2-1066222.000 UMBT FIRE E 20260515.pdf

PDF 2 MB Posted

Attached to
Mt. Bethel Fire Co. - Emergency Shelter 2020-63
Solicitation number
Not on record
Issued by
Northampton County, Pennsylvania

About this file

This file comprises electrical construction drawings and specifications for the Mt. Bethel Fire Company's emergency shelter addition project (Project 2020-63) located at 2341 North Delaware Drive, Mt. Bethel, Pennsylvania 18343, Upper Mount Bethel Township, Northampton County. The project involves the installation of a complete electrical, lighting, and power system for approximately 2,000 square feet of new addition space, including new toilet and shower facilities, accessible entrance, and storage areas. The electrical work encompasses new lighting fixtures (Lithonia brand LED panels and recessed downlights), receptacles, switches, exit signage, emergency lighting systems, panelboards, motor controllers, and related appurtenances. Key electrical components include a new 100-ampere Panel PP fed from the existing 400-ampere main distribution panel (MDP), three new rooftop units (CU-1, CU-2, and ERV-1) with associated disconnect switches and circuits, branch circuit wiring, conduit systems in both metallic and non-metallic configurations, and fire alarm system provisions. A pre-bid meeting is scheduled for July 9, 2026, at 9:00 A.M., with bid submissions due by July 28, 2026, at 12:00 P.M. prevailing time. The construction documents include detailed specifications for materials, installation procedures, quality assurance requirements, and testing protocols.

The specifications require all electrical work to comply with the National Electrical Code (NEC) 2017, International Building Code (IBC) 2018, and International Energy Conservation Code (IECC) 2018. The electrical contractor must provide comprehensive documentation including shop drawings for equipment approval, as-built drawings upon project completion, operation and maintenance manuals, and commissioning documentation. All materials must be new and UL-listed where required, with circuit breakers matching existing panelboard manufacturers in style and interrupting rating. The contractor bears responsibility for all cutting, patching, demolition of existing equipment as indicated on the demolition drawings, and coordination with mechanical, plumbing, and HVAC contractors. A one-year warranty on all materials, equipment, and workmanship from the date of owner acceptance is required. The specifications include detailed requirements for lighting controls including occupancy sensors with automatic shutoff within 30 minutes, time-switch controls with daylight savings capability, dimming controls compatible with LED fixtures, and comprehensive functional testing and commissioning per IECC requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E0.0: ELECTRICAL INFORMATION SHEET

E1.1: PARTIAL FLOOR PLAN - LIGHTING

E2.1: PARTIAL FLOOR PLAN - POWER

E2.2: PARTIAL ROOF PLAN - POWER

E3.0: ELECTRICAL DETAILS & SCHEDULES

E4.0: ELECTRICAL SPECIFICATIONS

ED1.1: PARTIAL FLOOR PLAN - DEMOLITION - POWER

DRAWING LIST

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER & CATALOG NUMBER

MOUNTING

DESCRIPTION WATTAGE

SURF SUS REC HGT

A LITHONIA - #CPX 2X4 AL07 80CRI SWW7 A12 MVOLT ● 2X4 RECESSED FLAT PANEL LED SET TO 4000LM, 35K 36W

B LITHONIA - #LDN6 35/30 L06 AR LSS MVOLT GZ10 ● RECESSED LED DOWNLIGHT 35W

C LITHONIA - #LDN6 35/30 L06 AR LSS MVOLT GZ10 ● RECESSED LED DOWNLIGHT WET LOCATION LISTED 35W

D LITHONIA - #WDGE2 LED 35K 80CRI VF MVOLT SRM ● EXTERIOR WALL SCONCE 18W

F LITHONIA - #CPX 2X4 AL07 80CRI SWW7 A12 MVOLT

PAC 4DF 36 ● 2X4 FLAT PANEL LED SET TO 4000LM, 35K SUSPENDED FROM ROOF

STRUCTURE WITH AIR CRAFT KIT 36W

G LITHONIA - #CPX 2X2 AL07 80CRI SWW7 A12 MVOLT ● 2X2 RECESSED FLAT PANEL LED SET TO 3200LM, 35K 28W

H LITHONIA - #CPX 1X4 AL07 80CRI SWW7 A12 MVOLT ● 1X4 RECESSED FLAT PANEL LED SET TO 3200LM, 35K 25W

E LITHONIA - #EXRG-EL-M6 ● EXIT SIGN

E1 LITHONIA - #ECRG-HO-RD-M6 ● EXIT SIGN WITH COMBINATION HEADS

EM LITHONIA - #ELM4L ELA WG ● EMERGENCY LIGHT WITH BATTERY PACK

EX LITHONIA: ERE-GY-T-WP-SQ ● WEATHERPROOF DUAL REMOTE HEADS

GENERAL LIGHTING FIXTURE SCHEDULE NOTES:

1. PROVIDE CORRECT TRIM FOR ALL FIXTURES INSTALLED IN A HARD CEILING OR SPECIALTY CEILING TYPE.

2. PROVIDE ALL APPROPRIATE MOUNTING HARDWARE. PROVIDE BACK/MOUNTING BOXES AS RECOMMENDED BY MANUFACTURER.

3. COORDINATE LOCATION OF ALL EXIT SIGNS IN THE FIELD WITH OWNER SUPPLIED EQUIPMENT, BULK HEADS AND SIGNAGE TO ENSURE

VISIBILITY FROM AT LEAST HALFWAY TO NEXT SIGN OR TO THE EXIT.

4. PROVIDE DOUBLE OR SINGLE FACE EXIT SIGNS AS INDICATED ON THE DRAWINGS. PROVIDE ARROWS AS INDICATED.

5. ALL FIXTURE FINISHES AND DECORATIVE DETAILS SHALL BE SELECTED BY THE ARCHITECT PRIOR TO FINAL ORDER. COLORS SHALL BE

SELECTED FROM FULL COLOR LINE (BOTH STANDARD, CUSTOM, AND PREMIUM).

6. FIXTURES INDICATED ARE THE BASIS OF DESIGN. ALL EQUALS SHALL HAVE THE SAME PERFORMANCE AND GENERAL SHAPE AND

OPTIONS. ALL EQUALS ARE TO BE APPROVED BY THE ARCHITECT AND ENGINEER PRIOR TO ORDERING.

7. ALL FIXTURES CONNECTED TO A DIMMER, LIGHTING CONTROL SYSTEM, OR STAGE LIGHTING CONTROL SYSTEM SHALL HAVE DRIVER

THAT COORDINATES WITH CONTROLLER. COORDINATE BEFORE ORDERING. AUDITORIUM FIXTURE DRIVERS SHALL BE SELECTED AS PER THEATRICAL SYSTEM BASIS OF DESIGN REQUIREMENTS AND THEN COORDINATED PRIOR TO FINAL ORDERING WITH SELECTED SYSTEM.

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE BRANCH CIRCUIT WIRING TO ALL ITEMS WHICH REQUIRE

ELECTRICAL CONNECTIONS. WHERE BRANCH CIRCUIT WIRING IS NOT SHOWN,

CONTRACTOR SHALL CONNECT ITEMS TO THE CIRCUITS INDICATED. EXACT ROUTING

OF CONDUITS AND WIRING SHALL BE DETERMINED BY THE CONTRACTOR IN

ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND SPECIFICATIONS.

2. CONTRACTOR SHALL USE ONLY THOSE WIRING METHODS ALLOWED IN THE

SPECIFICATIONS.

3. A MAXIMUM OF 3 CIRCUITS SHALL BE RUN IN ONE CONDUIT, CIRCUITS MUST BE ON

SEPARATE PHASES. CIRCUITS SHALL NOT SHARE A COMMON NEUTRAL.

4. MINIMUM WIRE SIZE SHALL BE #12AWG. MINIMUM CONDUIT SIZE SHALL BE 3/4".

5. THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND

CONDITIONS AT THE SITE.

6. ALLOW CLEAR SPACE IN FRONT OF ALL PANELBOARDS, SWITCHBOARDS, ELECTRICAL

EQUIPMENT, ETC., AS REQUIRED BY NEC.

7. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES WITH HVAC DUCTWORK,

PIPING, AND EQUIPMENT.

8. ALL LIGHTING FIXTURES TO BE COMPATIBLE WITH THE CEILING CONSTRUCTION.

9. ELECTRICAL CONTRACTOR TO SUPPLY ALL GROUNDING & BONDING REQUIREMENTS

PER NEC.

10. ELECTRICAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING IN EXISTING

BUILDING RELATED TO THE NEW ELECTRICAL WORK.

11. ELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL

MATERIALS EQUIPMENT AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE

OF ACCEPTANCE BY OWNER.

12. THE ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ARCHITECT & ENGINEER

AS-BUILT DRAWINGS AND OPERATION AND MAINTENANCE MANUALS INCLUDING ALL

NAMEPLATE DATA, WIRING DIAGRAMS, MAINTENANCE INSTRUCTIONS AND PARTS LIST

UPON PROJECT COMPLETION.

13. ELECTRICAL CONTRACTOR SHALL MAINTAIN A CLEAN AND SAFE WORK AREA AT ALL

TIMES. ALL SAFETY PROCEDURES AND ENFORCEMENT IS THE RESPONSIBILITY OF THE

CONTRACTOR. THE CONTRACTOR SHALL CONFORM TO ALL OSHA STANDARDS.

14. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL ACCESS PANELS NECESSARY

FOR A CODE COMPLIANT INSTALLATION.

15. ENSURE ALL CONTACTORS ARE LABELED WITH LOADS CONTROLLED. ALL

CONTACTORS SHALL BE LOCATED NEAR ELECTRICAL PANEL.

16. THESE DRAWINGS AND SPECIFICATIONS ARE NOT INTENDED TO SHOW THE LOCATION

OF EVERY WIRE, CONDUIT, FITTING, ETC., BUT IS UNDERSTOOD THAT THE

CONTRACTOR SHALL FURNISH AND INSTALL ALL MATERIALS AND LABOR FOR

COMPLETE WORKABLE SYSTEMS UNLESS NOTED OTHERWISE IN THIS SPECIFICATION

OR ON THE DRAWINGS.

17. CONTRACTOR SHALL PROVIDE BUT NOT BE LIMITED TO:

17.1. COMPLETE SYSTEM OF WIRING FOR EMERGENCY LIGHTING, LIGHT AND POWER,

PLUMBING AND HVAC EQUIPMENT.

17.2. ALL PANELS, SWITCHBOARDS, MOTOR CONTROLLERS, TRANSFORMERS,

DISCONNECTS, RECEPTACLES, SWITCHES, OUTLETS AND PLATES FOR SAME,

FEEDERS FROM PANELS AND RELATED APPURTNENANCES.

