This is a set of electrical plans and specifications for Phase 1 of the South Santa Rosa County Sports Complex, prepared by Grace Design for Santa Rosa County, Florida. The project encompasses the design of a Concession Building electrical system located at 5075 Gulf Breeze Parkway, Gulf Breeze, Florida 32563. The electrical plans detail comprehensive installations including a new pad-mounted transformer (480Y/277V, 3-phase, 4-wire secondary), main power panel (MP2) rated at 480Y/277V with a 400-amp main breaker, a secondary panel (LP2) at 208Y/120V with a 150-amp main breaker, mechanical equipment connections for heat pump units, exhaust fans, electric water heaters, and unit heaters, and extensive lighting systems including LED fixtures, motion sensors, occupancy sensors, and emergency lighting with battery backup. The plans specify conduit routing, panelboard coordination schedules, transformer specifications, circuit breaker assignments, and detailed lighting and power layouts across multiple rooms within the Concession Building. The design includes outdoor sports lighting for multiple lighting poles and futsol fields controlled through time-clock and lighting contactor systems. The sealed bid for this project was scheduled to be opened on Thursday, August 20, 2026, at 10:15 a.m., with a pre-bid meeting held on July 29, 2026, at 10:00 a.m. at the Santa Rosa County Engineering Office.
The electrical design reflects a total connected load of 155.06 kVA for the mechanical equipment and 32.66 kVA for the sports lighting system. All equipment specifications include manufacturer and catalog numbers for required components such as Acuity, Hubbell, and Cooper lighting fixtures, with provisions for equivalent substitutions submitted to the engineer ten days prior to bid for approval. The plans incorporate National Electrical Code (NEC) compliance requirements, including proper grounding to foundation rebar, water lines, and building steel, and specify NEMA-rated disconnects and enclosures throughout the system. No pricing information, set-asides, or funding source details are provided in these technical plans; the procurement process is managed through the Santa Rosa County Procurement Portal with questions to be submitted by August 6, 2026.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONDUIT RUN EXPOSED PERPENDICULAR OR PARALLEL TO BUILDING LINES
2#12, 1#12 GRD 1/2"C, 3#12, 1#12 GRD, 1/2"C, ETC.
HOMERUN TO PANELBOARD ANY CIRCUIT WITHOUT FURTHER DESIGNATION
CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALLS
CONDUIT RUN BELOW GRADE OR IN SLAB.
NON-FUSED DISCONNECT SWITCH
SURFACE MOUNTED POWER PANELBOARD
DUPLEX RECEPTACLE MOUNT 18" AFF UNLESS NOTED OTHERWISE
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE, MOUNTING HEIGHT AS NOTED
SINGLE POLE LIGHTING SWITCH, MOUNT 46" AFF
DUAL TECHNOLOGY CEILING MOUNTED MOTION SENSOR. SENSOR SWITCH
#CM-PDT-9-R. PROVIDE POWER PACK. PROVIDE WIRING IN CONDUIT FROM SENSOR
LED WALL MOUNTED LIGHT FIXTURE. SEE ARCHITECTURAL FOR MOUNTING HEIGHT
G
OS
NOMINAL 1'X4' VANDAL RESISTANT LED LIGHT FIXTURE, MARK 'LVR', TYPICAL
ELECTRICAL LEGEND - NEW WORK
TO POWER PACK PER MANUFACTURER'S RECOMMENDATIONS.
DUAL VOLTAGE POWER PACK MOUNTED ABOVE CEILING IN NEMA 1 ENCLOSURE.PP
POWER PACK SHALL BE SENSOR SWITCH #PP-20. PROVIDE WIRING IN CONDUIT
FROM POWER PACK TO ALL SENSORS IN SAME ROOM PER MANUFACTURER'S
RECOMMENDATIONS. PROVIDE ACCESS PANELS IN AREAS WITH HARD CEILING TYPES.
