Brieant Court House BMS Upgrade

PDF 6 MB Posted

Attached to
SDNY-Brieant Courthouse--1st Floor, 2nd Floor, and 6th Floor Option Renovation Build-outs
Solicitation number
47PC0219R0004
Issued by

About this file

As-built drawings and supplemental documents.

View the file

Other files

File Type Posted
9-P-09.dwg DWG drawing
9-M-06.dwg DWG drawing
3-07.dwg DWG drawing
7-03.dwg DWG drawing
9-M-10.dwg DWG drawing
9-FP-05.dwg DWG drawing
9-M-07.dwg DWG drawing
9-FP-09.dwg DWG drawing
9-P-08.dwg DWG drawing
3-23.dwg DWG drawing
9-E-19.dwg DWG drawing
9-FP-08.dwg DWG drawing
9-FP-04.dwg DWG drawing
9-M-11.dwg DWG drawing
3-24.dwg DWG drawing
9-E-10.dwg DWG drawing
7-04.dwg DWG drawing
47PC0219R0004_RFIs_SIGNED.pdf PDF
9-E-13.dwg DWG drawing
9-P-05.dwg DWG drawing
9-E-14.dwg DWG drawing
Amendment_4_-_SF30.pdf PDF
7-05.dwg DWG drawing
9-E-18.dwg DWG drawing
9-P-04.dwg DWG drawing
9-E-23.dwg DWG drawing
9-E-09.dwg DWG drawing
3-03.dwg DWG drawing
9-E-22.dwg DWG drawing
3-02.dwg DWG drawing
Air Balancing Report.pdf PDF
3-22.dwg DWG drawing
IMG_0167.JPG JPG image
IMG_0175.JPG JPG image
IMG_0173.JPG JPG image
IMG_0166.JPG JPG image
IMG_0168.JPG JPG image
IMG_0160.JPG JPG image
IMG_0220.JPG JPG image
IMG_0178.JPG JPG image
IMG_0191.JPG JPG image
Electrical_Panel2.jpg JPG image
IMG_0214.JPG JPG image
IMG_0215.JPG JPG image
IMG_0171.JPG JPG image
IMG_0197.JPG JPG image
IMG_0219.JPG JPG image
IMG_0210.JPG JPG image
IMG_0205.JPG JPG image
IMG_0157.JPG JPG image
Show 40 more

Latest 50 of 120 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRANSMITTAL LETTER

TO: Date: June 8, 2018

Trane Commercial Systems Project Name: Brieant Court House BMS Upgrade

19 Chapin Road Bldg. B Suite 200 Pine

Brook

Project #: 6N62-0071

New Jersey, NY 07058 Customer PO#:

We are sending you: Enclosed/Attached Under Separate Cover Shop Drawings Product Data Sheets Copy of Letter

Plans Copy of Letter Submittals

Specifications Samples Operations & Maint. Manuals

Damper Schedules Room Schedules Device Schedules

Valve Schedules Door Schedules As-Builts

This material/information is being sent:

Per your Request. For your Record and File For Correction & Resubmittal.

For your Review and Approval. Approved as Submitted. For issue to Subcontractors.

For your Review and Comment. Approved as Noted. Final Distributions

We have detailed these Submittals based on our interpretation of the contract drawings & specifications

Return 1 Approved Copy

Fabrication Held for Approval & Written Release

Equipment is being fabricated and any changes may create a delay in shipment and a possible increase in price.

Item Description / Comments Document # / Ref Rev # of Sets

1 Brieant Court House BMS Upgrade As-Built 6N62-0071 0 1

Message/Comments:

Delivered by: Date: 06/08/2018

Received by: Date: 06/08/2018

CC to: # of Copies TRANSMITTED BY:

Frank Merlino

Project Manager

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Tel. 914-275-2932

FAX

Please have your detailing department look carefully at the attached submittals. We cannot be held responsible for any cost or lead time changes incurred for modifications once the equipment has been released for fabrication.

Date: June 8, 2018

BUILDING AUTOMATION SYSTEM

AS-BUILT DRAWINGS

Brieant Court House BMS Upgrade 300 Quarropas Street

White Plains, NY 10601

Submitted To:

Trane Commercial Systems 19 Chapin Road Bldg. B Suite 200

Pine Brook New Jersey, NY 07058

Submitted By:

Frank Merlino Project Manager

JCI Contract: 6N62-0071

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Tel: 914-275-2932

Fax:

STAMPS

Creating a better climate for business.

Environmental Control System

Air Conditioning Heating Diagnostic Services Coil Cleaning Refrigeration Automatic Temperature Controls Facility Management Systems Fire Management Security Management Building Operations and Management Water Treatment Electrical Equipment Emergency Generator / Lighting Equipment Industrial Controls / Recording / Indication Equipment

Facility Management System

Air and Water System Balancing

Fire Management System

Security System

Lighting Services

Instrumentation System Installation

Building Operations Management

Energy Conservation Control

Training Programs

Performance Contracting

Planned Service Agreements

Brieant Court House BMS Upgrade

PROJECT TITLE

ARCHITECT

Phone:

ENGINEER

AKF One Liberty Plaza 165 Broadway, 22nd Floor New York, NY 10006 Phone: 212.354.5656

MECHANICAL CONTRACTOR

Trane Commercial Systems

19 Chapin Road New Jersey, NY 07058 Phone:

ELECTRICAL CONTRACTOR

Phone:

6N62-0071

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

DATE

Branch Information

CONTRACT NUMBER

AB

APPLICATION ENGINEER

06/06/18

PROJECT MANAGERSALES ENGINEER

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

FMMB

300 Quarropas Street White Plains, NY 10601

Brieant Court House BMS Upgrade 6N62-0071

LEGEND

2/183

Wire Symbol indicating:

Cable Destination (DA-T), Cable number (3), Number of wires and size (E.G. 2 #18 wires)

S

Main Air Supply Tube at 20 PSIG

D-N

15-20

Dual Air Supply Tube at

15/20 PSIG

Day=15, Night=20

S

High Pressure Air Supply Tube at 80 PSIG

Air line or Electrical Wire

Connected Lines or Wires

Crossing Lines or Wires, Not Connected

Pneumatic Tube indicating Tube Number

2/18

Wire Symbol indicating:

number of wires and size (E.G. 2 #18 wires)

Electrical Wire Terminal with Appropriate Number

Item Located on Panel Face

In-Line Restrictor

Opposed Blade Damper

Parallel Blade Damper

Air Flow Measuring Station

Filter

Humidifier

Fan

Pump

Heating or Cooling Coil

Ductwork or Piping with

Flow Direction Shown

Drawing Revision Symbol with Appropriate Number

Gage

Current Sensing Switch or Combination Current

Sensing switch & Command Relay

Duct Detector (Smoke, CO, CO2)

2-Way Valve with Actuator

N C

3-Way Valve with

Actuator

N 0

C N C

Vapor Tension Temperature Sensing Element (Low Limit)

Vapor Tension

Element (Hi Limit)

Paddle Type Flow Switch

Pressure Sensing Device

Bulb Type Temperature Sensing Element Located inside

Separable Socket/Well

Strap-on Bulb Type

Element

Combination Bulb Type

Element and Humidity Sensor (Duct Mount)

Humidity Sensing Element Located under Shield in Outside air

Located under Shield in Outside air

Device H

C N O

DRAWING INDEX

Rev Draw ing Description

ATC-1 NETWORK RISER

ATC-1A NETWORK RISER A

ATC-2 CH-1 & CH-2 FLOW LAYOUT

ATC-2A AIR COOLED CH-2 FLOW LAYOUT

ATC-2B CH-1 & CH-2 SEQUENCE OF OPERATION

ATC-2C CH-1 HARDWARE SCHEDULE PAGE 1

ATC-2D CH-1 WIRING DETAILS

ATC-2E CH-1 POINT TO POINT WIRING PAGE 1

ATC-2F CH-1 POINT TO POINT WIRING PAGE 2

ATC-2G REFRIGERANT EXHAUST FLOW DIAGRAM

ATC-3 HWS FLOW LAYOUT

ATC-3A HV-1, 2, 3 FLOW LAYOUT

ATC-3B HWS SEQUENCE OF OPERATION

ATC-3C HWS HARDWARE SCHEDULE

ATC-3D HWS WIRING DETAILS

ATC-3E HWS POINT TO POINT WIRING PAGE 1

ATC-3F HWS POINT TO POINT WIRING PAGE 2

ATC-4 AHU-1,2,3,4 FLOW LAYOUT

ATC-4A AHU-1,2,3,4 SEQUENCE OF OPERATION

ATC-4B AHU-1,2,3,4 HARDWARE SCHEDULE

ATC-4C AHU-1,2,3,4 WIRING DETAILS

ATC-4D AHU-1,2,3,4 POINT TO POINT WIRING PG - 1

ATC-4E AHU-1,2,3,4 POINT TO POINT WIRING PG - 2

ATC-5 FPB COOLING ONLY FLOW LAYOUT

ATC-6 MISC FLOW LAYOUT

CAT-1 PRODUCT LIT CAT

NAME: HWS-CP

DEVICE: FAC2611

MSTP ADD: 4

6N62-0071

Drawing Title

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

NETWORK RISER

ATC-1

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

NETWORK RISER

HUB OR SWITCH

EXISTING NETWORK OF

BRIEANT COURT

HOUSE

PENTHOUSE

NAME: NAE-8

DEVICE: NIE5910

IP ADD: 192.1.1.8

LOCATION: BOILER ROOM

SA BUS

DEVICE: IOM 4711

SA ADD: 4,5,6

(TYPICAL OF 3)

