4.5_-_IFB_-_Grace_-_Phase_1_ELEC_Plans_2026-05-08.pdf

PDF 1 MB Posted

Attached to
South Soccer Sports Complex
Solicitation number
26-042
Issued by
Santa Rosa County, Mount Carmel CDP, Florida

About this file

This is a set of electrical plans and specifications for Phase 1 of the South Santa Rosa County Sports Complex, prepared by Grace Design for Santa Rosa County, Florida. The project encompasses the design of a Concession Building electrical system located at 5075 Gulf Breeze Parkway, Gulf Breeze, Florida 32563. The electrical plans detail comprehensive installations including a new pad-mounted transformer (480Y/277V, 3-phase, 4-wire secondary), main power panel (MP2) rated at 480Y/277V with a 400-amp main breaker, a secondary panel (LP2) at 208Y/120V with a 150-amp main breaker, mechanical equipment connections for heat pump units, exhaust fans, electric water heaters, and unit heaters, and extensive lighting systems including LED fixtures, motion sensors, occupancy sensors, and emergency lighting with battery backup. The plans specify conduit routing, panelboard coordination schedules, transformer specifications, circuit breaker assignments, and detailed lighting and power layouts across multiple rooms within the Concession Building. The design includes outdoor sports lighting for multiple lighting poles and futsol fields controlled through time-clock and lighting contactor systems. The sealed bid for this project was scheduled to be opened on Thursday, August 20, 2026, at 10:15 a.m., with a pre-bid meeting held on July 29, 2026, at 10:00 a.m. at the Santa Rosa County Engineering Office.

The electrical design reflects a total connected load of 155.06 kVA for the mechanical equipment and 32.66 kVA for the sports lighting system. All equipment specifications include manufacturer and catalog numbers for required components such as Acuity, Hubbell, and Cooper lighting fixtures, with provisions for equivalent substitutions submitted to the engineer ten days prior to bid for approval. The plans incorporate National Electrical Code (NEC) compliance requirements, including proper grounding to foundation rebar, water lines, and building steel, and specify NEMA-rated disconnects and enclosures throughout the system. No pricing information, set-asides, or funding source details are provided in these technical plans; the procurement process is managed through the Santa Rosa County Procurement Portal with questions to be submitted by August 6, 2026.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONDUIT RUN EXPOSED PERPENDICULAR OR PARALLEL TO BUILDING LINES

2#12, 1#12 GRD 1/2"C, 3#12, 1#12 GRD, 1/2"C, ETC.

HOMERUN TO PANELBOARD ANY CIRCUIT WITHOUT FURTHER DESIGNATION

CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALLS

CONDUIT RUN BELOW GRADE OR IN SLAB.

NON-FUSED DISCONNECT SWITCH

SURFACE MOUNTED POWER PANELBOARD

DUPLEX RECEPTACLE MOUNT 18" AFF UNLESS NOTED OTHERWISE

GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE, MOUNTING HEIGHT AS NOTED

SINGLE POLE LIGHTING SWITCH, MOUNT 46" AFF

DUAL TECHNOLOGY CEILING MOUNTED MOTION SENSOR. SENSOR SWITCH

#CM-PDT-9-R. PROVIDE POWER PACK. PROVIDE WIRING IN CONDUIT FROM SENSOR

LED WALL MOUNTED LIGHT FIXTURE. SEE ARCHITECTURAL FOR MOUNTING HEIGHT

G

OS

NOMINAL 1'X4' VANDAL RESISTANT LED LIGHT FIXTURE, MARK 'LVR', TYPICAL

ELECTRICAL LEGEND - NEW WORK

TO POWER PACK PER MANUFACTURER'S RECOMMENDATIONS.

DUAL VOLTAGE POWER PACK MOUNTED ABOVE CEILING IN NEMA 1 ENCLOSURE.PP

POWER PACK SHALL BE SENSOR SWITCH #PP-20. PROVIDE WIRING IN CONDUIT

FROM POWER PACK TO ALL SENSORS IN SAME ROOM PER MANUFACTURER'S

RECOMMENDATIONS. PROVIDE ACCESS PANELS IN AREAS WITH HARD CEILING TYPES.