MOTOR RATED SWITCHM
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER. COORDINATE MOUNTING HEIGHT WITH COUNTERTOPS, ETC
EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP UNIT
DUAL TECHNOLOGY VACANCY SENSOR WALL MOUNTED LIGHTING SWITCH.VS
SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE WITH WEATHERPROOF COVER
G,WP
DUAL TECHNOLOGY OCCUPANCY SENSOR WALL MOUNTED LIGHTING SWITCH.OS
SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF
TIME AND LIGHTING CONTACTOR IN NEMA 1 ENCLOSURE FORTC LC
CONTROL OF EXTERIOR LIGHTING
S
S
S
S
CONDUIT RUN EXPOSED PERPENDICULAR OR PARALLEL TO BUILDING LINES
2#12, 1#12 GRD 1/2"C, 3#12, 1#12 GRD, 1/2"C, ETC.
HOMERUN TO PANELBOARD ANY CIRCUIT WITHOUT FURTHER DESIGNATION
CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALLS
CONDUIT RUN BELOW GRADE OR IN SLAB.
NON-FUSED DISCONNECT SWITCH
SURFACE MOUNTED POWER PANELBOARD
DUPLEX RECEPTACLE MOUNT 18" AFF UNLESS NOTED OTHERWISE
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE, MOUNTING HEIGHT AS NOTED
SINGLE POLE LIGHTING SWITCH, MOUNT 46" AFF
DUAL TECHNOLOGY CEILING MOUNTED MOTION SENSOR. SENSOR SWITCH
#CM-PDT-9-R. PROVIDE POWER PACK. PROVIDE WIRING IN CONDUIT FROM SENSOR
LED WALL MOUNTED LIGHT FIXTURE. SEE ARCHITECTURAL FOR MOUNTING HEIGHT
G
OS
NOMINAL 1'X4' VANDAL RESISTANT LED LIGHT FIXTURE, MARK 'LVR', TYPICAL
ELECTRICAL LEGEND - NEW WORK
TO POWER PACK PER MANUFACTURER'S RECOMMENDATIONS.
DUAL VOLTAGE POWER PACK MOUNTED ABOVE CEILING IN NEMA 1 ENCLOSURE.PP
POWER PACK SHALL BE SENSOR SWITCH #PP-20. PROVIDE WIRING IN CONDUIT
FROM POWER PACK TO ALL SENSORS IN SAME ROOM PER MANUFACTURER'S
RECOMMENDATIONS. PROVIDE ACCESS PANELS IN AREAS WITH HARD CEILING TYPES.
MOTOR RATED SWITCHM
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER. COORDINATE MOUNTING HEIGHT WITH COUNTERTOPS, ETC
EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP UNIT
DUAL TECHNOLOGY VACANCY SENSOR WALL MOUNTED LIGHTING SWITCH.VS
SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE WITH WEATHERPROOF COVER
G,WP
DUAL TECHNOLOGY OCCUPANCY SENSOR WALL MOUNTED LIGHTING SWITCH.OS
SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF
TIME AND LIGHTING CONTACTOR IN NEMA 1 ENCLOSURE FORTC LC
CONTROL OF EXTERIOR LIGHTING
S
S
S
S
REMARKSMOUNTINGBASIS OF DESIGN MANUFACTURER AND CATALOG No.MARK
LIGHTING FIXTURE SCHEDULE
LAMPS
1. SUBSTITUTIONS BY ACUITY, HUBBELL, OR COOPER SHALL BE SUBMITTED TO THE ENGINEER 10 DAYS PRIOR TO BID FOR PRIOR APPROVAL.
EMERGENCY LIGHTING UNIT. PROVIDE WITH EMERGENCY BATTERY
H.E. WILLIAMS # EMER/LED-WHT-D-277VBP SURFACE - WALL
WB SURFACE - WALLH.E. WILLIAMS # VWPH-L30-740-T3-SDGL-DIM-UNV 36W LED
NOTES:
1.8W LED BACKUP. PROVIDE WIREGUARD FOR UNITS LOCATED IN TRUCK BAYS ("WG").