DEVICE: IOM 2721

SA ADD: 7

NAME: GHWPx VFD

DEVICE:VFD

MSTP ADD: 5 TO 6

(TYPICAL OF 2)

NAME: SHWPx VFD

DEVICE:VFD

MSTP ADD: 7 TO 11

(TYPICAL OF 5)

BOILER 3

CONTROL

CABINET

NAME: BOILER 3 CONTROL

CABINET

DEVICE: THIRD PARTY

MSTP ADD: 13

COM

SH

LD

BLK

BLU

IN

BLK

WHT

BLU

OUT

WHT

FC TRUNK TERMINATION

NOTE: GROUND SHIELD

ONLY ONCE, AT THE NAE.

COM

PWR

BLK

BLU

IN

BLK

WHT

BLU

OUT

WHT

SA TRUNK TERMINATION

RED

RED

NOTE: GROUND SHIELD

ONLY ONCE, AT THE FEU.

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

ADS

120 VAC

120 VAC

UPS

NAME: CH-1-CP

DEVICE: FAC2611

MSTP ADD: 37

SA BUS

DEVICE: IOM 4711

SA ADD: 4

120 VAC

NAME: CP-x VFD

DEVICE:VFD

MSTP ADD: 16 TO 17

(TYPICAL OF 2)

NAME: CWPx VFD

DEVICE:VFD

MSTP ADD: 31 TO 33

(TYPICAL OF 3)

NAME: DTGPx VFD

DEVICE:VFD

MSTP ADD: 28 TO 30

(TYPICAL OF 3)

NAME: BTU METER

DEVICE: BTU METER

MSTP ADD: 26 TO 27

(TYPICAL OF 2)

DEVICE: IOM 4711

SA ADD: 7

DEVICE: IOM 2721

SA ADD: 5

DEVICE: IOM 2721

SA ADD: 6

FC BUS

MSTP TRUNK 1

EOL

ROOF

DEVICE: IOM 2721

SA ADD: 8

BILL OF MATERIALS

Designation Qty Part Number Description

Field Devices:

REPEATER1 1 4683-TTM-3F RS485 RPT,N2,MS/TP,24VAC

Panel Devices:

NIE 1 PAG200001AC0 PNL, NIE5510-3, 20X24

NIE-UPS 1 UPS_PC UNINTERRUPTIBLE POWER SUPPLY

WIRING LEGEND

FC BUS – 22 AWG STRANDED, 3-WIRE

TWISTED, SHIELDED CABLE

SA BUS – 22 AWG STRANDED, 4-WIRE,

2-TWISTED PAIR, SHIELDED CABLE

N2 BUS –

ETHERNET CABLE

MODBUS IP -

BOILER 2

CONTROL

CABINET

NAME: BOILER 2 CONTROL

CABINET

DEVICE: THIRD PARTY

MSTP ADD: 12

CHILLER-1

NAME: CHILLER-1

DEVICE: THIRD PARTY

MSTP ADD: 36

NAME: HV-1 VFD

DEVICE:VFD

MSTP ADD: 14

NAME: EF-1 VFD

DEVICE:VFD

MSTP ADD: 15

NAME: AHU-x-CP

DEVICE: FAC2611

MSTP ADD: 22 TO 25

(TYPICAL OF 4)

SA BUS

120 VAC

DEVICE: IOM 2721

SA ADD: 4

DEVICE: IOM 4711

SA ADD: 5,6

(TYPICAL OF 2)

REPEATER-1

(Located in AHU-4 Panel)

AIR COOLED CHILLER

(CH-2)

NAME: CHILLER-2

DEVICE: THIRD PARTY

MSTP ADD: 49

N2 TRUNK

EOL

NAME: TWRx VFD

DEVICE:VFD

N2 ADD: 2 TO 3

(TYPICAL OF 2)

NAME: DTGP4 VFD

DEVICE:VFD

N2 ADD: 34 Name: FPB-2-x device: VMA-1630

N2 ADD: 29 TO 34

(TYPICAL OF 6)

TO OTHER

N2 DEVICES

NAME: NAE-3

DEVICE: NAE4510

IP ADD: 192.1.1.3

LOCATION: 2ND FLOOR

TELEPHONE ROOM 206

2ND FLOOR

Name: FPB-3-x device: VMA-1630

N2 ADD: 26 TO 29

(TYPICAL OF 4)

TO OTHER

N2 DEVICES

NAME: NAE-4

DEVICE: NAE4510

IP ADD: 192.1.1.4

LOCATION: 3RD FLOOR

TELEPHONE ROOM 306

3RD FLOOR

FOURTH FLOOR

PENTHOUSE

SIXTH FLOOR

FIFTH FLOOR

THIRD FLOOR

SECOND FLOOR

FIRST FLOOR

GROUND FLOOR

6N62-0071

Drawing Title

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532

Phone: 914-275-2932

REFERENCE DRAWING

NETWORK RISER A

ATC-1A

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

NAME: NAE-7

DEVICE: NAE4510

IP ADD: 192.1.1.7

LOCATION: 6TH FLOOR

TELEPHONE ROOM 606

NAME: NAE-6

DEVICE: NAE4510

IP ADD: 192.1.1.6

LOCATION: 5TH FLOOR

TELEPHONE ROOM 506

NAME: NAE-5

DEVICE: NAE4510

IP ADD: 192.1.1.5

LOCATION: 4TH FLOOR

TELEPHONE ROOM 406

NAME: NAE-4

DEVICE: NAE4510

IP ADD: 192.1.1.4

LOCATION: 3RD FLOOR

TELEPHONE ROOM 306

NAME: NAE-3

DEVICE: NAE4510

IP ADD: 192.1.1.3

LOCATION: 2ND FLOOR

TELEPHONE ROOM 206

NAME: NAE-2

DEVICE: NAE4510

IP ADD: 192.1.1.2

LOCATION: 1ST FLOOR

TELEPHONE ROOM 106

NAME: NAE-1

DEVICE: NAE4510

IP ADD: 192.1.1.1

LOCATION: GROUND FLOOR

UPS ROOM

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING 16 PORT NETWORK HUB

LOCATION: TELEPHONE ROOM 406

HUB OR SWITCH

NAME: NAE-9

DEVICE: NAE5510

IP ADD: 192.1.1.9

LOCATION: PENTHOUSE MER

EXISTING

HUB OR SWITCH

NAME: NAE-8

DEVICE: NAE5510

IP ADD: 192.1.1.8

LOCATION: PENTHOUSE MER

NAME: OWS

DEVICE: METASYS OPERATOR WORKSTATION

IP ADD: 192.1.1.100

LOCATION: MAINTENANCE OFFICE

NAME: ADX

DEVICE: ADS METASYS SERVER /

OPERATOR WORKSTATION

IP ADD: 192.1.1.10

LOCATION: PENTHOUSE MER

CHWS

TO

AHU’S

CHWR

FROM

AHU’S

HL

CHW-DP

6N62-0071

Drawing Title

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

CH-1 & CH-2 FLOW LAYOUT

ATC-2

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

CHILLER 1

(CH-1)

COND

EVAPCOMP

CH-1 & CH-2 FLOW LAYOUT

SHARED GLOBALLY

LOCATED ON THE NORTH

SIDE OF THE BUILDING

OA-T

OA-H

NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.

NOTE: GREEN COLORED DEVICES ARE PROVIDED BY TRANE.

