Brieant Court House BMS Upgrade
PDF 6 MB Posted
- Attached to
- SDNY-Brieant Courthouse--1st Floor, 2nd Floor, and 6th Floor Option Renovation Build-outs
- Solicitation number
- 47PC0219R0004
About this file
As-built drawings and supplemental documents.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 9-P-09.dwg | DWG drawing | |
| 9-M-06.dwg | DWG drawing | |
| 3-07.dwg | DWG drawing | |
| 7-03.dwg | DWG drawing | |
| 9-M-10.dwg | DWG drawing | |
| 9-FP-05.dwg | DWG drawing | |
| 9-M-07.dwg | DWG drawing | |
| 9-FP-09.dwg | DWG drawing | |
| 9-P-08.dwg | DWG drawing | |
| 3-23.dwg | DWG drawing | |
| 9-E-19.dwg | DWG drawing | |
| 9-FP-08.dwg | DWG drawing | |
| 9-FP-04.dwg | DWG drawing | |
| 9-M-11.dwg | DWG drawing | |
| 3-24.dwg | DWG drawing | |
| 9-E-10.dwg | DWG drawing | |
| 7-04.dwg | DWG drawing | |
| 47PC0219R0004_RFIs_SIGNED.pdf | ||
| 9-E-13.dwg | DWG drawing | |
| 9-P-05.dwg | DWG drawing | |
| 9-E-14.dwg | DWG drawing | |
| Amendment_4_-_SF30.pdf | ||
| 7-05.dwg | DWG drawing | |
| 9-E-18.dwg | DWG drawing | |
| 9-P-04.dwg | DWG drawing | |
| 9-E-23.dwg | DWG drawing | |
| 9-E-09.dwg | DWG drawing | |
| 3-03.dwg | DWG drawing | |
| 9-E-22.dwg | DWG drawing | |
| 3-02.dwg | DWG drawing | |
| Air Balancing Report.pdf | ||
| 3-22.dwg | DWG drawing | |
| IMG_0167.JPG | JPG image | |
| IMG_0175.JPG | JPG image | |
| IMG_0173.JPG | JPG image | |
| IMG_0166.JPG | JPG image | |
| IMG_0168.JPG | JPG image | |
| IMG_0160.JPG | JPG image | |
| IMG_0220.JPG | JPG image | |
| IMG_0178.JPG | JPG image | |
| IMG_0191.JPG | JPG image | |
| Electrical_Panel2.jpg | JPG image | |
| IMG_0214.JPG | JPG image | |
| IMG_0215.JPG | JPG image | |
| IMG_0171.JPG | JPG image | |
| IMG_0197.JPG | JPG image | |
| IMG_0219.JPG | JPG image | |
| IMG_0210.JPG | JPG image | |
| IMG_0205.JPG | JPG image | |
| IMG_0157.JPG | JPG image |
Show 40 more
Latest 50 of 120 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRANSMITTAL LETTER
TO: Date: June 8, 2018
Trane Commercial Systems Project Name: Brieant Court House BMS Upgrade
19 Chapin Road Bldg. B Suite 200 Pine
Brook
Project #: 6N62-0071
New Jersey, NY 07058 Customer PO#:
We are sending you: Enclosed/Attached Under Separate Cover Shop Drawings Product Data Sheets Copy of Letter
Plans Copy of Letter Submittals
Specifications Samples Operations & Maint. Manuals
Damper Schedules Room Schedules Device Schedules
Valve Schedules Door Schedules As-Builts
This material/information is being sent:
Per your Request. For your Record and File For Correction & Resubmittal.
For your Review and Approval. Approved as Submitted. For issue to Subcontractors.
For your Review and Comment. Approved as Noted. Final Distributions
We have detailed these Submittals based on our interpretation of the contract drawings & specifications
Return 1 Approved Copy
Fabrication Held for Approval & Written Release
Equipment is being fabricated and any changes may create a delay in shipment and a possible increase in price.
Item Description / Comments Document # / Ref Rev # of Sets
1 Brieant Court House BMS Upgrade As-Built 6N62-0071 0 1
Message/Comments:
Delivered by: Date: 06/08/2018
Received by: Date: 06/08/2018
CC to: # of Copies TRANSMITTED BY:
Frank Merlino
Project Manager
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Tel. 914-275-2932
FAX
Please have your detailing department look carefully at the attached submittals. We cannot be held responsible for any cost or lead time changes incurred for modifications once the equipment has been released for fabrication.
Date: June 8, 2018
BUILDING AUTOMATION SYSTEM
AS-BUILT DRAWINGS
Brieant Court House BMS Upgrade 300 Quarropas Street
White Plains, NY 10601
Submitted To:
Trane Commercial Systems 19 Chapin Road Bldg. B Suite 200
Pine Brook New Jersey, NY 07058
Submitted By:
Frank Merlino Project Manager
JCI Contract: 6N62-0071
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Tel: 914-275-2932
Fax:
STAMPS
Creating a better climate for business.
Environmental Control System
Air Conditioning Heating Diagnostic Services Coil Cleaning Refrigeration Automatic Temperature Controls Facility Management Systems Fire Management Security Management Building Operations and Management Water Treatment Electrical Equipment Emergency Generator / Lighting Equipment Industrial Controls / Recording / Indication Equipment
Facility Management System
Air and Water System Balancing
Fire Management System
Security System
Lighting Services
Instrumentation System Installation
Building Operations Management
Energy Conservation Control
Training Programs
Performance Contracting
Planned Service Agreements
Brieant Court House BMS Upgrade
PROJECT TITLE
ARCHITECT
Phone:
ENGINEER
AKF One Liberty Plaza 165 Broadway, 22nd Floor New York, NY 10006 Phone: 212.354.5656
MECHANICAL CONTRACTOR
Trane Commercial Systems
19 Chapin Road New Jersey, NY 07058 Phone:
ELECTRICAL CONTRACTOR
Phone:
6N62-0071
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
DATE
Branch Information
CONTRACT NUMBER
AB
APPLICATION ENGINEER
06/06/18
PROJECT MANAGERSALES ENGINEER
REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY
FMMB
300 Quarropas Street White Plains, NY 10601
Brieant Court House BMS Upgrade 6N62-0071
LEGEND
2/183
Wire Symbol indicating:
Cable Destination (DA-T), Cable number (3), Number of wires and size (E.G. 2 #18 wires)
S
Main Air Supply Tube at 20 PSIG
D-N
15-20
Dual Air Supply Tube at
15/20 PSIG
Day=15, Night=20
S
High Pressure Air Supply Tube at 80 PSIG
Air line or Electrical Wire
Connected Lines or Wires
Crossing Lines or Wires, Not Connected
Pneumatic Tube indicating Tube Number
2/18
Wire Symbol indicating:
number of wires and size (E.G. 2 #18 wires)
Electrical Wire Terminal with Appropriate Number
Item Located on Panel Face
In-Line Restrictor
Opposed Blade Damper
Parallel Blade Damper
Air Flow Measuring Station
Filter
Humidifier
Fan
Pump
Heating or Cooling Coil
Ductwork or Piping with
Flow Direction Shown
Drawing Revision Symbol with Appropriate Number
Gage
Current Sensing Switch or Combination Current
Sensing switch & Command Relay
Duct Detector (Smoke, CO, CO2)
2-Way Valve with Actuator
N C
3-Way Valve with
Actuator
N 0
C N C
Vapor Tension Temperature Sensing Element (Low Limit)
Vapor Tension
Element (Hi Limit)
Paddle Type Flow Switch
Pressure Sensing Device
Bulb Type Temperature Sensing Element Located inside
Separable Socket/Well
Strap-on Bulb Type
Element
Combination Bulb Type
Element and Humidity Sensor (Duct Mount)
Humidity Sensing Element Located under Shield in Outside air
Located under Shield in Outside air
Device H
C N O
DRAWING INDEX
Rev Draw ing Description
ATC-1 NETWORK RISER
ATC-1A NETWORK RISER A
ATC-2 CH-1 & CH-2 FLOW LAYOUT
ATC-2A AIR COOLED CH-2 FLOW LAYOUT
ATC-2B CH-1 & CH-2 SEQUENCE OF OPERATION
ATC-2C CH-1 HARDWARE SCHEDULE PAGE 1
ATC-2D CH-1 WIRING DETAILS
ATC-2E CH-1 POINT TO POINT WIRING PAGE 1
ATC-2F CH-1 POINT TO POINT WIRING PAGE 2
ATC-2G REFRIGERANT EXHAUST FLOW DIAGRAM
ATC-3 HWS FLOW LAYOUT
ATC-3A HV-1, 2, 3 FLOW LAYOUT
ATC-3B HWS SEQUENCE OF OPERATION
ATC-3C HWS HARDWARE SCHEDULE
ATC-3D HWS WIRING DETAILS
ATC-3E HWS POINT TO POINT WIRING PAGE 1
ATC-3F HWS POINT TO POINT WIRING PAGE 2
ATC-4 AHU-1,2,3,4 FLOW LAYOUT
ATC-4A AHU-1,2,3,4 SEQUENCE OF OPERATION
ATC-4B AHU-1,2,3,4 HARDWARE SCHEDULE
ATC-4C AHU-1,2,3,4 WIRING DETAILS
ATC-4D AHU-1,2,3,4 POINT TO POINT WIRING PG - 1
ATC-4E AHU-1,2,3,4 POINT TO POINT WIRING PG - 2
ATC-5 FPB COOLING ONLY FLOW LAYOUT
ATC-6 MISC FLOW LAYOUT
CAT-1 PRODUCT LIT CAT
NAME: HWS-CP
DEVICE: FAC2611
MSTP ADD: 4
6N62-0071
Drawing Title
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
NETWORK RISER
ATC-1
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
NETWORK RISER
HUB OR SWITCH
EXISTING NETWORK OF
BRIEANT COURT
HOUSE
PENTHOUSE
NAME: NAE-8
DEVICE: NIE5910
IP ADD: 192.1.1.8
LOCATION: BOILER ROOM
SA BUS
DEVICE: IOM 4711
SA ADD: 4,5,6
(TYPICAL OF 3)
DEVICE: IOM 2721
SA ADD: 7
NAME: GHWPx VFD
DEVICE:VFD
MSTP ADD: 5 TO 6
(TYPICAL OF 2)
NAME: SHWPx VFD
DEVICE:VFD
MSTP ADD: 7 TO 11
(TYPICAL OF 5)
BOILER 3
CONTROL
CABINET
NAME: BOILER 3 CONTROL
CABINET
DEVICE: THIRD PARTY
MSTP ADD: 13
COM
SH
LD
BLK
BLU
IN
BLK
WHT
BLU
OUT
WHT
FC TRUNK TERMINATION
NOTE: GROUND SHIELD
ONLY ONCE, AT THE NAE.
