I apologize, but no file content was actually provided in your message. While you referenced a specific file name (472.24428.SAA WHV CF - EM Room and Control Center Renovation - Commtech Specs.pdf), the actual file contents or text are missing. Without the actual document text or content, I cannot generate a summary. If you would like me to analyze the document, please upload or paste the full text of the file, and I will be happy to provide a comprehensive professional summary.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Suppression, Plumbing, Heating Ventilation and Air Conditioning, Electrical, Security & Communication
Specifications.
File No. 472/24428 Department/Agency: Corrections
Project Name: EM Room and Control Center Upgrade
Location: Women’s Huron Valley Correctional Facility
February 10, 2025
State of Michigan Department of Technology, Management and Budget Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation File/No: 472/24428.SAA Funding Code No.: 472WHVMaintProj
WET-PIPE SPRINKLER SYSTEMS 211313 - 1
SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Pipes, fittings, and specialties.
2. Fire-protection valves.
3. Sprinklers.
4. Alarm devices.
1.3 DEFINITIONS
A. High-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure higher than standard 175 psig, but not higher than 250 psig.
B. Standard-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure of 175 psig maximum.
1.4 SYSTEM DESCRIPTIONS
A. Wet-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. Hose connections are included if indicated.
1.5 PERFORMANCE REQUIREMENTS
A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.
B. Sprinkler system design shall be approved by authorities having jurisdiction.
1. Margin of Safety for Available Water Flow and Pressure: 10 percent, including losses through water-service piping, valves, and backflow preventers.
2. Sprinkler Occupancy Hazard Classifications:
a. Automobile Parking Areas: Ordinary Hazard, Group 1.
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 2
b. Building Service Areas: Ordinary Hazard, Group 1.
c. Churches and Theaters: Light Hazard.
d. Electrical Equipment Rooms: Ordinary Hazard, Group 1.
e. Dry Cleaners: Ordinary Hazard, Group 2.
f. General Storage Areas: Ordinary Hazard, Group 1.
g. Laundries: Ordinary Hazard, Group 1.
h. Libraries except Stack Areas: Light Hazard.
i. Library Stack Areas: Ordinary Hazard, Group 2.
j. Machine Shops: Ordinary Hazard, Group 2.
k. Mechanical Equipment Rooms: Ordinary Hazard, Group 1.
l. Office and Public Areas: Light Hazard.
m. Repair Garages: Ordinary Hazard, Group 2.
n. Residential Living Areas: Light Hazard.
o. Restaurant Service Areas: Ordinary Hazard, Group 1.
3. Minimum Density for Automatic-Sprinkler Piping Design:
a. Residential (Dwelling) Occupancy: 0.05 gpm over 400-sq. ft. area.
b. Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. area.
c. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. area.
d. Ordinary-Hazard, Group 2 Occupancy: 0.20 gpm over 1500-sq. ft. area.
e. Extra-Hazard, Group 1 Occupancy: 0.30 gpm over 2500-sq. ft. area.
f. Extra-Hazard, Group 2 Occupancy: 0.40 gpm over 2500-sq. ft. area.
g. Special Occupancy Hazard: As determined by authorities having jurisdiction.
4. Minimum Density for Deluge-Sprinkler Piping Design:
a. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over entire area.
b. Ordinary-Hazard, Group 2 Occupancy: 0.20 gpm over entire area.
c. Extra-Hazard, Group 1 Occupancy: 0.30 gpm over entire area.
d. Extra-Hazard, Group 2 Occupancy: 0.40 gpm over entire area.
e. Special Occupancy Hazard: As determined by authorities having jurisdiction.
5. Maximum Protection Area per Sprinkler: Per UL listing.
6. Maximum Protection Area per Sprinkler:
a. Residential Areas: 400 sq. ft.
b. Office Spaces: 225 sq. ft.
c. Storage Areas: 130 sq. ft.
d. Mechanical Equipment Rooms: 130 sq. ft.
e. Electrical Equipment Rooms: 130 sq. ft.
f. Other Areas: According to NFPA 13 recommendations unless otherwise indicated.