MOTOR RATED SWITCHM

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER. COORDINATE MOUNTING HEIGHT WITH COUNTERTOPS, ETC

EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP UNIT

DUAL TECHNOLOGY VACANCY SENSOR WALL MOUNTED LIGHTING SWITCH.VS

SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF

GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE WITH WEATHERPROOF COVER

G,WP

DUAL TECHNOLOGY OCCUPANCY SENSOR WALL MOUNTED LIGHTING SWITCH.OS

SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF

TIME AND LIGHTING CONTACTOR IN NEMA 1 ENCLOSURE FORTC LC

CONTROL OF EXTERIOR LIGHTING

S

S

S

S

CONDUIT RUN EXPOSED PERPENDICULAR OR PARALLEL TO BUILDING LINES

2#12, 1#12 GRD 1/2"C, 3#12, 1#12 GRD, 1/2"C, ETC.

HOMERUN TO PANELBOARD ANY CIRCUIT WITHOUT FURTHER DESIGNATION

CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALLS

CONDUIT RUN BELOW GRADE OR IN SLAB.

NON-FUSED DISCONNECT SWITCH

SURFACE MOUNTED POWER PANELBOARD

DUPLEX RECEPTACLE MOUNT 18" AFF UNLESS NOTED OTHERWISE

GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE, MOUNTING HEIGHT AS NOTED

SINGLE POLE LIGHTING SWITCH, MOUNT 46" AFF

DUAL TECHNOLOGY CEILING MOUNTED MOTION SENSOR. SENSOR SWITCH

#CM-PDT-9-R. PROVIDE POWER PACK. PROVIDE WIRING IN CONDUIT FROM SENSOR

LED WALL MOUNTED LIGHT FIXTURE. SEE ARCHITECTURAL FOR MOUNTING HEIGHT

G

OS

NOMINAL 1'X4' VANDAL RESISTANT LED LIGHT FIXTURE, MARK 'LVR', TYPICAL

ELECTRICAL LEGEND - NEW WORK

TO POWER PACK PER MANUFACTURER'S RECOMMENDATIONS.

DUAL VOLTAGE POWER PACK MOUNTED ABOVE CEILING IN NEMA 1 ENCLOSURE.PP

POWER PACK SHALL BE SENSOR SWITCH #PP-20. PROVIDE WIRING IN CONDUIT

FROM POWER PACK TO ALL SENSORS IN SAME ROOM PER MANUFACTURER'S

RECOMMENDATIONS. PROVIDE ACCESS PANELS IN AREAS WITH HARD CEILING TYPES.

MOTOR RATED SWITCHM

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER. COORDINATE MOUNTING HEIGHT WITH COUNTERTOPS, ETC

EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP UNIT

DUAL TECHNOLOGY VACANCY SENSOR WALL MOUNTED LIGHTING SWITCH.VS

SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF

GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE WITH WEATHERPROOF COVER

G,WP

DUAL TECHNOLOGY OCCUPANCY SENSOR WALL MOUNTED LIGHTING SWITCH.OS

SENSOR SWITCH LINE VOLTAGE #WSD-PDT. MOUNT 46" AFF

TIME AND LIGHTING CONTACTOR IN NEMA 1 ENCLOSURE FORTC LC

CONTROL OF EXTERIOR LIGHTING

S

S

S

S

REMARKSMOUNTINGBASIS OF DESIGN MANUFACTURER AND CATALOG No.MARK

LIGHTING FIXTURE SCHEDULE

LAMPS

1. SUBSTITUTIONS BY ACUITY, HUBBELL, OR COOPER SHALL BE SUBMITTED TO THE ENGINEER 10 DAYS PRIOR TO BID FOR PRIOR APPROVAL.

EMERGENCY LIGHTING UNIT. PROVIDE WITH EMERGENCY BATTERY

H.E. WILLIAMS # EMER/LED-WHT-D-277VBP SURFACE - WALL

WB SURFACE - WALLH.E. WILLIAMS # VWPH-L30-740-T3-SDGL-DIM-UNV 36W LED

NOTES:

1.8W LED BACKUP. PROVIDE WIREGUARD FOR UNITS LOCATED IN TRUCK BAYS ("WG").