COM
PWR
BLK
BLU
IN
BLK
WHT
BLU
OUT
WHT
SA TRUNK TERMINATION
RED
RED
NOTE: GROUND SHIELD
ONLY ONCE, AT THE FEU.
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
ADS
120 VAC
120 VAC
UPS
NAME: CH-1-CP
DEVICE: FAC2611
MSTP ADD: 37
SA BUS
DEVICE: IOM 4711
SA ADD: 4
120 VAC
NAME: CP-x VFD
DEVICE:VFD
MSTP ADD: 16 TO 17
(TYPICAL OF 2)
NAME: CWPx VFD
DEVICE:VFD
MSTP ADD: 31 TO 33
(TYPICAL OF 3)
NAME: DTGPx VFD
DEVICE:VFD
MSTP ADD: 28 TO 30
(TYPICAL OF 3)
NAME: BTU METER
DEVICE: BTU METER
MSTP ADD: 26 TO 27
(TYPICAL OF 2)
DEVICE: IOM 4711
SA ADD: 7
DEVICE: IOM 2721
SA ADD: 5
DEVICE: IOM 2721
SA ADD: 6
FC BUS
MSTP TRUNK 1
EOL
ROOF
DEVICE: IOM 2721
SA ADD: 8
BILL OF MATERIALS
Designation Qty Part Number Description
Field Devices:
REPEATER1 1 4683-TTM-3F RS485 RPT,N2,MS/TP,24VAC
Panel Devices:
NIE 1 PAG200001AC0 PNL, NIE5510-3, 20X24
NIE-UPS 1 UPS_PC UNINTERRUPTIBLE POWER SUPPLY
WIRING LEGEND
FC BUS – 22 AWG STRANDED, 3-WIRE
TWISTED, SHIELDED CABLE
SA BUS – 22 AWG STRANDED, 4-WIRE,
2-TWISTED PAIR, SHIELDED CABLE
N2 BUS –
ETHERNET CABLE
MODBUS IP -
BOILER 2
CONTROL
CABINET
NAME: BOILER 2 CONTROL
CABINET
DEVICE: THIRD PARTY
MSTP ADD: 12
CHILLER-1
NAME: CHILLER-1
DEVICE: THIRD PARTY
MSTP ADD: 36
NAME: HV-1 VFD
DEVICE:VFD
MSTP ADD: 14
NAME: EF-1 VFD
DEVICE:VFD
MSTP ADD: 15
NAME: AHU-x-CP
DEVICE: FAC2611
MSTP ADD: 22 TO 25
(TYPICAL OF 4)
SA BUS
120 VAC
DEVICE: IOM 2721
SA ADD: 4
DEVICE: IOM 4711
SA ADD: 5,6
(TYPICAL OF 2)
REPEATER-1
(Located in AHU-4 Panel)
AIR COOLED CHILLER
(CH-2)
NAME: CHILLER-2
DEVICE: THIRD PARTY
MSTP ADD: 49
N2 TRUNK
EOL
NAME: TWRx VFD
DEVICE:VFD
N2 ADD: 2 TO 3
(TYPICAL OF 2)
NAME: DTGP4 VFD
DEVICE:VFD
N2 ADD: 34 Name: FPB-2-x device: VMA-1630
N2 ADD: 29 TO 34
(TYPICAL OF 6)
TO OTHER
N2 DEVICES
NAME: NAE-3
DEVICE: NAE4510
IP ADD: 192.1.1.3
LOCATION: 2ND FLOOR
TELEPHONE ROOM 206
2ND FLOOR
Name: FPB-3-x device: VMA-1630
N2 ADD: 26 TO 29
(TYPICAL OF 4)
TO OTHER
N2 DEVICES
NAME: NAE-4
DEVICE: NAE4510
IP ADD: 192.1.1.4
LOCATION: 3RD FLOOR
TELEPHONE ROOM 306
3RD FLOOR
FOURTH FLOOR
PENTHOUSE
SIXTH FLOOR
FIFTH FLOOR
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
GROUND FLOOR
6N62-0071
Drawing Title
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532
Phone: 914-275-2932
REFERENCE DRAWING
NETWORK RISER A
ATC-1A
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
NAME: NAE-7
DEVICE: NAE4510
IP ADD: 192.1.1.7
LOCATION: 6TH FLOOR
TELEPHONE ROOM 606
NAME: NAE-6
DEVICE: NAE4510
IP ADD: 192.1.1.6
LOCATION: 5TH FLOOR
TELEPHONE ROOM 506
NAME: NAE-5
DEVICE: NAE4510
IP ADD: 192.1.1.5
LOCATION: 4TH FLOOR
TELEPHONE ROOM 406
NAME: NAE-4
DEVICE: NAE4510
IP ADD: 192.1.1.4
LOCATION: 3RD FLOOR
TELEPHONE ROOM 306
NAME: NAE-3
DEVICE: NAE4510
IP ADD: 192.1.1.3
LOCATION: 2ND FLOOR
TELEPHONE ROOM 206
NAME: NAE-2
DEVICE: NAE4510
IP ADD: 192.1.1.2
LOCATION: 1ST FLOOR
TELEPHONE ROOM 106
NAME: NAE-1
DEVICE: NAE4510
IP ADD: 192.1.1.1
LOCATION: GROUND FLOOR
UPS ROOM
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING 16 PORT NETWORK HUB
LOCATION: TELEPHONE ROOM 406
HUB OR SWITCH
NAME: NAE-9
DEVICE: NAE5510
IP ADD: 192.1.1.9
LOCATION: PENTHOUSE MER
EXISTING
HUB OR SWITCH
NAME: NAE-8
DEVICE: NAE5510
IP ADD: 192.1.1.8
LOCATION: PENTHOUSE MER
NAME: OWS
DEVICE: METASYS OPERATOR WORKSTATION
IP ADD: 192.1.1.100
LOCATION: MAINTENANCE OFFICE
NAME: ADX
DEVICE: ADS METASYS SERVER /
OPERATOR WORKSTATION
IP ADD: 192.1.1.10
LOCATION: PENTHOUSE MER
CHWS
TO
AHU’S
CHWR
FROM
AHU’S
HL
CHW-DP
6N62-0071
Drawing Title
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
CH-1 & CH-2 FLOW LAYOUT
ATC-2
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
CHILLER 1
(CH-1)
COND
EVAPCOMP
CH-1 & CH-2 FLOW LAYOUT
SHARED GLOBALLY
LOCATED ON THE NORTH
SIDE OF THE BUILDING
OA-T
OA-H
NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.
NOTE: GREEN COLORED DEVICES ARE PROVIDED BY TRANE.