CWP2-DPS

CWP1-DPS

CWP3-DPS

CWP-3

CWP-2

CWP-1

CWP1-C

CWP1-S

CWP1 VFD

CWP1-O

CWP2-C

CWP2-S

CWP2 VFD

CWP2-O

CWP3-C

CWP3-S

CWP3 VFD

CWP3-O

CWL-T

CHWP-1

CHWP-2

CHWP-3

CHWP1-C

CHWP1-S

CHWP1 VFD

CHWP1-O

CHWP2-C

CHWP2-S

CHWP2 VFD

CHWP2-O

CHWP3-C

CHWP3-S

CHWP3 VFD

CHWP3-O

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

AS-1

NO

CWBYPV-O

EXPANSION

TANK

AIR ELIMATOR W/

BACKFLOW PREVENTION

CHEMICAL

FEED

PANEL

CT-2CT-1

NC

DRAIN

DRAIN

CT2CWS-T

EPB-S

(TYPICAL OF 2)

(EMERGENCY PUSH BUTTON)

LOCATED AT ENTRANCE OF PENTHOUSE

WIRED TO

CH-1 & CH-2 PANEL

CT1-C

CT1-S

CT-1 VFD

CT1-O

CT2-C

CT2-S

CT-2 VFD

CT2-O

CHW-F

24VAC

I/P PWR

Over BACnet MSTP

CHILLER 1

CONTROL

CABINET

CH1-EN

CH1-S

AIR COOLED CHILLER (CH-2)

CHWP-4

NC

C H

W

IS

O V

-C C

H W

IS

O

V

-SNC

C W

IS

O

V -C

C W

IS

O

V -S

CWE-T

CHWE-T

C H

W L -T

NOTE: GRAY COLORED DEVICES ARE PROVIDED BY MECHANICAL CONTRACTOR.

REFER DRAWING NUMBER ATC-2A FOR BOM

CH1-A

CHWR-T

CHWS-T

A

B

CONTINUE ON

DRAWING

ATC-2A

BTU

METER

FILTER FEEDER

N

C CHWBYPV-O

REV-1 11/02/20161

REV-2 1/09/20172

CT1CWS-T

6N62-0071

Drawing Title

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

AIR COOLED CH-2 FLOW LAYOUT

ATC-2A

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.

NOTE: GREEN COLORED DEVICES ARE PROVIDED BY TRANE.

AIR COOLED CH-2 FLOW LAYOUT

BILL OF MATERIALS

Designation Qty Part Number Description

Field Devices:

BTU METER 2 BTU-ST-INSTL34 SYS-10 STD WL CS 0.75-42"

2 SYSTEM-10-BAC BTU METER, BACNET

CH1-EN 1 RH2B-ULAC24V DPDT,10A,HC=24 VAC,W/LED

1 SH2B-05 DPDT RELAY BASE FOR RH2B

CHW-F 1 F-3500 INSERTION MAG METER

1 F-STD-INSTL1 INSTALL KIT, STD, WELDED

CH2CHWR-F 1 F-1210 FLOW METER, DUAL TURBINE, ANA OUT

1 F-STD-INSTL1 INSTALL KIT, STD, WELDED

CHWISOV-C 1 RIBU1C SPDT,10A,HC=10-30 VAC/DC,W/LED

CHWPx-C,-S 4 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY

CHWR-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT

1 TE-631AM-2 WELL TEMP SEN 6" 1K NI

CHWS-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT

1 TE-631AM-2 WELL TEMP SEN 6" 1K NI

CTx-C,-S 2 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY

CTxVLV-C 2 RIBU1C SPDT,10A,HC=10-30 VAC/DC,W/LED

CW-DP 1 DPT2301-050D PRESS SENS,DP,0-50 PSI,MA,0.25%

CW-F 1 F-3500 INSERTION MAG METER

1 F-STD-INSTL1 INSTALL KIT, STD, WELDED

CWISOV-C 1 RIBU1C SPDT,10A,HC=10-30 VAC/DC,W/LED

CWPx-C,-S 3 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY

CWR-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT

1 TE-631AM-2 WELL TEMP SEN 6" 1K NI

CWS-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT

1 TE-631AM-2 WELL TEMP SEN 6" 1K NI

EPBx-S 4 PILNCCB N/C CONTACT BLOCK

2 PILNOCB N/O CONTACT BLOCK

2 ST120SL-N1-BS PUSH PULL STA N1 SURFACE

PULL RESET BOIL SHUT-DOWN

ISOVS-C

ISOVS-S

ISOVR-C

ISOVR-S

COMP

EVAP

CH-2

CONTROL

CABINET

CH-2-C

CH2CHW-FCH2WR-T

CH2WS-T

AS-1 A

B

CONTINUE ON

DRAWING ATC-2

HEAT TRACING ON ALL

EXPOSED CHW LINES

ON ROOF

CHWP4-C

CHWP4-S

CHWP4 VFD

CHWP4-O

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

CH-1 & CH-2 SEQUENCE OF

OPERATION

ATC-2B

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

CH-1 & CH-2 SEQUENCE OF OPERATION

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

CHILLER CONTROL

A. ON SELECTED CHILLER OPEN ANY ISOLATION VALVES (CHWISOV-C OR CWISOV-C).

B. ON THE COOLING TOWERS CONFIRM CHILLER CW ISOLATION VALVES ARE OPEN. WHETHER ONE OR TWO CW PUMPS (CWPx-C) ARE OPERATING, BOTH TOWER CELLS ARE ENABLED (CTx-C) AND FANS ARE CONTROLLED TO THE SAME SPEED.

C. START SYSTEM CHILLED WATER (CHWPx-C) AND CONDENSER WATER PUMPS (CWPx-C) ON LOW SPEED

(ADJ.).

D. HAVE INITIAL CHILLED WATER SETPOINT AT 48 DEG. F; ALLOW CHILLER ON-BOARD CONTROLS TO RAMP

UP CHILLER AS NECESSARY TO MEET CONDITIONS. MAKE SURE PUMPS ARE MAINTAINING LOW FLOW AS A

MINIMUM.

E. ONCE CHILLERS HAVE STABILIZED CHECK OUTSIDE AIR TEMPERATURE (OA-T) FOR RESET OF CHWS

TEMPERATURE, MAINTAIN ΔT AT DESIGN OF CHILLER, E.G. 10 DEG. F, 12 DEG. F, ETC., ACROSS CHWS AND

CHWR TEMPERATURE.

F. HAVE CHW PUMPS (CHWPx-O) RAMP UP/DOWN AS NECESSARY TO MAINTAIN DESIGN ΔT ACROSS THE CHILLERS.

G. HAVE CHILLED WATER PLANT BY-PASS VALVE (CHWBYPV-O) CLOSED ON INITIAL STARTUP, AS THE SYSTEM RAMPS UP IF THERE IS A LOW FLOW SITUATION THAT CAN’T BE CORRECTED BY ADDING SPEED

TO THE CHW PUMPS (CHWPx-O) [E.G. EXCEEDING DP SETPOINT AND PUMPS AT MINIMUM SPEED] THEN THE BY-PASS (CHWBYPV-O) WILL BE MODULATED OPEN TO MAINTAIN LOW FLOW THROUGH CHILLER; ONCE SYSTEM HAS STABILIZED, BY-PASS VALVE (CHWBYPV-O) WILL MODULATE CLOSED AND USE CHW PUMPS TO MAINTAIN LOW FLOW USING BUILDING CHW SYSTEM’S DIFFERENTIAL PRESSURE WITH THE

DP SETPOINT BEING RESET BY THE AHU’S WORSE CASE VALVE POSITION.

H. CHW PUMPS (CHWPx-C) SHOULD BE STAGED AS A FUNCTION OF CHW FLOW RATIO (CHWFR = ACTUAL FLOW DIVIDED BY TOTAL PLANT DESIGN FLOW) AT A STAGING POINT OF 32%, I.E., ONE PUMP SHOULD

OPERATE WHEN THE CHWFR IS BELOW 47% AND TWO PUMPS SHOULD OPERATE WHEN CHWFR IS ABOVE 47%, WITH A TIME DELAY TO PREVENT SHORT CYCLING. THE 32% OPTIMUM STAGING POINT WILL BE RESET UPWARDS AS THE DP SETPOINT IS. THE RATE AND MAXIMUM STAGE UP % WILL BE DETERMINED DURING BALANCING AND FINALIZED DURING COMMISSIONING.

I. CHILLERS ARE MORE EFFICIENT AT HIGHER LEAVING WATER TEMPERATURES SO, IN GENERAL, OPTIMUM EFFICIENCY IS ACHIEVED WHEN THE CHILLED WATER SUPPLY TEMPERATURE (CHWS-T) SETPOINT IS AS HIGH AS POSSIBLE. WHERE ALL ZONES ARE CONTROLLED BY THE BMS, THE BEST RESET STRATEGY IS BASED ON VALVE POSITION WHERE THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT

IS RESET UPWARDS UNTIL THE VALVE CONTROLLING THE COIL THAT REQUIRES THE COLDEST WATER IS WIDE OPEN. THIS STRATEGY ENSURES THAT NO COIL IS STARVED; ALL ARE ABLE TO MAINTAIN THEIR

DESIRED SUPPLY AIR OR SPACE TEMPERATURE SETPOINTS.