7. Total Combined Hose-Stream Demand Requirement: According to NFPA 13 unless otherwise indicated:
a. Light-Hazard Occupancies: 100 gpm for 30 minutes.
b. Ordinary-Hazard Occupancies: 250 gpm for 60 to 90 minutes.
c. Extra-Hazard Occupancies: 500 gpm for 90 to 120 minutes.
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 3
8. Seismic Performance: Sprinkler piping shall withstand the effects of earthquake motions determined according to NFPA 13 and ASCE/SEI7.
1.6 SUBMITTALS
A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
B. Shop Drawings: For wet-pipe sprinkler systems. Include plans, elevations, sections, details, and attachments to other work.
1. Wiring Diagrams: For power, signal, and control wiring.
C. Delegated-Design Submittal: For sprinkler systems indicated to comply with performance requirements and design criteria, including analysis data signed by a licensed fire protection contractor.
D. Coordination Drawings: Sprinkler systems, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Domestic water piping.
2. HVAC ductwork
3. Items penetrating finished ceiling include the following:
a. Lighting fixtures.
b. Air outlets and inlets.
E. Qualification Data: For qualified Installer.
A. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that have been approved by authorities having jurisdiction, including hydraulic calculations if applicable.
1. Sprinklers shall be referred to on drawings, submittals and other documentation, by the sprinkler identification or Model number as specifically published in the appropriate agency listing or approval. Trade names or other abbreviated designations shall not be allowed.
B. Welding certificates.
C. Fire-hydrant flow test report.
D. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping."
E. Field quality-control reports.
F. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals.
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 4
1.7 QUALITY ASSURANCE
A. Installer Qualifications:
1. Installer's responsibilities include designing, fabricating, and installing sprinkler systems.
Base calculations on results of fire-hydrant flow test.
A. Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code.
B. All grooved couplings, fittings, valves, and specialties shall be the products of a single manufacturer. Grooving tools shall be of the same manufacturer as the grooved components.
1. All castings used for couplings housings, fittings, or valve and specialty bodies shall be date stamped for quality assurance and traceability.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
D. NFPA Standards: Sprinkler system equipment, specialties, accessories, installation, and testing shall comply with the following:
1. NFPA 13, "Installation of Sprinkler Systems."
1.8 PROJECT CONDITIONS
A. Interruption of Existing Sprinkler Service: Do not interrupt sprinkler service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary sprinkler service according to requirements indicated:
1. Notify Architect and Owner no fewer than two days in advance of proposed interruption of sprinkler service.
2. Do not proceed with interruption of sprinkler service without Architect's and Owner's written permission.
1.9 COORDINATION
A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HVAC equipment, and partition assemblies.
1.10 EXTRA MATERIALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Sprinkler Cabinets: Finished, wall-mounted, steel cabinet with hinged cover, and with space for minimum of six spare sprinklers plus sprinkler wrench. Include number of
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 5
sprinklers required by NFPA 13 and sprinkler wrench. Include separate cabinet with sprinklers and wrench for each type of sprinkler used on Project.
PART 2 - PRODUCTS
2.1 PIPING MATERIALS
A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, and fitting materials, and for joining methods for specific services, service locations, and pipe sizes.
2.2 STEEL PIPE AND FITTINGS
A. Schedule 40, Galvanized and Black Steel Pipe: ASTM A 135; ASTM A 795/A 795M, Type E; or ASME B36.10M, wrought steel; with wall thickness not less than Schedule 40 and not more than Schedule 40. Pipe ends may be factory or field formed to match joining method.
B. Galvanized and Black Steel Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M, standard-weight, seamless steel pipe with threaded ends.
C. Galvanized and Uncoated, Steel Couplings: ASTM A 865, threaded.
D. Malleable- or Ductile-Iron Unions: UL 860.
E. Cast-Iron Flanges: ASME 16.1, Class 125.
F. Steel Flanges and Flanged Fittings: ASME B16.5, Class 150.
G. Steel Welding Fittings: ASTM A 234/A 234M and ASME B16.9.
H. Grooved-Joint, Steel-Pipe Appurtenances:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Anvil International, Inc.
b. Apollo
c. Corcoran Piping System Co.
d. National Fittings, Inc.
e. Shurjoint Piping Products.
f. Tyco Fire & Building Products LP.
g. Victaulic Company.
