storage areas. The electrical work encompasses new lighting fixtures (Lithonia brand LED panels and recessed downlights), receptacles, switches, exit signage, emergency lighting systems, panelboards, motor controllers, and related appurtenances. Key electrical components include a new 100-ampere Panel PP fed from the existing 400-ampere main distribution panel (MDP), three new rooftop units (CU-1, CU-2, and ERV-1) with associated disconnect switches and circuits, branch circuit wiring, conduit systems in both metallic and non-metallic configurations, and fire alarm system provisions. A pre-bid meeting is scheduled for July 9, 2026, at 9:00 A.M., with bid submissions due by July 28, 2026, at 12:00 P.M. prevailing time. The construction documents include detailed specifications for materials, installation procedures, quality assurance requirements, and testing protocols.
The specifications require all electrical work to comply with the National Electrical Code (NEC) 2017, International Building Code (IBC) 2018, and International Energy Conservation Code (IECC) 2018. The electrical contractor must provide comprehensive documentation including shop drawings for equipment approval, as-built drawings upon project completion, operation and maintenance manuals, and commissioning documentation. All materials must be new and UL-listed where required, with circuit breakers matching existing panelboard manufacturers in style and interrupting rating. The contractor bears responsibility for all cutting, patching, demolition of existing equipment as indicated on the demolition drawings, and coordination with mechanical, plumbing, and HVAC contractors. A one-year warranty on all materials, equipment, and workmanship from the date of owner acceptance is required. The specifications include detailed requirements for lighting controls including occupancy sensors with automatic shutoff within 30 minutes, time-switch controls with daylight savings capability, dimming controls compatible with LED fixtures, and comprehensive functional testing and commissioning per IECC requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E0.0: ELECTRICAL INFORMATION SHEET
E1.1: PARTIAL FLOOR PLAN - LIGHTING
E2.1: PARTIAL FLOOR PLAN - POWER
E2.2: PARTIAL ROOF PLAN - POWER
E3.0: ELECTRICAL DETAILS & SCHEDULES
E4.0: ELECTRICAL SPECIFICATIONS
ED1.1: PARTIAL FLOOR PLAN - DEMOLITION - POWER
DRAWING LIST
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER & CATALOG NUMBER
MOUNTING
DESCRIPTION WATTAGE
SURF SUS REC HGT
A LITHONIA - #CPX 2X4 AL07 80CRI SWW7 A12 MVOLT ● 2X4 RECESSED FLAT PANEL LED SET TO 4000LM, 35K 36W
B LITHONIA - #LDN6 35/30 L06 AR LSS MVOLT GZ10 ● RECESSED LED DOWNLIGHT 35W
C LITHONIA - #LDN6 35/30 L06 AR LSS MVOLT GZ10 ● RECESSED LED DOWNLIGHT WET LOCATION LISTED 35W
D LITHONIA - #WDGE2 LED 35K 80CRI VF MVOLT SRM ● EXTERIOR WALL SCONCE 18W
F LITHONIA - #CPX 2X4 AL07 80CRI SWW7 A12 MVOLT
PAC 4DF 36 ● 2X4 FLAT PANEL LED SET TO 4000LM, 35K SUSPENDED FROM ROOF
STRUCTURE WITH AIR CRAFT KIT 36W
G LITHONIA - #CPX 2X2 AL07 80CRI SWW7 A12 MVOLT ● 2X2 RECESSED FLAT PANEL LED SET TO 3200LM, 35K 28W
H LITHONIA - #CPX 1X4 AL07 80CRI SWW7 A12 MVOLT ● 1X4 RECESSED FLAT PANEL LED SET TO 3200LM, 35K 25W
E LITHONIA - #EXRG-EL-M6 ● EXIT SIGN
E1 LITHONIA - #ECRG-HO-RD-M6 ● EXIT SIGN WITH COMBINATION HEADS
EM LITHONIA - #ELM4L ELA WG ● EMERGENCY LIGHT WITH BATTERY PACK
EX LITHONIA: ERE-GY-T-WP-SQ ● WEATHERPROOF DUAL REMOTE HEADS
GENERAL LIGHTING FIXTURE SCHEDULE NOTES:
1. PROVIDE CORRECT TRIM FOR ALL FIXTURES INSTALLED IN A HARD CEILING OR SPECIALTY CEILING TYPE.
2. PROVIDE ALL APPROPRIATE MOUNTING HARDWARE. PROVIDE BACK/MOUNTING BOXES AS RECOMMENDED BY MANUFACTURER.
3. COORDINATE LOCATION OF ALL EXIT SIGNS IN THE FIELD WITH OWNER SUPPLIED EQUIPMENT, BULK HEADS AND SIGNAGE TO ENSURE
VISIBILITY FROM AT LEAST HALFWAY TO NEXT SIGN OR TO THE EXIT.
4. PROVIDE DOUBLE OR SINGLE FACE EXIT SIGNS AS INDICATED ON THE DRAWINGS. PROVIDE ARROWS AS INDICATED.
5. ALL FIXTURE FINISHES AND DECORATIVE DETAILS SHALL BE SELECTED BY THE ARCHITECT PRIOR TO FINAL ORDER. COLORS SHALL BE
SELECTED FROM FULL COLOR LINE (BOTH STANDARD, CUSTOM, AND PREMIUM).
6. FIXTURES INDICATED ARE THE BASIS OF DESIGN. ALL EQUALS SHALL HAVE THE SAME PERFORMANCE AND GENERAL SHAPE AND
OPTIONS. ALL EQUALS ARE TO BE APPROVED BY THE ARCHITECT AND ENGINEER PRIOR TO ORDERING.
7. ALL FIXTURES CONNECTED TO A DIMMER, LIGHTING CONTROL SYSTEM, OR STAGE LIGHTING CONTROL SYSTEM SHALL HAVE DRIVER
THAT COORDINATES WITH CONTROLLER. COORDINATE BEFORE ORDERING. AUDITORIUM FIXTURE DRIVERS SHALL BE SELECTED AS PER THEATRICAL SYSTEM BASIS OF DESIGN REQUIREMENTS AND THEN COORDINATED PRIOR TO FINAL ORDERING WITH SELECTED SYSTEM.
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE BRANCH CIRCUIT WIRING TO ALL ITEMS WHICH REQUIRE
ELECTRICAL CONNECTIONS. WHERE BRANCH CIRCUIT WIRING IS NOT SHOWN,
CONTRACTOR SHALL CONNECT ITEMS TO THE CIRCUITS INDICATED. EXACT ROUTING
OF CONDUITS AND WIRING SHALL BE DETERMINED BY THE CONTRACTOR IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND SPECIFICATIONS.
2. CONTRACTOR SHALL USE ONLY THOSE WIRING METHODS ALLOWED IN THE
SPECIFICATIONS.
3. A MAXIMUM OF 3 CIRCUITS SHALL BE RUN IN ONE CONDUIT, CIRCUITS MUST BE ON
SEPARATE PHASES. CIRCUITS SHALL NOT SHARE A COMMON NEUTRAL.
4. MINIMUM WIRE SIZE SHALL BE #12AWG. MINIMUM CONDUIT SIZE SHALL BE 3/4".
5. THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND
CONDITIONS AT THE SITE.
6. ALLOW CLEAR SPACE IN FRONT OF ALL PANELBOARDS, SWITCHBOARDS, ELECTRICAL
EQUIPMENT, ETC., AS REQUIRED BY NEC.
7. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES WITH HVAC DUCTWORK,
PIPING, AND EQUIPMENT.
8. ALL LIGHTING FIXTURES TO BE COMPATIBLE WITH THE CEILING CONSTRUCTION.
9. ELECTRICAL CONTRACTOR TO SUPPLY ALL GROUNDING & BONDING REQUIREMENTS
PER NEC.
10. ELECTRICAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING IN EXISTING
BUILDING RELATED TO THE NEW ELECTRICAL WORK.
11. ELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL
MATERIALS EQUIPMENT AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE
OF ACCEPTANCE BY OWNER.
12. THE ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ARCHITECT & ENGINEER
AS-BUILT DRAWINGS AND OPERATION AND MAINTENANCE MANUALS INCLUDING ALL
NAMEPLATE DATA, WIRING DIAGRAMS, MAINTENANCE INSTRUCTIONS AND PARTS LIST
UPON PROJECT COMPLETION.
13. ELECTRICAL CONTRACTOR SHALL MAINTAIN A CLEAN AND SAFE WORK AREA AT ALL
TIMES. ALL SAFETY PROCEDURES AND ENFORCEMENT IS THE RESPONSIBILITY OF THE
CONTRACTOR. THE CONTRACTOR SHALL CONFORM TO ALL OSHA STANDARDS.
14. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL ACCESS PANELS NECESSARY
FOR A CODE COMPLIANT INSTALLATION.
15. ENSURE ALL CONTACTORS ARE LABELED WITH LOADS CONTROLLED. ALL
CONTACTORS SHALL BE LOCATED NEAR ELECTRICAL PANEL.
16. THESE DRAWINGS AND SPECIFICATIONS ARE NOT INTENDED TO SHOW THE LOCATION
OF EVERY WIRE, CONDUIT, FITTING, ETC., BUT IS UNDERSTOOD THAT THE
CONTRACTOR SHALL FURNISH AND INSTALL ALL MATERIALS AND LABOR FOR
COMPLETE WORKABLE SYSTEMS UNLESS NOTED OTHERWISE IN THIS SPECIFICATION
OR ON THE DRAWINGS.
17. CONTRACTOR SHALL PROVIDE BUT NOT BE LIMITED TO:
17.1. COMPLETE SYSTEM OF WIRING FOR EMERGENCY LIGHTING, LIGHT AND POWER,
PLUMBING AND HVAC EQUIPMENT.
17.2. ALL PANELS, SWITCHBOARDS, MOTOR CONTROLLERS, TRANSFORMERS,
DISCONNECTS, RECEPTACLES, SWITCHES, OUTLETS AND PLATES FOR SAME,
FEEDERS FROM PANELS AND RELATED APPURTNENANCES.
17.3. LIGHTING FIXTURES, LAMPS, BALLASTS AND APPURTENANCES.
18. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, FITTINGS OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR
COMPLETE INSTALLATION OF THE WORK. SUCH WORK MAY BE ACCOMPLISHED AT THE
SITE. ADDITIONAL BENDS, OFFSETS AND CONDUIT AS REQUIRED BY VERTICAL AND
HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS SHALL BE PROVIDED
TO COMPLETE THE WORK AT NO ADDITIONAL COST TO OWNER.