HORIZONTAL LED WALL PACK, TYPE III DISTRIBUTION

4000K, 3000 LUMENS, WET LOCATION LISTED

PHILLIPS #LPL-S-4L53-40K-UNV-F1 SURFACE - CEILINGLVR 53W LED

1x4 LED VANDAL-RESISTANT, LOW-PROFILE, LINEAR FIXTURE

4000K, 3500 LUMENS

RECESSEDSL 26W LED

LISTED FOR WET LOCATIONS

.H.E. WILLIAMS # L60-L20C-835-CS-W-WET/CC-AC/CAL/DRV/UNV

T

POWER RISER DIAGRAM

SS

SCALE: NONE

NEW POWER COMPANY PAD MOUNTED

TRANSFORMER. 480Y/277V, 3-PHASE, 4W

SECONDARY. VERIFY LOCATION WITH

POWER COMPANY AND SITE UTILITY

DRAWINGS BY VOLKERT

MAIN PANEL "MP2"

480Y/277V, 3PH, 4W,

WITH 400 AMP MAIN

BREAKER

GRD PER

NEC 250

SEE PANELBOARD COORDINATION

SCHEDULE FOR CONDUCTOR SIZES

ON HOUSEKEEPING PAD

DRY TYPE TRANSFORMER

T2

"LP2"

480V - 208Y/120V

CT CABINET

METER

** AVAILABLE RMS SYMMETRICAL FAULT CURRENT IN kA AT PANEL.

ALL PANEL LUGS 100 AMPS AND GREATER SHALL BE COPPER.

ALL LUGS ON CIRCUIT BREAKERS GREATER THAN 400 AMPS SHALL BE COPPER.

ALL PANELBOARD CABINETS SHALL BE DOOR IN DOOR CONSTRUCTION WITH FACTORY WELDED METAL CIRCUIT DIRECTORY HOLDERS.

* MINIMUM EQUIPMENT RATING. ALL EQUIPMENT SHALL BE FULLY RATED. SERIES RATINGS SHALL NOT BE ALLOWED.

LP2 NEMA 1 SURFACE 208Y/120 3 4 150 NO 10 225 225 BOLT-ON 4#1/0 #6 2"C NO

NOTE ALL BUSSING COPPER, INCLUDING NEUTRAL AND GROUND.

CONDUCTORS GROUND CONDUIT

MP2 NEMA 1 SURFACE 480Y/277 3 4 400 YES 42 400 400 BOLT-ON 4#600 NONE 4"C YES

PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG PANELBOARD COORDINATION SCHEDULE (CONCESSION BLDG ---- PH I)PH I)PH I)PH I)

MARK TYPE MOUNTING VOLTAGE PH WIRE MAIN

SERVICE

RATED

KAIC

RATING

PH BUS

RATING

N BUS

RATING

C/B TYPE

FEEDER INTEGRAL

TVSS

T2 480 208Y/120 3 4 45 3#4,#6G, 1"C #6 #6

TRANSFORMER SCHEDULE (CONCESSION BLDG TRANSFORMER SCHEDULE (CONCESSION BLDG TRANSFORMER SCHEDULE (CONCESSION BLDG TRANSFORMER SCHEDULE (CONCESSION BLDG ---- PH I)PH I)PH I)PH I)

MARK PRIMARY VOLTAGE SECONDARY VOLTAGE PHASE WIRE KVA PRIMARY FEEDER SIZE

SIZE GROUND TO 3/4" x 10' GROUND

ROD

SIZE GND TO FOUNDATION REBAR, WATER & BLDG

STEEL

SEAL

W

G a rd e n S t.

S u ite

P e n s a c o la

F

L

F L A

R w w w .g ra c e -d e s ig n .c o m

P h o n e

.4

.5

Sheet Reference No.

G

U L F

B R

E E

Z E

P K

W Y

G

U L F

B R

E E

Z E

F

L

S A

N T

A R

O S

A C

O U

N T

Y

S O

U T

H S

A N

T A

R O

S A

C O

U N

T Y

S P

O R

T S

C O

M P

L E

X A

T P

S C

DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING

D w n b y:

D e s ig n e d b y:

R e vi e w e d b y:

D a te

R e v.

C k d b y:

S u b m itt e d b y:

D ra w in g S c a le

P lo t s c a le

M

O F

F A

T T

N

IC

H

O L

M

N P ro je c t

N o

D ra w in g c o d e

D e s c ri p tio n D a te

A p p r.