17.3. LIGHTING FIXTURES, LAMPS, BALLASTS AND APPURTENANCES.

18. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, FITTINGS OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR

COMPLETE INSTALLATION OF THE WORK. SUCH WORK MAY BE ACCOMPLISHED AT THE

SITE. ADDITIONAL BENDS, OFFSETS AND CONDUIT AS REQUIRED BY VERTICAL AND

HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS SHALL BE PROVIDED

TO COMPLETE THE WORK AT NO ADDITIONAL COST TO OWNER.

19. EXCEPT WHERE SHOWN IN DIMESIONAL DETAIL, THE LOCATIONS OF SWITCHES,

RECEPTACLES, LIGHTS, AND OTHER EQUIPMENT SHOWN ON PLANS ARE

APPROXIMATE. SUCH ITEMS SHALL BE PLACED SO AS TO ELIMINATE INTERFERENCE

WITH DUCTS, PIPING AND EQUIPMENT. THE EXACT LOCATION SHALL BE DETERMINED IN

THE FIELD. ALL DOOR SWINGS SHALL BE VERIFIED SO THAT LIGHT SWITCHES ARE

PROPERLY LOCATED.

20. FIELD VERIFY EXISTING CONDITIONS AND COORDINATE ALL WORK WITH ALL OTHER

TRADES, AND ACTUAL CONDITIONS IN FIELD.

MOUNTING HEIGHT NOTES:

1. MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED.

IN MASONRY CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE

USED FOR REFERENCE TO NEAREST BLOCK OF BRICK COURSING.

2. THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS

SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWING OR

SPECIFICATIONS.

3. A '+' BESIDE A DEVICE INDICATES THAT DEVICE IS MOUNTED ABOVE A

COUNTER OR CASEWORK. COORDINATE WITH ARCHITECTURAL ROOM

ELEVATIONS, DETAILS, AND CASEWORK CONTRACTOR.

THE ELECTRICAL SYSTEMS PRESENTED ON THE SUBSEQUENT

DRAWINGS WERE DESIGNED IN ACCORDANCE WITH THE

FOLLOWING APPLICABLE CODES AND STANDARDS

· THE NATIONAL ELECTRICAL CODE (NEC), 2017

· INTERNATIONAL BUILDING CODE (IBC), 2018

· INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2018

SIGNAL SYSTEM

SMOKE DETECTOR

DUCT MOUNTED SMOKE DETECTOR

CARBON MONOXIDE DETECTOR

HEAT DETECTOR

ABBREVIATIONS & SYMBOL

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ATS AUTOMATIC TRANSFER SWITCH

CT COUNTERTOP

DC DUCT COIL

DF DRINKING FOUNTAIN

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

ERL EXISTING TO BE RELOCATED

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

GC GENERAL CONTRACTOR

GF GROUND FAULT INTERRUPTER

HC HVAC CONTRACTOR

HP HEAT PUMP

HV HIGH VOLUME

KES KITCHEN EQUIPMENT SUPPLIER

MW MICROWAVE

PC PLUMBING CONTRACTOR

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER

WM WALL MOUNTED

WP WEATHERPROOF

DRAWING NOTE BY SYMBOL

GENERAL ELECTRICAL DEMOLITION NOTES:

1. DEMOLITION OF ALL EXISTING ELECTRICAL EQUIPMENT AND ASSOCIATED PIPING SHALL BE

COORDINATED WITH NEW WORK INSTALLATION.

2. THIS CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY/ALL DAMAGES TO EXISTING

FLOORS, FLOOR TILES, WALLS, CEILINGS, FURNISHINGS, ETC. DUE TO THE REMOVAL

PROCESS OF ELECTRICAL EQUIPMENT AND ALL ASSOCIATED ITEMS.

3. ALL MATERIAL AND EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OF BY THE

CONTRACTOR.

4. CONTRACTOR SHALL REMOVE ALL EXISTING LIGHTING FIXTURES WHERE NEW FIXTURES

ARE SHOWN. THIS SHALL INCLUDE FITTINGS, SUPPORT DEVICES, ETC AND MAKE

PROVISIONS TO EXISTING CEILING SO THAT THE NEW FIXTURE MAY BE PROPERLY

INSTALLED.

5. MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS REMAINING IN OTHER AREAS.

6. ALL EXISTING CONDUITS AND WIRING NOT BEING USED SHALL BE REMOVED BACK TO

SOURCE.

7. WHERE MODIFICATIONS OR ADDITIONS TO EXISTING WORK IS TO BE DONE BY ANOTHER

CONTRACTOR, EXISTING EQUIPMENT, CONDUIT, DEVICES, SUPPORTS, AND

APPURTENANCES SHALL BE REMOVED AND REINSTALLED TO ACCOMMODATE

MODIFICATIONS OR ADDITIONS. THIS SHALL INCLUDE THE ADDITION OF DOORS, WALLS,

STRUCTURAL SUPPORTS, UNITS, ETC. COORDINATE WITH OTHER CONTRACTORS IN THE

FIELD PRIOR TO WORK COMMENCING. WHERE THE QUANTITY OF WORK CANNOT BE

DETERMINED PRIOR TO BID DUE TO CONCEALED CONDITIONS, PROVIDE $5,000

ALLOWANCE.

8. DEVICES SHOWN ARE BASED ON EXISTING DRAWINGS AND SITE SURVEY WHILE BUILDING

WAS IN OPERATION. ACTUAL LOCATIONS AND QUANTITIES MAY VARY. VERIFY IN FIELD.

9. ALL DORMANT CABLING AND WIRING SHALL BE REMOVED UNLESS NOTED AS FOR FUTURE

OR AS INSTRUCTED OTHERWISE BY OWNER.

10. COORDINATE THE REMOVAL OF THE POWER CONNECTIONS TO ALL MECHANICAL

EQUIPMENT TO BE REMOVED WITH THE MECHANICAL CONTRACTOR.

11. ALL CIRCUIT BREAKERS WHERE THE LOAD SERVING HAS BEEN REMOVED SHALL BE

MARKED AS SPARE.

12. ALL PANELBOARDS MODIFIED UNDER THE WORK SHALL RECEIVE REVISED, TYPED PANEL

SCHEDULES AS PROVIDED WITH ALL NEW PANELBOARDS.

13. REPLACE ANY DAMAGED EXISTING TO REMAIN ELECTRICAL, LIGHTING, AND LOW VOLTAGE

EQUIPMENT IN KIND.

14. EXTEND WIRING IN KIND FOR DEVICES TO BE REINSTALLED IN NEW CEILING AS

NECESSARY.

15. ALL SURFACE MOUNTED DEVICES SHALL BE INSTALLED IN 1 OR 2 SECTION SURFACE

MOUNTED RACEWAY AS REQUIRED TO ACCOMODATE BOTH LOW VOLTAGE AND LINE

VOLTAGE CABLES IN THE SAME RACEWAY. REFER TO SURFACE MOUNTING DETAIL FOR

MORE INFORMATION.

16. VERIFY IF BUILDING HAS PLENUM RETURN. IF PLENUM RETURN EXISTS, PROVIDE ALL

EXPOSED CABLING INSTALLED WITHIN PLENUM AS PLENUM RATED CABLE.

LIGHTING

2'x2' LIGHTING FIXTURE

2'x4' LIGHTING FIXTURE

2'x4' LIGHTING FIXTURE - EMERGENCY

1'x4' LIGHTING FIXTURE

WALL PACK LIGHTING FIXTURE

ROUND RECESSED DOWNLIGHT FIXTURE

NORMAL EMERGENCY FIXTURE

EMERGENCY BATTERY UNIT

REMOTE HEAD

EXIT SIGN - DOUBLE FACE

EXIT SIGN - CEILING MOUNTED WITH DIRECTIONAL ARROWS

EXIT SIGN - SINGLE FACE

WALL SCONCE

WIRING DEVICES

SINGLE POLE SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

3-WAY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

4-WAY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

KEY SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

SPRING WOUND TIME SWITCH, 5-MINUTE MAXIMUM DURATION

- 3'-10" AFF UNLESS OTHERWISE NOTED

SPRING WOUND TIME SWITCH, 1-HOUR MAXIMUM DURATION -

3'-10" AFF UNLESS OTHERWISE NOTED

DIMMER SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

MANUAL MOTOR STARTER SWITCH - 3'-10" AFF UNLESS

OTHERWISE NOTED

3-WAY DIMMER SWITCH - 3'-10" AFF UNLESS OTHERWISE

NOTED

OCCUPANCY SENSOR SWITCH - 3'-10" AFF UNLESS OTHERWISE

NOTED

PILOT LIGHT SWITCH - 3'-10" AFF UNLESS OTHERWISE NOTED

MANUAL OVERRIDE

SWITCH WITH OCCUPANCY SENSOR AND DIMMING CAPABILITY

- 3'-10" AFF UNLESS NOTED OTHERWISE

DUAL TECHNOLOGY OCCUPANCY SENSOR - 360°

DUAL TECHNOLOGY OCCUPANCY SENSOR - CORRIDOR

PATTERN

DUAL TECHNOLOGY OCCUPANCY SENSOR - CORNER MOUNT

CEILING MOUNTED DAYLIGHT SENSOR

MULTIPLE BUTTON DIGITAL CONTROL STATION WITH ON/OFF -

3'-10" AFF UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE - NEMA 5-20R, MOUNT 1'-6" AFF UNLESS

OTHERWISE NOTED

COUNTERTOP DUPLEX RECEPTACLE MOUNT 3" ABOVE

BACKSPLASH OR AT 3'-10"

TAMPERPROOF DUPLEX RECEPTACLE - NEMA 5-20R, MOUNT

1'-6" AFF UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE WITH USB PORT - MOUNT AT 1'-6"

UNLESS OTHERWISE NOTED

SINGLE RECEPTACLE - MOUNT 1'-6" AFF UNLESS OTHERWISE

NOTED

GFI DUPLEX RECEPTACLE - MOUNT AT 1'-6" AFF UNLESS

OTHERWISE NOTED

DUPLEX RECEPTACLE WITH TOP SWITCHED - 1'-8" AFF UNLESS

OTHERWISE NOTED

QUAD RECEPTACLE - NEMA 5-20R, MOUNT 1'-6" AFF UNLESS

OTHERWISE NOTED

SINGLE PHASE SPECIAL RECEPTACLE - MOUNT 1'-6" AFF

UNLESS OTHERWISE NOTED

THREE PHASE SPECIAL RECEPTACLE - MOUNT 1'-6" AFF

UNLESS OTHERWISE NOTED

FLOOR MOUNTED DUPLEX RECEPTACLE

PANELBOARDS

SURFACE MOUNTED PANEL

FLUSH MOUNTED PANEL

EXISTING SURFACE MOUNTED PANEL

EXISTING FLUSH MOUNTED PANEL

CIRCUITING

JUNCTION BOX

BRANCH CIRCUIT NUMBER FOR ALL ITEMS IN THIS ROOM

UNLESS OTHERWISE INDICATED - (*) INDICATES CONNECTION

TO CIRCUIT NUMBER SHOWN NEXT TO DEVICE

DEMOLITION DRAWING LINETYPE DESIGNATIONS

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NOTE:

NOT ALL ABBREVIATIONS AND SYMBOLS INDICATED MAY APPEAR ON THESE

CONTRACT DRAWINGS. THIS IS FOR REFERENCE ONLY.

