This document provides details regarding a pre-solicitation notice for design-build services. The General Services Administration seeks a design-build contractor to upgrade the exterior envelope of two existing buildings at the Pacific Highway Land Port of Entry in Blaine, Washington. The estimated cost of construction is between $15-20 million and the period of performance is 18 months. Interested parties are encouraged to register through beta.SAM.gov by September 16, 2020. The awarded firm fixed price design-build contract will require replacement of exterior walls and roofs to stop water intrusion, while addressing any biological growth and impacts to building systems. The solicitation will be conducted in two phases, with the most highly qualified offerors from phase one invited to submit proposals in phase two. The contract is set aside for small businesses and a stipend will be provided to unsuccessful phase two offerors.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Land Port of Entry
Design Standard
Additional
Appendices
December 2018
FOR OFFICIAL USE ONLY
WARNING: This document is FOR OFFICIAL USE ONLY (FOUO). It contains information that may be exempt from public release under the Freedom of Inf ormation Act (5 U.S.C. § 552). It is to be controlled, stored, handled, transmitted, distributed, and disposed of in accordance with DHS policy relating to FOUO inf ormation and is not to be released to the public or other personnel who do not have a valid “need-to-know” without prior approval of an authorized DHS official.
NII BUILDING PROTOTYPE
Land Port of Entry Design Standard
FOR OFFICIAL USE ONLY
WARNING: This document is FOR OFFICIAL USE ONLY (FOUO). It contains information that may be exempt from public release under the Freedom of Information Act (5 U.S.C. § 552). It is to be controlled, stored, handled, transmitted, distributed, and disposed of in accordance with DHS policy relating to FOUO information and is not to be released to the public or other personnel who do not have a valid “need-to-know” without prior approval of an authorized DHS official.
For Official Use Only
Enclosed NII IBuilding Drawings I
LPOE Design Standard—2018—ENCLOSED NII BUILDING I-1
WARNING: This document is FOR OFFICIAL USE ONLY (FOUO). It contains information that may be exempt from public release under the Freedom of Information Act (5 U.S.C. § 552). It is to be controlled, stored, handled, transmitted, distributed, and disposed of in accordance with DHS policy relating to FOUO information and is not to be released to the public or other personnel who do not have a valid “need-to-know” without prior approval of an authorized DHS official.
APPENDIX I. ENCLOSED NII BUILDING DRAWINGS
I.1 INTRODUCTION
The following sections provide details on the enclosed non-intrusive inspection (NII) building used in secondary inspection areas. This appendix provides previously approved designs for reference for the standard building details and should be confirmed with Customs and Border Protection (CBP) for any actual project.
I-2 ENCLOSED NII BUILDING DRAWINGS
I.2 NII BUILDING DRAWING
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.
GENERAL SERVICE ADMINISTRATION
U.S. LAND PORT OF ENTRY
STANDARDIZED ELEMENTS
2 0 1 S O U T H U P P E R B R O A D W A Y, C O R P U S C H R I S T I, T E X A S 78401
C
ER
TI
FI
C A
TI
O
N S
K
EY
P
LA
N
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
C O
N
TR
A C
TO
R
S B
U
IL
D
IN
G
PR
O
JE
C T
D R
A W
IN
G
A/E CON. NO.
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY/ST. ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
GS-07P-07-HH-D-0083
GS-P-07-08-HH-5166
RICHTER ARCHITECTS
STANDARDIZED ELEMENTS
LAND PORT OF ENTRY
STANDARDIZED ELEMENTS
STANDARDIZED ENCLOSED NON-INTRUSIVE
INSPECTION BUILDING
NA
ERIC COOK
100% CONSTRUCTION DOCUMENTS
06/03/2009
SCALE:
DATE DRAFTED: 09/01/09
SHEET SIZE: 24 x 36
FINAL DOCUMENTS
NOT FOR REGULATORY APPROVAL,
PERMITTING, OR CONSTRUCTION
ARCHITECT:
DAVID R. RICHTER
T.B.A.E. NO. 7113
PD
SC
A NA
20815.00 - LPOE SE - NII BUILDING.RVT
A 09/01/2009 MOD. TO 06/03/09 SUBMISSION
TITLE
Author Checker
NII-T-01
U.S. LAND PORT OF ENTRY
ENCLOSED NON-INTRUSIVE
INSPECTION BUILDING (NII)
ARCHITECT: RICHTER ARCHITECTS
Structural Engineer: Walter P. Moore and Associates
MEP Engineer: Goetting and Associates
ARCHITECTURAL:
NII-A-01 GEN. NOTES AND SPECIFICATIONS
NII-A-02 SPECIFICATIONS
NII-A-03 FLOOR PLANS
NII-A-04 CEILING PLANS
NII-A-05 ROOF PLANS
NII-A-06 ELEVATIONS
NII-A-07 ELEVATIONS AND BUILDING SECTIONS
NII-A-08 WALL SECTIONS
NII-A-09 DETAILS
NII-A-10 BOOTH DETAILS
STANDARDIZED ELEMENTS
April 15, 2009
Prepared for:
U.S. Customs and Border Protection Department of Homeland Security
United States General Services Administration
STRUCTURAL:
NII-S0.01 SPECIFICATIONS
NII-S0.02 SPECIFICATIONS
NII-S0.03 SPECIFICATIONS
NII-S0.04 SPECIFICATIONS
NII-S0.05 SPECIFICATIONS
NII-S0.06 SPECIFICATIONS
NII-S0.07 SPECIFICATIONS
NII-S0.08 SPECIFICATIONS
NII-S0.09 SPECIFICATIONS
NII-S1.00 GENERAL NOTES
NII-S1.02 GENERAL NOTES
NII-S2.01 NII FOUNDATION AND ROOF PLAN
NII-S2.02 3D VIEW AND ELEVATIONS
NII-S5.00 TYPICAL DETAILS
NII-S5.02 SECTIONS AND DETAILS
NII-S5.05 METAL BUILDING TYPICAL DETAILS
MECHANICAL:
NII-M-0-01 SYMBOLS AND ABBREV.
NII-M-0-02 SPECIFICATIONS
NII-M-0-03 SPECIFICATIONS
NII-M-0-04 SPECIFICATIONS
NII-M-0-05 SPECIFICATIONS
NII-M-0-06 DETAILS
NII-M-0-07 DETAILS
NII-M-0-08 SCHEDULES
NII-M-1-01 FLOOR PLAN
NII-M-1-02 3D PLAN
PLUMBING:
NII-P-0-01 SYMBOLS AND ABBREV.
NII-P-0-02 SPECIFICATIONS
NII-P-0-03 DETAILS
NII-P-1-01 PLUMBING
NII-P-1-02 PLUMBING
ELECTRICAL:
NII-E-0-01 SYMBOLS AND ABBREV.
NII-E-0-02 SPECIFICATIONS
NII-E-0-03 SPECIFICATIONS
NII-E-0-04 SCHEDULES
NII-E-0-05 SCHEDULES
NII-EL-01 SOUTH LIGHTING
NII-EL-02 NORTH LIGHTING
NII-EP-01 SOUTH AND NORTH POWER
DRAWING INDEX:
10' - 0" MINIMUM
M
IN
IM
U
M
NII BUILDING
VEHICLE
ENTRY
VEHICLE
EXIT
SUPPORT BOOTH
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.
GENERAL SERVICE ADMINISTRATION
U.S. LAND PORT OF ENTRY
STANDARDIZED ELEMENTS
2 0 1 S O U T H U P P E R B R O A D W A Y, C O R P U S C H R I S T I, T E X A S 78401
C
ER
TI
FI
C A
TI
O
N S
K
EY
P
LA
N
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
C O
N
TR
A C
TO
R
S B
U
IL
D
IN
G
PR
O
JE
C T
D R
A W
IN
G
A/E CON. NO.
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY/ST. ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
GS-07P-07-HH-D-0083
GS-P-07-08-HH-5166
RICHTER ARCHITECTS
STANDARDIZED ELEMENTS
LAND PORT OF ENTRY
STANDARDIZED ELEMENTS
STANDARDIZED ENCLOSED NON-INTRUSIVE
INSPECTION BUILDING
NA
ERIC COOK
100% CONSTRUCTION DOCUMENTS
06/03/2009
SCALE:
DATE DRAFTED: 09/01/09
SHEET SIZE: 24 x 36
FINAL DOCUMENTS
NOT FOR REGULATORY APPROVAL,
PERMITTING, OR CONSTRUCTION
ARCHITECT:
DAVID R. RICHTER
T.B.A.E. NO. 7113
PD
SC
A NA
20815.00 - LPOE SE - NII BUILDING.RVT
A 09/01/2009 MOD. TO 06/03/09 SUBMISSION
1" = 60'-0"
GENERAL NOTES AND SPECIFICATIONS
Author Checker
NII-A-01
GENERAL PROJECT NOTES:
INTENT:
THE FOLLOWING PLANS AND SPECIFICATIONS ARE INTENDED AS GUIDELINE DOCUMENTS FOR
THE CONSTRUCTION OF A NON-INTRUSIVE INSPECTION BUILDING FOR U.S. CUSTOMS AND
BORDER PROTECTION.
THESE DRAWINGS AND SPECIFICATIONS ARE NOT TO BE USED FOR CONSTRUCTION. THE SITE
SPECIFIC ENGINEER SHALL REVIEW, MODIFY, AND /OR ADD TO THESE DRAWINGS AS NECESSARY
TO ADAPT THE STRUCTIURE TO LOCAL CONDITIONS. EARTHWORK PREPARATION UNDER THE
BUILDING AND THE FOUNDATION DESIGN IS DEPENDENT ON LOCAL SOIL CONDITIONS AND
SPECIFIC GEOTECHNICAL RECOMMENDATIONS AT EACH PROJECT SITE. THE METAL BUILDING
MANUFACTURER / SUPPLIER WILL DESIGN THE METAL BUILDING FRAMES AND COMPOONENTS
TO THE LOCAL REQUIRED CONDITIONS FOR WIND, EARTHQUAKES, SNOW, ETC.