2. Pressure Rating: 175 psig minimum.
3. Galvanized and Uncoated, Grooved-End Fittings for Steel Piping: ASTM A 536, ductile-iron casting; with dimensions matching steel pipe. In applicable sizes, fittings shall be short pattern, with flow equal to standard pattern fittings. Basis of Design: Victaulic FireLock.
http://www.specagent.com/LookUp/?ulid=1431&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802326&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802327&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802328&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802329&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802330&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802331&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 6
a. Installation-Ready™ fittings for Schedule 40 grooved end steel piping in fire protection applications sizes NPS 1-¼ thru 2½ (DN 32 thru DN 65). Fittings shall consist of a ductile iron housing with Installation-Ready™ ends, prelubricated Grade “E” EPDM Type ‘A’ gasket, and ASTM A449 electroplated steel bolts and nuts. UL listed for a working pressure of 300 psi (2065 kPa) and FM approved for working pressure 365 psi (2517kPa).
4. Grooved-End-Pipe Couplings for Steel Piping: AWWA C606 and UL 213, rigid pattern, unless otherwise indicated, for steel-pipe dimensions. Include ferrous housing sections, EPDM-rubber center-leg gasket with pipe stop to ensure proper groove engagement, alignment, and pipe insertion depth, and ASTM A449 electroplated steel bolts and nuts.
1) Rigid Type: Housings cast with offsetting, angle-pattern, bolt pads to provide system rigidity and support and hanging in accordance with NFPA-13, fully installed at visual pad-to-pad offset contact. (Couplings that require exact gapping at specific torque ratings are not permitted.). Installation-Ready for complete installation without field disassembly. Basis of Design: Victaulic Style 009N and 107N.
2) Flexible Type: For use in locations where vibration attenuation and stress relief are required: Basis of Design: Victaulic Installation-Ready Style 177.
A. Stainless Steel Pressure-Seal Fittings: UL 213, FM-approved, 175-psig pressure rating with stainless steel housing, rubber O-rings, and pipe stop; for use with fitting manufacturers' pressure-seal tools.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Victaulic Company.
2.3 PIPING JOINING MATERIALS
A. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch thick or ASME B16.21, nonmetallic and asbestos free.
1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges: Full-face gaskets.
2. Class 250, Cast-Iron Flanges and Class 300, Steel Raised-Face Flanges: Ring-type gaskets.
B. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated.
C. Grooved Joint Lubricants: Lubricate gasket in accordance with the manufacturer’s published instructions with lubricant approved for the gasket elastomer and fluid media. Basis of Design:
Victaulic Vic-Lube.
http://www.specagent.com/LookUp/?ulid=1432&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802332&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 7
2.4 LISTED FIRE-PROTECTION VALVES
A. General Requirements:
1. Valves shall be UL listed or FM approved.
2. Minimum Pressure Rating for Standard-Pressure Piping: 175 psig.
3. Minimum Pressure Rating for High-Pressure Piping: 250 psig.
B. Ball Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Anvil International, Inc.
b. Victaulic Company.
2. Standard: UL 1091 except with ball instead of disc.
3. Valves NPS 1-1/2 and Smaller: Bronze or brass body with threaded or grooved ends.
Basis of Design: Victaulic Series 728Valves NPS 2 and NPS 2-1/2: Bronze body with threaded ends or ductile-iron body with grooved ends.
4. Valves NPS 2 and NPS 2-1/2: Bronze body with threaded ends or ductile-iron body with grooved ends.
5. Valves NPS 3: Ductile-iron body with grooved ends.
C. Bronze Butterfly Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Fivalco Inc.
b. Global Safety Products, Inc.
c. Milwaukee Valve Company.
d. Victaulic Company.