19. EXCEPT WHERE SHOWN IN DIMESIONAL DETAIL, THE LOCATIONS OF SWITCHES,
RECEPTACLES, LIGHTS, AND OTHER EQUIPMENT SHOWN ON PLANS ARE
APPROXIMATE. SUCH ITEMS SHALL BE PLACED SO AS TO ELIMINATE INTERFERENCE
WITH DUCTS, PIPING AND EQUIPMENT. THE EXACT LOCATION SHALL BE DETERMINED IN
THE FIELD. ALL DOOR SWINGS SHALL BE VERIFIED SO THAT LIGHT SWITCHES ARE
PROPERLY LOCATED.
20. FIELD VERIFY EXISTING CONDITIONS AND COORDINATE ALL WORK WITH ALL OTHER
TRADES, AND ACTUAL CONDITIONS IN FIELD.
MOUNTING HEIGHT NOTES:
1. MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED.
IN MASONRY CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE
USED FOR REFERENCE TO NEAREST BLOCK OF BRICK COURSING.
2. THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS
SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWING OR
SPECIFICATIONS.
3. A '+' BESIDE A DEVICE INDICATES THAT DEVICE IS MOUNTED ABOVE A
COUNTER OR CASEWORK. COORDINATE WITH ARCHITECTURAL ROOM
ELEVATIONS, DETAILS, AND CASEWORK CONTRACTOR.
THE ELECTRICAL SYSTEMS PRESENTED ON THE SUBSEQUENT
DRAWINGS WERE DESIGNED IN ACCORDANCE WITH THE
FOLLOWING APPLICABLE CODES AND STANDARDS
· THE NATIONAL ELECTRICAL CODE (NEC), 2017
· INTERNATIONAL BUILDING CODE (IBC), 2018
· INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2018
SIGNAL SYSTEM
SMOKE DETECTOR
DUCT MOUNTED SMOKE DETECTOR
CARBON MONOXIDE DETECTOR
HEAT DETECTOR
ABBREVIATIONS & SYMBOL
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ATS AUTOMATIC TRANSFER SWITCH
CT COUNTERTOP
DC DUCT COIL
DF DRINKING FOUNTAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ERL EXISTING TO BE RELOCATED
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
GC GENERAL CONTRACTOR
GF GROUND FAULT INTERRUPTER
HC HVAC CONTRACTOR
HP HEAT PUMP
HV HIGH VOLUME
KES KITCHEN EQUIPMENT SUPPLIER
MW MICROWAVE
PC PLUMBING CONTRACTOR
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER
WM WALL MOUNTED
WP WEATHERPROOF
DRAWING NOTE BY SYMBOL
GENERAL ELECTRICAL DEMOLITION NOTES:
1. DEMOLITION OF ALL EXISTING ELECTRICAL EQUIPMENT AND ASSOCIATED PIPING SHALL BE
COORDINATED WITH NEW WORK INSTALLATION.
2. THIS CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY/ALL DAMAGES TO EXISTING
FLOORS, FLOOR TILES, WALLS, CEILINGS, FURNISHINGS, ETC. DUE TO THE REMOVAL
PROCESS OF ELECTRICAL EQUIPMENT AND ALL ASSOCIATED ITEMS.
3. ALL MATERIAL AND EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OF BY THE
CONTRACTOR.
4. CONTRACTOR SHALL REMOVE ALL EXISTING LIGHTING FIXTURES WHERE NEW FIXTURES
ARE SHOWN. THIS SHALL INCLUDE FITTINGS, SUPPORT DEVICES, ETC AND MAKE
PROVISIONS TO EXISTING CEILING SO THAT THE NEW FIXTURE MAY BE PROPERLY
INSTALLED.
5. MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS REMAINING IN OTHER AREAS.
6. ALL EXISTING CONDUITS AND WIRING NOT BEING USED SHALL BE REMOVED BACK TO
SOURCE.
7. WHERE MODIFICATIONS OR ADDITIONS TO EXISTING WORK IS TO BE DONE BY ANOTHER
CONTRACTOR, EXISTING EQUIPMENT, CONDUIT, DEVICES, SUPPORTS, AND
APPURTENANCES SHALL BE REMOVED AND REINSTALLED TO ACCOMMODATE
MODIFICATIONS OR ADDITIONS. THIS SHALL INCLUDE THE ADDITION OF DOORS, WALLS,
STRUCTURAL SUPPORTS, UNITS, ETC. COORDINATE WITH OTHER CONTRACTORS IN THE
FIELD PRIOR TO WORK COMMENCING. WHERE THE QUANTITY OF WORK CANNOT BE
DETERMINED PRIOR TO BID DUE TO CONCEALED CONDITIONS, PROVIDE $5,000
ALLOWANCE.
8. DEVICES SHOWN ARE BASED ON EXISTING DRAWINGS AND SITE SURVEY WHILE BUILDING
WAS IN OPERATION. ACTUAL LOCATIONS AND QUANTITIES MAY VARY. VERIFY IN FIELD.
9. ALL DORMANT CABLING AND WIRING SHALL BE REMOVED UNLESS NOTED AS FOR FUTURE
OR AS INSTRUCTED OTHERWISE BY OWNER.
10. COORDINATE THE REMOVAL OF THE POWER CONNECTIONS TO ALL MECHANICAL
EQUIPMENT TO BE REMOVED WITH THE MECHANICAL CONTRACTOR.
11. ALL CIRCUIT BREAKERS WHERE THE LOAD SERVING HAS BEEN REMOVED SHALL BE
MARKED AS SPARE.
12. ALL PANELBOARDS MODIFIED UNDER THE WORK SHALL RECEIVE REVISED, TYPED PANEL
SCHEDULES AS PROVIDED WITH ALL NEW PANELBOARDS.
13. REPLACE ANY DAMAGED EXISTING TO REMAIN ELECTRICAL, LIGHTING, AND LOW VOLTAGE
EQUIPMENT IN KIND.
14. EXTEND WIRING IN KIND FOR DEVICES TO BE REINSTALLED IN NEW CEILING AS
NECESSARY.
15. ALL SURFACE MOUNTED DEVICES SHALL BE INSTALLED IN 1 OR 2 SECTION SURFACE
MOUNTED RACEWAY AS REQUIRED TO ACCOMODATE BOTH LOW VOLTAGE AND LINE
VOLTAGE CABLES IN THE SAME RACEWAY. REFER TO SURFACE MOUNTING DETAIL FOR
MORE INFORMATION.
16. VERIFY IF BUILDING HAS PLENUM RETURN. IF PLENUM RETURN EXISTS, PROVIDE ALL
EXPOSED CABLING INSTALLED WITHIN PLENUM AS PLENUM RATED CABLE.
LIGHTING
2'x2' LIGHTING FIXTURE
2'x4' LIGHTING FIXTURE
2'x4' LIGHTING FIXTURE - EMERGENCY
1'x4' LIGHTING FIXTURE
WALL PACK LIGHTING FIXTURE
ROUND RECESSED DOWNLIGHT FIXTURE
NORMAL EMERGENCY FIXTURE
EMERGENCY BATTERY UNIT
REMOTE HEAD
EXIT SIGN - DOUBLE FACE
EXIT SIGN - CEILING MOUNTED WITH DIRECTIONAL ARROWS
EXIT SIGN - SINGLE FACE
WALL SCONCE
WIRING DEVICES
SINGLE POLE SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED
3-WAY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED
4-WAY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED
KEY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED
SPRING WOUND TIME SWITCH, 5-MINUTE MAXIMUM DURATION
- 3'-10" AFF UNLESS OTHERWISE NOTED
SPRING WOUND TIME SWITCH, 1-HOUR MAXIMUM DURATION -
3'-10" AFF UNLESS OTHERWISE NOTED
DIMMER SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED
MANUAL MOTOR STARTER SWITCH - 3'-10" AFF UNLESS
OTHERWISE NOTED
3-WAY DIMMER SWITCH - 3'-10" AFF UNLESS OTHERWISE
NOTED
OCCUPANCY SENSOR SWITCH - 3'-10" AFF UNLESS OTHERWISE
NOTED
PILOT LIGHT SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED
MANUAL OVERRIDE
SWITCH WITH OCCUPANCY SENSOR AND DIMMING CAPABILITY
- 3'-10" AFF UNLESS NOTED OTHERWISE
DUAL TECHNOLOGY OCCUPANCY SENSOR - 360°
DUAL TECHNOLOGY OCCUPANCY SENSOR - CORRIDOR
PATTERN
DUAL TECHNOLOGY OCCUPANCY SENSOR - CORNER MOUNT
CEILING MOUNTED DAYLIGHT SENSOR
MULTIPLE BUTTON DIGITAL CONTROL STATION WITH ON/OFF -
3'-10" AFF UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE - NEMA 5-20R, MOUNT 1'-6" AFF UNLESS
OTHERWISE NOTED
COUNTERTOP DUPLEX RECEPTACLE MOUNT 3" ABOVE
BACKSPLASH OR AT 3'-10"
TAMPERPROOF DUPLEX RECEPTACLE - NEMA 5-20R, MOUNT
1'-6" AFF UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE WITH USB PORT - MOUNT AT 1'-6"
UNLESS OTHERWISE NOTED
SINGLE RECEPTACLE - MOUNT 1'-6" AFF UNLESS OTHERWISE
NOTED
GFI DUPLEX RECEPTACLE - MOUNT AT 1'-6" AFF UNLESS
OTHERWISE NOTED
DUPLEX RECEPTACLE WITH TOP SWITCHED - 1'-8" AFF UNLESS
OTHERWISE NOTED
QUAD RECEPTACLE - NEMA 5-20R, MOUNT 1'-6" AFF UNLESS
OTHERWISE NOTED
SINGLE PHASE SPECIAL RECEPTACLE - MOUNT 1'-6" AFF
UNLESS OTHERWISE NOTED
THREE PHASE SPECIAL RECEPTACLE - MOUNT 1'-6" AFF
UNLESS OTHERWISE NOTED
FLOOR MOUNTED DUPLEX RECEPTACLE
PANELBOARDS
SURFACE MOUNTED PANEL
FLUSH MOUNTED PANEL
EXISTING SURFACE MOUNTED PANEL
EXISTING FLUSH MOUNTED PANEL
CIRCUITING
JUNCTION BOX
BRANCH CIRCUIT NUMBER FOR ALL ITEMS IN THIS ROOM
UNLESS OTHERWISE INDICATED - (*) INDICATES CONNECTION
TO CIRCUIT NUMBER SHOWN NEXT TO DEVICE
DEMOLITION DRAWING LINETYPE DESIGNATIONS
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NOTE:
NOT ALL ABBREVIATIONS AND SYMBOLS INDICATED MAY APPEAR ON THESE
CONTRACT DRAWINGS. THIS IS FOR REFERENCE ONLY.