IT IS THEREFORE INTENDED THAT PORTIONS OF THESE DOCUMENTS WILL BE REVIEWED,
EVALUATED, REVISED IF NECESSARY, AND IMPLEMENTED BY ARCHITECTS, ENGINEERS OR
OTHER PROFESSIONALS QUALIFIED AND LICENSED IN EACH REFERENCED STATE. SUCH
PROFESSIONALS ARE GENERALLY REFERRED TO AS “PROJECT ARCHITECT” OR “ARCHITECT”
BY THESE SPECIFICATIONS, BUT ARE INTENDED TO REFER TO ANY AND ALL DULY LICENSED OR
QUALIFIED PROFESSIONAL CHARGED TO IMPLEMENT THESE PLANS IN THE REFERENCED STATE.
CODES:
THESE CONSTRUCTION DOCUMENTS HAVE BEEN FULLY DEVELOPED IN ACCORDANCE WITH
THE 2006 INTERNATIONAL BUILDING CODE. THESE CONSTRUCTION DOCUMENTS HAVE NOT
BEEN DEVELOPED IN CONSIDERATION OF ALL APPLICABLE LOCAL CODE REQUIREMENTS FOR
EACH REFERENCED SITE AND APPLICATION. IT IS PRESUMED THAT THE PROJECT ARCHITECT
AND ENGINEER WILL MAKE SUCH REVISIONS AND IMPLEMENTATION DETAILS SO AS TO COMPLY
WITH ALL ACCESSIBILITY, LIFE SAFETY, FIRE OR OTHER SUCH CODES OR IMPLIED STANDARDS OF
CARE AS MAY BE REQUIRED OR CUSTOMARY IN THE REFERENCED STATE.
TECHNICAL:
THESE BUILDINGS ARE INTENDED TO SUPPORT PROPRIETARY INSPECTION PROCESSES WHICH
ARE LARGELY NOT KNOWN BY RICHTER ARCHITECTS. THEREFORE, THERE MAY BE CERTAIN
ENGINEERING OR TECHNICAL REQUIREMENTS RELATED TO THE PROPRIETARY PROCESSES
WHICH HAVE NOT BEEN CONTEMPLATED BY THE DESIGN OR PLANS. IT IS PRESUMED THAT THE
PROJECT ARCHITECT WILL HAVE FULL KNOWLEDGE OF THE PROPRIETARY INSPECTION
PROCESSES AT THE TIME OF PROCUREMENT AND IMPLEMENT THESE REQUIREMENTS.
MATERIAL AVAILABILITY OR SUITABILITY:
IT IS EXPECTED THAT CERTAIN MATERIALS, EQUIPMENT, DETAILS, OR CONSTRUCTION SYSTEMS
ARE NOT AVAILABLE, COST EFFECTIVE OR TECHNICALLY SUITABLE FOR USE IN THE
REFERENCED STATE. IT IS PRESUMED THAT THE PROJECT ARCHITECT WILL CONSIDER SUCH
FACTORS AND MAKE SUCH SUBSTITUTIONS OR REVISIONS AS MAY BE PRUDENT OR NECESSARY.
THE PROJECT ARCHITECT WILL BE FULLY AND SOLELY RESPONSIBLE FOR SUCH DECISIONS.
BASIS OF DESIGN:
1.) AN INTERIOR CLEAR SPACE DIMENSION OF 60' WIDE x 170' LONG x 28' HIGH WILL BE
REQUIRED AT THE NII BUILDING.
2.) THE NII BUILDING WILL BE ACCOMPANIED BY ONE OF TWO SUPPORT BOOTHS - A LARGER
CONTROL, GROUND CONTROL AND DRIVER WAITING BOOTH OR A SMALLER GROUND
CONTROL AND DRIVER WAITING BOOTH. THE BOOTHS ARE DESIGNATED AS "LARGE BOOTH"
AND "SMALL BOOTH" IN THESE CONSTRUCTION DOCUMENTS. IT IS ASSUMED THAT A REMOTE
CONTROL BOOTH (NOT IN THIS CONTRACT) WILL BE UTILIZED ELSEWHERE ON THE SITE IF THE
"SMALL BOOTH" OPTION IS IMPLEMENTED.
THE SUPPORT BOOTHS SHALL BE PLACED A MINIMUM OF 10-FEET BEYOND THE EXIT END OF THE SCAN FACILITY AND A MINIMUM OF 10 FEET FROM THE OUTER EDGE OF THE DRIVER'S SIDE OF
THE SCAN FACILITY. SEE DIAGRAM:
3.) THE NII BUILDING ENTRY AND EXIT DOORS ARE REVERSIBLE. IE: A LEFT JUSTIFIED ENTRY DOOR CAN BE A RIGHT JUSTIFIED ENTRY DOOR BY ROTATING THE BUILDING ON THE SITE 180
DEGREES.
4.) THE FOUNDATION PERIMETER BEAM SHALL BE DESIGNED BY THE ENGINEER OF RECORD
FOR EACH REFERENCED SITE. CRITICAL DIMENSIONS RELATED TO THE PERIMETER BEAM SIZING
SHALL BE MAINTAINED IN ACCORDANCE WITH THESE DRAWINGS TO ACCOMODATE A MAXIMUM
OF 30" WIDE EXTERIOR CONCRETE SHIELD WALL. THESE CRITICAL DIMENSIONS ARE INDICATED
ON THE WALL SECTIONS.
5.) THE FOUNDATION INTERIOR SLAB IS NOT INCLUDED IN THIS CONTRACT. THE INTERIOR SLAB
SHALL BE DESIGNED, PROVIDED BY AND INSTALLED BY THE PROPRIETARY VENDOR IN
COORDINATION WITH THE ENGINEER OF RECORD FOR EACH REFERENCED SITE. THE SLAB
DESIGN SHALL BE COORDINATED WITH ALL PROPRIETARY INSPECTION PROCESS
REQUIREMENTS, AN OPTIONAL IN-SLAB RADIANT HEATING SYSTEM (NIC) AND THE FLOOR
DRAINAGE SYSTEM INDICATED IN THESE CONSTRUCTION DOCUMENTS.
6.) PROPRIETARY VENDOR'S WILL DESIGN, PROVIDE AND INSTALL SHIELDED VEHICULAR
DOORS IN LIEU OF THE OVERHEAD COILING VEHICULAR DOORS INDICATED IN THESE
DRAWINGS IF REQUIRED.
7.) ALL PERSONNEL DOOR SHIELDING REQUIRED SHALL BE PROVIDED BY THE PROPRIETARY
VENDOR.
8.) THE NII BUILDING SHALL HAVE A MINIMUM CLEAR DISTANCE OF 100 FEET FROM OTHER NII SCANNING EQUIPMENT. THE NII BUILDING SHALL HAVE A MINIMUM CLEAR DISTANCE OF 120 FEET
FROM RADIATION PORTAL MONITORS. VERIFY ALL CLEAR DISTANCES WITH PROPRIETARY
VENDORS.
9.) BIRD CONTROL ISSUES WILL BE COORDINATED WITH THE PROJECT ARCHITECT OF
RECORD AS REQUIRED FOR EACH REFERENCED SITE.
10.) THE ROUTING OF ALL REQUIRED CONDUIT FOR POWER, DATA, COMMUNICATION, ETC.
SHALL BE COORDINATED BY THE PROJECT ENGINEER OF RECORD.
NII OPTIONS: (TO BE DETERMINED AT EACH REFERENCED SITE)
1.) SUPPORT BOOTH CONFIGURATION:
A. "LARGE" BOOTH INCLUDING CONTROL, GROUND CONTROL AND DRIVER WAITING.
B. "SMALL" BOOTH INCLUDING GROUND CONTROL AND DRIVER WAITING.
2.) EXTERIOR WALL CLADDING:
A. METAL R-TYPE PANEL.
B. CONCRETE SHEILD WALL (THICKNESS TO BE DETERMINED BY PROPRIETARY VENDOR).
3.) VEHICULAR DOOR TYPE:
A. 15' WIDE x 16'-6" HIGH COILING OVERHEAD DOOR.
B. 15' WIDE x 16'-6" HIGH CONCRETE (THICKNESS TO BE DETERMINED BY VENDOR).
4.) RADIANT FLOOR HEATING SYSTEM: (NOT IN CONTRACT) REQUIRED AT NORTHERN
BORDER AND SHALL BE PROVIDED BY AND INSTALLED BY VENDOR.
5.) RADIANT CEILING HEATERS: REQUIRED AT NORTHERN BORDER.
6.) HEAT TRACING AT SANITARY SEWER: REQUIRED AT NORTHERN BORDER. SEE ELECTRIAL
AND PLUMBING DRAWINGS.
7.) BOILER OUTBUILDING:
A. REQUIRED AT NORTHER BORDER.
B. LOCATE BOILER INSIDE NII BUILDING (OUTSIDE 60' x 170' CLEAR DIMENSION).
8.) BOILER TYPE: (NOT IN CONTRACT)
A. GAS (TO BE PROVIDED BY AND INSTALLED BY VENDOR).
B. ELECTRIC (TO BE PROVIDED BY AND INSTALLED BY VENDOR).
9.) TRANSLUCENT R-TYPE PANELS: AS REQUIRED AT EACH REFERENCED SITE.
10.) INTERIOR CEILING LIGHTING: (SEE ELECTRICAL DRAWINGS)
A. FLUORESCENT (AT NORTHERN BORDER).
B. METAL HALIDE (AT SOUTHERN BORDER).
PROJECT SPECIFICATIONS:
SECTION 13122 - METAL BUILDING SYSTEMS:
PART 1 - GENERAL:
THIS SPECIFICATION NEEDS TO BE REVIEWED AND EDITED BY THE ARCHITECT/ENGINEER THAT IS TAKING THE LPOE STANDARD ELEMENTS AND ADAPTING THEM TO SUITE LOCAL CONDITIONS. IT
SHOULD BE MODIFIED TO MEETS LOCAL DESIGN AND CODE SPECIFIED CRITERIA AND MEET
SPECIFIC PROJECTS DEMANDS.
1.1 RELATED DOCUMENTS:
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND
SUPPLEMENTARY CONDITIONS AND DIVISION 1 SPECIFICATION SECTIONS, APPLY TO THIS SECTION.
1.2 SUMMARY:
A. THIS SECTION INCLUDES A SINGLE-STORY, SINGLE-SPAN, RIGID-FRAME-TYPE PRE-ENGINEERED METAL BUILDING OF THE NOMINAL LENGTH, WIDTH, EAVE HEIGHT, AND ROOF PITCH INDICATED.