CONTROL EQUIPMENT

MANUAL MOTOR STARTER - OVERLOADS SIZED TO

ACCOMODATE MOTOR - 4'-0" AFF UNLESS OTHERWISE NOTED

COMBINATION MOTOR STARTER - TYPE/SIZE/NEMA

ENCLOSURE AS INDICATED - MOUNT 4'-6" AFF TO CENTERLINE

OF OPERATING HANDLE. PROVIDE OVERCURRENT AND

OVERLOADS IN ACCORDANCE WITH MANUFACTURERS'

RECOMMENDATIONS FOR MOTOR HP

MOTOR - HORSEPOWER AS INDICATED

DISCONNECT SWITCH - AMPS/POLES/FUSES/NEMA

ENCLOSURE AS INDICATED - MOUNT 4'-6" AFF TO CENTERLINE

OR OPERATING HANDLE

TRANSFORMER

STANDARD MOUNTING HEIGHTS

9" BELOW

FINISHED

CEILING

WALL-MOUNTED CLOCKS, PROGRAM

BELLS, (OR AS SHOWN ON

ARCHITECTURAL DETAIL)

6" ABOVE DOOR NURSE CALL DOME LIGHT

6" ABOVE FIRE

HOUSE

CABINET

RED SIGNAL LIGHT

10'-0"

BATTERY LIGHTING UNITS AND REMOVE

WALL MOUNTED LIGHT HEADS (OR 1'-0"

BELOW FINISHED CEILING OF TOP UNIT)

8'-6" PENDANT-HUNG INDUSTRIAL AND STRIP

LIGHTING FIXTURES

7'-8"+

TELEVISION OUTLET AND SERVICE

RECEPTACLE - FOR SHELF MOUNTED

T.V. IN BEDROOMS

7'-6" OR 6" BELOW FINISHED CEILING,

WHICHEVER IS LOWER

CENTER ABOVE

DOOR OR WINDOW

OPENING

WARNING AND SIGNALING

FIXTURES/SIGNS

6'-8"

OR 6" BELOW FINISHED CEILING

WHICHEVER IS LOWER. FIRE ALARM

SIGNAL DEVICES AND ILLUMINATED FIRE

SIGNALS

6'-6"

TOP OF FLUSH AND SURFACE MOUNTED

ELECTRICAL LIGHTING OR POWER

PANELBOARDS AND TELEPHONE

CABINETS

6'-3"

TOP OF BACK-MOUNTED WALL EXIT

FIXTURES (NOT MOUNTED ABOVE

DOORS)

6'-0"

TOP OF HIGHEST ELECTRICAL SAFETY

DISCONNECT SWITCHES, MAGNETIC

STARTERS, CONTACTORS

4'-6"

CENTERLINE OF OPERATING HANDLE

FOR WALL MOUNTED DISCONNECT

SWITCHES AND MOTOR STARTERS;

WALL MOUNTED TELEPHONE AND PAY

STATIONS (3'-6" AT HANDICAP

LOCATIONS VERIFY EXACT HEIGHT

PRIOR TO ROUGH-IN)

3'-10"

WALL PHONE, ELECTRICAL DEVICE

LIGHTING SWITCHES, MANUAL MOTOR

STARTERS, SECURITY CARD, AND GFI

RECEPTACLES IN TOILET ROOMS OR

FOR SEPERATE SINKS NOT IN

CASEWORK

3'-6" FIRE ALARM PULL STATIONS

2'-0"

ELECTRICAL RECEPTACLES WITHIN

MECHANICAL SPACES, ELECTRICAL,

AND ELEVATOR ROOMS

1'-6"

ELECTRICAL RECEPTACLES,

TELEPHONE OUTLETS, DATA OUTLETS,

TELEPHONE/DATA OULETS

0" FINISHED FLOOR

M

T

30/3/NF/12

FVNR/SIZE1/3R

MS

CT

W

F

F

F

M

S

MS

S

D

C

H

P-1

ROOM #

ROOM NAME

OS

S

CT

T

DS

OS

USB

Dos

S

4S

KS

T5S

TS

DS

MS

3DS

OSS

PS

MOS

S

OS

LCS

J

PERMIT DOCUMENTS

05/15/2026

ARCHITECT OF RECORD:

Samantha Ciotti Falcone

AIA, LEED AP

ENGINEER OF RECORD:

DRAWN BY: xx

OWNER / CONTACT:

Dale Handelong

570-688-8268 dalehandelong@hotmail.com

22 South 2nd Street Emmaus, PA 18049

T: 610-297-0140 E: sam@scf-arch.com

These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect

PR

O

JE

C

T N

U M

BE

R

0-

M ou nt B et he l F ire

C o.

Ad di tio n to E xi st in g

Fi re

C om pa ny

N or th D el aw ar e

D riv e, M t.

Be th el

, P A

U pp er

M ou nt B et he l T w p, N or th am pt on C ou nt y

ELECTRICAL

INFORMATION

SHEET

E0.0

EXISTING SIREN

POLES

EXISTING SHED

A

C C

C C

B B

B B

OS

S

S

OS

OS

S

OS OS

OS

SOS

SD

O

S

S O S

S O

S

ST ST

S O

S

S4

S3

EM

EM

E E

EX

E1

D

1 1 1

A-30

A-30

A-30

A-30

A-30

D D

S3

OS

OS

A

2 2

A

EXISTING

OFFICE

CORRIDOR

CHANGING

EXISTING

STORAGE

NURSING/

CHANGING

WOMEN

103TABLE & CHAIR

STORAGE

MEN

ACCESSIBLE

CHANGING

CORRIDOR

C

S

OS

3 3

PHASE ONEPHASE TWO

A

AA

F F F

F F

E1A-30E1A-30

AA

A

A

AA

EM A-30

EM A-30

F

A A

A A

OS

OS

OS

EM

A-30

G

G

H

EM

A-30

EM

A-30

EM A-30

RENOVATED

TOILET/EXTRACTOR ROOM

EXISTING

GARAGE

EXISTING

BANQUET HALL

EXISTING

MULTI-PURPOSE ROOM

EXISTING

EXISTNG

KITCHEN

PERMIT DOCUMENTS

05/15/2026

ARCHITECT OF RECORD:

Samantha Ciotti Falcone

AIA, LEED AP

ENGINEER OF RECORD:

DRAWN BY: xx

OWNER / CONTACT:

Dale Handelong

570-688-8268 dalehandelong@hotmail.com

22 South 2nd Street Emmaus, PA 18049

T: 610-297-0140 E: sam@scf-arch.com

These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect

PR

O

JE

C

T N

U M

BE

R

0-

M ou nt B et he l F ire

C o.

Ad di tio n to E xi st in g

Fi re

C om pa ny

N or th D el aw ar e

D riv e, M t.

Be th el

, P A

U pp er

M ou nt B et he l T w p, N or th am pt on C ou nt y

PARTIAL FLOOR PLAN - LIGHTING

SCALE: 1/4"=1'-0"

PARTIAL

FLOOR PLAN -

LIGHTING

E1.1

1. ALL LIGHT FIXUTURES SHOWN ARE NEW UNLESS

OTHERWISE NOTED.

2. WIRE EXIT LIGHTS AND EMERGENCY LIGHTS TO

THE UNSWITCHED LEG OF THE LOCAL LIGHTING

CIRCUIT.

3. CONFIRM ALL LIGHTING FIXTURE TYPES AND

LOCATIONS WITH OWNER AND ARCHITECT PRIOR

TO COMMENCEMENT OF WORK.

4. REFER TO ARCHITECTURAL DRAWINGS FOR

EXACT DIMENSIONAL LOCATIONS AND

COORDINATION OF ALL DEVICES.

5. NEW CIRCUITS ARE FED FROM EXISTING PANELS.

WIRE NEW CIRCUITS TO EXISTING FREE

CIRCUITS OR SPACES, OR AS INDICATED ON

DRAWINGS. PROVIDE NEW CIRCUIT BREAKER

FOR ALL NEW CIRCUITS REPLACING EXISTING

BREAKERS. CIRCUIT BREAKER SHALL MATCH

EXISTING BREAKERS IN MANUFACTURER, STYLE,

TYPE AND INTERRUPTING RATING.

6. CIRCUITING AND PANEL SCHEDULES AS SHOWN

ARE FOR CLARITY ONLY. ELECTRICAL

CONTRACTOR SHALL COORDINATE IN FIELD

USING EXISTING SPARE CIRCUITING AND ADJUST

PANEL SCHEDULES TO MATCH. CONTRACTOR TO

TRACE ALL EXISTING CIRCUITS PRIOR TO REUSE.

GENERAL NOTES:

EXTERIOR FIXTURES SHALL BE CONTROLLED

VIA AN EXTERIOR MOUNTED PHOTOCELL

FACING THE NORTH SKY. CONNECT

EXTERIOR FIXTURES TO CIRCUIT CURRENTLY

SERVING EXISTING EXTERIOR

BUILDING-MOUNTED FIXTURES.

ALL NEW LIGHTING TO BE FED FROM NEW

PANEL "PP" CIRCUIT #16 UNLESS OTHERWISE

NOTED. REFER TO PANEL SCHEDULE.

CONNECT TO NEAREST 120V CIRCUIT USING

2#12, 1#12 GROUND IN 3/4" CONDUIT.