M a rk

:1

D

S H

E E

T

S U

B M

IT

T

E R

'S N

A M

E

SEAL

A

1 2 3 4 5 6

B

C

D

E

1 2 3 4 5 6

A

B

C

D

E

This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on

May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.

/8

/2

:0

:0

P

M S

\2

S

S R

C S p o rt s C o m p le x P h a s e

\2

S

S R

C S p o rt s C o m p le x

E L

E C

P h a s e

I

R

.r v t

E1-001

E L

E C

T R

IC

A

L L

E G

E N

D

S C

H E

D U

L E

S A

N D

D E

T A

IL

S

S A

A S

A A

S A

A

S A

A

-0

-0

NOTES 1. PROVIDE NEMA 1 DISCONNECT. VERIFY RATING WITH EQUIPMENT PROVIDED.

2. PROVIDE NEMA 3R DISCONNECT. VERIFY RATING WITH EQUIPMENT PROVIDED.

3. PROVIDE 20/1 MOTOR RATED TOGGLE SWITCH DISCONNECTAT EF AND CONNECT TO LIGHTING CIRCUIT CONTROLLED BY OCCUPANCY SENSORS. VERIFY CONTROLS WITH MECHANICAL.

HP-1 HEAT PUMP UNIT (INDOOR UNIT) 208/1 7.0 1.12 2#12,#12G,1/2"C LP2 15/2 30/2 1

HP-1 HEAT PUMP UNIT (OUTDOOR UNIT) 208/1 25.0 4.16 2#10,#10G,1/2"C LP2 40/2 60/2 2

EF-1 EXHAUST FAN 120/1 2.0 0.20 2#12,#12G,1/2"C LP2 20/1 20/1 3

EF-2 EXHAUST FAN 120/1 1.0 0.10 2#12,#12G,1/2"C LP2 20/1 20/1 3

EF-3 EXHAUST FAN 120/1 1.0 0.10 2#12,#12G,1/2"C LP2 20/1 20/1 3

EWH-1 ELECTRIC WATER HEATER 208/1 27.0 4.50 2#10,#10G,1/2"C LP2 30/2 30/2 1

EUH-1 ELECTRIC UNIT HEATER 208/1 30.0 5.00 2#10,#10G,1/2"C LP2 30/2 30/2 2

EUH-2 ELECTRIC UNIT HEATER 208/1 12.0 2.00 2#12,#12G,1/2"C LP2 15/2 30/2 2

EUH-3 ELECTRIC UNIT HEATER 208/1 24.0 4.00 2#10,#10G,1/2"C LP2 25/2 30/2 2

MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE (CONCESSION BLDG ---- PH I)PH I)PH I)PH I)

MARK ITEM VOLTAGE/ PHASE MCA

LOAD

(kVA)

WIRING PANEL FED FROM CIRCUIT BREAKER DISCONNECT NOTES

TOTAL CONNECTED LOAD (kVA) 155.06 TOTAL LOAD (AMPS) 186.5

CIRCUIT & CIRCUIT BREAKER NOTES:

* VERIFY C.B. RATING, LOAD, CIRCUIT SIZE, ETC WITH UTILITY/SITE ELECTRICAL DRAWINGS BY VOLKERT PRIOR TO RELEASING PANELS.

41 - - - - - - 42

18.0 18.0 18.0 35.6 32.4 33.1

TOTAL (kVA) A: 53.6 B: 50.4 C: 51.1 HIGH PHASE (AMPS) 193.5

PANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULE

MARK: MAIN PANEL "MP2" (480Y/277 VOLT, 3 PH, 4W, 400A MAIN BREAKER IN CONCESSION BLDG - PH I)

CKT

No.