CWP2-DPS
CWP1-DPS
CWP3-DPS
CWP-3
CWP-2
CWP-1
CWP1-C
CWP1-S
CWP1 VFD
CWP1-O
CWP2-C
CWP2-S
CWP2 VFD
CWP2-O
CWP3-C
CWP3-S
CWP3 VFD
CWP3-O
CWL-T
CHWP-1
CHWP-2
CHWP-3
CHWP1-C
CHWP1-S
CHWP1 VFD
CHWP1-O
CHWP2-C
CHWP2-S
CHWP2 VFD
CHWP2-O
CHWP3-C
CHWP3-S
CHWP3 VFD
CHWP3-O
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
AS-1
NO
CWBYPV-O
EXPANSION
TANK
AIR ELIMATOR W/
BACKFLOW PREVENTION
CHEMICAL
FEED
PANEL
CT-2CT-1
NC
DRAIN
DRAIN
CT2CWS-T
EPB-S
(TYPICAL OF 2)
(EMERGENCY PUSH BUTTON)
LOCATED AT ENTRANCE OF PENTHOUSE
WIRED TO
CH-1 & CH-2 PANEL
CT1-C
CT1-S
CT-1 VFD
CT1-O
CT2-C
CT2-S
CT-2 VFD
CT2-O
CHW-F
24VAC
I/P PWR
Over BACnet MSTP
CHILLER 1
CONTROL
CABINET
CH1-EN
CH1-S
AIR COOLED CHILLER (CH-2)
CHWP-4
NC
C H
W
IS
O V
-C C
H W
IS
O
V
-SNC
C W
IS
O
V -C
C W
IS
O
V -S
CWE-T
CHWE-T
C H
W L -T
NOTE: GRAY COLORED DEVICES ARE PROVIDED BY MECHANICAL CONTRACTOR.
REFER DRAWING NUMBER ATC-2A FOR BOM
CH1-A
CHWR-T
CHWS-T
A
B
CONTINUE ON
DRAWING
ATC-2A
BTU
METER
FILTER FEEDER
N
C CHWBYPV-O
REV-1 11/02/20161
REV-2 1/09/20172
CT1CWS-T
6N62-0071
Drawing Title
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
AIR COOLED CH-2 FLOW LAYOUT
ATC-2A
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.
NOTE: GREEN COLORED DEVICES ARE PROVIDED BY TRANE.
AIR COOLED CH-2 FLOW LAYOUT
BILL OF MATERIALS
Designation Qty Part Number Description
Field Devices:
BTU METER 2 BTU-ST-INSTL34 SYS-10 STD WL CS 0.75-42"
2 SYSTEM-10-BAC BTU METER, BACNET
CH1-EN 1 RH2B-ULAC24V DPDT,10A,HC=24 VAC,W/LED
1 SH2B-05 DPDT RELAY BASE FOR RH2B
CHW-F 1 F-3500 INSERTION MAG METER
1 F-STD-INSTL1 INSTALL KIT, STD, WELDED
CH2CHWR-F 1 F-1210 FLOW METER, DUAL TURBINE, ANA OUT
1 F-STD-INSTL1 INSTALL KIT, STD, WELDED
CHWISOV-C 1 RIBU1C SPDT,10A,HC=10-30 VAC/DC,W/LED
CHWPx-C,-S 4 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY
CHWR-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT
1 TE-631AM-2 WELL TEMP SEN 6" 1K NI
CHWS-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT
1 TE-631AM-2 WELL TEMP SEN 6" 1K NI
CTx-C,-S 2 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY
CTxVLV-C 2 RIBU1C SPDT,10A,HC=10-30 VAC/DC,W/LED
CW-DP 1 DPT2301-050D PRESS SENS,DP,0-50 PSI,MA,0.25%
CW-F 1 F-3500 INSERTION MAG METER
1 F-STD-INSTL1 INSTALL KIT, STD, WELDED
CWISOV-C 1 RIBU1C SPDT,10A,HC=10-30 VAC/DC,W/LED
CWPx-C,-S 3 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY
CWR-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT
1 TE-631AM-2 WELL TEMP SEN 6" 1K NI
CWS-T 1 TE-6300W-102 T-WELL 6" SS DIRECT MNT
1 TE-631AM-2 WELL TEMP SEN 6" 1K NI
EPBx-S 4 PILNCCB N/C CONTACT BLOCK
2 PILNOCB N/O CONTACT BLOCK
2 ST120SL-N1-BS PUSH PULL STA N1 SURFACE
PULL RESET BOIL SHUT-DOWN
ISOVS-C
ISOVS-S
ISOVR-C
ISOVR-S
COMP
EVAP
CH-2
CONTROL
CABINET
CH-2-C
CH2CHW-FCH2WR-T
CH2WS-T
AS-1 A
B
CONTINUE ON
DRAWING ATC-2
HEAT TRACING ON ALL
EXPOSED CHW LINES
ON ROOF
CHWP4-C
CHWP4-S
CHWP4 VFD
CHWP4-O
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
CH-1 & CH-2 SEQUENCE OF
OPERATION
ATC-2B
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
CH-1 & CH-2 SEQUENCE OF OPERATION
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
CHILLER CONTROL
A. ON SELECTED CHILLER OPEN ANY ISOLATION VALVES (CHWISOV-C OR CWISOV-C).
B. ON THE COOLING TOWERS CONFIRM CHILLER CW ISOLATION VALVES ARE OPEN. WHETHER ONE OR TWO CW PUMPS (CWPx-C) ARE OPERATING, BOTH TOWER CELLS ARE ENABLED (CTx-C) AND FANS ARE CONTROLLED TO THE SAME SPEED.
C. START SYSTEM CHILLED WATER (CHWPx-C) AND CONDENSER WATER PUMPS (CWPx-C) ON LOW SPEED
(ADJ.).
D. HAVE INITIAL CHILLED WATER SETPOINT AT 48 DEG. F; ALLOW CHILLER ON-BOARD CONTROLS TO RAMP
UP CHILLER AS NECESSARY TO MEET CONDITIONS. MAKE SURE PUMPS ARE MAINTAINING LOW FLOW AS A
MINIMUM.
E. ONCE CHILLERS HAVE STABILIZED CHECK OUTSIDE AIR TEMPERATURE (OA-T) FOR RESET OF CHWS
TEMPERATURE, MAINTAIN ΔT AT DESIGN OF CHILLER, E.G. 10 DEG. F, 12 DEG. F, ETC., ACROSS CHWS AND
CHWR TEMPERATURE.
F. HAVE CHW PUMPS (CHWPx-O) RAMP UP/DOWN AS NECESSARY TO MAINTAIN DESIGN ΔT ACROSS THE CHILLERS.
G. HAVE CHILLED WATER PLANT BY-PASS VALVE (CHWBYPV-O) CLOSED ON INITIAL STARTUP, AS THE SYSTEM RAMPS UP IF THERE IS A LOW FLOW SITUATION THAT CAN’T BE CORRECTED BY ADDING SPEED
TO THE CHW PUMPS (CHWPx-O) [E.G. EXCEEDING DP SETPOINT AND PUMPS AT MINIMUM SPEED] THEN THE BY-PASS (CHWBYPV-O) WILL BE MODULATED OPEN TO MAINTAIN LOW FLOW THROUGH CHILLER; ONCE SYSTEM HAS STABILIZED, BY-PASS VALVE (CHWBYPV-O) WILL MODULATE CLOSED AND USE CHW PUMPS TO MAINTAIN LOW FLOW USING BUILDING CHW SYSTEM’S DIFFERENTIAL PRESSURE WITH THE
DP SETPOINT BEING RESET BY THE AHU’S WORSE CASE VALVE POSITION.
H. CHW PUMPS (CHWPx-C) SHOULD BE STAGED AS A FUNCTION OF CHW FLOW RATIO (CHWFR = ACTUAL FLOW DIVIDED BY TOTAL PLANT DESIGN FLOW) AT A STAGING POINT OF 32%, I.E., ONE PUMP SHOULD
OPERATE WHEN THE CHWFR IS BELOW 47% AND TWO PUMPS SHOULD OPERATE WHEN CHWFR IS ABOVE 47%, WITH A TIME DELAY TO PREVENT SHORT CYCLING. THE 32% OPTIMUM STAGING POINT WILL BE RESET UPWARDS AS THE DP SETPOINT IS. THE RATE AND MAXIMUM STAGE UP % WILL BE DETERMINED DURING BALANCING AND FINALIZED DURING COMMISSIONING.
I. CHILLERS ARE MORE EFFICIENT AT HIGHER LEAVING WATER TEMPERATURES SO, IN GENERAL, OPTIMUM EFFICIENCY IS ACHIEVED WHEN THE CHILLED WATER SUPPLY TEMPERATURE (CHWS-T) SETPOINT IS AS HIGH AS POSSIBLE. WHERE ALL ZONES ARE CONTROLLED BY THE BMS, THE BEST RESET STRATEGY IS BASED ON VALVE POSITION WHERE THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT
IS RESET UPWARDS UNTIL THE VALVE CONTROLLING THE COIL THAT REQUIRES THE COLDEST WATER IS WIDE OPEN. THIS STRATEGY ENSURES THAT NO COIL IS STARVED; ALL ARE ABLE TO MAINTAIN THEIR
DESIRED SUPPLY AIR OR SPACE TEMPERATURE SETPOINTS.