1. EXTERIOR WALLS ARE COVERED WITH FACTORY-ASSEMBLED R-TYPE (22 GAUGE) WALL PANELS
ATTACHED TO FRAMING MEMBERS USING CONCEALED FASTENERS. ROOF SYSTEM CONSISTS OF
THE MANUFACTURER'S STANDARD R-TYPE ROOF PANEL.
2. MANUFACTURER'S STANDARD BUILDING COMPONENTS AND ACCESSORIES MAY BE USED,
PROVIDED COMPONENTS, ACCESSORIES, AND COMPLETE STRUCTURE CONFORM TO DESIGN
INDICATED AND SPECIFIED REQUIREMENTS.
B. RELATED SECTIONS: THE FOLLOWING SECTIONS CONTAIN REQUIREMENTS THAT RELATE TO
THIS SECTION:
1. CONCRETE FLOOR AND FOUNDATIONS AND INSTALLATION OF ANCHOR BOLTS ARE SPECIFIED IN
DIVISION 3 SECTION "CONCRETE WORK."
2. FINISH HARDWARE AND PROVISIONS FOR MASTERKEYING ARE SPECIFIED IN DIVISION 8 SECTION
"FINISH HARDWARE."
1.3 SYSTEM PERFORMANCE REQUIREMENTS:
A. GENERAL: ENGINEER, DESIGN, FABRICATE AND ERECT THE PRE-ENGINEERED METAL BUILDING
SYSTEM TO WITHSTAND LOADS FROM WINDS, GRAVITY, STRUCTURAL MOVEMENT INCLUDING
MOVEMENT THERMALLY INDUCED, AND TO RESIST IN-SERVICE USE CONDITIONS THAT THE
BUILDING WILL EXPERIENCE, INCLUDING EXPOSURE TO THE WEATHER, WITHOUT FAILURE.
1. DESIGN EACH MEMBER TO WITHSTAND STRESSES RESULTING FROM COMBINATIONS OF LOADS
THAT PRODUCE THE MAXIMUM ALLOWABLE STRESSES IN THAT MEMBER AS PRESCRIBED IN
MBMA'S "DESIGN PRACTICES MANUAL."
B. DESIGN LOADS: BASIC DESIGN LOADS, AS WELL AS AUXILIARY AND COLLATERAL LOADS, ARE
INDICATED ON THE DRAWINGS.
1. BASIC DESIGN LOADS INCLUDE LIVE LOAD, WIND LOAD, AND SEISMIC LOAD, IN ADDITION TO THE
DEAD LOAD.
2. AUXILIARY LOADS INCLUDE DYNAMIC LIVE LOADS SUCH AS THOSE GENERATED BY CRANES AND
MATERIAL HANDLING EQUIPMENT.
3. COLLATERAL LOADS INCLUDE ADDITIONAL DEAD LOADS OVER AND ABOVE THE WEIGHT OF THE
METAL BUILDING SYSTEM SUCH AS SPRINKLER SYSTEMS AND ROOF-MOUNTED MECHANICAL
SYSTEMS.
C. STRUCTURAL FRAMING AND ROOF AND SIDING PANELS: DESIGN PRIMARY AND SECONDARY
STRUCTURAL MEMBERS AND EXTERIOR COVERING MATERIALS FOR APPLICABLE LOADS AND
COMBINATIONS OF LOADS IN ACCORDANCE WITH THE METAL BUILDING MANUFACTURERS
ASSOCIATION'S (MBMA) "DESIGN PRACTICES MANUAL." ROOF AND SIDING PANELS SHALL BE 20
GAUGE.
1. STRUCTURAL STEEL: COMPLY WITH THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION'S
(AISC) "SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL
FOR BUILDINGS" FOR DESIGN REQUIREMENTS AND ALLOWABLE STRESSES.
2. LIGHT GAGE STEEL: COMPLY WITH THE AMERICAN IRON AND STEEL INSTITUTE'S (AISI)
"SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS" AND "DESIGN
OF LIGHT GAGE STEEL DIAPHRAGMS" FOR DESIGN REQUIREMENTS AND ALLOWABLE STRESSES.
3. WELDED CONNECTIONS: COMPLY WITH THE AMERICAN WELDING SOCIETY'S (AWS) "STANDARD
CODE FOR ARC AND GAS WELDING IN BUILDING CONSTRUCTION" FOR WELDING PROCEDURES.
D. BUILDING ACCESSORIES: PROVIDE METAL BUILDING SYSTEM ACCESSORIES THAT COMPLY
WITH THE FOLLOWING CRITERIA:
1. HOLLOW METAL DOORS AND FRAMES: COMPLY WITH THE STEEL DOOR INSTITUTE'S SDI-100
FOR TYPES, STYLES, AND DESIGN REQUIREMENTS AND WITH ANSI A115 FOR HARDWARE
PREPARATION.
2. STEEL WINDOWS: COMPLY WITH THE STEEL WINDOW INSTITUTE'S (SWI) "RECOMMENDED
SPECIFICATIONS FOR STEEL WINDOWS" FOR GRADE CLASSIFICATION AND TYPES.
1.4 SUBMITTALS:
A. GENERAL: COORDINATE ALL SUBMITTAL DATA WITH ARCHITECT OF RECORD.
1.5 QUALITY ASSURANCE:
A. INSTALLER QUALIFICATIONS: ENGAGE AN EXPERIENCED INSTALLER TO ERECT THE PRE-
ENGINEERED METAL BUILDING WHO HAS SPECIALIZED IN THE ERECTION AND INSTALLATION OF TYPES OF METAL BUILDINGS SYSTEMS SIMILAR TO THAT REQUIRED FOR THIS PROJECT AND WHO IS CERTIFIED IN WRITING BY THE METAL BUILDING SYSTEM MANUFACTURER AS QUALIFIED FOR
ERECTION OF THE MANUFACTURER'S PRODUCTS.
B. MANUFACTURER'S QUALIFICATIONS: PROVIDE PRE-ENGINEERED METAL BUILDINGS
MANUFACTURED BY A FIRM EXPERIENCED IN MANUFACTURING METAL BUILDINGS SYSTEMS THAT
ARE SIMILAR TO THOSE INDICATED FOR THIS PROJECT AND HAVE A RECORD OF SUCCESSFUL IN-
SERVICE PERFORMANCE.
C. SINGLE-SOURCE RESPONSIBILITY: OBTAIN THE METAL BUILDING SYSTEM COMPONENTS,
INCLUDING STRUCTURAL FRAMING, WALL AND ROOF COVERING, AND ACCESSORY COMPONENTS,
FROM ONE SOURCE FROM A SINGLE MANUFACTURER.
D. DESIGN CRITERIA: THE DRAWINGS INDICATE SIZES, PROFILES, AND DIMENSIONAL
REQUIREMENTS OF THE PRE-ENGINEERED METAL BUILDING SYSTEM. METAL BUILDING SYSTEMS
HAVING EQUAL PERFORMANCE CHARACTERISTICS WITH DEVIATIONS FROM INDICATED DIMENSIONS AND PROFILES MAY BE CONSIDERED, PROVIDED DEVIATIONS DO NOT CHANGE THE DESIGN CONCEPT
OR INTENDED PERFORMANCE. THE BURDEN OF PROOF FOR EQUALITY IS ON THE PROPOSER.
1.6 DELIVERY, STORAGE, AND HANDLING:
A. DELIVER PREFABRICATED COMPONENTS, SHEETS, PANELS, AND OTHER MANUFACTURED ITEMS
SO THEY WILL NOT BE DAMAGED OR DEFORMED. PACKAGE WALL AND ROOF PANELS FOR
PROTECTION AGAINST TRANSPORTATION DAMAGE.
B. HANDLING: EXERCISE CARE IN UNLOADING, STORING, AND ERECTING WALL AND ROOF COVERING
PANELS TO PREVENT BENDING, WARPING, TWISTING, AND SURFACE DAMAGE.
C. STACK MATERIALS ON PLATFORMS OR PALLETS, COVERED WITH TARPAULINS OR OTHER
SUITABLE WEATHERTIGHT VENTILATED COVERING. STORE METAL WALL AND ROOF PANELS SO
THAT WATER ACCUMULATIONS WILL DRAIN FREELY. DO NOT STORE PANELS IN CONTACT WITH
OTHER MATERIALS THAT MIGHT CAUSE STAINING, DENTING OR OTHER SURFACE DAMAGE.
1.7 WARRANTY:
A. ROOFING AND SIDING PANEL FINISH WARRANTY: FURNISH THE ROOFING AND SIDING PANEL MANUFACTURER'S WRITTEN WARRANTY, COVERING FAILURE OF THE FACTORY-APPLIED EXTERIOR
FINISH ON METAL WALL AND ROOF PANELS WITHIN THE WARRANTY PERIOD. THIS WARRANTY
SHALL BE IN ADDITION TO AND NOT A LIMITATION OF OTHER RIGHTS THE OWNER MAY HAVE
AGAINST THE CONTRACTOR UNDER THE CONTRACT DOCUMENTS.
1. WARRANTY PERIOD FOR FACTORY-APPLIED EXTERIOR FINISHES ON WALL AND ROOF PANELS IS
20 YEARS AFTER THE DATE OF SUBSTANTIAL COMPLETION.
1.8 EXTRA MATERIALS:
A. MAINTENANCE STOCK: FURNISH AT LEAST 5 PERCENT EXCESS OVER REQUIRED AMOUNT OF
NUTS, BOLTS, SCREWS, WASHERS, AND OTHER REQUIRED FASTENERS FOR EACH METAL BUILDING.
PACK IN CARTONS LABELED TO IDENTIFY THE CONTENTS AND STORE ON THE SITE WHERE
DIRECTED.
PART 2 - PRODUCTS:
2.1 MANUFACTURERS:
A. AVAILABLE MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
MANUFACTURERS OFFERING METAL BUILDING SYSTEMS THAT MAY BE INCORPORATED IN THE
WORK INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING:
1. A & M BUILDING SYSTEMS, INC.
2. AMERICAN BUILDINGS CO.
3. AMERICAN STEEL BUILDING CO., INC.
4. ATLANTIC BUILDING SYSTEMS.
5. BEHLEN MANUFACTURING CO.
6. BUTLER MANUFACTURING CO.
7. CECO BUILDINGS DIVISION.
8. GULF STATES MANUFACTURERS, INC.
9. MBCI METAL ROOF AND WALL SYSTEMS, INC.
10. SOUTHERN STRUCTURES, INC.
11. UNITED STRUCTURES OF AMERICA.
2.2 MATERIALS:
A. HOT-ROLLED STRUCTURAL STEEL SHAPES: COMPLY WITH ASTM A 36 OR A 529.
B. STEEL TUBING OR PIPE: COMPLY WITH ASTM A 500, GRADE B, ASTM A 501, OR ASTM A 53.
C. STEEL MEMBERS FABRICATED FROM PLATE OR BAR STOCK: PROVIDE 42,000 PSI MINIMUM YIELD
STRENGTH. COMPLY WITH ASTM A 529, ASTM A 570, OR ASTM A 572.