LOAD DESCRIPTION

BREAKER PHASE (kVA) PHASE (kVA) BREAKER

LOAD DESCRIPTION

CKT

No.P TRIP A B C A B C TRIP P

1 SPORTS LIGHTING POLE 'S1' 3 *20 2.50 10.40 70 3 PANEL 'LP2' 2

3 - - - 2.50 10.81 - - (VIA TFMR T2) 4

5 - - - 2.50 11.45 - - - 6

7 SPORTS LIGHTING POLE 'S2' 3 *20 4.00 4.50 *30 3 SPORTS LIGHTING POLE 'S7' 8

17 - - - 4.00 4.50 - - - 18

19 SPORTS LIGHTING POLE 'S4' 3 *20 2.50 4.50 *30 3 SPORTS LIGHTING POLE 'S9' 20

21 - - - 2.50 4.50 - - - 22

23 - - - 2.50 4.50 - - - 24

33 - - - 2.50 3.60 - - - 34

35 - - - 2.50 3.60 *30 2 FUTSOL FIELD 1 36

37 SPARE 3 100 3.60 - - - 38

39 - - - 30 2 SPARE 40

25 SPORTS LIGHTING POLE 'S5' 3 *20 2.50 4.50 *30 3 SPORTS LIGHTING POLE 'S10' 26

27 - - - 2.50 4.50 - - - 28

29 - - - 2.50 4.50 - - - 30

31 SPORTS LIGHTING POLE 'S6' 3 *20 2.50 3.60 *30 2 FUTSOL FIELD 1 32

9 - - - 4.00 4.50 - - - 10

11 - - - 4.00 4.50 - - - 12

13 SPORTS LIGHTING POLE 'S3' 3 *20 4.00 4.50 *30 3 SPORTS LIGHTING POLE 'S8' 14

15 - - - 4.00 4.50 - - - 16

TOTAL CONNECTED LOAD (kVA) 32.66 TOTAL LOAD (AMPS) 90.7

CIRCUIT & CIRCUIT BREAKER NOTES:

* PROVIDE HACR TYPE C.B. AND VERIFY C.B. RATING WITH ACTUAL EQUIPMENT PROVIDED.

** VERIFY C.B. RATING WITH ACTUAL EQUIPMENT PROVIDED.

41 SPARE 1 20 20 1 RE 42

2.7 2.3 3.0 7.7 8.5 8.4

TOTAL (kVA) A: 10.40 B: 10.81 C: 11.45 HIGH PHASE (AMPS) 95.4

PANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULEPANELBOARD SCHEDULE

MARK: PANEL "LP2" (208Y/120V, 3PH, 4W, 150A M.B. IN CONCESSION BLDG - PH I)

CKT

No.

LOAD DESCRIPTION

BREAKER PHASE (kVA) PHASE (kVA) BREAKER

LOAD DESCRIPTION

CKT

No.P TRIP A B C A B C TRIP P

1 LIGHTS - INDOOR 1 20 1.00 0.72 20 1 RECEPTS - RM 104,OUTDOOR 2

3 LIGHTS - INDOOR 1 20 0.80 0.36 20 1 RECEPTS - RM 102 4

5 LIGHTS - BLDG MTD EXT 1 20 0.18 1.08 20 1 RECEPTS - RM 103,OUTDOOR\ 6

7 RECEPTS - RM 101 1 20 0.18 0.72 20 1 RECEPTS - RM 106,OUTDOOR 8

9 RECEPTS - RM 101 1 20 0.18 0.70 20 1 RECEPTS - EWC 10

11 RECEPTS - RM 101 1 20 0.18 20 1 SPARE 12

13 RECEPTS - RM 101 1 20 0.18 0.66 *15 2 HP-1 (INDOOR UNIT) 14

15 RECEPTS - RM 101 1 20 0.18 0.66 - - 16

33 SPARE 1 20 2.00 **25 2 EUH-3 34

35 SPARE 1 20 2.00 - - 36

37 SPARE 1 20 20 1 SPARE 38

39 SPARE 1 20 20 1 SPARE 40

17 RECEPTS - RM 101 1 20 0.18 2.08 *40 2 HP-1 (OUTDOOR UNIT) 18

19 RECEPTS - RM 101 1 20 0.18 2.08 - - 20

21 RECEPTS - RM 101 1 20 0.18 2.25 **30 2 EWH-1 22

23 RECEPTS - RM 101 1 20 1.00 2.25 - - 24

25 RECEPTS - RM 101 1 20 1.00 2.50 **30 2 EUH-1 26

27 RECEPTS - RM 101 1 20 1.00 2.50 - - 28

29 RECEPTS - RM 101 ICE MACH 1 **20 1.50 1.00 **15 2 EUH-2 30

31 RECEPTS - RM 101 1 20 0.18 1.00 - - 32

SEAL

W

G a rd e n S t.