NOTE: CONTRARY TO CONVENTIONAL WISDOM, THE IMPACT OF RESET ON THE DEHUMIDIFICATION CAPABILITY OF AIR HANDLERS IS QUITE SMALL AND SHOULD NOT BE A CONCERN. SPACE HUMIDITY IS A FUNCTION OF THE SUPPLY AIR HUMIDITY RATIO, WHICH IN TURN, IS A FUNCTION OF THE COIL LEAVING DRY-BULB TEMPERATURE SETPOINT. REGARDLESS OF CHWST, THE AIR LEAVING A WET COOLING COIL IS NEARLY SATURATED; LOWERING CHWST ONLY SLIGHTLY REDUCES SUPPLY AIR HUMIDITY RATIO. AS LONG AS THE SUPPLY AIR TEMPERATURE CAN BE MAINTAINED AT THE DESIRED SETPOINT, RESETTING CHILLED WATER SUPPLY TEMPERATURE (CHWS-T) WILL NOT
IMPACT SPACE HUMIDITY.
CHILLER STAGING:
CHILLERS WILL BE STAGED MANUALLY VIA A KIRK KEY AND LOCKING SWITCH.
COOLING TOWER CONTROL:
1. INITIAL CHILLER START:
A. UPON RECEIVING CHILLER START COMMAND, COOLING TOWER WILL START AS OUTLINED:
i. CONFIRM CW VALVES ON CHILLER WILL ARE OPEN.
ii. AFTER CONFIRMATION OF VALVES OPEN, START FIRST CONDENSER WATER PUMP ON LOW AND RAMP UP OVER 30 SECONDS TO
CONTROL VALUE AS SENSED BY CONTROLS.
iii. START COOLING TOWER FANS AT LOW AND RAMP UP OVER 30 SECONDS.
2. AFTER CHILLER START-UP:
A. ALLOW SYSTEM TO STABILIZE OVER 5 MINUTE PERIOD AND THEN ALLOW CONTROL SYSTEM TO PROVIDE FOR BEST CONTROL TO
MAINTAIN THE BEST CWRT AS SHOWN IN EQUATION BELOW WITH A MAX OF 90 DEG. F:
CWRT = CHWST + A × PLR + B (1)
(A = –63 + 0.0053 × CDD65 – 0.0087 × WBDD55 + 1.67 × WB + 0.52 × APPROACH – 0.029 × GPM/TON B = 18 – 0.0033 × CDD65 + 0.0053 × WBDD55 – 0.26 × WB + 0.15 × APPROACH – 0.014 × GPM/TON)
THIS SETPOINT MUST BE BOUNDED BY THE MINIMUM CWRT-CHWST DIFFERENCE AT LOW LOAD SPECIFIED BY THE CHILLER
MANUFACTURER.
B. TO OBTAIN THE BEST CWRT STAGE PUMPS ON AS NECESSARY, USE VFD TO RAMP UP TO 100% SPEED AS PUMPS ARE STARTED OVER
30 SECONDS.
i. ALLOW PUMPS TO OPERATE FOR AT LEAST 10 MINUTES (ADJ.) TO PREVENT SHORT CYCLING.
ii. ONCE PUMPS ARE TURNED OFF DUE TO LOAD ALLOW AT LEAST 10 MINUTES (ADJ.) BEFORE PUMP CAN BE RE-STARTED TO PREVENT
SHORT CYCLING.
C. MODULATE BOTH VFDS ON COOLING TOWER FAN TO OBTAIN BEST CWRT.
3. COOLING TOWER SHUT DOWN:
A. WHEN CHILLER SYSTEM SHUTDOWN SEQUENCE IS RECEIVED, ALLOW CHILLER TO RUN THROUGH ITS SHUT DOWN PERIOD, TO BE DETERMINED BY CHILLER MANUFACTURER, AND AFTER APPROPRIATE TIME PREFORM THE FOLLOWING:
i. TURN OFF COOLING TOWER FAN(S).
ii. TURN OFF CONDENSER WATER PUMP(S).
iii. CLOSE ISOLATION VALVES AFTER 30 SECONDS TURNING PUMPS OFF.
CHILLER FAILURE SEQUENCE:
1. IF A FAILURE TO THE WATER COOLED CHILLER IS DETECT THE FOLLOWING WILL TAKE PLACE:
A. TURN COMMAND TO WATER CHILLER TO OFF.
B. TURN COOLING TOWER FANS OFF.
C. ALLOW CHILLED WATER PUMPS AND CONDENSER WATER PUMPS TO RUN FOR 10 MINUTES (ADJ.) BEFORE SHUTTING THEM DOWN.
D. AFTER PUMPS HAVE BEEN OFF FOR 30 SECONDS CLOSE ISOLATION VALVES IN THE CHILLED WATER LINE TO WATER COOLED
CHILLER AND CONDENSER WATER ISOLATION VALVE.
2. PLANT OPERATOR IS TO TRANSFER POWER BY TURNING THE KIRK KEY AND LOCKING POWER TO THE AIR COOLED CHILLER. THIS CAN
OCCUR (IMMEDIATELY OR AFTER 10 MINUTES) AFTER FAILURE TO WATER COOLED CHILLER.
3. PLANT OPERATOR WILL USE THE BAS TO TURN THE AIR COOLED CHILLER SYSTEM ON BY PUSHING THE “AIR COOLED CHILLER
ENABLE” BUTTON ON THE SCREEN. BY PUSHING THIS BUTTON THE FOLLOWING WILL HAPPEN:
A. BOTH CHILLED WATER ISOLATION VALVES WILL OPEN; AFTER FULLY OPEN AND CONFIRMED BY STATUS SWITCH ON VALVE THE AIR COOLED CHILLER CHILLED WATER PUMP WILL SOFT START AND RAMP UP TO SPEED OVER A 30 SECOND (ADJ.) PERIOD.
B. ONCE FLOW HAS BEEN ESTABLISHED AIR COOLED CHILLER WILL START AND OPERATE AT CHILLED WATER SUPPLY SETPOINT OF
45°F (ADJ.).
WHEN SWITCHING BACK TO WATER COOLED CHILLER:
1. PUSH “AIR COOLED CHILLER DISABLE” BUTTON.
A. AIR COOLED CHILLER WILL SHUT DOWN.
B. CHILLED WATER PUMP WILL RUN FOR 10 MINUTES (ADJ.) AFTER CHILLER IS SHUT DOWN.
C. ISOLATION VALVES WILL CLOSE AFTER PUMPS HAVE BEEN OFF FOR 30 SECONDS (ADJ.).
2. PLANT OPERATOR IS TO TRANSFER POWER BY TURNING THE KIRK KEY AND LOCKING POWER TO THE WATER COOLED CHILLER AFTER AIR COOLED CHILLER IS SHUT DOWN COMPLETELY, WHICH SHOULD BE AFTER AIR COOLED CHILLER PUMP IS OFF.
3. PLANT OPERATOR WILL USE THE BAS TO START THE WATER COOLED CHILLER BY PUSHING THE “WATER COOLED CHILLER ENABLE”
BUTTON. BY PUSHING THE BUTTON THE FOLLOWING WILL HAPPEN:
A. ISOLATION VALVES ON THE CONDENSER AND CHILLED WATER SIDE WILL FULLY OPEN; AFTER CONFIRMED STATUS OF VALVE OPEN CHILLED WATER PUMP(S) WILL SOFT START AND RAMP UP TO SPEED OVER A 30 SECOND (ADJ.) PERIOD.
B. COOLING TOWER FANS WILL START AS NEEDED AND RAMP UP OVER A 30 SECOND (ADJ.) PERIOD.
C. RESUME WITH NORMAL SEQUENCE FOR WATER COOLED CHILLER OPERATION.
APPROACH DESIGN TOWER LEAVING WATER TEMPERATURE MINUS WB, °F
CHWFR CHILLED WATER FLOW RATIO, ACTUAL FLOW DIVIDED BY TOTAL PLANT DESIGN FLOW
CHWST CHILLED WATER SUPPLY TEMPERATURE (LEAVING EVAPORATOR TEMPERATURE), °F
CWFR CONDENSER WATER FLOW RATIO, ACTUAL FLOW DIVIDED BY TOTAL PLANT DESIGN FLOW
CWRT CONDENSER WATER RETURN TEMPERATURE (LEAVING CONDENSER WATER TEMPERATURE), °F
CDD65 COOLING DEGREE-DAYS BASE 65°F
DP DIFFERENTIAL PRESSURE, FEET H2O
KW/TON CHILLER EFFICIENCY AT AHRI CONDITIONS, KW/TON
ΔT TEMPERATURE DIFFERENCE, °F
GPM/HP TOWER EFFICIENCY PER ASHRAE STANDARD 90.1
IPLV INTEGRATED PART LOAD VALUE PER AHRI 550/590, KW/TON
NPLV NON-STANDARD PART LOAD VALUE PER AHRI 550/590, KW/TON
RANGE DESIGN TOWER ENTERING MINUS LEAVING WATER TEMPERATURE, °F
PLR PLANT PART LOAD RATIO, CURRENT LOAD DIVIDED BY TOTAL PLANT DESIGN CAPACITY
TOPP THEORETICAL OPTIMUM PLANT PERFORMANCE
WB DESIGN WET-BULB TEMPERATURE, ASHRAE 1%, °F
WBDD55 WET-BULB COOLING DEGREE-DAYS BASE 55°F
REV-1 11/02/20161
REV-3 3/03/20173
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
CH-1 HARDWARE SCHEDULE PG 1
ATC-2C
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
Electrician/Fitter Range Controller Information Field Device
Tag
Point Type System
Name Object Name Expanded ID Lo
H i
Controller
Details
Trunk
Type Trunk Nbr
Trunk
Addr.