D. STEEL MEMBERS FABRICATED BY COLD FORMING: COMPLY WITH ASTM A 607, GRADE 50.
E. COLD-ROLLED CARBON STEEL SHEET: COMPLY WITH REQUIREMENTS OF ASTM A 366 OR
ASTM A 568.
F. HOT-ROLLED CARBON STEEL SHEET: COMPLY WITH REQUIREMENTS OF ASTM A 568 OR ASTM A 569.
G. STRUCTURAL QUALITY ZINC-COATED (GALVANIZED) STEEL SHEET: COMPLY WITH ASTM A 446
WITH G90 COATING COMPLYING WITH ASTM A 525. GRADE TO SUIT MANUFACTURER'S
STANDARDS.
H. ALUMINUM-COATED STEEL SHEETS: COMPLY WITH ASTM A 463 WITH T1-40 COATING.
I. ALUMINUM SHEETS: COMPLY WITH ASTM B 209 FOR ALCLAD ALLOY 3003 OR 3004 WITH TEMPER
AS REQUIRED TO SUIT FORMING OPERATIONS.
J. BOLTS FOR STRUCTURAL FRAMING: COMPLY WITH ASTM A 307 OR ASTM A 325 AS NECESSARY
FOR DESIGN LOADS AND CONNECTION DETAILS.
K. TRANSLUCENT PANELS: GLASS-FIBER-REINFORCED POLYESTER TRANSLUCENT PLASTIC
GLAZING PANELS COMPLYING WITH ASTM D 3841, TYPE CC1, LIMITED FLAMMABILITY, GRADE 2, WEATHER RESISTANT, CRINKLE FINISH BOTH SIDES, WEIGHING NOT LESS THAN 8 OZ. PER SQ. FT.
MATCH CONFIGURATION OF ADJACENT METAL PANELS.
1. COLOR: WHITE.
2. MASTIC: NONSTAINING SATURATED VINYL POLYMER AS RECOMMENDED BY PANEL
MANUFACTURER FOR SEALING LAPS.
L. THERMAL INSULATION: GLASS FIBER BLANKET INSULATION, COMPLYING WITH ASTM C 991, OF
0.5 LB PER CU. FT. DENSITY, THICKNESS AS INDICATED, WITH UL FLAME SPREAD CLASSIFICATION
OF 25 OR LESS, AND 2 INCH WIDE CONTINUOUS VAPOR-TIGHT EDGE TABS. METAL BUILDING
INSULATION SHALL COMPLY WITH NAIMA 202-96 (LATEST REVISION).
1. VAPOR BARRIER: VINYL FILM.
2. R-30 AT ROOF. TO BE INSTALLED BETWEEN PURLINS.
M. PAINT AND COATING MATERIALS: COMPLY WITH PERFORMANCE REQUIREMENTS OF THE
FEDERAL SPECIFICATIONS INDICATED. UNLESS SPECIFICALLY INDICATED OTHERWISE, COMPLIANCE WITH COMPOSITIONAL REQUIREMENTS OF FEDERAL SPECIFICATIONS INDICATED IS NOT REQUIRED.
1. SHOP PRIMER FOR FERROUS METAL: FAST-CURING, LEAD-FREE, UNIVERSAL PRIMER, SELECTED BY THE MANUFACTURER FOR RESISTANCE TO NORMAL ATMOSPHERIC CORROSION, COMPATIBILITY WITH FINISH PAINT SYSTEMS, AND CAPABILITY TO PROVIDE A SOUND FOUNDATION FOR FIELD-
APPLIED TOPCOATS DESPITE PROLONGED EXPOSURE. COMPLY WITH FS TT-P-645.
2. SHOP PRIMER FOR GALVANIZED METAL SURFACES: ZINC DUST-ZINC OXIDE PRIMER SELECTED
BY THE MANUFACTURER FOR COMPATIBILITY WITH SUBSTRATE. COMPLY WITH FS TT-P-641.
2.3 STRUCTURAL FRAMING:
A. RIGID FRAMES: FABRICATE FROM HOT-ROLLED STRUCTURAL STEEL SHAPES. PROVIDE
FACTORY-WELDED, SHOP-PAINTED, BUILT-UP "I-BEAM"-SHAPE OR OPEN-WEB-TYPE FRAMES
CONSISTING OF TAPERED OR PARALLEL FLANGE BEAMS AND TAPERED COLUMNS. FURNISH
FRAMES WITH ATTACHMENT PLATES, BEARING PLATES, AND SPLICE MEMBERS. FACTORY DRILL
FOR FIELD-BOLTED ASSEMBLY.
1. PROVIDE LENGTH OF SPAN AND SPACING OF FRAMES INDICATED. SLIGHT VARIATIONS IN
LENGTH OF SPAN AND FRAME SPACING MAY BE ACCEPTABLE IF NECESSARY TO MEET
MANUFACTURER'S STANDARD.
2. PROVIDE RIGID FRAMES AT ENDWALLS WHERE INDICATED.
B. PRIMARY ENDWALL FRAMING: PROVIDE THE FOLLOWING PRIMARY ENDWALL FRAMING
MEMBERS FABRICATED FOR FIELD-BOLTED ASSEMBLY:
1. ENDWALL COLUMNS: MANUFACTURER'S STANDARD SHOP-PAINTED, BUILT-UP FACTORY-
WELDED "I"-SHAPE OR COLD-FORMED "C" SECTIONS, FABRICATED FROM 14-GAGE (0.0747-INCH)
STEEL.
2. ENDWALL BEAMS: MANUFACTURER'S STANDARD SHOP-PAINTED "C"-SHAPE ROLL-FORMED
SECTIONS FABRICATED FROM 16-GAGE (0.0598-INCH) STEEL.
C. SECONDARY FRAMING: PROVIDE THE FOLLOWING SECONDARY FRAMING MEMBERS:
1. ROOF PURLINS, SIDEWALL AND ENDWALL GIRTS: "C"-OR "Z"-SHAPED SECTIONS FABRICATED FROM 16 GAGE (0.0598-INCH) SHOP-PAINTED ROLL-FORMED STEEL. PURLIN SPACERS SHALL BE
FABRICATED FROM 14-GAGE (0.0747-INCH) COLD-FORMED GALVANIZED STEEL SECTIONS.
2. EAVE STRUTS: UNEQUAL FLANGE "C"-SHAPED SECTIONS FORMED TO PROVIDE ADEQUATE
BACKUP FOR BOTH WALL AND ROOF PANELS. FABRICATE FROM 16-GAGE (0.0598-INCH) SHOP-
PAINTED ROLL-FORMED STEEL.
3. FLANGE AND SAG BRACING: 1-5/8- BY 1-5/8 INCH ANGLES FABRICATED FROM 16-GAGE
(0.0598-INCH) SHOP-PAINTED ROLL-FORMED STEEL.
4. BASE OR SILL ANGLES: FABRICATE FROM 14-GAGE (0.0747-INCH) COLD-FORMED GALVANIZED
STEEL SECTIONS.
5. SECONDARY ENDWALL STRUCTURAL MEMBERS, EXCEPT COLUMNS AND BEAMS, SHALL BE THE
MANUFACTURER'S STANDARD SECTIONS FABRICATED FROM 14-GAGE (0.0747-INCH) COLD-
FORMED GALVANIZED STEEL.
D. WIND BRACING: PROVIDE ADJUSTABLE WIND BRACING USING 1/2 INCH DIAMETER THREADED STEEL RODS; COMPLY WITH ASTM A 36 OR ASTM A 572, GRADE D. LOCATE INTERIOR END BAY
BRACING ONLY WHERE INDICATED. COORDINATE ADDITIONAL BRACING WITH ARCHITECT AND
ENGINEER.
E. BOLTS: PROVIDE SHOP-PAINTED BOLTS EXCEPT WHEN STRUCTURAL FRAMING COMPONENTS
ARE IN DIRECT CONTACT WITH ROOFING AND SIDING PANELS. PROVIDE ZINC-PLATED OR CADMIUM-
PLATED BOLTS WHEN STRUCTURAL FRAMING COMPONENTS ARE IN DIRECT CONTACT WITH
ROOFING AND SIDING PANELS.
F. SHOP PAINTING: CLEAN SURFACES TO BE PRIMED OF LOOSE MILL SCALE, RUST, DIRT, OIL, GREASE, AND OTHER MATTER PRECLUDING PAINT BOND. FOLLOW PROCEDURES OF SSPC-SP3 FOR
POWER-TOOL CLEANING, SSPC-SP7 FOR BRUSH-OFF BLAST CLEANING, AND SSPC-SP1 FOR
SOLVENT CLEANING.
1. PRIME GALVANIZED MEMBERS, AFTER PHOSPHORIC ACID PRETREATMENT, WITH
MANUFACTURER'S STANDARD ZINC DUST-ZINC OXIDE PRIMER.
2.4 ROOFING AND SIDING PANELS:
A. FACE SHEETS: FABRICATE WALL AND ROOF PANEL FACE SHEETS IN R-TYPE PROFILE
FROM 22-GAGE, STRUCTURAL QUALITY, GRADE C, ZINC-COATED STEEL SHEETS.
1. FABRICATE WALL PANELS IN A MANNER THAT WILL ELIMINATE CONDENSATE ON THE
INTERIOR SIDE. DESIGN JOINTS BETWEEN PANELS TO FORM WEATHERTIGHT SEALS.
B. ROOF PANELS: MANUFACTURER'S STANDARD FACTORY-FORMED R-TYPE ROOF PANEL
SYSTEM DESIGNED FOR MECHANICAL ATTACHMENT OF PANELS TO ROOF PURLINS. FORM
PANELS OF 22-GAGE, GRADE C, ZINC-COATED STEEL SHEETS.
1. CLIPS: PROVIDE 16-GAGE (0.0598-INCH) PANEL CLIPS.
2. CLEATS: FACTORY-CALKED, MECHANICALLY SEAMED CLEATS FORMED FROM 24-GAGE
(0.0239-INCH), GRADE C, ZINC-COATED STEEL SHEETS.