CONTROL EQUIPMENT
MANUAL MOTOR STARTER - OVERLOADS SIZED TO
ACCOMODATE MOTOR - 4'-0" AFF UNLESS OTHERWISE NOTED
COMBINATION MOTOR STARTER - TYPE/SIZE/NEMA
ENCLOSURE AS INDICATED - MOUNT 4'-6" AFF TO CENTERLINE
OF OPERATING HANDLE. PROVIDE OVERCURRENT AND
OVERLOADS IN ACCORDANCE WITH MANUFACTURERS'
RECOMMENDATIONS FOR MOTOR HP
MOTOR - HORSEPOWER AS INDICATED
DISCONNECT SWITCH - AMPS/POLES/FUSES/NEMA
ENCLOSURE AS INDICATED - MOUNT 4'-6" AFF TO CENTERLINE
OR OPERATING HANDLE
TRANSFORMER
STANDARD MOUNTING HEIGHTS
9" BELOW
FINISHED
CEILING
WALL-MOUNTED CLOCKS, PROGRAM
BELLS, (OR AS SHOWN ON
ARCHITECTURAL DETAIL)
6" ABOVE DOOR NURSE CALL DOME LIGHT
6" ABOVE FIRE
HOUSE
CABINET
RED SIGNAL LIGHT
10'-0"
BATTERY LIGHTING UNITS AND REMOVE
WALL MOUNTED LIGHT HEADS (OR 1'-0"
BELOW FINISHED CEILING OF TOP UNIT)
8'-6" PENDANT-HUNG INDUSTRIAL AND STRIP
LIGHTING FIXTURES
7'-8"+
TELEVISION OUTLET AND SERVICE
RECEPTACLE - FOR SHELF MOUNTED
T.V. IN BEDROOMS
7'-6" OR 6" BELOW FINISHED CEILING,
WHICHEVER IS LOWER
CENTER ABOVE
DOOR OR WINDOW
OPENING
WARNING AND SIGNALING
FIXTURES/SIGNS
6'-8"
OR 6" BELOW FINISHED CEILING
WHICHEVER IS LOWER. FIRE ALARM
SIGNAL DEVICES AND ILLUMINATED FIRE
SIGNALS
6'-6"
TOP OF FLUSH AND SURFACE MOUNTED
ELECTRICAL LIGHTING OR POWER
PANELBOARDS AND TELEPHONE
CABINETS
6'-3"
TOP OF BACK-MOUNTED WALL EXIT
FIXTURES (NOT MOUNTED ABOVE
DOORS)
6'-0"
TOP OF HIGHEST ELECTRICAL SAFETY
DISCONNECT SWITCHES, MAGNETIC
STARTERS, CONTACTORS
4'-6"
CENTERLINE OF OPERATING HANDLE
FOR WALL MOUNTED DISCONNECT
SWITCHES AND MOTOR STARTERS;
WALL MOUNTED TELEPHONE AND PAY
STATIONS (3'-6" AT HANDICAP
LOCATIONS VERIFY EXACT HEIGHT
PRIOR TO ROUGH-IN)
3'-10"
WALL PHONE, ELECTRICAL DEVICE
LIGHTING SWITCHES, MANUAL MOTOR
STARTERS, SECURITY CARD, AND GFI
RECEPTACLES IN TOILET ROOMS OR
FOR SEPERATE SINKS NOT IN
CASEWORK
3'-6" FIRE ALARM PULL STATIONS
2'-0"
ELECTRICAL RECEPTACLES WITHIN
MECHANICAL SPACES, ELECTRICAL,
AND ELEVATOR ROOMS
1'-6"
ELECTRICAL RECEPTACLES,
TELEPHONE OUTLETS, DATA OUTLETS,
TELEPHONE/DATA OULETS
0" FINISHED FLOOR
M
T
30/3/NF/12
FVNR/SIZE1/3R
MS
CT
W
F
F
F
M
S
MS
S
D
C
H
P-1
ROOM #
ROOM NAME
OS
S
CT
T
DS
OS
USB
Dos
S
4S
KS
T5S
TS
DS
MS
3DS
OSS
PS
MOS
S
OS
LCS
J
PERMIT DOCUMENTS
05/15/2026
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
ENGINEER OF RECORD:
DRAWN BY: xx
OWNER / CONTACT:
Dale Handelong
570-688-8268 dalehandelong@hotmail.com
22 South 2nd Street Emmaus, PA 18049
T: 610-297-0140 E: sam@scf-arch.com
These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect
PR
O
JE
C
T N
U M
BE
R
0-
M ou nt B et he l F ire
C o.
Ad di tio n to E xi st in g
Fi re
C om pa ny
N or th D el aw ar e
D riv e, M t.
Be th el
, P A
U pp er
M ou nt B et he l T w p, N or th am pt on C ou nt y
ELECTRICAL
INFORMATION
SHEET
E0.0
EXISTING SIREN
POLES
EXISTING SHED
A
C C
C C
B B
B B
OS
S
S
OS
OS
S
OS OS
OS
SOS
SD
O
S
S O S
S O
S
ST ST
S O
S
S4
S3
EM
EM
E E
EX
E1
D
1 1 1
A-30
A-30
A-30
A-30
A-30
D D
S3
OS
OS
A
2 2
A
EXISTING
OFFICE
CORRIDOR
CHANGING
EXISTING
STORAGE
NURSING/
CHANGING
WOMEN
103TABLE & CHAIR
STORAGE
MEN
ACCESSIBLE
CHANGING
CORRIDOR
C
S
OS
3 3
PHASE ONEPHASE TWO
A
AA
F F F
F F
E1A-30E1A-30
AA
A
A
AA
EM A-30
EM A-30
F
A A
A A
OS
OS
OS
EM
A-30
G
G
H
EM
A-30
EM
A-30
EM A-30
RENOVATED
TOILET/EXTRACTOR ROOM
EXISTING
GARAGE
EXISTING
BANQUET HALL
EXISTING
MULTI-PURPOSE ROOM
EXISTING
EXISTNG
KITCHEN
PERMIT DOCUMENTS
05/15/2026
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
ENGINEER OF RECORD:
DRAWN BY: xx
OWNER / CONTACT:
Dale Handelong
570-688-8268 dalehandelong@hotmail.com
22 South 2nd Street Emmaus, PA 18049
T: 610-297-0140 E: sam@scf-arch.com
These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect
PR
O
JE
C
T N
U M
BE
R
0-
M ou nt B et he l F ire
C o.
Ad di tio n to E xi st in g
Fi re
C om pa ny
N or th D el aw ar e
D riv e, M t.
Be th el
, P A
U pp er
M ou nt B et he l T w p, N or th am pt on C ou nt y
PARTIAL FLOOR PLAN - LIGHTING
SCALE: 1/4"=1'-0"
PARTIAL
FLOOR PLAN -
LIGHTING
E1.1
1. ALL LIGHT FIXUTURES SHOWN ARE NEW UNLESS
OTHERWISE NOTED.
2. WIRE EXIT LIGHTS AND EMERGENCY LIGHTS TO
THE UNSWITCHED LEG OF THE LOCAL LIGHTING
CIRCUIT.
3. CONFIRM ALL LIGHTING FIXTURE TYPES AND
LOCATIONS WITH OWNER AND ARCHITECT PRIOR
TO COMMENCEMENT OF WORK.
4. REFER TO ARCHITECTURAL DRAWINGS FOR
EXACT DIMENSIONAL LOCATIONS AND
COORDINATION OF ALL DEVICES.
5. NEW CIRCUITS ARE FED FROM EXISTING PANELS.
WIRE NEW CIRCUITS TO EXISTING FREE
CIRCUITS OR SPACES, OR AS INDICATED ON
DRAWINGS. PROVIDE NEW CIRCUIT BREAKER
FOR ALL NEW CIRCUITS REPLACING EXISTING
BREAKERS. CIRCUIT BREAKER SHALL MATCH
EXISTING BREAKERS IN MANUFACTURER, STYLE,
TYPE AND INTERRUPTING RATING.
6. CIRCUITING AND PANEL SCHEDULES AS SHOWN
ARE FOR CLARITY ONLY. ELECTRICAL
CONTRACTOR SHALL COORDINATE IN FIELD
USING EXISTING SPARE CIRCUITING AND ADJUST
PANEL SCHEDULES TO MATCH. CONTRACTOR TO
TRACE ALL EXISTING CIRCUITS PRIOR TO REUSE.
GENERAL NOTES:
EXTERIOR FIXTURES SHALL BE CONTROLLED
VIA AN EXTERIOR MOUNTED PHOTOCELL
FACING THE NORTH SKY. CONNECT
EXTERIOR FIXTURES TO CIRCUIT CURRENTLY
SERVING EXISTING EXTERIOR
BUILDING-MOUNTED FIXTURES.
ALL NEW LIGHTING TO BE FED FROM NEW
PANEL "PP" CIRCUIT #16 UNLESS OTHERWISE
NOTED. REFER TO PANEL SCHEDULE.
CONNECT TO NEAREST 120V CIRCUIT USING
2#12, 1#12 GROUND IN 3/4" CONDUIT.