Cable Destination
Bay/Terminal
Module
Type Termination Out Panel Panel Location
Reference
Drawing Cable Number
Wiring
/Tubing Termination In Device Termination Out Location
Wiring
/Tubing Termination In Device Location
Ref Detail
Shape
CH-1 FAC 2611 CH-CP ROOF M-401
CH-1 FAC 2611 MS/TP * * CH-CP ROOF M-401
UI IN-1 CH-1 CWS-T Condenser Water Supply Temperature FAC 2611 MS/TP * * UI IN-1 IN1, ICOM1 CH-CP ROOF M-401 2-CP-4-UI IN-1 2/22 2-Wire TE F131
UI IN-2 CH-1 CWR-T Condenser Water Return Temperature FAC 2611 MS/TP * * UI IN-2 IN2, ICOM2 CH-CP ROOF M-401 2-CP-4-UI IN-1 2/22 2-Wire TE F131
UI IN-3 CH-1 CHWS-T Chilled Water Supply Temperature FAC 2611 MS/TP * * UI IN-3 IN3, ICOM3 CH-CP ROOF M-401 2-CP-4-UI IN-3 2/22 2-Wire TE F131
UI IN-4 CH-1 CHWR-T Chilled Water Return Temperature FAC 2611 MS/TP * * UI IN-4 IN4, ICOM4 CH-CP ROOF M-401 2-CP-4-UI IN-4 2/22 2-Wire TE F131
UI IN-5 CH-1 CHW-DP Chilled Water Differential Pressure FAC 2611 MS/TP * * UI IN-5 IN5, +15V CH-CP ROOF M-401 2-CP-4-UI IN-5 2/22 -, + DPT2xxx (mA) F106
UI IN-6 CH-1 CW-DP Cond Water Differential Pressure FAC 2611 MS/TP * * UI IN-6 IN6, +15V CH-CP ROOF M-401 2-CP-4-UI IN-6 2/22 -, + DPT2xxx (mA) F106
BI IN-7 CH-1 CH1-S Chiller 1 Status FAC 2611 MS/TP * * BI IN-7 IN7, ICOM7 CH-CP ROOF M-401 2-CP-4-BI IN-7 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
BI IN-8 CH-1 CH1-A Chiller 1 Alarm FAC 2611 MS/TP * * BI IN-8 IN8, ICOM8 CH-CP ROOF M-401 2-CP-4-BI IN-8 2/22 See wiring detail Dry Contact F301
BO OUT-1 CH-1 CH1CWISOV-CChiller 1 CW Isolation Valve Command FAC 2611 MS/TP * * BO OUT-1 OUT1, 24V COM CH-CP ROOF M-401 2-CP-4-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-2 CH-1 CH1-EN Chiller 1 Enable FAC 2611 MS/TP * * BO OUT-2 OUT2, 24V COM CH-CP ROOF M-401 2-CP-4-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-3 CH-1 CH1CHWISOV-CChiller 1 CHW Isolation Valve Command FAC 2611 MS/TP * * BO OUT-3 OUT3, 24V COM CH-CP ROOF M-401 2-CP-4-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
CO OUT-4 CH-1 CHWP1-O Primary CHW Pump 1 Output FAC 2611 MS/TP * * CO OUT-4 OUT4, OCOM4 CH-CP ROOF M-401 2-CP-4-CO OUT-4 2/22 See VFD Detail VFD Speed Control (Vdc)
CO OUT-5 CH-1 CHWP2-O Primary CHW Pump 2 Output FAC 2611 MS/TP * * CO OUT-5 OUT5, OCOM5 CH-CP ROOF M-401 2-CP-4-CO OUT-5 2/22 See VFD Detail VFD Speed Control (Vdc)
CO OUT-6 CH-1 CHWP3-O Primary CHW Pump 3 Output FAC 2611 MS/TP * * CO OUT-6 OUT6, OCOM6 CH-CP ROOF M-401 2-CP-4-CO OUT-6 2/22 See VFD Detail VFD Speed Control (Vdc)
CO OUT-7 CH-1 CHWP4-O Primary CHW Pump 4 Output FAC 2611 MS/TP * * CO OUT-7 OUT7, OCOM7 CH-CP ROOF M-401 2-CP-4-CO OUT-7 2/22 See VFD Detail VFD Speed Control (Vdc)
AO OUT-8 CH-1 CHWBYPV-O Chilled Water Bypass Valve Output FAC 2611 MS/TP * * AO OUT-8 OUT8, OCOM8,24VAC, COM CH-CP ROOF M-401 2-CP-4-AO OUT-8 2/22 / 2/18 GRY, BLK/BLK, RED M92xx-GGx-x (Vdc) (Ext Source) F267
AO OUT-9 CH-1 CWBYPV-O Condenser Water Bypass Valve Output FAC 2611 MS/TP * * AO OUT-9 OUT9, OCOM9,24VAC, COM CH-CP ROOF M-401 2-CP-4-AO OUT-9 2/22 / 2/18 GRY, BLK/BLK, RED M92xx-GGx-x (Vdc) (Ext Source) F267
CH-1 IOM 4710 CH-CP ROOF M-401
CH-1 IOM 4710 SA Bus 1 5 CH-CP ROOF M-401
UI IN-1 CH-1 CH1CHW-F Chiller 1 CHW Flow IOM 4710 SA Bus 1 5 UI IN-1 IN1, +15V CH-CP ROOF M-401 4-2-CP-4-UI IN-1 2/22 See wiring detail Current Input (2 Wire) F106
UI IN-2 CH-1 CH2CHW-F Chiller 2 CHW Flow IOM 4710 SA Bus 1 5 UI IN-2 IN2, +15V CH-CP ROOF M-401 4-2-CP-4-UI IN-2 2/22 See wiring detail Current Input (2 Wire) F106
UI IN-3 CH-1 CW-F Condenser Water Flow IOM 4710 SA Bus 1 5 UI IN-3 IN3, +15V CH-CP ROOF M-401 4-2-CP-4-UI IN-3 2/22 See wiring detail Current Input (2 Wire) F106
UI IN-4 CH-1 CWP1-S Condenser Water Pump 1 Status IOM 4710 SA Bus 1 5 UI IN-4 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-4-UI IN-4 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
UI IN-5 CH-1 CWP2-S Condenser Water Pump 2 Status IOM 4710 SA Bus 1 5 UI IN-5 IN5, ICOM5 CH-CP ROOF M-401 4-2-CP-4-UI IN-5 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
UI IN-6 CH-1 CWP3-S Condenser Water Pump 3 Status IOM 4710 SA Bus 1 5 UI IN-6 IN6, ICOM6 CH-CP ROOF M-401 4-2-CP-4-UI IN-6 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
BI IN-7 CH-1 IOM 4710 SA Bus 1 5 BI IN-7 IN7, ICOM7 CH-CP ROOF M-401 4-2-CP-4-BI IN-7
BI IN-8 CH-1 IOM 4710 SA Bus 1 5 BI IN-8 IN8, ICOM8 CH-CP ROOF M-401 4-2-CP-4-BI IN-8
BO OUT-1 CH-1 CWP1-C Condenser Water Pump 1 Command IOM 4710 SA Bus 1 5 BO OUT-1 OUT1, 24V COM CH-CP ROOF M-401 4-2-CP-4-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-2 CH-1 CWP2-C Condenser Water Pump 2 Command IOM 4710 SA Bus 1 5 BO OUT-2 OUT2, 24V COM CH-CP ROOF M-401 4-2-CP-4-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-3 CH-1 CWP3-C Condenser Water Pump 3 Command IOM 4710 SA Bus 1 5 BO OUT-3 OUT3, 24V COM CH-CP ROOF M-401 4-2-CP-4-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
CO OUT-4 CH-1 IOM 4710 SA Bus 1 5 CO OUT-4 OUT4, OCOM4 CH-CP ROOF M-401 4-2-CP-4-CO OUT-4
CO OUT-5 CH-1 IOM 4710 SA Bus 1 5 CO OUT-5 OUT5, OCOM5 CH-CP ROOF M-401 4-2-CP-4-CO OUT-5
CO OUT-6 CH-1 IOM 4710 SA Bus 1 5 CO OUT-6 OUT6, OCOM6 CH-CP ROOF M-401 4-2-CP-4-CO OUT-6
CO OUT-7 CH-1 CWP1-O Condenser Water Pump 1 Output IOM 4710 SA Bus 1 5 CO OUT-7 CH-CP ROOF M-401 4-2-CP-4-CO OUT-7 2/22 See VFD Detail VFD Speed Control (Vdc)
AO OUT-8 CH-1 CWP2-O Condenser Water Pump 2 Output IOM 4710 SA Bus 1 5 AO OUT-8 OUT8, OCOM8 CH-CP ROOF M-401 4-2-CP-4-AO OUT-8 2/22 See VFD Detail VFD Speed Control (Vdc)