2. Standard: UL 1091.
3. Pressure Rating: 300 psig.
4. Body Material: Bronze.
5. End Connections: Threaded or copper-tube dimensioned grooved ends.
6. Basis of Design: Victaulic Series 608N.
D. Iron Butterfly Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Anvil International, Inc.
b. Fivalco Inc.
c. Global Safety Products, Inc.
http://www.specagent.com/LookUp/?uid=123456802338&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802339&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802340&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802341&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802342&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802343&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802344&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802345&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 8
d. Kennedy Valve; a division of McWane, Inc.
e. Milwaukee Valve Company.
f. NIBCO INC.
g. Pratt, Henry Company.
h. Shurjoint Piping Products.
i. Tyco Fire & Building Products LP.
j. Victaulic Company.
2. Standard: UL 1091.
3. Pressure Rating: 300 psig.
4. Body Material: Cast or ductile iron.
5. Seat: Pressure responsive elastomer.
6. Stem: Stainless steel, offset from the disc centerline to provide complete 360-degree circumferential seating.
7. Style: Lug or wafer.
8. End Connections: Grooved.
9. Basis of Design: Victaulic Series 705.
E. Check Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. AFAC Inc.
b. American Cast Iron Pipe Company; Waterous Company Subsidiary.
c. Anvil International, Inc.
d. Apollo
e. Clow Valve Company; a division of McWane, Inc.
f. Crane Co.; Crane Valve Group; Crane Valves.
g. Crane Co.; Crane Valve Group; Jenkins Valves.
h. Crane Co.; Crane Valve Group; Stockham Division.
i. Fire-End & Croker Corporation.
j. Fire Protection Products, Inc.
k. Fivalco Inc.
l. Globe Fire Sprinkler Corporation.
m. Groeniger & Company.
n. Kennedy Valve; a division of McWane, Inc.
o. Matco-Norca.
p. Metraflex, Inc.
q. Milwaukee Valve Company.
r. Mueller Co.; Water Products Division.
s. NIBCO INC.
t. Potter Roemer.
u. Reliable Automatic Sprinkler Co., Inc.
v. Shurjoint Piping Products.
w. Tyco Fire & Building Products LP.
x. United Brass Works, Inc.
y. Venus Fire Protection Ltd.
z. Victaulic Company.
aa. Viking Corporation.
http://www.specagent.com/LookUp/?uid=123456816897&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802346&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802347&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456816898&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802348&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802349&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802350&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802351&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456816899&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802352&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817253&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817256&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817258&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817260&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802353&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802354&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802355&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802356&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802357&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817262&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802358&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802359&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802360&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817264&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802361&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802362&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802363&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802364&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802366&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802367&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802368&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802369&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802370&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 9
bb. Watts Water Technologies, Inc.
2. Standard: UL 312.
3. Pressure Rating: 250 psig minimum.
4. Type: Spring-assisted swing check for vertical or horizontal installation.
5. Body Material: Cast or ductile iron.
6. End Connections: Flanged or grooved.
7. Basis of Design: Victaulic Series 717.
F. Bronze OS&Y Gate Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Crane Co.; Crane Valve Group; Crane Valves.
b. Crane Co.; Crane Valve Group; Stockham Division.
c. Milwaukee Valve Company.
d. NIBCO INC.
e. United Brass Works, Inc.
2. Standard: UL 262.
3. Pressure Rating: 175 psig.
4. Body Material: Bronze.
5. End Connections: Threaded.
G. Iron OS&Y Gate Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. American Cast Iron Pipe Company; Waterous Company Subsidiary.
b. American Valve, Inc.
c. Apollo
d. Crane Co.; Crane Valve Group; Crane Valves.
e. Crane Co.; Crane Valve Group; Jenkins Valves.
f. Crane Co.; Crane Valve Group; Stockham Division.
g. Hammond Valve.
h. Milwaukee Valve Company.
i. Mueller Co.; Water Products Division.
j. NIBCO INC.
k. Shurjoint Piping Products.
l. Tyco/JCI
m. Tyco Fire & Building Products LP.
n. United Brass Works, Inc.
o. Victaulic Company.
p. Watts Water Technologies, Inc.