NOTES BY SYMBOL:
(THIS DRAWING ONLY)
EXISTING SHED
WH-1CP-1
HP-1
EUH-2
EXISTING
OFFICE
EXISTING ATS
EXISTING MAIN DISCONNECT
EXISTING METER AND CT CABINETEXISTING 125kW GENERATOR
EXISTING ELECTRICAL SPACE
CTCT
WP
EXISTING 400A PANEL
"MDP"
EXISTING 100A PANEL
"A"
PP-18
PP-9
PP-1
PP-6
PP-9
PP-4
EH-37
30/1/20/1J
MDP-1
100/3/100/1
PP-15,17
30/2/25/1
PP-11,13
30/2/25/1
HP-2 100/3/100/1
MDP-2
D
D
CT
PP-3
CT
PP-2
PP-6
PP-6
PP-5
PP-7
PP-9
PP-9
PP-9
NEW PANEL "PP"
PP-18
PP-18
PP-18
M
PP-8 PP-10
CORRIDOR
CHANGING
EXISTING
STORAGE
EXISTING
BANQUET HALL
EXISTING
MULTI-PURPOSE ROOM
NURSING/
CHANGING
WOMEN
103TABLE & CHAIR
STORAGE
MEN
ACCESSIBLE
CHANGING
CORRIDOR
CT
PHASE ONEPHASE TWO
RELOCATED
EXISTING ELECTRIC
WALL HEATER
EUH-1
RENOVATED
TOILET/EXTRACTOR ROOM
EXISTING
GARAGE
EXISTING
EXISTNG
KITCHEN
PERMIT DOCUMENTS
05/15/2026
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
ENGINEER OF RECORD:
DRAWN BY: xx
OWNER / CONTACT:
Dale Handelong
570-688-8268 dalehandelong@hotmail.com
22 South 2nd Street Emmaus, PA 18049
T: 610-297-0140 E: sam@scf-arch.com
These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect
PR
O
JE
C
T N
U M
BE
R
0-
M ou nt B et he l F ire
C o.
Ad di tio n to E xi st in g
Fi re
C om pa ny
N or th D el aw ar e
D riv e, M t.
Be th el
, P A
U pp er
M ou nt B et he l T w p, N or th am pt on C ou nt y
PARTIAL FLOOR PLAN - POWER
SCALE: 1/4"=1'-0"
PARTIAL
FLOOR PLAN -
POWER
E2.1
1. ALL ELECTRICAL PANELS ARE EXISTING UNLESS OTHERWISE
NOTED.
2. CONFIRM ALL LOCATIONS WITH OWNER AND ARCHITECT
PRIOR TO COMMENCEMENT OF WORK.
3. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
DIMENSIONAL LOCATIONS AND COORDINATION OF ALL
DEVICES.
4. CONTRACTOR SHALL VERIFY CIRCUIT BREAKER,
DISCONNECT SWITCH, STARTER AND FUSE SIZES WITH
SELECTED EQUIPMENT MANUFACTURER'S SHOP DRAWINGS
PRIOR TO PLACING ORDER.
5. CONTRACTOR TO VERIFY THAT SPACE AND CAPACITY
EXISTS IN ELECTRICAL PANELS SPECIFIED FOR NEW
CIRCUITS PRIOR TO CONSTRUCTION.
6. NEW CIRCUITS ARE FED FROM EXISTING PANELS. WIRE NEW
CIRCUITS TO EXISTING FREE CIRCUITS OR SPACES, OR AS
INDICATED ON DRAWINGS. PROVIDE NEW CIRCUIT BREAKER
FOR ALL NEW CIRCUITS REPLACING EXISTING BREAKERS.
CIRCUIT BREAKER SHALL MATCH EXISTING BREAKERS IN
MANUFACTURER, STYLE, TYPE AND INTERRUPTING RATING.
7. CIRCUITING AND PANEL SCHEDULES AS SHOWN ARE FOR
CLARITY ONLY. ELECTRICAL CONTRACTOR SHALL
COORDINATE IN FIELD USING EXISTING SPARE CIRCUITING
AND ADJUST PANEL SCHEDULES TO MATCH. CONTRACTOR
TO TRACE ALL EXISTING CIRCUITS PRIOR TO REUSE.
GENERAL NOTES:
COORDINATE LOCATION OF DUCT DETECTOR WITH
MECHANICAL CONTRACTOR. DUCT DETECTOR SUPPLIED BY
EC, INSTALLED BY MC AND WIRED BY EC.
CONNECT TO NEAREST 120V CIRCUIT USING 2#12, 1#12
GROUND IN 3/4" CONDUIT.
NOTES BY SYMBOL:
(THIS DRAWING ONLY)
CU-1 CU-2
ADDITION
ROOF
EXISTING
ROOF
ERV-1
PHASE ONEPHASE TWO
D
200/3/175/3
MDP-6
WP
PP-14
60/3/50/3
MDP-3
WP
PP-14
60/3/50/3
MDP-4
WP
PP-14
EF-1
30/1/20/3
PP-12
PERMIT DOCUMENTS
05/15/2026
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
ENGINEER OF RECORD:
DRAWN BY: xx
OWNER / CONTACT:
Dale Handelong
570-688-8268 dalehandelong@hotmail.com
22 South 2nd Street Emmaus, PA 18049
T: 610-297-0140 E: sam@scf-arch.com
These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect
PR
O
JE
C
T N
U M
BE
R
0-
M ou nt B et he l F ire
C o.
Ad di tio n to E xi st in g
Fi re
C om pa ny
N or th D el aw ar e
D riv e, M t.
Be th el
, P A
U pp er
M ou nt B et he l T w p, N or th am pt on C ou nt y
PARTIAL FLOOR PLAN - POWER
SCALE: 1/4"=1'-0"
PARTIAL
ROOF PLAN -
POWER
E2.2
1. COORDINATE EXACT LOCATION AND POWER REQUIREMENTS
OF MECHANICAL UNITS WITH MECHANICAL CONTRACTOR.
2. CONTRACTOR SHALL VERIFY CIRCUIT BREAKER,
DISCONNECT SWITCH, STARTER AND FUSE SIZES WITH
SELECTED EQUIPMENT MANUFACTURER'S SHOP DRAWINGS
PRIOR TO PLACING ORDER.
GENERAL NOTES:
COORDINATE LOCATION OF DUCT DETECTOR WITH
MECHANICAL CONTRACTOR. DUCT DETECTOR SUPPLIED BY
EC, INSTALLED BY MC AND WIRED BY EC.
NOTES BY SYMBOL:
(THIS DRAWING ONLY)
PERMIT DOCUMENTS
05/15/2026
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
ENGINEER OF RECORD:
DRAWN BY: xx
OWNER / CONTACT:
Dale Handelong
570-688-8268 dalehandelong@hotmail.com
22 South 2nd Street Emmaus, PA 18049
T: 610-297-0140 E: sam@scf-arch.com
These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect
PR
O
JE
C
T N
U M
BE
R
0-
M ou nt B et he l F ire
C o.
Ad di tio n to E xi st in g
Fi re
C om pa ny
N or th D el aw ar e
D riv e, M t.
Be th el
, P A
U pp er
M ou nt B et he l T w p, N or th am pt on C ou nt y
ELECTRICAL
DETAILS &
SCHEDULES
E3.0
PARTIAL SINGLE-LINE DIAGRAM
NO SCALE
ETR
EXIST.
CT
CABINET
EXIST.
MAIN
DISC.
EXIST.
PANEL
'A'
120/240V, 1Ø,3W
100A MCB
ETR ETR ETR
1ST FLOOR
EXISTING UTILITY POLE WITH
UTILITY TRANSFORMERS
LOCATED IN PARKING LOT
EXIST.
PANEL
'MDP'
120/240V, 3Ø,4W
400A MCB
ETR
EXISTING WIREWAY
EXIST.
UTILITY
METER
ETR
PANEL: A (EXISTING) BUS AMP: 225A AMPS MAIN BREAKER: 100A
MOUNTING: SURFACE PHASE: 1 WIRE: 3 VOLTAGE: 240/120 AIC: 10,000
CKT CIRCUIT DESCRIPTION
BREAKER WIRE GND
COND
LOAD KVA/PH LOAD
COND
GND WIRE BREAKER
CIRCUIT DESCRIPTION CKT
P AMP NO SIZE SIZE KVA A B KVA SIZE SIZE NO AMP P
1 LIGHTS ROW 1 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 1 (EXISTING) 2
3 LIGHTS ROW 2 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 2 (EXISTING) 4
5 LIGHTS ROW 3 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 3 (EXISTING) 6
7 LIGHTS ROW 4 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 4 (EXISTING) 8
9 LIGHTS ROW 5 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 5 (EXISTING) 10
11 LIGHTS ROW 6 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 6 (EXISTING) 12
13 LIGHTS ROW 7 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 7 (EXISTING) 14
15 BULLET LIGHTS (EXISTING) 1 20 0 0.0 0 20 1 BULLET LIGHTS (EXISTING) 16
17 COACH LIGHTS (EXISTING) 1 20 0 0.0 0 20 1 BULLET LIGHTS (EXISTING) 18
19 ELEC AIR CLEANERS (EXISTING) 1 20 0 0.0 0 20 1 RECEPTACLES STAGE (EXISTING) 20
21 ELEC AIR CLEANERS (EXISTING) 1 20 0 0.0 0 20 1 RECEPTACLES (EXISTING) 22
23 ELEC AIR CLEANERS (EXISTING) 1 20 0 0.0 0 20 1 RECEPTACLES (EXISTING) 24
25 EXISTING LOAD 1 20 0 0.0 0 20 1 RECEPTACLES (EXISTING) 26
27 DUSK-TO-DAWN EAST END (EXISTING) 1 20 0 0.0 0 20 1 BINGO BOARDS (EXISTING) 28
29 EMERGENCY UNITS (EXISTING) 1 20 0 0.0 0 20 1 EXITS & OUTSIDE DOOR LIGHTS (EXIST) 30
TOTAL KVA/PHASE 0.0 0.0
TOTAL KVA PANEL 0.0
TOTAL AMPS PANEL 0
PANEL: MDP (EXISTING) BUS AMP: 400A AMPS MAIN BREAKER: 400A
MOUNTING: SURFACE PHASE: 3 WIRE: 4 VOLTAGE: 240/120V AIC: 10,000
CKT CIRCUIT DESCRIPTION
BREAKER LOAD KVA/PH LOAD BREAKER
CIRCUIT DESCRIPTION CKT
P AMP KVA A B C KVA AMP P
1 HP-1 (NEW) * (4#1,1#8G IN 1 1/2"C) 3 100
9.2 18.5 9.2
100 3 HP-2 (NEW) * (4#1,1#8G IN 1 1/2"C) 29.2 18.5 9.2
9.2 18.5 9.2
3 CU-1 (NEW) * (4#6,1#10G IN 1"C) 3 50
3.8 7.7 3.8
50 3 CU-2 (NEW) * (4#6,1#10G IN 1"C) 43.8 7.7 3.8
3.8 7.7 3.8
5 SUBPANEL "PP" * (REFER TO PANEL SCHEDULE) 3 100
5.7 20.3 14.6
175 3 ERV-1 (NEW) * (4#2/0,1#6G IN 2"C) 65.2 19.8 14.6
8.1 22.7 14.6
TOTAL KVA PER PHASE 46.5 46.0 48.8 NOTE: " * " DENOTES PROVIDE NEW CIRCUIT BREAKER.