C. FASTENERS: SELF-TAPPING SCREWS, BOLTS, NUTS, SELF-LOCKING RIVETS, SELF-
LOCKING BOLTS, END-WELDED STUDS, AND OTHER SUITABLE FASTENERS DESIGNED TO
WITHSTAND DESIGN LOADS.
1. PROVIDE METAL-BACKED NEOPRENE WASHERS UNDER HEADS OF FASTENERS BEARING
ON WEATHER SIDE OF PANELS.
2. USE ALUMINUM OR STAINLESS STEEL FASTENERS FOR EXTERIOR APPLICATION AND
GALVANIZED OR CADMIUM-PLATED FASTENERS FOR INTERIOR APPLICATIONS.
3. LOCATE AND SPACE FASTENINGS IN TRUE VERTICAL AND HORIZONTAL ALIGNMENT. USE
PROPER TOOLS TO OBTAIN CONTROLLED UNIFORM COMPRESSION FOR POSITIVE SEAL
WITHOUT RUPTURE OF NEOPRENE WASHER.
4. PROVIDE FASTENERS WITH HEADS MATCHING COLOR OF ROOFING OR SIDING SHEETS BY
MEANS OF PLASTIC CAPS OR FACTORY-APPLIED COATING.
D. ACCESSORIES: PROVIDE THE FOLLOWING SHEET METAL ACCESSORIES FACTORY-
FORMED OF THE SAME MATERIAL IN THE SAME FINISH AS ROOF AND WALL PANELS:
1. FLASHINGS.
2. CLOSERS.
3. FILLERS.
4. METAL EXPANSION JOINTS.
5. RIDGE COVERS.
6. FASCIAS.
E. FLEXIBLE CLOSURE STRIPS: CLOSED-CELL, EXPANDED CELLULAR RUBBER, SELF-
EXTINGUISHING FLEXIBLE CLOSURE STRIPS. CUT OR PREMOLD TO MATCH CONFIGURATION
OF ROOFING AND SIDING SHEETS. PROVIDE CLOSURE STRIPS WHERE INDICATED OR
NECESSARY TO ENSURE WEATHERTIGHT CONSTRUCTION.
F. SEALING TAPE: PRESSURE-SENSITIVE 100 PERCENT SOLIDS GREY POLYISOBUTYLENE
COMPOUND SEALING TAPE WITH RELEASE PAPER BACKING. PROVIDE PERMANENTLY
ELASTIC, NONSAG, NONTOXIC, NONSTAINING TAPE 1/2 INCH WIDE AND 1/8 INCH THICK.
G. JOINT SEALANT: ONE-PART ELASTOMERIC POLYURETHANE, POLYSULFIDE, OR SILICONE
RUBBER SEALANT AS RECOMMENDED BY THE BUILDING MANUFACTURER.
E. FLUOROPOLYMER FINISH: PROVIDE SHOP-APPLIED FLUOROPOLYMER FINISH TO
GALVANIZED STEEL ROOFING AND SIDING PANELS AND RELATED TRIM AND ACCESSORY
ELEMENTS.
1. CLEAN GALVANIZED STEEL WITH AN ALKALINE COMPOUND, THEN TREAT WITH A ZINC
PHOSPHATE CONVERSION COATING AND SEAL WITH A CHROMIC ACID RINSE.
2. APPLY A 2-COAT FLUOROPOLYMER COATING SYSTEM TO PRETREATED STEEL. COATING
SHALL CONSIST OF A SPECIALLY FORMULATED INHIBITIVE PRIMER APPLIED TO A DRY FILM
THICKNESS OF 0.15 MIL TO 0.25 MIL AND A FLUOROCARBON COLOR COAT CONTAINING NOT
LESS THAN 70 PERCENT POLYVINYLIDENE FLUORIDE RESIN BY WEIGHT APPLIED TO A DRY
FILM THICKNESS OF 0.80 MILS TO 1.3 MILS.
3. COLOR: AS INDICATED BY REFERENCE TO THE MANUFACTURER'S STANDARD COLOR
DESIGNATIONS.
2.5 PERSONNEL DOORS:
A. MATERIALS: FABRICATE PERSONNEL DOORS AND FRAMES FROM COMMERCIAL QUALITY,
COLD-ROLLED CARBON STEEL SHEET OR COMMERCIAL QUALITY HOT-ROLLED, PICKLED AND
OILED CARBON STEEL SHEET.
1. ZINC-COATED STEEL SHEETS: COMPLY WITH ASTM A 526; WITH G60 COATING COMPLYING
WITH ASTM A 525, MILL PHOSPHATIZED.
B. ANCHORS AND ACCESSORIES: PROVIDE MANUFACTURER'S STANDARD UNITS. FOR ITEMS
BUILT INTO EXTERIOR WALLS, USE GALVANIZED UNITS COMPLYING WITH ASTM A 153.
C. DOORS: PROVIDE 3'-0" WIDE BY 7'-0" HIGH INSULATED METAL DOORS. COMPLY WITH SDI-
108 FOR MATERIAL QUALITY, METAL GAGES, AND CONSTRUCTION DETAILS.
D. FRAMES: PROVIDE FRAMES OF THE TYPES AND SIZES INDICATED. COMPLY WITH SDI-100
FOR MATERIAL QUALITY, METAL GAGES, AND CONSTRUCTION DETAILS.
1. PROVIDE STANDARD HOLLOW METAL FRAMES FOR DOORS.
2. PREPARE FRAMES TO RECEIVE 3 SILENCERS ON STRIKE JAMBS OF SINGLE DOOR FRAMES
AND 2 SILENCERS ON HEADS OF FRAMES FOR PAIRS OF DOORS.
E. FABRICATION: FABRICATE UNITS TO BE RIGID, NEAT IN APPEARANCE, AND FREE FROM
DEFECTS, WARP, OR BUCKLE. PROVIDE CONTINUOUS WELDS ON EXPOSED JOINTS; GRIND,
DRESS, AND MAKE WELDS SMOOTH, FLUSH, AND INVISIBLE.
F. HARDWARE: PREPARE HOLLOW METAL UNITS TO RECEIVE MORTISED AND CONCEALED
FINISH HARDWARE, INCLUDING CUTOUTS, REINFORCING, DRILLING, AND TAPPING. COMPLY
WITH ANSI A115.
1. REINFORCE TO RECEIVE FIELD-APPLIED, SURFACE-MOUNTED FINISH HARDWARE.
2. LOCATE FINISH HARDWARE AS INDICATED.
3. PROVIDE HARDWARE FOR EACH DOOR LEAF, AS FOLLOWS:
4. HINGES: 1-1/2 PAIR, STEEL, TEMPLATE HINGES, 4-1/2 INCH BY 4-1/2 INCH.
5. LOCKSET: CYLINDRICAL TYPE, KEY IN KNOB.
6. THRESHOLD: EXTRUDED ALUMINUM (EXTERIOR DOORS ONLY).
7. SILENCERS: PNEUMATIC RUBBER TYPE FOR METAL FRAMES.
8. CLOSERS: HYDRAULIC, 1430-PS.
9. KICKPLATES.
G. SHOP-PAINT EXPOSED SURFACES, INCLUDING GALVANIZED SURFACES, USING
MANUFACTURER'S STANDARD BAKED-ON RUST-INHIBITIVE PRIMER.
SPECIFICATIONS CONTINUED ON NEXT SHEET...
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.
GENERAL SERVICE ADMINISTRATION
U.S. LAND PORT OF ENTRY
STANDARDIZED ELEMENTS
2 0 1 S O U T H U P P E R B R O A D W A Y, C O R P U S C H R I S T I, T E X A S 78401
C
ER
TI
FI
C A
TI
O
N S
K
EY
P
LA
N
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
C O
N
TR
A C
TO
R
S B
U
IL
D
IN
G
PR
O
JE
C T
D R
A W
IN
G
A/E CON. NO.
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY/ST. ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
GS-07P-07-HH-D-0083
GS-P-07-08-HH-5166
RICHTER ARCHITECTS
STANDARDIZED ELEMENTS
LAND PORT OF ENTRY
STANDARDIZED ELEMENTS
STANDARDIZED ENCLOSED NON-INTRUSIVE
INSPECTION BUILDING
NA
ERIC COOK
100% CONSTRUCTION DOCUMENTS
06/03/2009
SCALE:
DATE DRAFTED: 09/01/09
SHEET SIZE: 24 x 36
FINAL DOCUMENTS
NOT FOR REGULATORY APPROVAL,
PERMITTING, OR CONSTRUCTION
ARCHITECT:
DAVID R. RICHTER
T.B.A.E. NO. 7113
PD
SC
A NA
20815.00 - LPOE SE - NII BUILDING.RVT
A 09/01/2009 MOD. TO 06/03/09 SUBMISSION
SPECIFICATIONS
Author Checker
NII-A-02
SPECIFICATIONS CONTINUED FROM PREVIOUS SHEET:
2.6 OVERHEAD COILING DOORS:
A. GENERAL: PROVIDE COMPLETE OVERHEAD COILING DOOR ASSEMBLIES INCLUDING DOOR
CURTAIN, GUIDES, COUNTERBALANCE, HARDWARE, OPERATORS, AND INSTALLATION
ACCESSORIES. OVERHEAD VEHICULAR DOORS SHALL BE 15'-0" WIDE BY 16'-6" HIGH.
B. PERFORMANCE REQUIREMENTS: PROVIDE DOORS CERTIFIED TO WITHSTAND A 20-PSF WIND
LOAD PRESSURE WITH MAXIMUM DEFLECTION OF 1/120 OF THE OPENING WIDTH. CONFIRM
WITH LOCAL CODES AT EACH REFERENCED SITE.
C. DOOR CURTAIN: INTERLOCKING STEEL SLAT DOOR CURTAIN WITH ONE-PIECE SLATS FOR
THE FULL LENGTH OF DOOR WIDTH. FORM FROM 20-GAGE (0.0359-INCH), GRADE A,
STRUCTURAL QUALITY, ZINC-COATED STEEL SHEETS. PHOSPHATE TREAT BEFORE
FABRICATION.
D. ENDLOCKS: PROVIDE ENDLOCKS FABRICATED FROM MALLEABLE IRON CASTINGS,
GALVANIZED AFTER FABRICATION, SECURED TO CURTAIN SLATS WITH GALVANIZED RIVETS.