NOTE: CONTRARY TO CONVENTIONAL WISDOM, THE IMPACT OF RESET ON THE DEHUMIDIFICATION CAPABILITY OF AIR HANDLERS IS QUITE SMALL AND SHOULD NOT BE A CONCERN. SPACE HUMIDITY IS A FUNCTION OF THE SUPPLY AIR HUMIDITY RATIO, WHICH IN TURN, IS A FUNCTION OF THE COIL LEAVING DRY-BULB TEMPERATURE SETPOINT. REGARDLESS OF CHWST, THE AIR LEAVING A WET COOLING COIL IS NEARLY SATURATED; LOWERING CHWST ONLY SLIGHTLY REDUCES SUPPLY AIR HUMIDITY RATIO. AS LONG AS THE SUPPLY AIR TEMPERATURE CAN BE MAINTAINED AT THE DESIRED SETPOINT, RESETTING CHILLED WATER SUPPLY TEMPERATURE (CHWS-T) WILL NOT

IMPACT SPACE HUMIDITY.

CHILLER STAGING:

CHILLERS WILL BE STAGED MANUALLY VIA A KIRK KEY AND LOCKING SWITCH.

COOLING TOWER CONTROL:

1. INITIAL CHILLER START:

A. UPON RECEIVING CHILLER START COMMAND, COOLING TOWER WILL START AS OUTLINED:

i. CONFIRM CW VALVES ON CHILLER WILL ARE OPEN.

ii. AFTER CONFIRMATION OF VALVES OPEN, START FIRST CONDENSER WATER PUMP ON LOW AND RAMP UP OVER 30 SECONDS TO

CONTROL VALUE AS SENSED BY CONTROLS.

iii. START COOLING TOWER FANS AT LOW AND RAMP UP OVER 30 SECONDS.

2. AFTER CHILLER START-UP:

A. ALLOW SYSTEM TO STABILIZE OVER 5 MINUTE PERIOD AND THEN ALLOW CONTROL SYSTEM TO PROVIDE FOR BEST CONTROL TO

MAINTAIN THE BEST CWRT AS SHOWN IN EQUATION BELOW WITH A MAX OF 90 DEG. F:

CWRT = CHWST + A × PLR + B (1)

(A = –63 + 0.0053 × CDD65 – 0.0087 × WBDD55 + 1.67 × WB + 0.52 × APPROACH – 0.029 × GPM/TON B = 18 – 0.0033 × CDD65 + 0.0053 × WBDD55 – 0.26 × WB + 0.15 × APPROACH – 0.014 × GPM/TON)

THIS SETPOINT MUST BE BOUNDED BY THE MINIMUM CWRT-CHWST DIFFERENCE AT LOW LOAD SPECIFIED BY THE CHILLER

MANUFACTURER.

B. TO OBTAIN THE BEST CWRT STAGE PUMPS ON AS NECESSARY, USE VFD TO RAMP UP TO 100% SPEED AS PUMPS ARE STARTED OVER

30 SECONDS.

i. ALLOW PUMPS TO OPERATE FOR AT LEAST 10 MINUTES (ADJ.) TO PREVENT SHORT CYCLING.

ii. ONCE PUMPS ARE TURNED OFF DUE TO LOAD ALLOW AT LEAST 10 MINUTES (ADJ.) BEFORE PUMP CAN BE RE-STARTED TO PREVENT

SHORT CYCLING.

C. MODULATE BOTH VFDS ON COOLING TOWER FAN TO OBTAIN BEST CWRT.

3. COOLING TOWER SHUT DOWN:

A. WHEN CHILLER SYSTEM SHUTDOWN SEQUENCE IS RECEIVED, ALLOW CHILLER TO RUN THROUGH ITS SHUT DOWN PERIOD, TO BE DETERMINED BY CHILLER MANUFACTURER, AND AFTER APPROPRIATE TIME PREFORM THE FOLLOWING:

i. TURN OFF COOLING TOWER FAN(S).

ii. TURN OFF CONDENSER WATER PUMP(S).

iii. CLOSE ISOLATION VALVES AFTER 30 SECONDS TURNING PUMPS OFF.

CHILLER FAILURE SEQUENCE:

1. IF A FAILURE TO THE WATER COOLED CHILLER IS DETECT THE FOLLOWING WILL TAKE PLACE:

A. TURN COMMAND TO WATER CHILLER TO OFF.

B. TURN COOLING TOWER FANS OFF.

C. ALLOW CHILLED WATER PUMPS AND CONDENSER WATER PUMPS TO RUN FOR 10 MINUTES (ADJ.) BEFORE SHUTTING THEM DOWN.

D. AFTER PUMPS HAVE BEEN OFF FOR 30 SECONDS CLOSE ISOLATION VALVES IN THE CHILLED WATER LINE TO WATER COOLED

CHILLER AND CONDENSER WATER ISOLATION VALVE.

2. PLANT OPERATOR IS TO TRANSFER POWER BY TURNING THE KIRK KEY AND LOCKING POWER TO THE AIR COOLED CHILLER. THIS CAN

OCCUR (IMMEDIATELY OR AFTER 10 MINUTES) AFTER FAILURE TO WATER COOLED CHILLER.

3. PLANT OPERATOR WILL USE THE BAS TO TURN THE AIR COOLED CHILLER SYSTEM ON BY PUSHING THE “AIR COOLED CHILLER

ENABLE” BUTTON ON THE SCREEN. BY PUSHING THIS BUTTON THE FOLLOWING WILL HAPPEN:

A. BOTH CHILLED WATER ISOLATION VALVES WILL OPEN; AFTER FULLY OPEN AND CONFIRMED BY STATUS SWITCH ON VALVE THE AIR COOLED CHILLER CHILLED WATER PUMP WILL SOFT START AND RAMP UP TO SPEED OVER A 30 SECOND (ADJ.) PERIOD.

B. ONCE FLOW HAS BEEN ESTABLISHED AIR COOLED CHILLER WILL START AND OPERATE AT CHILLED WATER SUPPLY SETPOINT OF

45°F (ADJ.).

WHEN SWITCHING BACK TO WATER COOLED CHILLER:

1. PUSH “AIR COOLED CHILLER DISABLE” BUTTON.

A. AIR COOLED CHILLER WILL SHUT DOWN.

B. CHILLED WATER PUMP WILL RUN FOR 10 MINUTES (ADJ.) AFTER CHILLER IS SHUT DOWN.

C. ISOLATION VALVES WILL CLOSE AFTER PUMPS HAVE BEEN OFF FOR 30 SECONDS (ADJ.).

2. PLANT OPERATOR IS TO TRANSFER POWER BY TURNING THE KIRK KEY AND LOCKING POWER TO THE WATER COOLED CHILLER AFTER AIR COOLED CHILLER IS SHUT DOWN COMPLETELY, WHICH SHOULD BE AFTER AIR COOLED CHILLER PUMP IS OFF.

3. PLANT OPERATOR WILL USE THE BAS TO START THE WATER COOLED CHILLER BY PUSHING THE “WATER COOLED CHILLER ENABLE”

BUTTON. BY PUSHING THE BUTTON THE FOLLOWING WILL HAPPEN:

A. ISOLATION VALVES ON THE CONDENSER AND CHILLED WATER SIDE WILL FULLY OPEN; AFTER CONFIRMED STATUS OF VALVE OPEN CHILLED WATER PUMP(S) WILL SOFT START AND RAMP UP TO SPEED OVER A 30 SECOND (ADJ.) PERIOD.

B. COOLING TOWER FANS WILL START AS NEEDED AND RAMP UP OVER A 30 SECOND (ADJ.) PERIOD.

C. RESUME WITH NORMAL SEQUENCE FOR WATER COOLED CHILLER OPERATION.

APPROACH DESIGN TOWER LEAVING WATER TEMPERATURE MINUS WB, °F

CHWFR CHILLED WATER FLOW RATIO, ACTUAL FLOW DIVIDED BY TOTAL PLANT DESIGN FLOW

CHWST CHILLED WATER SUPPLY TEMPERATURE (LEAVING EVAPORATOR TEMPERATURE), °F

CWFR CONDENSER WATER FLOW RATIO, ACTUAL FLOW DIVIDED BY TOTAL PLANT DESIGN FLOW

CWRT CONDENSER WATER RETURN TEMPERATURE (LEAVING CONDENSER WATER TEMPERATURE), °F

CDD65 COOLING DEGREE-DAYS BASE 65°F

DP DIFFERENTIAL PRESSURE, FEET H2O

KW/TON CHILLER EFFICIENCY AT AHRI CONDITIONS, KW/TON

ΔT TEMPERATURE DIFFERENCE, °F

GPM/HP TOWER EFFICIENCY PER ASHRAE STANDARD 90.1

IPLV INTEGRATED PART LOAD VALUE PER AHRI 550/590, KW/TON

NPLV NON-STANDARD PART LOAD VALUE PER AHRI 550/590, KW/TON

RANGE DESIGN TOWER ENTERING MINUS LEAVING WATER TEMPERATURE, °F

PLR PLANT PART LOAD RATIO, CURRENT LOAD DIVIDED BY TOTAL PLANT DESIGN CAPACITY

TOPP THEORETICAL OPTIMUM PLANT PERFORMANCE

WB DESIGN WET-BULB TEMPERATURE, ASHRAE 1%, °F

WBDD55 WET-BULB COOLING DEGREE-DAYS BASE 55°F

REV-1 11/02/20161

REV-3 3/03/20173

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

CH-1 HARDWARE SCHEDULE PG 1

ATC-2C

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

Electrician/Fitter Range Controller Information Field Device

Tag

Point Type System

Name Object Name Expanded ID Lo

H i

Controller

Details

Trunk

Type Trunk Nbr

Trunk

Addr.