TOTAL KVA 141.3
TOTAL AMPS 339.8
EXIST.
PANEL
'ELECTRIC
HEAT' ('EH')
120/240V 3Ø,4W
200A MLO
ETR
240V 200A
ETR
EXISTING WIREWAY
1. NEW CIRCUITS ARE FED FROM EXISTING PANELS. WIRE NEW
CIRCUITS TO EXISTING FREE CIRCUITS OR SPACES, OR AS
INDICATED ON DRAWINGS. PROVIDE NEW CIRCUIT BREAKER
FOR ALL NEW CIRCUITS REPLACING EXISTING BREAKERS.
CIRCUIT BREAKER SHALL MATCH EXISTING BREAKERS IN
MANUFACTURER, STYLE, TYPE AND INTERRUPTING RATING.
GENERAL NOTES:
TYPICAL GFI RECEPTACLE WITH
WEATHER PROOF COVER (WHERE
INDICATED ON THE DRAWINGS)
GALVANIZED RIGID STEEL
CONDUIT WITH GOOSENECK
THROUGH THE ROOF
ROOF PENETRATION AND
SEAL BY GENERAL
CONTRACTOR
WEATHER
TIGHT NUT
FLEXIBLE LIQUID TIGHT
CONDUIT TO DISCONNECT
SWITCH
ROOF MEMBRANE BY
GENERAL CONTRACTOR
(TYPICAL)
ROOF INSULATION BY
GENERAL CONTRACTOR
(TYPICAL)
ROOF DECK BY GENERAL
CONTRACTOR (TYPICAL)
STEEL SUPPORT BY
ELECTRICAL
CONTRACTOR
ELECTRICAL CONDUIT
ELECTRICAL JUNCTION BOX BY
ELECTRICAL CONTRACTOR
12"
TYPICAL DISCONNECT SWITCH BY
ELECTRICAL CONTRACTOR MOUNTED ON
SIDE OF ROOF-TOP UNIT
WEATHER
TIGHT NIPPLE
CONDUIT ROOF PENETRATION FOR DISCONNECT DETAIL
NO SCALE
TYPICAL GFI RECEPTACLE WITH
WEATHER PROOF COVER (WHERE
INDICATED ON THE DRAWINGS)
GALVANIZED RIGID STEEL
CONDUIT WITH
GOOSENECK THROUGH
THE ROOF
ROOF PENETRATION AND
SEAL BY GENERAL
CONTRACTOR
WEATHER
TIGHT NUT
FLEXIBLE LIQUID TIGHT CONDUIT
ROOF MEMBRANE BY
GENERAL CONTRACTOR
ROOF INSULATION BY
GENERAL CONTRACTOR
ROOF DECK BY
GENERAL CONTRACTOR
STEEL SUPPORT BY
ELECTRICAL
CONTRACTOR
ELECTRICAL CONDUIT
ELECTRICAL JUNCTION BOX
BY ELECTRICAL
CONTRACTOR
12"
CONDUIT ROOF PENETRATION FOR RECEPTACLE DETAIL
NO SCALE
MINIMUM 1" THICK COMPOUND
WITHIN OPENING, FLUSH WITH
BOTH SURFACES OF THE WALL
GYPSUM WALLBOARD/STUD WALL ASSEMBLY
CONDUIT
MINIMUM 2-1/2" THICK MINERAL
WOOL INSULATION FIRMLY PACKED
SECTION 'A-A'
NOTE:
MINIMUM 2HR FIRE RATING OF SEALING ASSEMBLY
UL SYSTEM W-L-1027
REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED WALL LOCATIONS
A
A
WALL CONDUIT PENETRATION DETAIL
NO SCALE
FROM
REST
OF
CIRCUIT
EMT
6' - 0" FLEX
CONDUIT MAX.
(TYP)
TYPICAL LIGHT FIXTURE WIRING DETAIL
NO SCALE
PANEL: PP BUS AMP: 100A AMPS MAIN BREAKER: 100A
MOUNTING: RECESSED PHASE: 3 WIRE: 4 VOLTAGE: 240/120 AIC: 10,000
CKT CIRCUIT DESCRIPTION
BREAKER WIRE GND
COND
LOAD KVA/PH LOAD
COND
GND WIRE BREAKER
CIRCUIT DESCRIPTION CKT
P AMP NO SIZE SIZE KVA A B C KVA SIZE SIZE NO AMP P
1 RECEPTACLE - MEN'S ROOM 1 20 2 12 12 3/4" 0.2 0.4 0.2 3/4" 12 12 2 20 1 RECEPTACLE - WOMEN'S ROOM 2
3 RECEPTACLE - MEN'S ROOM 1 20 2 12 12 3/4" 0.2 0.4 0.2 3/4" 12 12 2 20 1 RECEPTACLE - WOMEN'S ROOM 4
5 RECEPTACLE - MECHANICAL ROOM 1 20 2 12 12 3/4" 0.2 0.7 0.5 3/4" 12 12 2 20 1 RECEPTACLES - NURSING/CHANGING 6
7 WATER COOLER 1 20 2 12 12 3/4" 0.4 0.6 0.2 3/4" 12 12 2 20 1 CP-1 8
9 CONVENIENCE RECEPTACLES 1 20 2 12 12 3/4" 0.9 1.9 1.0 3/4" 12 12 2 20 1 WH-1 10
EUH-1 2 25 3 10 10 3/4"
2.1 2.4 0.3 3/4" 12 12 2 20 1 EF-1 12
13 2.1 2.6 0.5 3/4" 12 12 2 20 1 ROOFTOP RECEPTACLES 14
EUH-2 2 25 3 10 10 3/4"
2.1 3.0 0.9 3/4" 12 12 2 20 1 LIGHTING - NEW ADDITION 16
17 2.1 2.8 0.7 3/4" 12 12 2 20 1 RECEPTACLES - FUTURE STORAGE 18
19 0.0 0.0 0.0 20
21 0.0 0.0 0.0 22
23 2.1 2.1 0.0 24
25 2.1 2.1 0.0 26
27 0.0 0.0 0.0 28
29 0.0 0.0 0.0 30
31 0.0 0.0 0.0 32
33 0.0 0.0 0.0 34
35 0.0 0.0 0.0 36
37 0.0 0.0 0.0 38
39 0.0 0.0 0.0 40
41 0.0 0.0 0.0 42
TOTAL KVA/PHASE 5.7 5.2 8.1
TOTAL KVA PANEL 19.0
TOTAL AMPS PANEL 46
NEW
PANEL
'PP'
NEW
4#1, 1#8G IN 1 1/2"C
PERMIT DOCUMENTS
05/15/2026
ARCHITECT OF RECORD:
Samantha Ciotti Falcone
AIA, LEED AP
ENGINEER OF RECORD:
DRAWN BY: xx
OWNER / CONTACT:
Dale Handelong
570-688-8268 dalehandelong@hotmail.com
22 South 2nd Street Emmaus, PA 18049
T: 610-297-0140 E: sam@scf-arch.com
These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect
PR
O
JE
C
T N
U M
BE
R
0-
M ou nt B et he l F ire
C o.
Ad di tio n to E xi st in g
Fi re
C om pa ny
N or th D el aw ar e
D riv e, M t.
Be th el
, P A
U pp er
M ou nt B et he l T w p, N or th am pt on C ou nt y
ELECTRICAL
SPECIFICATIONS
E4.0
PART 1 - GENERAL
ELECTRICAL SPECIFICATIONS
PART 2 - PRODUCTS
PART 3 - EXECUTION
A. IT IS THE INTENT OF THESE SPECIFICATIONS AND ACCOMPANYING DRAWINGS TO
GENERALLY DESCRIBE THE WORK NECESSARY FOR THE INSTALLATION OF A
COMPLETE ELECTRICAL, LIGHTING, AND POWER SYSTEM (INCLUDING FIRE ALARM).
B. THESE DRAWINGS AND SPECIFICATIONS ARE NOT INTENDED TO SHOW THE
LOCATION OF EVERY WIRE, CONDUIT, FITTING, ETC., BUT IS UNDERSTOOD THAT
THE CONTRACTOR SHALL FURNISH AND INSTALL ALL MATERIALS AND LABOR FOR
COMPLETE WORKABLE SYSTEMS UNLESS NOTED OTHERWISE IN THIS
SPECIFICATION OR ON THE DRAWINGS.
C. CONTRACTOR SHALL PROVIDE BUT NOT BE LIMITED TO:
1. COMPLETE SYSTEM OF WIRING FOR EMERGENCY LIGHTING, LIGHT AND
POWER, PLUMBING, HVAC EQUIPMENT, FIRE ALARM ALONG WITH TELEPHONE
AND DATA EQUIPMENT INSTALLATION.
2. ALL PANELS, SWITCHBOARDS, MOTOR CONTROLLERS, TRANSFORMERS,
DISCONNECTS, RECEPTACLES, SWITCHES, OUTLETS AND PLATES FOR SAME,
FEEDERS FROM PANELS AND RELATED APPURTNENANCES.
3. LIGHTING FIXTURES, LAMPS, BALLASTS AND APPURTENANCES.
D. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, FITTINGS OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR
COMPLETE INSTALLATION OF THE WORK. SUCH WORK MAY BE ACCOMPLISHED AT
THE SITE. ADDITIONAL BENDS, OFFSETS AND CONDUIT AS REQUIRED BY VERTICAL
AND HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS SHALL BE
PROVIDED TO COMPLETE THE WORK AT NO ADDITIONAL COST TO THE OWNER.
E. EXCEPT WHERE SHOWN IN DIMENSIONAL DETAIL, THE LOCATIONS OF SWITCHES,
RECEPTACLES, LIGHTS AND OTHER EQUIPMENT SHOWN ON PLANS ARE
APPROXIMATE. SUCH ITEMS SHALL BE PLACED SO AS TO ELIMINATE
INTERFERENCE WITH DUCTS, PIPING AND EQUIPMENT. THE EXACT LOCATION
SHALL BE DETERMINED IN THE FIELD. ALL DOOR SWINGS SHALL BE VERIFIED SO
THAT LIGHT SWITCHES ARE PROPERLY LOCATED.
F. FIELD VERIFY EXISTING CONDITIONS AND COORDINATE ALL WORK WITH ALL
OTHER TRADES, AND ACTUAL CONDITIONS IN FIELD.