S u ite

P e n s a c o la

F

L

F L A

R w w w .g ra c e -d e s ig n .c o m

P h o n e

.4

.5

Sheet Reference No.

G

U L F

B R

E E

Z E

P K

W Y

G

U L F

B R

E E

Z E

F

L

S A

N T

A R

O S

A C

O U

N T

Y

S O

U T

H S

A N

T A

R O

S A

C O

U N

T Y

S P

O R

T S

C O

M P

L E

X A

T P

S C

DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING

D w n b y:

D e s ig n e d b y:

R e vi e w e d b y:

D a te

R e v.

C k d b y:

S u b m itt e d b y:

D ra w in g S c a le

P lo t s c a le

M

O F

F A

T T

N

IC

H

O L

M

N P ro je c t

N o

D ra w in g c o d e

D e s c ri p tio n D a te

A p p r.

M a rk

:1

D

S H

E E

T

S U

B M

IT

T

E R

'S N

A M

E

SEAL

A

1 2 3 4 5 6

B

C

D

E

1 2 3 4 5 6

A

B

C

D

E

This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on

May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.

/8

/2

:0

:0

P

M S

\2

S

S R

C S p o rt s C o m p le x P h a s e

\2

S

S R

C S p o rt s C o m p le x

E L

E C

P h a s e

I

R

.r v t

E1-002

S C

H E

D U

L E

S

S A

A S

A A

S A

A

S A

A

-0

-0

R E

F

OSOS

PP

PP

OS

WB

V S

BP

CONCESSION

STORAGE

ELECTRICAL

STORAGE

WOMENS RR

JANITORIAL

MENS RR

LVR

LVRLVR LVR LVR

LVR

LVR

O S

BP

BP

LVR

LVRLVR LVR LVR

O S

LVR

LVR

LVR

LVR LVR

LVR

LVR

LVR

VS

LVR

WB

WB

WB

WB WB

WB

WB

WBWB

LP2-5

LVR

LP2-1

EF-1 EF-2 EF-3

M M M

"LP2"

LP2-3

a a a a a a b b

SL

bSL bSL bSL

SEAL

W

G a rd e n S t.

S u ite

P e n s a c o la

F

L

F L A

R w w w .g ra c e -d e s ig n .c o m

P h o n e

.4

.5

Sheet Reference No.

G

U L F

B R

E E

Z E

P K

W Y

G

U L F

B R

E E

Z E

F

L

S A

N T

A R

O S

A C

O U

N T

Y

S O

U T

H S

A N

T A

R O

S A

C O

U N

T Y

S P

O R

T S

C O

M P

L E

X A

T P

S C

DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING

D w n b y:

D e s ig n e d b y:

R e vi e w e d b y:

D a te

R e v.

C k d b y:

S u b m itt e d b y:

D ra w in g S c a le

P lo t s c a le

M

O F

F A

T T

N

IC

H

O L

M

N P ro je c t

N o

D ra w in g c o d e

D e s c ri p tio n D a te

A p p r.

M a rk

:1

D

S H

E E

T

S U

B M

IT

T

E R

'S N

A M

E

SEAL

A

1 2 3 4 5 6

B

C

D

E

1 2 3 4 5 6

A

B

C

D

E

This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on

May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.

/8

/2

:0

:1

P

M S

\2

S

S R

C S p o rt s C o m p le x P h a s e

\2

S

S R

C S p o rt s C o m p le x

E L

E C

P h a s e

I

R

.r v t

E1-101

L

IG

H T

IN

G

P L

A N

S A

A S

A A

S A

A

S A

A

-0

-0

PLAN

NORTH

1/4" = 1'-0"E1-101

1 LIGHTING PLAN

SCALE: 1/4" = 1'-0"

0 2' 4' 8'

ROUTE EXTERIOR LIGHTING CIRCUIT THROUGH CONTACTOR WITH

TIME CLOCK CONTROL. PROVIDE 20A/2P LIGHTING CONTACTOR AND

7-DAY/24-HOUR PROGRAMMABLE DIGITAL TIME CLOCK ADJACENT

TO PANEL "LP2".