HORIZONTAL LED WALL PACK, TYPE III DISTRIBUTION
4000K, 3000 LUMENS, WET LOCATION LISTED
PHILLIPS #LPL-S-4L53-40K-UNV-F1 SURFACE - CEILINGLVR 53W LED
1x4 LED VANDAL-RESISTANT, LOW-PROFILE, LINEAR FIXTURE
4000K, 3500 LUMENS
RECESSEDSL 26W LED
LISTED FOR WET LOCATIONS
.H.E. WILLIAMS # L60-L20C-835-CS-W-WET/CC-AC/CAL/DRV/UNV
T
POWER RISER DIAGRAM
SS
SCALE: NONE
NEW POWER COMPANY PAD MOUNTED
TRANSFORMER. 480Y/277V, 3-PHASE, 4W
SECONDARY. VERIFY LOCATION WITH
POWER COMPANY AND SITE UTILITY
DRAWINGS BY VOLKERT
MAIN PANEL "MP2"
480Y/277V, 3PH, 4W,
WITH 400 AMP MAIN
BREAKER
GRD PER
NEC 250
SEE PANELBOARD COORDINATION
SCHEDULE FOR CONDUCTOR SIZES
ON HOUSEKEEPING PAD
DRY TYPE TRANSFORMER
T2
"LP2"
480V - 208Y/120V
CT CABINET
METER
** AVAILABLE RMS SYMMETRICAL FAULT CURRENT IN kA AT PANEL.
ALL PANEL LUGS 100 AMPS AND GREATER SHALL BE COPPER.
ALL LUGS ON CIRCUIT BREAKERS GREATER THAN 400 AMPS SHALL BE COPPER.
ALL PANELBOARD CABINETS SHALL BE DOOR IN DOOR CONSTRUCTION WITH FACTORY WELDED METAL CIRCUIT DIRECTORY HOLDERS.
* MINIMUM EQUIPMENT RATING. ALL EQUIPMENT SHALL BE FULLY RATED. SERIES RATINGS SHALL NOT BE ALLOWED.
LP2 NEMA 1 SURFACE 208Y/120 3 4 150 NO 10 225 225 BOLT-ON 4#1/0 #6 2"C NO
NOTE ALL BUSSING COPPER, INCLUDING NEUTRAL AND GROUND.
CONDUCTORS GROUND CONDUIT
MP2 NEMA 1 SURFACE 480Y/277 3 4 400 YES 42 400 400 BOLT-ON 4#600 NONE 4"C YES
PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG ---- PH I)PH I)PH I)PH I)
MARK TYPE MOUNTING VOLTAGE PH WIRE MAIN
SERVICE
RATED
KAIC
RATING
PH BUS
RATING
N BUS
RATING
C/B TYPE
FEEDER INTEGRAL
TVSS
T2 480 208Y/120 3 4 45 3#4,#6G, 1"C #6 #6
TRANSFORMER SCHEDULE (CONCESSION BLDG TRANSFORMER SCHEDULE (CONCESSION BLDG TRANSFORMER SCHEDULE (CONCESSION BLDG TRANSFORMER SCHEDULE (CONCESSION BLDG ---- PH I)PH I)PH I)PH I)
MARK PRIMARY VOLTAGE SECONDARY VOLTAGE PHASE WIRE KVA PRIMARY FEEDER SIZE
SIZE GROUND TO 3/4" x 10' GROUND
ROD
SIZE GND TO FOUNDATION REBAR, WATER & BLDG
STEEL
SEAL
W
G a rd e n S t.
S u ite
P e n s a c o la
F
L
F L A
R w w w .g ra c e -d e s ig n .c o m
P h o n e
.4
.5
Sheet Reference No.
G
U L F
B R
E E
Z E
P K
W Y
G
U L F
B R
E E
Z E
F
L
S A
N T
A R
O S
A C
O U
N T
Y
S O
U T
H S
A N
T A
R O
S A
C O
U N
T Y
S P
O R
T S
C O
M P
L E
X A
T P
S C
DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING
D w n b y:
D e s ig n e d b y:
R e vi e w e d b y:
D a te
R e v.
C k d b y:
S u b m itt e d b y:
D ra w in g S c a le
P lo t s c a le
M
O F
F A
T T
N
IC
H
O L
M
N P ro je c t
N o
D ra w in g c o d e
D e s c ri p tio n D a te
A p p r.
M a rk
:1
D
S H
E E
T
S U
B M
IT
T
E R
'S N
A M
E
SEAL
A
1 2 3 4 5 6
B
C
D
E
1 2 3 4 5 6
A
B
C
D
E
This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on
May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.