G. ALL DEBRIS MATERIAL RESULTING FROM NEW WORK SHALL, UNLESS OTHERWISE
INDICATED, BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE PREMISES BY HIM.
A. PROVIDE (FURNISH AND INSTALL) ALL WORK SPECIFIED OR INDICATED, IN
CONFORMANCE WITH THE MANUFACTURER'S PUBLISHED INSTALLATION
INSTRUCTIONS, COMPLETE WITH ALL APPURTENANCES, ARRANGED TO MEET JOB
CONDITIONS, FOR COMPLETE OPERATING SYSTEMS IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE (NEC) AND ALL OTHER LOCAL CODES/REGULATIONS. ALL
EQUIPMENT AND MATERIALS INSTALLED SHALL BEAR THE LABEL OF THE
UNDERWRITER'S LABORATORIES, INC., WHERE SO REQUIRED BY THE NFPA
REGULATIONS.
A. APPROVAL OF MATERIALS AND EQUIPMENT WILL BE BASED ON THE
MANUFACTURER'S PUBLISHED DATA. PROOF THAT THE ITEMS FURNISHED
CONFORM TO THE SPECIFIED REQUIREMENTS AS INDICATED BELOW SHALL BE
SUBMITTED FOR APPROVAL.
B. WHERE MATERIAL AND EQUIPMENT ARE SPECIFIED TO CONFORM TO THE
STANDARDS OF THE UNDERWRITER'S LABORATORIES (UL), INC., THE UL LABEL OR
LISTING WILL BE ACCEPTABLE AS SUFFICIENT EVIDENCE THAT THE ITEMS CONFORM
TO REQUIREMENTS.
C. EQUIPMENT DESIGN, FABRICATION, TESTING, PERFORMANCE AND INSTALLATION
SHALL, UNLESS SHOWN OTHERWISE, COMPLY WITH AND MEET ALL THE APPLICABLE
REQUIREMENTS OF NFPA 70 (THE NEC), ANSI C2, REFERENCED INDUSTRIAL CODES
AND STANDARDS AND LOCAL CODES HAVING JURISDICTION.
A. ALL MATERIALS SHALL BE NEW. THE CONTRACTOR MAY SELECT DEVICES AS
INDICATED ON THESE DRAWINGS. SUBSTITUTES MAY BE SUBMITTED AND USED
WITH WRITTEN APPROVAL OF OWNER/ARCHITECT/ENGINEER. SUBMIT SHOP
DRAWINGS TO OWNER/ARCHITECT/ENGINEER FOR APPROVAL.
B. SHOP DRAWINGS SHALL INCLUDE BUT ARE NOT LIMITED TO:
1. LIGHTING FIXTURES
2. RECEPTACLES, BOXES, ENCLOSURES
3. PANELBOARDS
4. CONDUIT,WIRING, FITTINGS
5. DISCONNECT SWITCHES
6. SWITCHES, COVER PLATES
7. TIME CLOCKS, PHOTOCELLS AND LIGHTING CONTACTOR
C. SUBMITTALS SHALL BE MADE FOR THE EQUIPMENT LISTED ABOVE. THE ARCHITECT
SHALL MAKE THE ULTIMATE DECISION ON COLOR AND FINISH FOR ALL DEVICES
SUCH AS RECEPTACLES, SWITCHES, SWITCH PLATES, AS WELL AS ANY OTHER
CONTROL DEVICES. THIS APPROVAL SHALL BE MADE BEFORE ANY ITEMS ARE
ORDERED.
D. PRODUCT REQUIREMENTS: MATERIALS AND EQUIPMENT TO BE PROVIDED SHALL BE
THE STANDARD CATALOGED PRODUCTS OF MANUFACTURERS REGULARLY
ENGAGED IN THE MANUFACTURE OF THE PRODUCTS. MATERIALS AND EQUIPMENT
SHALL MEET THE SPECIFIED AND DETAILED REQUIREMENTS INDICATED, BE
SUITABLE FOR THE INSTALLATION SHOWN AND SHALL REPRESENT PRODUCTS THAT
HAVE BEEN IN SATISFACTORY USE AT LEAST TWO YEARS. PRODUCTS NOT MEETING
ALL SPECIFIED REQUIREMENTS WILL NOT BE ACCEPTED.
E. OWNER INSTRUCTION AND OPERATION MANUALS SHALL BE PROVIDED TO INSTRUCT
IN THE PROPER OPERATION AND MAINTENANCE OF ALL WORK. PROVIDE A MINIMUM
OF (3) THREE OPERATING MANUALS FOR ALL WORK.
A. ALL WORK AND MATERIALS SHALL CONFORM TO ALL CODES, ORDINANCES,
REGULATIONS, STANDARDS AND RULES. ALL PERMITS, UTILITY FEES AND COSTS,
INSPECTION CERTIFICATES AND APPROVALS SHALL BE SECURED AND PAID BY THE
CONTRACTOR.
B. WORK SHALL NOT BE COVERED UP NOR ENCLOSED UNTIL IT HAS BEEN INSPECTED,
TESTED AND APPROVED. ANY WORK THAT IS ENCLOSED OR COVERED UP BEFORE
SUCH INSPECTION AND TEST, SHALL BE UNCOVERED. AFTER IT HAS BEEN
INSPECTED AND APPROVED, ALL UNCOVERED ITEMS SHALL BE RESTORED TO ITS
ORIGINAL COVERED CONDITION AT NO ADDITIONAL COST TO THE OWNER.
C. SECURE ELECTRICAL INSPECTION CERTIFICATE FROM AUTHORIZED AGENT.
A. PLAN CONSTRUCTION SCHEDULE TO COORDINATE WITH ALL OTHER TRADES,
UNLESS A SCHEDULED CHANGE HAS BEEN ARRANGED WITH THE
OWNER/ARCHITECT/ENGINEER.
B. COORDINATION SHALL INCLUDE ADEQUATE CLEARANCES FOR THE INSTALLATION
AND MAINTENANCE OF EQUIPMENT AND PHYSICAL AND ELECTRICAL
REQUIREMENTS OF ITEMS OR EQUIPMENT REQUIRING CONNECTIONS.
A. EQUIPMENT AND MATERIALS STORED AT THE SITE, PRIOR TO FINAL INSTALLATION,
SHALL BE FULLY PROTECTED FROM DAMAGE, DIRT, DEBRIS, AND WEATHER. DENTS,
MARRED FINISHES AND OTHERWISE DAMAGED EQUIPMENT SHALL BE REPAIRED TO
ITS ORIGINAL CONDITION OR REPLACED.
A. SECURE ALL EQUIPMENT, DEVICES AND RACEWAYS.
B. ELECTRICAL COMPONENTS AND SYSTEMS AND THEIR ATTACHMENTS SHALL BE
DESIGNED TO RESTRAIN SEISMIC FORCES AS REQUIRED BY ALL AUTHORITIES AND
LOCAL ORDINANCES HAVING JURISDICTION
C. ALL CONDUITS SHALL BE SECURELY FASTENED WITHIN 3 FEET OF EACH OUTLET
BOX, JUNCTION BOX, CABINET, FITTING OR END OF CONDUIT, OR AS SHOWN ON THE
DRAWINGS.
D. SUPPORTS SHALL BE HOT-DIPPED GALVANIZED STEEL OR AS INDICATED ON THE
DRAWINGS.
E. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT OR
CONDUIT.
A. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED AS HEREIN SPECIFIED AND
INDICATED ON THE DRAWINGS. EQUIPMENT TO BE IDENTIFIED SHALL INCLUDE, BUT
NOT BE LIMITED TO THE FOLLOWING:
1. ELECTRICAL POWER AND BRANCH CIRCUIT CONDUCTORS
2. FEEDER CONDUITS
3. OUTLET BOXES (COVER PLATES)
4. PANELBOARDS
5. DISCONNECTS
B. NAMEPLATES SHALL GENERALLY BE BLACK TYPED LETTERS WITH WHITE
BACKGROUND OR WHITE TYPED LETTERS WITH BLACK BACKGROUND ON
LAMINATED PLASTIC WITH BEVELED EDGES. LETTERS SHALL BE A MINIMUM OF 1/8"
HIGH. CONDUIT MARKERS SHALL BE STANDARD PRE-PRINTED FLEXIBLE PLASTIC
SHEET MATERIAL OR SELF-ADHERING VINYL LABELS. WIRE MARKERS SHALL BE
LAMINATED PLASTIC NAMEPLATES, SELF-ADHERING VINYL LABELS OR TAPE. 3
C. PROVIDE A TYPED DIRECTORY FOR EACH PANELBOARD INDICATING THE ITEM/ITEMS
CONTROLLED BY EACH CIRCUIT. THE DIRECTORY SHALL BE LOCATED ON THE
INSIDE OF THE HINGED DOOR TO THE PANEL.
A. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED AS HEREIN SPECIFIED AND THE
CONTRACTOR SHALL REMOVE ALL MATERIALS/EQUIPMENT AS INDICATED ON
DRAWINGS IN THEIR ENTIRETY. ITEMS SURROUNDING THE MATERIALS/EQUIPMENT
TO BE REMOVED SHALL REMAIN UNDISTURBED AND INTACT.
B. THE CONTRACTOR SHALL REPAIR ANY MARRED OR DAMAGED SURFACES THAT ARE
THE RESULT OF THE DEMOLITION PROCESS.
C. ANY EQUIPMENT DAMAGED AS A RESULT OF THE DEMOLITION PROCESS SHALL BE
FIXED/RESTORED TO WORK AS NEW OR REPLACED IN LIKE KIND.
A. WIRE AND CONDUCTORS
1. INSULATED CURRENT-CARRYING WIRE AND GROUNDING CONDUCTORS SHALL
BE COPPER AND SHALL CONFORM TO NFPA 70 AND ASTM B3 (SOFT OR
ANNEALED COPPER WIRE).
2. CONDUCTORS NO. 10 AWG AND SMALLER SHALL BE SOLID ROUND COPPER
WIRE. CONDUCTORS NO. 8 AWG AND LARGER SHALL BE STRANDED
CONCENTRIC COPPER WIRE.
3. MULTICONDUCTOR CABLE: COMPLY WITH NEMA WC 70 FOR ARMORED CABLE
(TYPE AC) AND METAL-CLAD CABLE (TYPE MC) WITH GROUND WIRE (ONLY
ALLOWABLE FOR CIRCUITS 40A OR LESS). WHERE USED IN HEALTH CARE
FACILITIES, IT SHALL BE RATED PER NEC REQUIREMENTS. HEALTH CARE
FACILITY (HCF) CABLE SHALL BE OF ALUMINUM ARMOR, AND PROVIDED WITH
ALL NECESSARY CONNECTORS. MEET UL STANDARD 4; NEC ARTICLE 517.