2. Standard: UL 262.
3. Pressure Rating: 250 psig minimum.
http://www.specagent.com/LookUp/?uid=123456802371&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817265&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817267&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802372&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802373&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802374&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817268&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802375&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817272&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817275&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817279&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802376&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802377&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817281&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802378&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802379&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802380&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802381&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802382&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 10
4. Body Material: Cast or ductile iron.
5. End Connections: Flanged or grooved.
6. Basis of Design: Victaulic Series 771.
H. Indicating-Type Butterfly Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Anvil International, Inc.
b. Fivalco Inc.
c. Global Safety Products, Inc.
d. Kennedy Valve; a division of McWane, Inc.
e. Milwaukee Valve Company.
f. NIBCO INC.
g. Shurjoint Piping Products.
h. Tyco Fire & Building Products LP.
i. Victaulic Company.
2. Standard: UL 1091.
3. Pressure Rating: 175 psig minimum.
4. Valves NPS 2 and Smaller:
a. Valve Type: Ball or butterfly.
b. Body Material: Bronze or brass.
c. End Connections: Threaded or grooved.
d. Basis of Design: Victaulic Series 728.
5. Valves NPS 2-1/2 and Larger:
a. Valve Type: Butterfly.
b. Body Material: Cast or ductile iron.
c. Seat: Pressure-responsive elastomer.
d. Stem: Stainless steel, offset from the disc centerline to provide complete 360-degree circumferential seating.
e. End Connections: Flanged, grooved, or wafer.
f. Basis of Design: Victaulic Series 705.
6. Valve Operation: Weatherproof actuator housing with integral electrical, 125-V ac, prewired, two-circuit, supervisory switch visual indicating device.
I. NRS Gate Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. American Cast Iron Pipe Company; Waterous Company Subsidiary.
b. American Valve, Inc.
c. Clow Valve Company; a division of McWane, Inc.
http://www.specagent.com/LookUp/?uid=123456802383&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802384&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802385&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817283&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802386&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802387&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802388&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802389&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802390&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817285&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802391&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817288&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 11
d. Crane Co.; Crane Valve Group; Stockham Division.
e. Kennedy Valve; a division of McWane, Inc.
f. Mueller Co.; Water Products Division.
g. NIBCO INC.
h. Tyco Fire & Building Products LP.
i. Victaulic Company.
2. Standard: UL 262.
3. Pressure Rating: 250 psig minimum.
4. Body Material: Cast or ductile iron with indicator post flange.
5. Stem: Nonrising.
6. End Connections: Flanged or grooved.
7. Basis of Design: Victaulic Series 772.
J. Indicator Posts:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. American Cast Iron Pipe Company; Waterous Company Subsidiary.
b. American Valve, Inc.
c. Clow Valve Company; a division of McWane, Inc.
d. Crane Co.; Crane Valve Group; Stockham Division.
e. Kennedy Valve; a division of McWane, Inc.
f. Mueller Co.; Water Products Division.
g. NIBCO INC.
h. Tyco Fire & Building Products LP.
i. Victaulic Company.
2. Standard: UL 789.
3. Type: Horizontal for wall mounting.
4. Body Material: Cast iron with extension rod and locking device.
5. Operation: Wrench or handwheel.
6. Basis of Design: Victaulic Series 773.
2.5 TRIM AND DRAIN VALVES
A. General Requirements:
1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
2. Pressure Rating: 175 psig minimum.
B. Angle Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
http://www.specagent.com/LookUp/?uid=123456817291&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817293&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817296&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802392&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802393&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817298&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802394&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817300&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817307&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817308&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817309&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802395&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802396&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1452&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 12
a. Fire Protection Products, Inc.
b. United Brass Works, Inc.
C. Ball Valves:
1. Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Affiliated Distributors.
b. Anvil International, Inc.
c. Barnett.
d. Conbraco Industries, Inc.; Apollo Valves.
e. Fire-End & Croker Corporation.
f. Fire Protection Products, Inc.
g. Flowserve.
h. FNW.
i. Jomar International, Ltd.
j. Kennedy Valve; a division of McWane, Inc.
k. Kitz Corporation.
l. Legend Valve.
m. Metso Automation USA Inc.
n. Milwaukee Valve Company.
o. NIBCO INC.
p. Potter Roemer.
q. Red-White Valve Corporation.
r. Southern Manufacturing Group.
s. Stewart, M. A. and Sons Ltd.
t. Tyco Fire & Building Products LP.
u. Victaulic Company.
v. Watts Water Technologies, Inc.