NOTES BY SYMBOL:

(THIS DRAWING ONLY)

EXISTING SHED

WH-1CP-1

HP-1

EUH-2

EXISTING

OFFICE

EXISTING ATS

EXISTING MAIN DISCONNECT

EXISTING METER AND CT CABINETEXISTING 125kW GENERATOR

EXISTING ELECTRICAL SPACE

CTCT

WP

EXISTING 400A PANEL

"MDP"

EXISTING 100A PANEL

"A"

PP-18

PP-9

PP-1

PP-6

PP-9

PP-4

EH-37

30/1/20/1J

MDP-1

100/3/100/1

PP-15,17

30/2/25/1

PP-11,13

30/2/25/1

HP-2 100/3/100/1

MDP-2

D

D

CT

PP-3

CT

PP-2

PP-6

PP-6

PP-5

PP-7

PP-9

PP-9

PP-9

NEW PANEL "PP"

PP-18

PP-18

PP-18

M

PP-8 PP-10

CORRIDOR

CHANGING

EXISTING

STORAGE

EXISTING

BANQUET HALL

EXISTING

MULTI-PURPOSE ROOM

NURSING/

CHANGING

WOMEN

103TABLE & CHAIR

STORAGE

MEN

ACCESSIBLE

CHANGING

CORRIDOR

CT

PHASE ONEPHASE TWO

RELOCATED

EXISTING ELECTRIC

WALL HEATER

EUH-1

RENOVATED

TOILET/EXTRACTOR ROOM

EXISTING

GARAGE

EXISTING

EXISTNG

KITCHEN

PERMIT DOCUMENTS

05/15/2026

ARCHITECT OF RECORD:

Samantha Ciotti Falcone

AIA, LEED AP

ENGINEER OF RECORD:

DRAWN BY: xx

OWNER / CONTACT:

Dale Handelong

570-688-8268 dalehandelong@hotmail.com

22 South 2nd Street Emmaus, PA 18049

T: 610-297-0140 E: sam@scf-arch.com

These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect

PR

O

JE

C

T N

U M

BE

R

0-

M ou nt B et he l F ire

C o.

Ad di tio n to E xi st in g

Fi re

C om pa ny

N or th D el aw ar e

D riv e, M t.

Be th el

, P A

U pp er

M ou nt B et he l T w p, N or th am pt on C ou nt y

PARTIAL FLOOR PLAN - POWER

SCALE: 1/4"=1'-0"

PARTIAL

FLOOR PLAN -

POWER

E2.1

1. ALL ELECTRICAL PANELS ARE EXISTING UNLESS OTHERWISE

NOTED.

2. CONFIRM ALL LOCATIONS WITH OWNER AND ARCHITECT

PRIOR TO COMMENCEMENT OF WORK.

3. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT

DIMENSIONAL LOCATIONS AND COORDINATION OF ALL

DEVICES.

4. CONTRACTOR SHALL VERIFY CIRCUIT BREAKER,

DISCONNECT SWITCH, STARTER AND FUSE SIZES WITH

SELECTED EQUIPMENT MANUFACTURER'S SHOP DRAWINGS

PRIOR TO PLACING ORDER.

5. CONTRACTOR TO VERIFY THAT SPACE AND CAPACITY

EXISTS IN ELECTRICAL PANELS SPECIFIED FOR NEW

CIRCUITS PRIOR TO CONSTRUCTION.

6. NEW CIRCUITS ARE FED FROM EXISTING PANELS. WIRE NEW

CIRCUITS TO EXISTING FREE CIRCUITS OR SPACES, OR AS

INDICATED ON DRAWINGS. PROVIDE NEW CIRCUIT BREAKER

FOR ALL NEW CIRCUITS REPLACING EXISTING BREAKERS.

CIRCUIT BREAKER SHALL MATCH EXISTING BREAKERS IN

MANUFACTURER, STYLE, TYPE AND INTERRUPTING RATING.

7. CIRCUITING AND PANEL SCHEDULES AS SHOWN ARE FOR

CLARITY ONLY. ELECTRICAL CONTRACTOR SHALL

COORDINATE IN FIELD USING EXISTING SPARE CIRCUITING

AND ADJUST PANEL SCHEDULES TO MATCH. CONTRACTOR

TO TRACE ALL EXISTING CIRCUITS PRIOR TO REUSE.

GENERAL NOTES:

COORDINATE LOCATION OF DUCT DETECTOR WITH

MECHANICAL CONTRACTOR. DUCT DETECTOR SUPPLIED BY

EC, INSTALLED BY MC AND WIRED BY EC.

CONNECT TO NEAREST 120V CIRCUIT USING 2#12, 1#12

GROUND IN 3/4" CONDUIT.

NOTES BY SYMBOL:

(THIS DRAWING ONLY)

CU-1 CU-2

ADDITION

ROOF

EXISTING

ROOF

ERV-1

PHASE ONEPHASE TWO

D

200/3/175/3

MDP-6

WP

PP-14

60/3/50/3

MDP-3

WP

PP-14

60/3/50/3

MDP-4

WP

PP-14

EF-1

30/1/20/3

PP-12

PERMIT DOCUMENTS

05/15/2026

ARCHITECT OF RECORD:

Samantha Ciotti Falcone

AIA, LEED AP

ENGINEER OF RECORD:

DRAWN BY: xx

OWNER / CONTACT:

Dale Handelong

570-688-8268 dalehandelong@hotmail.com

22 South 2nd Street Emmaus, PA 18049

T: 610-297-0140 E: sam@scf-arch.com

These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect

PR

O

JE

C

T N

U M

BE

R

0-

M ou nt B et he l F ire

C o.

Ad di tio n to E xi st in g

Fi re

C om pa ny

N or th D el aw ar e

D riv e, M t.

Be th el

, P A

U pp er

M ou nt B et he l T w p, N or th am pt on C ou nt y

PARTIAL FLOOR PLAN - POWER

SCALE: 1/4"=1'-0"

PARTIAL

ROOF PLAN -

POWER

E2.2

1. COORDINATE EXACT LOCATION AND POWER REQUIREMENTS

OF MECHANICAL UNITS WITH MECHANICAL CONTRACTOR.

2. CONTRACTOR SHALL VERIFY CIRCUIT BREAKER,

DISCONNECT SWITCH, STARTER AND FUSE SIZES WITH

SELECTED EQUIPMENT MANUFACTURER'S SHOP DRAWINGS

PRIOR TO PLACING ORDER.

GENERAL NOTES:

COORDINATE LOCATION OF DUCT DETECTOR WITH

MECHANICAL CONTRACTOR. DUCT DETECTOR SUPPLIED BY

EC, INSTALLED BY MC AND WIRED BY EC.

NOTES BY SYMBOL:

(THIS DRAWING ONLY)

PERMIT DOCUMENTS

05/15/2026

ARCHITECT OF RECORD:

Samantha Ciotti Falcone

AIA, LEED AP

ENGINEER OF RECORD:

DRAWN BY: xx

OWNER / CONTACT:

Dale Handelong

570-688-8268 dalehandelong@hotmail.com

22 South 2nd Street Emmaus, PA 18049

T: 610-297-0140 E: sam@scf-arch.com

These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect

PR

O

JE

C

T N

U M

BE

R

0-

M ou nt B et he l F ire

C o.

Ad di tio n to E xi st in g

Fi re

C om pa ny

N or th D el aw ar e

D riv e, M t.

Be th el

, P A

U pp er

M ou nt B et he l T w p, N or th am pt on C ou nt y

ELECTRICAL

DETAILS &

SCHEDULES

E3.0

PARTIAL SINGLE-LINE DIAGRAM

NO SCALE

ETR

EXIST.

CT

CABINET

EXIST.

MAIN

DISC.

EXIST.

PANEL

'A'

120/240V, 1Ø,3W

100A MCB

ETR ETR ETR

1ST FLOOR

EXISTING UTILITY POLE WITH

UTILITY TRANSFORMERS

LOCATED IN PARKING LOT

EXIST.

PANEL

'MDP'

120/240V, 3Ø,4W

400A MCB

ETR

EXISTING WIREWAY

EXIST.

UTILITY

METER

ETR

PANEL: A (EXISTING) BUS AMP: 225A AMPS MAIN BREAKER: 100A

MOUNTING: SURFACE PHASE: 1 WIRE: 3 VOLTAGE: 240/120 AIC: 10,000

CKT CIRCUIT DESCRIPTION

BREAKER WIRE GND

COND

LOAD KVA/PH LOAD

COND

GND WIRE BREAKER

CIRCUIT DESCRIPTION CKT

P AMP NO SIZE SIZE KVA A B KVA SIZE SIZE NO AMP P

1 LIGHTS ROW 1 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 1 (EXISTING) 2

3 LIGHTS ROW 2 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 2 (EXISTING) 4

5 LIGHTS ROW 3 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 3 (EXISTING) 6

7 LIGHTS ROW 4 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 4 (EXISTING) 8

9 LIGHTS ROW 5 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 5 (EXISTING) 10

11 LIGHTS ROW 6 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 6 (EXISTING) 12

13 LIGHTS ROW 7 (EXISTING) 1 20 0 0.0 0 20 1 LIGHTS ROW 7 (EXISTING) 14

15 BULLET LIGHTS (EXISTING) 1 20 0 0.0 0 20 1 BULLET LIGHTS (EXISTING) 16

17 COACH LIGHTS (EXISTING) 1 20 0 0.0 0 20 1 BULLET LIGHTS (EXISTING) 18

19 ELEC AIR CLEANERS (EXISTING) 1 20 0 0.0 0 20 1 RECEPTACLES STAGE (EXISTING) 20

21 ELEC AIR CLEANERS (EXISTING) 1 20 0 0.0 0 20 1 RECEPTACLES (EXISTING) 22

23 ELEC AIR CLEANERS (EXISTING) 1 20 0 0.0 0 20 1 RECEPTACLES (EXISTING) 24

25 EXISTING LOAD 1 20 0 0.0 0 20 1 RECEPTACLES (EXISTING) 26

27 DUSK-TO-DAWN EAST END (EXISTING) 1 20 0 0.0 0 20 1 BINGO BOARDS (EXISTING) 28

29 EMERGENCY UNITS (EXISTING) 1 20 0 0.0 0 20 1 EXITS & OUTSIDE DOOR LIGHTS (EXIST) 30

TOTAL KVA/PHASE 0.0 0.0

TOTAL KVA PANEL 0.0

TOTAL AMPS PANEL 0

PANEL: MDP (EXISTING) BUS AMP: 400A AMPS MAIN BREAKER: 400A

MOUNTING: SURFACE PHASE: 3 WIRE: 4 VOLTAGE: 240/120V AIC: 10,000

CKT CIRCUIT DESCRIPTION

BREAKER LOAD KVA/PH LOAD BREAKER

CIRCUIT DESCRIPTION CKT

P AMP KVA A B C KVA AMP P

1 HP-1 (NEW) * (4#1,1#8G IN 1 1/2"C) 3 100

9.2 18.5 9.2

100 3 HP-2 (NEW) * (4#1,1#8G IN 1 1/2"C) 29.2 18.5 9.2

9.2 18.5 9.2

3 CU-1 (NEW) * (4#6,1#10G IN 1"C) 3 50

3.8 7.7 3.8

50 3 CU-2 (NEW) * (4#6,1#10G IN 1"C) 43.8 7.7 3.8

3.8 7.7 3.8

5 SUBPANEL "PP" * (REFER TO PANEL SCHEDULE) 3 100

5.7 20.3 14.6

175 3 ERV-1 (NEW) * (4#2/0,1#6G IN 2"C) 65.2 19.8 14.6

8.1 22.7 14.6

TOTAL KVA PER PHASE 46.5 46.0 48.8 NOTE: " * " DENOTES PROVIDE NEW CIRCUIT BREAKER.