4. THE CONTRACTOR SHALL PROVIDE APPROPRIATELY SIZED FEEDERS, BRANCH,
CONTROL AND MISCELLANEOUS CONDUCTORS APPROPRIATELY SIZED IN
CONFORMANCE WITH THE NATIONAL ELECTRIC CODE.
5. ALL WIRING SHALL BE INSTALLED IN CONDUIT OR MULTICONDUCTOR CABLE
WHERE ALLOWED.
6. BUILDING WIRE SHALL BE TYPE THW, THHN/THHW OR XHHW WITH A MINIMUM
TEMPERATURE RATING OF 75 DEGREES C.
7. A GREEN GROUND WIRE SHALL BE RUN WITH ALL CIRCUITS.
8. CONTRACTOR SHALL ACCOUNT FOR VOLTAGE DROP WHEN PROVIDING LONG
LEAD LENGTHS OF CONDUCTORS.
B. INSTALLATION
1. RACEWAYS AND WIRING SHALL BE INSTALLED AS INDICATED AND CIRCUITS
SHALL NOT BE COMBINED WITHOUT PRIOR APPROVAL.
2. CONDUCTORS OF SPECIAL SERVICE SYSTEMS AND POWER SYSTEMS SHALL
NOT OCCUPY THE SAME ENCLOSURE WITH LIGHT AND POWER CONDUCTORS
OR THE SAME ENCLOSURE WITH EACH OTHER. CONDUCTORS SHALL BE
CONTINUOUS WITH SPLICES AND CONNECTIONS MADE IN OUTLET, JUNCTION OR
PULL BOXES ONLY.
3. ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR CODED AS
FOLLOWS:
CONDUCTOR 208/120V 480/277V
PHASE A BLACK BROWN
PHASE B RED ORANGE
PHASE C BLUE YELLOW
NEUTRAL WHITE WHITE
GROUND GREEN GREEN
4. CONDUCTORS UP TO AND INCLUDING NO.8 AWG SHALL BE MANUFACTURED
WITH COLORED INSULATING MATERIALS. CONDUCTORS LARGER THAN NO.8
AWG SHALL HAVE ENDS IDENTIFIED WITH COLORED PLASTIC TAPE IN ALL
OUTLET, PULL OR JUNCTION BOXES. ALL CONTROL CIRCUIT CONDUCTORS
SHALL BE IDENTIFIED AT EACH CONNECTION POINT.
5. CONNECTIONS AND SPLICES SHALL BE MADE IN APPROVED ENCLOSURES
UTILIZING SOLDERLESS PRESSURE CONNECTORS AND ADEQUATE INSULATION
WITH VINYL-PLASTIC ELECTRICAL INSULATING TAPE. CONDUCTOR
IDENTIFICATION SHALL BE PROVIDED WITHIN EACH ENCLOSURE WHERE A TAP,
SPLICE OR TERMINATION IS MADE AND AT THE EQUIPMENT TERMINAL OF EACH
CONDUCTOR.
6. WHERE SEVERAL FEEDERS PASS THROUGH A COMMON PULLBOX, THE FEEDERS
SHALL BE TAGGED TO CLEARLY INDICATE THE ELECTRICAL CHARACTERISTICS,
CIRCUIT NUMBER AND PANEL DESIGNATION.
7. MAXIMUM CABLE PULLING TENSION SHALL NOT EXCEED VALUES
RECOMMENDED BY CABLE MANUFACTURER.
8. CIRCUIT CONDUCTORS SHALL BE SAME AWG SIZE FROM SOURCE TO LOAD.
NEUTRAL WIRES SHALL BE THE SAME SIZE AS PHASE WIRES EXCEPT AS NOTED
ON DRAWINGS.
9. ALL 600V RATED WIRE CONNECTIONS, NO.8 AWG AND LARGER, STUD-TYPE OR
FLAT-BAR TYPE EQUIPMENT TERMINALS SHALL BE TERMINATED WITH A
COMPRESSION TYPE LUG.
10. MULTICONDUCTOR CABLE MAY ONLY BE USED WHERE CONCEALED IN WALLS
OR ABOVE ACCESSIBLE CEILINGS IN ACCORDANCE WITH THE NEC.
MULTICONDUCTOR CABLE SHALL BE SUPPORTED INDEPENDENT OF CEILING
STRUCTURE.
11. MULTICONDUCTOR CABLE IN PLENUM SPACES SHALL BE COMPLIANT WITH NEC
300.22 - MC CABLE EMPLOYING A SMOOTH OR CORRUGATED METAL SHEATH
WITHOUT AN OVERALL NONMETALLIC COVERING.
A. PROVIDE ALL ELECTRICAL SYSTEM GROUNDS AS REQUIRED BY THE NATIONAL
ELECTRICAL CODE, AND THE NATIONAL ELECTRICAL SAFETY CODE.
B. THE FOLLOWING SHALL BE SOLIDLY GROUNDED:
1. CONDUIT SYSTEM (NEC ARTICLE 250)
2. ALL EQUIPMENT WITH ANY ELECTRICAL CONNECTIONS
3. NEUTRAL LEAD OF LOW TENSION SECONDARY SERVICE
C. A SEPARATE GROUNDING CONDUCTOR SHALL BE FURNISHED AND INSTALLED FOR
ALL ELECTRICAL CIRCUITS. ALL ELECTRICAL EQUIPMENT ENCLOSURES AND
CONDUCTOR ENCLOSURES SHALL BE GROUNDED.
D. ALL FEEDER DISCONNECTS AND BREAKERS RATED 1000 AMPERES AND ABOVE IN A
SOLIDLY GROUNDED WYE SYSTEM WITH GREATER THAN 150 VOLTS TO GROUND,
BUT NOT EXCEEDING 600 VOLTS PHASE TO PHASE SHALL BE PROVIDED WITH
GROUND FAULT PROTECTION.
A. RACEWAY
1. ELECTRICAL METALLIC TUBING (EMT) SHALL BE METALLIC CONDUIT OF THE THIN
WALL TYPE IN STRAIGHT LENGTHS, ELBOWS, OR BENDS AND SHALL CONFORM
TO ANSI C80.3 AND THE REQUIREMENTS OF UL 797.
2. COUPLINGS AND CONNECTORS FOR EMT SHALL BE HEX-NUT
EXPANSION-GLAND, COMPRESSION TYPE, ZINC OR CADMIUM-PLATED. CRIMP,
SPRING OR SET-SCREW TYPE FITTINGS ARE NOT ACCEPTABLE. WHERE EMT
ENTERS OUTLET BOXES, CABINETS OR OTHER ENCLOSURES, CONNECTORS
SHALL BE THE INSULATED-THROAT TYPE, WITH LOCKNUTS. FITTINGS SHALL
MEET THE REQUIREMENTS OF ANSI/NEMA FBI.
3. FLEXIBLE METALLIC CONDUIT (FMC) SHALL MEET THE REQUIREMENTS OF UL 1.
4. RIGID GALVANIZED STEEL CONDUIT (RMC) SHALL CONFORM TO UL 6 AND ANSI
C80.1. CONDUIT FITTINGS SHALL CONFORM TO ANSI/NEMA FBI.
5. INTERMEDIATE METAL CONDUIT (IMC) SHALL MEET THE REQUIREMENTS OF ANSI
C80.6.
6. FURNISH AND INSTALL BUSHINGS, AS MANUFACTURED BY O.Z. OR T&B
COMPANIES FOR ALL POWER SYSTEM CONDUITS AND LIGHTING CIRCUIT
CONDUITS 1-1/4" AND LARGER.
7. LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT (LTFMC): STEEL, CONSTRUCTED OF
SINGLE STRAP, FLEXIBLE CONTINUOUS, INTERLOCKED, AND DOUBLE-WRAPPED
METAL WITH A LIQUID-TIGHT JACKET OF FLEXIBLE POLYVINYL CHLORIDE (PVC)
CONFORMING TO NEMA RN1.
8. RIGID NONMETALLIC CONDUIT (RNC) SHALL COMPLY WITH NEMA TC2, SCHEDULE
40 AND SCHEDULE 80 PVC. RNC FITTINGS SHALL COMPLY WITH NEMA TC3,
MATCH TO CONDUIT TYPE AND MATERIAL.
B. BOXES
1. JUNCTION BOXES AND PULL BOXES SHALL HAVE SUFFICIENT VOLUME TO
ACCOMMODATE THE NUMBER OF CONDUCTORS ENTERING THE BOX IN
ACCORDANCE WITH THE REQUIREMENTS OF NFPA 70 ARTICLE 314. BOXES
SHALL BE CADMIUM-PLATED OR ZINC-COATED SHEETMETAL. JUNCTION BOXES
AND PULL BOXES FOR USE WITH THE CONDUIT SYSTEMS SHALL NOT BE LESS
THAN 1 1/2 " DEEP AND 4" BY 4". PULL AND JUNCTION BOXES SHALL BE
FURNISHED WITH HINGED OR SCREW-FASTENED COVERS.
C. INSTALLATION
1. CONDUIT AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70
AND AS SPECIFIED HEREIN.
2. INSTALL RACEWAYS SQUARE WITH BUILDING WALLS AND FASTENED TO
BUILDING STRUCTURE.
3. EMT SHALL BE INSTALLED INDOORS IN DRY LOCATIONS NOT SUBJECT TO
MECHANICAL INJURY. ALSO, CONCEALED CIRCUITS AND CIRCUITS LOCATED IN
PLENUM SHALL BE EMT UNLESS OTHERWISE NOTED.
4. RMC CONDUIT SHALL BE USED IN ALL OPEN SHOP AREAS TO A MINIMUM
ELEVATION OF 15'-0" AFF.
5. RMC AND IMC WITH THREADED FITTINGS SHALL BE INSTALLED OUTDOORS,
WHERE UNDERGROUND, OR IN AREAS SUBJECT TO WEATHER AND/OR
MECHANICAL INJURY.
6. RNC SHALL BE INSTALLED OUTDOORS, WHERE UNDERGROUND, OR IN AREAS
SUBJECT TO WEATHER AND/OR MECHANICAL INJURY. FOR RNC, USE
SOLVENT-CEMENTED JOINTS IN DUCTS AND FITTINGS AND MAKE WATERTIGHT
ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS. STAGGER
COUPLINGS SO THOSE OF ADJACENT DUCTS DO NOT LIE IN THE SAME PLANE.