KEY NOTES:

R E

F

LP2-27

LP2-2

"MP2"

G,WP

CONCESSION

STORAGE

ELECTRICAL

STORAGE

WOMENS RR

JANITORIAL

MENS RR

G,WP

GG,AC G

G

HP-1

HP-1

EH-1

EH-3

EH-2

G,48"

GG

G

G,WP

EWH-1

G

LP2-18/20

LP2-14/16

LP2-22/24

LP2-6

LP2-31 LP2-7 LP2-9 LP2-11 LP2-13 LP2-15

LP2-25 LP2-23 LP2-21 LP2-19

G G

LP2-17

LP2-26/282

LP2-10

LP2-30/32

LP2-34/36

LP2-8

EWC

G

LP2-4

G

G

TC

LC

"LP2"

"T2"

CT CABINET AND

3-PHASE CT

METER BASE

G,WP

G

LP2-29

G,AC G,AC

G G

SEAL

W

G a rd e n S t.

S u ite

P e n s a c o la

F

L

F L A

R w w w .g ra c e -d e s ig n .c o m

P h o n e

.4

.5

Sheet Reference No.

G

U L F

B R

E E

Z E

P K

W Y

G

U L F

B R

E E

Z E

F

L

S A

N T

A R

O S

A C

O U

N T

Y

S O

U T

H S

A N

T A

R O

S A

C O

U N

T Y

S P

O R

T S

C O

M P

L E

X A

T P

S C

DRAWING SCALES SHOWN BASED ON 22"x34" DRAWING

D w n b y:

D e s ig n e d b y:

R e vi e w e d b y:

D a te

R e v.

C k d b y:

S u b m itt e d b y:

D ra w in g S c a le

P lo t s c a le

M

O F

F A

T T

N

IC

H

O L

M

N P ro je c t

N o

D ra w in g c o d e

D e s c ri p tio n D a te

A p p r.

M a rk

:1

D

S H

E E

T

S U

B M

IT

T

E R

'S N

A M

E

SEAL

A

1 2 3 4 5 6

B

C

D

E

1 2 3 4 5 6

A

B

C

D

E

This item has been digitally signed & sealed by Scott A. Adams, PE license No. FL 57949 on

May 8, 2026. Printed copies of this document are not considered signed & sealed and the signature must be verified on any electronic copies.

/8

/2

:0

:2

P

M S

\2

S

S R

C S p o rt s C o m p le x P h a s e

\2

S

S R

C S p o rt s C o m p le x

E L

E C

P h a s e

I

R

.r v t

E1-201

P O

W E

R

S

IG

N A

L P

L A

N

S A

A S

A A

S A

A

S A

A

-0

-0

1/4" = 1'-0"E1-201

1 POWER & SIGNAL PLAN

PLAN

NORTH

SCALE: 1/4" = 1'-0"

0 2' 4' 8'

PROVIDE CT CABINET AND 3-PHASE CT METER. VERIFY ALL

REQUIREMENTS, LOCATION ETC. WITH FLORIDA POWER AND LIGHT

(FPL) PRIOR TO CONSTRUCTION. SERVICE CONDUCTORS FROM CT

CABINET TO MAIN POWER PANEL "MP2" SHALL BE ROUTED

UNDERGROUND (BELOW SLAB) UNLIT ENTERING MAIN PANEL "MP2".

SEE "MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE" FOR

ELECTRICAL REQUIREMENTS.

KEY NOTES:

2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS
Sheets
E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS
E1-002 - SCHEDULES
E1-101 - LIGHTING PLAN
E1-201 - POWER & SIGNAL PLAN
2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-002 - SCHEDULES
Sheets
E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS
E1-002 - SCHEDULES
E1-101 - LIGHTING PLAN
E1-201 - POWER & SIGNAL PLAN
2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-101 - LIGHTING PLAN
Sheets
E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS
E1-002 - SCHEDULES
E1-101 - LIGHTING PLAN
E1-201 - POWER & SIGNAL PLAN
2426102_SSRC Sports Complex_ELEC_Phase I_R26 - Sheet - E1-201 - POWER & SIGNAL PLAN
Sheets
E1-001 - ELECTRICAL LEGEND, SCHEDULES AND DETAILS
E1-002 - SCHEDULES
E1-101 - LIGHTING PLAN
E1-201 - POWER & SIGNAL PLAN
2026-05-08T13:17:10-0500