E. BOTTOM BAR: PROVIDE BOTTOM BAR ON DOOR CURTAIN CONSISTING OF TWO 1/8-INCH-
THICK ANGLES OF THE SAME METAL AS THE DOOR CURTAIN SLATS. PROVIDE FLEXIBLE
RUBBER, VINYL, OR NEOPRENE WEATHER SEAL AND CUSHION BUMPER ON THE BOTTOM BAR.
F. CURTAIN JAMB GUIDES: PROVIDE CURTAIN JAMB GUIDES, BUILT UP USING STEEL ANGLES, CHANNELS AND FLAT BARS COMPLYING WITH ASTM A 36. GALVANIZE AFTER FABRICATION.
G. WEATHER SEALS: 1/8-INCH-THICK CONTINUOUS RUBBER OR NEOPRENE SHEET WEATHER
SEALS ON METAL PRESSURE BARS SECURED TO INSIDE OF CURTAIN COIL HOOD. AT DOOR
JAMBS, USE 1/8-INCH-THICK CONTINUOUS STRIP SECURED TO EXTERIOR SIDE OF JAMB GUIDE.
H. COUNTERBALANCE: ADJUSTABLE STEEL HELICAL TORSION SPRING COUNTERBALANCE,
MOUNTED AROUND A STEEL SHAFT IN A SPRING BARREL AND CONNECTED TO DOOR CURTAIN
WITH BARREL RINGS. USE GREASE-SEALED BEARINGS OR SELF-LUBRICATING GRAPHITE
BEARINGS FOR ROTATING MEMBERS.
I. BRACKETS: CAST-IRON OR COLD-ROLLED STEEL PLATE MOUNTING BRACKETS WITH BELL-
MOUTH GUIDE GROOVE FOR CURTAIN.
J. HOOD: FORM TO ENCLOSE THE COILED CURTAIN AND OPERATING MECHANISM ENTIRELY AT
THE OPENING HEAD AND TO ACT AS A WEATHER SEAL. CONTOUR TO SUIT END BRACKETS TO
WHICH ATTACHED. ROLL AND REINFORCE TOP AND BOTTOM EDGES FOR STIFFNESS. PROVIDE
CLOSED ENDS FOR SURFACE-MOUNTED HOODS, AND ANY PORTION OF BETWEEN-JAMB
MOUNTING PROJECTING BEYOND WALL FACE. PROVIDE INTERMEDIATE SUPPORT BRACKETS
TO PREVENT SAG.
1. FABRICATE HOODS FOR STEEL DOORS OF 24-GAGE (0.0239-INCH), ZINC-COATED STEEL
SHEET. PHOSPHATE TREAT BEFORE FABRICATION.
K. SHOP FINISH: EXCEPT FOR TIGHTLY JOINED AND LUBRICATED SURFACES, SHOP-CLEAN AND
PRIME FERROUS AND GALVANIZED METAL SURFACES, BOTH EXPOSED AND CONCEALED, WITH
THE MANUFACTURER'S STANDARD RUST-INHIBITIVE PRIMER.
L. MANUAL DOOR OPERATORS: PROVIDE MANUAL DOOR OPERATORS IN ADDITION TO
AUTOMATIC OPERATORS. PROVIDE CHAIN HOIST OPERATOR UNIT.
1. CHAIN HOIST OPERATION: PROVIDE OPERATOR CONSISTING OF AN ENDLESS CADMIUM-
PLATED ALLOY STEEL HAND CHAIN, CHAIN POCKET WHEEL AND GUARD, AND GEARED
REDUCTION UNIT WITH MAXIMUM 35-LB. PULL FOR DOOR OPERATION. DESIGN CHAIN HOIST
WITH SELF-LOCKING MECHANISM ALLOWING CURTAIN TO BE STOPPED AT ANY POINT IN ITS
TRAVEL AND TO REMAIN IN THAT POSITION UNTIL MOVEMENT IS REACTIVATED. FURNISH CHAIN
WITH CHAIN HOLDER SECURED TO OPERATOR GUIDE.
M. ELECTRIC DOOR OPERATORS: FURNISH ELECTRIC OPERATOR ASSEMBLY OF SIZE AND
CAPACITY RECOMMENDED BY MANUFACTURER, COMPLETE WITH NEMA RATED MOTOR AND
FACTORY-PREWIRED MOTOR CONTROLS, GEAR REDUCTION UNIT, SOLENOID-OPERATED BRAKE,
REMOTE CONTROL STATIONS, CONTROL DEVICES, CONDUIT AND WIRING FROM CONTROLS TO
MOTOR AND CENTRAL STATIONS, AND ACCESSORIES REQUIRED FOR PROPER OPERATION.
1. PROVIDE A HAND-OPERATED DISCONNECT OR MECHANISM FOR AUTOMATICALLY ENGAGING A
SPROCKET AND CHAIN OPERATOR AND RELEASING THE BRAKE FOR EMERGENCY MANUAL
OPERATION. INCLUDE INTERLOCK DEVICE TO AUTOMATICALLY PREVENT MOTOR FROM
OPERATING WHEN MANUAL OPERATOR IS ENGAGED.
2. ELECTRIC MOTORS: HIGH-STARTING TORQUE, REVERSIBLE, CONSTANT DUTY, CLASS A
INSULATED ELECTRIC MOTOR WITH OVERLOAD PROTECTION, SIZED TO MOVE DOOR IN EITHER
DIRECTION, FROM ANY POSITION, AT NOT LESS THAN 2/3 FT. NOR MORE THAN 1 FT. PER
SECOND. COORDINATE WIRING REQUIREMENTS AND CURRENT CHARACTERISTICS OF MOTORS
WITH BUILDING ELECTRICAL SYSTEM.
3. FURNISH OPEN-DRIP-PROOF-TYPE MOTOR AND CONTROLLER WITH NEMA TYPE 1 ENCLOSURE.
4. REMOTE CONTROL STATION TO BE LOCATED IN SUPPORT BOOTH: NEMA-APPROVED,
MOMENTARY CONTACT, 3-BUTTON CONTROL STATION WITH PUSH BUTTON CONTROLS LABELED
"OPEN," "CLOSE," AND "STOP."
5. EXTERIOR UNITS: FULL-GUARDED, SURFACE-MOUNTED, STANDARD DUTY WEATHERPROOF-
TYPE REMOTE CONTROL STATIONS WITH NEMA TYPE 4 ENCLOSURES. PROVIDE UNITS
DESIGNED FOR KEY OPERATION.
6. AUTOMATIC REVERSING CONTROL: FURNISH EACH DOOR WITH AN AUTOMATIC SAFETY
SWITCH, EXTENDING FULL WIDTH OF THE DOOR BOTTOM, LOCATED WITHIN A NEOPRENE OR
RUBBER ASTRAGAL MOUNTED TO BOTTOM RAIL OF THE DOOR. CONTACT WITH THE SWITCH
BEFORE FULLY CLOSING WILL IMMEDIATELY STOP DOWNWARD TRAVEL AND REVERSE
DIRECTION TO THE FULLY OPENED POSITION. PROVIDE PNEUMATICALLY ACTUATED AUTOMATIC
BOTTOM BAR.
2.7 STEEL WINDOW MEMBERS:
FORM FROM STANDARD HOT-ROLLED STEEL SHAPES, OR COLD-FORMED STEEL PLATE, BAR,
SHEET, OR STRIP, AS DESIGNED BY THE MANUFACTURER TO COMPLY WITH SPECIFIED
REQUIREMENTS.
A. TRIM MEMBERS INCLUDE GLAZING BEADS, SCREEN FRAMES, WEATHERSTRIP RETAINERS,
FLASHING, AND SIMILAR ITEMS NOT FUNCTIONING AS PRIME STRUCTURAL MEMBERS. PROVIDE
UNITS OF EXTRUDED ALUMINUM OR OF FORMED SHEET ALUMINUM OR STAINLESS STEEL.
B. MULLIONS AND SUBFRAMES: FORM OF HOT-ROLLED OR COLD-FORMED STEEL, OF
MANUFACTURER'S STANDARD PROFILE FOR SPAN AND SPACING INDICATED.
C. FASTENERS: PROVIDE BRONZE, BRASS, STAINLESS STEEL, OR OTHER METAL FASTENERS
WARRANTED BY THE MANUFACTURER TO BE NONCORROSIVE AND COMPATIBLE WITH WINDOW
MEMBERS, TRIM, HARDWARE, ANCHORS, AND OTHER COMPONENTS OF CONNECTED WORK.
D. ANCHORS, CLIPS, AND WINDOW ACCESSORIES: DEPENDING ON STRENGTH AND CORROSION-
INHIBITING REQUIREMENTS, FABRICATE UNITS OF STAINLESS STEEL, HOT-DIP ZINC-COATED
STEEL OR IRON COMPLYING WITH ASTM A 123, OR BRONZE/BRASS.
E. WEATHERSTRIPPING: PROVIDE WEATHERSTRIPPING AS RECOMMENDED BY THE
MANUFACTURER, APPLIED TO EACH OPERABLE SASH.
F. GLAZING STOPS: PROVIDE EXTRUDED ALUMINUM OR FORMED STEEL, SNAP-ON OR
SCREWED-TYPE GLAZING STOPS.
G. HARDWARE: PROVIDE STANDARD DESIGN FOR OPERATION INDICATED, OF DIE-CAST STEEL,
MALLEABLE IRON, OR BRONZE, WITH STEEL OR BRONZE OPERATING ARMS.
H. WINDOW TYPES (OPERATION): ALL FIXED UNITS (WITHOUT VENTS).
I. WINDOW CLASSIFICATION (GRADE): AS FOLLOWS:
1. STANDARD INTERMEDIATE WINDOWS: PROVIDE UNITS COMPLYING WITH SWI RECOMMENDED
SPECIFICATIONS (3.0 LBS. PER FT.).
J. GALVANIZED AND PRIME COAT FINISH: PROVIDE SSPC-SP1 CLEANING, SSPC-SP8 PICKLING, AND ASTM A 123 HOT-DIP GALVANIZING, FOLLOWED BY HOT PHOSPHATE TREATMENT, CHROMIC
ACID RINSE, METAL PRIMER DIP COATING, 1-MIL DRY FILM PAINT THICKNESS.