D. Globe Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Fire Protection Products, Inc.
b. United Brass Works, Inc.
E. Plug Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Southern Manufacturing Group.
http://www.specagent.com/LookUp/?uid=123456802397&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802398&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1453&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802399&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802400&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802401&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817310&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802402&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802403&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802404&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802405&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802406&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817311&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802407&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802408&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802409&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802410&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802411&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802413&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802414&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802415&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817312&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802416&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802417&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802418&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1455&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802419&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802420&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1457&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802421&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 13
2.6 SPRINKLER SPECIALTY PIPE FITTINGS
A. Branch Outlet Fittings:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Anvil International, Inc.
b. National Fittings, Inc.
c. Shurjoint Piping Products.
d. Tyco Fire & Building Products LP.
e. Victaulic Company.
2. Standard: UL 213.
3. Pressure Rating: 175 psig minimum.
4. Body Material: Ductile-iron housing with EPDM seals and bolts and nuts.
5. Type: Mechanical-T and -cross fittings.
6. Configurations: Snap-on and strapless, ductile-iron housing with branch outlets.
7. Size: Of dimension to fit onto sprinkler main and with outlet connections as required to match connected branch piping.
8. Branch Outlets: Grooved, plain-end pipe, or threaded.
9. Basis of Design: Victaulic Style 920 / 920N.
B. Flow Detection and Test Assemblies:
1. Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. AGF Manufacturing Inc.
b. Reliable Automatic Sprinkler Co., Inc.
c. Tyco Fire & Building Products LP.
d. Victaulic Company.
2. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
3. Pressure Rating: 175 psig minimum.
4. Body Material: Cast-bronze or ductile-iron housing with orifice, sight glass, and integral test valve.
5. Size: Same as connected piping.
6. Inlet and Outlet: Threaded or grooved.
7. Basis of Design: Victaulic Series 747.
C. Branch Line Testers:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Elkhart Brass Mfg. Company, Inc.
b. Fire-End & Croker Corporation.
http://www.specagent.com/LookUp/?ulid=1466&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802462&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802463&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802464&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802465&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802466&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1467&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802467&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802468&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802469&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802470&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1468&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802471&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802472&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 14
c. Potter Roemer.
2. Standard: UL 199.
3. Pressure Rating: 175 psig.
4. Body Material: Brass.
5. Size: Same as connected piping.
6. Inlet: Threaded.
7. Drain Outlet: Threaded and capped.
8. Branch Outlet: Threaded, for sprinkler.
D. Sprinkler Inspector's Test Fittings:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. AGF Manufacturing Inc.
b. Triple R Specialty.
c. Tyco Fire & Building Products LP.
d. Victaulic Company.
e. Viking Corporation.
2. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
3. Pressure Rating: 175 psig minimum.
4. Body Material: Cast-bronze or ductile-iron housing with sight glass.
5. Size: Same as connected piping.
6. Inlet and Outlet: Threaded or grooved.
7. Basis of Design: Victaulic Style 720 TestMaster™ II.
E. Adjustable Drop Nipples:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. CECA, LLC.
b. Corcoran Piping System Co.
c. Merit Manufacturing; a division of Anvil International, Inc.
2. Standard: UL 1474.
3. Pressure Rating: 250 psig minimum.
4. Body Material: Steel pipe with EPDM-rubber O-ring seals.
5. Size: Same as connected piping.
6. Length: Adjustable.
7. Inlet and Outlet: Threaded.
2.7 SPRINKLERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
http://www.specagent.com/LookUp/?uid=123456802473&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1469&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802474&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802475&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802476&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802477&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802478&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1470&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802479&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802480&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817314&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1473&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 15
1. AFAC Inc.
2. Globe Fire Sprinkler Corporation.
3. Reliable Automatic Sprinkler Co., Inc.
4. Tyco Fire & Building Products LP.
5. Venus Fire Protection Ltd.
6. Victaulic Company.
7. Viking Corporation.
B. General Requirements:
1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
2. Pressure Rating for Residential Sprinklers: 175 psig maximum.
3. Pressure Rating for Automatic Sprinklers: 175 psig minimum.
4. Pressure Rating for High-Pressure Automatic Sprinklers: 250 psig minimum
C. Automatic Sprinklers with Heat-Responsive Element:
1. Early-Suppression, Fast-Response Applications: UL 1767.
2. Nonresidential Applications: UL 199.
3. Residential Applications: UL 1626.
4. Characteristics: Nominal 1/2-inch orifice with Discharge Coefficient K of 5.6, and for
"Ordinary" temperature classification rating unless otherwise indicated or required by application.