/8
/2
:0
:0
P
M S
\2
S
S R
C S p o rt s C o m p le x P h a s e
\2
S
S R
C S p o rt s C o m p le x
E L
E C
P h a s e
I
R
.r v t
E1-001
E L
E C
T R
IC
A
L L
E G
E N
D
S C
H E
D U
L E
S A
N D
D E
T A
IL
S
S A
A S
A A
S A
A
S A
A
-0
-0
NOTES 1. PROVIDE NEMA 1 DISCONNECT. VERIFY RATING WITH EQUIPMENT PROVIDED.
2. PROVIDE NEMA 3R DISCONNECT. VERIFY RATING WITH EQUIPMENT PROVIDED.
3. PROVIDE 20/1 MOTOR RATED TOGGLE SWITCH DISCONNECTAT EF AND CONNECT TO LIGHTING CIRCUIT CONTROLLED BY OCCUPANCY SENSORS. VERIFY CONTROLS WITH MECHANICAL.
HP-1 HEAT PUMP UNIT (INDOOR UNIT) 208/1 7.0 1.12 2#12,#12G,1/2"C LP2 15/2 30/2 1
HP-1 HEAT PUMP UNIT (OUTDOOR UNIT) 208/1 25.0 4.16 2#10,#10G,1/2"C LP2 40/2 60/2 2
EF-1 EXHAUST FAN 120/1 2.0 0.20 2#12,#12G,1/2"C LP2 20/1 20/1 3
EF-2 EXHAUST FAN 120/1 1.0 0.10 2#12,#12G,1/2"C LP2 20/1 20/1 3
EF-3 EXHAUST FAN 120/1 1.0 0.10 2#12,#12G,1/2"C LP2 20/1 20/1 3
EWH-1 ELECTRIC WATER HEATER 208/1 27.0 4.50 2#10,#10G,1/2"C LP2 30/2 30/2 1
EUH-1 ELECTRIC UNIT HEATER 208/1 30.0 5.00 2#10,#10G,1/2"C LP2 30/2 30/2 2
EUH-2 ELECTRIC UNIT HEATER 208/1 12.0 2.00 2#12,#12G,1/2"C LP2 15/2 30/2 2
EUH-3 ELECTRIC UNIT HEATER 208/1 24.0 4.00 2#10,#10G,1/2"C LP2 25/2 30/2 2
MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG ---- PH I)PH I)PH I)PH I)
MARK ITEM VOLTAGE/ PHASE MCA
LOAD
(kVA)
WIRING PANEL FED FROM CIRCUIT BREAKER DISCONNECT NOTES
TOTAL CONNECTED LOAD (kVA) 155.06 TOTAL LOAD (AMPS) 186.5
CIRCUIT & CIRCUIT BREAKER NOTES:
* VERIFY C.B. RATING, LOAD, CIRCUIT SIZE, ETC WITH UTILITY/SITE ELECTRICAL DRAWINGS BY VOLKERT PRIOR TO RELEASING PANELS.
41 - - - - - - 42
18.0 18.0 18.0 35.6 32.4 33.1
TOTAL (kVA) A: 53.6 B: 50.4 C: 51.1 HIGH PHASE (AMPS) 193.5
PANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULE
MARK: MAIN PANEL "MP2" (480Y/277 VOLT, 3 PH, 4W, 400A MAIN BREAKER IN CONCESSION BLDG - PH I)
CKT
No.