TOTAL KVA 141.3

TOTAL AMPS 339.8

EXIST.

PANEL

'ELECTRIC

HEAT' ('EH')

120/240V 3Ø,4W

200A MLO

ETR

240V 200A

ETR

EXISTING WIREWAY

1. NEW CIRCUITS ARE FED FROM EXISTING PANELS. WIRE NEW

CIRCUITS TO EXISTING FREE CIRCUITS OR SPACES, OR AS

INDICATED ON DRAWINGS. PROVIDE NEW CIRCUIT BREAKER

FOR ALL NEW CIRCUITS REPLACING EXISTING BREAKERS.

CIRCUIT BREAKER SHALL MATCH EXISTING BREAKERS IN

MANUFACTURER, STYLE, TYPE AND INTERRUPTING RATING.

GENERAL NOTES:

TYPICAL GFI RECEPTACLE WITH

WEATHER PROOF COVER (WHERE

INDICATED ON THE DRAWINGS)

GALVANIZED RIGID STEEL

CONDUIT WITH GOOSENECK

THROUGH THE ROOF

ROOF PENETRATION AND

SEAL BY GENERAL

CONTRACTOR

WEATHER

TIGHT NUT

FLEXIBLE LIQUID TIGHT

CONDUIT TO DISCONNECT

SWITCH

ROOF MEMBRANE BY

GENERAL CONTRACTOR

(TYPICAL)

ROOF INSULATION BY

GENERAL CONTRACTOR

(TYPICAL)

ROOF DECK BY GENERAL

CONTRACTOR (TYPICAL)

STEEL SUPPORT BY

ELECTRICAL

CONTRACTOR

ELECTRICAL CONDUIT

ELECTRICAL JUNCTION BOX BY

ELECTRICAL CONTRACTOR

12"

TYPICAL DISCONNECT SWITCH BY

ELECTRICAL CONTRACTOR MOUNTED ON

SIDE OF ROOF-TOP UNIT

WEATHER

TIGHT NIPPLE

CONDUIT ROOF PENETRATION FOR DISCONNECT DETAIL

NO SCALE

TYPICAL GFI RECEPTACLE WITH

WEATHER PROOF COVER (WHERE

INDICATED ON THE DRAWINGS)

GALVANIZED RIGID STEEL

CONDUIT WITH

GOOSENECK THROUGH

THE ROOF

ROOF PENETRATION AND

SEAL BY GENERAL

CONTRACTOR

WEATHER

TIGHT NUT

FLEXIBLE LIQUID TIGHT CONDUIT

ROOF MEMBRANE BY

GENERAL CONTRACTOR

ROOF INSULATION BY

GENERAL CONTRACTOR

ROOF DECK BY

GENERAL CONTRACTOR

STEEL SUPPORT BY

ELECTRICAL

CONTRACTOR

ELECTRICAL CONDUIT

ELECTRICAL JUNCTION BOX

BY ELECTRICAL

CONTRACTOR

12"

CONDUIT ROOF PENETRATION FOR RECEPTACLE DETAIL

NO SCALE

MINIMUM 1" THICK COMPOUND

WITHIN OPENING, FLUSH WITH

BOTH SURFACES OF THE WALL

GYPSUM WALLBOARD/STUD WALL ASSEMBLY

CONDUIT

MINIMUM 2-1/2" THICK MINERAL

WOOL INSULATION FIRMLY PACKED

SECTION 'A-A'

NOTE:

MINIMUM 2HR FIRE RATING OF SEALING ASSEMBLY

UL SYSTEM W-L-1027

REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED WALL LOCATIONS

A

A

WALL CONDUIT PENETRATION DETAIL

NO SCALE

FROM

REST

OF

CIRCUIT

EMT

6' - 0" FLEX

CONDUIT MAX.

(TYP)

TYPICAL LIGHT FIXTURE WIRING DETAIL

NO SCALE

PANEL: PP BUS AMP: 100A AMPS MAIN BREAKER: 100A

MOUNTING: RECESSED PHASE: 3 WIRE: 4 VOLTAGE: 240/120 AIC: 10,000

CKT CIRCUIT DESCRIPTION

BREAKER WIRE GND

COND

LOAD KVA/PH LOAD

COND

GND WIRE BREAKER

CIRCUIT DESCRIPTION CKT

P AMP NO SIZE SIZE KVA A B C KVA SIZE SIZE NO AMP P

1 RECEPTACLE - MEN'S ROOM 1 20 2 12 12 3/4" 0.2 0.4 0.2 3/4" 12 12 2 20 1 RECEPTACLE - WOMEN'S ROOM 2

3 RECEPTACLE - MEN'S ROOM 1 20 2 12 12 3/4" 0.2 0.4 0.2 3/4" 12 12 2 20 1 RECEPTACLE - WOMEN'S ROOM 4

5 RECEPTACLE - MECHANICAL ROOM 1 20 2 12 12 3/4" 0.2 0.7 0.5 3/4" 12 12 2 20 1 RECEPTACLES - NURSING/CHANGING 6

7 WATER COOLER 1 20 2 12 12 3/4" 0.4 0.6 0.2 3/4" 12 12 2 20 1 CP-1 8

9 CONVENIENCE RECEPTACLES 1 20 2 12 12 3/4" 0.9 1.9 1.0 3/4" 12 12 2 20 1 WH-1 10

EUH-1 2 25 3 10 10 3/4"

2.1 2.4 0.3 3/4" 12 12 2 20 1 EF-1 12

13 2.1 2.6 0.5 3/4" 12 12 2 20 1 ROOFTOP RECEPTACLES 14

EUH-2 2 25 3 10 10 3/4"

2.1 3.0 0.9 3/4" 12 12 2 20 1 LIGHTING - NEW ADDITION 16

17 2.1 2.8 0.7 3/4" 12 12 2 20 1 RECEPTACLES - FUTURE STORAGE 18

19 0.0 0.0 0.0 20

21 0.0 0.0 0.0 22

23 2.1 2.1 0.0 24

25 2.1 2.1 0.0 26

27 0.0 0.0 0.0 28

29 0.0 0.0 0.0 30

31 0.0 0.0 0.0 32

33 0.0 0.0 0.0 34

35 0.0 0.0 0.0 36

37 0.0 0.0 0.0 38

39 0.0 0.0 0.0 40

41 0.0 0.0 0.0 42

TOTAL KVA/PHASE 5.7 5.2 8.1

TOTAL KVA PANEL 19.0

TOTAL AMPS PANEL 46

NEW

PANEL

'PP'

NEW

4#1, 1#8G IN 1 1/2"C

PERMIT DOCUMENTS

05/15/2026

ARCHITECT OF RECORD:

Samantha Ciotti Falcone

AIA, LEED AP

ENGINEER OF RECORD:

DRAWN BY: xx

OWNER / CONTACT:

Dale Handelong

570-688-8268 dalehandelong@hotmail.com

22 South 2nd Street Emmaus, PA 18049

T: 610-297-0140 E: sam@scf-arch.com

These documents are instruments of the Architect's service for use solely with respect to this project. The Architect shall retain all common law, statutory and other reserved rights, including the copyright. They are not to be used for any purpose by any other party outside of the scope of this work without the specific written consent of the Architect

PR

O

JE

C

T N

U M

BE

R

0-

M ou nt B et he l F ire

C o.

Ad di tio n to E xi st in g

Fi re

C om pa ny

N or th D el aw ar e

D riv e, M t.

Be th el

, P A

U pp er

M ou nt B et he l T w p, N or th am pt on C ou nt y

ELECTRICAL

SPECIFICATIONS

E4.0

PART 1 - GENERAL

ELECTRICAL SPECIFICATIONS

PART 2 - PRODUCTS

PART 3 - EXECUTION

A. IT IS THE INTENT OF THESE SPECIFICATIONS AND ACCOMPANYING DRAWINGS TO

GENERALLY DESCRIBE THE WORK NECESSARY FOR THE INSTALLATION OF A

COMPLETE ELECTRICAL, LIGHTING, AND POWER SYSTEM (INCLUDING FIRE ALARM).

B. THESE DRAWINGS AND SPECIFICATIONS ARE NOT INTENDED TO SHOW THE

LOCATION OF EVERY WIRE, CONDUIT, FITTING, ETC., BUT IS UNDERSTOOD THAT

THE CONTRACTOR SHALL FURNISH AND INSTALL ALL MATERIALS AND LABOR FOR

COMPLETE WORKABLE SYSTEMS UNLESS NOTED OTHERWISE IN THIS

SPECIFICATION OR ON THE DRAWINGS.

C. CONTRACTOR SHALL PROVIDE BUT NOT BE LIMITED TO:

1. COMPLETE SYSTEM OF WIRING FOR EMERGENCY LIGHTING, LIGHT AND

POWER, PLUMBING, HVAC EQUIPMENT, FIRE ALARM ALONG WITH TELEPHONE

AND DATA EQUIPMENT INSTALLATION.

2. ALL PANELS, SWITCHBOARDS, MOTOR CONTROLLERS, TRANSFORMERS,

DISCONNECTS, RECEPTACLES, SWITCHES, OUTLETS AND PLATES FOR SAME,

FEEDERS FROM PANELS AND RELATED APPURTNENANCES.

3. LIGHTING FIXTURES, LAMPS, BALLASTS AND APPURTENANCES.

D. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, FITTINGS OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR

COMPLETE INSTALLATION OF THE WORK. SUCH WORK MAY BE ACCOMPLISHED AT

THE SITE. ADDITIONAL BENDS, OFFSETS AND CONDUIT AS REQUIRED BY VERTICAL

AND HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS SHALL BE

PROVIDED TO COMPLETE THE WORK AT NO ADDITIONAL COST TO THE OWNER.

E. EXCEPT WHERE SHOWN IN DIMENSIONAL DETAIL, THE LOCATIONS OF SWITCHES,

RECEPTACLES, LIGHTS AND OTHER EQUIPMENT SHOWN ON PLANS ARE

APPROXIMATE. SUCH ITEMS SHALL BE PLACED SO AS TO ELIMINATE

INTERFERENCE WITH DUCTS, PIPING AND EQUIPMENT. THE EXACT LOCATION

SHALL BE DETERMINED IN THE FIELD. ALL DOOR SWINGS SHALL BE VERIFIED SO

THAT LIGHT SWITCHES ARE PROPERLY LOCATED.