D. Open Sprinklers with Heat-Responsive Element Removed: UL 199.
1. Characteristics:
a. Nominal 1/2-inch Orifice: With Discharge Coefficient K between 5.3 and 5.8.
b. Nominal 17/32-inch Orifice: With Discharge Coefficient K between 7.4 and 8.2.
E. Sprinkler Finishes:
1. Chrome plated.
2. Bronze.
3. Painted.
F. Special Coatings:
1. Wax.
2. Lead.
3. Corrosion-resistant paint.
G. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers.
1. Ceiling Mounting: Steel with white polyester coating, two piece adjustable, recessed.
2. Sidewall Mounting: Steel with white polyester coating, two piece, adjustable, recessed.
http://www.specagent.com/LookUp/?uid=123456802484&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802485&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802486&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802487&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802488&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802489&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802490&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 16
H. Sprinkler Guards:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Reliable Automatic Sprinkler Co., Inc.
b. Tyco Fire & Building Products LP.
c. Victaulic Company.
d. Viking Corporation.
2. Standard: UL 199.
3. Type: Wire cage with fastening device for attaching to sprinkler.
I. Escutcheons and guards shall be listed, supplied, and approved for use with the sprinkler by the sprinkler manufacturer.
J. Wrenches shall be provided by the sprinkler manufacturer that directly engage the wrench boss cast in the sprinkler body.
K. In lieu of rigid connections to dry sprinkler heads, a Victaulic VicFlex™ dry sprinkler, Model VS1, may be used. The sprinkler shall provide a vertical or horizontal flexible connection with a bend radius to 2”, and allow for up to 4 bends.
2.8 ALARM DEVICES
A. Alarm-device types shall match piping and equipment connections.
B. Water-Motor-Operated Alarm:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Globe Fire Sprinkler Corporation.
b. Tyco Fire & Building Products LP.
c. Victaulic Company.
d. Viking Corporation.
2. Standard: UL 753.
3. Type: Mechanically operated, with Pelton wheel.
4. Alarm Gong: Cast aluminum with red-enamel factory finish.
5. Size: 10-inch diameter.
6. Components: Shaft length, bearings, and sleeve to suit wall construction.
7. Inlet: NPS 3/4.
8. Outlet: NPS 1 drain connection.
9. Basis of Design: Victaulic Style 760.
C. Water-Flow Indicators:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
http://www.specagent.com/LookUp/?ulid=1474&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802491&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802492&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802493&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802494&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1476&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802495&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802496&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802497&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802498&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1479&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 17
a. ADT Security Services, Inc.
b. McDonnell & Miller; ITT Industries.
c. Potter Electric Signal Company.
d. System Sensor; a Honeywell company.
e. Viking Corporation.
f. Watts Industries (Canada) Inc.
2. Standard: UL 346.
3. Water-Flow Detector: Electrically supervised.
4. Components: Two single-pole, double-throw circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V dc; complete with factory-set, field-adjustable retard element to prevent false signals and tamperproof cover that sends signal if removed.
5. Type: Paddle operated.
6. Pressure Rating: 250 psig.
7. Design Installation: Horizontal or vertical.
D. Pressure Switches:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. AFAC Inc.
b. Barksdale, Inc.
c. Detroit Switch, Inc.
d. Potter Electric Signal Company.
e. System Sensor; a Honeywell company.
f. Tyco Fire & Building Products LP.
g. United Electric Controls Co.
h. Viking Corporation.
2. Standard: UL 346.
3. Type: Electrically supervised water-flow switch with retard feature.
4. Components: Single-pole, double-throw switch with normally closed contacts.
5. Design Operation: Rising pressure signals water flow.
E. Valve Supervisory Switches:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Fire-Lite Alarms, Inc.; a Honeywell company.
b. Kennedy Valve; a division of McWane, Inc.
c. Potter Electric Signal Company.
d. System Sensor; a Honeywell company.