Cable Destination

Bay/Terminal

Module

Type Termination Out Panel Panel Location

Reference

Drawing Cable Number

Wiring

/Tubing Termination In Device Termination Out Location

Wiring

/Tubing Termination In Device Location

Ref Detail

Shape

CH-1 FAC 2611 CH-CP ROOF M-401

CH-1 FAC 2611 MS/TP * * CH-CP ROOF M-401

UI IN-1 CH-1 CWS-T Condenser Water Supply Temperature FAC 2611 MS/TP * * UI IN-1 IN1, ICOM1 CH-CP ROOF M-401 2-CP-4-UI IN-1 2/22 2-Wire TE F131

UI IN-2 CH-1 CWR-T Condenser Water Return Temperature FAC 2611 MS/TP * * UI IN-2 IN2, ICOM2 CH-CP ROOF M-401 2-CP-4-UI IN-1 2/22 2-Wire TE F131

UI IN-3 CH-1 CHWS-T Chilled Water Supply Temperature FAC 2611 MS/TP * * UI IN-3 IN3, ICOM3 CH-CP ROOF M-401 2-CP-4-UI IN-3 2/22 2-Wire TE F131

UI IN-4 CH-1 CHWR-T Chilled Water Return Temperature FAC 2611 MS/TP * * UI IN-4 IN4, ICOM4 CH-CP ROOF M-401 2-CP-4-UI IN-4 2/22 2-Wire TE F131

UI IN-5 CH-1 CHW-DP Chilled Water Differential Pressure FAC 2611 MS/TP * * UI IN-5 IN5, +15V CH-CP ROOF M-401 2-CP-4-UI IN-5 2/22 -, + DPT2xxx (mA) F106

UI IN-6 CH-1 CW-DP Cond Water Differential Pressure FAC 2611 MS/TP * * UI IN-6 IN6, +15V CH-CP ROOF M-401 2-CP-4-UI IN-6 2/22 -, + DPT2xxx (mA) F106

BI IN-7 CH-1 CH1-S Chiller 1 Status FAC 2611 MS/TP * * BI IN-7 IN7, ICOM7 CH-CP ROOF M-401 2-CP-4-BI IN-7 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

BI IN-8 CH-1 CH1-A Chiller 1 Alarm FAC 2611 MS/TP * * BI IN-8 IN8, ICOM8 CH-CP ROOF M-401 2-CP-4-BI IN-8 2/22 See wiring detail Dry Contact F301

BO OUT-1 CH-1 CH1CWISOV-CChiller 1 CW Isolation Valve Command FAC 2611 MS/TP * * BO OUT-1 OUT1, 24V COM CH-CP ROOF M-401 2-CP-4-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-2 CH-1 CH1-EN Chiller 1 Enable FAC 2611 MS/TP * * BO OUT-2 OUT2, 24V COM CH-CP ROOF M-401 2-CP-4-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-3 CH-1 CH1CHWISOV-CChiller 1 CHW Isolation Valve Command FAC 2611 MS/TP * * BO OUT-3 OUT3, 24V COM CH-CP ROOF M-401 2-CP-4-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

CO OUT-4 CH-1 CHWP1-O Primary CHW Pump 1 Output FAC 2611 MS/TP * * CO OUT-4 OUT4, OCOM4 CH-CP ROOF M-401 2-CP-4-CO OUT-4 2/22 See VFD Detail VFD Speed Control (Vdc)

CO OUT-5 CH-1 CHWP2-O Primary CHW Pump 2 Output FAC 2611 MS/TP * * CO OUT-5 OUT5, OCOM5 CH-CP ROOF M-401 2-CP-4-CO OUT-5 2/22 See VFD Detail VFD Speed Control (Vdc)

CO OUT-6 CH-1 CHWP3-O Primary CHW Pump 3 Output FAC 2611 MS/TP * * CO OUT-6 OUT6, OCOM6 CH-CP ROOF M-401 2-CP-4-CO OUT-6 2/22 See VFD Detail VFD Speed Control (Vdc)

CO OUT-7 CH-1 CHWP4-O Primary CHW Pump 4 Output FAC 2611 MS/TP * * CO OUT-7 OUT7, OCOM7 CH-CP ROOF M-401 2-CP-4-CO OUT-7 2/22 See VFD Detail VFD Speed Control (Vdc)

AO OUT-8 CH-1 CHWBYPV-O Chilled Water Bypass Valve Output FAC 2611 MS/TP * * AO OUT-8 OUT8, OCOM8,24VAC, COM CH-CP ROOF M-401 2-CP-4-AO OUT-8 2/22 / 2/18 GRY, BLK/BLK, RED M92xx-GGx-x (Vdc) (Ext Source) F267

AO OUT-9 CH-1 CWBYPV-O Condenser Water Bypass Valve Output FAC 2611 MS/TP * * AO OUT-9 OUT9, OCOM9,24VAC, COM CH-CP ROOF M-401 2-CP-4-AO OUT-9 2/22 / 2/18 GRY, BLK/BLK, RED M92xx-GGx-x (Vdc) (Ext Source) F267

CH-1 IOM 4710 CH-CP ROOF M-401

CH-1 IOM 4710 SA Bus 1 5 CH-CP ROOF M-401

UI IN-1 CH-1 CH1CHW-F Chiller 1 CHW Flow IOM 4710 SA Bus 1 5 UI IN-1 IN1, +15V CH-CP ROOF M-401 4-2-CP-4-UI IN-1 2/22 See wiring detail Current Input (2 Wire) F106

UI IN-2 CH-1 CH2CHW-F Chiller 2 CHW Flow IOM 4710 SA Bus 1 5 UI IN-2 IN2, +15V CH-CP ROOF M-401 4-2-CP-4-UI IN-2 2/22 See wiring detail Current Input (2 Wire) F106

UI IN-3 CH-1 CW-F Condenser Water Flow IOM 4710 SA Bus 1 5 UI IN-3 IN3, +15V CH-CP ROOF M-401 4-2-CP-4-UI IN-3 2/22 See wiring detail Current Input (2 Wire) F106

UI IN-4 CH-1 CWP1-S Condenser Water Pump 1 Status IOM 4710 SA Bus 1 5 UI IN-4 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-4-UI IN-4 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

UI IN-5 CH-1 CWP2-S Condenser Water Pump 2 Status IOM 4710 SA Bus 1 5 UI IN-5 IN5, ICOM5 CH-CP ROOF M-401 4-2-CP-4-UI IN-5 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

UI IN-6 CH-1 CWP3-S Condenser Water Pump 3 Status IOM 4710 SA Bus 1 5 UI IN-6 IN6, ICOM6 CH-CP ROOF M-401 4-2-CP-4-UI IN-6 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

BI IN-7 CH-1 IOM 4710 SA Bus 1 5 BI IN-7 IN7, ICOM7 CH-CP ROOF M-401 4-2-CP-4-BI IN-7

BI IN-8 CH-1 IOM 4710 SA Bus 1 5 BI IN-8 IN8, ICOM8 CH-CP ROOF M-401 4-2-CP-4-BI IN-8

BO OUT-1 CH-1 CWP1-C Condenser Water Pump 1 Command IOM 4710 SA Bus 1 5 BO OUT-1 OUT1, 24V COM CH-CP ROOF M-401 4-2-CP-4-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-2 CH-1 CWP2-C Condenser Water Pump 2 Command IOM 4710 SA Bus 1 5 BO OUT-2 OUT2, 24V COM CH-CP ROOF M-401 4-2-CP-4-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-3 CH-1 CWP3-C Condenser Water Pump 3 Command IOM 4710 SA Bus 1 5 BO OUT-3 OUT3, 24V COM CH-CP ROOF M-401 4-2-CP-4-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