F. FIELD VERIFY EXISTING CONDITIONS AND COORDINATE ALL WORK WITH ALL

OTHER TRADES, AND ACTUAL CONDITIONS IN FIELD.

G. ALL DEBRIS MATERIAL RESULTING FROM NEW WORK SHALL, UNLESS OTHERWISE

INDICATED, BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE

REMOVED FROM THE PREMISES BY HIM.

A. PROVIDE (FURNISH AND INSTALL) ALL WORK SPECIFIED OR INDICATED, IN

CONFORMANCE WITH THE MANUFACTURER'S PUBLISHED INSTALLATION

INSTRUCTIONS, COMPLETE WITH ALL APPURTENANCES, ARRANGED TO MEET JOB

CONDITIONS, FOR COMPLETE OPERATING SYSTEMS IN ACCORDANCE WITH THE

NATIONAL ELECTRIC CODE (NEC) AND ALL OTHER LOCAL CODES/REGULATIONS. ALL

EQUIPMENT AND MATERIALS INSTALLED SHALL BEAR THE LABEL OF THE

UNDERWRITER'S LABORATORIES, INC., WHERE SO REQUIRED BY THE NFPA

REGULATIONS.

A. APPROVAL OF MATERIALS AND EQUIPMENT WILL BE BASED ON THE

MANUFACTURER'S PUBLISHED DATA. PROOF THAT THE ITEMS FURNISHED

CONFORM TO THE SPECIFIED REQUIREMENTS AS INDICATED BELOW SHALL BE

SUBMITTED FOR APPROVAL.

B. WHERE MATERIAL AND EQUIPMENT ARE SPECIFIED TO CONFORM TO THE

STANDARDS OF THE UNDERWRITER'S LABORATORIES (UL), INC., THE UL LABEL OR

LISTING WILL BE ACCEPTABLE AS SUFFICIENT EVIDENCE THAT THE ITEMS CONFORM

TO REQUIREMENTS.

C. EQUIPMENT DESIGN, FABRICATION, TESTING, PERFORMANCE AND INSTALLATION

SHALL, UNLESS SHOWN OTHERWISE, COMPLY WITH AND MEET ALL THE APPLICABLE

REQUIREMENTS OF NFPA 70 (THE NEC), ANSI C2, REFERENCED INDUSTRIAL CODES

AND STANDARDS AND LOCAL CODES HAVING JURISDICTION.

A. ALL MATERIALS SHALL BE NEW. THE CONTRACTOR MAY SELECT DEVICES AS

INDICATED ON THESE DRAWINGS. SUBSTITUTES MAY BE SUBMITTED AND USED

WITH WRITTEN APPROVAL OF OWNER/ARCHITECT/ENGINEER. SUBMIT SHOP

DRAWINGS TO OWNER/ARCHITECT/ENGINEER FOR APPROVAL.

B. SHOP DRAWINGS SHALL INCLUDE BUT ARE NOT LIMITED TO:

1. LIGHTING FIXTURES

2. RECEPTACLES, BOXES, ENCLOSURES

3. PANELBOARDS

4. CONDUIT,WIRING, FITTINGS

5. DISCONNECT SWITCHES

6. SWITCHES, COVER PLATES

7. TIME CLOCKS, PHOTOCELLS AND LIGHTING CONTACTOR

C. SUBMITTALS SHALL BE MADE FOR THE EQUIPMENT LISTED ABOVE. THE ARCHITECT

SHALL MAKE THE ULTIMATE DECISION ON COLOR AND FINISH FOR ALL DEVICES

SUCH AS RECEPTACLES, SWITCHES, SWITCH PLATES, AS WELL AS ANY OTHER

CONTROL DEVICES. THIS APPROVAL SHALL BE MADE BEFORE ANY ITEMS ARE

ORDERED.

D. PRODUCT REQUIREMENTS: MATERIALS AND EQUIPMENT TO BE PROVIDED SHALL BE

THE STANDARD CATALOGED PRODUCTS OF MANUFACTURERS REGULARLY

ENGAGED IN THE MANUFACTURE OF THE PRODUCTS. MATERIALS AND EQUIPMENT

SHALL MEET THE SPECIFIED AND DETAILED REQUIREMENTS INDICATED, BE

SUITABLE FOR THE INSTALLATION SHOWN AND SHALL REPRESENT PRODUCTS THAT

HAVE BEEN IN SATISFACTORY USE AT LEAST TWO YEARS. PRODUCTS NOT MEETING

ALL SPECIFIED REQUIREMENTS WILL NOT BE ACCEPTED.

E. OWNER INSTRUCTION AND OPERATION MANUALS SHALL BE PROVIDED TO INSTRUCT

IN THE PROPER OPERATION AND MAINTENANCE OF ALL WORK. PROVIDE A MINIMUM

OF (3) THREE OPERATING MANUALS FOR ALL WORK.

A. ALL WORK AND MATERIALS SHALL CONFORM TO ALL CODES, ORDINANCES,

REGULATIONS, STANDARDS AND RULES. ALL PERMITS, UTILITY FEES AND COSTS,

INSPECTION CERTIFICATES AND APPROVALS SHALL BE SECURED AND PAID BY THE

CONTRACTOR.

B. WORK SHALL NOT BE COVERED UP NOR ENCLOSED UNTIL IT HAS BEEN INSPECTED,

TESTED AND APPROVED. ANY WORK THAT IS ENCLOSED OR COVERED UP BEFORE

SUCH INSPECTION AND TEST, SHALL BE UNCOVERED. AFTER IT HAS BEEN

INSPECTED AND APPROVED, ALL UNCOVERED ITEMS SHALL BE RESTORED TO ITS

ORIGINAL COVERED CONDITION AT NO ADDITIONAL COST TO THE OWNER.

C. SECURE ELECTRICAL INSPECTION CERTIFICATE FROM AUTHORIZED AGENT.

A. PLAN CONSTRUCTION SCHEDULE TO COORDINATE WITH ALL OTHER TRADES,

UNLESS A SCHEDULED CHANGE HAS BEEN ARRANGED WITH THE

OWNER/ARCHITECT/ENGINEER.

B. COORDINATION SHALL INCLUDE ADEQUATE CLEARANCES FOR THE INSTALLATION

AND MAINTENANCE OF EQUIPMENT AND PHYSICAL AND ELECTRICAL

REQUIREMENTS OF ITEMS OR EQUIPMENT REQUIRING CONNECTIONS.

A. EQUIPMENT AND MATERIALS STORED AT THE SITE, PRIOR TO FINAL INSTALLATION,

SHALL BE FULLY PROTECTED FROM DAMAGE, DIRT, DEBRIS, AND WEATHER. DENTS,

MARRED FINISHES AND OTHERWISE DAMAGED EQUIPMENT SHALL BE REPAIRED TO

ITS ORIGINAL CONDITION OR REPLACED.

A. SECURE ALL EQUIPMENT, DEVICES AND RACEWAYS.

B. ELECTRICAL COMPONENTS AND SYSTEMS AND THEIR ATTACHMENTS SHALL BE

DESIGNED TO RESTRAIN SEISMIC FORCES AS REQUIRED BY ALL AUTHORITIES AND

LOCAL ORDINANCES HAVING JURISDICTION

C. ALL CONDUITS SHALL BE SECURELY FASTENED WITHIN 3 FEET OF EACH OUTLET

BOX, JUNCTION BOX, CABINET, FITTING OR END OF CONDUIT, OR AS SHOWN ON THE

DRAWINGS.

D. SUPPORTS SHALL BE HOT-DIPPED GALVANIZED STEEL OR AS INDICATED ON THE

DRAWINGS.

E. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT OR

CONDUIT.

A. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED AS HEREIN SPECIFIED AND

INDICATED ON THE DRAWINGS. EQUIPMENT TO BE IDENTIFIED SHALL INCLUDE, BUT

NOT BE LIMITED TO THE FOLLOWING:

1. ELECTRICAL POWER AND BRANCH CIRCUIT CONDUCTORS

2. FEEDER CONDUITS

3. OUTLET BOXES (COVER PLATES)

4. PANELBOARDS

5. DISCONNECTS

B. NAMEPLATES SHALL GENERALLY BE BLACK TYPED LETTERS WITH WHITE

BACKGROUND OR WHITE TYPED LETTERS WITH BLACK BACKGROUND ON

LAMINATED PLASTIC WITH BEVELED EDGES. LETTERS SHALL BE A MINIMUM OF 1/8"

HIGH. CONDUIT MARKERS SHALL BE STANDARD PRE-PRINTED FLEXIBLE PLASTIC

SHEET MATERIAL OR SELF-ADHERING VINYL LABELS. WIRE MARKERS SHALL BE

LAMINATED PLASTIC NAMEPLATES, SELF-ADHERING VINYL LABELS OR TAPE. 3

C. PROVIDE A TYPED DIRECTORY FOR EACH PANELBOARD INDICATING THE ITEM/ITEMS

CONTROLLED BY EACH CIRCUIT. THE DIRECTORY SHALL BE LOCATED ON THE

INSIDE OF THE HINGED DOOR TO THE PANEL.

A. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED AS HEREIN SPECIFIED AND THE

CONTRACTOR SHALL REMOVE ALL MATERIALS/EQUIPMENT AS INDICATED ON

DRAWINGS IN THEIR ENTIRETY. ITEMS SURROUNDING THE MATERIALS/EQUIPMENT

TO BE REMOVED SHALL REMAIN UNDISTURBED AND INTACT.

B. THE CONTRACTOR SHALL REPAIR ANY MARRED OR DAMAGED SURFACES THAT ARE

THE RESULT OF THE DEMOLITION PROCESS.

C. ANY EQUIPMENT DAMAGED AS A RESULT OF THE DEMOLITION PROCESS SHALL BE

FIXED/RESTORED TO WORK AS NEW OR REPLACED IN LIKE KIND.

A. WIRE AND CONDUCTORS

1. INSULATED CURRENT-CARRYING WIRE AND GROUNDING CONDUCTORS SHALL

BE COPPER AND SHALL CONFORM TO NFPA 70 AND ASTM B3 (SOFT OR

ANNEALED COPPER WIRE).

2. CONDUCTORS NO. 10 AWG AND SMALLER SHALL BE SOLID ROUND COPPER

WIRE. CONDUCTORS NO. 8 AWG AND LARGER SHALL BE STRANDED

CONCENTRIC COPPER WIRE.