LOAD DESCRIPTION
BREAKER PHASE (kVA) PHASE (kVA) BREAKER
LOAD DESCRIPTION
CKT
No.P TRIP A B C A B C TRIP P
1 SPORTS LIGHTING POLE 'S1' 3 *20 2.50 10.40 70 3 PANEL 'LP2' 2
3 - - - 2.50 10.81 - - (VIA TFMR T2) 4
5 - - - 2.50 11.45 - - - 6
7 SPORTS LIGHTING POLE 'S2' 3 *20 4.00 4.50 *30 3 SPORTS LIGHTING POLE 'S7' 8
17 - - - 4.00 4.50 - - - 18
19 SPORTS LIGHTING POLE 'S4' 3 *20 2.50 4.50 *30 3 SPORTS LIGHTING POLE 'S9' 20
21 - - - 2.50 4.50 - - - 22
23 - - - 2.50 4.50 - - - 24
33 - - - 2.50 3.60 - - - 34
35 - - - 2.50 3.60 *30 2 FUTSOL FIELD 1 36
37 SPARE 3 100 3.60 - - - 38
39 - - - 30 2 SPARE 40
25 SPORTS LIGHTING POLE 'S5' 3 *20 2.50 4.50 *30 3 SPORTS LIGHTING POLE 'S10' 26
27 - - - 2.50 4.50 - - - 28
29 - - - 2.50 4.50 - - - 30
31 SPORTS LIGHTING POLE 'S6' 3 *20 2.50 3.60 *30 2 FUTSOL FIELD 1 32
9 - - - 4.00 4.50 - - - 10
11 - - - 4.00 4.50 - - - 12
13 SPORTS LIGHTING POLE 'S3' 3 *20 4.00 4.50 *30 3 SPORTS LIGHTING POLE 'S8' 14
15 - - - 4.00 4.50 - - - 16
TOTAL CONNECTED LOAD (kVA) 32.66 TOTAL LOAD (AMPS) 90.7
CIRCUIT & CIRCUIT BREAKER NOTES:
* PROVIDE HACR TYPE C.B. AND VERIFY C.B. RATING WITH ACTUAL EQUIPMENT PROVIDED.
** VERIFY C.B. RATING WITH ACTUAL EQUIPMENT PROVIDED.
41 SPARE 1 20 20 1 RE 42
2.7 2.3 3.0 7.7 8.5 8.4
TOTAL (kVA) A: 10.40 B: 10.81 C: 11.45 HIGH PHASE (AMPS) 95.4
PANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULE
MARK: PANEL "LP2" (208Y/120V, 3PH, 4W, 150A M.B. IN CONCESSION BLDG - PH I)
CKT
No.
LOAD DESCRIPTION
BREAKER PHASE (kVA) PHASE (kVA) BREAKER
LOAD DESCRIPTION
CKT
No.P TRIP A B C A B C TRIP P
1 LIGHTS - INDOOR 1 20 1.00 0.72 20 1 RECEPTS - RM 104,OUTDOOR 2
3 LIGHTS - INDOOR 1 20 0.80 0.36 20 1 RECEPTS - RM 102 4
5 LIGHTS - BLDG MTD EXT 1 20 0.18 1.08 20 1 RECEPTS - RM 103,OUTDOOR\ 6
7 RECEPTS - RM 101 1 20 0.18 0.72 20 1 RECEPTS - RM 106,OUTDOOR 8
9 RECEPTS - RM 101 1 20 0.18 0.70 20 1 RECEPTS - EWC 10
11 RECEPTS - RM 101 1 20 0.18 20 1 SPARE 12
13 RECEPTS - RM 101 1 20 0.18 0.66 *15 2 HP-1 (INDOOR UNIT) 14
15 RECEPTS - RM 101 1 20 0.18 0.66 - - 16
33 SPARE 1 20 2.00 **25 2 EUH-3 34
35 SPARE 1 20 2.00 - - 36
37 SPARE 1 20 20 1 SPARE 38
39 SPARE 1 20 20 1 SPARE 40
17 RECEPTS - RM 101 1 20 0.18 2.08 *40 2 HP-1 (OUTDOOR UNIT) 18
19 RECEPTS - RM 101 1 20 0.18 2.08 - - 20
21 RECEPTS - RM 101 1 20 0.18 2.25 **30 2 EWH-1 22
23 RECEPTS - RM 101 1 20 1.00 2.25 - - 24
25 RECEPTS - RM 101 1 20 1.00 2.50 **30 2 EUH-1 26
27 RECEPTS - RM 101 1 20 1.00 2.50 - - 28
29 RECEPTS - RM 101 ICE MACH 1 **20 1.50 1.00 **15 2 EUH-2 30
31 RECEPTS - RM 101 1 20 0.18 1.00 - - 32
SEAL
W
G a rd e n S t.