2.8 SHEET METAL ACCESSORIES:
A. GENERAL: PROVIDE COATED STEEL SHEET METAL ACCESSORIES WITH COATED STEEL
ROOFING AND SIDING PANELS.
B. GUTTERS: FORM IN 8-FOOT-LONG SECTIONS, COMPLETE WITH END PIECES, OUTLET TUBES, AND OTHER SPECIAL PIECES AS REQUIRED. SIZE IN ACCORDANCE WITH SMACNA. JOIN
SECTIONS WITH RIVETED AND SOLDERED OR SEALED JOINTS. PROVIDE EXPANSION-TYPE SLIP
JOINT AT CENTER OF RUNS. FURNISH GUTTER SUPPORTS SPACED 36 INCHES ON CENTER,
CONSTRUCTED OF SAME METAL AS GUTTERS. PROVIDE BRONZE, COPPER, OR ALUMINUM WIRE
BALL STRAINERS AT OUTLETS. FINISH TO MATCH ROOF FASCIA AND RAKE.
C. DOWNSPOUTS: FORM IN 10-FOOT-LONG SECTIONS, COMPLETE WITH ELBOWS AND
OFFSETS. JOIN SECTIONS WITH 1-1/2-INCH TELESCOPING JOINTS. PROVIDE FASTENERS
DESIGNED TO HOLD DOWNSPOUTS SECURELY 1 INCH AWAY FROM WALLS; LOCATE FASTENERS
AT TOP AND BOTTOM AND AT APPROXIMATELY 5 FEET ON CENTER IN BETWEEN. FINISH TO
MATCH WALL PANELS.
SECTION 13129 - CONTROL BOOTHS:
PART 1 - GENERAL:
1.1 RELATED DOCUMENTS:
A. ALL PERFORMANCE AND MATERIAL REQUIREMENTS DEFINED IN REMAINING SECTIONS
CONTINUED WITHIN THIS PROJECT MANUAL, IN CONJUNCTION WITH THE CONSTRUCTION
DRAWINGS APPLY TO THE CONSTRUCTION, DELIVERY AND INSTALLATION OF THE INSPECTION
BOOTH UNITS REQUIRED BY THIS PROJECT.
1.2 SUMMARY:
A. THIS PROJECT REQUIRES THE DESIGN, CONSTRUCTION, DELIVERY AND INSTALLATION OF
THE REFERENCED (2) TWO NII SUPPORT BOOTHS AS DESCRIBED IN THE CONSTRUCTION
DOCUMENTS AS "SMALL BOOTH" AND "LARGE BOOTH". THE SCOPE OF WORK SHALL INCLUDE
THE ASSEMBLED & INSTALLED INSPECTION BOOTH STRUCTURES, FIXTURES, FINISHES AND
COMPLETE AND OPERATIONAL ELECTRICAL AND MECHANICAL SYSTEMS IN COMPLIANCE WITH
THE CONTRACT DOCUMENTS. FINAL CONNECTION OF ELECTRICAL POWER, SANITARY TO THE
FINISHED INSPECTION STRUCTURE WILL BE PROVIDED BY THE GENERAL CONTRACTOR.
COMMUNICATIONS AND DATA CABLING WILL BE PROVIDED AND INSTALLED BY THE GENERAL
CONTRACTOR AS DIRECTED BY THE PROJECT ARCHITECT OF RECORD FOR EACH REFERENCED
SITE. BOOTHS SHALL BE FULLY PAINTED FRAME AND EXTERIOR.
B. BOOTH COMPONENTS AND ASSEMBLY SHALL MEET ALL THE REQUIREMENTS OF TYPE III
BULLET RESISTANCE. THE TYPE III BULLET RESISTANCE APPLIES, NO MATTER WHAT IS
INDICATED ELSEWHERE IN THESE CONSTRUCTION DOCUMENTS.
1.3 PERFORMANCE REQUIREMENTS:
A. MODULAR BUILDING SYSTEM:
1. DESIGN AND CONSTRUCTION OF THE MODULAR BUILDING UNITS AND THEIR FINAL ASSEMBLY
SHALL CONFORM TO ALL APPLICABLE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE
2006 EDITION.
2. TRANSPORTING OF THE INSPECTION BOOTH UNITS TO THE PROJECT SITE SHALL BE DONE IN
STRICT COMPLIANCE WITH ALL APPLICABLE CODES, GUIDELINES AND REGULATIONS.
1.4 SUBMITTALS:
A. GENERAL: COORDINATE ALL SUBMITTAL DATA WITH ARCHITECT OF RECORD.
1. STRUCTURAL DESIGN AND CONSTRUCTION PLANS AND DETAILS FOR THE COMPLETE
CONTROL BOOTH UNIT WILL BE REQUIRED. DOCUMENTS SHALL INDICATE STRUCTURAL DESIGN
BY A LICENSED STRUCTURAL ENGINEER CURRENTLY QUALIFIED TO LEGALLY PRACTICE IN THE
REFERENCED STATE. THE STRUCTURAL ENGINEER’S REGISTRATION SEAL SHALL BE AFFIXED
TO ALL DRAWING SHEETS. INDICATE ALL DESIGN LOADING (VERTICAL AND LATERAL) ON THE
PLANS.
2. PROVIDE DRAWINGS, EQUIPMENT AND MATERIALS DATA FOR ELECTRICAL, PLUMBING AND
HVAC SYSTEM FOR ENGINEERS AND ARCHITECTS REVIEW AND APPROVAL.
3. PROVIDE MATERIAL DATA AND SHOP DRAWINGS, WHEN APPLICABLE FOR ALL
ARCHITECTURAL MATERIALS AND FINISHES.
1.5 COORDINATION:
A. COORDINATE ALL ASPECTS OF MANUFACTURING, DELIVERY, INSTALLATION AND FINAL
UTILITY CONNECTIONS AND TERMINATION WITH ALL REQUIRED SUB-CONTRACTOR AND
SUPPLIERS TO PROVIDE THE OWNER A SUBSTANTIALLY COMPLETED FACILITY READY FOR
IMMEDIATE OWNER OCCUPANCY FOR INTENDED USE.
1.6 MANUFACTURES:
A. MANUFACTURING FIRMS INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING:
1. KEYSTONE STRUCTURES, INC.
1.7 FABRICATION:
A. PROVIDE MODULAR BUILDING SYSTEM UTILIZING DESIGN CONCEPTS AND MATERIALS
DESCRIBED IN THE CONTRACT DOCUMENTS THAT INCLUDE, BUT ARE NOT LIMITED TO THE
FOLLOWING:
1. STRUCTURAL STEEL PERIMETER FRAME
2. GALVANIZED METAL ROOF DECKING
3. STRUCTURAL STEEL FRAMING
4. RIGID ROOF INSULATION BOARD.
PART 2 -PRODUCTS:
2.1 MANUFACTURERS:
A. SUBSTITUTES: SUBSTITUTE PRODUCTS AND MANUFACTURER'S WILL BE ACCEPTED WITH
APPROVAL BY THE PROJECT ARCHITECT.
2.2 PRODUCTS:
A. INSULATION: EXTRUDED-POLYSTYRENE BOARD INSULATION. PROVDIDE IN THE
THICKNESSES INDICATED ON THE DRAWINGS. COMPY WITH ASTM E 84, ASTM E 119 AND ASTM
E 136.
B. REMOVABLE RUBBER FLOOR MATTS: HEATTRAK WALKWAY MAT OR EQUAL.
1. HEATTRAK, WALKWAY MATS, 120V, CUSTOM SIZED TO FIT EACH SPACE WITHIN BOOTH. MAT
SHALL BE CONTINUOUS THROUGHOUT ENTIRE FLOOR SURFACE.
2. HEATTRAK SNOW MELTING MATS, WWW.HEATTRAK.COM
C. LINEAR METAL CEILING: HUNTER DOUGLAS, LUXALON SERIES. DEEP BOX 8 SYSTEM OR
EQUAL. 8" WIDTH.
D. ALUMINUM INVERTED LOUVERS: INDUSTRIAL LOUVER, INC. DELANO, MN 55328 OR EQUAL.
WWW.INDUSTRIALLOUVERS.COM. EXTRUDED INVERTED BLADE EQUIPMENT SCREEN, 4"
DEPTH, MODEL 450-XPI. COMPLY WITH THE FOLLOWING:
1. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM), ASTM B209 - SPECIFICATION FOR
ALUMINUM AND ALUMINUM-ALLOY SHEET AND PLATE. ASTM B221 - SPECIFICATION FOR
ALUMINUM AND ALUMINUM-ALLOY EXTRUDED BARS, RODS, WIRE, SHAPES, AND TUBES.
2. AIR MOVEMENT AND CONTROL ASSOCIATION (AMCA), AMCA STANDARD 500 - TEST METHOD
FOR LOUVERS, DAMPERS, AND SHUTTERS. AMCA PUBLICATION 261 - DIRECTORY OF LICENSES
PRODUCTS, CURRENT EDITION.
3. SHEET METAL AND AIR CONDITION CONTRACTORS NATIONAL ASSOCIATION (SMACNA),
SMACNA - ARCHITECTURAL SHEET METAL MANUAL, CURRENT EDITION.
4. AMERICAN ARCHITECTURAL MANUFACTURER'S ASSOCIATION (AAMA), AAMA STANDARD 605 -
VOLUNTARY SPECIFICATION FOR HIGH PERFORMANCE ORGANIC COATING ON ARCHITECTURAL
EXTRUSIONS AND PANELS.
E. ROOF MEMBRANE: DURO-LAST, SINGLE-PLY PVC ROOFING OR EQUAL. INSTALL AS PER
MANUFACTURER'S RECOMMENDATIONS.
F. GLAZING: BULLET RESISTANT. MUST COMPLY WITH ASTM F1233, CLASS III
POLYCARBONATE GLAZING.
G. STAINLESS STEEL INTERIOR WALL PANELS: 18 GAUGE, BRUSHED 304 STAINLESS STEEL.
INSTALL PANELS WITH HORIZONTALLY ORIENTED BRUSH PATTERN. MOUNT TO STEEL ANGLES
WITH 304 STAINLESS STEEL SQUARE HEAD TAPCON SCREWS AT 8" O.C. SEE INTERIOR
SECTIONAL ELEVATIONS FOR SCREW PATTERNS.