2. Standard: UL 346.
3. Type: Electrically supervised.
4. Components: Single-pole, double-throw switch with normally closed contacts.
5. Design: Signals that controlled valve is in other than fully open position.
http://www.specagent.com/LookUp/?uid=123456802500&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817319&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802501&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817322&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802502&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802503&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1481&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802504&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802505&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802506&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802507&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817325&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802508&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802509&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802510&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=1482&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817326&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817327&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802511&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817328&mf=04&src=wd
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 18
PART 3 - EXECUTION
3.1 PREPARATION
A. Perform fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results for system design calculations required in "Quality Assurance" Article.
B. Report test results promptly and in writing.
3.2 SERVICE-ENTRANCE PIPING
A. Connect sprinkler piping to water-service piping for service entrance to building.
3.3 PIPING INSTALLATION
A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical.
1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with Architect before deviating from approved working plans.
B. Piping Standard: Comply with requirements for installation of sprinkler piping in NFPA 13.
C. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes.
D. Install unions adjacent to each valve in pipes NPS 2 and smaller.
E. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections.
F. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff valve, and sized and located according to NFPA 13.
G. Install sprinkler piping with drains for complete system drainage.
H. Install alarm devices in piping systems.
I. Install hangers and supports for sprinkler system piping according to NFPA 13. Comply with requirements for hanger materials in NFPA 13.
J. Fill sprinkler system piping with water.
K. Install sleeves for piping penetrations of walls, ceilings, and floors.
L. Install sleeve seals for piping penetrations of concrete walls and slabs.
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 19
M. Install escutcheons for piping penetrations of walls, ceilings, and floors.
N. No flexible sprinkler heads or piping allowed. All rigid piping to be installed.
O. All exposed fire protection piping to be painted red to match the existing piping.
3.4 JOINT CONSTRUCTION
A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure ratings same as or higher than system's pressure rating for aboveground applications unless otherwise indicated.
B. Install unions adjacent to each valve in pipes NPS 2 and smaller.
C. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections.
D. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
E. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly.
F. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with gasket and bolts according to ASME B31.9.
G. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows:
1. Apply appropriate tape or thread compound to external pipe threads.
2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged.
H. Twist-Locked Joints: Insert plain end of steel pipe into plain-end-pipe fitting. Rotate retainer lugs one-quarter turn or tighten retainer pin.
I. Steel-Piping, Cut-Grooved Joints: Cut square-edge groove in end of pipe according to AWWA C606 in accordance with the manufacturer’s latest published instructions. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for steel-pipe joints. Grooved coupling manufacturer’s factory trained field representative shall provide on-site training for contractor’s field personnel in the proper use of grooving tools, application of groove, and installation of grooved piping products. The factory trained representative shall periodically visit the jobsite to ensure best practices in grooved product installation are being followed. Contractor shall remove and replace any improperly installed products.
J. Steel-Piping, Roll-Grooved Joints: Roll rounded-edge groove in end of pipe according to AWWA C606 in accordance with the manufacturer’s latest published instructions. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for steel-pipe grooved joints. Grooved coupling manufacturer’s
Design and Construction Division Women’s Huron Valley Correctional Facility EM Room and Control Center Renovation
WET-PIPE SPRINKLER SYSTEMS 211313 - 20
factory trained field representative shall provide on-site training for contractor’s field personnel in the proper use of grooving tools, application of groove, and installation of grooved piping products. The factory trained representative shall periodically visit the jobsite to ensure best practices in grooved product installation are being followed. Contractor shall remove and replace any improperly installed products.
K. Dissimilar-Material Piping Joints: Make joints using adapters compatible with materials of both piping systems.
3.5 VALVE AND SPECIALTIES INSTALLATION
A. Install listed fire-protection valves, trim and drain valves, specialty valves and trim, controls, and specialties according to NFPA 13 and authorities having jurisdiction.
B. Install listed fire-protection shutoff valves supervised open, located to control sources…