7. FMC AND LTFMC WITH SEPARATE GROUND WIRE SHALL BE INSTALLED IN AREAS
SUBJECT TO VIBRATION IN MAXIMUM SIX FOOT LENGTHS PROPERLY
SUPPORTED.
8. WHERE APPLICABLE, CONDUITS SHALL BE FASTENED TO ALL SHEET METAL
BOXES, GUTTERS AND CABINETS WITH TWO LOCKNUTS AND A BUSHING.
9. THE CONTRACTOR SHALL FURNISH AND INSTALL ABOVE GRADE CONDUIT
SYSTEMS AS SPECIFIED, INCLUDING ALL NECESSARY SUPPORTS, HANGERS,
AND OTHER HARDWARE. IF THERE ARE ANY MAJOR DISCREPANCIES, CHANGES
OR QUESTIONABLE ROUTING, THE CONTRACTOR SHALL NOTIFY THE OWNER'S
REPRESENTATIVE FOR RESOLUTION AND/OR APPROVAL.
10. EXPOSED CONDUIT SHALL BE NEATLY AND EVENLY SPACED AND SHALL RUN
PARALLEL TO CEILING, FLOORS, WALLS OR OTHER PERMANENT STRUCTURES.
11. CONDUIT IN FINISHED AREAS SHALL BE INSTALLED CONCEALED.
12. CONDUIT SHALL BE SECURELY CLAMPED AND SUPPORTED AT LEAST EVERY 10
FEET VERTICALLY AND 8 FEET HORIZONTALLY. GALVANIZED PIPE STRAPS SHALL
BE FASTENED TO STRUCTURE WITH BOLTS, SCREWS AND ANCHORS.
13. CONDUIT AND BOXES SHALL NOT BE SUPPORTED FROM T-BAR CEILING WIRES.
14. EXPANSION FITTINGS WITH FLEXIBLE GROUND STRAP SHALL BE PROVIDED IN
CONDUIT RUNS CROSSING BUILDING EXPANSION JOINTS.
15. CONTRACTOR SHALL AVOID MORE THAN THREE 90 DEGREE BENDS, OR
EQUIVALENT, IN A RUN BETWEEN PULL FITTINGS.
16. EMERGENCY LIGHTING SYSTEM WIRING SHALL BE IN RIGID CONDUIT, EMT OR
SURFACE RACEWAY.
D. SAFTEY SWITCHES
1. SAFETY SWITCHES SHALL BE FUSED OR NON-FUSED AS REQUIRED. THEY
SHALL BE THE HEAVY-DUTY TYPE AS MANUFACTURED BY SIEMENS, GENERAL
ELECTRIC, SQUARE D OR APPROVED EQUAL. THE SAFETY SWITCHES SHALL
HAVE A POSITIVE QUICK MAKE AND QUICK BREAK OPERATING MECHANISM
WITH SAFETY INTERLOCKING COVER AND EXTERNAL OPERATING HANDLE.
E. RECEPTACLES
1. DUPLEX AND QUADRUPLEX RECEPTACLES SHALL BE FLUSH, HEAVY DUTY,
GENERAL USE, 20A, 120V, GROUNDING TYPE, INDUSTRIAL SPECIFICATION
GRADE AS MANUFACTURED BY HUBBELL OR APPROVED EQUAL, NEMA 5-20R
CONFIGURATION. COLOR SHALL BE IVORY.
2. GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLES SHALL BE STRAIGHT
BLADE, GENERAL USE, SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL
OR APPROVED EQUAL, NEMA 5-20 CONFIGURATION, 120V, COMPLYING WITH UL
498 AND UL 943. GFCI UNITS SHALL BE DESIGNED FOR INSTALLATION IN A 2 3/4"
DEEP OUTLET BOX WITHOUT AN ADAPTER. COLOR SHALL BE IVORY.
F. WALL SWITCHES, RECEPTACLE AND OTHER MISCELLANEOUS DEVICE PLATES
1. DEVICE PLATES AND RECEPTACLE COVER PLATES SHALL BE LABELED (ON THE
INSIDE) SHOWING THE CIRCUIT NUMBER.
2. FOR LOCATIONS WHERE THERE ARE MULTIPLE DEVICES, THE COVER PLATE
SHALL BE ONE SOLID PIECE TO SUIT THE DEVICES INSTALLED. ALL PLATES
SHALL FIT SNUGLY AND TIGHTLY AGAINST THE FINISHED BUILDING'S
SURFACES.
3. FOR THE CASE OF DIMMERS GANGED TOGETHER, THE CONTRACTOR SHALL
APPLY THE APPROPRIATE DERATING FACTORS AS THE MULTIPLE DIMMERS ARE
GANGED TOGETHER.
4. PLATES FOR SURFACE BOXES SHALL BE CADMIUM PLATED OR GALVANIZED.
G. BOXES AND FITTINGS
1. COMPLY WITH UL 514B, FITTINGS FOR CONDUIT AND OUTLET BOXES.
2. JUNCTION AND PULL BOXES SHALL BE INSTALLED WHERE SHOWN ON THE
DRAWINGS, OR AT SUCH LOCATIONS AS MAY BE REQUIRED TO FACILITATE THE
PULLING OF CABLES.
3. PULL BOXES SHALL BE FURNISHED AND INSTALLED ON CONDUIT RUNS LONGER
THAN 100 FEET OR WITH MORE THAN THREE RIGHT-ANGLE BENDS.
4. OUTLET BOXES SHALL BE EQUIPPED WITH PLASTER RINGS, EXTENSION RINGS
AND FIXTURE STUDS WHERE REQUIRED. ALL UNUSED OPENINGS IN BOXES
SHALL BE CLOSED WITH FACTORY MADE KNOCKOUT SEALS.
5. BOXES AND ENCLOSURES SHALL BE SECURELY MOUNTED TO THE BUILDING
STRUCTURE WITH SUPPORTING FACILITIES INDEPENDENT OF THE CONDUIT
ENTERING OR LEAVING THE BOXES.
H. INSTALLATION
1. WIRING DEVICES SHALL BE INSTALLED AND TESTED TO VERIFY THE UNITS ARE
WORKING AS INTENDED.
2. CONTRACTOR SHALL TROUBLESHOOT ANY DEVICES NOT FUNCTIONING
PROPERLY OR AS INTENDED. CONTRACTOR SHALL EITHER RESTORE THE
PROBLEMATIC DEVICE OR REPLACE IT IN LIKE KIND. RETEST UNTIL DEVICES
ARE VERIFIED TO BE IN WORKING CONDITION.
3. BARRIERS BETWEEN ADJACENT DEVICES SHALL BE INSTALLED WHERE
REQUIRED PER NEC 406.4(G).
A. CONTRACTOR SHALL PROVIDE AND INSTALL ENCLOSED BREAKERS AND SWITCHES
WITH TRIP RATINGS, REQUIRED POLES AND VOLTAGES AS INDICATED ON THE
DRAWINGS.
B. UNITS SHALL BE MANUFACTURED BY SIEMENS, GENERAL ELECTRIC, SQUARE D OR
APPROVED EQUIVALENT.
C. ENCLOSURES SHALL COMPLY WITH NEMA AB 1 AND NEMA KS 1 TO MEET
ENVIRONMENTAL CONDITIONS OF THE INSTALLED LOCATION. ENCLOSURES
SHALL BE NEMA 250, TYPE I, UNLESS OTHERWISE INDICATED.
D. COMPLY WITH APPLICABLE PORTIONS OF NECA 1, NEMA PB 1.1, AND NEMA PB 2.1
FOR INSTALLATION OF ENCLOSED SWITCHES AND CIRCUIT BREAKERS.
A. COMBINATION CONTROLLERS
1. COMBINATION MOTOR CONTROLLERS WITH DISCONNECT IN COMMON
ENCLOSURE, USING THERMAL MAGNETIC CIRCUIT BREAKER CONFORMING TO
NEMA AB1, WITH INTEGRAL THERMAL AND INSTANTANEOUS MAGNETIC TRIP IN
EACH POLE.
2. ENCLOSURE SHALL BE NEMA TYPE 1 UNLESS OTHERWISE NOTED AND
CONFORM TO NEMA ICS 6. ENCLOSURE SHALL BE FABRICATED FROM STEEL
AND FINISH SHALL BE MANUFACTURER'S STANDARD GRAY.
B. MOTOR DISCONNECTING SWITCHES
1. SHOULD ANY MOTORS BE LOCATED OUT OF SIGHT OR GREATER THAN 50 FEET
FROM THEIR CONTROLLERS, THE CONTRACTOR SHALL FURNISH AND INSTALL A
NON-FUSED SAFETY SWITCH IN CLOSE VICINITY TO THE MOTOR.
A. A FIXTURE SHALL BE INSTALLED AT EACH LOCATION INDICATED ON DRAWINGS.
B. NEW LAMPS OF THE PROPER TYPE AND WATTAGE SHALL BE INSTALLED
IMMEDIATELY PRIOR TO SUBSTANTIAL COMPLETION OF THE PROJECT.
CONTRACTOR SHALL REFER TO THE LIGHTING FIXTURE SCHEDULE. LAMPS SHALL
BE GENERAL ELECTRIC, OSRAM SYLVANIA, OR VENTURE LIGHTING.
C. FLUORESCENT LIGHTING FIXTURES IDENTIFIED AS INBOARD/OUTBOARD LIGHTS
SHALL BE THE TWO BALLAST TYPE. ONE BALLAST SHALL BE CIRCUITED TO THE
INBOARD LIGHTING CIRCUIT. THE OTHER BALLAST SHALL BE CIRCUITED TO A
SEPARATE, DEDICATED CIRCUIT. THESE FIXTURES SHALL BE TAGGED AS BEING
POWERED FROM TWO SEPARATE SOURCES. TANDEM WIRE THE BALLASTS WHERE
APPLICABLE PER IECC 2009.
D. FLUORESCENT FIXTURES SHALL CONFORM TO REQUIREMENTS IN THE LIGHTING
FIXTURE SCHEDULE. BALLASTS SHALL BE ENERGY SAVING, INSTANT START, SOLID
STATE ELECTRONIC.
E. BALLASTS SHALL HAVE A MINIMUM POWER FACTOR OF…
This is the start of the file's text. The full file is on GovTribe.