S u ite
P e n s a c o la
F
L
F L A
R w w w .g ra c e -d e s ig n .c o m
P h o n e
.4
.5
Sheet Reference No.
G
U L F
B R
E E
Z E
P K
W Y
G
U L F
B R
E E
Z E
F
L
S A
N T
A R
O S
A C
O U
N T
Y
S O
U T
H S
A N
T A
R O
S A
C O
U N
T Y
S P
O R
T S
C O
M P
L E
X A
T P
S C
DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING
D w n b y:
D e s ig n e d b y:
R e vi e w e d b y:
D a te
R e v.
C k d b y:
S u b m itt e d b y:
D ra w in g S c a le
P lo t s c a le
M
O F
F A
T T
N
IC
H
O L
M
N P ro je c t
N o
D ra w in g c o d e
D e s c ri p tio n D a te
A p p r.
M a rk
:1
D
S H
E E
T
S U
B M
IT
T
E R
'S N
A M
E
SEAL
A
1 2 3 4 5 6
B
C
D
E
1 2 3 4 5 6
A
B
C
D
E
This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on
May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.
/8
/2
:0
:0
P
M S
\2
S
S R
C S p o rt s C o m p le x P h a s e
\2
S
S R
C S p o rt s C o m p le x
E L
E C
P h a s e
I
R
.r v t
E1-002
S C
H E
D U
L E
S
S A
A S
A A
S A
A
S A
A
-0
-0
R E
F
OSOS
PP
PP
OS
WB
V S
BP
CONCESSION
STORAGE
ELECTRICAL
STORAGE
WOMENS RR
JANITORIAL
MENS RR
LVR
LVRLVR LVR LVR
LVR
LVR
O S
BP
BP
LVR
LVRLVR LVR LVR
O S
LVR
LVR
LVR
LVR LVR
LVR
LVR
LVR
VS
LVR
WB
WB
WB
WB WB
WB
WB
WBWB
LP2-5
LVR
LP2-1
EF-1 EF-2 EF-3
M M M
"LP2"
LP2-3
a a a a a a b b
SL
bSL bSL bSL
SEAL
W
G a rd e n S t.
S u ite
P e n s a c o la
F
L
F L A
R w w w .g ra c e -d e s ig n .c o m
P h o n e
.4
.5
Sheet Reference No.
G
U L F
B R
E E
Z E
P K
W Y
G
U L F
B R
E E
Z E
F
L
S A
N T
A R
O S
A C
O U
N T
Y
S O
U T
H S
A N
T A
R O
S A
C O
U N
T Y
S P
O R
T S
C O
M P
L E
X A
T P
S C
DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING
D w n b y:
D e s ig n e d b y:
R e vi e w e d b y:
D a te
R e v.
C k d b y:
S u b m itt e d b y:
D ra w in g S c a le
P lo t s c a le
M
O F
F A
T T
N
IC
H
O L
M
N P ro je c t
N o
D ra w in g c o d e
D e s c ri p tio n D a te
A p p r.
M a rk
:1
D
S H
E E
T
S U
B M
IT
T
E R
'S N
A M
E
SEAL
A
1 2 3 4 5 6
B
C
D
E
1 2 3 4 5 6
A
B
C
D
E
This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on
May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.
/8
/2
:0
:1
P
M S
\2
S
S R
C S p o rt s C o m p le x P h a s e
\2
S
S R
C S p o rt s C o m p le x
E L
E C
P h a s e
I
R
.r v t
E1-101
L
IG
H T
IN
G
P L
A N
S A
A S
A A
S A
A
S A
A
-0
-0
PLAN
NORTH
1/4" = 1'-0"E1-101
1 LIGHTING PLAN
SCALE: 1/4" = 1'-0"
0 2' 4' 8'
ROUTE EXTERIOR LIGHTING CIRCUIT THROUGH CONTACTOR WITH
TIME CLOCK CONTROL. PROVIDE 20A/2P LIGHTING CONTACTOR AND
7-DAY/24-HOUR PROGRAMMABLE DIGITAL TIME CLOCK ADJACENT
TO PANEL "LP2".