AO OUT-9 CH-1 CWP3-O Condenser Water Pump 3 Output IOM 4710 SA Bus 1 5 AO OUT-9 OUT9, OCOM9 CH-CP ROOF M-401 4-2-CP-4-AO OUT-9 2/22 See VFD Detail VFD Speed Control (Vdc)
CH-1 IOM 4710 CH-CP ROOF M-401
CH-1 IOM 4710 SA Bus 1 6 CH-CP ROOF M-401
UI IN-1 CH-1 CT1VIB-A Tower 1 Vibration Alarm IOM 4710 SA Bus 1 6 UI IN-1 IN1, ICOM1 CH-CP ROOF M-401 4-2-CP-5-UI IN-1 2/22 See wiring detail Dry Contact F301
UI IN-2 CH-1 CT2VIB-A Tower 2 Vibration Alarm IOM 4710 SA Bus 1 6 UI IN-2 IN2, ICOM2 CH-CP ROOF M-401 4-2-CP-5-UI IN-2 2/22 See wiring detail Dry Contact F301
UI IN-3 CH-1 IOM 4710 SA Bus 1 6 UI IN-3 IN3, ICOM3 CH-CP ROOF M-401 4-2-CP-5-UI IN-3
UI IN-4 CH-1 IOM 4710 SA Bus 1 6 UI IN-4 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-5-UI IN-4
UI IN-5 CH-1 CT1-S Tower 1 Status IOM 4710 SA Bus 1 6 UI IN-5 IN5, +15V CH-CP ROOF M-401 4-2-CP-5-UI IN-5 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
UI IN-6 CH-1 CT1ISOV-S Tower 1 Isolation Valve Status IOM 4710 SA Bus 1 6 UI IN-6 IN6, +15V CH-CP ROOF M-401 4-2-CP-5-UI IN-6 2/22 See wiring detail Dry Contact F301
BI IN-7 CH-1 CT2-S Tower 2 Status IOM 4710 SA Bus 1 6 BI IN-7 IN7, +15V CH-CP ROOF M-401 4-2-CP-5-BI IN-7 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
BI IN-8 CH-1 CT2ISOV-S Tower 2 Isolation Valve Status IOM 4710 SA Bus 1 6 BI IN-8 IN8, +15V CH-CP ROOF M-401 4-2-CP-5-BI IN-8 2/22 See wiring detail Dry Contact F301
BO OUT-1 CH-1 CT1-C Tower 1 Command IOM 4710 SA Bus 1 6 BO OUT-1 OUT1, OCOM1 CH-CP ROOF M-401 4-2-CP-5-BO OUT-1 2/22 See VFD Detail VFD Speed Control (Vdc)
BO OUT-2 CH-1 CT2-C Tower 2 Command IOM 4710 SA Bus 1 6 BO OUT-2 OUT2, OCOM2 CH-CP ROOF M-401 4-2-CP-5-BO OUT-2 2/22 See VFD Detail VFD Speed Control (Vdc)
BO OUT-3 CH-1 CH2-EN Chiller 2 Enable IOM 4710 SA Bus 1 6 BO OUT-3 CH-CP ROOF M-401 4-2-CP-5-BO OUT-3 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501
CO OUT-4 CH-1 CT1ISOV-C Tower 1 Isolation Valve Command IOM 4710 SA Bus 1 6 CO OUT-4 CH-CP ROOF M-401 4-2-CP-5-CO OUT-4 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501
CO OUT-5 CH-1 CT2ISOV-C Tower 2 Isolation Valve Command IOM 4710 SA Bus 1 6 CO OUT-5 IN1, +15V CH-CP ROOF M-401 4-2-CP-5-CO OUT-5 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501
CO OUT-6 CH-1 IOM 4710 SA Bus 1 6 CO OUT-6 IN2, +15V CH-CP ROOF M-401 4-2-CP-5-CO OUT-6
CO OUT-7 CH-1 IOM 4710 SA Bus 1 6 CO OUT-7 IN3, +15V CH-CP ROOF M-401 4-2-CP-5-CO OUT-7
AO OUT-8 CH-1 CT1-O Tower 1 Output IOM 4710 SA Bus 1 6 AO OUT-8 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-5-AO OUT-8 2/22 See VFD Detail VFD Speed Control (Vdc)
AO OUT-9 CH-1 CT2-O Tower 2 Output IOM 4710 SA Bus 1 6 AO OUT-9 IN5, ICOM5 CH-CP ROOF M-401 4-2-CP-5-AO OUT-9 2/22 See VFD Detail VFD Speed Control (Vdc) F301
CH-1 IOM 3731 IN6, ICOM6 CH-CP ROOF M-401
CH-1 IOM 3731 SA Bus 1 4 IN7, ICOM7 CH-CP ROOF M-401
BI IN-1 CH-1 CH1CHWISOV-SChiller 1 CHW Isolation Valve Status IOM 3731 SA Bus 1 4 BI IN-1 IN8, ICOM8 CH-CP ROOF M-401 4-2-CP-6-BI IN-1 2/22 See wiring detail Dry Contact F301
BI IN-2 CH-1 CH1CWISOV-SChiller 1 CW Isolation Valve Status IOM 3731 SA Bus 1 4 BI IN-2 OUT1, OCOM1 CH-CP ROOF M-401 4-2-CP-6-BI IN-2 2/22 See wiring detail Dry Contact F301
BI IN-3 CH-1 CHWP1-S Primary CHW Pump 1 Status IOM 3731 SA Bus 1 4 BI IN-3 OUT2, OCOM2 CH-CP ROOF M-401 4-2-CP-6-BI IN-3 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
BI IN-4 CH-1 CHWP2-S Primary CHW Pump 2 Status IOM 3731 SA Bus 1 4 BI IN-4 CH-CP ROOF M-401 4-2-CP-6-BI IN-4 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
BI IN-5 CH-1 CHWP3-S Primary CHW Pump 3 Status IOM 3731 SA Bus 1 4 BI IN-5 CH-CP ROOF M-401 4-2-CP-6-BI IN-5 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
BI IN-6 CH-1 CHWP4-S Primary CHW Pump 4 Status IOM 3731 SA Bus 1 4 BI IN-6 IN1, +15V CH-CP ROOF M-401 4-2-CP-6-BI IN-6 2/22 OUT, COM Current Relay Motor Lead Motor Lead See wiring detail Motor Status (Contact) F301
BI IN-7 CH-1 CH2HT-A Chiller 2 Heat Trace Alarm IOM 3731 SA Bus 1 4 BI IN-7 IN2, ICOM2 CH-CP ROOF M-401 4-2-CP-6-BI IN-7 2/22 See wiring detail Dry Contact F301
BI IN-8 CH-1 EPB-S Emergency Shutdown IOM 3731 SA Bus 1 4 BI IN-8 IN3, +15V CH-CP ROOF M-401 4-2-CP-6-BI IN-8 2/22 See wiring detail Dry Contact F301
BO OUT-1 CH-1 CHWP1-C Primary CHW Pump 1 Command IOM 3731 SA Bus 1 4 BO OUT-1 IN4, ICOM4 CH-CP ROOF M-401 4-2-CP-6-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-2 CH-1 CHWP2-C Primary CHW Pump 2 Command IOM 3731 SA Bus 1 4 BO OUT-2 IN5, ICOM5 CH-CP ROOF M-401 4-2-CP-6-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-3 CH-1 CHWP3-C Primary CHW Pump 3 Command IOM 3731 SA Bus 1 4 BO OUT-3 IN6, ICOM6 CH-CP ROOF M-401 4-2-CP-6-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-4 CH-1 CHWP4-C Primary CHW Pump 4 Command IOM 3731 SA Bus 1 4 BO OUT-4 IN7, ICOM7 CH-CP ROOF M-401 4-2-CP-6-BO OUT-4 2/22 COIL-,COIL+ Relay COM, NO 2/14 See wiring detail VFD (w/o Safety) (Sw Hi, EXT) F1043
BO OUT-5 CH-1 IOM 3731 SA Bus 1 4 BO OUT-5 IN8, ICOM8 CH-CP ROOF M-401 4-2-CP-6-BO OUT-5
BO OUT-6 CH-1 IOM 3731 SA Bus 1 4 BO OUT-6 OUT1, 24V COM CH-CP ROOF M-401 4-2-CP-6-BO OUT-6
BO OUT-7 CH-1 IOM 3731 SA Bus 1 4 BO OUT-7 OUT2, 24V COM CH-CP ROOF M-401 4-2-CP-6-BO OUT-7
BO OUT-8 CH-1 REFHORN-C Refrigerant Horn Command IOM 3731 SA Bus 1 4 BO OUT-8 OUT3, 24V COM CH-CP ROOF M-401 4-2-CP-6-BO OUT-8 2/22 COIL+,COIL- Relay COM,NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501
NOTE: (*) PLEASE REFER RISER DRAWING FOR TRUNK NUMBER & TRUNK ADDRESS.