H. COUNTERTOPS, SPLASHES, DRAWERS AND BENCH SEATS: 14 GAUGE, 304 STAINLESS
STEEL WITH CONTINUOUSLY WELDED SEAMS. FABRICATE COUNTERS AS ONE MONOLITHIC
UNIT WITH INTEGRAL TURNED-DOWN EDGES.
1. PROVIDE MITERED AND WELDED UNITS AT ALL CORNERS, ONLY.
2. PROVIDE PRE-FABRICATED FULL-EXTENSION DRAWER UNITS FABRICATED OF STAINLESS
STEEL. DRAWER GUIDES SHALL HAVE 150# MINIMUM LOADING CAPACITY.
I. INTERIOR BLINDS: PROVIDE BLINDS FOR ALL GLAZING OPENINGS, INCLUDING GLAZING
OPENING BETWEEN DRIVER WAITING AND CONTROL ROOMS. BLINDS SHALL BE FULL HEIGHT
AND WIDTH OF GLAZING DIMENSIONS INDICATED ON THE DRAWINGS.
1. HUNTER-DOUGLAS, ROLLER SHADE FR, SHEERWEAVE 7100 ROLLER SHADE OR EQUAL.
2. PVC COATED FIBERGLASS LAMINATED WITH 2-PLY 100% BLACKOUT FILM.
3. MEET OR EXCEED FEDERAL FR SPECIFICATION NFPA701 (SMALL SCALE)
D. ROOF VENTILATORS: SEE MECHANICAL DRAWINGS AND SPECIFICATIONS FOR ROOF
VENTILATOR INFORMATION.
E. CONTINUOUS RIDGE VENTILATORS: NOT APPLICABLE.
F. WALL LOUVERS: SEE MECHANICAL DRAWINGS AND SPECIFICATIONS FOR WALL LOUVER
INFORMATION.
2.9 FABRICATION:
A. GENERAL: DESIGN PREFABRICATED COMPONENTS AND NECESSARY FIELD
CONNECTIONS REQUIRED FOR ERECTION TO PERMIT EASY ASSEMBLY AND DISASSEMBLY.
1. FABRICATE COMPONENTS IN SUCH A MANNER THAT ONCE ASSEMBLED, THEY MAY BE
DISASSEMBLED, REPACKAGED, AND REASSEMBLED WITH A MINIMUM AMOUNT OF LABOR.
2. CLEARLY AND LEGIBLY MARK EACH PIECE AND PART OF THE ASSEMBLY TO CORRESPOND
WITH PREVIOUSLY PREPARED ERECTION DRAWINGS, DIAGRAMS, AND INSTRUCTION
MANUALS.
B. STRUCTURAL FRAMING: SHOP-FABRICATE FRAMING COMPONENTS TO INDICATED SIZE
AND SECTION WITH BASE PLATES, BEARING PLATES, AND OTHER PLATES REQUIRED FOR
ERECTION, WELDED IN PLACE. PROVIDE HOLES FOR ANCHORING OR CONNECTIONS
SHOP-DRILLED OR PUNCHED TO TEMPLATE DIMENSIONS.
1. SHOP CONNECTIONS: PROVIDE POWER RIVETED, BOLTED, OR WELDED SHOP
CONNECTIONS.
2. FIELD CONNECTIONS: PROVIDE BOLTED FIELD CONNECTIONS.
PART 3 - EXECUTION:
3.1 ERECTION:
A. FRAMING: ERECT FRAMING TRUE TO LINE, LEVEL, PLUMB, RIGID, AND SECURE. LEVEL
BASE PLATES TO A TRUE EVEN PLANE WITH FULL BEARING TO SUPPORTING STRUCTURES,
SET WITH DOUBLE-NUTTED ANCHOR BOLTS. USE A NONSHRINKING GROUT TO OBTAIN
UNIFORM BEARING AND TO MAINTAIN A LEVEL BASE LINE ELEVATION. MOIST CURE GROUT
FOR NOT LESS THAN 7 DAYS AFTER PLACEMENT.
B. PURLINS AND GIRTS: PROVIDE RAKE OR GABLE PURLINS WITH TIGHT-FITTING CLOSURE
CHANNELS AND FASCIAS. LOCATE AND SPACE WALL GIRTS TO SUIT DOOR AND WINDOW
ARRANGEMENTS AND HEIGHTS. SECURE PURLINS AND GIRTS TO STRUCTURAL FRAMING
AND HOLD RIGIDLY TO A STRAIGHT LINE BY SAG RODS.
C. BRACING: PROVIDE DIAGONAL ROD OR ANGLE BRACING IN ROOF AND SIDEWALLS AS
INDICATED.
1. MOVEMENT-RESISTING FRAMES MAY BE USED IN LIEU OF SIDEWALL ROD BRACING, TO
SUIT MANUFACTURER'S STANDARDS.
2. WHERE DIAPHRAGM STRENGTH OF ROOF OR WALL COVERING IS ADEQUATE TO RESIST
WIND FORCES, ROD OR ANGLE BRACING WILL NOT BE REQUIRED.
D. FRAMED OPENINGS: PROVIDE SHAPES OF PROPER DESIGN AND SIZE TO REINFORCE
OPENINGS AND TO CARRY LOADS AND VIBRATIONS IMPOSED, INCLUDING EQUIPMENT
FURNISHED UNDER MECHANICAL AND ELECTRICAL WORK. SECURELY ATTACH TO
BUILDING STRUCTURAL FRAME.
3.2 ROOFING AND SIDING:
A. GENERAL: ARRANGE AND NEST SIDELAP JOINTS SO PREVAILING WINDS BLOW OVER, NOT
INTO, LAPPED JOINTS. LAP RIBBED OR FLUTED SHEETS ONE FULL RIB CORRUGATION.
APPLY PANELS AND ASSOCIATED ITEMS FOR NEAT AND WEATHERTIGHT ENCLOSURE. AVOID
"PANEL CREEP" OR APPLICATION NOT TRUE TO LINE. PROTECT FACTORY FINISHES FROM
DAMAGE.
1. FIELD CUTTING OF EXTERIOR PANELS BY TORCH IS NOT PERMITTED.
2. PROVIDE WEATHERSEAL UNDER RIDGE CAP. FLASH AND SEAL ROOF PANELS AT EAVE
AND RAKE WITH RUBBER, NEOPRENE, OR OTHER CLOSURES TO EXCLUDE WEATHER.
B. ROOF SHEETS: PROVIDE SEALANT TAPE AT LAPPED JOINTS OF RIBBED OR FLUTED ROOF
SHEETS AND BETWEEN ROOF SHEETS AND PROTRUDING EQUIPMENT, VENTS, AND
ACCESSORIES.
1. APPLY A CONTINUOUS RIBBON OF SEALANT TAPE TO CLEAN, DRY SURFACE OF THE
WEATHER SIDE OF FASTENINGS ON END LAPS, AND ON SIDE LAPS OF CORRUGATED
NESTING-TYPE, RIBBED, OR FLUTED PANELS AND ELSEWHERE AS NEEDED TO MAKE ROOF
SHEETS WEATHERPROOF TO DRIVING RAINS.
C. WALL SHEETS: APPLY ELASTOMERIC SEALANT CONTINUOUSLY BETWEEN METAL BASE
CHANNEL (SILL ANGLE) AND CONCRETE AND ELSEWHERE AS NECESSARY FOR
WATERPROOFING. HANDLE AND APPLY SEALANT AND BACKUP IN ACCORDANCE WITH THE
SEALANT MANUFACTURER'S RECOMMENDATIONS.
1. ALIGN BOTTOM OF WALL PANELS AND FASTEN PANELS WITH BLIND RIVETS, BOLTS, OR
SELF-TAPPING SCREWS. FASTEN FLASHINGS AND TRIM AROUND OPENINGS AND SIMILAR
ELEMENTS WITH SELF-TAPPING SCREWS. FASTEN WINDOW AND DOOR FRAMES WITH
MACHINE SCREWS OR BOLTS. WHEN BUILDING HEIGHT REQUIRES TWO ROWS OF PANELS
AT GABLE ENDS, ALIGN LAP OF GABLE PANELS OVER WALL PANELS AT EAVE HEIGHT.
2. INSTALL SCREW FASTENERS WITH POWER TOOLS HAVING CONTROLLED TORQUE
ADJUSTED TO COMPRESS NEOPRENE WASHER TIGHTLY WITHOUT DAMAGE TO WASHER,
SCREW THREADS, OR PANELS. INSTALL SCREWS IN PREDRILLED HOLES.
3. PROVIDE WEATHERPROOF ESCUTCHEONS FOR PIPE AND CONDUIT PENETRATING
EXTERIOR WALLS.
D. SHEET METAL ACCESSORIES: INSTALL GUTTERS, DOWNSPOUTS, VENTILATORS,
LOUVERS, AND OTHER SHEET METAL ACCESSORIES IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS FOR POSITIVE ANCHORAGE TO BUILDING AND
WEATHERTIGHT MOUNTING. ADJUST OPERATING MECHANISM FOR PRECISE OPERATION.
E. HOLLOW METAL DOORS AND FRAMES: INSTALL DOORS AND FRAMES STRAIGHT, PLUMB,
AND LEVEL. SECURELY ANCHOR FRAMES TO BUILDING STRUCTURE. SET UNITS WITH 1/8-
INCH MAXIMUM CLEARANCE BETWEEN DOOR AND FRAME AT JAMBS AND HEAD AND 3/4-
INCH MAXIMUM BETWEEN DOOR AND FLOOR. ADJUST HARDWARE FOR PROPER
OPERATION.
F. OVERHEAD COILING DOORS: SET DOORS AND OPERATING EQUIPMENT COMPLETE WITH
NECESSARY HARDWARE, JAMB AND HEAD MOLD STOPS, ANCHORS, INSERTS, HANGERS,
AND EQUIPMENT SUPPORTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
ADJUST MOVING HARDWARE FOR PROPER OPERATION.
G. WINDOWS: ANCHOR WINDOWS SECURELY IN PLACE. SEAL PERIMETER OF EACH UNIT
WITH THE ELASTOMERIC SEALANT USED FOR PANELS. ADJUST AND LUBRICATE OPERATING
SASH AND HARDWARE FOR PROPER OPERATION. CLEAN SURFACES OF WINDOW UNITS.
MOUNT SCREENS DIRECT TO FRAMES WITH TAPPED SCREW CLIPS.
H. THERMAL INSULATION: INSTALL INSULATION CONCURRENTLY WITH INSTALLATION OF
ROOF PANELS IN ACCORDANCE WITH…