KEY NOTES:
R E
F
LP2-27
LP2-2
"MP2"
G,WP
CONCESSION
STORAGE
ELECTRICAL
STORAGE
WOMENS RR
JANITORIAL
MENS RR
G,WP
GG,AC G
G
HP-1
HP-1
EH-1
EH-3
EH-2
G,48"
GG
G
G,WP
EWH-1
G
LP2-18/20
LP2-14/16
LP2-22/24
LP2-6
LP2-31 LP2-7 LP2-9 LP2-11 LP2-13 LP2-15
LP2-25 LP2-23 LP2-21 LP2-19
G G
LP2-17
LP2-26/282
LP2-10
LP2-30/32
LP2-34/36
LP2-8
EWC
G
LP2-4
G
G
TC
LC
"LP2"
"T2"
CT CABINET AND
3-PHASE CT
METER BASE
G,WP
G
LP2-29
G,AC G,AC
G G
SEAL
W
G a rd e n S t.
S u ite
P e n s a c o la
F
L
F L A
R w w w .g ra c e -d e s ig n .c o m
P h o n e
.4
.5
Sheet Reference No.
G
U L F
B R
E E
Z E
P K
W Y
G
U L F
B R
E E
Z E
F
L
S A
N T
A R
O S
A C
O U
N T
Y
S O
U T
H S
A N
T A
R O
S A
C O
U N
T Y
S P
O R
T S
C O
M P
L E
X A
T P
S C
DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING
D w n b y:
D e s ig n e d b y:
R e vi e w e d b y:
D a te
R e v.
C k d b y:
S u b m itt e d b y:
D ra w in g S c a le
P lo t s c a le
M
O F
F A
T T
N
IC
H
O L
M
N P ro je c t
N o
D ra w in g c o d e
D e s c ri p tio n D a te
A p p r.
M a rk
:1
D
S H
E E
T
S U
B M
IT
T
E R
'S N
A M
E
SEAL
A
1 2 3 4 5 6
B
C
D
E
1 2 3 4 5 6
A
B
C
D
E
This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on
May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.
/8
/2
:0
:2
P
M S
\2
S
S R
C S p o rt s C o m p le x P h a s e
\2
S
S R
C S p o rt s C o m p le x
E L
E C
P h a s e
I
R
.r v t
E1-201
P O
W E
R
S
IG
N A
L P
L A
N
S A
A S
A A
S A
A
S A
A
-0
-0
1/4" = 1'-0"E1-201
1 POWER & SIGNAL PLAN
PLAN
NORTH
SCALE: 1/4" = 1'-0"
0 2' 4' 8'
PROVIDE CT CABINET AND 3-PHASE CT METER. VERIFY ALL
REQUIREMENTS, LOCATION ETC. WITH FLORIDA POWER AND LIGHT
(FPL) PRIOR TO CONSTRUCTION. SERVICE CONDUCTORS FROM CT
CABINET TO MAIN POWER PANEL "MP2" SHALL BE ROUTED
UNDERGROUND (BELOW SLAB) UNLIT ENTERING MAIN PANEL "MP2".
SEE "MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE" FOR
ELECTRICAL REQUIREMENTS.
KEY NOTES:
| 2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS |
| Sheets |
| E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS |
| E1-002 - SCHEDULES |
| E1-101 - LIGHTING PLAN |
| E1-201 - POWER & SIGNAL PLAN |
| 2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-002 - SCHEDULES |
| Sheets |
| E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS |
| E1-002 - SCHEDULES |
| E1-101 - LIGHTING PLAN |
| E1-201 - POWER & SIGNAL PLAN |
| 2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-101 - LIGHTING PLAN |
| Sheets |
| E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS |
| E1-002 - SCHEDULES |
| E1-101 - LIGHTING PLAN |
| E1-201 - POWER & SIGNAL PLAN |
| 2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-201 - POWER & SIGNAL PLAN |
| Sheets |
| E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS |
| E1-002 - SCHEDULES |
| E1-101 - LIGHTING PLAN |
| E1-201 - POWER & SIGNAL PLAN |
| 2026-05-08T13:17:10-0500 | |
| Scott A Adams |
File details come from the government source that posted it. Updated .