This pre-solicitation notice seeks construction services for renovations and upgrades at three land port of entry facilities located in Vermont. Renovations include creating office spaces, restrooms, security upgrades, and replacing inspection booths. Temporary facilities are also required during construction. The estimated value is between $1 and $2 million. The solicitation will be available on October 17th and bids are due by November 18th. The contract is a 100% small business set-aside under NAICS Code 236220. A pre-bid site visit will be held on October 29th. The General Services Administration is the contracting agency.
West Berkshire Booth Replacement Scope of Work
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 285-053-002_Port_Refresh_East_Richford_LPOE_dwgs.pdf | ||
| 47PB0020B0001_Tab_2_Richford_Booth_Replace_SOW_2019_07_02.pdf | ||
| AD-101_Rev_1.pdf | ||
| Port_Refresh_East_Richford_LPOE_Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WEST BERKSHIRE – BOOTH REPLACEMENT PROJECT
FFR 17-1345
’-9
6’
-1
11’-10”12’-0”3’-0” 11’-8” 3’-8”
MIRROR
FIELD MEASUREMENTS
CURB HEIGHT - 7”
BOOTH SIZE – 4’-7” X 6’-4”
ROADWAY SLOPE / See Elevations page. (approx. 20’)
Heated
HVAC/ELECTRICAL/DATA CHASE
• HVAC UNIT located on roof of booth under canopy.
• Provide electrical outlet on roof for equipment usage by repair personnel.
• Continue chase horizontally under windows and counter.
• Add vertical chase to ceiling for data and electrical to CCTV in location shown. No exposed conduit.
LIGHTING
• Interior: 2 2X2 LED lights over counter.
• Exterior: LED light over doors and one mounted on side without door. See elevation drawings for locations.
HEATING
• Quick recovery unit.
• Heated Floor Mat sized to the booth floor.
WINDOWS and DOORS
• Level 3, BR Rated glass with tinting.
• Add shades for each window.
COUNTER
• Solid surface material
• Blocking under counter for CPU hanger.
• Minimum of three (3) 2” grommet holes for wire management.
BOOTH ENVELOPE
• Level 3, BR rated material. All exterior piping and connections to be sealed.
CAMERAS AND MICROPHONES
• Install two (2) cameras with microphone capability, or install separate microphone under camera, on booth as shown. They are to be mounted at approximately 60” to 66” – actual height to be determined at time of installation to insure viewing inside vehicle is correct.
STATEMENT OF WORK
WEST BERKSHIRE – BOOTH REPLACEMENT PROJECT
FFR 17-1345
EQUIPMENT RE-INSTALLATION AND NEW
• Install panel to house the RPM annunciators (2), the switch to the siren, duress button and switch for lane lights. Wire all items into this panel and label accordingly.
• Add a radio console in booth.
• Replace existing siren with a new siren.
• Add two (2) Cameras and Microphones, can be combined unit or separate.- see note under
“Cameras and Microphones.”
• Add CCTV Monitor (23”) and bracket suspended from ceiling.
SIGNAGE AND LANE PAVEMENT/RE-ALIGNMENT
• Score pavement starting from the start of LANE 1 under canopy, realign curbing and pave area sloping the roadway to meet at the top of the curb at booth and tapering away toward the building. Pavement slope not to exceed 3% and transition to be gradual for vehicle to easily transition back to level roadway. Refer to Elevation drawing.
• Install three 2” posts in pavement at LANE 1.(signage provided by CBP).
11’-10”
6’-1”
8’-0”
HVAC/DATA
CHASE
CEILING HATCH
LIGHTING
LIGHTING
COUNTER
RIGHT SIDE
LEFT SIDE
BUILDING
OUTBOUND LANE
CAMERA AND MIC
CAMERA AND MIC
PLAN VIEW
11’-10”
6’-1”
8’-0”
HVAC/ELEC/
DATA CHASE
HVAC/ELECTRICAL/DATA CHASE
• UTILIZE CHASE FOR WIRING
RUNS AND OUTLETS, PANELS
AND DATA BOXES.
COUNTER
1N DATA & 1 DUPLEX
AT CEILING FOR CCTV.
1 DUPLEX BELOW
COUNTER.
3N/1R DATA & 1 QUAD
BELOW COUNTER.
3N/1T DATA & 1 QUAD
BELOW COUNTER.
1 DUPLEX BELOW
COUNTER.
RIGHT SIDE
LEFT SIDE
CPU HANGER
LOCATION.
PANEL BOX TO HOUSE:
• SIREN BUTTON
• RPM ANNUNCIATORS
• DURESS BUTTON
• SWITCH FOR LANE LIGHTS
DATA – 3N/1R AND 3N/1T
DATA – 1N
DUPLEX
QUAD
KEY AND NOTES
PLAN VIEW - ELECTRICAL/DATA
BUILDING
OUTBOUND LANE
ANGLED WALL
SOLID SURFACE
COUNTER
DATA/ELECTRICAL CHASE
MOUNTING BRACKET FOR CCTV
DATA & ELECTRICAL FOR CCTV
PANEL BOX TO HOUSE:
• SIREN BUTTON
• RPM ANNUNCIATORS
• DURESS BUTTON
• SWITCH FOR LANE LIGHTS
SINGLE DATA FOR CCTV
3N/1R DATA
3N/1T DATA
DUPLEX
QUAD
HEATED FLOOR
MAT
ELECTRICAL FOR
HEATED FLOOR MAT
CPU HANGER
ELEVATION – Interior facing Canada
KEY
ROLLER SHADES
ELEVATIONS
SLOPE ROADWAY UP TO MEET CURB AT BOOTH AND
GRADE DOWN TO EXISTING LEVEL ON BUILDING SIDE.
REPLACE CURBING AS NECESSARY.
Create a gradual hump in roadway so vehicle is angled not more than 3% . Extend hump past booth for easy transition back to grade.
7”
ROADWAY IN LANE 1
CURB CURB
7”
8”
HEIGHT OF CANOPY IS 13’-8”
41’-4”
11’-8”
NEW BOOTH ELEVATION
DIRECTION OF TRAVEL ENTERING THE USA VIA LANE 1
EXTERIOR LIGHTING
BACK DOOR
CAMERA W/MIC
8’-0”
7”
8”
HEIGHT OF CANOPY IS 13’-8”
41’-4”
11’-8”
NEW BOOTH ELEVATION
DIRECTION OF TRAVEL IN OUTBOUND LANE TO CANADA
CAMERA W/MIC
EXTERIOR DUPLEX
HVAC UNIT
EXTERIOR LIGHTING