3. MULTICONDUCTOR CABLE: COMPLY WITH NEMA WC 70 FOR ARMORED CABLE

(TYPE AC) AND METAL-CLAD CABLE (TYPE MC) WITH GROUND WIRE (ONLY

ALLOWABLE FOR CIRCUITS 40A OR LESS). WHERE USED IN HEALTH CARE

FACILITIES, IT SHALL BE RATED PER NEC REQUIREMENTS. HEALTH CARE

FACILITY (HCF) CABLE SHALL BE OF ALUMINUM ARMOR, AND PROVIDED WITH

ALL NECESSARY CONNECTORS. MEET UL STANDARD 4; NEC ARTICLE 517.

4. THE CONTRACTOR SHALL PROVIDE APPROPRIATELY SIZED FEEDERS, BRANCH,

CONTROL AND MISCELLANEOUS CONDUCTORS APPROPRIATELY SIZED IN

CONFORMANCE WITH THE NATIONAL ELECTRIC CODE.

5. ALL WIRING SHALL BE INSTALLED IN CONDUIT OR MULTICONDUCTOR CABLE

WHERE ALLOWED.

6. BUILDING WIRE SHALL BE TYPE THW, THHN/THHW OR XHHW WITH A MINIMUM

TEMPERATURE RATING OF 75 DEGREES C.

7. A GREEN GROUND WIRE SHALL BE RUN WITH ALL CIRCUITS.

8. CONTRACTOR SHALL ACCOUNT FOR VOLTAGE DROP WHEN PROVIDING LONG

LEAD LENGTHS OF CONDUCTORS.

B. INSTALLATION

1. RACEWAYS AND WIRING SHALL BE INSTALLED AS INDICATED AND CIRCUITS

SHALL NOT BE COMBINED WITHOUT PRIOR APPROVAL.

2. CONDUCTORS OF SPECIAL SERVICE SYSTEMS AND POWER SYSTEMS SHALL

NOT OCCUPY THE SAME ENCLOSURE WITH LIGHT AND POWER CONDUCTORS

OR THE SAME ENCLOSURE WITH EACH OTHER. CONDUCTORS SHALL BE

CONTINUOUS WITH SPLICES AND CONNECTIONS MADE IN OUTLET, JUNCTION OR

PULL BOXES ONLY.

3. ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR CODED AS

FOLLOWS:

CONDUCTOR 208/120V 480/277V

PHASE A BLACK BROWN

PHASE B RED ORANGE

PHASE C BLUE YELLOW

NEUTRAL WHITE WHITE

GROUND GREEN GREEN

4. CONDUCTORS UP TO AND INCLUDING NO.8 AWG SHALL BE MANUFACTURED

WITH COLORED INSULATING MATERIALS. CONDUCTORS LARGER THAN NO.8

AWG SHALL HAVE ENDS IDENTIFIED WITH COLORED PLASTIC TAPE IN ALL

OUTLET, PULL OR JUNCTION BOXES. ALL CONTROL CIRCUIT CONDUCTORS

SHALL BE IDENTIFIED AT EACH CONNECTION POINT.

5. CONNECTIONS AND SPLICES SHALL BE MADE IN APPROVED ENCLOSURES

UTILIZING SOLDERLESS PRESSURE CONNECTORS AND ADEQUATE INSULATION

WITH VINYL-PLASTIC ELECTRICAL INSULATING TAPE. CONDUCTOR

IDENTIFICATION SHALL BE PROVIDED WITHIN EACH ENCLOSURE WHERE A TAP,

SPLICE OR TERMINATION IS MADE AND AT THE EQUIPMENT TERMINAL OF EACH

CONDUCTOR.

6. WHERE SEVERAL FEEDERS PASS THROUGH A COMMON PULLBOX, THE FEEDERS

SHALL BE TAGGED TO CLEARLY INDICATE THE ELECTRICAL CHARACTERISTICS,

CIRCUIT NUMBER AND PANEL DESIGNATION.

7. MAXIMUM CABLE PULLING TENSION SHALL NOT EXCEED VALUES

RECOMMENDED BY CABLE MANUFACTURER.

8. CIRCUIT CONDUCTORS SHALL BE SAME AWG SIZE FROM SOURCE TO LOAD.

NEUTRAL WIRES SHALL BE THE SAME SIZE AS PHASE WIRES EXCEPT AS NOTED

ON DRAWINGS.

9. ALL 600V RATED WIRE CONNECTIONS, NO.8 AWG AND LARGER, STUD-TYPE OR

FLAT-BAR TYPE EQUIPMENT TERMINALS SHALL BE TERMINATED WITH A

COMPRESSION TYPE LUG.

10. MULTICONDUCTOR CABLE MAY ONLY BE USED WHERE CONCEALED IN WALLS

OR ABOVE ACCESSIBLE CEILINGS IN ACCORDANCE WITH THE NEC.

MULTICONDUCTOR CABLE SHALL BE SUPPORTED INDEPENDENT OF CEILING

STRUCTURE.

11. MULTICONDUCTOR CABLE IN PLENUM SPACES SHALL BE COMPLIANT WITH NEC

300.22 - MC CABLE EMPLOYING A SMOOTH OR CORRUGATED METAL SHEATH

WITHOUT AN OVERALL NONMETALLIC COVERING.

A. PROVIDE ALL ELECTRICAL SYSTEM GROUNDS AS REQUIRED BY THE NATIONAL

ELECTRICAL CODE, AND THE NATIONAL ELECTRICAL SAFETY CODE.

B. THE FOLLOWING SHALL BE SOLIDLY GROUNDED:

1. CONDUIT SYSTEM (NEC ARTICLE 250)

2. ALL EQUIPMENT WITH ANY ELECTRICAL CONNECTIONS

3. NEUTRAL LEAD OF LOW TENSION SECONDARY SERVICE

C. A SEPARATE GROUNDING CONDUCTOR SHALL BE FURNISHED AND INSTALLED FOR

ALL ELECTRICAL CIRCUITS. ALL ELECTRICAL EQUIPMENT ENCLOSURES AND

CONDUCTOR ENCLOSURES SHALL BE GROUNDED.

D. ALL FEEDER DISCONNECTS AND BREAKERS RATED 1000 AMPERES AND ABOVE IN A

SOLIDLY GROUNDED WYE SYSTEM WITH GREATER THAN 150 VOLTS TO GROUND,

BUT NOT EXCEEDING 600 VOLTS PHASE TO PHASE SHALL BE PROVIDED WITH

GROUND FAULT PROTECTION.

A. RACEWAY

1. ELECTRICAL METALLIC TUBING (EMT) SHALL BE METALLIC CONDUIT OF THE THIN

WALL TYPE IN STRAIGHT LENGTHS, ELBOWS, OR BENDS AND SHALL CONFORM

TO ANSI C80.3 AND THE REQUIREMENTS OF UL 797.

2. COUPLINGS AND CONNECTORS FOR EMT SHALL BE HEX-NUT

EXPANSION-GLAND, COMPRESSION TYPE, ZINC OR CADMIUM-PLATED. CRIMP,

SPRING OR SET-SCREW TYPE FITTINGS ARE NOT ACCEPTABLE. WHERE EMT

ENTERS OUTLET BOXES, CABINETS OR OTHER ENCLOSURES, CONNECTORS

SHALL BE THE INSULATED-THROAT TYPE, WITH LOCKNUTS. FITTINGS SHALL

MEET THE REQUIREMENTS OF ANSI/NEMA FBI.

3. FLEXIBLE METALLIC CONDUIT (FMC) SHALL MEET THE REQUIREMENTS OF UL 1.

4. RIGID GALVANIZED STEEL CONDUIT (RMC) SHALL CONFORM TO UL 6 AND ANSI

C80.1. CONDUIT FITTINGS SHALL CONFORM TO ANSI/NEMA FBI.

5. INTERMEDIATE METAL CONDUIT (IMC) SHALL MEET THE REQUIREMENTS OF ANSI

C80.6.

6. FURNISH AND INSTALL BUSHINGS, AS MANUFACTURED BY O.Z. OR T&B

COMPANIES FOR ALL POWER SYSTEM CONDUITS AND LIGHTING CIRCUIT

CONDUITS 1-1/4" AND LARGER.

7. LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT (LTFMC): STEEL, CONSTRUCTED OF

SINGLE STRAP, FLEXIBLE CONTINUOUS, INTERLOCKED, AND DOUBLE-WRAPPED

METAL WITH A LIQUID-TIGHT JACKET OF FLEXIBLE POLYVINYL CHLORIDE (PVC)

CONFORMING TO NEMA RN1.

8. RIGID NONMETALLIC CONDUIT (RNC) SHALL COMPLY WITH NEMA TC2, SCHEDULE

40 AND SCHEDULE 80 PVC. RNC FITTINGS SHALL COMPLY WITH NEMA TC3,

MATCH TO CONDUIT TYPE AND MATERIAL.

B. BOXES

1. JUNCTION BOXES AND PULL BOXES SHALL HAVE SUFFICIENT VOLUME TO

ACCOMMODATE THE NUMBER OF CONDUCTORS ENTERING THE BOX IN

ACCORDANCE WITH THE REQUIREMENTS OF NFPA 70 ARTICLE 314. BOXES

SHALL BE CADMIUM-PLATED OR ZINC-COATED SHEETMETAL. JUNCTION BOXES

AND PULL BOXES FOR USE WITH THE CONDUIT SYSTEMS SHALL NOT BE LESS

THAN 1 1/2 " DEEP AND 4" BY 4". PULL AND JUNCTION BOXES SHALL BE

FURNISHED WITH HINGED OR SCREW-FASTENED COVERS.

C. INSTALLATION

1. CONDUIT AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70

AND AS SPECIFIED HEREIN.

2. INSTALL RACEWAYS SQUARE WITH BUILDING WALLS AND FASTENED TO

BUILDING STRUCTURE.

3. EMT SHALL BE INSTALLED INDOORS IN DRY LOCATIONS NOT SUBJECT TO

MECHANICAL INJURY. ALSO, CONCEALED CIRCUITS AND CIRCUITS LOCATED IN

PLENUM SHALL BE EMT UNLESS OTHERWISE NOTED.

4. RMC CONDUIT SHALL BE USED IN ALL OPEN SHOP AREAS TO A MINIMUM

ELEVATION OF 15'-0" AFF.

5. RMC AND IMC WITH THREADED FITTINGS SHALL BE INSTALLED OUTDOORS,

WHERE UNDERGROUND, OR IN AREAS SUBJECT TO WEATHER AND/OR

MECHANICAL INJURY.