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
CH-1 WIRING DETAILS
ATC-2D
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
DETAIL F106
FIELD
DEVICE
Output
+ VDC +15 V
CURRENT INPUT -
INTERNAL SOURCE (2 Wire)
IN#
CONTROLLER
DETAIL F131 TEMPERATURE SENSOR INPUT
RTD
Temperature Element
IN#
ICOM#
CONTROLLER
DETAIL F267
24 VAC
H
N
CONTROLLER
OUT#
OCOM#
2 Red
1 Black
3 Gray
Side A:
Mounted away from damper
To change the spring return direction to CW, mount the actuator to the damper shaft so that Side B of the actuator is away from the damper. With power applied, the actuator now drives CCW from the 0° position, and spring returns CW.
Counterclockwise (CCW) Spring Return Direction – Clockwise (CW) Powered Operation
0-10VDC OUTPUT to M92xx-GGx and HGx or VA92xx-GGx and HGx
CONTROLLER
OUT#
OCOM#
Counterclockwise (CCW) Spring Return Direction – Clockwise (CW) Powered Operation
2 Red
1 Black
3 Gray
Side A:
Mounted away from damper
2 Red
1 Black
3 Gray
Side A:
Mounted away from damper
4 Orange
Master-Slave Application
24 VAC
H
N
DETAIL F301 BINARY INPUT (DRY CONTACT)
FIELD DEVICE
DRY CONTACT
(N.O. or N.C. as required)
CONTROLLER
DETAIL F365
N.C.
N.O.
Switch S1
N.O.
N.C.
Switch S2
Factory Set at
20 Degrees
Factory Set at 70 Degrees
Connect to switch contact as required
Blk/Red
Blk/Gry
Blk/Blu
Wht/Red
Wht/Blu
Wht/Gry
BINARY INPUT from M92xx-xxx-x, and VA92xx-xxx-x
ICOM#
IN#
CONTROLLER
DETAIL F501 24 VAC BINARY OUTPUT
(Switch High, EXT Sourced)
FIELD
DEVICE
CONTROLLER
OUT#
24V Hot
24V Com
OCOM#
SET TRIAC JUMPER
TO EXTERNALLY
SOURCED (EXT)
FOR ASSOCIATED
BINARY OUTPUT(S).
DETAIL F578
Black
Red
ON-OFF CONTROL to M92xx-BGx-x and VA92xx-BGx-x (Switch High, EXT Sourced)
24V Com
OCOM#
M9210-BGx-x
M9220-BGx-x
To change the spring return direction to CW, mount the actuator to the damper shaft so that Side B of the actuator is away from the damper. With power applied, the actuator now drives CCW from the 0° position, and spring returns CW.
Side A
24V Hot
24V Com
SET TRIAC JUMPER TO EXTERNALLY
SOURCED (EXT) FOR ASSOCIATED
BINARY OUTPUT(S).
Black
Red
M9208-BGx-x
Side A
SET TRIAC JUMPER TO EXTERNALLY
SOURCED (EXT) FOR ASSOCIATED
BINARY OUTPUT(S).
M9203-BGx-x
DETAIL F901 24 VAC TRIAC OUTPUT
(Switch High, EXT Sourced)
FIELD
DEVICE
24V Com
OCOM#
DETAIL F1043 VFD without Safeties Wiring
POWER
TO VFD
SPEED INPUT
START/STOP
FIELD VERIFY
TERMINATIONS
Current Relay
Coil
24V HOT
24V COM
VFD
COMMAND
Contact
FAULT OR ALARM
STATUS
(If used)
IF A CURRENT RELAY IS PROVIDED
FOR FAN STATUS SENSE THE
POWER OF THE VFD INSTEAD OF
THE LOAD SIDE OF THE MOTOR.
SPEED
DRIVE FAULT
OUTPUT
IF WIRING TO A BINARY OUTPUT SET THE TRIAC
JUMPER TO EXTERNAL (EXT). IF WIRING TO A
RELAY OUTPUT TERMINAL OUT# = OUT# NO.
O U
T#
V
C
2C
H W
IS
O
V- C
6N62-0071
Drawing Title
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
CH-1 POINT TO POINT WIRING PG 1
ATC-2E
Project Title
NO. REVIS ION-LOCATION ECN DATE BY
Sal es Engineer Project Manager Appli cati on Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Inform ation CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
CH-1 PANEL WIRING DETAILS PAGE 1
124816326412
O N
Address:
SA
P
W R
C O
M
SA BUS
FC BUS
C O
M
SH
LD+1
5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24 VAC
C O
M
FAC2611-0
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
O N1 2 3 4 5 6
CURRENT LOOP
SA
TO
S A
D
EV
IC
E
TO
N
EX
T
FC
D
EV
IC
E M
S/
TP
M S/
TP
FR
O M
L A
ST
F
C D
EV
IC
E
IC
O
M
IN
1-
S
O U
T#
1C
W
IS
O V
-C
O U
T#
1-
EN
O U
T#
1C
H W
IS
O
V- C
V
C O
M
0V A
C
PO
W
ER
IC
M
1-
A
HOT
COM
PS-1 GROUND
120VAC
A
B
IN
+1 5V
4-20 mA
R
EF
R
IG
-A
IN
C
M
C H
W -F
IN
C
C
-F
124816326412
O N
Address:
See Room Schedule
SA
FC
IN
IC
O
M
IN
IC
O
M
IN
IN
IC
O
M
IN
IC
O
M
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
BINARY
O U
T1 O
C O
M
O U
T2 O
C O
M
BINARY
H O
T
24V
C O
M
IOM3731-0
FC EOL
IN SA
PW
R
C O
M
+ - C
O M
SH
LD
SA/FC BUS
O U
T3 O
C O
M
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
TRIAC JUMPERS
OUT1
INT
EXT
OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
C O
M
IC
O
M
IN
C H
2C H
W
IS
O V-
M
D
TG
P1
-S
M
P2
M
P3
M
P4
U
T#
P1
-C
O U
T#
P2
-C
O U
T#
P3
-C
O U
T#
P4
-C
O U
T#
2-
EN
TO
N
EX
T
SA
D
EV
IC
E
SA SA
FR
O
M L
A
ST
S A
D
EV
IC
E
124816326412
O
Address:
SA
FC
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
IOM4711
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
C O
M
+ - C
O M
SH
LD
SA/FC BUS
C O
M
TO
N
EX
T
SA
D
EV
IC
E
SA SA
FR
O
M L
A
ST
S A
D
EV
IC
E
IN
C
0-10V
H
2C H
-F
1K Ni
M
IN
C H
2C H
W L-
T
M
IN
C H
2C H
W E
-T
IN
C
H
W R
-P
IN
C
H
W
-P
C
O M
O U
T#
W
BY
PV
-O
O C
O M
O
P1 -O
O C
O M
O
P2 -O
O C
O M
O
P3 -O
O C
O M
O
P4 -O
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
CH-1 POINT TO POINT WIRING PG 2
ATC-2F
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
HOT
COM
PS-1
GROUND
120VAC
CH-1 PANEL WIRING DETAILS PAGE 2
12481
O
V
IN
IC
O
M
IN
IC
O
M
V
IN
IC
O
M
IN
IC
O
M
V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
BINARY
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
IOM4711
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
P
R
C O
M
+ - C
O M
S H
L D
SA/FC BUS
IC
O
M
IN
C T
-S
O U
T
V
C T
-C
O U
T
V
C T
-C
V
C O
M
IC
O
M
IN
C T
-S
T O
N E
X T
S A
D E
V
IC
E S
A
S A
F R
O M
L A
S T
S A
D E
V
IC
E
IC
O
M
V
IB
-A
IC
O
M
IN
C T
V
IB
-A
O C
O M
O U
-O
O C
O M
O U
T
C T
12481
O
V
IN
IC
O
M
IN
IC
O
M
V
IN
IC
O
M
IN
IC
O
M
V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