CO OUT-4 CH-1 IOM 4710 SA Bus 1 5 CO OUT-4 OUT4, OCOM4 CH-CP ROOF M-401 4-2-CP-4-CO OUT-4

CO OUT-5 CH-1 IOM 4710 SA Bus 1 5 CO OUT-5 OUT5, OCOM5 CH-CP ROOF M-401 4-2-CP-4-CO OUT-5

CO OUT-6 CH-1 IOM 4710 SA Bus 1 5 CO OUT-6 OUT6, OCOM6 CH-CP ROOF M-401 4-2-CP-4-CO OUT-6

CO OUT-7 CH-1 CWP1-O Condenser Water Pump 1 Output IOM 4710 SA Bus 1 5 CO OUT-7 CH-CP ROOF M-401 4-2-CP-4-CO OUT-7 2/22 See VFD Detail VFD Speed Control (Vdc)

AO OUT-8 CH-1 CWP2-O Condenser Water Pump 2 Output IOM 4710 SA Bus 1 5 AO OUT-8 OUT8, OCOM8 CH-CP ROOF M-401 4-2-CP-4-AO OUT-8 2/22 See VFD Detail VFD Speed Control (Vdc)

AO OUT-9 CH-1 CWP3-O Condenser Water Pump 3 Output IOM 4710 SA Bus 1 5 AO OUT-9 OUT9, OCOM9 CH-CP ROOF M-401 4-2-CP-4-AO OUT-9 2/22 See VFD Detail VFD Speed Control (Vdc)

CH-1 IOM 4710 CH-CP ROOF M-401

CH-1 IOM 4710 SA Bus 1 6 CH-CP ROOF M-401

UI IN-1 CH-1 CT1VIB-A Tower 1 Vibration Alarm IOM 4710 SA Bus 1 6 UI IN-1 IN1, ICOM1 CH-CP ROOF M-401 4-2-CP-5-UI IN-1 2/22 See wiring detail Dry Contact F301

UI IN-2 CH-1 CT2VIB-A Tower 2 Vibration Alarm IOM 4710 SA Bus 1 6 UI IN-2 IN2, ICOM2 CH-CP ROOF M-401 4-2-CP-5-UI IN-2 2/22 See wiring detail Dry Contact F301

UI IN-3 CH-1 IOM 4710 SA Bus 1 6 UI IN-3 IN3, ICOM3 CH-CP ROOF M-401 4-2-CP-5-UI IN-3

UI IN-4 CH-1 IOM 4710 SA Bus 1 6 UI IN-4 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-5-UI IN-4

UI IN-5 CH-1 CT1-S Tower 1 Status IOM 4710 SA Bus 1 6 UI IN-5 IN5, +15V CH-CP ROOF M-401 4-2-CP-5-UI IN-5 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

UI IN-6 CH-1 CT1ISOV-S Tower 1 Isolation Valve Status IOM 4710 SA Bus 1 6 UI IN-6 IN6, +15V CH-CP ROOF M-401 4-2-CP-5-UI IN-6 2/22 See wiring detail Dry Contact F301

BI IN-7 CH-1 CT2-S Tower 2 Status IOM 4710 SA Bus 1 6 BI IN-7 IN7, +15V CH-CP ROOF M-401 4-2-CP-5-BI IN-7 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

BI IN-8 CH-1 CT2ISOV-S Tower 2 Isolation Valve Status IOM 4710 SA Bus 1 6 BI IN-8 IN8, +15V CH-CP ROOF M-401 4-2-CP-5-BI IN-8 2/22 See wiring detail Dry Contact F301

BO OUT-1 CH-1 CT1-C Tower 1 Command IOM 4710 SA Bus 1 6 BO OUT-1 OUT1, OCOM1 CH-CP ROOF M-401 4-2-CP-5-BO OUT-1 2/22 See VFD Detail VFD Speed Control (Vdc)

BO OUT-2 CH-1 CT2-C Tower 2 Command IOM 4710 SA Bus 1 6 BO OUT-2 OUT2, OCOM2 CH-CP ROOF M-401 4-2-CP-5-BO OUT-2 2/22 See VFD Detail VFD Speed Control (Vdc)

BO OUT-3 CH-1 CH2-EN Chiller 2 Enable IOM 4710 SA Bus 1 6 BO OUT-3 CH-CP ROOF M-401 4-2-CP-5-BO OUT-3 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501

CO OUT-4 CH-1 CT1ISOV-C Tower 1 Isolation Valve Command IOM 4710 SA Bus 1 6 CO OUT-4 CH-CP ROOF M-401 4-2-CP-5-CO OUT-4 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501

CO OUT-5 CH-1 CT2ISOV-C Tower 2 Isolation Valve Command IOM 4710 SA Bus 1 6 CO OUT-5 IN1, +15V CH-CP ROOF M-401 4-2-CP-5-CO OUT-5 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501

CO OUT-6 CH-1 IOM 4710 SA Bus 1 6 CO OUT-6 IN2, +15V CH-CP ROOF M-401 4-2-CP-5-CO OUT-6

CO OUT-7 CH-1 IOM 4710 SA Bus 1 6 CO OUT-7 IN3, +15V CH-CP ROOF M-401 4-2-CP-5-CO OUT-7

AO OUT-8 CH-1 CT1-O Tower 1 Output IOM 4710 SA Bus 1 6 AO OUT-8 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-5-AO OUT-8 2/22 See VFD Detail VFD Speed Control (Vdc)

AO OUT-9 CH-1 CT2-O Tower 2 Output IOM 4710 SA Bus 1 6 AO OUT-9 IN5, ICOM5 CH-CP ROOF M-401 4-2-CP-5-AO OUT-9 2/22 See VFD Detail VFD Speed Control (Vdc) F301

CH-1 IOM 3731 IN6, ICOM6 CH-CP ROOF M-401

CH-1 IOM 3731 SA Bus 1 4 IN7, ICOM7 CH-CP ROOF M-401

BI IN-1 CH-1 CH1CHWISOV-SChiller 1 CHW Isolation Valve Status IOM 3731 SA Bus 1 4 BI IN-1 IN8, ICOM8 CH-CP ROOF M-401 4-2-CP-6-BI IN-1 2/22 See wiring detail Dry Contact F301

BI IN-2 CH-1 CH1CWISOV-SChiller 1 CW Isolation Valve Status IOM 3731 SA Bus 1 4 BI IN-2 OUT1, OCOM1 CH-CP ROOF M-401 4-2-CP-6-BI IN-2 2/22 See wiring detail Dry Contact F301

BI IN-3 CH-1 CHWP1-S Primary CHW Pump 1 Status IOM 3731 SA Bus 1 4 BI IN-3 OUT2, OCOM2 CH-CP ROOF M-401 4-2-CP-6-BI IN-3 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

BI IN-4 CH-1 CHWP2-S Primary CHW Pump 2 Status IOM 3731 SA Bus 1 4 BI IN-4 CH-CP ROOF M-401 4-2-CP-6-BI IN-4 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

BI IN-5 CH-1 CHWP3-S Primary CHW Pump 3 Status IOM 3731 SA Bus 1 4 BI IN-5 CH-CP ROOF M-401 4-2-CP-6-BI IN-5 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

BI IN-6 CH-1 CHWP4-S Primary CHW Pump 4 Status IOM 3731 SA Bus 1 4 BI IN-6 IN1, +15V CH-CP ROOF M-401 4-2-CP-6-BI IN-6 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301

BI IN-7 CH-1 CH2HT-A Chiller 2 Heat Trace Alarm IOM 3731 SA Bus 1 4 BI IN-7 IN2, ICOM2 CH-CP ROOF M-401 4-2-CP-6-BI IN-7 2/22 See wiring detail Dry Contact F301

BI IN-8 CH-1 EPB-S Emergency Shutdown IOM 3731 SA Bus 1 4 BI IN-8 IN3, +15V CH-CP ROOF M-401 4-2-CP-6-BI IN-8 2/22 See wiring detail Dry Contact F301

BO OUT-1 CH-1 CHWP1-C Primary CHW Pump 1 Command IOM 3731 SA Bus 1 4 BO OUT-1 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-6-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-2 CH-1 CHWP2-C Primary CHW Pump 2 Command IOM 3731 SA Bus 1 4 BO OUT-2 IN5, ICOM5 CH-CP ROOF M-401 4-2-CP-6-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-3 CH-1 CHWP3-C Primary CHW Pump 3 Command IOM 3731 SA Bus 1 4 BO OUT-3 IN6, ICOM6 CH-CP ROOF M-401 4-2-CP-6-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-4 CH-1 CHWP4-C Primary CHW Pump 4 Command IOM 3731 SA Bus 1 4 BO OUT-4 IN7, ICOM7 CH-CP ROOF M-401 4-2-CP-6-BO OUT-4 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043

BO OUT-5 CH-1 IOM 3731 SA Bus 1 4 BO OUT-5 IN8, ICOM8 CH-CP ROOF M-401 4-2-CP-6-BO OUT-5

BO OUT-6 CH-1 IOM 3731 SA Bus 1 4 BO OUT-6 OUT1, 24V COM CH-CP ROOF M-401 4-2-CP-6-BO OUT-6

BO OUT-7 CH-1 IOM 3731 SA Bus 1 4 BO OUT-7 OUT2, 24V COM CH-CP ROOF M-401 4-2-CP-6-BO OUT-7

BO OUT-8 CH-1 REFHORN-C Refrigerant Horn Command IOM 3731 SA Bus 1 4 BO OUT-8 OUT3, 24V COM CH-CP ROOF M-401 4-2-CP-6-BO OUT-8 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501

NOTE: (*) PLEASE REFER RISER DRAWING FOR TRUNK NUMBER & TRUNK ADDRESS.