6. RNC SHALL BE INSTALLED OUTDOORS, WHERE UNDERGROUND, OR IN AREAS

SUBJECT TO WEATHER AND/OR MECHANICAL INJURY. FOR RNC, USE

SOLVENT-CEMENTED JOINTS IN DUCTS AND FITTINGS AND MAKE WATERTIGHT

ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS. STAGGER

COUPLINGS SO THOSE OF ADJACENT DUCTS DO NOT LIE IN THE SAME PLANE.

7. FMC AND LTFMC WITH SEPARATE GROUND WIRE SHALL BE INSTALLED IN AREAS

SUBJECT TO VIBRATION IN MAXIMUM SIX FOOT LENGTHS PROPERLY

SUPPORTED.

8. WHERE APPLICABLE, CONDUITS SHALL BE FASTENED TO ALL SHEET METAL

BOXES, GUTTERS AND CABINETS WITH TWO LOCKNUTS AND A BUSHING.

9. THE CONTRACTOR SHALL FURNISH AND INSTALL ABOVE GRADE CONDUIT

SYSTEMS AS SPECIFIED, INCLUDING ALL NECESSARY SUPPORTS, HANGERS,

AND OTHER HARDWARE. IF THERE ARE ANY MAJOR DISCREPANCIES, CHANGES

OR QUESTIONABLE ROUTING, THE CONTRACTOR SHALL NOTIFY THE OWNER'S

REPRESENTATIVE FOR RESOLUTION AND/OR APPROVAL.

10. EXPOSED CONDUIT SHALL BE NEATLY AND EVENLY SPACED AND SHALL RUN

PARALLEL TO CEILING, FLOORS, WALLS OR OTHER PERMANENT STRUCTURES.

11. CONDUIT IN FINISHED AREAS SHALL BE INSTALLED CONCEALED.

12. CONDUIT SHALL BE SECURELY CLAMPED AND SUPPORTED AT LEAST EVERY 10

FEET VERTICALLY AND 8 FEET HORIZONTALLY. GALVANIZED PIPE STRAPS SHALL

BE FASTENED TO STRUCTURE WITH BOLTS, SCREWS AND ANCHORS.

13. CONDUIT AND BOXES SHALL NOT BE SUPPORTED FROM T-BAR CEILING WIRES.

14. EXPANSION FITTINGS WITH FLEXIBLE GROUND STRAP SHALL BE PROVIDED IN

CONDUIT RUNS CROSSING BUILDING EXPANSION JOINTS.

15. CONTRACTOR SHALL AVOID MORE THAN THREE 90 DEGREE BENDS, OR

EQUIVALENT, IN A RUN BETWEEN PULL FITTINGS.

16. EMERGENCY LIGHTING SYSTEM WIRING SHALL BE IN RIGID CONDUIT, EMT OR

SURFACE RACEWAY.

D. SAFTEY SWITCHES

1. SAFETY SWITCHES SHALL BE FUSED OR NON-FUSED AS REQUIRED. THEY

SHALL BE THE HEAVY-DUTY TYPE AS MANUFACTURED BY SIEMENS, GENERAL

ELECTRIC, SQUARE D OR APPROVED EQUAL. THE SAFETY SWITCHES SHALL

HAVE A POSITIVE QUICK MAKE AND QUICK BREAK OPERATING MECHANISM

WITH SAFETY INTERLOCKING COVER AND EXTERNAL OPERATING HANDLE.

E. RECEPTACLES

1. DUPLEX AND QUADRUPLEX RECEPTACLES SHALL BE FLUSH, HEAVY DUTY,

GENERAL USE, 20A, 120V, GROUNDING TYPE, INDUSTRIAL SPECIFICATION

GRADE AS MANUFACTURED BY HUBBELL OR APPROVED EQUAL, NEMA 5-20R

CONFIGURATION. COLOR SHALL BE IVORY.

2. GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLES SHALL BE STRAIGHT

BLADE, GENERAL USE, SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL

OR APPROVED EQUAL, NEMA 5-20 CONFIGURATION, 120V, COMPLYING WITH UL

498 AND UL 943. GFCI UNITS SHALL BE DESIGNED FOR INSTALLATION IN A 2 3/4"

DEEP OUTLET BOX WITHOUT AN ADAPTER. COLOR SHALL BE IVORY.

F. WALL SWITCHES, RECEPTACLE AND OTHER MISCELLANEOUS DEVICE PLATES

1. DEVICE PLATES AND RECEPTACLE COVER PLATES SHALL BE LABELED (ON THE

INSIDE) SHOWING THE CIRCUIT NUMBER.

2. FOR LOCATIONS WHERE THERE ARE MULTIPLE DEVICES, THE COVER PLATE

SHALL BE ONE SOLID PIECE TO SUIT THE DEVICES INSTALLED. ALL PLATES

SHALL FIT SNUGLY AND TIGHTLY AGAINST THE FINISHED BUILDING'S

SURFACES.

3. FOR THE CASE OF DIMMERS GANGED TOGETHER, THE CONTRACTOR SHALL

APPLY THE APPROPRIATE DERATING FACTORS AS THE MULTIPLE DIMMERS ARE

GANGED TOGETHER.

4. PLATES FOR SURFACE BOXES SHALL BE CADMIUM PLATED OR GALVANIZED.

G. BOXES AND FITTINGS

1. COMPLY WITH UL 514B, FITTINGS FOR CONDUIT AND OUTLET BOXES.

2. JUNCTION AND PULL BOXES SHALL BE INSTALLED WHERE SHOWN ON THE

DRAWINGS, OR AT SUCH LOCATIONS AS MAY BE REQUIRED TO FACILITATE THE

PULLING OF CABLES.

3. PULL BOXES SHALL BE FURNISHED AND INSTALLED ON CONDUIT RUNS LONGER

THAN 100 FEET OR WITH MORE THAN THREE RIGHT-ANGLE BENDS.

4. OUTLET BOXES SHALL BE EQUIPPED WITH PLASTER RINGS, EXTENSION RINGS

AND FIXTURE STUDS WHERE REQUIRED. ALL UNUSED OPENINGS IN BOXES

SHALL BE CLOSED WITH FACTORY MADE KNOCKOUT SEALS.

5. BOXES AND ENCLOSURES SHALL BE SECURELY MOUNTED TO THE BUILDING

STRUCTURE WITH SUPPORTING FACILITIES INDEPENDENT OF THE CONDUIT

ENTERING OR LEAVING THE BOXES.

H. INSTALLATION

1. WIRING DEVICES SHALL BE INSTALLED AND TESTED TO VERIFY THE UNITS ARE

WORKING AS INTENDED.

2. CONTRACTOR SHALL TROUBLESHOOT ANY DEVICES NOT FUNCTIONING

PROPERLY OR AS INTENDED. CONTRACTOR SHALL EITHER RESTORE THE

PROBLEMATIC DEVICE OR REPLACE IT IN LIKE KIND. RETEST UNTIL DEVICES

ARE VERIFIED TO BE IN WORKING CONDITION.

3. BARRIERS BETWEEN ADJACENT DEVICES SHALL BE INSTALLED WHERE

REQUIRED PER NEC 406.4(G).

A. CONTRACTOR SHALL PROVIDE AND INSTALL ENCLOSED BREAKERS AND SWITCHES

WITH TRIP RATINGS, REQUIRED POLES AND VOLTAGES AS INDICATED ON THE

DRAWINGS.

B. UNITS SHALL BE MANUFACTURED BY SIEMENS, GENERAL ELECTRIC, SQUARE D OR

APPROVED EQUIVALENT.

C. ENCLOSURES SHALL COMPLY WITH NEMA AB 1 AND NEMA KS 1 TO MEET

ENVIRONMENTAL CONDITIONS OF THE INSTALLED LOCATION. ENCLOSURES

SHALL BE NEMA 250, TYPE I, UNLESS OTHERWISE INDICATED.

D. COMPLY WITH APPLICABLE PORTIONS OF NECA 1, NEMA PB 1.1, AND NEMA PB 2.1

FOR INSTALLATION OF ENCLOSED SWITCHES AND CIRCUIT BREAKERS.

A. COMBINATION CONTROLLERS

1. COMBINATION MOTOR CONTROLLERS WITH DISCONNECT IN COMMON

ENCLOSURE, USING THERMAL MAGNETIC CIRCUIT BREAKER CONFORMING TO

NEMA AB1, WITH INTEGRAL THERMAL AND INSTANTANEOUS MAGNETIC TRIP IN

EACH POLE.

2. ENCLOSURE SHALL BE NEMA TYPE 1 UNLESS OTHERWISE NOTED AND

CONFORM TO NEMA ICS 6. ENCLOSURE SHALL BE FABRICATED FROM STEEL

AND FINISH SHALL BE MANUFACTURER'S STANDARD GRAY.

B. MOTOR DISCONNECTING SWITCHES

1. SHOULD ANY MOTORS BE LOCATED OUT OF SIGHT OR GREATER THAN 50 FEET

FROM THEIR CONTROLLERS, THE CONTRACTOR SHALL FURNISH AND INSTALL A

NON-FUSED SAFETY SWITCH IN CLOSE VICINITY TO THE MOTOR.

A. A FIXTURE SHALL BE INSTALLED AT EACH LOCATION INDICATED ON DRAWINGS.

B. NEW LAMPS OF THE PROPER TYPE AND WATTAGE SHALL BE INSTALLED

IMMEDIATELY PRIOR TO SUBSTANTIAL COMPLETION OF THE PROJECT.

CONTRACTOR SHALL REFER TO THE LIGHTING FIXTURE SCHEDULE. LAMPS SHALL

BE GENERAL ELECTRIC, OSRAM SYLVANIA, OR VENTURE LIGHTING.

C. FLUORESCENT LIGHTING FIXTURES IDENTIFIED AS INBOARD/OUTBOARD LIGHTS

SHALL BE THE TWO BALLAST TYPE. ONE BALLAST SHALL BE CIRCUITED TO THE

INBOARD LIGHTING CIRCUIT. THE OTHER BALLAST SHALL BE CIRCUITED TO A

SEPARATE, DEDICATED CIRCUIT. THESE FIXTURES SHALL BE TAGGED AS BEING

POWERED FROM TWO SEPARATE SOURCES. TANDEM WIRE THE BALLASTS WHERE

APPLICABLE PER IECC 2009.

D. FLUORESCENT FIXTURES SHALL CONFORM TO REQUIREMENTS IN THE LIGHTING

FIXTURE SCHEDULE. BALLASTS SHALL BE ENERGY SAVING, INSTANT START, SOLID

STATE ELECTRONIC.

E. BALLASTS SHALL HAVE A MINIMUM POWER FACTOR OF…

This is the start of the file's text. The full file is on GovTribe.