BINARY
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
IOM4711
O U
T
O C
O M
O U
T
O C
O M
O U
T
O C
O M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
R
C O
M
+ - C
O M
S H
L
SA/FC BUS
M
P
-S
V
C O
M
IC
O
M
P
-S
IC
O
M
P
-S
T O
N E
X T
S A
D E
V
IC
E S
A
S A
F R
O M
L A
S T
S A
D E
V
IC
E
M
IN
C T
C
-T
M
IN
C T
C
M
C W
IS
O
V -S
IC
O
M
C
H W
IS
O
V -S
O U
T
P
-C
O U
T
V
C W
P
-C
O U
T
P
-C
O C
O M
O U
P
-O
O C
O M
O U
P
-O
O C
O M
O U
T
C W
P
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
REFRIGERANT EXHAUST FLOW
DIAGRAM
ATC-2G
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
REFRIGERANT EXHAUST FLOW LAYOUT
COMBUSTION OA
VENT OAEA TO ROOF
EF-1
NC
OAD-C
OAD-S
NC
REFRIGERANT
MONITORING PANEL
BMS
TO CHILLERS
PENTHOUSE
COMBDPR-C
COMBDPR-S
BILL OF MATERIALS
Designation Qty Part Number Description
Field Devices:
COMBDPR-C 1 M9220-BAC-3 DAMPER ACTUATOR 20 NM SR
EF1-C,-S 1 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY
OAD-C 1 M9220-BAC-3 DAMPER ACTUATOR 20 NM SR
EF1-C
EF1-S
STARTER
H N120 VAC
OAD-S
COMB-S
EF-1 WIRING DETAILS
EF-C
(SOFT)
OAD
BREAK
GLASS
EMRDMP1-C
EMRDMP2-C
COMBDPR
TO BOILER
PANEL
H N24 VAC
SDR-1
EMERGENCY
SHUTDOWN
SWITCH
BREAKGLASS WIRING DETAILS
TYPICAL OF 4
COMBUSTION AIR
FROM SIDE OF
BUILDING
BLR3-A
BLR2-A
L
HW-DP
AS-1
Drawing Title
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
HWS FLOW LAYOUT
ATC-3
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
HWS FLOW LAYOUT
BOILER 1
BOILER 3
BOILER 2
GHWP-1
GHWP-2
(STAND-BY)
GHWP2-C
GHWP2-S
GHWP2 VFD
GHWP2-O
GHWP1-C
GHWP1-S
GHWP1 VFD
GHWP1-O
CP-1
CP1 VFD
CP-2
CP2 VFD
HWS
FROM HV-1,2 & 3
FROM AHU-1,2,3 & 4TO AHU-1,2,3 & 4
SHWP1-DPS
SHWP2-DPS
SHWP3-DPS
SHWP4-DPS
SHWP-2
SHWP-3
SHWP-4
BP2
BP3
SHWP-1
P4-C P4-S
BP2-C
BP2-S
P4-C P4-S
BP3-C
BP3-S
DECOUPLER
SHWP1-C
SHWP1-S
SHWP1 VFD
SHWP1-O
SHWP2-C
SHWP2-S
SHWP2 VFD
SHWP2-O
SHWP3-C
SHWP3-S
SHWP3 VFD
SHWP3-O
SHWP4-C
SHWP4-S
SHWP4 VFD
SHWP4-O
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
SHWP-5
FILTER FEEDER
RADIATION
(WEST)
RADIATION
(SOUTH)
RADIATION
(NORTH)
RADIATION
(EAST)
AIR SEPARATOR
NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.
BOILER 2
CONTROL
CABINET
BLR2-EN
BOILER 1
CONTROL
CABINET
BOILER 3
CONTROL
CABINET
BLR3-EN
NOTE: GREEN COLORED DEVICES ARE PROVIDED BY TRANE.
BLR2LW-T
ZWS-T
W
S -T
H W
R -T
BLR2-S
BLR3-S
SHARED GLOBALLY
LOCATED ON THE NORTH
SIDE OF THE BUILDING
OA-T
OA-H
EPB-S
(TYPICAL OF 2)
(EMERGENCY PUSH BUTTON)
LOCATED AT ENTRANCE OF MECH. RM
WIRED TO
B-2 & B-3 PANEL
TO HV-1,2 & 3
BLR3LW-T
BLR2-FS
BLR3-FS
REFER PAGE ATC-6
FOR MORE DETAILS
REFER PAGE ATC-6
FOR MORE DETAILS
REFER PAGE ATC-6
FOR MORE DETAILS
REFER PAGE ATC-6
FOR MORE DETAILS
NOTE: GRAY COLORED DEVICES ARE PROVIDED BY MECHANICAL CONTRACTOR.
REFER DRAWING NUMBER ATC-3A FOR BOM
A
B
EXISTING
COMMUNICATION
NETWORK
BLR1BYPV-C
BLR1BYPV-S
BLR3ISOV-C
BLR3ISOV-S
BLR2ISOV-C
BLR2ISOV-S
FTRS1-T
FTRS2-T
FTRS3-T
FTRS4-T
SHWP5-DPS
REV-1 11/02/20161
REV-2 12/09/20162
SHWP5-C
SHWP5-S
SHWP5 VFD
SHWP5-O
NOTE: RED COLORED DEVICES ARE CONTROLLED BY THE BOILERS OR PROVIDED INTERNALLY AND PRE-INSTALLED.
H E
A D
M P
CP1-C
CP1-S
CP2-C
CP2-S
HWBYPV-O
HWS HWR
R A
D
R A
D
6TH FLR
R A
D
R A
D
5TH FLR
R A
D
R A
D
4TH FLR
R A
D
R A
D
3RD FLR
R A
D
R A
D
2ND FLR
R A
D
R A
D
1ST FLR
TYPICAL RADIATION (FLR + ZONE)
ZN-TZN-T
ZN-TZN-T
ZN-TZN-T
ZN-TZN-T
ZN-TZN-T
ZN-TZN-T
BLR1ISOV-C
BLR1ISOV-S
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
HV-1, 2, 3 FLOW LAYOUT
ATC-3A
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
HV-1
V
HV-2
V
HV-3
V
HV-1, 2, 3 FLOW LAYOUT
[FLOW DIAGRAM IS INCLUDED FOR AS-BUILT PURPOSES, THE ONLY THING THAT WAS CHANGED WAS A CORRECTION TO THE LOCATION OF THE LOW TEMP ALARM SENSOR (DOWNSTREAM OF HEATING COIL.)]
NOTE: BLUE COLORED DEVICES ARE ALREADY EXISTING.
HWS
HWR
OA
EA
DA
RA
DA-T
SF VFD
RA-T
PFILT-S
NO MAD-O
NC
MAD-O
NC
MAD-O
RM-T
EF-S
EF STARTER
LT-ALT-A
SF-C
SF-S
SF-O
HV-x FLOW LAYOUT
HWS
HWR
NO
HTG-O
C
REV-1 11/02/20161
ABFMMB
Johnson Controls, Inc.
8 Skyline Dr.
Hawthorne, NY 10532 Phone: 914-275-2932
REFERENCE DRAWING
HWS SEQUENCE OF OPERATION
ATC-3B
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Brieant Court House BMS Upgrade
300 Quarropas Street White Plains, NY 10601
HWS SEQUENCE OF OPERATION
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2016
HOT WATER SYSTEM CONTROL: (STANDARD CONTROL SEQUENCE IS MENTIONED)
SYSTEM ENABLE:
THE HOT WATER SYSTEM WILL BE ENABLED WHEN THE OUTDOOR AIR TEMPERATURE DROPS BELOW THE HEATING OUTDOOR AIR LOCK OUT SETPOINT (HTGOATLOCKOUT-SP 65⁰F ADJ)
AND DISABLED WHEN OT RISES ABOVE. THE HWS CAN BE MANUALLY ENABLED BY CHAGING THE SYSTEM-ENABLE PARAMETER FROM “DISABLED” TO “ENABLE” LOCATED ON THE HWS
GRAPHIC.
HOT WATER TEMPERATURE RESET:
WHEN OSA TEMPERATURE IS ABOVE 65 F (ADJ.) HAVE HOT WATER SUPPLY TEMPERATURE AT 80 F (ADJ.). AS OSA TEMPERATURE GOES BELOW 65 F (ADJ.) TO 55 F (ADJ.) HAVE HOT WATER SUPPLY TEMPERATURE GO FROM 80 F (ADJ.) TO 130 F (ADJ.). AS THE OSA TEMPERATURE GOES BELOW 55 F (ADJ.) HAVE HOT WATER SUPPLY TEMPERATURE GO TO 165 F (ADJ.). THE RESET TABLE SHALL BE ADJUSTABLE WITHOUT PROGRAM MODIFICATION VIA MAXIMUM AND MINIMUM SETPOINTS TO DICTATE THE RANGES OF THE HW SUPPLY RESET FOR
EACH OF 3 OSA STAGES OF RESET. THE OSA PARAMETER WILL ALSO BE ADJUSTABLE WITH MINIMUM AND MAXIMUM VALUES LOCATED ON THE GRAPHIC WITH THE TITLE “HOT WATER
RESET”
BOILER CONTROL:
THIS SYSTEM CONSISTS OF THREE BOILERS…