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

CH-1 WIRING DETAILS

ATC-2D

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

DETAIL F106

FIELD

DEVICE

Output

+ VDC +15 V

CURRENT INPUT -

INTERNAL SOURCE (2 Wire)

IN#

CONTROLLER

DETAIL F131 TEMPERATURE SENSOR INPUT

RTD

Temperature Element

IN#

ICOM#

CONTROLLER

DETAIL F267

24 VAC

H

N

CONTROLLER

OUT#

OCOM#

2 Red

1 Black

3 Gray

Side A:

Mounted away from damper

To change the spring return direction to CW, mount the actuator to the damper shaft so that Side B of the actuator is away from the damper. With power applied, the actuator now drives CCW from the 0° position, and spring returns CW.

Counterclockwise (CCW) Spring Return Direction – Clockwise (CW) Powered Operation

0-10VDC OUTPUT to M92xx-GGx and HGx or VA92xx-GGx and HGx

CONTROLLER

OUT#

OCOM#

Counterclockwise (CCW) Spring Return Direction – Clockwise (CW) Powered Operation

2 Red

1 Black

3 Gray

Side A:

Mounted away from damper

2 Red

1 Black

3 Gray

Side A:

Mounted away from damper

4 Orange

Master-Slave Application

24 VAC

H

N

DETAIL F301 BINARY INPUT (DRY CONTACT)

FIELD DEVICE

DRY CONTACT

(N.O. or N.C. as required)

CONTROLLER

DETAIL F365

N.C.

N.O.

Switch S1

N.O.

N.C.

Switch S2

Factory Set at

20 Degrees

Factory Set at 70 Degrees

Connect to switch contact as required

Blk/Red

Blk/Gry

Blk/Blu

Wht/Red

Wht/Blu

Wht/Gry

BINARY INPUT from M92xx-xxx-x, and VA92xx-xxx-x

ICOM#

IN#

CONTROLLER

DETAIL F501 24 VAC BINARY OUTPUT

(Switch High, EXT Sourced)

FIELD

DEVICE

CONTROLLER

OUT#

24V Hot

24V Com

OCOM#

SET TRIAC JUMPER

TO EXTERNALLY

SOURCED (EXT)

FOR ASSOCIATED

BINARY OUTPUT(S).

DETAIL F578

Black

Red

ON-OFF CONTROL to M92xx-BGx-x and VA92xx-BGx-x (Switch High, EXT Sourced)

24V Com

OCOM#

M9210-BGx-x

M9220-BGx-x

To change the spring return direction to CW, mount the actuator to the damper shaft so that Side B of the actuator is away from the damper. With power applied, the actuator now drives CCW from the 0° position, and spring returns CW.

Side A

24V Hot

24V Com

SET TRIAC JUMPER TO EXTERNALLY

SOURCED (EXT) FOR ASSOCIATED

BINARY OUTPUT(S).

Black

Red

M9208-BGx-x

Side A

SET TRIAC JUMPER TO EXTERNALLY

SOURCED (EXT) FOR ASSOCIATED

BINARY OUTPUT(S).

M9203-BGx-x

DETAIL F901 24 VAC TRIAC OUTPUT

(Switch High, EXT Sourced)

FIELD

DEVICE

24V Com

OCOM#

DETAIL F1043 VFD without Safeties Wiring

POWER

TO VFD

SPEED INPUT

START/STOP

FIELD VERIFY

TERMINATIONS

Current Relay

Coil

24V HOT

24V COM

VFD

COMMAND

Contact

FAULT OR ALARM

STATUS

(If used)

IF A CURRENT RELAY IS PROVIDED

FOR FAN STATUS SENSE THE

POWER OF THE VFD INSTEAD OF

THE LOAD SIDE OF THE MOTOR.

SPEED

DRIVE FAULT

OUTPUT

IF WIRING TO A BINARY OUTPUT SET THE TRIAC

JUMPER TO EXTERNAL (EXT). IF WIRING TO A

RELAY OUTPUT TERMINAL OUT# = OUT# NO.

O U

T#

V

C

2C

H W

IS

O

V- C

6N62-0071

Drawing Title

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

CH-1 POINT TO POINT WIRING PG 1

ATC-2E

Project Title

NO. REVIS ION-LOCATION ECN DATE BY

Sal es Engineer Project Manager Appli cati on Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Inform ation CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

CH-1 PANEL WIRING DETAILS PAGE 1

124816326412

O N

Address:

SA

P

W R

C O

M

SA BUS

FC BUS

C O

M

SH

LD+1

5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24 VAC

C O

M

FAC2611-0

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

O N1 2 3 4 5 6

CURRENT LOOP

SA

TO

S A

D

EV

IC

E

TO

N

EX

T

FC

D

EV

IC

E M

S/

TP

M S/

TP

FR

O M

L A

ST

F

C D

EV

IC

E

IC

O

M

IN

1-

S

O U

T#

1C

W

IS

O V

-C

O U

T#

1-

EN

O U

T#

1C

H W

IS

O

V- C

V

C O

M

0V A

C

PO

W

ER

IC

M

1-

A

HOT

COM

PS-1 GROUND

120VAC

A

B

IN

+1 5V

4-20 mA

R

EF

R

IG

-A

IN

C

M

C H

W -F

IN

C

C

-F

124816326412

O N

Address:

See Room Schedule

SA

FC

IN

IC

O

M

IN

IC

O

M

IN

IN

IC

O

M

IN

IC

O

M

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

BINARY

O U

T1 O

C O

M

O U

T2 O

C O

M

BINARY

H O

T

24V

C O

M

IOM3731-0

FC EOL

IN SA

PW

R

C O

M

+ - C

O M

SH

LD

SA/FC BUS

O U

T3 O

C O

M

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

TRIAC JUMPERS

OUT1

INT

EXT

OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8

C O

M

IC

O

M

IN

C H

2C H

W

IS

O V-

M

D

TG

P1

-S

M

P2

M

P3

M

P4

U

T#

P1

-C

O U

T#

P2

-C

O U

T#

P3

-C

O U

T#

P4

-C

O U

T#

2-

EN

TO

N

EX

T

SA

D

EV

IC

E

SA SA

FR

O

M L

A

ST

S A

D

EV

IC

E

124816326412

O

Address:

SA

FC

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

IOM4711

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

C O

M

+ - C

O M

SH

LD

SA/FC BUS

C O

M

TO

N

EX

T

SA

D

EV

IC

E

SA SA

FR

O

M L

A

ST

S A

D

EV

IC

E

IN

C

0-10V

H

2C H

-F

1K Ni

M

IN

C H

2C H

W L-

T

M

IN

C H

2C H

W E

-T

IN

C

H

W R

-P

IN

C

H

W

-P

C

O M

O U

T#

W

BY

PV

-O

O C

O M

O

P1 -O

O C

O M

O

P2 -O

O C

O M

O

P3 -O

O C

O M

O

P4 -O

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

CH-1 POINT TO POINT WIRING PG 2

ATC-2F

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

HOT

COM

PS-1

GROUND

120VAC

CH-1 PANEL WIRING DETAILS PAGE 2

12481

O

V

IN

IC

O

M

IN

IC

O

M

V

IN

IC

O

M

IN

IC

O

M

V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

BINARY

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

IOM4711

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

P

R

C O

M

+ - C

O M

S H

L D

SA/FC BUS

IC

O

M

IN

C T

-S

O U

T

V

C T

-C

O U

T

V

C T

-C

V

C O

M

IC

O

M

IN

C T

-S

T O

N E

X T

S A

D E

V

IC

E S

A

S A

F R

O M

L A

S T

S A

D E

V

IC

E

IC

O

M

V

IB

-A

IC

O

M

IN

C T

V

IB

-A

O C

O M

O U

-O

O C

O M

O U

T

C T

12481

O

V

IN

IC

O

M

IN

IC

O

M

V

IN

IC

O

M

IN

IC

O

M

V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

BINARY

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

IOM4711

O U

T

O C

O M

O U

T

O C

O M

O U

T

O C

O M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

R

C O

M

+ - C

O M

S H

L

SA/FC BUS

M

P

-S

V

C O

M

IC

O

M

P

-S

IC

O

M

P

-S

T O

N E

X T

S A

D E

V

IC

E S

A

S A

F R

O M

L A

S T

S A

D E

V

IC

E

M

IN

C T

C

-T

M

IN

C T

C

M

C W

IS

O

V -S

IC

O

M

C

H W

IS

O

V -S

O U

T

P

-C

O U

T

V

C W

P

-C

O U

T

P

-C

O C

O M

O U

P

-O

O C

O M

O U

P

-O

O C

O M

O U

T

C W

P

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

REFRIGERANT EXHAUST FLOW

DIAGRAM

ATC-2G

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

REFRIGERANT EXHAUST FLOW LAYOUT

COMBUSTION OA

VENT OAEA TO ROOF

EF-1

NC

OAD-C

OAD-S

NC

REFRIGERANT

MONITORING PANEL

BMS

TO CHILLERS

PENTHOUSE

COMBDPR-C

COMBDPR-S

BILL OF MATERIALS

Designation Qty Part Number Description

Field Devices:

COMBDPR-C 1 M9220-BAC-3 DAMPER ACTUATOR 20 NM SR

EF1-C,-S 1 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY

OAD-C 1 M9220-BAC-3 DAMPER ACTUATOR 20 NM SR

EF1-C

EF1-S

STARTER

H N120 VAC

OAD-S

COMB-S

EF-1 WIRING DETAILS

EF-C

(SOFT)

OAD

BREAK

GLASS

EMRDMP1-C

EMRDMP2-C

COMBDPR

TO BOILER

PANEL

H N24 VAC

SDR-1

EMERGENCY

SHUTDOWN

SWITCH

BREAKGLASS WIRING DETAILS

TYPICAL OF 4

COMBUSTION AIR

FROM SIDE OF

BUILDING

BLR3-A

BLR2-A

L

HW-DP

AS-1

Drawing Title

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

HWS FLOW LAYOUT

ATC-3

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

HWS FLOW LAYOUT

BOILER 1

BOILER 3

BOILER 2

GHWP-1

GHWP-2

(STAND-BY)

GHWP2-C

GHWP2-S

GHWP2 VFD

GHWP2-O

GHWP1-C

GHWP1-S

GHWP1 VFD

GHWP1-O

CP-1

CP1 VFD

CP-2

CP2 VFD

HWS

FROM HV-1,2 & 3

FROM AHU-1,2,3 & 4TO AHU-1,2,3 & 4

SHWP1-DPS

SHWP2-DPS

SHWP3-DPS

SHWP4-DPS

SHWP-2

SHWP-3

SHWP-4

BP2

BP3

SHWP-1

P4-C P4-S

BP2-C

BP2-S

P4-C P4-S

BP3-C

BP3-S

DECOUPLER

SHWP1-C

SHWP1-S

SHWP1 VFD

SHWP1-O

SHWP2-C

SHWP2-S

SHWP2 VFD

SHWP2-O

SHWP3-C

SHWP3-S

SHWP3 VFD

SHWP3-O

SHWP4-C

SHWP4-S

SHWP4 VFD

SHWP4-O

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

SHWP-5

FILTER FEEDER

RADIATION

(WEST)

RADIATION

(SOUTH)

RADIATION

(NORTH)

RADIATION

(EAST)

AIR SEPARATOR

NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.

BOILER 2

CONTROL

CABINET

BLR2-EN

BOILER 1

CONTROL

CABINET

BOILER 3

CONTROL

CABINET

BLR3-EN

NOTE: GREEN COLORED DEVICES ARE PROVIDED BY TRANE.

BLR2LW-T

ZWS-T

W

S -T

H W

R -T

BLR2-S

BLR3-S

SHARED GLOBALLY

LOCATED ON THE NORTH

SIDE OF THE BUILDING

OA-T

OA-H

EPB-S

(TYPICAL OF 2)

(EMERGENCY PUSH BUTTON)

LOCATED AT ENTRANCE OF MECH. RM

WIRED TO

B-2 & B-3 PANEL

TO HV-1,2 & 3

BLR3LW-T

BLR2-FS

BLR3-FS

REFER PAGE ATC-6

FOR MORE DETAILS

REFER PAGE ATC-6

FOR MORE DETAILS

REFER PAGE ATC-6

FOR MORE DETAILS

REFER PAGE ATC-6

FOR MORE DETAILS

NOTE: GRAY COLORED DEVICES ARE PROVIDED BY MECHANICAL CONTRACTOR.

REFER DRAWING NUMBER ATC-3A FOR BOM

A

B

EXISTING

COMMUNICATION

NETWORK

BLR1BYPV-C

BLR1BYPV-S

BLR3ISOV-C

BLR3ISOV-S

BLR2ISOV-C

BLR2ISOV-S

FTRS1-T

FTRS2-T

FTRS3-T

FTRS4-T

SHWP5-DPS

REV-1 11/02/20161

REV-2 12/09/20162

SHWP5-C

SHWP5-S

SHWP5 VFD

SHWP5-O

NOTE: RED COLORED DEVICES ARE CONTROLLED BY THE BOILERS OR PROVIDED INTERNALLY AND PRE-INSTALLED.

H E

A D

M P

CP1-C

CP1-S

CP2-C

CP2-S

HWBYPV-O

HWS HWR

R A

D

R A

D

6TH FLR

R A

D

R A

D

5TH FLR

R A

D

R A

D

4TH FLR

R A

D

R A

D

3RD FLR

R A

D

R A

D

2ND FLR

R A

D

R A

D

1ST FLR

TYPICAL RADIATION (FLR + ZONE)

ZN-TZN-T

ZN-TZN-T

ZN-TZN-T

ZN-TZN-T

ZN-TZN-T

ZN-TZN-T

BLR1ISOV-C

BLR1ISOV-S

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

HV-1, 2, 3 FLOW LAYOUT

ATC-3A

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

HV-1

V

HV-2

V

HV-3

V

HV-1, 2, 3 FLOW LAYOUT

[FLOW DIAGRAM IS INCLUDED FOR AS-BUILT PURPOSES, THE ONLY THING THAT WAS CHANGED WAS A CORRECTION TO THE LOCATION OF THE LOW TEMP ALARM SENSOR (DOWNSTREAM OF HEATING COIL.)]

NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.

HWS

HWR

OA

EA

DA

RA

DA-T

SF VFD

RA-T

PFILT-S

NO MAD-O

NC

MAD-O

NC

MAD-O

RM-T

EF-S

EF STARTER

LT-ALT-A

SF-C

SF-S

SF-O

HV-x FLOW LAYOUT

HWS

HWR

NO

HTG-O

C

REV-1 11/02/20161

ABFMMB

Johnson Controls, Inc.

8 Skyline Dr.

Hawthorne, NY 10532 Phone: 914-275-2932

REFERENCE DRAWING

HWS SEQUENCE OF OPERATION

ATC-3B

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Brieant Court House BMS Upgrade

300 Quarropas Street White Plains, NY 10601

HWS SEQUENCE OF OPERATION

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2016

HOT WATER SYSTEM CONTROL: (STANDARD CONTROL SEQUENCE IS MENTIONED)

SYSTEM ENABLE:

THE HOT WATER SYSTEM WILL BE ENABLED WHEN THE OUTDOOR AIR TEMPERATURE DROPS BELOW THE HEATING OUTDOOR AIR LOCK OUT SETPOINT (HTGOATLOCKOUT-SP 65⁰F ADJ)

AND DISABLED WHEN OT RISES ABOVE. THE HWS CAN BE MANUALLY ENABLED BY CHAGING THE SYSTEM-ENABLE PARAMETER FROM “DISABLED” TO “ENABLE” LOCATED ON THE HWS

GRAPHIC.

HOT WATER TEMPERATURE RESET:

WHEN OSA TEMPERATURE IS ABOVE 65 F (ADJ.) HAVE HOT WATER SUPPLY TEMPERATURE AT 80 F (ADJ.). AS OSA TEMPERATURE GOES BELOW 65 F (ADJ.) TO 55 F (ADJ.) HAVE HOT WATER SUPPLY TEMPERATURE GO FROM 80 F (ADJ.) TO 130 F (ADJ.). AS THE OSA TEMPERATURE GOES BELOW 55 F (ADJ.) HAVE HOT WATER SUPPLY TEMPERATURE GO TO 165 F (ADJ.). THE RESET TABLE SHALL BE ADJUSTABLE WITHOUT PROGRAM MODIFICATION VIA MAXIMUM AND MINIMUM SETPOINTS TO DICTATE THE RANGES OF THE HW SUPPLY RESET FOR

EACH OF 3 OSA STAGES OF RESET. THE OSA PARAMETER WILL ALSO BE ADJUSTABLE WITH MINIMUM AND MAXIMUM VALUES LOCATED ON THE GRAPHIC WITH THE TITLE “HOT WATER

RESET”

BOILER CONTROL:

THIS SYSTEM CONSISTS OF THREE BOILERS…